Goldstar WG5005R Service Manual

Page 1
Room Air Conditioner
SERVICE MANUAL
MODELS: WG5005R
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Room Air Conditioner
SERVICE MANUAL
CAUTION
website http://www.lgservice.com
• BEFORE SERVICING THE UNIT, READ THE SAFETY PRECAUTIONS IN THIS MANUAL.
Page 2
2 Room Air Conditioner
Air Conditioner Service Manual
TABLE OF CONTENTS
Safety Precautions..........................................................................................................................................3
Dimensions .....................................................................................................................................................7
Outside Dimensions..............................................................................................................
.....................7
Product Specifications ...............................................................................................................................
...8
Installation ...............................................................................................................................
........................9
Select the Best Location ..........................................................................................................
..................9
How to Install .....................................................................................................................
.........................9
Installation Kits Contents ...............................................................................................................
..........10
How to Secure the Drain Pipe....................................................................................................................11
Operation ......................................................................................................................................................12
Feature ....................................................................................................................................................12
About the Controls of the Air Conditioner ................................................................................................13
Disassembly..................................................................................................................................................14
Mechanical Parts......................................................................................................................................14
Air Handling Parts....................................................................................................................................15
Electrical Parts .........................................................................................................................................16
Refrigerating Cycle...................................................................................................................................17
Schematic Diagram.......................................................................................................................................20
Circuit Diagram.........................................................................................................................................20
Electronic Control Device.........................................................................................................................21
Components Location(For Main P.W.B ASM)...........................................................................................22
Troubleshooting Guide.................................................................................................................................23
Piping System ........................................................................................................................................23
Troubleshooting Guide .............................................................................................................................24
Exploded View ..............................................................................................................................................32
Replacement Parts List ................................................................................................................................33
Page 3
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
Service Manual 3
Safety Precautions
Safety Precautions
To prevent injury to the user or other people and property damage, the following instructions must be followed. Incorrect operation due to ignoring instruction will cause harm or damage. The seriousness is
classified by the following indications.
Meanings of symbols used in this manual are as shown below.
WARNING
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property only.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property only.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property only.
This symbol indicates the possibility of death or serious injury.
This symbol indicates the possibility of injury or damage to property only.
WARNING
Installation
Always install the expansion panel(s).
• Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock haz­ards.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Be sure not to do.
Be sure to follow the instruction.
Installation
Always install the expansion panel(s).
• Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock haz­ards.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Be sure not to do.
Be sure to follow the instruction.
Installation
Always install the expansion panel(s).
• Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock haz­ards.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Be sure not to do.
Be sure to follow the instruction.
Installation
Always install the expansion panel(s).
• Improper assembly or installation may cause incorrect operation, including injury, fire, and electric shock haz­ards.
Do not place the power cord near a heater.
• It may cause fire and electric shock.
Be sure not to do.
Be sure to follow the instruction.
Do not use the power cord near flammable gas or combustibles such as gasoline, benzene, thinner, etc.
• It may cause explosion or fire.
Do not disassemble or modify products.
• It may cause electric shock and failure.
GasolinGasolinGasolinGasolinGasolinGasolinGasolinGasolin
CAUTION
Page 4
4 Room Air Conditioner
Safety Precautions
Plug in the power plug prop- erly.
• Otherwise, it will cause electric
shock or fire.
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
4 Room Air Conditioner
Safety Precautions
Plug in the power plug prop- erly.
• Otherwise, it will cause electric
shock or fire.
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
4 Room Air Conditioner
Safety Precautions
Plug in the power plug prop- erly.
• Otherwise, it will cause electric
shock or fire.
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
4 Room Air Conditioner
Safety Precautions
Plug in the power plug prop­erly.
• Otherwise, it will cause electric
shock or fire.
Do not operate or stop the unit by inserting or pulling out the power plug.
• It will cause electric shock or fire.
Do not damage or use an unspecified power cord.
• It will cause electric shock or fire.
Do not modify power cord length.
• It will cause electric shock or fire
Use the air conditioner on a single outlet circuit.(See page
7.) Do not share the outlet with other appliances.
Always plug into a grounded outlet.
• No grounding may cause electric
Unplug the unit if strange sounds, odors, or smoke come from it.
• Otherwise it will cause fire and
electric shock accident.
Do not use the socket if it is loose or damaged.
• It may cause fire and electric
Do not operate with wet hands or in damp environ­ment.
• It ma cause electric shock.
Operation Operation Operation Operation
ON
• It will cause electric shock or fire.
shock.
shock.
Page 5
Service Manual 5Service Manual 5Service Manual 5Service Manual 5
Close all doors, windows and other outside openings to the room.
• The air conditioner must be operated in a enclosed area to be most effective.
Ventilate before operating air conditioner when gas goes out.
• It may cause explosion, fire, and burn.
switch of the main body of appliance. Contact service center after taking the power plug ut from the socket.
• There is risk of fire or electric shock.
Do not clean the air conditioner with water.If water enters the product, turn off the power
• Water may enter the unit and degrage the insulation. It may cause an electric shock.
Installation
Never touch the metal parts of the unit when removing the filter.
• They are sharp and may cause injury.
CAUTION
Do not block the inlet or out­let.
• It may cause failure of appliance or performance deteriorate.
Ensure that the outer case is not damaged by age or wear.
• If the outer case is damaged, it must be repaired or replaced immediately. Leaving it damaged could result in the air conditioner falling out of the window, creating a safety hazard.
Page 6
Wa
x
Thinner
Wa
x
Thinner
Operation Operation
Be cautious not to touch the sharp edges when installing
• It may cause injury.
Sharp edges
Unplug the air conditioner before cleaning it.
• Since the fan rotates at high speed during operation, it may cause injury.
Hold the plug by the head when taking it out.
Unplug the air conditioner if it will not be used for a long period.
• It may cause electric shock and damage.
Do not put a pet or nouse plant where it will be exposed to direct air flow
• It will waste power consumption in vain and it may cause accident.
Do not use this appliance for special purposes such as pets, foods, precision machinery, or objucts of art.
• This could injury the pet or plant. • It is an air conditioner, not a preci­sion refrigeration system.
Always insert the filter securely. Clean it every two weeks.
• Operation without filters will cause failure.
6 Room Air Conditioner6 Room Air Conditioner6 Room Air Conditioner6 Room Air Conditioner
Use a soft cloth to clean. Do not use wax, thinner, or a strong detergent.
• The appearance of the air condi­tioner may deteriorate, change color, or develop surface flaws.
Do not drink water drained from air conditioner. Do not direct airflow at room occu­pants only.
• It is not sanitary and could cause illness or personal injury hazard.
Page 7
Service Manual 7
Dimensions
Dimensions
H
D
W
W mm(inch) 439(17 5/16")
H mm(inch) 283(11 1/8") D mm(inch) 326(12
13
/16")
Model
Dimension
All Model
Outside Dimensions
This symbol alerts you to the risk of electric shock.
This symbol alerts you to hazards that could cause harm to the air conditioner.
This symbol indicates special notes.
NOTICE
Symbols Used in this Manual
Page 8
8 Room Air Conditioner
Product Specifications
Product Specifications
SPECIFICATIONS ARE SUBJECT TO MINOR CHANGE WITHOUT NOTICE FOR FURTHER IMPROVEMENT.
8 Room Air Conditioner
Product Specifications
Product Specifications
SPECIFICATIONS ARE SUBJECT TO MINOR CHANGE WITHOUT NOTICE FOR FURTHER IMPROVEMENT.
8 Room Air Conditioner
Product Specifications
Product Specifications
SPECIFICATIONS ARE SUBJECT TO MINOR CHANGE WITHOUT NOTICE FOR FURTHER IMPROVEMENT.
8 Room Air Conditioner
Product Specifications
Product Specifications
SPECIFICATIONS ARE SUBJECT TO MINOR CHANGE WITHOUT NOTICE FOR FURTHER IMPROVEMENT.
NOTICE
COOLING CAPACITY (BTU/h) 5,050
POWER SUPPLY (Phase, V, Hz) 1ø, 115V, 60HZ
INPUT (W) 520
OPERATING CURRENT (AMP.) 4.8
REFRIGERANT CONTROL CAPILLARY TUBE
REFRIGERANT CHARGE (R-22)
205g(7.2 Oz)
INSIDE FAN TURBO
OUTSIDE FAN ROPELLER FAN WITH SLINGER RING
AIR DISCHARGE 2-WAY (RIGHT AND LEFT)
CHASSIS TOP-DOWN
PROTECTOR
TEMPERATURE CONTROL THERMISTOR
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
WG5005R
MODELS
ITEMS
COOLING CAPACITY (BTU/h) 5,050
POWER SUPPLY (Phase, V, Hz) 1ø, 115V, 60HZ
INPUT (W) 520
OPERATING CURRENT (AMP.) 4.8
REFRIGERANT CONTROL CAPILLARY TUBE
REFRIGERANT CHARGE (R-22)
205g(7.2 Oz)
INSIDE FAN TURBO
OUTSIDE FAN ROPELLER FAN WITH SLINGER RING
AIR DISCHARGE 2-WAY (RIGHT AND LEFT)
CHASSIS TOP-DOWN
PROTECTOR
TEMPERATURE CONTROL THERMISTOR
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
MODELS
ITEMS
COOLING CAPACITY (BTU/h) 5,050
POWER SUPPLY (Phase, V, Hz) 1ø, 115V, 60HZ
INPUT (W) 520
OPERATING CURRENT (AMP.) 4.8
REFRIGERANT CONTROL CAPILLARY TUBE
REFRIGERANT CHARGE (R-22)
205g(7.2 Oz)
INSIDE FAN TURBO
OUTSIDE FAN ROPELLER FAN WITH SLINGER RING
AIR DISCHARGE 2-WAY (RIGHT AND LEFT)
CHASSIS TOP-DOWN
PROTECTOR
TEMPERATURE CONTROL THERMISTOR
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
MODELS
ITEMS
COOLING CAPACITY (BTU/h) 5,050
POWER SUPPLY (Phase, V, Hz) 1ø, 115V, 60HZ
INPUT (W) 520
OPERATING CURRENT (AMP.) 4.8
REFRIGERANT CONTROL CAPILLARY TUBE
REFRIGERANT CHARGE (R-22)
205g(7.2 Oz)
INSIDE FAN TURBO
OUTSIDE FAN ROPELLER FAN WITH SLINGER RING
AIR DISCHARGE 2-WAY (RIGHT AND LEFT)
CHASSIS TOP-DOWN
PROTECTOR
TEMPERATURE CONTROL THERMISTOR
• OVERLOAD PROTECTOR FOR COMPRESSOR
• INTERNAL PROTECTOR FOR FAN MOTOR
MODELS
ITEMS
Page 9
Service Manual 9
Window Requirements
All supporting parts should be secured to firm wood, masonry, or metal.
1. This unit is designed for installation in standard double hung windows with actual opening widths of 21" to 35". The upper and lower sash must open sufficiently to allow a clear vertical opening of 12" from the bottom of the sash to the window stool.
2. If storm window presents interference, fasten a 2" wide wood strip to the inner window sill across the full width of the sill. The wood strip should be thick enough to raise the height of the window sill so that the unit can be installed without interference by the storm window frame. See Figure. 3. Top of wood strip should be approximately 3/4" higher than the storm window frame (STORM WIN­DOW FRAME) or wood strip (OUTDOORS) to help con­densation to drain properly to the outside.
3. Install a second wood strip (approximately 6" long by 11/2" wide and same thickness as first strip) in the center of the outer sill flush against the back off the inner sill. This will raise the L bracket as shown Figure. 3.
4. If the distance between STORM WINDOW FRAME and WOOD STRIP MOUNTED ON TOP OF INNER SILL is more than 1", two of wood strip are not necessary.
NOTICE
Installation
Installation
Select the Best Location
How to Install
This air conditioner is designed with a button-down chassis so it can be easily installed in a window.
1. To prevent vibration and noise, make sure the unit is installed securely and firmly.
2. Install the unit where the sun does not shine directly on
the unit.
3. The outside of the cabinet must extend outward for at
least 10" and there should be no obstacles, such as a fence or wall, within 20" from the back of the cabinet because it will prevent heat radiation of the condenser. Restriction of outside air will greatly reduce the cooling efficiency of the air conditioner.
CAUTION: All side louvers of the cabinet
must remain exposed on the outdside of the structure.
4. Install the unit slanted slightly so the back is slightly lower than the front (about 1/4"). This will force con­densed water to the outside.
5. Install the unit with the bottom about 30"~60" above the floor level.
ABOUT / "
Over 20"
HEAT
RADIATION
FENCE
AWNING
OUTSIDE
INSIDE
COOLED AIR
30"-60"
1
2
OUTDOORSINDOORS
INNER SILL
OUTER
SILL
INNER
SILL
WOOD STRIP MOUNTED
ON TOP OF INNER SILL
WOOD STRIP
FOR
L
BRACKET
3
/4"
CLEARANCE
1" MAX.
STORM
WINDOW
FRAME
OUTDOORSINDOORS
OUTER
SILL
Figure 1
Figure 2
Figure 3
Page 10
10 Room Air Conditioner
Installation
Installation Kits Contents(some Models)
Before Installation (Some Models Including Installation Kit)
1. Insert the guide panels into the guides of the air conditioner. Fasten the curtains to the unit with screws (TYPE A), as shown Figure. 4.
2. Cut the adhesive-backed seal strip (TYPE E) to the window width. Remove the backing from the seal strip and attach the seal strip to the underside of the bottom window. (Figure. 5)
Start Installation (Some Models Including Installation Kit)
1. Locating Unit in Window
Open the window and mark center line with pencil on the center of the inner sill, as shown in Figure. 6.
2. Attach L Bracket
a. Install the L brackets behind the inner window sill, with the
short side of bracket as shown. Use the 2 screws (TYPE A) provided.
b. The bracket helps to hold unit securely in place. Be sure to
place bracket edge flush against back of inner sill. See Figure.7.
HARDWARE
TYPE F: 1EA
(SASH SEAL)
(Not adhesive backed)
TYPE E: 1EA
(SEAL STRIP)
(Adhesive backed)
TYPE G: 2EA
(GUIDE PANEL)
TYPE D: 3EA
(L BACKET)
TYPE A: 14EA
(SHORT SCREW)
10mm
TYPE B: 2EA
(WOOD SCREW)
16mm
TYPE H: 1EA
(UPPER GUIDE)
16mm
TYPE C: 2EA
(WOOD SCREW)
ROOM SIDE
CENTER LINE
INNER SILL
SEAL STRIP (TYPE E)
OUTSIDE
INSIDE
L
BRACKET
OUTER SILL
INNER SILL
TYPE A
7.5"
7.5"
CENTER LINE
TYPE A
TYPE A
TYPE A
Figure 4
Figure 5
Figure 6
Figure 7
Page 11
Service Manual 11
CAUTION: During the following step, hold
unit firmly until window sash is lowered to
top channel behind side panel frames. Personal injury or property damage may result if unit falls from window.
3. Install the Air Conditioner in the Window
a. Carefully lift the air conditioner and slide it into the open win-
dow. Make sure the bottom guide of the air conditioner drops into the notches of the L bracket.
IMPORTANT :
When the air conditioner drops into the L bracket, the air conditioner will be centered in window opening as shown in Figure. 8.
b. While steadying the air conditioner, carefully bring the
window sash down behind the upper guide of the air conditioner, as shown in Figure. 9.
4. Secure the Guide Panels
Extend the guide panels (TYPE G) to fill the window opening using 2 screws (TYPE B), 2 screws(TYPE C) to secure them as shown in Figure. 10.
5. Install the Sash Seal and Sash Lock
a. Cut the sash seal (TYPE F) to the window width.
Stuff the sash seal between the glass and the window to prevent air and insects from getting into the room, as shown in Figure. 10.
b. Fasten the L bracket using a (TYPE A) screw, as
shown in Figure. 10.
6. Window installation of room air conditioner is now completed. See ELECTRICAL DATA for attaching power cord to electrical outlet.
In humid weather, excess water may cause the BASE PAN to overflow. To drain the water, remove the DRAIN CAP and secure the DRAIN PIPE to the rear hole of the BASE PAN. (Figure. 11)
Press the drain pipe into the hole by pushing down and away from the fins to avoid injury.
Installation
How to Secure the Drain pipe
hang push
1 2
DRAIN PIPE
DRAIN CAP
CENTER LINE
SEAL
WINDOW FRAME
BOTTOM GUIDE
ABOUT 1/4"
UPPER GUIDE
L
BRACKET
L BRACKET
FOAM SEAL
(
TYPE
F)
TYPE A
TYPE B
TYPE C
Figure 8
Figure 9
Figure 10
Figure 11
Page 12
12 Room Air Conditioner
Operation
Feature
Insulation Resistance Test
About the Controls of the Air Conditioner
DESIGNED FOR COOLING ONLY
POWERFUL AND INCREDIBLE COOLING
TOP-DOWN CHASSIS FOR THE SIMPLE INSTALLATION AND SERVICE
BUILT-IN ADJUSTABLE THERMOSTAT
WASHABLE ONE-TOUCH FILTER
COMPACT SIZE
1. Unplug the power cord and connect a jumper between 2 pins (black and white).
2. The grounding conductor (green or green and yellow) is to be open.
3. Measure the resistance value with an ohm meter between the jumpered lead and each exposed metallic part
on the equipment at all positions [except Off] of the ROCKER SWITCH.
4. The value should be over 1 MΩ.
Operation
CAUTION:The Remote Controller will not function properly if strong light strikes the sensor window of the air conditioner or if there are obstacles between the Remote Controller and the air conditioner.
Power
Temp
Fan Speed
Timer Mode
Auto
Swing
Page 13
Page 14
Disassemblyly
Mechanical Parts
Disassembly
NOTICE
14 Room Air Conditioner
1. FRONT GRILLE
1. Disconnect the unit from source of power.
2. Using a screwdriver, remove the screw from the front
grille. (See Figure 13)
3. Push the front grille up from the bottom.
Pull the top of the front grille away from the cabinet as the top tabs lift out of their slots. (See Figure 14)
4. Replace the grille by placing the tabs in the slots and
push the grille until it snaps into place.
2. CABINET
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to section 1)
3. Remove 10 screws that secure the cabinet to the base
pan and condenser. (See Figure 15)
4. Lift the cabinet from the unit.
5. Re-install by referring to the procedures above.
3. CONTROL PANEL
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section 2)
4. Remove 2 screws that secure the control panel to control
box and base pan. (See Figure 16)
5. Pull the control board toward yourself.
NOTICE
6. Disconnect one housing terminal and 3 wires for the fan
7. Re-install components by referring to procedures above.
Controls, wires, and capacitor are now accessi­ble for servicing. Discharge the capacitor before servicing.
motor and compressor. (See Figure 17)
(Refer to wiring diagram on page 19 in this manual or on control box.)
NOTICE
Page 15
4. AIR GUIDE UPPER
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section 2)
4. Remove the control board. (Refer to Section 3)
5. Remove tape that attached the air guide upper and
lower.
6. Lift air guide upper upward. (See Figure 18)
7. Re-install by referring to the procedures above.
5. ORIFICE, TURBO FAN AND FAN
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section 2)
4. Remove the control panel. (Refer to Section 3)
5. Remove the air guide upper. (Refer to Section 4)
6. Remove 2 screws that secure the condenser to the base pan.
7. Remove the screw that secures the shroud to channel of condenser.
8. Press the snap area of shroud with your thumbs. This allows you to remove it from the condenser.
9. Remove 1 screw that secure the evaporator to the base pan. (See Figure 19)
10. Remove the orifice by pushing the snap area of the air guide blower. (See Figure 20)
11. Remove the clamp springs which are clamped to the boss of fan and turbo fan by hand plier.
(See Figure 21)
12. Pull the fan and turbo fan outward.
13. Re-install by referring to the procedures above.
Disassembly
Air Handling Parts
Figure 19
Figure 18
Figure 20
Figure 21
Service Manual 15
Page 16
Disassembly
6. MOTOR
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section 2)
4. Remove the control panel. (Refer to Section 3)
5. Remove the air guide upper. (Refer to Section 4)
6. Remove the compressor, turbo fan, axial fan and
shroud. (Refer to Section 5)
7. Remove 4 screws that secure the motor to the mount
motor of shroud. (See Figure 22)
8. Remove the motor.
9. Re-install by referring to the procedures above.
7. AIR GUIDE LOWER AND SHROUD
1. Disconnect the unit from the power source.
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section 2)
4. Remove the control panel. (Refer to Section 3)
5. Remove the air guide upper. (Refer to Section 4)
6. Remove the compressor, turbo fan, axial fan.
(Refer to Section 5)
7. Remove the motor. (Refer to Section 6)
8. Remove 2 screws that secure the shroud to the base
pan. (See Figure 23)
9. Lift air guide lower and shroud upward.
(See Figure 23)
10. Re-install by referring to the procedures above.
8. OVERLOAD PROTECTOR
1. Remove the front grille and cabinet. (Refer to Section 1, 2)
2. Remove the nut which fastens the terminal cover.
3. Remove the terminal cover.
4. Remove all the leads from the overload protector.
5. Remove the overload protector.
6. Re-install the components by referring to the removal procedure above. (See Figure 24)
9. COMPRESSOR
1. Remove the front grille and cabinet. (Refer to Section 1, 2)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the overload protector. (Refer to Section 8)
4. After discharging the unit completely, unbrace the suction and discharge pipes at the compressor con­nections.
5. Remove 3 nuts which fasten the compressor.
6. Remove the compressor.
7. Re-install by referring to the removal procedure above. (See Figure 25)
Electrical Parts
Figure 22
Figure 23
Figure 24
Figure 25
16 Room Air Conditioner
Page 17
Disassembly Disassembly Disassembly Disassembly
Refrigerating Cycle
10. CAPACITOR
Service Manual 17
10. CAPACITOR
10. CAPACITOR
10. CAPACITOR
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
3. Discharge the capacitor by placing a 20 Kresistor
3. Discharge the capacitor by placing a 20 Kresistor
3. Discharge the capacitor by placing a 20 Kresistor
3. Discharge the capacitor by placing a 20 Kresistor across the capacitor terminals.
across the capacitor terminals.
across the capacitor terminals.
across the capacitor terminals.
4. Remove all the leads of capacitor terminals.
4. Remove all the leads of capacitor terminals.
4. Remove all the leads of capacitor terminals.
4. Remove all the leads of capacitor terminals.
5. Re-install the components by referring to the removal
5. Re-install the components by referring to the removal
5. Re-install the components by referring to the removal
5. Re-install the components by referring to the removal procedure above. (See Figure 26)
procedure above. (See Figure 26)
procedure above. (See Figure 26)
procedure above. (See Figure 26)
11. THERMISTOR
11. THERMISTOR
11. THERMISTOR
11. THERMISTOR
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
2. Remove the control panel. (Refer to Section 3)
3. Remove the main PCB inside the control box.
3. Remove the main PCB inside the control box.
3. Remove the main PCB inside the control box.
3. Remove the main PCB inside the control box.
4. Remove the thermostat.
4. Remove the thermostat.
4. Remove the thermostat.
4. Remove the thermostat.
5. Re-install the components by referrig to the 
5. Re-install the components by referrig to the 
5. Re-install the components by referrig to the 
5. Re-install the components by referrig to the  temoval procedure above.
temoval procedure above.
temoval procedure above.
temoval procedure above.
Figure 26
12. POWER CORD
1. Disconnect the unit from source of power.
1. Disconnect the unit from source of power.
1. Disconnect the unit from source of power.
1. Disconnect the unit from source of power.
2. Remove the front grille. (Refer to Section 1)
2. Remove the front grille. (Refer to Section 1)
2. Remove the front grille. (Refer to Section 1)
2. Remove the front grille. (Refer to Section 1)
3. Remove the cabinet. (Refer to Section .2)
3. Remove the cabinet. (Refer to Section .2)
3. Remove the cabinet. (Refer to Section .2)
3. Remove the cabinet. (Refer to Section .2)
Remove a screw that secures control panel to control
4.
4.
4.
4. box. (Refer to Section 3)
box. (Refer to Section 3)
box. (Refer to Section 3)
box. (Refer to Section 3)
5. Pull the power cord. (See Figure 29)
5. Pull the power cord. (See Figure 29)
5. Pull the power cord. (See Figure 29)
5. Pull the power cord. (See Figure 29)
6. Re-install by referring to procedures above.
6. Re-install by referring to procedures above.
6. Re-install by referring to procedures above.
6. Re-install by referring to procedures above.
6. Re-install by referring to the procedures above.
6. Re-install by referring to the procedures above.
6. Re-install by referring to the procedures above.
6. Re-install by referring to the procedures above.
R erating Cyc
13. CONDENSER
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
1. Remove the cabinet. (Refer to Section 2)
2. Discharge the refrigerant by using a refrigerant recovery
2. Discharge the refrigerant by using a refrigerant recovery
2. Discharge the refrigerant by using a refrigerant recovery
2. Discharge the refrigerant by using a refrigerant recovery system.
system.
system.
system.
3. Remove 2 screws which fasten the condenser.
3. Remove 2 screws which fasten the condenser.
3. Remove 2 screws which fasten the condenser.
3. Remove 2 screws which fasten the condenser. (See Figure 30)
(See Figure 30)
(See Figure 30)
(See Figure 30)
4. After discharging the refrigerant completely, unbraze the
4. After discharging the refrigerant completely, unbraze the
4. After discharging the refrigerant completely, unbraze the
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.
interconnecting tube at the condenser connections.
interconnecting tube at the condenser connections.
interconnecting tube at the condenser connections.
5. Remove the condenser.
5. Remove the condenser.
5. Remove the condenser.
5. Remove the condenser.
le
Figure 27
Figure 29
Figure 30
Page 18
Disassembly
15. EVAPORATOR
1. Remove the cabinet. (Refer to Section 2)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the air guide upper. (Refer to Section 4)
4. After discharging the refrigerant completely, unbraze the interconnecting tube at the evapo­rator connections.
5. Remove the evaporator.
6. Re-install by referring to the procedures above.
16. CAPILLARY TUBE
1. Remove the cabinet. (Refer to Section 2)
2. Discharge the refrigerant by using a refrigerant recovery system.
3. Remove the air guide upper. (Refer to Section 4)
4. After discharging the refrigerant completely, unbraze the interconnecting tube of the capil­lary tube.
5. Remove the capillary tube.
6. Re-install by referring to the procedures above.
Replacement of the refrigeration cycle.
1. When replacing the refrigerating cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.
2. After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.
3. Solder service valves into the pinch-off tube ports, leaving the valves open.
4. Solder the pinch-off tubes with service valves.
5. After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.
6. Evacuate as follows: 6-1. Connect the vacuum pump, as illustrated in
figure 31A.
6-2. Start the vacuum pump. Slowly open manifold
valves A and B with two full turns counter­clockwise and leave the valves closed. The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.
CAUTION: If high vacuum equip-
ment is used, just crack valves A
and B for a few minutes, then open
slowly with the two full turns counter-clockwise. This will keep oil from foaming and being drawn into the vacuum pump.
6-3. Operate the vacuum pump for 20 to 30 minutes,
until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes. A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.
6-4. Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure 20B. Open valve C. Discharge the line at the manifold connection.
6-5. The system is now ready for final charging.
7. Recharge as follows: 7-1. Rotary compressor systems are charged from
the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.
7-2. Connect the charging cylinder as shown in fig-
ure 31B. With valve C open, discharge the hose at the manifold connection.
7-3. Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
7-4. If more charge is required, the high-side will
not take it. Close valve A.
7-5. With the unit running, open valve B and add
the balance of the charge. a. Do not add the liquid refrigerant to the low-
side.
b. Watch the low-side gauge, allow pressure to
rise to 30 lbs(0.2MP).
c. Turn off valve B and allow the pressure to
drop.
d. Repeat steps B and C until the balance of
the charge is in the system.
7-6. When the unit is operating correctly, use the
pinch-off tool with the unit still running and the clamp on the pinch-off tube. Using a tube cut­ter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leak­age of the pinch-off connection.
NOTICE
18 Room Air Conditioner
Page 19
Disassembly
Equipment needed: Vacuum pump, charging cylinder, manifold gauge, brazing equipment, pinch-off tool capable of making a vapor proof seal, leak detector, tubing cutter, hand tools to remove components and service valve.
B
A
B
A
B
A
COMPOUND GAUGE
SEE INSETS
BELOW
CAPILLARY TUBE
EVAPORATOR (LOW PRESSURE SIDE)
COMPRESSOR
CONDENSER (HIGH PRESSURE SIDE)
EXTERNAL VACUUM PUMP
LO HI
CHARGING CYLINDER
MANIFOLD
GAUGE
C
Figure 31A-Pulling Vacuum
Figure 31B-Charging
Service Manual 19
Page 20
Schematic Diagram
Schematic Diagram
Circuit Diagram
DESCRIPTION & NAME
FAN MOTOR MAIN PCB DISPLAY TERMITOR COMPRESSOR POWER CORD ASSY
CAPACITOR OVERLOAD PROTECTOR
Q'TY
1 1 1 1 1 1 1 1
REF. NO
1 2 3 4 5 6 7 8
20 Room Air Conditioner
Page 21
WP
Vcc
Digit3 (Scan3)
Digit4 (Scan4)
Digit1 (Scan1)
Digit2 (Scan2)
Digit0 (Scan0)
MAIN POWER
COMP
HERM
FAN
C
CAPACITOR
MOTOR
FAN
120 1/2W
ZNR01J
SVC271D-14A
250V/T2A
FUSE
G4A-1A-E-LG
RY-COMP
1000
D02D~D05D
1N4004
35V
D03D
D02D
POWER TRANS
1
2
7
4
D05D
+
D04D
C01D
R01J
CN-WOR
C01J
0.1/275V
CN-BK
CN-BL
CN-RD
RY-HI
RY-LOW
RY-MED
C06D
5V
0.01
0.1
50V
16V
1000
10V
0.01
50V
50V
C04D
12V
IC01D
C03D
C02D
7812
O
I
+
220
C05D
O
IC02D
7805
+
I
C01L
680pF
1K
ULN2004A
IC01G
R01L
5V
1K
R01E
20
R02E
20K
R12F
10K
R02F
0.001
C02F
R01F
10K
C01F
0.001
ROOM-TH
PIPE-TH
SYNC
S/V-
4WAY
MOTOR
3
14
RY-SYNC
RY-4WAY
CN-4WAY
11
33
11
CN-SYNC
33
12V
RY-HI
RY-MED
ULN2004A
IC01M
9
15
16
821
12V
4 4
3
2
OR1H
RY-SYNC
RY-LOW
RY-4WAY
RY-COMP
111213
654107
OR2H
5V
12.1K
R21H
R03H
0K
12.1K
1%
1%
R22H
HVB
KEY1
LED out2
LED out1
LED out0
34 35 36
LED out3
Receiver
30
Buzzer
333231
HI
MED
ION
292827
SLIDE SW
40
KEY0
37 38 39
VDD
SEG-g
41 42 43
SEG-f
SEG-e
44
SEG-d
TMP87CH47U
MICOM
4
SEG-b
SEG-a
SEG-c
321
765
Room TH
Option2
Option1
Pipe TH
232625
24
SYNC
LOW
4WAY
COMP
202122
/Reset
Osc out
Osc in
16
VAref
VSS
1819 17 131415
TEST
11
SCL
SDA
10
9
8
Tx
12
Rx
5V
A1
3
4
GND SDA
SCL
A2
A0
1
2
EEPROM
CAT93C46
SMW250-02
1
1
2 2
CN-TH1
5V
R01B
R02H
R01H
1%
6.2K
1%
12.1K
RT8.00MG
1M
OSC01B
50V
C01A
0.01
+
C02A
1uF
10V
3
20K
R01A
6
10
AIR PURIFIER
220
R07G
710
8
9
12V
16
2
12
15
3
6
220
220
220
220
220
R03G
314
512
6 11
4 13
R05G
R06G
220
R04G
116
2 15
R01G
R02G
11
10
7
8
9
8
9
10
A/RESTART
12 6
7
11
14
13
4
5
A/SWING
g
E/SAVER
+
88 SEGMENT
GND
RECEIVER
BZ01E
-4002
PKM13EPY
Vout
Vcc
8
10V
5V
220
C22L
d d
DEFROST
f
c
FAN
DRY/HEAT
TIMER
7
1
e
f
e
2
3
d
COOL
4
5
b
Digit1
a
b f
b
cc
e
g g
a a
Digit0
5V
5V
17
1
17
1
D03F
5V
ENERGY
SAVER
SW3
D07F
TEMP UP
SW7
1K
R04P
6
5
20K
20K
R02P
8
7
R03P
5V
A101S
D02F
TIMER
SW2
D01F
FAN
SW1
TEMP DOWN
D05F
SW5
MODE
D04F
SW4
D08F
AUTO SWING
SW8
SW6
ON/OFF
D06F
14
4
2
16
3
15
A101S
Q03G
A101S
Q02G
5
13
Q01G
A101S
1
IC01A
S7136
2
3.6V
5V
Q04G
CN-DISPCN-DISP
Electronic Control Device
Schematic Diagram
Service Manual 21
Page 22
Components Location (For Main P.W.B ASM)
Trouleshooting Glwide
22 Room Air Conditioner
Page 23
Troubleshooting Guide
Troubleshooting Guide
Piping System
Following is a brief description of the important components and their function in what is called the refrigeration system. Reference should be made to Figure 32 to follow the refrigerating cycle and the flow of the refrigerant in the cooling cycle.
COOLED AIR
HOT DISCHARGED AIR
MOTOR
COMPRESSOR
ROOM AIR HEAT LOAD
CAPILLARY TUBE
(LIQUID REFRIGERANT)
LIQUID OUTLET
VAPOR INLET COMPLETE LIQUID BOIL OFF POINT
SUCTION LINE COOL LOW PRESSURE VAPOR
LIQUID PRESSURE DROP
DISCHARGE
LINE
NOT HIGH PRESSURE
VAPOR
OUTSIDE COOLING AIR FOR REFRIGERANT PASS THROUGH
EVAPORATOR COILS CONDENSER COILS
ROOM AIR CONDITIONER
CYCLE OF REFRIGERATION
HIGH PRESSURE VAPOR LIQUID REFRIGERANT LOW PRESSURE VAPOR
OIL
Figure 32
Service Manual 23
CONDENSER COILS
FAN
CAPILLARY
MOTOR
TUBE
TURBO FAN EVAPORATOR
COILS
Page 24
Troubleshooting Guide
Troubleshooting Guide
In general, possible trouble is classified in two kinds. The one is called Starting Failure which is caused by an electrical defect. The other is Ineffective Air Conditioning
caused by a defect in the refrigeration circuit and improper application.
Unit is running but cooling is ineffective.
Ineffective Cooling
Satisfactory operation with temperature difference of inlet & outlet air; 44~50°F (7~10°C)
Replacement of unit if the unit is beyond repair.
Check outdoor coil (heat exchanger) and fan operation.
Check heat load increase.
Check cold air circulation for smooth flow.
Check gas leakage.
Clean condenser.
Not on separate circuit
Check inside gas pressure.
Adjust refrigerant charge.
Malfunction of compressor.
Replacement of compressor.
Check clogging in refrigera­tion circuit.
Repair clogging in refrigeration circuit.
Dirty indoor coil (heat exchanger)
Repair gas leak.
Malfunction of fan.
Clogging of air filter.
Obstruction at air outlet.
Remove obstruction.
24 Room Air Conditioner
Page 25
Troubleshooting Guide
Fails to Start
Improper thermostat setting
Loose terminal connection
Improper wiring
Check of power source.
Drop of power voltage.
Capacitor check.
Replacement.
Check of control switch setting.
Compressor fails only to start.
Defect of compressor capacitor.
Replacement of compressor (Motor damaged).
Irregular motor insulation (Ω)
Irregular motor resistance (Ω)
Check of circuit breaker and fuse.
Gas leakage of feeler bulb of thermostat.
Check control switch.
Fan only fails to start.
Improper wiring.
Defect of fan motor capacitor.
Replacement of fan motor.
Regular but fails to start.
Replacement of compressor. (Locking of piston, metal.)
Irregular motor resistance (Ω) Irregular motor insulation (Ω)
Service Manual 25
Page 26
Troubleshooting Guide
ELECTRIC PARTS TROUBLESHOOTING GUIDE:
Possible Trouble 1
The unit does not operate.
Is the Trans input power
AC 115V?
Is the Trans output power
about AC 14V?
Is shorted the Trans. output?
Is output Voltage of IC01D
DC 12V?
Is output Voltage of IC02D
DC 5V?
Is the voltage No.18 of Micom
DC 5V?
Exchange Main P.W.B Ass'y.
Is the
connection between
Main and Display
all right?
Is the reset circuit all right?
(The No.14 of Micom
is 5V.)
Check the Fuse.
Check the wiring diagram.
Check the Main
P.W.B pattern.
Exchange the Trans.
Exchange D02D~D05D.
Exchange IC01D.
Exchange IC02D.
Exchange IC01A.
Connect connector
exactly.
Check the
P.W.B
pattern.
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
NO
YES
26 Room Air Conditioner
Page 27
Troubleshooting Guide
Is Temp.
setting set lower than Room
Temp.-0.5°C?
Is the voltage No.10
of IC01M 0V?
Exchange IC01M.
Set the Temp. setting to lower Temp.
Wait 3 Minutes
Is the Unit for 3 minutes
delay?
Exchange MAIN P.W.B Ass'y.
Is the voltage N0.7 of
IC01M DC 5V?
Check the RY-COMP.
Check the wiring
Diagram.
NO
NO
NO NO
YES
YES
YES
YES
Possible Trouble 2
The compressor does not operate.
Is the wire connection of
RY-COMP all right?
Check the RY-COMP.
Connect LEAD Wire to
RY-COMP again.
NO
YES
Possible Trouble 3
The compressor always operate.
Exchange IC01M.
Exchange IC01M.
Is the voltage NO.1 or 4
of IC01M DC 5V?
Is the voltage NO.13 or 16
of IC01M 0V?
Check the RY-Hi or RY-Lo.
Check the wiring diagram.
NO
NO
YES
YES
Possible Trouble 4
Fan does not operate.
Service Manual 27
Page 28
Troubleshooting Guide
Is the voltage of Battery
about over 2.3V?
Exchange Receiver Ass'y.
Is the connection of CN-DISP1 all right?
Is the voltage No.16
of CN-DISP1 on Main P.W.B
Ass'y DC 5V?
Exchange the battery.
Check the P.W.B pattern.
Connect connector to CN-DISP1 exactly.
NO
NO
NO
YES
YES
YES
Possible Trouble 5
Romote controller does not operate.
NO
NO
NO
NO
YES
YES
YES
Is the IC01G all right?
Is the connection of CN-DISP1 all right?
Exchange the display P.W.B Ass'y.
Exchange IC01G.
Exchange Q01G,
Q02G, Q03G, Q04G
Connect connector to CN-DISP1 exactly.
Does the Q01G,
Q02G, Q03G Q04G operate normally
on main P.W.B Ass'y?
Possible Trouble 6
It displays abnormally on Display P.W.B Ass'y.
28 Room Air Conditioner
Page 29
Troubleshooting Guide
Room Air Conditioner Voltage Limits
NAME PLATE RATING MINIMUM MAXIMUM
115V ± 10% 103.5V 126.5V
COMPLAINT CAUSE REMEDY
Fan motor will not run. No power Check voltage at outlet. Correct if none.
Power supply cord Check voltage to rotary switch. If none, check
power supply cord. Replace cord if circuit is open.
Rocker switch Check switch continuity. Refer to wiring diagram
for terminal identification. Replace switch if defective.
Wire disconnected or Connect wire. Refer to wiring diagram for connection loose terminal identification. Repair or replace loose
terminal.
Capacitor (Discharge Test capacitor. capacitor before testing.) Replace if not within ±10% of manufacturer's
rating. Replace if shorted, open, or damaged.
Will not rotate Fan blade hitting shroud or blower wheel hitting
scroll. Re-align assembly. Units using slinger ring condenser fans must
have 0.22~0.25 inch clearance to the base. If necessary, shim up the bottom of the fan motor with mounting screw(s).
Check fan motor bearings; if motor shaft will not rotate, replace the motor.
Fan motor runs. Revolves on overload Check voltage. See limits on this page.
If not within limits, call an electrician. Test capacitor.
Check bearings. Does the fan blade rotate
freely?
If not, replace fan motor. Pay attention to any change from high speed to
low speed. If the speed does not change, replace the motor.
Service Manual 29
Page 30
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Fan motor noise. Tubo Fan If cracked, out of balance, or partially missing,
replace it.
Axial Fan If cracked, out of balance, or partially missing,
replace it. Loose set screw Tighten it. Worn bearings If knocking sounds continue when running or
loose, replace the motor. If the motor hums or
noise appears to be internal while running,
replace motor.
Compressor will not run, Voltage Check voltage. See the limits on the preceding fan motor runs. page. If not within limits, call an electrician.
Wiring Check the wire connections; if loose, repair or
replace the terminal. If the wires are discon-
nected, refer to wiring diagram for identification,
and replace the wires. Check the wire connections;
If not according to the wiring diagram, correct
the connections. Rocker Switch Check for continuity, refer to the wiring diagram
for terminal identification. Replace the switch if
the circuit is open. Thermostat Check the position of knob. If not at the coldest
setting, advance the knob to this setting and
restart the unit.
Check the continuity of the thermostat. Replace
the thermostat if the circuit is open.
Capacitor (discharge Check the capacitor. capacitor before Replace if not within ±10% of manufacturers servicing.) rating, replace if shorted, open, or damaged.
Compressor Check the compressor for open circuit or
ground. If open or grounded, replace the
compressor. Overload
Check the compressor overload if externally mounted.
Replace if open. (If the compressor temperature is
high, remove the overload, cool, and retest.)
Compressor cycles on Voltage Check the voltage. See the limits on the overload. preceding page. If voltage is not within these limits,
call an electrician. Overload Check overload, if externally mounted.
Replace if open. (If the compressor temperature
is high, remove the overload, cool, and retest.)
30 Room Air Conditioner
Page 31
Troubleshooting Guide
COMPLAINT CAUSE REMEDY
Compressor cycles on Fan motor If not running, determine the cause. Replace if overload. required.
Condenser air flow Remove the cabinet, inspect the interior surface restriction of the condenser. If restricted, clean carefully
with a vacuum cleaner (do not damage fins) or
brush. Clean the interior base before
re-assembling. Condenser fins If the condenser fins are closed over a large
(damaged) area on the coil surface, head pressures will
increase, causing the compressor to cycle.
Straighten the fins or replace the coil. Capacitor Test the capacitor. Wiring Check the terminals. If loose, repair or replace. Refrigeration system Check the system for a restriction.
Insufficient cooling Air filter If restricted, clean or replace.
Unit undersized Determine if the unit is properly sized for the
area to be cooled.
Excessive noise Turbo Fan or Axial Fan Check the set screw, or clamp. If loose or miss-
ing, correct. If the tubo fan or axial fan is hitting
scroll or barrier, rearrange the air handling parts.
Copper tubing Remove the cabinet and carefully rearrange the
tubing not to contact the cabinet,
compressor, shroud, and barrier.
Service Manual 31
Page 32
Exploded View
32 Room Air Conditioner
Exploded Vie w
267110
B A E
Temp
Fan Speed
Timer Mode
Pow er
Auto
Swing
264110
15 9830
238310
W0CZZ
249950
35 4210
237200
268711-1
268711-2
349480
567480
352380-1
W48602
148000
359012
149980
135312
147582-2
147582-1
346811
352115
731 273
554030
359011
W48602
552113
35211A
352113
352380-2
749740
130410
130410
130910
C
567502
554 030
D
550140
Page 33
Replacement Parts List
Service Manual 33
Replacement Parts List
LOCATION
NO.
130410 Base Assembly,Single 3041A10040P R 352380-2 Guide,Air 5238A10026A R 352380-1 Guide,Air 5238A10025A R
349480 Orifice 4948A20031B R
148000 Supporter 4800A30012A R
149980 Shroud 4998A10028B R
359011 Fan,Axial 5900A20042A R
346811 Motor Assembly,AC 4681A20116E R
359012 Fan,Turbo 5900A20040A R
W48602 Clamp,Spring 3H02932B R
354210 Evaporator Assembly,First 5421A20176B R
554030 Condenser Assembly,First 5403A20174A R
352115 Tube Assembly,Evaporator(In) 5211A25019B R
552102 Tube,Bending 5210A31415B R
552113 Tube Assembly,Condenser(Out) 5211A21145A R
35211A Tube Assembly,Suction 5211A21228B R
352113 Tube Assembly,Discharge 5211A21305A R
554030 Compressor Set,China 2520UCAA011 R
567502 Overload Protect 6750U-L050A R
550140 Damper,Compressor 5040AR4195A R
249950 Case Assembly,Control 4995A20378F R
237200 Panel,Control 3720A30076A R
567480 Thermistor,NTC 6323A20004R R
W0CZZ Capacitor,Film,Box 0CZZA20005B R
238310 Escutcheon 3831A10038D R 268711-1 PCB Assembly,Display 6871A20449A R 268711-2 PCB Assembly,Main 6871A10129D R
264110 Power Cord Assembly 6411A20056A R
130910 Cabinet Assembly,Single 3091A10055A R
135312 Grille Assembly,Front 3531A10243A R
159830 Filter Assembly,Air Cleaner 5231A20029A R 147582-1 Louver,Vertical 4758A30041A R 147582-2 Louver,Vertical 4758A30041B R
267110 Remote Controller Assembly 6711A20034C R
749740 Guide 4974A30066B R
731273 Install Part Assembly,Single 3127A20098A R
PART NO.
WG5005R
REMARKDESCRIPTION
Page 34
P/No.: 3828A20517A
February, 2005
Printed in China
Loading...