Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Installation and Servicing
To be left with the user
221422A.10.98
5226
75e
G.C. No. 47 313 16
Fanned Flue Combination Boiler
With Honeywell gas control
This is a Cat I2H Appliance
The instructions consist of three parts, User, Installation and Servicing Instructions, which include the Guarantee Registration Card.
The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use)
Regulations, be handed to the user on completion of the installation.
Guarantee Registration
Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances' are manufactured to the very highest standard so we are pleased
to offer our customers' a Comprehensive First Year Guarantee.
In the center pages are to be found your Guarantee Registration Card, which we recommend you complete and
return as soon as possible.
If this card is missing you can obtain a copy or record your registration by telephoning the Heatcall Customer
Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of:
Service number 01773 828100.
✔
All replacement parts
❏
✔
All labour charges
❏
✔
All call-out charges
❏
Customer Services:
Tel: (01773) 828100
One Contact Local Service
Fax: (01773) 828070
REGISTER YOUR GLOW-WORM APPLIANCE
FOR 1ST YEAR GUARANTEE PROTECTION
CALL 0181 380 2555
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Important Information
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler,
without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the
current issue of the Statutory Requirements, see Section 1.4.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is
deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with
liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0087.
Product/production certified by: Notified body 0087.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning
gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment
designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic
compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is
broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or
going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
CONTENTSDESCRIPTIONSECTIONPAGE No.
INSTRUCTIONS
FOR USE
Introduction3
Clock Settings4
Lighting the Boiler5
General Data16
INSTALLATION
INSTRUCTIONS
Boiler Position28
Flue and Ventilation39
Heating System411
Domestic Hot Water System514
Installation Preparation614
Flue Preparation716
Gas and Water Connections817
Electrical Connections918
Boiler Fixing1020
Commissioning1121
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Introduction
Please read these instructions and follow them carefully for the
safe and economical use of your Combination boiler.
This boiler must have been installed by a competent person in
accordance with the rules in force in the countries of destination.
Once the pilot has been lit and the controls set, the boiler is
automatic in operation.
The Swift-flow combination boiler is able to provide room
heating as part of a central heating system and domestic hot
water direct from the cold water supply, without the need for
secondary storage.
The boiler can be fitted with one of two makes of clock, which
look like this:-
Digital timer
IMPORTANT NOTICE:
This boiler is for use only on G20 gas.
Clock / Timer
Electro / mechanical
clock / timer
Gas Leak or Fault
If a gas leak or fault exists or is suspected, turn the boiler off and
consult your local gas company or your local installation/
servicing company.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than
in the summer.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off tap.
Boilers Installed in Compartments
If the boiler has been fitted into a compartment or cupboard, do
not obstruct the compartment air supply vents.
Do not use the compartment for storage.
The colours of three core flexible cable are, blue - neutral, brown
- live, green and yellow - earth.
As the markings on your plug may not correspond with these
colours continue as follows:The wire coloured blue must be connected to the terminal
marked “N” or “Black”.
The wire coloured brown must be connected to the terminal
marked “L” or “Red”.
The wire coloured green and yellow must be connected to the
terminal marked “E” or “Green” or the earth symbol
PVC flexible cable having a conductor size of 0.75mm
0.20mm) must be used within the boiler casing to connect to the
boiler.
Electrical Supply Failure
The boiler will not work without an electrical supply.
6509
Normal operation of the boiler should resume when the electrical
supply is restored.
Note. The boiler safety cutoff may have operated, please refer
to the following section to reset.
Reset any external controls, to resume normal operation of the
central heating.
The digital timer, has a lithium battery back up and will not need
resetting.
Boiler Safety Cutoff Reset Button
The boiler is fitted with a safety cutoff device to prevent damage
through overheating.
Should the main burner go out during a demand the red neon
on the Reset Button will light.
In certain circumstances the red neon light may not come on,
due to no system demand. It is suggested that a hot water draw
off tap be opened to create a demand, the neon should then
come on.
Allow the boiler and system to cool down waiting at least a
minimum of four minutes before pressing the Reset button.
If the problem persists, turn the boiler off and consult the local
gas company or your installation/ servicing company.
.
2
(24/
Electrical Supply
WARNING. The boiler must be earthed.
The boiler must be connected to a 230V~50Hz permanent
supply.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should preferably be by a double pole switched fused
spur box. The fused spur box should be readily accessible and
preferably adjacent to the appliance. It should be identified as
to its use.
Alternatively a fused 3A 3 pin plug and shuttered unswitched
socket may be used.
3
221422A
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Setting Instructions for Electro/mechanical
Clock - if fitted
This clock has a twenty four hour dial, that is, 1pm is 13.
To set the time, turn the whole face clockwise until the pointer
is against the time of day.
To set any “Off” time, push the tappets outwards.
To set any “On” time, push the tappets inwards.
Time can be set either “On” or “Off” in fifteen minute segments.
Note. The clock supplied could be fitted with an override device,
see diagram 1, which switches the clock programme “On” or
“Off” permanently.
The switch will need to be repositioned to resume programmed
working.
CLOCK FACE
0
OVERRIDE
SWITCH
12
11
13
14
15
16
17
18
19
20
21
22
23
24
CONSTANT OFF
0
PROGRAMMED
CONSTANT ON
I
10
9
3
2
1
I
8
7
6
5
4
POINTER
TAPPETS
Diagram 1
Setting Instructions for the 7 Day Digital
Clock/Timer
This is a 24 hour clock/timer, that is 1pm is 13:00, and has 8
“ON” and 8 “OFF” daily switching actions.
It is fitted with a lithium battery back up which protects the
programme in the event of an electrical failure. The battery
should have a life of several years.
5673
P
AUTO
I
MT
WTh
P
DAYHRMIN
RUN
FS
R
Su
Setting the Clock
1. With both AUTO and RUN switches set to the central
position, press R reset button, the display will flash.
2. Set RUN switch to .
3. Set day of week by pressing button DAY.
4. Set time of day by pressing buttons HR and MIN.
5. Set RUN switch to the central position, colon will flash, this
indicates the clock is set.
With the clock set, the factory preset programme shown below
will operate.
4956
MON/FRI
ON -06:30
OFF -08:30
ON -16:30
OFF -22:30
SAT/SUN
ON -07:00
OFF -09:00
ON -16:00
OFF -23:00
Setting Timed Programmes
With the clock set to the correct time, see SETTING THE
CLOCK paragraphs 1-4, and then continue as follows:
1.Set RUN switch to P , the display will indicate
the 1st (ON) preset programme and the symbol .
2.Set day of week to be programmed by pressing the
DAY button.
Note: The days can be selected individually or as
groups:
Mon-Fri., Mon-Sat., Mon-Sun., Sat/Sun.
An arrow will be displayed under the day
or days selected.
3.Set time of day by pressing the buttons HR and MIN.
4.Press button P to confirm programmes, the
display will indicate the 2nd (OFF) preset
programme and subsequently, 3rd, 4th, 5th, 6th,
7th, 8th.
5.Repeat procedures 2, 3 and 4 until desired
programmes are set.
Note. It is not a requirement to use the 8 on/off
programmes.
6.Set the RUN switch the central position, your
appliance will now operate at the programmed times.
General Notes.
With the AUTO switch in the I position the central
heating will operated constantly ON.
With the AUTO switch in the O position the central
heating will not operate.
Soft Override button indicated by the
symbol
current central heating programme for the
next available.
ON time programmes are indicated by the symbol
, this function will override the
.
Diagram 2
221422A
4
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
To Light the Boiler
1. Check that all five isolating valves are open, the slots in line
with the length of the valve, see diagram 3.
2. Open the door, by pushing at the side opposite to the hinge.
3. CAUTION. A sealed pressurised system must be filled and
pressurised by a competent person.
Only operate the boiler when you are sure that the system has
been filled and pressurised. Check this by looking at the
pressure gauge “A”, diagram 4, it should read 0.7bar minimum.
4. Check reset button neon, refer to previous instructions on
page 3.
5. Open a hot water tap, check that water flows, then close it.
6. If you are in any doubt about the boiler being filled with water
contact your installation/servicing company or the local gas
company.
7. Check that the electrical supply to the boiler is ON at the
external isolator.
8. Set switch “C”, clock/timer (if fitted) and any remote controls
as required.
Close the door.
In certain circumstances, a surge in water pressure may cause
the appliance to operate momentarily, this will be indicated by
the pump starting and the fan speed increasing. This is quite
normal.
Central Heating Selector Switch
For central heating set switch “C” to “On” as shown in diagram
4. The main burner will light.
When the heating is controlled by a room thermostat and/or a
time switch, switch “C” must be set “On”.
If a hot water tap is opened while the boiler is on for heating, the
burner flame will increase in size and priority will be given to hot
water.
When the hot water tap is closed, the main burner flames will
decrease in size but will remain alight until the boiler controls or
any heating controls switch it off.
Which ever position switch “C” is in domestic hot water will be
available.
To Turn the Central Heating Off
To turn the heating off for short periods, set switch “C” to “Off”
as shown in diagram 4.
To turn on again set switch “On”, see diagram 4.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the
appliance it is recommended that it is checked and serviced as
necessary at regular intervals. The frequency of servicing will
depend upon the particular installation conditions and usage,
but in general once a year should be enough.
If this appliance is installed in a rented property there is a duty
of care imposed on the owner of the property by the current
issue of the Gas Safety (Installation and Use) Regulations,
Section 35.
Servicing/maintenance should be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
behind the controls access door, see diagram 4.
COLD WATER
SUPPLY IN
HEATING
FLOW
SAFETY
VALVE
DISCHARGE
SLOT (OPEN)
SWITCH
ON
GAS SERVICE
COCK
HEATING
RETURN
DRAIN
POINT
CENTRAL HEATING
SELECTOR SWITCH 'C'
5044
HOT WATER
OUT
SLOT (OPEN)
Diagram 3
CONTROL
RESET
BUTTON
6088
6625
To Turn the Boiler Off
To turn the boiler off, isolate the boiler from the electrical supply.
To turn on again following the operating instructions.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than
in the summer.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off.
5
SWITCH
OFF
PRESSURE
GAUGE ‘A’
Diagram 4
221422A
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Clearances
The boiler requires a clearance in front, below and at the sides
of the casing for safety, servicing and maintenance access, see
diagram 2.1.
Protection Against Freezing
If the boiler is to be out of use for any long periods during severe
weather, it is recommended that the whole system, including
the combination boiler, should be drained to avoid the risk of
freezing.
If in doubt, contact you installation/servicing company for advice.
Draining and Filling
CAUTION. This boiler works in a pressurised system which
must only be drained, refilled and pressurised by a competent
person.
Note: If the pressure gauge indicates a loss of system pressure,
that is, less than 0.7bar, YOU MUST CONTACT YOUR
INSTALLER.
Pressure Relief Safety Valve
CAUTION. A pressure relief safety valve and discharge pipe is
fitted to the boiler. This valve must not be touched. Should there
be any discharge from the pipe, turn the boiler off, isolate from
the electrical supply and contact your installation/servicing
company.
Cleaning
WARNING. This appliance contains metal parts (components)
and care should be taken when handling and cleaning with
particular regard to edges.
The boiler casing can be cleaned using a mild liquid detergent
with a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may
damage the paint work
Boiler Casing
CAUTION. Do not remove or adjust the casing in any way, as
incorrect fitting may result in incorrect operation or failure to
operate at all. If in doubt seek advice from the local gas
company or your installation/servicing company.
Replacement Parts
If replacement parts are required apply to your local supplier or
British Gas.
Please quote the name of the appliance.
MOUNTING
WALL
82mm
2257A
101
63
2.5
C
L
C
25
1 General
331
168
117
SAFETY
VALVE
DISCHARGE
783
L
450
2257
63
25
ALL DIMENSIONS in MILLIMETRES
15mm COMPRESSION
DOMESTIC WATER
6
221422A
22mm COMPRESSION
CENTRAL HEATING
KEY:
66
1
1
/
(
2
/
in. BSPT)
2
Rc
GAS CONNECTION
107
107
66
2.5
Diagram 1.1
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
1.1 Installation
Materials and equipment should be fit for their purpose and of
suitable quality and workmanship.
1.2 Important Notice
This boiler is for use only on natural gas, G20.
1.3 Sheet Metal Parts
WARNING. When installing or servicing this boiler care should
be taken when handling the edges of sheet metal parts to avoid
any possibility of personal injury.
1.4 Requirements
The installation of this boiler must be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
Manufacturer’s instructions, supplied.
Manufacturer’s instructions must not be taken as overriding
statutory requirements.
1.5 Data Label
The data label is on the inner case cover.
1.6 Data
See tables 1 and 2
1.7 Gas Supply
The gas installation shall be in accordance with the rules in force
in the countries of destination.
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at
the boiler.
1.8 Electrical Supply
WARNING. This boiler must be earthed.
All system components shall be of an approved type.
The electrical installation shall be in accordance with the rules
in force in the countries of destination.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should be by a double pole switched fused spur box,
having a minimum contact separation of 3mm in each pole. The
fused spur box should be readily accessible and preferably
adjacent to the appliance.It should be identified as to its use.
Alternatively, a fused 3A 3pin plug and unswitched socket may
be used, provided they are not used in a room containing a bath
or shower.
The mains supply cable and other cables connected to the
boiler must be the PVC flexible type of at least 0.75mm
● Ball valves are fitted in water and gas connections, plus a drain point on all water connections.
❋ Boiler starts at an inlet pressure of 0.5bar but requires 0.8bar for maximum output.
■ For larger systems use an additional expansion vessel, see Section 4.
2 Boiler Position
2.1 Location
This boiler must be installed in accordance with the rules in
force in the countries of destination.
This boiler is not suitable for fitting outside.
Any electrical switch must be positioned so that it cannot be
touched by a person using the bath or shower.
The boiler must be mounted on a flat wall which is sufficiently
robust to take its weight, refer to
Section 1, “Data”.
If the location of the boiler or any part of the system is subject
to severe cold weather conditions, it is recommended that a
frost thermostat is fitted. Any part of the system that may be
vulnerable to freezing must be protected.
If the boiler is to be fitted into a cupboard, compartment or
unusual location, special procedures are necessary.
Make sure that the cupboard or compartment air vents are
positioned to be clear of obstructions at all times, refer to
Section 3, Cupboard/Compartment Ventilation.
5
DIMENSIONS
IN MILLIMETRES
INCREASE TO 25MM CLEARANCE
FROM COMBUSTIBLE MATERIAL
150
2) Type T630mA
800
2
)
2267
5
5
2.2 Clearances
The boiler should be positioned so that at least the minimum
operational and servicing clearances are provided, see diagram
2.1. Additional clearances may be required around the boiler for
installation.
221422A
8
5
5
150
Diagram 2.1
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.1 Flue
The flue must be installed in accordance with the rules in force
in the countries of destination.
3.2 Flue Position and Length
The air and flue ducting connect to the top of the boiler using the
elbow which can be positioned in one of three possible directions:
Rearward, left or right.
The standard flue is able to provide the duct length range shown
in diagram 3.1 for a rear flue or diagram 3.2 for a side flue.
If a longer flue duct is required, do not extend the ductings.
A 1, 2 and 3metre flue system and elbow/ terminal kit must be
used and can be supplied.
This is able to provide the duct length range shown in diagram
3.3 for rear flue or diagram 3.4 for a side flue.
A Flue Bend Kit or Vertical Flue Kit can be supplied with
instructions.
To make a neat finish to the flue outlet a flue collar kit, part No.
443286, with instructions, is available.
The use of this collar will mean that the flue lengths will need to
be altered, full instructions are given in the kit.
3.3 Terminal Position
The minimum acceptable siting dimensions for the terminal
from obstructions, other terminals and ventilation openings are
shown in diagram 3.5.
The terminal must be exposed to the external air, the position
allowing free passage of air across it at all times.
Car port or similar extensions of a roof only, or roof and one wall,
require special consideration with respect to any openings,
doors, vents or windows under the roof. Care is required to
protect the roof if made of plastic sheeting. If the car port
comprises of a roof and two or more walls seek advice from the
local gas undertaking before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering, an
aluminium shield 1500mm long should be fitted immediately
beneath the guttering or eaves. If the terminal is fitted within
450mm below painted eaves or a painted gutter, an aluminium
shield 750mm long should be fitted immediately beneath the
guttering or eaves.
3.4 Timber Frame Buildings
If the boiler is to be installed in a timber frame building seek
advice from the local gas undertaking or from Hepworth Heating
Ltd.
WALL THICKNESS 'X': 75 TO 400mm
'X'
REAR FLUE - STANDARD
DISTANCE 'Y': 80 TO 343mm
Diagram 3.1
2311
2309
1m DISTANCE 'X': 75 TO 898mm
2m DISTANCE 'X': 75 TO 1898mm
3m DISTANCE 'X': 75 TO 2890mm
'X'
REAR FLUE - LONG
1m DISTANCE 'Y': 80 TO 833mm
2m DISTANCE 'Y': 80 TO 1833mm
3m DISTANCE 'Y': 80 TO 2833mm
2310
Diagram 3.3
2308
'Y'
SIDE FLUE - STANDARD
Left or Right
Diagram 3.2
SIDE FLUE - LONG
Left or Right
9
'Y'
Diagram 3.4
221422A
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.5 Terminal Guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
be central over the terminal.
The guard should be similar to that shown in diagram 3.5 and
can be bought from:
Tower Flue Components Ltd.
Morley Road
Tonbridge
Kent
TN9 1RA
A
A
F
G
UNDER CAR PORT etc.
2816
C
B,C
G
A
E
G
B,C
K
F
F
G
K
L
L
K
G
their type K3
3.6 Room Ventilation
Ventilation must be provided in accordance with the rules in
force in the countries of destination. The boiler is room sealed,
so where the boiler is fitted in a room or space, a permanent air
vent is not required.
3.7 Cupboard/Compartment Ventilation
If the boiler is to be fitted in a cupboard or compartment,
permanent high and low level air vents must be provided for
ventilation. The vents must have at least the effective areas
shown in Table 2.
TABLE 2 75e
PositionAir fromAir Direct
ofRoom orfrom
Air VentInternal spaceOutside
High Vent248cm2 38in
2
124cm2 19in
2
D
J
F
H,I
K
MINIMUM SITING DIMENSIONS FOR
FANNED FLUE TERMINALS
POSITION
MINIMUM
SPACING
mm
A DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING300
B BELOW GUTTER, DRAIN/SOIL PIPE75
C BELOW EAVES200
D BELOW A BALCONY OR CAR PORT200
E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES75
F FROM INTERNAL OR EXTERNAL
CORNERS300
G ABOVE ADJACENT GROUND OR
BALCONY LEVEL300
H FROM SURFACE FACING THE
TERMINAL600
IFACING TERMINALS1200
J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING1200
K VERTICAL FROM A TERMINAL1500
L HORIZONTALLY FROM A TERMINAL 300
Low Vent248cm2 38in
221422A
2
124cm2 19in
2
10
4783
Diagram 3.5
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
Btu/h x
1000kW
60
50
40
30
SYSTEM HEATING LOAD
FEET
15
10
5
AVAILABLE PUMP HEAD
0
GRUNDFOS
16
14
12
10
REMAINING CONVEYING CAPACITY OF PUMP
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
0
0
F
C
40
VARIOUS SYSTEM HEATING LOADS.
20
35
17
30.6
15
25
*
11
19.8
10
M
5
P
U
M
P
P
C
C
U
U
R
V
E
FLOW RATE
R
V
E
-
S
E
T
T
I
N
G
3
-
S
E
T
T
I
N
G
2
23
22
18
1715
1920
4.03.53.0
21
4.5
4
3
2
1
0
11
2.55.0
13
P
U
M
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL
RANGE
LITRES/Min
GALLONS/Min
SYSTEM DIFFERENTIAL TEMPERATURE
Diagram 4.1
WILO
Btu/h x
1000kW
60
16
50
14
40
12
10
30
SYSTEM HEATING LOAD
FEET
M
5
15
4
10
3
2
5
AVAILABLE PUMP HEAD
1
0
0
11
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
P
U
M
2.55.0
REMAINING CONVEYING CAPACITY OF PUMP
VARIOUS SYSTEM HEATING LOADS.
- Setting 2- Setting 1
P
U
M
P
C
U
R
V
E
-
S
E
T
N
G
T
I
N
1
/
W
I
L
FLOW RATE
G
2
/
W
I
L
O
S
E
T
T
I
N
O
S
E
T
T
I
N
G
18
1715
4.03.53.0
G
1920
21
4.5
P
C
U
R
V
E
-
S
E
T
T
I
13
22
23
0
C
0
F
40
20
35
17
30.6
15
25
11
19.8
10
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL
RANGE
LITRES/Min
GALLONS/Min
*
SYSTEM DIFFERENTIAL TEMPERATURE
Diagram 4.1A
11
221422A
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.1 General Notes
The boiler is intended for use in a sealed system only.
4.2 Safety Valve
The safety valve is an integral part of the boiler.
It cannot be adjusted but has a manual test device.
4.3 Pressure Gauge
A pressure gauge is incorporated into the boiler to indicate the
system pressure.
The gauge has a cold fill set pointer.
4.4 Pump
The circulation pump is integral with the boiler.
The remaining circulating pressure head available from the
boiler is shown in diagram 4.1, Grundfos or diagram 4.1A, Glowworm Wilo.
4.5 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of
8Litres, (1.76gall). If the system water content exceeds the
maximum quoted in Section 1, Data, an additional vessel
should be connected into the system as close as possible to the
central heating return connection of the boiler, see diagram 4.2.
The pressure shall not be less that the static head at the point
of connection, that is, the height of the top point of the system
above the expansion vessel.
4.6 Flow Rate
A valve must be incorporated in the main flow or return of the
system, valve “A” shown in the flow diagram 4.2. This valve
must be lockable and positioned so that inadvertent closure or
unauthorised interference is not possible. The design differential
can be between 11°C (20°F) and 17°C (30°F), dependent upon
the system resistance and the available pump head.
Grundfos Pump
The pump adjuster should normally be left at maximum (3) but
in some cases it is permissible to adjust the pump to a lower
setting (2), see diagram 4.1.
To use diagram 4.1 start with the required heating system load.
In the example shown the 80e maximum boiler output has been
chosen, 17.6kW (60,000Btu/h).
Draw a horizontal line from the required system differential
temperature axis to intersect the curve.
In the example 11°C (19.8°F) has been chosen,
shown . At the point of intersection draw a vertical
line to cross the pump curve, from this point draw a further
horizontal line to determine the available pump head. In the
example 1.9m (6ft4in) is available. A greater pump head can be
achieved by choosing a higher system differential temperature,
up to a maximum of 4.0m (13ft) at a system differential of 17°C
(30.6°F). The system must be designed such that the available
pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h)
then it is permissible to adjust the pump setting to (2),
shown . This results in an available pump head of
2.1m (7ft). This is the maximum that can be achieved with the
pump at this setting.
Glow-worm Wilo Pump
The pump adjuster should normally be left at maximum (2) but
in some cases it is permissible to adjust to a lower setting (1),
see diagram 4.1A.
To use diagram 4.1A start with the required heating system
load.
In the example shown the 80e maximum boiler output has been
chosen, 17.6kW (60,000Btu/h).
Draw a horizontal line from the required system differential
temperature axis to intersect the curve. In the example 11°C
(19.8°F) has been chosen,shown . At the point of
intersection draw a vertical line to cross the pump curve. From
this point draw a further horizontal line to determine the available
pump head. In the example 1.9m (6ft3in) is available. A greater
pump head can be achieved by choosing a higher system
differential temperature, up to a maximum of 4.0m (13ft) at a
system differential of 17°C (30.6°F). The system must be
designed such that the available pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h)
then it is permissible to adjust the pump setting to (1),
shown . This results in an available pump head
of 4.2m (13ft9in). This is the maximum than can be achieved
with the pump at this setting.
4.7 Bypass
It is essential that a bypass is fitted in all installations, 22mm o.d.
minimum. The bypass must have a lockable valve “B” in
diagram 4.2, incorporated in a position so that inadvertent
closure or unauthorised interference is not possible.
The bypass MUST be fitted before any system control. A
radiator bypass is NOT recommended.
4.8 Make-up
Provision should be made for replacing water lost from the
system using a make up bottle mounted in a position higher than
the top point of the system, connected through a non-return
valve to the return side of the heating circuit, see diagram 4.2.
Alternatively, provision for make-up can be made by prepressurisation of the circuit
221422A
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.9 Filling Sealed Systems
Provision for filling the system at a low level must be made.
Three methods of filling are shown in diagram 4.3.
There must be no permanent connection to the mains water
supply, even through a non-return valve.
NOTE: It is important that fittings used for connection to potable
water comply with the water undertakers requirements.
4.10 Corrosion Inhibitor
If an inhibitor is to be used in the system, contact the inhibitor
manufacturer so that they can recommend their most suitable
product.
When fitting the boiler into an existing system, special care
should be taken to drain the entire system, including radiators,
then thoroughly cleaning out before fitting the boiler whether or
not adding an inhibitor.
4.11 Draining
A draining tap must be provided at the lowest points of the
system, which will allow the entire system to be drained. An
additional draining tap MUST be fitted close to the boiler.
The flow and return isolation valves are provided with drain
points for boiler heat exchanger drainage.
METHOD 1
TEMPORARY
HOSE
COMBINED
CHECK VALVE
AND VACUUM
BREAKER
HEATING
SYSTEM
3-LITRE
MAKE-UP
BOTTLE
(if required)
NON-RETURN
VALVE
AUTO AIR
VENT
ADDITIONAL
EXPANSION
VESSEL
(if required)
HEATING
CIRCUIT
BOILER
MIN. 22mm
DIA. BY-PASS
RETURN
'A'
FLOW CONTROL
VALVE
'B'
BY-PASS
VALVE
DOMESTIC
WATER
HOT
FILLING
POINT
DRAIN
POINT
2818
METHOD 2
COLD SUPPLY
METHOD 3
SUPPLY
PIPE
SUPPLY
PIPE
TEMPORARY
HOSE
SUPPLY
PIPE
CISTERN
SUPPLY
STOP VALVE
HOSE
UNIONS
SUPPLY STOP
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HOSE
UNIONS
SUPPLY STOP
VALVE
OVERFLOW
SERVICING
VALVE
HOSE
UNIONS
SERVICING
VALVE
SERVICING
VALVE
PRESSURE
REDUCING
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
3132
HEATING
SYSTEM
HEATING
SYSTEM
Diagram 4.2
13
Diagram 4.3
221422A
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Domestic Hot Water System
5.1 General
The domestic hot water service must be in accordance with the
rules in force in the countries of destination.
5.2 Water Pressure
For the minimum and maximum working pressures of the
domestic hot water circuit of the boiler refer to Section 1.6 Data.
If the cold water supply pressure exceeds the maximum, a
governor must be fitted in the supply to the boiler to reduce the
pressure to within the limits given.
5.3 “Hard” Water Areas
In areas where the water is “hard”, more than 200mg/litre, it is
recommended that a proprietary scale reducer is fitted in the
cold water supply to the boiler. Check the total water “hardness”,
using the kit supplied, in the door, following the instructions
given. Consult the local water company for additional advice.
A double check valve assembly must be fitted upstream of the
scale reducer. For the relative position of the scale reducer and
pressure reducing valve, if required, refer to the manufacturer’s
instructions.
6 Installation Preparation
6.1 Unpacking
Remove the top carton and cut out the flue template from the
inner flap.
Open the control door, see diagram 6.1.
Remove the two screws securing the outer case and then lift it
at the top and pull it forwards and off.
Remove the cover of the inner case, secured with four screws,
see diagram 6.2.
Disconnect the gas service cock union and the front unions of
the isolation valves, see diagram 6.3.
Slightly loosen the clips of the gas service cock and the isolating
valves.
Remove the two boiler securing screws then remove the boiler
from the mounting frame, by pulling the studs from the clips and
unhooking it at the top.
6.2 Marking
The boiler mounting frame is the same width as the boiler but the
flue connection sticks out above it.
Place the boiler mounting frame on the wall in the required
position, see diagram 2.1 to maintain minimum clearances.
Make sure that the isolation valves are at the bottom facing
forwards and that the frame top is horizontal, then mark the four
wall fixing points through the holes in the two horizontal straps.
Position the flue template on the wall, the arrow points on the
centres of the two upper fixing points previously marked, see
diagram 6.4 which also shows dimensions.
For rear flue, mark the rear flue position as required, centre and/
or diameter.
OUTER CASE
SECURING SCREW (2)
( IF CLOCK FITTED (4) )
CENTRAL HEATING
SELECTOR SWITCH
CLOCKTIMER
IF FITTED
DOOR
RESET
SWITCH + NEON
6625
221422A
14
OUTER CASE
Diagram 6.1
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installation Preparation
For a side flue, mark the horizontal flue centre line at the sides
of the template. Extend the flue centre line horizontally left or
right to the internal corner where the flue is required to exit to
outside. Mark the position of the circular hole, on the flue exit
wall, using the dimensions given in diagram 6.5.
From the flue position marks, check that the flue terminal will be
in a suitable position, see diagram 3.6.
6.3 Flue Hole Cutting
Cut the hole horizontally in the wall, to the diameter shown in
diagram 6.4, using, preferably, a core drill.
5216
SECURING
SCREW (4)
DATA
LABEL
INNER
CASE
COVER
Diagram 6.2
6.4 Wall Sleeve
Note: If required, an optional Wall Sleeve Kit, Part No. 900862,
is available, complete with fixing instructions.
6.5 Boiler Mounting Frame Fixing
Position the flue template over the flue hole and check the
position of the wall fixing points. Mark the position of the fixing
holes again, if required.
Drill the four fixing holes and insert wall plugs to suit
No.10x50mm long screws.
Secure the boiler mounting frame to the wall using
No.10x50mm long screws.
C
MIN.
CLEARANCE
87
104
L
FLUE
CENTRELINE
115Dia.
0176M
CLIP (5)
UNION (5)
5232
584
480
CORNER
(Right Flue)
FLUE
TEMPLATE
(Cut from
carton top
BOILER
MOUNTING FRAME
FIXING POINTS
inner flap)
C
L
168168
115Dia.
300
CORNER
(Left Flue)
FLUE
CENTRE
LINE
TOP OF
BOILER
Diagram 6.4
2304
Diagram 6.3
15
Diagram 6.5
221422A
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
7.1 Flue Length
For a rear flue, measure the distance from the outside wall face
to the boiler mounting wall. Check that the flue length will be
suitable, see diagram 3.1 for a standard flue system or diagram
3.3 for a 1, 2 or 3metre flue system.
For a side flue, measure the distance from the outside wall face
to the side of the boiler mounting frame. Check that the flue
length will be suitable, see diagram 3.2 for a standard flue
system or diagram 3.4 for a 1, 2 or 3metre flue system.
All flue systems are installed in a similar manner to the standard
flue.
7.2 Rear Flue
Mark the air duct assembly and the flue duct at the lengths
shown in diagram 7.1 and 7.2, then cut to length, cutting square
and removing any burrs.
7.3 Side Flue
Mark the air duct assembly and the flue duct at the lengths
shown in diagram 7.1 and 7.3 then cut to length, cutting square
and removing any burrs.
7.4 Air Duct
Locate the flue duct and air duct in the flue elbow, making sure
that the flue duct is located in the flue terminal and the flue elbow
but is free to move to allow for expansion.
Check that the flue terminal is in the correct position and sticking
out the correct distance from the outside wall face, see diagram
7.1 and appropriate diagram 7.2 or 7.3.
Drill a hole, diameter as shown in diagram 7.4, in each side of the
air duct, through the holes in the flue elbow. Secure the air duct
to the flue elbow using the two screws supplied in the loose items
pack.
Seal around the joint between the air duct and the flue elbow
using the tape provided in the loose items pack.
Stick the self-adhesive seal, supplied in the flue pack, around
the air duct, in a position so that it will be flush with the outside
wall when installed, see diagram 7.5.
If the boiler is not to be fitted for some time, cover the hole in the
wall
7.5 Internal Access Flue
If access to the outside wall surface is not practical, the flue
system can be installed from inside. Use of the optional wall
sleeve kit is recommended, see diagram 7.5.
( AIR DUCT ASSEMBLY)X + 173
X
OUTSIDE
WALL
FACE
X + 125 ( FLUE DUCT )
REAR DUCT STANDARD - LONG
Y + 181
(FLUE DUCT)
Y
Y + 229
(AIR DUCT
ASSEMBLY)
OUTSIDE
WALL FACE
SIDE OF
BOILER
MOUNTING
FRAME
SIDE FLUE DUCTS
STANDARD OR LONG
FLUE
TERMINAL
FLUE DUCT
3.3 DIA HOLE IN EACH
SIDE OF THE AIR DUCT
TAPE
2333
BOILER
MOUNTING
WALL
Diagram 7.2
2301
Diagram 7.3
2334
22
2335
63
FLUE
TERMINAL
FLUE AIR DUCT
FLUE
DUCT
OUTSIDE
WALL
FACE
FLUE TERMINAL
221422A
Diagram 7.1
INTERNAL ACCESS
16
AIR DUCT
SCREW (2)
OUTSIDE
WALL FACE
AIR
DUCT
FLUE
TERMINAL
SEAL
FLUE
ELBOW
Diagram 7.4
2302
WALL
SLEEVE
Diagram 7.5
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Gas and Water Connections
8.1 Gas Connection
Provision is made for the gas supply to be connected from
below or through the wall at the rear of the boiler, see diagram
8.1 for position.
Refer also to “Gas Supply”, Section 1.7.
Make the gas supply connection to the gas service cock.
Slacken or remove the clip, as preferred, while making the
connection. Do not subject the gas service cock to heat as you
may damage the seals.
8.2 Water Connections
Provision is made for the domestic cold water inlet to be
connected from below or through an internal wall at the rear of
the boiler, see diagram 8.1 for position. Refer also to Section
5 “Domestic Hot Water System”.
Provision is made for the domestic hot outlet, heating flow and
return to be connected from below, through an internal wall at
the rear of the boiler or from above, passing down either side of
the boiler, see diagram 8.2 for clearances. Take care that any
pipework connected from above, within the boiler mounting
frame will clear the expansion vessels.
If necessary, temporarily fit the boiler, refer to Section 10.1,
“Mounting the Boiler”.
Flush out the domestic water and heating system before
connecting the boiler.
Make the connections to the domestic hot water outlet and the
heating system by means of the isolating valves, see diagram
8.1.
Slacken or remove the clips, as preferred, while making the
connections. Do not subject any of the isolating valves to heat
as you may damage the seals.
Make sure that the drain points on the isolating valves are
positioned towards the front of the boiler, also that the drain and
operating screw heads are accessible.
'NOTCH' MARKING POSITION OF
SAFETY VALVE DISCHARGE
63
DOMESTIC
COLD
WATER
SUPPLY IN
CENTRAL
HEATING
FLOW
GAS
SERVICE
CENTRAL
HEATING
RETURN
COCK
SLOT (CLOSED)
DRAIN POINT
BOILER
MOUNTING
FRAME
DOMESTIC
HOT
WATER
OUT
SLOT
(CLOSED)
Diagram 8.1
2297
2298
8.3 Safety Valve Discharge
WARNING. It must not discharge above an entrance or window
or any type of public access area.
A short discharge pipe is supplied loose with the boiler, which
when fitted to the safety valve, will end below the boiler at the
mark between the cold water inlet and the heating flow, for
position and dimension see diagram 8.1.
This must be extended, using not less than 15mm od pipe, to
discharge, in a visible position, outside the building, facing
downwards, preferably over a drain. The pipe must have a
continuous fall and be routed to a position so that any discharge
of water, possibly boiling, or steam cannot create any danger to
persons, damage to property or external electrical components
and wiring.
Note. To ease future servicing it is advisable to use a compression
type fitting to extend the discharge pipe.
17
Diagram 8.2
221422A
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
9.1 Supply Cable Connection
CAUTION: To prevent an induced current from switching the
central heating on, when not required, it is important that the
heating system control cables are separated from the other
mains supply cables.
The boiler requires a permanent mains supply through an
external isolator which must also isolate any heating system
controls, see diagram 9.2.
Any heating system controls must not interrupt the permanent
mains supply to the boiler.
Remove the electrical connector from the loose items pack.
Remove the two screws and cover from the connector, see
diagram 9.1.
Using PVC cable of a suitable length and rating as stated in
Section 1.8 “Electrical Supply”, connect the mains supply cable
to the appropriate terminals of the connector, see diagram 9.2.
Standard colours are, Brown - Live, Blue - Neutral, Green and
Yellow - Earth.
The mains cable outer insulation must not be cut back external
to the plug, see diagram 9.1.
Make the earth cable of a greater length so that if the cable is
strained the earth would be the last to become disconnected.
CAUTION: It is ESSENTIAL to make sure that the polarity is
correct.
9.2 Heating System Controls
CAUTION: To prevent an induced current from switching the
central heating on, when not required, it is important that the
heating system control cables are separated from the other
mains supply cables.
The heating system should have installed: a programmer and
room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the
room thermostat.
Note: For further information, see The Building Regulations
1991 - Conservation of fuel and power, 1995 edition - Appendix
G, table 4b.
If electrical controls are not to be used to regulate the heating
system, do not disturb the red link cable.
When any form of electrical control is being used to regulate the
heating system, remove the red link cable and connect heating
system controls in series.
The mains cable outer insulation must not be cut back external
to the plug.
9.5 Cable and Connector Securing
After completing all the connections to the boiler, secure the
cable(s) with the cover, using the two screws previously removed,
see diagram 9.1.
Clip the connector into position with the cable(s) at the back.
Secure all cables in the clamp immediately behind the connector.
If necessary also secure cables to the wall, using suitable cable
clips.
Keep all cables away from hot surfaces.
RED LINK
Remove when
connecting any
heating system
controls.
MAINS
CABLE
Diagram 9.1
CABLE
CLAMP
E
N
L
3
COVER
SCREW (2)
1
2
2643
9.3 Clock/Timer Kit
An internal clock/timer kit can be supplied, refer to the literature
supplied with it.
9.4 Frost Thermostat
If the installation requires protection by a “frost thermostat”,
connect a single pole type, to the appropriate terminals of the
connector.
221422A
18
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
EXTERNAL CLOCK
RED LINK.
REMOVE WHEN
CONNECTING ANY
HEATING SYSTEM
CONTROLS
(3) (L) (N) (E)(2)
CLOCK
TIME
CONTROL
JUNCTION
BOX
3 AMP
FUSE
DOUBLE
POLE
ISOLATOR
230V~50Hz
PERMANENT
MAINS SUPPLY
LNE
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
SWITCH
CONTACTS
ROOM
THERMOSTAT
FROST
THERMOSTAT
ELECTRICITY SUPPLY CONNECTIONS
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
MAINS POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz ROOM STAT. NO FROST STAT.
INTEGRAL CLOCK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(1)
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
POTENTIAL
FROST STAT.
230V~50Hz
FROST STAT. NO ROOM STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
230V~50Hz
FROST STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
MAINS
POTENTIAL
FROST STAT.
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT. USED AS LINK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
230V~50Hz
POTENTIAL
FROST STAT.
RED
LINK
MAINS
MAINS
POTENTIAL
ROOM STAT.
5217
(3) (L)(N)(2)(1)
3 AMP
FUSE
230V~50Hz
PERMANENT MAINS
DOUBLE
LN
POLE
ISOLATOR
SUPPLY
POTENTIAL
FREE ROOM STAT. NO FROST STAT.
(E)
E
POTENTIAL FREE
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT.
19
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
E
230V~50Hz
PERMANENT MAINS
SUPPLY
230V~50Hz
FROST STAT.
JUNCTION
BOX
230V~50Hz
POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
Diagram 9.2
221422A
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.1 Mounting the Boiler
After installing the boiler mounting frame, domestic and heating
water systems, making the electrical connections and preparing
the flue components, carry on as below:
Lift the boiler into position, hooking it on the boiler mounting
frame at the top, then loosely fit the two boiler securing screws
at the top, see diagram 6.3.
10.2 Gas and Water Connections
Locate the boiler water pipes into the isolation valves and the
gas service cock union halves. Fully push the boiler back to the
mounting frame, locating the studs into the clips.
Make the compression joint on the isolating valves and join the
gas service cock union. Secure all of the valves and gas service
cock with the clips.
10.3 Boiler Securing
Secure the boiler by tightening the two boiler securing screws
at the top.
10.4 Discharge Pipe
Remove the two control housing securing screws, see diagram
10.1.
Remove the control housing and support the control housing on
a surface or by screwing it to the front edge of the base, using
one of the securing screws, see diagram 10.1.
If required , to improve access, the air pressure switch can be
removed, refer to the service instructions, section 4.31.
Fit the short discharge pipe to the safety valve using the nut and
olive supplied loose, see diagram 10.2.
Extend the discharge pipe, using only a compression type fitting
to join the discharge extension, refer also to Section 8.3 “Safety
Valve Discharge”.
FASCIA
CONTROL HOUSING
SECURING SCREW (2)
SECURING
SCREW
(To support the
control housing if
necessary)
UNION
CONNECTION
CONTROL HOUSING
COVER SECURING
SCREW
FASCIA
SECURING
SCREW (3)
CONTROL
HOUSING
COVER
Diagram 10.1
3894 S
2795
10.5 Clock/timer Kit (if applicable)
Fit the clock/timer kit following the appropriate sections of the
instructions supplied with it.
10.6 Electrical Connector
Connect the two halves of the electrical connector together.
Clip the connector into position on the boiler mounting frame.
Secure the cables with cable clamp immediately behind the
connector.
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test earth continuity and short circuit of all cables
3. Test the polarity of the mains.
DISCHARGE PIPE
'NOTCH'
Diagram 10.2
221422A
20
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.7 Flue Fixing
Fit the self-adhesive gasket, supplied in the loose items pack,
to the flue elbow, see diagram 10.3.
Push the prepared ductings into and through the wall sleeve,
the longest protrusion of the flue terminal is positioned at the
top.
Note: The foam seal is a tight fit in the wall sleeve and the flue
system should not be inserted unless the cement has fully set
or it can be held from the other side.
Fit the flue elbow to the top of the boiler, see diagram 10.3, using
the four screws supplied loose. To assist with the location of the
flue elbow into the fan outlet, loosen the two wing nuts on the
flue collector angle and the two fan securing screws.
Tighten the four screws of the flue elbow evenly to ensure a
good seal at the gasket. Tighten the wing nuts and screws, if
slackened, to secure the flue collector and fan.
Make the wall good internally around the air duct.
Check that the ductings do not slope down towardsthe boiler.
11 Commissioning
11.1 Filling Domestic Water Circuit
Check that the boiler is isolated from the electrical supply, at the
external isolator.
Fully open the domestic water supply stop cock or valve in the
supply to the boiler.
Open the two domestic water isolation valves, slots in line with
the length of the valve, see diagram 8.1.
Open all hot water draw-off taps and close them when water
flows. Check for water soundness of the whole domestic water
system and boiler.
11.2 Filling the Heating System
It is essential that a bypass is fitted in all installations, 22mm o.d.
minimum. The bypass must have a lockable valves “B” in
diagram 4.2, incorporated in a position so that inadvertent
closure or unauthorised interference is not possible.
The bypass MUST be fitted before any system control. A
radiator bypass is not recommended.
Open the two central heating isolating valves, slots in line with
the length of the valve, see diagram 8.1.
Flush, fill and vent the system refer to Section 4.9 “Filling
Sealed Systems”.
WARNING. SEVERAL COMPONENTS OPERATE ON MAINS
VOLTAGE AND WITH THE OUTER CASE REMOVED, LIVE
COMPONENTS BECOME EXPOSED.
To assist in filling and venting, the pump may be operated:
Connect the electrical supply, set switch “C” to “On”, any
remote heating systems controls, time switch and/or room
thermostat to call for heat, see diagram 11.1.
Note. If the clock/timer kit is to be fitted, refer to the setting
instructions in the Instructions for Use.
Make sure that the automatic air vent is operating correctly, see
diagram 11.2.
Take care not to splash any of the electrical components.
Alternate the position of switch “C” between “On” and “Off”
positions to ensure that water flows through all parts of the
boiler and air is not trapped in the boiler internal bypass.
FLUE ELBOW
(REAR FLUE
SHOWN)
GASKET
SECURING
SCREW (4)
FLUE
COLLECTOR
FAN
SECURING
SCREW (2)
WING
NUT
Diagram 10.3
Pressurise the system until the pressure is 1.5bar (21.5lbf/in2).
Check the heating system and boiler for water soundness.
Check the operation of the safety valve by turning the safety
valve knob in the direction of the arrow.
Lower the pressure to the initial cold fill design pressure, refer
to Section 1.6 “Data”. Position the set pointer on the boiler
pressure gauge at this pressure also.
11.3 Preparation for Lighting
Isolate the boiler from the mains electrical supply at the external
isolator.
Test for soundness and purge air from the gas supply. Turn on
the gas service cock, slot in line with the length of the cock.
Loosen the burner pressure test point screw and connect a
suitable pressure gauge, see diagram 11.3.
11.4 Burner Pressure - Hot Water
The burner pressure is factory preset and no adjustment should
be required.
Connect the electrical supply; the pump will operate for about 30
seconds, then the pump will stop.
Fully open the largest hot water draw off tap whereby the main
burner will light, the flames gradually increasing to the maximum.
Check the soundness of the boiler gas joints, with the main
burner on, using a leak detection fluid. Take care not to splash
any of the electrical components.
Fully open the hot water throttle, (clockwise), see diagram 11.5.
Check that the water flow rate is not less than:
10.5 l/min (2.3 g/min), equivalent to 5.7 seconds to fill a 1 litre
container, or 3.3 seconds to fill a 1 pint container.
To achieve this flow rate a water pressure of at least 0.8bar is
required during commissioning, although subsequently the
appliance will work at a minimum pressure of 0.5bar.
This flow rate should prevent any modulation of the gas pressure.
2336
21
221422A
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
Check the burner pressure is within +/-0.35mbar (+/-0.14in wg).
of 15.6mbar (6.3in wg). If this is incorrect, the burner pressure
may be adjusted to the correct setting by turning the hot water
gas pressure adjuster (potentiometer), using an insulated
screwdriver, see diagram 11.4 . Gain access to the adjusters on
the control board by removing the control housing cover, see
diagram 10.1. Turn the adjuster slowly, always making adjustment
by reducing below the required pressure then increasing up to
the required setting, (turn clockwise to increase).
Close the hot water draw off.
If the maximum pressure cannot be obtained, check that the gas
supply of adequate size, refer to Section 1.7.
11.5 Gas Rate Modulation
The minimum gas rate is factory preset and no adjustment
should be required.
ALWAYS CHECK HOT WATER BURNER PRESSURE FIRST
- REFER TO SECTION 11.4.
To check the minimum gas rate, first make sure that the boiler is
isolated from the electrical supply at the external isolator.
Disconnect one of the electrical connectors (grey), from the
modulator, see diagram 11.3.
Insulate the connector to make sure that it does not contact any
metallic part of the boiler.
Switch on the electrical supply.
Fully open a hot water draw off tap and the main burner will light
at the minimum gas rate.
Check that the burner pressure is 2.4mbar +/-0.2mbar, (1.0in wg
+/-0.1in wg). If this is incorrect, it may be adjusted by removing
the cap and turning the larger adjusting nut of the modulator,
(anti-clockwise to decrease the pressure).
If the above adjustment was necessary, it will be essential to
check that the maximum pressure can still be obtained. Push the
spindle gently in to the stop and hold it in. The maximum
pressure should not be less than 16.1mbar, (6.5in wg). If this
pressure cannot be achieved, obtain it by turning the small
adjusting nut, (clockwise to increase the pressure). Always
adjust the minimum pressure first.
If the maximum pressure is unattainable, check that the gas
supply is of adequate size, refer to Section 1.7 “Gas Supply”. Put
right as necessary.
Isolate the boiler from the electrical supply then reconnect the
modulator cable and refit the cap.
SWITCH 'ON'
CENTRAL HEATING
SELECTOR SWITCH 'C'
PRESSURE
GAUGE 'A'
AUTOMATIC AIR
VENT CAP
SWITCH 'OFF'
5044
CONTROL
RESET
BUTTON +
NEON
5048
Diagram 11.1
4447 S
11.6 Domestic Water Flow Rate
Adjust the water throttle to obtain a flow rate of: 9.0 L/min (2.0
gall/min), equivalent to 6.7 seconds to fill a 1 litre container, or 3.8
seconds to fill a 1 pint container.
Close the tap when adjustment is satisfactory.
The minimum water flow rate is 3.6Litre/min (0.8gall/min)
equivalent to 16.5 seconds to fill a 1Litre container (9.5 seconds
to fill a 1pint container). If this flow rate cannot be achieved,
check that there is no partial blockage and that the supply is of
adequate size. Put right as necessary.
Close the hot water draw off tap.
221422A
22
Diagram 11.2
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.7 Burner Pressure - Heating
The burner pressure is factory preset and no adjustment should
be required.
Check that all remote heating system controls, room thermostats,
integral clock and the like are switched on/programmed and
calling for heat.
Set switch “C” to “On” as shown in diagram 11.1.
The pump will circulate water through the boiler and the main
burner will light.
Check that the burner pressure, with the heating system cold to
prevent any modulation of the gas pressure, is within +/-
0.2mbar (+/-0.08in wg) of 8.0mbar (3.4in wg), the central
heating pressure.
If the burner pressure is incorrect, it may be adjusted to the
correct setting by turning the central heating gas pressure
adjuster (potentiometer), using an insulated screwdriver, see
diagram 11.4. Turn the adjuster slowly, always making
adjustment by reducing below the required pressure then
increasing up to the required setting, (turn clockwise to increase).
Isolate the boiler from the electrical supply.
Remove the pressure gauge and tighten the test point screw.
Fit the cover and secure the control housing with the screws
previously removed.
Test for gas soundness around the burner pressure test point
with the main burner alight, using leak detection fluid. Take care
not to splash any of electrical components.
11.8 Temperature Settings
The domestic hot water outlet and central heating flow
temperatures are factory preset and sealed, therefore cannot
be adjusted.
The nominal temperature setting for the domestic hot water
outlet is 55
The nominal maximum flow temperature setting for central
heating is 82
o
C (131oF) at a flow rate of 3.6Litre/min (0.8gall/min).
o
C (180oF).
LARGE
ADJUSTING
NUT (MIN.
PRESSURE)
SMALL
ADJUSTMENT
NUT (MAX.
PRESSURE)
CAP
CENTRAL
HEATING
GAS PRESSURE
ADJUSTER
DO NOT
ADJUST
SPINDLE
SCREW
CONTROL
BOARD
TEST
POINT
ELECTRICAL
CONNECTOR
(GREY)
Diagram 11.3
HOT WATER
GAS
PRESSURE
ADJUSTER
5052
5085
11.9 Heating System - Commissioning
Check that all remote controls and integral clock are calling for
heat.
Fully open all radiator valves, flow control valve “A” and bypass
valve “B”, see diagram 4.2.
Set the heating system in operation and balance the radiators.
Adjust the control valve “A” to achieve the required system
differential temperature between the flow and return.
Turn off all radiators, then adjust bypass valve “B” to achieve the
same temperature difference between the boiler flow and
return.
Refer to Section 4.6 and diagram 4.1 and 4.1A.
Allow the system to reach maximum temperature then switch
off, isolate the boiler from the electrical supply and drain the
system rapidly whilst still hot.
Fill and vent the system as described in Section 11.2 “Filling the
Central Heating Circuit”. Add inhibitor, if applicable, refer to
Section 4.10 “Inhibitor”.
Lower the pressure to the initial cold fill design pressure, using
the external draining tap, close to the boiler, refer Table 2 and
Section 4.11.
Lock or remove the handles from the spindles of flow control
valve “A” and bypass valve “B” to prevent unauthorised
adjustment.
Diagram 11.4
11.10 Completion
The user control door is designed for left or right hand hinging.
If required the hinge can be moved to the other side to that
supplied, as follows:
Remove the hinge pin bracket securing screw then remove the
hinge pin retaining bracket and holding the door, remove the
hinge pin. Prise out the hinge pin bushes and fit on to the
opposite side of the door, see diagram 11.6.
Remove the screw and nut and fit to the opposite side of the
case. After removing the hinge pin retaining bracket refit the
door and hinge pin. Refit the hinge pin retaining bracket and fit
the securing screw.
Fit the catch assembly, supplied in the loose items pack, see
diagram 11.6.
23
221422A
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
If required, fit the plastic covers to hide the bracket securing
screws.
Change the position of the “Push” label to suit the new door
opening.
Clock/timer, if fitted, remove the screws, nuts and washers to
release the cover plate, see diagram 11.6.
Stick the casing label to the right hand side of the clock/timer.
Fit the outer case, secure with the four screws, see diagram
11.6.
Note: Secure with the two outer screws only if there is no clock/
timer fitted.
Set the boiler and any remote heating control to the desired
settings, then close the door.
11.11 Instruct the User
Instruct and demonstrate the lighting procedure, then advise
the user of the efficient and safe operation of the boiler.
Instruct and demonstrate the operation of any heating system
controls.
Advise the user on the use and maintenance of any scale
reducer and pass on any relevant instructional documents.
Advise the user that to ensure the continued efficient and safe
operation of the appliance it is recommended that it is checked
and serviced at regular intervals.The frequency of servicing will
depend upon the particular installation and usage, but in general
once a year should be enough.
Draw attention, if applicable, to the current issue of the Gas
Safety (Installation and Use) Regulations, Section 35, which
imposes a duty of care on all persons who let out any property
containing a gas appliance.
It is the Law that any servicing is carried out by a competent
person.
Advise the user of the precautions necessary to prevent damage
to the system and building in the event of the heating system
being out of use during frost and freezing conditions.
Reminder - Leave these instructions with the user.
DOMESTIC
HOT
WATER
THROTTLE
HINGE PIN RETAINING
BRACKET
BRACKET
SECURING
SCREW
HINGE PIN
NUT &
WASHER(2)
SCREW
(2)
PLASTIC COVERS
COVER
PLATE
2801
Diagram 11.5
6624
221422A
24
CATCH
ASSEMBLY
HINGE
PIN
PLASTIC
BUSH (2)
SECURING
NUT
OUTER CASE
SECURING
SCREWS (4)
SPACER
Diagram 11.6
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the
boiler it is recommended that it is checked and serviced as
necessary at regular intervals.
The frequency of servicing will depend upon the particular
installation conditions and usage, but in general once a year
should be enough.
The servicing of this boiler must be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
NOTE: To obtain a products of combustion reading, remove
the outer case see diagram 6.1Installation Instructions.
Disconnect the clear upper tube from the air pressure switch,
see diagram 1.2 and 4.28, insert the analyser probe into the
tube.
Typical values for this boiler at maximum domestic hot water
demand is:- CO
These are based on a 300mm length rear flue.
Make sure the appliance does not modulate whilst checking
combustion and allow the appliance to warm up for five minutes
before taking a reading.
Unless stated otherwise, parts removed or renewed during
servicing should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying
components, ALWAYS test for gas soundness and carry out
functional checks of controls.
Throw away all used sealing washers, gaskets and “O” rings
when renewing components.
Use the new ones supplied with the replacement.
6.5% to 7.5% and CO 0.003% to 0.013%.
2
1.2 Data Label
The data label is positioned on the front of the inner case cover,
see diagram 1.2.
1.3 Isolation of Boiler
Before starting any servicing or the replacement of parts,
isolate the boiler from the electrical supply at the external
isolator and close the gas service cock, see diagram 1.1.
BEFORE DRAINING THE BOILER, REFER TO SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door catch
is spring loaded, to open, push the side opposite to the hinge
then pull.
Remove the two screws securing the outer case then unhook
the case at the top and pull it forwards and off, see diagram
6.1Installation Instructions.
Note: Remove the four securing screws if there is a clock/timer
fitted.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four screws,
see diagram 1.2.
boiler will be under the supply water pressure. Before any parts
of this circuit are disconnected, turn the domestic cold water
isolating valve off, open the hot water taps to reduce the water
pressure in the boiler, close the hot water isolating valve and
drain the boiler at the valves, see diagram 1.1.
After replacing any water containing part of the central heating
circuit, make up the water loss, vent all air and pressurise the
system. Refer to “Commissioning” in the Installation Instructions.
Check for water soundness and that the safety valve seats
without leaking.
COLD WATER
SUPPLY IN
HEATING
FLOW
GAS
SERVICE COCK
HEATING
RETURN
HOT
WATER
OUT
SAFETY
VALVE
DISCHARGE
SLOT
SLOT
(CLOSED)
DRAIN
POINT
(CLOSED)
Diagram 1.1
SECURING
SCREW (4)
DATA
LABEL
INNER
CASE
COVER
PILOT
WINDOW
SCREW (2)
AIR
PRESSURE
SWITCH
AUTOMATIC AIR
Diagram 1.2
5266
VENT CAP
2793
5234
1.6 System Pressures and Draining
All parts containing water of the central heating circuit within the
boiler, are under the system pressure. Before any parts of this
circuit are disconnected, reduce the system pressure at the
external draining tap, turn the central heating isolating valves
off, and drain at the drain points on the appropriate valves, see
diagram 1.1.
All water containing parts of the domestic hot water circuit of the
25
Diagram 1.3
221422A
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Servicing
2.1 Isolation and Access
Before commencing, refer to Section 1.1.
Isolate the boiler from the electrical supply and close the gas
service cock, refer to Section 1.3.
Remove the outer case and the cover of the inner case, refer to
Sections 1.4 and 1.5.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the flue collector secured by two wing nuts and hook
bolts, see diagram 4.1.
Remove the main burner, refer to Section 4.2.
2.2 Cleaning Heat Exchanger
Place a sheet of paper or similar in the combustion chamber, to
act as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove paper
together with any debris.
Do not use a brush with metallic bristles.
2.3 Cleaning Main Burner
Use a vacuum cleaner or suitable brush to clean the burner
thoroughly, making sure that all burner ports are clear and
unobstructed.
Do not use a brush with metallic bristles.
2.4 Service Checks
Inspect the spark and sensing electrodes, Clean or renew if
necessary, refer to Sections 4.4, 4.5, 4.6 and 4.7.
Check the main injector, cleaning or renewing as necessary,
refer to Section 4.3.
Before replacing any of the parts removed during servicing,
inspect the condition of all seals and joints, renewing them as
necessary.
Check the condition of the combustion chamber insulation.
If renewing, refer to Section 4.30.
Check that the spark and sensing gaps are as shown in diagram
2.1.
2.6 Operational Checks
Light the boiler, carry out operational checks and any necessary
adjustments as described in “Commissioning” in the Installation
Instructions.
2.7 Completion
Hook the outer case on at the top and secure with the screws
previously removed, see diagram 6.1 Installation Instructions.
Close the door.
SENSING
ELECTRODE
SPARK
ELECTRODE
+0.5
5
-0.5
EARTH
ELECTRODE
+0.5
3
-0.5
-0.5
5017
5059
2.5 Initial Assembly
Make sure that the main burner is located on the main injector
and is horizontal, the tips of the rearmost blade under the two
burner guides.
The combustion chamber front panel should be fitted loosely,
then the flue collector also fitted loosely, making sure that it is
seated correctly on the heat exchanger and over the top edge
of the front panel.
To fit the fan, locate it into the rear bracket and ease the flue
elbow onto the fan outlet and secure with the two screws, see
diagram 4.1.
When fitting the flexible tubes to the air pressure switch make
sure the lower (red) tube from the fan connects to the lower
connection of the switch.
Connect the electrical cables to the fan, the polarity of the two
connectors is not important, see diagram 4.1.
Secure the flue collector and combustion chamber front panel
by tightening the wing nuts and screws, evenly, see diagrams
4.1 and 4.2.
221422A
SPARK AND SENSING GAP
26
Diagram 2.1
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
3.1 Initial Checks
If the boiler fails to operate, first check the following:-
1) That the electrical supply is available at the boiler and the
fuses are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED
BY INCORRECT TESTING WITH THE POWER ON.
2) Make sure that the system pressure gauge registers 0.7bar,
minimum, and that the automatic air vent works. Refer to
Installation Instructions, Section 11.2.
3) That the gas supply is available at the boiler and purged of
air.
4) That the boiler is set for the required service.
5) With the boiler central heating selector switched “Off”, see
diagram 6.1Installation Instructions, check that the domestic
water supply is available and water flows freely from the hot
taps. Close the taps.
6) With the boiler central heating selector switched “ON”, see
diagram 6.1Installation Instructions, check that all heating system
controls, if fitted, are working correctly and calling for heat. If not
isolate the boiler from the electrical supply.
Disconnect the rear multipole connector at the base of the boiler
and release the cable from the clamp. Remove the connector
cover and dependent on the type of control fitted test for
continuity, mains or at terminals 1 and 2, see diagram 3.1.
7) Check reset button see diagram 6.1 Installation Instructions,
- if red neon is lit press button. In certain circumstances the red
neon light may not come on, due to no system demand. Turn
on a domestic hot water draw off tap to create a demand, the
light should come on, if reset is required.
Allow the boiler and system to cool down waiting at least a
minimum of four minutes before pressing the reset button.
If this is satisfactory proceed with the detailed fault finding as
Section 3.3.
1
2
E
N
L
3
CABLE
CLAMP/COVER
SCREW (2)
CABLE
CLAMP
2883
CABLE TO
REMOTE
HEATING
CONTROLS
MAINS
CABLE
Diagram 3.1
3.2 Clock/Timer
If the clock has failed it can be bypassed by disconnecting the
plug at the wall frame.
Gain access to the control box refer to Section 4.12, disconnect
the clock wiring harness from the 4 way terminal block. Fit a
yellow link between the terminals Y1 and Y2.
This is a temporary measure and the clock should be repaired
or replaced as soon as possible.
27
221422A
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
CONTROL BOARD
TERMINALS,
BLOCK 3
CONTROL BOARD
TERMINALS,
BLOCK 2
3
2
2B
2B
2A
2A
2A
TRANSFORMER
CONTROL BOARD
PERMANENT
LIVE 230V~50Hz
T2A
FUSE
LOW
VOLT
24V~
CVI IGNITION UNIT
230V~
br
b
br
br
4b
5b
6b3a
br
b
or
p
y
bl
w
br
b
br
LN
br
N/CN/O
br
(L)
OPTIONAL
SWITCHED LIVE
FROM ROOM
STAT. 230V~50Hz
COMMON
CLOCK/TIMER
b
(N)
b
p
y
(L)
(N)
ON
PUMP
APS
FAN
RESET /
NVLO
INDICATOR
C
3
36
M
(N)
BOILER
OVERHEAT CUT OFF
br
3.3 Electrical
Preliminary electrical system checks, as outlined in a Multimeter
Instruction book, are the first checks to be carried out during a
fault finding procedure.
Isolate the boiler from the electrical supply, refer to Section 1.3.
Gain access to the boiler controls by removing the outer case,
refer to Section 1.4. Check that all cables and connectors are
secure.
Gain access to the control board, refer to Section 4.12. Check
all cables at the multipin connectors on the board.
Test the two fuses on the main control board and renew as
necessary. Fuse 1 type (2AT), Fuse 2 type T (630 mA). If a fuse
fails repeatedly or the initial fault-finding checks described in
Section 1.1 indicate a boiler fault, check the boiler electrical
circuits and follow the fault finding procedures, see diagram 3.2,
3.3, 3.4 and for clock/timer fault finding, diagram 3.5 and 3.6.
On completion of a fault finding task that has required the
disconnection and making of electrical connections then checks,
for earth continuity, polarity and resistance to earth must be
carried out.
5034
y
BROWN....................................br
BLUE ........................................b
RED...........................................r
PURPLE...................................p
VIOLET.....................................v
KEY
MAINS
FUNCTIONAL FLOW
Diagram 3.2
221422A
28
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
1 2 3 4 5 6 7 8 9 10 11 12
GAS VALVE
MODUREG
TRANSFORMER
TERMINAL No's
BLOCK 1
1
BLOCK 4
4
GREY
GREY
CVI IGNITION UNIT
GREY
GREY
8
TRANSFORMER
DHW
HIGH
LIMIT
7
24V
2
1
GREY
CVI IGNITION UNIT
1
TERMINAL No's
BLACK
YELLOW
WHITE
RED
GREY
GREY
WATER
PRESSURE
SWITCH
CONTROL BOARD
1
1
Fuse rating
1
630 mA Fuse
1
1
1
5067
D.H.W.
FLOW
SWITCH
CH SELECTOR
SWITCH
CH THERMISTOR
D.H.W.
THERMISTOR
RED
RED
ORANGE
ORANGE
PURPLE
PURPLE
RED
RED
BROWN
BROWN
ORANGE
ORANGE
PURPLE
PURPLE
4
4
4
4
4
4
4
4
Diagram 3.3
29
221422A
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
Carry out the initial fault finding checks described in Section 3.1.
Check that gas, water and electricity are available at the boiler.
Before starting tests isolate the boiler, make sure that the remote controls are not
calling for duty and there is no domestic hot water demand.
Remove the outer case, control housing and it's cover.
Check all connections on the control board and the boiler components, rectify or renew
as necessary. Two dummy two way connectors are provided for ease of testing
continuity. Remove fuses and test for continuity, if faulty, check cables and connections
for shorting to E or N, rectify if necessary and replace fuse, with spare provided.
Check central heating water pressure, repressurize if necessary.
Make sure boiler is cold. Check all pipes and connections between the Air Pressure
Switch (APS) fan and combustion sample point. Make sure sample point cap is fitted
correctly. The boiler will go to lockout if the boiler overheat cut off goes open circuit,
or the boiler fails to detect flame.
Isolate supply, disconnect cables, is there
continuity, across boiler overheat cut off, brown and
black on APS, DHW cut out, and yellow and grey
on W.P.S. Is there 8kΩ-10KΩ across CH and DHW
thermistor ?
NO
5063
Replace faulty
device.
YES
Disconnect red cables to
flow switch, turn on hot
water tap. Is there
continuity between red
cables ?
YES
Turn off hot water tap
is there open circuit,
between red flow switch
cables ?
YES
Connect all cables
restore supply, does pump
run for ≈ 30 seconds.
YES
NO
NO
NO
Replace faulty
flow switch.
Replace faulty
flow switch.
Is there
230V ac at
pump ?
YES
NO
Replace faulty
main PCB .
faulty pump
rectify.
AB
NO
Turn on hot water tap,
is red lockout neon lit.
YES
CONTINUED
221422A
30
Diagram 3.4
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
NO
Is burner
NO
pressure
at full DHW.
YES
Reduce DHW
water flow,
does burner
modulate.
YES
YES
A
B
NO
NO
Press reset switch
wait 15 seconds between
attempts. Are there sparks
at electrode ?
YES
Does burner light ?
YES
Does boiler go to lockout
after ≈ 10 seconds ?
YES
Isolate supply, Check
dimensions of sense
electrode and condition of
lead. If ok replace CVI
ignition unit ?
Does the DC voltage
across the modureg
reduce.
YES
NO
NO
NO
Check for shorting
check lead connections
to electrodes.
Check lead connections
to electrodes
Check
dimensions of
spark electrode,
if ok replace
CVI gas valve
unit.
Faulty main
PCB, replace.
5064
Turn off hot tap,
does burner
extinguish.
YES
Turn on CH
demand, does
pump operate.
YES
As heating
system
becomes
satisfied does
burner pressure
reduce ?
YES
D
NO
NO
NO
Normal
operation.
Faulty modureg, replace.
Faulty main PCB, replace.
Is there 230V ac on pump ?
YES
Faulty pump, replace.
Faulty main PCB, replace.
NO
Faulty main
PCB, replace.
C
CONTINUED
31
Diagram 3.4
221422A
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
NO
D
Faulty main
PCB.
Faulty CVl
ignition unit.
NO
NO
Is there between
15 - 30 V DC on the two
greys on CN1 main PCB ?
YES
Is there between
15 - 30 V DC on the
Modureg coil ?
YES
Faulty coil.
C
NO
5065
Faulty
transformer,
replace.
Faulty CVI
ignition
unit, replace.
NO
NO
Is there 24V ac on white
and red CNI on main PCB ?
YES
Faulty main
PCB, replace.
Is there 230ac on brown
and blue, on fan ?
YES
Faulty fan,
replace.
Is there 230ac between
NO
NO
Is there 230ac between
yellow on CH Overheat
Thermostat and Neutral.
YES
brown pin 10 and blue
pin 11 an CVI ignition
connector ?
YES
Is fan turning.
YES
NO
221422A
32
Faulty CVI
ignition unit.
Faulty APS,
replace.
Diagram 3.4
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
If mains potential room thermostat is connected, make sure that the switch live is connected
to Pin 1 in the 5 pole connector.
Check continuity of clock/timer harness, ensure an electrical supply is available,
make sure that remote controls are calling for heat.
Isolate the boiler from electrical supply,
remove outer case.
3 Fault Finding
5665
Switch on electrical supply, is there a
display on clock/timer?
YES
Disconnect and insulate the yellow cables from
heating common and heating on
Advance clock/timer until a demand is indicated
Is there now continuity between heating
common and heating on?
YES
Clock/timer in order if no central heating,
refer to main fault finding.
DIGITAL CLOCK/TIMER FAULT FINDING
NO
NO
Faulty clock/timer. Replace.
Faulty clock/timer. Replace.
Diagram 3.5
CLOCK FAULT FINDING
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1 in
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remote
controls are calling for heat.
Does clock keep time
No
Faulty clock
replace
Yes
No
Isolate electrical supply set clock to on period
Is there continuity across
common and heating on
Clock in order if no
central heating refer to
Yes
Set clock to off period. Is there continuity
across common and heating on
No
main fault finding
ELECTRO/MECHANICAL CLOCK/TIMER FAULT FINDING
33
5666
Yes
Diagram 3.6
221422A
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
Before replacing any part please read points below:Replacement of parts must only be carried out by a competent
person.
1. Refer to Section 1.1.
2. Always isolate the boiler from the electrical and as required,
the gas supply, as Section 1.3.
3. On completion, make good any water loss and pressurise the
system to initial design pressure, refer to “Commissioning” in
the Installation Instructions.
Before starting refer to Section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.4
and 1.5
4.1 Fan
Disconnect the two electrical connectors at the fan, see diagram
4.1. It is not necessary to disconnect the green and yellow earth
cable.
Remove the two flexible tubes from the fan.
When replacing the tubes from the air pressure switch ensure
the lower (red) tube from the fan connects to the lower connection
of the switch.
Remove the fan, secured with two screws at the front, also
located into the flue elbow and clip at the rear.
To renew the motor and impeller, remove the three screws
securing it to the housing.
Transfer the earth cable to the replacement motor terminal
marked, fitting the earth cable and shakeproof washer when
securing the fan.
To fit the fan, locate it into the flue elbow and rear bracket, push
fully upward into the flue elbow to ensure a good seal, then
secure the fan with the two screws.
The polarity of the two electrical connectors is not important.
FLUE COLLECTOR
SECURING
SCREW (2)
WINGNUT/
HOOK BOLT (2)
FLUE
COLLECTOR
ELECTRICAL
CONNECTORS
AIR PRESSURE
SWITCH TUBES
REAR BRACKET
Diagram 4.1
5086
2844
6084
4.2 Main Burner
Remove the inner case as Section 1.5.
Slacken the two wing nuts securing the flue collector, see
diagram 4.2.
Remove the combustion chamber front panel, secured with four
screws, see diagram 4.2.
Remove the burner support bracket wing nut and securing
screw, see diagram 4.2
Remove the spark electrode assembly from the burner secured
by two screws see diagram 4.3 and carefully lay it down in the
combustion chamber.
NOTE: the sensing lead will be connected to the burner.
Disconnect the lead when the burner is being removed.
Remove the main burner from the main injector at the rear.
Raise the burner up and forwards. Take care not to damage the
combustion chamber insulation.
Remove the sensing electrode and fit to new burner.
Make sure the sensing lead is reconnected and the main burner
is fitted correctly on assembly, located on the main injector and
horizontal, the tips of the rearmost blade under the two burner
guides, see diagram 4.3.
Locate the combustion chamber front panel under the front
edge of the flue hood on assembly, then secure all screws and
wing nuts.
SCREW (4)
COMBUSTION
CHAMBER
FRONT PANEL
WINGNUT (2)
WINGNUT
Diagram 4.2
221422A
34
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.3 Main Injector
Remove the main burner, refer to Section 4.2.
Unscrew the main injector.
When fitting the main injector, fit the new sealing washer,
supplied, to ensure gas soundness.
4.4 Spark Electrode
Remove the inner case as Section 1.5.
Slacken the two wing nuts securing the flue collector, see
diagram 4.2.
Remove the combustion chamber front panel, secured with four
screws.
Remove the spark and earth electrode assembly leads and
silicone tubes, securing nuts and washers
Disconnect the leads and silicone tubes.
NOTE: the ignition lead is black and the earth lead is white
4.5 Sensing Electrode
Remove the main burner refer to Section 4.2
4.6 Ignition Lead
Remove inner case as section 1.5, disconnect electrode
assembly and lead as described in section 4.4.
Remove silicone tube and disconnect black lead at the ignition
unit on gas valve. Slacken sealing angle and withdraw lead.
SPARK
ELECTRODE
SECURING
SCREW (2)
SILICONE
TUBES
EARTH ELECTRODE
SEALING ANGLE
6086
Diagram 4.4
6629
4.7 Sensing Lead
Remove main burner as described in Section 4.2 disconnect
the lead from sensing electrode, disconnect lead at the ignition
unit on gas valve.
Slacken sealing angle and withdraw lead.
4.8 Boiler Overheat Cutoff
Remove user control switch bracket by slackening securing
screws, disconnect electrical connections, see diagram 4.6.
Disconnect the boiler overheat cutoff electrical connectors, see
diagram 4.5.
Remove the overheat cutoff, secured with two screws, see
diagram 4.5.
Use the heat sink compound supplied, between the mounting
plate and the cutoff, when fitting it.
SENSING
ELECTRODE
6085
SECURING
SCREW (2)
Diagram 4.5
SECURING SCREW (2)
5029
USER
CONTROL
SWITCH
BRACKET
Diagram 4.3
ELECTRICAL
CONNECTORS
SELECTOR SWITCH
35
CONTROL RESET
BUTTON
Diagram 4.6
221422A
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.9 Water Pressure Switch
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the control housing, secured with two screws. Support
control housing on a surface or by screwing it to front edge of the
base, using the outer case securing screw, see diagram 4.10.
Disconnect the electrical connectors at the pressure microswitch,
see diagram 4.7.
Remove pressure switch, see diagram 4.7.
Replace the “O” ring seal with the new seal provided.
Make sure that the switch terminals are facing diagonally
forwards to give access, as shown in diagram 4.7.
Reconnect the electrical connections, refer to diagram 4.12.
4.10 Domestic Hot Water High Limit Control
Remove the pump, see Section 4.25.
Disconnect the electrical connectors at the domestic hot water
high limit control, see diagram 4.8.
Remove the high limit control from the flow pipe, secured with
two screws.
Use the heat sink compound supplied, between the mounting
plate and the control.
When refitting the electrical connections to the high limit control
the polarity is not important, see diagram 4.12.
4.11 Pressure Gauge
Remove the control housing assembly, see Section 4.9
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge bracket.
Disconnect the pressure gauge connection from the safety
valve, discard the washer, see diagram 4.9.
Remove the pressure gauge secured with the retaining spring
tabs.
Locate the supplied washer under the pressure gauge connection
when refitted to the safety valve.
4.12 Control Boards
Remove the clock/timer mounting bracket securing screws, see
diagram 4.29.
Remove control housing cover and fascia, see diagram 4.10.
Remove the control housing assembly, Section 4.9.
Disconnect all multi-pin connectors, see diagram 4.11.
Remove the control boards from the support posts, noting their
correct positions. Great care must be taken when handling any
control board.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI
STATIC HOLDER UNTIL IMMEDIATE REQUIREMENT.
To connect the multi-pin connectors correctly, see diagram
4.15.
When replacing the main control board check and if necessary
adjust the main burner gas pressure in both the hot water and
central heating modes. Refer to “Commissioning” in the
Installation Instructions.
D.H.W. HIGH LIMIT
CONTROL
ELECTRICAL
CONNECTORS
SAFETY
VALVE
SEALING
WASHER
PRESSURE
GAUGE
CONNECTION
SECURING
SCREW (2)
PRESSURE
GAUGE
SECURING
SCREW (2)
4816
WATER
PRESSURE
SWITCH
Diagram 4.7
6630
D.H.W.
HIGH
LIMIT
CONTROL
Diagram 4.8
2831
PRESSURE
GAUGE
BRACKET
Diagram 4.9
221422A
36
Page 37
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.13 Transformer
Before starting, refer to Section 1.1
Isolate the boiler from the electrical supply, refer to section 1.3
Remove the outer case, refer to section 1.4
Remove the control housing, refer to section 4.9. Support the
control housing, see diagram 4.10.
Disconnect the electrical connectors from the transformer, see
diagram 4.11.
FASCIA
CONTROL
HOUSING
COVER
SECURING
SCREW
CONTROL HOUSING
SECURING SCREW (2)
FASCIA
SECURING
SCREW (3)
SECURING SCREW
(To support the control
housing if necessary)
3904
Remove the transformer, noting the correct position.
Reconnect the cables, refer to diagram 4.15.
TRANSFORMER
ELECTRICAL
CONNECTORS (6)
4 WAY
TERMINAL
BLOCK
5015
CONTROL
HOUSING
COVER
WIRING AS
DIAGRAM 4.12
Y
Y
1
2
B
Y
Y
*
Y
YBRB
BR
L
N
TIMER/CLOCK
(IF FITTED)
Diagram 4.10
4 WAY
TERMINAL
BLOCK
NOTE:
REMOVE YELLOW
*
LINK BEFORE
FITTING
CLOCK / TIMER
MULTI-PIN
CONNECTOR
(6)
CONTROL
BOARD
Y
Y
COMMON
HEATING ON
Diagram 4.11
5229
BR
B
CLOCK / TIMER
L
N
37
Diagram 4.12
221422A
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.14 Gas Valve
If applicable remove the clock/timer mounting bracket, see
diagram 4.29
Remove control box housing, see Section 4.9.
Remove the user control switch bracket, see diagram 4.6.
Disconnect the ignition unit and 2 electrical connectors. see
diagram 4.13.
Remove the four extended hexagon screws at the right hand
side of the gas valve,
Support the gas valve, disconnect the union nut at the gas
service cock and remove the valve complete with the inlet pipe.
Separate the valve from the pipe, noting the fitted position.
Discard the “O” rings and fit the new ones supplied.
Fit modulator cables the polarity is not important.
Check and adjust the main burner gas pressure in the hot water
and central heating modes, refer to “Commissioning” in the
Installation Instructions.
4.15 Ignition Unit
Remove control box housing, see Section 4.11.
Remove the user control switch bracket, see diagram 4.6.
Remove the ignition unit securing screws. see diagram 4.14.
Disconnect the electrical connector and the three electrode
leads.
Remove ignition unit.
Note: when re-fitting make sure the electrode leads are fitted to
the correct terminals. see diagram 4.14.
4.16 Central Heating Selector Switch and
Control Rest Button
Slacken the user control switch bracket securing screws and
remove the bracket from the keyhole slots, see diagram 4.6.
Pull the leads from the switch, see diagram 4.16.
To remove the switch press in the tabs on each side of it.
THE POLARITY OF THE ELECTRICAL CONNECTORS IS
IMPORTANT, SEE DIAGRAM 4.15.
4.17 Modulator
Isolate the boiler from the electrical supply and close the gas
service cock, refer to Section 1.3.
Remove the outer case, refer to Section 1.4.
Disconnect the two electrical connectors at the modulator, see
diagram 4.17.
Remove the modulator, secured with two screws.
Discard the gasket and fit the new one supplied, when fitting the
modulator.
Light, check and adjust the boiler if necessary, refer to
“Commissioning” in the Installation Instructions.
4.18 Domestic Hot Water Flow Switch
Before commencing refer to Section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.3.
Remove the outer case, refer to Section 1.4.
SECURING
SCREW
(4+4)
ELECTRICAL
CONNECTORS (2)
5233
SECURING
SCREW
SECURING
IGNITION UNIT
Diagram 4.13
SCREW
SECURING
SCREW (2)
EARTH
ELECTRODE
LEAD
SENSING
ELECTRODE
SPARK
LEAD
ELECTRODE
LEAD
Isolate the domestic hot water inlet, release the domestic water
pressure and drain, refer to Section 1.3 and 1.6.
Remove the control housing, refer to Section 4.9.
Remove the pressure gauge bracket, see diagram 4.9.
Disconnect the flow switch cables at the in line connectors.
Slacken or remove the clip securing the isolating valve, to ease
removal.
To remove the flow switch disconnect the water inlet pipe
assembly union nuts, see diagram 4.18, noting the fitted position.
Discard the sealing washers and use the new ones supplied.
It is recommended that the water inlet filter is cleaned or
renewed at this stage.
Make sure that the switch is positioned correctly, with the flow
arrow pointing upwards.
Diagram 4.14
5288
221422A
38
Page 39
Supplied By www.heating spares.co Tel. 0161 620 6677
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.19 Thermistor - Heating
Release the water pressure and drain the heating circuit of the
boiler, refer to Sections 1.3 and 1.6.
Disconnect the cables from the thermistor, see diagram 4.19.
Remove the thermistor, complete with its “O” ring.
The polarity of the electrical connections is not important.
4.20 Thermistor - Domestic Hot Water
On minimum clearance installations, remove the pump, see
Section 4.25.
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Disconnect the cables from the thermistor, see diagram 4.19.
Remove the thermistor complete with its “O” ring.
The polarity of the electrical connections is not important.
4.21 Safety Valve
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.11.
Disconnect the union nuts to release the safety valve, see
diagram 4.20.
ELECTRICAL
CONNECTORS
GAS
VALVE
CONTROL RESET
BUTTON
SELECTOR
SWITCH
5027
Diagram 4.16
5043
4.22 Water Inlet Filter
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3, 1.6 and 4.19 or 4.18 diagram.
4.23 Domestic Hot Water Throttle
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe assembly, refer to
Section 4.18.
Remove the cap nut and carefully remove the throttle adjuster,
by unscrewing and pushing it out, see diagram 4.21.
Clean if necessary, taking care not to damage the throttle body.
Reset the domestic hot water flow rate refer to Section 11.7 in
Installation Instructions.
4.24 Mini Expansion Vessel
Release the water pressure and drain the domestic circuit of the
boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe complete with the
mini-expansion vessel from the boiler, refer to Section 4.18.
When refitting use the new sealing washer supplied.
GASKET
MODULATOR
TORX
SCREW (2)
SPACER
ELECTRICAL
CONNECTOR (2)
221422A
40
HONEYWELL
Diagram 4.17
Page 41
Supplied By www.heating spares.co Tel. 0161 620 6677
FLOW
SWITCH
FILTER
UNION
NUT
WATER
FILTER
UNION NUT
VIEW ON ARROW 'A'
4 Replacement of Parts
5267
FLOW SWITCH
LOCKNUT
'A'
FLOW SWITCH
ELECTRICAL
CABLES
SAFETY
VALVE
2794
DISCHARGE
PIPE
UNION
NUT
UNION
NUT
Diagram 4.20
WATER
INLET
PIPE
ASSEMBLY
ISOLATING VALVE
UNION
NUT
'O' RING
THROTTLE
Diagram 4.18
6631
CAP
NUT
THROTTLE
ADJUSTER
'O' RING
Diagram 4.21
MINI
EXPANSION
VESSEL
4600
5271
CENTRAL
HEATING
THERMISTOR
CONNECTORS
D.H.W.
THERMISTOR
'O' RING
Diagram 4.19
41
SEALING WASHER
Diagram 4.22
221422A
Page 42
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.25 Pump
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove control housing, see Section 4.9.
Disconnect the electrical connectors at the water pressure
microswitch. Remove the water pressure switch, refer to
Section 4.9.
Remove the terminal cover from the pump and disconnect the
cable, see diagram 4.23.
Disconnect the pump at the unions.
Discard the sealing washers.
Make sure that the flow direction arrow is pointing upward when
fitting, and use the new sealing washers.
Refit water pressure switch, refer to Section 4.9.
The flow adjuster on the new pump should be set to that of the
original, refer also to Section 4.6 in the Installation Instructions.
The flow rate should be controlled by means of a valve in the
heating flow, refer to Section 11.10 in the Installation Instructions.
Note: Should the pump fail to operate, refer to diagram 4.23. If
all is in order, but the pump still does not operate, remove the
end screw, or cap, see diagram 4.23, then turn the pump spindle
to release any temporary seizure.
DO NOT HIT THE SPINDLE.
PUMP
SPINDLE
END
SCREW
PUMP
ADJUSTER
TERMINAL
COVER SCREW
FLOW
DIRECTION
ARROW
UPPER
PUMP
UNION
LOWER
PUMP
UNION
5223
4.26 Automatic Air Vent
Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6.
Remove the automatic air vent, see diagram 4.24.
SLACKEN THE SMALL CAP ON THE AIR VENT. THIS MUST
NOT BE RE-TIGHTENED.
When refitting use the new sealing washer provided.
4.27 Heat Exchanger
Release the water pressure and drain the central heating and
domestic hot water circuits refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the flue collector, secured with two wing nuts and hook
bolts, see diagram 4.1.
Remove the main burner, refer to Section 4.2.
Remove the automatic air vent, refer to
Section 4.29.
If renewing the heat exchanger, transfer the air vent, using the
new sealing washers provided.
Disconnect the union nuts of the heat exchanger to remove it,
see diagram 4.24.
Locate the raised location tabs on the combustion chamber
sides into the slots on the heat exchanger, see diagram 4.24.
Make sure that the main burner is located on the main injector
and is horizontal, the tips of the rearmost blade under the two
burner guides, see diagram 4.3.
The combustion chamber front panel should be fitted loosely,
then the flue collector also fitted loosely, ensuring that it is
seated correctly on the heat exchanger and over the top edge
of the front panel.
LOCATION
SLOT
CAP
UNION (4)
Diagram 4.23
2284
AUTOMATIC
AIR VENT
SEALING
WASHER
Diagram 4.24
221422A
42
Page 43
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.28 Combustion Chamber Insulation
Remove the fan, refer to Section 4.1.
Remove the flue collector, secured with two wing nuts and hook
bolts, see diagram 4.1.
Remove the combustion chamber front panel, secured with four
screws, see diagram 4.2.
Remove the front insulation piece secured with a clip, see
diagram 4.25.
Slide out both side insulation pieces
Pull the lower rear insulation forwards, then slide the upper rear
insulation down from behind the heat exchanger.
COMBUSTION CHAMBER
FRONT PANEL
CLIP
FRONT
INSULATION
5269
SIDE INSULATION PIECES
LOWER REAR INSULATION
43
SENSING
ELECTRODE
UPPER
REAR
INSULATION
Diagram 4.25
221422A
Page 44
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.29 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be
removed from the wall. As an alternative, a separate expansion
vessel of the same specification may be connected as close as
possible to the boiler, leaving the original in position, refer to the
Installation Instructions.
Remove the outer case and the cover of the inner case, refer to
Section 1.4 and 1.5.
Release the water pressure and drain, refer to Section 1.3 and
1.6.
Remove the fan from the flue collector, refer to Section 4.1.
Remove the flue elbow, secured to the boiler with four screws
and to the air duct with two screws, see diagram 4.26.
Disconnect the boiler water connection union nuts at the front
of the isolating valves, see diagram 1.1.
Disconnect the gas service cock union.
Disconnect the safety valve discharge pipe from the boiler, see
diagram 4.20.
Separate the two parts of the boiler multi-pole electrical
connector.
Slacken the clips of the gas service cock and the water isolating
valves.
Remove the boiler from the mounting frame, secured with two
screws at the top, see diagram 4.26. Pull the boiler from the
isolating valves. Unhook the boiler at the top and lift off.
Carefully lay the boiler down on its side for access to the
expansion vessel.
Disconnect the union nut connection, see diagram 4.27 and
discard the sealing washer for the new one supplied.
Remove the expansion vessel, secured with three clamping
screws.
Connect the union nut, when fitting the expansion vessel,
before clamping it.
SECURING
SCREW (4)
FLUE
ELBOW
BOILER MOUNTING
FRAME SCREW (2)
UNION NUT
CONNECTION AND
SEALING WASHER
AIR DUCT
SECURING
SCREW (2)
Diagram 4.26
2270S
2861
CLAMPING SCREW (3)
Diagram 4.27
AIR PRESSURE
SWITCH TUBES
CLEAR
RED
ELECTRICAL
CONNECTORS
AIR PRESSURE
SWITCH
5276
Diagram 4.28
221422A
44
Page 45
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.30 Viewing Window
Remove the viewing window, secured with two screws. When
fitting a new window use the gasket provided, see diagram 1.2.
4.31 Casing Seal
Remove the old seal, clean out the old adhesive.
Glue the new seal into place, making sure that there are no
breaks in it.
CLOCK/
TIMER
4.32 Air Pressure Switch
Disconnect the two electrical connectors at the air pressure
switch, see diagram 4.28.
Remove the flexible tubes from the switch.
Remove the air pressure switch, secured with two screws.
When replacing the tubes to the air pressure switch make sure
that the lower (red) tube from the fan connects to the lower
connection of the switch.
The polarity of the electrical connections is important, refer to
diagram 4.15.
4.33 Clock/Timer - if fitted
ELECTRO/MECHANICAL and DIGITAL clock/timer - Release
the mounting bracket securing screws, see diagram 4.29
Disconnect electrical cables, release securing clip to remove
the clock/timer spacer, see diagram 4.30.
6507
y
y
br b
COMMON
HEATING ON
SECURING
SCREWS (2)
ELECTRICAL
CONNECTIONS
MAINS
LIVE (L)
KEY
brBROWN
bBLUE
yYELLOW
MAINS
NEUTRAL (N)
SECURING CLIP (2)
MOUNTING
BRACKET
SPACER
PLATE
TIMER/CLOCK
6515
Diagram 4.29
45
Diagram 4.30
221422A
Page 46
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Spare Parts
5.1 Part Identification
The key number in diagram 5.1 and the first column of the list
will help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part number
and the description from the list together with the model name
and serial number information from the data label.
The data label is positioned on the inner case cover, see
diagram 6.1 Installation Instructions.