Supplied By www.heating spares.co Tel. 0161 620 6677
221045A.05.97
Servicing Instructions
To be left with the user
120
G.C. No. 47 313 13
Fanned Flue Combination Boiler
4559
This is a Cat I 2H appliance
Customer Services:
Tel: (01773) 828100
One Contact Total Service
Fax: (01773) 828070
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 G e n e r a l
The instructions consist of three parts, Installation,
Servicing and Instructions for Use which includes the
Guarantee Registration Card. The instructions are an
integral part of the appliance and must, to comply with
the current issue of the Gas Safety (Installation and Use)
Regulations, be handed to the user on completion of the
installation.
CE Mark
This boiler meets the requirements of Statutory
Instrument, No. 3083 The Boiler (Efficiency)
Regulations, and therefore is deemed to meet the
requirements of Directive 92/42/EEC on the efficiency
requirements for new hot water boilers fired with liquid
or gaseous fuels.
Type test for purposes of Regulation 5 certified by:-
Notified body 0087.
Product/production certified:-Notified body 0087.
The CE mark on this appliance shows compliance with:-
1. Directive 90/396/EEC on the approximation of the
Laws of the Member States relating to appliances
burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the
Laws of the Member States relating to electrical
equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the
Laws of the Member States relating to electromagnetic
compatibility.
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of
the boiler it is recommended that it is checked and
serviced as necessary at regular intervals. The frequency
of servicing will depend upon the particular installation
conditions and usage, but in general once a year should
be enough.
COLD WATER
SUPPLY IN
SAFETY
VALVE
DISCHARGE
SLOT (CLOSED)
OUTER CASE SECURING
SCREW (2)
SELECTOR SWITCH
DOOR
OUTER CASE
PLASTIC PLUGS (2)
GAS SERVICE
COCK
HEATING
FLOW
COVER PLATE
HOT WATER
OUT
HEATING
RETURN
SLOT (CLOSED)
DRAIN
POINT
Diagram 1.1
Diagram 1.2
An Aid to Servicing
To obtain a products of combustion reading, make sure
that the main burner is alight. Remove the plastic cap,
see diagram 1.4 and connect the analyser probe to the
tube, replace cap after use.
1.2 Data Label
The data label is positioned on the front of the inner case
cover, see diagram 1.3.
2793
4578
The servicing of this boiler must be carried out by a
competent person in accordance with the rules in force in
the countries of destination.
Unless stated otherwise, parts removed or renewed
during servicing should be fitted in the reverse order
to removal.
After completing any servicing, or renewing of gas
carrying components, ALWAYS test for gas soundness
and carry out functional checks of controls.
Discard all used sealing washers, gaskets and “O” rings
when renewing components.
Use the new ones supplied with the replacement.
2221045A
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
1 G e n e r a l
1.3 Isolation of Boiler
Before commencing any servicing or the replacement of
parts, isolate the boiler from the electrical supply at the
external isolator and close the gas service cock, see
diagram 1.1.
BEFORE DRAINING THE BOILER, REFER TO
SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door
catch is spring loaded, to open, push the side opposite to
the hinge then pull.
Remove the two screws securing the outer case then
unhook the case at the top and pull it forward and off,
see diagram 1.2.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four
screws, see diagram 1.3.
1.6 System Pressures and Draining
WARNING. All parts containing water of the central
heating circuit within the boiler, are under the system
pressure. Before any parts of this circuit are
disconnected, reduce the system pressure at the external
draining tap. Turn the central heating isolating valves
off and drain at the drain points on the appropriate
valves, see diagram 1.1.
SECURING
SCREW (4)
DATA
LABEL
INNER
CASE
COVER
PILOT WINDOW
SCREW (2)
4579
Diagram 1.3
4580
PLASTIC
CAP
All water containing parts of the domestic hot water
circuit of the boiler will be under the supply water
pressure. Before any parts of this circuit are
disconnected, turn the domestic cold water isolating
valve off, open the hot water taps to reduce the water
pressure in the boiler, close the hot water isolating valve
and drain the boiler at the valves, see diagram 1.1.
After replacing any water containing part of the central
heating circuit, make up the water loss, vent all air and
pressurise the system. Refer to “Commissioning” in the
Installation Instructions.
Check for water soundness.
Diagram 1.4
3
221045A
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
2.1 Pilot Check
Check that the pilot flame is burning correctly and of the
correct size, see diagram 2.1. If the pilot flame is not
correct, the pilot injector will require removing, as
detailed later.
2.2 Isolation and Access
Before starting, refer to Section 1.1.
Isolate the boiler from the electrical supply and close the
gas service cock, refer to Section 1.3.
Remove the outer case and the inner case cover, refer to
Sections 1.4 and 1.5.
Disconnect the electrical plug connector and air pressure
tube from the fan, see diagram 2.2.
Follow steps 1 to 4 on diagram 2.2 to remove the
hooks bolts.
Step 1 - Slacken the two thumb screws securing the
collector but do not remove.
Step 2 - Unhook the hook bolts.
Step 3 - Turn the hook bolts.
Step 4 - Remove the hook bolts.
Remove the fan securing screws.
SPARK GAP
4.5mm to 5.5mm
FAN OUTLET
SEAL
FAN
SECURING
SCREWS
FLAME
LENGTH
25mm
Diagram 2.1
PLUG
4574
4581
Pull the fan forwards, at the bottom and rotate to
disengage the fan outlet to flue elbow and rear bracket.
Take care not to damage the seal.
Tilt the fan and withdraw.
Remove the flue collector, note, this may be a tight fit.
Remove the combustion chamber front panel, secured
with four screws, see diagram 2.3.
Slacken, but do not remove the gland seal
securing screw.
Should the pilot burner assembly require servicing, it
will be necessary to disconnect the pilot and
thermocouple nut as this stage, see diagram 2.4.
Remove the pilot burner assembly securing screws
and washers.
When removing the pilot burner assembly, note the pilot
injector is loose and that the electrode and lead are
connected and must not be used to hang the assembly by,
see diagram 2.4.
Remove the main burner from the main injector at the
rear. Raise the burner up and forward, easing the pilot
assembly forward and clear, taking care not to damage
the combustion chamber insulation or pilot burner
assembly, see diagram 2.5.
THUMB
SCREW (2)
FLUE
COLLECTOR
AIR
PRESSURE
TUBE
STEP 1
Slacken do
not remove
STEP 3
STEP 2
STEP 4
4221045A
Diagram 2.2
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
2.3 Heat Exchanger
Place a sheet of paper or similar in the combustion
chamber, to act as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove
paper together with any debris.
2.4 Main Injector
4582
HEAT
EXCHANGER
Inspect the injector and clean as necessary.
Do not use wire or a sharp instrument on the hole.
2.5 Main Burner
Use a vacuum cleaner or suitable brush to clean the
burner thoroughly, making sure that all burner ports are
clear and free from obstructions.
Do not use a brush with metallic bristles.
2.6 Service Checks
Before replacing any parts removed during servicing,
inspect the condition of all seals and joints, renewing
them as necessary.
Check the condition of the combustion
chamber insulation.
Check that the spark gap is as shown in diagram 2.1.
2.7 Note. Reassembly
Make sure that the main burner baffle has located in the
side guides and that the burner is located on the
main injector.
Refit the hook bolts.
The combustion chamber front panel should be fitted
loosely, then the flue collector also fitted loosely, make
sure that it is seated onto the heat exchanger and over the
top edge of the front panel.
SECURING
SCREW (4)
COMBUSTION
CHAMBER FRONT PANEL
SPARK
ELECTRODE
SPARK
ELECTRODE
RETAINING CLIP
PILOT INJECTOR
SECURING
SCREW AND
WASHER (2)
Diagram 2.3
4583
THERMOCOUPLE
NUT
IGNITION
LEAD
To fit the fan, locate it into the rear bracket and ease the
flue elbow onto the fan outlet, making sure that the fan
outlet seal is correctly positioned. Secure with the two
screws, see diagram 2.2.
Refit electrical connector making sure that the red spots
are aligned.
Secure the flue collector and combustion chamber front
panel by tightening the thumb screws and securing
screws, see diagram 2.2 and 2.3.
2.8 Operational Checks
Light the boiler, carry out operational checks and any
necessary adjustments as described in “Commissioning”
in the Installation Instructions.
5
WING NUT
PILOT TUBE
NUT
SEALING GLAND
SECURING SCREW
Diagram 2.4
221045A
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
WING NUT
BURNER
BRACKET
STEP 1STEP 3
45844585
BURNER
WING NUT
BURNER
BRACKET
SECURING
SCREW
4586
BURNER
GUIDE
STEP 2STEP 4
SIDE
GUIDES
MAIN INJECTOR
BURNER
4587
6221045A
Diagram 2.5
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
3.1 Initial Checks
3 F a u l t F i n d i n g
If the boiler fails to operate, first check the following:
1. That the electrical supply is available at the boiler and
the fuses are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE
DAMAGED BY INCORRECT TESTING WITH THE
POWER ON.
2. Make sure that the system pressure gauge registers
0.7bar, minimum and that the automatic air vent works.
Refer to Installation Instructions, Section 11.2.
3. That the gas supply is available at the boiler and
purged of air.
4. Is the pilot burner lit? - If the pilot burner will not
light refer to Section 3.2. If the pilot burner fails to
remain alight, refer to Section 3.3
5. That the boiler is set for the required service.
6. With the boiler central heating selector switched
“Off”, see diagram 3.2 check that the domestic water
supply is available and water flows freely from the hot
taps. Close the taps.
7. With the boiler central heating selector switched
“ON”, see diagram 3.2, check that all heating system
controls, if fitted, are working correctly and calling for
heat. If not isolate the boiler from the electrical supply.
Disconnect the rear multi-pole connector at the base of
the boiler and release the cable from the clamp.
E
N
L
3
CABLE
CLAMP/COVER
SCREW (2)
SWITCH
(OFF)
C.Htg.
SELECTOR
SWITCH
1
2
PIEZO BUTTON
SWITCH
(ON)
CABLE TO
REMOTE
HEATING
CONTROLS
MAINS
CABLE
CABLE
CLAMP
Diagram 3.1
GAS CONTROL KNOB
CLOCK/TIMER
(IF FITTED)
2883
Remove the connector cover and dependent on the type
of control fitted test for continuity, mains or low voltage
at terminals 1 and 2, see diagram 3.1.
If this is satisfactory continue with the detailed
fault finding.
PRESSURE
GAUGE
Orange Light
‘MAINS’
Green Light
‘RUNNING’
Red Light
LOW C.Htg.
WATER
PRESSURE
Diagram 3.2
7
221045A
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
PILOT WILL NOT LIGHT
START HERE
3 F a u l t F i n d i n g
Check gas line - open all cocks,
rectify any blockages, purge out
any air. Does pilot light?
NO
Apply match to pilot burner instead
of pressing piezo unit button.
Does pilot light?
NO
Undo tubing nut at pilot burner.
Press multifunctional control knob.
Does gas flow freely?
NO
Rectify blockage in pilot injector,
or renew pilot injector.
NO
Undo tubing nut at pilot outlet of
mulitfunctional control.
Press multifunctional control knob.
Does gas flow freely?
NO
YES
YES
YES
YES
Does pilot stay alight when
multi-functional control knob
is released?
NO
PILOT SATISFACTORY
Does pilot flame
envelope thermocouple?
NO
Check aeration. If necessary clean pilot, rectify blockage in pilot
injector, or replace.
Check thermocouple circuit using
thermocouple and boiler overheat
cut-off fault finding.
YES
YES
Change blocked pilot tube.
NO
Change multifunctional control.
On pressing piezo unit button is
there a spark across electrode gap?
NO
Remove electrode from pilot bracket.
Hold tip close to pilot burner and
operate piezo unit.
Is there a spark across gap?
NO
Pull ignition lead off piezo unit.
Using blade of an insulated screwdriver, touch unit chassis and leave
approx. 4mm gap from connection
tag on piezo unit. Operate piezo.
Is there a spark across gap?
NO
Change
piezo unit.
YES
YES
YES
Change electrode
assembly.
8221045A
Check electrode gap. Reposition,
or replace electrode as necessary.
Diagram 3.3
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
With the boiler cold, check connections of the thermocouple, boiler overheat cut-off and multifunctional
control. Disconnect overheat cutoff connectors at points A and B at the multifunctional control,
see diagram 3.5. Test continuity of the overheat cutoff. Is there continuity?
YES
Re-connect boiler overheat cutoff to points
A and B. Disconnect thermocouple at point
D of the mulitfunctional control. Test continuity
between point C and the body of the multifunctional control. Is there continuity?
NO
YES
Faulty boiler overheat cutoff, renew.
Faulty cutoff connectors into
multifunctional control, either at A or
C. Renew where faulty.
NO
Test continuity of thermocouple between inner
connection point D and point E.
Is there continuity?
YES
Thermocouple and boiler overheat
circuit satisfactory.
3.2 Pilot Burner and Ignition System
Symptom: The pilot burner will not light or stay alight.
Test the pilot burner and ignition system as shown in
diagram 3.3.
3.3 Thermocouple and Overheat Cutoff
Symptom: The pilot burner fails to stay alight.
On completion of initial checks, as Section 3.1.
Test the thermocouple, overheat cutoff and thermocouple
connectors, as described in Fault Finding diagram 3.4
and shown in diagram 3.5.
NO
Faulty thermocouple, renew.
CONNECTION
'A'
CONNECTION 'E'
MULTIFUNCTIONAL
CONTROL
Diagram 3.4
4588
Check the millivoltage of the thermocouple closed
circuit at points “A” and “E”, this should be within the
range of 6 to 11mV, see diagram 3.5.
BOILER
OVERHEAT CUTOFF
9
CONNECTION
'D'
CONNECTION
'C'
CONNECTION
'B'
Diagram 3.5
221045A
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
3.4 Clock/Timer - if fitted
If the clock has failed it can be bypassed by
disconnecting the plug at the wall frame.
Disconnect the plug at the control box and connect this
plug to the connection at the wall frame.
This is a temporary measure and the clock should be
repaired or replaced as soon as possible.
3.5 Electrical
Preliminary electrical system checks, as outlined in a
Multimeter Instruction book, are the first checks to be
carried out during a fault finding procedure.
Isolate the boiler from the electrical supply, refer to
Section 1.3.
Gain access to the boiler controls by removing the outer
case, refer to Section 1.4. Check that all cables and
connectors are secure.
Gain access to the control board, refer to Section 4.13.
Check all cables at the multi-pin connectors on
the board.
PERMANENT
LIVE
240V~50Hz
(L)
OPTIONAL
SWITCHED LIVE
FROM ROOM
STAT. 240V~50Hz
(N)
M
(L)
ON
COMMON
CLOCK/TIMER
0192M
br
b
br
p
p
Test the two fuses on the main control board and renew
as necessary, the fuse are, type 2AT and type 3.15AT.
If a fuse fails repeatedly or the initial fault finding
checks described in Section 3.1 indicate a boiler fault,
check the boiler electrical circuits and follow the fault
finding procedures, see diagram 3.5, 3.6, 3.7 and 3.8
and for clock/timer fault diagram 3.9.
On completion of a fault finding task that has required
the disconnection and making of electrical connections
then checks, for earth continuity, polarity and resistance
to earth must be carried out.
KEY
PUMP
br
(N)
b
br
LN
33
2A
2
b
FUSE 1
2
4
br........................BROWN
b.........................BLUE
p.........................PURPLE
CONTROL BOARD
2
TERMINALS, CN 2
CONTROL BOARD
3
TERMINALS, CN 3
CONTROL BOARD
4
TERMINALS, CN 4
TRANSFORMER
LOW
VOLT.
26V~
10221045A
b
240V~
2
CONTROL BOARD
br
2
Diagram 3.6
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
MAIN MULTIFUNCTIONAL CONTROL SOLENOID
DHW CUT OFF
CONTROL
C
N/C
N/O
WATER PRESSURE
w
SWITCH
(SHOWN IN
PRESSURISED
STATE)
DHW
FLOW
SELECTOR
SWITCH
w
CH
THERMISTOR
USER
CONTROL
BOARD
THERMISTOR
DHW
r
LN
TRANSFORMER
TO REMOTE
HEATING
CONTROL
SWITCH
p
p
bk
y
240V~
26V~
p
p
5 WAY PLUG/SOCKET
r
r
or
or
p
p
1
0195M
1
1
1
bk
r
1
1
4
4
4
4
br
br
4
4
4
4
4
4
AIR PRESSURE
D.C.
FAN
Diagram 3.7
N/C
C
N/O
SWITCH
1
FAN DRIVER
P.C.B.
2 2 2 2 22 2 2
1
1
1
p g y b gry w rScreen
gry
p
y
or
KEY
br
bk
b
g
gry
or
p
r
v
w
y
- Brown
- Black
- Blue
- Green
- Grey
- Orange
- Purple
- Red
- Violet
- White
- Yellow
v
r
gry
gry
p
or
y
MAIN PCBFAN DRIVER PCB
CN 1
1
CN 4
4
CN 5
5
CN 6
6
CN 7
7
1
2
5
5
5
5
6
6
6
7
7
7
7
CONTROL
BOARD
CN 1
CN 2
11
221045A
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
Carry out the initial fault finding checks described in Section 3.1.
Check that gas, water and electricity are available at the boiler.
Before commencing tests isolate the boiler, make sure that the remote controls are not calling for duty and there
is no domestic hot water demand.
Remove the outer case, control housing and it's cover.
Check all connections on the control board and the boiler components, rectify or renew as necessary.
Two dummy two way connectors are provided for ease of testing continuity.
Remove fuses and test for continuity, if faulty, check cables and connections for shorting to E or N, rectify if
necessary and replace fuse, with spare provided.
Check central heating water pressure, repressurize if necessary.
Make sure boiler is cold. Check all pipes and connections between the Air Pressure Switch (APS) fan and
combustion sample point, also between fan and gas/air ratio unit. Make sure sample point cap is fitted correctly.
Make sure the pilot is alight. Make sure venturi is not blocked.
Isolate supply
remove CN6 is
there continuity
between
Red and Violet?
NO
Faulty APS.
Replace.
YES
YES
Replace CN6.
With no demand to the boiler.
Restore power.
Does the mains Orange LED
come on?
Does the boiler light?
Does fan run at full
speed for approx
30 seconds?
Isolate supply.
Restore supply.
During the 30 second is
there approx 26V ac on
Black and Red from the
transformer at CN1?
YES
NO
NO
YES
YES
NO
NO
Is there 240V ac at
Blue and Brown on CN3.
YES
Faulty LED.
Does not effect
boiler operation.
Isolate supply, is there
continuity at flow switch?
NO
Faulty main PCB.
Replace.
Faulty transformer.
Replace.
NO
Check electricity
supply.
YES
Faulty flow switch.
Replace.
continued
(a)
Is there 26V ac on
Orange and Yellow at
CN7 and greater than 3V
dc on Grey and Purple?
YES
Isolate supply. Is the
resistance at CN2 on the
fan driver pcb between
White and Grey, Grey
and Purple, Purple and
White approx 2.5Ω ?
YES
Is there continuity at CN2
on the fan driver pcb
between White and the
fan motor laminations?
(repeat with Grey and
Purple)
NO
NO
YES
NO
Faulty main PCB.
Replace.
Faulty fan.
Replace.
Faulty fan.
Replace.
Faulty fan driver
pcb. Replace.
Diagram 3.8
12221045A
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
YES
(a)
3 F a u l t F i n d i n g
After about 30 seconds from
“switch on” does fan go to low
speed?
YES
Isolate supply. Restore
supply with no demand.
Is there 24Vac between
grey wire on CN6 and Pin 2
on CN1 for about 30
seconds.
YES
Isolate supply.
Reconnect CN6,
restore power supply.
YES
Does pump run for
about 30 seconds?
YES
NO
NO
NO
Isolate supply disconnect central heating thermistor,
is resistance of thermistor between 8KΩ and 11KΩ?
NOYES
Faulty thermistor.
Replace.
Faulty APS.
Replace.
During the 30
second period is
there 240V at pump.
YES
NO
Faulty main PCB.
Replace.
Faulty main PCB.
Replace.
After about 30 seconds
does pump go off?
YES
Open DHW tap at full
rate. Does burner
pressure go to 13.1mb?
YES
NO
NO
Faulty pump.
Replace.
Faulty main PCB.
Replace.
Is the burner
pressure between
0.1 and 13.1 mb ?
Does green
demand light
come on?
YES
NO
NO
YES
Check venturi air
signal at test point
Is this approx 2.5mb
YES
Faulty fan.
Replace.
Faulty gas/air ratio
unit. Replace.
NO
continued
(a)
continued
(b)
13
continued
(c)
Diagram 3.8 cont.
221045A
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
YES
(a)
(b)
YES
Restore supply.
Is there about 24V
ac multifunctional
control?
YES
NOYES
(c)
Isolate supply disconnect Red in line connectors to
flow switch, is there continuity across flow switch?
YES
Reconnect flow switch,
disconnect Purple in line
connectors to DHW thermistor.
Is the resistance between
8KΩ and 11KΩ?
YES
Faulty LED.
Does not
effect boiler
operation.
NO
Faulty DHW thermistor.
Replace.
Isolate supply, remove
CN1. Is there continuity
across DHW O/H stat?
NO
YES
Faulty flow switch.
Replace.
NO
NO
Turn the DHW flow off.
Turn on the CH.
Does pump run?
NO
Faulty main PCB.
Replace.
YES
Is burner pressure
about 5.6mb?
SYSTEM O.K.
NO
YES
Faulty
multifunctional
control.
Is there continuity across
C and N/O at low water
pressure switch?
YES
Faulty main PCB.
Replace.
Faulty DHW O/H stat.
Replace.
NO
Faulty water
pressure switch.
Replace.
14221045A
Diagram 3.8 cont.
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
If a mains potential room thermostat is connected, ensure that the switch live is connected to PIN 1 in the
5 pole connector.
Check continuity of clock/timer harness, ensure an electrical supply is available, ensure that remote
controls are calling for heat.
Isolate the boiler from electrical supply, remove outer case.
YES
Switch on electrical supply, is there a display
on clock/timer?
YES
Disconnect and insulate the purple cables
from heating common and heating on.
YES
Advance clock/timer until a demand is indicated
Is there now continuity between heating
common and heating on?
YES
Clock/timer in order if no central heating,
refer to main fault finding.
NO
NO
Faulty clock/timer.
Replace.
Faulty clock/timer.
Replace.
DIGITAL CLOCK/TIMER STYLE 1 and 2 FAULT FINDING
CLOCK FAULT FINDING
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1 in
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remote
controls are calling for heat.
Make sure the override switch if fitted is in the " " position
Does clock keep time
No
Faulty clock
replace
Yes
No
Isolate electrical supply set clock to on period
Is there continuity across
common and heating on
Clock in order if no
central heating refer to
Yes
Set clock to off period. Is there continuity
across common and heating on
No
main fault finding
ELECTRO/MECHANICAL CLOCK/TIMER FAULT FINDING
Diagram 3.9
5667
Yes
Diagram 3.9
15
221045A
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
Before replacing any part please read points below:Replacement of parts must only be carried out by a
competent person.
Unless stated otherwise all parts are refitted in the
reverse order to removal.
1. Refer to Section 1.1.
CLOCK/TIMER
(if fitted)
4589
2. Always isolate the boiler from the electrical and as
required the gas supply as Section 1.3.
3. Unless stated otherwise, gain access as appropriate
parts of Sections 1.4 and 1.5.
4. On completion, make good any water loss and
pressurise the system to initial design pressure, refer to
“Commissioning” in the Installation Instructions.
If the red light “flashes”, momentarily interrupt the
electrical supply.
4.1 Fan
Refer to the appropriate parts of Section 2.2.
After fan has been fitted, check the burner pressure and
if necessary adjust.
4.2 Main Burner
Refer to the appropriate parts of Section 2.2.
Note. There is no need to remove the fan or flue
collector assemblies.
CONTROL
HOUSING
SECURING
SCREW (2)
SUPPORT
BRACKET
FAN DRIVER
CONTROL
HOUSING)
TOP CONTROL
HOUSING COVER
BOTTOM CONTROL
HOUSING COVER
4.3 Main Injector
Refer to the appropriate parts of Section 2.2.
Note. There is no need to remove the fan or the flue
collector assemblies.
4.4 Pilot Burner/Injector
Refer to the appropriate parts of Section 2.2
Note. There is no need to remove the fan or flue
collector assemblies.
4.5 Spark Electrode/Ignition Lead
Refer to the appropriate parts of Section 2.2.
Note. There is no need to remove the fan or flue
collector assemblies.
Remove the controls housing assembly and support, see
diagram 4.1.
If this is not possible place on a surface, making sure that
the control knob is protected.
Remove the spark electrode/ignition lead from the pilot
burner assembly, see diagram 2.4.
SCREW(2)
CLOCK/TIMER
(if fitted)
Diagram 4.1
Disconnect the ignition lead from the piezo unit, refer to
Section 4.11.
16221045A
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.6 Thermocouple
Remove the sealing gland, secured with a single screw,
see diagram 2.4.
Remove the spark electrode/lead, see diagram 2.4.
Disconnect the thermocouple at both ends, see diagram
2.4 and 4.2.
Remove the thermocouple.
Do not tighten the thermocouple nut more than a quarter
turn beyond finger tight or make any sharp bends in the
capillary.
4.7 Boiler Overheat Cutoff
Remove the control housing as the appropriate part of
Section 4.1.
Remove piezo unit bracket, disconnect lead, see
diagram 4.3.
Disconnect the boiler overheat cutoff electrical
connectors from the multifunctional control, see
diagram 4.2.
Remove the boiler overheat cutoff, secured with two
screws, see diagram 4.2.
SECURING
SCREW (2)
OVERHEAT
CUTOFF
CONNECTORS
ELECTRICAL
CONNECTORS
THERMOCOUPLE NUT
4591
Use the heat sink compound supplied, between the
mounting plate and the cutoff, when fitting it.
4.8 Water Pressure Switch
Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6.
Disconnect the electrical connectors at the water pressure
microswitch, see diagram 4.4.
Remove pressure switch.
Replace the “O” ring seal with the new seal provided.
Make sure that the switch terminals are facing diagonally
forwards to give access, as shown in diagram 4.4.
Reconnect the electrical connections, refer to
diagram 4.11.
PIEZO UNIT
BRACKET
IGNITION
LEAD
PIEZO
UNIT
SECURING
SCREW (2)
SELECTOR SWITCH
Diagram 4.2
2848
Diagram 4.3
4592
17
WATER
PRESSURE
SWITCH
Diagram 4.4
221045A
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.9 Pump
Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6.
Disconnect the electrical connectors at the water pressure
microswitch. Remove the water pressure switch, refer to
Section 4.8.
Remove the terminal cover from the pump and
disconnect the cable, see diagram 4.5.
Disconnect the pump at the unions.
Discard the sealing washers.
PUMP
SPINDLE
4593
PUMP
ADJUSTER
TERMINAL COVER
SCREW
FLOW DIRECTION
ARROW
Make sure that the flow direction arrow is pointing
upward when fitting and use the new sealing washers.
Refit water pressure switch, refer to Section 4.8.
The flow adjuster on the new pump should be set to that
of the original, refer also to Section 4.6 in the
Installation Instructions.
The flow rate should be controlled by means of a valve
in the heating flow, refer to Section 11.10 in the
Installation Instructions.
Note: Should the pump fail to operate, refer to diagram
3.8. If all is in order, but the pump still does not operate,
remove the end screw, see diagram 4.5, then turn the
pump spindle to release any temporary seizure.
DO NOT HIT THE SPINDLE.
4.10 Domestic Hot Water High Limit Control
Remove the pump, see Section 4.9.
Disconnect the electrical connectors at the domestic hot
water high limit control, see diagram 4.6.
Remove the high limit control from the flow pipe,
secured with two screws.
END
SCREW
D.H.W. HIGH LIMIT CONTROL
UPPER
PUMP
UNION
LOWER
PUMP
UNION
Diagram 4.5
4594
Use the heat sink compound supplied, between the
mounting plate and the control.
When refitting the electrical connections to the high limit
control the polarity is not important, see diagram 4.11.
4.11 Piezo Unit
Remove the piezo unit bracket, see diagram 4.3.
Disconnect the ignition lead at the piezo unit.
Remove the piezo unit from the bracket.
D.H.W.
ELECTRICAL
CONNECTORS
SECURING
SCREW (2)
18221045A
HIGH
LIMIT
CONTROL
Diagram 4.6
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.12 Pressure Gauge
Remove the control housing assembly, see diagram 4.1.
Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge bracket.
Disconnect the pressure gauge connection from the
safety valve, discard the washer, see diagram 4.7.
Remove the pressure gauge secured with the
retaining tabs.
Locate the supplied new washer under the pressure
gauge connection when refitting the safety valve.
4.13 Control Boards
CAUTION. Great care must be taken when handling
any control board.
THE MAIN CONTROL BOARD MUST BE KEPT IN
THE ANTI STATIC HOLDER UNTIL NEEDED.
Note. Timer/clock may be removed to improve access,
see Section 4.32 or the control housing bottom half can
be removed.
Main Control Board
Remove control housing cover securing screw, see
diagram 4.8.
Remove the control housing assembly as shown in
diagram 4.1.
Lift the control housing cover to gain access to
the board.
SAFETY
VALVE
SEALING
WASHER
PRESSURE
GAUGE
CONNECTION
SECURING
SCREW (2)
PRESSURE GAUGE
FASCIA
CONTROL
HOUSING
SECURING
SCREW (2)
FASCIA
SECURING
SCREW (3)
HINGE PIN
PRESSURE
GAUGE
BRACKET
Diagram 4.7
TEMPERATURE
CONTROL KNOB
CONTROL
HOUSING
COVER
SECURING
SCREW
CONTROL
HOUSING
COVER
2831
4595
Disconnect all multipin connectors, see diagram 4.8.
Remove the control board from the support posts.
To reconnect the multipin connectors correctly, see
diagram 4.11.
When replacing the main control board check and if
necessary adjust the main burner gas pressure in both the
domestic hot water and central heating modes. Refer to
“Commissioning” in the Installation Instructions.
Fan Driver Board
Remove the fan driver control housing assembly
securing screws.
Remove the multipin connectors, see diagram 4.9.
Release the board from its support posts then remove the
nut and screw securing the board to the cover, see
diagram 4.9.
User Control Board
Remove the fascia, see diagram 4.8.
Remove the multipin connector.
TRANSFORMER
MULTI-PIN
CONNECTORS
USER CONTROL
BOARD
SUPPORT POSTS
Diagram 4.8
Remove the control board from the supports posts.
19
221045A
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
p
4.14 Transformer
Note. Timer/clock may be removed to improve access,
see Section 4.32 or the control housing bottom half can
be removed.
Remove the control housing cover screw, see
diagram 4.8.
Remove control housing assembly, see diagram 4.1.
Remove the control housing cover and disconnect the
electrical connectors from the transformer, see
diagram 4.8.
Remove the transformer securing screws (2 off) from
beneath the control housing, remove the transformer and
insulation.
To connect the transformer cables correctly, refer to
diagram 4.11.
FAN DRIVER
BOARD
SUPPORT
POSTS
FAN DRIVER
CONTROL
HOUSING
SECURING
SCREW NUT
MULTI-PIN
CONNECTORS
Diagram 4.9
4596
p
r
g/y
KEY
p
PURPLE
r
RED
b
BLUE
br
BROWN
g/y
GREEN/YELLOW
240V~50Hz PERMANENT
MAINS SUPPLIED
FUSED AT 3A
br
b
g/y
p
r
Diagram 4.10
b
br
CLOCK/
TIMER
br
b
br
p
COMMON
b
(L)
(N)
HEATING ON
4774
20221045A
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
y+or 26Volts ac
gry+p 3 Volts dc
CN7
AIR
PRESSURE
SWITCH
✽ 230V-50Hz
PERMANENT MAINS
SUPPLY FUSED AT 3A
12NL
p p g/y b br
NO
gry
r
CENTRAL HEATING
SELECTOR
SWITCH
DC
FAN
C
NC
v
THERMISTOR
CH
PUMP
DHW
FLOW
SWITCH
screenedscreened
r
w
gry
b
y
g
p
THERMISTOR
DHW
WATER
PRESSURE
SWITCH
gry
MULTI-FUNCTIONAL
CONTROL
C
NO
w
b
y
g
p
NC
r
FAN
DRIVER
BOARD
or ypgry
r
0205M
g/y
or yp gryw
r
L
N
CN3
p
p
r
r
br
br
or
or
p
p
gry
p
y
or
TRANSFORMER
bbr
MAINS
bbr
FUSE 2AT
KEY:
CN4
w
b
bk
br
g/y
gry
or
v
r
y
p
CN5
MAIN CONTROL BOARD
bk
NLNL
230V~
TXR
- WHITE
- BLUE
- BLACK
- BROWN
- GREEN/YELLOW
- GREY
- ORANGE
- VIOLET
- RED
- YELLOW
- PURPLE
bbr
CN7
FUSE
3.15AT
CN1
rv
CNCNO
gry
p
y
or
p
p
bk
y
bk
r
DHW
HIGH LIMIT
CONTROL
gry
CN6
g/y
g/y
ww
21
USER CONTROL
BOARD
CHASSIS
EARTH
Diagram 4.11
221045A
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.15 Multifunctional Control and Gas/Air
Ratio Unit Assembly: diagram 4.12
Remove control housing, see diagram 4.1.
Remove the piezo bracket, see diagram 4.3.
Disconnect the two electrical connectors at the front of
the multifunctional control.
Disconnect the boiler overheat cutoff connectors.
Disconnect the thermocouple nut at the
multifunctional control.
Disconnect the pilot supply tube at the
multifunctional control.
Disconnect the gas/air ratio unit tubes at the
bulkhead connectors.
Remove the four, right hand, extended hexagon screws
from the multifunctional control.
Break the gas connection at the wall frame.
Remove the multifunctional control valve and gas/air
ratio unit assembly, taking care not to damage the tubes.
Multifunctional Control
Remove the four, left hand, extended hexagon screws
from the multifunctional control.
GAS/AIR
RATIO UNIT
TUBE NUTS
ELECTRICAL
CONNECTORS
HEXAGON
SCREWS (4)
BOILER
OVERHEAT
CUTOFF
CONNECTOR
BOILER
OVERHEAT
CUTOFF
CONNECTOR
GAS
CONNECTION
MULTIFUNCTIONAL
CONTROL
4597
HEXAGON
SCREWS
(4)
PILOT
SUPPLY
TUBE
THERMOCOUPLE
NUT
'O' RING
Discard the “O” rings and fit the new ones, supplied.
Check and adjust the main burner gas pressure in both
the domestic hot water and central heating modes, refer
to “Commissioning” in the Installation Instructions.
Gas/Air Ratio Unit Assembly
Disconnect the gas/air ratio unit sensing tubes.
Remove the two securing screws, see diagram 4.12.
4.16 Central Heating Selector Switch
Slacken the piezo bracket securing screws and remove
the bracket from the keyhole slots, see diagram 4.3.
Pull the leads from the switch.
To remove the switch press in the tabs on each side.
The polarity of the electrical connections is not
important.
'O' RING
VENTURI AIR
SIGNAL TEST
POINT
SCREW (2)
GAS/AIR
RATIO UNIT
SENSING
TUBE NUTS
22221045A
GAS/AIR
RATIO UNIT
Diagram 4.12
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.17 Domestic Hot Water Flow Switch
The replacement of this part can be done within the
limits of “minimum clearances”. Should there be a side
clearance of 150mm or more then the multifunctional
control/air ratio unit assembly need not be removed.
Isolate the domestic hot water inlet and drain, refer to
Sections 1.3 and 1.6.
When replacing the flow switch it is recommended that
the water inlet filter is cleaned or renewed.
When replacing the flow switch make sure that it is
correctly positioned, with the flow direction arrow
pointing upward.
Remove the burner as Section 2.2.
Remove the multifunctional control and air/ratio
assembly as described in Section 4.15.
Disconnect the front sensing tube.
Disconnect the flow switch connectors, see
diagram 4.13.
Remove the locknut from the flow switch and lower the
domestic hot water inlet pipe assembly, including flow
switch, from the base of the main panel.
FLOW
SWITCH
FILTER
UNION
NUT
ELECTRICAL
CONNECTORS
UNION NUTS
GAS/AIR RATIO
SENSING TUBE
4599
WATER INLET
PIPE ASSEMBLY
Disconnect the filter union nut.
ISOLATING
VALVE
CENTRAL
HEATING
THERMISTOR
UNION
NUT
Diagram 4.13
4598
23
'O' RING
ELECTRICAL
CONNECTORS
D.H.W.
THERMISTOR
'O' RING
Diagram 4.14
221045A
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.18 Thermistor - Heating
Release the water pressure and drain the heating circuit
of the boiler, refer to Sections 1.3 and 1.6.
Gain access by removing the piezo bracket, see
diagram 4.3.
Disconnect the cables from the thermistor, see
diagram 4.14.
Remove the thermistor, complete with its “O” ring.
The polarity of the electrical connections is
not important.
4.19 Thermistor - Domestic Hot Water
The replacement of this part can be done within the
limits of the minimum clearances. Should there be a
side clearance of 150mm or more then the pump need
not be removed.
Remove the pump, refer to Section 4.9.
Release the water pressure and drain the domestic hot
water circuit of the boiler, refer to Section 1.3. and 1.6.
Disconnect the cables from the thermistor, see
diagram 4.14.
Remove the thermistor complete with its “O” ring.
The polarity of the electrical connections is not
important.
SAFETY
VALVE
PRESSURE
GAUGE
CONNECTION
CAP NUT
SEALING
WASHER
THROTTLE
ADJUSTER
DISCHARGE
PIPE
UNION
NUT
Diagram 4.15
2794
46004601
4.20 Safety Valve
Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.12.
Disconnect the union nuts to release the safety valve, see
diagram 4.15.
4.21 Water Inlet Filter
Refer to the appropriate parts of Section 4.17.
4.22 Domestic Hot Water Throttle
Release the water pressure and drain the domestic hot
water circuit of the boiler, refer to Section 1.3 and 1.6.
Refer to Section 4.17 to gain access to the throttle.
Remove the cap nut and carefully remove the throttle
adjuster, by unscrewing, it may be necessary to push the
throttle adjuster out from the rear, see diagram 4.16.
Clean if necessary, taking care not to damage the
throttle body.
‘O’ RING
Diagram 4.16
MINI EXPANSION
VESSEL
SEALING
WASHER
Diagram 4.17
Reset the domestic hot water flow rate refer to Section
11.7 in the Installation Instructions.
24221045A
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.23 Mini Expansion Vessel
Release the water pressure and drain the domestic hot
water circuit at the boiler, refer to Sections 1.3 and 1.6
Remove the control housing as Section 4.1.
Note. It may be possible, in some circumstance, to
remove the mini expansion vessel by hand.
Remove the multifunctional control, refer to
Section 4.15.
When refitting use the new sealing washer supplied, see
diagram 4.17.
4.24 Automatic Air Vent
Release the water pressure and drain the central heating
circuit of the boiler, refer to Sections 1.2 and 1.6.
Remove the automatic air vent, see diagram 4.18.
SLACKEN THE SMALL CAP ON THE AIR VENT.
THIS MUST NOT BE RETIGHTENED.
LOCATION
SLOT
CAP
SEALING
WASHER
4602
AUTOMATIC
AIR VENT
When refitting use the new washer supplied.
4.25 Heat Exchanger
Release the water pressure and drain the central heating
and domestic hot water circuits refer to Section 1.3
and 1.6.
Remove the fan from the flue collector, refer to
Section 2.2.
Remove the flue collector, refer to Section 2.2.
Remove the main burner, refer to Section 2.2.
Remove the automatic air vent, refer to Section 4.24.
If renewing the heat exchanger, transfer the air vent,
using the new sealing washers provided.
Disconnect the front gas/air ratio sensing tube, see
diagram 4.18. Make sure that no water enters the tube.
Disconnect the union nuts of the heat exchanger to
remove it, see diagram 4.18.
Reassembly Notes.
Locate the raised location tabs on the combustion
chamber sides into the slots on the heat exchanger, see
diagram 4.18.
UNION
NUTS
UNION
NUTS
GAS/AIR RATIO
SENSING TUBE
Diagram 4.18
Make sure that the main burner baffle has located in the
side guides and that the burner is located on the main
injector.
The combustion chamber front panel should be fitted
loosely, then the flue collector also fitted loosely, make
sure that it is seated correctly on the heat exchanger and
over the top edge of the front panel.
25
221045A
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
SECURING
SCREW (4)
COMBUSTION CHAMBER
FRONT PANEL
Diagram 4.19
4.26 Combustion Chamber Insulation
Remove the combustion chamber front panel secured
with four screws, see diagram 4.19.
Remove the front insulation, secured with a clip, see
diagram 4.20.
4603
COMBUSTION
CHAMBER
FRONT PANEL
CLIP
FRONT
INSULATION
4604
Slide out both side insulation pieces.
Remove the burner as in Section 2.2.
Pull the lower rear insulation forward, then slide the
upper rear insulation down from behind the heat
exchanger, see diagram 4.20.
SIDE INSULATION PIECES
LOWER REAR INSULATION
26221045A
UPPER REAR INSULATION
Diagram 4.20
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.27 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be
removed from the wall. As an alternative, a separate
expansion vessel of the same specification may be
connected as close as possible to the boiler, leaving the
original in position, refer to Section 4.5 in the
Installation Instructions.
Release the water pressure and drain the central heating
and domestic water circuits, refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to
Section 2.2.
Remove the flue elbow, refer to Section 10 of the
Installation Instructions.
Disconnect the boiler water connection union nuts at the
front of the isolating valves, see diagram 1.1.
Disconnect the gas service cock union.
Disconnect the safety valve discharge pipe from the
boiler, see diagram 1.1.
4605
SECURING (2)
LOCATION
CLIPS
Separate the two parts of the boiler multi-pole
electrical connector.
Slacken the clips of the gas service cock and the water
isolating valves.
Remove the boiler from the mounting frame, secured
with two screws at the top, see diagram 4.21. Pull the
boiler from the isolating valves. Unhook the boiler at
the top and lift off.
Carefully lay the boiler down on its side for access to the
expansion vessel.
Disconnect the union nut connection, see diagram 4.22
and discard the sealing washer.
Remove the expansion vessel, secured with three
clamping screws.
Connect the union nut, when fitting the expansion vessel,
before clamping it.
CLIP
(5)
UNIONS (5)
UNION NUT
CONNECTION AND
SEALING WASHER
Diagram 4.21
2861
27
CLAMPING SCREW (3)
Diagram 4.22
221045A
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
FRAME
GLASS
SECURING
SCREW (2)
GASKET
Diagram 4.23
4.28 Pilot Viewing Window
Remove the pilot viewing window, secured with two
screws. When fitting a new window use the gasket
provided, see diagram 4.23.
4.29 Inner Cover Case Seal
Remove the old seal, clean out the old adhesive.
Glue the new seal into place, make sure that there are no
breaks in it.
4.30 Air Pressure Switch
Remove the flue collector, refer to Section 2.2.
4606
CLEAR
GREY
AIR
PRESSURE
TUBES
4607
SCREWS (2)
AIR PRESSURE
SWITCH
VIOLET
ELECTRICAL
CONNECTORS
RED
RED
Diagram 4.24
Disconnect the three electrical connectors at the air
pressure switch, see diagram 4.24. Remove the flexible
tubes from the switch. Remove the air pressure switch,
secured with two screws.
When replacing the tubes to the air pressure switch make
sure that the forward (clear) tube from the air pressure
switch connects to the tee on the incoming air
sensing tube.
The rear most (coloured) tube connects to the fan
pressure sensing tube.
When reconnecting the electrical cables refer to
diagram 4.11.
4.31 Air/Gas Ratio Sensing Venturi
Remove the fan assembly and flue collector, refer to
Section 2.2.
Disconnect the tube nut and screw to release the sensing
venturi, see diagram 4.25.
4608
SCREW
VENTURI
TUBE
NUT
Diagram 4.25
28221045A
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
CLOCK/TIMER
SECURING
SCREWS (2)
ELECTRICAL
CONNECTIONS
pp
br
4609
SECURING CLIP (2)
4777
MOUNTING
BRACKET
SPACER
TIMER/CLOCK
b
KEY
br BROWN
b BLUE
p PURPLE
MAINS
NEUTRAL (N)
MAINS
LIVE (L)
HEATING ON
RETAINING
TABS (4)
DIGITAL CLOCK/TIMER STYLE 1
ILLUSTRATED
COMMON
Diagram 4.26
4.32 Clock/Timer - if fitted
Digital clock/timer - Style 1 - Release the mounting
bracket securing screws, see diagram 4.26.
Disconnect the electrical cables, squeeze the retaining
tabs to release the clock/timer, see diagram 4.26.
Electro/mechanical and Digital clock/timer - Style 2 Release the mounting bracket securing screws, see
diagram 4.26.
Disconnect electrical cables, release securing clip to
remove the clock/timer and spacer, see diagram 4.27.
ELECTRO/MECHANICAL and
DIGITAL CLOCK/ TIMER
STYLE 2 ILLUSTRATED
Diagram 4.27
29
221045A
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
5 S p a r e P a r t s
5.1 Part Identification
The key number in diagram 5.1 and the first column of
the list will help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part
number and the description from the list together with
the model name and serial number information from the
data label. The data label is positioned on the inner case
cover, see diagram 1.3.
Supplied By www.heating spares.co Tel. 0161 620 6677
5 S p a r e P a r t s
4610
15
3
4
5
6
26
8
7
12
14
1
16
21
24
19
11
17A
20
17B
2
10
18
22
23
13
31
9
Diagram 5.1
221045A
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide
information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are
usual only if the material is broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your
hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Because of our constant endeavour for improvement details may vary slightly from those in the instructions.
32221045A
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.