Supplied By www.heating spares.co Tel. 0161 620 6677
Important Information
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler,
without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the
current issue of the Statutory Requirements, see Section 1.4.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed
to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous
fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0087.
Product/production certified by: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning
gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment
designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic
compatibility.
Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE, GLASSYARN, MINERAL WOOL
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is
broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or
going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
CONTENTS DESCRIPTION SECTION PAGE No.
INSTRUCTIONS
FOR USE
INSTALLATION
INSTRUCTIONS
Introduction3
Clock Settings4
Lighting the Boiler5
General Data17
Boiler Position29
Flue and Ventilation310
Heating System412
Domestic Hot Water System513
Appliance and Flue Preparation614
Flue Preparation716
Gas and Water Connections818
Electrical Connections919
Boiler Fixing1020
Commissioning1122
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Introduction
Please read these instructions and follow them carefully for the safe
and economical use of your Combination boiler.
This boiler must have been installed by a competent person in
accordance with the rules in force in the countries of destination.
Once the pilot has been lit and the controls set, the boiler is
automatic in operation.
The Swift-flow combination boiler is able to provide room heating as
part of a central heating system and domestic hot water direct from
the cold water supply, without the need for secondary storage.
The boiler can be fitted with one of two makes of clock, which look
like this:-
Clock / Timer
Digital
timer
Electro /
mechanical
clock / timer
IMPORTANT NOTICE:
This boiler is for use only on G20 gas.
Gas Leak or Fault
If a gas leak or fault exists or is suspected, turn the boiler off and
consult your local gas company or your local installation/servicing
company.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than in
the summer.
The nominal temperature setting for the Domestic Hot Water is
0
60
C (1400F) at a flow rate of 5litre per minute (1.1gal/min)
The specific water rate is 16.8litre per minute based on a 30
temperature rise.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off tap.
0
Boilers Installed in Compartments
If the boiler has been fitted into a compartment or cupboard, do not
obstruct the compartment air supply vents.
Do not use the compartment for storage.
Electrical Supply
WARNING. The boiler must be earthed.
The boiler must be connected to a 230V~50Hz permanent supply.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should preferably be by a double pole switched fused spur
box. The fused spur box should be readily accessible and preferably
6509
C
adjacent to the appliance.
It should be identified as to its use.
A fused three pin plug and shuttered socket outlet may be used
instead of the fused spur box.
PVC flexible cable must be used within the boiler casing to
connect to the boiler.
The colours of three core flexible cable are,
Brown - Live, Blue - Neutral,
Green and Yellow - Earth.
As the markings on your plug may not correspond with these
colours, continue as follows:
The cable coloured blue must be connected to the plug terminal
marked “N” or “Black”.
The cable coloured brown must be connected to the plug
terminal marked “L” or “Red”.
The cable coloured green and yellow must be connected to the
plug terminal marked “E” or “Green” or theearth symbol
.
Electrical Supply Failure
The boiler will not work without an electrical supply.
Normal operation of the boiler should resume when the electrical
supply is restored.
Note. The boiler safety cutoff may have operated, please refer
to the following section to reset.
Reset any external controls, to resume normal operation of the
central heating.
The digital timer, has a lithium battery back up and will not need
resetting.
Boiler Safety Cutoff Reset Button
The boiler is fitted with a safety cutoff device to prevent damage
through overheating.
Should the main burner go out during a demand the red neon
on the Reset Button will light.
In certain circumstances the red neon light may not come on,
due to no system demand. It is suggested that a hot water draw
off tap be opened to create a demand, the neon should then
come on.
Allow the boiler and system to cool down waiting at least a
minimum of four minutes before pressing the Reset button.
If the problem persists, turn the boiler off and consult the local
gas company or your installation/servicing company.
3
221474C
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
Setting Instructions for Electro/mechanical
Clock - if fitted
This clock has a twenty four hour dial, that is, 1pm is 13.
To set the time, turn the whole face clockwise until the pointer is
against the time of day.
To set any “Off” time, push the tappets outwards.
To set any “On” time, push the tappets inwards.
Time can be set either “On” or “Off” in fifteen minute segments.
Note. The clock supplied could be fitted with an override device,
see diagram 1, which switches the clock programme “On” or “Off”
permanently.
The switch will need to be repositioned to resume programmed
working.
CLOCK FACE
0
OVERRIDE
SWITCH
12
11
13
14
15
16
17
18
19
20
21
22
23
24
CONSTANT OFF
0
PROGRAMMED
CONSTANT ON
I
10
9
3
2
1
I
8
7
6
5
4
POINTER
TAPPETS
Diagram 1
Setting Instructions for the 7 Day Digital
Clock/Timer
This is a 24 hour clock/timer, that is 1pm is 13:00, and has 8 “ON”
and 8 “OFF” daily switching actions.
It is fitted with a lithium battery back up which protects the programme
in the event of an electrical failure. The battery should have a life
of several years.
I
MT
P
AUTO
WTh
RUN
FS
DAYHRMIN
R
P
Su
5673
Setting the Clock
1. With both AUTO and RUN switches set to the central position,
press R reset button, the display will flash.
2. Set RUN switch to .
3. Set day of week by pressing button DAY.
4. Set time of day by pressing buttons HR and MIN.
5. Set RUN switch to the central position, colon will flash, this
indicates the clock is set.
With the clock set, the factory preset programme shown below will
operate.
4956
MON/FRI
ON -06:30
OFF -08:30
ON -16:30
OFF -22:30
SAT/SUN
ON -07:00
OFF -09:00
ON -16:00
OFF -23:00
Setting Timed Programmes
With the clock set to the correct time, see SETTING THE CLOCK
paragraphs 1-4, and then continue as follows:
1.Set RUN switch to P , the display will
indicate the 1st (ON) preset programme and the
symbol
2.Set day of week to be programmed by pressing the
as groups:
3.Set time of day by pressing the buttons
HR and MIN.
4.Press button P to confirm programmes, the
display will indicate the 2nd (OFF) preset
programme andsubsequently, 3rd, 4th, 5th, 6th.
5.Repeat procedures 2, 3 and 4 until desired
programmes.
6.Set the RUN switch the central position, your
appliance will now operate at the
programmed times.
General Notes.
heating will not operate.
current central heating programme for the
next available.
.
DAY button.
Note. The days can be selected individually or
Mon-Fri., Mon-Sat., Mon-Sun., Sat/Sun.
An arrow will be displayed under the day or
days selected.
7th, 8th.
programmes are set.
Note. It is not a requirement to use the 8 on/off
With the AUTO switch in the I position the central
heating will operated constantly ON.
With the AUTO switch in the O position the central
Soft Override button indicated by the
symbol
ON time programmes are indicated by the
symbol
, this function will override the
.
Diagram 2
221474C
4
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
User Indicator Lights
Identify the lights be reference to diagram 3.
The Orange - Mains light - shows that the electrical supply to the
boiler is on.
The Green - Running light - shows that the boiler is working
normally, in either the central heating or hot water modes.
If the Red - Low Central Heating water pressure light flashes
continually it is warning of a loss of pressure in the central heating
system.
During this time the red light will continue to flash and the boiler will
not work.
If this happens you MUST call your installation or servicing company.
To Operate the Boiler
1. Check that all five isolating valves are open, the slots in line with
the length of the valve, see diagram 4.
2. Open the door, by pushing at the side opposite to the hinge.
3. CAUTION. A sealed pressurised system must be filled and
pressurised by a competent person.
Only operate the boiler when you are sure that the system has been
filled and pressurised. Check this by looking at the pressure gauge
“A”, diagram 3, it should read 0.7bar minimum.
4. Check reset button neon, refer to previous instructions on page
3.
5. Open a hot water tap, check that water flows, then close it.
6. If you are in any doubt about the boiler being filled with water
contact your installation/servicing company or the local gas company.
7. Check that the electrical supply to the boiler is ON at the external
isolator.
8. Set switch “C”, clock/timer (if fitted) and any remote controls as
required.
Close the door.
In certain circumstances, a surge in water pressure may cause the
appliance to operate momentarily, this will be indicated by the pump
starting and the fan speed increasing. This is quite normal.
Central Heating Selector Switch
For central heating set switch “C” to “On” as shown in diagram 3.
The main burner will light to provide central heating.
Note, when the central heating is also controlled by a room
thermostat, clock/timer or other remote control these controls must
be calling for heat for the boiler to operate.
The user central heating temperature control enables you to control
the temperature of the central heating water. The knob can be set
between Minimum, about 55
If a hot water tap is opened while the boiler is on for heating, the
burner flame will increase in size and priority will be given to hot
water. When the hot water tap is closed, the main burner flames will
decrease in size but will remain alight until the boiler controls or any
heating controls switch it off.
For domestic hot water only, set switch “C” to “Off”, as shown in
diagram 3.
The main burner will then light when any domestic hot water tap is
opened and go out when the tap is closed.
Which ever position switch “C” is in domestic hot water will be
available.
O
C and Maximum, about 80OC.
To Turn the Central Heating Off
To turn the heating off for short periods, set switch “C” to “Off” as
shown in diagram 3 and make sure all the domestic hot water draw
off taps are closed.
Set switch “C” to “On” as shown in diagram 3 to turn the central
heating on again..
To Turn the Boiler Off
To turn the boiler off, isolate the boiler from the electrical supply.
To turn on again following the operating instructions.
Domestic Hot Water Temperature
NOTE. The mains water temperature in the winter is lower than in
the summer.
The water temperature can be increased or reduced by adjusting
the flow rate at the hot water draw off.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the appliance
it is recommended that it is checked and serviced as necessary at
regular intervals. The frequency of servicing will depend upon the
particular installation conditions and usage, but in general once a
year should be enough.
If this appliance is installed in a rented property there is a duty of
care imposed on the owner of the property by the current issue of
the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
To obtain service, please call your installer or Heatcall (Glowworm’s own service organisation) using the telephone number
behind the controls access door, see diagram 3.
Please be advised that the ‘Benchmark’ logbook should be
completed by the installation engineer on completion of
commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and have
a registration number. Both should be recorded in your boiler
Logbook. You can check your installer is CORGI registered by
calling CORGI direct on :- 01256 372300.
Clearances
The boiler requires a clearance in front, below and at the sides of
the casing for safety, servicing and maintenance access, see
diagram 5.
Protection Against Freezing
If the boiler is to be out of use for any long periods during severe
weather, it is recommended that the whole system, including the
combination boiler, should be drained to avoid the risk of freezing.
If in doubt, contact you installation/servicing company for advice.
Draining and Filling
CAUTION. This boiler works in a pressurised system which must
only be drained, refilled and pressurised by a competent person.
Note: If the pressure gauge indicates a loss of system pressure,
that is, less than 0.7bar, YOU MUST CONTACT YOUR INSTALLER.
5
221474C
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
Instructions for Use
0183M
Pressure Relief Safety Valve
CAUTION. A pressure relief safety valve and discharge pipe is
fitted to the boiler. This valve must not be touched. Should there
be any discharge from the pipe, turn the boiler off, isolate from the
electrical supply and contact your installation/servicing company.
Cleaning
WARNING. This appliance contains metal parts (components) and
care should be taken when handling and cleaning with particular
regard to edges.
The boiler casing can be cleaned using a mild liquid detergent with
a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may
damage the paint work
Boiler Casing
CAUTION. Do not remove or adjust the casing in any way, as
incorrect fitting may result in incorrect operation or failure to operate
at all. If in doubt seek advice from the local gas company or your
installation/ servicing company.
Replacement Parts
If replacement parts are required apply to your local supplier or
British Gas.
Please quote the name of the appliance.
COLD WATER
SUPPLY IN
HEATING
FLOW
SAFETY
VALVE
DISCHARGE
SLOT(OPEN)
✽5
HEATING
RETURN
GAS
SERVICE
COCK
WATER VALVES
DRAIN
POINT
HOT
WATER
OUT
SLOT(OPEN)
Diagram 4
✽5
2793
SWITCH
'OFF'
5044
SWITCH
'ON'
PRESSURE GAUGE
‘A’
CENTRAL HEATING
SELECTOR SWITCH
'C'
CONTROL
RESET
BUTTON
6504
140
800
✽5
5
5
150
Orange Light 'MAINS'
Green Light 'RUNNING'
Red Light 'LOW C.H. WATER
PRESSURE'
221474C
125
ele
Diagram 3
6
✽ Increase to 25mm clearance from
combustible material
Diagram 5
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.1 Important Notice
This boiler is for use only on natural gas (G20).
1.2 Sheet Metal Parts
WARNING. When installing the boiler, care should be taken to
avoid any possibility of injury when handling sheet metal parts.
1.3 Notes for Information
The instructions consist of three parts, Installation, Servicing and
Instructions for Use, which includes the Guarantee Registration
Card. The instructions are an integral part of the appliance and
must be handed to the user on completion of the installation.
Materials and equipment should be fit for their purpose and of
suitable quality and workmanship.
1.4 Statutory Requirements
The installation of the boiler must be carried out by a competent
person in accordance with the relevant requirements of the current
issue of:-
Manufacturer’s instructions, supplied.
The Gas Safety (Installation and Use) Regulations, The Building
Regulations, The Local Water Company Byelaws, The Building
Standards (Scotland) Regulations (applicable in Scotland), The
Health and Safety at Work Act, Control of Substances Hazardous
to Health (COSHH), The Electricity at Work Regulations and any
local regulations which may apply.
Detailed recommendations are contained in the current issue of the
following British Standards and Codes of Practice:-
BS5440 Part 1 and 2, BS6798, BS5449, BS6700, BS5546, BS6891,
BS4814, BS7074 Part 1 and 2, BS7478, BS7593, BS7671.
Manufacturer’s instructions must not be taken as overriding statutory
requirements.
1.5 Data Label
The data label is on the inner case cover.
1.6 Data
See Tables 1 and 2.
All dimensions are given in millimetres
(except as noted).
1.7 Gas Supply
The gas installation must be in accordance with the rules in force in
the countries of destination.
The supply from the governed gas meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at the
boiler.
1.8 Electrical Supply
WARNING: The boiler must be earthed.
The installation must be in accordance with the rules in force in the
countries of destination.
All system components shall be of an approved type.
Connection of the whole electrical system of the boiler and any
heating system controls to the electrical supply, must be through
one common isolator.
Isolation should preferably be by a double pole switched 3A fused
spur box, with a minimum separation of 3mm in both poles. The
fused spur box should be readily accessible and preferably adjacent
to the appliance. It should be identified as to its use.
A fused 3A three pin plug and shuttered socket outlet may be used
instead of the fused spur box, provided that they are not used in a
room containing a fixed bath or shower.
48
114
ALL DIMENSIONS IN MILLIMETRES
KEY:
22 mm COMPRESSION
CENTRAL HEATING
15 mm COMPRESSION
DOMESTIC WATER
Rc 1/2 (1/2in. BSPT)
GAS CONNECTION
168
331
130
783
66
450
107
107
66
6514
70
25
2.5
7
Diagram 1.1
221474C
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
● Ball valves are fitted in water and gas connections, plus a drain point on all water connections.
✽ Boiler starts at an inlet pressure of 0.6bar but requires 0.8bar for maximum output.
■ For larger systems use an additional expansion vessel, see Section 4.
221474C
8
Internal Fuse rating:Fuse 1Type 2AT
Fuse 2 Type 3.15AT
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Boiler Position
2.1 Boiler Position
The boiler must be installed in accordance with the rules in force of
the countries of destination.
The boiler is not suitable for outside installation.
Any electrical switch or boiler control using mains electricity must be
positioned so that it cannot be touched by a person using a bath or
shower.
The boiler must be mounted on a flat wall which is sufficiently robust
to take its weight, refer to Table 2.
If the boiler is to be fitted into a cupboard, compartment or unusual
location, special procedures are necessary.
Make sure that the cupboard or compartment air vents are positioned
to be clear of obstructions at all times, refer to Section 3.7.
0183M
✽5
✽5
800
2.2 Clearances
The boiler should be positioned so that at least the minimum
operational and servicing clearances are provided, see diagram
2.1.
Installation Clearances
For rear flue installation the dimension between the boiler mounting
wall and a permanent facing wall must be a minimum of “X”, see
diagram 3.1 and 3.3, plus 272mm.
For side flue installation the dimension between any adjacent
permanent walls must be a minimum of “Y”, see diagram 3.2 and
3.3, plus 332mm.
For flue installations where internal clearances are not practicable,
then external installation will be necessary.
Note: If the appliance is to be installed in a building where access
to the outside is not possible, due to height or other restriction a
internal flue installation kit is available. Part No. 452481.
This includes a larger wall sleeve (150mm dia.) which allows the
flue terminal to be inserted through the wall to the outside of the
building.
For a wall thickness up to 300mm, provided there is sufficient space
available, the flue can be fully installed from the inside.
For a wall thickness over 300mm the external flue hole will need to
be made good from the outside.
If there is insufficient clearance the flue can be installed from
outside.
140
5
5
150
✽ Increase to 25mm clearance from
combustible material
Refer to text, Section 2.2 Clearances,
"Installation Clearances"
✽5
Diagram 2.1
9
221474C
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.1 Flue
The flue must be installed in accordance with the rules in force in
the countries of destination. For UK, see current issue of BS5440
Part 1.
3.2 Flue Position and Length
The air and flue ducting connect to the top of the boiler using a flue
elbow and can be positioned in one of three directions:
rearward, left or right.
The standard flue will provide the range shown in diagram 3.1 for
a rear flue or diagram 3.2 for a side flue.
If a longer flue duct is required, do not extend the ductings. A 1, 2
or 3metre flue system and elbow/terminal kit must be used and can
be supplied. This will provide the range shown in diagram 3.3 for
a rear flue, diagram 3.4 for a side flue.
A Flue Bend Kit or Vertical Flue Kit can be supplied, with instructions.
3.3 Terminal Position
The minimum acceptable siting dimensions for the terminal from
obstructions, other terminals and ventilation openings are shown in
diagram 3.5.
The terminal must be exposed to the external air, the position
allowing free passage of air across it at all times.
WALL THICKNESS ‘X’: 75 to 400mm
“X”
REAR FLUE - STANDARD
DISTANCE ‘Y’: 80 to 338mm
638563846383
Diagram 3.1
6382
“Y”
Car ports or similar extensions of a roof only, or a roof and one wall,
require special consideration with respect to any openings, doors,
vents or windows under the roof. Care is required to protect the roof
if made of plastic sheeting. If the car port comprises of a roof and
two or more walls, seek advice from the local gas undertaking
before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering, an
aluminium shield 1500mm long should be fitted immediately beneath
the guttering or eaves. If the terminal is fitted within 450mm below
painted eaves or a painted gutter, an aluminium shield 750mm long
should be fitted immediately beneath the guttering or eaves.
SIDE FLUE - STANDARD
Left or Right
1m FLUE DISTANCE ‘X’: 75 to 880mm
2m FLUE DISTANCE ‘X’: 75 to 1880mm
3m FLUE DISTANCE ‘X’: 75 to 2880mm
“X”
REAR FLUE 1,2 and 3 metre
1m FLUE DISTANCE ‘Y’: 80 to 818mm
2m FLUE DISTANCE ‘Y’: 80 to 1818mm
3m FLUE DISTANCE ‘Y’: 80 to 2818mm
Diagram 3.2
Diagram 3.3
SIDE FLUE 1,2 and 3 metre
Left or Right
221474C
10
“Y”
Diagram 3.4
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Flue and Ventilation
3.4 Terminal Guard
A terminal guard is required if persons could come into contact with
the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a
minimum of 50mm clearance from any part of the terminal and be
central over the terminal.
The guard should be similar to that shown in diagram 3.5, and can
be bought from:
Tower Flue Components Ltd
Morley Road
Tonbridge
Kent
TN9 1RA
their type K3.
3.5 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should be
fitted in accordance with the Institute of Gas Engineers document
IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking
or Hepworth Heating Ltd.
3.6 Room Ventilation
The boiler is room sealed, so when it is installed in a room or space,
a permanent air vent is not required.
3.7 Cupboard or Compartment Ventilation
If the boiler is to be fitted in a cupboard or compartment, permanent
high and low level air vents must be provided The vents must have
at least the effective areas as given in Table 3.
D
K
C
K
L
L
K
G
F
MINIMUM
SPACING
in mm
A
B,C
A
F
G
Under Car Port etc.
G
A
E
G
F
G
H,I
MINIMUM SITING DIMENSIONS
FOR FANNED FLUE
TERMINALS POSITION
B,C
K
F
J
ADIRECTLY BELOW AN OPENABLE
WINDOW, AIR VENT, OR ANY OTHER
VENTILATION OPENING300
BBELOW GUTTER, DRAIN/SOIL PIPE75
CBELOW EAVES200
DBELOW A BALCONY OR CAR PORT200
EFROM VERTICAL DRAIN PIPES AND
SOIL PIPES75
FFROM INTERNAL OR EXTERNAL
CORNERS300
GABOVE ADJACENT GROUND OR
BALCONY LEVEL300
HFROM A SURFACE FACING THE
TERMINAL600
IFACING TERMINALS1200
JFROM OPENING (DOOR/WINDOW) IN
CAR PORT INTO DWELLING1200
KVERTICAL FROM A TERMINAL1500
LHORIZONTALLY FROM A TERMINAL300
0103M
TABLE 3
PositionAir fromAir Direct
ofRoom orfrom
Air VentInternal spaceOutside
High Vent392cm2 (60.8in2)196cm2 (30.4in2)
Low Vent392cm
2
(60.8in2)196cm2 (30.4in2)
11
4783
Diagram 3.5
221474C
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
kW
22
20
18
16
14
12
10
FEET
20
15
10
Btu/h x1000
80
70
60
50
40
30
M
6
5
4
3
4 Heating System
PUMP CURVE - SETTING 3
˚C˚F
20
35
17
30
15
11
10
5
0
✽ ACCEPTABLE
DIFFERENTIAL
RANGES
25
20
15
10
5
0
✽
0194M
SYSTEM DIFFERENTIAL TEMPERATURE
2
5
1
AVAILABLE PUMP HEADSYSTEM HEATING LOAD
0
111520253035 Litres/Min
2.53.03.54.04.55.05.56.06.57.0Gallons/Min
PUMP CURVE - SETTING 2
FLOW RATE
4.1 General Notes
The boiler is for use in sealed water systems only.
4.2 Safety Valve
The safety valve is an integral part of the boiler and it cannot be
adjusted.
4.3 Pressure Gauge
A pressure gauge is incorporated into the boiler to indicate the
system pressure.
4.4 Pump
The pump is integral with the boiler.
The remaining circulating pressure head available from the pump is
shown in diagram 4.1.
4.5 Expansion Vessel
The boiler has an integral expansion vessel with a capacity of
8Litres (1.76gallons), with a charge pressure of 0.75bar.
The maximum heating system water content using the fitted
expansion vessel ranges from 119Litres with a cold fill pressure of
0.7bar, to 98Litres with a cold fill pressure of 1.05bar. If, due to a
high static head, the cold fill pressure is higher, then the expansion
vessel pre-fill pressure must be increased, and the maximum
system volume decreased.
4.6 Flow Rate
A valve must be incorporated in the main flow or return of the
system, valve “A” shown in the flow in diagram 4.2. This valve must
be lockable and positioned so that inadvertent closure or
unauthorised interference is not possible. The design differential
can be between 11oC (20oF) and 17oC (30oF), dependent on the
system resistance and the available pump head. The pump
adjuster should normally be left at maximum (3) but in some cases
Diagram 4.1
it is permissible to adjust the pump to a lower setting (2). See
diagram 4.1.
To use diagram 4.1 start with the required heating system load.
In the example shown the maximum boiler output has been chosen,
23.5kW (80,000Btu/h).
Draw a horizontal line from the required system differential
temperature axis to intersect the curve. In the example 11
o
(19.8oF) has been chosen, shown - - - -. At the point of intersection
draw a vertical line to cross the pump curve. From this point draw
a further horizontal line to determine the available pump head. In
the example 2.4m (7ft9in) is available. A greater pump head can be
achieved by choosing a higher system differential temperature, up
to a maximum of 3.8m (12ft 6in) at a system differential of 17oC
(30.6oF). The system must be designed such that the available
pump head is not exceeded.
If the heating system load is less than 14.7kW (50,000Btu/h) then
it is permissible to adjust the pump setting to (2), shown
This results in an available pump head of 2.1m (7ft). This is the
maximum that can be achieved with the pump at this setting.
4.7 Bypass
It is ESSENTIAL that a bypass of 22mm od minimum is fitted to all
installations. The bypass must have a lockable valve, “B” in
diagram 4.2, incorporated in a position so that inadvertent closure
is not possible.
The bypass MUST be fitted before any system control. A radiator
bypass is NOT recommended.
4.8 Make Up
Provision can be made for replacing water lost from the system
using a make up bottle mounted in a position higher than the top
point of the system, connected through a non-return valve to the
return side of the heating circuit, see diagram 4.2.
Alternatively, provision for make up can be made by prepressurisation of the circuit.
C
221474C
12
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Heating System
4.9 Filling Sealed Systems
Provision for filling the system at a low level must be made.
Three methods of filling are shown in diagram 4.3. There must be
no permanent connection to the mains water supply, even through
a non-return valve.NOTE: It is important that fittings used for
connection to potable water comply with the water undertakers
requirements.
4.10 Corrosion Inhibitor
If an inhibitor is to be used in the system, contact a manufacturer so
that they can recommend their most suitable product.
When fitting the boiler into an existing system, special care should
be taken to drain the entire system, including radiators, then
thoroughly cleaning out before fitting the boiler whether or not
adding an inhibitor.
3-LITRE
MAKE-UP
BOTTLE
(if required)
NON-RETURN
VALVE
DOMESTIC
WATER
BOILER
2818
4.11 Draining Tap
A draining tap must be provided at the lowest points of the system,
which will allow the entire system to be drained. An additional
draining tap MUST be fitted close to the boiler.
The flow and return isolation valves are provided with drain points
for boiler heat exchanger drainage.
METHOD 1
TEMPORARY
HOSE
SUPPLY
PIPE
METHOD 2
TEMPORARY
HOSE
COMBINED
CHECK VALVE
AND VACUUM
BREAKER
HOSE
UNIONS
SUPPLY STOP
VALVE
SERVICING
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
0051M
HEATING
SYSTEM
HEATING
SYSTEM
ADDITIONAL
EXPANSION
VESSEL
(if required)
HEATING
CIRCUIT
AUTO AIR
VENT
RETURN
'A'
FLOW CONTROL
VALVE
MIN. 22mm
DIA. BY-PASS
'B'
BY-PASS
VALVE
5 Domestic Hot Water System
HOT
COLD SUPPLY
FILLING
POINT
DRAIN
POINT
Diagram 4.2
SUPPLY
PIPE
METHOD 3
CISTERN
SUPPLY
STOP VALVE
SUPPLY
PIPE
HOSE
UNIONS
SUPPLY STOP
VALVE
OVERFLOW
SERVICING
VALVE
HOSE
UNIONS
SERVICING
VALVE
PRESSURE
REDUCING
VALVE
DOUBLE CHECK
VALVE ASSEMBLY
HEATING
SYSTEM
Diagram 4.3
5.1 General
The domestic hot water service must be in accordance with the
rules in force in the countries of destination.
5.2 Water Pressure
For the minimum and maximum working pressures of the domestic
hot water circuit of the boiler, refer to Section 1.6. If the cold water
supply pressure exceeds the maximum, a pressure reducing valve
must be fitted in the supply to the boiler to reduce the pressure to
within the limits given.
5.3 “Hard” Water Areas
In areas where the water is “hard”, that is, more than 200mg/litre,
it is recommended that a proprietary scale reducer is fitted in the
cold supply to the boiler. Check the total water “hardness” using the
kit supplied, in the door, following the instructions given. Consult
the local water company for additional advice.
A double check valve assembly must be fitted upstream of the scale
reducer. For the relative position of the scale reducer and pressure
reducing valve, if required, refer to the manufacturer’s instructions.
13
221474C
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Appliance and Flue Preparation
6.1 Unpacking
Remove the top carton and cut out the flue template from the inner
flap.
Open the control door, see diagram 6.1.
Remove the two screws securing the outer case and then lift it at the
top and pull it forwards and off, seediagram 6.1.
Remove the cover of the inner case, secured with four screws, see
diagram 6.2
Slacken flue collector thumb screws.
Remove the fan securing screws.
Disconnect the electrical plug connector and air pressure tube from
the fan, see diagram 6.3.
Pull the fan forwards, at the bottom and rotate to disengage the fan
outlet from rear bracket.
Take care not to damage the seal.
Tilt the fan and withdraw.
Disconnect the gas cock union and the front unions of the isolation
valves, see diagram 6.4.
Slightly loosen the clips of the gas service cock and the isolating
valves.
Remove the two boiler securing screws then remove the boiler from
the mounting frame, by pulling the studs from the clips and
unhooking it at the top.
6.2 Marking
The boiler mounting frame is the same width as the boiler case. The
flue connection is on the top.
IMPORTANT: Should internal flue installation kit (Part No. 452481)
which will enable the flue terminal to be inserted through the wall to
the outside of the building be used, provision should be made to
prevent any injury or damage due to falling debris.
Place the boiler mounting frame on the wall in the required position,
see diagram 2.1, to maintain minimum clearances. Make sure that
the isolation valves are at the bottom facing forward and that the
frame top is horizontal, then mark the four wall fixing points through
the holes in the two horizontal straps.
Position the flue template on the wall, the arrow points on the
centres of the two upper fixing points previously marked, see
diagram 6.5 which also gives dimensions.
For a rear flue, mark the position as required.
For a side flue, mark the horizontal flue centre line at the sides of the
template. Extend the flue centre line horizontally left or right to the
internal corner where the flue is required to exit to outside.
Mark the position of the circular hole, on the flue exit wall, using the
dimensions given in diagram 6.6.
From the flue position marks, check that the flue terminal will be in
a suitable position, see diagram 3.5.
6.3 Flue Hole Cutting
Having marked out the flue centre, cut a hole for the flue, using,
preferably, a 130mm minimum core drill.
Note: If using the internal flue installation kit, the hole should be
150mm diameter.
Cut the hole horizontally in the wall, making sure that it does not
slope down towards the boiler.
RESET SWITCH AND
NEON INDICATOR
CENTRAL
HEATING
SELECTOR
SWITCH
OUTER CASE
SECURING SCREW (2)
DOOR
(IF CLOCK TIMER
FITTED(4))
INNER CASE
COVER
FAN SECURING
SCREWS
VIEWING
WINDOW
DATA
LABEL
CLOCK TIMER
SECURING
SCREW (4)
ELECTRICAL
PLUG
125
electronic
Diagram 6.1
Diagram 6.2
6504
4561
6920
221474C
14
AIR
PRESSURE
TUBE
Diagram 6.3
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
6 Appliance and Flue Preparation
6.4 Wall Sleeve
Note: If required, an optional Wall Liner Kit, Part No. 900861, is
available, complete with fixing instructions.
SECURING
SCREW (2)
6921
6.5 Boiler Mounting Frame Fixing
Position the flue template over the flue hole and check the position
of the wall fixing points. Mark the position of the fixing holes again,
if required.
Drill the four fixing holes and insert wall plugs to suit No.10x50mm
screws.
Secure the boiler mounting frame to the wall using No.10x50mm
screws.
CORNER (Right Flue)
CORNER (Left Flue)
0177M
UNIONS (5)
LOCATION CLIPS
MIN. CLEARANCE
111.5 70
FLUE
TEMPLATE
591.5
(Cut from
480
carton top
inner flap)
CLIP (5)
130 Dia.
FLUE
CENTRELINE
BOILER
MOUNTING FRAME
FIXING POINTS
Diagram 6.4
TOP OF
BOILER
168168
FLUE
CENTRE
LINE
130 Dia.
Diagram 6.6
0176M
300
Diagram 6.5
15
221474C
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
7.1 Flue Length
For a rear flue, measure the distance from the outside wall face to
the boiler mounting wall. Check that the flue length will be suitable,
see diagram 3.1 for a standard flue system or diagram 3.3 for a 2
or 3metre flue system.
For a side flue, measure the distance from the outside wall face to
the side of the boiler mounting frame. Check that the flue length will
be suitable, see diagram 3.2 for a standard flue system or diagram
3.4 for a 2 or 3metre flue system.
7.2 Rear Flue
Note. Do not cut the flue duct at the pre-drilled end.
Mark the air duct/terminal assembly and the flue duct at the lengths
shown in diagram 7.1 then cut to length, cutting square and
removing any burrs.
7.3 Side Flue
Note. Do not cut the flue duct at the pre-drilled end.
Mark the air duct/ terminal assembly and the flue duct at the lengths
shown in diagram 7.2 then cut to length, cutting square and
removing any burrs.
"X"
OUTSIDE
WALL
FACE
"X" plus 120
(FLUE DUCT,
AIR DUCT/TERMINAL ASSEMBLY)
BOILER
6470
MOUNTING
WALL
Diagram 7.1
7.4 Flue Assembly
Locate the flue duct, drilled end, onto the flue elbow and secure with
screw supplied in loose items pack, see diagram 7.3.
Slide the spacer onto the flue duct.
Locate the flue duct/elbow into the air duct/terminal spigot and the
air duct/terminal into the flue elbow making sure of the correct
alignment of top. Drill the air duct and secure/seal (external fixing,
do not seal) as shown in diagram 7.3.
7.5 Wall Liner
If a wall liner is used, fit self adhesive seal as follows:
For wall thickness up to 300mm fit the self adhesive seal to the air
duct, see diagram 7.5, make sure the joint is on top.
For wall thickness over 300mm see diagram 7.4.
6386
AIR DUCT/
TERMINAL
OUTSIDE
WALL FACE
"Y"
"Y" plus 182
(FLUE DUCT,
AIR DUCT/
TERMINAL
ASSEMBLY)
SIDE OF
BOILER
MOUNTING
FRAME
SEALING TAPE
6471
Diagram 7.2
FLUE DUCT/
ELBOW
FLUE ELBOW
FLUE
SPACER
FLUE DUCT
SECURING
SCREW (1)
221474C
16
3mm Drill
Diagram 7.3
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
7 Flue Preparation
7.6 Internal Flue Assembly
Note: This requires the use of the internal flue installation kit.
Place the flue assembly into the flue hole to make sure that the flue
terminal is correctly positioned and is the correct distance from the
outside wall face, see diagram 7.6 and the appropriate diagram 7.1
or 7.2.
7.7 External Flue Assembly
Remove the flue elbow from the air/terminal duct and the flue duct.
From outside place the flue/air duct assembly into and through the
wall.
FOAM
SEAL
AIR DUCT/
TERMINAL
AIR DUCT/
TERMINAL
20mm
63876388
Diagram 7.4
130 DIA
CORE
DRILLED
HOLE
48
Q minus 55mm
Q
WALL
LINER
FOAM
SEAL
Diagram 7.5
6389
17
FLUE
TERMINAL
OUTSIDE
WALL FACE
FOAM
SEAL
AIR
DUCT
Diagram 7.6
221474C
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
8 Gas and Water Connections
8.1 Gas Connection
The gas supply can be connected from below or through the wall
at the rear of the boiler, see diagram 8.1 for position.
Refer also to Section 1.7.
Make the gas supply connection to the gas service cock. Slacken
or remove the clip, as desired, whilst making the connection. Do not
subject the gas service cock to heat.
8.2 Water Connections
Provision is made for the water connections to be made from below
or through an internal wall at the rear of the boiler, see diagram 8.1
for position.
Provision is made for the domestic hot water outlet and heating flow
and return pipes to be connected from above, if desired, passing
down either side of the boiler, see diagram 8.2 for clearances. Take
care that any pipework connected from above, within the boiler
mounting frame will clear the expansion vessels.
Flush out the domestic hot water and the heating systems before
connecting to the boiler.
Make the connections to the domestic hot water outlet by straight
connector and heating systems by way of the isolating valves, see
diagram 8.1.
Slacken or remove the clips, as desired, while making the
connections. Do not subject any of the isolating valves to heat.
Make sure that the drain points on the isolating valves are positioned
towards the front of the boiler, also that the drain and operating
screw heads are accessible.
8.3 Safety Valve Discharge
WARNING. It must not discharge above an entrance or window or
any type of public access area.
A short discharge pipe is supplied loose with the boiler, which when
fitted to the safety valve, will end below the boiler at the mark
between the cold water inlet and the heating flow, for position and
dimension see diagram 8.1.
This must be extended, using not less than 15mm od pipe, to
discharge, in a visible position, outside the building, facing downward,
preferably over a drain.The pipe must have a continuous
fall and be routed to a position so that any discharge of water,
possibly boiling, or steam cannot create any danger to persons,
damage to property or external electrical components and wiring.
Note. To make future servicing easier it is advisable to use a
compression type fitting to extend thedischarge pipe.
‘NOTCH’ MARKING POSITION OF
SAFETY VALVE DISCHARGE
63
DOMESTIC
COLD WATER
SUPPLY IN
SLOT (CLOSED)
HEATING
FLOW
HEATING
RETURN
GAS
SERVICE
COCK
DRAIN
POINT
20mm
EXPANSION
VESSEL POSITION
BOILER
MOUNTING
FRAME
DOMESTIC
HOT WATER
OUT
SLOT (CLOSED)
Diagram 8.1
46mm
2297
221474C
18
140
80
90
DOMESTIC
WATER
NOTE:
Keep any pipework
clear of shaded area
320
CENTRAL
HEATING
Diagram 8.2
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
EXTERNAL CLOCK
RED LINK.
REMOVE WHEN
CONNECTING ANY
HEATING SYSTEM
CONTROLS
CLOCK
TIME
CONTROL
JUNCTION
BOX
3 AMP
FUSE
DOUBLE
POLE
ISOLATOR
230V~50Hz
PERMANENT
MAINS SUPPLY
LNE
(3) (L) (N) (E)(2)
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
SWITCH
CONTACTS
ROOM
THERMOSTAT
FROST
THERMOSTAT
ELECTRICITY SUPPLY CONNECTIONS
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
MAINS POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz ROOM STAT. NO FROST STAT.
INTEGRAL CLOCK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(1)
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
MAINS
POTENTIAL
FROST STAT.
230V~50Hz
FROST STAT. NO ROOM STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
3 AMP
FUSE
DOUBLE
LN
POLE
ISOLATOR
230V~50Hz
FROST STAT.
INTEGRAL CLOCK
(3) (L)(N)(2)(1)
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
MAINS
POTENTIAL
FROST STAT.
POTENTIAL
JUNCTION
BOX
E
230V~50Hz
PERMANENT MAINS
SUPPLY
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT. USED AS LINK
TO BOILER
5 POLE CONNECTOR ON
MOUNTING FRAME
(E)
230V~50Hz
POTENTIAL
FROST STAT.
MAINS
RED
LINK
0060M
(3) (L)(N)(2)(1)
3 AMP
FUSE
230V~50Hz
PERMANENT MAINS
DOUBLE
LN
POLE
ISOLATOR
SUPPLY
POTENTIAL
FREE ROOM STAT. NO FROST STAT.
(E)
E
POTENTIAL FREE
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
230V~50Hz
ROOM STAT.
19
3 AMP
FUSE
DOUBLE
POLE
LN
ISOLATOR
E
230V~50Hz
PERMANENT MAINS
SUPPLY
230V~50Hz
FROST STAT.
JUNCTION
BOX
230V~50Hz
POTENTIAL
ROOM STAT.
RED LINK.
REMOVE WHEN
CONNECTING
SYSTEM CONTROLS
Diagram 9.1
221474C
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
9 Electrical Connections
9.1 Supply Cable Connection
The boiler requires a permanent mains supply through an isolator
which must also isolate any heating system controls, see diagram
9.1.
Any heating system controls must not interrupt the permanent
mains supply to the boiler.
Remove the electrical connector from the loose
items pack.
Remove the two screws and cover from the connector, see diagram
9.2.
Using PVC cable of suitable length and rating as stated in Section
1.8, connect the mains supply cable to the appropriate terminals of
the connector, see diagram 9.1.
Standard colours are, Brown - Live; Blue - Neutral; Green and
Yellow - Earth.
The mains cable outer insulation must not be cut back external to
the plug, see diagram 9.2.
Make the earth cable of a greater length so that if the cable is
strained the earth would be the last to become disconnected.
CAUTION. It is essential that the polarity is correct.
9.2 Heating System Controls
CAUTION: To prevent an induced current from switching the
central heating on, when not required, it is important that the heating
system control cables are separated from the other mains supply
cables.
The heating system should have installed: a programmer and room
thermostat controlling the boiler.
Thermostatic radiator valves may be installed in addition to the
room thermostat.
Note: For further information, see The Building Regulations 1991 Conservation of fuel and power, 1995 edition - Appendix G, table 4b.
If electrical controls are not to be used to regulate the heating
system, do not disturb the red link cable.
When any form of electrical control is being used to regulate the
heating system, remove the red link cable and connect heating
system controls in series.
The mains cable outer insulation must not be cut back external to
the plug.
RED LINK
Remove when
connecting any
heating system
controls.
1
2
E
N
L
3
MAINS
CABLE
CABLE
CLAMP
COVER
SCREW (2)
Diagram 9.2
9.3 Clock/Timer
An internal clock/timer kit can be supplied, refer to the literature
supplied with it.
9.4 Frost Thermostat
If the installation requires protection by a “frost thermostat”, connect
a single pole type, to the appropriate terminals of the connector.
9.5 Cable and Connector Securing
After completing all the connections to the boiler, secure the
cable(s) with the cover, using the two screws previously removed,
see diagram 9.2.
2643
10 Boiler Fixing
10.1 Mounting the Boiler
After installing the flue, boiler mounting frame, gas, domestic and
heating systems, making the electrical connections and preparing
the flue components, continue as below:
Lift the boiler into position, hooking it onto the boiler mounting frame
at the top, fully push the boiler back to the mounting frame, locating
the studs into the clips, then loosely fit the two boiler securing
screws at the top, see diagram 10.1.
10.2 Internal Flue Fixing
Fit gasket to flue elbow.
Secure the flue assembly to the boiler, see diagram 10.1.
Fit the fan to the flue elbow spigot making sure the fan sealing ring
is fitted correctly and secure with the previously removed screws.
Secure the flue collector screws.
Make good internally and externally around flue.
221474C
10.3. External Flue Fixing
Fit gasket to flue elbow.
Locate flue elbow onto the boiler.
Fit the fan to the flue elbow spigot making sure the fan sealing ring
is fitted correctly and secure with the previously removed screws.
Secure the flue collector screws.
Pull the flue/air duct(s) forward and engage onto the flue elbow, see
diagram 10.2. Check the wall face to terminal dimension, see
diagram 7.6.
Push the air duct back into the wall, whilst holding the flue duct onto
the flue elbow, then secure the flue duct to the elbow, see diagram
10.2.
Pull the air duct back into engagement with the flue elbow and
secure/seal.
Make good internally and externally around flue.
20
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
10.4 Gas and Water Connections
Locate the boiler water pipes into the isolation valves and the gas
service into the gas cock union halves.
Make the compression joint on the isolating valves and join the gas
service cock union. Secure all of the valves and gas service cock
with the clips.
10.5 Boiler Securing
Secure the boiler by tightening the two boiler securing screws at the
top.
10.6 Discharge Pipe
Remove the control housing cover front securing screw and the two
control housing securing screws, see diagram 10.3.
Note. When removing and replacing the control box make sure you
protect the cables from damage.
Remove the control housing and support as shown in diagram 10.4.
If this is not possible, place on a surface, making sure that the
control knob is protected.
Remove the pressure gauge complete with bracket, see diagram
10.5.
Fit the short discharge pipe to the safety valve using the nut and
olive supplied loose, see diagram 10.6.
Extend the discharge, refer to Section 8.3.
Refit the pressure gauge.
10.7 Clock/timer Kit (if applicable)
Fit the clock/timer kit following the appropriate sections of the
instructions supplied with it.
10.8 Electrical Connector
Connect the two halves of the electrical connector together.
Clip the connector into position on the boiler mounting frame and
secure the cables with cable clamp immediately behind the
connector.
Carry out preliminary electrical system checks using a suitable
Multimeter and its instructions.
WALLSLEEVE
AIR DUCT/
TERMINAL
AIR DUCT/
TERMINAL
AIR DUCT/
TERMINAL
WALL FACE
FLUE DUCT
FLUE DUCT
0204M
FLUE
ELBOW
FLUE
ELBOW
3mm Drill
Sealing
Tape
FLUE
DUCT/
ELBOW
Diagram 10.2
FLUE ELBOW/
AIR DUCT
SECURING
SCREW (4)
BOILER SECURING
SCREW (2)
Diagram 10.1
4571
21
4573
CONTROL HOUSING
COVER SECURING
SCREWS
CONTROL
HOUSING
SECURING
SCREWS
Diagram 10.3
221474C
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
10 Boiler Fixing
SUPPORT
BRACKET
Diagram 10.4
4572
SAFETY
VALVE
SEALING
WASHER
PRESSURE
GAUGE
CONNECTION
SECURING
SCREW (2)
PRESSURE GAUGE
UNION
CONNECTION
DISCHARGE PIPE
2831
PRESSURE
GAUGE
BRACKET
Diagram 10.5
2795
11 Commissioning
11.1 Filling Domestic Water Circuit
Check that the boiler is isolated from the electrical supply, at the
external isolator.
Fully open the domestic water supply stop cock or valve in the
supply to the boiler.
Open the two domestic water isolation valves, slots in line with the
length of the valve, see diagram 8.1.
Open all hot water draw-off taps and close them when the water
flows. Check for water soundness of the complete domestic water
system.
11.2 Filling the Heating Circuit
REMINDER: It is essential that a bypass is fitted in all installations,
refer to Section 4.7.
Open the two central heating isolating valves, slots in line with the
length of the valve, see diagram 8.1.
Flush, fill and vent the system refer to Section 4.9.
‘NOTCH’
Diagram 10.6
WARNING. Several components operate on mains voltage and with
THE OUTER CASE REMOVED THEY BECOME EXPOSED.
To assist in filling and venting, the pump may be used.
IMPORTANT: Make sure that the gas supply is still isolated at this
stage
Turn on the electrical supply, if red lockout neon is lit press reset
switch, wait 15 seconds between attempts, set switch “C” to “ON”
(see diagram 11.1) any remote heating system controls, time
switch and room thermostat, for duty, see diagram 11.1.
Note. If the clock/timer kit is to be fitted, refer to the setting
instructions in the Instructions for Use.
Make sure that the automatic air vent is operating correctly, see
diagram 1.2.
Alternate the position of switch “C” between “ON” and “OFF” to
make sure that water flows through all parts of the boiler and air is
not trapped in the boiler internal bypass.
Pressurise the system until the pressure is 1.5bar (21.5lbf/in
pressure gauge “A”, see diagram 11.1.
Check the heating system and boiler for water soundness.
2
),
221474C
22
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.3 Preparation for Lighting
Isolate the boiler from the mains electrical supply at the external
isolator.
Test for soundness and purge air from the gas supply in accordance
with the rules in force in the countries of destination. Turn on the gas
service cock, slot in line with the length of the cock.
Remove the burner pressure test point screw and connect a
suitable pressure gauge, see diagram 11.2.
Remove the combustion chamber negative pressure test point
screw and connect to the pressure gauge as above, see diagram
11.1.
Note: The resultant readings given are differential pressures
11.4 Burner Pressure - Hot Water
The burner pressure will always require checking and in the
majority of installations will require adjustment. Provision for this is
made in the form of a potentiometer on the main P.C.B.
Note: All adjustments to be made while the appliance is hot.
The pressures are to be measured as a p (differential pressure).
It is therefore essential that one side of the manometer is connected
to the valve test point, and the other side is connected to the
negative pressure test point, see diagrams 11.1 and 11.2.
Connect the electrical supply, the pump will operate for about 30
seconds, then the pump stops.
Half open a hot water draw off tap and the main burner will light at
minimum gas rate.
Check that the burner pressure is 1.2mbar +/-0.2mbar. If this is
incorrect, it may be adjusted by turning the minimum pressure
potentiometer with a insulated screwdriver (anticlockwise to
decrease pressure), see diagram 11.3.
Disconnect the electrical supply, and replace the jumper.
Switch on the electrical supply.
If the above adjustment was necessary, it will be essential to check
that the maximum pressure can still be obtained.
SWITCH 'ON'
SWITCH 'OFF'
5044
6391
NEON
RESET
CENTRAL HEATING
SELECTOR SWITCH 'C'
BUTTON
Fully open the largest hot water draw off tap whereby the main
burner will light, the flames gradually increasing to maximum.
Check the soundness of the boiler gas joints, with the main burner
on, using leak detection fluid. Take care not to splash any of the
electrical components.
Fully open the hot water throttle, (clockwise), see diagram 11.4.
Check that the water flow rate is not less than 14Litre/min (3.1gall/
min) to prevent any modulation of the gas pressure. This is
equivalent to 4.3 seconds to fill a 1Litre container (2.4 seconds for
1pint).
To achieve this flow rate a water pressure of at least 0.8bar is
required during commissioning, although subsequently the appliance
will work at a minimum pressure of 0.5bar.
This flow rate should prevent any modulation of the gas pressure.
Check the burner pressure is within +/-0.2mbar of 16.8mbar, the hot
water burner pressure. If this is incorrect, the burner pressure may
be adjusted to the correct setting by turning the hot water gas
pressure adjuster (potentiometer), using an insulated screwdriver,
see section 11.5.
NOTE: If any adjustments have to be made, set the minimum
pressure first.
Close the hot water draw off.
11.5 Gas Rate Modulation
ALWAYS CHECK HOT WATER BURNER PRESSURE FIRST REFER TO SECTION 11.4.
Note: All adjustments to be made while the appliance is hot.
Check the minimum gas pressure.
First, make sure that the boiler is isolated from the electrical supply
at the external isolator. Remove the jumper, see diagram 11.3,
taking care not to mislay it
Note: This will lock the appliance at minimum gas rate
Switch on the electrical supply.
NEGATIVE
PRESSURE
TEST POINT
PRESSURE
GAUGE 'A'
Diagram 11.1
TEST
POINT
To measure gas pressure as p a second test point
is located in the bottom of the combustion chamber.
Diagram 11.2
6378
23
221474C
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
Fully open a hot water draw off tap.
Check that the burner pressure is 16.8mbar. If this is incorrect, it
may be adjusted by turning the hot water gas pressure potentiometer
with a insulated screwdriver (clockwise to increase pressure), see
diagram 11.3.
Check minimum pressure again.
If the maximum pressure is unobtainable, check that the gas supply
is of adequate size, refer to Section 1.7. Put right as necessary.
11.6 Domestic Water Flow Rate
Adjust the water throttle to obtain a flow rate of 12Litre a minute
(2.6gall/min), clockwise to increase, see diagram 11.4. This is
equal to 5.0 seconds to fill a 1Litre container, 2.8 seconds to fill a
1pint container.
Close the tap when adjustment is satisfactory.
The minimum water flow rate for operation of the boiler is 3.6Litre
a minute, (0.8gall/min), equal to 16.5 seconds to fill a 1Litre
container, 9.5 seconds for 1pint. If this flow rate cannot be achieved,
check that there is no blockage and that the supply pressure is
adequate.
Refer to Table 2.
Close the hot water draw off tap.
11.7 Burner Pressure - Heating
Check that all remote heating system controls, room thermostats,
time switches and the like are switched on/programmed and calling
for heat.
Set switch “C” to “ON”, white flash showing, see diagram 11.1.
The pump will circulate water through the boiler and the main burner
will light.
Check that the burner pressure, with the heating system cold and
temperature control knob at maximum, to prevent any modulation
of the gas pressure, is within +/-0.2mbar, of 8.0mbar. If the burner
pressure is incorrect, it may be adjusted to the correct setting by
turning the central heating gas pressure adjuster (potentiometer)
using an insulated screwdriver, see diagram 11.3. Turn the adjuster
slowly, always making adjustment by reducing below the required
pressure then increasing up to the required setting, turn clockwise
to increase.
Isolate the boiler from the electrical supply.
Remove the pressure gauge and replace the test point screws on
gas valve and combustion chamber, see diagrams 11.1 and 11.2.
Test for gas soundness around the burner pressure test points with
the main burner alight, using a suitable leak detection fluid.
Refit the cover of the control housing and refit the housing to the
boiler.
11.9 Heating System Commissioning
Check that all remote system controls and integral clock are calling
for heat.
Fully open radiator valves, flow control valve “A” and bypass valve
“B”, see diagram 4.2.
Set the heating system in operation and balance the radiators.
Adjust the flow control valve “A” to achieve the required system
differential temperature between the boiler flow and return.
Turn off all radiators, then adjust bypass valve “B” to achieve the
same temperature difference between the boiler flow and return.
Refer to Section 4.6 and diagram 4.1.
Allow the system to reach maximum temperature then switch off,
isolate the boiler from the electrical supply and drain the system
rapidly whilst hot, using the external drain tap at the lowest point of
the system.
Fill and vent the system as described previously in Section 11.2.
Add the inhibitor, if required, refer to Section 4.10.
Lower the pressure to the initial cold fill design pressure, using the
draining tap, close to the boiler, refer to Table 2 and 4 Section 4.11.
Set pointer on the pressure gauge to this pressure.
Lock or remove the handles from the spindles of flow control valve
“A” and bypass valve “B” to prevent unauthorised adjustment.
FROM
C.V.I.
CONTROL
BOARD
HOT WATER
GAS PRESSURE
POTENTIOMETER
6390
11.8 Temperature Settings
The domestic hot water outlet and central heating flow temperatures
are factory preset and sealed.
The nominal temperature setting for the Domestic Hot Water outlet
o
C (140oF) at a flow rate of 5Litre a minute (1.1gal/min).
is 60
The specific water rate is 16.8litre per minute based on a 30
temperature rise.
The nominal flow temperature setting for central heating is 80
o
F), with the user central heating temperature control set to
(176
maximum.
221474C
o
C
o
C
24
JUMPER
CENTRAL
HEATING
GAS PRESSURE
POTENTIOMETER
MINIMUM
PRESSURE
POTENTIOMETER
Diagram 11.3
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
11 Commissioning
11.10 Completion
The user control door is designed for left or right hand hinging. If
required the hinge can be moved to the other side to that supplied,
as follows:
Remove the hinge pin bracket securing screw then remove the
hinge pin retaining bracket and, holding the door, remove the hinge
pin. Prise out the hinge pin bushes and fit on to the opposite side
of the door, see diagram 11.5.
Remove the screw and nut and fit to the opposite side of the case.
After removing the other hinge pin retaining bracket refit the door
and hinge pin. Refit the hinge pin retaining bracket and fit the
securing screw.
Fit the catch assembly, supplied on the loose items pack, see
diagram 11.5.
If required, fit the plastic covers to hide the bracket securing screw.
Change the position of the “Push” label to suit new door opening.
Clock/timer, if fitted, remove the screws, nuts and washers to
release the cover plate, see diagram 11.5.
Stick the casing label to the right hand side of the clock/timer.
Fit the outer case, secure with the four screws, see diagram 11.5.
Note: Secure with the two outer screws only if there is no clock/timer
fitted.
Set the boiler and any remote heating control to the desired
settings, then close the door.
11.11 Instruct the User
Instruct and demonstrate the lighting procedure and advise the
user on the safe and efficient operation of the boiler.
Instruct on and demonstrate the operation of any heating system
controls.
Advise the user on the use and maintenance of any scale reducer
and pass on any relevant instructional documents.
Advise that to ensure the continued efficient and safe operation of
the boiler it is recommended that it is checked and serviced at
regular intervals. The frequency of servicing will depend upon the
installation conditions and usage, but in general, once a year
should be enough.
Draw attention, if applicable, to the current issue of the Gas Safety
(Installation and Use) Regulations, Section 35, which imposes a
duty of care on all persons who let out any property containing a gas
appliance.
It is the Law that all gas appliances are serviced by a competent
person.
Advise the user of the precautions necessary to prevent damage to
the system, boiler and the building, in the event of the heating
system being out of use during frost or freezing conditions.
Advise the user that the permanent mains electrical supply must not
be switched off whilst the pilot flame is alight.
Reminder, leave the Installation and Servicing Instructions with the
user.
Advise the user that the ‘Benchmark’ logbook should be completed
by the installation engineer on completion of commissioning or
servicing.
HINGE PIN
RETAINING
BRACKET
BRACKET
SECURING
SCREW
HINGE PIN
SCREW
(2)
DOMESTIC
HOT WATER
THROTTLE
NUT &
WASHER
(2)
COVER
PLATE
PLASTIC COVERS
OUTER CASE
HINGE PIN
SECURING
SCREWS (4)
PLASTIC BUSH (2)
CATCH
ASSEMBLY
SECURING NUT
2801
Diagram 11.4
6380
25
Diagram 11.5
221474C
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
1 General Data
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the boiler it
is recommended that it is checked and serviced as necessary at
regular intervals. The frequency of servicing will depend upon the
particular installation conditions and usage, but in general once a
year should be enough.
The servicing of this boiler must be carried out by a competent
person in accordance with the rules in force in the countries of
destination.
Unless stated otherwise, parts removed or renewed during servicing
should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying
components, ALWAYS test for gas soundness and carry out
functional checks of controls.
Discard all used sealing washers, gaskets and “O” rings when
renewing components.
Use the new ones supplied with the replacement.
An Aid to Servicing
To obtain a products of combustion reading, make sure that the
main burner is alight. Remove the plastic cap, see diagram 1.2 and
connect the analyser probe to the tube, replace cap after use.
1.2 Data Label
The data label is positioned on the front of the inner case cover, see
diagram 1.1.
1.3 Isolation of Boiler
Before commencing any servicing or the replacement of parts,
isolate the boiler from the electrical supply at the external isolator
and close the gas service cock, see diagram 4 User Instructions.
BEFORE DRAINING THE BOILER, REFER TO SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door catch is
spring loaded, to open, push the side opposite to the hinge then pull.
Remove the two screws securing the outer case then unhook the
case at the top and pull it forward and off, see diagram 6.1
Installation Instructions.
Note: Remove the four securing screws if there is a clock/timer
fitted.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four screws, see
diagram 1.1.
1.6 System Pressures and Draining
WARNING. All parts containing water of the central heating circuit
within the boiler, are under the system pressure. Before any parts
of this circuit are disconnected, reduce the system pressure at the
external draining tap. Turn the central heating isolating valves off
and drain at the drain points on the appropriate valves, see diagram
4 User Instructions.
All water containing parts of the domestic hot water circuit of the
boiler will be under the supply water pressure. Before any parts of
this circuit are disconnected, turn the domestic cold water isolating
valve off, open the hot water taps to reduce the water pressure in the
boiler, and drain the boiler at the valves, see diagram 4 User
Instructions.
After replacing any water containing part of the central heating
circuit, make up the water loss, vent all air and pressurise the
system. Refer to “Commissioning” in the Installation Instructions.
Check for water soundness.
SECURING
SCREW (4)
DATA
LABEL
INNER
CASE
COVER
BURNER WINDOW
SCREW (2)
Diagram 1.1
6354
221474C
26
4580
PLASTIC
CAP
Diagram 1.2
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Servicing
2.2 Isolation and Access
Before starting, refer to Section 1.1.
Isolate the boiler from the electrical supply and close the gas
service cock, refer to Section 1.3.
Remove the outer case and the inner case cover, refer to Sections
1.4 and 1.5.
Disconnect the electrical plug connector from the fan, see diagram
2.1.
Remove the flue collector securing screws, see diagram 2.1.
Remove the fan securing screws.
Pull the fan forwards, at the bottom and rotate to disengage the fan
outlet to flue elbow and rear bracket.
Take care not to damage the seal.
Tilt the fan and withdraw.
Remove the flue collector, note, this may be a tight fit.
Remove the combustion chamber front panel, secured with four
screws, see diagram 2.2.
Remove the spark electrode assembly from the burner, secured by
2 nuts, see diagram 2.3 and carefully lay it down in the combustion
chamber.
Remove the burner support bracket wing nut and securing screw,
see diagram 2.4.
NOTE: The sensing lead is connected to the burner. Disconnect
the lead when the burner is being removed.
Remove the main burner from the main injector at the rear, see
diagram 2.4. Raise the burner up and forwards. Take care not to
damage the combustion chamber insulation.
2.3 Heat Exchanger
Place a sheet of paper or similar in the combustion chamber, to act
as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove paper
together with any debris.
FAN OUTLET
SEAL
FAN
SECURING
SCREWS
FLUE
COLLECTOR
SECURING
SCREWS (2)
HEAT
EXCHANGER
SECURING
SCREW (4)
PLUG
Diagram 2.1
6922
5684
2.4 Main Injector
Inspect the injector and clean as necessary.
Do not use wire or a sharp instrument on the hole.
2.5 Main Burner
Use a vacuum cleaner or suitable brush to clean the burner
thoroughly, making sure that all burner ports are clear and free from
obstructions.
Do not use a brush with metallic bristles.
COMBUSTION
CHAMBER FRONT PANEL
Diagram 2.2
27
221474C
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Servicing
2.6 Service Checks
Before replacing any parts removed during servicing, inspect the
condition of all seals and joints, renewing them as necessary.
Check the condition of the combustion chamber insulation.
Check that the spark and sensing gaps are as shown in diagram
2.3.
2.7 Note. Reassembly
Make sure the sensing lead is reconnected and the main burner is
fitted correctly on assembly, located on the main injector and
horizontal, the tips of the rearmost blade under the two burner
guides, see diagram 2.4.
Locate the combustion chamber front panel under the front edge
of the flue hood on assembly, then secure all screws and wing nuts.
The combustion chamber front panel should be fitted loosely, then
the flue collector also fitted loosely, make sure that it is seated onto
the heat exchanger and over the top edge of the front panel.
To fit the fan, locate it into the rear bracket and ease the flue elbow
onto the fan outlet, making sure that the fan outlet seal is correctly
positioned. Secure with the two screws, see diagram 2.1.
Refit electrical connector making sure that the red spots are
aligned.
Refit the sensing tube.
+0.5
5
-0.5
SPARK
ELECTRODE
SECURING
NUT AND
WASHER (2)
+0.5
3
-0.5
EARTH
ELECTRODE
5059
+0.5
5
-0.5
5018
Secure the flue collector and combustion chamber front panel by
tightening the securing screws, see diagram 2.1 and 2.2.
Refit the inner case cover, see diagram 1.1.
2.8 Operational Checks
Light the boiler, carry out operational checks and any necessary
adjustments as described in “Commissioning” in the Installation
Instructions.
2.9 Completion
Hook the outer case on at the top and secure with the screws
previously removed, see diagram 6.1 Installation Instructions.
Close the door.
SILICONE
TUBES
SEALING ANGLE
Diagram 2.3
221474C
28
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
2 Servicing
SECURING
SCREW
BURNER
BURNER
BRACKET
WING NUT
SPARK
ELECTRODE
EARTH
ELECTRODE
5695
BURNER
GUIDE
MAIN INJECTOR
5697
SENSING LEAD
Diagram 2.4
29
221474C
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
3.1 Initial Checks
If the boiler fails to operate, first check the following:
1) That the electrical supply is available at the boiler and the fuses
are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED
BY INCORRECT TESTING WITH THE POWER ON.
2) Make sure that the system pressure gauge registers 0.7bar,
minimum, and that the automatic air vent works. Refer to Installation
Instructions, Section 11.2.
3) That the gas supply is available at the boiler and purged of air.
4) That the boiler is set for the required service.
5) With the boiler central heating selector switched “Off”, see
diagram 6.1 Installation Instructions, check that the domestic water
supply is available and water flows freely from the hot taps. Close
the taps.
6) With the boiler central heating selector switched “ON”, see
diagram 6.1 Installation Instructions, check that all heating system
controls, if fitted, are working correctly and calling for heat. If not
isolate the boiler from the electrical supply. Disconnect the rear
multipole connector at the base of the boiler and release the cable
from the clamp.
Remove the connector cover and dependent on the type of control
fitted test for continuity of mains at terminals 1 and 2, see diagram
3.1.
7) Check reset button - if red neon is lit press button. In certain
circumstances the red neon light may not come on, due to no
system demand. Turn on a domestic hot water draw off tap to
create a demand, the light should come on, if reset is required.
Allow the boiler and system to cool down waiting at least a minimum
of four minutes before pressing the reset button.
If this is satisfactory proceed with the detailed fault finding as
Section 3.3.
On completion of a fault finding task that has required the
disconnection and making of electrical connections then checks,
for earth continuity, polarity and resistance to earth must be carried
out.
3.2 Clock/Timer
If the clock has failed it can be bypassed by isolating electrical
supply and gaining access to the control box. Refer to Section 4.14,
disconnect the clock wiring harness from the 4 way terminal block.
Fit a yellow link between the terminals Y1 and Y2.
This is a temporary measure and the clock should be repaired or
replaced as soon as possible.
3.3 Electrical
Preliminary electrical system checks, as outlined in a Multimeter
Instruction book, are the first checks to be carried out during a fault
finding procedure.
WARNING: Should fault finding have to be carried out on the CVI
box, see diagram 4.13. Precautions should be taken as this box
carries high voltage.
Isolate the boiler from the electrical supply, refer to Section 1.3.
Gain access to the boiler controls by removing the outer case, refer
to Section 1.4. Check that all cables and connectors are secure.
Gain access to the control board, refer to Section 4.14. Check all
cables at the multipin connectors on the board.
Test the two fuses on the main control board and renew as
necessary. Fuse 1 type (2AT), Fuse 2 type (3.15 AT). If a fuse fails
repeatedly or the initial fault-finding checks described in Section 3.1
indicate a boiler fault, check the boiler electrical circuits and follow
the fault finding procedures, see diagram 3.2, 3.3, 3.4, 3.5 and for
clock/timer fault finding, diagram 3.6 and 3.7.
2
E
N
L
3
CABLE
CLAMP/COVER
SCREW (2)
2883
CABLE TO
REMOTE
HEATING
CONTROLS
1
MAINS
CABLE
CABLE
CLAMP
Diagram 3.1
221474C
30
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
PERMANENT
LIVE 230V~50Hz
(L)
OPTIONAL
SWITCHED LIVE
FROM ROOM
STAT. 230V~50Hz
(N)
M
(L)
ON
COMMON
CLOCK/TIMER
6421
br
b
br
y
y
(N)
b
CONTROL BOARD
4
TERMINALS
CONTROL BOARD
3
TERMINALS,
BLOCK 3
CONTROL BOARD
2
TERMINALS,
BLOCK 2
b
br
PUMP
LOW
VOLT
28V~
r
TRANSFORMER
5b
RESET /
NVLO
INDICATOR
12 11 10 9 8 7 6 5 4 3 2 1
6b
4b
3a
p
or
b
230V~
br
b
r
br
LN
3
T2A
2B
FUSE
white
2B
2A
2A
2A
3
4
CONTROL BOARD
(N)
KEY
brBROWN y YELLOW
bBLUE or ORANGE
rRED
pPURPLE
vVIOLET
31
CVI IGNITION UNIT
(N)
Diagram 3.2
221474C
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
CVI IGNITION UNIT
1
2
3 Fault Finding
gry
gry
y
1
6473
1
1
USER
CONTROL
BOARD
N/C
N/O
WATER PRESSURE
SWITCH
w
(SHOWN IN
PRESSURISED
STATE)
DHW
FLOW
SENSOR
w
THERMISTOR
DHW
THERMISTOR
C
CH
TRANSFORMER
TO REMOTE
HEATING
CONTROL
r
w
bk
SELECTOR
SWITCH
bk
LN
230V~
bk
26V~
r
p
y
5 WAY PLUG/SOCKET
br
br
or
or
p
p
gry
p
y
or
1
1
1
4
4
8
8
8
4
4
4
4
4
4
5
5
5
5
D.C.
FAN
1
FAN DRIVER
P.C.B.
2 2 2 2 222 2
1
1
1
p g y b gry w rScreen
KEY
br
bk
b
g
gry
or
p
r
v
w
y
- Brown
- Black
- Blue
- Green
- Grey
- Orange
- Purple
- Red
- Violet
- White
- Yellow
gry
p
or
y
CONTROL
BOARD
MAIN PCBFAN DRIVER PCB
CN 1
1
CN 4
4
CN 5
5
CN 7
7
CN 8
8
1
CN 1
CN 2
2
7
7
7
7
Diagram 3.3
221474C
32
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
Carry out initial Fault Finding checks described in Section 3.1 and 3.4. Check that gas, water and electricity
are available at the boiler.
Before starting the test, isolate the boiler from the electrical supply, ensure that the remote
controls are not calling for duty. Refer to the functional flow diagrams in conjuction with the
following fault finding.
START
Remove outer case control housing, control housing cover, user control knob and the cover.
Check all connections on the controls boards. Rectify or renew as necessary.
6420
Restore power to the appliance.
Is the Orange 'Mains' light illuminated?
NO
YES
Does Pump run?
NO
YES
Turn on DHW tap
Does DHW work OK?
NO
YES
Is green LED lit?
NO
YES
With central heating demand on.
Can the temperature be varied by rotating the
control knob?
YES
Turn off C.H. and D.H.W demand.
Simulate a leak on Central Heating Circuit by
draining the appliance. As pressure approaches
'ZERO' does the Red 'Low Pressure' light flash?
NO
NO
Faulty 'User Control' Replace
Refer to Electrical Control Fault Finding
Refer to Fault Finding
Faulty 'User Control' Replace
Faulty 'User Control Replace
See Electrical Controls fault finding for
'Water Pressure Switch', if in order
replace faulty user control
YES
User Control board in order
To stop Red 'Low Pressure' light flashing.
Refill C.H circuit to 0.7 bar then switch the
electrical supply to the appliance off and then on.
Proceed to Electrical Controls fault finding
if fault persists.
33
Diagram 3.4
221474C
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
start
Replace
CVI box.
Is there
continuity across
yellow & black
on WPS?
Faulty water
pressure switch.
Replace
Is there 300Vdc
NO
DC power out of
pins on CVI box
to gas valve?
Check continuity
on valve.If faulty
replace.
Apply CH
demand.
NO
YES
YES
NO
Is ignition
burner pressure
at least 2.0 mb?
Does red
lockout light?
YES
YES
YES
NO
Is there 230Vac
CN2B pins 5 & 6
on main PCB?
NO
YES
Reset lockout
switch.
Does fan run
at ignition rate?
YES
Is there a spark
at electrode?
NO
Is TXR
supply 230Vac?
Is there
at least 30Vac on
TXR secondary?
YES
YES
6418
NO
NO
NO
Do sparks stop
after burner is lit?
YES
Faulty
CVI
Does burner
pressure increase
after ignition?
NO
NO
Faulty sense
electrode
YES
Does boiler
go to lockout?
NO
Correct CH
operation
Faulty
main
PCB
YES
Isolate supply. Is the
resistance at CN2 on
the fan driver PCB
between White and
Grey, Grey and Purple,
Purple and White
approx 2.5ohms ?
Is there continuity at
CN2 on the fan driver
PCB between White
and the fan motor
laminations? (repeat
with Grey and Purple).
Faulty
CVI
Is there
30Vac CN7 on
pins 3 & 4 and
0.8Vdc on pin 1
& 2 CN7?
YES
NO
YES
NO
Faulty
TXR
NO
Faulty
main
PCB
Faulty fan.
Replace.
Faulty fan.
Replace.
Faulty fan driver
PCB. Replace.
221474C
34
Diagram 3.5
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
3 Fault Finding
6419
NO
Is DHW thermistor
10k ohms cold?
Faulty DHW
thermistor.
Is the Vdc on CN4
pins 8/9 greater
than 10 Volts
YES
Faulty
flow
sensor.
YES
Faulty
main
PCB.
NO
NO
Switch off CH
demand.Switch
on DHW.
Does boiler go into
ignition sequence?
Does boiler
go to lockout?
Is there continuity
of boiler protection
thermostat?
Faulty
DHW
stat.
NO
YES
YES
Faulty
main
PCB.
Has CH
overheat gone
open circuit?
NO
Faulty sense
electrode.
NO
Correct
operation.
YES
YES
Is there 230Vac
on CN2-B pin
7+8 to pump?
NO
Faulty
main
PCB.
NO
Turn to
release.
YES
Is CH thermistor
resistance correct
10k ohms cold
1.6k ohms hot?
NO
Faulty CH
thermistor.
YES
Check pump
spindle is free.
YES
Replace
pump.
35
Diagram 3.5
221474C
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
e
If mains potential room thermostat is connected, make sure that the switch live is connected
If mains potential room thermostat is connected, ensure that the switch live is connected to
to Pin 1 in the 5 pole connector.
Pin 1 in the 5 pole connector.
Check continuity of clock/timer harness, make sure an electrical supply is available,
Check continuity of clock/timer harness, ensure an electrical supply is available,
make sure that remote controls are calling for heat.
ensure that remote controls are calling for heat.
Isolate the boiler from electrical supply,
remove outer case.
3 Fault Finding
5665
Switch on electrical supply, is there a
display on clock/timer?
YES
Disconnect and insulate the yellow cables from
heating common and heating on
Advance clock/timer until a demand is indicated
Is there now continuity between heating
common and heating on?
YES
Clock/timer in order if no central heating,
refer to main fault finding.
NO
NO
Faulty clock/timer. Replace.
Faulty clock/timer. Replace.
DIGITAL CLOCK/TIMER
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remot
controls are calling for heat.
Does clock keep time
Yes
Isolate electrical supply set clock to on period
Is there continuity across
common and heating on
Yes
Set clock to off period. Is there continuity
across common and heating on
No
No
Clock in order if no
central heating refer to
main fault finding
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
Before replacing any part please read points below:Replacement of parts must only be carried out by a competent
person.
Unless stated otherwise all parts are refitted in the reverse order to
removal.
1. Refer to Section 1.1.
2. Always isolate the boiler from the electrical and as required the
gas supply as Section 1.3.
3. Unless stated otherwise, gain access as appropriate parts of
Sections 1.4 and 1.5.
4. On completion, make good any water loss and pressurise the
system to initial design pressure, refer to “Commissioning” in the
Installation Instructions.
If the red light “flashes”, momentarily interrupt the electrical supply.
4.1 Fan
Refer to the appropriate parts of Section 2.2.
After fan has been fitted, check the burner pressure and if necessary
adjust, refer to Installation Instructions, section 11.4.
4.2 Main Burner
Refer to the appropriate parts of Section 2.2.
CLOCK/TIMER
(if fitted)
Note. There is no need to remove the fan or flue collector
assemblies.
4.3 Main Injector
Refer to the appropriate parts of Section 2.2.
Note. There is no need to remove the fan or the flue collector
assemblies.
4.4 Spark Electrode
Remove the inner case as Section 1.5.
Slacken the two screws securing the flue collector, see diagram 2.1.
Remove the combustion chamber front panel, secured with four
screws.
Remove the spark and earth electrode assembly leads and silicone
tubes, securing nuts and washers
Disconnect the leads and silicone tubes.
NOTE: the ignition lead is black and the earth lead is white
4.5 Sensing Electrode
Remove the main burner refer to Section 4.2.
4.6 Ignition Lead
Remove inner case as Section 1.5.
Disconnect spark electrode assembly, and lead as described in
Section 4.4.
Disconnect lead at the ignition unit on gas valve. Remove silicone
4589
tube, slacken sealing angle and withdraw lead.
Refer to diagram 4.13.
CONTROL
HOUSING
SECURING
SCREW (2)
TOP CONTROL
HOUSING COVER
BOTTOM CONTROL
HOUSING COVER
6362
SUPPORT
BRACKET
FAN DRIVER
CONTROL
HOUSING)
SECURING
SCREW (2)
SCREW(2)
CLOCK/TIMER
(if fitted)
Diagram 4.1
37
ELECTRICAL
CONNECTORS (2)
Diagram 4.2
221474C
Page 38
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.7 Sensing Lead
Remove main burner as described in Section 4.2. Disconnect the
lead from sensing electrode.
Disconnect lead at the ignition unit on gas valve.
Slacken sealing angle and withdraw lead.
Refer to diagram 4.13.
4.8 Earthing Lead
Refer to section 4.6, and diagram 4.13.
4.9 Boiler Overheat Cutoff
Remove user control switch bracket by slackening securing screws,
disconnect electrical connectors, see diagram 4.3.
Disconnect the boiler overheat cutoff electrical connectors, see
diagram 4.2.
Remove the overheat cutoff, secured with two screws, see diagram
4.2.
Use the heat sink compound supplied, between the mounting plate
and the cutoff, when fitting it.
When refitting the electrical connections to the boiler overheat cut
off, the polarity is not important.
4.10 Water Pressure Switch
Release the water pressure and drain the central heating circuit of
the boiler, refer to Section 1.3 and 1.6.
Remove the control housing as Section 4.13.
Disconnect the electrical connectors at the pressure microswitch,
see diagram 4.4.
Remove pressure switch, see diagram 4.4.
Replace the “O” ring seal with the new seal provided.
Make sure that the switch terminals are facing diagonally forwards
to give access, as shown in diagram 4.4.
Reconnect the electrical connections, refer to diagram 4.11.
4.11 Pump
Release the water pressure and drain the central heating circuit of
the boiler, refer to Section 1.3 and 1.6.
Disconnect the electrical connectors at the water pressure
microswitch. Remove the water pressure switch, refer to Section
4.10.
Remove the terminal cover from the pump and disconnect the
cable, see diagram 4.5.
Disconnect the pump at the unions.
Discard the sealing washers.
Make sure that the flow direction arrow is pointing upward when
fitting and use the new sealing washers.
Refit water pressure switch, refer to Section 4.10.
The flow adjuster on the new pump should be set to that of the
original, refer also to Section 4.6 in the Installation Instructions.
The flow rate should be controlled by means of a valve in the heating
flow, refer to Section 11.9 in the Installation Instructions.
Note: Should the pump fail to operate, refer to diagram 3.5. If all
is in order, but the pump still does not operate, remove the end
screw, see diagram 4.5. Access to the end screw will be aided if the
ignition unit is first removed. See section 4.17 for details. Then turn
the pump spindle to release any temporary seizure.
DO NOT HIT THE SPINDLE.
221474C
SECURING SCREW (2)
USER
CONTROL
SWITCH
BRACKET
ELECTRICAL
CONNECTORS
SELECTOR SWITCH
PUMP
SPINDLE
END
SCREW
38
CONTROL RESET
BUTTON
PUMP
ADJUSTER
TERMINAL COVER
SCREW
2848
Diagram 4.3
4592
WATER
PRESSURE
SWITCH
Diagram 4.4
4593
FLOW DIRECTION
ARROW
UPPER
PUMP
UNION
LOWER
PUMP
UNION
Diagram 4.5
Page 39
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.12 Boiler Protection Thermostat
Remove the pump, see Section 4.11.
Disconnect the electrical connectors at the domestic hot water high
limit control, see diagram 4.6.
Remove the high limit control from the flow pipe, secured with two
screws.
When refitting the electrical connections to the high limit control the
polarity is not important, see diagram 4.11.
Use the heat sink compound supplied, between the mounting plate
and the control.
4.13 Pressure Gauge
Remove the control housing assembly, see diagram 4.1.
Release the water pressure and drain the central heating circuit of
the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge bracket.
Disconnect the pressure gauge connection from the safety valve,
discard the washer, see diagram 4.7.
Remove the pressure gauge secured with the retaining tabs.
Locate the supplied new washer under the pressure gauge
connection when refitting the safety valve.
ELECTRICAL
CONNECTORS
6377
BOILER
PROTECTION
THERMOSTAT
4.14 Control Boards
CAUTION. Great care must be taken when handling any control
board.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI
STATIC HOLDER UNTIL NEEDED.
Note. Timer/clock may be removed to improve access, see Section
4.32 or the control housing bottom half can be removed.
Main Control Board
Remove control housing cover securing screw, see diagram 4.8.
Remove the control housing assembly as shown in diagram 4.1.
Lift the control housing cover to gain access to the board.
Disconnect all multipin connectors, see diagram 4.8.
Remove the control board from the support posts.
To reconnect the multipin connectors correctly, see diagram 4.11.
When replacing the main control board check and adjust the main
burner gas pressure in both the domestic hot water and central
heating modes. Check also minimum burner pressure. Refer to
“Commissioning” in the Installation Instructions.
Fan Driver Board
Remove the fan driver control housing assembly securing screws.
SAFETY
VALVE
SEALING
WASHER
PRESSURE
GAUGE
CONNECTION
SECURING
SCREW (2)
PRESSURE GAUGE
SECURING
SCREW (2)
Diagram 4.6
2831
PRESSURE
GAUGE
BRACKET
Diagram 4.7
Remove the multipin connectors, see diagram 4.9.
Release the board from its support posts then remove the nut and
screw securing the board to the cover, see diagram 4.9.
User Control Board
Remove the fascia, see diagram 4.8.
Remove the multipin connector.
Remove the control board from the supports posts.
39
221474C
Page 40
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
FASCIA
CONTROL
HOUSING
SECURING
SCREW (2)
FASCIA
SECURING
SCREW (3)
HINGE PIN
TRANSFORMER
MULTI-PIN
CONNECTORS
TEMPERATURE
CONTROL KNOB
CONTROL
HOUSING
COVER
SECURING
SCREW
CONTROL
HOUSING
COVER
4595
4.15 Transformer
Note. Timer/clock may be removed to improve access, see Section
4.32 or the control housing bottom half can be removed.
Remove the control housing cover screw, see diagram 4.8.
Remove control housing assembly, see diagram 4.1.
Remove the control housing cover and disconnect the electrical
connectors from the transformer, see diagram 4.8.
Remove the transformer securing screws (2 off) from beneath the
control housing, remove the transformer and insulation.
To connect the transformer cables correctly, refer to diagram 4.11.
FAN DRIVER
BOARD
FAN DRIVER
CONTROL
HOUSING
SECURING
SCREW NUT
4596
USER CONTROL
BOARD
WIRING AS
DIAGRAM 4.12
Y
Y
Y1
Y2
*
Y
SUPPORT POSTS
BR
B
L
N
B
BRY
Diagram 4.8
Note:
*
Remove
'Yellow Link'
before fitting
Clock/Timer
4 WAY
TERMINAL
BLOCK
SUPPORT
POSTS
Y
Y
COMMON
HEATING ON
MULTI-PIN
CONNECTORS
BR
B
CLOCK /
TIMER
L
N
Diagram 4.9
5229
221474C
40
Diagram 4.10
Page 41
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
rwgrybygp
screened
DC
FAN
RESET NVLO
INDICATOR,VIEW
FROM REAR
or
b
b
230V-50Hz PERMANENT
MAINS SUPPLY FUSED
AT 3A
Y P G/Y B BR
(L)
123N
screened
6368
r
w
gry
b
y
g
p
gry
L N E
BOILER
PROTECTION
THERMOSTAT
GAS VALVE
r
BOILER
OVERHEAT
CUT OFF
FLOW SENSOR
PUMP
gry
b
br
r
p
or
p
RESET
NVLO
INDICATOR
THERMISTOR
DHW
THERMISTOR
CH
b
14 5 6 7 8
IGNITION UNIT
w
FAN
DRIVER
BOARD
or ypgry
y1
y2
NL
yy
b br
WIRING AS
DIAGRAM 4.12A
y
or
USER CONTROL
BOARD
p gry
CENTRAL HEATING
SELECTOR
SWITCH
w
L
TRANSFORMER
N
bbr
br
CN3
NL
p
MAINS
y
br
CN4
br
or
or
p
p
gry
p
CN5
y
or
ww
b
L
N
CN2A
230V~ 50Hz
TXR
FUSE 2AT
KEY:
w
- WHITE
b
- BLUE
bk
- BLACK
br
- BROWN
g/y
- GREEN/YELLOW
gry
- GREY
or
- ORANGE
v
- VIOLET
r
- RED
y
- YELLOW
p
- PURPLE
MAIN CONTROL BOARD
WATER
PRESSURE
SWITCH
r
bk
r
b
br
b
CN2B
CN7
FUSE
CN1
CN8
3.15AT
C
NO
NC
bk
gry
p
y
or
bk
y
bk
r
gry
gry
r
w
bk
CHASSIS
EARTH G/Y
g/y
g/y
g/y
CONTROL
HOUSING
41
Diagram 4.11
221474C
Page 42
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.16 Gas Valve
Remove control box housing, see diagram 4.1.
Remove the user control switch bracket, see diagram 4.3.
Remove the ignition unit securing screws, see diagram 4.12.
Remove ignition unit.
Disconnect sensing tubes noting which way they fit.
Remove the four extended hexagon screws at the right hand side
of the gas valve,
Support the gas valve, disconnect the union nut at the gas service
cock and remove the valve complete with the inlet pipe.
Separate the valve from the pipe, noting the fitted position.
Discard the “O” rings and fit the new ones supplied.
Fit gas valve cables. The polarity is not important.
Check and adjust the main burner gas pressure in the hot water
and central heating modes, refer to “Commissioning” in the
Installation Instructions.
4.17 Ignition unit
Remove control box housing, see diagram 4.1.
Remove the user control switch bracket, see diagram 4.3.
Remove the ignition unit securing screws. see diagram 4.13.
Disconnect the electrical connector and the three electrode leads.
Remove ignition unit.
Note: when re-fitting make sure the electrode leads are fitted to the
correct terminals, see diagram 4.13.
SECURING
SCREW
SENSING
TUBES
(4+4)
IGNITION UNIT SECURING
SCREW
GAS VALVE
SECURING
CONNECTOR
SCREW
6369
IGNITION UNIT
Diagram 4.12
IGNITION (CVI)
UNIT
5288
4.18 Domestic Hot Water Flow Sensor
Before commencing refer to Section 1.1
Isolate the boiler from the electrical supply, refer to Section 1.3.
Remove the outer case, refer to Section 1.4.
Isolate the domestic hot water inlet, release the domestic water
pressure and drain, refer to Section 1.3 and 1.6.
Remove the control housing, refer to Section 4.14.
Remove the user control switch bracket, see diagram 4.14.
Remove the pressure gauge bracket, see diagram 4.7.
Disconnect the flow sensor cables at the inline connectors.
Remove the flow sensor by disconnecting the union nuts, see
diagram 4.15, noting the fitted position.
Slacken or remove the clip securing the isolating valve, to ease
removal.
Discard the sealing washers and use the new ones supplied.
It is recommended that the water inlet filter is cleaned or renewed
at this stage.
Make sure that the sensor is positioned correctly, with the flow
arrow pointing upwards.
SECURING
SCREW (2)
EARTH
ELECTRODE
LEAD
SPARK
ELECTRODE
LEAD
SENSING
ELECTRODE
LEAD
Diagram 4.13
5027
CONTROL
RESET BUTTON
ELECTRICAL
CONNECTORS
221474C
42
SELECTOR
SWITCH
Diagram 4.14
Page 43
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.19 Thermistor - Heating
Gain access, by removing the user control switch bracket, see
diagram 4.3.
Disconnect the cables from the thermistor, see diagram 4.16.
IMPORTANT: Do not remove cable retaining strap.
Unclip the thermistor.
NOTE: When the thermistor is replaced, it must be repositioned at
the same location as before.
The polarity of the electrical connections is not important.
4.20 Thermistor - Domestic Hot Water
Disconnect the cables from the thermistor, see diagram 4.16.
IMPORTANT: Do not remove cable retaining strap.
Unclip the thermistor.
NOTE: When the thermistor is replaced, it must be repositioned at
the same location as before.
The polarity of the electrical connections is not important.
4.21 Safety Valve
Release the water pressure and drain the central heating circuit of
the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.13.
Disconnect the union nuts to release the safety valve, see diagram
4.17.
4.22 Water Inlet Filter
Refer to the appropriate parts of Section 4.18.
FLOW
SENSOR
FILTER
UNION
NUT
WATER
FILTER
WATER
INLET PIPE
ASSEMBLY
UNION NUT
VIEW ON ARROW 'A'
UNION
ISOLATING
NUT
VALVE
6364
FLOW SWITCH
LOCKNUT
'A'
FLOW SWITCH
ELECTRICAL
CABLES
THROTTLE
Diagram 4.15
4.23 Domestic Hot Water Throttle
Release the water pressure and drain the domestic hot water circuit
of the boiler, refer to Section 1.3 and 1.6.
Refer to Section 4.18 to gain access to the throttle.
Remove the cap nut and carefully remove the throttle adjuster, by
unscrewing, it may be necessary to push the throttle adjuster out
from the rear, see diagram 4.18.
Clean if necessary, taking care not to damage the throttle body.
Reset the domestic hot water flow rate refer to Section 11.6 in the
Installation Instructions.
4.24 Mini Expansion Vessel
Release the water pressure and drain the domestic hot water circuit
at the boiler, refer to Sections 1.3 and 1.6
Remove the control housing as diagram 4.1 .
Note. It may be possible, in some circumstance, to remove the mini
expansion vessel by hand.
When refitting use the new sealing washer supplied, see diagram
4.19.
4.25 Automatic Air Vent
Release the water pressure and drain the central heating circuit of
the boiler, refer to Sections 1.2 and 1.6.
Remove the automatic air vent, see diagram 4.20.
SLACKEN THE SMALL CAP ON THE AIR VENT. THIS MUST
NOT BE RETIGHTENED.
When refitting use the new washer supplied.
6370
CENTRAL
HEATING
THERMISTOR
ELECTRICAL
CONNECTORS
D.H.W.
THERMISTOR
Diagram 4.16
43
221474C
Page 44
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.26 Heat Exchanger
Release the water pressure and drain the central heating and
domestic hot water circuits refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 2.2.
Remove the flue collector, refer to Section 2.2.
Remove the main burner, refer to Section 2.2.
Remove the automatic air vent, refer to Section 4.25. If renewing
the heat exchanger, transfer the air vent, using the new sealing
washers provided.
Disconnect the front gas/air ratio sensing tube, see diagram 4.20.
Make sure that no water enters the tube.
Disconnect the union nuts of the heat exchanger to remove it, see
diagram 4.20.
Reassembly Notes.
Locate the raised location tabs on the combustion chamber sides
into the slots on the heat exchanger, see diagram 4.20.
Make sure that the main burner baffle has located in the side guides
and that the burner is located on the main injector.
The combustion chamber front panel should be fitted loosely, then
the flue collector also fitted loosely, make sure that it is seated
correctly on the heat exchanger and over the top edge of the front
panel.
4.27 Combustion Chamber Insulation
Note: Before handling the insulation panels, it is advisable to
dampen them with water to prevent dusting and consequently avoid
any inhalation or skin irritation.
Remove the combustion chamber front panel secured with four
screws, see diagram 4.21.
Remove the front insulation piece, secured with a clip, see diagram
4.22.
Slide out both side insulation pieces.
Remove the burner as in Section 2.2.
Pull the lower rear insulation forward, then slide the upper rear
insulation down from behind the heat exchanger, see diagram 4.22.
SAFETY
VALVE
PRESSURE
GAUGE
CONNECTION
CAP NUT
SEALING
WASHER
THROTTLE
ADJUSTER
‘O’ RING
DISCHARGE
PIPE
UNION
NUT
Diagram 4.17
Diagram 4.18
2794
4600
6371
221474C
44
SEALING
WASHER
MINI EXPANSION
VESSEL
Diagram 4.19
Page 45
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
LOCATION
SLOT
CAP
SEALING
WASHER
AUTOMATIC
AIR VENT
6923
COMBUSTION
CHAMBER
FRONT PANEL
CLIP
FRONT
INSULATION
6392
UNION
NUTS
GAS/AIR RATIO
SENSING TUBE
FLUE
COLLECTOR
SECURING
SCREWS (2)
SECURING
SCREW (4)
UNION
NUTS
SIDE INSULATION PIECES
Diagram 4.20
6924
LOWER REAR INSULATION
COMBUSTION CHAMBER
FRONT PANEL
Diagram 4.21
45
UPPER REAR INSULATION
Diagram 4.22
221474C
Page 46
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.28 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be removed
from the wall. As an alternative, a separate expansion vessel of the
same specification may be connected as close as possible to the
boiler, leaving the original in position, refer to Section 4.5 in the
Installation Instructions.
Release the water pressure and drain the central heating and
domestic water circuits, refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 2.2.
Remove the flue elbow, refer to Section 10 of the Installation
Instructions.
Disconnect the boiler water connection union nuts at the front of the
isolating valves, see diagram 1.1.
Disconnect the gas service cock union.
Disconnect the safety valve discharge pipe from the boiler, see
diagram 1.1.
Separate the two parts of the boiler multi-pole electrical connector.
Slacken the clips of the gas service cock and the water isolating
valves.
Remove the boiler from the mounting frame, secured with two
screws at the top, see diagram 4.23. Pull the boiler from the
isolating valves. Unhook the boiler at the top and lift off.
Carefully lay the boiler down on its side for access to the expansion
vessel.
Disconnect the union nut connection, see diagram 4.24 and discard
the sealing washer.
Remove the expansion vessel, secured with three clamping screws.
Connect the union nut, when fitting the expansion vessel, before
clamping it.
4.29 Burner Viewing Window
Remove the burner viewing window, secured with two screws.
When fitting a new window use the gasket provided, see diagram
4.25.
4.30 Inner Cover Case Seal
Remove the old seal, clean out the old adhesive.
Glue the new seal into place, make sure that there are no breaks
in it.
4.31 Air/Gas Ratio Sensing Venturi
Remove the fan assembly and flue collector, refer to Section 2.2.
Disconnect the tube nut and screw to release the sensing venturi,
see diagram 4.26.
UNION NUT
CONNECTION AND
SEALING WASHER
2861
LOCATION
CLIPS
CLIP
(5)
SECURING (2)
6925
SECURING
SCREW (2)
SCREW
CLAMPING SCREW (3)
FRAME
6366
GLASS
VENTURI
Diagram 4.24
4606
GASKET
Diagram 4.25
UNIONS (5)
221474C
Diagram 4.23
46
TUBE
NUT
Diagram 4.26
Page 47
Supplied By www.heating spares.co Tel. 0161 620 6677
4 Replacement of Parts
4.32 Clock/Timer - if fitted
ELECTRO/MECHANICAL and DIGITAL clock/timer - Release the
mounting bracket securing screws, see diagram 4.27.
Note: Care should be taken here, as these screws also retain the
fan driver control housing in position, see diagram 4.1.
Disconnect electrical cables, release securing clip to remove the
clock/timer spacer plate, see diagram 4.28.
6507
CLOCK/TIMER
SECURING
SCREWS (2)
ELECTRICAL
CONNECTIONS
y
y
br b
KEY
br BROWN
b BLUE
y YELLOW
MAINS
NEUTRAL (N)
SECURING CLIP (2)
6515
MOUNTING
BRACKET
SPACER
PLATE
COMMON
MAINS
LIVE (L)
HEATING ON
ELECTRO/MECHANICAL and
DIGITAL CLOCK/TIMER
Diagram 4.27
DIGITAL CLOCK/ TIMER
47
TIMER/CLOCK
Diagram 4.28
221474C
Page 48
Supplied By www.heating spares.co Tel. 0161 620 6677
5 Spare Parts
5.1 Part Identification
The key number in diagram 5.1 and the first column of the list will
help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part number and
the description from the list together with the model name and serial
number information from the data label. The data label is positioned
on the inner case cover, see diagram 1.1.
Because of our constant endeavour for improvement details may
vary slightly from those shown in these instructions.