AFE18-60A
ALL FUEL SYSTEM CONTROL BOARD
INSTALLATION INSTRUCTIONS
DESCRIPTION
Goodman Manufacturing Company, L.P. © 2004 - 2008
5151 San Felipe, Suite 500, Houston, TX 77056
www.goodmanmfg.com
P/N: IO-627A Date: October 2008
The AFE18 control is designed for use in heat pump
applications where the indoor coil is located above/downstream of a gas or fossil fuel furnace. It will operate with
single and two stage heat pumps and single and two stage
furnaces. The AFE18 control will turn the heat pump unit off
when the furnace is turned on. An anti-short cycle feature
is also incorporated which initiates a 3 minute timed off
delay when the compressor goes off. On initial power up or
loss and restoration of power, this 3 minute timed off delay
will be initiated. The compressor won’t be allowed to restart
until the 3 minute off delay has expired. Also included is a
5 second de-bounce feature on the “Y, E, W1 and O”
thermostat inputs. These thermostat inputs must be present
for 5 seconds before the AFE18 control will respond to it.
An optional outdoor thermostat, OT18-60A, can be used
with the AFE18 to switch from heat pump operation to
furnace operation below a specific ambient temperature
setting, i.e. break even temperature during heating. When
used in this manner, the “Y” heat demand is switched to the
“W1” input to the furnace by the outdoor thermostat and the
furnace is used to satisfy the first stage “Y” heat demand.
On some controls, if the outdoor thermostat fails closed in
this position during the heating season, it will turn on the
furnace during the cooling season on a “Y” cooling demand.
In this situation, the furnace produces heat and increases
the indoor temperature thereby never satisfying the cooling
demand. The furnace will continue to operate and can only
be stopped by switching the thermostat to the off position or
removing power to the unit and then replacing the outdoor
thermostat. When the AFE18 receives a “Y” and “O”
input from the indoor thermostat, it recognizes this as a
cooling demand in the cooling mode. If the outdoor thermostat is stuck in the closed position switching the “Y” demand
to the “W1” furnace input during the cooling mode as
described above, the AFE18 won’t allow the furnace to
operate. The outdoor thermostat will have to be replaced
to restore the unit to normal operation.
AFE18-60A INSTALLATION
The AFE18-60A should be installed on the side of the
furnace close to the 24Vac controls wires for field connections. The system must be connected in accordance with
the wiring diagram supplied with the AFE18 control and
shown in these instructions. Standard thermostat cables
can be used for wiring connections between the thermostat
and heat pump unit. See Fig. 1.
ATTENTION INSTALLING PERSONNEL
As a professional installer you have an obligation to know the product better than the customer. This
includes all safety precautions and related items.
Prior to actual installation, thoroughly familiarize yourself with this Instruction Manual. Pay special
attention to all safety warnings. Often during installation or repair it is possible to place yourself in a
position which is more hazardous than when the unit is in operation.
Remember, it is your responsibility to install the product safely and to know it well enough to be able to
instruct a customer in its safe use.
Safety is a matter of common sense...a matter of thinking before acting. Most dealers have a list of
specific good safety practices...follow them.
The precautions listed in this Installation Manual are intended as supplemental to existing practices.
However, if there is a direct conflict between existing practices and the content of this manual, the
precautions listed here take precedence.
An optional outdoor thermostat, OT18-60A, can be installed in the heat pump unit and used with the AFE18.
When used, the tab on the AFE18 control board next to the
terminal strip for the heat pump field wiring connections
must be broken for the outdoor thermostat to function with
the control. The thermostat can be field adjusted to a breakeven temperature set point appropriate for the installation.
Refer to the installation instructions provided with the
OT18-60A for the appropriate mounting location for the
heat pump unit.
OPERATION
1.0 COOLING
On heat pump units, when the room thermostat is set to the
cooling mode, 24Vac is constantly supplied to terminal “O”
of the AFE18 at the thermostat input and to the reversing
valve. The constant 24V ac at the “O” terminal of the AFE18
is a signal that the unit is in the cooling mode and its software
won’t allow the furnace to be turned on.
1.1. On a demand for cooling on a single stage heat pump,
the room thermostat energizes “Y” and “G”. This supplies 24Vac to terminals “G” and “Y” of the AFE18. If
the 3 minute anti-short delay has expired, the “Y” output to the heat pump unit will be energized and the
compressor and condenser fan will start. On ASZ two
stage heat pumps, the room thermostat energizes “Y1”
and “G”. This supplies 24Vac to terminals “G” and “Y1”
of the AFE18. If the 3 minute anti-short delay has expired, the “Y” output to the heat pump unit will be energized and the compressor will operate on low stage
and condenser fan and indoor fan will operate on low
speed.
1.2 When an “Y2” demand is initiated on ASZ two stage
heat pumps, 24Vac is supplied to terminal “Y2” of the
AFE18 and terminal “Y2” of the heat pump. The control board in the ASZ unit changes the compressor to
high stage and condenser fan and indoor fan to high
speed operation. When the “Y2” demand is satisfied,
the control board in the ASZ unit will return the compressor to low stage and condenser fan and indoor
fan back to low speed operation. On some digital/
electronic thermostats, “Y2” will remain energized
until the first stage demand “Y” is satisfied.
1.3 When the “Y” cooling demand is satisfied, the room
thermostat removes the 24Vac from terminals “Y” and
“G” and the unit turns off. The 3 minute anti-short cycle
delay is initiated for the compressor.
2.0 HEATING
On heat pump units, when the room thermostat is set to
the heating mode, the reversing valve is not energized.
This is a signal to the
AFE18 that the unit is in the heating
mode. As long as the thermostat is set for heating, the
reversing valve will be in the de-energized position for
heating except during a defrost cycle.
2.1 On a demand for heat on a single stage heat pump,
the room thermostat energizes “Y” and “G”. This supplies 24Vac to terminal “Y” of the AFE18, to the “Y”
terminal of the defrost board in the heat pump and the
to the “G” terminal of the furnace. The heat pump and
indoor fan will start in the heat mode. On a demand for
heat on an ASZ two stage heat pump the room thermostat energizes “Y1” and “G”. This supplies 24Vac
to terminal “Y1” of the AFE18, to the “Y” terminal of
the defrost board in the heat pump and to the “G” terminal of the furnace. The compressor will start in low
stage and the condenser fan and indoor fan will start
on low speed in the heat mode. As long as 24Vac is
present at terminal “Y” of the defrost board during the
heating mode, the defrost board accumulates compressor run time.
2.2 When an “Y2” demand is initiated on ASZ two stage
heat pumps, 24Vac is supplied to terminal “Y2” of the
AFE18 and terminal “Y2” of the heat pump. The control board in the ASZ unit changes the compressor to
high stage and condenser fan and indoor fan to high
speed operation. When the “Y2” demand is satisfied,
the control board in the ASZ unit will return the compressor to low stage and condenser fan and indoor
fan back to low speed operation. On some digital/
electronic thermostats, “Y2” will remain energized
until the first stage demand “Y” is satisfied.
2.2B If outdoor thermostat, OT18-60A, is used and the tem-
perature is below the set point, i.e. break even point,
the outdoor thermostat will switch the “Y” heating demand to the “W1” input to the furnace. The AFE18 will
remove the “Y” and “Y2” demands from the heat pump
if present and remove the “G” demand from the furnace. With the “Y” input to the heat pump removed,
the compressor will be turned off and the defrost board
will store the compressor’s accumulated run time in
memory. The furnace will be turned on and remain on
until the “Y” demand for heating is satisfied. The indoor blower will operate at the speed designed for furnace only operation. The unit will operate this way on
a demand for heating as long as the outdoor thermostat remains in this position.
2