Glow-worm SwiftFlow 120 Servicing Instructions

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
221045A.05.97
Servicing Instructions
To be left with the user
120
G.C. No. 47 313 13
Fanned Flue Combination Boiler
4559
This is a Cat I 2H appliance
Customer Services: Tel: (01773) 828100
One Contact Total Service
Fax: (01773) 828070
Hepworth Heating Ltd.,
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 G e n e r a l
The instructions consist of three parts, Installation, Servicing and Instructions for Use which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
CE Mark
This boiler meets the requirements of Statutory Instrument, No. 3083 The Boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by:-
Notified body 0087. Product/production certified:- Notified body 0087. The CE mark on this appliance shows compliance with:-
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
1.1 Servicing or Replacing Parts
To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
COLD WATER SUPPLY IN
SAFETY VALVE DISCHARGE
SLOT (CLOSED)
OUTER CASE SECURING SCREW (2)
SELECTOR SWITCH
DOOR
OUTER CASE
PLASTIC PLUGS (2)
GAS SERVICE COCK
HEATING FLOW
COVER PLATE
HOT WATER OUT
HEATING RETURN
SLOT (CLOSED)
DRAIN POINT
Diagram 1.1
Diagram 1.2
An Aid to Servicing
To obtain a products of combustion reading, make sure that the main burner is alight. Remove the plastic cap, see diagram 1.4 and connect the analyser probe to the tube, replace cap after use.
1.2 Data Label
The data label is positioned on the front of the inner case cover, see diagram 1.3.
2793
4578
The servicing of this boiler must be carried out by a competent person in accordance with the rules in force in the countries of destination.
Unless stated otherwise, parts removed or renewed during servicing should be fitted in the reverse order to removal.
After completing any servicing, or renewing of gas carrying components, ALWAYS test for gas soundness and carry out functional checks of controls.
Discard all used sealing washers, gaskets and “O” rings when renewing components.
Use the new ones supplied with the replacement.
2221045A
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
1 G e n e r a l
1.3 Isolation of Boiler
Before commencing any servicing or the replacement of parts, isolate the boiler from the electrical supply at the external isolator and close the gas service cock, see diagram 1.1.
BEFORE DRAINING THE BOILER, REFER TO SECTION 1.6.
1.4 Outer Case Removal
The door opens to the left or right hand side. The door catch is spring loaded, to open, push the side opposite to the hinge then pull.
Remove the two screws securing the outer case then unhook the case at the top and pull it forward and off, see diagram 1.2.
1.5 Cover - Inner Case
Remove the cover of the inner case, secured by four screws, see diagram 1.3.
1.6 System Pressures and Draining
WARNING. All parts containing water of the central heating circuit within the boiler, are under the system pressure. Before any parts of this circuit are disconnected, reduce the system pressure at the external draining tap. Turn the central heating isolating valves off and drain at the drain points on the appropriate valves, see diagram 1.1.
SECURING SCREW (4)
DATA LABEL
INNER CASE COVER
PILOT WINDOW SCREW (2)
4579
Diagram 1.3
4580
PLASTIC CAP
All water containing parts of the domestic hot water circuit of the boiler will be under the supply water pressure. Before any parts of this circuit are disconnected, turn the domestic cold water isolating valve off, open the hot water taps to reduce the water pressure in the boiler, close the hot water isolating valve and drain the boiler at the valves, see diagram 1.1.
After replacing any water containing part of the central heating circuit, make up the water loss, vent all air and pressurise the system. Refer to “Commissioning” in the Installation Instructions.
Check for water soundness.
Diagram 1.4
3
221045A
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
2.1 Pilot Check
Check that the pilot flame is burning correctly and of the correct size, see diagram 2.1. If the pilot flame is not correct, the pilot injector will require removing, as detailed later.
2.2 Isolation and Access
Before starting, refer to Section 1.1. Isolate the boiler from the electrical supply and close the
gas service cock, refer to Section 1.3. Remove the outer case and the inner case cover, refer to
Sections 1.4 and 1.5. Disconnect the electrical plug connector and air pressure
tube from the fan, see diagram 2.2. Follow steps 1 to 4 on diagram 2.2 to remove the
hooks bolts. Step 1 - Slacken the two thumb screws securing the
collector but do not remove. Step 2 - Unhook the hook bolts. Step 3 - Turn the hook bolts. Step 4 - Remove the hook bolts. Remove the fan securing screws.
SPARK GAP
4.5mm to 5.5mm
FAN OUTLET SEAL
FAN SECURING SCREWS
FLAME LENGTH 25mm
Diagram 2.1
PLUG
4574
4581
Pull the fan forwards, at the bottom and rotate to disengage the fan outlet to flue elbow and rear bracket.
Take care not to damage the seal. Tilt the fan and withdraw. Remove the flue collector, note, this may be a tight fit. Remove the combustion chamber front panel, secured
with four screws, see diagram 2.3. Slacken, but do not remove the gland seal
securing screw. Should the pilot burner assembly require servicing, it
will be necessary to disconnect the pilot and thermocouple nut as this stage, see diagram 2.4.
Remove the pilot burner assembly securing screws and washers.
When removing the pilot burner assembly, note the pilot injector is loose and that the electrode and lead are connected and must not be used to hang the assembly by, see diagram 2.4.
Remove the main burner from the main injector at the rear. Raise the burner up and forward, easing the pilot assembly forward and clear, taking care not to damage the combustion chamber insulation or pilot burner assembly, see diagram 2.5.
THUMB SCREW (2)
FLUE COLLECTOR
AIR PRESSURE TUBE
STEP 1 Slacken do not remove
STEP 3
STEP 2
STEP 4
4221045A
Diagram 2.2
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
2.3 Heat Exchanger
Place a sheet of paper or similar in the combustion chamber, to act as a collector for deposits removed.
Brush the heat exchanger with a suitable brush, remove paper together with any debris.
2.4 Main Injector
4582
HEAT EXCHANGER
Inspect the injector and clean as necessary. Do not use wire or a sharp instrument on the hole.
2.5 Main Burner
Use a vacuum cleaner or suitable brush to clean the burner thoroughly, making sure that all burner ports are clear and free from obstructions.
Do not use a brush with metallic bristles.
2.6 Service Checks
Before replacing any parts removed during servicing, inspect the condition of all seals and joints, renewing them as necessary.
Check the condition of the combustion chamber insulation.
Check that the spark gap is as shown in diagram 2.1.
2.7 Note. Reassembly
Make sure that the main burner baffle has located in the side guides and that the burner is located on the main injector.
Refit the hook bolts. The combustion chamber front panel should be fitted
loosely, then the flue collector also fitted loosely, make sure that it is seated onto the heat exchanger and over the top edge of the front panel.
SECURING SCREW (4)
COMBUSTION CHAMBER FRONT PANEL
SPARK ELECTRODE
SPARK ELECTRODE RETAINING CLIP
PILOT INJECTOR
SECURING SCREW AND WASHER (2)
Diagram 2.3
4583
THERMO­COUPLE NUT
IGNITION LEAD
To fit the fan, locate it into the rear bracket and ease the flue elbow onto the fan outlet, making sure that the fan outlet seal is correctly positioned. Secure with the two screws, see diagram 2.2.
Refit electrical connector making sure that the red spots are aligned.
Secure the flue collector and combustion chamber front panel by tightening the thumb screws and securing screws, see diagram 2.2 and 2.3.
2.8 Operational Checks
Light the boiler, carry out operational checks and any necessary adjustments as described in “Commissioning” in the Installation Instructions.
5
WING NUT
PILOT TUBE NUT
SEALING GLAND SECURING SCREW
Diagram 2.4
221045A
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
2 S e r v i c i n g
WING NUT
BURNER BRACKET
STEP 1 STEP 3
45844585
BURNER
WING NUT
BURNER BRACKET
SECURING SCREW
4586
BURNER GUIDE
STEP 2 STEP 4
SIDE GUIDES
MAIN INJECTOR
BURNER
4587
6221045A
Diagram 2.5
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
3.1 Initial Checks
3 F a u l t F i n d i n g
If the boiler fails to operate, first check the following:
1. That the electrical supply is available at the boiler and the fuses are in order.
NOTE: THE BOILER CONTROL BOARDS CAN BE DAMAGED BY INCORRECT TESTING WITH THE POWER ON.
2. Make sure that the system pressure gauge registers
0.7bar, minimum and that the automatic air vent works. Refer to Installation Instructions, Section 11.2.
3. That the gas supply is available at the boiler and purged of air.
4. Is the pilot burner lit? - If the pilot burner will not light refer to Section 3.2. If the pilot burner fails to remain alight, refer to Section 3.3
5. That the boiler is set for the required service.
6. With the boiler central heating selector switched “Off”, see diagram 3.2 check that the domestic water supply is available and water flows freely from the hot taps. Close the taps.
7. With the boiler central heating selector switched “ON”, see diagram 3.2, check that all heating system controls, if fitted, are working correctly and calling for heat. If not isolate the boiler from the electrical supply. Disconnect the rear multi-pole connector at the base of the boiler and release the cable from the clamp.
E
N
L
3
CABLE CLAMP/COVER SCREW (2)
SWITCH (OFF)
C.Htg. SELECTOR SWITCH
1
2
PIEZO BUTTON
SWITCH (ON)
CABLE TO REMOTE HEATING CONTROLS
MAINS CABLE
CABLE CLAMP
Diagram 3.1
GAS CONTROL KNOB
CLOCK/TIMER (IF FITTED)
2883
Remove the connector cover and dependent on the type of control fitted test for continuity, mains or low voltage at terminals 1 and 2, see diagram 3.1.
If this is satisfactory continue with the detailed fault finding.
PRESSURE GAUGE
Orange Light ‘MAINS’
Green Light ‘RUNNING’
Red Light LOW C.Htg. WATER PRESSURE
Diagram 3.2
7
221045A
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
PILOT WILL NOT LIGHT START HERE
3 F a u l t F i n d i n g
Check gas line - open all cocks, rectify any blockages, purge out any air. Does pilot light?
NO
Apply match to pilot burner instead of pressing piezo unit button. Does pilot light?
NO
Undo tubing nut at pilot burner. Press multifunctional control knob. Does gas flow freely?
NO
Rectify blockage in pilot injector, or renew pilot injector.
NO
Undo tubing nut at pilot outlet of mulitfunctional control. Press multifunctional control knob. Does gas flow freely?
NO
YES
YES
YES
YES
Does pilot stay alight when multi-functional control knob is released?
NO
PILOT SATISFACTORY
Does pilot flame envelope thermocouple?
NO
Check aeration. If necessary ­clean pilot, rectify blockage in pilot injector, or replace.
Check thermocouple circuit using thermocouple and boiler overheat cut-off fault finding.
YES
YES
Change blocked pilot tube.
NO
Change multifunctional control.
On pressing piezo unit button is there a spark across electrode gap?
NO
Remove electrode from pilot bracket. Hold tip close to pilot burner and operate piezo unit. Is there a spark across gap?
NO
Pull ignition lead off piezo unit. Using blade of an insulated screw­driver, touch unit chassis and leave approx. 4mm gap from connection tag on piezo unit. Operate piezo. Is there a spark across gap?
NO
Change piezo unit.
YES
YES
YES
Change electrode assembly.
8221045A
Check electrode gap. Reposition, or replace electrode as necessary.
Diagram 3.3
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
With the boiler cold, check connections of the thermocouple, boiler overheat cut-off and multifunctional control. Disconnect overheat cutoff connectors at points A and B at the multifunctional control, see diagram 3.5. Test continuity of the overheat cutoff. Is there continuity?
YES
Re-connect boiler overheat cutoff to points A and B. Disconnect thermocouple at point D of the mulitfunctional control. Test continuity between point C and the body of the multi­functional control. Is there continuity?
NO
YES
Faulty boiler overheat cutoff, renew.
Faulty cutoff connectors into multifunctional control, either at A or C. Renew where faulty.
NO
Test continuity of thermocouple between inner connection point D and point E. Is there continuity?
YES
Thermocouple and boiler overheat circuit satisfactory.
3.2 Pilot Burner and Ignition System
Symptom: The pilot burner will not light or stay alight. Test the pilot burner and ignition system as shown in
diagram 3.3.
3.3 Thermocouple and Overheat Cutoff
Symptom: The pilot burner fails to stay alight. On completion of initial checks, as Section 3.1. Test the thermocouple, overheat cutoff and thermocouple
connectors, as described in Fault Finding diagram 3.4 and shown in diagram 3.5.
NO
Faulty thermocouple, renew.
CONNECTION 'A'
CONNECTION 'E'
MULTIFUNCTIONAL
CONTROL
Diagram 3.4
4588
Check the millivoltage of the thermocouple closed circuit at points “A” and “E”, this should be within the range of 6 to 11mV, see diagram 3.5.
BOILER OVERHEAT CUTOFF
9
CONNECTION 'D'
CONNECTION 'C'
CONNECTION 'B'
Diagram 3.5
221045A
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
3.4 Clock/Timer - if fitted
If the clock has failed it can be bypassed by disconnecting the plug at the wall frame.
Disconnect the plug at the control box and connect this plug to the connection at the wall frame.
This is a temporary measure and the clock should be repaired or replaced as soon as possible.
3.5 Electrical
Preliminary electrical system checks, as outlined in a Multimeter Instruction book, are the first checks to be carried out during a fault finding procedure.
Isolate the boiler from the electrical supply, refer to Section 1.3.
Gain access to the boiler controls by removing the outer case, refer to Section 1.4. Check that all cables and connectors are secure.
Gain access to the control board, refer to Section 4.13. Check all cables at the multi-pin connectors on the board.
PERMANENT LIVE 240V~50Hz
(L)
OPTIONAL SWITCHED LIVE FROM ROOM STAT. 240V~50Hz
(N)
M
(L)
ON
COMMON
CLOCK/TIMER
0192M
br
b
br
p
p
Test the two fuses on the main control board and renew as necessary, the fuse are, type 2AT and type 3.15AT.
If a fuse fails repeatedly or the initial fault finding checks described in Section 3.1 indicate a boiler fault, check the boiler electrical circuits and follow the fault finding procedures, see diagram 3.5, 3.6, 3.7 and 3.8 and for clock/timer fault diagram 3.9.
On completion of a fault finding task that has required the disconnection and making of electrical connections then checks, for earth continuity, polarity and resistance to earth must be carried out.
KEY
PUMP
br
(N)
b
br
LN
3 3
2A
2
b
FUSE 1
2
4
br........................BROWN
b.........................BLUE
p.........................PURPLE
CONTROL BOARD
2
TERMINALS, CN 2 CONTROL BOARD
3
TERMINALS, CN 3 CONTROL BOARD
4
TERMINALS, CN 4
TRANSFORMER
LOW VOLT. 26V~
10221045A
b
240V~
2
CONTROL BOARD
br
2
Diagram 3.6
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
MAIN MULTIFUNCTIONAL CONTROL SOLENOID
DHW CUT OFF
CONTROL
C
N/C
N/O
WATER PRESSURE
w
SWITCH
(SHOWN IN
PRESSURISED
STATE)
DHW
FLOW
SELECTOR
SWITCH
w
CH
THERMISTOR
USER
CONTROL
BOARD
THERMISTOR
DHW
r
LN
TRANS­FORMER
TO REMOTE
HEATING
CONTROL
SWITCH
p p
bk
y
240V~
26V~
p p
5 WAY PLUG/SOCKET
r r
or or
p p
1
0195M
1 1
1
bk
r
1 1
4 4
4 4
br br
4 4
4 4
4 4
AIR PRESSURE
D.C. FAN
Diagram 3.7
N/C
C
N/O
SWITCH
1
FAN DRIVER
P.C.B.
2 2 2 2 2 2 2 2
1 1 1
p g y b gry w r Screen
gry p
y or
KEY
br bk b g gry or p r v w y
- Brown
- Black
- Blue
- Green
- Grey
- Orange
- Purple
- Red
- Violet
- White
- Yellow
v r
gry
gry p or y
MAIN PCB FAN DRIVER PCB
CN 1
1
CN 4
4
CN 5
5
CN 6
6
CN 7
7
1 2
5 5 5 5
6 6
6
7 7 7 7
CONTROL BOARD
CN 1 CN 2
11
221045A
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
Carry out the initial fault finding checks described in Section 3.1.
Check that gas, water and electricity are available at the boiler.
Before commencing tests isolate the boiler, make sure that the remote controls are not calling for duty and there
is no domestic hot water demand.
Remove the outer case, control housing and it's cover. Check all connections on the control board and the boiler components, rectify or renew as necessary. Two dummy two way connectors are provided for ease of testing continuity. Remove fuses and test for continuity, if faulty, check cables and connections for shorting to E or N, rectify if necessary and replace fuse, with spare provided. Check central heating water pressure, repressurize if necessary. Make sure boiler is cold. Check all pipes and connections between the Air Pressure Switch (APS) fan and combustion sample point, also between fan and gas/air ratio unit. Make sure sample point cap is fitted correctly. Make sure the pilot is alight. Make sure venturi is not blocked.
Isolate supply remove CN6 is there continuity between Red and Violet?
NO
Faulty APS. Replace.
YES
YES
Replace CN6. With no demand to the boiler. Restore power. Does the mains Orange LED come on?
Does the boiler light?
Does fan run at full speed for approx 30 seconds?
Isolate supply. Restore supply. During the 30 second is there approx 26V ac on Black and Red from the transformer at CN1?
YES
NO
NO
YES
YES
NO
NO
Is there 240V ac at Blue and Brown on CN3.
YES
Faulty LED. Does not effect boiler operation.
Isolate supply, is there continuity at flow switch?
NO
Faulty main PCB. Replace.
Faulty transformer. Replace.
NO
Check electricity supply.
YES
Faulty flow switch. Replace.
continued (a)
Is there 26V ac on Orange and Yellow at CN7 and greater than 3V dc on Grey and Purple?
YES
Isolate supply. Is the resistance at CN2 on the fan driver pcb between White and Grey, Grey and Purple, Purple and White approx 2.5 ?
YES
Is there continuity at CN2 on the fan driver pcb between White and the fan motor laminations? (repeat with Grey and Purple)
NO
NO
YES
NO
Faulty main PCB. Replace.
Faulty fan. Replace.
Faulty fan. Replace.
Faulty fan driver pcb. Replace.
Diagram 3.8
12221045A
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
YES
(a)
3 F a u l t F i n d i n g
After about 30 seconds from “switch on” does fan go to low speed?
YES
Isolate supply. Restore supply with no demand. Is there 24Vac between grey wire on CN6 and Pin 2 on CN1 for about 30 seconds.
YES
Isolate supply. Reconnect CN6, restore power supply.
YES
Does pump run for about 30 seconds?
YES
NO
NO
NO
Isolate supply disconnect central heating thermistor, is resistance of thermistor between 8K and 11K?
NO YES
Faulty thermistor. Replace.
Faulty APS. Replace.
During the 30 second period is there 240V at pump.
YES
NO
Faulty main PCB. Replace.
Faulty main PCB. Replace.
After about 30 seconds
does pump go off?
YES
Open DHW tap at full rate. Does burner pressure go to 13.1mb?
YES
NO
NO
Faulty pump. Replace.
Faulty main PCB. Replace.
Is the burner pressure between
0.1 and 13.1 mb ?
Does green demand light come on?
YES
NO
NO
YES
Check venturi air signal at test point Is this approx 2.5mb
YES
Faulty fan. Replace.
Faulty gas/air ratio unit. Replace.
NO
continued (a)
continued (b)
13
continued (c)
Diagram 3.8 cont.
221045A
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
YES
(a)
(b)
YES
Restore supply. Is there about 24V ac multifunctional control?
YES
NOYES
(c)
Isolate supply disconnect Red in line connectors to flow switch, is there continuity across flow switch?
YES
Reconnect flow switch, disconnect Purple in line connectors to DHW thermistor. Is the resistance between 8K and 11K?
YES
Faulty LED. Does not effect boiler operation.
NO
Faulty DHW thermistor. Replace.
Isolate supply, remove CN1. Is there continuity across DHW O/H stat?
NO
YES
Faulty flow switch. Replace.
NO
NO
Turn the DHW flow off. Turn on the CH. Does pump run?
NO
Faulty main PCB. Replace.
YES
Is burner pressure about 5.6mb?
SYSTEM O.K.
NO
YES
Faulty multifunctional control.
Is there continuity across C and N/O at low water pressure switch?
YES
Faulty main PCB. Replace.
Faulty DHW O/H stat. Replace.
NO
Faulty water pressure switch. Replace.
14221045A
Diagram 3.8 cont.
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F a u l t F i n d i n g
If a mains potential room thermostat is connected, ensure that the switch live is connected to PIN 1 in the 5 pole connector. Check continuity of clock/timer harness, ensure an electrical supply is available, ensure that remote controls are calling for heat.
Isolate the boiler from electrical supply, remove outer case.
YES
Switch on electrical supply, is there a display on clock/timer?
YES
Disconnect and insulate the purple cables from heating common and heating on.
YES
Advance clock/timer until a demand is indicated Is there now continuity between heating common and heating on?
YES
Clock/timer in order if no central heating, refer to main fault finding.
NO
NO
Faulty clock/timer. Replace.
Faulty clock/timer. Replace.
DIGITAL CLOCK/TIMER STYLE 1 and 2 FAULT FINDING
CLOCK FAULT FINDING
If a mains potential room thermostat is connected, make sure that the switch line is connected to pin 1 in
the 5 pole connector.
Check continuity of clock harness, make sure an electrical supply is available make sure that remote
controls are calling for heat.
Make sure the override switch if fitted is in the " " position
Does clock keep time
No
Faulty clock replace
Yes
No Isolate electrical supply set clock to on period Is there continuity across common and heating on
Clock in order if no central heating refer to
Yes
Set clock to off period. Is there continuity across common and heating on
No
main fault finding
ELECTRO/MECHANICAL CLOCK/TIMER FAULT FINDING
Diagram 3.9
5667
Yes
Diagram 3.9
15
221045A
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
Before replacing any part please read points below:­Replacement of parts must only be carried out by a
competent person. Unless stated otherwise all parts are refitted in the
reverse order to removal.
1. Refer to Section 1.1.
CLOCK/TIMER (if fitted)
4589
2. Always isolate the boiler from the electrical and as required the gas supply as Section 1.3.
3. Unless stated otherwise, gain access as appropriate parts of Sections 1.4 and 1.5.
4. On completion, make good any water loss and pressurise the system to initial design pressure, refer to “Commissioning” in the Installation Instructions.
If the red light “flashes”, momentarily interrupt the electrical supply.
4.1 Fan
Refer to the appropriate parts of Section 2.2. After fan has been fitted, check the burner pressure and
if necessary adjust.
4.2 Main Burner
Refer to the appropriate parts of Section 2.2. Note. There is no need to remove the fan or flue
collector assemblies.
CONTROL HOUSING SECURING SCREW (2)
SUPPORT BRACKET
FAN DRIVER CONTROL HOUSING)
TOP CONTROL HOUSING COVER
BOTTOM CONTROL HOUSING COVER
4.3 Main Injector
Refer to the appropriate parts of Section 2.2. Note. There is no need to remove the fan or the flue
collector assemblies.
4.4 Pilot Burner/Injector
Refer to the appropriate parts of Section 2.2 Note. There is no need to remove the fan or flue
collector assemblies.
4.5 Spark Electrode/Ignition Lead
Refer to the appropriate parts of Section 2.2. Note. There is no need to remove the fan or flue
collector assemblies. Remove the controls housing assembly and support, see
diagram 4.1. If this is not possible place on a surface, making sure that
the control knob is protected. Remove the spark electrode/ignition lead from the pilot
burner assembly, see diagram 2.4.
SCREW(2)
CLOCK/TIMER (if fitted)
Diagram 4.1
Disconnect the ignition lead from the piezo unit, refer to Section 4.11.
16221045A
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.6 Thermocouple
Remove the sealing gland, secured with a single screw, see diagram 2.4.
Remove the spark electrode/lead, see diagram 2.4. Disconnect the thermocouple at both ends, see diagram
2.4 and 4.2. Remove the thermocouple. Do not tighten the thermocouple nut more than a quarter
turn beyond finger tight or make any sharp bends in the capillary.
4.7 Boiler Overheat Cutoff
Remove the control housing as the appropriate part of Section 4.1.
Remove piezo unit bracket, disconnect lead, see diagram 4.3.
Disconnect the boiler overheat cutoff electrical connectors from the multifunctional control, see diagram 4.2.
Remove the boiler overheat cutoff, secured with two screws, see diagram 4.2.
SECURING SCREW (2)
OVERHEAT CUTOFF CONNECTORS
ELECTRICAL CONNECTORS
THERMOCOUPLE NUT
4591
Use the heat sink compound supplied, between the mounting plate and the cutoff, when fitting it.
4.8 Water Pressure Switch
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Disconnect the electrical connectors at the water pressure microswitch, see diagram 4.4.
Remove pressure switch. Replace the “O” ring seal with the new seal provided. Make sure that the switch terminals are facing diagonally
forwards to give access, as shown in diagram 4.4. Reconnect the electrical connections, refer to
diagram 4.11.
PIEZO UNIT BRACKET
IGNITION LEAD
PIEZO UNIT
SECURING SCREW (2)
SELECTOR SWITCH
Diagram 4.2
2848
Diagram 4.3
4592
17
WATER PRESSURE SWITCH
Diagram 4.4
221045A
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.9 Pump
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Disconnect the electrical connectors at the water pressure microswitch. Remove the water pressure switch, refer to Section 4.8.
Remove the terminal cover from the pump and disconnect the cable, see diagram 4.5.
Disconnect the pump at the unions. Discard the sealing washers.
PUMP SPINDLE
4593
PUMP ADJUSTER
TERMINAL COVER SCREW
FLOW DIRECTION ARROW
Make sure that the flow direction arrow is pointing upward when fitting and use the new sealing washers.
Refit water pressure switch, refer to Section 4.8. The flow adjuster on the new pump should be set to that
of the original, refer also to Section 4.6 in the Installation Instructions.
The flow rate should be controlled by means of a valve in the heating flow, refer to Section 11.10 in the Installation Instructions.
Note: Should the pump fail to operate, refer to diagram
3.8. If all is in order, but the pump still does not operate, remove the end screw, see diagram 4.5, then turn the pump spindle to release any temporary seizure.
DO NOT HIT THE SPINDLE.
4.10 Domestic Hot Water High Limit Control
Remove the pump, see Section 4.9. Disconnect the electrical connectors at the domestic hot
water high limit control, see diagram 4.6. Remove the high limit control from the flow pipe,
secured with two screws.
END SCREW
D.H.W. HIGH LIMIT CONTROL
UPPER PUMP UNION
LOWER PUMP UNION
Diagram 4.5
4594
Use the heat sink compound supplied, between the mounting plate and the control.
When refitting the electrical connections to the high limit control the polarity is not important, see diagram 4.11.
4.11 Piezo Unit
Remove the piezo unit bracket, see diagram 4.3. Disconnect the ignition lead at the piezo unit. Remove the piezo unit from the bracket.
D.H.W.
ELECTRICAL CONNECTORS
SECURING SCREW (2)
18221045A
HIGH LIMIT CONTROL
Diagram 4.6
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.12 Pressure Gauge
Remove the control housing assembly, see diagram 4.1. Release the water pressure and drain the central heating
circuit of the boiler, refer to Section 1.3 and 1.6. Remove the pressure gauge bracket. Disconnect the pressure gauge connection from the
safety valve, discard the washer, see diagram 4.7. Remove the pressure gauge secured with the
retaining tabs. Locate the supplied new washer under the pressure
gauge connection when refitting the safety valve.
4.13 Control Boards
CAUTION. Great care must be taken when handling any control board.
THE MAIN CONTROL BOARD MUST BE KEPT IN THE ANTI STATIC HOLDER UNTIL NEEDED.
Note. Timer/clock may be removed to improve access, see Section 4.32 or the control housing bottom half can be removed.
Main Control Board
Remove control housing cover securing screw, see diagram 4.8.
Remove the control housing assembly as shown in diagram 4.1.
Lift the control housing cover to gain access to the board.
SAFETY VALVE
SEALING WASHER
PRESSURE GAUGE CONNECTION
SECURING SCREW (2)
PRESSURE GAUGE
FASCIA
CONTROL HOUSING SECURING SCREW (2)
FASCIA SECURING SCREW (3)
HINGE PIN
PRESSURE GAUGE BRACKET
Diagram 4.7
TEMPERATURE CONTROL KNOB
CONTROL HOUSING COVER SECURING SCREW
CONTROL HOUSING COVER
2831
4595
Disconnect all multipin connectors, see diagram 4.8. Remove the control board from the support posts. To reconnect the multipin connectors correctly, see
diagram 4.11. When replacing the main control board check and if
necessary adjust the main burner gas pressure in both the domestic hot water and central heating modes. Refer to “Commissioning” in the Installation Instructions.
Fan Driver Board
Remove the fan driver control housing assembly securing screws.
Remove the multipin connectors, see diagram 4.9. Release the board from its support posts then remove the
nut and screw securing the board to the cover, see diagram 4.9.
User Control Board
Remove the fascia, see diagram 4.8. Remove the multipin connector.
TRANSFORMER
MULTI-PIN CONNECTORS
USER CONTROL BOARD
SUPPORT POSTS
Diagram 4.8
Remove the control board from the supports posts.
19
221045A
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
p
4.14 Transformer
Note. Timer/clock may be removed to improve access, see Section 4.32 or the control housing bottom half can be removed.
Remove the control housing cover screw, see diagram 4.8.
Remove control housing assembly, see diagram 4.1. Remove the control housing cover and disconnect the
electrical connectors from the transformer, see diagram 4.8.
Remove the transformer securing screws (2 off) from beneath the control housing, remove the transformer and insulation.
To connect the transformer cables correctly, refer to diagram 4.11.
FAN DRIVER BOARD
SUPPORT POSTS
FAN DRIVER CONTROL HOUSING
SECURING SCREW NUT
MULTI-PIN CONNECTORS
Diagram 4.9
4596
p
r
g/y
KEY
p
PURPLE
r
RED
b
BLUE
br
BROWN
g/y
GREEN/YELLOW
240V~50Hz PERMANENT MAINS SUPPLIED FUSED AT 3A
br
b
g/y
p
r
Diagram 4.10
b
br
CLOCK/ TIMER
br
b
br
p
COMMON
b
(L)
(N)
HEATING ON
4774
20221045A
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
y+or 26Volts ac gry+p 3 Volts dc CN7
AIR PRESSURE SWITCH
230V-50Hz PERMANENT MAINS SUPPLY FUSED AT 3A
12 NL
p p g/y b br
NO
gry
r
CENTRAL HEATING SELECTOR SWITCH
DC FAN
C
NC
v
THERMISTOR CH
PUMP
DHW FLOW SWITCH
screened screened
r w
gry b
y g p
THERMISTOR DHW
WATER PRESSURE SWITCH
gry
MULTI-FUNCTIONAL CONTROL
C
NO
w
b y
g p
NC
r
FAN
DRIVER
BOARD
or ypgry
r
0205M
g/y
or y p gry w
r
L
N
CN3
p p
r r br br or or
p p
gry
p y or
TRANSFORMER
bbr
MAINS
bbr
FUSE 2AT
KEY:
CN4
w b bk br g/y gry or v r y p
CN5
MAIN CONTROL BOARD
bk
NLNL 230V~
TXR
- WHITE
- BLUE
- BLACK
- BROWN
- GREEN/YELLOW
- GREY
- ORANGE
- VIOLET
- RED
- YELLOW
- PURPLE
bbr
CN7
FUSE
3.15AT
CN1
rv
CNCNO
gry
p y or
p p
bk y
bk r
DHW HIGH LIMIT CONTROL
gry
CN6
g/y
g/y
ww
21
USER CONTROL
BOARD
CHASSIS EARTH
Diagram 4.11
221045A
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.15 Multifunctional Control and Gas/Air Ratio Unit Assembly: diagram 4.12
Remove control housing, see diagram 4.1. Remove the piezo bracket, see diagram 4.3. Disconnect the two electrical connectors at the front of
the multifunctional control. Disconnect the boiler overheat cutoff connectors. Disconnect the thermocouple nut at the
multifunctional control. Disconnect the pilot supply tube at the
multifunctional control. Disconnect the gas/air ratio unit tubes at the
bulkhead connectors. Remove the four, right hand, extended hexagon screws
from the multifunctional control. Break the gas connection at the wall frame. Remove the multifunctional control valve and gas/air
ratio unit assembly, taking care not to damage the tubes.
Multifunctional Control
Remove the four, left hand, extended hexagon screws from the multifunctional control.
GAS/AIR RATIO UNIT TUBE NUTS
ELECTRICAL CONNECTORS
HEXAGON SCREWS (4)
BOILER OVERHEAT CUTOFF CONNECTOR
BOILER OVERHEAT CUTOFF CONNECTOR
GAS CONNECTION
MULTIFUNCTIONAL CONTROL
4597
HEXAGON SCREWS (4)
PILOT SUPPLY TUBE
THERMO­COUPLE NUT
'O' RING
Discard the “O” rings and fit the new ones, supplied. Check and adjust the main burner gas pressure in both
the domestic hot water and central heating modes, refer to “Commissioning” in the Installation Instructions.
Gas/Air Ratio Unit Assembly
Disconnect the gas/air ratio unit sensing tubes. Remove the two securing screws, see diagram 4.12.
4.16 Central Heating Selector Switch
Slacken the piezo bracket securing screws and remove the bracket from the keyhole slots, see diagram 4.3.
Pull the leads from the switch. To remove the switch press in the tabs on each side. The polarity of the electrical connections is not
important.
'O' RING
VENTURI AIR SIGNAL TEST POINT
SCREW (2)
GAS/AIR RATIO UNIT SENSING TUBE NUTS
22221045A
GAS/AIR RATIO UNIT
Diagram 4.12
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.17 Domestic Hot Water Flow Switch
The replacement of this part can be done within the limits of “minimum clearances”. Should there be a side clearance of 150mm or more then the multifunctional control/air ratio unit assembly need not be removed.
Isolate the domestic hot water inlet and drain, refer to Sections 1.3 and 1.6.
When replacing the flow switch it is recommended that the water inlet filter is cleaned or renewed.
When replacing the flow switch make sure that it is correctly positioned, with the flow direction arrow pointing upward.
Remove the burner as Section 2.2. Remove the multifunctional control and air/ratio
assembly as described in Section 4.15. Disconnect the front sensing tube. Disconnect the flow switch connectors, see
diagram 4.13. Remove the locknut from the flow switch and lower the
domestic hot water inlet pipe assembly, including flow switch, from the base of the main panel.
FLOW SWITCH
FILTER UNION NUT
ELECTRICAL CONNECTORS
UNION NUTS
GAS/AIR RATIO SENSING TUBE
4599
WATER INLET PIPE ASSEMBLY
Disconnect the filter union nut.
ISOLATING VALVE
CENTRAL HEATING THERMISTOR
UNION NUT
Diagram 4.13
4598
23
'O' RING
ELECTRICAL CONNECTORS
D.H.W. THERMISTOR
'O' RING
Diagram 4.14
221045A
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.18 Thermistor - Heating
Release the water pressure and drain the heating circuit of the boiler, refer to Sections 1.3 and 1.6.
Gain access by removing the piezo bracket, see diagram 4.3.
Disconnect the cables from the thermistor, see diagram 4.14.
Remove the thermistor, complete with its “O” ring. The polarity of the electrical connections is
not important.
4.19 Thermistor - Domestic Hot Water
The replacement of this part can be done within the limits of the minimum clearances. Should there be a side clearance of 150mm or more then the pump need not be removed.
Remove the pump, refer to Section 4.9. Release the water pressure and drain the domestic hot
water circuit of the boiler, refer to Section 1.3. and 1.6. Disconnect the cables from the thermistor, see
diagram 4.14. Remove the thermistor complete with its “O” ring. The polarity of the electrical connections is not
important.
SAFETY VALVE
PRESSURE GAUGE CONNECTION
CAP NUT
SEALING WASHER
THROTTLE ADJUSTER
DISCHARGE PIPE
UNION NUT
Diagram 4.15
2794
46004601
4.20 Safety Valve
Release the water pressure and drain the central heating circuit of the boiler, refer to Section 1.3 and 1.6.
Remove the pressure gauge, refer to Section 4.12. Disconnect the union nuts to release the safety valve, see
diagram 4.15.
4.21 Water Inlet Filter
Refer to the appropriate parts of Section 4.17.
4.22 Domestic Hot Water Throttle
Release the water pressure and drain the domestic hot water circuit of the boiler, refer to Section 1.3 and 1.6.
Refer to Section 4.17 to gain access to the throttle. Remove the cap nut and carefully remove the throttle
adjuster, by unscrewing, it may be necessary to push the throttle adjuster out from the rear, see diagram 4.16.
Clean if necessary, taking care not to damage the throttle body.
‘O’ RING
Diagram 4.16
MINI EXPANSION VESSEL
SEALING WASHER
Diagram 4.17
Reset the domestic hot water flow rate refer to Section
11.7 in the Installation Instructions.
24221045A
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.23 Mini Expansion Vessel
Release the water pressure and drain the domestic hot water circuit at the boiler, refer to Sections 1.3 and 1.6
Remove the control housing as Section 4.1. Note. It may be possible, in some circumstance, to
remove the mini expansion vessel by hand. Remove the multifunctional control, refer to
Section 4.15. When refitting use the new sealing washer supplied, see
diagram 4.17.
4.24 Automatic Air Vent
Release the water pressure and drain the central heating circuit of the boiler, refer to Sections 1.2 and 1.6.
Remove the automatic air vent, see diagram 4.18. SLACKEN THE SMALL CAP ON THE AIR VENT.
THIS MUST NOT BE RETIGHTENED.
LOCATION SLOT
CAP
SEALING WASHER
4602
AUTOMATIC AIR VENT
When refitting use the new washer supplied.
4.25 Heat Exchanger
Release the water pressure and drain the central heating and domestic hot water circuits refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 2.2.
Remove the flue collector, refer to Section 2.2. Remove the main burner, refer to Section 2.2. Remove the automatic air vent, refer to Section 4.24.
If renewing the heat exchanger, transfer the air vent, using the new sealing washers provided.
Disconnect the front gas/air ratio sensing tube, see diagram 4.18. Make sure that no water enters the tube.
Disconnect the union nuts of the heat exchanger to remove it, see diagram 4.18.
Reassembly Notes. Locate the raised location tabs on the combustion
chamber sides into the slots on the heat exchanger, see diagram 4.18.
UNION NUTS
UNION NUTS
GAS/AIR RATIO SENSING TUBE
Diagram 4.18
Make sure that the main burner baffle has located in the side guides and that the burner is located on the main injector.
The combustion chamber front panel should be fitted loosely, then the flue collector also fitted loosely, make sure that it is seated correctly on the heat exchanger and over the top edge of the front panel.
25
221045A
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
SECURING SCREW (4)
COMBUSTION CHAMBER FRONT PANEL
Diagram 4.19
4.26 Combustion Chamber Insulation
Remove the combustion chamber front panel secured with four screws, see diagram 4.19.
Remove the front insulation, secured with a clip, see diagram 4.20.
4603
COMBUSTION CHAMBER FRONT PANEL
CLIP
FRONT INSULATION
4604
Slide out both side insulation pieces. Remove the burner as in Section 2.2. Pull the lower rear insulation forward, then slide the
upper rear insulation down from behind the heat exchanger, see diagram 4.20.
SIDE INSULATION PIECES
LOWER REAR INSULATION
26221045A
UPPER REAR INSULATION
Diagram 4.20
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
4.27 Expansion Vessel
Renewal of the expansion vessel requires the boiler to be removed from the wall. As an alternative, a separate expansion vessel of the same specification may be connected as close as possible to the boiler, leaving the original in position, refer to Section 4.5 in the Installation Instructions.
Release the water pressure and drain the central heating and domestic water circuits, refer to Section 1.3 and 1.6.
Remove the fan from the flue collector, refer to Section 2.2.
Remove the flue elbow, refer to Section 10 of the Installation Instructions.
Disconnect the boiler water connection union nuts at the front of the isolating valves, see diagram 1.1.
Disconnect the gas service cock union. Disconnect the safety valve discharge pipe from the
boiler, see diagram 1.1.
4605
SECURING (2)
LOCATION CLIPS
Separate the two parts of the boiler multi-pole electrical connector.
Slacken the clips of the gas service cock and the water isolating valves.
Remove the boiler from the mounting frame, secured with two screws at the top, see diagram 4.21. Pull the boiler from the isolating valves. Unhook the boiler at the top and lift off.
Carefully lay the boiler down on its side for access to the expansion vessel.
Disconnect the union nut connection, see diagram 4.22 and discard the sealing washer.
Remove the expansion vessel, secured with three clamping screws.
Connect the union nut, when fitting the expansion vessel, before clamping it.
CLIP
(5)
UNIONS (5)
UNION NUT CONNECTION AND SEALING WASHER
Diagram 4.21
2861
27
CLAMPING SCREW (3)
Diagram 4.22
221045A
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
FRAME
GLASS
SECURING SCREW (2)
GASKET
Diagram 4.23
4.28 Pilot Viewing Window
Remove the pilot viewing window, secured with two screws. When fitting a new window use the gasket provided, see diagram 4.23.
4.29 Inner Cover Case Seal
Remove the old seal, clean out the old adhesive. Glue the new seal into place, make sure that there are no
breaks in it.
4.30 Air Pressure Switch
Remove the flue collector, refer to Section 2.2.
4606
CLEAR
GREY
AIR PRESSURE TUBES
4607
SCREWS (2)
AIR PRESSURE SWITCH
VIOLET
ELECTRICAL CONNECTORS
RED
RED
Diagram 4.24
Disconnect the three electrical connectors at the air pressure switch, see diagram 4.24. Remove the flexible tubes from the switch. Remove the air pressure switch, secured with two screws.
When replacing the tubes to the air pressure switch make sure that the forward (clear) tube from the air pressure switch connects to the tee on the incoming air sensing tube.
The rear most (coloured) tube connects to the fan pressure sensing tube.
When reconnecting the electrical cables refer to diagram 4.11.
4.31 Air/Gas Ratio Sensing Venturi
Remove the fan assembly and flue collector, refer to Section 2.2.
Disconnect the tube nut and screw to release the sensing venturi, see diagram 4.25.
4608
SCREW
VENTURI TUBE NUT
Diagram 4.25
28221045A
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
4 R e p l a c e m e n t o f P a r t s
CLOCK/TIMER
SECURING SCREWS (2)
ELECTRICAL CONNECTIONS
pp
br
4609
SECURING CLIP (2)
4777
MOUNTING BRACKET
SPACER
TIMER/CLOCK
b
KEY
br BROWN b BLUE p PURPLE
MAINS NEUTRAL (N)
MAINS LIVE (L)
HEATING ON
RETAINING TABS (4)
DIGITAL CLOCK/TIMER STYLE 1 ILLUSTRATED
COMMON
Diagram 4.26
4.32 Clock/Timer - if fitted
Digital clock/timer - Style 1 - Release the mounting bracket securing screws, see diagram 4.26.
Disconnect the electrical cables, squeeze the retaining tabs to release the clock/timer, see diagram 4.26.
Electro/mechanical and Digital clock/timer - Style 2 ­Release the mounting bracket securing screws, see diagram 4.26.
Disconnect electrical cables, release securing clip to remove the clock/timer and spacer, see diagram 4.27.
ELECTRO/MECHANICAL and DIGITAL CLOCK/ TIMER STYLE 2 ILLUSTRATED
Diagram 4.27
29
221045A
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
5 S p a r e P a r t s
5.1 Part Identification
The key number in diagram 5.1 and the first column of the list will help identify the spare part.
5.2 Ordering
When ordering any spare part, please quote the part number and the description from the list together with the model name and serial number information from the data label. The data label is positioned on the inner case cover, see diagram 1.3.
Key No Part No Description GC No
1 800512 Fan assembly 278 129 2 205724 Main injector assembly 278 130 3 203433 Pilot burner 379 485 4 202627 Spark electrode with lead 278 131 5 203518 Pilot injector 381 656 6 202435 Thermocouple 378 204 7 432869 Boiler over heat cut off assy 376 988 8 432868 DHW high limit control assy 313 024 9 900501 Piezo unit) 382 585 9 900501 Piezo unit) 384 146 10 800134 Pressure gauge assembly 313 294 11 202217 Control board inc fuses 278 132 12 800513 Transformer 278 133 13 800510 Multifunctional control 278 134 14 202068 Central heating selector switch 382 813 15A 800504 Thermistor assembly-Domestic 278 135 15B 800504 Thermistor assembly-Heating 278 135 16 800136 DHW switch assembly 313 277 17A 202226 Fuse 1 278 136 17B 202240 Fuse 2 *** ***
alternatives
}
18 800155 Water pressure switch assembly 278 142 19 202218 User PCB 278 141 20 202221 Air pressure switch assy 278 137 21 208214 Water inlet filter 281 359 22 800153 Automatic air vent assembly 313 285 23 800149 Safety valve assembly 397 677 24 203373 Gas/air ratio unit 278 138 26 800515 Fan driver board 278 140
30221045A
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
5 S p a r e P a r t s
4610
15
3
4
5
6
26
8
7
12
14
1
16
21
24
19
11
17A
20
17B
2
10
18
22
23
13
31
9
Diagram 5.1
221045A
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer.
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Because of our constant endeavour for improvement details may vary slightly from those in the instructions.
32221045A
Loading...