•Refer to Service Manual RS6200006 for installation, operation, and troubleshooting information.
•All safety information must be followed as provided in the Service Manual.
•Refer to the appropriate Parts Catalog for part number information.
•See models on page 3.
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does
not assume any responsibility for property damage or personal injury due to improper service
procedures or services performed by an unqualified person.
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
DSXC160241AA
BRAND:
D: Del uxe
Goodman®
Brand
A: Amana ®
Brand
PRODUCT
FAMILY:
S: Split System
COMMUNICATION
FEATURE:
C: 4 -wire
Communication
Read y
PR ODUCT TYPE:
C: Condenser R- 22
H: He at Pump R -2 2
X: Co ndenser R-410A
Z: H eat P u mp R-410A
arising from improper service or service procedures. If
you install or perform service on this unit, you assume
responsibility for any personal injury or property damage
which may result. Many jurisdictions require a license to
install or service heating and air conditioning equipment.
2
Disconnect ALL power before servicing or installing this unit. Multiple power
sources may be present. Failure to do so may cause property damage, personal
injury or death.
Goodman will not be responsible
for any injury or property damage
WARNING
HIGH VOLTAGE!
WARNING
WARNING
an "entry level technician" as specified by the Air-Conditioning, Heating, and Refrigeration Institute (AHRI) may
use this information. Attempting to install or repair this
unit without such background may result in product
damage, personal injury or death.
ONLY individuals meeting (at a
minimum) the requirements of
PRODUCT IDENTIFICATION
The model number is used for positive identification of component parts used in manufacturing. Please use this number
when requesting service or parts information.
* Indicates minor revision & is not used for order entry or inventory management
WARNING
WARNING
WARNING
WARNING
Serious property damage, personal injury, reduced unit
performance and/or hazardous conditions may result
from the use of such non-approved devices.
The United States Environmental Protection Agency (“EPA”) has issued various regulations regarding the introduction and disposal of refrigerants introduced into this unit. Failure to follow
these regulations may harm the environment and can lead to the imposition of substantial fines.
These regulations may vary by jurisdiction. Should questions arise, contact your local EPA office.
Do not connect or use any device
that is not design certified by
Goodman for use with this unit.
WARNING
WARNING
do not store combustible materials or use gasoline or
other flammable liquids or vapors in the vicinity of this
appliance.
To prevent the risk of property
damage, personal injury, or death,
3
PRODUCT DESIGN
Models covered by this manual come with a new 4-wire communicating PCB. When paired with a compatible communicating indoor unit and a communicating thermostat, these
models can support 4-wire communication protocol and provide more troubleshooting information. These models are also
backward compatible with the legacy thermostat wiring.
*SXC16 models are available in 2, 3, 4 and 5 ton sizes and
use R-410A refrigerant. They are designed for 208/230 volt
single phase applications.
The condenser air is pulled through the condenser coil by a
direct drive propeller fan. This condenser air is then discharged out of the top of the cabinet.
These units are designed for free air discharge, so no additional resistance like duct work shall be attached.
The suction and liquid line connections on present models
are of the sweat type for field piping with refrigerant type copper. Front seating valves are factory installed to accept the
field run copper. The total refrigerant charge for a normal installation is factory installed in the condensing unit. *SXC
units are charged for the matching evaporator coil and a 15
foot refrigerant line set.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Conditioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has adequate capacity to heat or cool the conditioned space.
*SXC16 models use the Copeland Scroll "Ultratech" Series
compressors which are specifically designed for R-410A refrigerant. There are a number of design characteristics which
are different from the traditional reciprocating and/or scroll
compressors.
"Ultratech" Series scroll compressors with Copeland
ComfortAlert diagnostics will not have a discharge thermostat, some of the early model scroll compressors required
discharge thermostats.
Due to their design Scroll compressors are inherently more
tolerant of small quantities of liquid refrigerant.
NOTE: Even though the compressor section of a Scroll compressor is more tolerant of liquid refrigerant, continued
floodback or flooded start conditions may wash oil from the
bearing surfaces causing premature bearing failure.
"Ultratech" Series scroll compressors use "POE" or
polyolester oil which is NOT compatible with mineral oil based
lubricants like 3GS. "POE" oil must be used if additional oil
is required.
Operating pressures and amp draws may differ from standard reciprocating and/or scroll compressors. This information may be found in the "Cooling Performance Data" section.
This unit is for outdoor installation only. Refer to figure for
minimum clearances from the sides of the unit to full walls
and other objects.
NOTE: This unit cannot be completely enclosed. At least
one side must be unrestricted.
These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for example, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.
DO NOT locate the unit:
* Directly under a vent termination for a gas appliance.
* Within 3 feet of a clothes drier vent
* Where the refreezing of defrost water would create
a hazard
* Where water may rise into the unit.
NOT
RECOMMENDED
BBB
®
AAAAA
C
AA
A
Model TypeABCAA
AA
AA
C
AA
CC
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
WARNING
To avoid possible injury, explosion or death, practice
safe handling of refrigerants.
4
Residential10"10"18"20"
Light Commercial12'12"18"24"
CONDENSING UNIT SPECIFICATIONS
A/DSXC160[24-60]1A*
Dimensions
ModelDimensions - W x D x H
*SXC160241A*29 x 29 x 32¼
*SXC160361A*29 x 29 x 38¼
*SXC160481A*35½ x 35½ x 38¼
*SXC160601A*35½ x 35½ x 38¼
A/DSXC160241A* - A/DSXC160601A*
*S XC160241A**SXC16036A**SXC160481A**SXC160601A*
Cooling Capac it y, B TUH24,00036,00048,00 060,000
Com pressor
R.L. Am ps10.316.721.225.6
L.R. Am ps52.082.096.0118.0
Low Pressure Switch
Open610 P S IG610 P S IG610 P SIG610 P S IG
Close420 P S IG420 P S IG420 P SIG420 P S IG
Condens er Fan M otor
Horsepower1/121/61/61/6
F.L. A mps0.61.01.01.0
Liquid Line, Inc he s O . D. *3/8"3/8"3/8"3/ 8"
Suc t ion Line, Inc hes O.D. *3/4"7/8"1-1/8"1-1/8"
Refrigerant Charge137.0157.0202.0197.0
Powe r Supply208/230-60-1208/ 230-60-1208/2 30-60-1208/230 -60-1
Minim um Circ uit A m pac it y
Maxim um O vercurrent Device
Elec t rical Conduit S iz e
Power S upply (Inches )1/2 or 3/41/2 or 3/ 41/ 2 or 3/41/2 or 3/4
(1)
(2)
13.521.927.533.0
20354550
App rox im at e Shipp ing Weight282282296296
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the S & R plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.
5
CONDENSING UNIT SPECIFICATIONS
ASXC160[24-36]1B*
Dimensions
ModelDim ensions - W x D x H
ASX C160241B*29 x 29 x 30¼
ASX C160361B*29 x 29 x 30¼
ASXC160241BBA SXC160241BCASXC160361BBASXC 16 0361 B C
Cooling Capa c ity , BTUH24,00024,00036,0 0036,000
Com pressor
R.L. Am ps10.311.716. 715 .3
L.R. Am ps52.058.382. 083 .0
Low Pres s ure S wit c h
Open22 P S IG22 P S IG22 PS IG22 P S IG
Clos e50 P S IG50 P S IG50 PS IG50 P S IG
High P ress ure S wit c h
Open610 P S IG610 P S IG610 P SIG610 P S IG
Clos e420 PS IG420 PS IG420 P S IG420 P S IG
Condenser F an Mot or
Horsepo we r1/ 61/61/61/6
F.L. A m ps1.11.10. 90.9
Liquid Line, Inches O .D. *3/8"3/8"3/8"3/8"
S uct ion Line , Inch es O . D.*3/4 "3/ 4"7/ 8"7 /8"
Refrigerant Charge100.088.0110.096.0
P ower Su pply208/23 0-60-1208/230 -60-1208/230-60 -1208/230-60-1
Min im um C irc uit Ampac it y
(1)
Maximum Overcurrent Device
(2)
14.015.721. 820.0
20203535
E lec tric al Conduit S iz e
Power Supply (Inches)1/2 or 3/41/2 or 3/41/2 or 3/41/2 or 3/4
Approximate Shipping Weight198198202202
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the S & R plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
6
CONDENSING UNIT SPECIFICATIONS
ASXC160[48-60]1B*
Dimensions
ModelDim ensions - W x D x H
ASX C160481B*35½ x 35½ x 36¼
ASX C160601B*35½ x 35½ x 38¼
AS XC160481B*AS XC160481BCASXC 160601B *A SXC 160601BC
Cooling Capacity, BTUH48,00048,00060,00060,000
Com pressor
R.L. A mps21.221.225.628.8
L.R. A mps96.0104.0118. 0152.9
Low Pressure Switch
Open610 PS IG610 PS IG610 PS IG610 PS IG
Close420 PS IG420 P S IG420 P S IG420 P S IG
Condenser Fan M otor
Horsepower1/61/61/61/6
F.L. Am ps1. 01.21.01.2
Liquid Line, Inc hes O. D.*3/8"3/ 8"3/8"3/8"
Suc t ion Line, Inches O . D.*1 1/8"1 1/8"1 1/ 8"1 1/8"
Refrigerant Charge135.0135.0200.0200.0
Power S upply208/230-60-1208/230-60-1208/230-60-1208/ 230-60-1
M inimum Circ uit A m pac ity
Maximum Overcurrent Device
Elec tric al Conduit S ize
Power Supply (Inc hes)1/2 or 3/41/2 or 3/41/2 or 3/41/2 or 3/4
Approxim ate S hipping W eight241241301301
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the S & R plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
(1)
(2)
27.527.733.037.2
45455060
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.
7
CONDENSING UNIT SPECIFICATIONS
DSXC160[24-36]1A*
Dimensions
ModelDimensions - W x D x H
DSXC160241A *29 x 29 x 30¼
DSXC160361A *29 x 29 x 30¼
Open22 P S IG22 PSIG22 PSIG22 PSIG
Close50 PS IG50 PSIG50 PSIG50 PSIG
High Pressure Switch
Open610 PSIG610 PS IG610 PS IG610 P S IG
Close420 PS IG420 PS IG420 P S IG420 PSIG
Condenser Fan Motor
Horsepower1/61/61/61/6
F.L. Am ps1.11.10.90.9
Liquid Line, Inches O. D. *3/8"3/ 8"3/ 8"3/8"
Suc tion Line, Inches O .D.*3/ 4"3/4"7/ 8"7/8"
Refrigerant Charge100.088.0110.096.0
Power Supply208/230-60-1208/230-60-1208/230-60-1208/230-60-1
Minim um Circ ui t Am pac it y
Maximum Overcurrent Device
Electri cal Conduit Size
Power Supply (Inches)1/2 or 3/ 41/2 or 3/ 41/2 or 3/41/2 or 3/4
Approximate Shipping Weight198198202202
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the S & R plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
(1)
(2)
14.015.721.820.0
20203535
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit
breakers and wires in accordance with all national and/or local electrical codes. Use copper wire only.
8
CONDENSING UNIT SPECIFICATIONS
DSXC160[48-60]1B*
Dimensions
ModelDimensions - W x D x H
DSXC160481B*35½ x 35½ x 36¼
DSXC160601B*35½ x 35½ x 38¼
Open610 PSIG610 PSIG610 PSIG610 P SIG
Close420 PSIG420 PSIG420 PSIG420 PSIG
Conden ser F a n Mot o r
Horsepower1/61/61/61/6
F.L. Amps1.01.21.01. 2
Liquid Line, Inches O.D.*3/8"3/8"3/8"3/8"
Suct i on Line, Inc hes O. D. *1 1/8"1 1/8"1 1/8"1 1/8"
Refrigerant Charge135.0135.0200.0200.0
Power Supply208/230-60-1208/230-60-1208/230-60-1208/230-60-1
Minimum Circuit Ampac ity
Maximum Overcurrent Device
Elec t ric al Conduit S i z e
Power Supply (Inches)1/ 2 or 3/41/ 2 or 3/41/2 or 3/41/2 or 3/4
Approximat e Shipping Weight241241301301
*
Up to 24' in equivalent line length
(1)
Wire size should be determined in accordance with National Electrical Codes; extensive wire runs will require larger wire sizes.
(2)
Maximum Overcurrent Protection Device: MUST use Time Delay Fuse or HACR type Circuit Breaker of the same size as noted.
NOTES:
•Always check the S & R plate for electrical data on the unit being installed.
•Installer will need to supply 7/8" to 1-1/8" adapters for suction line connections (4 & 5 ton units).
•Installer will need to supply 3/4" to 7/8" adapters for suction line connections (3 ton unit).
•Unit is charged with refrigerant for 15' of 3/8" liquid line. System charge must be adjusted per Installation Instructions Final Charge
Procedure.
•Installation of these units requires the specified TXV Kit to be installed on the indoor coil. THE SPECIFIED TXV IS DETERMINED BY THE
OUTDOOR UNIT, NOT THE INDOOR COIL.
(1)
(2)
27.527.733.037.7
45455060
NOTE: This data is provided as a guide, it is important to electrically connect the unit and properly size fuses/circuit breakers and
wires in accordance with all national and/or local electrical codes. Use copper wire only.
Unit specifications are subject to change without notice. ALWAYS refer to the unit's serial plate for the most up-to-date general
and electrical information.
M O DE L : *SX C16 0361A* / CA *F3743*6* * + TX V / M BV C1 600* *-1* *, Design S ub co o ling @ A HR I 95°F Co nd ition s, 5° - 7°F @ the Ser v. Vlv .