Goodman ACV series, AMV series, AMH series, ADS series, AMS series Service Instructions Manual

...
Page 1
Service Instructions
80%, 90%, 95% Gas Furnaces & Accessories
ACS, ACV, ADS, ADV, AMH, AMS, AMV, DCS, DDS, DHS, DMS, GCH, GCS, GDH, GDS, GCV, GHS, GKS, GME, GMH, GMS, GMV
This manual is to be used by qualified, professionally trained HVAC technicians only. Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures or services performed by an unqualified person.
Copyright © 2006-2007 Goodman Manufacturing Company, L.P.
RS6610004 Rev. 2
November 2007
www.goodmanmfg.com www.amana-hac.com
Page 2
TABLE OF CONTENTS
IMPORTANT INFORMATION ........................... 2-3
PRODUCT IDENTIFICATION ........................ 4-14
OPERATING INSTRUCTIONS .................... 20-22
ACCESSORIES ........................................... 23-27
PRODUCT DESIGN .................................... 28-79
SYSTEM OPERATION ................................ 80-91
POLARIZATION & PHASING ............................. 92
MAINTENANCE ............................................ 93-95
SERVICING .................................................96-128
TROUBLESHOOTING .............................. 105-106
SERVICING TABLE OF CONTENTS ................ 98
ACCESSORIES WIRING DIAGRAMS ......129-131
IMPORTANT INFORMATION
Pride and workmanship go into every product to provide our customers with quality products. It is possible, however, that during its lifetime a product may require service. Products should be serviced only by a qualified service technician who is familiar with the safety procedures required in the repair and who is equipped with the proper tools, parts, testing instruments and the appropriate service manual. REVIEW ALL SERVICE INFORMATION IN THE APPROPRIATE
SERVICE MANUAL BEFORE BEGINNING REPAIRS.
IMPORTANT NOTICES FOR CONSUMERS AND SERVICERS
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS
WARNING
T
O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH,
DO NOT STORE COMBUSTIBLE MATER IALS OR USE GASOLINE OR OTHER
FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE.
WARNING
GOODMAN WILL NOT BE RESPONSIBLE FOR ANY INJURY OR PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE PROCEDURES. IF YOU INSTALL OR PERFORM SERVICE ON THIS UNIT, YOU ASSUME RESPONSIBILITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH
MAY RESULT.
MANY JURISDICTIONS REQUIRE A L ICENSE TO INSTALL O R SERVICE HEATING AND AIR CONDITIONING EQUIPMENT.
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT.
BE PRESENT.
DAMAGE, PERSONAL INJURY OR DEATH.
FAILURE TO DO SO MAY CAU SE PROPERTY
MULTIPLE POWER SOURCES MAY
2
Page 3
IMPORTANT INFORMATION
Special Warning for In stallation of Furna ce or Air Handling Units in Enclosed Areas such as Garages, Utility Rooms or Parking Areas
Carbon monoxide producing devices (such as an automobile, space heater, gas w ater heater, etc.) should not b e operated i n enclosed ar eas such as unventilated garages, utility rooms or parking areas bec ause of the danger of carbon monoxide (CO) poisoning resulting from the exhaust emissions. If a furnace or air handler is installed in an enclosed area such as a garage, utility ro om or parking area and a carbon monoxid e producing device is operated therein, there must be adequate, direct outside ventilation.
This vent ilation is necess ary to avoid the danger of C O poisoning wh ich can occur if a carbon monoxide producing device continues to operate in the enclo sed area. Carbon monoxide emis sions can be (re )circulated througho ut the structure if the furnace or ai r handler is operating in any mode.
CO can cause serious illness including permanent brain damage or death.
To locate an authorized servicer, please consult your telephone book or the dealer from whom you purchased this product. For further assistance, please contact:
CONSUMER INFORMATION LINE GOODMAN® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
customerservice@goodmanmfg.com
fax us at: (731) 863-2382
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-713-861-2500.
(Not a technical assistance line for dealers.)
Your telephone company will bill you for the call.
Your telephone company will bill you for the call.
CONSUMER INFORMATION LINE
AMANA® BRAND PRODUCTS
TOLL FREE
1-877-254-4729 (U.S. only)
email us at:
hac.consumer.affairs@amanahvac.com
fax us at: (931) 438-4362
(Not a technical assistance line for dealers.)
Outside the U.S., call 1-931-433-6101.
(Not a technical assistance line for dealers.)
3
Page 4
PRODUCT IDENTIFICATION
The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information.
G M S 9 070 3 B X A A
Product Type
A: Amana® Brand D: Amana
Distinctions
G: Goodman
®
TM
Supply Type
M: Upflow/Horizontal D: Dedicated Downflow C: Downflow/Horizontal H: High Air Flow
Furnace Type
E: Two Stage/X-13 Motor S: Single Stage/Multi-speed V: Two Stage/Variable-speed H: Two Stage/Multi-speed
Brand
AFUE
8: 80% 9: 90%
95: 95%
Nominal Input
Minor Revision
A: Initial
Release
Major Revision
A: Initial
Release
Additional Features
N: Natural Gas X: Low NOx
Cabinet Width
A: 14" B: 17 1/2" C: 21" D: 24 1/2"
Airflow Capability @ 0.5" ESP
3: 1200 CFM 4: 1600 CFM 5: 2000 CFM
045: 45,000 Btuh 070: 70,000 Btuh 090: 90,000 Btuh 115: 115,000 Btuh 140: 140,000 Btuh
4
Page 5
PRODUCT IDENTIFICATION
MODEL # MFG. # 80 % GAS FURNACES
ADS8* ADS8*****AA
Amana® Brand 80% Gas Furnace
changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks, and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry.The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. Chassis sizes are now 14",
17.5", 21" wide.
, 39" tall,
Dedicated Downflow
, Induced Draft, 39" 80% furnace redesign
ADV8* ADV8******AA
ADV8*****BA ADV8*****BA ADV8*****BB
AMH8*
AMS8* AMS8*****AA
AMV8* AMV8*****AA
AMH8*****AA AMH8*****AB AMH8*****AC
AMV8*****BA AMV8*****BA AMV8*****BB
Amana® Brand 80% Variable Speed Gas Furnace
2-Stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and Million-Air stainless steel tubular heat exchanger. Chassis sizes are now 17.5", 21" wide.
Amana® Brand 80% Variable Speed Gas Furnace
2-Stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control, sizes are now 17.5", 21" wide. BB models utilized the round nose inducer motor.
Amana® Brand 80% Gas Furnace
cabinet and front panels, PSC motor, standardized blower decks and a 120V silicon nitride igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5" 21, and 24.5" wide. ***AB Models used a round nose inducer motor. ***AC models revert back to Jakel square nose inducer.
Amana® Brand Gas Furnace
changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. Chassis sizes are now 14",
17.5", 21" and 24.5" wide.
Amana® Brand 80% Variable Speed Gas Furnace
or Right, 2-Stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and Million-Air stainless steel tubular heat exchanger. Chassis sizes are now 17.5", 21" wide.
Amana® Brand 80% Variable Speed Gas Furnace
2-Stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control,120 volt silicon nitride igniter and Million-Air stainless steel tubular heat exchanger. Chassis sizes are now 17.5", 21" wide. BB models used the round nose inducer motor.
120 volt silicon nitride igniter
, 39" tall, Upflow/Horizontal Left or Right, Induced Draft, new grey painted
, 39" tall, Upflow/Horizontal Right or Left, Induced Draft, furnace redesign
- 2 stage heat gas furnace, 39" tall, Dedicated Downflow,
- 2 stage heat gas furnace, 39" tall, Dedicated Downflow,
and Million-Air stainless steel tubular heat exchanger. Chassis
- 2 stage heat gas furnace, 39" tall, Upflow/Horizontal Left
- 2 stage heat gas furnace, 39" tall, Dedicated Downflow,
DDS8* DDS8******AA
DHS8* DHS8******AA
DMS8* DMS8******AA
GDH8*
GDS8*
GDH8*****AA GDH8*****AB GDH8*****AC
GDS8*****AA GDS8*****BA GDS8*****BB GDS8*****BC
Amana®
redesign changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5" and 21" wide.
Amana® Distinctions™ Brand 80% Gas Furnace
design), Induced Draft, furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5", 21" wide.
Amana® Distinctions™ Brand 80% Gas Furnace
furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14",
17.5", 21" and 24.5" wide.
Goodman® Brand 80% Gas Furnace
and front panels, PSC motor, standardized blower decks and a 120V Silicon Nitride igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5" and 21" wide. ***AB Models used a round nose inducer motor. ***AC models revert back to Jakel square nose inducer.
Goodman® Brand 80% Gas Furnace
new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5", 21" wide. ***BB Models used a round nose inducer motor. ***BC models revert back to Jakel square nose inducer.
Distinctions™ Brand 80% Gas Furnace
, 39" tall,
Dedicated Downflow
, 39" tall, Dedicated Downflow, 2-stage/multi-speed, Induced Draft,
, 39" tall,
, 39" tall, Upflow/Horizontal Left or Right, Induced Draft,
Dedicated Downflow
, 39" tall, Upflow/Horizontal Left or Right, (High Air Flow
, Induced Draft, new grey painted cabinet
, Induced Draft, furnace
5
Page 6
PRODUCT IDENTIFICATION
MODEL # MFG. # 80 % GAS FURNACES
GHS8*
GME8*
GMH8*
GMS8*
GMV8*
GHS8*****AA GHS8*****BA GHS8*****BB GHS8*****BC GHS8*****BD
GME8*****AA GME8*****AB GME8*****AC
GMH8*****AA GMH8*****AB GMH8*****AC
GMS8*****AA GMS8*****BA GMS8*****BB GMS8*****BC GMS8*****BD
GMV8*****AA GMV8*****BA
Goodman® Brand 80% Gas Furnace
Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5", 21" wide. ***BB Models used a round nose inducer motor. ***BC models revert back to Jakel square nose inducer.
Goodman® Brand
cabinet and front panels, X-13 motor, standardized blower decks and a 120V silicon nitride igniter.. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 17.5" and 21" wide. ***AB Models used a round nose inducer motor. ***AC models revert back to Jakel square nose inducer.
Goodman® Brand 80% Gas Furnace
painted cabinet and front panels, PSC motor, standardized blower decks and a 120V silicon nitride igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5" and 21" wide. ***AB Models used a round nose inducer motor. ***AC models revert back to Jakel square nose inducer.
Goodman® Brand 80% Gas Furnace
painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes are now 14", 17.5", 21" and 24.5" wide. ***BB Models used a round nose inducer motor. ***BC models revert back to Jakel square nose inducer.
Goodman® Brand 80% Variable Speed
2-stage Induced Draft, new grey painted cabinet and front panels, standardized blower decks and a 120V Silicon NitrideIgnitor. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. Chassis sizes of 17.5", 21" wide.
80% Gas Furnace
, 39" tall, Upflow/Horizontal Left or Right, (High Air Flow Design),
, 39" tall, Upflow/Horizontal Left or Right, Induced Draft, new grey painted
, 39" tall, Upflow/Horizontal Left or Right, Induced Draft, new grey
, 39" tall, Upflow/Horizontal Left or Right, Induced Draft, new grey
- 2 stage heat Gas Furnace, 39" tall, Upflow/Horizontal Left or Right,
6
Page 7
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
ACS9*
ACS9*
ACV9*
ACV9*
P1257001F
through
P1257006F
P1257007F
through
P1257010F
P1257703F,
P1257705F
P1257707F
Amana® Brand 90% Gas Furnace
new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
Amana® Brand 90% Gas Furnace
new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
(Note: The "P" numbers to the left include the following design changes.)
new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
Amana® Brand 90% Variable Speed
Right, 40" tall, 2-stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 21" and 24.5" wide.
Amana® Brand 90% Variable Speed
Right, 40" tall, 2-stage Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 21" and 24.5" wide.
(Note: The "P" numbers to the left include the following design changes.)
new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. We also have a new drain elbow with a side drain port hole added. It is used when placing the furnace in the horizontal left application.
, Downflow/Horizontal Left and Right, 40" tall, Induced Draft,
, Downflow/Horizontal Left and Right, 40" tall, Induced Draft,
Incorporates a
- 2 stage Gas Furnace, Downflow/Horizontal Left and
- 2 stage Gas Furnace, Downflow/Horizontal Left and
Incorporates a
AMS9*
AMS9*
P1256601F P1256606F
P1256607F
through
P1256610F
Amana® Brand 90% Gas Furnace
two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
Amana® Brand 90% Gas Furnace
two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
(Note: The "P" numbers to the left include the following design changes.)
new crimped designed blower housing and a new blower deck. The crimped blower housing will
fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by
not adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
, Upflow/Horizontal Left and Right, 40" tall, Induced Draft, new
, Upflow/Horizontal Left and Right, 40" tall, Induced Draft, new
Incorporates a
7
Page 8
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
Amana® Brand 95% Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new
two tone grey painted cabinet and front panels, standardized blower decks and a 120V Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. Two stage heat, single stage cooling.
Amana® Brand 95% Gas Furnace, Upflow/Horizontal Left and Right, 40" tall, Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
AMH95
AMS95
AMH95***AA AMH95***AB AMH95***AC
AMS95***AA AMS95***AB
AMV9*
AMV9*
P1257401F, P1257403F,
P1257405F
through
P1257406F
P1257407F,
P1257408F
Amana® Brand 90% Variable Speed - 2 stage Gas Furnace, Upflow/Horizontal Left and Right, 40" tall, 2-stage Induced Draft, furnace redesign changes that include new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
Amana® Brand 90% Variable Speed - 2 stage Gas Furnace, Upflow/Horizontal Left and Right, 40" tall, 2-stage Induced Draft, furnace redesign changes that include new two tone grey painted cabinet and front panels, standardized blower decks and a Surestart Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. (Note: The "P" numbers to the left include the following design changes.) Incorporates a new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
8
Page 9
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
Amana® Distinctions™ Brand 90% Gas Furnace, Downflow/Horizontal Left and Right, 40" tall,
Induced Draft, furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
Amana® Distinctions™ Brand 90% Gas Furnace, Downflow/Horizontal Left and Right, 40" tall, Induced Draft, furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. (Note: The "P" numbers to the left include the following design changes.) Incorporates a new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
Amana® Distinctions™ Brand 90% Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
DCS9*
DCS9*
DMS9*
P1257102F, P1257104F,
P1257106F
P1257107F P1257108F
P1256701F,
P1256706F
DMS9*
P1256707F
through
P1256710F
Amana® Distinctions™ Brand 90% Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, furnace design changes that include new two tone grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. (Note: The "P" numbers to the left include the following design changes.) Incorporates a new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
9
Page 10
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
GCS9*
P1257201F,
P1257202F
P1257204F,
P1257206F
Goodman® Brand 90% Gas Furnace,
new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
Downflow/Horizontal Left and Right, 40" tall, Induced Draft,
GCS9*
GCH9*
GCV9*
GKS9*
P1257207F
through
P1257209F
GCH9***AA GCH9***AB
P1257803F,
P1257805F
GKS9****AA GKS9****AB GKS9****AC
Goodman® Brand 90% Gas Furnace,
Downflow/Horizontal Left and Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. (Note: The "P" numbers to the left include the following design changes.) Incorporates a new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
Goodman® Brand 90% Gas Furnace,
Downflow/Horizontal Left and Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a 120V Silicon Nitride igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sie are now
17.5", 21" and 24.5" wide. Two stage heat, single stage cooling.
Goodman® Brand 90% Variable Speed
- 2 Stage Gas Furnace, 40" tall, Upflow/Horizontal Left or Right, Induced Draft, new grey painted cabinet and front panels, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 21" and 24.5" wide. (BA models use Surestat Silicon Nitride igniters.)
Goodman® Brand 92.1% Gas Furnace
, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
GMS9*
GMS9*
GMS95*
GMV9*
P1256801F
through
P1256802F
P1256804F,
P1256806F
P1256807F
through
P1256809F
GMS9****AA GMS9****AB
P1257603F -
P1257607F
Goodman® Brand 90% Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini­Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and
24.5" wide.
Goodman® Brand 90% Gas Furnace
, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini­Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and
24.5" wide.
Note: The "P" numbers to the left include the following design changes.
(
) Incorporates a new crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
Goodman® Brand 95% Gas Furnace
, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new grey painted cabinet and front panels, PSC motor, standardized blower decks and a Carbide Mini­Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and
24.5" wide.
Goodman® Brand 90% Variable Speed
- 2 stage heat Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, 2-stage Induced Draft, new grey painted cabinet and front panels, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes of 17.5", 21" and 24.5" wide.
10
Page 11
PRODUCT IDENTIFICATION
MODEL # MFG. # DESCRIPTION
GMV9*
GMH95*
GMV95*
P1257610F -
P1257611F
GMH95***AA GMH95***AB
GMH95***AC
GMV95***AA GMV95***AB GMV95***BA GMV95***BB
Goodman® Brand 90% Variable Speed
Right, 40" tall, 2-stage Induced Draft, new grey painted cabinet and front panels, standardized blower decks and a Carbide Mini-Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes of 17.5", 21" and 24.5" wide.
(Note: The "P" numbers to the left include the following design changes.)
crimped designed blower housing and a new blower deck. The crimped blower housing will not fit inside of the previous "P" numbers for this same model. Redesigned 90° drain elbow by adding a side drain port hole. The side port drain tube is only used when placing the furnace in the horizontal left application.
Goodman® Brand 95% Gas Furnace, Upflow/Horizontal Left or Right, 40" tall, Induced Draft, new two tone grey painted cabinet and front panels, standardized blower decks and a 120V Silicon Nitride Igniter. Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and a Million-Air stainless steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide. Two stage heat, single stage cooling.
Goodman® Brand 95% Variable Speed
40" tall, 2-stage Induced Draft, new grey painted cabinet and front panels, new standardized blower decks, new blower housing and a Carbide Mini-Igniter.(BA model has 120V Silicon Nitride igniters.) Left or right gas pipe entry. The furnaces also feature an integrated electronic ignition control and aluminized steel tubular heat exchanger. NOx Certified. Chassis sizes are now 17.5", 21" and 24.5" wide.
- 2 stage heat Gas Furnace, Upflow/Horizontal Left or
Incorporates a new
- 2 stage Gas Furnace, Upflow/Horizontal Left or Right,
11
Page 12
PRODUCT IDENTIFICATION
MODEL # MFG # DESCRIPTION
Fossil Fuel Kit. The AFE18-60A control is designed for use where the indoor coil is located
above/downstream of a gas or fossil fuel furnace when used with a heat pump. It will operate
AFE18-60A
N/A
with single and two stage heat pumps and single and two stage furnaces. The AFE18-60A control will turn the heat pump unit off when the furnace is turned on. An anti-short cycle feature initiates a 3 minute timed off delay when the compressor goes off.
AMU1620 AMU1625 AMU2020 AMU2025
GMU1620 GMU1625 GMU2020 GMU2025
ASAS-10 ASAS-11 ASAS-12 ASAS-18
CFB17 CFB21 CFB24
DCVK-20
DCVK-30
P1251305F P1251306F P1251307F P1251308F
N/A
P1251301F P1251302F P1251303F P1251304F
P1228004F P1228005F P1228003F
P1254001F
P1254002F
Media Air Cleaner. For use with current architectural grey Goodman® and Amana® Brand 80% and 90% variable speed furnace models. The Amana (AMU*) and Goodman (GMU*) Media Air Cleaner is a high efficiency air filtration device designed to remove dirt, dust, pollen and other microscopic particles from the air passing through it. Flexible performance range up to 2,000 CFM capacity. The air cleaner should be installed in the system so that all the system air is circulated through the air cleaner. The air cleaner will only remove the airborne contaminants delivered to it. Maximum performance is obtained when the system blower is set for continuous operation. Carbon filters (optional) are available.
Electronic Air Cleaner. For use with current architectural grey Goodman® and Amana® Brand 80% and 90% variable speed furnace models. The High-Efficiency Electronic Air Cleaner is designed to remove air contaminants down to .01 microns. Carbon filters (optional) remove odors. Dual indicator lights show unit operation at a glance. Electronic proving switch cycles the air cleaner On/Off with the system fan. Durable powder-coat paint finish resists corrosion.
Downflow Subbase Kit. For use with select Goodman®, Amana® Brand & Amana® Distinctions™ Brand furnace models ACS9, ACV9, DCS9, GCH9, GCS9, GCV9. These kits are available for the following furnace widths: 17.5" wide (CFB17), 21" wide (CFB21) and 24" wide (CFB24). The kits must be used to prevent excessive temperature from reaching combustible materials, if the furnace is installed on a combustible floor. This subbase effectively separated the furnace base and plenum from combustible materials. To ensure safe installation, do not install the counterflow floor base directly on carpeting, tile, or other combustible material other than wood flooring.
Concentric Vent Kit. For use with Amana® Brand furnace models ACS9, AMS9, AMS95, ACV9, AMV9, AMH95, DCS9, DMS9, GCS9, GMS9, GMS95,GCH9, GKS9, GCV9, GMV9,GMH95, GMV95. This kit is designed to allow terminations of a direct vent furnace to be
"concentrically" vented through a wall or roof. This kit allows a single penetration to support terminations for both the vent/flue and the combustion air intake pipe. The DCVK-20 (2") and DCVK-30 (3") kits are certified for models listed above. See specification sheets on future models for use of the vent kit.
Side Wall Only Concentric Vent Kit. For use with 90% furnace models ACS9, AMS9, ACV9,
0170K00000S
N/A
AMV9, AMH95, DCS9, DMS9, GCH9, GCS9, GKS9, GMS9, GCV9, GMH95, GMV9, GMV95.
This kit is to be used with 2" or 3" vent systems. The vent kit must terminate outside the structure. This kit is NOT intended for use with single pipe (indirect vent) installations.
12
Page 13
PRODUCT IDENTIFICATION
MODEL # MFG # DESCRIPTION
Dehumidistat. For use with Goodman® and Amana® Brand two-stage variable speed furnace
models ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9, GMV95. Wall mounted, 24 volt humidity control available as a Dehumidistat used to reduce the airflow in the air conditioning
DEHUM1
EFR01
FTK03A
HA02
P1227801F
P1221001
P1221002F
P1171304F P1171305F
P1129112F
mode when necessary to lower the humidity in an occupied home to prevent dew build-up associated with high humidity levels. This control features a moisture-sensitive nylon element and also provides positive ON-OFF settings for manual operation. The control is a normally closed switch that opens on humidity rise causing the blower to switch to a lower speed to control the humidity within the structure.
External Filter Rack Kit. For use with Goodman® and Amana® Brand 90% upflow variable speed gas furnace models AMH95, AMS9, AMS95, GMH95, GMS9, GMS95, DMS9, AMV9, GMV9, GMV95. This kit is intended to provide a location, external to the furnace casing, for installation of a permanent filter. The rack is mounted over the indoor air blower compartment area of either side panel, and provide filter retention as well as a location for attaching return air ductwork.
Furnace Twinning Kit. This kit allows Goodman® or Amana® Brand single stage 80% and single stage 90% gas furnaces to operate at the same time from a single thermostat. The two furnaces to be "twinned" must be the exact same model with their circulating air blowers set to deliver the same air flow at the same time. The furnaces may deliver different CFM's in the cooling mode, if applicable. This kit cannot be used to control more than two furnaces.
High Altitude Kit. The kit is designed to convert Goodman®, Amana® Brand & Amana® Distinctions™ Brand 80% gas furnace models (AMH8*, AMS8*, ADS8*, DMS8*, DDS8*, DHS8*, GDS8*, GMH8*, GMS8*, GDS8*, GHS8*) for higher altitudes. This kit is required when installing these furnaces above their maximum rated altitude. This kit contains # 43-49, 55-58 gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit.
HALP10
HALP11
HALP13
P1129112F
P1129113F
P1129112F
High Altitude Propane Gas Conversion Kit. Used on Goodman® and Amana® Brand 90% single stage (ACS9, AMS9, DCS9, DMS9, GCS9, GMS9) furnace models. This kit is required when installing furnaces above their maximum rated altitude. This kit contains propane gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit.
High Altitude Propane Gas Conversion Kit. Used on Goodman® and Amana® Brand 90% single stage (ACV9, AMV9, GCV9, GMV9, GMV95) furnace models. This kit is required when installing furnaces above their maximum rated altitude. This kit contains propane gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit.
High Altitude Propane Gas Conversion Kit. Used on Goodman® and Amana® Brand 90% two stage (ACV9, GCV9) furnace models. This kit is required when installing furnaces above their maximum rated altitude. This kit contains propane gas orifices. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installation instructions of the kit.
13
Page 14
PRODUCT IDENTIFICATION
MODEL # MFG # DESCRIPTION
HANG11-12
P1210305F P1210306F
High Altitude Natural Gas Kit
models
ACS9, AMS9, DCS9, DMS9, GCS9
the furnaces above their maximum rated altitude. This kit contains natural gas orifices. The orifices in the kit have been selected with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installations of the kit.
. For use with Goodman® and Amana® Brand 90% furnace
and
GMS9.
These kits are required when installing
HANG13-14
HANG16
HAPS27-29
HAPS31
LPLP01
LPT-00A
P1210307F P1210308F
P1210310F
P1210518F
through
P1210520F
P1210522F
P1237701F
N/A
High Altitude Natural Gas Kit
models
AMV9, GMV9, GMV95.
. For use with Goodman® and Amana® Brand 90% furnace
These kits are required when installing the furnaces above their maximum rated altitude. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installations of the kit.
High Altitude Natural Gas Kit
models
ACV9, GCV9.
These kits are required when installing the furnaces above their
. For use with Goodman® and Amana® Brand 90% furnace
maximum rated altitude. The orifices in the kit have been selected as a result of testing with the American Gas Association. They will provide appropriate derating at the altitude listed in the High Altitude Charts as shown in the installations of the kit.
High Altitude Pressure Switch Kit
furnace models
AMS9, ACS9, DCS9, DMS9, GSC9, GMS9, AMV9, GMV9 and GMV95.
. For use with selected Goodman® and Amana® Brand 90%
This kit contains a high altitude pressure switch that must be used at altitudes above the rated altitudes because of reduced air density.
High Altitude Pressure Switch Kit
furnace models
ACV9, GCV9.
. For use with selected Goodman® and Amana® Brand 90%
This kit contains a high altitude pressure switch that must be
used at altitudes above the rated altitudes because of reduced air density.
LP Gas Low Pressure Kit. Designed for application on Goodman® and Amana® Brand's 90% single-stage and two-stage gas fired furnace product installed on LP gas listed in this manual. The kit monitors gas line pressure with a pressure switch and disables the unit's gas valve if the line pressure drops below acceptable levels. Application of the LPLP kit is aimed at reducing the occurrence of sooted heat exchangers in product installed on LP gas.
LP Conversion Kit
models
ADS8, AMS8, GDS8, GMS8, DMS8, DDS8, DHS8, GHS8, ACS9, AMS9, AMS95,
DCS9, DMS9, GCS9, GKS9, GMS9 and GMS95.
. For use with Goodman®, Amana® Brand & Amana® Distinctions™ Brand
This kit converts
only
single-stage gas fired units from natural to propane gas. The conversion from natural gas (as shipped from the factory) to propane gas requires: replacing the burner orifices, replacing gas valve regulator spring (all single stage units) and applying identification labels.
NOx screens must be removed when
converting 80% furnaces to this LP kit.
LP Conversion Kit
LPM-03B
N/A
variable speed models. This kit includes the LP gas valve, (1.25mm, # 55 orifices), installation instructions and a label to show that the furnace has been converted.
LP Conversion Kit
LPM-05
N/A
models using a White-Rodgers 36G54 2-stage gas valve kit. Includes regulator springs, #55 orifices, instructions and a label to show the furnace has been converted to L.P.
Internal Filter Retention Kit.
RF000180
N/A
Distinctions™ Brand 90% bottom of the furnace and contains enough hardware for (10) furnaces. This kit is NOT to be used on horizontal applications.
Internal Filter Retention Kit.
RF000181
N/A
Distinctions™ Brand 90% bottom of the furnace and contains enough hardware for (10) furnaces. This kit is NOT to be used on horizontal applications.
SBT14 SBT17 SBT21 SBT24
N/A
Downflow Subbase.
furnace models furnace widths: 14" wide (SBT14) 17.5" wide (SBT17), 21" wide (SBT21) and 24" wide (SBT24).
14
. For use with Goodman® and Amana® Brand 80% and 90% 2-stage
. For use with Goodman® and Amana® Brand 2-stage variable speed
For use with Goodman®, Amana® Brand & Amana®
upflow only
furnaces. This kit allows a filter to be installed in the
For use with Goodman®, Amana® Brand and Amana®
counterflow only
furnaces. This kit allows a filter to be installed in the
For use with Goodman® and Amana® Brand 80% dedicated downflow
ADV8, ADS8, GDS8 and GDH8
. These kits are available for the following
Page 15
ACCESSORIES
AMANA® BRAND & AMANA® DISTINCTIONS™ BRAND 80% FURNACE ACCESSORIES
Model Number
Description
ADS80453ANA X X X X X
ADS80703ANA X X X X X
ADS80904BNA X X X X X
ADS81155CNA X X X X X
ADV80703BX X X X X X
ADV80905CX X X X X X
ADV81155CX X X X X X
AMH80453ANA X
AMH80703ANA X
AMH80704BNA X
AMH80903BNA X
AMH80904BNA X
AMH80905CNA X
AMH81155CNA X
AMH81405DNA X
AMS80453ANA X X X X
AMS80703ANA X X X X
AMS80704BNA X X X X
AMS80903BNA X X X X
AMS80904BNA X X X X
AMS80905CNA X X X X
AMS81155CNA X X X X
AMS81405DNA X X X X
AMV80704BXA X X X X X X
AMV80905CXA X X X X X X
AMV81155CXA X X X X X X
DMS80453ANA X X X X
DMS80703ANA X X X X
DMS80704BNA X X X X
DMS80904BNA X X X X
DMS80905CNA X X X X
DMS81155CNA X X X X
DMS81405DNA X X X X
DDS80453AXA X X X X X
DDS80703AXA X X X X X
DDS80904BXA X X X X X
DDS81155CXA X X X X X
DHS80453AXA X X X X
DHS80704BXA X X X X
DHS80905CXA X X X X
X - Available for this model (1) Up to 7,000 ft. (2) 7,001 to 11,000 ft. (3) 7,001 to 9,000 ft. Not used in this application. (4) 9,001 to 11,000 ft. (5) MUST use single stage thermostat with FTK03A Note: All installations above 7,000 ft. require a pressure switch change.
AFE180-60A
Fossil Fuel Kit
AMU
ASAS
Media Air Cleaners
Electronic Air Cleaner
EFR01
DEHUM1
Dehumidistat
FTK03A
External Filter Rack
Furnace Twinning Kit
(5)
(5)
HA02
LPM-03B
Propane Gas Conversion Kit
High Altitude Natural Gas Kit
XX
XX
SBT14
LPT-00A
Propane Gas Conversion Kit
SBT17
Downflow Subbase 14"
Downflow Subbase 17.5"
SBT21
Downflow Subbase 21"
(5) XX
(5) XX
(5)
(5)
(5)
(5)
XX
XX
XX
XX
LPM-05
Propane Gas Conversion Kit
15
Page 16
ACCESSORIES
GOODMAN® BRAND 80% FURNACE ACCESSORIES
16
Model Number
Description
GDS80453ANA X X X X X
GDS80703ANA X X X X X
GDS80904BNA X X X X X
GDS81155CNA X X X X X
GDH80453AXA
GDH80703AXA
GDH80904BXA
GDH81155CXA
GHS80453A*A X X X X
GHS80704C*A X X X X
GHS80703B*A X X X X
GME80704BX* X X X X X
GME80905CX* X X X X X
GME81155CX* X X X X X
GMH80453ANA X (5) X X
GMH80453AXA X (5) X X
GMH80703ANA X (5) X X
GMH80703AXA X (5) X X
GMH80704BNA X (5) X X
GMH80704BXA X (5) X X
GMH80903BNA X (5) X X
GMH80904BNA X (5) X X
GMH80904BXA X (5) X X
GMH80905CNA X (5) X X
GMH80905CXA X (5) X X
GMH81155CNA X (5) X X
GMH81155CXA X (5) X X
GMH81405DNA X (5) X X
GMH81405DXA X (5) X X
GMS80453ANA X X X X
GMS80703ANA X X X X
GMS80704BNA X X X X
GMS80903BNA X X X X
GMS80904BNA X X X X
GMS80905CNA X X X
GMS81155CNA X X X
GMS81405DNA X X X
GMV80704BXA X X X X X X
GMV80905CXA X X X X X X
GMV81155CXA X X X X X X
X - Available for this model (1) Up to 7,000 ft. (2) 7,001 to 11,000 ft. (3) 7,001 to 9,000 ft. Not used in this application. (4) 9,001 to 11,000 ft. (5) MUST use single stage thermostat with FTK03A Note: All installations above 7,000 ft. require a pressure switch change.
X(5)XXXX
X(5)XXXX
X (5)XXXX
X(5)XXXX
GMU
GSAS
AFE180-60A
Media
Electronic
Air Cleaner
Fossil Fuel Kit
Air Cleaners
EFR01
DEHUM1
Furnace
External
Dehumidistat
Filter Rack
HA02
FTK03A
High Altitud
Twinning Kit
LPM-03B
Propane Gas
Propane Gas
Conversion Kit
Natural Gas Kit
SBT14
SBT17
17.5"
SBT21
21"
Downflow Subbase
LPT-00A
14"
Conversion Kit
Downflow Subbase
Downflow Subbase
LPM-05
Propane Gas
Conversion Kit
Page 17
ACCESSORIES
AMANA® BRAND & AMANA® DISTINCTIONS™ BRAND 90% & 95% Furnace Accessories
Model Number
Description
ACS90453BXA X X X X X X
ACS90703BXA X X X X X X
ACS90704CXA X X X X X X
ACS90904CXA X X X X X X X
ACS90905DXA X X X X X X X
ACS91155DXA X X X X X X
AMH950453BXA X X X X X
AMH950703BXA X X X X X
AMH950704CXA X X X X
AMH950904CXA X X X X
AMH950905DXA X X X X
AMH951155DXA X X X X
AMS90453BXA X X X X X X
AMS90703BXA X X X X X X
AMS90704CXA X X X X X X
AMS90904CXA X X X X X X X
AMS90905DXA X X X X X X X
AMS91155DXA X X X X X X
AMS950453BXA X X X X X X
AMS950703BXA X X X X X X
AMS950704CXA X X X X X
AMS950905CXA X X X X X
AMS950905DXA X X X X X
AMS951155DXA X X X X X
ACV90704CXA X X X X X X X X X
ACV90905DXA XXX XXXX XXX
AMV90453BXA X X X X X X
AMV90704CXA X X X X X X
AMV90905DXA XXX XXXX
AMV91155DXA X X X X X X
DCS90703BXA X X X X X X
DCS90904CXA X X X X X X X
DCS91155DXA X X X X X X
DMS90453BXA X X X X X X
DMS90703BXA X X X X X X
DMS90704CXA X X X X X X
DMS90904CXA X X X X X X X
DMS90905DXA X X X X X X X
DMS91155DXA X X X X X X
AMU
ASAS
CFB17
CFB21
CFB24
DCVK-20
AFE180-60A
Fossil Fuel Kit
Media Air Cleaners
Electronic Air Cleaner
Downflow Subbase 21"
Downflow Subbase 17.5"
Downflow Subbase 24"
DCVK-30
Concentric Vent Kit (2")
Concentric Vent Kit (3")
EFR01
FTK03A
HALP10
HALP11
HANG11
HANG12
DEHUM1
Dehumidistat
External Filter Rack
Furnace Twinning Kit
High Altitude Propane Gas Kit
High Altitude Natural Gas Kit
High Altitude Propane Gas Kit
HANG13
High Altitude Natural Gas Kit
High Altitude Natural Gas Kit
HAPS27
HANG14
High Altitude Natural Gas Kit
HAPS28
High Altitude Pressure Switch
High Altitude Pressure Switch
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(5) (2)
(5) (2)
(5) (2)
(5) (2)
(5) (2)
(5) (2)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(4) (1) (2) (4)
(2)
(2)
(2)
(2)
(2)
(2)
(2) (3) (4)
(2) (3) (4)
(2) X X X
(2) X X X
(2) (3) (4)
(2) (3) (4)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) (1) (2)
(4) X X
(4) X X
(4) X X
(4) X X
(4) X X
(4) X X
(4) X X
(4) X X
(4) X X
LPLP01
HAPS29
High Altitude Pressure Switch
Propane Low Pressure Switch
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
(2) X X X
(2) X X X
LPM-03B
Propane Gas Conversion Kit
LPM-05
Propane Gas Conversion Kit
X - Available for this model (1) Up to 7,000 ft. (2) 7,001 to 11,000 ft. (3) 7,001 to 9,000 ft. Not used in this application. (4) 9,001 to 11,000 ft. (5) MUST use single stage thermostat with FTK03A Note: All installations above 7,000 ft. require a pressure switch change. Note: For installations in Canada the Goodman 90% furnace is certified only to 4,500 ft.
LPT-00A
Propane Gas Conversion Kit
17
Page 18
ACCESSORIES
GOODMAN® BRAND 90% & 95% Furnace Accessories
Model Number
Description
GCH90453BXA X X X X X X
GCH90703BXA X X X X X X
GCH90704CXA X X X X X
GCH90904CXA X X X X X
GCH90905CXA X X X X X
GCH91155DXA X X X X X
GCS90453BXA XXXX X X X
GCS90703BXA XXXX X X X
GCS90904CXA X X X X X X X
GCS91155DXA X X X X X X X
GKS90453BXA* X X X X X X X
GKS90703BXA* X X X X X X X
GKS90704CXA* X X X X X X X
GKS90904CXA* X X X X X X X
GKS90905DXA* X X X X X X X
GKS91155DXA* X X X X X X X
GMH950453BXA XXXX XXX X
GMH950703BXA XXXX XXX X
GMH950704CXA XXXX XX X
GMH950904CXA X X X X X X
GMH950905DXA X X X X X X
GMH951155DXA X X X X X X
GMS90453BXA X X X X X X X
GMS90703BXA X X X X X X X
GMS90904CXA X X X X X X X
GMS91155DXA X X X X X X X
GMS950453BXA X X X X X X X
GMS950703BXA X X X X X X X
GMS950904CXA X X X X X X X
GMS951155DXA X X X X X X X
GCV90704CXA X X X X XXXXX
GCV90905DXA X X X X XXXX (2) (2) (2) X (1) (1)
GMV90703BXA X X X XXXXX
GMV90905CXA X X X XXXXX
GMV91155DXA X X X XXXX
GMV950453BXA X X X X X X X
GMV950704CXA X X X XXXX
GMV950905DXA X X X XXXX (2)(3)(4)(2)X (1) (1)
GMV951155DXA X X X XXXX (2)(3)(4)(2)X (1) (1)
X - Available for this model (1) Up to 7,000 ft. (2) 7,001 to 11,000 ft. (3) 7,001 to 9,000 ft. Not used in this application. (4) 9,001 to 11,000 ft. (5) MUST use single stage thermostat with FTK03A Note: All installations above 7,000 ft. require a pressure switch change. Note: For installations in Canada the Goodman 90% furnace is certified only to 4,500 ft.
AFE180-60A
Fossil Fuel Kit
GMU
Media Air Cleaners
GSAS
CFB17
CFB21
CFB24
DCVK-20
DCVK-30
Electronic Air C leaner
Downflow Subbase 21"
Downflow Subbase 24"
Concentric Vent Kit (2")
Downflow Subbase 17.5"
Concentric Vent Kit (3")
0170K00000S
Concentric Side Wall Vent Kit (3")
EFR01
FTK03A
HALP10
HALP11
HALP13
HANG11
DEHUM1
Dehumidistat
External Filter Rack
Furnace Twinn ing Kit
High Altitude Propane Gas Kit
High Altitude Propane Gas Kit
HANG12
High Altitude Natural Gas Kit
High Altitude Natural Gas Kit
High Altitude Propane Gas Kit
(5) (2) (3) (4) (2)
HAPS27
HANG13
HANG14
High Altitude Natural Gas Kit
High Altitude Natural Gas Kit
HAPS28
HANG16
High Altitude Natural Gas Kit
High Altitude Pressure Switch
High Altitude Pressure Switch
LPLP01
HAPS29
HAPS31
LPM-03B
High Altitude Pressure Switch
Propane Gas Conversion Kit
High Altitude Pressure Switch
Propane Low Pressure Switch
XX
LPT-00A
Propane Gas Conversion Kit
(5) (2) (3) (4) (2) XX
(5) (2) (3) (4) (2) XX
(5) (2) (3) (4) (2) XX
(5) (2) (3) (4) (2) XX
(5) (2) (3) (4) (2)
(2) (1) (4) (2)
(2) (3) (4) (2)
(2) (3) (4) (2)
(2) (3) (4) (2)
XX
XX X
XX X
XX X
XX X
(3) (1) (2) XX
(3) (1) (2) XX
(3) (1) (2) XX
(3) (1) (2) XX
(3) (1) (2)
(3) (1) (2)
(5)
(5)
(5)
XX
XX
XX
XX
XX
(5) XX
(5) XX
(5) XX
(2) (3) (4) (2) XXX
(2) (3) (4) (2)
(2) (3) (4) (2)
(2) (3) (4) (2)
(2) (3) (4) (2)
(2) (3) (4) (2)
XXX
XXX
XXX
XXX
XXX
(2) (3) (4) (2) XXX
(2) (3) (4) (2) XXX
(2) (2) (2) X (1) (1)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4)
(2) (3) (4) (2)
(2) (3) (4) (2)
(2) X
(2) X
(2) X
(1) (1)
(1) (1)
(1) (1)
X
(1) (1)
X
(1) (1)
LPM-05
RF000180
RF000181
Propane Gas Conversion Kit
Internal Filter Retention Kit (Downflow)
Internal Filter Retention Kit (Upflow/Horiz)
18
Page 19
OPERATING INSTRUCTIONS
F
O
Y
O
R
R
E
A
D
B
E
o
n
d
u
o
y
W
A
R
N
p
lo
x
e
s
n
o
s
r
e
p
a
s
i
T
h
A
.
w
a
h
it
th
b
e
u
B
.
B
E
O
F
a
fo
e
a
r
a
e
c
b
u
s
ttle
e
H
A
W
D D d I p I c
C
. U
o
e
s
N
r
e
v
e
d
a
,
n
h
te
h
n
c
p
x
e
r
o
o
n
D
o
D
.
Im
m
e
th
a
e
p
m
e
t
s
y
s
f
I
IN
G
:
io
m
n
y
a
lt c
u
s
e
r
u
l in
a
ju
r
p
li
p
e
c
a
n
ig
n
itio
n
n
r
D
o
.
r
e
O
R
E
P
g
. B
r
s
a
o
m
s
e
s
o
th
e
f
n
T
D
T
O
o
n
o
tr
t
o
t
t
o
n
o
o
n
t u
o
s
a
m
i
e
d
m
h
.
n
F
e
o
a
c
o
u
f
y
ll th
a
fir
e
h
r
o
u
y
ly
n
o
t
o
e
s
u
y
r
t
't
n
d
o
ic
ia
.
F
n
o
l
io
s
o
n
.
t
h
is
t
e
u
s
ia
d
te
ly
c
p
lia
a
e
c
n
a
d
a
n
n
a
o
y
d d
n
n
E
e
g
e lo
o
O
to
y
u
c e e
t
llo
o
n
n e
a
ls
.
o
t c
r
a
ll
a
n
y
f
o
lo
s
s
r
a
h
t
o
n
e
s
o
w
ic
v
e
e
h
g
li
o
t
y
r
t
o
t
R
A
T
IN
G
e
to
s
m
r
u
s
e
a
h
s
i
a
s
.
r
Y
O
F
U
I
lig
a
n
t
y
h
e
y
a
n
h
e
l
e
n
h
o
p
a
n
y a
ll
c
ly
r
o
u
y
th
w
e
g
a
a
e
r
o
t
y
h
c
d
e
tm
r
p
a
e
to
n
d
p
u
s
If t
le
e
h
e
v
it
ir
p
a
e
r
,
a
r
o
t
e
te
m
e
n
c
a
li
p
p
u
q
a
ie
f
a
li
d
to
p
r
la
e
r
t
n
o
c
s
g
a
S
U
R
A
F
E
T
Y
F
O
R
E
O
P
E
R
A
T
IN
G
llo
o
f
t
o
w
e
s
e
h
t
in
s
lif
v
ic
h
s
ie
v
S
a
t
c
in
g s o n
h
in
r
a
c
p
if d
e
c
l
o
e
p
g
p
o
r
ty
r
.
e
e
p
a
a
h
u
e
h
t
t
e
m
ll n
e
h
t
r
E
M
p
lia
p
s
ic
r
y
o
s
s
a
u
s
p
a
g
u
r
t.
o
w
ill n
ll
a
te
d
r
n
a
y
v
r
e
s
n
a
w
ic
h
e
s
i
t
I
.
t
o
il
tic
a
m
o
a
t
lly b
y
e
r
n
r
b
u
l
l
a
ll e
a
L
w
p
r
e
p
y
d
u
n
o
a
r
t to
x
th
flo
e
d
a
n
a
ir
n
G
A
S
L
.
e
c
n
;
h
c
it
b
r
u
u
ild
in
g
li
p
p
u
o
r
f
r
e
lie
's
in
r
tr
s i
l
p
p
u
s
s
e
r
tu
n
th
r
g
e
o
t p
in
h
s
u
ifi
l
a
q
u
s
d
e
r
y
ir
p
a
m
a
b
s
a
h
t
r
a
n
ic
h
c
e
t
ic
e
p
f
t
th
o
r
a
a
h
h
e
b
e
s
io
s
n
t
u
c
r
in
t
s
m
a
d
e
,
a
g
u
ip
q
e
d
p
ig
h
l
s
t
.
n
h
d
a
ia
e
c
n
l
p
p
a
e
h
t o
r
w
l
il
.
m
a
tio
c
u ,
c
s
a
o
r
c
i
v
e
r
s
e
u
n
e
e
i
n
a
e
c
o
u
n
n
tu
u t
n n
o
e
lt in
n
o
n
d
's
e
ig
o
h
r
b
.
s
l
o
r
.
t
le
n
e
r
v
b
n
r
y
fir
a
e
e
r
d
.
e
r
w
t
a
in
t
c
p
e
s
tr
o
l
.
r
e
w
t
a
r
e
A
R
V
E
A
I
L
A
V
S
S
E
la
le
is
q
u
r
tra
n
e
p
r
o
c
C
e
A
.
m
u
a
u
d
'a
A
B
.
V
e
n
r
u
n
c
e
p
e
Q
U
N
e
C
.
q
u
S
i la
é
p
r
te
n
d
é
D
N
e
.
d
a
te
c
e
m
r
to
u
E
R
ttr
e
în
o
r
a
t
n
i d
o
m
t
llu
A
le
f
i
e
o
ta
r u
v
E
o
p
m
a
r
e
t
l
c
e
p
n
s
h
n p e
t
e d
a l'e
M
T
I
le
e
a
lle
e
p
p 'u
a
m
N
r
d
in
s
e
n
N N n A e R f S
in
u
la
a
e
r
d
e
n
c
s
ic
la
c
c
o
E
in
s
t
s
c
u
r
le
c
é
d
h
c
e
t d
n
d
s
e
m
a
o
s
la
u
p
o
c
e
n
il
e
a
r
is
d
itif
s
p
o
n iq
e
m
u
t
t
e
n
le
r
e
b
le
û
u
r
T
D
E
L
E
r
o
u
t
a
u
u
t
o
t
r
u
e
d
e
g
.
a
z
s
z
a
g
n
t
o
p u
'a
u
s
m
c
c
t
S
R
E
F
A
I
t
e
n
t
s
a
p
e
h
u
c
o
t
e
r
e a
u
is
il
r
e
'u
t
le
e
p
p
im
r
m
e
m
p
n
lo
a
y
p
s
e
à
r
e
t
e
c
n
is
r
e
u
s
r
o
u
p
i
e
n
o
n
s
e
r d
e
ie
n
c
.
s
o
u
t
u
o
e
r
s
s
m
n
a
in
e
;
ja
e
tte
n
te
s
r
e
u
r
e
l
p
a
e
p
;
fo
la
e
r
c
m
r
e
x
e
n
u
r
h
e
d
ir
s
v
e
s
r
e
u
, c
a
p
m
o
u
q
ie
n
lifié
a
r
p
a
u
t
o
t
e
r
m
m
q
d
a
e
n
N
T
M
D
E
E
E
N
A
M
R
C
Q
ic
u
q
o
N
T
tio
n
u
r
m
t
r
e
p
m
d
'a
b
le
m
r
F
d
e
R
e
lu
s
le
r
'IL
d
r
e
c
a
u
n
u
c
é
d l
n
t
la
d
e
n
e
n
e
r m
a
c
o e
t
n
a
n
p
lo
e
c
e
te
m
p
o
u
e
i
t
d
i o
u
n
:
d
s
le
s
n
a
p
ie
d
n
e
c
in
n
m
s
g
e
a
a
h
ie
v
s
d
e
e
o
e
d
s
p
a
e
t
r llu
m
e
a
q
g
u
p
N
e
.
u
r
e
l
û
r
a
n
lle
u
e
n
e
m
A
IR
E
F
O
p
ie
'a
l
r
a
p
p
l
ifle
n
d
p
s
è
r
r
e
u
q
lo
d
s
r
u n
u
a
e le
g
r is
s
d
iv
u
e
a
A
Y
U
N
E
r
e
'a
m
u
ll
'a
p
l
t
u
p
r
r
e
in
t
n
u
o
p
h
é
l
é
t
ia
r
in c
e
io
t e r
u
n
d
e
n
n
t le
e
te
m
fo
é
p
t
e
n
h
o
ttr
e
le
in
s
s
.
z
a
p
a
,
d
o
é
n
p
l
e
l
'a
d
ie
v
e
r
lo
p
e
m
d
e
r
, n
é
e
c
a
p
e
e
i
c
i
n
h
u
q
n
tte
o
d
u
la
e
n
o
in
u
n
u
s
l
i
e
r
p
a
a
p
o
u
t
e
n
n
p
l'a
in
r
e
t
e
c
p
s
e
è
m
t
s
y
s
t é
p
lo
g
n
o
l'a u
T
T
R
E
H
E
IR
L
E
e
e
r
s
n
e
u
é
r
o
u
rie
m
u
i
e
v
i a
a
s
t.
N
C
r
u
u
p
ir
s
O
a
p
r
e
u
a
n u
ú
d t
u
r
e
le
p
d
m
'o
u
te
s
f
li
a
r
e
e
c
a
'il
tie
a
r
p
d
e
é
s
lle llu
o
r
n c
s
ls
a
e
t
d la
e
.
D
i
é
s
n
r
r
i
til à
p
n
é
p c
d
e
p
t m
e
n
n
a
n
u
p
x
e
e
, d
e
s
in
.
e
s
Il
.
e
s
u
e
s
e
m
e
r
t
n
T
IO
N
N
e
c
é
r
e
l
h
e
n
c
c
,
r
t
l
E
U
R
D
l
e
iq
u
e
r
le
t
c
e
im
â
t
b
le
d
is
r
e
u
s
v
.
n
o
is
i
tio
d
s
n
u
s
le
c
i
v
e
r
d
u
io
s
s
n
f
e
f
c
e
t
te
n
d
r
e
la
q
o
n
c
Q
i
u
.
r
e
a
r
u
p
e
.
e
i
d
é
t
g
n
o
l
p
. A
e
p
p
le
r
e
il
t
e
r
a
ô
r
n
t
o
e
e
l
l'e
u
a
s
a
n
á
a
s
p
te
c
e
l
u
lo
io
s
n
io
s
s
n
t
E
R
,
r
a
E
G
A
Z
;
.
n
t
z
a
g
e
e
s
d
e
a
g
z
e
t
.
e
u
t
é
n
u
t
.
E
S
E
I
r
p m e
s o
i
d
R
h
'y
s o
i
e
e
p
le p
s itio p
M
L
is
e
E
Ê
T
R
!
le
c
,
r
r
e
r
if
p
E
tio
p
e
p
e
n
u
le l'a
c
. f
r
z
e
ie
s
r
é
u
u
r
p
à
a
t
t
s
o
m
r
h
e
t
lim
ta
e
n
tio
n
r
g
n
e
a
é
m
l
i
e
a
e
to
u
m
a
tiq
m
b
le
û
r
u
r
a
o
c
d
u
r
e
le
i
v
m
in
in
u
q
)
(
5
a
u
t
o
t
r
e
l
a
le
p
h
t
il n s l'a
U
D
le
o
e
o
u
t
r
o
u
d
le
e
c
é
R
l
t
é
!
r
e
P
s
a
s
ie
n
s
é
u
u
r
p
d
s
'o
u
d
e
r
d
r
e
i
v
o
c
u
n
p
la
le
e
c
p
s
o
u
s
e
il
r
a
m
r
e
à
a
t
t
s
o
m
s
e
e
e
in
u
it
.
s
e
t
il e
e
r
p
e
p
is
n
s
fo
r
u
r
e
C
R
O
U
E
G
A
Z
m
r
o
s
h
e
t
lim
n
e
ta
tio
à
r
d
e
d
e
u
d
le
ie
v
r
.
r
e
c
r
la
p
e
c
n
e
tio
n
le
r
e
r
l'a
a
p
g
a
le
r
le
e
n
.
e
r
n
e
r
e
E
T
p
o
a
le
e
.
n
ttr
e
'a
l
e
l
r
p
a
io
t
c
d
z
o
P
O
r
r
e
ro
e
s
n
s
a
tt
e
A
R
C
M
u
p u
d
pas
e
d
u
l
'a
d
e e
,
d
u
n
p
n
g
t
c
ô
r
n
n
H
E
é
s
d
e
n
s
o
i
t
c é
t
iq
tte
u
e
l
e
u
r
t
a
é
r d
e
l'a
e
p
s
'u
d
n
é
t
o
e
y
a
s
e
s
n
t.
O
"
à
a
z
g
u
la
r
e
is
r
e
s
y
e
il,
r
p
a
p
d
u
e
r
e
a
g
B
in
e
s
d
tte
tiq
é
u
e
à
r
e
l'é
s
s
a
p
à
a
z
g
u
O
"
'a
é
d
s
c
c
.
.
e
u
r
t
a
é
r
d
s
m
,
e
h
c
a
r
c
o
t
e
n
l
u
p
u
n
r
te
h
n
c
.
a
z
'A
L
D
M
'A
P
P
A
t
a
m
e
r
é
p
tr
iq
d
e
u
e
tio
d
n
s
'e a
g
d
u
le
d
'a
a
u
e
u
r
s
é
it
u
r
c
.
b
p
lu
s
a
a
p
s
y
r
c
c
z
t
s
tt
e
u r
e
ic
IS
R
u
n
z
c
c
e
s
s
a
e
il.
r
è
m
t
e
à
A
R
R
E
F
F
h
a
o
m
.
S
u
r
.
e ta
N
/
ir
s
iy
'a
l
e
i
E
e
r l'a
tr
e
à
è
T
/
p
i c
c
p
M
é r
d
n
S
"
to
e
r
p
u
t le
è
r
p
is
p
r
u
d
s
'e
t le
s
c
,
s
a
é
c
s
d
e
n
s
o
i
t
s
e
iv
u
a
A
R
C
.
e
e
le
s
is
io
s
m
I
O
N
é
i
it
u
r
n
.
H
E
"
n
IL
la
p
lu
b
.
s
e
s
s
a
il s
e
'il
r
a
p
p
tie
.
n
"
O
A
R
R
E
T
/
F
F
.
s
"
1
2
1
1
7
7
0
0
N
r
in
t
s
s
e
tte
c
e
d
m
e
t
la
é
le
tr
iq
c
n
t
a
é
t
e
, n
u
e
e
lle
u
n
m
n
ô
le
r
t
p
s
e
o
t
d
e
r
u
u
r
e
o
n
a
p
l
à
t
e
c
d
e
r
e
g
d
a
z
ô
le
r
t
n
a
e
n
n
a
e
n
t
io
s
m
e
t
la
t
e
s
p
a
m
C
o
m
t a
le
p
e
p
d
u
e
r
e
P
E
R
D
E
L
la
à
t
a
é
n
le
o
s
é
ra
p
c
n
t
o
le
a
p
O
P
E
R
A
T
IN
N
S
T
I
t
w
p
a
u v
c
n
!
n
. e
o T a
F
o
f l le
R
y
e a e
l n
r
e
le
e F
d
p o
n
c
s
lo w
o
s
U
C
O
N
T
I
S
A
R
R
1
.
o
n
e
v
b
o
a
io
n
t
a
m
r
o
in
f
s
t
s
in
g
.
t
t
e
p
lia
p
.
e
c
n
d
w
ith
a
n
ig
itio
n
n
.
n
e
r
u
b
h
e
t
lig
s
ly
t
h
a
h
b
y
r
e
to
r
O
F
"
a
o
r
t
a
u
th
e
a
r
l
f
B
"
o
llo
w
o
a
b
e
v
m
e
ll
G
IN
L
A
R
D
in
.
g
t
e
t
s
,
e
t
a
e
r
n
T
r
u
o
y
ll
a
c
d
a
p
m
o
n
G
A
S
s
w
t
e
s
to
r
e
th
m
.
r
d
e
to
r
e
v
"
l.
e
n
a
p
s
.
r
n
d
.
io
.
n
t
P
i
o
s
"
F
g
y
n
. T
s
a
n
h
e
o
o
o
u
y
f
I
.
r
"
A
S
E
T
R
IV
E
E
G
A
U
Z
L
r
u
y
T
e
IN
.
A
P
O
P
L
ti
t
.
n
g
e
a
p
lia
p
c
n
P
o
s
O
F
F
"
E
L
M
A
N
O
N
"
M
A
N
U
A
G
L
E
V
E
R
S
H
O
O
N
P
O
S
I
A
N
C
I
E
e
io
it
n
.
la
p
o
2
.
R
le
é
g
.
3
. C
p
o
u
4
C
e
a
.
t
d
'a
llu
a
llu
m
5
.
P
s
o
u
it
s
p
o
6
. A
te
n
t
.
z
g
a
A
E
R
V
I
U
E
, E
L
A
/M
R
A
S
N
W
T
IO
N
G
A
Z
p
la
n
8
1 1
s S
7
.
. R
9
.
0
.
1
.
d
q
.
1
. C
2 fa 3
.
p
.
4
c
A
R
R
la
r
u
'il n
P
s
o
u
s
p
o
it
e
m
M
r
t
t
e
R
l
é
g
e
S
i l'a
u
r
t
s
n
i
g
e
a
a
lifié
u
R
g
é
u
o
u
t p
P
o
u
s
o
N
e
R
m
e
N
P
O
S
C
H
E
"
G
S
T
O
1
.
2
.
3
.
4
. T
D
5
. P D
6
. W
th
o
7
. to
8
. R
9
.
0
1 1
1
s
1
.
2
. T
3
. P D 4
.
R
e
P
!
th
is
la
l.
e
b
h
e
t
S
e
t
T
d
s
in
g P
T
p .S .If
o
f
O
S
if
R
r
h
e
t u h
e
u
m
n a
u
u
o
e
e
s
p
a
ll
f
o
f
n
r is
lia
p
p
a
n
c
w
i
h
e
c
i
v
o
t
y
o
r
t
o
t
n
h
t
s
e
g
h
a
f
n
e
c
o
o
r
o
t
a
it
fiv
(
5
e
)
g
a
r
o
e
ll
f
ll g
e
n
s
e
m s
h
e
t
y
t
e
f
a
th
is
la
e
b
,
s
n
o
t
o
g
o
c
a
s
g
h
s
O
N
"
"
.
p
la
e
e
a
c
c
c
e
ll
a
o
n
n
r
e
h
t
o
t
w
r
e
t th
s
o
m
r
e
th
e
a
lia
p
p
i
h
llo
e
t
w
n
G
a
s
f
f
T
o
ic
v
te
e
r
h
c
T
O
T
U
e
h
t
e
h
t
t
e
o
n
ff a
r
u
ll e
is
ic
v
e
r
e
th
h
s
u
g
e
o
n
o
t fo
c
r
o
c
la
e
p
e
c
e
f
a
s
e
h
t
d
a
lo
o
t
a
t
t
s
o
m
o
t
o
w
r
e
h
e
t
e
is
c
e
ip
u
q
h
a
o
m
u
t
a
tic
l
b
h
e
t
h
t
g
i c
s
tr
o
o
n
l le
.
in
m
te
u
t
o
s
,
s
lu
c
n
in
d
i
g
,
s
a
S
T
O
P
a
tio
m
r
o
n
f
I
.
l if
n
't s
o
d
y
o
u
.
e
p
t
s
t
e
x
n
r
e
v
e
l
o
l
r
t
p
s
e
s
l.
n
e
a
e
l
ic
r
t
c
e
n
c
a
li
p
p
a
to
ta
e
t
d
ir
s
e
w
n
c
ill n
t
o
"
io
s
n
t
c
u
r
t
s
ia
n
A
l
p
p
"
e
c
ic
n
ia
n
g
o
r
a
R
N
O
F
m
r
to
t
a
t
s
o
le
tric
c
p
o
b
t
e
r
e
p
s
a
tr
n
o
o
c
.
e
r
t
n
e
c
c
a
l
o
19
Page 20
OPERATING INSTRUCTIONS
F
O
Y
O
R
U
R
E
A
D
B
E
F
y
f
I
o
n
d
u
ju
n itio
O
s
t u d
e
n
c
o
:
lt c
u
r
s
e
a
y y
r
e
c
n
D
o
P
. B
m
e
flo
e
D
tr
t
o
t
t
s
t
a
i
. F
n
a
c
fir
h
u
r o
y
r
t
F
o
.
s
i
h
t
c
a
a
e
n
a
a
u
o
f
lo
s
s
r
o
h
a
t
n
o
s
e
d
o
d
ic
v
e
w
e
h
ic
o
li
g
t
y
r
t
o
n
t
E
N
R
G
A
T
I
s
t
o
e
e
s
m
u
r
h
s
i
s
a
g
a
v
e
o
.
r
O
Y
O
S
F
U
I
to
y
lig
t
a
h
y
n le
e
c
n
y
a
h
u
c
e
a
p
n
y
o
e
h
e
o
ls
r
n
l
a
ll
o
r
c
u
y
y
llo
a
g
w
e
t
h
e
r
t
o
n e
t
c
y
y
h
a
c
d
tm
e
r
p
e
a
d
a
n
to
h
s
u
p
.
If th
le
e
e
v t
i
e
a
ir
p
r
o
,
o
e
te
a
m
r
t
a
p
p
lia
i
e
c
n
ll
ie
if
d
l
a
q
u
a
to
r
e
d
p
n
la
c
g
o
r
o
t
n
c
s
a
A
R
W
N
IN
G
e
x
p
lo
io
s
m
n
a
o
n
s
r
p
e
l in
T
A
.
w th
B
B
.
a
b
s
W
C
. U
N
h
te
o
D
D
.
Im t
s
a
p
s
i
h
p
lia
a
h
it
ig
n
n
.
b
n
r
e
e
r
u
E
F
O
R
E
g
r
e
f
o
a
a
r
o
s
e
a
s
u
e
c ttle
e
o
t
h
n
T
H
O
A
T
o
n
D
o
D
o
n
o
o
d
n
o
m
e
m
I
h
n
p
o
e
o
u
y
f
I
ll th
a
c
o
e
s
n
ly
y
o to
e
s
u
r
e
v
e
't
o
n
d
d
a
n
,
h
n
c
ic
ia
.
n
l
p
x
e
r
o
i
o
s
e
u
s
o
t
n
o
e
ly
t
a
m
e
i
d
a
h
e
lia
p
p
n
a
d
n
m
e
t
s
y
S
R
A
F
E
T
Y
O
R
E
O
P
E
R
A
T
IN
G
llo
o
f
w
h
e
t
t
o
in
s
p
g
life
.
e
v
a
h
a
u
e
h
t
t
h
m
s
e
e
ll n
h
t
ie
r
M
E
a
lia
p
p
s
ic
r
t
o
y
in
s
g
s
a
s
s
p
u
g
a
r
o
u
n
t.
in
o
w
r
ill
a
l
l
a
c
t
p
r
e
d
y
a
n
f
v
e
r
s
a
e
n
l w
h
ic
e
s
ro
ty
e
r
p
e
is
t
I
.
lo
t
i
p
a
tic
to
m
a
y
ll
y
b
e
r
n
u
r
b
n
u
o
a
r
l
l
a
ll e
x
flo
t
to
e
t
h
n
d
a
ir
a
n
a
G
A
S
L
L
e
.
n
c
w
h
;
c
t
i
b
r
ild
u
u
in
g
p
u
p
li
e
r
o
r
f
l
p
ie
's
in
r
tr
s
p
p
li
u
s
s
r
e
th
e
g
n
t
r
u
r
p
h
in
t
u
s
o
n
u
q
s
ie
d
f
li
a
y
a
m
a
ir
p
e
a
h
s
t
a
r
p
b
e
c
i
n
h
ic
c
e
t
p
y
t o
a
r
th
f
e
b
h
s
a
h
e
io
n
in
m
d
a
q
ip
u
lig
a
h
h
t
d
r
o
w
il
.
a
m
t
u
c
,
c
a
s
o
r
v
r
e
r
e
s
e
e
n
ia
n
c
e
u
n
s
t
tr
u
c
s
e
a
g
,
e
d
p
h
s
t
d
n
.
a
p
li
a
p
e
e
n
c
l
n
's
e
ig
o
r
b
h
io
.
n
s
n
l
o
tr
o
.
le
e
r
v
t
y
b
n
r
u
ic
e
u
lt in
a
fir
e
.
r
e
w
t
a
d
r
u
n
e
in
to
t
p
c
e
s
o
n
l
tr
o
.
r
e
w
a
t
d
r
e
n
A
R
V
A
E
I
L
A
V
E
R
S
S
E
T
M
I
la
le
ttr
le
e
is
e
d
q
u
r
e
tra
e
n
în
a
e
lle
o
r
p
r
o
c
C
e
p
a
p
t
A
.
m
n
u
i d
'u
o
t
a
u
m
a
d
'a
llu
m
A
B
.
V
A
N
le
if
e
n
r
r
u
e
d
o
e
n
c
ta
r
e
in
s
n
e
v
p
u
e
Q
U
E
N N n A e R f S
C
D
in
N
e
o
u
p
.
q
la
u
S
i la
m
a
r
e
r
a
é
p
r
te
te
n
d
e
le
c
d
é
n
c
s
a
p
N
e
.
d
l'e
s
n
a
te
h
ic
n
c
e
m
r
p
la
c
to
te
u
c
o
E
in
s
tr
c
u
s
le
c
h
e
d
é
c
t d
n
e
d
s
m
a
p
la
o
s
u
o
c
e
n
e
il
r
a
is
d
o
p
n
itif
s
n
e
t
iq
m
e
u
t
le
r
e
b
le
û
u
r
T
D
E
L
E
o
u
a
t
u
u
t
o
t
t
F
o
s m
;
h
s
ie
r
d
r
u
. R
z
a
g
e
g
p
s
z
a
t
n
o
'a
u
s
m
c
c
u
R
E
A
I
S
e
t
n
t
s
a
p
e
h
r
e
u
o
c
t
e
a
u
is
il
r
e
'u
t
im
le
p
e
p
r
m
e
n
a
y
o
l
p
m
te
à
e
c
p
s
e
r
u
e
s
s
i
n
r
u
r
n
e
o
n
s
r
e
p
i
d
e
n
ie
c
.
s
u
o
t
u
o
e
r
s
n
a
in
;
e
j
a
e
tte
n
te
s
r
e
u
le
a
p
p
e
r
fo
la
e
r
c
m
r
x
e
u
e
n
r
e
ir
v
s
e
r
e
d
u
, c
a
p
m
o
a
u
lifié
q
n
p
r
a
u
t
o
t
e
r
m
d
q
a
e
m
n
N
T
E
T
T
R
M
D
E
E
N
A
M
R
C
H
E
L
Q
u
i
e
n
q
u
o
n
N
tio
e
m
e
l
r
le
'IL
e
a
c
n
d n
r m
n
p
e
p
t
u
c
T
:
s
n
s
a
n
d
n
e
c
in
n
u
r
m
s
g
e
a
m
ie
v
e
d
e
t
r
e
t
p
r
o
a
p
s
'a
d
llu
g
a
m
le
û
r
u
b
r
N
.
m
e
u
lle
a
n
m
F
R
E
A
I
F
l'a
ie
d
e
p
r
a
p
r
p
le
e
if
n
r
lu
s
q
s
d
lo
u
r
iv
n
a
e
u
a
r
A
U
Y
'a
d
r
llu
m
e
r
e
in
t
n
u
c
u
n
u
h
p
o
é
l
é
t
d
é
ia
n
e
te
m
é
p
h
t
le
t
la
le
tr
e
t
le
.
a
z
g
e
n
p
o
é
r
e
d
l
le
e
n
r
e
i
e
v
lo
p
m
e
a
is
o
in
c
e
,
é
c
n
e
c
t
h
ic
n
ie
n
e
n
tte
a
o
u
d
o
l
o
u
io
s
n
a
p
p
r
a
e
t
c
te
m
e
n
t o
u
in
r
o
u
c
e
p
s
è
t
s
y
s
d
u
e
i
n
o
i
p
é
é
t
t
e
le
e
s
p
é
r
u
o
u
ie
d
ie
a
r
ls
, d
u
m
h
a
in
s
e
ill
u
v
e
e
d
q
e
i a
u
llu
m
e
e
n
t
a
s
p
.
t
n
e
O
N
C
T
é
d
u
p
o
r
l
d
è
s
u
p
la
n
l'a
u
e
ir
e
t
l
.
o
s
d
u
u
O
N
D
E
l'a
ie
r
l
p
a
p
r
é
le
u
r
e
p
u
t
r
e
l
s
n
d
a
n
e
t le
fo
is
n
r
u
e
o
n
v
n
ú
d
tio
c
u
in
s
r
t
s
le
p
le
a
p
e
r
,
is
d
'a
s
m
d
r
d
r
e
'o
u
til à
te
e
p
n
s
a
q
u
a
lif
.
e
l
a
r
p
a
e
in
d
e
n
c
n
u
'il
é
s
t
l
a
i
e
A
ie
.
t
r
a
p
n
e
te
l'a
r
a
p
p
m
c
e
d
e
n
o
lo
d
n
é
s
g
a
E
IR
E
te
e
c
p
s
e
r
n
t m
a
n
p
e
x
n
e
s
e
s
e
.
e
l
I
.
e
s
e e
r
t
IO
N
N
c
e
le
r
h
e
c
c
,
r
E
U
R
D
c
iq
e
u
r
t
m
e
i
b
t
â
d
u
r
e
s
is
o
in
.
d
s
n
u
s
ic
v
r
e
u
d
n
o
i c
e
f
e
t
la
e
d
te
r
Q
u
ic
n
o
p
e
e
r
u
r
ie
.
p
lo
g
n
é
p
le
p
e
e
r
il e
t
e
le
ô
r
t
l'e
a
u
n
s
á
a
s
p
u
e
l
lo
io
s
n
io
s
s
n
t
s
E
R
,
a
r
E
G
A
Z
;
.
t
n
e
g
a
z
d
e
s
e
a
g
z
.
t
e
f
e
u
q t
é r
u
n
t
.
M
E
N
S
E
I
r
m
s o
i
d
R
h
'y
s o
i e
e
p
le p
s itio p
M
E
T
Ê
tio
s
n
le
r
th
l
e
r
'a
e
p
a
r
p
e
g
a le
e
r
b
l
e
e
.
n
c
e
r
n
e
if
,
p
r
e
E
T
E
p
tio
r
o
a
p
a e
le
.
n
ttr
e
e
l'a
p
t
le
r
e
a
p
r
io
n
t
c
d
z
e
l'
o
é
u
P
O
le
r
l'a
r
e
r
o
c
s
le
e n
. f
a
s
e
r
e
tt
R
lim
in l
p h
s
le
D
o
le
L
is
z
e
!
d
ie
e
u
r
r
u
é
p
o
m
r
e
t
a
t
s
n
ta
io
e
n
t
a
e
g
n
é
m
il
a
t
u
o
m
a
tiq
a
m
û
le
r
r
u
o
c
d
u
r
e
le
i
v
(
q
m
in
u
)
5
a
t
u
o
t
r
e
R
le
il
U
é
o
u
t
d
u
o
r
c
é
e
le
e
P
s
a
s
!
r
u
p
s
n
ie
r
é
d
s
d
'o
e
r
u
d
o
c
d
u
r
e
i
v
n
la
p
e
le
c
p
e
il
s
o
u
s
r
a
t
s
o
m
r
e
à
t
a
n
s
e
e
m
e
u
it
in
.
s
e
t
il e
e
e
p
r
a
p
n
is
s
r
r
u
f
o
C
R
O
U
E
G
A
Z
m
e
r
h
t
t
s
o
lim
ta
e
n
tio
à
r
d
d
e
e
le
d
ie
v
r
u
.
e
r
c
r
la
p
e
c
e
n
A
R
C
H
E
o
i
t
c
u
r
in
t
s
s
c
e
t
e
e
t
e
m
t
la
à é
le
tr
c
iq
d
t
n
a
t
é
r
pas
n
e
,
e
u
n
e
u
ll
e
m
d
e
l
ô
r
n
t
te
p
s
u
o
u
r
l'a
e
d
u
n
o
r
e
d
à
l'é
p
a
t
d
e
u
c
r
e
g
e
, p
z
a
d
e
l
ô
r
n
t
a
a
n
e
n
n
o
i
n
e
s
t
e
m
t
a
l
p
e
t
a
s
n
C
o
m
m
t a
e
p
le
p d
e
r
u
e
P
E
R
D
E
L
la
à
t
a
n
é
le
c
o
s
é
ra
p
ô
r
n
t
o
c
le
p
a
n
s
d
e
s
n
é
tiq
e
tte
u
.
l
e
r
u
a
t
r
p
é
a
e
u
d
e
l'a
p
p
y
s
d
'u
n
é
o
t
e
y
a
s
e
s
t.
e
n
u
à
z
g
a
O
"
la
r
is
e
r
s
e
c
y
l,
i
e
a
r
p
p
d
e
r
g
u
e
a
s
n
i
e
d
s
B
e
tt
é
e
e
tiq
e
u
s
s
a
à
r
e
l'é
u
à
z
g
a
O
"
u
d
'a
c
c
.
s
é
.
e
d
e
r
u
a
t
p
r
é
c
r
m
a
e
h
, s
n
e
t c
p
u
le
o
t
n
u
r
n
h
c
e
.
g
z
a
'
L
A
D
M
'A
P
P
A
R
a
tu
m
e
r
p
é
t
tr
iq
e
d
u
e
t
io
d
s
n
'e
n
a
z
g
u
d
le
'a
d
c
a
u
n
e
r
c z
ic
é
a
s
t tte
u r
I
l'a
c
r
u
s
é
it
r
u
c
e
s
a
b
s
lu
p
s il.
e
r
è
t
e
m
à
F
F
/
A
R
R
E
T
"
to
e
p
r
a
p
h
o
.
S u
r
ta
N
s
iy l'a
i
S
E
r
tr
à
è
t le
u
is
r
p
m
c
i
c
io
t
.
e
p
/
M
e
é
r
i
e
r
d
n
e
S
u
d
s
è
p
r
'e
t
le
s
c
,
s
a
it
r
u
c
é
s
d
s
n
e
.
é
u
iv
s
t
n
a
A
R
C
H
E
"
.
le
s
m
io
s
s
n
i
O
N
I
IL
e
.
s
s
b
a
lu
p
la
s
e
p
a
p
e
il
'il
r
s
tie
e
n
.
A
/
O
F
"
F
s
R
R
E
T
"
.
1
2
7
1
2
7
1
0
O
P
E
N
R
A
T
I
N
S
T
R
I
G
1
. th
2
.
3
.
4
. T
D
5
. P D
6
.
o
7
. to
8
. R
9
.
1
0 1
1
s
1
.
2
.
3
. P D 4
.
W
th
.S .If
R
e
S
T
O
P
!
d
a
is
la
t
S
e
t
T
u
n
r
h
is
c
i
e
v
d
o
n
h
u
s
n
o
a
it f
m
s
e
ll
n
e
h
e
t
in
n
th
,
a
s
g P
u
s
h
"
O
p
e
la
n
T
u
r
o
w
p
e
e
t th
th
e
o
f
llo
w
G
f
O
f
ic
v
r
e
T
t
S
e
t
n
T
u
r
s
if
e
h
u
s
o
n
R
e
p
t
l.
e
b
h
e
o
m
h
r
e
t
a
ll
o
w
p
f
o
f
a
lia
p
p
e
n
c
a
h
c
w
i
h
e
lig
o
t
y
r
t
o
t
th
c
e
g
a
s
e
.
c
o
r
f
o
t
in
m
iv
(
5
e
)
n
i
,
s
g
a
r
o
f
ll g
e
m
s
,
s
a
e
t
f
a
s
in
.
y
is
la
l if
e
b
y
t
x
e
n
o
t
o
g
r
n
o
t
c
a
s
g
.
N
"
e
a
c
e
s
c
c
a
ll
le
e
o
n
c
o
t
r
a
p
h
e
t
ta
s
o
t
m
r
e
a
lia
p
p
n
c
e
u
r
in
t
s
h
e
t
a
s
T
A
o
p
p
e
te
h
ic
n
c
O
T
U
R
m
e
r
h
t
h
e
o
ff a
ll e
le
is
o
t
ic
v
e
r
th
g
e
s
a
o
t fo
.
e
c
r
la
e
c
c
o
n
t
y
e
t
f
a
s
e
h
lo
w
o
t
t
a
t
s
e
r
a
th
o
e
t
is
e
ip
q
u
e
p
i
t
a
m
o
u
t
a
lly
c
n
b
r
u
h
e
t
h
t
n
o
tr
o
l le
e
v
u
te
to
s
c
le
c
e
n
d
u
in
g
l
S
F
T
O
P
!
io
n
t
a
m
r
o
f
d
o
u
o
s
't
n
.
e
p
t
s
le
e
r
v
l
o
p
s
e
a
n
l.
ic
r
t p
lia
.
e
c
n
to
d
e
s
e
ir
d
w
ill n
o
t o
p
T
o
"
io
s
n
t
c
a
n
e
"
n
c
a
li
ia
o
n
g
r
a
s
N
O
F
F
o
o
lo
t
ta
s
t
tric
c
p
w
o
p
e
b
e
fo
r
c
tr
l
o
n
o
le
e
s
c
c
a
o
l
r
U
C
T
IO
N
S
1
.
A
R
R
o
i
t
a
m
r
o
in
f
s
t
e
s
in
g
t
e
t
ia
e
.
n
c
l
p
p
w
d
ith
a
n
ig
e
h
t
s
ig
h
t
l
e
h
n
a
b
y
r
to
r
O
F
"
F
o
a
r
u
t a
n
e
h
t
r
a
lo
o
f
B
"
"
o
llo
w
e
v
b
o
a
ll
e
m
G
IN
A
R
D
in
g
.
t
t
e
s
a
te
r
e
,
n
T
u
r
a
ll
u
r
o
c
y
d
o
m
c
p
.
y
n
a
G
T
A
S
e
s
w
t
e
s
to
r
e
th
e
m
d
.
r
e
to
e
r
v
O
"
e
l.
a
n
p
s
n
o
e
o
b
v
a
n
.
.
n
itio
n
.
e
n
r
u
b
r
.
d
P
o
"
io
.
n
t
i
s
g
y
. T
a
s
e
h
n
f
I
.
r
u
o
y
A
S
E
L
T
V
E
R
I
E
G
U
A
Z
O
A
P
in
tt
g
.
a
p
lia
p
P
F
F
"
R
O
B
M
A
N
U
O
N
"
L
IN
A
N
P
C
I
L
E
c
n
e
io
it
o
s
n
.
la
p
o
R
le
é
g
2
.
.
3
. C
p
o
u
a
C
e
t
4
.
d
'a
llu
a
llu
m
P
o
s
u
5
.
it
s
p
o
6
. A
te
t
n
g
.
z
a
p
la
n
8
1 1
7
.
. R
9
.
0
.
1
. S
d q
1 2 fa 3 p
4
.
. C
.
.
c
A
R
R
la
r
u
s S
'il n
P
o
s
u
p
it
s
o
e
m
r
t
t
e
M R
l
é
g
e
i l'a
u
r
t
s
n
i
g
e
a
lifi
a
u
R
é
g
o
u
u
t p
P
o
u
o
s
N
e
R
e
m
G
A
A
N
Z
E
T
I
E
, E
L
N
P
O
M
/
M
E
V
O
S
A
R
C
H
E
"
A
N
G
U
A
A
S
L
E
R
S
H
N
O
W
N
P
O
S
IT
IO
N
20
Page 21
OPERATING INSTRUCTIONS
FOR YOUR SAFETY READ BEFORE OPERATING
If you do not follow these instructions exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically lights the burners. Do not try to light the burners by hand.
B. BEFORE OPERATING smell around the appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electric switch; do not use any telephone in your building. Immediately call your supplier from a neighbor's phone. Follow the gas suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
C. Use only your hand to move the gas control switch or knob. Never use tools. If the gas control switch or knob will not operate, don't try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance.
4. This appliance is equipped with an automatic ignition system which automatically lights the burners. Do not try to light the burners by hand.
5. Remove control access panel.
6. Move the gas control switch or knob to "OFF".
GAS CONTROL SWITCH SHOWN IN "ON" POSITION
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP!above on this label. Follow "B" in the safety information above on this label. If you don't smell gas, go to the next step.
8. Move the gas control switch or knob to "ON".
9. Replace control access panel.
10. Turn on all electric power to the appliance.
11. Set the thermostat to the desired setting.
12. If the appliance will not operate, follow the instructions "To Turn Off Gas To Appliance" and call your service technician or gas supplier.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to its lowest setting.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove control access panel.
4. Move the gas control switch or knob to "OFF". Do not force.
5. Replace control access panel.
WARNING: Improper
alteration, service or maintenance can cause injury or property damage. Refer to the user's information manual provided with this
consult a qualified
or the gas supplier.
This furnace must be
instructions and local codes. In the absence of local codes, follow the National Fuel Gas
Code, ANSI Z223.1.
For indoor installation.
PGB & PGJ For outdoor installation only.
If notWARNING:
installed, operated and maintained in accordance with the manufacturer's instructions, this product could expose you to substances in fuel combustion which can cause death or serious illness and which are known to the State of California to cause cancer, birth defects or other reproductive harm. This product contains fiberglass insulation. Fiberglass insulation contains a chemical
California to cause cancer.
FOR YOUR SAFETY
other flammable vapors and liquids in the vicinity of this or any other appliance.
Do not store or use gasoline or
0140F00001P
21
Page 22
OPERATING INSTRUCTIONS
CONSIGNES DE SECURITE - LIRE
AVANT D'ALLUMER L'APPAREIL
AVERTISSEMENT: Le non-respect des instructions qui suivent peut
^
entrainer un risque d'incendie ou d'explosion causant des dommages, des blessures ou la mort.
A. Cet appareil comporte pas de veilleuse. Il est muni d'un mecanisme qui allume automatiquement le bruleur. N
B. Sentir tout autour de l'appariel AVANT D'ALLUMER afin de deceler toute fuite de gaz. Assurez-vous de sentir tout pres du plancher car certains gaz sont plus lourds que l'air et se deposeront sur le plancher.
SI VOUS SENTEZ UNE ODEUR DE GAZ: Ne tentez d'allumer aucun appariel.
Ne touchez pas aux interrupteurs electriques; n'utiliser aucun telephone dans l'edifice ou vous vous trouvez. Appelez immediatement votre fournisseur de gaz en utilisant le telephone d'un voisin et suivez les instructions du fournisseur. Appelez les pompiers si vous ne parvenez pas a rejoindre votre fournisseur de gaz.
C. N'utiliser que votre main pour pousser ou tourner le commande du gaz. N'utilisez jamais d'outils. Si vous ne parvenez pas a pousser ou a tourner la commande, ne tentez pas de la reparer; appelez un reparateur qualifie. Forcer la commande ou essayer de la reparer peut entrainer un risque d'incendie ou d'explosion.
D. N'utilisez pas cet appareil si l'une de ses parties a ete dans l'eau. Si cela se produit, demandez immediatement a un reparateur qualifie d'inspecter l'appareil et de remplacer toute piece du systeme de controle et toute commande de gaz ayant ete dans l'eau.
^^
'allumez paz le bruleur manuellement.
^
^
0140F00002P
1. UN INSTANT! Lisez d'abord les consignes
INSTRUCTIONS DE SERVICE
de securite ci-dessus.
2. Reglez le thermostat a son point le plus bas.
3. Coupez l'alimentation electrique de l'appareil.
4. Cet appareil est muni d'un mecanisme qui allume automatiquement le bruleur. Ne tentez pas d'allumer le bruleur manuellement.
5. Retirez le panneau d'acces de la commande.
6. Mettez la commande de gaz a la position
^
ARRET ("OFF").
7. Attendez cinq (5) minutes afin de permettre a tout gaz present d'etre evacue. Si vous sentez une odeur de gaz a ce moment, ARRETEZ! et suivez les consignes de securite donnees au paragraphe B ci-dessus. Si vous ne sentez pas de gaz, passez a l'etape suivante.
8. Mettez la commande de gaz a la position MARCHE ("ON").
9. Remettez la panneau d'acces de la commande en place.
10. Retablissez l'alimenation electrique de l'appareil.
11. Reglez le thermostat a le temperature desiree.
12. Si l'appareil ne fonctionne pas, suivez les instructions intitulees "Arret du gaz" et appelez un reparateur qualifie ou votre fournisseur de gaz.
1. Reglez le thermostat a son point le plus bas.
2. Coupez l'alimentation electrique de l'appareil si vous devez effectuer un entretien.
3. Retirez le panneau d'acces de la commande.
4. Mettez la commande de gaz a la position ARRET ("OFF").
5. Remettez le panneau d'acces de la commande en place.
^
^
^
^
^
^
ARRET DU GAZ
^
Commande de gaz en position
"MARCHE"
22
Page 23
ACCESSORIES
EXTERNAL FILTER RACK KIT
( EFR01 )
SLOTS IN FILTER CLEAR SCREWS
ON UNIT
UNIT SIDE
PANEL
BLOWER DECK
SCREWS
FRONT
OF UNIT
BASE
OF UNIT
RETURN AIR
CUTOUT AREA
LOWER EDGE
SCREW
EFR01 EXTERNAL FILTER RACK KIT
Used on Models
90% Upflow Model Furnaces
FILTER RACK ASSEMBLY
(FACE FILTER OPENING
TOWARDS FRONT
OF UNIT)
23
Page 24
ACCESSORIES
INTERNAL FILTER RETENTION KIT
RF000180 RF000181
FILTER
ACCESS
DOOR
FILTER ANGLE
SCREW
FILTER RAILS (2)
FILTER ANGLES (2)
FILTER
RAIL
SCREW
BASE
SIDE PANEL
FILTER ANGLE
SCREW
FILTER
RAIL
SCREW
FI
LTER
RETURN
DUCT
FILTER SUPPORT BRACKET
AIR FLOW
F
LTER
I
RF000180
Quantity Part # Description
20 10690301 Filter Angle 20 20242801 Filter Rail 10 20178501 Filter Retainer 80 M0211216 Screw
1 20512701 Installation Instructions
INTO BACK PANEL LANCES,
FRONT TO BE PLACED
UNDER BASEPAN FLANGE.
24
INSERT LEGS
RF000181
Quantity Part # Description
10 10368501 Filter Bracket 20 M0211216 Screws
1 20512701 Installation Instructions
Each "RF" contains enough components to make (10) filter kits.
Page 25
ACCESSORIES
CONCENTRIC VENT CONVERSION KIT
( DCVK-20
The DCVK-20 (2") or the DCVK­30 (3") is a new concentric vent kit approved with furnaces listed in this manual.
This concentric vent kit allows for vertical or horizontal vent termina­tion. The illustrations give a brief view of the kit and its application.
See the section in this manual under "Vent Flue and Combustion Air Pipe Terminations" for more information or consult the Installa­tion and Operating Instructions (IO-619B).
DCVK-30 )
Combustion Air
Roof Boot/Flashing (Field Supplied)
Vent
Vent
DCVK
Maintain 12" (18" for Canada) minimum clearance above highest anticipated snow level. Maximum of 24" above roof.
Support (Field Supplied)
45 Elbow (Field Supplied)
Combustion Air
Vent
Combustion Air
Strap (Field Supplied)
45 Elbow (Field Supplied)
(Vertical Installation)
Combustion Air
Vent
Flush to
1" maximum
DCVK
(Horizontal Installation)
25
Page 26
PRODUCT IDENTIFICATION
SIDE WALL VENT KIT
(0170K00000S)
Description
This side wall only vent kit #0170K00000S is to be used with 2” or 3” vent systems. This kit is NOT intended for use with single pipe (indirect vent) installations.
The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side­by-side or with one pipe above the other.
See the section in this manual under "Vent Flue and Combustion Air Pipe Termina­tions" for more information or consult the Installation Instructions (IO-635).
26
Horizontal Installation
Vertical Installation
Page 27
ACCESSORIES
CONCENTRIC VENT CONVERSION KIT
( HCVK
Horizontal
(HCVK)
VCVK )
Vertical
(VCVK)
Connection for Fresh Air Intake Pipe to Furnace
Connection for Vent/Fl ue Pipe
from Furnace
Pipe to Furnace
Tee
Inside
Combustio n
Air Intake Pi pe
Outside
Seal Penetration
with Caulking
Wall Thickness
3/4" Minimum
13 3/4" Maximum
Vent/Flue Termination
with Tee
12" Minimum Above
Grade or Highest
Anticipated Snow Level
HVCK Installation
Concentric Vents Kits HVCK and VCVK are suitable for use with the 90% efficient furnace products listed in this manual.
Combustion Air
Intake Pipe
Roof Thickness
3/4" Minimum 22" Maximum
Interior Section
of Concentric Vent Assembly
Must Be Adequately
Secured and Supported
Sanitary Tee
Connection for Fresh Air Intake Pipe to Furnace
(Tee, Pipe, & 2" to 4" Reducer)
12" Minimum Above
Roof or Highest
Anticipated Snow Level
Outside
Inside
Connection for
Vent/ Flue Pipe
From Furnace
Vent/Flue
Termination
Seal Penetration
with Flashing and Caulking
VCVK Installation
27
Page 28
PRODUCT DESIGN
Safety
Please adhere to the following warnings and cautions when installing, adjusting, altering, servicing, or operating the fur­nace.
WARNING
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER INSTALLATION,
ADJUSTMENT, ALTERATI ON, SERVICE OR MAINTENANCE, R EFER TO THIS
MANUAL.
QUALIFIED INSTALLER, SERVICE AGENCY OR THE GAS SUPPLIER.
T
MAY CAUSE SERIOUS ILLNESS OR DEATH AND WHICH ARE KNOWN TO THE
S
REPRODUCTIVE HARM.
TO PREVENT POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH
DUE TO ELECTRICAL SHOCK, THE FURNACE MUST BE LOCATED TO PROTECT
THE ELECTRICAL COMPONENTS FROM WATER.
Charge (ESD) Precautions NOTE: Discharge body’s static electricity before touching
unit. An electrostatic discharge can adversely affect electri­cal components.
Use the following precautions during furnace installation and servicing to protect the integrated control module from dam­age. By putting the furnace, the control, and the person at the same electrostatic potential, these steps will help avoid exposing the integrated control module to electrostatic dis­charge. This procedure is applicable to both installed and uninstalled (ungrounded) furnaces.
1. Disconnect all power to the furnace. Do not touch the
2. Firmly touch a clean, unpainted, metal surface of the
3. Service integrated control module or connecting wiring
4. Discharge any static electricity from your body to ground
OR ADDITIONAL ASSISTANCE OR INFORMATION, CONSULT A
F
WARNING
HIS PRODUCT CONTAINS OR PRODUCES A CHEMICAL OR CHEMICALS WHICH
TATE OF CALIFORNIA TO CAUSE CANCER, BI RTH DEFECTS OR OTHER
WARNING
integrated control module or any wire connected to the control prior to discharging your body’s electrostatic charge to ground.
furnace near the control. Any tools held in a person’s hand during grounding will be discharged.
following the discharge process in Step 2. Use caution not to recharge your body with static electricity; (i.e., do not move or shuffle your feet, do not touch ungrounded objects, etc.). If you come in contact with an ungrounded object, repeat Step 2 before touching control or wires.
before removing a new control from its container. Follow Steps 1 through 3 if installing the control on a furnace. Return any old or new controls to their containers before touching any ungrounded object.
Product Application
This product is designed for use as a residential home gas furnace. It is not designed or certified for use in mobile home, trailer, or recreational vehicle applications.
This furnace can be used in the following non-industrial commercial applications: Schools, Office buildings, Churches,
Retail stores, Nursing homes, Hotels/motels, Common or office areas. In such applications, the furnace must be installed
with the
installation instructions.
The 80% and 90% furnaces are ETL certified appliances and are appropriate for use with natural or propane gas. (NOTE: If using propane gas, a propane conversion kit is required).
One important difference between the 80% and 90% furance is that the 90% furnace is a dual certified appliance.
Dual certification means that the combustion air inlet pipe is optional and the furnace can be vented as a:
Non-direct vent (single pipe) central forced air furnace in which combustion air is taken from the installation area or from air ducted from the outside or,
Direct vent (dual pipe) central forced air furnace in which all combustion air supplied directly to the furnace burn­ers through a special air intake system outlined in this manual and the installation instructions.
IMPORTANT NOTE: The 80% furnace cannot be installed as a direct vent (i.e.., sealed combustion) furnace. The burner box is present only to help reduce sound trans­mission from the burners to the occupied space.
To ensure proper installation, operation and servicing, thor­oughly read the installation and service manuals for specif­ics pertaining to the installation, servicing and application of this product.
WARNING
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE,
P
EXPLOSION, SMOKE, SOOT, CONDENSTAION, ELECTRICAL SHOCK OR CARBON
MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION, REPAIR, OPERATIO N,
OR MAINTENANCE OF THIS PRODUCT.
WARNING
T
O PREVENT PROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE,
DO NOT INSTALL THIS FURNACE IN A MOBILE HOME, TRAILER, OR RECREATIONAL
VEHICLE.
To ensure proper furnace operation, install, operate, main­tain and service the furnace in accordance with the installa­tion, operation and service instructions, all local building codes and ordinances. In their absence, follow the latest edition of the National Fuel Gas Code (NFPA 54/ANSI Z223.1), and/or CAN/CGA B149 Installation Codes, local plumbing or waste water codes, and other applicable codes.
A copy of the National Fuel Gas Code (NFPA 54/ANSI Z223.1) can be obtained from any of the following:
28
Page 29
PRODUCT DESIGN
American National Standards Institute 1430 Broadway New York, NY 10018
National Fire Protection Association 1 Batterymarch Park Quincy, MA 02269
CSA International 8501 East Pleasant Valley Cleveland, OH 44131
A copy of the CAN/CGA B149 Installation Codes can be obtained from:
CSA International 178 Rexdale Boulevard Etobicoke, Ontario, Canada M9W, 1R3
The rated heating capacity of the furnace should be greater than or equal to the total heat loss of the area to be heated. The total heat loss should be calculated by an approved method or in accordance with “ASHRAE Guide” or “Manual J-Load Calculations” published by the Air Conditioning Con­tractors of America.
Location Requirements and Considerations
WARNING
O PREVENT POSSIBLE EQUIPMENT DAMAGE, PROPERTY DAMAGE, PERSONAL
T
INJURY OR DEATH, THE FO LLOWING BULLET POINTS MUST BE OBSERVED
WHEN INSTALLING THE UNIT.
Follow the instructions listed below when selecting a fur­nace location. Refer also to the guidelines provided in the Combustion and Ventilation Air Requirements section in this manual or the installation instructions for details.
Centrally locate the furnace with respect to the pro­posed or existing air distribution system.
Ensure the temperature of the return air entering the furnace is between 55°F and 100°F when the furnace is heating.
Provide provisions for venting combustion products outdoors through a proper venting system. Special consideration should be given to vent/flue pipe routing and combustion air intake pipe when applicable.
80% Furnaces: All installations must be vented in accordance with National Fuel Gas Code, NFPA 54/ ANSI Z223.1 - lateset edition. In Canada the furnaces must be vented in accordance with the National Stan­dard of Canada, CAN/CGA B149.
90% Furnaces: Refer to the Vent/Flue Pipe and Com- bustion Air Pipe -Termination Locations section in this
manual or the installation instructions for appropriate termination locations. Also for 90% furnaces, refer to
the Vent/Flue Pipe and Combustion Air Pipe -Termi- nation Locations section in this manual or the instal­lation instructions to determine if the piping system from furnace to termination can be accomplished within the guidelines given. NOTE: The length of flue and/or combustion air piping can be a limiting factor in the location of the furnace.
Locate the 90% furnace so that the condensate can be piped at a downward slope away from the furnace to the drain. Do not locate the furnace or its conden­sate drainage system in any area subject to below freezing temperatures without proper freeze protec­tion. Refer to the Condensate Drain Lines and Trap section in this manual or the installation instructions for further details.
Set the 90% furnace on a level floor to enable proper condensate drainage. If the floor becomes wet or damp at times, place the furnace above the floor on a con­crete base sized approximately 1-1/2" larger than the base of the furnace. Refer to the Horizontal Applica- tions and Considerations section in this manual or the installation instructions for leveling of horizontal furnaces.
Ensure upflow or horizontal furnaces are not installed directly on carpeting, or any other combustible mate­rial. The only combustible material allowed is wood.
A special accessory subbase must be used for up­right counterflow unit installations over any combus­tible material (including wood). Refer to subbase in­structions for installation details. (NOTE: A subbase will not be required if an air conditioning coil is located beneath the furnace between the supply air opening and the combustible floor.
Exposure to contaminated combustion air will result in safety and performance-related problems. Do not install the furnace where the combustion air is ex­posed to the following substances:
chlorinated waxes or cleaners chlorine-based swimming pool chemicals water softening chemicals deicing salts or chemicals carbon tetrachloride halogen type refrigerants cleaning solutions (such as perchloroethylene) printing inks paint removers varnishes hydrochloric acid cements and glues antistatic fabric softeners for clothes dryers and masonry acid washing materials
Seal off a non-direct vent furnace if it is installed near an area frequently contaminated by any of the above substances. This protects the non-direct vent furnace from airborne contaminants. To ensure that the en-
29
Page 30
PRODUCT DESIGN
closed non-direct vent furnace has an adequate sup- ply of combustion air, vent from a nearby uncontami­nated room or from outdoors. Refer to the Combus- tion and Ventilation Air Requirements section in this manual or the installation instructions for details.
If the furnace is used in connection with a cooling unit, install the furnace upstream or in parallel with the cooling unit coil. Premature heat exchanger fail­ure will result if the cooling unit coil is placed ahead of the furnace.
If the furnace is installed in a residential garage, posi­tion the furnace so that the burners and ignition source are located not less than 18 inches (457 mm) above the floor. Protect the furnace from physical damage by vehicles.
If the furnace is installed horizontally, the furnace ac­cess doors must be vertical so that the burners fire horizontally into the heat exchanger. Do not install the unit with the access doors on the “up/top” or “down/ bottom” side of the furnace.
Clearances and Accessibility
Installations must adhere to the clearances to combustible materials to which this furnace has been design certified. The minimum clearance information for this furnace is pro­vided on the unit’s clearance label. These clearances must be permanently maintained. Refer to Specification Sheet for minimum clearances to combustible materials. Clearances must also accommodate an installation’s gas, electrical, and drain trap and drain line connections. If the alternate combustion air intake or vent/flue connections are used on a 90% furnace, additional clearances must be provided to accommodate these connections. Refer to Vent Flue Pipe and Combustion Air Pipe section in this manual or the in­stallation instructions for details. NOTE: In addition to the required clearances to combustible materials, a minimum of 24 inches service clearance must be available in front of the unit.
A furnace installed in a confined space (i.e., a closet or utility room) must have two ventilation openings with a total minimum free area of 0.25 square inches per 1,000 BTU/hr of furnace input rating. One of the ventilation openings must be within 12 inches of the top; the other opening must be within 12 inches of the bottom of the confined space. In a typical construction, the clearance between the door and door frame is usually adequate to satisfy this ventilation re­quirement.
Furnace Suspension
If suspending the furnace from rafters or joist, use 3/8" threaded rod and 2”x2”x1/8” angle iron as shown in the fol­lowing figure. If the furnace is installed in a crawl space it must also be suspended from the floor joist or supported by a concrete pad. Never install the furnace on the ground or allow it to be exposed to water. The length of rod will depend on the application and the clearances necessary.
PROVIDE 8" MINIMUM CLEARANCE BETWEEN
CENTER ROD AND FURNACE CABINET
TO ALLOW FOR CIRCULATOR BL OWER REMOVAL.
3/8" DIAMETER
THREADED ROD
(6 PLACES)
HOLD DOWN
NUTS
SUPPORT
NUTS
GAS PIPING
2"X2"X1/8" ANGLE IRON
(3 PLACES)
ALTERNATE GAS PIPING
POSITION AS CLOSE AS POSSIBLE TO BLOWER DECK TO ALLOW FOR
CIRCULATOR BLOWER REMOVAL.
ASSURE FURNACE IS LEVEL FROM
END TO END.
ON
90% FURNACES MAKE SURE THE UNIT HAS A SLIGHT
FORWARD TILT WITH THE FRONT
OF THE FURNACE 0"-3/4"
BELOW THE BACK OF THE FURNACE.
CONDENSATE
DRAIN
TILT OUTWARD TO ALLOW FOR
DOOR AND CIRCULATOR BLOWER
REMOVAL.
90% Suspended Furnace Shown
(80% Furnace Similar)
EXISTING FURNACE REMOVAL
NOTE: When an existing furnace is removed from a venting
system serving other appliances, the venting system may be too large to properly vent the remaining attached appli­ances.
The following vent testing procedure is reproduced from the
American National Standard/National Standard of Canada for Gas-Fired Central Furnaces ANSI Z21.47, latest edition, CSA-2.3b, latest edition Section 1.23.1.
The following steps shall be followed with each appliance connected to the venting system placed in operation, while any other appliances connected to the venting system are not in operation:
a. Seal any unused openings in the venting system;
b. Inspect the venting system for proper size and horizontal pitch,
as required by the National Fuel Gas Code, ANSI Z223.1 or the CSA B149 Installation Codes and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition;
c. In so far as practical, close all building doors and windows and all
doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they shall operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers;
d. Follow the lighting instructions. Place the appliance being in-
spected in operation. Adjust thermostat so appliance shall oper­ate continuously;
e. Test for draft hood equipped spillage at the draft hood relief
opening after 5 minutes of main burner operation. Use the flame of a match or candle;
f. After it has been determined that each appliance connected to the
venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use;
g. If improper venting is observed during any of the above tests, the
common venting system must be corrected.
30
Page 31
PRODUCT DESIGN
Corrections must be in accordance with the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 and/or CSA B149 Installation Codes.
If resizing is required on any portion of the venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code ANSI Z223.1 and/or CSA B149
Installation Codes.
Thermostat Requirements
A single-stage furnace requires a single-stage thermostat while the two-stage furnace requires a two-stage thermostat for proper operation (see note below). The single-stage ther­mostat provides "W1" for only one stage of heat while the two-stage thermostat provides "W1" and a "W2" terminals for control of low stage and high stage heat. Refer to Electri- cal Connections - 24 Volt Thermostat Wiring section in this manual or the installation instructions for correct installation procedure for these thermostats.
NOTE: A single-stage thermostat with only one heating stage can be used to control a two-stage furnace. The ap­plication of a single-stage thermostat does not offer "true" thermostat driven two-stage operation, but provides a timed transition from low to high fire. The furnace will run on low stage for a fixed period of time before stepping up to high stage to satisfy the thermostat's call for heat. The delay period prior to stepping up can be set at either 5 or 10 min­utes through the DIP switch adjacent to the Heat Off delay DIP switches on the integrated control module. To use a single-stage thermostat, turn off power to the furnace, move the thermostat selection jumper on the integrated contro module from the "two-stage" position to the "single-stage" position, turn power back on. Refer to the following figures.
T
W
TSTAT
O
S
I
N
G
L E
T-Stat selection jumper in single-stage thermostat position.
ON
DIP switch position 3: ON Delay Period: 10 minutes.
3
2
1
NOTE: The AMH, GCH, GDH, GMH and GME hybrid fur­naces require a single stage thermostat. These furnaces utilize a control board with single stage or two stage capa­bility. The second stage feature is established by setting a dip switch on the board, either one stage or two stage. All of the second stage timing is then controlled by dipswitch 3 on the circuit board.
T W O
TSTAT
S
I
OFF
N
G
L E
DIP switch position 3: OFF Delay Period: 5 minutes.
3
2
1
HEAT OFF
DELAY
MODE
SECOND
STAGE
ONLY
100
SECOND
DELAY
2-STAGE
5
MINUTES
1
F F
O
2
F F
O
3
F
F O
N O
N O
N O
150
SECOND
DELAY
1-STAGE
AUTO
Dehumidistat Requirements
A dehumidistat can be used in conjunction with the two­stage variable speed 80% or 90% furnace to lower the hu­midity in the conditioned space. The dehumidistat will im­prove dehumidification of the conditioned air by prompting the furnace to reduce the speed of the circulator blower dur­ing operation in the cooling mode. To be compatible with these furnaces, a dehumidistat must operate on 24 VAC and utilize a switch which opens on humidity rise. Refer to Electrical Connections - 24 Volt Dehumidistat Wiring sec­tion in this manual or the installation instructions for correct installation procedure.
Thermostat and Dehumidistat Location
In an area having good air circulation, locate the thermostat and dehumidistat (if applicable) about five feet high on a vi­bration-free inside wall. Do not install the thermostat or dehumidistat where it may be influenced by any of the fol­lowing:
Drafts, or dead spots behind doors, in corners, or un­der cabinets.
Hot or cold air from registers.
Radiant heat from the sun.
Light fixtures or other appliances.
Radiant heat from a fireplace.
Concealed hot or cold water pipes, or chimneys.
Unconditioned areas behind the thermostat and dehumidistat, such as an outside wall.
DRAFTS OR DEAD SPOTS
-BEHIND DOORS
-IN CORNERS
-UNDER CABINETS
HOT
COLD
Thermostat Influences
31
Page 32
PRODUCT DESIGN
Consult the instructions packaged with the thermostat and dehumidistat for mounting instructions and further precau­tions.
COMBUSTION AND VENTILATION AIR REQUIREMENTS
WARNING
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MA Y OCCUR
P
IF THE FURNACE IS NOT PROVIDED WITH ENOUGH FRESH AIR FOR PROPER
COMBUSTION AND VENTILAT ION OF FLUE GASES. MOS T HOMES REQUIRE
OUTSIDE AIR BE SUPPLIED TO THE FURNACE AREA.
9.3.1.5 Makeup air requirements for the operation of exhaust fans, kitchen ventilation systems, clothes dryers, and fireplaces shall be considered in determining the adequacy of a space to provide combustion air require­ments.
9.3.2 Indoor Combustion Air. The required volume of indoor air shall be determined in accordance with the method in 9.3.2.1 or 9.3.2.2 ex­cept that where the air infiltration rate is known to be less than 0.40 ACH, the method in 9.3.2.2 shall be used. The total required volume shall be the sum of the required volume calculated for all appliances located within the space. Rooms communicating directly with the space in which the appliances are installed through openings not furnished with doors, and through combustion air openings sized and located in accordance with 9.3.2.3, are considered a part of the required volume.
Improved construction and additional insulation in buildings have reduced heat loss by reducing air infiltration and es­cape around doors and windows. These changes have helped in reducing heating/cooling costs but have created a prob­lem supplying combustion and ventilation air for gas fired and other fuel burning appliances. Appliances that pull air out of the house (clothes dryers, exhaust fans, fireplaces, etc.) increase the problem by starving appliances for air.
If this furnace is to be installed in the same space with other gas appliances, such as a water heater, ensure there is an adequate supply of combustion and ventilation air for the other appliances. Refer to the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1 (Section 9.3), or CAN/ CGA B149 Installation Codes (Sections 7.2, 7.3, or 7.4), or applicable provisions of the local building codes for deter­mining the combustion air requirements for the appliances.
Most homes will require outside air be supplied to the fur­nace area by means of ventilation grilles or ducts connect­ing directly to the outdoors or spaces open to the outdoors such as attics or crawl spaces.
The following information on air for combustion and ventilation is reproduced from the National Fuel Gas Code NFPA 54/ANSI
Z223.1 Section 9.3.
9.3* Air for Combustion and Ventilation.
9.3.2.1* Standard Method. The minimum required volume shall be 50
3
per 10000/Btu/hour (4.8m3/kW).
ft
9.3.2.2* Known Air Infiltration Rate Method. Where the air infiltra­tion rate of a structure is known, the minimum required volume shall be determined as follows:
(1) For appliances other than fan-assisted, calculate using the following
equation:
Required Volume
(2) For fan-assisted appliances, calculate using the following equation:
Required Volume
where:
I
I
ACH = air change per hour (percent of volume of space exchanged
(3) For purposes of this calculation, an infiltration rate greater than
= all appliances other than fan-assisted input in Btu per
other
fan
0.60 ACH shall not be used in the equations in 9.3.2.2(1) and
9.3.2.2(2).
hour
= fan-assisted appliances input in Btu per hour
per hour, expressed as a decimal)
> ________ _________
other
> ________ _________
fan
3
21 ft
ACH 1000 Btu/hr
15 ft
ACH 1000 Btu/hr
I
other
(
3
I
(
fan
)
)
9.3.1 General.
9.3.1.1 Air for combustion, ventilation, and dilution of flue gases for
appliances installed in buildings shall be obtained by application of one of the methods covered in 9.3.2 through 9.3.6. Where the requirements of 9.3.2 are not met, outdoor air shall be introduced in accordance with methods covered in 9.3.3 through 9.3.6.
Exception No. 1: This provision shall not apply to direct vent appliances.
9.3.1.2 Appliances of other than natural draft design and other than Category 1 vented appliances shall be provided with combustion, ven­tilation, and dilution air in accordance with the appliance manufacturer’s instructions.
9.3.1.3 Appliances shall be located so as not to interfere with proper circulation of combustion, ventilation, and dilution air.
9.3.1.4 Where used, a draft hood or a barometric draft regulator shall be installed in the same room or enclosure as the appliance served so as to prevent any difference in pressure between the hood or regulator and the combustion air supply.
32
9.3.2.3 Indoor Opening Size and Location. Openings used to connect indoor spaces shall be sized and located in accordance with the follow­ing:
(1)*Combining spaces on the same story. Each opening shall have a
minimum free area of 1 in.2/1000Btu/hr (2200 mm2/kW) of the total input rating of all appliances in the space but not less than 100 in. (0.60m2). One opening shall commence within 12 in. (300 mm) of the top, and one opening shall commence within 12 in. (300 mm) of the bottom, of the enclosure [see Figure A.9.3.2.3(1)]. The mini- mum dimension of air openings shall be not less than 3 in. (80 mm).
2
Page 33
PRODUCT DESIGN
A
NOTE: Each opening must have a free area of not less than one square inch per 1000 BTU of the total input rating of all equip­ment in the enclosure, but not less than 100 square inches.
Chimney or G as Vent
Furnace
Water Heater
Opening
Opening
Chimney or Gas Vent
Water Heater
Furnace
Ventilation louvers (each end of attic)
Outlet A ir
Inlet air duct [ends 1 ft (300 mm) above floor]
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure.
Figure A.9.2.3.3.(1) All Combustion Air from Adjacent
Indoor Spaces through Indoor Combustion Air Openings.
(2) Combining spaces in different stories. The volumes of spaces in
different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of 2 in.2/1000 Btu/hr (4400 mm2/kW) of total input rating of all appliances.
9.3.3 Outdoor Combustion Air. Outdoor combustion air shall be provided through opening(s) to the outdoors in accordance with the methods in 9.3.3.1 or 9.3.3.2. The minimum dimension of air openings shall not be less than 3 in. (80 mm).
9.3.3.1 Two Permanent Openings Method. Two permanent open­ings, one commencing within 12 in. (300 mm) of the top and one com­mencing within 12 in. (300 mm) of the bottom, of the enclosure shall be provided. The openings shall communicate directly, or by ducts, with the outdoors or spaces that freely communicate with the outdoors, as follows:
(1)*Where directly communicating with the outdoors or where commu-
nicating to the outdoors through vertical ducts, each opening shall have a minimum free area of 1 in.2/4000 Btu/hr (550 min2/kW) of total input rating of all appliances in the enclosure. [See Figure
A.9.3.3.1(1)(a) and Figure A.9.3.3.1(1)(b).]
Chimney or Gas Vent
Ventilation louvers (each end of attic)
NOTE: The inlet and outlet air openings must each have a free area of not less than one square inch per 4000 BTU of the total input rating of all equipment in the enclosure.
Outlet Air
Water Heater
lternate
air inlet
Furnace
Inlet Air
Figure A.9.3.3.1(1)(b) All Combustion Air
From Outdoors through Ventilated Attic.
(2)*Where communicating with the outdoors through horizontal ducts,
each opening shall have a minimum free area of 1 in.2/2000 Btu/hr (1100 min2/kW) of total input rating of all appliances in the enclo­sure. [See Figure A.9.3.3.1(2).]
Chimney or Gas Vent
NOTE: The air duct openings must have a free area of not less than one square inch per 2000 BTU of the total input rating of all equipment in the enclosure*.
Furnace
Water Heater
Outlet air duct
Inlet air duct
Figure A.9.3.3.1(2) All Combustion Air From Outdoors
through Horizontal Ducts.
9.3.3.2* One Permanent Opening Method. One permanent open-
ings, commencing within 12 in. (300 mm) of the top of the enclosure, shall be provided. The appliance shall have clearances of at least 1 in. (25 mm) from the sides and back and 6 in. (150 mm) from the front of the appliance. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors or spaces that freely communicate with the outdoors (see Figure A.9.3.3.2) and shall have a minimum free area of the following: (1) 1 in.
2
/3000 Btu/hr (700 mm2 per kW) of the total input rating of all
appliances located in the enclosure, and
(2) Not less than the sum of the areas of all vent connectors in the
space.
Ventilation louver s for unheated crawl sp ace
Figure A.9.3.3.1(1)(a) All Combustion Air From Outdoors -
Inlet Air from Ventilated Crawl Space and Outlet Air
to Ventilated Attic.
33
Page 34
PRODUCT DESIGN
NOTE: The single opening mus t have a free area of not less than one square inch per 3000 BTU of the total in put rating of all equi p­ment in the enclosure, but not less than the sum of t he areas of all ven t connectors in the confined space.
Chimney or Gas Vent
Furnace
Water Heater
Opening
Alternat e Opening Locatio n
9.3.7 Louvers, Grilles, and Screens.
9.3.7.1 Louvers and Grilles. The required size of openings for com-
bustion, ventilation, and dilution air shall be based on the net free area of each opening. Where the free area through a design of louver or grille or screen is known, it shall be used in calculating the size opening required to provide the free area specified. Where the louver and grille design and free area are not known, it shall be assumed that wood louvers will have 25 percent free area, and metal louvers and grilles will have 75 percent free area. Nonmotorized louvers and grilles shall be fixed in the open position.
9.3.7.2 Minimum Scree Mesh Size. Screens shall not be smaller than 1/4 in. mesh.
Figure A.9.3.3.2 All Combustion Air
From Outdoors through Single Combustion Air Opening.
9.3.4 Combination Indoor and Outdoor Combustion Air. The use of
a combination of indoor and outdoor combustion air shall be in accor­dance with (1) through (3) (see example calculation in Annex J]:
(1) Indoor Openings: Where used, openings connecting the interior
spaces shall comply with 9.3.2.3.
(2) Outdoor Opening(s) Location. Outdoor opening(s) shall be located
in accordance with 9.3.3.
(3) Outdoor Opening(s) Size. The outdoor opening(s) size shall be
calculated in accordance with the following:
(a) The ratio of the interior spaces shall be the available volume of
all communicating spaces divided by the required volume.
(b) The outdoor size reduction factor shall be 1 minus the ratio of
interior spaces.
(c) The minimum size of outdoor opening(s) shall be the full size
of outdoor opening(s) calculated in accordance with 9.3.3, multiplied by the reduction factor. The minimum dimension of air openings shall not be less than 3 in. (80 mm).
9.3.5 Engineered Installations. Engineered combustion air installa­tions shall provide an adequate supply of combustion, ventilation, and dilution air and shall be approved by the authority having jurisdiction.
9.3.6 Mechanical Combustion Air Supply. Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied form outdoors at the minimum rate of 0.35 ft3/min per 1000 Btu/hr (0.034 m3/min per kW) for all appliances located within the space.
9.3.6.1 Where exhaust fans are installed, additional air shall be provided to replace the exhausted air.
9.3.7.3 Motorized Louvers. Motorized louvers shall be interlocked with the appliance so they are proven in the full open position prior to main burner ignition and during main burner operation. Means shall be provided to prevent the main burner form igniting should the louver fail to open during burner startup and to shut down the main burner if the louvers close during burner operation.
9.3.8 Combustion Air Ducts. Combustion air ducts shall comply with
9.3.8.1 through 9.3.8.8.
9.3.8.1 Ducts shall be constructed of galvanized steel or a material hav­ing equivalent corrosion resistance, strength, and rigidity.
Exception: Within dwellings units, unobstructed stud and joist spaces shall not be prohibited from conveying combustion air, provided that not more than one fireblock is removed.
9.3.8.2 Ducts shall terminate in an unobstructed space, allowing free movement of combustion air to the appliances.
9.3.8.3 Ducts shall serve a single space.
9.3.8.4 Ducts shall not serve both upper and lower combustion air
openings where both such openings are used. The separation between ducts servicing upper and lower combustion air openings shall be main­tained to the source of combustion air.
9.3.8.5 Ducts shall not be screened where terminating in an attic space.
9.3.8.6 Horizontal upper combustion air ducts shall not slope down-
ward toward the source of combustion air.
9.3.8.7 The remaining space surrounding a chimney liner, gas vent, spe­cial gas vent, or plastic piping installed within a masonry, metal, or factory built chimney shall not be used to supply combustion air.
9.3.6.2 Each of the appliances served shall be interlocked to the me­chanical air supply system to prevent main burner operation where the mechanical air supply system is not in operation.
9.3.6.3 Where combustion air is provided by the building’s mechanical ventilation system, the system shall provide the specified combustion air rate in addition to the required ventilation air.
34
Exception: Direct vent appliances designed for installation in a solid fuel-burning fireplace where installed in accordance with the manufacture’s installation instructions.
9.3.8.8 Combustion air intake openings located on the exterior of the building shall have the lowest side of the combustion air intake openings located at least 12 in. (300 mm) vertically from the adjoining grade level.
Page 35
PRODUCT DESIGN
Category I Venting (Vertical Venting) (80% Furnaces Only)
WARNING
TO PREVENT POSSIBLE PERSONAL INJURY OR DEATH DUE TO
ASPHYXIATION, NON-CO NDENSING GAS FIRED WARM AIR FURNACES MUST
C
ATEGORY I VENTED. DO NOT VENT ANY OF THESE FURNACES USING
BE
CATEGORY III VE NTING.
Category I Venting is venting at a non-positive pressure. A furnace vented as Category I is considered a fan-assisted appliance and does not have to be "gas tight." NOTE: Single­Stage and Two-Stage gas furnaces with induced draft blow­ers draw products of combustion through a heat exchanger allowing in some instances common venting with natural draft appliances (i.e. water heaters).
All installations must be vented in accordance with National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition. In Canada, the furnaces must be vented in accordance with the National Standard of Canada, CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions and amendments.
NOTE: The vertical height of the Category I venting system must be at least as great as the horizontal length of the venting system.
Upflow or Horizontal units are shipped with the induced draft blower discharging from the top of the furnace ("Top" is as viewed for an upflow installation). The induced draft blower can be rotated 90 degrees for Category I venting. Refer to the following figure. For horizontal installations, a four inch single wall pipe can be used to extend the induced draft blower outlet 1/2” beyond the furnace cabinet. Vent the fur­nace in accordance with the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition. In Canada, vent the furnace in accordance with the National Standard of Canada, CAN/ CGA B149.1 and CAN/CGA B149.2 - latest editions and amendments.
Supply Air
WARNING
O PREVENT POSSIBLE DEATH OR PERSONAL INJURY DUE TO
T
ASPHYXIATION, COMMON VENTING WITH OTHER MANUFACTURER'S
INDUCED DRAFT APPLIANCES IS NOT ALLOWED.
The minimum vent diameter for the Category I venting sys­tem is as shown in the following chart:
MODEL
045 070 090 115 140
UPFLOW COUNTERFLOW
MINIMUM VENT
4 Inch 4 Inch 4 Inch 4 Inch 4 Inch 4 Inch 5 Inch 5 Inch 5 Inch 5 Inch
Under some conditions, larger vents than those shown above may be required or allowed.
When an existing furnace is removed from a venting system serving other appliances, the venting system may be too
large to properly vent the remaining attached appliances. For complete details refer to Exisiting Furnace Removal sec­tion of this manual.
When resizing any portion of the common venting system, use the appropriate table in Appendix G in the latest edition of the National Fuel Gas Code NFPA 54/ANSI Z223.1.
80% Upflow Rotated Induced Draft Blower
WARNING
TO PREVENT DEATH OR SERIOUS IL LNESS TO BUILDING OCCUPANTS DUE
TO FLUE PRODUCTS LEAKING INTO THE BUILDING, PROPER INSTALLATION OF
GASKETS AND SCREWS IS ESSENTIAL FOR PROVIDING A GAS TIGHT SEAL
BETWEEN THE PARTITION PANEL AND THE INDUCED DRAFT BLOWER.
Make sure all wires are at least one inch from flue pipe. Relocate junction box to right side of cabinet if necessary. Refer to Electrical Connections section of this manual for instructions.
35
Page 36
PRODUCT DESIGN
Masonry Chimneys
Proper Chimney
Termination?
(Check 1)
Yes
No
Line, terminate with
listed vent cap
(Fix 1)
Crown
Clay Tile Size Generally 12" x 12" (24" Length)
Breech
Clean Out
Throat
Damper
Wash
Clay Tile Size: 8" x 8" x12"
(Each x 24" Length)
Attic Floor
1/2" to 1" Air Space
Second Floor
First Floor
F.A.F. Vent Connector
Fan Assisted Forced Air Furnace
Natural Draft Water Heater
Roof Line
Water Heater Vent Connector
Basement Floor
Chimney channel
free of solid and
liquid fuel
appliances?
(Check 2)
Yes
Crown in good
condition
(Check 3)
Yes
Cleanout free of
debris?
(Check 4)
Yes
Liner in good
condition?
(Check 5)
Yes
Dilution air
available? (Check 6)
Yes
Complete the
installation.
(Check 7)
No
No
No
No
No
Change venting
arrangements
(Fix 2)
Rebuild crown
(Fix 3)
and/or Reline
(Fix 4)
Reline (Fix 4)
Reline (Fix 4)
Reline (Fix 4)
Typical Multiple Flue Clay Tile Chimney
Checklist Summary
This checklist serves as a summary of the items to be checked before venting an 80% furnace into a masonry chimney. In addition, we recommend that a qualified ser­viceman use this checklist to perform a yearly inspection of the furnace venting system.
This checklist is only a summary. For detailed information on each of the procedures mentioned, see the paragraph referenced with each item.
This inspection is based upon a draft topical report, "Ma­sonry Chimney Inspection and Relining", issued by the Gas Research Institute. While not yet finalized, we believe this report represents the best information on this subject which is currently available.
36
Check 1 - Proper chimney termination.
A masonry chimney used as a vent for gas fired equipment must extend at least three feet above the highest point where it passes through the roof. It must extend at least two feet higher than any portion of a building within a horizontal dis­tance of 10 feet. In addition, the chimney must terminate at least 3 feet above any forced air inlet located within 10 feet. The chimney must extend at least five feet above the high­est connected equipment draft hood outlet or flue collar.
If the chimney does not meet these termination requirements, but all other requirements in the checklist can be met, it may be possible for a mason to extend the chimney. If this will not be practical, see Fix 1.
Page 37
PRODUCT DESIGN
10' or Less
2' Min.
Ridge
Termination 10 Feet Or Less From Ridge, Wall or
Wall or Parapet
Ridge
Termination More Than 10 Feet From Ridge, Wall or
Check 2 - Any solid or liquid fuel appliances vented into this chimney channel.
Solid fuel appliances include fireplaces, wood stoves, coal furnaces, and incinerators.
Liquid fuel appliances include oil furnaces, oil-fired boilers and oil-fired water heaters.
Appliances which burn propane (sometimes referred to as LP (liquefied petroleum)) gas are considered gas-fired appli­ances.
2' Min.
Wall or Parapet
Chimney
10' or Less
2' Min.
Chimney
Parapet
More than 10'
: No Height
NOTE
above parapet required when distance from walls or parapet is more than 10 feet.
More than 10'
10'
2' Min .
Chimney
Parapet
3' Min.
3' Min.
3' Min .
Chimney
Height above any roof surface within 10 feet horizontally.
3' Min .
Check 3 - Chimney Crown Condition.
Damage from condensate usually shows up first in the crown. If any of the following trouble signs are present, the condi­tion of the crown is not satisfactory:
a) Crown leaning b) Bricks missing c) Mortar missing d) Tile liner cracked e) No tile liner f) Salt staining at mortar joints. (White stains, and mor-
tar becomes sandy and/or erodes.)
For problems a, b, or c, see Fix 3. If problems d, e, or f are present, see Fix 4. IMPORTANT: It may be necessary to follow both Fix 3 and Fix 4.
Check 4 - Debris in Cleanout
A cleanout (dropleg) must be present such that the upper edge of the cleanout cover is at least 12 inches below the lower edge of the lowest chimney inlet opening.
A chimney without a cleanout could become partially blocked by debris. If no cleanout is present, the chimney must be relined (Fix 4).
Remove the cleanout cover, and examine the cleanout for debris. If significant amounts of any of the following are found:
Fuel oil residue
Bricks
Mortar or sand
Pieces of the tile liner
Rusted pieces of the metallic liner
reline the chimney (Fix 4).
Check 5 - Liner Condition.
If a metal liner is present, it must be checked. It cannot be assumed that all existing metal liners are correctly installed and in good condition.
Remove the lowest existing vent connector, and examine the inside of the elbow or tee at the base of the liner. A small amount of soot may be considered acceptable, provided the installer vacuums it away. If rusted pieces of the liner have collected here, the metal liner must be removed and replaced (Fix 4).
Next, gently tap the inside of the liner with a Phillips screw­driver. If the screwdriver perforates the liner, or if the tapping does not sound like metal hitting metal, the liner must be removed and replaced (Fix 4).
Remember that all appliances must be vented inside the liner. Venting one appliance inside the liner and another ap­pliance outside the liner is not acceptable.
Next, use a flashlight and small mirror to sight up the liner. B vent must be supported so as to not come into direct contact with the chimney walls or tile liner. If it is not, it can probably be rehung so as to be acceptable. A thimble or fire stop may be helpful here.
37
Page 38
PRODUCT DESIGN
Flexible liners should be hung straight or nearly straight. If it is spiraled in the chimney and in good condition, it should be rehung. To do this, break the top seal; pull up and cut off the excess liner length, and refit the top seal. Use caution when doing this, as the cut edges of flexible liners may be sharp.
The surfaces of the liner must be physically sound. If gaps or holes are present, the metal liner must be removed and replaced (Fix 4).
Finally, confirm that the metal liner is the correct size for the appliances to be installed. Use the GAMA tables and rules.
If a metal liner is not present, a clay tile liner must be present, or the chimney must be lined (Fix 4).
Use a flashlight and small mirror at the cleanout or vent connector to inspect the clay tile liner. If any of the following problems are present:
Tile sections misaligned
Tile sections missing
Gaps between tile sections
Signs of condensate drainage at the cleanout or vent connectors
Mortar protruding from between tile sections
Use of sewer pipe or drainage pipe rather than an ap­proved fire clay tile
reline the chimney (Fix 4). Next, measure the size of the liner. It may be possible to do
this from the cleanout. The liner must be at least as large as the minimum size established by the tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CGA B149.1 and CAN/ CGA B149.2 - latest editions and amendments. If the liner is too small or too large, then the chimney must be relined (Fix 4).
Check 6 - Dilution Air.
If gas-fired appliances are to be vented into a clay tile liner, a source of dilution air is required.
Dilution air cannot be obtained through:
Induced draft appliances
Natural draft appliances with vent dampers
Sufficient dilution air can ordinarily be obtained through the draft hood of a natural draft appliance only if the appliance’s vent connector does not include a vent damper.
If dilution air will not be available, the chimney must be re­lined (Fix 4).
Check 7 - Complete the Installation.
If Checks 1 through 6 have been satisfactory, and the liner is an acceptable size as determined by the tables in Na­tional Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions and amendments, then the clay tile liner can probably be used as a vent for the gas appliances. However, the installer must keep in mind the following factors which may render the tile liner unsuit­able for use as a vent:
38
Extremely cold weather
Long vent connectors
Masonry chimneys with no air gap between the liner and the bricks. (In practice, this can be difficult to detect.)
Exterior chimneys (The tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions and amend­ments assume interior chimneys.)
If, in the judgment of the local gas utility, installer, and/or local codes; one or more of the above factors is likely to present a problem, the chimney must be relined (Fix 4).
Fix 1 - Liner Termination.
Any cap or roof assembly used with a liner must be ap­proved by the liner manufacturer for such use. The liner and cap/roof assembly must then terminate above the roof in accordance with the manufacturer’s instructions.
In some cases, a shorter extension above the roof may be possible with a liner than would be required with a masonry chimney.
For further information on relining, see Fix 4.
Fix 2 - Change Venting Arrangements
If the masonry chimney has more than one channel, it may be possible to vent the gas appliances into one channel and vent the solid or liquid fuel appliance(s) into another channel(s). Do not vent an 80% furnace inside of a metal liner with other appliances vented outside the liner.
Alternatively, the homeowner may agree to discontinue use of the fireplace (solid fuel appliance). If so, the tile liner must be cleaned to remove creosote buildup. The fireplace open­ing must then be permanently sealed.
If oil-fired appliance(s) are being replaced by gas-fired appliance(s), the tile liner must first be cleaned to remove the fuel oil residue.
If none of the above options are practical, the 80% furnace may need to be vented vertically with B vent.
Under some conditions a 90%+ furnace could be installed rather than an 80%. The 90% furnace can be vented hori­zontally or vertically through PVC pipe.
Fix 3 - Rebuild the Crown.
If the chimney crown is damaged, a qualified mason must repair it in accordance with nationally recognized building codes or standards. One such standard which may be refer­enced is the Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances, ANSI/NFPA 211.
Page 39
PRODUCT DESIGN
Fix 4 - Relining.
Relining options include B vent and flexible liners. If the chimney has diagonal offsets, B vent probably cannot
be used. If B vent is to be used, it must be supported adequately.
Supports (such as fire stops or thimbles) must be used to prevent the B vent from coming into direct contact with the tile liner or chimney walls. Direct contact would result in higher heat loss, with an increased possibility of poor vent­ing system performance.
It is not acceptable to vent one appliance inside the B vent and other appliances outside. The excess space between the B vent and the chimney walls must be covered at the top of the chimney by a weatherproof, corrosion resistant flash­ing.
The B vent should then be topped with a listed vent cap. The listed vent cap will, when installed per the manufacturer’s instructions, prevent problems due to rain, birds, or wind effects.
A B vent installed as described in this section is considered to be an enclosed vent system, and the sizing tables in National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edi­tion and in the National Standard of Canada, CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions and amend­ments may be used.
If a flexible liner is to be used, it must be made of the proper materials:
For most residential applications, an aluminum liner should be acceptable.
If the combustion air supplied to the furnace will be contaminated with compounds containing chlorine or fluorine, a liner of AL29-4C stainless steel should be used. Common sources of chlorine and fluorine com­pounds include indoor swimming pools and chlorine bleaches, paint strippers, adhesives, paints, varnishes, sealers, waxes (which are not yet dried) and solvents used during construction and remodeling. Various com­mercial and industrial processes may also be sources of chlorine/fluorine compounds.
Heavier gauge 300 and 400 series stainless steel lin­ers were developed for use with oil or solid fuel appli­ances. They are not suitable for use with gas-fired appliances. Flexible liners specifically intended and tested for gas applications are listed in the UL "Gas and Oil Equipment Directory". (UL Standard 1777).
For sizing of flexible liners, see Note 22 and the tables in the National Fuel Gas Code NFPA 54/ANSI Z223.1 - latest edition and in the National Standard of Canada, CAN/CGA B149.1 and CAN/CGA B149.2 - latest editions and amend­ments.
To install the liner, read and follow the liner manufacturer’s instructions and your local codes. Excess liner length should be pulled out of the chimney and cut off. Use caution when doing this, as the cut edges of flexible liners may be sharp.
Do not spiral excess liner inside of the chimney. Support the liner as recommended by the liner manufacturer.
Some manufacturers of flexible liners offer an insulation sleeve designed to be added to the liner before it is installed in the chimney. (Poured insulation, either vermiculite or other ma­terials, is no longer recommended.) Insulation will need to be added to the flexible liner if:
It is required by the liner manufacturer’s instructions.
The previous liner was properly sized and installed, and suffered from condensation damage.
It is required by your local building codes.
Even if none of those three conditions exist which require additional liner insulation, the installer may wish to consider it if:
The local climate is very cold.
The chimney is very tall.
The vent connectors used are very long or have a large number of elbows.
Local experience indicates that flexible liners installed without insulation are likely to have condensation prob­lems.
Insulation must be selected and installed in accordance with the liner manufacturer’s instructions.
Finally, cap the chimney and terminate the liner in accor­dance with the liner manufacturer’s instructions.
Horizontal Applications and Considerations
Horizontal applications, in particular, may dictate many of the installation’s specifics such as airflow direction, duct­work connections, flue and/or combustion air pipe connec­tions, etc. The basic application of this furnace as a hori­zontal furnace differs only slightly from an upright installa­tion. When installing a furnace horizontally, additional con­sideration must be given to the following:
(90% Furnaces Only)
ALTERNATE VENT/F LUE AND COMBUSTION AIR INTAKE LOCATIONS
GAS LINE WITH DRIP LEG (3" MINIMUM)
(90% Furnaces Only)
DRAIN PAN
FURNACE MUST BE SUPPORTED AT BOTH ENDS AND MIDDLE
FURNACE M UST BE LEVEL FROM END TO END
(90% Furnaces Only)
4 3/4" MINIMUM DRAIN TRAP CLEARANCE
36" MINIMUM SERVICE CLEARANCE REQUIRED
(90% Furnaces Only)
FURNACE MUST BE LEVEL OR SLIGHTLY TILTED FORWARD WITH THE DOORS 0" - 3/4" BELOW THE BACK PANEL
(90% Furnaces Only)
DRAIN LINE WITH 1/4" PER FOOT DOWNWARD SLOPE
90% Horizontal Furnace Shown
(80% Horizontal Furnace Similar)
39
Page 40
PRODUCT DESIGN
Drain Trap and Lines (90% Furnaces Only)
In horizontal applications the condensate drain trap is se­cured to the furnace side panel, suspending it below the furnace. A minimum clearance of 4 3/4" below the furnace must be provided for the drain trap. Additionally, the appro­priate downward piping slope must be maintained from the drain trap to the drain location. Refer to Condensate Drain Trap and Lines section in this manual or the installation instructions for further details. If the drain trap and drain line will be exposed to temperatures near or below freezing, ad­equate measures must be taken to prevent condensate from freezing. NOTE: The use of insulation and/or heat tape is recommended. Failure to provide proper condensate drain­age can result in property damage.
Leveling (90% Furnaces Only)
Leveling ensures proper condensate drainage from the heat exchanger and induced draft blower. For proper flue pipe drainage, the furnace must be level lengthwise from end to end. The furnace should also be level from back to front or have a slight tilt with the access doors downhill (approxi­mately 3/4") from the back panel. The slight tilt allows the heat exchanger condensate, generated in the recuperator coil, to flow forward to the recuperator coil front cover.
Alternate Vent/Flue and Combustion Air Connections (90% Furnaces Only)
NOTE: Alternate combustion fresh air inlet location on the
right hand panel side of 90% furnace models has been discontinued since November 2005.
In horizontal installations provisions for alternate flue and combustion air piping are available for upflow furnaces with left discharge. In these positions the flue and combustion air piping can be run vertically through the side of the fur­nace. Refer to the following figure "Recommended Installa­tion Positions" for further detail. The standard piping con­nections may also be used in these positions. Refer to Vent/ Flue Pipe and Combustion Air Pipe section in this manual or the installation instructions for details concerning the con­version to the alternate vent/flue and combustion air con­nections on the 90% furnace.
AIR
DISCHARGE
Side
Return
Duct
Connection
AIR
DISCHARGE
UPFLOW HORIZONTAL
LEFT AIR DISCHARGE
Bottom Return
Duct
Connection
UPFLOW HORIZONTAL
RIGHT AIR DISCHARGE
Bottom Return
Duct
Connection
UPFLOW UPRIGHT
ALTERNATE FLUE AND COMBUSTION AIR PIPE LOCATIONS
ALTERNATE FLUE AND COMBUSTI ON AIR PIPE LOCATIONS
Side
Return
Duct
Connection
Bottom Return
Duct
Connection
AIR
DISCHARGE
Connection
COUNTERFLOW
UPRIGHT
Bottom Return
Duct
Connection
COUNTERFLOW HORIZONTAL
RIGHT AIR DISCHARGE
AIR
DISCHARGE
COUNTERFLOW HORIZONTAL
LEFT AIR DISCHARGE
Bottom
Return
Duct
ALTERNATE FLUE AND COMBUSTION AIR PIPE LOCATIONS
AIR
DISCHARGE
ALTERNATE FLUE AND COMBUSTION AIR PIPE LOCATIONS
AIR
DISCHARGE
Bottom Return
Duct
Connection
90% Furnace Recommended Installation Positions
NOTE: Alternate "vertical" piping connections can not be
used when an upflow 90% furnace is installed with supply air discharging to the right or when a counterflow furnace is installed with supply discharging to the left. In this case, use the standard flue and combustion air piping connec­tions
Alternate Electrical and Gas Line Connections
The 80% & 90% furnaces have provisions allowing for elec­trical and gas line connections through either side panel. In horizontal applications the connections can be made either through the “top” or “bottom” of the furnace.
Drain Pan (90% Furnaces Only)
A drain pan must be provided if the furnace is installed above a conditioned area. The drain pan must cover the entire area under the furnace (and air conditioning coil if applicable).
40
Freeze Protection (90% Furnaces Only)
If the drain trap and drain line will be exposed to tempera­tures near or below freezing, adequate measures must be taken to prevent condensate from freezing. NOTE: The use of insulation and/or heat tape is recommended. Failure to provide proper condensate drainage can result in property damage.
Page 41
PRODUCT DESIGN
Propane Gas and/or High Altitude Installations
WARNING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF
THE CORRECT CONV ERSION KITS ARE NOT INSTALLED.
MUST BE APPLIE D TO INSURE SAFE AN D PROPER FURNACE OPERATI ON.
CONVERSIONS MUST BE PERFORMED BY A QUALIF IED INSTALLER OR SERVICE
AGENCY.
THE APPROPRIATE KITS
ALL
Do not use commercially available “no hub connectors” other
than those shipped with this product. It is the responsibility of the installer to follow the manufac-
turers’ recommendations and to verify that all vent/flue pip­ing and connectors are compatible with furnace flue prod­ucts. Additionally, it is the responsibility of the installer to ensure that all piping and connections possess adequate structural integrity and support to prevent flue pipe separa­tion, shifting, or sagging during furnace operation.
This furnace is shipped from the factory configured for natu­ral gas at standard altitude. Propane gas installations re­quire an orifice change to compensate for the energy con­tent difference between natural and propane gas.
High altitude installations may require both a pressure switch and an orifice change. These changes are necessary to com­pensate for the natural reduction in the density of both the gas fuel and the combustion air at higher altitude.
Refer to the Accessories Charts in this manual or product Specification Sheet for a tabular listing of appropriate manufacturer’s kits for propane gas and/or high altitude in­stallations. The indicated kits must be used to insure safe and proper furnace operation. All conversions must be per­formed by a qualified installer, or service agency.
VENT/FLUE PIPE AND COMBUSTION AIR PIPE (90% FURNACES ONLY)
WARNING
FAILURE TO FOLLOW THESE INSTRUCTIONS CAN RESULT IN BODILY INJURY OR
DEATH.
CAREFU LLY RE AD AND FOLLOW ALL I NSTR UCTI ONS GI VEN I N THIS
SECTION.
WARNING
UPON COMPLETION OF THE FURNACE INSTALLATION, CAREFULLY INSPECT THE
ENTIRE FLUE SYSTEM BO TH INSIDE AND OUTSIDE THE FURNACE TO ASSURE IT
IS PROPERLY SEALED.
PERSONAL INJURY OR DEATH DUE TO EXPOSURE TO FLUE PRODUCTS,
INCLUDING CARBON MONOXIDE.
LEAKS IN THE FLUE SYSTEM CAN RESULT IN SERIOUS
A condensing gas furnace achieves its high level of efficiency by extracting almost all of the heat from the products of combustion and cooling them to the point where condensa­tion takes place. Because of the relatively low flue gas tem­perature and water condensation requirements, PVC pipe is used as venting material.
This furnace must not be connected to Type B, BW, or L vent or vent connector, and must not be vented into any portion of a factory built or masonry chimney except when used as a pathway for PVC as described later in this sec­tion. Never common vent this appliance with another appli- ance or use a vent which is used by a solid fuel appliance.
Dual Certification: Non-Direct/Direct Vent (90% Furnaces Only)
The 90% furnace is dual certified and may be installed as a non-direct vent (single pipe) or direct vent (dual pipe) appli­ance. A non-direct vent installation requires only a vent/ flue pipe. A direct vent installation requires both a vent/ flue pipe and a combustion air intake pipe. Refer to the ap­propriate section for details concerning piping size, length, number of elbows, furnace connections, and terminations.
Concentric Vent Termination (90% Furnaces Only)
The Concentric Vent Kits DCVK-20 and DCVK-30 are de­signed to allow the terminations of a direct vent furnace to be "concentrically" vented through a wall or roof. These kits allow a single penetration to support terminations for both the vent/flue pipe and the combustion air intake pipe.
The Sidewall Vent Kit # 0170K00000S is used with 2" or 3" dual pipe installations. This kit in NOT intended for use with single pipe (non-direct vent) installations. You MUST con­nect the kit as a (direct vent) two-pipe installation.
NOTE: This kit is not certified for, and must not be applied to any furnace not listed in this service manual.
Refer to the directions provided with the concentric vent kit for installation specifications.
NOTE: The previously used concentric vent kits, HCVK (de­signed for horizontal, through the wall terminations) and the VCVK were approved for use in Service Bulletins GF-172 and S-199 (designed for vertical, through the roof termina­tions.) The appropriate kit must be used for a given termina­tion placement (horizontal or vertical).
Materials and Joining Methods (90% Furnaces Only)
WARNING
T
O AVOID BODILY I NJURY, FIRE OR EXPLOSION, SOLVENT CEMENTS MUST BE
KEPT AWAY F ROM ALL IGNITION SOURCES (I.E., SPARKS, OPEN FLAMES, AND
EXCESSIVE HEAT) AS THEY ARE COMBUS TIBLE LIQUIDS.
CEMENT VAPORS OR CONTACT WITH SKIN AND/OR EYES.
A
VOID BREATHING
Two or three inch nominal diameter PVC Schedule 40 pipe meeting ASTM D1785, PVC primer meeting ASTM F656, and PVC solvent cement meeting ASTM D2564 specifica­tions must be used. Fittings must be DWV type fittings meet­ing ASTM D2665 and ASTM D3311. Carefully follow the manufacturer’s instructions for cutting, cleaning, and sol­vent cementing of PVC.
41
Page 42
PRODUCT DESIGN
As an alternative to PVC pipe, primer, solvent cement, and fittings, ABS materials which are in compliance with the following specifications may be used. Two or three inch ABS Schedule 40 pipe must meet ASTM D1527 and, if used in Canada, must be CSA listed. Solvent cement for ABS to ABS joints must meet ASTM D2235 and, if used in Canada, must be CSA listed. The solvent cement for the PVC to ABS transition joint must meet ASTM D3138. Fittings must be DWV type fittings meeting ASTM D2661 and ASTM D3311 and, if used in Canada, must be CSA listed. Carefully follow the manufacturers’ instructions for cutting, cleaning, and solvent cementing PVC and/or ABS.
All 90° elbows must be medium radius (1/4 bend DWV) or long radius (Long sweep 1/4 bend DWV) types conforming to ASTM D3311. A medium radius (1/4 bend DWV) elbow measures 3 1/16" minimum from the plane of one opening to the centerline of the other opening for 2" diameter pipe, and 4 9/16" minimum for 3" pipe.
Proper Vent/Flue and Combustion Air Piping Practices (90% Furnaces Only)
Adhere to these instructions to ensure safe and proper fur­nace performance. The length, diameter, and number of el­bows of the vent/flue pipe and combustion air pipe (when applicable) affects the performance of the furnace and must be carefully sized. All piping must be installed in accordance with local codes and these instructions.
Piping must be adequately secured and supported to pro­hibit sagging, joint separation, and/or detachment from the furnace. Horizontal runs of vent/flue piping must be supported every three feet and must maintain a 1/4 inch per foot down­ward slope, back towards the furnace, to properly return condensate to the furnace’s drain system. Allowances should be made for minor expansion and contraction due to tem­perature variations. For this reason, particular care must be taken to secure piping when a long run is followed by a short offset of less than 40 inches.
Precautions should be taken to prevent condensate from freezing inside the vent/flue pipe and/or at the vent/flue pipe termination. All vent/flue piping exposed to freezing termperatures below 35° F for extended periods of time must be insulated with 1/2" thick closed cell foam. Also all vent/ flue piping exposed outdoors in excess of the terminations shown in this manual (or in unheated areas) must be insu­lated with 1/2" thick closed cell foam such as "Armaflex" or "Insultube". Inspect piping for leaks prior to installing insula­tion.
Termination Locations (90% Furnaces Only) NOTES: Refer to Location Requirements and Considerations
section of this manual or the installation instructions for com­bustion air contaminant restrictions.
The following bullets and diagram describe the restrictions concerning the appropriate location of vent/flue pipe and com­bustion air intake pipe (when applicable) terminations. Re­fer to Non-Direct Vent (Single Pipe) Piping and Direct Vent (Dual Pipe) Piping sections located in this manual or the installation instructions for specific details on termination construction.
All terminations must be located at least 12 inches above ground level or the anticipated snow level.
Vent terminations must terminate at least 3 feet above any forced air inlet located within 10 feet.
NOTE: This provision does not apply to the combus­tion air intake termination of a direct vent application.
The vent termination of a non-direct vent application must terminate at least 4 feet below, 4 feet horizon­tally from, or 1 foot above any door, window, or gravity air inlet into any building.
The vent termination of a direct vent application must terminate at least 12 inches from any opening through which flue gases may enter a building (door, window, or gravity air inlet).
The vent termination of vent pipe run vertically through a roof must terminate at least 12 inches above the roof line (or the anticipated snow level) and be at least 12 inches from any vertical wall (including any antici­pated snow build up).
A vent termination shall not terminate over public walk­ways or over an area where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves, or other equipment.
The combustion air intake termination of a direct vent application should not terminate in an area which is frequently dusty or dirty.
NOTE: In Canada, the Canadian Fuel Gas Code takes pre­cedence over the preceding termination restrictions.
OTHER THAN
COMBUSTION AIR
TERMINATION INTAKE
NON-DIRECT VENT
VENT/FLUE TERMINATION
NO TERMINATIONS ABOVE WALKWAY
3"
GRADE OR HIGHEST
ANTICIPATED
SNOW LEVEL
FORCED AIR
INLET
10'
12"
12"
DIRECT VENT
VENT/FLUE TERMINATION
12"
VENT/FLUE TERMINATION
4'
4'
12"
NON-DIRECT VENT
42
90% Furnace Vent Termination Clearances
Page 43
PRODUCT DESIGN
Canadian Venting Requirements (90% Furnaces Only)
In Canada, venting must conform to the requirements of the current CAN/CGA-B149 Installation Code. Use only CSA listed two or three inch diameter PVC or ABS pipe, solvent cement, and fittings throughout. Carefully follow the manu­facturers’ instructions for cutting, cleaning, and solvent ce­menting PVC and/or ABS.
The vent can be run through an existing unused chimney provided the space between the vent pipe and the chimney is insulated and closed with a weather-tight, corrosion-re­sistant flashing.
The vent shall not be located:
Less than 12 inches above the finished grade line.
Less than 36 inches from any building opening or any gas service regulator. For gas service regulators in the Province of Ontario, 72 inches.
Less than 72 inches from the combustion air intake of another appliance.
Directly above a gas utility meter or service regulator.
Over a walkway unless located 84 inches above grade.
Standard Furnace Connections (90% Furnaces Only)
It is the responsibility of the installer to ensure that the pip­ing connections to the furnace are secure, airtight, and ad­equately supported.
As shipped, attachment "couplings" for vent/flue and com­bustion air intake pipe connections are provided on the furnace’s top cover (upflow). To use the standard connec­tions, field supplied vent/flue pipe and combustion air intake pipe (when applicable) should be secured directly to the fur­nace at these locations.
Vent/Flue Pipe (90% Furnaces Only)
Vent/flue pipe can be secured to the vent/flue coupling us­ing the rubber coupling and worm gear hose clamps pro­vided with this furnace. Torque hose clamps to 20 inch-lbs (see "Standard Connections" figure). The rubber coupling allows separation of the vent/flue pipe from the furnace dur­ing servicing. NOTE: Do not use other commercially avail­able "no hub connectors" due to possible material conflicts. The vent/flue pipe can also be secured using a PVC or ABS elbow or coupling using the appropriate glue (see Materials and Joining Methods section in this manual or the installa­tion instructions for further details).
NOTE: For non-direct vent installations, a minimum of one 90° elbow must be installed on the combustion air intake coupling to guard against inadvertent blockage.
Combustion Air Pipe (90% Furnaces Only)
Direct Vent Installations
On upflow units secure the combustion air intake pipe di­rectly to the air intake coupling. On counterflow units se­cure the combustion air intake pipe to the air intake cou­pling using the rubber coupling and worm gear hose clamps
provided with the unit. The counterflow rubber coupling al­lows service removal of air intake piping internal to the fur­nace blower compartment. NOTE: Because of probable ma­terial conflicts, do not use other commercially available “no hub connectors”. The combustion air intake pipe can also be secured directly to the counterflow unit air intake pipe coupling.
Non-Direct Vent Installations
A minimum of one 90° elbow must be installed on the com­bustion air intake “coupling” to guard against inadvertent blockage.
(DIRECT VENT ONLY)
90 PVC
ELBOW
(NON-DIRECT VENT)
COMBUSTION
AIR PIPE
OR
VENT/FLUE
PIPE
RUBBER
COUPLING
WITH WORM
GEAR CLAMPS
UPFLOW COUNTERFLOW
90 PVC ELBOW
(NON-DIRECT VENT)
COMBUSTION
AIR PIPE
(DIRECT VENT ONLY)
OR
RUBBER
COUPLINGS
WITH WORM
GEAR CLAMPS
VENT/FLUE
PIPE
90% Furnace Vent/Flue & Combustion Air
Standard Connections
Alternate Furnace Connections (90% Furnaces Only) NOTE: Alternate combustion fresh air inlet location on the
right hand panel side of 90% furance models was discontin­ued since November 2005).
If the standard locations are undesirable for a specific instal­lation, alternate side panel locations are available for both alternate combustion air inlet and vent/flue pipe connections. These locations may be of particular benefit to upright upflow installations requiring additional access to an A coil or to horizontal installations desiring vent/flue (and combustion air intake) piping run vertically from the side of the cabinet.
NOTE: Standard and alternate locations can be combined (i.e., an installation may use the standard combustion air intake location but use the alternate vent/flue location or vice versa), if needed.
CAUTION
DGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES A PRECAUTION
E
WHEN REMOVING HOLE PLUGS.
The alternate vent/flue location is the large hole directly in line with the induced draft blower outlet. Refer to the follow­ing “Alternate Vent/Flue Location” figure for details.
43
Page 44
PRODUCT DESIGN
WARNING
HE RUBBER ELBOW IS NOT DESIGNED TO SUPPORAT A LOAD. WHEN THE
T
RUBBER ELBOW IS MOUNTED EXTERNALLY TO THE FURNACE CABINET,
EXTREME CARE MUST BE TAKEN TO ADEQUATELY SUPPORT FIELD-SUPPLIED
VENT/FLUE PIPIN G, AS DAMAGE CAN RESULT IN LEAKS CAUSING BODILY
INJURY OR DEATH DUE TO EXPOSURE TO FLUE GASES, INCLUDING CARBON
MONOXIDE.
For upright installations, externally mount the rubber el­bow to the vent/flue coupling using a worm gear hose clamp. Secure field supplied vent/flue piping to the rubber elbow using a worm gear hose clamp. NOTE: Use of the alternate vent/flue location for upright installations, requires the drain trap be installed on the same side of the unit as the flue pipe.
For horizontal installations, externally secure the field-sup- plied vent/flue pipe directly to the vent/flue coupling using a PVC or ABS coupling or elbow.
3
REMOVE
PIPE
*
***
M1
O F
*
F
23PC
ON
**
UPFLOW
1
REMOVE
4 SCREWS
REMOVE
AND RELOCATE
DETACH RUBBER
ELBOW FRO M
ID BLOWER AND
VENT/FLUE
PIPE
COUNTERFLOW/UPRIGHT
(UPFLOW SIMILAR)
1.
REMOVE
4 SCREWS
5
2
COUNTERFLOW
**
ON
23PC
*
O F F
M1
ID BLOWER WITH
***
*
RUBBER COUPLING
**
ON
23PC
*
O F F
1
M
***
*
5
ADDITIONAL PLUG
FROM DRAIN KIT
7
EXTERNALLY
MOUNT
RUBBER ELBOW
6
SECURE TO
AND HOSE
CLAMPS
3
REMOVE
PIPE
REMOVE
AND RELOCATE
DETATCH RUBBER
ELBOW FROM
ID BLOWER AND
1
REMOVE
3 SCREWS
5
2
VENT/FLUE
PIPE
Alternate Combustion Air Intake Location (90% Fur­naces Only)
NOTE: Alternate combustion fresh air inlet location on the
right hand panel side of 90% furance models was discontinued since November 2005).
The alternate combustion air intake location is the large hole not in line with the induced draft blower outlet. Refer to the following "Alternate Combustion Air Intake Location” figure for details.
CAUTION
E SURE NOT TO DAMAGE INTERNAL WIRING OR OTHER COMPONENTS WHEN
B
REINSTALLING COUPLING AND SCREWS.
For non-direct vent installations installed horizontally, a minimum of one 90° elbow must be installed on the com­bustion air intake coupling to guard against inadvertent block­age. No elbow is required on the alternate combustion air intake of upright installations, however, a minimum clear­ance of 2 inches is required to assure proper air supply.
For direct vent installations, secure field-supplied combus- tion air intake pipe directly to the air intake coupling.
1
REMOVE
4 SCREWS
UPFLOW
SECURE
TO CABINET
REMOVE
4
2
RELOCATE
3
REMOVE
AND
2 REMOVE AND CUT
1
REMOVE
3 SCREWS
3 ADDITIONAL PLUG FROM
DRAIN KIT
5
1
REMOVE
4 SCREWS
COUNTERFLOW
5
2" CLEARANCE
REQUIRED
(NON-DIRECT
VENT)
3
.
REMOVE
AND
RELOCATE
6
SECURE TO
ID BLOWER WITH
RUBBER COUPLING
AND HOSE
CLAMPS
*
*
123
M
PC
ON
*
O F F
*
*
**
SECURE TO
CABINET WITH
UPFLOW/HORIZONTAL
(COUNTERFLOW SIMILAR)
90% Furnace Alternate Vent/Flue Location
44
6
SCREWS
UPFLOW/H ORIZONTAL SHOW N
(COUNTERFLOW SIMILAR)
90% Furnace Alternate Combustion
Air Intake Location
Non-Direct Vent (Single Pipe) Piping (90% Furnaces Only)
Non-direct vent installations require only a vent/flue pipe. The vent pipe can be run horizontally with an exit through the side of the building or run vertically with an exit through the roof of the building. The vent can also be run through an existing unused chimney; however, it must extend a mini­mum of 12 inches above the top of the chimney. The space
Page 45
PRODUCT DESIGN
between the vent pipe and the chimney must be closed with a weather-tight, corrosion-resistant flashing. For details con­cerning connection of the vent/flue pipe to the furnace, refer to Vent/Flue Pipe and Combustion Air Pipe - Standard Fur- nace Connections or Alternate Furnace Connections sec­tion in this manual or the installation instructions for specific details. Refer to the following Non-Direct Vent (Single Pipe) Piping - Vent/Flue Pipe Terminations section in this manual or the installation instructions for specific details on termi­nation construction.
Although non-direct vent installations do not require a com- bustion air intake pipe, a minimum of one 90° elbow must be attached to the furnace’s combustion air intake if, an upright installation uses the standard intake location, or a horizontal installation uses the alternate air intake location. This elbow will guard against inadvertent blockage of the air intake.
GKS9
Non-Direct Vent (Single Pipe)
Maximum Allowable Length of Vent/Flue Pipe (ft)
Models
(kBTU_Tons)
045_3 2 68656259565350
070_3
070_4 2 55524946434037
090_4
090_5
115_5 3 68656259565350
Pipe
(4)
Size
(in.) 2345678
2 36333027242118 3 68656259565350
2 37343128252219 3 68656259565350 2 39363330272421 3 68656259565350
Number of Elbows
(1) (2)
(3) (5)
NOTE: Alternate combustion fresh air inlet location on the right hand panel side of 90% furance models was discontinued since November 2005).
Vent/Flue Pipe Lengths (Non-Direct Vent) and Diam­eters (90% Furnaces Only)
Refer to the following tables for applicable length, elbows, and pipe diameter for construction of the vent/flue pipe sys­tem of a non-direct vent installation. In addition to the vent/ flue pipe, a single 90° elbow must be secured to the com­bustion air intake to prevent inadvertent blockage. The tee or elbows used in the vent/flue termination must be included when determining the number of elbows in the piping sys­tem.
AMS9, ACS9, DMS9, DCS9, GMS9, GCH9, GCS9
Non-Direct Ve nt (Single Pipe)
Maximum Allow able Length of Vent/Flue Pipe (ft)
Unit Input
(BTU)
45,000 2 68 65 62 59 56 53 50 70,000 2 68 65 62 59 56 53 50 90,000 2 60 57 55 52 50 47 45
115,000
1) One 90° elbow should be secured to the combustion air intake con­nection.
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
3) Tee used in the vent/flue termination must be included when deter­mining the number of elbows in the piping system.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
Pipe
(4)
Size
(inc.)2345678
2 25222017151210 3 58555249464340
Number of Elbow s
(3) (5 )
(1) (2 )
AMH95, GMH95, AMS95, GMS95
Non-Direct Ve nt (Single Pipe)
Maximum Allow able Length of Vent/Flue Pipe (f t)
Mod els
(kBtu_Tons
)
045_3 2 68 65 62 59 56 53 50 070_3 2 68 65 62 59 56 53 50 070_4 2 46 43 40
090_4
090_5 3 68 65 62 59 56 53 50 115_5 3 68 65 62 59 56 53 50
1) One 90° elbow should be secured to the combustion air intake connection.
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
3) Tees and/or elbows used in the vent/flue termination must be in­cluded when determining the number of elbows in the piping sys-
tem.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
Pipe
(4)
Size
(inc.)2345678
2 161310 3 68656259565350
Number of Elbow s
Not Rec ommended
(3) (5 )
(1) (2 )
Vent/Flue and Combustion Air Pipe Lengths and Diam­eters (95% Furnaces Only)
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue and com­bustion air intake pipe systems of a non-direct vent (single pipe) installation. The number of elbows tabulated repre­sents the number of elbows and/or tees in each (Vent/Flue & Combustion Air Intake) pipe. Elbows and/or tees used in the terminations must be included when determining the number of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objectionable, insulation of the combustion air pipe may be required. Use 1/2” thick closed cell foam insulation such as Armaflex or Insultube where required.
45
Page 46
PRODUCT DESIGN
ACV9, AMV9, GCV9, GMV9, GMV95
UPFLOW
Non-Direct Vent (Single Pipe)
Maximum Allowable Length of Vent/Flue Pipe (ft)
(4)
Unit Input
45,000 2 7168656259565350
70,000
90,000 3 7168656259565350
115,000 3 49 46 43 40 37 34 31 28
Pipe
(inch)
12345678
2 4946434037343128 3 7168656259565350
Number of Elbows
COUNTERFLOW
Non-Direct Vent (Single Pipe)
Maximum Allowable Length of Vent/Flue Pipe (ft)
(1)(2)
(3)(5)
(1)(2)
TEE
12 " MINIMUM TO
ROOF OR
HIGHEST ANTICIPATED
SNOW LEVEL
(4)
Unit Input
70,000
90,000
1) One 90° elbow should be secured to the combustion air intake connection.
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
3) Tee used in the vent/flue termination must be included when deter­mining the number of elbows in the piping system.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
Pipe
(inch)
12345678 2 6158555249464340 3 7168656259565350 2 6158555249464340 3 7168656259565350
Number of Elbows
(3)(5)
Vent/Flue Pipe Terminations (90% Furnaces Only)
The vent/flue pipe may terminate vertically, as through a roof, or horizontally, as through an outside wall.
Vertical vent/flue pipe termination should be as shown in the following figures. Refer to Vent/Flue Pipe and Combus- tion Air Pipe - Termination Locations section in this manual or the installation instructions for details concerning loca­tion restrictions. The penetration of the vent through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent.
90% Furnace Standard Vertical Termination
(Single Pipe)
90º
MEDIUM RADIUS
ELBOW
12" MINIMUM
90% Furnace Alternate Vertical Termination
(Single Pipe)
Horizontal vent/flue pipe terminations should be as shown in the following figure. Refer to Vent/Flue Pipe and Combus- tion Air Pipe - Termination Locations section in this manual or the installation instructions for details concerning loca­tion restrictions. A 2 3/8" diameter wall penetration is re­quired for 2" diameter pipe while a 3 1/2" diameter hole is required for 3" diameter pipe. To secure the pipe passing through the wall and prohibit damage to piping connections, a coupling should be installed on either side of the wall and solvent cemented to a length of pipe connecting the two couplings. The length of pipe should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall. The wall penetration should be sealed with silicone caulking material.
46
Page 47
PRODUCT DESIGN
WALL
INSIDE
ELBOW OR COUPLING
90% Furnace Horizontal Termination (Single Pipe)
12" MINIMUM
OUTSIDE
COUPLING
MINIM UM
12"
FROM
WALL
TEE
ELBOW
TURNED
DOWN
12"
TO GROUND OR
HIGHEST ANTICIPATED
SNOW LEVEL
VENT/FLUE TEE
90° ELBOW TURNED
OR
DOWN
or the installation instructions for specific details on termi­nation construction.
For details concerning connection of pipes to the furnace, refer to the Vent/Flue Pipe and Combustion Pipe - Stan-
or
dard Furnace Connections or Alternate Furnace Connec­tions section in this manual or the installation instructions.
Vent/Flue and Combustion Air Pipe Lengths (Direct Vent) and Diameters (90% Furnaces Only)
Refer to the following tables for applicable length, elbows, and pipe diameter for construction of the vent/flue and com­bustion air intake pipe systems of a direct vent (dual pipe) installation. The number of elbows tabulated represents the number of elbows and/or tees in each (Vent/Flue & Com­bustion Air Intake) pipe. Elbows and/or tees used in the terminations must be included when determining the num­ber of elbows in the piping systems.
If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objectionable, insulation of the combustion air pipe may be required. Use 1/2" thick closed cell foam insulation such as "Armaflex" or "Insultube" where required.
AMS9, ACS9, DMS9, DCS9, GCH9, GMS9, GCS9
12" MINIMUM ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
90% Furnace Horizontal Termination (Single Pipe)
Above Highest Anticipated Snow Level
In a basement installation, the vent/flue pipe can be run be­tween joist spaces. If the vent pipe must go below a joist and then up into the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows.
Direct Vent (Dual Pipe) Piping (90% Furnaces Only)
Direct vent installations require both a combustion air in­take and a vent/flue pipe. The pipes may be run horizontally and exit through the side of the building or run vertically and exit through the roof of the building. The pipes may be run through an existing unused chimney; however, they must extend a minimum of 12 inches above the top of the chim­ney. The space between the pipes and the chimney must be closed with a weather tight, corrosion resistant flashing. Both the combustion air intake and a vent/flue pipe termina­tions must be in the same atmospheric pressure zone. Re­fer to Vent/Flue and Combustion Air Pipe - Termination Lo- cations or Concentric Vent Termination section in this manual
Max imum Allowable Length of Vent/Flue & Combustion
Unit Input
(Btu)
45,000
70,000
90,000
115,000
115,000
1) One 90° elbow should be secured to the combustion air intake connection.
2) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
3) Tee used in the vent/flue termination must be included when deter­mining the number of elbows in the piping system.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
Direct Vent (Dual Pipe)
Air Intake Pipe (ft)
Vent/Flue/Air
Int ake
Termination
Standard Alt ernate 2 55 52 49 46 43 40 37 Standard Alt ernate 2 55 52 49 46 43 40 37 Standard Alt ernate 2 42 39 36 33 30 27 24 Standard 2 262320 Alternate 2 7 10 Standard Alt ernate 3 74 70 66 62 58 54 50
Pipe Size
(in.)2345678
Number of Elbows
(4)
2 68656259565350
2 68656259565350
2 55524946434037
Not Recommended
3 88878076726864
(1)(2)(3)(5)
Not Recommended
Vent/Flue and Combustion Air Pipe Lengths and Diam­eters (95% Furnaces Only)
Refer to the following table for applicable length, elbows, and pipe diameter for construction of the vent/flue and com­bustion air intake pipe systems of a direct vent (dual pipe) installation. The number of elbows tabulated represents the number of elbows and/or tees in each (Vent/Flue & Com­bustion Air Intake) pipe. Elbows and/or tees used in the terminations must be included when determining the num­ber of elbows in the piping systems.
47
Page 48
PRODUCT DESIGN
If the combustion air intake pipe is to be installed above a finished ceiling or other area where dripping of condensate will be objectionable, insulation of the combustion air pipe may be required. Use 1/2” thick closed cell foam insulation such as Armaflex or Insultube where required.
AMH9, GMH9, AMS95, GMS95
Maximum Allow able Length of Vent/Flue & Combustion
Vent/Flue/Air Intake
Unit Input
(Btu)
045_3
070_3
070_4
090_4
090_5
115_5
Termination
Standard Alternate 2 55 52 49 46 43 40 37 Standard Alternate 2 55 52 49 46 43 40 37 Standard Alternate 2 33 30 27 Standard Alternate 3 55 52 49 46 43 40 37 Standard Alternate 3 55 52 49 46 43 40 37 Standard Alternate 3 55 52 49 46 43 40 37
1) Minimum requirement for each vent pipe is five (5) feet in length and one elbow/tee.
2) Tees and/or elbows used in the vent/flue termination must be in­cluded when determining the number of elbows in the piping sys-
tem.
3) 3” diameter pipe can be used in place of 2” diameter pipe.
4) Increased Clearance Configurations using (2) 45 deg. Long Sweep elbows should be considered equivalent to one 90 deg. elbow.
Maximum Allowable Length of Vent/Flue & Combustion
Unit Input
(Btu)
Vent/Flue/Air Intake
Termination
045_3
070_3
070_4
090_4
090_5
115_5
Direct Ve nt (Dual Pipe)
Air Intake Pipe (f t)
Pip e
(4)
Size
(in.)
2 68656259565350
2 68656259565350
24643
3 68656259565350
3 68656259565350
3 68656259565350
Number of Elbow s
2345678
40
(1)(2 )(3)(5 )
Not Rec ommende d
GKS9
Direct Vent (Dual Pipe)
Air Intake Pipe (ft)
Pipe
Size
(in.)
Number of Elbows
(4)
2345678
(1)(2)(3)(5)
Standard 2 68656259565350 Alternate 2 55 52 49 46 43 40 37 Standard 2 36333027242118 Alternate 2 23 20 17 14 11 8 5 Standard 3 68656259565350 Alternate 3 55 52 49 46 43 40 37 Standard 2 55524946434037 Alternate 2 42 39 36 33 30 27 24 Standard 2 37343128252219 Alternate 2 24 21 18 15 12 9 6 Standard 3 68656259565350 Alternate 3 55 52 49 46 43 40 37 Standard 2 39363330272421 Alternate 2 26 23 20 17 14 11 8 Standard 3 68656259565350 Alternate 3 55 52 49 46 43 40 37 Standard 3 68656259565350 Alternate 3 55 52 49 46 43 40 37
1) Elbows and/or tees used in terminations must be included when determining quantity of allowable elbows in the system.
2) Number of elbows tabulated are for each (Vent/Flue & Combustion Air Intake) pipe.
3) Minimum requirements for each Vent/Flue & Combustion Air Intake pipe is five (5) feet in length and one elbow/tee.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
ACV9, AMV9, GCV9, GMV9, GMV95
UPFLOW
Direct Vent (Dual Pipe)
of Vent/Flue & Combustion Air Intake Pipe (ft)
Unit Input
(Btu)
45,000
Termination
Style
Standard 2 71 68 65 62 59 56 53 50 Alternate 2 58 55 52 49 46 43 40 37
Standard
70,000
Alternate
90,000
115,000
Standard 3 71 68 65 62 59 56 53 50 Alternate 3 57 54 51 48 45 42 39 36 Standard 3 49 46 43 40 37 34 31 28 Alternate 3 35 32 29 26 23 20 17 14
Pi p e (inch)
Maximum Allow able Length
(4)
Number of Elbow s
(1)(2)(3 )(5)
12345678
2 4946434037343128 3 7168656259565350 2 3633302724211815 3 5754514845423936
COUNTERFLOW
Direct Vent (Dual Pipe)
of Vent/Flue & Combustion Air Intake Pipe (ft)
Unit Input
(Btu)
Termination
Style
Pi p e (inch)
Standard
70,000
Alternate
Standard
90,000
Alternate
1) Elbows and/or tees used in terminations must be included when determining quantity of allowable elbows in the system.
2) Number of elbows tabulated are for each (Vent/Flue & Combustion Air Intake) pipe.
3) Minimum requirements for each Vent/Flue & Combustion Air Intake pipe is five (5) feet in length and one elbow/tee.
4) 3” diameter pipe can be used in place of 2” diameter pipe.
5) Increased Clearance Configurations using (2) 45 deg. Long Sweep
elbows should be considered equivalent to one 90 deg. elbow.
Maximum Allow able Length
(4)
Number of Elbow s
(1)(2)(3 )(5)
12345678 2 4946434037343128 3 7168656259565350 2 3633302724211815 3 5754514845423936 2 6158555249464340 3 7168656259565350 2 4845423936333027 3 5754514845423936
Vent/Flue and Combustion Air Pipe Terminations
VENT/FLUE AND COMBUSTION AIR PIPE TERMINATIONS
The vent/flue and combustion air pipes may terminate verti­cally, as through a roof, or horizontally, as through an out­side wall.
48
Page 49
PRODUCT DESIGN
12" MIN
Vertical pipe terminations should be as shown in the follow­ing figure. Refer to Section IX, Vent/Flue Pipe and Com- bustion Pipe - Termination Locations for details concerning location restrictions. The penetrations through the roof must be sealed tight with proper flashing such as is used with a plastic plumbing vent.
TEE
VENT/FLUE
12" MINIMUM
COMBUSTION
AIR INTAKE
90º
MEDIUM RADIUS
ELBOWS
24" MAX
AIR INTAKE
90° MEDIUM RADIUS ELBOW
24" MAX
3" MIN
12" MINIMUM TO ROOF OR
HIGHEST ANTICIPATED SNOW LEVEL
SCREEN
24" MAXI MUM 3" MINI MUM
90% Furnace Vertical Terminations (Dual Pipe)
Horizontal terminations should be as shown in the following figure. Refer to Vent/Flue Pipe and Combustion Pipe - Ter- mination Location section in this manual or the installation instructions for location restrictions. A 2 3/8" diameter wall penetration is required for 2" diameter pipe while a 3 1/2" diameter hole is required for 3" diameter pipe. To secure the pipe passing through the wall and prohibit damage to piping connections, a coupling should be installed on either side of the wall and solvent cemented to a pipe connecting the two couplings. The pipe length should be the wall thickness plus the depth of the socket fittings to be installed on the inside and outside of the wall. The wall penetration should be sealed with silicone caulking material.
90% Alternate Horizontal Vent Termination (Dual Pipe)
12" MIN.
VENT/FLUE
TEE
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
SUPPORT
STRAPS
COMBUSTION AIR INTAKE.
SCREEN
90° MEDIUM RADIUS ELBOWS
3" MIN.
24" MAX.
12" MIN. ABOVE
HIGHEST ANTICIPATED
SNOW LEVEL
90% Furnace Standard Horizontal Terminations
Above Anticipated Snow Level
(Dual Pipe)
3" MIN
24" MAX
3" MIN
24" MAX
90% Standard Horizontal Terminations (Dual Pipe)
12" MIN
90% Furnace Alternate Vent Termination
Above Anticipated Snow Level
(Dual Pipe)
In a basement installation, the pipes may be run between the joist spaces. If the pipes must go below the joist and then up into the last joist space to penetrate the header, two 45° elbows should be used to reach the header rather than two 90° elbows.
49
Page 50
PRODUCT DESIGN
V
VENT/INTAKE T ERMINATIONS F OR I NSTALLATION OF M UL-
TIPLE D IRECT V ENT F URNACES
If more than one direct vent furnace is to be installed verti­cally through a common roof top, maintain the same mini­mum clearances between the exhaust vent and air intake terminations of adjacent units as with the exhaust vent and air intake terminations of a single unit.
If more than one direct vent furnace is to be installed hori­zontally through a common side wall, maintain the clear­ances as in the following figure. Always terminate all ex­haust vent outlets at the same elevation and always termi­nate all air intakes at the same elevation.
90° Medium Radius Elbows
ents
2. The vent termination must be located at least 12” above ground or normally expected snow accumulation levels.
3. Do NOT terminate over public walkways. Avoid areas where condensate may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
4. The vent termination shall be located at least 4’ horizontally from any electric meter, gas meter, regulator and any relief equipment. These distances apply ONLY to U.S. Installations.
5. The vent termination shall be located at least 3’ above any forced air inlet located within 10’; and at least 10’ from a combustion air intake of another appliance, except another direct vent furnace intake.
3" Min.
24" Max.
3" Min.
24" Max.
24" Max.
3" Min.
Screen
90% Furance Horizontal Venting of Multiple Units
(Dual Pipe)
Concentric Vent Kits (DCVK) Application
The DCVK-20 and DCVK-30 kit is designed to allow the terminations of a direct vent furnace to be “concentrically” vented through a wall or roof. This kit allows a single pen­etration to support terminations for both the vent/flue pipe and the combustion air intake pipe.
(DCVK) Vent Termination Clearances
1. Determine termination locations based on clearances specified in furnace installation instructions, and following steps as shown in Figures 1,3,6,7,8 and 9.
6. In Canada, the Canadian Fuel Gas Code takes precedence over the preceding termination instructions.
3" or 4" Diameter SDR-26 Pipe
2" or 3" Diameter
Y Concentric Fitting
2 or 2 1/2" Diameter SDR-26 Pipe
2" or 3" Diameter Rain Cap
FIGURE 2
These kits are for vertical or horizontal termination of the combustion air inlet and the exhaust vent pipes on Category IV gas-fired condensing furnaces. The DCVK-30 kit can be used for 3” diameter pipe systems. The DCVK-20 kit can be used for the 2” diameter pipe system. Refer to Table 2 for the correct pipe size for the furnace. Both the combustion air inlet and the exhaust vent pipes must attach to the termination kit. The termination kit must terminate outside the structure and must be installed per the instructions outlined below for vertical or horizontal termination. Vertical termination is preferred. Field supplied pipe and fittings are required to complete the installation.
9"
12"
Direct Vent
Terminal
50,000 Btuh
or less
12"
FIGURE 1
50
3'
G
12"
Forced Air Inlet
Direct Vent Terminal
More than 50,000 Btuh
1. Determine the pipe diameters required for installation from Table 1. Do not include the field supplied 45° el­bow in the total elbow count. If more than four elbows are required, reduce the length of both the inlet and the exhaust pipes five feet for each additional elbow used.
E
D
A
R
Elbows are DWV long radius type for 2" and 3" vents.
NOTE: Feet of pipe is whichever pipe run is the longest, either the inlet or outlet side.
Page 51
PRODUCT DESIGN
DCVK KITS
MAXIM UM ALLOWABLE LENGTH OF VENT
GA S INP UT RA TE
(KBtu/hr)
45
70
90 3" DCVK-30 54 51 48 45 42 39
115
MAXIM UM ALLOWABLE LENGTH OF VENT
GA S INP UT RA TE
(KBtu/hr)
45
70
70
90 3" DCVK-30 54 51 48 45 42 39
115
2. Determine the best location for the termination kit. See Figure 3 for vertical termination or Figure 6 and Figure 7 for horizontal termination. Roof termination is preferred since it is less susceptible to damage, has reduced intake contaminants and less visible vent vapors. For side termination, consideration should be given to:
a. Possible damage from the vapors to plants/shurbs,
other equipment and building materials
b. Possible damage to the terminal from foreign ob-
jects
c. Wind effects that may cause recirculation of flue
products, debris or light snow
d. Visible vent vapors.
SINGLE STAGE FURNACE
AND COMBUSTION AIR PIPE FEET
PIPE
DIAMETER
TWO-STAGE FURNACE
AND COMBUSTION AIR PIPE FEET
DIAMETER
KIT NUM B ER
2" DCVK-20 55 52 49 46 43 40
2" DCVK-20 55' 50' 45' 40' NA NA
3" DCVK-30 55' 50' 45' 40' NA NA
PIPE
KIT NUM B ER
2" DCVK-20 55 52 49 46 43 40
2" DCVK-20 33 30 27 24 21 18
3" DCVK-30 54 51 48 45 42 39
3" DCVK-30 32 29 26 23 20 17
234567
234567
TABLE 1
Number of Elbows
Number of Elbows
WARNING
DO NOT OPERATE THE FURNACE WITH THE RAIN CAP REMOVED AS
RECIRUCLATION OF THE FLUE GASES MAY OCCUR.
COLLECT INSIDE THE LARGER COMBUSTIN AIR PIPE AND FLOW TO THE
BURNER ENCLOSURE.
PROPERTY DAMAGE, EQUIPMENT DAMAGE, PERSONAL INJURY OR DEATH.
F
AILURE TO FOLLOW THIS WARNING CAN RESULT IN
WATER MAY ALSO
6. Install the Y concentric fitting and the pipe assembly through the structure’s opening. For vertical termina­tion, install the parts through the field supplied roof boot/ flashing. NOTE: Do not allow insulation or other mate­rials to accumulate inside the pipe assembly when in­stalling through the structure’s opening.
7. Secure the assembly to the structure as shown in Fig­ure 3 or Figure 7 using field supplied metal strapping or equivalent material.
NOTE:
Ensure that the strap is installed to prevent movement of termination kit in side wall.
Ensure the termination height is above the roof surface or anticipated snow level as shown in Figure 3 for vertical termination.
Ensure the termination location clearance dimensions are as shown in Figure 6 and Figure 7 for horizontal terminiation.
Roof Overhang
1" max.
12" min.
Vent
Maintain 12" (18" for Canada) minimum clearance above highest anticipated snow level. Maximum of
Combustion Air
Roof Boot/Flashing (Field Supplied)
Vent
24" above roof.
Support (Field Supplied)
FIGURE 3
45 Elbow (Field Supplied)
Combustion Air
b
m
o
C
r
i
A
n
o
i
t
s
u
Vent
Maintain 12" clearance above highest anticipated snow level or grade, whichever is greater.
FIGURE 6
51
Page 52
PRODUCT DESIGN
Vent
Combustion Air
Strap (Field Supplied)
45 Elbow (Field Supplied)
Combustion Air
Flush to
1" maximum
Vent
FIGURE 7
8. Install the rain cap and the small diameter pipe assem­bly in the Y concentric fitting and the large pipe assem­bly. Ensure that the small diameter pipe is bottomed out and securely cemented in the Y concentric fitting.
9. Cement the furnace combustion air and vent pipes to the concentric vent termination assembly. See Figure 3 or Figure 7 for proper pipe attachment.
10. Operate the furnace through one heat cycle to ensure combustion air and vent pipes are properly connected to the concentric termination connections.
MULTI-VENT TERMINATION CLEARANCES
When two (2) or more furnaces are vented near each other, each furnace must be individually vented.
Two (2) vent terminations may be installed as shown in Fig­ure 8 and Figure 9, but the next vent termination must be at least 36” away from first 2 terminations. It is important that vent terminations be made as shown to avoid recirculation of flue gases.
1" Maximum (TYP.)
r
i
A
n
t
o
i
s
u
b
m
Co
Vent
"A"
Vent
Exhaust
Dimension "A" is touching or 2" maximum separation.
FIGURE 9
Concentric Sidewall Vent Kit (0170K00000S)
This (sidewall only) vent kit is to be used with 2” or 3” vent systems. The vent kit must terminate outside the structure and may be installed with the intake and exhaust pipes located side-by side or with one pipe above the other. This kit is NOT intended for use with single pipe (non-direct vent) installations.
"A"
st
u
a
h
x
E
12" Min. Grade (18" for Canada) or Snow Level
Combustion Air
Dimension "A" is touching or 2" maximum separation.
FIGURE 8
52
1. Determine the best location for the vent terminal. In addition to all applicable codes, consider the follow­ing when determining the location:
a. The vent terminal should be located so as to mini-
mize the total length and number of elbows in the piping. Consult the furnace installation instructions for the pipe lengths and number of elbows allowed.
b. Terminal should be positioned where vent vapors will
not damage plants, shrubs, air conditioning equip­ment or building materials.
c. Terminal should be located where it will not be af-
fected by wind gusts, snow, airborne leaves or other debris, and where it will not allow recirculation of flue gases.
Page 53
PRODUCT DESIGN
d. Terminal should be located where it will not be dam-
aged or exposed to foreign objects such as stones, balls, etc.
e. Terminal should be located where vent vapors are not
objectionable.
2. Using the vent terminal base as a template, locate the pipe holes and the four mounting screw holes on the wall.
3. Cut two 3 7/8” diameter holes for the vent and intake pipes.
4. Drill four 3/16” diameter holes for inserting the plastic screw anchors into the wall.
Vent
Base
Minimum 12"
to overhang
Combustion
Air
2" Screws x4
Vent Cap
Vent
Minimum 12" clearance
above highest snow
level or grade
1" Screws x4
Field-Supplied
Reducing Couplings,
if required
2" or 3" Pipe
Seal all holes through
wall with sealant
3" Pipe
Condensate Drain Lines and Drain Trap (90% Furnaces Only)
A condensing gas furnace achieves its high level of effi­ciency by extracting almost all of the heat from the prod­ucts of combustion and cooling them to the point where condensation takes place. The condensate which is gener­ated must be piped to an appropriate drain location.
In upright installations, the furnace’s drain hoses may exit either the right or left side of the furnace. NOTE: If the alter­nate vent/flue outlet is utilized in an upright installation, the drain trap and drain connections must be located on the same side as the alternate vent/flue outlet.
In horizontal installations, the drain hoses will exit through the bottom (down side) of the unit with the drain trap sus­pended beneath the furnace. The field-supplied drain sys­tem must be in accordance with all local codes and the instructions in the following sections.
5. Insert the four plastic screw anchors into the screw holes and mount the vent terminal base to the wall us­ing the four 2” long screws provided.
6. Assemble the vent terminal cap to the vent terminal base, using four 1” long screws provided.
7. Install 3” diameter vent and air intake pipes into the back side of the openings in the vent terminal base.
8. Seal all gaps between the pipes and wall.
9. Using RTV silicone sealant, seal the vent pipe to the vent cap. This will allow the terminal to be disas­sembled later if necessary for cleaning. DO NOT use PVC solvent cement to seal this connection.
NOTE: To downsize the piping to 2” diameter, use a field­supplied reducing coupling.
10. Operate the furnace for 15 minutes to ensure that it is working properly and that all piping joints are sealed to prevent the escape of combustion products into the home.
11. For installations where two or more furnaces are to be vented using this kit, ensure a minimum clearance of 1” between the vent terminal caps. To prevent conden­sate freezing problems, do not install multiple vent kits above one another.
WARNING
N UPRIGHT UPFLOW INS TALLATIONS, THE DRAIN T RAP MUST BE MOUNTED ON
I
THE OPPOSITE S IDE OF THE UNIT FROM THE JUNCTION BOX.
REDUCE THE RISK OF WATER REACHING THE JUNC TION BOX IN THE EVENT OF
A BLOCKED DRAIN CONDITION.
CAN RESULT IN POSSIBLE PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH
DUE TO ELE CTRI CAL SH OCK.
AILURE TO FOLLOW THESE INSTRUCTIONS
F
HIS WILL
T
Follow the bullets listed below when installing the drain sys­tem. Refer to the following sections for specific details con­cerning furnace drain trap installation and drain hose hook ups.
The drain trap supplied with the furnace must be used.
The drain line between furnace and drain location must be constructed of 3/4" PVC or CPVC.
The drain line between furnace and drain location must maintain a 1/4" per foot downward slope toward the drain.
Do not trap the drain line in any other location than at the drain trap supplied with the furnace.
Do not route the drain line outside where it may freeze.
53
Page 54
PRODUCT DESIGN
If the drain line is routed through an area which may see temperatures near or below freezing, precau­tions must be taken to prevent condensate from freezing within the drain line.
If an air conditioning coil is installed with the furnace, a common drain may be used. An open tee must be installed in the drain line, near the cooling coil, to relieve positive air pressure from the coil’s plenum. This is necessary to prohibit any interference with the function of the furnace’s drain trap.
UPRIGHT INSTALLATIONS
In an upright installation drain hoses are connected to drain ports on the rubber elbow and the recouperator coil front cover. The drain lines are then routed through the right or left side panel and into the drain trap secured to the outside of the cabinet.
NOTE: Refer to Condensate Drain Lines and Drain Trap - Alternate Vent/Flue Hose Connections section in this manual
or the installation instructions for upright installations using an alternate vent/flue outlet.
Standard Right or Left Side Drain Hose Connections
Upright installations using the standard vent/flue outlet re­quire drain hoses to be connected as shown in the following figures.
NOTE: For left side drainage, grommets will have to be relo­cated to left side panel.
RIGHT SIDE
PANEL
RUBBER
ELBOW
RUBBER ELBOW
DRAIN PORT
RED HOSE CLAMP
TUBE 1
HOSE
SIDE PANEL
B
GROMMET
HOLES
TUBE(S) 2
FRONT COVER
DRAIN PORT
RED HOSE
CLAMP
HOSE
A
GREEN
HOSE
CLAMPS
(3 PLACES)
90% Furnace Upright “Standard”
Drain Hose Connections (Right Side)
DRAIN TRAP
LEFT
SIDE PANEL
FRONT COVER
DRAIN PORT
RED HOSE
CLAMP
HOSE A
SIDE PANEL
GROMMET
HOLES
TUBE(S) 2
DRAIN
TRAP
HOSE B
RUBBER
ELBOW
RUBBER
ELBOW
DRAIN PORT
RED HOSE
CLAMP
TUBE 1
GREEN HOSE
CLAMPS
(3 PLACES)
90% Furnace Upright “Standard”
Drain Hose Connections (Left Side)
NOTE: Ensure hoses and tubes maintain a downward slope
for proper drainage and that they are not kinked or binding.
Alternate Vent/Flue Drain Hose Connections
Upright installations using the alternate vent/flue outlet will require "right-side only" drain hoses to be connected as shown in the following figure. Refer to Vent/Flue Pipe and Combustion Air Pipe section in this manual or the installa­tion instructions for details on alternate vent/flue pipe con­nection.
RUBBER ELBOW
(EXTERNALLY
MOUNTED)
RUBBER
ELBOW
DRAIN PORT
FRONT COVER
DRAIN PORT
TUBE 1
HOSE B
HOSE A
TUBE(S) 2
HOSE
CLAMPS
(5 PLACES)
SIDE PANEL
GROMMET
HOLES
DRAIN TRAP
90% Furnace Upright “Alternate”
Drain Hose Connections (Right Side Only)
NOTE: Ensure hoses and tubes maintain a downward slope
for proper drainage and are not kinked or binding. For details concerning mounting of the drain trap, refer to
the following section.
54
Upright Drain Trap Mounting (Left or Right Side Panel)
1. Insert drain tubes into drain trap and position the drain trap against the side panel. NOTE: Drain tubes must reach the bottom of the drain trap.
2. Secure drain trap to side panel at the mounting holes located below the grommet drain holes.
Page 55
PRODUCT DESIGN
3. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
NOTE: Ensure hoses and tubes maintain a downward slope for proper drainage and that they are not kinked or binding.
Horizontal Installations RIGHT SIDE DOWN
Horizontal installations with the right side down require that the drain hoses be connected to the right side front cover drain port and the rubber elbow drain port.
FRONT COVER DRAIN PORT
RED HOSE
HOSE A
HOSE B
SIDE PANEL
GROMMET
HOLES
DRAIN TRAP
NOTE: Ensure hoses and tubes maintain a downward slope for proper drainage and are not kinked or bound.
For details concerning mounting of the drain trap, refer to
Condensate Drain Lines and Drain Trap - Horizontal Drain Trap Mounting section in this manual or the installation in-
structions.
LEFT SIDE DOWN
Horizontal installations with the left side panel down will require drain hoses to be connected to the left side front cover drain port and the induced draft blower drain port.
NOTE: Relocation of the front cover pressure switch hose is required from the right side (as shipped) pressure tap to the left (down) side tap. The pressure switch hose must be connected to the down side to guard against blocked drain conditions. The hose must be cut to appropriate length to minimize sagging.
CLAMP
FRONT COVER
TUBES 2
GREEN
HOSE
CLAMP
(3 PLACES)
PRESSURE
TAP
TUBE 1
RUBBER
ELBOW
RUBBER ELBOW
DRAIN PORT
RED HOSE
CLAMP
90% Furnace Horizontal
Drain Hose Connections (Right Side Down)
RIGHT
SIDE
PANEL
INDUCED
DRAFT BLOWER
DRAIN PORT
HOSE B
LEFT SIDE
PANEL
FRONT
COVER
PRESSURE
TAP
FRONT COVER
DRAIN PORT
RED HOSE CLAMP
SIDE PANEL
GROMMET
HOLES
HOSE A
GREEN HOSE
CLAMPS
(3 PLACES)
TUBE(S) 2
DRAIN TRAP
90% Furnace Horizontal
Drain Hose Connections (Left Side Down)
NOTE: Ensure hoses and tubes maintain a downward slope
for proper drainage and that they are not kinked or binding. For details concerning mounting of the drain trap, refer to
Condensate Drain Lines and Drain Trap - Horizontal Drain Trap Mounting in this manual or the installation instructions.
Horizontal Drain Trap Mounting (Left or Right Side Panel)
1. Position the drain trap against side panel with drain tubes inserted into trap. Note that the trap may be orientated with the outlet facing either the furnace’s top cover or base pan.
2. Secure drain trap to side panel at the dimples or crosshairs located on either side of the grommet drain holes.
3. Confirm that tubes reach bottom of drain trap and that all hoses maintain a downward slope and are not kinked or binding.
4. Attach PVC drain line to drain trap outlet with either a 90° elbow or coupling.
GAS SUPPLY AND PIPING
The furnace rating plate includes the approved furnace gas input rating and gas types. The furnace must be equipped to operate on the type of gas applied. This includes any conversion kits required for alternate fuels and/or high alti­tude.
55
Page 56
PRODUCT DESIGN
p
CAUTION
PROPANE GAS CONVERSION
O PREVENT UNRELI ABLE OPERATION OR EQUIP MENT DAMAGE, THE INLET
T
GAS SUPPLY PRESSURE MUST BE AS SPECIFIED ON THE UNIT RATING PLATE
WITH ALL OTHE R HOUSEHOLD GAS FIRED APPLIANCES OPERATING.
Inlet gas supply pressures must be maintained within the ranges specified below. The supply pressure must be con­stant and available with all other household gas fired appli­ances operating. The minimum gas supply pressure must be maintained to prevent unreliable ignition. The maximum must not be exceeded to prevent unit overfiring.
Inlet Gas Supply Pressure
Natural Gas
Pro
ane Gas
Minimum: 5.0" W.C. Maximum :10.0" W.C.
Minimum:11.0" W.C. Maximum :13.0" W.C.
HIGH ALTITUDE DERATE
When this furnace is installed at high altitude, the appropri­ate High Altitude orifice kit must be applied. This is required due to the natural reduction in the density of both the gas fuel and combustion air as altitude increases. The kit will provide the proper design certified input rate within the speci­fied altitude range.
High altitude kits are purchased according to the installa­tion altitude and usage of either natural or propane gas. Refer to the product Specification Sheet or Technical Manual for a tabular listing of appropriate altitude ranges and corre­sponding manufacturer’s high altitude (Natural, Propane gas, and/or Pressure Switch) kits.
Do not derate the furnace by adjusting the manifold pres­sure to a lower pressure than specified on the furnace rating plate. The combination of the lower air density and a lower manifold pressure will prohibit the burner orifice from draw­ing the proper amount of air into the burner. This may cause incomplete combustion, flashback, and possible yellow tip­ping.
In some areas the gas supplier may artificially derate the gas in an effort to compensate for the effects of altitude. If the gas is artificially derated, the appropriate orifice size must be determined based upon the BTU/ft3 content of the derated gas and the altitude. Refer to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and information provided by the gas supplier to determine the proper orifice size.
A different pressure switch may be required at high altitude regardless of the BTU/ft3 content of the fuel used. Refer to the product Specification Sheet or Technical Manual for a tabular listing of appropriate altitude ranges and correspond­ing manufacturer’s pressure switch kits.
WARNING
P
OSSIBLE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH MAY OCCUR IF
THE CORRECT CONVERSION KITS ARE NOT INSTALLED.
MUST BE APPLIED TO I NSURE SAFE AND PROPER FURNACE OPERATION.
CONVERSIONS MUST BE PERFORMED BY A QUALIFIED INSTALLER OR SERVICE
AGENCY.
HE APPROPRIATE KITS
T
A
LL
This unit is configured for natural gas. The appropriate manufacturer’s propane gas conversion kit, must be applied for propane gas installations. The single-stage 80% and 90% furnaces use LPT-00A LP Conversion Kit. The two-stage 80% and 90% furnace models using a White-Rodgers 36E54 two-stage valve require an LPM-03B LP conversion kit. Two­stage 80% and 90% furnace models using a White-Rodgers 36G54 two-stage valve require an LPM-05 LP conversion kit. Refer to the specification sheet for the model you are servicing. Refer to the “propane gas and/or High Altitude Installations” section for details.
GAS VALVE
This unit is equipped with a 24 volt gas valve controlled dur­ing furnace operation by the integrated control module. As shipped, the valve is configured for natural gas. The valve is field convertible for use with propane gas by using the ap­propriate propane gas conversion kit. Taps for measuring the gas supply pressure and manifold pressure are provided on the valve. The gas supply pressure on White-Rodger
"G" model gas valve, used on single stage furnaces, can be checked with a gas pressure test kit (Part #0151K00000S) available through our authorized dis­tributors.
The gas valve has a manual ON/OFF control located on the valve itself. This control may be set only to the “ON” or “OFF” position. Refer to the Lighting Instructions Label or the “Put- ting the Furnace Into Operation” section of this manual or the installation instructions for use of this control during start up and shut down periods.
GAS PIPING CONNECTIONS
CAUTION
T
O AVOID POSSI BLE UNSATISFACTORY OPERATION OR EQUIPMENT DAMAGE
DUE TO UNDERFIRING OF EQUIPMENT, USE THE PROPER SIZ E OF
NATURAL/PROPANE GAS PIPING NEEDED WHEN RUNNING PIPE FROM THE
METER/TANK TO THE FURN ACE.
56
Page 57
PRODUCT DESIGN
When sizing a trunk line, be sure to include all appliances which will operate simultaneously when sizing a trunk line.
The gas piping supplying the furnace must be properly sized based on the gas flow required, specific gravity of the gas, and length of the run. The gas line installation must comply with local codes, or in their absence, with the latest edition of the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
Natural Gas Capacity of Pipe
In Cubic Feet of Gas Per Hour (CFH)
Length of Nominal Black Pipe Size
Pipe in Feet 1/2" 3/4" 1" 1 1/4" 1 1/2"
10 132 278 520 1050 1600 20 92 190 350 730 1100 30 73 152 285 590 980 40 63 130 245 500 760 50 56 115 215 440 670 60 50 105 195 400 610 70 46 96 180 370 560 80 43 90 170 350 530 90 40 84 160 320 490
100 38 79 150 305 460
(Pressure 0.5 psig or less and pressure drop of 0.3" W.C.; Based on 0.60 Specific Gravity Gas)
CFH =
BTUH Furnace Input Heating Value of Gas (BTU/Cubic Foot)
9. Connect the furnace to the building piping by one of the following methods:
– Rigid metallic pipe and fittings. – Semi-rigid metallic tubing and metallic fittings. Alu
minum alloy tubing must not be used in exterior locations. In order to seal the grommet cabinet penetration, rigid pipe must be used to reach the outside of the cabinet. A semi-rigid connector to the gas piping may be used from there.
10. Use listed gas appliance connectors in accordance with
their instructions. Connectors must be fully in the same room as the furnace.
11. Protect connectors and semi-rigid tubing against physi-
cal and thermal damage when installed. Ensure alumi­num-alloy tubing and connectors are coated to protect against external corrosion when in contact with masonry, plaster, or insulation, or subjected to repeated wetting by liquids such as water (except rain water), detergents, or sewage.
CAUTION
To connect the furnace to the building’s gas piping, the installer must supply a ground joint union, drip leg, manual shutoff valve, and line and fittings to connect to gas valve. In some cases, the installer may also need to supply a transition piece from 1/2" pipe to a larger pipe size.
The following stipulations apply when connecting gas pip­ing. Refer to the following figures for typical gas line con­nections to the furnace.
1. Use black iron or steel pipe and fittings for the build­ing piping.
2. Use pipe joint compound on male threads only. Pipe joint compound must be resistant to the action of the fuel used.
3. Use ground joint unions.
4. Install a drip leg to trap dirt and moisture before it can enter the gas valve. The drip leg must be a minimum of three inches long.
5. Install a 1/8" NPT pipe plug fitting, accessible for test gage connection, immediately upstream of the gas supply connection to the furnace.
6. Use two pipe wrenches when making connection to the gas valve to keep it from turning. The orientation of the gas valve on the manifold must be maintained as shipped from the factory.
7. Install a manual shutoff valve between the gas meter and unit within six feet of the unit. If a union is in­stalled, the union must be downstream of the manual shutoff valve, between the shutoff valve and the fur­nace.
8. Tighten all joints securely.
DGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES A PRECAUTION
E
WHEN REMOVING HOLE PLUGS.
DIRECT/STANDARD INLET PIPING
When gas piping enters directly to the gas valve through the standard inlet hole (upflow through the right side panel), the
installer must supply straight pipe with a ground joint union to reach the exterior of the furnace. NOTE: The rigid pipe must be long enough to reach the outside of the cabinet to seal the grommet cabinet penetration on 90% furnaces. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
INDIRECT/ALTERNATE INLET PIPING
When gas piping enters indirectly to the gas valve through the alternate gas inlet hole the installer must supply the following fittings (starting from the gas valve) to reach the outside of the cabinet (NOTE: On the 90% furnaces the in­staller must swap the alternate inlet hole plug with the stan­dard inlet grommet in order to seal the cabinet):
Coupling.
90 degree elbow.
2 inch close nipple.
90 degree elbow.
Straight pipe, with a ground joint union, to reach the exterior of the furnace. NOTE: The rigid pipe must be long enough to reach the outside of the cabinet so as to seal the grommet cabinet penetration on the 90% furnaces. A semi-rigid connector to the gas piping can be used outside the cabinet per local codes.
57
Page 58
PRODUCT DESIGN
A
A
GAS VALVE
BURN ERS
LTERNATE GAS LINE
LOCAT ION
MANI FOLD
MANUAL
SHUT O FF VALVE
(UPSTREA M FROM
GROUND JOINT
PIPE UNION)
MANUAL
SHUT OFF VALVE
(UPS TREAM F ROM
GROUND JOINT
PIPE UNION)
ALTERNATE
GAS LINE
LOCA TION
PLUG IN
LTERNATE
GAS LINE
HOLE
GROUND JOINT
PIPE UNION
HEIGHT REQUIRED
BY LOCAL CO DE
GROMMET
IN STANDARD
GAS LINE HOLE
DRIP LEG
UPFLOW
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION)
GROUND JOINT
PIPE UNION
DRIP LEG
GAS VALVE
BURNERS
GROMMET IN STANDARD
GAS LINE HOLE
HEIGHT REQUIRED
BY LOCA L CODE
GROMMET
IN STAND ARD
GAS LINE HOLE
DRIP LEG
BURNERS
GROUND JOINT
PIPE UNION
GAS VALV E
**
*
*
GROUND J OINT
PIPE UNIO N
COUNTERFLOW
MANUAL SHUT-OFF VALVE
(UPSTREAM FROM GROUND
JOINT PIPE UNION )
DRIP LEG
GROMMET I N STANDARD
GAS LINE HOLE
PLUG IN
ALTERNATE
GAS LINE
HOLE
GAS VALVE
MANIFO LD
BURNERS
PLUG IN ALTERNATE
GAS LINE HOLE
ALTERNATE GAS
LINE LOC ATION
MANIFOLD
HORIZONTAL [UPFLOW MODEL]
NOTES: 1. WHEN GAS LINE IS IN THE ALTERNATE
58
LOCATION, SWAP THE POSITION OF THE PLUG AND GROMMET
(90% Furnace Shown, 80% Furnace Similiar)
DRAIN TRAP
.
Gas Piping Connections
ALTERNATE
GAS LI NE LOCATI ON
MANIFOLD
HORIZONTAL[COUNTERFLOW]
2. DRIP LEG MAY TERMINATE WITH A 1/2" X 1/8" PIPE PLUG TO ACCOMMODATE LINE GAS PRESSURE MEASUREMENT.
DRAIN TRAP
PLUG IN ALTERNATE
GAS LI NE HOLE
Page 59
PRODUCT DESIGN
GAS PIPING CHECKS
Before placing unit in operation, leak test the unit and gas connections.
WARNING
TO AVOID THE POSSIBLITY OF EXPLOSION OR FIRE, NEVER USE A MATCH
OR OPEN FLAME TO TEST FOR LEAKS.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved testing methods.
NOTE: Never exceed specified pressures for testing. Higher pressure may damage the gas valve and cause subsequent overfiring, resulting in heat exchanger failure. Disconnect this unit and shutoff valve from the gas supply piping system before pressure testing the supply piping system with pres­sures in excess of 1/2 psig (3.48 kPa). Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping sys­tem with test pressures equal to or less than 1/2 psig (3.48 kPa).
Complete information regarding tank sizing for vaporization, recommended regulator settings, and pipe sizing is avail­able from most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most standard commercial compounds, special pipe dope must be used. Shellac-based compounds resistant to the actions of liquefied petroleum gases such as Gasolac®, Stalactic®, Clyde’s® or John Crane® are satisfactory.
Refer to the following illustration for typical propane gas in­stallations and piping.
First Stage Regulator
200 PSIG Maximum
5 to 15 PSIG (20 PSIG Max.)
Continuous
Second Stage Regulator
11" W.C.
PROPANE GAS TANKS AND PIPING
WARNING
ROPANE GAS IS HEAVIER THAN AIR AND ANY LEAKING GAS CAN SETTLE IN
P
ANY LOW AREAS OR CONFI NED SPACE S.
PERSONAL INJURY, OR DEATH DUE TO FIRE OR EXPLOSION CAUSED BY A
PROPANE GAS LEAK, INSTALL A GAS DETECTI ON WARNING DEVICE.
TO PREVENT PROPERTY DAMAGE,
A gas detecting warning system is the only reliable way to detect a propane gas leak. Iron oxide (rust) can reduce the level of odorant in propane gas. Do not rely on your sense of smell. Contact a local propane gas supplier about installing a gas detecting warning system. If the presence of gas is suspected, follow the instructions on Pages 19--22 of this manual.
All propane gas equipment must conform to the safety stan­dards of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 11 inch WC at the furnace manifold with all gas appliances in operation. Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liq­uid, and “wetted surface” area of the container or con­tainers.
2. Proper pressure regulation. (Two-stage regulation is rec­ommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between second stage regulator and the appliance. Pipe size will depend on length of pipe run and total load of all appli­ances.
Typical Propane Gas Installation
WARNING
I
F THE GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCAVATED
AREA OR A CONFINED SPACE, IT IS STRONGLY RECOMMENDED TO
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING
WARNING DEVICE IN CASE OF A GAS LEAK.
SINCE PROPANE GAS I S HEAVIER THAN AIR, ANY LEAKING GAS CAN
SETTLE IN ANY LOW AREAS OR CONFINED SPACES.
PROPANE GAS ODORANT MAY FADE, MAKING THE GAS UNDETECTABLE
EXCEPT WITH A WARNING DEVICE.
WARNING
AN UNDETECTED GAS LEAK WILL CREATE A DANGER OF EXPLOSION
OR FIR E.
IF THE PRESENCE OF GAS IS SUSPECTED, FOLLOW THE
INSTRUCTIONS ON THE COVER OF THIS MANUAL.
COULD RESULT IN
SERIOUS PERSONAL INJURY OR DEATH.
FAILURE TO DO SO
59
Page 60
PRODUCT DESIGN
WARNING
F THE INFORMATION IN THESE INSTRUCTIONS IS NOT FOLLOWED EXACTLY, A
I
FIRE OR EXPLOSION MAY RE SULT CAUSING PROPERTY DAMAGE, PERSONAL
INJURY OR LOSS OF LIFE.
O NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND
D
LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE.
WHAT TO DO IF YOU SMELL GAS
PHONE IN YOUR BUILDING.
PHONE.
DEPARTMENT. –
NSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER,
I
SERVICE AGENCY OR THE GAS SUPPLIER.
Sizing Between First and Second Stage Regulator*
Maximum P ropane Capacities listed are based on 2 psig pressure drop at 10 psig setting. Capacities in 1,000 BTU/hour.
Pipe or Tubing
Length
Feet
100 220 540 1,000 1,700 2,600 1,000 2,300 125 200 490 900 1,400 2,300 900 2,100 150 190 430 830 1,300 2,100 830 1,900 175 170 400 780 1,200 1,900 770 1,700 200 160 380 730 1,100 1,800 720 1,500
To convert to capacities at 15 psig settings - multiply by 1.130 To convert to capacities at 5 psig settings - multiply by 0.879
Sizing Between Second or Second Stage Regulator & Appliance*
Maximum P ropane Capacities listed are based on 1/2" W.C. pressure drop at 11" W.C. setting. Capacities in 1,000 BTU/hour.
Pipe or Tubing Length
Feet
100 11 26 55 90 138 78 162 307 630 976 125 10 24 48 81 122 69 146 275 567 866 150 9 21 43 72 109 63 132 252 511 787 200 8 19 39 66 100 54 112 209 439 665 250 8 17 36 60 93 48 100 185 390 590
*Data in accordance with NFPA pamphlet No. 54
O NOT TRY TO LIGHT ANY APPLIANCE.
D
O NOT TOUCH ANY ELECTRICAL SWITCH; DO NOT USE ANY
D
MMEDIATELY CALL YOUR GAS SUPPLIER FROM A NEIGHBOR’S
I
FOLLOW THE GA S SUPPLIER’S INSTRUCTIONS.
F YOU CANNOT REACH YOUR G AS SUPPLIER, CALL THE FIRE
I
Tubing Size, O.D. Type L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4"
10 730 1,700 3,200 5,300 8,300 3,200 7,500 20 500 1,100 220 3,700 5,800 2,200 4,200 30 400 920 2,000 2,900 4,700 1,800 4,000 40 370 850 1,700 2,700 4,100 1,600 3,700 50 330 770 1,500 2,400 3,700 1,500 3,400 60 300 700 1,300 2,200 3,300 1,300 3,100 80 260 610 1,200 1,900 2,900 1,200 2,600
Tubing Size, O.D. Type L
3/8" 1/2" 5/8" 3/4" 7/8" 1/2" 3/4" 1" 1-1/4" 1-1/2"
10 39 92 199 329 501 275 567 1,071 2,205 3,307 20 26 62 131 216 346 189 393 732 1,496 2,299 30 21 50 107 181 277 152 315 590 1,212 1,858 40 19 41 90 145 233 129 267 504 1,039 1,559 50 18 37 79 131 198 114 237 448 913 1,417 60 16 35 72 1,211 187 103 217 409 834 1,275 80 13 29 62 104 155 89 185 346 724 1,066
Propane Gas Piping Charts
:
Nominal Pipe Size
Schedule 40
Nominal Pipe Size
Schedule 40
When installing a propane storage tank, the contractor must consider proper tank sizing, safety, efficiency, ground char­acteristics and aesthetics. For a residential customer, the size may range from 100-1,000 gallons, depending on house­hold use. Typically, a 500 gallon tank is ample for an aver­age four-bedroom home. However, it is best to consult your local propane supplier to ensure the proper sizing for pro­pane storage requirements. Determining the correct tank size for each household is a function of demand, economy, efficiency and convenience. It is a process that requires cooperation between the propane supplier and customer.
ELECTRICAL CONNECTIONS
WARNING
TO AVOID THE RISK OF ELECTRICAL SHOCK, WIRING TO THE UNIT MUST BE
PROPERLY POLARIZED AND GROUNDED.
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLI NG THIS UNIT.
BE PRESENT.
DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER SOURCES MAY
FAILURE TO DO SO MAY CAUSE PROPERTY
CAUTION
L
ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS.
WIRING ERRORS CAN COUSE IMPROPER AND DANGEROUS OPERATION. VERIFY PROPER OPERATION AFTER SERVICING.
WIRING HARNESS
The wiring harness is an integral part of this furnace. Field alteration to comply with electrical codes should not be re­quired. Wires are color coded for identification purposes. Refer to the wiring diagram for wire routings. If any of the original wire as supplied with the furnace must be replaced, it must be replaced with wiring material having a tempera­ture rating of at least 105° C. Any replacement wiring must be copper conductor.
115 VOLT LINE CONNECTIONS
Before proceeding with electrical connections, ensure that the supply voltage, frequency, and phase correspond to that specified on the unit rating plate. Power supply to the fur­nace must be N.E.C. Class 1, and must comply with all applicable codes. The furnace must be electrically grounded in accordance with local codes or, in their absence, with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
60
Page 61
PRODUCT DESIGN
r
Use a separate fused branch electrical circuit containing properly sized wire, and fuse or circuit breaker. The fuse or circuit breaker must be sized in accordance with the maxi­mum overcurrent protection specified on the unit rating plate. An electrical disconnect must be provided at the furnace location.
NOTE: Line polarity must be observed when making field connections.
N
I
N
G
A
W
R
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance.
WARNING
TO AVOID THE RISK OF ELECTRICAL SHOCK, INJURY, OR DEATH, THE
FURNACE MUST BE ELECTRICALLY GROUNDED IN ACCORDANCE WITH LOCAL
CODES OR, IN THEIR ABSENCE, WITH THE LATEST EDITION OF THE
NATIONAL ELECTRIC CODE.
IN 90% FURNACE UPRIGHT UPFLOW INSTALLATIONS, THE DRAIN TRAP MUST
BE MOUNTED ON THE OPPOSITE SIDE OF THE UNIT FROM THE JUNCTION
BOX.
THIS WILL REDUCE THE RISK OF WATER REACHING THE JUNCTION
BOX IN THE EVENT OF A BLOCKED DRAIN CONDITION.
Connect hot, neutral, and ground wires as shown in the wir­ing diagram located on the unit’s blower door. Line polarity must be observed when making field connections. Line volt­age connections can be made through either the right or left side panel.
The 80% and 90% furnaces are shipped configured for a left side electrical connection with the junction box located inside the burner compartment. To make elec­trical connections through the opposite side of the fur­nace, the junction box must be relocated to the other side of the burner compartment prior to making elec­trical connections, refer to the following figures.
CAUTION
DGES OF SHEET METAL HOLES MAY BE SHARP. USE GLOVES A PRECAUTION
E
WHEN REMOVING HOLE PLUGS.
STANDARD
JUNCTION BOX
LOCATION
ALTERNATE
JUNCTION BOX
LOCATION
115 VOLT LINE CONNECTION OF ACCESSORIES (HUMIDIFIER AND ELECTRONIC AIR CLEANER)
WARNING
HIGH VOLTAGE
ISCONNECT
D
CHANGING A NY ELECTRICAL WIRING.
SOURCES MAY BE PRESENT.
PROPERTY DAMA GE, PERSONAL INJURY OR DEATH.
POWER BEFORE SERVICING OR
ALL
MULTIPLE POWER
FAILURE TO DO S O MAY CAUSE
All 80% & 90% furnaces have an integrated ignition con­trol that is equipped with line voltage accessory termi­nals for controlling power to an optional field-supplied humidifier and/or electronic air cleaner.
Accessory Load Specifications
Humidifier 1.0 Amp maximum at 120 VAC
Electronic Air Cleane
1.0 Amp maximum at 120 VAC
Turn OFF power to the furnace before installing any acces­sories. Follow the humidifier or air cleaner manufacturers’ instructions for locating, mounting, grounding, and control­ling these accessories.
HUMIDIFIER WIRING
On 80% & 90% furnaces, accessory wiring connections are to be made through the 1/4" quick connect terminals pro­vided on the furnace integrated control module. The Humidi- fier and Electronic Air Cleaner hot and neutral terminals are identified as HUM and EAC. All field wiring must conform to applicable codes. Connections should be made as shown below.
80% Furnace Junction Box Relocation
*
**
*
STANDARD
JUNCTION BOX
LOCATION
*
***
*
90% Furnace Junction Box Relocation
ALTERNATE
JUNCTION BOX
LOCATION
61
Page 62
PRODUCT DESIGN
OPTIONAL
ACCESORIES
ELECTRONIC
AIR CLEANER
HUMIDIFIER
EAC-H
HUM-H
L
120 VAC
HOT AND
PARK
TERMINALS
12 PIN
CONNECTOR
Accessory Wiring
(WR50A65 Ignition Control Shown)
A R T U E N
120 VAC
NEUTR AL
TERMINALS
INTEGRATED
CONTROL
MODULE
A 40 V.A. transformer and an integrated electronic control are built into the furnace to allow use with most cooling equip­ment. Consult the wiring diagram, located in the Technical Manual or on the blower door for further details of 115 Volt and 24 Volt wiring.
THERMOSTAT WIRING - 80% & 90% SINGLE-STAGE
The single stage furnace will have a "W" terminal and will use a single stage thermostat. The following drawing illus­trates the typical field wiring for a heat only single stage system and a single stage heating/single stage cooling sys­tem. Refer to the following figures for proper connections to the integrated control module.
Thermostat
Single-Stage Heating
(
W
G
R
)
12 CIRCUIT CONNECTO R
INTEGRATED
CONTROL MODULE
EAC-H
HUM-H
HUMIDIFI ER
ELECTRONIC AIR CLEANER
OPTIONAL ACCESSORIES
HUM-N
EAC-N
Accessory Wiring
(WR50V-51 Ignition Control)
If it is necessary for the installer to supply additional line voltage wiring to the inside of the furnace, the wiring must conform to all local codes, and have a minimum tempera­ture rating of 105°C. All line voltage wire splices must be made inside the furnace junction box.
The integrated control module humidifier terminals (HUM) are energized with 115 volts whenever the induced draft blower is energized. The integrated control module electronic air cleaner terminals (EAC) are energized with 115 volts when­ever the circulator blower is energized.
24 VOLT THERMOSTAT WIRING NOTE: Low voltage connections can be made through ei-
ther the right or left side panel. Wire routing must not inter­fere with circulator blower operation, filter removal, or routine maintenance.
C
Y
G R
Furnace Integrated
W
Control Module
Single-Stage Heating Only
Thermostat
Single-Stage Heating
with
Y
C
C G R WY
Y C
Remote
Condensing Unit
(Single-Stage Cooling)
G
W
R
Single-Stage Heating with Single-Stage Cooling
Typical Field Wiring - Single-Stage Gas Furnaces
(24 VAC Control Circuit)
Thermostat Wiring - 80% & 90% Two-Stage Variable Speed Furnaces
As a two-stage furnace, the furnace integrated control mod­ule provides terminals for both “W1” and “W2”, and “YLO” and “Y” thermostat connections. This allows the furnace to support the following system applications: ‘Two-Stage Heat­ing Only’, ‘Single-Stage Heating with Single-Stage Cooling’, ‘Two-Stage Heating with Single-Stage Cooling’, and ‘Two­Stage Heating with Two-Stage Cooling’. Refer to the follow­ing figures and table for proper connections to the integrated control module.
Single-Stage Cooling
()
Furnace Integrated
Control Module
62
Page 63
PRODUCT DESIGN
W2
W1
C
G
R
C G R W1Y
W2
Thermostat
Two-Stage Heating
()
Furnace Integrated
Control Module
Two-Stage Heating Only
Typical Field Wiring - Two-Stage Gas Furnaces
(24 VAC Control Circuit)
Thermostat
Single-Stage Heating
with
Single-Stage Cooling
()
Y
YLO
Condensing Unit
(Single-Stage Cooling)
Y
Y C
Remote
B/C G R W1 W2O
G
W
R
Furnace Integrated
DEHUM
Control Module
NEU
HOT
Dehumidistat
[Optional]
Single-Stage Heating with Single-Stage Cooling
NOTE:
To apply a single-stage heating thermostat, the thermostat selector jumper on the integrated Control
must
module
be set on single stage.
W2
W1
YLO
YLO
YLO
Remote
Condensing Unit
(Two-Stage Cooling)
W2
W1
W1 W2
HOT
Dehumidistat
[Optional]
Two-Stage Heating with Two-Stage Cooling
Typical Field Wiring
Two-Stage Variable Speed Gas Furnaces
(24VAC Control Circuit)
Single-Stage Thermostat Application - 80% and 90% Variable Speed Two-Stage Furnaces
A single-stage thermostat with only one heating stage can be used to control this furnace. The application of a single­stage thermostat does not offer “true” thermostat-driven two­stage operation, but provides a timed transition from low to high stage. The furnace will run on low stage for a fixed period of time before stepping up to high stage to satisfy the thermostat’s call for heat. The delay period prior to stepping up can be set at either 5 or 10 minutes through the DIP switch adjacent to the Heat Off delay DIP switches on the integrated control module. To use a single-stage thermo­stat, turn off power to the furnace, move the thermostat se­lection jumper on the integrated control module from the “two­stage” position to the “single-stage” position, turn power back on. Refer to the following figures.
T
W
TSTAT
O
S
I N G L E
T-Stat selection jumper in single-stage thermostat position.
ON
3
2
1
T
W
O
TSTAT
S
I
N
OFF
G L E
3
2
1
W1 W2
Remote
Condensing Unit
Two-Stage Heating with Single-Stage Cooling
HOT
Dehumidistat
[Optional]
DIP switch position 3: ON Delay Period: 10 minutes.
DIP switch position 3: OFF Delay Period: 5 minutes.
Single-Stage Thermostat Application
63
Page 64
PRODUCT DESIGN
Thermostat Wiring Reference Chart
( ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9, GMV95 )
Mode
Thermostat Connection Connection Options
24 Volts HOT R
From Room Thermostat
Two-Stage Variable Speed Furnace
R
On Two-Stage Integrated Control Module
To
Furnace Circulator Blower Operation
During Call From Thermostat
N/A
24 Volts COMMON C
GENERALHEATINGCOOLING
Low Stage Connection
For
"Two-Stage" Heating
High Stage Connection
For
"Two-Stage" Heating
Connection For
"Single-Stage" Cooling
Low Stage Connection
For
"Two-Stage" Cooling
High Stage Connection
For
"Two-Stage" Cooling
Continuous Fan
FAN
Connection
[Any Application]
From Room Thermostat
From Room
W1
Thermostat
From Room
W2
Thermostat
From Room
Y
Thermostat
From Room
Y1
Thermostat
From Room
Y2
Thermostat
From Room
G
Thermostat
To
To
To
To
To
To
To
C
W1
W2
Y
Y-LO
Y
G
On Two-Stage Integrated Control Module
On Two-Stage Integrated Control Module
On Two-Stage Integrated Control Module
On Two-Stage Integrated Control Module
On Two Stage Integrated Control Module
On Two-Stage Integrated Control Module
On Two-Stage Integrated Control Module
N/A
Circulator blower will operate on selected
Low Stage Heating
Circulator blower will operate on selected
High Stage Heating
Circulator blower will operate on selected
High Stage Cooling
delay and 45 second "OFF" delay)
Circulator blower will operate at 65% of
selected High Stage Cooling
Circulator blower will operate on selected
High Stage Cooling
delay and 45 second "OFF" delay)
Circulator blower will operate at
56% of selected
High Stage Cooling Speed Tap
speed tap
speed tap
speed tap (5 second "ON"
speed tap
speed tap (5 second "ON"
CONTINUOUS
24 VOLT T HERMOSTAT W IRING
NOTE: Wire routing must not interfere with circulator blower
operation, filter removal, or routine maintenance. As a two-stage furnace, the furnace integrated control
module provides terminals for both “W1” and “W2”, and “YLO” and “Y” thermostat connections. This allows the furnace to support the following system applications: ‘Two­Stage Heating Only’, ‘Two-Stage Heating with Single-Stage Cooling’, and ‘Two-Stage Heating with Two-Stage Cooling’. Refer to the following figures and table for proper connec­tions to the integrated control module.
64
Low voltage connections can be made through either the right or left side panel. Thermostat wiring entrance holes are located in the blower compartment. The following figure shows connections for a “heat only” system and “heat/cool system”.
This furnace is equipped with a 40 VA transformer to facili­tate use with most cooling equipment. Consult the wiring diagram, located on the blower compartment door, for fur­ther details of 115 Volt and 24 Volt wiring.
Page 65
PRODUCT DESIGN
INGLE STAGE THERMOSTAT APPLICATION
S
()
Y
G
YLO
(Single-Stage Cooling)
NOTE: To apply a single- stage heating thermostat, the
Two-Stage Heating with Single-Stage Cooling
B/C G R W1 W2O
Y
Y C
Remote
Condensing Unit
Single-Stage Heating with Single-Stage Cooling
thermostat selector jumper on the integrated Control module
YLO
Condensing Unit
(Single-Stage Cooling)
be set on single stage.
must
Y
B/C G R W1 W2O
Y
Y C
Remote
W
R
NEU
HOT
W2
W1
G
R
NEU
HOT
24 Volt Dehumidistat Wiring - Two-Stage Variable Speed Gas Furnaces
The optional usage of a dehumidistat allows the furnace’s circulator blower to operate at a slightly lower speed dur-
Thermostat
Single-Stage Hea ting with
Single-Stage Cooling
ing a combined thermostat call for cooling and dehumidistat call for dehumidification. This lower blower speed enhances dehumidification of the conditioned air as it passes through the AC coil. For proper function, a dehumidistat applied to this furnace must operate on 24 VAC and utilize a switch
DEHUM
TWIN
Furnace Integrated
Control Module
which opens on humidity rise. To install/connect a dehumidistat:
1. Turn OFF power to furnace.
Dehumidistat
[Optional]
2. Secure the dehumidistat neutral wire (typically the white
3. Secure the dehumidistat hot wire (typically the black
4. Secure the dehumidistat ground wire (typically the green
Ther mostat
Two-Stage Heating
with
Single-Stage Cooling
()
5. Turn ON power to furnace. To enable the dehumidify function on the circulator blower
interface board:
1. Cut the jumper wire labeled "CUT FOR DEHUM" lo-
Furnace Integrated
DEHUM
TWIN
Control Module
Once the jumper wire is cut, the dehumidify function is enabled during a combination call for cooling (T-Stat) and
Dehumidistat
[Optional]
dehumidification (Dehum-Stat). The yellow LED adjacent to the DEHUM screw terminal will be illuminated during dehumidification.
lead) to the screw terminal marked "DEHUM" on the furnace integrated control module.
lead) to the screw terminal marked "R" on the furnace integrated control module.
lead) to the ground screw on the furnace junction box. NOTE: Ground wire may not be present on all dehumidistats.
cated adjacent to the DEHUM screw terminal. NOTE:
(W14 imprinted on the circuit board is the "CUT FOR DEHUM" location.)
YLO
Y
YLO
YLO
Condensing Unit
(Two-Stage Cooling)
Two-Stage Heating with Two-Stage Cooling
Y
Y C
Remote
B/C G R W1 W2O
W2
W1
G
R
Thermostat
Two-Stage Heating
with
Two-Stage Cooling
()
Furnace Integrated
DEHUM
TWIN
Control Module
NEU
HOT
Dehumidistat
[Optional]
( 50V51 and 50V61 )
Integrated Ignition Control Module
65
Page 66
PRODUCT DESIGN
Fossil Fuel Applications
The 80% & 90% Single-Stage and Two-Stage furnaces can be used in conjunction with a heat pump in a fossil fuel application. A fossil fuel application is where an outdoor tem­perature sensor determines the most cost efficient means of heating (heat pump, gas furnace, or both).
A heat pump thermostat with two stages of heat is required to properly use the single-stage furnace with a heat pump. A heat pump thermostat with three stages of heat is re­quired to properly use the two-stage furnace with a heat pump. Refer to dual fuel, AFE-18-60A installation manual (IO-627) for additional wiring instructions.
CONTINUOUS FAN OPERATION
SINGLE STAGE 80% AND 90% FURNACES
The single stage furnace control will energize the heating circulator fan speed when the fan switch on the thermostat is turned to the "ON" position.
TWO STAGE 80% & 90% VARIABLE SPEED FURNACES
The two stage furnace control will energize ECM blower mo­tor when the fan switch on the thermostat is turned to the "ON" position. Continuous fan speed will be 56% of high stage cooling. This fan speed will provide circulation with less electricity than conventional single stage equipment.
CIRCULATOR BLOWER SPEED ADJUSTMENT
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFOR CHANGING SPEED TAPS.
D
ULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO DO
M
SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DE ATH.
All 80% & 90% single-stage and two-stage furnaces ship at high speed for cooling and the speeds listed in the Specifi­cation Sheet for heating. These speeds should be adjusted by the installer to match the job requirements. See Specifi­cation Sheet or Technical Manual for details.
Connect the correct motor leads to the COOL, HEAT, and PARK terminals. If the heating speed equals cooling speed, use the jumper wire provided. All unused motor leads that are not connected to "PARK" terminals on the control must be taped to prevent shorts.
All 80% & 90% Two-Stage Variable Speed furnaces are shipped with heating speed set at “B” and cooling speed set at “D”. Use the following procedure to select the heating and cooling speed needed for your unit.
Use the "GREEN" CFM LED, adjacent to the integrated control module fuse to verify airflow quantity. The green CFM LED blinks once for each 100 CFM of airflow.
1. Determine the tonnage of the cooling system installed with the furnace. If the cooling capacity is in BTU/hr divide it by 12,000 to convert capacity to TONs.
EXAMPLE: Cooling Capacity of 30,000 BTU/hr.
30,000/12,000 = 2.5 Tons
2. Determine the proper air flow for the cooling system. Most cooling systems are designed to work with air flows between 350 and 450 CFM per ton. Most manufactur­ers recommend an air flow of about 400 CFM per ton.
EXAMPLE: 2.5 tons X 400 CFM per ton = 1000 CFM The cooling system manufacturer’s instructions must
be checked for required air flow. Any electronic air clean­ers or other devices may require specific air flows, con­sult installation instructions of those devices for require­ments.
3. Knowing the furnace model, locate the high stage cool­ing air flow charts in the Product Data Book applicable to your model. Look up the cooling air flow determined in step 2 and find the required cooling speed and adjust­ment setting.
EXAMPLE: A *MV90704CXA furnace installed with a
2.5 ton air conditioning system. The air flow needed is 1000 CFM. Looking at the cooling speed chart for *MV90704CXA, find the air flow closest to 1000 CFM. A cooling airflow of 990 CFM may be attained by setting the cooling speed to “C” and the adjustment to “-” (mi­nus). NOTE: Continous Fan Speed will be 56% of high stage cooling.
4. Locate the blower speed selection DIP switches on the integrated control module. Select the desired "cooling" speed tap by positioning switches 1 and 2 appropriately. Select the desired "adjust" tap by positioning switches 3 and 4 appropriately. Refer to the following figure for switch positions and their corresponding taps. Turn off power to furnace for a minimum of 10 seconds, allowing the motor to reset and recognize the new speed selec­tion. Turn on power to furnace. Verify CFM by counting the number of times the green CFM LED blinks.
66
Page 67
PRODUCT DESIGN
87 4321
65
Cooling
Speed Tap A
87
87
87
65
65
65
Cooling
Speed Tap B
Cooling
Speed Tap C
Cooling
Speed
Tap D
*
Cooling Speed Taps
(
* indicates factory setting)
O F F
432 1
O F F
432 1
ONO
432 1
ONO
O F F
O N
F F
N
Normal
+ (Plu s)
Adjust
- (Minus) Adjust
(
Heating
Speed
Tap A
Heating
Speed
Tap B
Heating
Speed
Tap C
Heating
Speed
Tap D
(
65
87
432 1
*
O
O
F
F
F
F
432 1
65
87
O
O
F
N
F
432 1
65
87
ONO
F F
Adjust Taps
*
indicates factory setting)
87 4321
65
O
O
F
F
F
F
87 4321
65
*
O
O
F
N
F
65
87 4321
ONO
F F
65
87 4321
ONO
N
Heating Speed Taps
* indicates factory setting)
OFF
100% CFM
Cooling
Demand
100% CFM
OFF
1 min
Profile B ramps up to full cooling demand airflow by first stepping up to 50% of the full demand for 30 sec­onds. The motor then ramps to 100% of the required airflow. A one (1) minute OFF delay at 100% of the cooling airflow.
OFF OFF
50% CFM
1/2 min
100% CFM 100% CFM
1 min
Cooli ng Demand
Profile C ramps up to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 min­utes. The motor then steps up to the full demand air­flow. Profile C also has a one (1) minute, 100% OFF delay.
100% CFM100% CFM82% CFM
7 1/2 min
Cooling Demand
1 min
Profile D ramps up to 50% of the demand for 1/2 minute, then ramps to 82% of the full cooling demand airflow and operates there for approximately 7 1/2 minutes. The motor then steps up to the full demand airflow. Profile D has a 1/2 minute at 50% airflow OFF delay.
OFF
5. The variable speed circulator blower also offers several custom ON/OFF ramping profiles. These profiles may be used to enhance cooling performance and increase control level. The ramping profiles are selected using DIP switches 5 and 6. Refer to the following figure for switch positions and their corresponding taps. Refer to the bul­let points below for a description of each ramping profile. Turn OFF power to the furnace for a minimum of 10 sec­onds, allowing motor to reset and recognize the new profile selection. Turn ON power to the furnace. Verify profile selection by counting the green CFM LED blinks and timing each step of the ramping profile.
Profile A provides only an OFF delay of one (1) minute at 100% of the cooling demand airflow.
50% CFMOFF OFF
1/2 min
82% CFM
7 1/2 min
Ramping
Profile Tap A
Ramping
Profile Tap B
Ramping
Profile Tap C
Ramping
Profile Tap D
Cooling Demand
87 4321
*
87
87
87
100% CFM 50% CFM
65
O
O
F
F
F
F
432 1
65
O
O
F
N
F
432 1
65
ONO
F F
432 1
65
ONO
N
1/2 min
Ramping Profiles
indicates factory setting)
(
*
67
Page 68
PRODUCT DESIGN
6. Select the heating speed from the heating speed chart in the Product Data Book applicable to your model for your model. The adjust setting (already established by the cooling speed selection) determines which set of speeds are available. The selected speed must provide a temperature rise within the rise range listed with the particular model.
Example: The *MV90704CXA is set for 990 CFM on
cooling, the “ADJUST” is set to “-” (minus). The four heating speeds available are “A Minus”, “B Minus”, “C Minus”, and “D Mi­nus”. “A Minus” has a rise of 56°F for both stages which is within the 30-60°F rise range for the *MV90704CXA. This setting will keep electrical consumption to a mini­mum. Set the “Heat” speed DIP switches to “A”.
7. Select the desired “heating” speed tap by positioning switches 7 and 8 appropriately. Refer to figure above. Turn off power to furnace for a minimum of 10 seconds, allowing motor to reset and recognize new speed selec­tion. Turn on power to furnace. Verify selected CFM by counting the green CFM LED blinks.
In general lower heating speeds will: reduce electrical con­sumption, lower operating sound levels of the blower, and increase the outlet air temperature delivered to the home. The speeds available allow the blower performance to be optimized for the particular homeowner’s needs.
2
90
SECOND
DELAY
150
SECOND
DELAY
Single-Stage 80% and 90% Settings
1
N O
2
1
N O
F F
O
F F
O
120
SECOND
DELAY
180
SECOND
DELAY
3
2
1
2
1
Heat Off
Delay
ON
2
90 Seconds
ON 1
ON
OFF
3 2
1
Heat Off
Delay
120 Seconds
N O
N O
F F
O
F F
O
CIRCULATOR BLOWER TIMINGS 80% & 90% Furnaces NOTE: Items in this section refer to the air circulator blower
fan,
NOT to the induced draft blower. The induced draft blower timing sequence is not adjustable. The circulator blower fan timing is adjustable only on models with optional
“heating fan OFF delay” adjustment pins or switches. It is NOT adjustable in any other circumstances.
As shipped, the circulator blower fan will remain on for 150 seconds after the gas valve closes. When a call for cooling occurs, the circulator fan comes on and remains on for 45 seconds after the call for cooling ends. During normal heating operation, the circulator fan will come on approximately 30 seconds after the gas valve opens.
Blower Heat Off Delay Timings
The integrated control module provides a selectable heat off delay function. The heat off delay period may be set to 90, 120, 150, 180 seconds using the DIP switches or jumper provided on the control module. The delay is factory shipped at 150 seconds but may be changed to suit the installation requirements and/or homeowner preference. Refer to the following figures for switch positions and corresponding de­lay times.
OFF
ON 1
OFF OFF
3 2
3 2
1
Heat Off
150 Seconds
Heat Off
180 Seconds
Heat Off Delay
(* indicates factory setting)
Two-Stage Variable Speed
80% and 90% Settings
*
Delay
Delay
68
Page 69
PRODUCT DESIGN
CIRCULATING AIR AND FILTERS DUCTWORK - AIR FLOW
Duct systems and register sizes must be properly designed for the C.F.M. and external static pressure rating of the fur­nace. Ductwork should be designed in accordance with the recommended methods of "Air Conditioning Contractors of America" manual D.
A duct system should be installed in accordance with Stan­dards of the National Board of Fire Underwriters for the In­stallation of Air Conditioning, Warm Air Heating and Venti­lating Systems, Pamphlets No. 90A and 90B.
A return air filter is not supplied with the furnace. The in­staller must supply a means of filtering all of the return air. Filter(s) shall comply with UL900 or CAN/ULC-S111 Stan­dards. If the furnace is installed without filters, the warranty will be voided.
The following two charts show the bottom and side return filter sizes available for each size furnace. Larger sizes are also acceptable.
SIDE RETURN BOTTOM RETURN
Cabinet
Width
(In.)
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return.
Nominal
Filter
Size (In.)
Approx.
Flow Area
(In.)
Cabinet
Width
(In.)
Nominal
Filter
Size (In.)
Approx.
Flow Area
(In.)
All 16x25x1 400 14" 14X25X1 350
17-1/2 14X25X1 350
21 16x25x1 400
24-1/2 20X25X1 500
AMV9, ACV9, GMV9, GCV9, GMV95
COOLI NG AIRFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
0453_XA 376* 384 480 576 --- --- ---
0703_XA --- 564* 564* 564* 672 --- ---
0704_XA --- --- 564* 564* 672 768 ---
0904_XA --- --- 752* 752* 752* 768 ---
Input__Airflow
0905_XA --- --- --- 752* 752* 768 800
1155_XA --- --- --- 940* 940* 940* 800
*Minimum filter area dictated by heating airflow requirement.
Disposable Minimum Filter Area (in2)
[Based on a 300 ft/min filter face velocity]
COOLING AI RFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
0453_XA 188* 192 240 288 --- --- ---
0703_XA --- 282* 282* 282* 336 --- ---
0704_XA --- --- 260* 260* 336 384 ---
0904_XA --- --- 376* 376* 376* 384 ---
Input__Airflow
0905_XA --- --- --- 376* 376* 384 480
AMV8, ADV8, AMH8, AMS8, ADS8, DDS8, DMS8,
DHS8, GMS8, GDH8, GDS8, GHS8, GME8, GMH8,
GMV8
FURNACE INPUT FILTER SIZE TYPE
45M 68M
90M 115M 135M
45M
68M
90M 115M 135M
PERMANENT NOMINAL 600 F.M. FACE VELOCITY DISPOSABLE NOMINAL 300 F.M. FACE VELOCITY
MINIMUM FILTER SIZES
2
160 in
2
241 in
2
320 in
2
400 in
2
370 in
2
320 in
2
483 in
2
640 in
2
800 in
2
738 in
permanent permanent permanent permanent permanent disposable disposable disposable disposable disposable
115_XA --- --- --- 470* 470* 470* 480
69
Page 70
PRODUCT DESIGN
AMV9, ACV9, GMV9, GCV9, GMV95
EXAMPLE:
COOLING AIRFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
0453__XA 376* 384 480 576 --- --- ---
0704__XA --- --- 627* 627* 672 768 ---
0905__XA --- --- --- 836* 836* 836* 960
Input__Airflow
1155__XA --- --- --- 940* 940* 940* 960
COOLING AIRFLOW REQUIREMENT (CFM)
600 800 1000 1200 1400 1600 2000
0704__XA --- --- 320* 320* 336 384 ---
Input
0905__XA --- --- --- 427* 427* 427* 480
Airflow
*Minimum filter area dictated by heating airflow requirement.
Permanent Minimum Filter Area (sq. in)
[Based on a 600 ft/min filter face velocity]
[Based on 300 ft/min filter face velocity]
UPFLOW
COUNTERFLOW
Permanent Minimum Filter Area (in2)
[Based on 600 ft/min filter face velocity]
The sketch below shows how the filter is retained over the bottom return air opening on (Upflow) 90% furnace installa­tions only with kit # RF000180.
CAPTIVE LANCES
IN BACK PANEL
FILTER
RETAINER
FURNACE FRONT
FILTER
FURNACE BOTTOM
Optional (RF000180) Bottom Return Filter Retention
One inch throwaway filters should be sized for a face veloc­ity of 300 feet per minute or less (14x25x1 throwaway = 730 CFM maximum, 16x25x1 throwaway = 830 CFM maximum, 18x25x1 throwaway = 940 CFM maximum, 20x25x1 throw­away = 1040 CFM maximum) All other filters should be sized according to their manufacturer's instructions.
To find the miminum filter requirement (in2) for either perma­nent or disposable filters divide the required airflow (CFM) by the rated velocity of the filter, either 300ft/min for disposable filter or 600ft/min for permanent filter. Multiply the number by 144 in.2 to obtain the minimum filter requirement (in2).
2
2
Filter Size (in2) =
2
Filter Size (in
) =
Filter Size = 672in
Filter Size = 336in
1400 CFM x 144 in
600 ft./min. (Permanent)
1400 CFM x 144 in
300 (Disposable) ft./min.
2
Disposable
2
Permanent
Upflow furnaces with air delivery of less than 1800 CFM:
Use one side return or one bottom return ductwork connec­tion.
Upflow furnaces with air delivery of 1800 CFM or higher:
Use two side returns or one side return and one bottom return connection.
Guide dimples locate the side and bottom return cutout lo­cations. Use a straight edge to scribe lines connecting the dimples. Cut out the opening on these lines. An undersized opening will cause reduced airflow. For bottom return con­nection, remove the bottom of the cabinet before setting the furnace on the raised platform or return air duct.
A closed return duct system must be used, with the return duct connected to the furnace.
NOTE: Ductwork must never
be attached to the back of the furnace. Supply and return
connections to the furnace may be made with flexible joints to reduce noise transmission, if desired. If a central return is used, a connecting duct must be installed between the unit and the utility room wall so the blower will not interfere with combustion air or draft. The room, closet, or alcove must not be used as a return air chamber.
When the furnace is used in connection with a cooling unit, the furnace should be installed in parallel with or on the upstream side of the cooling unit to avoid condensation in the heating element. With a parallel flow arrangement, the dampers or other means used to control the flow of air must be adequate to prevent chilled air from entering the furnace and, if manually operated, must be equipped with means to prevent operation of either unit unless the damper is in the full heat or cool position.
When the furnace is heating, the temperature of the return air entering the furnace must be between 55°F and 100°F.
UPRIGHT FILTER INSTALLATIONS
Depending on the installation and/or customer preference, differing filter arrangements can be applied. Filters can be installed in the central return register, the bottom of the blower compartment (upflow filter kit # RF000180), a side panel external filter rack kit (upflow filter kit # EFR01), or the ductwork above a counterflow furnace (kit # RF000181).
70
Page 71
PRODUCT DESIGN
As an alternative a media air filter or electronic air cleaner can be used as the requested filter. Refer to the following minimum filter requirement charts for determination of the minimum filter area to ensure proper unit performance. The following figures show possible filter locations. NOTE: A duct­work access door must be used in counterflow applications to allow filter removal. If the filter rack is used, the side of the plenum must be at least as tall as dimension "A" shown in the following illustration. For dimension of "A" refer to the following chart.
COUNTERFLOW FILTER INSTALLATION
This furnace has provisions for the installation of return air filters at the counterflow top return. The furnace will accommodate the following filter sizes depending on cabi­net size:
Return Air
Optional
Access
Door
COUNTERFLOW TOP RETURN
Cabinet
Width
14 15.1
17 1/2 14.2
21 13.0
24 1/2 11.3
14 20.4
17 1/2 19.7
21 18.8
24 1/2 17.7
14 25.5
17 1/2 25.0
21 24.3
24 1/2 23.4
Filter Area
2
(in
)
600
800
1000
Qty.
2
2
2
"A" Min
Filter Size
(in)
15x20x1
20x20x1
25x20x1
Dimension "A:
(in)
ADDITIONAL FILTERING ACCESSORIES
Internal Filter Retention Kit
These kits can be used only on 90% furnaces with either Up-flow installations kit (RF000180) or Down-flow kit (RF000181). These kits should not be used for Horizontal installations. See the accessories section of this
manual for more information.
External Filter Rack Kit (EFR01)
The external filter rack kit is intended to provide a location external to the furnace casing, for installation of a perma­nent filter on upflow model furnaces. The rack is designed to mount over the indoor blower compartment area of either side panel, and provide filter retention as well as a location for attaching return air ductwork.
Electronic Air Cleaner (ASAS and GSAS) or Media Air Cleaner (AMU and GMU)
The electronic air cleaner and media air cleaner are multi­positional high efficiency air filtration devices that can be installed in any position, except with the access door fac­ing down. The best location for the air cleaner is in the re­turn air duct next to the blower compartment. Before install­ing the air cleaner, consider the application. The electronic air cleaner must be readily accessible for periodic inspec­tion and cleaning of the pre-filters and electronic cells while the media air cleaner must be readily accessible for peri­odic inspection and replacement of the Media Air Cleaner (AMU and GMU) filter cartridge (3 per carton) M0-1056, M1­1056, M2-1056, M8-1056, to maintain maximum efficiency and trouble-free operation. Carbon Filters 1156-3 and 1856­3 (set of 3) are also available. See Product Catalog for ex­act filter for your model.
Refer to Minimum Filter Area tables to determine filter area requirement. NOTE: Filters can also be installed elsewhere in the duct system such as a central return.
Horizontal Installations
Filter(s) must be installed external to the furnace casing for horizontal installations. For most installations it is prefer­able to use a central return with filters installed in the duct behind the return air grill. In this way filter replacement is relatively simple by merely removing the grille, rather than going into the attic or crawl space.
71
Page 72
PRODUCT DESIGN
NORMAL SEQUENCE OF OPERATION Goodman / Amana® Distinctions™ Brand Single-Stage
80% or 90% Furnaces White-Rodgers 50A55 Integrated Ignition Control
POWER UP
1. 115 VAC power applied to furnace.
2. Integrated ignition control module performs internal checks.
3. Integrated ignition control module LED will light.
4. Integrated ignition control monitors safety circuits con­tinuously.
5. Furnace awaits call from thermostat.
NORMAL HEATING SEQUENCE
1. R and W thermostat contacts close, initiating a call for heat.
2. Integrated control module performs safety circuit checks.
3. The induced draft blower is energized causing pres­sure switch contacts to close. Induced draft blower remains energized for pre-purge period. Humidifier ter­minals are energized with induced draft blower.
4. Ignitor warm up begins after pre-purge is completed. The White-Rodgers 50A55 ignition control has a vari­able ignitor warm up period between a
mum and a 5-second minimum.
5. Gas valve opens at end of ignitor warm up period, deliv­ering gas to burners to establish flame.
6. The control checks for a signal from the flame sensor within seven (4) seconds after the gas valve is ener­gized. Gas will only continue to flow if a flame signal is present.
7. Circulator blower is energized on heat speed following a fixed thirty (30) second blower on delay. Electronic air cleaner terminals are energized with circulator blower.
8. Furnace runs, integrated control module monitors safety circuits continously.
9. R and W thermostat contacts open, allowing the gas valve to cycle off.
10. Induced draft blower is de-energized following a fifteen (15) -second post purge. Humidifier terminals are de­energized.
11. Circulator blower is de-energized following a selectable heat off delay period (90, 120, 150 or 180 seconds). Electronic air cleaner terminals are de-energized.
12. Furnace awaits next call from thermostat.
The adjustable delay-off timing allows the installer to cus­tomize the comfort level.
17-second maxi-
Cooling Mode
The normal operational sequence in cooling mode is as follows:
1. R and Y thermostat contacts close, initiating a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized.
4. Circulator blower is energized on cool speed following a fixed five (5) second on delay. Electronic air cleaner terminals are energized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run, integrated control module monitors safety circuits con­tinuously.
6. R and Y thermostat contacts open, completing the call for cool.
7. Outdoor fan and compressor are de-energized.
8. Circulator blower is de-energized following a fixed forty five (45) second cool off delay period. Electronic air cleaner terminals are de-energized.
9. Furnace awaits next call from thermostat.
Fan Only Mode
The normal operational sequence in fan only mode is as follows:
1. R and G thermostat contacts close, initiating a call for fan.
2. Integrated control module performs safety circuit checks.
3. Circulator blower is energized on heat speed. Elec­tronic air cleaner terminals are energized.
4. Circulator blower runs, integrated control module moni­tors safety circuits continuously.
5. R and G thermostat contacts open, completing the call for fan.
6. Circulator blower is de-energized. Electronic air cleaner terminals are de-energized.
7. Furnace awaits next call from thermostat.
72
Page 73
PRODUCT DESIGN
NORMAL SEQUENCE OF OPERATION
Goodman Two-Stage 80% or 90% Furnaces
White-Rodgers 50M56 Integrated Ignition Control
POWER UP
The normal power up sequence is as follows:
115 VAC power applied to furnace.
Integrated control module performs internal checks.
Integrated control module LED will light.
Integrated control module monitors safety circuits con-
tinuously.
Furnace awaits call from thermostat.
HEATING MODE
(MODE DIP SWITCH IS SET TO “1 STG” POSITION)
The normal operational sequence in heating mode is as fol­lows:
R and W thermostat contacts close, initiating a call for
heat.
Integrated control module performs safety circuit checks.
Induced draft blower is energized for 15 second prepurge
period causing pressure switch contacts to close.
Igniter warm up begins after 15 second prepurge expires.
Low and high stage gas valves open at end of igniter
warm up period, delivering gas to burners and establish­ing flame.
Integrated control module monitors flame presence. Gas
valve will remain open only if flame is detected.
Circulator blower is energized on high heat speed fol-
lowing a fixed thirty second blower on delay. Electronic air cleaner terminals are energized with circulator blower.
Furnace operates; integrated control module monitors
safety circuits continuously.
R and W thermostat contacts open, completing the call
for heat.
Gas valve closes, extinguishing flame.
Induced draft blower is de-energized following a fifteen
second post purge.
The circulator blower remains at high heat speed for thirty
seconds. The circulator blower then switches to low heat speed for the remainder of the selected heat off delay period. For example, the selected heat off delay period is 150 seconds. The circulator blower operates at high heat for 30 seconds and at low speed for 150 - 30 = 120 seconds.
Furnace awaits the next call from thermostat.
(MODE DIP SWITCH IS SET TO “2 STG” POSITION)
The normal operational sequence in sequence is as fol­lows:
R and W thermostat contacts close, initiating a call
for heat.
Integrated control module performs safety circuit
checks.
Induced draft blower is energized for 15 second
prepurge period causing pressure switch contacts to close.
Igniter warm up begins after 15 second prepurge ex-
pires.
Low and high-stage gas valves open at end of igniter
warm up period, delivering gas to burners and estab­lishing flame.
High-stage gas valve closes after five seconds; low-
stage gas valve remains open.
Integrated control module monitors flame presence.
Gas valve will remain open only if flame is detected.
Circulator blower is energized on low heat speed fol-
lowing a fixed thirty second blower on delay. Electronic air cleaner terminals are energized with circulator blower.
Furnace is now operating in low-stage heating mode.
Furnace operates; integrated control module monitors
safety circuits continuously.
If low-stage delay period expires, control will shift op-
eration from low-stage heating mode operation to high­stage heating mode operation. Control will energize cir­culator blower high heat speed and high stage gas valve.
Furnace is now operating in high-stage heating mode.
R and W thermostat contacts open, completing the
call for heat.
Induced draft blower is de-energized following a fifteen
second post purge.
Circulator blower is de-energized following a heat off
delay period (selectable 100 or 150 seconds; factory set at 150 seconds).
If the furnace is operating in the low-stage heating mode when thermostat contacts open, circulator re­mains at low heat speed for the selected delay off pe­riod.
If the furnace is operating in high-stage heating mode when the thermostat contacts open, the circulator blower remains at high heat speed for thirty seconds. The cir­culator blower then switches to low heat speed for the remainder of the selected heat off delay period. For example, the selected heat off delay period is 150 sec­onds. The circulator blower operates at high heat for 30 seconds and at low speed for 150 - 30 = 120 seconds.
Furnace awaits the next call from thermostat.
73
Page 74
PRODUCT DESIGN
COOLING MODE
The normal operational sequence in cooling mode is as fol­lows:
R and Y thermostat contacts close, initiating a call for
cool.
Integrated control module performs safety circuit checks.
Outdoor fan and compressor are energized.
Circulator blower is energized on cool speed following a
fixed five second on delay. Electronic air cleaner termi­nals are energized with circulator blower.
Furnace circulator blower and outdoor cooling unit run,
integrated control module monitors safety circuits con­tinuously.
R and Y thermostat contacts open, completing the call
for cool.
Outdoor fan and compressor are de-energized.
Circulator blower is de-energized following a fixed forty
five second cool off delay period. Electronic air cleaner terminals are de-energized.
Furnace awaits the next call from thermostat.
FAN ONLY MODE
The normal operational sequence in fan only mode is as follows:
R and G thermostat contacts close, initiating a call for
fan.
Integrated control module performs safety circuit
checks.
Circulator blower is energized on low heat speed. Elec-
tronic air cleaner terminals are energized.
Circulator blower runs, integrated control module moni-
tors safety circuits continuously.
R and G thermostat contacts open, completing the call
for fan.
Circulator blower is de-energized. Electronic air cleaner
terminals are de-energized.
Furnace awaits the next call from thermostat.
74
Page 75
PRODUCT DESIGN
NORMAL SEQUENCE OF OPERATION
Goodman Two-Stage 80% or 90% Furnaces
White-Rodgers 50V51 Integrated Ignition Control
POWER UP
The normal power up sequence is as follows:
1. 115 VAC power applied to furnace.
2. Integrated control module performs internal checks.
3. Integrated control module LED will light.
4. Integrated control module monitors safety circuits continuously.
5. Furnace awaits call from thermostat.
HEATING MODE
The normal operational sequence in heating mode is as fol­lows:
1. R and W1 (or R and W1/W2) thermostat contacts close, initiating a call for heat.
2. Integrated control module performs safety circuit checks.
3. Induced draft blower is energized on high speed for a 15­second prepurge. Humidifier terminals are energized with induced draft blower.
4. Induced draft blower steps to low speed following prepurge. Low stage pressure switch contacts are closed.
5. Igniter warm up begins upon step to low speed and pres­ence of closed low stage pressure switch contacts.
6. Gas valve opens at end of igniter warm up period, deliv­ering gas to burners and establishing flame.
7. Integrated control module monitors flame presence. Gas valve will remain open only if flame is detected.
8. If the thermostat call is for low heat, gas valve and in­duced draft blower will continue on low stage. If the call is for high heat, the gas valve and induced draft blower will change to high stage.
9. Circulator blower is energized on heat speed following a fixed thirty (30) second blower on delay. The circulator blower requires thirty (30) seconds to ramp up to full speed. Electronic air cleaner terminals are energized with circulator blower.
10. Furnace is now operating on the specified stage called for by the two-stage thermostat.
11. Furnace runs, integrated control module monitors safety circuits continuously.
12. If the two-stage thermostat changes the call from low heat to high heat, the integrated control module will im­mediately switch the induced draft blower, gas valve, and circulator blower to their high stage settings.
13. If the two-stage thermostat changes the call from high heat to low heat, the control will immediately switch the induced draft blower and gas valve to their low stage settings. The circulator blower will remain on high heat­ing speed for thirty (30) seconds before switching to the low heat circulating speed.
14. R and W1 (or R and W1/W2) thermostat contacts open, allowing the gas valve to cycle off.
15. Induced draft blower is de-energized following a fifteen (15) second post purge. Humidifier terminals are de­energized.
16. Circulator blower continues running for the selected heat off delay period (90, 120, 150 or 180 seconds). The speed run during this period depends on the last heat call provided by the thermostat.
If the last call for heat was a call for low heat, the air circulator motor will run on low heat speed for the du­ration of the heat off delay period (90, 120, 150 or 180 seconds).
If the last call for heat was a call for high heat, the air circulating motor will run on the high heating speed for thirty (30) seconds and then switch to the low heating speed for the balance of the heat off delay period (60, 90, 120 or 150 seconds).
17. Circulator blower and electronic air cleaner terminals are de-energized.
18. Circulator blower ramps down to OFF during the 30 seconds following the heat off delay period.
19. Furnace awaits next call from thermostat.
COOLING MODE
The normal operational sequence in cooling mode is as follows:
1. R and YLO/G or Y/G thermostat contacts close, initi­ating a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized to their appropriate speed.
4. Circulator blower is energized on the appropriate cool speed at the level and time determined by the se­lected ramping profile. Electronic air cleaner termi­nals are energized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run their appropriate speed, integrated control module monitors safety circuits continuously.
6. R and YLO/G or Y/G thermostat contacts open, com­pleting the call for cool.
7. Outdoor fan and compressor are de-energized.
8. Circulator blower continues running during a cool off delay period. The OFF delay time and airflow level are determined by the selected ramping profile.
9. Electronic air cleaner terminals and circulator blower are de-energized.
10. Furnace awaits next call from thermostat.
75
Page 76
PRODUCT DESIGN
FAN ONLY MODE
The normal operational sequence in fan only mode is as
follows:
1. R and G thermostat contacts close, initiating a call for fan.
2. Integrated control module performs safety circuit checks.
3. Circulator blower is energized on continuous fan speed (56% of high stage cooling) following a five (5) second delay. Electronic air cleaner terminals are energized.
4. Circulator blower runs, integrated control module moni­tors safety circuits continuously.
5. R and G thermostat contacts open, completing the call for fan.
6. Circulator blower is de-energized. Electronic air cleaner terminals are de-energized.
7. Furnace awaits next call from thermostat.
DEHUMIDIFICATION M ODE
The normal operational sequence in dehumidification mode is as follows:
1. R and YLO/G or Y/G thermostat contacts close, initiaing a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized to their ap­propriate speed.
4. Circulator blower is energized on the appropriate cool speed at the level and time determined by the selected ramping profile. Electronic air cleaner terminals are en­ergized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run their appropriate speed, integrated control module moni­tors safety circuits continuously.
6. Dehumidistat opens on humidity rise allowing the fur­nace circulator blower to operate at 80% of the cooling speed during combined thermostat call for cooling and dehumidistat call for dehumidification.
7. Humidistat opens on humidity fall allowing furnace cir­culator blower to switch back to normal cooling speed.
8. R and YLO/G or Y/G thermostat contacts open, com­pleting the call for cool.
9. Outdoor fan and compressor are de-energized.
10. Circulator blower continues running during a cool off delay period. The OFF delay time and airflow level are determined by the selected ramping profile.
11. Electronic air cleaner terminals and circulator blower are de-energized.
12. Furnace awaits next call from thermostat.
76
Page 77
PRODUCT DESIGN
NORMAL SEQUENCE OF OPERATION
Amana® Bramd Single-Stage 80% or 90% Furnaces
White-Rodgers 50A65 Integrated Ignition Control
POWER UP
1. 115 VAC power applied to furnace.
2. Integrated ignition control performs internal checks.
3. Integrated ignition control module LED will light.
4. Integrated ignition control monitors safety circuits continuously.
5. Furnace awaits call from thermostat.
NORMAL HEATING SEQUENCE
1. Thermostat calls for heat .
2. The induced draft blower is energized for pre-purge pe­riod.
3. The igniter is energized following pre-purge and is al­lowed to preheat.
4. The gas valve is energized delivering gas to the burners and starting combustion.
5. The control checks for a signal from the flame sensor within seven (4) seconds after the gas valve is ener­gized. Gas will only continue to flow if a signal is present.
6. Circulator blower is energized on heat speed following a fixed thirty second blower on delay. Electronic air cleaner terminals are energized with circulator blower.
7. Furnace runs, integrated control module monitors safety circuits continuously.
9. R and W thermostat contacts open, allowing the gas valve to cycle off.
10. Induced draft blower is de-energized following a fifteen (15) -second post purge. Humidifier terminals are de­energized.
11. Circulator blower is de-energized following a selectable heat off delay period (90, 120, 150 or 180 seconds). Electronic air cleaner terminals are de-energized.
The adjustable delay-off timing allows the installer to cus­tomize the comfort level.
COOLING MODE
The normal operational sequence in cooling mode is as fol­lows:
1. R and Y thermostat contacts close, initiating a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized.
4. Circulator blower is energized on cool speed following a fixed five second on delay. Electronic air cleaner ter­minals are energized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run, integrated control module monitors safety circuits con­tinuously.
6. R and Y thermostat contacts open, completing the call for cool.
7. Outdoor fan and compressor are de-energized.
8. Circulator blower is de-energized following a fixed forty five second cool off delay period. Electronic air cleaner terminals are de-energized.
9. Furnace awaits next call from thermostat.
FAN ONLY MODE
The normal operational sequence in fan only mode is as follows:
1. R and G thermostat contacts close, initiating a call for fan.
2. Integrated control module performs safety circuit checks.
3. Circulator blower is energized on heat speed. Elec­tronic air cleaner terminals are energized.
4. Circulator blower runs, integrated control module moni­tors safety circuits continuously.
5. R and G thermostat contacts open, completing the call for fan.
6. Circulator blower is de-energized. Electronic air cleaner terminals are de-energized.
7. Furnace awaits next call from thermostat.
77
Page 78
PRODUCT DESIGN
NORMAL SEQUENCE OF OPERATION
Amana® Brand Two-Stage 80% and 90% Furnaces
White-Rodgers 50V61 Integrated Ignition Control
POWER UP
The normal power up sequence is as follows:
1. 115 VAC power applied to furnace.
2. Integrated control module performs internal checks.
3. Integrated control module LED will light.
4. Integrated control module monitors safety circuits con­tinuously.
5. Furnace awaits call from thermostat.
HEATING MODE
The normal operational sequence in heating mode is as follows:
1. R and W1 (or R and W1/W2) thermostat contacts close, initiating a call for heat.
2. Integrated control module performs safety circuit checks.
3. Induced draft blower is energized on high speed for a
15-second prepurge. Humidifier terminals are energized
with induced draft blower.
4. Induced draft blower steps to low speed following prepurge. Low stage pressure switch contacts are closed.
5. Igniter warm up begins upon step to low speed and presence of closed low stage pressure switch contacts.
6. Gas valve opens at end of igniter warm up period, deliv­ering gas to burners and establishing flame.
7. Integrated control module monitors flame presence. Gas valve will remain open only if flame is detected.
8. If the thermostat call is for low heat, gas valve and in­duced draft blower will continue on low stage. If the call is for high heat, the gas valve and induced draft blower will change to high stage.
9. Circulator blower is energized on heat speed following a fixed thirty (30) second blower on delay. The circula­tor blower requires thirty (30) seconds to ramp up to full speed. Electronic air cleaner terminals are energized with circulator blower.
10. Furnace is now operating on the specified stage called for by the two-stage thermostat.
11. Furnace runs, integrated control module monitors safety circuits continuously.
12. If the two-stage thermostat changes the call from low heat to high heat, the integrated control module will im­mediately switch the induced draft blower, gas valve, and circulator blower to their high stage settings.
13. If the two-stage thermostat changes the call from high heat to low heat, the control will immediately switch the induced draft blower and gas valve to their low stage settings. The circulator blower will remain on high heat­ing speed for thirty (30) seconds before switching to the low heat circulating speed.
14. R and W1 (or R and W1/W2) thermostat contacts open, allowing the gas valve to cycle off.
15. Induced draft blower is de-energized following a fifteen (15) second post purge. Humidifier terminals are de­energized.
16. Circulator blower continues running for the selected heat off delay period (90, 120, 150 or 180 seconds). The speed run during this period depends on the last heat call provided by the thermostat.
If the last call for heat was a call for low heat, the air circulator motor will run on low heat speed for the dura­tion of the heat off delay period (90, 120, 150 or 180 seconds).
If the last call for heat was a call for high heat, the air circulating motor will run on the high heating speed for thirty (30) seconds
17. Circulator blower and electronic air cleaner terminals are de-energized.
18. Circulator blower ramps down to OFF during the 30 sec­onds following the heat off delay period.
19. Furnace awaits next call from thermostat.
78
Page 79
PRODUCT DESIGN
COOLING MODE
The normal operational sequence in cooling mode is as fol­lows:
1. R and YLO/G or Y/G thermostat contacts close, initiat­ing a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized to their ap­propriate speed.
4. Circulator blower is energized on the appropriate cool speed at the level and time determined by the selected ramping profile. Electronic air cleaner terminals are en­ergized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run their appropriate speed, integrated control module moni­tors safety circuits continuously.
6. R and YLO/G or Y/G thermostat contacts open, com­pleting the call for cool.
7. Outdoor fan and compressor are de-energized.
8. Circulator blower continues running during a cool off de­lay period. The OFF delay time and airflow level are determined by the selected ramping profile.
9. Electronic air cleaner terminals and circulator blower are de-energized.
10. Furnace awaits next call from thermostat.
FAN ONLY MODE
The normal operational sequence in fan only mode is as follows:
1. R and G thermostat contacts close, initiating a call for fan.
2. Integrated control module performs safety circuit checks.
3. Circulator blower is energized on continuous fan speed (56% of high stage cooling) following a five (5) second delay. Electronic air cleaner terminals are en­ergized.
4. Circulator blower runs, integrated control module monitors safety circuits continuously.
5. R and G thermostat contacts open, completing the call for fan.
6. Circulator blower is de-energized. Electronic air cleaner terminals are de-energized.
7. Furnace awaits next call from thermostat.
DEHUMIDIFICATION M ODE
The normal operational sequence in dehumidification mode is as follows:
1. R and YLO/G or Y/G thermostat contacts close, initiaing a call for cool.
2. Integrated control module performs safety circuit checks.
3. Outdoor fan and compressor are energized to their ap­propriate speed.
4. Circulator blower is energized on the appropriate cool speed at the level and time determined by the selected ramping profile. Electronic air cleaner terminals are en­ergized with circulator blower.
5. Furnace circulator blower and outdoor cooling unit run their appropriate speed, integrated control module moni­tors safety circuits continuously.
6. Dehumidistat opens on humidity rise allowing the fur­nace circulator blower to operate at 80% of the cooling speed during combined thermostat call for cooling and dehumidistat call for dehumidification.
7. Humidistat opens on humidity fall allowing furnace cir­culator blower to switch back to normal cooling speed.
8. R and YLO/G or Y/G thermostat contacts open, com­pleting the call for cool.
9. Outdoor fan and compressor are de-energized.
10. Circulator blower continues running during a cool off de­lay period. The OFF delay time and airflow level are de­termined by the selected ramping profile.
11. Electronic air cleaner terminals and circulator blower are de-energized.
12. Furnace awaits next call from thermostat.
79
Page 80
SYSTEM OPERATION
HEATING - Abnormal Operation
(Amana® Brand 80% and 90% Single Stage Furnaces
- White Rodgers 50A65 Ignition Control)
The following presents the probable causes of questionable furnace operation and how to fix them. Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses. Next, refer to the Troubleshooting Chart on the following pages for an interpretation of the LED signals and to the information in this section for a description of the problem.
1. Internal Control Failure with Integrated Ignition Control. Check for voltage to the furnace and low volt­age at the control board. Check for blown fuse on the control board. If the control determines it has an inter­nal fault, it enters a locked-out state. Any of the situa­tions mentioned will cause the diagnostic LED to pro­vide no signal. The control board should only be re­placed only after all other checks from the Troubleshoot- ing Chart have been verified.
2. System Lockout. If a flame is not sensed during the first seven (4) seconds after the gas valve is energized, the control turns off the gas. There will then be a 30 second delay while the induced draft blower is ener­gized to purge the heat exchanger. The ignitor will next be energized and preheated for 20 seconds. The gas valve will then be energized. If flame is not sensed in seven (4) seconds the gas valve will be de-energized and another purge will occur. The control will cycle the gas valve a total of three (3) times before it determines it cannot establish measurable combustion and enters a locked out state. The diagnostic light code for this prob­lem is one short flash followed by a longer pause. The control can be reset and brought out of lockout mode by turning the thermostat off for more than 5 seconds and less than 20 seconds and then back on. It can also be reset by turning off the electrical disconnect switch to the furnace for a minimum of 5 seconds.
NOTE: The control board will automatically reset one hour after lockout occurs. If the furnace frequently has to be re­set, it means that a problem exists that should be cor­rected. Refer to Troubleshooting Chart on the following pages for aid in determining the cause.
3. Pressure Switch Stuck Closed. If the control senses the pressure switch is closed when the induced draft blower is off, it waits until the fault is corrected. The diagnostic light code for this problem is two short flashes followed by a longer pause. The probable cause is either a faulty pressure switch or wiring.
4. Pressure Switch Stuck Open. If, after the induced draft blower is energized, the pressure switch does not close, within 5 minutes, the control will go into a 1-hour lock­out. The control will automatically reset from lockout and restart the ignition sequence. The diagnostic light code for this problem is three short flashes followed by a pause.
The probable causes are either disconnected hose to the pressure switch, faulty pressure switch or wiring, restricted air intake or flue piping.
5. Open Primary or Auxiliary Limit. If the limit control opens, the air circulator blower will be turned on until the limit closes. The induced draft blower will turn off for 5 seconds then turn off. The diagnostic light code for this problem is four short flashes followed by a pause. The probable cause is either low conditioned air flow due to dirty filter or resistance in duct work, faulty limit, faulty blower, or blower speed set to low.
6. Flame Sensed with No Call for Heat. If the control senses a flame when the gas valve is de-energized, it will run the air circulation blower and the induced draft blower continuously with no further furnace operation. The diagnostic flash code for this is a five flashes. The probable causes are either a short to ground in flame sense circuit, miswiring, lingering burner flame or a slow closing gas valve.
7. Open Rollout Limit. If the rollout control opens, the air circulator blower will be energized all the time. The diag­nostic light code for this problem is six flashes followed by a pause. The probable cause is either restricted flue piping or improper air requirements.
8. Low Flame Sense Signal. If the furnace continues to operate and the micro-amp signal from the flame sensor falls below specified level, the diagnostic light code for this problem will be seven flashes followed by a pause. The probable cause is either a coated/oxidized sensor, incorrectly positioned senser in burner flame or lazy burner flame due to improper gas pressure or combus­tion air.
9. Igniter circuit or poor ground (AMS8, AMS9, ADS8, ACS9). Improperly connected igniter, bad igniter or poor ground to the equipment. The diagnostic light code for this problem is eight flashes.
10. Reversed Polarity. If the 115V or 24V AC power leads are reversed, the furnace will fail to operate. The diag­nostic light code for this problem is continously flash- ing. The probable cause is either the 115V AC power to furnace or integrated control module is reversed, the 24V AC wires to transformer are reversed, or poor unit ground.
80
Page 81
SYSTEM OPERATION
HEATING - Abnormal Operation
(Amana® Brand 80% & 90% Variable Speed Furnaces ­White Rodgers 50V61 Ignition Control)
The following presents the probable causes of questionable furnace operation and how to fix them. Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses. Next, refer to the Troubleshooting Chart on the following pages for an interpretation of the LED signals and to the information in this section for a description of the problem.
1. Internal Control Failure with Integrated Ignition Control. Check for voltage to the furnace and low volt­age at the control board. Check for blown fuse on the control board. If the control determines it has an internal fault, it enters a locked-out state. Any of the situations mentioned will cause the diagnostic LED to provide no signal. The control board should only be replaced only after all other checks from the Troubleshooting Chart have been verified.
2. System Lockout. If a flame is not sensed during the first seven (4) seconds after the gas valve is energized, the control turns off the gas. There will then be a 30 second delay while the induced draft blower is energized to purge the heat exchanger. The ignitor will again be energized and preheated for (20) seconds. The gas valve will then be energized. If flame is not sensed the gas valve will be de-energized and another purge will occur and a third ignitor warm up for (20) seconds will occur. The control will cycle the gas valve a total of three (3) times before it determines it cannot establish measur­able combustion and enters a locked out state. The di­agnostic light code for this problem is one short flash followed by a longer pause. The control can be reset and brought out of lockout mode by turning the thermostat off for more than 5 seconds and less than (20) seconds and then back on. It can also be reset by turning off the electrical disconnect switch to the furnace for a mini­mum of (5) seconds.
NOTE: The control board will automatically reset one hour after lockout occurs. If the furnace frequently has to be re­set, it means that a problem exists that should be corrected. Refer to Troubleshooting Chart on the following pages for aid in determining the cause.
3. Low Stage Pressure Switch Stuck Closed. If the con- trol senses the low stage pressure switch is closed when the induced draft blower is off, it waits until the fault is corrected. The diagnostic light code for this problem is two short flashes followed by a longer pause. The prob­able cause is either a faulty pressure switch or wiring.
4. Pressure Switch Stuck Open. If, after the induced draft blower is energized, the pressure switch does not close within 5 minutes, the control will go into a 1-hour lock­out. The control will automatically reset from lockout and restart the ignition sequence. The diagnostic light code for this problem is three short flashes followed by a pause.
The probable causes are either disconnected hose to the pressure switch, faulty pressure switch or wiring, restricted air intake or flue piping.
5. Open Primary or Auxiliary Limit. If the limit control opens, the air circulator blower will be turned on until the limit closes. The induced draft blower will turn on for (15) seconds, then turn off. The diagnostic light code for this problem is four short flashes followed by a pause. The probable cause is either low conditioned air flow due to dirty filter or resistance in duct work, faulty limit, faulty blower, or blower speed set to low.
6. Flame Sensed with No Call for Heat. If the control senses a flame when the gas valve is de-energized, it will run the air circulation blower and the induced draft blower continuously with no further furnace operation. The diagnostic flash code for this is a five flashes. The probable causes are either a short to ground in flame sense circuit, miswiring, lingering burner flame or a slow closing gas valve.
7. Low Flame Sense Signal. If the furnace continues to operate and the micro-amp signal from the flame sensor falls below specified level, the diagnostic light code for this problem will be seven flashes followed by a pause. The probable cause is either a coated/oxidized sensor, incorrectly positioned senser in burner flame or lazy burner flame due to improper gas pressure or combus­tion air.
8. Reversed Polarity. If the 115V or 24V AC power leads are reversed, the furnace will fail to operate. The diag­nostic light code for this problem is continously flash- ing. The probable cause is either the 115V AC power to furnace or integrated control module is reversed, the 24V AC wires to transformer are reversed, or poor unit ground.
9. Check Igniter or No Ground Condition. Check for broken or improperly connected igniter. Check for proper ground and correct. The diagnostic light code for this problem is eight flashes followed by a pause.
10. High Stage Pressure Switch Stuck Open. This con- dition can occur if the pressure switch hose is blocked or pinched. Check for blocked flue and/or inlet air pipe. Blocked drain, weak induced draft blower and malfunc­tioning pressure switch are possible. The diagnostic light code for this problem is nine flashes followed by a pause.
81
Page 82
SYSTEM OPERATION
HEATING - Abnormal Operation
(Goodman / Amana® Distinctions™ Brand 80% Furnaces
- White Rodgers 50A55 Ignition Control)
The following presents the probable causes of question­able furnace operation and how to fix them. Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses. Next, refer to the Troubleshooting Chart on the following pages for an interpretation of the LED signals and to the information in this section for a description of the problem.
1. Internal Control Failure with Integrated Ignition Control. Check for voltage to the furnace and low volt­age at the control board. Check for blown fuse on the control board. If the control determines it has an inter­nal fault, it enters a locked-out state. Any of the situa­tions mentioned will cause the diagnostic LED to pro­vide no signal. The control board should only be re- placed after all other checks from the Troubleshooting Chart have been verified.
2. System Lockout. If a flame is not sensed during the first seven (4) seconds after the gas valve is energized, the control turns off the gas. There will then be a 30 second delay while the induced draft blower is ener­gized to purge the heat exchanger. The ignitor will next be energized and preheated for (8) seconds. The gas valve will then be energized. If flame is not sensed in seven (4) seconds the gas valve will be de-energized and another purge will occur. The control will cycle the gas valve a total of three (3) times before it determines it cannot establish measurable combustion and enters a locked out state. The diagnostic light code for this problem is one short flash followed by a longer pause. The control can be reset and brought out of lockout mode by turning the thermostat off for more than (5) seconds and less than (20) seconds and then back on. It can also be reset by turning off the electrical discon­nect switch to the furnace for a minimum of 5 sec­onds.
NOTE: The control board will automatically reset one hour after lockout occurs. If the furnace frequently has to be reset, it means that a problem exists that should be cor­rected. Refer to Troubleshooting Chart on the following pages for aid in determining the cause.
3. Pressure Switch Stuck Closed. If the control senses the pressure switch is closed when the induced draft blower is off, it waits until the fault is corrected. The diagnostic light code for this problem is two short flashes followed by a longer pause. The probable cause is either a faulty pressure switch or wiring.
4. Pressure Switch Stuck Open. If, after the induced draft blower is energized, the pressure switch does not close within 5 minutes, the control will go into a 1-hour lock­out. The control will automatically reset from lockout adn restart the ignition sequence. The diagnostic light code for this problem is three short flashes followed by a pause. The probable causes are either disconnected hose to the pressure switch, faulty pressure switch or wiring, or restricted air intake or flue piping.
5. Open Primary or Auxiliary Limit. If the limit control opens, the air circulator blower will be turned on until the limit closes. The induced draft blower will turn off for 5 seconds then turn off. The diagnostic light code for this problem is four short flashes followed by a pause. The probable cause is either low conditioned air flow due to dirty filter or resistance in duct work, faulty limit, faulty blower, or blower speed set to low.
6. Flame Sensed with No Call for Heat. If the control senses a flame when the gas valve is de-energized, it will run the air circulation blower and the induced draft blower continuously with no further furnace operation. The diagnostic flash code for this is a five flashes. The probable causes are either a short to ground in flame sense circuit, miswiring, lingering burner flame or a slow closing gas valve.
7. Open Rollout Limit. If the rollout control opens, the air circulator blower will be energized all the time. The diag­nostic light code for this problem is six flashes followed by a pause. The probable cause is either restricted flue piping or improper air requirements.
8. Low Flame Sense Signal. If the furnace continues to operate and the micro-amp signal from the flame sensor falls below specified level, the diagnostic light code for this problem will be seven flashes followed by a pause. The probable cause is either a coated/oxidized sensor, incorrectly positioned senser in burner flame or lazy burner flame due to improper gas pressure or combus­tion air.
9. Igniter circuit or poor ground (AMS8, AMS9, ADS8, ACS9). Improperly connected igniter, bad igniter or poor ground to the equipment. The diagnostic light code for this problem is eight flashes.
82
Page 83
SYSTEM OPERATION
NORMAL SEQUENCE OF OPERATION
Goodman 2-Stage Variable Speed
Integrated Ignition Control
Refer to Timing Charts for sequencing. The normal power up sequence is as follows:
115 VAC power applied to furnace.
Integrated control module performs internal checks.
Integrated control module flashes LED lights.
Integrated control module monitors safety circuits continuously.
Furnace awaits call from thermostat.
NORMAL HEATING SEQUENCE
R and W1 (or R and W1/W2) thermostat contacts close, initiating a call for heat.
Integrated control module performs safety circuit checks.
Induced draft blower is energized on high speed for a 15-second prepurge. Humidifier terminals are ener­gized with induced draft blower.
Induced draft blower steps to low speed following prepurge. Low stage pressure switch contacts are closed.
Igniter warm up begins upon step to low speed and presence of closed low stage pressure switch con­tacts.
Gas valve opens at end of igniter warm up period, de­livering gas to burners and establishing flame.
Integrated control module monitors flame presence. Gas valve will remain open only if flame is sensed.
If the thermostat call is for low heat, gas valve and induced draft blower will continue on low stage. If the call is for high heat, the gas valve and induced draft blower will change to high stage.
Circulator blower is energized on the appropriate heat speed following a fixed thirty second blower on delay. The circulator blower requires 30 seconds to ramp up to full speed. Electronic air cleaner terminals are en­ergized with circulator blower.
Furnace is now operating on the specified stage called for by the two-stage thermostat.
Furnace runs, integrated control module monitors safety circuits continuously.
If the two-stage thermostat changes the call from low heat to high heat, the integrated control module will immediately switch the induced draft blower, gas valve, and circulator blower to their high stage settings.
If the two-stage thermostat changes the call from high heat to low heat, the control will immediately switch the induced draft blower and gas valve to their low stage settings. The circulator blower will remain on high heating speed for thirty seconds before switch­ing to the low heat circulating speed.
R and W1 (or R and W1/W2) thermostat contacts open, completing the call for heat.
Gas valve closes, extinguishing flame.
Induced draft blower is de-energized following a fif­teen second post purge. Humidifier terminals are de­energized.
Circulator blower continues running for the selected heat off delay period (90, 120, 150 or 180 seconds). The speed run during this period depends on the last heat call provided by the thermostat.
If the last call for heat was a call for high heat, the air circulating motor will run on the high heating speed for thirty seconds and then switch to the low heating speed for the balance of the heat off delay period
Electronic air cleaner terminals is de-energized
Circulator blower ramps down to OFF during the 30 seconds following the heat off delay period.
Furnace awaits next call from thermostat.
NORMAL COOLING SEQUENCE - INTEGRATED IGNITION CONTROL
R and YLO/G or Y/G thermostat contacts close, initi­ating a call for cool.
Integrated control module performs safety circuit checks.
Outdoor fan and compressor are energized to their appropriate speed.
Circulator blower is energized on the appropriate cool speed following a fixed five second on delay. The circulator blower requires 30 seconds to ramp up to full speed. Electronic air cleaner terminals are ener­gized with circulator blower.
Furnace circulator blower and outdoor cooling unit run their appropriate speed, integrated control module monitors safety circuits continuously.
R and YLO/G or Y/G thermostat contacts open, com­pleting the call for cool.
Outdoor fan and compressor are de-energized.
Circulator blower continues running for a cool off de­lay period. The OFF delay time and airflow level are determined by the selected ramping profile.
Electronic air cleaner terminals and circulator blower are de-energized.
Furnace awaits next call from thermostat.
83
Page 84
SYSTEM OPERATION
CONSTANT F AN
R and G thermostat contacts close, initiating a call for fan.
Integrated control module performs safety circuit checks.
Circulator blower is energized on continuous fan speed (56% of high stage cooling) following a five (5) second delay. Electronic air cleaner terminals are energized.
Circulator blower runs, integrated control module moni­tors safety circuits continuously.
R and G thermostat contacts open, completing the call for fan.
Circulator blower is de-energized. Electronic air cleaner terminals are de-energized.
Furnace awaits next call from thermostat.
START-UP P ROCEDURE AND A DJUSTMENT
Furnace must have a 115 VAC power supply properly con­nected and grounded. Proper polarity must be maintained for correct operation. An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access door in place except for inspection and maintenance.
This furnace is also equipped with a self-diagnosing elec­tronic control module. In the event a furnace component is not operating properly, the control module LED will flash on and off in a factory-programmed sequence, depending on the problem encountered. This light can be viewed through the observation window in the blower access door. Refer to the Troubleshooting Chart for further explanation of the light- ing codes.
Follow the start-up and adjustment items, refer to further information in Section XIII, Operational Checks.
FURNACE OPERATION
Purge gas lines of air prior to start-up. Do not purge lines into an enclosed burner compartment.
Check for leaks using an approved chloride-free soap and water solution, an electronic combustible gas detector, or other approved method. Verify that all required kits (pro­pane gas, high altitude, etc.) have been appropriately in­stalled.
NOTE: An interlock switch prevents furnace operation if the blower door is not in place. Keep the blower access doors in place except for inspection and maintenance.
FURNACE S TART-UP
1. Close the manual gas shutoff valve external to the fur­nace.
2. Turn off the electrical power to the furnace.
3. Set the room thermostat to the lowest possible setting.
4. Remove the burner compartment door.
NOTE: This furnace is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand.
5. Move the furnace gas valve manual control to the OFF position.
6. Wait five minutes then smell for gas. Be sure check near the floor as some types of gas are heavier than air.
7. If you smell gas after five minutes, immediately follow the instructions on page 3 of this manual. If you do not smell gas after five minutes, move the furnace gas valve manual control to the ON position.
8. Replace the burner compartment door.
9. Open the manual gas shutoff valve external to the fur­nace.
10. Turn on the electrical power to the furnace.
11. Adjust the thermostat to a setting above room tempera­ture.
12. After the burners are lit, set the thermostat to desired temperature.
NOTE: There is an approximate 40 second delay between thermostat energizing and burner firing.
FURNACE S HUTDOWN
1. Set the thermostat to lowest setting.
2. Turn off the electrical power supply to the furnace.
3. Remove the burner compartment door and move the fur­nace gas valve manual control to the OFF position.
4. Close manual gas shutoff valve external to the furnace.
5. Replace the burner compartment door.
84
Page 85
SYSTEM OPERATION
HEATING - Abnormal Operation
(Goodman 80% & 90% Variable Speed Furnaces - White Rodgers 50V51 Ignition Control)
The following presents the probable causes of questionable furnace operation and how to fix them. Look through the observation window in the blower access door and make a note of the number of flashes in sequence between pauses. Next, refer to the Troubleshooting Chart on the following pages for an interpretation of the LED signals and to the information in this section for a description of the problem.
1. Internal Control Failure with Integrated Ignition Control. Check for voltage to the furnace and low volt­age at the control board. Check for blown fuse on the control board. If the control determines it has an internal fault, it enters a locked-out state. Any of the situations mentioned will cause the diagnostic LED to provide no signal. The control board should only be replaced only after all other checks from the Troubleshooting Chart have been verified.
2. System Lockout. If a flame is not sensed during the first seven (4) seconds after the gas valve is energized, the control turns off the gas. There will then be a 30 second delay while the induced draft blower is energized to purge the heat exchanger. The ignitor will again be energized and preheated for (8) seconds. The gas valve will then be energized. If flame is not sensed the gas valve will be de-energized and another purge will occur and a third ignitor warm up for (9) seconds will occur. The control will cycle the gas valve a total of three (3) times before it determines it cannot establish measur­able combustion and enters a locked out state. The di­agnostic light code for this problem is one short flash followed by a longer pause. The control can be reset and brought out of lockout mode by turning the thermostat off for more than (5) seconds and less then (20) seconds and then back on. It can also be reset by turning off the electrical disconnect switch to the furnace for a mini­mum of 5 seconds.
NOTE: The control board will automatically reset one hour after lockout occurs. If the furnace frequently has to be re­set, it means that a problem exists that should be corrected. Refer to Troubleshooting Chart on the following pages for aid in determining the cause.
3. Low Stage Pressure Switch Stuck Closed. If the con- trol senses the low stage pressure switch is closed when the induced draft blower is off, it waits until the fault is corrected. The diagnostic light code for this problem is two short flashes followed by a longer pause. The prob­able cause is either a faulty pressure switch or wiring.
4. Pressure Switch Stuck Open. If, after the induced draft blower is energized, the pressure switch does not close within 5 minutes, the control will go into a 1-hour lockout. The control will automatically reset fro lockout and restart the ignition sequance. The diagnostic light code for this problem is three short flashes followed by a pause.
The probable causes are either disconnected hose to the pressure switch, faulty pressure switch or wiring, restricted air intake or flue piping.
5. Open Primary or Auxiliary Limit. If the limit control opens, the air circulator blower and induced draft blower will be turned on until the limit closes. The diagnostic light code for this problem is four short flashes fol­lowed by a pause. The probable cause is either low conditioned air flow due to dirty filter or resistance in duct work, faulty limit, faulty blower, or blower speed set to low.
6. Flame Sensed with No Call for Heat. If the control senses a flame when the gas valve is de-energized, it will run the air circulation blower and the induced draft blower continuously with no further furnace operation. The diagnostic flash code for this is a five flashes. The probable causes are either a short to ground in flame sense circuit, miswiring, lingering burner flame or a slow closing gas valve.
7. Low Flame Sense Signal. If the furnace continues to operate and the micro-amp signal from the flame sen­sor falls below specified level. The diagnostic light code for this problem is seven flashes followed by a pause. The probable cause is either a coated/oxidized sensor, incorrectly positioned senser in burner flame or lazy burner flame due to improper gas pressure or combus­tion air.
8. Reversed Polarity. If the 115V or 24V AC power leads are reversed, the furnace will fail to operate. The diag­nostic light code for this problem is continously flash- ing. The probable cause is either the 115V AC power to furnace or integrated control module is reversed, the 24V AC wires to transformer are reversed, or poor unit ground.
9. Check Igniter or No Ground Condition. Check for broken or improperly connected igniter. Check for proper ground and correct. The diagnostic light code for this problem is eight flashes followed by a pause.
10. High Stage Pressure Switch Stuck Open. This con- dition can occur if the pressure switch hose is blocked or pinched. Check for blocked flue and/or inlet air pipe. Blocked drain, weak induced draft blower and malfunc­tioning pressure switch are possible. The diagnostic light code for this problem is nine flashes followed by a pause.
85
Page 86
SYSTEM OPERATION
TROUBLESHOOTING CHART
Symptoms of Abnormal
Operation
Associated
LED Code
Fault Description(s) Possible Causes Corrective Action
2
AMH8, AMS8, ADS8, DDS8, DMS8, DHS8,
GME8, GMH8, GMS8, GDS8, GHS8
Cautions and Notes
• Furnace fails to operate.
• Integrated control module diagnostic LED provides no signal.
• Furnace fails to operate.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing ONE (1) flash.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing TWO (2) flashes.
• Induced draft blower runs continuously with no further furnace operation.
• Integrated control module diagnostic LED is flashing THREE (3) flashes.
NONE
1
1 FLASH
2
2 FLASHES
3
3 FLASHES
• No 115 volt power to furnace, or no 24 volt power to integrated control module.
• Blown fuse or circuit breaker.
• Integrated control module has an internal fault.
• Furnace lockout due to an excessive number of ignition attempt (1 total) and “retries” (2 total)1. After a total of 3 tries for ignition, lockout occurs.
"Recycles" are infinite.
• Auxiliary Limit Open
• Pressure switch circuit is closed.
• Induced draft blower is not operating.
• Pressure switch circuit not closed.
• Induced draft blower is operating.
• Manual disconnect switch OFF, door switch open, or 24 volt wires improperly connected or loose.
• Blown fuse or circuit breaker.
• Integrated control module
has an internal fault.
• Failure to establish flame. Cause may be no gas to burners, bad igniter or igniter alignment, improper orifices, or coated/ oxidized or improperly connected flame sensor.
• Loss of flame after establishment. Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in flue or improper induced draft blower performance.
• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Induced draft blower pressure switch contacts sticking.
• Shorts in pressure switch circuit.
• Pressure switch hose blocked, pinched or connected improperly.
• Blocked flue or weak induced draft blower.
• Incorrect pressure switch setpoint or malfunctioning switch contacts.
• Loose or improperly connected wiring.
• Assure 115 and 24 volt power to furnace integrated control module.
• Check integrated control module fuse (3A). Replace if necessary.
• Check for possible shorts in 115 and 24 volt circuits. Repair as necessary.
• Replace bad integrated control module.
• Locate and correct
gas interruption.
• Replace or realign
igniter.
• Check flame sense
signal. Sand sensor if coated and/or oxidized.
• Check flue piping for
blockage, proper length, elbows, and termination.
• Verify proper induced
draft blower perfor­mance.
• Check circulator
blower speed and performance. Correct speed or replace blower if necessary.
• Replace induced draft blower pressure switch.
• Repair short.
• Inspect pressure switch hose. Repair, if necessary,
• Inspect flue for blockage, proper length, elbows, and termination.
• Correct pressure switch setpoint or contact motion.
• Tighten or correct wiring connection.
• Turn power OFF prior to repair.
• Replace integrated control module fuse with 3A automotive fuse.
• Read precautions in “Electrostatic Discharge” section of manual.
• Turn power OFF prior to repair.
• Igniter is fragile, handle with care.
• Clean flame sensor with steel wool.
• See “Combustion and Ventilation Air Requirements” and “Category I Venting (Vertical Venting)” section for details.
• See Product Data Bulletin for allowable rise range and proper circulator speed.
• Turn power OFF prior to repair.
• Replace pressure switch with proper replace­ment part.
• Turn power OFF prior to repair.
• See “Combustion and Ventilation Air Requirements” and “Category I Venting (Vertical Venting)” section for details.
• Replace pressure switch. with proper replace­ment part.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
86
Page 87
SYSTEM OPERATION
TROUBLESHOOTING CHART
Symptoms of Abnormal
Operation
Associated
LED
(2)(5)
Code
• Circulator blower runs continuously. No furnace operation.
• Integrated control module
4
4 FLASHES
diagnostic LED is flashing FOUR (4) flashes.
• Induced draft blower and circulator blower runs continuously. No furnace operation.
5
5 FLASHES
• Integrated control module diagnostic LED is flashing FIVE (5) flashes.
• Furnace fails to operate.
• Integrated control module
6
diagnostic LED is flashing SIX (6) flashes.
6 FLASHES
• Normal furnace operation.
7
• Integrated control module diagnostic LED
7 FLASHES
is flashing SEVEN (7) flashes.
• Furnace not operating.
• Integrated control
module diagnostic LED is flashing EIGHT (8)
8
8 FLASHES
3
flashes.
• Integrated control module diagnostic LED is flashing
C
continuously.
CONTINUOUS
FLASHING
• LED is steady on
2
LED Flash codes will cease if power to the control module is interrupted through the disconnect or door switch.
3
8 Flases - applies to AMS8/ADS8 Models only (Silicon Nitride Models Only)
5
Integrated circuit boards on new furnace models AMH, GMH, GCH, GMS, GDS, GHS, GKS hold last 5 faults for service reference.
On Steady
Fault
Description(s)
• Primary limit circuit is open.
• Flame sensed with no call for heat.
• Rollout limit open.
• Flame sense microamp signal is low.
• Problem with
igniter ciruit.
• Polarity of 115 volt or 24 volt power is reversed.
• Normal operation.
AMH8, AMS8, ADS8, DDS8, DMS8, DHS8,
GME8, GMH8, GMS8, GDH8, GDS8, GHS8
Possible Causes Corrective Action Cautions and Notes
• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Short to ground in flame sense circuit.
• Lingering burner flame.
• Slow closing gas valve.
• Flame rollout.
• Misaligned burners, blocked flue and/or air inlet pipe, or failed induced draft blower.
• Loose or improperly connected wiring.
• Flame sensor is coated/ oxidized.
• Flame sensor incor­rectly positioned in burner flame.
• Lazy burner flame due to improper gas pressure or combustion air.
• Improperly connected igniter.
• Bad igniter.
• Poor unit ground.
• Polarity of 115 volt AC power to furnace or integrated control module is reversed.
• Wires to 24 volt side of transformer are reversed.
• Poor unit ground.
• Normal operation. • None.
•Check filters and ductwork for blockage. Clean filters or remove obstruction.
• Check circulator blower speed and perfor­mance. Correct speed or replace blower if necessary.
• Correct short at flame sensor or in flame sensor wiring.
• Check for lingering flame.
• Verify proper operation of gas valve.
• Check burners for proper alignment.
• Check flue and air inlet piping for blockage, proper length, elbows, and termination. Correct as necessary.
• Check induced draft blower for proper performance. Replace, if necessary.
• Tighten or correct wiring connection.
• Sand flame sensor is coated/oxidized.
• Inspect for proper sensor alignment.
• Check inlet air piping for blockage, proper length, elbows, and termination.
• Compare current gas pressure to rating plate info. Adjust as needed.
• Check and correct wiring from inte­grated control module to igniter.
• Replace Bad igniter.
• Check and correct unit ground wiring.
• Review wiring diagram to correct polarity.
• Reverse wires connected to 24 volt side of transformer.
• Verify proper ground. Correct if necessary.
• Check and correct wiring if necessary.
• See Product Data Bulletin for allowable rise range and proper circulator speed.
• Turn power OFF prior to repair.
• Turn power OFF prior to repair.
• See “Vent/Flue Pipe” section for piping details.
• Replace induced draft blower with proper replacement part.
• Turn power OFF prior to repair.
• Clean flame sensor with steel wool.
• See “Vent/Flue Pipe” section for piping details.
• See rating plate for proper gas pressure.
• Turn power OFF prior to repair.
• Replace igniter with proper replacement part.
• Turn power OFF prior to repair.
• Normal operation.
87
Page 88
SYSTEM OPERATION
TROUBLESHOOTING CHART
Symptoms of Abnormal
Operation
• Furnace fails to operate.
• Integrated control module diagnostic LED provides no signal.
• LED is Steady On
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing ONE (1) time.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing TWO (2) times.
• Induced draft blower runs continuously with no further furnace operation.
• Integrated control module diagnostic LED is flashing THREE (3) times.
Associated
LED Code
NONE
ON
CONTINUOUS
ON
1
1 FLASH
2
2 FLASHES
3
3 FLASHES
Description(s)
2
• No 115 volt power to furnace, or no 24 volt power to integrated control module.
• Blown fuse or circuit breaker.
• Integrated control module has an internal fault.
• Normal Operation
• Furnace lockout due to an exces­sive number of ignition “retries” (3 total)1.
• "Recycles" are infinite.
• Pressure switch circuit is closed.
• Induced draft blower is not operating.
• Pressure switch circuit not closed.
• Induced draft blower is operating.
lt Description(s) Fault
AMS9, ACS9, DMS9, DCS9, GMS9,
GCS9, GKS9, AMS95, GMS95
Possible Causes
• Manual disconnect switch OFF, door switch open, or 24 volt wires improperly connected or loose.
• Blown fuse or circuit breaker.
• Integrated control module has internal fault.
• Normal operation.
• Failure to establish flame. Cause may be no gas to burners, front cover pressure switch stuck open, bad igniter or igniter alignment, improper orifices, or coated/ oxidized or improperly connected flame sensor.
• Loss of flame after establishment. Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in flue and/or combustion air piping), front cover pressure switch opening, or improper induced draft blower performance.
• Induced draft blower pressure switch contacts sticking.
• Shorts in pressure switch circuit.
• Pressure switch hose blocked, pinched or connected improperly.
• Blocked flue and/or inlet air pipe, blocked drain system, or weak induced draft blower.
• Incorrect pressure switch setpoint or malfunctioning switch contacts.
• Loose or improperly connected wiring.
Corrective Action
• Assure 115 and 24 volt power to furnace integrated control module.
• Check integrated control module fuse (3A). Replace if necessary.
• Check for possible shorts in 115 and 24 volt circuits. Repair as necessary.
• Replace bad integrated control module.
• None.
• Locate and correct gas interruption.
• Check front cover pressure switch operation (hose, wiring, contact operation). Correct if necessary.
• Replace or realign igniter.
• Check flame sense signal. Sand sensor if coated and/or oxidized.
• Check flue piping for blockage, proper length, elbows, and termination.
• Verify proper induced draft blower perfor­mance.
• Replace induced draft blower pressure switch.
• Repair short.
• Inspect pressure switch hose. Repair, if necessary,
• Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination. Check drain system. Correct as necessary.
• Correct pressure switch setpoint or contact motion.
• Tighten or correct wiring connection.
Cautions
and Notes
• Turn power OFF prior to repair.
• Replace integrated control module fuse with 3A automotive fuse.
• Read precautions in “Electrostatic Discharge” section of manual.
• Normal operation.
• Turn power OFF prior to repair.
• Igniter is fragile, handle with care.
• Sand flame sensor with emery cloth.
• See “Vent/ Flue Pipe” section for piping details.
• Turn power OFF prior to repair.
• Replace pressure switch with proper replacement.
• Turn power OFF prior to repair.
• Replace pressure switch with proper replacement part.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED Flash code will cease if power to the control module is interrupted through the disconnect or door switch.
88
Page 89
SYSTEM OPERATION
TROUBLESHOOTING CHART
Symptoms of Abnormal
Operation
• Circulator blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing FOUR (4) flashes.
• Induced draft blower and circulation blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing FIVE (5) flashes.
• Circulator blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing SIX (6) flashes.
• Normal furnace operation.
• Integrated control module diagnostic LED is flashing SEVEN (7) flashes.
• Furnace not operating.
• Integrated control module diagnostic LED is flashing EIGHT (8) flashes.
Associated
LED Code
4
4 FLASHES
5
5 FLASHES
6
6 FLASHES
7
7 FLASHES
8
8 FLASHES
2
Fault
Description(s)
• Primary or auxiliary limit circuit is open.
• Flame sensed with no call for heat.
• Rollout limit circuit is open.
• Flame sense microamp signal is low.
• Problem with igniter circuit.
AMS9, ACS9, DMS9, DCS9, GMS9,
GCS9, GKS9, AMS95, GMS95
Possible Causes Corrective Action Cautions and Notes
• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Faulty primary or auxiliary limit switch.
• Loose or improperly connected wiring.
• Short to ground in flame sense circuit.
• Flame rollout.
• Misaligned burners, blocked flue and/or air inlet pipe, or failed induced draft blower.
• Loose or improperly connected wiring.
• Faulty rollout limit.
• Flame sensor is coated/ oxidized.
• Flame sensor incorrectly positioned in burner flame.
• Lazy burner flame due to improper gas pressure or combustion air.
• Improperly connected igniter.
• Bad igniter.
• Poor unit ground.
• Check primary/auxiliary limit. Replace if necessary
• Check filters and ductwork for blockage. Clean filters or remove obstruction.
• Check circulator blower speed and performance. Correct speed or replace blower if necessary.
• Tighten or correct wiring connection.
• Correct short at flame sensor or in flame sensor wiring.
• Check burners for proper alignment.
• Check flue and air inlet piping for blockage, proper length, elbows, and termination. Correct as necessary.
• Check induced draft blower for proper performance. Replace, if necessary.
• Tighten or correct wiring connection.
• Sand flame sensor is coated/oxidized.
• Inspect for proper sensor alignment.
• Check inlet air piping for blockage, proper length, elbows, and termination.
• Compare current gas pressure to rating plate info. Adjust as needed.
• Check and correct wiring
from integrated control module to igniter.
• Replace bad igniter.
• Check and correct unit
ground wiring.
• Turn power OFF prior to repair.
• Replace primary/ auxiliary limit switch with proper replace­ment part.
• Replace blower with correct replacement part.
• Turn power OFF prior to repair.
• Turn power OFF prior to repair.
• See “Vent/Flue Pipe” section for piping details.
• Replace rollout limit with correct replacement part.
• Replace induced draft blower with correct replace­ment part.
• Turn power OFF prior to repair.
• Sand flame sensor with emery clot.
• See “Vent/Flue Pipe” section for piping details.
• See rating plate for proper gas pressure.
• Turn power OFF prior to repair.
• Replace igniter with proper replacement part.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing continu-
ously.
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
3
8 Flashes - Applies to AMS95, AMS9, ACS9 Models only (Silicon Nitride Models Only)
CONTINUOUS/
RAPID FLASH
• Polarity of 115
C
or 24 volt power is reversed.
• Polarity of 115 volt AC power to furnace or integrated control module is reversed.
• Wires to 24 volt side of transformer are reversed.
• Poor unit ground.
• Review wiring diagram to correct polarity.
• Reverse wires going to 24 volt side of trans­former.
• Verify proper ground. Correct if necessary.
• Turn power OFF prior to repair.
89
Page 90
SYSTEM OPERATION
TROUBLESHOOTING CHART ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9
Symptoms of Abnormal
Operation
• Furnace fails to operate.
• Integrated control module diagnostic LED provides no signal.
LED is steady ON.
Associated
LED Code
NONE
ON
CONTINUOUS
ON
2
Fault
Description(s)
• No 115 volt power to furnace, or no 24 volt power to integrated control module.
• Blown fuse or circuit breaker.
• Intergrated contol module has an internal fault
• Normal operation.
Possible Causes
• Manual disconnect switch OFF, door switch open, or 24 volt wires improperly connected or loose.
• Blown fuse or circuit breaker.
• Intergrated contol module has an internal fault
•Normal operation.
Corrective Action Cautions and Notes
• Assure 115 and 24 volt power to furnace integrated control module.
• Check integrated control module fuse (3A). Replace if necessary.
• Check for possible shorts in 115 and 24 volt circuits. Repair as necessary.
• Replace bad intergrated control module.
• None.
• Turn power OFF prior to repair.
• Replace integrated control module fuse with 3A automotive fuse.
• Read precautions in “Electrostatic Discharge” section of manual.
• Normal operation.
• Failure to establish flame. Cause may be no gas to burners, bad igniter or igniter alignment, improper orifices, or coated/oxidized or improperly connected flame sensor.
• Loss of flame after establishment. Cause may be interrupted gas supply, lazy burner flames (improper gas pressure or restriction in flue or improper induced draft blower performance.
• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Induced draft blower
pressure switch contacts sticking.
• Shorts in pressure switch
circuit.
• Pressure switch hose
blocked, pinched or connected improperly.
• Blocked flue or weak
induced draft blower.
• Incorrect pressure switch
setpoint or malfunctioning switch contacts.
• Loose or improperly
connected wiring.
1
2
3
• Furnace lockout due to an excessive number of ignition “retries” (3 total)1.
• Auxiliary limit open
• Low stage pressure switch circuit is closed.
• Induced draft blower is not operating.
•Pressure switch circuit not closed.
• Induced draft blower is operating.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing ONE (1) flash.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing TWO (2) flashes.
• Induced draft blower runs continuously with no further furnace operation.
• Integrated control module diagnostic LED is flashing THREE (3) flashes.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
4
Applies to ADV8, AMV8, GMV8 only.
1 FLASH
2 FLASHES
3 FLASHES
• Locate and correct gas interruption.
• Replace or realign igniter.
• Check flame sense signal. Sand sensor if coated and/or oxidized.
• Check flue piping for blockage, proper length, elbows, and termination.
• Verify proper induced draft blower perfor­mance.
• Check circulator blower speed and performance. Correct speed or replace blower if necessary.
• Replace induced draft blower pressure switch.
• Repair short.
• Inspect pressure switch hose. Repair, if necessary,
• Inspect flue for blockage, proper length, elbows, and termination.
• Correct pressure switch setpoint or contact motion.
• Tighten or correct wiring connection.
90
• Turn power OFF prior to repair.
• Igniter is fragile, handle with care.
• Sand flame sensor with emery cloth.
• See “Combustion and Ventilation Air Requirements” and “Category I Venting (Vertical Venting)” section for details.
• See Product Data Bulletin for allowable rise range and proper circulator speed.
• Turn power OFF prior to repair.
• Replace pressure switch with proper replacement part.
•Turn power OFF prior to repair.
•See “Combustion and Ventilation Air Requirements” and “Category I Venting (Vertical Venting)” section for details.
• Replace pressure switch with proper replace­ment part.
Page 91
SYSTEM OPERATION
TROUBLESHOOTING CHART ADV8, AMV8, ACV9, AMV9, GMV8, GCV9, GMV9
Symptoms of Abnormal
Operation
• Circulator blower runs continuously. No furnace operation.
• Integrated control module diagnostic LED is flashing FOUR (4) flashes.
• Integrated control module diagnostic LED is flashing FIVE (5) times.
• Induced draft blower and circulator blower run continuously. No furnace operation.
• Furnace fails to operate.
• Integrated control module diagnostic LED is flashing
continuously.
• Normal furnace operation.
• Integrated control module diagnostic LED is flashing SEVEN (7) flashes.
• Furnace not operating.
• Integrated control module diagnostic LED is flashing EIGHT (8) flashes.
• Furnace operating on low stage gas with high stage induced draft blower
• High stage circulator blower (temperature, of conditioned air, lower than typical).
• Integrated control module diagnostic LED is flashing
NINE (9) flashes.
1
Integrated control module will automatically attempt to reset from lockout after one hour.
2
LED flash code will cease if power to control module is interrupted throught the disconnect or door switch.
4
Applies to ADV8, AMV8, GMV8 only.
Associated LED Code
4
4 FLASHES
5
5 FLASHES
C
CONTINUOUS
FLASHING
7
7 FLASHES
8
8 FLASHES
9
9 FLASHES
Fault
2
Description(s)
• Primary limit circuit is open.
• Flame
sensed with no call for heat.
• Polarity of 115 volt power is reversed.
• Flame sense microamp signal is low.
• Problem with igniter circuit.
• High stage pressure switch circuit does not close in response to high stage induced draft blower operation.
Possible Causes
• Insufficient conditioned air over the heat exchanger. Blocked filters, restrictive ductwork, improper circulator blower speed, or failed circulator blower.
• Flame rollout.
• Misaligned burners, blocked flue and/or air inlet pipe, or failed induced draft blower.
• Loose or improperly connected wiring.
• Short to ground in flame sense circuit.
• Lingering burner flame.
• Slow closing gas valve
• Polarity of 115 volt AC power to furnace or integrated control module is reversed.
• Poor unit ground.
• Flame sensor is coated/oxidized.
• Flame sensor incorrectly positioned in burner flame.
• Lazy burner flame due to improper gas pressure or combus­tion air.
• Improperly connected igniter
• Bad igniter
• Poor unit ground
• Pressure switch hose blocked, pinched or connected improperly.
• Blocked flue and/or inlet air pipe, blocked drain
system, or weak induced draft blower.
• Incorrect pressure switch setpoint or malfunctioning switch contacts.
• Loose or improperly connected wiring.
Corrective Action
• Check filters and ductwork for blockage. Clean filters or remove obstruction.
• Check circulator blower speed and performance. Correct speed or replace blower if necessary.
• Check burners for proper alignment.
• Check flue and air inlet piping for blockage, proper length, elbows, and termination. Correct as necessary.
• Check induced draft blower for proper performance. Replace, if necessary.
• Tighten or correct wiring connection.
• Correct short at flame sensor or in flame sensor wiring.
• Check for lingering flame
• Verify proper operation of gas valve
• Review wiring diagram to correct polarity.
• Verify proper ground. Correct if necessary.
• Check and correct wiring.
• Sand flame sensor is coated/oxidized.
• Inspect for proper sensor alignment.
• Check inlet air piping for blockage, proper length, elbows, and termination.
• Compare current gas pressure to rating plate info. Adjust as needed.
• Check and correct wiring from integrated control module to igniter
• Replace bad igniter
• Check and correct unit ground wiring
• Inspect pressure switch hose. Repair, if necessary.
• Inspect flue and/or inlet air piping for blockage, proper length, elbows, and termination. Check drain system. Correct as neces­sary.
• Correct pressure switch setpoint or contact motion.
• Tighten or correct wiring connection.
• Turn power OFF
• See Product Data
• Replace pressure
• Turn power OFF
• Turn power OFF
• Turn power OFF
• Sand flame sensor
• See “Vent/Flue
• See rating plate
• Turn power OFF
• Replace igniter
• Turn power OFF
• Replace
Cautions and Notes
prior to repair.
Bulletin for allowable rise range and proper circulator speed.
See “Vent/Flue Pipe” section for piping details.
switch with proper replacement part.
prior to repair.
prior to repair.
prior to repair.
with emery clot.
Pipe” section for piping details.
for proper gas pressure.
prior to repair.
with replacement part.
prior to repair.
pressure switch with proper replacement part.
91
Page 92
POLARIZATION AND PHASING
As more and more electronic's are introduced to the Heat­ing Trade, Polarization of incoming power and phasing of primary to secondary voltage on transformers becomes more important.
Polarization has been apparent in the Appliance industry since the introduction of the three prong plug, however, the Heating Industry does not use a plug for incoming power, but is hard wired.
Some of the electronic boards being used today, with flame rectification, will not function properly and/or at all without polarization of incoming power. Some also require phas­ing between the primary and secondary sides of step-down transformers.
To instill new working habits for our trade, we recommend that these two items be checked during normal installa­tion and/or service calls. See as follows:
CHECKING FOR PHASING - PRIMARY TO SECONDARY OF UNMARKED TRANSFORMERS*
METER READS 24 VOLTS
.
.
.
.
.
.
METER READS 120 VOLTS
VOLT / OHM METER
INCOMING POWER
GND
METER READS 0 VOLTS
GND
VOLT / OHM METER
THIS IS THE COMMON OR NEUTRAL LEG
METER READS 120 VOLTS
THIS IS L1 OR THE HOT POWER LEG
These then should be wired to the furnace accordingly.
D
N
G
C
R
N
L1
VOLT / OHM METE R
C
R
TRANSFORMER
D
N
G
SECONDARY
LINE VOLTAGE L1 (HOT)
VOLT / OH M M ETE R
LINE VOLTAGE (NEUTRAL)
PRIMARY
VOLT / OHM METE R
VOLT / OHM METE R
READS 96 VOLTS - IN PHASE
D
N
G
C
R
VOLT / OH M M ETE R
READS 144 VOLTS - OUT OF PHASE
N
L1
If meter reads approximately 96 volts - the primary to secondary are in phase - if reads approximately 144 volts out of phase
- reverse low voltage wires. *NOTE: For flame rectification the common side of the secondary voltage (24 V) is cabinet grounded. If you were to bench
test a transformer the primary neutral and secondary common must be connected together for testing purposes.
D
N
G
C
24 V
120 V
R
PHASING SYMBOL
92
NEUTRAL
L1
Some transformers will display phasing symbols as shown in the illustration to the left to assist in determining proper transformer phasing.
Checking for polarization and phasing should become a habit in servicing. Let's start now.
NOTE: Newer integrated ignition controls have a diagnostic flash code for reversed polarity (Refer to Troubleshooting- Diagnostic Chart for LED Codes).
Page 93
MAINTENANCE
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVICING OR
D
INSTALLING THIS UNIT.
BE PRESENT.
DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER SOURCES MAY
FAILURE TO DO SO MAY CAUSE PROPERTY
CAUTION
IF YOU MUST HANDLE THE ITNITOR, HANDLE WITH CARE. TOUCHING
THE IGNITOR BODY WITH BARE FINGERS, ROUGH HANDLING, OR
VIBRATION COULD RESULT IN EARLY IGNITOR FAILURE.
QUALIFIED SERVICER SHOULD EVER HANDLE THE IGNITOR.
ONLY A
ANNUAL INSPECTION
The furnace should be inspected by a qualified installer, or service agency at least once per year. This check should be performed at the beginning of the heating season. This will ensure that all furnace components are in proper working order and that the heating system functions appropriately. Pay particular attention to the following items. Repair or service as necessary.
Flue pipe system. Check for blockage and/or leak­age. Check the outside termination and the connec­tions at and internal to the furnace.
Combustion air intake pipe system (where applicable). Check for blockage and/or leakage. Check the out­side termination and the connection at the furnace.
Heat exchanger. Check for corrosion and/or buildup within the heat exchanger passageways.
Burners. Check for proper ignition, burner flame, and flame sense.
Drainage system. Check for blockage and/or leakage. Check hose connections at and internal to furnace.
Wiring. Check electrical connections for tightness and/ or corrosion. Check wires for damage.
Filters.
AIR FILTER
WARNING
NEVER OPERATE FURNACE WIHTOUT A FILTER INSTALLED A S DUST
AND LINT WILL BUILD UP ON INTERNAL PARTS RESULTING IN LOSS OF
EFFICIENCY, EQUIPMENT DAMAMGE, AND POSSIBLE FIRE.
Filters must be used with this furnace. Filters do not ship with these furnaces but must be provided by the installer for proper furnace operation.
Remember that dirty filters are the most common cause of inadequate heating or cooling performance.
Maintenance
Improper filter maintenance is the most common cause of inadequate heating or cooling performance. Filters should be cleaned (permanent) or replaced (disposable) every two months or as required. It is the owner's responsibility to keep air filters clean. When replacing a filter, it must be replaced with a filter of the same type and size.
Filter Removal
Depending on the installation, differing filter arrangements can be applied. Filters can be installed in the central return register, the bottom of the blower compartment (upflow only), a side panel external filter rack kit (upflow only), or the ductwork above a counterflow furnace. A media air filter or electronic air cleaner can be used as an alternate filter. The filter sizes given in the Product Design section of this manual or the product Specification Sheet must be followed to en­sure proper unit performance. Refer to the following informa­tion for removal and installation of filters.
FILTER REMOVAL PROCEDURE
Media Air Filter or Electronic Air Cleaner Removal
Follow the manufacturer’s directions for service.
Upright Counterflow Filter Removal
To remove filters from the ductwork above an upright counterflow installation:
1. Turn off electrical power to furnace.
2. Remove access door in ductwork above furnace.
3. Remove filters.
4. Remove blower compartment door. Vacuum compart­ment. Replace blower compartment door .
5. Replace filters opposite of removal.
6. Replace access door in ductwork.
Horizontal Unit Filter Removal
Filters in horizontal installations are located in the central return register.
INDUCED DRAFT AND CIRCULATION BLOWERS
The bearings in the induced draft blower and circulator blower motors are permanently lubricated by the manufacturer. No further lubrication is required. Check motor windings for ac­cumulation of dust which may cause overheating. Clean as necessary.
93
Page 94
MAINTENANCE
CONDENSATE DRAINAGE SYSTEM (QUALIFIED SERVICER ONLY)
The drain tubes, standpipe, and field supplied drain line must be checked annually and cleaned as often as necessary to ensure proper condensate drainage.
FLUE PASSAGES (QUALIFIED SERVICER ONLY)
At the start of each heating season, inspect and, if neces­sary, clean the furnace flue passages.
CLEANING FLUE PASSAGES (QUALIFIED SERVICER ONLY)
1. Turn OFF the electrical power and gas supply to the furnace.
2. Disconnect the gas line and remove the burner/ mani­fold assembly by removing the screws securing the as­sembly to the partition panel.
3. Disconnect the flue pipe system from the induced draft blower.
4. Remove the induced draft blower and, drain and pres­sure tap hoses from the recuperator coil front cover .
5. Remove the recuperator coil front cover to expose the coil tubes and turbulators.
6. Remove the recuperator coil turbulators individually by slowly pulling each turbulator forward firmly .
7. Clean the recuperator coil tubes using a long handle wire brush, such as a gun cleaning brush.
8. Clean the primary heat exchanger tubes using a wire brush attached to a length of high grade stainless steel cable, such as drain cleanout cable. Attach a variable speed reversible drill to the other end of the cable. Slowly rotate the cable with the drill and insert it into one of the heat exchanger tubes. While reversing the drill, work the cable in and out several times to obtain sufficient cleaning. Repeat for each tube.
9. Clean residue from furnace using a vacuum cleaner.
10. Replace the parts removed in the previous steps in re­verse order.
1 1. Turn on electrical power and gas to furnace. Check for
leaks and proper unit operation.
12. Severe heat exchanger fouling is an indication of an op­erational problem. Perform the steps listed in the Sys- tem Operation section of this manual to reduce the chances of repeated fouling.
FLAME SENSOR (QUALIFIED SERVICER ONLY)
Under some conditions, the fuel or air supply can create a nearly invisible coating on the flame sensor. This coating acts as an insulator, causing a drop in the flame sensing signal. If this occurs, a qualified servicer must carefully clean the flame sensor with steel wool. After cleaning, the flame sensor output should be as listed on the specification sheet.
BURNERS
WARNING
HIGH VOLTAGE E
LECTRICAL COMPONENT S ARE CONTAINED IN BOTH
COMPARTMENTS .
DEATH, DO NOT REMOVE ANY INTERNAL COMPARTMENT COVERS
OR ATTEMPT ANY ADJUSTMENT.
SERVICE AGENT AT ONCE IF AN ABNORM AL FLAME
APPEARANCE SHOU LD DEVELOP.
TO AVOID ELECTRICAL SHOCK, INJURY OR
CONTACT A QUALIFIED
Periodically during the heating season make a visual check of the burner flames. Turn the furnace on at the thermostat. Wait a few minutes since any dislodged dust will alter the normal flame appearance. Flames should be stable, quiet, soft and blue with slightly orange tips. They should not be yellow. They should extend directly outward from the burner ports without curling downward, floating or lifting off the ports.
Check the burner flames for:
1. Good adjustment
2. Stable, soft and blue
3. Not curling, floating, or lifting off.
Burner Flame
TEST EQUIPMENT
Proper test equipment for accurate diagnosis is as essen­tial as regular hand tools.
The following is a must for every service technician and ser­vice shop.
1. Dial type thermometers or thermocouple meter (optional)
- to measure dry bulb temperature.
2. Amprobe - to measure amperage and voltage.
3. Volt-Ohm Meter - testing continuity , capacitors, and mo­tor windings.
4. Inclined Manometer - to measure static pressure, pres­sure drop across coils, filters, and draft.
5. Water Manometer (12") - to test gas inlet and manifold pressure.
Other recording type instruments can be essential in solv­ing abnormal problems, however, in many instances they may be rented from local sources.
Proper equipment promotes faster, more efficient service and accurate repairs resulting in fewer call backs.
94
Page 95
MAINTENANCE
A
LWAYS CONNECT A MONOMETER TO THE OUTLET TAP AT THE GAS
VALVE BEFORE ADJUSTING THE PRESSURE REGULATOR.
I
N NO CASE
SHOULD THE FINAL MANIFOLD PRESSURE VARY MORE THAN PLUS OR
MINUS .3 INCHES WAT ER COLUMN FROM 3.5 INCHES WATER COLUMN
FOR NATURAL GAS OR 10 INCHES WATER COLUMN FOR PROPANE GAS.
CAUTION
HEATING PERFORMANCE TEST
Before attempting to diagnose an operating fault, run a heat­ing performance test and apply the results to the Service
Problem Analysis Guide.
To conduct a heating performance test, the BTU input to the furnace must be calculated.
After the heating cycle has been in operation for at least fifteen minutes and with all other gas appliances turned off, the gas meter should be clocked.
To find the BTU input, multiply the number of cubic feet of gas consumed per hour by the heating value of the gas be­ing used. (The calorific value of the gas being used is found by contacting your local utility.)
EXAMPLE: It is found by the gas meter, that it takes forty (40) seconds for the hand on the cubic foot dial to make one complete revolution, with all appliances off, except the fur­nace. Take this information and locate it on the gas rate chart. Observe the forty (40) seconds, locate and read across to the one (1) cubic foot dial column. There we find the num­ber 90, which shows that ninety (90) cubic feet of gas will be consumed in one (1) hour.
Let's assume the local gas utility has stated that the calo­rific value of the gas is 1,025 BTU per cubic foot.
Multiplying the ninety (90) cubic feet by 1,025 BTU per cu­bic foot gives us an input of 92,250 BTUH.
Checking the BTU input on the rating plate of the furnace being tested.
EXAMPLE:
INPUT: 92,000 BTU/HR OUTPUT CAP: 84,000
Should the figure you calculated not fall within five (5) per­cent of the nameplate rating of the unit, adjust the gas valve pressure regulator or resize orifices.
To adjust the pressure regulator on the gas valve, turn down (clockwise) to increase pressure and input, and out (coun­terclockwise) to decrease pressure and input.
Since normally propane gas is not installed with a gas meter, clocking will be virtually impossible. The gas orifices used with propane are calculated for 2500 BTU per cubic foot gas and with proper inlet pressures and correct piping size, full capacity will be obtained.
With propane gas, no unit gas valve regulator is used; how­ever, the second stage supply line pressure regulator should be adjusted to give 11" water column with all other gas con­suming appliances running.
The dissipation of the heat transferred to the heat exchanger is now controlled by the amount of air circulated over its surface.
The amount (CFM) of air circulated is governed by the exter­nal static pressure in inches of water column of duct work, cooling coil, registers, etc., applied externally to the unit versus the motor speed tap (direct drive) or pulley adjust­ments of the motor and blower (belt drive).
A properly operating unit must have the BTU per hour input and CFM of air, within the limits shown to prevent short cy­cling of the equipment. As the external static pressure goes up, the temperature rise will also increase. Consult the proper tables for temperature rise limitation.
95
Page 96
SERVICING
1
One
1
CUBIC FEET
GAS RATE -- CUBIC FEET PER HOUR
Seconds for
One
Revolution
10 90 180 360 720 1800 36 25 50 100 200 500 11 82 164 327 655 1636 37 -- -- 97 195 486 12 75 150 300 600 1500 38 23 47 95 189 474 13 69 138 277 555 1385 39 -- -- 92 185 462 14 64 129 257 514 1286 40 22 45 90 180 450 15 60 120 240 480 1200 41 -- -- -- 176 439 16 56 113 225 450 1125 42 21 43 86 172 429 17 53 106 212 424 1059 43 -- -- -- 167 419 18 50 100 200 400 1000 44 -- 41 82 164 409 19 47 95 189 379 947 45 20 40 80 160 400 20 45 90 180 360 900 46 -- -- 78 157 391 21 43 86 171 343 857 47 19 38 76 153 383 22 41 82 164 327 818 48 -- -- 75 150 375 23 39 78 157 313 783 49 -- -- -- 147 367 24 37 75 150 300 750 50 18 36 72 144 360 25 36 72 144 288 720 51 -- -- -- 141 355 26 34 69 138 277 692 52 -- -- 69 138 346 27 33 67 133 265 667 53 17 34 -- 136 340 28 32 64 129 257 643 54 -- -- 67 133 333 29 31 62 124 248 621 55 -- -- -- 131 327 30 30 60 120 240 600 56 16 32 64 129 321 31 -- -- 116 232 581 57 -- -- -- 126 316 32 28 56 113 225 563 58 -- 31 62 124 310 33 -- -- 109 218 545 59 -- -- -- 122 305 34 26 53 106 212 529 60 15 30 60 120 300 35 -- -- 103 206 514
1/4
cu/ft
Size of Test Dial
1/2
cu/ft
1
cu/ft
2
cu/ft5cu/ft
Seconds for
One
Revolution
1/4
cu/ft
Size of Test Dial
1/2
cu/ft
1
cu/ft
cu/ft
2
5
cu/ft
96
Page 97
SERVICING
•••
Service Problem No Heat Unsatisfactory Heat
POSSIBLE CAUSE
DOTS IN ANALYSIS
GUIDE INDICATE
"POSSIBLE CAUSE"
Power Failure Blown Fuse Loose Conne c tio n Shorted or Broken Wires No Low Voltage Faulty Thermostat Faulty Transformer Poor or High Res istance Ground Improper Heat Anticipator Setting Improper Thermostat Location Faulty Limit or Roll Ou t Switch Faulty Flame Sensor Faulty Ignition Control Gas Valve or Gas Supply Shut Off Faulty Induced Draft Blower Faulty Blower Motor (PSC & ECM) Broken or Shorted Ignitor Dirty Flame Sensor, Low UA Stuck Gas Valve Faulty Gas Valve Open Auxiliary Lim it Improper A ir Flow or Distribution Cycling on Limit Delayed Ignition Flashback Orifice Size Gas Pressure Cracked He at Exchanger Furnace Undersized Furnace Oversized Faulty Pressure Switch Blocked o r R es tricted Flue Open Roll Out S witch Bouncing On Pressure Switch
Test Method
Remedy
SYMPTOM
Burner Won't Ignite
System Will Not Start
Burner Ignites-Locks Out
Burner Shuts Off prior to T'Stat being Satisfied
••
••
••
Long Cycles
Short Cycles
••
Too Much Heat
Soot and /or Fum es
Not Enough Heat
Test Voltage S-1 Test Voltage S-4 Check Wiring S-2 Check Wiring S-3A Check Transformer S-4 Check Therm os tat S-3A
Check Transformer S-4 Measure Ground Resistance S-17B Adjust Heat Anticipator Setting S-3B
Relocate Therm os tat S-316
Test Control S-300 / S-302 Test Flam e S ens or S-314 Test Control S-313 Turn Valves to O n Position S-317 Test Induced Draft Motor S-303 Test Blower Motor (PSC & ECM) S-16A,B,C Test Ignitor S-308 Clean Flame S en sor S-314 Replace Gas Valve S-304 Replace Gas Valve S-304
Reset Control S-301 Check Duct Static S-200
Check Controls & Temperature Rise S-201 / S-300 Test for Delayed Ig nition S-312 Test for Flashback S-309 / S-311 Check Orifices S-306 / S-311
Check Gas Pressure S-307
Check Burner Flames S-305 Replace with Proper Size Furnace S-318
Replace with Proper Size Furnace S-318 Test Pressure Switch S-310 Check Flue/D rawdown Pres s ure S-310 Test Flam e Roll Out Co ntrol S -302 Test Negative Pressure S-310
See Service Procedure Reference
97
Page 98
SERVICING
SERVICE NUMBERS
S-1 CHECKING VOLTAGE .............................................................................................................. 99
S-2 CHECKING WIRING .................................................................................................................99
S-3 CHECKING THERMOSTAT, WIRING, AND ANTICIPATOR .................................................... 99
S-3A Thermostat and Wiring ............................................................................................................ 99
S-3B Heating Anticipator...................................................................................................................99
S-4 CHECKING TRANSFORMER AND CONTROL CIRCUIT....................................................100
S-15 CHECKING CAPACITOR ....................................................................................................... 101
S-15A Resistance Check ..................................................................................................................101
S-16A CHECKING AIR CIRCULATOR BLOWER MOTOR ............................................................. 101
S-200 CHECKING DUCT STATIC .................................................................................................... 113
S-201 CHECKING TEMPERATURE RISE ....................................................................................... 113
S-300 CHECKING PRIMARY LIMIT CONTROL.............................................................................. 114
S-301 CHECKING AUXILIARY LIMIT CONTROL ............................................................................ 115
S-302 CHECKING FLAME ROLLOUT CONTROL ......................................................................... 117
S-303 TEST INDUCED DRAFT MOTOR ......................................................................................... 118
S-304 CHECKING GAS VALVE .........................................................................................................118
S-305 CHECKING MAIN BURNERS ................................................................................................ 118
S-306 CHECKING ORIFICES ........................................................................................................... 118
S-307 CHECKING GAS PRESSURE................................................................................................ 119
S-308 CHECKING HOT SURFACE IGNITOR.................................................................................. 122
S-309 CHECKING FOR FLASHBACK .............................................................................................. 123
S-310 CHECKING PRESSURE CONTROL .................................................................................... 123
S-311 HIGH ALTITUDE APPLICATON (USA) ................................................................................... 124
S-312 CHECKING FOR DELAYED IGNITION ................................................................................. 124
S-313 CHECKING IGNITION CONTROL BOARDS .......................................................................124
S-314 CHECKING FLAME SENSOR................................................................................................ 128
98
Page 99
SERVICING
L
INE VOLTAGE NOW PRESENT
WARNING
S-1 CHECKING VOLTAGE
3. If any wires must be replaced, replace with AWM, 105°C. 2/64 thick insulation of the same gauge or its equivalent.
WARNING
HIGH VOLTAGE D
ISCONNECT ALL POWER BEFORE SERVICING OR
CHANGING ANY ELECTRICAL WIRIN G.
SOURCES MAY BE PRESENT.
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER
FAILURE TO DO SO MAY CAUSE
1. Remove the burner door on 80% and 90% furnaces to gain entry to the Junction Box. Earlier designed 80% furnaces have the Junction Box located in the blower compartment.
2. Remove cover from the Junction Box and gain access to incoming power lines.
With Power ON:
WARNING
LINE VOLTAGE NOW PRESENT
3. Using a voltmeter, measure the voltage across the hot and neutral connections.
NOTE: To energize the furnace, the Door Interlock Switch must be engaged at this point.
4. No reading - indicates open wiring, open fuse, no power,
or faulty Door Interlock Switch. from unit to fused dis­connect service. Repair as needed.
5. With ample voltage at line voltage connectors, energize
the furnace blower motor by jumpering terminals R to G on the integrated ignition control.
6. With the blower motor in operation, the voltage should
be 1 15 volts ± 10 percent.
7. If the reading falls below the minimum voltage, check
the line wire size. Long runs of undersized wire can cause low voltage. If wire size is adequate, notify the local power company of the condition.
8. After completing check and/or repair , replace Junction
Box cover and reinstall the service panel doors.
9. Turn on electrical power and verify proper unit operation.
S-2 CHECKING WIRING
WARNING
DISCONNECT ALL POWER BEFORE SERVICING.
1. Check wiring visually for signs of overheating, damaged insulation and loose connections.
2. Use an ohmmeter to check continuity of any suspected open wires.
CHECKING THERMOSTAT, WIRING
AND ANTICIPATOR
S-3A THERMOSTAT AND WIRING
WARNING
DISCONNECT ALL POWER BEFORE SERVICING.
1. Remove the blower compartment door to gain access to the thermostat low voltage wires located at the furnace integrated control module terminals.
2. Remove the thermostat low voltage wires at the furnace control panel terminal board.
3. Jumper terminals R to W (or W1 and W2 for two-stage models) on the integrated ignition control.
With Power On (and Door Interlock Switch closed):
4. Induced Draft Motor must run and pull in pressure switch.
5. If the hot surface ignitor heats and at the end of the
ignitor warm-up period the gas valve opens and the burn­ers ignite, the trouble is in the thermostat or wiring.
6. With power off, check the continuity of the thermostat
and wiring. Repair or replace as necessary .
If checking the furnace in the air conditioning mode, pro-
ceed as follows.
7. With power off, Jumper terminals R to Y (or Y1 or Y2 for
two-stage models) to G.
8. Turn on the power .
9. If the furnace blower motor starts and the condensing
unit runs, then the trouble is in the thermostat or wiring. Repair or replace as necessary .
10. After completing check and/or repair of wiring and check
and/or replacement of thermostat, reinstall blower com­partment door .
1 1. Turn on electrical power and verify proper unit operation.
S-3B HEATING ANTICIPATOR
The heating anticipator is a wire wound adjustable heater which is energized during the "ON" cycle to help prevent overheating of the conditioned space.
The anticipator is a part of the thermostat and if it should fail for any reason, the thermostat must be replaced.
99
Page 100
SERVICING
The heating anticipator setting for furnaces covered in this manual is 0.70 Amps.
If the anticipator current draw is unknown, then a current amp draw should be measured to determine the anticipator setting. Use an amprobe as shown in the following drawing.
10 TURNS OF THERMOSTAT WIRE (From "W" on thermostat)
STATIONARY JAW OF AMPROBE
READS 4 AMPS CURRENT DRAW WOULD BE .4 AMPS
Checking Heating Anticipator Current (Amp) Draw
WARNING
LINE VOLTAGE NOW PRESENT
3. Use a voltmeter, check voltage across terminals R and C. Must read 24 V AC.
4. No voltage indicates faulty transformer, open fuse, bad wiring, bad splice, or open door interlock switch.
5. Check transformer primary voltage at incoming line volt­age connections, fuse, splices, and blower door inter­lock switch.
6. If line voltage is available to the primary side of trans­former and not at secondary side, the transformer is inoperative. Replace.
7. After completing check and/or replacement of trans­former and check and/or repair of control circuit, rein­stall blower compartment door .
8. Turn on electrical power and verify proper unit operation.
S-10B Capacitance Check
Cooling Anticipator
The cooling anticipator is a small heater (resistor) in the thermostat. During the "OFF" cycle it heats the bimetal ele­ment helping the thermostat call for the next cooling cycle. This prevents the room temperature from rising too high be­fore the system is restarted. A properly sized anticipator should maintain room temperature within 1 1/2 to 2 degrees.
The anticipator is fixed in the subbase and is not to be re­placed. If the anticipator should fail for any reason, the sub­base must be changed.
S-4 CHECKING TRANSFORMER AND CONTROL
CIRCUIT
A step-down transformer 120 volt primary to 24 volt second­ary, 40 VA (Heating and Cooling Models) supplies ample capacity of power for either operation.
WARNING
HIGH VOLTAGE
ISCONNECT ALL POWER BEFORE SERVICING OR
D
CHANGING ANY ELECTRICAL WIRING.
SOURCES MAY BE PRESENT.
PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.
MULTIPLE POWER
FAILURE TO DO SO MAY CAUSE
VOLT / OHM METER
15 AMP F USE
AMMETER
Testing Capacitance
With power On (and Door Interlock Switch closed):
WARNING
LINE VOLTAGE NOW PRESENT
1. Remove blower compartment door to gain access to the thermostat low voltage wires located at the furnace inte­grated control module.
2. Remove the thermostat low voltage wires at the furnace integrated control module terminals.
With Power On (and Door Interlock Switch closed):
100
Using a hookup as shown above, take the current and volt­age readings and use them in the formula:
Capacitance (MFD)= 2650 x Current/Voltage
4. After completing check and/or replacement of capaci­tor, reinstall blower compartment door.
5. Turn on electrical power and verify proper unit operation.
Loading...