Glow-worm Swift flow 75e, SwiftFlow 80E Instructions For Use Installation And Servicing

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Installation and Servicing
To be left with the user
221422A.10.98
5226
75e
G.C. No. 47 313 16
Fanned Flue Combination Boiler
With Honeywell gas control
This is a Cat I2H Appliance
The instructions consist of three parts, User, Installation and Servicing Instructions, which include the Guarantee Registration Card.
The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use)
Regulations, be handed to the user on completion of the installation.
Guarantee Registration
Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances' are manufactured to the very highest standard so we are pleased
to offer our customers' a Comprehensive First Year Guarantee.
In the center pages are to be found your Guarantee Registration Card, which we recommend you complete and
return as soon as possible.
If this card is missing you can obtain a copy or record your registration by telephoning the Heatcall Customer
Our Guarantee gives you peace of mind plus valuable protection against breakdown by covering the cost of:
Service number 01773 828100.
All replacement parts
All labour charges
All call-out charges
One Contact Local Service
Fax: (01773) 828070
REGISTER YOUR GLOW-WORM APPLIANCE
FOR 1ST YEAR GUARANTEE PROTECTION
CALL 0181 380 2555
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
Important Information
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler, without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the current issue of the Statutory Requirements, see Section 1.4.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0087. Product/production certified by: Notified body 0087. The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state. INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
Introduction 3 Clock Settings 4 Lighting the Boiler 5
General Data 1 6
INSTALLATION
INSTRUCTIONS
Boiler Position 2 8 Flue and Ventilation 3 9 Heating System 4 11 Domestic Hot Water System 5 14 Installation Preparation 6 14 Flue Preparation 7 16 Gas and Water Connections 8 17 Electrical Connections 9 18 Boiler Fixing 10 20 Commissioning 11 21
SERVICING
INSTRUCTIONS
Servicing 2 26 Fault Finding 3 27 Replacement Parts 4 34 Spare Parts 5 46
General Data 1 25
221422A
2
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Introduction
Please read these instructions and follow them carefully for the safe and economical use of your Combination boiler.
This boiler must have been installed by a competent person in accordance with the rules in force in the countries of destination.
Once the pilot has been lit and the controls set, the boiler is automatic in operation.
The Swift-flow combination boiler is able to provide room heating as part of a central heating system and domestic hot water direct from the cold water supply, without the need for secondary storage.
The boiler can be fitted with one of two makes of clock, which look like this:-
Digital timer
IMPORTANT NOTICE: This boiler is for use only on G20 gas.
Clock / Timer
Electro / mechanical clock / timer
Gas Leak or Fault
If a gas leak or fault exists or is suspected, turn the boiler off and consult your local gas company or your local installation/ servicing company.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than in the summer.
The water temperature can be increased or reduced by adjusting the flow rate at the hot water draw off tap.
Boilers Installed in Compartments
If the boiler has been fitted into a compartment or cupboard, do not obstruct the compartment air supply vents.
Do not use the compartment for storage.
The colours of three core flexible cable are, blue - neutral, brown
- live, green and yellow - earth. As the markings on your plug may not correspond with these
colours continue as follows:­The wire coloured blue must be connected to the terminal
marked “N” or “Black”. The wire coloured brown must be connected to the terminal
marked “L” or “Red”. The wire coloured green and yellow must be connected to the
terminal marked “E” or “Green” or the earth symbol PVC flexible cable having a conductor size of 0.75mm
0.20mm) must be used within the boiler casing to connect to the boiler.
Electrical Supply Failure
The boiler will not work without an electrical supply.
6509
Normal operation of the boiler should resume when the electrical supply is restored.
Note. The boiler safety cutoff may have operated, please refer to the following section to reset.
Reset any external controls, to resume normal operation of the central heating.
The digital timer, has a lithium battery back up and will not need resetting.
Boiler Safety Cutoff Reset Button
The boiler is fitted with a safety cutoff device to prevent damage through overheating.
Should the main burner go out during a demand the red neon on the Reset Button will light.
In certain circumstances the red neon light may not come on, due to no system demand. It is suggested that a hot water draw off tap be opened to create a demand, the neon should then come on.
Allow the boiler and system to cool down waiting at least a minimum of four minutes before pressing the Reset button.
If the problem persists, turn the boiler off and consult the local gas company or your installation/ servicing company.
.
2
(24/
Electrical Supply
WARNING. The boiler must be earthed. The boiler must be connected to a 230V~50Hz permanent
supply. Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through one common isolator.
Isolation should preferably be by a double pole switched fused spur box. The fused spur box should be readily accessible and preferably adjacent to the appliance. It should be identified as to its use.
Alternatively a fused 3A 3 pin plug and shuttered unswitched socket may be used.
3
221422A
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Setting Instructions for Electro/mechanical Clock - if fitted
This clock has a twenty four hour dial, that is, 1pm is 13. To set the time, turn the whole face clockwise until the pointer
is against the time of day. To set any “Off” time, push the tappets outwards. To set any “On” time, push the tappets inwards. Time can be set either “On” or “Off” in fifteen minute segments. Note. The clock supplied could be fitted with an override device,
see diagram 1, which switches the clock programme “On” or “Off” permanently.
The switch will need to be repositioned to resume programmed working.
CLOCK FACE
0
OVERRIDE
SWITCH
12
11
13
14
15
16
17
18
19
20
21
22
23
24
CONSTANT OFF
0
PROGRAMMED CONSTANT ON
I
10
9
3
2
1
I
8
7
6
5
4
POINTER
TAPPETS
Diagram 1
Setting Instructions for the 7 Day Digital Clock/Timer
This is a 24 hour clock/timer, that is 1pm is 13:00, and has 8 “ON” and 8 “OFF” daily switching actions.
It is fitted with a lithium battery back up which protects the programme in the event of an electrical failure. The battery should have a life of several years.
5673
P
AUTO
I
MT
WTh
P
DAY HR MIN
RUN
FS
R
Su
Setting the Clock
1. With both AUTO and RUN switches set to the central position, press R reset button, the display will flash.
2. Set RUN switch to .
3. Set day of week by pressing button DAY.
4. Set time of day by pressing buttons HR and MIN.
5. Set RUN switch to the central position, colon will flash, this indicates the clock is set.
With the clock set, the factory preset programme shown below will operate.
4956
MON/FRI
ON - 06:30 OFF - 08:30 ON - 16:30 OFF - 22:30
SAT/SUN
ON - 07:00 OFF - 09:00 ON - 16:00 OFF - 23:00
Setting Timed Programmes
With the clock set to the correct time, see SETTING THE CLOCK paragraphs 1-4, and then continue as follows:
1. Set RUN switch to P , the display will indicate the 1st (ON) preset programme and the symbol .
2. Set day of week to be programmed by pressing the DAY button.
Note: The days can be selected individually or as groups:
Mon-Fri., Mon-Sat., Mon-Sun., Sat/Sun. An arrow will be displayed under the day
or days selected.
3. Set time of day by pressing the buttons HR and MIN.
4. Press button P to confirm programmes, the display will indicate the 2nd (OFF) preset programme and subsequently, 3rd, 4th, 5th, 6th, 7th, 8th.
5. Repeat procedures 2, 3 and 4 until desired programmes are set.
Note. It is not a requirement to use the 8 on/off programmes.
6. Set the RUN switch the central position, your appliance will now operate at the programmed times.
General Notes.
With the AUTO switch in the I position the central heating will operated constantly ON.
With the AUTO switch in the O position the central heating will not operate.
Soft Override button indicated by the symbol current central heating programme for the next available.
ON time programmes are indicated by the symbol
, this function will override the
.
Diagram 2
221422A
4
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
To Light the Boiler
1. Check that all five isolating valves are open, the slots in line with the length of the valve, see diagram 3.
2. Open the door, by pushing at the side opposite to the hinge.
3. CAUTION. A sealed pressurised system must be filled and pressurised by a competent person.
Only operate the boiler when you are sure that the system has been filled and pressurised. Check this by looking at the pressure gauge “A”, diagram 4, it should read 0.7bar minimum.
4. Check reset button neon, refer to previous instructions on page 3.
5. Open a hot water tap, check that water flows, then close it.
6. If you are in any doubt about the boiler being filled with water contact your installation/servicing company or the local gas company.
7. Check that the electrical supply to the boiler is ON at the external isolator.
8. Set switch “C”, clock/timer (if fitted) and any remote controls as required.
Close the door. In certain circumstances, a surge in water pressure may cause
the appliance to operate momentarily, this will be indicated by the pump starting and the fan speed increasing. This is quite normal.
Central Heating Selector Switch
For central heating set switch “C” to “On” as shown in diagram
4. The main burner will light. When the heating is controlled by a room thermostat and/or a
time switch, switch “C” must be set “On”. If a hot water tap is opened while the boiler is on for heating, the
burner flame will increase in size and priority will be given to hot water.
When the hot water tap is closed, the main burner flames will decrease in size but will remain alight until the boiler controls or any heating controls switch it off.
Which ever position switch “C” is in domestic hot water will be available.
To Turn the Central Heating Off
To turn the heating off for short periods, set switch “C” to “Off” as shown in diagram 4.
To turn on again set switch “On”, see diagram 4.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
If this appliance is installed in a rented property there is a duty of care imposed on the owner of the property by the current issue of the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Heatcall (Glow­worm’s own service organisation) using the telephone number behind the controls access door, see diagram 4.
COLD WATER SUPPLY IN
HEATING FLOW
SAFETY VALVE DISCHARGE
SLOT (OPEN)
SWITCH ON
GAS SERVICE COCK
HEATING RETURN
DRAIN POINT
CENTRAL HEATING SELECTOR SWITCH 'C'
5044
HOT WATER OUT
SLOT (OPEN)
Diagram 3
CONTROL RESET BUTTON
6088
6625
To Turn the Boiler Off
To turn the boiler off, isolate the boiler from the electrical supply. To turn on again following the operating instructions.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than in the summer.
The water temperature can be increased or reduced by adjusting the flow rate at the hot water draw off.
5
SWITCH OFF
PRESSURE GAUGE ‘A’
Diagram 4
221422A
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Clearances
The boiler requires a clearance in front, below and at the sides of the casing for safety, servicing and maintenance access, see diagram 2.1.
Protection Against Freezing
If the boiler is to be out of use for any long periods during severe weather, it is recommended that the whole system, including the combination boiler, should be drained to avoid the risk of freezing.
If in doubt, contact you installation/servicing company for advice.
Draining and Filling
CAUTION. This boiler works in a pressurised system which must only be drained, refilled and pressurised by a competent person.
Note: If the pressure gauge indicates a loss of system pressure, that is, less than 0.7bar, YOU MUST CONTACT YOUR INSTALLER.
Pressure Relief Safety Valve
CAUTION. A pressure relief safety valve and discharge pipe is fitted to the boiler. This valve must not be touched. Should there be any discharge from the pipe, turn the boiler off, isolate from the electrical supply and contact your installation/servicing company.
Cleaning
WARNING. This appliance contains metal parts (components) and care should be taken when handling and cleaning with particular regard to edges.
The boiler casing can be cleaned using a mild liquid detergent with a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may damage the paint work
Boiler Casing
CAUTION. Do not remove or adjust the casing in any way, as incorrect fitting may result in incorrect operation or failure to operate at all. If in doubt seek advice from the local gas company or your installation/servicing company.
Replacement Parts
If replacement parts are required apply to your local supplier or British Gas.
Please quote the name of the appliance.
MOUNTING WALL
82mm
2257A
101
63
2.5
C
L
C
25
1 General
331
168
117
SAFETY VALVE DISCHARGE
783
L
450
2257
63
25
ALL DIMENSIONS in MILLIMETRES
15mm COMPRESSION DOMESTIC WATER
6
221422A
22mm COMPRESSION CENTRAL HEATING
KEY:
66
1
1
/
(
2
/
in. BSPT)
2
Rc GAS CONNECTION
107
107
66
2.5
Diagram 1.1
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General
1.1 Installation
Materials and equipment should be fit for their purpose and of suitable quality and workmanship.
1.2 Important Notice
This boiler is for use only on natural gas, G20.
1.3 Sheet Metal Parts
WARNING. When installing or servicing this boiler care should be taken when handling the edges of sheet metal parts to avoid any possibility of personal injury.
1.4 Requirements
The installation of this boiler must be carried out by a competent person in accordance with the rules in force in the countries of destination.
Manufacturer’s instructions, supplied. Manufacturer’s instructions must not be taken as overriding
statutory requirements.
1.5 Data Label
The data label is on the inner case cover.
1.6 Data
See tables 1 and 2
1.7 Gas Supply
The gas installation shall be in accordance with the rules in force in the countries of destination.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
1.8 Electrical Supply
WARNING. This boiler must be earthed. All system components shall be of an approved type. The electrical installation shall be in accordance with the rules
in force in the countries of destination. Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through one common isolator.
Isolation should be by a double pole switched fused spur box, having a minimum contact separation of 3mm in each pole. The fused spur box should be readily accessible and preferably adjacent to the appliance.It should be identified as to its use.
Alternatively, a fused 3A 3pin plug and unswitched socket may be used, provided they are not used in a room containing a bath or shower.
The mains supply cable and other cables connected to the boiler must be the PVC flexible type of at least 0.75mm
0.20mm) .
2
(24/
TABLE 1
75e
NOMINAL kW HEAT INPUT(NETT) Btu/h NOMINAL kW HEAT OUTPUT Btu/h BURNER mbar PRESSURE in.wg APPROX. m3/h GAS RATE ft3/h
C.H.
MAX
18.2
62,000
16.12
55,000
8.0
3.4
2.0
69.5
D.H.W.
MAX
27.5
93,750
22.0
75,000
15.6
6.3
2.6
92.5
MIN
10.7
36,576
8.79
30000
2.4
1.0
1.2
42.1
WATER THROTTLE
MINI EXPANSION VESSEL
EXPANSION VESSEL
FANNED FLUE
HEAT EXCHANGER
MAIN BURNER
FLOW SWITCH
SAFETY VALVE
GAS VALVE
PRESSURE SWITCH
5228
AUTOMATIC AIR VENT
SPARK ELECTRODE
PUMP
D.H.W. COLD INLET
7
C.H. FLOW
GAS SUPPLY
SAFETY VALVE DISCHARGE
C.H. RETURN
Diagram 1.2
D.H.W. HOT OUTLET
221422A
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
TABLE 2
1 General
Lift Weight 37.0kg (81.4lb) Total Weight 50.4kg (111lb)
Gas connection Rc
1
/2 (1/2in BSPT)
Heating and return 22mm compression
Domestic hot water 15mm compression
Safety valve Preset 3bar (43.5lbf/in Safety valve discharge 15mm copper Water content 1.74 litres (0.38 gallon)
D.H.W 0.5 to 10bar
working pressure (7.25 to 188lbf/in
Maximum Heating 119 litres
system water (26.2 gallons) content using with a cold fitted expansion fill pressure vessel. of 0.7bar
2
)
Electrical supply 230V~50Hz Electrical rating 154W fused 3A
Internal Fuse rating 1) Type T2A
Expansion vessel capacity 8 litres (1.76 gallons)
Heating cold fill 0.7bar pressure minimum (10.1lbf/in2)
Ball valves are fitted in water and gas connections, plus a drain point on all water connections.
Boiler starts at an inlet pressure of 0.5bar but requires 0.8bar for maximum output.
For larger systems use an additional expansion vessel, see Section 4.
2 Boiler Position
2.1 Location
This boiler must be installed in accordance with the rules in force in the countries of destination.
This boiler is not suitable for fitting outside. Any electrical switch must be positioned so that it cannot be
touched by a person using the bath or shower. The boiler must be mounted on a flat wall which is sufficiently
robust to take its weight, refer to Section 1, “Data”. If the location of the boiler or any part of the system is subject
to severe cold weather conditions, it is recommended that a frost thermostat is fitted. Any part of the system that may be vulnerable to freezing must be protected.
If the boiler is to be fitted into a cupboard, compartment or unusual location, special procedures are necessary.
Make sure that the cupboard or compartment air vents are positioned to be clear of obstructions at all times, refer to Section 3, Cupboard/Compartment Ventilation.
5
DIMENSIONS IN MILLIMETRES
INCREASE TO 25MM CLEARANCE FROM COMBUSTIBLE MATERIAL
150
2) Type T630mA
800
2
)
2267
5
5
2.2 Clearances
The boiler should be positioned so that at least the minimum operational and servicing clearances are provided, see diagram
2.1. Additional clearances may be required around the boiler for installation.
221422A
8
5
5
150
Diagram 2.1
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.1 Flue
The flue must be installed in accordance with the rules in force in the countries of destination.
3.2 Flue Position and Length
The air and flue ducting connect to the top of the boiler using the elbow which can be positioned in one of three possible directions:
Rearward, left or right. The standard flue is able to provide the duct length range shown
in diagram 3.1 for a rear flue or diagram 3.2 for a side flue. If a longer flue duct is required, do not extend the ductings. A 1, 2 and 3metre flue system and elbow/ terminal kit must be
used and can be supplied. This is able to provide the duct length range shown in diagram
3.3 for rear flue or diagram 3.4 for a side flue. A Flue Bend Kit or Vertical Flue Kit can be supplied with
instructions. To make a neat finish to the flue outlet a flue collar kit, part No.
443286, with instructions, is available. The use of this collar will mean that the flue lengths will need to
be altered, full instructions are given in the kit.
3.3 Terminal Position
The minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in diagram 3.5.
The terminal must be exposed to the external air, the position allowing free passage of air across it at all times.
Car port or similar extensions of a roof only, or roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if made of plastic sheeting. If the car port comprises of a roof and two or more walls seek advice from the local gas undertaking before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering, an aluminium shield 1500mm long should be fitted immediately beneath the guttering or eaves. If the terminal is fitted within 450mm below painted eaves or a painted gutter, an aluminium shield 750mm long should be fitted immediately beneath the guttering or eaves.
3.4 Timber Frame Buildings
If the boiler is to be installed in a timber frame building seek advice from the local gas undertaking or from Hepworth Heating Ltd.
WALL THICKNESS 'X': 75 TO 400mm
'X'
REAR FLUE - STANDARD
DISTANCE 'Y': 80 TO 343mm
Diagram 3.1
2311
2309
1m DISTANCE 'X': 75 TO 898mm 2m DISTANCE 'X': 75 TO 1898mm 3m DISTANCE 'X': 75 TO 2890mm
'X'
REAR FLUE - LONG
1m DISTANCE 'Y': 80 TO 833mm 2m DISTANCE 'Y': 80 TO 1833mm 3m DISTANCE 'Y': 80 TO 2833mm
2310
Diagram 3.3
2308
'Y'
SIDE FLUE - STANDARD Left or Right
Diagram 3.2
SIDE FLUE - LONG Left or Right
9
'Y'
Diagram 3.4
221422A
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.5 Terminal Guard
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal.
The guard should be similar to that shown in diagram 3.5 and can be bought from:
Tower Flue Components Ltd. Morley Road Tonbridge Kent TN9 1RA
A
A
F
G
UNDER CAR PORT etc.
2816
C
B,C
G
A
E
G
B,C
K
F
F
G
K
L
L
K
G
their type K3
3.6 Room Ventilation
Ventilation must be provided in accordance with the rules in force in the countries of destination. The boiler is room sealed, so where the boiler is fitted in a room or space, a permanent air vent is not required.
3.7 Cupboard/Compartment Ventilation
If the boiler is to be fitted in a cupboard or compartment, permanent high and low level air vents must be provided for ventilation. The vents must have at least the effective areas shown in Table 2.
TABLE 2 75e Position Air from Air Direct
of Room or from Air Vent Internal space Outside
High Vent 248cm2 38in
2
124cm2 19in
2
D
J
F
H,I
K
MINIMUM SITING DIMENSIONS FOR FANNED FLUE TERMINALS POSITION
MINIMUM SPACING
mm
A DIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING 300 B BELOW GUTTER, DRAIN/SOIL PIPE 75 C BELOW EAVES 200 D BELOW A BALCONY OR CAR PORT 200 E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 75 F FROM INTERNAL OR EXTERNAL
CORNERS 300 G ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300 H FROM SURFACE FACING THE
TERMINAL 600 I FACING TERMINALS 1200 J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING 1200 K VERTICAL FROM A TERMINAL 1500 L HORIZONTALLY FROM A TERMINAL 300
Low Vent 248cm2 38in
221422A
2
124cm2 19in
2
10
4783
Diagram 3.5
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
Btu/h x 1000 kW
60
50
40
30
SYSTEM HEATING LOAD
FEET
15
10
5
AVAILABLE PUMP HEAD
0
GRUNDFOS
16
14
12
10
REMAINING CONVEYING CAPACITY OF PUMP
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
0
0
F
C
40
VARIOUS SYSTEM HEATING LOADS.
20
35
17
30.6
15
25
*
11
19.8
10
M
5
P
U
M
P
P
C
C
U
U
R
V
E
FLOW RATE
R
V
E
-
S
E
T
T
I
N
G
3
-
S
E
T
T
I
N
G
2
23
22
18
1715
19 20
4.03.53.0
21
4.5
4
3
2
1
0
11
2.5 5.0
13
P
U
M
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL RANGE
LITRES/Min GALLONS/Min
SYSTEM DIFFERENTIAL TEMPERATURE
Diagram 4.1
WILO
Btu/h x 1000 kW
60
16
50
14
40
12
10
30
SYSTEM HEATING LOAD
FEET
M
5
15
4
10
3
2
5
AVAILABLE PUMP HEAD
1
0
0
11
SHOWING RELATIVE SYSTEM DIFFERENTIAL AT
P
U
M
2.5 5.0
REMAINING CONVEYING CAPACITY OF PUMP
VARIOUS SYSTEM HEATING LOADS.
- Setting 2- Setting 1
P
U
M
P
C
U
R
V
E
-
S
E
T
N
G
T
I
N
1
/
W
I
L
FLOW RATE
G
2
/
W
I
L
O
S
E
T
T
I
N
O
S
E
T
T
I
N
G
18
1715
4.03.53.0
G
19 20
21
4.5
P
C
U
R
V
E
-
S
E
T
T
I
13
22
23
0
C
0
F
40
20
35
17
30.6
15
25
11
19.8
10
15
10
5
5
0
0
ACCEPTABLE
*
DIFFERENTIAL RANGE
LITRES/Min GALLONS/Min
*
SYSTEM DIFFERENTIAL TEMPERATURE
Diagram 4.1A
11
221422A
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.1 General Notes
The boiler is intended for use in a sealed system only.
4.2 Safety Valve
The safety valve is an integral part of the boiler. It cannot be adjusted but has a manual test device.
4.3 Pressure Gauge
A pressure gauge is incorporated into the boiler to indicate the system pressure.
The gauge has a cold fill set pointer.
4.4 Pump
The circulation pump is integral with the boiler. The remaining circulating pressure head available from the
boiler is shown in diagram 4.1, Grundfos or diagram 4.1A, Glow­worm Wilo.
4.5 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of 8Litres, (1.76gall). If the system water content exceeds the maximum quoted in Section 1, Data, an additional vessel should be connected into the system as close as possible to the central heating return connection of the boiler, see diagram 4.2.
The pressure shall not be less that the static head at the point of connection, that is, the height of the top point of the system above the expansion vessel.
4.6 Flow Rate
A valve must be incorporated in the main flow or return of the system, valve “A” shown in the flow diagram 4.2. This valve must be lockable and positioned so that inadvertent closure or unauthorised interference is not possible. The design differential can be between 11°C (20°F) and 17°C (30°F), dependent upon the system resistance and the available pump head.
Grundfos Pump
The pump adjuster should normally be left at maximum (3) but in some cases it is permissible to adjust the pump to a lower setting (2), see diagram 4.1.
To use diagram 4.1 start with the required heating system load. In the example shown the 80e maximum boiler output has been
chosen, 17.6kW (60,000Btu/h). Draw a horizontal line from the required system differential
temperature axis to intersect the curve. In the example 11°C (19.8°F) has been chosen,
shown . At the point of intersection draw a vertical line to cross the pump curve, from this point draw a further horizontal line to determine the available pump head. In the example 1.9m (6ft4in) is available. A greater pump head can be achieved by choosing a higher system differential temperature, up to a maximum of 4.0m (13ft) at a system differential of 17°C (30.6°F). The system must be designed such that the available pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h) then it is permissible to adjust the pump setting to (2), shown . This results in an available pump head of
2.1m (7ft). This is the maximum that can be achieved with the pump at this setting.
Glow-worm Wilo Pump
The pump adjuster should normally be left at maximum (2) but in some cases it is permissible to adjust to a lower setting (1), see diagram 4.1A.
To use diagram 4.1A start with the required heating system load.
In the example shown the 80e maximum boiler output has been chosen, 17.6kW (60,000Btu/h).
Draw a horizontal line from the required system differential temperature axis to intersect the curve. In the example 11°C (19.8°F) has been chosen,shown . At the point of intersection draw a vertical line to cross the pump curve. From this point draw a further horizontal line to determine the available pump head. In the example 1.9m (6ft3in) is available. A greater pump head can be achieved by choosing a higher system differential temperature, up to a maximum of 4.0m (13ft) at a system differential of 17°C (30.6°F). The system must be designed such that the available pump head is not exceeded.
If the heating system load is less than 13.2kW (45,000Btu/h) then it is permissible to adjust the pump setting to (1), shown . This results in an available pump head of 4.2m (13ft9in). This is the maximum than can be achieved with the pump at this setting.
4.7 Bypass
It is essential that a bypass is fitted in all installations, 22mm o.d. minimum. The bypass must have a lockable valve “B” in diagram 4.2, incorporated in a position so that inadvertent closure or unauthorised interference is not possible.
The bypass MUST be fitted before any system control. A radiator bypass is NOT recommended.
4.8 Make-up
Provision should be made for replacing water lost from the system using a make up bottle mounted in a position higher than the top point of the system, connected through a non-return valve to the return side of the heating circuit, see diagram 4.2.
Alternatively, provision for make-up can be made by pre­pressurisation of the circuit
221422A
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.9 Filling Sealed Systems
Provision for filling the system at a low level must be made. Three methods of filling are shown in diagram 4.3.
There must be no permanent connection to the mains water supply, even through a non-return valve.
NOTE: It is important that fittings used for connection to potable water comply with the water undertakers requirements.
4.10 Corrosion Inhibitor
If an inhibitor is to be used in the system, contact the inhibitor manufacturer so that they can recommend their most suitable product.
When fitting the boiler into an existing system, special care should be taken to drain the entire system, including radiators, then thoroughly cleaning out before fitting the boiler whether or not adding an inhibitor.
4.11 Draining
A draining tap must be provided at the lowest points of the system, which will allow the entire system to be drained. An additional draining tap MUST be fitted close to the boiler.
The flow and return isolation valves are provided with drain points for boiler heat exchanger drainage.
METHOD 1
TEMPORARY HOSE
COMBINED CHECK VALVE AND VACUUM BREAKER
HEATING SYSTEM
3-LITRE MAKE-UP BOTTLE (if required)
NON-RETURN VALVE
AUTO AIR VENT
ADDITIONAL EXPANSION VESSEL (if required)
HEATING CIRCUIT
BOILER
MIN. 22mm DIA. BY-PASS
RETURN
'A'
FLOW CONTROL VALVE
'B'
BY-PASS VALVE
DOMESTIC
WATER
HOT
FILLING POINT
DRAIN POINT
2818
METHOD 2
COLD SUPPLY
METHOD 3
SUPPLY PIPE
SUPPLY PIPE
TEMPORARY HOSE
SUPPLY PIPE
CISTERN
SUPPLY STOP VALVE
HOSE UNIONS
SUPPLY STOP VALVE
DOUBLE CHECK VALVE ASSEMBLY
HOSE UNIONS
SUPPLY STOP VALVE
OVERFLOW
SERVICING VALVE
HOSE UNIONS
SERVICING VALVE
SERVICING VALVE
PRESSURE REDUCING VALVE
DOUBLE CHECK VALVE ASSEMBLY
3132
HEATING SYSTEM
HEATING SYSTEM
Diagram 4.2
13
Diagram 4.3
221422A
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Domestic Hot Water System
5.1 General
The domestic hot water service must be in accordance with the rules in force in the countries of destination.
5.2 Water Pressure
For the minimum and maximum working pressures of the domestic hot water circuit of the boiler refer to Section 1.6 Data.
If the cold water supply pressure exceeds the maximum, a governor must be fitted in the supply to the boiler to reduce the pressure to within the limits given.
5.3 “Hard” Water Areas
In areas where the water is “hard”, more than 200mg/litre, it is recommended that a proprietary scale reducer is fitted in the cold water supply to the boiler. Check the total water “hardness”, using the kit supplied, in the door, following the instructions given. Consult the local water company for additional advice.
A double check valve assembly must be fitted upstream of the scale reducer. For the relative position of the scale reducer and pressure reducing valve, if required, refer to the manufacturer’s instructions.
6 Installation Preparation
6.1 Unpacking
Remove the top carton and cut out the flue template from the inner flap.
Open the control door, see diagram 6.1. Remove the two screws securing the outer case and then lift it
at the top and pull it forwards and off. Remove the cover of the inner case, secured with four screws,
see diagram 6.2. Disconnect the gas service cock union and the front unions of
the isolation valves, see diagram 6.3. Slightly loosen the clips of the gas service cock and the isolating
valves. Remove the two boiler securing screws then remove the boiler
from the mounting frame, by pulling the studs from the clips and unhooking it at the top.
6.2 Marking
The boiler mounting frame is the same width as the boiler but the flue connection sticks out above it.
Place the boiler mounting frame on the wall in the required position, see diagram 2.1 to maintain minimum clearances. Make sure that the isolation valves are at the bottom facing forwards and that the frame top is horizontal, then mark the four wall fixing points through the holes in the two horizontal straps.
Position the flue template on the wall, the arrow points on the centres of the two upper fixing points previously marked, see diagram 6.4 which also shows dimensions.
For rear flue, mark the rear flue position as required, centre and/ or diameter.
OUTER CASE SECURING SCREW (2) ( IF CLOCK FITTED (4) )
CENTRAL HEATING SELECTOR SWITCH
CLOCKTIMER IF FITTED
DOOR
RESET SWITCH + NEON
6625
221422A
14
OUTER CASE
Diagram 6.1
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Installation Preparation
For a side flue, mark the horizontal flue centre line at the sides of the template. Extend the flue centre line horizontally left or right to the internal corner where the flue is required to exit to outside. Mark the position of the circular hole, on the flue exit wall, using the dimensions given in diagram 6.5.
From the flue position marks, check that the flue terminal will be in a suitable position, see diagram 3.6.
6.3 Flue Hole Cutting
Cut the hole horizontally in the wall, to the diameter shown in diagram 6.4, using, preferably, a core drill.
5216
SECURING SCREW (4)
DATA LABEL
INNER CASE COVER
Diagram 6.2
6.4 Wall Sleeve
Note: If required, an optional Wall Sleeve Kit, Part No. 900862, is available, complete with fixing instructions.
6.5 Boiler Mounting Frame Fixing
Position the flue template over the flue hole and check the position of the wall fixing points. Mark the position of the fixing holes again, if required.
Drill the four fixing holes and insert wall plugs to suit No.10x50mm long screws.
Secure the boiler mounting frame to the wall using No.10x50mm long screws.
C
MIN. CLEARANCE
87
104
L
FLUE CENTRELINE
115Dia.
0176M
CLIP (5)
UNION (5)
5232
584
480
CORNER (Right Flue)
FLUE TEMPLATE (Cut from carton top
BOILER MOUNTING FRAME FIXING POINTS
inner flap)
C
L
168 168
115Dia.
300
CORNER (Left Flue)
FLUE CENTRE LINE
TOP OF BOILER
Diagram 6.4
2304
Diagram 6.3
15
Diagram 6.5
221422A
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
7.1 Flue Length
For a rear flue, measure the distance from the outside wall face to the boiler mounting wall. Check that the flue length will be suitable, see diagram 3.1 for a standard flue system or diagram
3.3 for a 1, 2 or 3metre flue system. For a side flue, measure the distance from the outside wall face
to the side of the boiler mounting frame. Check that the flue length will be suitable, see diagram 3.2 for a standard flue system or diagram 3.4 for a 1, 2 or 3metre flue system.
All flue systems are installed in a similar manner to the standard flue.
7.2 Rear Flue
Mark the air duct assembly and the flue duct at the lengths shown in diagram 7.1 and 7.2, then cut to length, cutting square and removing any burrs.
7.3 Side Flue
Mark the air duct assembly and the flue duct at the lengths shown in diagram 7.1 and 7.3 then cut to length, cutting square and removing any burrs.
7.4 Air Duct
Locate the flue duct and air duct in the flue elbow, making sure that the flue duct is located in the flue terminal and the flue elbow but is free to move to allow for expansion.
Check that the flue terminal is in the correct position and sticking out the correct distance from the outside wall face, see diagram
7.1 and appropriate diagram 7.2 or 7.3. Drill a hole, diameter as shown in diagram 7.4, in each side of the
air duct, through the holes in the flue elbow. Secure the air duct to the flue elbow using the two screws supplied in the loose items pack.
Seal around the joint between the air duct and the flue elbow using the tape provided in the loose items pack.
Stick the self-adhesive seal, supplied in the flue pack, around the air duct, in a position so that it will be flush with the outside wall when installed, see diagram 7.5.
If the boiler is not to be fitted for some time, cover the hole in the wall
7.5 Internal Access Flue
If access to the outside wall surface is not practical, the flue system can be installed from inside. Use of the optional wall sleeve kit is recommended, see diagram 7.5.
( AIR DUCT ASSEMBLY)X + 173
X
OUTSIDE
WALL
FACE
X + 125 ( FLUE DUCT )
REAR DUCT STANDARD - LONG
Y + 181
(FLUE DUCT)
Y
Y + 229 (AIR DUCT ASSEMBLY)
OUTSIDE WALL FACE
SIDE OF BOILER MOUNTING FRAME
SIDE FLUE DUCTS STANDARD OR LONG
FLUE TERMINAL
FLUE DUCT
3.3 DIA HOLE IN EACH SIDE OF THE AIR DUCT
TAPE
2333
BOILER MOUNTING WALL
Diagram 7.2
2301
Diagram 7.3
2334
22
2335
63
FLUE TERMINAL
FLUE AIR DUCT
FLUE DUCT
OUTSIDE WALL FACE
FLUE TERMINAL
221422A
Diagram 7.1
INTERNAL ACCESS
16
AIR DUCT
SCREW (2)
OUTSIDE WALL FACE
AIR DUCT
FLUE TERMINAL
SEAL
FLUE ELBOW
Diagram 7.4
2302
WALL SLEEVE
Diagram 7.5
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Gas and Water Connections
8.1 Gas Connection
Provision is made for the gas supply to be connected from below or through the wall at the rear of the boiler, see diagram
8.1 for position. Refer also to “Gas Supply”, Section 1.7. Make the gas supply connection to the gas service cock.
Slacken or remove the clip, as preferred, while making the connection. Do not subject the gas service cock to heat as you may damage the seals.
8.2 Water Connections
Provision is made for the domestic cold water inlet to be connected from below or through an internal wall at the rear of the boiler, see diagram 8.1 for position. Refer also to Section 5 “Domestic Hot Water System”.
Provision is made for the domestic hot outlet, heating flow and return to be connected from below, through an internal wall at the rear of the boiler or from above, passing down either side of the boiler, see diagram 8.2 for clearances. Take care that any pipework connected from above, within the boiler mounting frame will clear the expansion vessels.
If necessary, temporarily fit the boiler, refer to Section 10.1, “Mounting the Boiler”.
Flush out the domestic water and heating system before connecting the boiler.
Make the connections to the domestic hot water outlet and the heating system by means of the isolating valves, see diagram
8.1. Slacken or remove the clips, as preferred, while making the
connections. Do not subject any of the isolating valves to heat as you may damage the seals.
Make sure that the drain points on the isolating valves are positioned towards the front of the boiler, also that the drain and operating screw heads are accessible.
'NOTCH' MARKING POSITION OF SAFETY VALVE DISCHARGE
63
DOMESTIC COLD WATER SUPPLY IN
CENTRAL HEATING FLOW
GAS SERVICE
CENTRAL HEATING RETURN
COCK
SLOT (CLOSED)
DRAIN POINT
BOILER MOUNTING FRAME
DOMESTIC HOT WATER OUT
SLOT (CLOSED)
Diagram 8.1
2297
2298
8.3 Safety Valve Discharge
WARNING. It must not discharge above an entrance or window or any type of public access area.
A short discharge pipe is supplied loose with the boiler, which when fitted to the safety valve, will end below the boiler at the mark between the cold water inlet and the heating flow, for position and dimension see diagram 8.1.
This must be extended, using not less than 15mm od pipe, to discharge, in a visible position, outside the building, facing downwards, preferably over a drain. The pipe must have a continuous fall and be routed to a position so that any discharge of water, possibly boiling, or steam cannot create any danger to persons, damage to property or external electrical components and wiring.
Note. To ease future servicing it is advisable to use a compression type fitting to extend the discharge pipe.
17
Diagram 8.2
221422A
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
9.1 Supply Cable Connection
CAUTION: To prevent an induced current from switching the central heating on, when not required, it is important that the heating system control cables are separated from the other mains supply cables.
The boiler requires a permanent mains supply through an external isolator which must also isolate any heating system controls, see diagram 9.2.
Any heating system controls must not interrupt the permanent mains supply to the boiler.
Remove the electrical connector from the loose items pack. Remove the two screws and cover from the connector, see
diagram 9.1. Using PVC cable of a suitable length and rating as stated in
Section 1.8 “Electrical Supply”, connect the mains supply cable to the appropriate terminals of the connector, see diagram 9.2.
Standard colours are, Brown - Live, Blue - Neutral, Green and Yellow - Earth.
The mains cable outer insulation must not be cut back external to the plug, see diagram 9.1.
Make the earth cable of a greater length so that if the cable is strained the earth would be the last to become disconnected.
CAUTION: It is ESSENTIAL to make sure that the polarity is correct.
9.2 Heating System Controls
CAUTION: To prevent an induced current from switching the central heating on, when not required, it is important that the heating system control cables are separated from the other mains supply cables.
The heating system should have installed: a programmer and room thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the room thermostat.
Note: For further information, see The Building Regulations 1991 - Conservation of fuel and power, 1995 edition - Appendix G, table 4b.
If electrical controls are not to be used to regulate the heating system, do not disturb the red link cable.
When any form of electrical control is being used to regulate the heating system, remove the red link cable and connect heating system controls in series.
The mains cable outer insulation must not be cut back external to the plug.
9.5 Cable and Connector Securing
After completing all the connections to the boiler, secure the cable(s) with the cover, using the two screws previously removed, see diagram 9.1.
Clip the connector into position with the cable(s) at the back. Secure all cables in the clamp immediately behind the connector. If necessary also secure cables to the wall, using suitable cable
clips. Keep all cables away from hot surfaces.
RED LINK Remove when connecting any heating system controls.
MAINS CABLE
Diagram 9.1
CABLE CLAMP
E
N
L
3
COVER SCREW (2)
1
2
2643
9.3 Clock/Timer Kit
An internal clock/timer kit can be supplied, refer to the literature supplied with it.
9.4 Frost Thermostat
If the installation requires protection by a “frost thermostat”, connect a single pole type, to the appropriate terminals of the connector.
221422A
18
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
EXTERNAL CLOCK
RED LINK.
REMOVE WHEN CONNECTING ANY HEATING SYSTEM CONTROLS
(3) (L) (N) (E) (2)
CLOCK
TIME CONTROL
JUNCTION
BOX
3 AMP
FUSE
DOUBLE
POLE
ISOLATOR 230V~50Hz
PERMANENT
MAINS SUPPLY
LNE
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
SWITCH CONTACTS
ROOM
THERMOSTAT
FROST
THERMOSTAT
ELECTRICITY SUPPLY CONNECTIONS
INTEGRAL CLOCK
(3) (L) (N) (2) (1)
3 AMP FUSE
DOUBLE
LN
POLE
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION BOX
E
230V~50Hz PERMANENT MAINS SUPPLY
MAINS POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
230V~50Hz ROOM STAT. NO FROST STAT.
INTEGRAL CLOCK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(1)
INTEGRAL CLOCK
(3) (L) (N) (2) (1)
3 AMP FUSE
DOUBLE
POLE
LN
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION BOX
E
230V~50Hz PERMANENT MAINS SUPPLY
POTENTIAL
FROST STAT.
230V~50Hz FROST STAT. NO ROOM STAT.
INTEGRAL CLOCK
(3) (L) (N) (2) (1)
3 AMP FUSE
DOUBLE
LN
POLE
ISOLATOR
230V~50Hz FROST STAT.
INTEGRAL CLOCK
(3) (L) (N) (2) (1)
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
MAINS
POTENTIAL
FROST STAT.
JUNCTION BOX
E
230V~50Hz PERMANENT MAINS SUPPLY
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
230V~50Hz ROOM STAT. USED AS LINK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
230V~50Hz
POTENTIAL
FROST STAT.
RED LINK
MAINS
MAINS
POTENTIAL
ROOM STAT.
5217
(3) (L) (N) (2) (1)
3 AMP FUSE
230V~50Hz PERMANENT MAINS
DOUBLE
LN
POLE
ISOLATOR
SUPPLY
POTENTIAL FREE ROOM STAT. NO FROST STAT.
(E)
E
POTENTIAL FREE
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
230V~50Hz ROOM STAT.
19
3 AMP FUSE
DOUBLE
POLE
LN
ISOLATOR
E
230V~50Hz PERMANENT MAINS SUPPLY
230V~50Hz FROST STAT.
JUNCTION BOX
230V~50Hz
POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN CONNECTING SYSTEM CONTROLS
Diagram 9.2
221422A
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.1 Mounting the Boiler
After installing the boiler mounting frame, domestic and heating water systems, making the electrical connections and preparing the flue components, carry on as below:
Lift the boiler into position, hooking it on the boiler mounting frame at the top, then loosely fit the two boiler securing screws at the top, see diagram 6.3.
10.2 Gas and Water Connections
Locate the boiler water pipes into the isolation valves and the gas service cock union halves. Fully push the boiler back to the mounting frame, locating the studs into the clips.
Make the compression joint on the isolating valves and join the gas service cock union. Secure all of the valves and gas service cock with the clips.
10.3 Boiler Securing
Secure the boiler by tightening the two boiler securing screws at the top.
10.4 Discharge Pipe
Remove the two control housing securing screws, see diagram
10.1. Remove the control housing and support the control housing on
a surface or by screwing it to the front edge of the base, using one of the securing screws, see diagram 10.1.
If required , to improve access, the air pressure switch can be removed, refer to the service instructions, section 4.31.
Fit the short discharge pipe to the safety valve using the nut and olive supplied loose, see diagram 10.2.
Extend the discharge pipe, using only a compression type fitting to join the discharge extension, refer also to Section 8.3 “Safety Valve Discharge”.
FASCIA
CONTROL HOUSING SECURING SCREW (2)
SECURING SCREW (To support the control housing if necessary)
UNION CONNECTION
CONTROL HOUSING COVER SECURING SCREW
FASCIA SECURING SCREW (3)
CONTROL HOUSING COVER
Diagram 10.1
3894 S
2795
10.5 Clock/timer Kit (if applicable)
Fit the clock/timer kit following the appropriate sections of the instructions supplied with it.
10.6 Electrical Connector
Connect the two halves of the electrical connector together. Clip the connector into position on the boiler mounting frame.
Secure the cables with cable clamp immediately behind the connector.
Carry out preliminary electrical system checks as below:
1. Test insulation resistance to earth of mains cables.
2. Test earth continuity and short circuit of all cables
3. Test the polarity of the mains.
DISCHARGE PIPE
'NOTCH'
Diagram 10.2
221422A
20
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.7 Flue Fixing
Fit the self-adhesive gasket, supplied in the loose items pack, to the flue elbow, see diagram 10.3.
Push the prepared ductings into and through the wall sleeve, the longest protrusion of the flue terminal is positioned at the top.
Note: The foam seal is a tight fit in the wall sleeve and the flue system should not be inserted unless the cement has fully set or it can be held from the other side.
Fit the flue elbow to the top of the boiler, see diagram 10.3, using the four screws supplied loose. To assist with the location of the flue elbow into the fan outlet, loosen the two wing nuts on the flue collector angle and the two fan securing screws.
Tighten the four screws of the flue elbow evenly to ensure a good seal at the gasket. Tighten the wing nuts and screws, if slackened, to secure the flue collector and fan.
Make the wall good internally around the air duct. Check that the ductings do not slope down towardsthe boiler.
11 Commissioning
11.1 Filling Domestic Water Circuit
Check that the boiler is isolated from the electrical supply, at the external isolator.
Fully open the domestic water supply stop cock or valve in the supply to the boiler.
Open the two domestic water isolation valves, slots in line with the length of the valve, see diagram 8.1.
Open all hot water draw-off taps and close them when water flows. Check for water soundness of the whole domestic water system and boiler.
11.2 Filling the Heating System
It is essential that a bypass is fitted in all installations, 22mm o.d. minimum. The bypass must have a lockable valves “B” in diagram 4.2, incorporated in a position so that inadvertent closure or unauthorised interference is not possible.
The bypass MUST be fitted before any system control. A radiator bypass is not recommended.
Open the two central heating isolating valves, slots in line with the length of the valve, see diagram 8.1.
Flush, fill and vent the system refer to Section 4.9 “Filling Sealed Systems”.
WARNING. SEVERAL COMPONENTS OPERATE ON MAINS VOLTAGE AND WITH THE OUTER CASE REMOVED, LIVE COMPONENTS BECOME EXPOSED.
To assist in filling and venting, the pump may be operated: Connect the electrical supply, set switch “C” to “On”, any remote heating systems controls, time switch and/or room thermostat to call for heat, see diagram 11.1.
Note. If the clock/timer kit is to be fitted, refer to the setting instructions in the Instructions for Use.
Make sure that the automatic air vent is operating correctly, see diagram 11.2.
Take care not to splash any of the electrical components. Alternate the position of switch “C” between “On” and “Off”
positions to ensure that water flows through all parts of the boiler and air is not trapped in the boiler internal bypass.
FLUE ELBOW (REAR FLUE SHOWN)
GASKET
SECURING SCREW (4)
FLUE COLLECTOR
FAN SECURING SCREW (2)
WING NUT
Diagram 10.3
Pressurise the system until the pressure is 1.5bar (21.5lbf/in2). Check the heating system and boiler for water soundness.
Check the operation of the safety valve by turning the safety valve knob in the direction of the arrow.
Lower the pressure to the initial cold fill design pressure, refer to Section 1.6 “Data”. Position the set pointer on the boiler pressure gauge at this pressure also.
11.3 Preparation for Lighting
Isolate the boiler from the mains electrical supply at the external isolator.
Test for soundness and purge air from the gas supply. Turn on the gas service cock, slot in line with the length of the cock.
Loosen the burner pressure test point screw and connect a suitable pressure gauge, see diagram 11.3.
11.4 Burner Pressure - Hot Water
The burner pressure is factory preset and no adjustment should be required.
Connect the electrical supply; the pump will operate for about 30 seconds, then the pump will stop.
Fully open the largest hot water draw off tap whereby the main burner will light, the flames gradually increasing to the maximum.
Check the soundness of the boiler gas joints, with the main burner on, using a leak detection fluid. Take care not to splash any of the electrical components.
Fully open the hot water throttle, (clockwise), see diagram 11.5. Check that the water flow rate is not less than:
10.5 l/min (2.3 g/min), equivalent to 5.7 seconds to fill a 1 litre container, or 3.3 seconds to fill a 1 pint container.
To achieve this flow rate a water pressure of at least 0.8bar is required during commissioning, although subsequently the appliance will work at a minimum pressure of 0.5bar.
This flow rate should prevent any modulation of the gas pressure.
2336
21
221422A
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
Check the burner pressure is within +/-0.35mbar (+/-0.14in wg). of 15.6mbar (6.3in wg). If this is incorrect, the burner pressure may be adjusted to the correct setting by turning the hot water gas pressure adjuster (potentiometer), using an insulated screwdriver, see diagram 11.4 . Gain access to the adjusters on the control board by removing the control housing cover, see diagram 10.1. Turn the adjuster slowly, always making adjustment by reducing below the required pressure then increasing up to the required setting, (turn clockwise to increase).
Close the hot water draw off. If the maximum pressure cannot be obtained, check that the gas
supply of adequate size, refer to Section 1.7.
11.5 Gas Rate Modulation
The minimum gas rate is factory preset and no adjustment should be required.
ALWAYS CHECK HOT WATER BURNER PRESSURE FIRST
- REFER TO SECTION 11.4. To check the minimum gas rate, first make sure that the boiler is
isolated from the electrical supply at the external isolator. Disconnect one of the electrical connectors (grey), from the modulator, see diagram 11.3.
Insulate the connector to make sure that it does not contact any metallic part of the boiler.
Switch on the electrical supply. Fully open a hot water draw off tap and the main burner will light
at the minimum gas rate. Check that the burner pressure is 2.4mbar +/-0.2mbar, (1.0in wg
+/-0.1in wg). If this is incorrect, it may be adjusted by removing the cap and turning the larger adjusting nut of the modulator, (anti-clockwise to decrease the pressure).
If the above adjustment was necessary, it will be essential to check that the maximum pressure can still be obtained. Push the spindle gently in to the stop and hold it in. The maximum pressure should not be less than 16.1mbar, (6.5in wg). If this pressure cannot be achieved, obtain it by turning the small adjusting nut, (clockwise to increase the pressure). Always adjust the minimum pressure first.
If the maximum pressure is unattainable, check that the gas supply is of adequate size, refer to Section 1.7 “Gas Supply”. Put right as necessary.
Isolate the boiler from the electrical supply then reconnect the modulator cable and refit the cap.
SWITCH 'ON'
CENTRAL HEATING SELECTOR SWITCH 'C'
PRESSURE GAUGE 'A'
AUTOMATIC AIR VENT CAP
SWITCH 'OFF'
5044
CONTROL RESET BUTTON + NEON
5048
Diagram 11.1
4447 S
11.6 Domestic Water Flow Rate
Adjust the water throttle to obtain a flow rate of: 9.0 L/min (2.0 gall/min), equivalent to 6.7 seconds to fill a 1 litre container, or 3.8 seconds to fill a 1 pint container.
Close the tap when adjustment is satisfactory. The minimum water flow rate is 3.6Litre/min (0.8gall/min)
equivalent to 16.5 seconds to fill a 1Litre container (9.5 seconds to fill a 1pint container). If this flow rate cannot be achieved, check that there is no partial blockage and that the supply is of adequate size. Put right as necessary.
Close the hot water draw off tap.
221422A
22
Diagram 11.2
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.7 Burner Pressure - Heating
The burner pressure is factory preset and no adjustment should be required.
Check that all remote heating system controls, room thermostats, integral clock and the like are switched on/programmed and calling for heat.
Set switch “C” to “On” as shown in diagram 11.1. The pump will circulate water through the boiler and the main
burner will light. Check that the burner pressure, with the heating system cold to
prevent any modulation of the gas pressure, is within +/-
0.2mbar (+/-0.08in wg) of 8.0mbar (3.4in wg), the central heating pressure.
If the burner pressure is incorrect, it may be adjusted to the correct setting by turning the central heating gas pressure adjuster (potentiometer), using an insulated screwdriver, see diagram 11.4. Turn the adjuster slowly, always making adjustment by reducing below the required pressure then increasing up to the required setting, (turn clockwise to increase).
Isolate the boiler from the electrical supply. Remove the pressure gauge and tighten the test point screw. Fit the cover and secure the control housing with the screws
previously removed. Test for gas soundness around the burner pressure test point
with the main burner alight, using leak detection fluid. Take care not to splash any of electrical components.
11.8 Temperature Settings
The domestic hot water outlet and central heating flow temperatures are factory preset and sealed, therefore cannot be adjusted.
The nominal temperature setting for the domestic hot water outlet is 55
The nominal maximum flow temperature setting for central heating is 82
o
C (131oF) at a flow rate of 3.6Litre/min (0.8gall/min).
o
C (180oF).
LARGE ADJUSTING NUT (MIN. PRESSURE)
SMALL ADJUSTMENT NUT (MAX. PRESSURE)
CAP
CENTRAL HEATING GAS PRESSURE ADJUSTER
DO NOT ADJUST
SPINDLE
SCREW
CONTROL BOARD
TEST POINT
ELECTRICAL CONNECTOR (GREY)
Diagram 11.3
HOT WATER GAS PRESSURE ADJUSTER
5052
5085
11.9 Heating System - Commissioning
Check that all remote controls and integral clock are calling for heat.
Fully open all radiator valves, flow control valve “A” and bypass valve “B”, see diagram 4.2.
Set the heating system in operation and balance the radiators. Adjust the control valve “A” to achieve the required system
differential temperature between the flow and return. Turn off all radiators, then adjust bypass valve “B” to achieve the
same temperature difference between the boiler flow and return.
Refer to Section 4.6 and diagram 4.1 and 4.1A. Allow the system to reach maximum temperature then switch
off, isolate the boiler from the electrical supply and drain the system rapidly whilst still hot.
Fill and vent the system as described in Section 11.2 “Filling the Central Heating Circuit”. Add inhibitor, if applicable, refer to Section 4.10 “Inhibitor”.
Lower the pressure to the initial cold fill design pressure, using the external draining tap, close to the boiler, refer Table 2 and Section 4.11.
Lock or remove the handles from the spindles of flow control valve “A” and bypass valve “B” to prevent unauthorised adjustment.
Diagram 11.4
11.10 Completion
The user control door is designed for left or right hand hinging. If required the hinge can be moved to the other side to that supplied, as follows:
Remove the hinge pin bracket securing screw then remove the hinge pin retaining bracket and holding the door, remove the hinge pin. Prise out the hinge pin bushes and fit on to the opposite side of the door, see diagram 11.6.
Remove the screw and nut and fit to the opposite side of the case. After removing the hinge pin retaining bracket refit the door and hinge pin. Refit the hinge pin retaining bracket and fit the securing screw.
Fit the catch assembly, supplied in the loose items pack, see diagram 11.6.
23
221422A
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
If required, fit the plastic covers to hide the bracket securing screws.
Change the position of the “Push” label to suit the new door opening.
Clock/timer, if fitted, remove the screws, nuts and washers to release the cover plate, see diagram 11.6.
Stick the casing label to the right hand side of the clock/timer. Fit the outer case, secure with the four screws, see diagram
11.6. Note: Secure with the two outer screws only if there is no clock/
timer fitted. Set the boiler and any remote heating control to the desired
settings, then close the door.
11.11 Instruct the User
Instruct and demonstrate the lighting procedure, then advise the user of the efficient and safe operation of the boiler.
Instruct and demonstrate the operation of any heating system controls.
Advise the user on the use and maintenance of any scale reducer and pass on any relevant instructional documents.
Advise the user that to ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced at regular intervals.The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that any servicing is carried out by a competent person.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Reminder - Leave these instructions with the user.
DOMESTIC HOT WATER THROTTLE
HINGE PIN RETAINING BRACKET
BRACKET SECURING SCREW
HINGE PIN
NUT & WASHER(2)
SCREW (2)
PLASTIC COVERS
COVER PLATE
2801
Diagram 11.5
6624
221422A
24
CATCH ASSEMBLY
HINGE PIN
PLASTIC BUSH (2)
SECURING NUT
OUTER CASE SECURING SCREWS (4)
SPACER
Diagram 11.6
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.
The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
The servicing of this boiler must be carried out by a competent person in accordance with the rules in force in the countries of destination.
NOTE: To obtain a products of combustion reading, remove the outer case see diagram 6.1Installation Instructions. Disconnect the clear upper tube from the air pressure switch, see diagram 1.2 and 4.28, insert the analyser probe into the tube.
Typical values for this boiler at maximum domestic hot water demand is:- CO These are based on a 300mm length rear flue.
Make sure the appliance does not modulate whilst checking combustion and allow the appliance to warm up for five minutes before taking a reading.
Unless stated otherwise, parts removed or renewed during servicing should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying components, ALWAYS test for gas soundness and carry out functional checks of controls.
Throw away all used sealing washers, gaskets and “O” rings when renewing components.
Use the new ones supplied with the replacement.
6.5% to 7.5% and CO 0.003% to 0.013%.
2
1.2 Data Label
The data label is positioned on the front of the inner case cover, see diagram 1.2.
1.3 Isolation of Boiler
Before starting any servicing or the replacement of parts, isolate the boiler from the electrical supply at the external isolator and close the gas service cock, see diagram 1.1.
BEFORE DRAINING THE BOILER, REFER TO SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door catch is spring loaded, to open, push the side opposite to the hinge then pull.
Remove the two screws securing the outer case then unhook the case at the top and pull it forwards and off, see diagram
6.1Installation Instructions. Note: Remove the four securing screws if there is a clock/timer
fitted.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four screws, see diagram 1.2.
boiler will be under the supply water pressure. Before any parts of this circuit are disconnected, turn the domestic cold water isolating valve off, open the hot water taps to reduce the water pressure in the boiler, close the hot water isolating valve and drain the boiler at the valves, see diagram 1.1.
After replacing any water containing part of the central heating circuit, make up the water loss, vent all air and pressurise the system. Refer to “Commissioning” in the Installation Instructions.
Check for water soundness and that the safety valve seats without leaking.
COLD WATER SUPPLY IN
HEATING FLOW
GAS SERVICE COCK
HEATING RETURN
HOT WATER OUT
SAFETY VALVE DISCHARGE
SLOT SLOT (CLOSED)
DRAIN POINT
(CLOSED)
Diagram 1.1
SECURING SCREW (4)
DATA LABEL
INNER CASE COVER
PILOT WINDOW SCREW (2)
AIR PRESSURE SWITCH
AUTOMATIC AIR
Diagram 1.2
5266
VENT CAP
2793
5234
1.6 System Pressures and Draining
All parts containing water of the central heating circuit within the boiler, are under the system pressure. Before any parts of this circuit are disconnected, reduce the system pressure at the external draining tap, turn the central heating isolating valves off, and drain at the drain points on the appropriate valves, see diagram 1.1.
All water containing parts of the domestic hot water circuit of the
25
Diagram 1.3
221422A
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Servicing
2.1 Isolation and Access
Before commencing, refer to Section 1.1. Isolate the boiler from the electrical supply and close the gas
service cock, refer to Section 1.3. Remove the outer case and the cover of the inner case, refer to
Sections 1.4 and 1.5. Remove the fan from the flue collector, refer to Section 4.1. Remove the flue collector secured by two wing nuts and hook
bolts, see diagram 4.1. Remove the main burner, refer to Section 4.2.
2.2 Cleaning Heat Exchanger
Place a sheet of paper or similar in the combustion chamber, to act as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove paper together with any debris.
Do not use a brush with metallic bristles.
2.3 Cleaning Main Burner
Use a vacuum cleaner or suitable brush to clean the burner thoroughly, making sure that all burner ports are clear and unobstructed.
Do not use a brush with metallic bristles.
2.4 Service Checks
Inspect the spark and sensing electrodes, Clean or renew if necessary, refer to Sections 4.4, 4.5, 4.6 and 4.7.
Check the main injector, cleaning or renewing as necessary, refer to Section 4.3.
Before replacing any of the parts removed during servicing, inspect the condition of all seals and joints, renewing them as necessary.
Check the condition of the combustion chamber insulation. If renewing, refer to Section 4.30.
Check that the spark and sensing gaps are as shown in diagram
2.1.
2.6 Operational Checks
Light the boiler, carry out operational checks and any necessary adjustments as described in “Commissioning” in the Installation Instructions.
2.7 Completion
Hook the outer case on at the top and secure with the screws previously removed, see diagram 6.1 Installation Instructions.
Close the door.
SENSING ELECTRODE
SPARK ELECTRODE
+0.5
5
-0.5
EARTH ELECTRODE
+0.5
3
-0.5
-0.5
5017
5059
2.5 Initial Assembly
Make sure that the main burner is located on the main injector and is horizontal, the tips of the rearmost blade under the two burner guides.
The combustion chamber front panel should be fitted loosely, then the flue collector also fitted loosely, making sure that it is seated correctly on the heat exchanger and over the top edge of the front panel.
To fit the fan, locate it into the rear bracket and ease the flue elbow onto the fan outlet and secure with the two screws, see diagram 4.1.
When fitting the flexible tubes to the air pressure switch make sure the lower (red) tube from the fan connects to the lower connection of the switch.
Connect the electrical cables to the fan, the polarity of the two connectors is not important, see diagram 4.1.
Secure the flue collector and combustion chamber front panel by tightening the wing nuts and screws, evenly, see diagrams
4.1 and 4.2.
221422A
SPARK AND SENSING GAP
26
Diagram 2.1
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
3.1 Initial Checks
If the boiler fails to operate, first check the following:-
1) That the electrical supply is available at the boiler and the fuses are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED BY INCORRECT TESTING WITH THE POWER ON.
2) Make sure that the system pressure gauge registers 0.7bar, minimum, and that the automatic air vent works. Refer to Installation Instructions, Section 11.2.
3) That the gas supply is available at the boiler and purged of air.
4) That the boiler is set for the required service.
5) With the boiler central heating selector switched “Off”, see diagram 6.1Installation Instructions, check that the domestic water supply is available and water flows freely from the hot taps. Close the taps.
6) With the boiler central heating selector switched “ON”, see diagram 6.1Installation Instructions, check that all heating system controls, if fitted, are working correctly and calling for heat. If not isolate the boiler from the electrical supply.
Disconnect the rear multipole connector at the base of the boiler and release the cable from the clamp. Remove the connector cover and dependent on the type of control fitted test for continuity, mains or at terminals 1 and 2, see diagram 3.1.
7) Check reset button see diagram 6.1 Installation Instructions,
- if red neon is lit press button. In certain circumstances the red neon light may not come on, due to no system demand. Turn on a domestic hot water draw off tap to create a demand, the light should come on, if reset is required.
Allow the boiler and system to cool down waiting at least a minimum of four minutes before pressing the reset button.
If this is satisfactory proceed with the detailed fault finding as Section 3.3.
1
2
E
N
L
3
CABLE CLAMP/COVER SCREW (2)
CABLE CLAMP
2883
CABLE TO REMOTE HEATING CONTROLS
MAINS CABLE
Diagram 3.1
3.2 Clock/Timer
If the clock has failed it can be bypassed by disconnecting the plug at the wall frame.
Gain access to the control box refer to Section 4.12, disconnect the clock wiring harness from the 4 way terminal block. Fit a yellow link between the terminals Y1 and Y2.
This is a temporary measure and the clock should be repaired or replaced as soon as possible.
27
221422A
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
CONTROL BOARD TERMINALS, BLOCK 3 CONTROL BOARD TERMINALS, BLOCK 2
3
2
2B
2B
2A
2A
2A
TRANSFORMER
CONTROL BOARD
PERMANENT LIVE 230V~50Hz
T2A FUSE
LOW VOLT 24V~
CVI IGNITION UNIT
230V~
br
b
br
br
4b 5b
6b3a
br
b
or
p
y
bl
w
br
b
br
LN
br
N/C N/O
br
(L)
OPTIONAL SWITCHED LIVE FROM ROOM STAT. 230V~50Hz
COMMON
CLOCK/TIMER
b
(N)
b
p
y
(L)
(N)
ON
PUMP
APS
FAN
RESET / NVLO INDICATOR
C
3
36
M
(N)
BOILER OVERHEAT CUT OFF
br
3.3 Electrical
Preliminary electrical system checks, as outlined in a Multimeter Instruction book, are the first checks to be carried out during a fault finding procedure.
Isolate the boiler from the electrical supply, refer to Section 1.3. Gain access to the boiler controls by removing the outer case,
refer to Section 1.4. Check that all cables and connectors are secure.
Gain access to the control board, refer to Section 4.12. Check all cables at the multipin connectors on the board.
Test the two fuses on the main control board and renew as necessary. Fuse 1 type (2AT), Fuse 2 type T (630 mA). If a fuse fails repeatedly or the initial fault-finding checks described in Section 1.1 indicate a boiler fault, check the boiler electrical circuits and follow the fault finding procedures, see diagram 3.2,
3.3, 3.4 and for clock/timer fault finding, diagram 3.5 and 3.6. On completion of a fault finding task that has required the
disconnection and making of electrical connections then checks, for earth continuity, polarity and resistance to earth must be carried out.
5034
y
BROWN....................................br
BLUE ........................................b
RED...........................................r
PURPLE...................................p
VIOLET.....................................v
KEY
MAINS FUNCTIONAL FLOW
Diagram 3.2
221422A
28
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
1 2 3 4 5 6 7 8 9 10 11 12
GAS VALVE MODUREG
TRANSFORMER TERMINAL No's
BLOCK 1
1
BLOCK 4
4
GREY GREY
CVI IGNITION UNIT
GREY GREY
8
TRANSFORMER
DHW HIGH LIMIT
7
24V
2
1
GREY
CVI IGNITION UNIT
1
TERMINAL No's
BLACK
YELLOW
WHITE RED GREY
GREY
WATER PRESSURE SWITCH
CONTROL BOARD
1
1
Fuse rating
1
630 mA Fuse
1
1
1
5067
D.H.W. FLOW SWITCH
CH SELECTOR SWITCH
CH THERMISTOR
D.H.W. THERMISTOR
RED RED
ORANGE
ORANGE
PURPLE PURPLE
RED
RED
BROWN
BROWN
ORANGE
ORANGE
PURPLE
PURPLE
4 4
4 4
4 4
4 4
Diagram 3.3
29
221422A
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
Carry out the initial fault finding checks described in Section 3.1.
Check that gas, water and electricity are available at the boiler.
Before starting tests isolate the boiler, make sure that the remote controls are not
calling for duty and there is no domestic hot water demand.
Remove the outer case, control housing and it's cover. Check all connections on the control board and the boiler components, rectify or renew as necessary. Two dummy two way connectors are provided for ease of testing continuity. Remove fuses and test for continuity, if faulty, check cables and connections for shorting to E or N, rectify if necessary and replace fuse, with spare provided. Check central heating water pressure, repressurize if necessary. Make sure boiler is cold. Check all pipes and connections between the Air Pressure Switch (APS) fan and combustion sample point. Make sure sample point cap is fitted correctly. The boiler will go to lockout if the boiler overheat cut off goes open circuit, or the boiler fails to detect flame.
Isolate supply, disconnect cables, is there continuity, across boiler overheat cut off, brown and black on APS, DHW cut out, and yellow and grey on W.P.S. Is there 8k-10K across CH and DHW thermistor ?
NO
5063
Replace faulty device.
YES
Disconnect red cables to flow switch, turn on hot water tap. Is there continuity between red cables ?
YES
Turn off hot water tap is there open circuit, between red flow switch cables ?
YES
Connect all cables restore supply, does pump run for 30 seconds.
YES
NO
NO
NO
Replace faulty flow switch.
Replace faulty flow switch.
Is there 230V ac at pump ?
YES
NO
Replace faulty main PCB .
faulty pump rectify.
AB
NO
Turn on hot water tap, is red lockout neon lit.
YES
CONTINUED
221422A
30
Diagram 3.4
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
NO
Is burner
NO
pressure at full DHW.
YES
Reduce DHW water flow, does burner modulate.
YES
YES
A
B
NO
NO
Press reset switch wait 15 seconds between attempts. Are there sparks at electrode ?
YES
Does burner light ?
YES
Does boiler go to lockout after 10 seconds ?
YES
Isolate supply, Check dimensions of sense electrode and condition of lead. If ok replace CVI ignition unit ?
Does the DC voltage across the modureg reduce.
YES
NO
NO
NO
Check for shorting check lead connections to electrodes.
Check lead connections to electrodes
Check dimensions of spark electrode, if ok replace CVI gas valve unit.
Faulty main PCB, replace.
5064
Turn off hot tap, does burner extinguish.
YES
Turn on CH demand, does pump operate.
YES
As heating system becomes satisfied does burner pressure reduce ?
YES
D
NO
NO
NO
Normal operation.
Faulty modureg, replace.
Faulty main PCB, replace.
Is there 230V ac on pump ?
YES
Faulty pump, replace.
Faulty main PCB, replace.
NO
Faulty main PCB, replace.
C
CONTINUED
31
Diagram 3.4
221422A
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
NO
D
Faulty main PCB.
Faulty CVl ignition unit.
NO
NO
Is there between 15 - 30 V DC on the two greys on CN1 main PCB ?
YES
Is there between 15 - 30 V DC on the Modureg coil ?
YES
Faulty coil.
C
NO
5065
Faulty transformer, replace.
Faulty CVI ignition unit, replace.
NO
NO
Is there 24V ac on white and red CNI on main PCB ?
YES
Faulty main PCB, replace.
Is there 230ac on brown and blue, on fan ?
YES
Faulty fan, replace.
Is there 230ac between
NO
NO
Is there 230ac between yellow on CH Overheat Thermostat and Neutral.
YES
brown pin 10 and blue pin 11 an CVI ignition connector ?
YES
Is fan turning.
YES
NO
221422A
32
Faulty CVI ignition unit.
Faulty APS, replace.
Diagram 3.4
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
If mains potential room thermostat is connected, make sure that the switch live is connected to Pin 1 in the 5 pole connector. Check continuity of clock/timer harness, ensure an electrical supply is available, make sure that remote controls are calling for heat.
Isolate the boiler from electrical supply, remove outer case.
3 Fault Finding
5665
Switch on electrical supply, is there a display on clock/timer?
YES
Disconnect and insulate the yellow cables from heating common and heating on
Advance clock/timer until a demand is indicated Is there now continuity between heating common and heating on?
YES
Clock/timer in order if no central heating, refer to main fault finding.
DIGITAL CLOCK/TIMER FAULT FINDING
NO
NO
Faulty clock/timer. Replace.
Faulty clock/timer. Replace.
Diagram 3.5
CLOCK FAULT FINDING
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1 in
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remote
controls are calling for heat.
Does clock keep time
No
Faulty clock replace
Yes
No Isolate electrical supply set clock to on period Is there continuity across common and heating on
Clock in order if no central heating refer to
Yes
Set clock to off period. Is there continuity across common and heating on
No
main fault finding
ELECTRO/MECHANICAL CLOCK/TIMER FAULT FINDING
33
5666
Yes
Diagram 3.6
221422A
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
Before replacing any part please read points below:­Replacement of parts must only be carried out by a competent
person.
1. Refer to Section 1.1.
2. Always isolate the boiler from the electrical and as required, the gas supply, as Section 1.3.
3. On completion, make good any water loss and pressurise the system to initial design pressure, refer to “Commissioning” in the Installation Instructions.
Before starting refer to Section 1.1 Isolate the boiler from the electrical supply, refer to Section 1.4
and 1.5
4.1 Fan
Disconnect the two electrical connectors at the fan, see diagram
4.1. It is not necessary to disconnect the green and yellow earth cable.
Remove the two flexible tubes from the fan. When replacing the tubes from the air pressure switch ensure
the lower (red) tube from the fan connects to the lower connection of the switch.
Remove the fan, secured with two screws at the front, also located into the flue elbow and clip at the rear.
To renew the motor and impeller, remove the three screws securing it to the housing.
Transfer the earth cable to the replacement motor terminal marked, fitting the earth cable and shakeproof washer when securing the fan.
To fit the fan, locate it into the flue elbow and rear bracket, push fully upward into the flue elbow to ensure a good seal, then secure the fan with the two screws.
The polarity of the two electrical connectors is not important.
FLUE COLLECTOR
SECURING SCREW (2)
WINGNUT/ HOOK BOLT (2)
FLUE COLLECTOR
ELECTRICAL CONNECTORS
AIR PRESSURE SWITCH TUBES
REAR BRACKET
Diagram 4.1
5086
2844
6084
4.2 Main Burner
Remove the inner case as Section 1.5. Slacken the two wing nuts securing the flue collector, see
diagram 4.2. Remove the combustion chamber front panel, secured with four
screws, see diagram 4.2. Remove the burner support bracket wing nut and securing
screw, see diagram 4.2 Remove the spark electrode assembly from the burner secured
by two screws see diagram 4.3 and carefully lay it down in the combustion chamber.
NOTE: the sensing lead will be connected to the burner. Disconnect the lead when the burner is being removed.
Remove the main burner from the main injector at the rear. Raise the burner up and forwards. Take care not to damage the combustion chamber insulation.
Remove the sensing electrode and fit to new burner. Make sure the sensing lead is reconnected and the main burner
is fitted correctly on assembly, located on the main injector and horizontal, the tips of the rearmost blade under the two burner guides, see diagram 4.3.
Locate the combustion chamber front panel under the front edge of the flue hood on assembly, then secure all screws and wing nuts.
SCREW (4)
COMBUSTION CHAMBER FRONT PANEL
WINGNUT (2)
WINGNUT
Diagram 4.2
221422A
34
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.3 Main Injector
Remove the main burner, refer to Section 4.2. Unscrew the main injector. When fitting the main injector, fit the new sealing washer,
supplied, to ensure gas soundness.
4.4 Spark Electrode
Remove the inner case as Section 1.5. Slacken the two wing nuts securing the flue collector, see
diagram 4.2. Remove the combustion chamber front panel, secured with four
screws. Remove the spark and earth electrode assembly leads and
silicone tubes, securing nuts and washers Disconnect the leads and silicone tubes. NOTE: the ignition lead is black and the earth lead is white
4.5 Sensing Electrode
Remove the main burner refer to Section 4.2
4.6 Ignition Lead
Remove inner case as section 1.5, disconnect electrode assembly and lead as described in section 4.4.
Remove silicone tube and disconnect black lead at the ignition unit on gas valve. Slacken sealing angle and withdraw lead.
SPARK ELECTRODE
SECURING SCREW (2)
SILICONE TUBES
EARTH ELECTRODE
SEALING ANGLE
6086
Diagram 4.4
6629
4.7 Sensing Lead
Remove main burner as described in Section 4.2 disconnect the lead from sensing electrode, disconnect lead at the ignition unit on gas valve.
Slacken sealing angle and withdraw lead.
4.8 Boiler Overheat Cutoff
Remove user control switch bracket by slackening securing screws, disconnect electrical connections, see diagram 4.6.
Disconnect the boiler overheat cutoff electrical connectors, see diagram 4.5.
Remove the overheat cutoff, secured with two screws, see diagram 4.5.
Use the heat sink compound supplied, between the mounting plate and the cutoff, when fitting it.
SENSING ELECTRODE
6085
SECURING SCREW (2)
Diagram 4.5
SECURING SCREW (2)
5029
USER CONTROL SWITCH BRACKET
Diagram 4.3
ELECTRICAL CONNECTORS
SELECTOR SWITCH
35
CONTROL RESET BUTTON
Diagram 4.6
221422A
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.9 Water Pressure Switch
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the control housing, secured with two screws. Support control housing on a surface or by screwing it to front edge of the base, using the outer case securing screw, see diagram 4.10.
Disconnect the electrical connectors at the pressure microswitch, see diagram 4.7.
Remove pressure switch, see diagram 4.7. Replace the “O” ring seal with the new seal provided. Make sure that the switch terminals are facing diagonally
forwards to give access, as shown in diagram 4.7. Reconnect the electrical connections, refer to diagram 4.12.
4.10 Domestic Hot Water High Limit Control
Remove the pump, see Section 4.25. Disconnect the electrical connectors at the domestic hot water
high limit control, see diagram 4.8. Remove the high limit control from the flow pipe, secured with
two screws. Use the heat sink compound supplied, between the mounting
plate and the control. When refitting the electrical connections to the high limit control
the polarity is not important, see diagram 4.12.
4.11 Pressure Gauge
Remove the control housing assembly, see Section 4.9 Release the water pressure and drain the central heating circuit
of the boiler, refer to Section 1.3 and 1.6. Remove the pressure gauge bracket. Disconnect the pressure gauge connection from the safety
valve, discard the washer, see diagram 4.9. Remove the pressure gauge secured with the retaining spring
tabs. Locate the supplied washer under the pressure gauge connection
when refitted to the safety valve.
4.12 Control Boards
Remove the clock/timer mounting bracket securing screws, see diagram 4.29.
Remove control housing cover and fascia, see diagram 4.10. Remove the control housing assembly, Section 4.9. Disconnect all multi-pin connectors, see diagram 4.11. Remove the control boards from the support posts, noting their
correct positions. Great care must be taken when handling any control board.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI STATIC HOLDER UNTIL IMMEDIATE REQUIREMENT.
To connect the multi-pin connectors correctly, see diagram
4.15. When replacing the main control board check and if necessary
adjust the main burner gas pressure in both the hot water and central heating modes. Refer to “Commissioning” in the Installation Instructions.
D.H.W. HIGH LIMIT CONTROL
ELECTRICAL CONNECTORS
SAFETY VALVE
SEALING WASHER
PRESSURE GAUGE CONNECTION
SECURING SCREW (2)
PRESSURE GAUGE
SECURING SCREW (2)
4816 WATER PRESSURE SWITCH
Diagram 4.7
6630
D.H.W. HIGH LIMIT CONTROL
Diagram 4.8
2831
PRESSURE GAUGE BRACKET
Diagram 4.9
221422A
36
Page 37
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.13 Transformer
Before starting, refer to Section 1.1 Isolate the boiler from the electrical supply, refer to section 1.3 Remove the outer case, refer to section 1.4 Remove the control housing, refer to section 4.9. Support the
control housing, see diagram 4.10. Disconnect the electrical connectors from the transformer, see
diagram 4.11.
FASCIA
CONTROL HOUSING COVER SECURING SCREW
CONTROL HOUSING SECURING SCREW (2)
FASCIA SECURING SCREW (3)
SECURING SCREW (To support the control housing if necessary)
3904
Remove the transformer, noting the correct position. Reconnect the cables, refer to diagram 4.15.
TRANSFORMER
ELECTRICAL CONNECTORS (6)
4 WAY TERMINAL BLOCK
5015
CONTROL HOUSING COVER
WIRING AS DIAGRAM 4.12
Y
Y
1
2
B
Y
Y
*
Y
YBRB
BR
L
N
TIMER/CLOCK (IF FITTED)
Diagram 4.10
4 WAY TERMINAL BLOCK
NOTE: REMOVE YELLOW
*
LINK BEFORE FITTING CLOCK / TIMER
MULTI-PIN CONNECTOR (6)
CONTROL BOARD
Y
Y
COMMON
HEATING ON
Diagram 4.11
5229
BR
B
CLOCK / TIMER
L
N
37
Diagram 4.12
221422A
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.14 Gas Valve
If applicable remove the clock/timer mounting bracket, see diagram 4.29
Remove control box housing, see Section 4.9. Remove the user control switch bracket, see diagram 4.6. Disconnect the ignition unit and 2 electrical connectors. see
diagram 4.13. Remove the four extended hexagon screws at the right hand
side of the gas valve, Support the gas valve, disconnect the union nut at the gas
service cock and remove the valve complete with the inlet pipe. Separate the valve from the pipe, noting the fitted position. Discard the “O” rings and fit the new ones supplied. Fit modulator cables the polarity is not important. Check and adjust the main burner gas pressure in the hot water
and central heating modes, refer to “Commissioning” in the Installation Instructions.
4.15 Ignition Unit
Remove control box housing, see Section 4.11. Remove the user control switch bracket, see diagram 4.6. Remove the ignition unit securing screws. see diagram 4.14. Disconnect the electrical connector and the three electrode
leads. Remove ignition unit. Note: when re-fitting make sure the electrode leads are fitted to
the correct terminals. see diagram 4.14.
4.16 Central Heating Selector Switch and Control Rest Button
Slacken the user control switch bracket securing screws and remove the bracket from the keyhole slots, see diagram 4.6.
Pull the leads from the switch, see diagram 4.16. To remove the switch press in the tabs on each side of it. THE POLARITY OF THE ELECTRICAL CONNECTORS IS
IMPORTANT, SEE DIAGRAM 4.15.
4.17 Modulator
Isolate the boiler from the electrical supply and close the gas service cock, refer to Section 1.3.
Remove the outer case, refer to Section 1.4. Disconnect the two electrical connectors at the modulator, see
diagram 4.17. Remove the modulator, secured with two screws. Discard the gasket and fit the new one supplied, when fitting the
modulator. Light, check and adjust the boiler if necessary, refer to
“Commissioning” in the Installation Instructions.
4.18 Domestic Hot Water Flow Switch
Before commencing refer to Section 1.1 Isolate the boiler from the electrical supply, refer to Section 1.3. Remove the outer case, refer to Section 1.4.
SECURING SCREW (4+4)
ELECTRICAL CONNECTORS (2)
5233
SECURING SCREW
SECURING
IGNITION UNIT
Diagram 4.13
SCREW
SECURING SCREW (2)
EARTH ELECTRODE LEAD
SENSING ELECTRODE
SPARK
LEAD
ELECTRODE LEAD
Isolate the domestic hot water inlet, release the domestic water pressure and drain, refer to Section 1.3 and 1.6.
Remove the control housing, refer to Section 4.9. Remove the pressure gauge bracket, see diagram 4.9. Disconnect the flow switch cables at the in line connectors. Slacken or remove the clip securing the isolating valve, to ease
removal. To remove the flow switch disconnect the water inlet pipe
assembly union nuts, see diagram 4.18, noting the fitted position. Discard the sealing washers and use the new ones supplied. It is recommended that the water inlet filter is cleaned or
renewed at this stage. Make sure that the switch is positioned correctly, with the flow
arrow pointing upwards.
Diagram 4.14
5288
221422A
38
Page 39
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
FAN
G/Y
Y
AIR PRESSURE SWITCH
230V-50Hz PERMANENT
MAINS SUPPLY FUSED
AT 3A
Y P G/Y B BR
(L)
123N
DHW FLOW SWITCH
P
R
YYBBR
BR
BK
THERMISTOR (CH)
OR
OR
R
BLOCK 4
BR
B
P
P
P
BR
P
RESET NVLO
OR
INDICATOR
THERMISTOR (DHW)
SELECTOR
BR
SWITCH
BR
BR
B
REMOTE HTG CONTROL
FLOW SWITCH CH SELECTOR
SWITCH
CH THERMISTOR
DHW THERMISTOR
BR
N
MAINS
B
1 4 5 6 7 8
IGNITION UNIT
W
BR
BLOCK 3
BLOCK 2A
L
BOILER OVERHEAT CUT OFF
WATER
PRESSURE
SWITCH
B
230V
B
BR
NLNLNL
TXR 230V
OUT CIRCUIT
MODULATOR
GAS VALVE
L N E
HIGH LIMIT
CONTROL
N
L
8
7
230V AC TOP
6V BTM 24V
BLOCK 2B
PUMP
CVI OUTPUT 230V
DHW CUT
TXR SEC
TO PCB
COLOUR CODE
W- WHITE B- BLUE BK- BLACK BR -BROWN G/Y- GREEN/
YELLOW
KEY:
GY
GY- GREY OR- ORANGE V- VIOLET R-RED Y- YELLOW P- PURPLE
1
MODUREG
4
NO
5
NC
6
FAN/APS(C)
7
RESET
8
LOCKOUT NEON
5062
GY
GY
G/Y
B
Y
DHW
GY
BK
W
PUMP
N
L
BR
E
B
G/Y
R
B
B
BR
G/Y
G/Y
G/Y G/Y
CONTROL
BLOCK 1
HOUSING
4 WAY TERMINAL
Y1 Y2 N L
BLOCK
CONTROL BOARD
WIRING AS DIAGRAM 4.12A
39
CHASSIS EARTH G/Y
RESET NVLO INDICATOR,VIEW FROM REAR
OR B
BP
Diagram 4.15
221422A
Page 40
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.19 Thermistor - Heating
Release the water pressure and drain the heating circuit of the boiler, refer to Sections 1.3 and 1.6.
Disconnect the cables from the thermistor, see diagram 4.19. Remove the thermistor, complete with its “O” ring. The polarity of the electrical connections is not important.
4.20 Thermistor - Domestic Hot Water
On minimum clearance installations, remove the pump, see Section 4.25.
Release the water pressure and drain the domestic circuit of the boiler, refer to Section 1.3 and 1.6.
Disconnect the cables from the thermistor, see diagram 4.19. Remove the thermistor complete with its “O” ring. The polarity of the electrical connections is not important.
4.21 Safety Valve
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.11. Disconnect the union nuts to release the safety valve, see
diagram 4.20.
ELECTRICAL CONNECTORS
GAS VALVE
CONTROL RESET BUTTON
SELECTOR SWITCH
5027
Diagram 4.16
5043
4.22 Water Inlet Filter
Release the water pressure and drain the domestic circuit of the boiler, refer to Section 1.3, 1.6 and 4.19 or 4.18 diagram.
4.23 Domestic Hot Water Throttle
Release the water pressure and drain the domestic circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe assembly, refer to Section 4.18.
Remove the cap nut and carefully remove the throttle adjuster, by unscrewing and pushing it out, see diagram 4.21.
Clean if necessary, taking care not to damage the throttle body. Reset the domestic hot water flow rate refer to Section 11.7 in
Installation Instructions.
4.24 Mini Expansion Vessel
Release the water pressure and drain the domestic circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the domestic hot water inlet pipe complete with the mini-expansion vessel from the boiler, refer to Section 4.18.
When refitting use the new sealing washer supplied.
GASKET
MODULATOR
TORX SCREW (2)
SPACER
ELECTRICAL CONNECTOR (2)
221422A
40
HONEYWELL
Diagram 4.17
Page 41
Supplied By www.heating spares.co Tel. 0161 620 6677
FLOW SWITCH
FILTER UNION NUT
WATER FILTER
UNION NUT
VIEW ON ARROW 'A'
4 Replacement of Parts
5267
FLOW SWITCH LOCKNUT
'A'
FLOW SWITCH ELECTRICAL CABLES
SAFETY VALVE
2794 DISCHARGE PIPE
UNION NUT
UNION NUT
Diagram 4.20
WATER INLET PIPE ASSEMBLY
ISOLATING VALVE
UNION NUT
'O' RING
THROTTLE
Diagram 4.18
6631
CAP NUT
THROTTLE ADJUSTER
'O' RING
Diagram 4.21
MINI EXPANSION VESSEL
4600
5271
CENTRAL HEATING THERMISTOR
CONNECTORS
D.H.W. THERMISTOR
'O' RING
Diagram 4.19
41
SEALING WASHER
Diagram 4.22
221422A
Page 42
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.25 Pump
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Remove control housing, see Section 4.9. Disconnect the electrical connectors at the water pressure
microswitch. Remove the water pressure switch, refer to Section 4.9.
Remove the terminal cover from the pump and disconnect the cable, see diagram 4.23.
Disconnect the pump at the unions. Discard the sealing washers. Make sure that the flow direction arrow is pointing upward when
fitting, and use the new sealing washers. Refit water pressure switch, refer to Section 4.9. The flow adjuster on the new pump should be set to that of the
original, refer also to Section 4.6 in the Installation Instructions. The flow rate should be controlled by means of a valve in the
heating flow, refer to Section 11.10 in the Installation Instructions. Note: Should the pump fail to operate, refer to diagram 4.23. If
all is in order, but the pump still does not operate, remove the end screw, or cap, see diagram 4.23, then turn the pump spindle to release any temporary seizure.
DO NOT HIT THE SPINDLE.
PUMP SPINDLE
END SCREW
PUMP ADJUSTER
TERMINAL COVER SCREW
FLOW DIRECTION ARROW
UPPER PUMP UNION
LOWER PUMP UNION
5223
4.26 Automatic Air Vent
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the automatic air vent, see diagram 4.24. SLACKEN THE SMALL CAP ON THE AIR VENT. THIS MUST
NOT BE RE-TIGHTENED. When refitting use the new sealing washer provided.
4.27 Heat Exchanger
Release the water pressure and drain the central heating and domestic hot water circuits refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 4.1. Remove the flue collector, secured with two wing nuts and hook
bolts, see diagram 4.1. Remove the main burner, refer to Section 4.2. Remove the automatic air vent, refer to Section 4.29. If renewing the heat exchanger, transfer the air vent, using the
new sealing washers provided. Disconnect the union nuts of the heat exchanger to remove it,
see diagram 4.24. Locate the raised location tabs on the combustion chamber
sides into the slots on the heat exchanger, see diagram 4.24. Make sure that the main burner is located on the main injector
and is horizontal, the tips of the rearmost blade under the two burner guides, see diagram 4.3.
The combustion chamber front panel should be fitted loosely, then the flue collector also fitted loosely, ensuring that it is seated correctly on the heat exchanger and over the top edge of the front panel.
LOCATION SLOT
CAP
UNION (4)
Diagram 4.23
2284
AUTOMATIC AIR VENT
SEALING WASHER
Diagram 4.24
221422A
42
Page 43
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.28 Combustion Chamber Insulation
Remove the fan, refer to Section 4.1. Remove the flue collector, secured with two wing nuts and hook
bolts, see diagram 4.1. Remove the combustion chamber front panel, secured with four
screws, see diagram 4.2. Remove the front insulation piece secured with a clip, see
diagram 4.25. Slide out both side insulation pieces Pull the lower rear insulation forwards, then slide the upper rear
insulation down from behind the heat exchanger.
COMBUSTION CHAMBER FRONT PANEL
CLIP
FRONT INSULATION
5269
SIDE INSULATION PIECES
LOWER REAR INSULATION
43
SENSING ELECTRODE
UPPER REAR INSULATION
Diagram 4.25
221422A
Page 44
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.29 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be removed from the wall. As an alternative, a separate expansion vessel of the same specification may be connected as close as possible to the boiler, leaving the original in position, refer to the Installation Instructions.
Remove the outer case and the cover of the inner case, refer to Section 1.4 and 1.5.
Release the water pressure and drain, refer to Section 1.3 and
1.6. Remove the fan from the flue collector, refer to Section 4.1. Remove the flue elbow, secured to the boiler with four screws
and to the air duct with two screws, see diagram 4.26. Disconnect the boiler water connection union nuts at the front
of the isolating valves, see diagram 1.1. Disconnect the gas service cock union. Disconnect the safety valve discharge pipe from the boiler, see
diagram 4.20. Separate the two parts of the boiler multi-pole electrical
connector. Slacken the clips of the gas service cock and the water isolating
valves. Remove the boiler from the mounting frame, secured with two
screws at the top, see diagram 4.26. Pull the boiler from the isolating valves. Unhook the boiler at the top and lift off.
Carefully lay the boiler down on its side for access to the expansion vessel.
Disconnect the union nut connection, see diagram 4.27 and discard the sealing washer for the new one supplied.
Remove the expansion vessel, secured with three clamping screws.
Connect the union nut, when fitting the expansion vessel, before clamping it.
SECURING SCREW (4)
FLUE ELBOW
BOILER MOUNTING FRAME SCREW (2)
UNION NUT CONNECTION AND SEALING WASHER
AIR DUCT SECURING SCREW (2)
Diagram 4.26
2270S
2861
CLAMPING SCREW (3)
Diagram 4.27
AIR PRESSURE SWITCH TUBES
CLEAR
RED
ELECTRICAL CONNECTORS
AIR PRESSURE SWITCH
5276
Diagram 4.28
221422A
44
Page 45
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.30 Viewing Window
Remove the viewing window, secured with two screws. When fitting a new window use the gasket provided, see diagram 1.2.
4.31 Casing Seal
Remove the old seal, clean out the old adhesive. Glue the new seal into place, making sure that there are no
breaks in it.
CLOCK/ TIMER
4.32 Air Pressure Switch
Disconnect the two electrical connectors at the air pressure switch, see diagram 4.28.
Remove the flexible tubes from the switch. Remove the air pressure switch, secured with two screws. When replacing the tubes to the air pressure switch make sure
that the lower (red) tube from the fan connects to the lower connection of the switch.
The polarity of the electrical connections is important, refer to diagram 4.15.
4.33 Clock/Timer - if fitted
ELECTRO/MECHANICAL and DIGITAL clock/timer - Release the mounting bracket securing screws, see diagram 4.29
Disconnect electrical cables, release securing clip to remove the clock/timer spacer, see diagram 4.30.
6507
y
y
br b
COMMON
HEATING ON
SECURING SCREWS (2)
ELECTRICAL CONNECTIONS
MAINS LIVE (L)
KEY
br BROWN b BLUE y YELLOW
MAINS NEUTRAL (N)
SECURING CLIP (2)
MOUNTING BRACKET
SPACER PLATE
TIMER/CLOCK
6515
Diagram 4.29
45
Diagram 4.30
221422A
Page 46
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Spare Parts
5.1 Part Identification
The key number in diagram 5.1 and the first column of the list will help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part number and the description from the list together with the model name and serial number information from the data label.
The data label is positioned on the inner case cover, see diagram 6.1 Installation Instructions.
Key No. Part No Description GC No
1 452316 Fan assembly 278 416 2 205733 Main injector assembly (75e) 278 417 3 202631 Spark electrode 278 420 4 202632 Sensing electrode 278 421 5 800745 Boiler over heat cut off assy 278 413 6 432868 DHW high limit control assy 313 024 7 800134 Pressure gauge assembly 313 294 8 202253 Control board 375 724 9 202250 Central heating selector switch 382 813 10 202251 Control reset switch 375 724 11A 800504 Thermistor assembly-Domestic 278 135 11 800504 Thermistor assembly-Heating 278 135 12 800136 DHW switch assembly 313 277 13 202240 Fuse 2 T(630 mA) - not illustrated ­14 202226 Fuse 1 (2AT) - not illustrated 278 136 15 800345 Water pressure switch assembly 313 767 16 800744 Gas valve 278 422 17 204536 Air pressure switch assy 278 419 18 800153 Automatic air vent assembly 313 285 19 800149 Safety valve assembly 397 677 20 208214 Water inlet filter 281 359 21 800322 Transformer 313 761 22 202252 C.V.I. Ignition module 375 736
221422A
46
Page 47
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Spare Parts
6
5
11
5270
10
17
21
4
9
2
20
16
19
8
12
7
18
3
15
22
47
1
Diagram 5.1
221422A
Page 48
Supplied By www.heating spares.co Tel. 0161 620 6677
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
221422A
48
Loading...