Glowworm Ultimate 70FF, Ultimate 80FF Installation & Servicing Instructions Manual

Page 1
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
One Contact Total Service
Customer Services: Tel: (01773) 828100 Fax: (01773) 828070
Installation & Servicing Instructions
220683B.11.96
To be left with the user
70FF 80FF
GC 41 319 86 GC 41 319 60
4098
Fanned Flue Boiler
Reference in these instructions to British Standards Regulations/Requirements apply only to the United Kingdom.
For Ireland the rules in force must be used.
This is a Cat I2H Appliance
BS 6332 BS 5258
Page 2
2
220683B
SIDE ELEVATION FRONT ELEVATION
B
AP
C
D
E
J
L
M
C
L
D
N
F
G
H
PUMPED
RETURN
PUMPED
FLOW
K
0075(a)M
WATER CONNECTIONS 22mm COPPER PIPE
GAS CONNECTIONS RC
1
/2 (1/2 in. BSPT)
MODEL A B C D E F G H J K L M N P
80FF 70 300 63 146 78 360 146 94 700 574 14 63 130 38
Diagram 1.1
1 G e n e r a l
The instructions consist of two parts, Installation and Servicing Instructions and Instructions for Use, which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
Important Notice
This boiler is for use only on G20 gas. This boiler can be used on open vented or sealed water
systems. When used on an open vented system domestic hot water
can only be provided by a pumped circulation. Wherever possible, all material, appliances and
components used shall comply with requirements of applicable British Standards.
Where no British Standards exist, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
Sheet Metal Parts
WARNING. When installing or servicing this boiler care should be taken when handling sheet metal parts, to avoid any possibility of personal injury.
1.1 Statutory Requirements
The installation of the boiler must be carried out by a competent person in accordance with the relevant requirements of the current issue of:
The manufacturer’s instructions, supplied. The Gas Safety (Installation and Use) Regulations, The
Building Regulations, Local Water Company Byelaws, The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH), The Electricity at Work Regulations and any local regulations which may apply.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice.
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
All dimensions are given in millimetres (except as noted)
Page 3
3
220683B
1.2 Data
See Table 1 and diagram 1.1. All dimensions are given in millimetres (except as
noted).
1.3 Range Rating
This boiler is range rated and may be adjusted to suit individual system requirements.
Table 2 gives the ratings and settings.
1 G e n e r a l
DATA TABLE 1. MODEL TOTAL DRY
WEIGHT (Including Terminal)
LIFT WEIGHT
WATER CONTENT
GAS CONNECTION
ELECTRICITY RATING
WATER CONNECTION
ELECTRICITY SUPPLY
DATA LABEL
70FF/80FF
51 kg (112 lb)
45.3 kg (100lb)
3.35 litre (0.74 gallon)
Rc 1/2 in.
71W
Internal fuse F1A
2x22mm copper pipes from
top of case
240V~50Hz, fused 3A
Bottom right hand side of case
TABLE 2. 80FF RANGE RATING NOMINAL kW
HEAT INPUT Btu/h
NOMINAL kW HEAT OUTPUT Btu/h
BURNER m bar SETTING PRESSURE in. w.g.
APPROX. m3/h GAS RATE ft3/h
Min. Medium Max.
25.97 27.65 29.31
88,600 94,300 100,000
20.52 21.98 23.45
70,000 75,000 80,000
12.8 14.5 16.3
5.1 5.8 6.5
2.4 2.6 2.7 86 92 97
BURNER INJECTOR MARKING: 205710 BURNER INJECTOR SIZE: 4.0 mm PILOT INJECTOR MARKING: 7218
TABLE 2. 70FF RANGE RATING NOMINAL kW
HEAT INPUT Btu/h
NOMINAL kW HEAT OUTPUT Btu/h
BURNER m bar SETTING PRESSURE in. w.g.
APPROX. m3/h GAS RATE ft3/h
Min. Medium Max.
22.39 24.03 25.64
76,400 82,000 87,500
17.58 19.05 20.52
60,000 65,000 70,000
13.3 15.3 17.2
5.3 6.1 6.9
2.0 2.2 2.4 74 80 85
BURNER INJECTOR MARKING: 205701 BURNER INJECTOR SIZE: 3.8 mm PILOT INJECTOR MARKING: 7218
Page 4
4
220683B
1.4 B.S.I. Certification
This boiler is certificated to the current issue of British Standard 6332 Part 1, invoking the current issue of BS5258 Part 1 for performance and safety. It is, therefore, important that no alteration is made to this boiler without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the B.S.I. Certification of the boiler, warranty and could infringe the current issue of the Statutory Requirements.
CE Mark
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
1.5 Gas Supply
The gas installation shall be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
On completion test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
1.6 Electrical Supply
WARNING. This boiler must be earthed. All system components shall be of an approved type and
shall be connected in accordance with the current issue of BS7671 and any applicable local regulations.
Connection of the boiler and system controls to the mains supply must be through a common isolator and must be fused 3A, maximum. This method of connection must be by a fused double pole isolating switch, with a minimum contact separation of 3mm on both poles. The switch should be readily accessible and preferably adjacent to the appliance. It should supply the appliance only and be easily identifiable as so doing.
Alternatively, an unswitched shuttered socket outlet and 3A fused 3 pin plug, both to the current issue of BS1363 may be used provided that they are not used in a room containing a bath or shower.
Wiring to the boiler must be to the current issue of BS6500 Table 16, not less than 0.75mm2 (24/0.20mm).
1 General
1.7 Contents of Packaging
The boiler is delivered in one pack, refer to Section 4.1 for contents.
1.8 Water System
This boiler may be fitted to an open vented or a sealed water system.
1.9 Drain
System
A draining tap must be provided at the lowest points of the system which will allow the entire system, boiler and hot water cylinder be drained.
Draining taps should be to the current issue of BS2879.
Boiler
A draining point is fitted at the bottom right hand side of the heat exchanger.
Cover controls to avoid water damage. If required remove combustion chamber front cover to
improve access.
1.10 Safety Valve
A safety valve need not be fitted to an open vented system.
1.11 Location
This boiler is not suitable for outdoor installation. This boiler may be installed in any room, although
particular attention is drawn to the requirements of the current issue of BS7671 with respect to the installation of a boiler in a room containing a bath or shower. The electrical provisions of the Building Standards (Scotland) apply to such installations in Scotland.
The boiler must be mounted on a flat wall which is sufficiently robust to take its total weight.
The boiler may be fitted to a wall made of combustible material.
Page 5
5
220683B
1.12 Boiler Clearances
Refer to diagram 1.2. This boiler must be positioned so that at least the
minimum operational and servicing clearances are provided.
Additional clearances may be required for installation. If fixtures are positioned next to the boiler they should
be made removable for access to pipework. At least a minimum of 500mm clearance must be left in
front of the boiler for servicing, see diagram 1.2.
1.13 Room Ventilation
The boiler is room sealed and does not require the room or space containing it to have permanent air vents.
1.14 Boilers in a Compartment
Where the installation of the boiler will be in an unusual position, special requirements are needed, the current issue of BS6798 gives detailed guidance on these requirements.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. An existing cupboard or compartment modified for the purpose may be used. Details of essential requirements for cupboard or compartment design are given in the current issue of BS6798.
The doorway opening should be of sufficient size to allow for easy removal of the boiler.
Where the boiler is fitted in a cupboard or compartment, permanent high and low level ventilation must be provided. The minimum ventilation areas required are given in Table 3.
1.15 Timber Frame Building
If the boiler is to be installed a timber frame building it should be fitted in accordance with the British Gas publication “Guide for Gas Installation in Timber Framed Housing”, reference DM2. If in doubt seek advice from the local gas undertaking or Hepworth Heating Ltd.
1 General
Diagram 1.2
MINIMUM CLEARANCES FROM WALLS CEILING, FLOOR, CUPBOARD, WORKTOPS, AND INFLAMMABLE MATERIALS
500mm
Additional clearances may be required for installation
65mm
6mm6mm
FRONT
VIEW
100mm
0081M
SIDE OR REAR FLUE 5mm
5mm
TABLE 3. COMPARTMENT AIR VENTS
VENTILATION HIGH LEVEL LOW LEVEL REQUIREMENTS VENT AREA VENT AREA
VENTILATION FROM ROOM OR SPACE
VENTILATION FROM OUTSIDE
MODEL
cm
2
in
2
cm
2
in
2
80FF 264 41 264 41 70FF 231 35 231 35
80FF 264 41 264 41 70FF 231 35 231 35
80FF 132 21 132 21 70FF 116 18 116 18
80FF 132 21 132 21 70FF 116 18 116 18
Page 6
6
220683B
Note. Detailed recommendations for flue are given in the current issue of BS5440 Part 1.
2.1 Terminal Position
The minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in diagram 2.1.
The terminal must be exposed to the external air, the position allowing free passage of air across it at all times.
Car ports or similar extensions of a roof only, or a roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if it is made of plastic sheeting. If the car port consists of a roof and two or more walls, seek advice from the local gas company before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering or painted soffit an aluminium shield 1500mm long should be fitted immediately beneath the guttering or eaves. If the terminal is fitted within 450mm below painted eaves or a painted gutter, an aluminium shield 750mm long should be fitted immediately beneath the guttering or eaves.
2.2 Terminal Guard
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal.
A suitable guard, reference Type “K3”, can be obtained from:
Tower Flue Components Ltd., Morley Road, Tonbridge, Kent. TN9 1RA
Diagram 2.1
2 F l u e a n d V e n t i l a t i o n
MINIMUM SITING DIMENSIONS FOR FANNED FLUE TERMINALS POSITION
A DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING 300 B BELOW GUTTER, DRAIN/SOIL PIPE 75 C BELOW EAVES 200 D BELOW A BALCONY OR CAR PORT 200 E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 75 F FROM INTERNAL OR EXTERNAL
CORNERS 300 G ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300 H FROM A SURFACE FACING THE
TERMINAL 600
I FACING TERMINALS 1200
J FROM OPENING (DOOR/WINDOW) IN
CAR PORT INTO DWELLING 1200 K VERTICAL FROM A TERMINAL 1500 L HORIZONTALLY FROM A TERMINAL 300
MINIMUM SPACING
in mm
0103M
A
A
F
G
E
A
G
G
G
B,C
B,C
F
F
K
K
K
C
G
L
L
Under Car Port etc.
H,I
J
D
F
K
0161M
Page 7
7
220683B
The installation of the boiler must comply with the requirements of the current issue of BS6798.
3.1 Frost Protection
If the position of the boiler is such that it may be vulnerable to freezing it should be protected as specified in the current issue of BS5422. It is recommended that a frost protection thermostat be fitted.
3.2 Pump
The pump, with integral valves, should be fitted in the heating flow pipework from the boiler, it should be set to produce a temperature difference of 11oC (20oF) between the flow and return, with the boiler thermostat set at “MAX”, which is about 82oC (180oF).
The pressure loss of the boiler can be found from diagram 3.1.
High resistance microbore systems may require a higher duty pump.
3.3 Bypass - Fully Pumped and Sealed Water System
A bypass MUST be fitted to a fully pumped and sealed water systems.
Where the water system allows the boiler and pump to operate on bypass only, the bypass connection must be at least 2.5metres away from the boiler.
The flow through the boiler must not be allowed to fall such that there is a temperature difference greater than 20oC between flow and return.
3 W a t e r S y s t e m s
1000
750
500
250
0
0 5 10 15 20 25 30
Flow rate (litres/minute)
Water pressure loss
(mm head of water)
PRESSURE LOSS OF BOILER 80FF
0088(a)M
30.6
litre/min
Design Flow Rate
The intersection point indicates the Flow Rate required to achieve 110C temperature difference.
Diagram 3.1
PRESSURE LOSS OF BOILER
30.6
LITRE/MIN
Page 8
8
220683B
3.4 Water System
For an open vented system the boiler must be supplied from an unrestricted water supply taken from a feed and expansion cistern fitted at a maximum height of 27metres above the boiler.
The cold feed must be 15mm minimum size. It is important that the relative positions of the pump,
cold feed and open vent are as shown in diagram 3.2. The unrestricted open vent from the boiler must rise
continuously to discharge over the feed and expansion cistern.
3.5 Domestic Hot Water System
General. The domestic hot water service must be in accordance with the current issue of BS5546, refer also to the current issue of BS6700.
3.6 Cylinder
For all systems supplying domestic hot water the cylinder must be indirect. It is recommended that the cylinder be fitted with some form of temperature control.
3.7 Fully Pumped Domestic Hot Water
The connection for this type of system MUST be as shown in diagram 3.2 and 3.3.
3 W a t e r S y s t e m s
Diagram 3.2
0089M
FEED AND EXPANSION CISTERN
22mm VENT (MIN.)
15mm (MINIMUM) COLD FEED
OPEN VENTED FULLY PUMPED WATER SYSTEM RECOMMENDED RELATIONSHIP BETWEEN PUMP COLD FEED AND VENT
450mm MIN. HEIGHT
1150mm MIN.
RETURN
FLOW
CYLINDER
PUMP
HEATING
150mm MAX.
There must always be a cold water path to the return connection of the boiler.
BOILER
22mm (MINIMUM) BY-PASS WITH LOCKSHIELD VALVE
FLOW
RET.
Page 9
9
220683B
3.8 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593 on the use of inhibitors in central heating systems.
If an inhibitor is to be used, contact a manufacturer or Hepworth Heating Ltd., for their recommendations as to the best product to use.
When installing in an existing system take special care to drain the entire system, including radiators, then thoroughly cleaning out before installing the boiler whether or not adding an inhibitor.
3 W a t e r S y s t e m s
Diagram 3.3
FLOW
RETURN
1metre Min.
27 metres
Max.
22mm VENT & 15mm COLD FEED TO BE FITTED IN ACCORDANCE WITH BS 5449
INDIRECT CYLINDER
ALTERNATIVE SYSTEM CONTROL VALVES
HEATING SYSTEM
PUMP
FULLY PUMPED CIRCULATION BYPASS (DIAGRAMMATIC)
0091(b)M
BYPASS 22mm MIN WITH LOCKSHIELD VALVE
4114
22 x 28 UNION CONNECTION
28mm PIPE
Page 10
10
220683B
3 LITRES (0.66 gals) MAKE-UP BOTTLE (if required)
NON-RETURN VALVE
AUTO AIR VENT
FLOW
DRAIN COCK
BOILER
SAFETY VALVE
(Make-up alternatives)
EXPANSION VESSEL
PRESSURE GAUGE
CIRCULATING PUMP
FILLING POINT
AIR RELEASE POINT
HEATING
CIRCUIT
22mm (min) BY-PASS WITH LOCKSHIELD  VALVE 
RETURN
Diagram 3.4
3.9 Sealed Water Systems
The installation should comply with the appropriate requirements of the current issue of BS4841, BS5449, BS6759, BS6798 and BS7074 Part 1 and 2, see diagram
3.4 for suggested layout.
3.10 Safety Valve
A safety valve must be fitted to a sealed water system. It shall be preset, nonadjustable with a lift pressure of
3bar, incorporating seating of a resilient material, a test device and a connection for drain.
The drain from the safety valve must be routed clear of any electrical fittings and positioned so that any discharge can be seen.
3.11 Expansion Vessel
A diaphragm type expansion vessel, conforming to the current issue of BS4814 (see also BS7404 Part 1 and 2) must be connected at a point close to the inlet side of the circulating pump, see diagram 3.4 unless laid down differently by the manufacturer.
The expansion vessel volume depends upon the total water system volume and the initial system design pressure. For any system an accurate calculation of the vessel size is given in the current issue of BS7074 Part 1.
Example. For an initial system design pressure of 0.7bar the minimum total vessel volume required is 0.063xTotal System volume.
Note. A higher initial design pressure requires a larger volume expansion vessel.
Guidance on vessel sizing is also given in the current issue of BS5449 and BS7074 Part 1.
The charge pressure must not be less than the static head of the system, that is, the height of the highest point of the system above the expansion vessel.
The water content of the boiler is given in Data Table 1.
3 W a t e r S y s t e m s
5814
Page 11
11
220683B
3.12 Pressure Gauge
A pressure gauge with a set pointer and covering at least the range 0 to 4bar (0 to 60lb/in2) shall be permanently fitted to the system in a position where it can be seen when filling the system.
3.13 Domestic Hot Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE.
The domestic hot water cylinder must be of the indirect coil type. It must be suitable for working at a gauge pressure of 0.35bar above the safety valve setting.
3.14 Domestic Hot Water System ­Unvented
Where a storage system will not have a vent to atmosphere the installation must comply with Building Regulations and local Water Company Bye-laws, see also the current issue of BS6700.
If fitting into an existing system the local authority must also be advised.
3.15 Filling a Sealed Water System
Provision for filling the system at low level must be made. Three methods are shown in diagram 3.5. There must be no permanent connection to the mains water supply, even through a non-return valve.
3.16 Water Makeup
Provision must be made for replacing water lost from the system. A make up vessel mounted above the highest point of the system and connected through a non-return valve to the system on the return side of either the hot water cylinder or heating system, see diagram 3.4.
Alternatively provision for make up can be made by a filling loop.
METHOD 1
METHOD 2
METHOD 3
SUPPLY STOP VALVE
SUPPLY PIPE
HOSE UNIONS
SERVICING VALVE
TEMPORARY HOSE
HEATING SYSTEM
HEATING SYSTEM
TEMPORARY HOSE
HOSE UNIONS
SERVICING VALVE
SUPPLY PIPE
SUPPLY STOP VALVE
DOUBLE CHECK VALVE ASSEMBLY
HEATING SYSTEM
SERVICING VALVE
SUPPLY STOP VALVE
SUPPLY PIPE
HOSE UNIONS
DOUBLE CHECK VALVE ASSEMBLY
OVERFLOW
CISTERN
COMBINED CHECK VALVE AND VACUUM BREAKER
PRESSURE REDUCING VALVE
0051M
Diagram 3.5
3 W a t e r S y s t e m s
Page 12
12
220683B
Diagram 4.1
Diagram 4.2
Diagram 4.3
Standard Flue terminal illustrated.
Standard Flue terminal illustrated.
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
REAR FLUE LENGTHS
Distance R = Wall thickness
STD. 75mm to 685mm 1M 75mm to 1015mm 2M 75mm to 2015mm 3M 75mm to 2995mm
SIDE FLUE LENGTHS
Distance S = External wall face to boiler case
STD. 81mm to 693mm 1M 81mm to 1023mm 2M 81mm to 2023mm 3M 81mm to 3003mm
4791
4125
4126
CARTON TOP
WALL TEMPLATE
LOOSE ITEMS PACK
MOUNTING BRACKET
INSTRUCTIONS
BOILER
4.1 Unpacking
Open the carton, check the items supplied against the boiler pack contents list on the flap, see diagram 4.1.
4.2 Flue Position and Length
Determine flue application, length and terminal position before starting.
Refer to diagram 4.2 or 4.3. If you are using a Flue Bend or a Vertical Flue Kit,
please follow the instructions supplied with that kit. To make a neat finish to the flue outlet a flue collar kit,
part No. 443286, with instructions, is available. The use of this collar will mean that the flue lengths will
need to be altered, full instructions are given in the kit.
Page 13
13
220683B
4.3 Flue Preparation
All flue assemblies are designed for initial installation, given that there is sufficient clearance opposite to the flue for the installation of the flue.
If there is insufficient clearance the flue can be installed externally from outside.
For a wall thickness up to 300mm provided there is sufficient space available, the flue can be fully installed from the inside.
For a wall thickness of over 300mm the external flue hole will need to be made good from the outside.
4.4 Rear and Side Flue Application
Select the boiler location and flue application, with due regard to the terminal position.
Take the template from the boiler pack and temporarily position it on the wall, making sure that the minimum clearances are maintained, see diagram 1.2.
For a rear flue mark the position of the flue as diagram 4.4.
For a side flue, extend the centre line horizontally left or right to the corner adjacent surface where the flue is required to exit to outside. Mark the position of the centre of the flue and boiler, see diagram 4.4.
4.5 Flue Hole Cutting
Having marked out the flue centre cut a hole for the flue using, preferably, a 115mm minimum core drill.
4.6 Wall Sleeve
If the wall thickness “Q” is less than 300mm cut the wall sleeve to the required length, see diagram 4.5.
Fit the wall sleeve. Make good around the wall sleeve at both internal and
external wall faces, through the wall sleeve if internal access only is available.
If the wall thickness “Q” is greater than 300mm the wall sleeve must be fitted flush with the INSIDE wall face. If the inner end of the sleeve sticks out into the cavity then, if desired, the wall sleeve can be trimmed back to the depth of the inner skin of brickwork. Make good at the internal wall face but leave the external wall face until the flue has been fitted.
Diagram 4.4
SIDE FLUE
REAR FLUE
75mm
115mm MINIMUM HOLE
0098M
BOILER CENTRE LINE
FLUE CENTRE LINE
14mm
300mm MAX LENGTH
Q
Q
Diagram 4.5
4443
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
WALL SLEEVE
Page 14
14
220683B
Reposition the template, making sure of dimensional alignment with the flue hole.
Mark the boiler fixing points and mounting bracket position, see diagram 4.6.
Drill holes and plug, to suit No.12x2in woodscrews, fit the screws allowing sufficient clearance, about 5mm, to accept the swing brackets, see diagram 4.6.
Secure the mounting bracket to the wall with No.12x2in woodscrews and plugs, see diagram 4.6.
4.7 Flue Duct
Mark the duct to the length required, this length allows for expansion, see diagram 4.7 for rear flue and diagram
4.8 for side flue, then cut square and remove any burrs.
4.8 Air Duct/Terminal
Mark the duct length, see diagram 4.9 for rear flue and diagram 4.10 for side flue, then cut square and remove any burrs.
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
Diagram 4.6
5mm
7 dia.
BOILER CENTRELINE
7 dia.
NO. 12x2in.
3
/16in. dia.
PLUG
TOP BOILER MOUNTING HOLES
TEMPLATE
BOILER MOUNTING BRACKET
FLUE CENTRELINE
MOUNTING BRACKET FIXING POINTS
BOILER CENTRELINE
FLUE CENTRELINE
4096
NO. 12x2in.
3
/16in. dia.
PLUG
Page 15
15
220683B
Diagram 4.7
Diagram 4.8
Diagram 4.9
Diagram 4.10
STANDARD FLUE TERMINAL
Q
BOILER
CENTRE
LINE
BOILER
CENTRE
LINE
Q
T MINUS 188mm
Q PLUS 5mm
LONG FLUE TERMINAL
LONG FLUE TERMINAL
STANDARD FLUE TERMINAL
FLUE DUCT
4128
4130
4127
4129
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
Page 16
16
220683B
4.9 Air Duct/Terminal and Flue Duct Assembly
Locate the flue duct into the air duct/terminal, see diagram 4.11.
Take the flue manifold from the loose items pack together with the sealant. Place the sealant onto the flue manifold.
Fully locate the flue manifold in to the air duct/terminal and flue duct assembly as shown in diagram 4.11, make sure the correct alignment of the “Top”s.
Drill two 3mm diameter holes through the air duct/ terminal to the flue manifold secure with the two self tapping screws supplied in the loose items pack.
It should now not be possible to remove the manifold.
4.10 Wall thickness up to 300mm
Fit the self adhesive foam seal provided in the loose items pack around the air duct/terminal at the position shown in diagram 4.12.
4.11 Wall thickness over 300mm
Fit the self adhesive foam seal around the air duct/ terminal such that, when installed, the seal will be within the wall sleeve, see diagram 4.12.
4.12 Flue Assembly - Installation
If the boiler is not to be fitted for some time cover the hole in the wall.
On limited access installations push the flue assembly into and through the wall sleeve and hole such that it is within the wall sleeve and does not stick out into the room. see diagram 4.13. Do not push the flue assembly too far into the holes as it has to be pulled back into the boiler and secured.
Note that the foam seal is a tight fit in the wall sleeve, so either the wall sleeve will need to be rigidly fixed in the wall, that is, the cement has fully set or it can be held from the other side whilst inserting the flue assembly.
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
Page 17
17
220683B
4131
4 F l u e a n d A p p l i a n c e P r e p a r a t i o n
Diagram 4.12
10mm
Q
WALL THICKNESS­UP TO 300mm
Q-25mm
Q
WALL THICKNESS­OVER 300mm
FOAM SEAL
FOAM SEAL
4132
Diagram 4.11
Diagram 4.13
GASKET (PRE-ATTACHED)
WALL SLEEVE
4082
FLUE DUCT
5mm
3mm DRILL SIZE
FLUE MANIFOLD
SEALANT
AIR DUCT/TERMINAL ASSEMBLY
Page 18
18
220683B
WASHER
FRONT COVER
NUT
CONTROLS COVER
FRONT COVER
WING NUT
4115
5.1 Boiler Preparation
With the boiler still in the bottom tray, slide the controls tray upwards and remove it as shown in diagram 5.1.
Remove the front cover by undoing (and keeping) the screw and wing nuts and lifting the front cover off, see diagram 5.1.
Remove the packing piece from inside the front cover. Place front cover on one side until required. Fit suitable compression fittings to the boiler
connections.
5.2 Mounting the Boiler
As necessary, fit the blanking plate, see diagram 5.2. Now make sure that the top, swing brackets are
UPRIGHT. Lift the boiler into position, hooking over the mounting
bracket. Swing the brackets over the two screws at the top.
Hold the swing bracket(s) in place whilst tightening the screw(s) on to it, see diagram 5.3.
Remove the blue and red electrical connections from the fan, see diagram 5.4.
Break the air pressure switch tube connections, see diagram 5.4.
Remove the fan assembly by removing the screws at the front, slackening the screws at the rear and sliding it out, see diagram 5.4. Taking care not to damage the gasket.
Secure the flue assembly to the boiler using the previously fitted dogpoint screws noting that these are keyhole fixings, see diagram 5.5.
Make sure of the correct fitting of the flue to the boiler. For a side outlet cut the fan duct extension to the length
required, see diagram 5.6. Remove any burrs and fit as diagram 5.6. Fit the fan duct extension to the elbow and assembly to
the fan, see diagram 5.6 Do not secure at this point with the screw. Position the fan assembly and engage the fan duct
extension over the flue manifold. Make sure, by pushing in the flue duct extension that a secure seal is made. Mark the final position of the fan duct extension in the screw hole on the elbow, remove the assembly, seal with sealant, supplied in the loose items pack and secure with the screw as diagram 5.6.
Secure the elbow to the fan outlet with the Jubilee clip. For rear outlet cut and fit the fan duct extension as
shown in diagram 5.6. Fit fan assembly by engaging the fan duct extension over
the flue manifold spigot, see diagram 5.7.
5 B o i l e r I n s t a l l a t i o n
Diagram 5.1
4617
GASKETNUT (3)
BLANKING PLATE
Diagram 5.2
Secure the fan assembly with the screws previously slackened and removed.
Reconnect the blue and red electrical connections to the fan, the polarity of the connections is not important.
Reconnect the air pressure switch tubes as shown in diagram 5.4.
Page 19
19
220683B
5.3 Water Circulation System
Complete the water connections to the boiler. Fill, vent and flush the system. Check for any water leaks and put right.
5.4 Safety Valve Discharge
Fit a suitable discharge pipe to the safety valve and route it to outside the building so that any discharge can be seen but will not cause injury to persons, damage to property or any electrical installation.
5.5 Gas Connection
Make the gas connection to the Rc1/2in gas service cock, see diagram 6.1.
Check for leaks using a suitable leak detection fluid.
5.6 Control Box Removal
Remove the electrical control box securing screws, see diagram 5.8. Slide the box forward and release, hook it onto the lip bracket at the front, see diagram 5.8.
5 B o i l e r I n s t a l l a t i o n
0167(A)M
Diagram 5.3
5mm
Pipe omitted for clarity
MOUNTING BRACKET
SECURING SCREWS (2)
SWING BRACKET
LOCATION PLUG
GASKET
RED
CLEAR
REAR SECURING SCREW (2) (SLACKEN)
KEYHOLE
5874
4134
ELECTRICAL CONNECTIONS
Diagram 5.4
Diagram 5.5
AIR PRESSURE TUBES
SECURING SCREWS (2)
Page 20
20
220683B
Diagram 5.6
REAR
RIGHT
LEFT
Cutting 'MARK' lengths. Lefthand flue does not require cutting.
SEALANT
FAN
DUCT
EXTENSION
REAR
3mm dia. drill
Diagram 5.7
FLUE ELBOW
JUBILEE CLIP
SCREW (2)
SEALANT
FAN DUCT EXTENSION
FLUE MANIFOLD SPIGOT
VERTICAL
4089
4093
5.7 Electrical Connection
WARNING. This boiler must be earthed. Take care not to damage any internal wiring and
capillaries. Take plastic cable retaining clip, from the loose items
pack, peel off the backing paper and position it in a suitable place to secure the incoming cable.
Using heat resistant (to 85oC) cable of at least 0.75mm
2
(24/0.2mm) to the current issue of BS6500 Table 16 and of suitable length, thread through cable clamps, secure into the plastic clips and connect to appropriate terminals, see diagram 5.9 and 9.5.
Standard colours are, brown - live (L), blue - neutral (N) and green/yellow - earth (E).
The mains cable outer insulation must not be cut back external to the cable clamp.
Make sure the cable is suitably secured. When making connections, make sure that the earth
conductor is made of a greater length than the current carrying conductors, so that if the cable is strained the earth conductor would be the last to become disconnected.
SIDE LEFT
SIDE RIGHT
5 B o i l e r I n s t a l l a t i o n
FAN DUCT EXTENSION
(REAR FLUE OUTLET ILLUSTRATED)
Page 21
21
220683B
5.8 Pump Connection
The pump must be connected directly to the control box, as shown in diagram 5.9 threading the cable through the cable clamp in the side of the control box.
5.9 External Controls
Any external controls must only be wired to interrupt the red link between terminals SL and 9.
Make sure that the supply cable and all external cables are secured and away from hot surfaces.
5.10 Testing
Checks to ensure electrical safety must be carried out by a competent person.
After installation of the system, preliminary electrical system checks as below should be carried out.
1. Test insulation resistance to earth.
2. Test continuity and short circuit of all cables,
3. Test the polarity of the mains. The installer is requested to advise and give guidance to
the user of the controls scheme used with the boiler.
Diagram 5.9
FIXING SCREWS
Diagram 5.8
LIP BRACKET
PUMP CABLE
4619
4620
3310
5 B o i l e r I n s t a l l a t i o n
Remove red link between 9 & SL when fitting a time control etc (If no switch is fitted, link will make the circulation pump run constantly).
CABLE CLAMPS
IGNITION LEAD
MAINS CABLE
Page 22
22
220683B
6 C o m m i s s i o n i n g
6.1 All Systems
Commissioning should be carried out by a competent person in accordance with the current issue of BS6798.
Make sure that the system has been thoroughly flushed out with cold water without the pump in place.
Refit the pump, fill the system with water, making sure that all air is properly vented from the system and pump.
Before operating the boiler check that all external controls are calling for heat.
6.2 Sealed Water Systems Only
Flush the whole of the system with cold water without the pump in place. Refit the pump and fill until the pressure gauge registers 2.7bar (40lbf/in2). Clear any air locks and check for water soundness.
Check the operation of the safety valve, by allowing the water pressure to rise until the valve opens. The valve should open within +/-0.3bar (+/-4.3lbf/in2) of the preset pressure. Where this is not possible conduct a manual check and test.
Release cold water to initial system design pressure. The set pointer on the pressure gauge should be set to
coincide with the indicating pointer.
6.3 Initial Lighting and Testing
CAUTION. This work must be carried out by a competent person, in accordance with the current issue of BS6798.
Make sure that all naked lights and cigarettes are out. Identify the controls by reference to diagram 6.1. Check that the boiler is isolated from the electrical
supply. Makes sure that the control thermostat is turned to “O”
the “Off” position. Turn the gas service cock “On”, see diagram 6.1. Test the pilot supply tube and its connections for gas
soundness as follows: Disconnect the ignition lead from the PCB, see
diagram 5.9.
Diagram 6.1
Diagram 6.2
NOTE:
DO NOT ADJUST ANY OTHER SETTING SCREWS
MAIN BURNER PRESSURE TEST SCREW
MULTI­FUNCTIONAL CONTROL
OVERHEAT SAFETY CUT OFF
GAS SERVICE COCK (SHOWN OFF)
SETTING
POINT
CONTROL THERMOSTAT KNOB
PLASTIC COVER
4085
4108
GAS
PRESSURE
ADJUSTMENT
SCREW
Page 23
23
220683B
Remove the combustion chamber front, see diagram 6.3. WARNING. The fan operates on mains voltage,
terminals will become live. Turn the electrical supply on and check that all remote
controls are calling for heat. Check that the pump is circulating water through the
system. To complete the test it is necessary to operate the boiler
without its case, but UNDER ALL OTHER CIRCUMSTANCES the case must be correctly fitted and sealed.
Turn the control thermostat knob fully clockwise and the fan will work.
Note. There will be no sparks at the pilot. Take care and light the pilot with a match.
Test the pilot supply and connections for gas soundness, using a suitable leak detection fluid.
Very cold weather may delay the operating sequence. The pilot rate is preset and must not be adjusted.
The step adjustment screw must not be touched. The pilot flame length should be as shown in
diagram 6.4. Turn the control thermostat knob to “O” and isolate the
boiler from the electrical supply. Fit the combustion chamber front. Reconnect the ignition lead to the PCB. Stick the self adhesive arrow indicator to the data label,
against the rating that the boiler is going to be set to, for future reference. The arrow is in the loose items pack.
Loosen the main burner pressure test point screw and connect a suitable pressure gauge, see diagram 6.2.
Make sure that any remote controls are calling for heat. Switch on/connect the electrical supply to the boiler and
heating system, neon 1 will light.
Diagram 6.3
VIEWING WINDOW
SECURING SCREW (4)
4138
6 C o m m i s s i o n i n g
Diagram 6.4
SPARK GAP 2 to 4mm
10 to 20mm FLAME LENGTH
NOTE:
PILOT SHIELD REMOVED FOR CLARITY
4146
4139
Page 24
24
220683B
6.4 Testing - Electrical
Turn the boiler thermostat knob fully clockwise to the maximum setting, which is about 82oC (180oF), neon 2 will light.
The lighting sequence is automatic as follows: The fan operates The spark ignition operates Neon 3 will light The pilot solenoid opens
The pilot burner lights The ignition spark stops The main solenoid opens and after a short period of time the main burner will
light, look through viewing window, see diagram 6.3. Very cold weather may delay the operating sequence.
1. With the main burner alight, turn the gas service cock “Off”, see diagram 6.1.
After a short period the main burner and pilot will go out.
2. The correct working of the flame supervision device is shown by neon 4 going out within 10 seconds and the ignition starting up.
Neons 1, 2 and 3 should stay alight.
3. If the above does not happen, refer to fault finding Section 9.1.
4. To carry on turn gas service cock “On” see diagram 6.1.
When the boiler switches “Off”, both the pilot and main burner go out. The automatic lighting sequence will work again when heat is required.
6.5 Testing - Gas
With the boiler on proceed as follows: Test for gas soundness around the boiler gas components
using a suitable leak detection fluid, in accordance with the current issue of BS6891.
Check the main burner gas pressure at least 10 minutes after the boiler has lit, refer to Data Label.
If necessary adjust the gas pressure to obtain the required setting turning screw clockwise, to decrease pressure, see diagram 6.2.
Should any doubt exist about the gas rate, check it using the gas meter test dial and stop watch, at least 10 minutes after the burner has lit, making sure that all gas burning appliances and pilot lights are off.
}
}
Neon 4 will light
Turn the control thermostat knob fully anticlockwise to “O”. Remove the pressure gauge from the test point and refit screw, making sure a gas tight seal is made.
When the control thermostat is turned to the “Off” position, by hand, wait at least 30 seconds before turning “On” again.
There may be an initial smell given off from the boiler when new, this is quite normal and it will disappear after a short period of time.
Refit the electrical controls box, see diagram 5.8. Note. The neon indicator lights on the printed circuit
board are an aid to fault finding, for details refer to Section 9.
6.6 Testing - Open Vented
Allow the system to reach maximum working temperature and examine for water leaks.
There should be no undue noise in the system and no pumping over of water or entry of air at the open vent above the feed and expansion cistern.
All systems - The boiler should be turned off and the system drained off as rapidly as possible, whilst still hot.
6.7 Adjustment - Fully Pumped Open Vented and Sealed Water Systems
When commissioning the system the boiler should first be fired with the bypass fully closed on full service, that is, central heating and domestic hot water. Adjust the pump to the system design setting then balance the system. Having achieved a satisfactory condition operate the boiler with the bypass fully closed on minimum load, normally this will be central heating only with one radiator in the main living area operating. The bypass valve should be gradually opened to achieve a temperature difference no greater than 20oC between the flow and return.
UNDER NO CIRCUMSTANCES SHOULD THIS VALVE BE LEFT IN THE FULLY CLOSED POSITION.
6 C o m m i s s i o n i n g
Page 25
25
220683B
6 C o m m i s s i o n i n g
Diagram 6.6
Diagram 6.5
WING NUT
NUT
TOP SEAL
SIDE SEAL
WASHER
CONTROLS COVER
SLIDERS
4140
4088
NOTE: MAKE SURE OF CORRECT ENGAGEMENT
6.8 Sealed Water Systems ONLY
Adjust the system to initial design pressure. The set pointer on the pressure gauge should be set to coincide with the indicating pointer.
6.9 Thermostatic Radiator Valves
If thermostatic radiator valves are fitted care must be taken to ensure that an adequate flow rate through the boiler when they close, refer to the current issue of BS7478 for guidance.
6.10 Operational Checks and Completion
Adjust the boiler thermostat and any system controls to their required settings.
Do not attempt to adjust the thermostat calibration screw.
Operate the boiler again on full service and check that the balancing is satisfactory, making adjustments as necessary.
Fit the front cover by hooking it under at the top and securing with the wing nut, washer and nut previously removed, refer to diagram 6.5.
Fit the controls cover by hooking into the sliders and pushing it back as far as it will go, see diagram 6.6.
6.11 Protection Against Freezing
If the boiler is to be out of use for a period of time during severe weather conditions we recommend that the whole of the system, including the boiler, be drained off to avoid the risk of freezing up.
Page 26
26
220683B
Instruct and demonstrate the safe and efficient operation of the boiler, heating system and domestic hot water system.
Advise the user, that to ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that servicing is carried out by a competent person.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Reminder, leave these instructions with the user.
7 I n s t r u c t i o n s t o t h e U s e r
Page 27
27
220683B
Notes, To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
It is the Law that any servicing is carried out by a competent person.
Before servicing turn off the gas and isolate the electrical supply to the boiler.
After completing a service always test for gas soundness and carryout functional check on controls.
Unless stated otherwise all parts are replaced in the reverse order to removal.
8.1 Access
Refer to diagram 6.6 and slide the controls cover forwards and off.
Remove the outer case, see diagram 6.5. Note. As an aid to servicing the air pressure switch tube
connection can be used to obtain a products of combustion reading.
Remove the RED tube from the connection on the air pressure switch and insert the analyser probe into t he tube.
Switch on the electrical supply to operate the fan and turn the gas supply on.
On completion of the test switch off the electrical supply and the gas supply and reconnect the red tube to the air pressure switch.
8.2 Cleaning Heat Exchanger Flueways
Disconnect the air pressure tubes, see diagram 5.4. Remove the violet and red electrical connections from
the fan, see diagram 5.4. Remove the fan complete with fan duct extension taking
care not to damage the gasket, see diagram 5.4. Vertical Flue Only, carefully remove the restrictor plate
and additional gaskets. Remove the flue hood, noting that there are keyhole slots
at the rear, see diagram 8.1. Remove the combustion chamber cover, see diagram 6.3. Remove the burner as Section 8.3. Place a sheet of paper in the base of the combustion
chamber. Remove the baffles, note, when replacing they are
marked “Front”, see diagram 8.2. Clean the heat exchanger flueways with a suitable stiff
brush. Remove the paper together with any debris.
Diagram 8.2
Diagram 8.1
Diagram 8.3
SECURING SCREW (4)
GASKET
FLUEHOOD
SECURING NUT AND SHAKEPROOF WASHER
PILOT PIPE
ELECTRODE AND LEAD ASSEMBLY
UNION CONNECTOR
BAFFLE (4)
80FF Illustrated
41164109
4087
8 S e r v i c i n g
Page 28
28
220683B
8.3 Main Burner
Disconnect the pilot pipe union connector and pilot burner, securing nut and shakeproof washer together with the pilot shield. Remove the pilot burner assembly taking care not to damage the electrode and lead assembly, see diagram 8.3.
Remove the securing screw from the burner support bracket, see diagram 8.4.
Remove the main burner from the main injector at the rear. Raise the burner up and forwards, easing the pilot pipe down, to clear, take care not to damage the combustion chamber insulation or the pilot pipe.
Use a vacuum cleaner or suitable stiff brush to clean the burner thoroughly, making sure that all the burner ports are clear and unobstructed.
Continue cleaning heat exchanger as Section 8.2. Note. On refitting and after cleaning the heat exchanger
make sure the burner is fitted correctly, that is, located on the main injector and horizontal.
8.4 Main Injector
With the main burner removed the main injector can be inspected and cleaned as necessary, see diagram 8.5.
If removing for cleaning do not use a wire or sharp instrument on the hole.
Use a little suitable sealant on the external thread when refitting making sure a gas tight seal is made.
8.5 Pilot Burner/Electrode and Pilot Injector
Clean the pilot burner and electrode. To remove the electrode release the spring clip, see
diagram 8.6. When removing and replacing the pilot injector from the
pilot burner take care not to damage the electrode, see diagram 8.6, clean the injector by blowing through it.
Check that the spark gap is as shown in diagram 6.4.
8.6 Operational Checks
After completing a service and before fitting the case, check condition of the case seal and renew if necessary.
Examine flue hood and terminal to make sure they are clean and clear of obstructions.
Light the boiler and carryout the functional checks as described in Section 6.
8 S e r v i c i n g
Diagram 8.4
Diagram 8.5
Diagram 8.6
SECURING SCREW
BURNER SUPPORT BRACKET
MAIN BURNER INJECTOR
PILOT INJECTOR
ELECTRODE
PILOT BURNER
SPRING CLIP
4112
4111
4143
Page 29
29
220683B
9.1 Electrical
Important. On completion of the Service/Fault Finding task which has required the breaking and remaking of the electrical connections the earth continuity, polarity, short circuit and resistance to earth checks must be repeated using a suitable multimeter.
Refer to neon indicators “An Aid to Fault Finding” diagram 9.1, Boiler Fault Finding diagram 9.2, Pump Overrun Fault Finding diagram 9.3, the Functional Flow diagram 9.4 , and the Pictorial Wiring diagram 9.5.
9.2 Electrical Supply Failure
Failure of the electrical supply will cause the burner to go out.
Operation will normally resume on restoration of the electrical supply. If the burner does not relight after an electrical supply failure the overheat device may need resetting.
Remove the control cover, see diagram 6.6 and push the rest button on the front of the control box, see diagram 6.1.
If the cutoff operates at any other time press the rest button and the burner should relight. If the fault persists refer to fault finding chart.
9 F a u l t F i n d i n g
Diagram 9.1
Neon Indicators - An Aid to Fault Finding
THE NEON INDICATORS ARE AN AID TO FAULT FINDING ONLY. FAILURE OF ANY OF THE NEON INDICATORS DOES NOT WARRANT THE
REPLACEMENT OF AN OTHERWISE SATISFACTORY PRINTED CIRCUIT BOARD (PCB).
Is neon 1 lit? Fault with mains supply or PCB fuse
Ignition, pilot or flame proving fault ­see detailed fault finding chart.
Air flow proving fault - that is fan or air pressure switch - see detailed fault finding chart.
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
Overheat cut off device tripped or thermostat, overheat cut off device faulty
- see detailed fault finding chart.
Is neon 2 lit?
Is neon 4 lit?
System satisfactory
Is neon 3 lit?
Is main burner operating?
Multi-functional control/harness problem
- see detailed fault finding chart.
NEON INDICATORS
3324
Page 30
30
220683B
9 F a u l t F i n d i n g
Diagram 9.2
Is neon 1 lit?
YES
YES
Is neon 2 lit?
YES
NO
Correct power supply problem.
NO
YES
Is there 240V~ between 6 on thermostat and N ?
Replace thermostat.
NO
YES
NO
Is neon 3 lit?
Is there 240V~ between "N/C" on air pressure switch and N ?
YES
Check yellow cable between printed circuit board and air pressure switch. If satisfactory replace printed circuit board.
YES
NO
Is there 240V~ between "C" on air pressure switch and N ?
Replace air pressure switch.
Does fan run?
YES
NO
NO
YES
Replace fan.
YES
Replace printed circuit board.
Does fan Hunt?
NO
Inspect air tubes for leaks, kinks and correct fitting. If satisfactory replace faulty air pressure switch.
NO
Is there 240V~between "N/O" on air pressure switch and N ?
NO
NO
Inspect electrode lead /connection for poor contact. Check electrical supply polarity and correct if necessary. If satisfactory replace printed circuit board.
YES
With pilot lit does spark stop?
NO
Replace main solenoid
YES
Replace multi-functional control.
YES
Is Neon 4 lit?
NO
Does main burner light?
System satisfactory
NO
YES
NO
YES
YES
NO
NO
Is there 240V~ between SL and N and between L and N ?
Is there 240V~ between yellow connection on overheat device and N ?
YES
Is there 240V~ between motor connections on fan?
YES
Isolate electrical supply test fan harness continuity. If satisfactory replace printed circuit board.
Before detailed checking of electrical components ensure that remote controls are calling for heat. Check the gas supply is free of obstructions and purged of air. Check the overheat cutoff has not operated. For fully pumped systems only. Isolate the electrical supply and physically check ALL cables, connections and the printed circuit board fuse. Check the air tubes to the air pressure switch. Switch on the electrical supply and check for correct polarity. Turn the boiler thermostat to its maximum setting. Also check fuses.
Check overheat reset. If satisfactory replace overheat device.
Is there a spark at pilot burner?
Check lead continuity and inspect electrode and lead for damage.
Check for pilot jet blockage, incorrect electrode adjustment isolate supply. Remove plug from multifunctional control. Check continuity of pilot solenoid between EV1 and COM, continuity OK?
Does pilot light?
NO
Replace multifunctional control
Replace pilot solenoid.
NO
YES
Isolate supply. Remove plug from the multifunctional control. Check continuity of main solenoid between EV2 and COM. Continuity OK?
M A I N T E R M I N A L S T R I P
C O N T R O L T H E R M O S T A T
Page 31
31
220683B
Diagram 9.3
Pump overrun Operation
The Control Thermostat has a pump overrun facility built into it, when the Control Thermostat is set at maximum only, the pump overrun will keep the
pump running to allow the boiler to cool down after which it will stop, providing the remote controls are NOT calling for heat.
YES
NO
NO
Faulty Pump overrun. Replace Control Thermostat
YES
Is there 240V~ on L ?
NO
Pump overrun in order.
NO
NO
Faulty pump / wiring ? Replace or repair as necessary.
Is there 240V~ on 9 connection on thermostat?
Is there 240V~ on P for pump?
Faulty connections between thermostat and terminal strip. Repair.
Faulty internal wiring between main terminal strip and thermostat. Repair.
Faulty permanent live feed. Replace.
YES
YES
YES
Turn off remote controls, does the pump stop after a short period of time?
Fault Finding
Turn boiler Control Thermostat to maximum, with the remote controls calling for heat,
does the pump continue to run after the appliance has shut down on boiler control thermostat?
9 F a u l t F i n d i n g
Page 32
32
220683B
9 F a u l t F i n d i n g
Diagram 9.4
FUSE TYPE F1A 1 AMP
AIR PRESSURE SWITCH CONNECTIONS
0097M
SPARK ELECTRODE
O/H CUTOFF
CONTROL STAT
FAN
AIR PRESSURE SWITCH
PILOT SOLENOID
MAIN SOLENOID
N
N
N
N
N
N
N
(N/O) (C)
(N/C)
L
K2
K1
6
3
N
N
b w
w
br
y
y
y
r b
r
bk
b
y
br b
b
bk
b
KEY
bk BLACK br BROWN b BLUE
w WHITE r RED y YELLOW
SL
MAIN TERMINAL STRIP CONNECTIONS CONTROL THERMOSTAT CONNECTIONS PRINTED CIRCUIT BOARD CONNECTIONS
FULLY PUMPED OPEN VENTED OR SEALED WATER SYSTEM
PN
9
9
8
7
P
L
PUMP
br b
br
r
brbr
THERMOSTAT
PUMP
OVERRUN
PURPLE
b
b
*
RED
LINK
*
Remove red link between 9 & SL when fitting a time control etc (if no switch is fitted, link will make the circulation pump run constantly)
Page 33
33
220683B
Diagram 9.5
r
FULLY PUMPED OPEN VENTED OR SEALED WATER SYSTEM
KEY:
b - BLUE bk - BLACK br - BROWN g/y - GREEN/YELLOW r - RED y - YELLOW w - WHITE p - PURPLE
g/y
FAN
MULTI-FUNCTIONAL CONTROL
ELECTRODE
PLUG
AIR PRESSURE SWITCH
C
NO
NC
y
r
b
bk
g/y
CHASSIS EARTH
Remove red link between 9 and SL when fitting
a time control etc (If no switch is fitted, link will make the circulation pump run constantly)
CHASSIS EARTH
L N
CIRCULATION PUMP
E
E
N
L
240~50Hz PERMANENT MAINS SUPPLY FUSED AT 3-AMP
N
L
9
8
7
SL
g/y
p
b
br
br
3-PLUGS
br b
r
br
y
w y
6
8
9
7
3
COMBINED THERMOSTAT AND PUMP OVERRUN
OVERHEAT CUTOFF
SWITCH CONTROL, TIME SWITCH, PROGRAMMER ETC. (if fitted)
SEE NOTE
4117
9 F a u l t F i n d i n g
F1A 1 AMP FUSE
g/y
SEQUENCE BOARD
g/y
br
b
br
b
g/y
Page 34
34
220683B
1 0 R e p l a c e m e n t o f P a r t s
CONTROL KNOB
RETAINING CLIP
SPLIT GROMMET
Diagram 10.1
SHAKEPROOF WASHERS AND SCREWS
CONTROL THERMOSTAT
ELECTRICAL CONNECTIONS BROWN 9 RED 8 PURPLE 7 YELLOW 6 & 3
LOCKNUT
ELECTRICAL CONNECTIONS
4113
10 Replacement of Parts
Note. Replacement of parts must only be carried out by a competent person.
Before replacing any parts isolate the boiler from the electrical supply and turn the gas supply off at the gas service cock, indicator slot should be vertical.
Unless state otherwise, all parts are replaced in the reverse order to removal.
After replacing any parts always test for gas soundness and if necessary carryout functional check of controls.
10.1 Access
Gain access as Section 8.1.
10.2 Control Thermostat/Pump Overrun ­diagram 10.1 and 10.2
Remove and support the electrical control box, refer to Section 5.6.
Remove the control knob. Remove the electrical connections from the thermostat body.
Release the thermostat body by unscrewing the two screws and shakeproof washers in the front of the control box.
Remove the split pin and withdraw the thermostat phial from its pocket. Release the capillary from the base and plastic retaining clip then remove it from the split grommet. Release the capillary from its clips. Remove the thermostat complete from the boiler.
Reassembly note. When fitting the thermostat, make sure that the thermostat phial is covered with heat sink compound then fully inserted into the phial pocket and that the capillary is within the gland seal, see diagram
10.2. Remake the electrical connections. There must be no kinks or sharp bends in the capillary.
10.3 Over Heat Cutoff Device - diagram
10.1, 10.2 and 10.2A
Remove and support the electrical control box, refer to Section 5.6.
Remove the overheat cutoff electrical connections. Disconnect the air pressure switch plug from the PCB. Remove the locking nut from the overheat cutoff. Release the capillary from the retaining clips then
remove it from the split grommet. Remove the split pin and then the phial. When refitting use the heat sink compound supplied.
Page 35
35
220683B
10.4 Control Board (PCB) - diagram 102A
Release the control box, refer to Section 5.6. Disconnect the three electrical plugs and ignition lead. Release the cables from the plastic retaining clip, then
disconnect the cables from the PCB to the main terminal strip, control thermostat and earth connection.
Release the main terminal strip and plastic label. Carefully pull the board away from its supports. When refitting refer to wiring diagram 9.5.
10.5 Pilot Burner and Pilot Injector
Proceed as Section 8.3 and 8.5.
10.6 Electrode
Proceed as Section 8.3 and 8.5. Gain access as Section 5.6 to remove lead from control
box.
Diagram 10.2 Diagram 10.2A
1 0 R e p l a c e m e n t o f P a r t s
PHIAL POCKET
THERMOSTAT
PUMP
OVERRUN
PHIAL
ELECTRICAL PLUGS
OVERHEAT CUTOFF ELECTRICAL CONNECTION "WHITE" CABLE
CHASSIS EARTH CONNECTION
MAIN TERMINAL STRIP SECURING SCREW (2)
ELECTRICAL CONNECTION
SL BROWN CABLE
PLASTIC RETAINING CLIP
ELECTRICAL CONNECTION
N BLUE CABLE
SPLIT PIN
GLAND SEAL (Right hand illustrated)
SUPPORT POST (4)
IGNITION LEAD
SPLIT PIN
PHIAL POCKET
RETAINING CLIP
4110
BOILER THERMOSTAT ELECTRICAL CONNECTION NO.6 "YELLOW" CABLE
3328
OVERHEAT CUTOFF DEVICE PHIAL
NOTE: All capillaries and cables should be situated within the "Gland Seal".
Page 36
36
220683B
1 0 R e p l a c e m e n t o f P a r t s
10.7 Multifunctional Control - diagram 10.3
Disconnect the pilot supply by unscrewing the tubing nut at the multifunctional control, take care as there is a restrictor on the pilot pipe.
Disconnect the electrical plug. Support the multifunctional control, remove the four
extended screws from the flanged connections at the left and right hand side.
Remove and discard the original “O” rings from the flanged connections and fit the new “O” ring supplied, into recess, before fitting the replacement multifunctional control.
After assembly test for gas soundness and purge in accordance with the current issue of BS6891.
10.8 Solenoid - diagram 10.3
Remove the electrical plug from the multifunctional control. Remove the securing screw and then the solenoid Assembly.
10.9 Main Burner
Remove the main burner as Section 8.3.
10.10 Main Injector
Remove the main burner as Section 8.3. Remove the main injector as Section 8.4.
10.11 Insulation - 10.4
Combustion Chamber Front Remove the retaining screw then the insulation.
Sides
Slide the insulation out.
Rear
With the side insulation removed the rear insulation can be removed and replaced.
Diagram 10.3
SOLENOIDS
SECURING SCREW
PILOT PIPE TUBING NUT
RESTRICTOR
ELECTRICAL PLUG
EXTENDED SCREW (8)
4123
10.12 Viewing Window - diagram 10.5
Remove the push on fixes and then the window. When replacing take care not to damage the gasket.
10.13 Air Pressure Switch - diagram 10.6
Release the control box as Section 5.6. Remove the air pressure tubes and electrical connections
from the PCB, release the screws and remove the switch. When fitting the replacement make sure that the plastic
tubes and electrical connections are made as shown in diagram 9.5 and 10.6.
10.14 Fan - diagram 5.4
Remove the electrical connections and disconnect the air pressure tubes.
Remove the fan assembly securing screws at the front and slacken those at the rear and withdraw the assembly.
Make sure that the earth connection is remade onto the new fan assembly.
The polarity of the other connections is not important.
Page 37
37
220683B
Diagram 10.4
Diagram 10.5
Diagram 10.6
RED
CLEAR
AIR PRESSURE SWITCH TUBES
ELECTRICAL CONNECTIONS
CONTROL BOX
FRONT INSULATION
RETAINING SCREW
SIDE INSULATION
REAR INSULATION
AIR PRESSURE SWITCH
PUSH ON FIX
RETAINING PLATE
GASKET
VIEWING WINDOW
SECURING POINTS
SECURING SCREWS
4118
4095
4122
1 0 R e p l a c e m e n t o f P a r t s
Page 38
38
220683B
11.1 Part Identification
The key number on the diagram and the list will help to identify the part.
11.2 Ordering
When ordering any spare parts please quote the number and description from the list together with the model name and serial number.
If ordering from British Gas also quote the GC number of the appliance and part.
1 1 S p a r e P a r t s
1 800442 Multifunctional control 278 021 2 208040 “O” ring 334 592 3 205710 Injector 80FF 278 024 3 205701 Injector 70FF 313 393 4 203432 Pilot burner 278 023 5 411194 Sight glass 355 153 6 800421 Fan assembly 278 008 7 202626 Spark electrode and lead 313 998 8 K3580 Clip 390 983 9 202552 Thermostat 278 009 10 202201 Air pressure switch 313 992 11 800275 Control knob 313 609 12 13 202015 Fuse 334 750 14 900817 Control board PCB 313 301 15 800479 Overheat cutoff device 278 188
Key No. Part No. Description GC Part No.
Page 39
39
220683B
1 1 S p a r e P a r t s
Diagram 11.1
4
6
2
1
9
10
5
7
8
11
3
13
14
15
4119
Page 40
40
220683B
Control of Substances Hazradous to Health
Because of our constant endeavour for improvement details may vary slightly from those in the instructions.
INFORMATION FOR THE INSTALLER AND SERVICE ENGINEER.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
CERAMIC FIBRE/INSULATION PADS. These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation of the eyes or severe irritation to the skin seek medical attention.
THERMOSTATS
These contain very small amounts of xylene in the sealed phial and capillary. If broken, under normal circumstances the fluid does not cause a problem, but in case of skin
contact, wash with cold water. If swallowed drink plenty of water and seek medical attention.
CUT-OFF DEVICES
These contain activated charcoal and a very small amount of chlorodifluormethane in the sealed phial and capillary.
If broken, under normal circumstances the fluid does not cause a problem. If there is irritation to the eyes or skin then seek medical attention.
Loading...