Goodman AGZ-BM013A Installation Manual

Installation, Operation and Maintenance Manual
Group: Chiller
Part Number: 331975001
Effective: March 2012
Supersedes: January 2012
Air-Cooled Scroll Compressor Water Chillers
AGZ 010BS – AGZ 034BS, Packaged Chiller AGZ 010BM – AGZ 034BM, Remote Evaporator
10 to 34 Tons, 35 to 120 kW
R-407C
60 Hertz
Software Version AGZSU0102D
IOMM 1155
Table of Contents
Introduction........................................3
General Description...................................3
Inspection ..................................................3
Installation .................................................3
Handling ....................................................3
Location.....................................................4
Service Access...........................................4
Vibration Isolators .....................................5
Chilled Water System ................................9
Water Connections...................................11
Refrigerant Charge ..................................11
Unit Component Location .......................11
Glycol Solutions......................................12
Evaporator Water Flow and Pressure Drop12
R-407C Units ....................................14
Control Layout and Operation.......16
Control Center .........................................16
Start-up and Shutdown....................16
Pre Start-up..............................................16
Start-up ....................................................16
Sequence of Operation ............................17
Physical Data ....................................18
AGZ-BS, R-407C....................................18
AGZ-BM, R-407C...................................20
Electrical Data..................................22
Field Wiring.............................................22
R-407C ....................................................22
Notes for Electrical Data .........................25
Dimensions & Weights.....................27
Remote Evaporators ................................29
ACZ/AGZ Dimensions and Weights .......30
Lubrication.............................................. 31
Electrical Terminals ................................ 31
Condensers.............................................. 31
Refrigerant Sight glass............................ 31
Standard MicroTech II Controller. 32
Table of Contents .................................... 32
Overview................................................. 33
General Description ................................ 33
Setpoint Security..................................... 37
Equipment Protection Alarms ................. 37
Control Functions and Definitions.......... 38
Unit Enable ............................................. 39
Unit Mode............................................... 39
Power Up Start Delay ............................. 40
Ice Mode Start Delay .............................. 40
Unit State ................................................ 40
Evaporator Water Pump State Control .... 41
Condenser Fans....................................... 43
Low OAT Start........................................ 43
Circuit Capacity Overrides ..................... 43
Maximum LWT Rate .............................. 44
Low Ambient Lockout ............................ 44
Compressor Control................................ 44
Using the Controller................................ 47
Menu Screens.......................................... 48
BAS Interface................................... 60
Service............................................... 61
Thermostatic Expansion Valve ............... 61
Filter-Driers............................................. 61
Liquid Line Solenoid .............................. 61
Optional Controls.................................... 62
Troubleshooting Chart ............................ 65
System Maintenance ........................31
General ....................................................31
©2012 Daikin. Illustrations and data cover the Daikin product at the time of publication and we reserve the right to make changes in design and construction at anytime without notice. ™® The following are trademarks or registered trademarks of their respective companies: BACnet from ASHRAE; LONMARK, LonTalk, LONWORKS, and the LONMARK logo are managed, granted and used by LONMARK International under a license granted by Echelon Corporation; Compliant Scroll from Copeland Corporation; ElectroFin from AST ElectroFin Inc.; Modbus from Schneider Electric; FanTrol, MicroTech II, Open Choices, and SpeedTrol from Daikin.
2 AGZ 010B through 034B IOMM 1155

Introduction

General Description

Daikin air-cooled water chillers are complete, self-contained automatic refrigerating units. Every unit is completely assembled, factory wired, charged, and tested. Each unit consists of air-cooled condensers, Copeland Compliant Scroll hermetic compressor, brazed plate-to-plate evaporator, and complete refrigerant piping. Liquid line components include sight-glass/moisture indicator, solenoid valve, and thermal expansion valve. Other features include a compressor heater, and evaporator heater for chilled water freeze protection.
The electrical control center includes all equipment protection and operating controls necessary for automatic operation. Condenser fan motors are three-phase (except single-phase on No. 1 fan with SpeedTrol option) and started by their own contactors and have inherent overload protection. Each compressor has solid-state motor protection for inherent thermal overload protection except Model AGZ 010 that has internal line breakage.

Software Version

This manual is based on software version AGZSU0102D. The software version can be displayed by pressing the Enter and Menu keys simultaneously. Exit by pressing Menu.

Inspection

Check all items carefully against the bill of lading. Inspect all units for damage upon arrival. Report shipping damage and file a claim with the carrier. Check the unit nameplate before unloading to be sure it agrees with the power supply available. Units are shipped FOB factory and Daikin is not responsible for physical damage after unit leaves the factory.
Note: Unit shipping and operating weights are listed on pages 18 and 19.

Installation

Note: Installation must be performed by trained, experienced personnel who are familiar
with local codes and regulations, especially concerning refrigerant release to the atmosphere.
!
WARNING
Sharp edges and coil surfaces can cause personal injury. Avoid contact with them.

Handling

Be careful to avoid rough handling of the unit. Do not push or pull the unit from anything other than the base. Block the pushing vehicle away from the unit to prevent damage to the sheet-metal cabinet and end frame (see Figure 1). To lift the unit, lifting slots are provided in the base of the unit. Arrange spreader bars and cables to prevent dam
HAZARD IDENTIFICATION INFORMATION
Warnings indicate potentially hazardous situations, which can result in property damage, severe personal
injury, or death if not avoided.
age to condenser coils or cabinet (see Figure 2).
!
WARNING
!
CAUTION
Cautions indicate potentially hazardous situations, which can result in personal injury or equipment
damage if not avoided.
IOMM 1155 AGZ 010B through 034B 3
Figure 1, Suggested Pushing Arrangement
BLOCKING REQUIRED ACROSS FULL WIDTH
Figure 2, Suggested Lifting Arrangement
SPREADER BAR (2)
NOTE:: The fork lift slots can be used for lifting by inserting sufficiently strong pipe through them as shown in Figure 2. Use the outboard slots on three-fan units and the only two on two-fan units.
PIPE SLUNG THRU OPENINGS IN LEGS (2)

Location

Unit Placement

AGZ units are for outdoor applications and can be mounted on a roof or at ground level. Set units on a solid and level foundation. For roof-mounted applications, install the unit on a steel channel or I­beam frame to support the unit above the roof. For ground level applications, install the unit on a substantial base that will not settle. A one-piece concrete slab with footings extended below the frost line is recommended. Be sure the foundation is level (within 1/2” [13 mm] over its length and width). The foundation must support the operating weights listed in the Physical Data Tables on pages 18 and
19. It is recommended that the unit be raised a few inches with a suitable support, located at least under the m
ounting locations, to allow
under it.
Since its operation is affected by wind, the unit should be located so that its length is parallel with the prevailing wind. If this is not practical, use field fabricated wind deflectors.
water to drain from under the unit and to facilitate cleaning

Service Access

Each end of the unit must be accessible after installation for periodic service. Compressors, filter­driers, and liquid line solenoid valve are accessible from the end of the unit. High-pressure, low­pressure, and motor protector controls are on the compressor. Most operating, equipment protection, and starting controls are located in the unit control box.
The fan deck with the condenser fans and motors can be removed from the top of the unit.
4 AGZ 010B through 034B IOMM 1155

Clearances

The flow of air to and from the condenser coil must not be limited. Restricting airflow or allowing air recirculation will result in a decrease in unit performance and efficiency. There must be no obstruction above the unit that would deflect discharge air downward where it could be recirculated back to the inlet of the condenser coil. The condenser fans are propeller type and will not operate with ductwork on the fan outlet.
Install the unit with enough side clearance for air entrance to the coil and for servicing. Provide service access to the evaporator, compressors, electrical control panel and piping components as shown in Figure 3. Do not block access to the unit with piping or conduit.
Do not allow debris to accumulate near the unit. Air movement may draw debris into the condenser coil causing air starvation. Give special consideration to low ambient operation where snow can accumulate. Keep condenser coils and fan discharge free of snow or other obstructions to permit adequate airflow.

Sound Isolation

The low sound levels of the AGZ chiller are suitable for most applications. When additional sound reduction is necessary, locate the unit away from sound sensitive areas. Avoid locations beneath windows or between structures where normal operating sounds may be objectionable. Reduce structurally transmitted sound by isolating water lines, electrical conduit and the unit itself. Use wall sleeves and rubber isolated piping hangers to reduce transmission of water or pump noise into occupied spaces. Use flexible electrical conduit to isolate sound through electrical conduit. Spring isolators are effective in reducing the low amplitude sound generated by the Discus semi-hermetic compressors and for unit isolation in sound-sensitive areas.
Figure 3, Clearance requirements
4 Ft. (1220mm)
Clearance for Air Inlet
4 Ft.
(1220mm)
Clearance for
Service Access
4 Ft. (1220mm)
Clearance for Air Inlet
The recommended minimum side clearance between two units is 8 feet (2440mm).
The unit must not be installed in a pit or enclosure that is deeper or taller than the height of the unit unless extra space is provided. The minimum clearance on each side of the unit is 6 feet (1828mm) when installed in a pit. The pit cannot be deeper than the unit.
The minimum clearance to a side wall or building taller than the unit height is 6 feet (1828mm) provided no solid wall above 6 feet (1828mm) tall is closer than 12 feet (3658mm) to the opposite side of the unit.
4 Ft.
(1220mm)
Clearance for
Service Access

Vibration Isolators

Vibration isolators are recommended for all roof-mounted installations or wherever vibration transmission is a consideration.
IOMM 1155 AGZ 010B through 034B 5
The unit should be initially placed on shims or blocks at the listed free height. When all piping, wiring, flushing, charging, etc. is completed, the springs are adjusted upward to loosen the blocks or shims that are then removed.
A rubber anti-skid pad is part of the isolator. Installation of spring isolators requires flexible piping connections and at least three feet of flexible conduit to avoid straining the piping and transmitting vibration and noise. These units cannot be bolted to isolators.
Table 1, Packaged & Remote Evaporator, R-I-S Isolator Locations, Aluminum Fins
UNIT SIZE
010
013
017
020
025
029
034
OPER.
WGT LBS.
1085
1170
1280
1505
1610
1800
2270
LF RF LB RB
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3 Lime Lime Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3 Lime Lime Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3 Lime Lime Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Charcoal Charcoal Brick Red Brick Red
Note: See dimension drawing for location of isolators.
R-I-S, ALUMINUM FINS
MOUNTING LOCATION
KIT PART
NUMBER
332325001
332325001
332325001
332325002
332325002
332325002
332325003
Table 2, Packaged & Remote Evaporator, R-I-S Isolator Locations, Copper Fins
UNIT SIZE
010
013
017
020
025
029
034
OPER.
WGT LBS.
1085
1170
1280
1505
1610
1800
2270
LF RF LB RB
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Brick Red Brick Red Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3 Lime Lime Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3 Lime Lime Brick Red Brick Red
RP-3 RP-3 RP-3 RP-3
Charcoal Charcoal Lime Lime
RP-3 RP-3 RP-3 RP-3
Charcoal Charcoal Lime Lime
Note: See dimension drawing for location of isolators.
R-I-S, COPPER FINS
MOUNTING LOCATION
KIT PART
NUMBER
332325001
332325001
332325001
332325002
332325002
332325004
332325004
6 AGZ 010B through 034B IOMM 1155
Table 3, Packaged & Remote Evaporator, Spring Isolator Locations, Al. Fins
,
UNIT SIZE
010
013
017
020
025
029
034
OPER.
WGT LBS.
1085
1170
1280
1505
1610
1800
2270
LF RF LB RB
C1PE-1D-340 C1PE-1D-340 C1PE-1D-340 C1PE-1D-340
Red Red Red Red
C1PE-1D-340 C1PE-1D-340 C1PE-1D-340 C1PE-1D-340
Red Red Red Red
C1PE-1D-510 C1PE-1D-510 C1PE-1D-510 C1PE-1D-510
Black Black Black Black
C1PE-1D-675 C1PE-1D-675 C1PE-1D-340 C1PE-1D-340
Dark Purple Dark Purple Red Red
C1PE-1D-675 C1PE-1D-675 C1PE-1D-340 C1PE-1D-340
Dark Purple Dark Purple Red Red
C1PE-1D-900 C1PE-1D-900 C1PE-1D-510 C1PE-1D-510
Dark Green Dark Green Black Black
C1PE-1D-900 C1PE-1D-900 C1PE-1D-510 C1PE-1D-510
Dark Green Dark Green Black Black
Note:
1. See dimension drawing for location of isolators.
2. C1PE designates one spring per housing.
SPRINGS, ALUMINUM FINS
MOUNTING LOCATION
KIT PART
NUMBER
332320001
332320001
332320003
332320004
332320004
332320006
332320006
Table 4, Packaged & Remote Evaporator, Spring Isolator Locations, Cu. Fins
SPRINGS
UNIT SIZE
010
013
017
020
025
029
034
OPER.
WGT LBS.
1085
1170
1280
1505
1610
1800
2270
LF RF LB RB
C1PE-1D-340 C1PE-1D-340 C1PE-1D-340 C1PE-1D-340
Red Red Red Red
C1PE-1D-510 C1PE-1D-510 C1PE-1D-510 C1PE-1D-510
Black Black Black Black
C1PE-1D-510 C1PE-1D-510 C1PE-1D-510 C1PE-1D-510
Black Black Black Black
C1PE-1D-900 C1PE-1D-900 C1PE-1D-510 C1PE-1D-510
Dark Green Dark Green Black Black
C1PE-1D-900 C1PE-1D-900 C1PE-1D-510 C1PE-1D-510
Dark Green Dark Green Black Black
C1PE-1D-900 C1PE-1D-900 C1PE-1D-675 C1PE-1D-675
Dark Green Dark Green Dark Purple Dark Purple
C1PE-1D-1200 C1PE-1D-1200 C1PE-1D-900 C1PE-1D-900
Gray Gray Dark Green Dark Green
Note:
1. See dimension drawing for location of isolators.
2. C1PE designates one spring per housing.
COPPER FINS
MOUNTING LOCATION
KIT PART
NUMBER
332320001
332320003
332320003
332320006
332320006
332320007
332320008
IOMM 1155 AGZ 010B through 034B 7
.
S
S

Corner Weights

Packaged Chiller
AGZ-
010A 013A 017A 020A 025A 029A 034A
RF LF RB LB
BS
279 275 267 263 315 297 288 271 344 323 316 297 502 475 271 257 531 496 301 282 583 238 353 326 779 761 369 361
RBI
LBI
Control
Panel
RFI
LFI
Remote Evaporator
AGZ-
BM
010A 013A 017A
020A
025A 029A 034A
LF RF LB RB
257 264 236 243 290 286 246 243 312 309 266 263
446 443 241 240
453 449 245 243 488 487 296 295 656 703 297 318
CP-1, Spring Isolator RP-3, Rubber-in-Shear Isolator
1/2-13 TAP
ø3.38
LOCATING PIN TO BE INSTALLED HERE
MOUNTING MOLDED IN DURULENE. WEATHER RESISTANT (WR)
1.75 (R)
4.13
5.50
2.50
ø.56DIA
2 HOLES
.25
DRAWING NUMBER 3319880
ALL DIMENSION
ARE IN DECIMAL INCHE
8 AGZ 010B through 034B IOMM 1155

Chilled Water System

Water Piping

Local authorities can supply the installer with the proper building and safety codes required for proper installation.
Install piping with minimum bends and changes in elevation to minimize pressure drop. Consider the following when installing water piping:
1. Vibration eliminators to reduce vibration and noise transmission to the building.
2. Shutoff valves to isolate the unit from the piping system during unit servicing.
3. Manual or automatic air vent valves at the high points of the system. Install drains at
the lowest points in the system.
4. Maintaining adequate system water pressure (expansion tank or regulating valve).
5. Temperature and pressure indicators located at the unit to aid in unit servicing. Pressure
gauge taps must be installed in the chilled water inlet and outlet piping or as shown in Figure 4.
6. A strainer or other means of removing foreign matter from the water before it enters the
pump. Place the strainer far enough upstream to prevent cavitation at the pump inlet (consult pump manufacturer for recommendations). The use of a strainer can prolong pump life and keep system performance up.
7. A 40-mesh strainer is required in the water line just before the inlet of the evaporator.
This will help prevent foreign material from entering and decreasing the performance of the evaporator.
!
CAUTION
If a separate disconnect is used for the 110V supply to the evaporator heating cable, mark the disconnect clearly so the disconnect is not accidentally shut off during cold seasons. Failure to do so can cause a failure of the evaporator.
8. The brazed plate evaporator has a thermostat and heating cable to prevent freeze-up
down to -20F (-29C). The heating cable should be wired to a separate 110V supply circuit. As shipped from the factory, the heating cable is wired to the control circuit. Protect all water piping to the unit from freezing.
9. If the unit is used as a replacement chiller on a previously existing piping system, flush
the system thoroughly before unit installation. Perform regular water analysis and chemical water treatment on the evaporator immediately at equipment start-up.
10. When glycol is added to the water system for freeze protection, the refrigerant suction
pressure will be lower, cooling performance less, and water side pressure drop greater. If the percentage of glycol is high, or if propylene is used instead of ethylene glycol, the added pressure drop and loss of performance could be substantial. Reset the freezestat and low leaving water alarm temperatures. The freezestat is factory set to default at 38F (3.3C). Reset the freezestat setting to approximately 4 to 5 degrees F (2.3 to 2.8 degrees C) below the leaving chilled water setpoint temperature. See the section titled “Glycol Solutions” on page 12 for additional information concerning glycol.
11. Perform
a prelim
inary leak check before insulating the piping and filling the system.
12. Include a vapor barrier on the piping insulation to prevent condensation and possible
damage to the building structure.
IOMM 1155 AGZ 010B through 034B 9
Figure 4, Typical Field Evaporator Water Piping
Ai
r
Vent
Strainer
Inlet
P
Outlet
Drain
NOTES:
1. Chilled water piping within the unit enclosure must be insulated in the field.
2. Support piping independently of the unit and install per local codes.
Vibration
Eliminators
Flow
Switch
Isolation
Val ves

System Volume

It is important to have adequate water volume in the system to provide an opportunity for the chiller to sense a load change, adjust to the change and stabilize. As the expected load change becomes more rapid, a greater water volume is needed. The system water volume is the total amount of water in the evaporator, air handling products and associated piping. If the water volume is too low, operational problems can occur, including rapid compressor cycling, rapid loading and unloading of compressors, erratic refrigerant flow in the chiller, improper motor cooling, shortened equipment life and other undesirable occurrences.
For normal comfort cooling applications, where the cooling load changes relatively slowly, we recommend a minimum system volume of three to four times the flow rate (GPM). For example, if the design chiller flow rate is 120 GPM, we recommend a minimum system volume of 360 to 480 gallons.
Since there are many other factors that can influence performance, systems may successfully operate below these suggestions. However, as the water volume decreases below these suggestions, the possibility of problems increases.

Variable Chilled Water flow

Variable chilled water flow systems are not recommended for this class of equipment due to limited unloading capability.

Flow Switch

Mount a water flow switch in the leaving water line to shut down the unit when water flow is interrupted.
A flow switch is available from Daikin (part number 017503300). It is a “paddle” type
switch and adaptable to pipe sizes down to 1 1/4” (32mm) nominal. Certain minimum flow rates are required to close the switch and are listed in Table 5. Install the switch as shown in Figure 5. Connect the normally open contacts of the flow switch in the unit control center at terminals 4 and 5. There is also a set of normally closed contacts on the switch that can be used for an indicator light or an alarm to indicate when a “no-flow” condition exists. Freeze protect any flow switch that is installed outdoors. Follow
10 AGZ 010B through 034B IOMM 1155
Figure 5, Flow Switch Installation
installation instructions provided with the flow switch. Calibrate the flow switch to open at one-half of nominal flow rate.
NOTE: Differential pressure switches are not recommended for outdoor installation. They are subject to damage from freezing.
Table 5, Flow Switch Settings
(NOTE !)
Min.
Adjst.
Max.
Adjst.
Flow
Flow Lpm 0.8 1.1 2.2 2.8 4.3 11.4 22.9 35.9 38.6
Flow
Flow Lpm 2.8 4.1 6.1 7.3 11.4 27.7 53.4 81.8 90.8
NOTES:
1. A segmented 3-inch paddle (1, 2, and 3 inches) is furnished mounted, plus a 6-inch paddle loose.
2. Flow rates for a 2-inch paddle trimmed to fit the pipe.
3. Flow rates for a 3-inch paddle trimmed to fit the pipe.
4. Flow rates for a 3-inch paddle.
5. Flow rates for a 6-inch paddle.
inch 1 1/4 1 1/2 2 2 1/2 3 4 5 6 8 Pipe Size
mm 32 (2) 38 (2) 51 63 (3) 76 102 (4) 127 (4) 153 (4) 204 (5)
gpm 5.8 7.5 13.7 18.0 27.5 65.0 125.0 190.0 205.0 Lpm 1.3 1.7 3.1 4.1 6.2 14.8 28.4 43.2 46.6 gpm 3.7 5.0 9.5 12.5 19.0 50.0 101.0 158.0 170.0
No
gpm 13.3 19.2 29.0 34.5 53.0 128.0 245.0 375.0 415.0 Lpm 3.0 4.4 6.6 7.8 12.0 29.1 55.6 85.2 94.3 gpm 12.5 18.0 27.0 32.0 50.0 122.0 235.0 360.0 400.0
No

Water Connections

The unit has 3-inch holes for the chilled water piping to enter the unit. The connections are made to the evaporator water connections located within the unit. Chilled water piping within the unit must be insulated.

Refrigerant Charge

All units are designed for R-407C and are shipped with an operating charge. The operating charge for each unit is shown in the Physical Data Tables on pages 18 and 19.

Unit Component Location

Chilled Water
Inlet Connection
Chilled Water
Outlet Connection
Evaporator
Control Panel
Tandem Scroll Compressors
Charging Valve
Solenoid Valve, Expansion Valve
Optional Hot Gas Bypass Valve Filter Drier
IOMM 1155 AGZ 010B through 034B 11

Glycol Solutions

The use of glycol antifreeze solutions will decrease unit capacity and increase the pressure drop through the cooler. See Product Manual Catalog ACZAGZB1 for specific ratings and correction factors.
!
CAUTION
Do not use automotive grade antifreeze. Industrial grade glycols must be used. Automotive antifreeze contains inhibitors that will cause plating on the copper tubes within the chiller evaporator. The type, storage, disposal, and handling of glycol used must be consistent with local codes.

Evaporator Water Flow and Pressure Drop

Evaporator flow rate must fall between the minimum and maximum values shown in the evaporator pressure drop curve, Figure 6. Flow rates outside of these limits result in a chilled water Delta-T
Measure the chilled water pressure drop through the evaporator at field-installed pressure taps. It is important not to include the effect of valves or strainers in these readings.
Do not vary the chilled water flow through the evaporator while the compressors are operating.
outside the operating range of the controller
.
12 AGZ 010B through 034B IOMM 1155
Figure 6, Evaporator Water Pressure Drop Curves
A
A
A
A
AGZ 010
GZ 020
GZ 025
GZ 029
GZ 034
AGZ 017
AGZ 013
Minimum Flow Nominal Flow Maximum Flow
AGZ
Model
010
013
017
020
025
029
034
Flow Rate
gpm L/s ft. kPa gpm L/s ft. kPa gpm L/s ft. kPa
15.0 0.9 2.4 7.1 24.0 1.5 5.8 17.3 40.0 2.5 15.2 45.5
19.5 1.2 1.5 4.5 31.2 2.0 3.7 11.0 52.0 3.3 9.6 28.9
24.0 1.5 1.7 5.0 38.4 2.4 4.1 12.2 64.0 4.0 10.7 32.1
30.0 1.9 2.3 6.8 48.0 3.0 5.6 16.7 80.0 5.0 14.5 43.4
34.5 2.2 1.8 5.3 55.2 3.5 4.3 13.0 92.0 5.8 11.4 34.3
40.7 2.6 1.7 5.0 65.0 4.1 4.0 12.1 108.4 6.8 10.9 32.6
49.8 3.1 1.6 4.7 79.7 5.0 3.9 11.7 132.8 8.4 10.4 31.2
Pressure
Drop
Flow Rate
Pressure
Drop
Flow Rate
Pressure
Drop
IOMM 1155 AGZ 010B through 034B 13

R-407C Units

AGZ chillers are available with R-407C refrigerant as non-ARI certified units. R-407C is a zeotropic blend of three compounds, and as such exhibits the characteristic of glide. It does not behave as one substance like R-22 does. Glide is the difference (in degrees F) between the beginning and end phase-change process in either the evaporator or condenser. During these processes, different ratios of the refrigerant’s components change phase from the beginning to the end of the process. The following functions, conditions and settings will differ from units charged with R-22.
1. Different physical data and electrical data
2. Polyolester lubricants are used instead of mineral oil.
3. The saturated pressure/temperature relationship
4. Control and alarm settings
5. Charging procedures
1. Lubrication. The units are factory-charged with polyoester (POE) lubricant and one of the
following lubricants must be used if lubricant is to be added to the system:
POEs are very hygroscopic and will quickly absorb moisture if exposed to air. Pump the lubricant into the unit through a closed transfer system. Avoid overcharging the unit.
Copeland Ultra 22 CC Mobil EAL Arctic 22 CC ICI EMKARATE RL RL 32CF
2. Pressure/temperature relationship. See Table 6 on page 15 for the saturated pressure-
erature chart. Due to refrigerant glide, use the following procedures for superheat and
p
tem subcooling measurement.
To determine superheat, only vapor must be present at the point of measurement, no liquid. Use the temperature reading, the pressure reading and the Saturated P/T Chart. If the pressure is measured at 78 psig, the chart shows the saturated vapor
50.6F. If the temperature is measured at 60F, the superheat is 9.4 degrees F.
To determine subcooling, only liquid must be present, no vapor. Use the temperature reading, the pressure reading and the Saturated P/T Chart. If the pressure is measured at 250 psig, the chart shows the saturated liquid measured at 98F, the subcooling is 10.2 degrees F.
3. Control and alarm settings. The software that controls the operation of the unit is factory-
set for operation with R-407C.
4. Charging procedure. Packaged units are factory-charged with R-407C. Remote evaporator
units have a nitrogen/helium holding charge, which must be removed prior to system charging procedure. Use the following procedure if recharging in the field is necessary:
Whether topping off a charge or replacing the circuit’s entire charge, always remove the refrigerant from the charging vessel as a liquid. Many of the cylinders for the newer refrigerants have a dip tube so that liquid is drawn off when the cylinder is in the upright position. Do not vapor charge out of a cylinder unless the entire contents will be charged into the system.
temperature to be 108.2F. If the temperature is
temperature to be
With the system in a 250-micron or lower vacuum, liquid can be charged into the high side. Initially charge about 80 percent of the system total charge.
Start the system and observe operation. Use standard charging procedures (liquid only) to top off the charge.
14 AGZ 010B through 034B IOMM 1155
It may be necessary to add refrigerant through the compressor suction. Because the refrigerant leaving the cylinder must be a liquid, exercise care to avoid damage to the compressor. A sight glass can be connected between the charging hose and the compressor. It can be adjusted to have liquid leave the cylinder and vapor enter the compressor.
Table 6, R-407C Pressure/Temperature Chart
Pressure
(PSIG)
20 -10.7 1.5 150 74.8 84.9 22 -8.2 4.0 155 76.8 86.8 24 -5.7 6.4 160 78.7 88.7 26 -3.4 8.7 165 80.6 90.5 28 -1.1 11.0 170 82.5 92.3 30 1.1 13.1 175 84.3 94.0 32 3.2 15.2 180 86.1 95.8 34 5.3 17.2 185 87.8 97.5 36 7.3 19.2 190 89.6 99.1 38 9.2 21.0 195 91.3 100.7 40 11.1 22.9 200 92.9 102.3 42 12.9 24.7 205 94.6 103.9 44 14.7 26.4 210 96.2 105.4 46 16.4 28.1 215 97.7 107.0 48 18.1 29.7 220 99.3 108.4 50 19.7 31.3 225 100.8 109.9 52 21.3 32.9 230 102.3 111.4 54 22.9 34.4 235 103.8 112.8 56 24.4 35.9 240 105.3 114.2 58 25.9 37.4 245 106.7 115.6 60 27.4 38.8 250 108.2 116.9 62 28.8 40.2 255 109.6 118.2 64 30.2 41.6 260 111.0 119.6 66 31.6 43.0 265 112.3 120.9 68 33.0 44.3 270 113.7 122.1 70 34.3 45.6 275 115.0 123.4 72 35.6 46.9 280 116.3 124.7 74 36.9 48.1 285 117.6 125.9 76 38.2 49.3 290 118.9 127.1 78 39.4 50.6 295 120.2 128.3 80 40.6 51.8 300 121.4 129.5 82 41.9 52.9 305 122.7 130.7 84 43.0 54.1 310 123.9 131.8 86 44.2 55.2 315 125.1 133.0 88 45.4 56.3 320 126.3 134.1 90 46.5 57.4 325 127.5 135.2 92 47.6 58.5 330 128.7 136.3 94 48.7 59.6 335 129.8 137.4 96 49.8 60.7 340 131.0 138.5
98 50.9 61.7 345 132.1 139.6 100 51.9 62.7 350 133.2 140.6 105 54.5 65.2 355 134.3 141.7 110 57.0 67.7 360 135.4 142.7 115 59.5 70.0 365 136.5 143.7 120 61.8 72.3 370 137.6 144.7 125 64.1 74.6 375 138.7 145.7 130 66.4 76.7 380 139.8 146.7 135 68.5 78.8 385 140.8 147.7 140 70.7 80.9 390 141.8 148.7 145 72.8 82.9 395 142.9 149.6
Liquid Temp
(°F)
Vapor Temp
(°F)
Pressure
(PSIG)
Liquid Temp
(°F)
Vapor Temp
(°F)
IOMM 1155 AGZ 010B through 034B 15

Control Layout and Operation

Control Center

All electrical controls are enclosed in a weatherproof control center with tool-locked, hinged access doors. The left-hand section contains the microprocessor controller and control input and output terminals. All high-voltage components are located on the right side of the panel.
ON/OFF Switch
MicroTech II
Controller
SpeedTrol Location
Field Connection
Termin als

Start-up and Shutdown

Pre Start-up

1. The chilled-water system should be flushed and cleaned. Proper water treatment is required to
prevent corrosion and organic growth.
2. Open all electric disconnects and check all electric connections for tightness.
3. Inspect all water piping for flow direction and correct connections at the evaporator.
4. Verify thermostat water temperature sensor is installed in the leaving water line (supply to
building). On all AGZ units the sensor well and sensor are factory mounted.
5. Check compressor oil level. The oil level should be visible in the oil sight glass.
6. Check voltage of the unit power supply and make certain voltage is within 10% of nameplate
rating. Check unit power supply wiring for proper ampacity and a minimum insulation temperature of 75C. Check for proper phasing using a phase sequence meter.
7. Verify all mechanical and electrical inspections have been completed according to local codes.
8. Open control stop switch S1(off). Turn on the main power and control disconnect switches.
This will energize crankcase heaters. Wait at least 24 hours before starting up unit.
9. Open all water flow valves and start the chilled water pump. Check all piping for leaks and
vent the air from the evaporator as well as from the system piping. Flush the evaporator and system piping to obtain clean, noncorrosive water in the evaporator.
Control Transformer
24-Volt Trans.
Non-Fused Disc.
or
Power Block
Fan Contactors
Fan Protection
Compressor Contactors

Start-up

1. Set temperature controller to the desired chilled water temperature. Set the chilled water
Delta-T.
2. Start auxiliary equipment by turning on the following: time clock (if present), ambient
thermostat and/or remote on/off switch, chilled water pump.
3. If the controller calls for cooling, the unit will begin the start-up sequence.
16 AGZ 010B through 034B IOMM 1155
4. After running the unit for a short time, check the oil level in the compressor (1/4 to 1/3 of the glass), rotation of fans, and flashing in refrigerant sight glass.
5. Verify superheat temperature is at the factory setting of 8 to 12 degrees F (4.4 to 6.7 degrees C).
After system performance has stabilized, complete the current AGZ Start-Up Form
6. (obtainable from benefits. Return the form to Daikin through your sales representative.
the local Daikin sales office) to establish inception of warranty

Sequence of Operation

Start-Up

With the control circuit power on, 115V power is applied through the control circuit fuse F1 to the compressor crankcase heaters, the compressor motor protections and the primary of the 24V control circuit transformer. The 24V transformer provides power to the microprocessor controller.
When a remote time clock, manual switch, or the unit controller turns on the chilled water pump, the flow switch closes and satisfies the flow requirement. If the chilled water temperature is above the stage-on temperature, and all equipment protection devices are closed, the unit will start. The controller will operate the unit in response to the leaving chiller water temperature or reset signals that may be present.

Equipment Protection Alarms

The following conditions will shut down the unit and activate the alarm circuit:
No evaporator water flow Low evaporator pressure High condenser pressure Motor protection system Phase voltage protection (Optional) Outside ambient temperature Evaporator freeze protection Sensor failures
The following alarms will limit unit operation:
Condenser pressure stage down, unloads unit at high discharge pressures Low ambient lockout, shuts off unit at low ambient temperatures Low evaporator pressure hold, holds stage #1 until pressure rises Low evaporator pressure unload, shuts off stage #2

Unit Enable Selection

Enables unit operation from local keypad, digital input, or Building Automation System.

Unit Mode Selection

Selects standard cooling, ice, glycol, or test operation mode.

Condenser fan control

Control of condenser fans is provided by the MicroTech II controller. The control steps condenser fans based on discharge pressure.

Shutdown

As the leaving water control is satisfied, it will stage off the lag compressor unloading the unit. The second stage will de-energize the liquid line solenoid valve SV1 and shut off the lead compressor. The compressor crankcase heaters will energize when the compressors shut off, keeping the small amount of refrigerant in the plate heat exchanger from migrating to the compressor. See page 55 for detailed explanation of compressor staging.
IOMM 1155 AGZ 010B through 034B 17

Physical Data

AGZ-BS, R-407C

Table 7, Physical Data, AGZ 010BS through 017BS, Packaged, R-407C
PHYSICAL DATA
BASIC DATA
Unit Capacity @ ARI Conditions (1), Tons (kW) 10.0 (36.2) 13.7 (48.2) 15.8 (55.6)
Number Of Refrigerant Circuits 1 1 1
Unit Operating Charge, R-407C Lb. (kg) 22.0 (10.0) 24.0 (10.9) 31.0 (14.1)
Cabinet Dimensions, LxWxH, In. 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8
Cabinet Dimensions, LxWxH, (mm) (1869) x (1176) x (1289) (1869) x (1176) x (1289) (1869) x (1176) x (1289)
Unit Operating Weight, Lb. (kg) 1095 (498) 1190 (541) 1300 (591)
Unit Shipping Weight, Lb. (kg) 1085 (493) 1170 (532) 1280 (582)
Add'l Weight If Copper Finned Coils, Lb. (kg) 176 (80.0) 176 (80.0) 264 (120.0)
COMPRESSORS
Type Scroll Scroll Scroll
Nominal Horsepower 6.0 / 6.0 7.5 / 7.5 9.0 / 9.0
Oil Charge Per Compressor of a Tandem Set, oz. (g) 60 (1701) 85 (2410) 110 (3119)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DSPLACEMENT
Standard Staging 0 – 50 – 100 0 – 50 – 100 0 – 50 – 100
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 30.3 (2.8) 30.3 (2.8) 30.3 (2.8)
Finned Height x Finned Length, In. 84 x 52 84 x 52 84 x 52
Finned Height x Finned Length, (mm) (2134) x (1321) (2134) x (1321) (2134) x (1321)
Fins Per Inch x Rows Deep: 16 x 2 16 x 2 16 x 3
Pumpdown Capacity Lb. (kg) 35.3 (16.0) 35.3 (16.0) 52.9 (24.0)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 2 – 26 (660) 2 – 26 (660) 2 – 26 (660)
Number Of Motors - HP (kW) 2 – 1.0 (0.75) 2 – 1.0 (0.75) 2 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 13950 (6584) 13950 (6584) 12000 (5664)
DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 0.9 (3.6) 1.7 (6.3) 2.0 (7.6)
Maximum Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 350 (2413) 350 (2413) 350 (2413)
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range.
010B 013B 017B
AGZ MODEL NUMBER
18 AGZ 010B through 034B IOMM 1155
Table 8, Physical Data, AGZ 020BS through 034BS, Packaged, R-407c
PHYSICAL DATA
BASIC DATA
Unit Capacity @ ARI Conditions (1), Tons (kW) 20.6 (72.4) 22.7 (79.8) 27.7 (97.5) 34.0 (119.5)
Number Of Refrigerant Circuits 1 1 1 1
Unit Operating Charge, Lb. (kg) 38.0 (17.3] 42.0 (19.1) 47.0 (21.3) 50.0 (22.7)
Cabinet Dimensions, LxWxH, In. 106.2x 46.3 x 50.8 106.2x 46.3 x 50.8 106.2x 46.3 x 58.8 106.2x 46.3 x 58.8
Cabinet Dimensions, LxWxH, (mm)
Unit Operating Weight, Lbs. (kg) 1590 (723) 1635 (743) 1830 (832) 2315 (1052)
Unit Shipping Weight, Lbs. (kg) 1570 (714) 1610 (732) 1800 (818) 2270 (1032) Add'l Weight If Copper Finned Coils, Lb. (kg)
COMPRESSORS
Type Scroll Scroll Scroll Scroll
Nominal Horsepower 12.0 / 12.0 13.0 / 13.0 15.0 / 15.0 20.0 / 20.0 Oil Charge Per Compressor of a Tandem Set,
oz. (g)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DISPLACEMENT
Standard Staging 0 –50 - 100 0 – 50 – 100 0 – 50 – 100 0 – 50 – 100
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 49.0 (4.6) 49.0 (4.6) 58.3 (5.4) 58.3 (5.4)
Finned Height x Finned Length, In. 84 x 84 84 x 84 100 x 84 100 x 84
Finned Height x Finned Length, (mm) (2134) x (2134) (2134) x (2134) (2545 ) x (2134) (2545 ) x (2134)
Fins Per Inch x Rows Deep 16 x 3 16 x 3 16 x 3 16 x 3
Pumpdown Capacity, Lb. (kg) 85.4 (38.8) 85.4 (38.8) 101.6 (46.2) 101.6 (46.2)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660) 3 – 26 (660)
Number Of Motors - HP (kW) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75) 3 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 20925 (9877) 20925 (9877) 19800 (9346) 19800 (9346)
DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 2.2 (8.2) 3.0 (11.5) 4.0 (15.1) 5.6 (21.0)
Max. Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 350 (2413) 350 (2413) 350 (2413) 350 (2413)
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range.
020B 025B 029B 034B
(2697) x (1176) x
(1289)
426 (194) 426 (194) 508 (231) 508 (231)
110 (3119) 110 (3119) 110 (3119) 158 (4479)
AGZ MODEL NUMBER
(2697) x (1176) x
(1289)
(2697) x (1176) x
(1493)
(2697) x (1176) x
(1493)
IOMM 1155 AGZ 010B through 034B 19

AGZ-BM, R-407C

Table 9, Physical Data, AGZ 010BM through 017BM, Remote Evaporator, R-407C
PHYSICAL DATA
BASIC DATA
Unit Capacity @ ARI Conditions (1), Tons (kW) 10.0 (36.2) 13.7 (48.2) 15.8 (55.6)
Number Of Refrigerant Circuits 1 1 1
Unit Operating Charge, Lb. (kg) 13 (5.9) 14 (5.3) 17 (7.7)
Cabinet Dimensions, LxWxH, In. 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8 73.6 x 46.3 x 50.8
Cabinet Dimensions, LxWxH, (mm) (1869) x (1176) x (1289) (1869) x (1176) x (1289) (1869) x (1176) x (1289)
Unit Operating Weight, Lb. (kg) 950 (431) 1276 (579) 1278 (580)
Unit Shipping Weight, Lb. (kg) 1025 (465) 1350 (613) 1363 (619)
Add'l Weight If Copper Finned Coils, Lb. (kg) [176 (80.0) [176 (80.0) [264 (120.0)
COMPRESSORS
Type Scroll Scroll Scroll
Nominal Horsepower 6.0 / 6.0 7.5 / 7.5 9.0 / 9.0
Oil Charge Per Compressor of a Tandem Set, oz. (g) 60 (1701) 85 (2410) 110 (3119)
CAPACITY REDUCTION STEPS - PERCENT OF COMPRESSOR DSPLACEMENT
Standard Staging 0 – 50 – 100 0 – 50 – 100 0 – 50 – 100
CONDENSERS - HIGH EFFICIENCY FIN AND TUBE TYPE WITH INTEGRAL SUBCOOLING
Coil Face Area, One of Two Sides, Sq. Ft. (M2) 30.3 (2.8) 30.3 (2.8) 30.3 (2.8)
Finned Height x Finned Length, In. 84 x 52 84 x 52 84 x 52
Finned Height x Finned Length, (mm) (2134) x (1321) (2134) x (1321) (2134) x (1321)
Fins Per Inch x Rows Deep [16 x 2 16 x 2 16 x 3
Pumpdown Capacity Lb. (kg) 35.3 (16.0) 35.3 (16.0) 52.9 (24.0)
CONDENSER FANS - DIRECT DRIVE PROPELLER TYPE
Number Of Fans - Fan Diameter, In. (mm) 2 – 26 (660) 2 – 26 (660) 2 – 26 (660)
Number Of Motors - HP (kW) 2 – 1.0 (0.75) 2 – 1.0 (0.75) 2 – 1.0 (0.75)
Fan And Motor RPM, 60 Hz 1140 1140 1140
60 Hz Total Unit Airflow, CFM (l/s) 13950 (6584) 13950 (6584) 12000 (5664)
REMOTE DIRECT EXPANSION EVAPORATOR - BRAZED PLATE-TO-PLATE
Water Connection Size Victaulic, In. (mm) 2 (51) 2 (51) 2 (51)
Water Volume, Gallons (L) 0.9 (3.6) 1.7 (6.3) 2.0 (7.6)
Liquid Line Conn. Braze, inches 1.125 1.125 1.125
Suction Line Conn. Braze, Inches 2.125 2.125 2.125
Temperature Sensor Conn. NPT, Inches 0.75 0.75 0.75
Dry Weight, lbs (kg) 50 (22) 75 (34) 87 (39)
Operating Weight, lbs (kg) 58 (26) 88 (40) 109 (49)
Maximum Refrigerant Working Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Maximum Water Pressure, psig (kPa) 450 (3103) 450 (3103) 450 (3103)
Vent and Drain Conn. Field Field Field
NOTE: Nominal capacity based on 95°F ambient air and 54°F/44°F water range and does not take field-installed lines into account.
010B 013B 017B
AGZ MODEL NUMBER
20 AGZ 010B through 034B IOMM 1155
Loading...
+ 46 hidden pages