SERVICE MANUAL provides various service information, including the mechanical and electrical
parts etc. This room air conditioner was manufactured and assembled under a strict quality control system.
The refrigerant is charged at the factory. Be sure to read the safety precautions prior to servicing the unit.
1.1 SAFETY PRECAUTIONS
1. When servicing the unit, set the ROTARY SWITCH
or POWER SWITCH to OFF and unplug the power
cord.
2. Observe the original lead dress.
If a short circuit is found, replace all parts which
have been overheated or damaged by the short
circuit.
3. After servicing the unit, make an insulation resistance test to protect the customer from being
exposed to shock hazards.
1. Unplug the power cord and connect a jumper
between 2 pins (black and white).
2. The grounding conductor (green) is to be open.
3. Measure the resistance value with an ohm meter
between the jumpered lead and each exposed
metallic part on the equipment at all the positions
(except OFF) of the ROTARY SWITCH.
• Slide-in and slide-out chassis for the simple
installation and service.
• Side air-intake, side cooled-air discharge.
1.5 CONTROL LOCATIONS
1.5.1 COOLING ONLY MODEL
• VENTILATION
The ventilation lever must be in the CLOSE position
in order to maintain the best cooling conditions.
When a fresh air is necessary in the room, set the
ventilation lever OPEN position.
The damper is opened and room air is exhausted.
• THERMOSTAT
Thermostat will automatically control the temperature
of the room. Select a higher number for a cooler
temperature in the room. The temperature is selected
by positioning the knob to the desired position.
The 5 or 6 position is a normal setting for average
conditions.
• Built-in adjustable THERMOSTAT
• Washable one-touch filter
• Compact size
• Reliable and efficient rotary compressor is equipped.
• OPERATION
Off- Turns air conditioner off.
Med Fan- Med speed fan operation without cooling.
Low Fan- Low speed fan operation without cooling.
High Cool - Cooling with high speed fan operation.
Med Cool - Cooling with med speed fan operation.
Low Cool - Cooling with low speed fan operation.
• OPERATION
Off
Low Fan
Low Cool
( ) :
( ) :
Turns the air conditioner off.
Permits the low fan speed operation
without cooling (heating).
( ) :
Permits cooling with the low fan
speed operation.
High Cool
( ) :
Permits cooling with the high fan
speed operation.
Low Heat
( ) :
Permits heating with the low fan
speed operation.
High Heat
( ) :
Permits heating with the high fan
speed operation.
• Auto Swing (For R1403/WR1210)
On: Air Swing is operated while operation knob is set to
A slight heat odor may come from the unit when
first switching to HEAT after the cooling season
is over.
This odor, caused by fine dust particles on the
heater, will disappear quickly.
LGE Internal Use Only
1.5.2 COOLING ONLY MODEL WITH REMOTE CONTROL AND TOUCH TYPE
6
6
7
7
8
8
9
9
■ M1203R
DISPLAY
32
9
6
5
1
Fan Speed
■ WM-1211
54
3
2
3
TimerMode
Energy
Saver
6
9
6
1
54
Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air
conditioner or if there are obstacles between the Remote Control unit and the air conditioner.
7
REMOTE CONTROL
Powe r
1
Temp
4
Auto
Swing
2
Powe r
1
Temp
5
Fan Speed
4
8
SleepMode
Energy
Auto
Saver
Swing
6
2
7
POWER BUTTON
To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again.
This button takes priority over any other buttons.
OPERATION MODE SELECTION BUTTON
Every time you push this button, it will toggle COOL, FAN and DRY.
ON/OFF TIMER BUTTON
Everytime you push this betton, timer is set as follows.(1Hours ➔2Hours➔ 3Hours➔ 4Hours➔ 5Hours➔ 6Hours➔
7Hours➔ 8Hours➔ 9Hours➔ 10Hours➔ 11Hours➔ 12Hours➔ Cancel)
FAN SPEED SELECTOR
Everytime you push this button, it is set as follows.
( High [
FF33
] ➔ Low[
FF11
] ➔ Med[
FF22
]➔ High[
FF33
]... )
ROOM TEMPERATURE SETTING BUTTON
This button can automatically control the temperature of the room.
The temperature can be set within a range of 16˚C to 30˚C by 1˚C.
Select the lower number for lower temperature of the room.
ENERGY SAVER
The fan stops when the compressor stops cooling.
Approximately every 3 minutes the fan will tern on and check the room air to determine if cooling is needed.
AUTO SWING
This button can automatically control the air flow direction.
SLEEP MODE BUTTON
Press the sleep mode button to set the time you want the unit to turn off automatically. The timer is programmed in one
hour increment by pressing the button. Every time you push this button, the remaining time will be set as follows.(1Hour ➔
2Hours ➔ 3Hours ➔ 4Hours ➔ 5Hours ➔ 6Hours ➔ 7Hours ➔ 0Hour ➔ 1Hour➔ 2Hours➔... )
Note: The Sleep Mode will be operated at low fan speed for quiet sleeping. The temperature will automatically rise by 1°C
over the next 30 minutes and by 2°C in 1 hour for comfortble sleeping.
Precaution: The Remote Control unit will not function properly if strong light strikes the sensor window of the air
conditioner or if there are obstacles between the Remote Control unit and the air conditioner.
POWER BUTTON
To turn the air conditioner ON, push the button. To turn the air conditioner OFF, push the button again.
This button takes priority over any other buttons.
OPERATION MODE SELECTION BUTTON
Every time you push this button, it will toggle between COOL, FAN and DRY as follows.
ROOM TEMPERATURE SETTING BUTTON
This button can automatically control the temperature of the room. The temperature can be set within a range of 60°F to
86°F by 1°F. (16°C to 30°C by 1°C)
Select the lower number for lower temperature of the room.
FAN SPEED SELECTOR
Every time you push this button, it is set as follows.
(Hi ➔ Low ➔ Mid ➔ Hi ➔ Low ➔...)
ON/OFF TIMER BUTTON
You can set the time when the unit will turn on or turn off automatically by pressing the timer button. If the unit is operating,
this button controls the time it will be turned off. If the unit is off state, this button controls the time it will start. Every time
you push this button, the remaining time will be set as follows.
This button can automatically control the air flow direction.
SLEEP MODE BUTTON
Press the sleep mode button to set the time you want the unit to turn off automatically. The timer is programmed in one
hour increment by pressing the button. Every time you push this button, the remaining time will be set as follows.(1Hour ➔
2Hours ➔ 3Hours ➔ 4Hours ➔ 5Hours ➔ 6Hours ➔ 7Hours ➔ 0Hour ➔ 1Hour➔ 2Hours➔... )
Note: The Sleep Mode will be operated at low fan speed for quiet sleeping. The temperature will automatically rise by 1°C
over the next 30 minutes and by 2°C in 1 hour for comfortble sleeping.
ENERGY SAVER
If you push this button, the fan stops when the compressor stops cooling. Approximately every 3 minutes the fan will turn
on and check the room air temperature to determine if cooling is necessary.
— Before the following disassembly, POWER SWITCH set to OFF and disconnect the power cord.
2.1 MECHANICAL PARTS
2.1.1 FRONT GRILLE
1. Open the lnlet grille upward .
2. Remove the screw which fastens the front grille.
3. Pull the front grille from the right side.
4. Remove the front grille.
5. Re-install the component by referring to the
removal procedure, above.(See Figure 1)
2.1.2 CABINET
1. After disassembling the FRONT GRILLE, remove
the 2 screws which fasten the cabinet at both
sides.
2. Remove the 2 screws which fasten the cabinet at
back.
3. Pull the base pan forward. (See Figure 2)
4. Remove the cabinet.
5. Re-install the component by referring to the
removal procedure, above.
Figure 1
Figure 2
2.1.3 CONTROL BOX
1. Remove the front grille. (Refer to section 2.1.1)
2. Remove the cabinet. (Refer to section 2.1.2)
3. Remove the 2 screws which fasten the control box
cover.
4. Remove two housings which connect compressor
wire and motor wire in the control box.
5.Discharge the capacitor by placing a 20,000
ohmresistor across the capacitor terminals.
6. Remove the 2 screws which fasten the control
box.
7. Pull the control box forward completely.
8. Re-install the components by referring to the
removal procedure, above. (See Figure 3)
(Refer to the circuit diagram found on pages
34~37 in this manual and on the control box.)
1. Remove the control box. (Refer to section 2.1.3)
2. Remove the knobs and the screw which fasten
control panel from control box.
3. Remove the screw which located in the front.
4. Open the bottom side of control box.
5. Remove the screw and the clamp which fastens
the capacitor.
6. Disconnect all the leads of capacitor terminals.
7. Re-install the components by referring to the
removal procedure, above. (See Figure 11)
2.3.4 POWER CORD
1. Remove the control box. (Refer to section 2.1.3)
2. Open the control box. (Refer to section 2.3.3)
3. Disconnect the grounding screw from the control
box.
4. Disconnect the 2 receptacles.
5. Remove a screw which fastens the clip cord.
(See Figure 12)
6. Remove the power cord.
7. Re-install the component by referring to the above
removal procedure, above.
(Use only one ground-marked hole for ground
connection.)
8. If the supply cord of this appliance is damaged, it
must be replaced by the special cord. (The
special cord means the cord which has the same
specification marked on the supply cord attached
at the unit.)
Figure 11
Figure 12
2.3.5 THERMOSTAT
1. Remove the control box. (Refer to section 2.1.3)
2. Open the control box. (Refer to section 2.3.3)
3. Remove the 2 screws which fasten the thermostat.
4. Disconnect 2 leads of thermostat terminals.
5. Remove the thermostat.
6. Re-install the components by refereing to the
above removal procedure. (See Figure 13)
2.3.6 ROTARY SWITCH
1. Remove the control box. (Refer to section 2.1.3)
2. Open the control box. (Refer to section 2.3.3)
3. Remove the 2 screws which fasten the rotary
switch.
4. Disconnect all the leads of the rotary switch
terminals.
5. Remove the rotary switch.
6. Re-install the components by referring to the
above removal procedure. (See Figure 14)
2. Remove the evaporator. (Refer to section 2.2.1)
3. Remove the orifice. (Refer to section 2.2.1)
4. Remove the blower. (Refer to section 2.2.1)
5. Remove the fan. (Refer to section 2.2.2)
6. Remove the control box cover and disconnect 5 or
4 wires of motor housing. (Refer to section 2.1.3)
7. Remove the 2 or 4 screws which fasten the motor
from the mount motor. (See Figure 15)
8. Remove the motor.
9. Re-install the components by referring to the
removal procedure, above.(See Figure 15)
2.4 REFRIGERATING CYCLE
CAUTION
Discharge the refrigerant system using a
FreonTMRecovery System.
If there is no valve to attach the recovery
system, install one (such as a WATCO A-1)
before venting the FreonTM. Leave the valve in
place after servicing the system.
2.4.1 CONDENSER
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 4 screws which fasten the
brace.(Refer to section 2.2.1)
3. Remove the 5 screws which fasten the condenser
and shroud.
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the condenser
connections.
5. Remove the condenser.
6. Re-install the component by referring to notes.
(See Figure 16)
Figure 15
Figure 16
2.4.2 EVAPORATOR
1. Remove the cabinet. (Refer to section 2.1.2)
2. Remove the 2 screws which fasten the evaporator.
3. Move the evaporator sideways carefully.
(Refer to section 2.2.1)
4. After discharging the refrigerant completely,
unbraze the interconnecting tube at the evaporator
connections.
5. Remove the evaporator.
6. Re-install the component by referring to notes.
(See Figure 17)
2. After discharging the refrigerant completely,
unbraze the interconnecting tube at the capillary
tube.(See caution above)
NOTES
— Replacement of the refrigeration cycle.
1. When replacing the refrigeration cycle, be sure to
Discharge the refrigerant system using a Freon
recovery System.
If there is no valve to attach the recovery system,
install one (such as a WATCO A-1) before venting
the FreonTM. Leave the valve in place after
servicing the system.
2. After discharging the unit completely, remove the
desired component, and unbraze the pinch-off
tubes.
3. Solder service valves into the pinch-off tube ports,
leaving the valves open.
4. Solder the pinch-off tubes with Service valves.
5. Evacuate as follows.
1) Connect the vacuum pump, as illustrated figure
18A.
2) Start the vacuum pump, slowly open manifold
valves A and B with two full turns
counterclockwise and leave the valves open.
The vacuum pump is now pulling through valves
A and B up to valve C by means of the manifold
and entire system.
CAUTION
If high vacuum equipment is used, just crack
valves A and B for a few minutes, then open
slowly with the two full turns counterclockwise.
This will keep oil from foaming and being
drawn into the vacuum pump.
3) Operate the vacuum pump for 20 to 30 minutes,
until 600 microns of vaccum is obtained. Close
valves A and B, and observe vacuum gauge for
a few minutes. A rise in pressure would
indicate a possible leak or moisture remaining in
the system. With valves A and B closed, stop
the vacuum pump.
4) Remove the hose from the vacuum pump and
place it on the charging cylinder. See figure
18B.
Open valve C.
Discharge the line at the manifold connection.
5) The system is now ready for final charging.
TM
3. Remove the capillary tube.
4. Re-install the component by referring to notes.
6. Recharge as follows :
1) Refrigeration cycle systems are charged from
the High-side. If the total charge cannot be put
in the High-side, the balance will be put in the
suction line through the access valve which you
installed as the system was opened.
2) Connect the charging cylinder as shown in figure
18B.
With valve C open, discharge the hose at the
manifold connection.
3) Open valve A and allow the proper charge to
enter the system. Valve B is still closed.
4) If more charge is required, the high-side will not
take it. Close valve A.
5) With the unit running, open valve B and add the
balance of the charge.
a. Do not add the liquid refrigerant to the Low-
side.
b. Watch the Low-side gauge; allow pressure to
rise to 30 lbs.
c. Turn off valve B and allow pressure to drop.
d. Repeat steps b. and c. until the balance of the
charge is in the system.
6) When satisfied the unit is operating correctly,
use the pinch-off tool with the unit still running
and clamp on to the pinch-off tube. Using a tube
cutter, cut the pinch-off tube about 2 inches from
the pinch-off tool. Use sil-fos solder and solder
pinch-off tube closed. Turn off the unit, allow it to
set for a while, and then test the leakage of the
pinch-off connection.