Glow-worm Space Saver K.F.B 60, Space Saver K.F.B 70 Installation And Servicing Instructions

Supplied By www.heating spares.co Tel. 0161 620 6677
220692C.01.98.
Installation and Servicing Instructions
To be left with user
S P A C E S A V E R
K . F . B
60 GC 41 319 11
4757
70 GC 41 319 12
Fanned Flue
Boiler
Fully Pumped system.
Open Vented or Sealed.
This is a Cat I2H Appliance
BS 6332 BS 5258
Customer Services: Tel: (01773) 828100
One Contact Local Service
Fax: (01773) 828070
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries:
Tel: (01773) 824141 Fax: (01773) 820569
Supplied By www.heating spares.co Tel. 0161 620 6677
Contents
Section Title Page No
Location Map
1 2 3
SECTION
4 5 6 7
GENERAL ............................... 3
WATER SYSTEMS .................. 7
BOILER LOCATION ................ 11
FLUE and VENTILATION ........ 13
FLUE INSTALLATION ............. 15
INSTALLATION ....................... 21
COMPLETION
and COMMISSIONING ........... 29
8
FRONT PANEL
ASSEMBLY ............................ 34
9 10 11 12
USER INFORMATION ............ 35
SERVICING ............................ 36
FAULT FINDING ..................... 41
REPLACEMENT
OF PARTS .............................. 46
A519 ASHBOURNE
Milford
Site
MILFORD
A6 DERBY
Belper and Milford
Factory Sites
A6 MATLOCK
B6013 RIPLEY
BELPER
Nottingham Rd
Site
N
2890
A609 NOTTINGHAM
Belper
13
SPARES ................................. 51
Control of Substances Hazardous to Health
Information for the Installer and Service Engineer
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation and Seals
Ceramic fibre and glass fibre used in insulation panels, rope and gaskets.
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the
lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Thermostat
This contains a very small amount of xylene in the sealed phial and capillary. If broken, under normal circumstances the fluid does not
cause a problem, but in cases of skin contact, wash with cold water.
If swallowed drink plenty of water and seek medical attention.
Cut-Off Devices
These contain activated charcoal and a very small amount of chlorodifluormethane in the sealed phial and capillary.
If broken, under normal circumstances the fluid does not cause a problem.
2
220692C
If there is irritation to the eyes or skin then seek medical attention.
2
Supplied By www.heating spares.co Tel. 0161 620 6677
The instructions consist of two parts, Installation and Servicing Instructions and Instructions for Use, which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installations and Use) Regulations,be handed to the user on completion of the installation.
Important Notices
General
70
TOP VIEW
R F
55
35
WATER CONNECTIONS 28mm COMPRESSIONS
GAS CONNECTION Rc1/2(1/2"B.S.P.T.)
SIDE
40
FLUE OUTLET
1
3060
SECTION
This boiler is for use on natural gas (G20) as distributed in the United Kingdom and cannot be used on any other gas.
Wherever possible, all materials, appliances and components to be used shall comply with the requirements of applicable British Standards.
Where no British Standard exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
This boiler must have fully pumped circuits, but is suitable for use with open vented or sealed water systems.
This boiler is not suitable for outdoor locations.
Sheet Metal Parts
450
458
FRONT VIEW
445
155
285­315
130 700­728
125
SIDE VIEW
WARNING. When installing or servicing the boiler care should be taken when handling sheet metal parts to avoid any possibility of personal injury.
REAR FLUE OUTLET
Statutory Requirements
The installation of the boiler MUST be carried out by a competent person in accordance with the relevant requirements of the current issue of:
Manufacturer’s instructions supplied.
FRONT VIEW BOILER OUTLINE
ALL DIMENSIONS ARE IN MILLIMETRES
3
15
125
50
687
FLUE TERMINAL DETAIL
102
63
3
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
1
The Gas Safety (Installation and Use) Regulations, The Building Regulations, The Building Standards (Scotland) Regulations, (applicable in Scotland) Local Water Company Bye-laws, Health and Safety at Work Act, Control of Substances Hazardous to Health, The
SECTION
Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice, BS6798, BS5440 Part 1 and 2, BS6700, BS5449, BS6891, BS4814, BS7074 Part 1 and 2, BS5446, BS7478, BS7593, BS7671.
Manufacturer’s notes must not be taken as overriding statutory requirements.
General
B.S.I. Certification
The boiler is certificated to the current issue of BS6332 Part 1, invoking the current issue of BS5258 Part 1 for performance and safety. It is, therefore, important that no alteration is made to the boiler without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the B.S.I. Certification of the boiler, the warranty and could also infringe the current issue of the Statutory Requirements.
CE Mark
The CE Mark on this appliance shows compliance with Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
The CE Mark on this appliance shows compliance with Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
4
220692C
4
Supplied By www.heating spares.co Tel. 0161 620 6677
Range Rating
The boiler is range rated and may be adjusted to suit individual system requirements, refer to the relevant column of the table.
General
Range Rating K.F.B K.F.B
Nominal min
Heat med
Input max (Gross)
Nominal min
Heat med
Ouput max
Burner min
Setting med
Pressure max
Btu/h 64935 78947
kW 19.03 23.14
Btu/h 70064 84416
kW 20.54 24.74
Btu/h 75000 89709
kW 21.98 26.29
Btu/h 50000 60000
kW 14.66 17.59
Btu/h 55000 65000
kW 16.12 19.05
Btu/h 60000 70000
kW 17.59 20.52 in wg 4.2 4.6 mbar 10.6 11.4
in wg 4.9 5.2 mbar 12.2 13.0
in wg 5.6 5.9
mbar 14.0 14.6
Space Saver Space Saver
60 70
1
SECTION
Data T able
Data Label Position
Space Saver Space Saver
Model K.F.B K.F.B
60 70
Lifting 32.4kg 32.4kg Weight (71.4lb) (71.4lb)
Total 46.1kg 46.1kg Weight (dry)* (101.6lb) (101.6lb)
Water 2.13 litres 2.13 litres Content (0.47 gal) (0.47 gal)
1
Gas Rc Connection (1/2" BSPT) (1/2" BSPT)
Water 28mm 28mm
Connection Compression Compression
Electrical 240V~50Hz fused 3A max supply
Internal Fuse to BS4265 sheet 2. Type F1A Fuse Rating
Power rating 55W
3038
/
2
Rc1/
* Note: The weight of the water is negligible
2
5
Space Saver K.F.B 60
G.C. Number 41 319 11
Space Saver K.F.B 70
G.C. Number 41 319 12
5
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
1
General
Gas Supply
SECTION
Electrical Supply
The gas installation shall be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
On completion test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
WARNING. THIS BOILER MUST BE EARTHED. All system components shall be of an approved type
and shall be connected in accordance with the current issue of BS7671 and any applicable local regulations.
Connection of the boiler and system controls to the mains supply must be through a common isolator and must be fused 3A maximum. The method of connection should be, preferably, an unswitched shuttered socket outlet and 3 pin plug, both to the current issue of BS1363.
Draining T ap
Alternatively, a double pole isolating switch may be used, provided it has a minimum contact separation of 3mm in both poles. The isolator should be clearly marked showing its purpose. See also Section 6, Electrical Connection and System Controls.
Wiring to the boiler must be to the current issue of BS6500 Table 16, not less than 0.75mm2 (24/
0.20mm).
The boiler is provided with a draining tap at the lower right hand side for draining the heat exchanger in the event of the boiler being out of use during freezing conditions.
A draining tap must also be provided at the lowest points of the system which will allow the entire system and hot water cylinder to be drained.
Draining taps shall be to the current issue of BS2879.
Safety V alve
A safety valve need not be fitted to an open vented system.
6
220692C
6
Supplied By www.heating spares.co Tel. 0161 620 6677
Water Systems
2
Notes: Open Vented and Sealed Water Systems
Pump
See chart for pressure drop of the boiler. The pump should be fitted in the flow
pipe from the boiler and have isolating valves each side, integral if possible.
The variable duty pump should be set to give a temperature difference of 11oC (20oF) between flow and return with the thermostat set at “MAX” which is about 82oC (180oF).
High resistance microbore systems may require a higher duty pump.
UNIT
litre / min.
gal / min.
1400 1200 1000
800 600 400
WATER FLOW RATE
At 11˚C (20˚F) differential
HEAT SETTING
Min.
60 70
19.1
4.2
Flow rate (gallons / minute)
1234567
0
22.9
5.0
60 70
22.9
5.0
Max.
26.7
5.9
50 40 30 20
4778
SECTION
Bypass
200
0
Water pressure drop (mm head of water)
PRESSURE DROP OF BOILER
A BYPASS MUST BE FITTED, see also Section 7. The flow through the boiler must not be allowed to fall
below......
Space Saver K.F.B 60 - 12.6 litres/min (2.8 galls/min) Space Saver K.F.B 70 - 14.76 litres/min (3.2 galls/min)
Where the water system can allow the boiler and pump to operate on bypass only, the bypass must be at least
2.0metres away from the boiler.
0 5 10 15 20 25 30 35
Flow rate (litres / minute)
10 0
Water pressure drop (inches head of water)
Inhibitor
If an inhibitor is to be used refer to the current issue of BS5449 and BS7593, contact a manufacturer for their recommendations as to the best product to use.
When using in an existing system take special care to drain the entire system, including the radiators, then thoroughly cleaning out before fitting the boiler whether or not adding an inhibitor
7
7
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
1
Water Sysems (Open Vented)
Open (Vented) Water System
For an open (vented) system the boiler must be supplied from an unrestricted water supply taken from a feed and expansion cistern situated at a
SECTION
maximum height of 27.5 metres (90ft) above the boiler.
The cold feed supply must be 15mm minimum size.
The vent must rise continuously and be unrestricted.
It is important that the relative positions of the pump, cold feed and open vent are as shown.
Domestic Hot Water Cylinder
450mm MIN. HEIGHT
1metre MIN.
27.5metres MAX.
Open (vented) system. Recommended relationship between pump, cold feed and vent.
UNRESTRICTED CONTINUOUSLY 22mm (MIN) VENT
FEED AND EXPANSION CISTERN
15mm (MINIMUM) UNRESTRICTED COLD FEED
22mm (MINIMUM) BY-PASS WITH LOCKSHIELD VALVE
RET.
RET.
CYLINDER
2886
FLOW
The hot water cylinder must be of the double feed fully indirect type. Not the self priming type.
BOILER
PUMP
HEATING
FLOW 150mm MAX
8
220692C
8
Supplied By www.heating spares.co Tel. 0161 620 6677
Water Systems (Sealed)
Sealed W ater Systems
The installation must comply with the appropriate requirements of the current issue of BS5449, BS6798, BS4814 and BS7074 Part 1 and 2.
See the diagrammatic layout.
3 LITRES (0.66 gal) MAKE-UP BOTTLE (if required)
AUTO AIR
NON­RETURN VALVE
VENT
2
2888
AIR RELEASE POINT
SECTION
Safety V alve
A safety valve must be fitted to a sealed system.
It shall be preset, non-adjustable with a lift pressure of 3bar, incorporating seating of a resilient material, a test device and a connection for drain.
The drain from the safety valve must be routed clear of any electrical fittings and positioned so that any discharge can be seen.
Expansion V essel
FILLING POINT
CIRCULATING PUMP
PRESSURE GAUGE
EXPANSION VESSEL
(Make-up alternatives)
FLOW
LOCKSHIELD
CIRCUIT
HEATING
RETURN
22mm (min)
BYPASS
WITH
VALVE
DRAIN COCK
SAFETY VALVE
BOILER
A diaphragm type expansion vessel, conforming to the current issue of BS4814 (see also BS7074 Part 1 and 2) must be connected at a point close to the inlet side of the circulating pump, see the diagrammatic layout, unless laid down differently by the manufacturer.
The expansion vessel volume depends on the total water system volume and the initial system design pressure. For any system an accurate calculation of vessel size is given in the current issue of BS7074 Part 1.
Example: For an initial system design pressure of
0.7bar, the minimum total vessel volume required is
0.063xTotal System volume. Note. A higher initial design pressure requires a larger
volume expansion vessel. Guidance on vessel sizing is also given in the current
issue of BS5449 and BS7074 Part 1. The charge pressure must not be less than the static head
of the system, that is, the height of the highest point of the system above the expansion vessel.
The water capacity of the boiler is given in the Data Table.
9
220692C
9
Supplied By www.heating spares.co Tel. 0161 620 6677
2
Water Systems (Sealed)
Pressure Gauge
A pressure gauge with a set pointer and covering at least 0 to 4bar (0 to 60lb in2) shall be fitted permanently to the system in a position where it can be seen when filling the system.
SECTION
Domestic Hot Water Cylinder
SINGLE FEED INDIRECT CYLINDERS ARE NOT SUITABLE
The hot water cylinder must be of the indirect coil type. It must be suitable for working at a gauge pressure of
0.35bar above the safety valve setting.
UNVENTED
Where a storage system will not have a vent to atmosphere the installation must comply with the Building Regulations and the local Water Company bylaws, see also the current issue of BS5546 and BS6700.
METHOD 1
TEMPORARY HOSE
SUPPLY PIPE
METHOD 2
TEMPORARY HOSE
SUPPLY PIPE
METHOD 3
CISTERN
HOSE UNIONS
SUPPLY STOP VALVE
DOUBLE CHECK VALVE ASSEMBLY
HOSE UNIONS
SUPPLY STOP VALVE
OVERFLOW
SERVICING VALVE
COMBINED CHECK VALVE AND VACUUM BREAKER
SERVICING VALVE
SERVICING VALVE
PRESSURE REDUCING VALVE
0051M
HEATING SYSTEM
HEATING SYSTEM
HEATING SYSTEM
10
If fitting into an existing system the local authority must be informed.
Water Make Up
Provision should be made for replacing water loss from the system using a filling loop or a make up bottle mounted in a position higher than the top point of the system, connected through a non-return valve to the return side of either the heating circuit or the hot water cylinder.
Alternatively, provision for make up can be made by pre-pressurisation of the circuit.
SUPPLY STOP VALVE
SUPPLY PIPE
HOSE UNIONS
DOUBLE CHECK VALVE ASSEMBLY
Filling Sealed Water Systems
Provision for filling the system at low level must be made. Three methods are shown in the diagram. There must be no permanent connection to the mains water supply, even through a non-return valve.
220692C
10
Supplied By www.heating spares.co Tel. 0161 620 6677
The boiler may be installed in any room although particular attention is drawn to the requirements of the current issue of BS7671 with respect to the installation of a boiler in a room containing a bath or shower. Any electrical switch or boiler control using mains electricity should be so situated that it cannot be touched by a person using the bath or shower. The electrical provisions of the Building Standards (Scotland) are applicable to such installations in Scotland.
Boiler Location
10mm
70mm
5mm
3
2891
SECTION
5mm
The boiler must be mounted on a flat wall which is sufficiently robust to take its complete weight, see Data Table.
Boiler Clearances
The boiler must be positioned so that at least the minimum operational and servicing spaces are as shown.
500mm
10mm
100mm
WHERE EXTERNAL ACCESS TO THE
5mm
FLUE IS NOT PRACTICAL THEN
CLEARANCE MUST BE ADEQUATE
TO PERMIT INSTALLATION OFF THE
FLUE ASSEMBLY
5mm
11
11
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
2
Boiler Location
Timber Frame Buildings
SECTION
Cupboard or Compartment Ventilation
Where the boiler is fitted in a cupboard or compartment, permanent high and low level ventilation must be provided. The ventilation areas required are given in the Table.
Where the installation of the boiler will be in an unusual location, special procedures are necessary, refer to the current issue of BS6798 for guidance.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose.
If the boiler is to be installed in a timber frame building, it should be fitted in accordance with the British Gas Publication “Guide for Gas Installation in Timber Framed Housing” reference DM2. If in doubt, seek advice from the local gas undertaking or Hepworth Heating Ltd.
S P A C E S A V E R K . F . B 6 0
VENTILATION HIGH LEVEL LOW LEVEL REQUIREMENTS VENT AREA VENT AREA
FROM ROOM OR SPACE
FROM OUTSIDE
198cm2 (30in2) 198cm2 (30in2)
99cm2 (15in2) 99cm2 (15in2)
An existing cupboard or compartment modified for the purpose may be used. Refer to the current issue of BS6798 for guidance.
The doorway opening should be of sufficient size to allow for easy removal of the boiler.
S P A C E S A V E R K . F . B 7 0
VENTILATION HIGH LEVEL LOW LEVEL REQUIREMENTS VENT AREA VENT AREA
FROM ROOM OR SPACE
FROM OUTSIDE
237cm2 (36in2) 237cm2 (36in2)
119cm2 (18in2) 119cm2 (18in2)
12
220692C
12
Supplied By www.heating spares.co Tel. 0161 620 6677
Flue and Ventilation
The flue must be installed in accordance with the current issue of BS5440 Part 1.
The boiler must be installed so that the terminal is exposed to the external air.
4
0103M
A
C
It is important that the position of the terminal allows the free passage of air across it at all times.
Terminal Position
The minimum acceptable spacings from the terminal to obstructions and ventilation openings are as shown in the diagram.
Where the terminal is fitted within 600mm (24in) below plastic guttering an aluminium shield 1500mm (5ft) long should be fitted to the underside and immediately beneath the guttering or eaves.
Where the terminal is fitted within 450mm (18in) below eaves or painted guttering an aluminium shield 750mm (2ft6in) long should be fitted to the underside and immediately beneath the guttering or eaves.
Terminal Protection
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and be central over the terminal.
A suitable terminal guard can be bought from,
B,C
A
F
G
Car Port etc.
MINIMUM SITING DIMENSIONS FOR FLUE TERMINALS
A DIRECTLY BELOW AN OPENABLE WINDOW, AIR VENT, 300
OR ANY OTHER VENTILATION OPENING
B BELOW GUTTER, DRAIN/SOIL PIPE 75 C BELOW EAVES 200 D BELOW A BALCONY OR CAR PORT 200 E FROM VERTICAL DRAIN PIPES AND SOIL PIPES 75
F FROM INTERNAL OR EXTERNAL CORNERS 300 G ABOVE ADJACENT GROUND OR BALCONY LEVEL 300 H FROM A SURFACE FACING THE TERMINAL 600
I FACING TERMINALS 1200
J FROM OPENING (DOOR/WINDOW) 1200
IN CARPORT INTO DWELLING
K VERTICAL FROM A TERMINAL 1500 L HORIZONTALLY FROM A TERMINAL 300
G
A
E
G
H,I
B,C
K
F
F
G
J
K
K
L
L
K
G
D
F
SPACING
SECTION
MIN.
(mm)
4783
Tower Flue Components Ltd., Morley Road, Tonbridge, Kent. TN9 1RA their reference K3.
13
13
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
2
Flue and Ventilation
Flue Position and Length
Note. If a longer flue duct is required DO NOT extend the ducting. A special long flue system and terminal can be supplied and MUST be used.
SECTION
DETERMINE FLUE APPLICATION, LENGTH, AND TERMINAL POSITION BEFORE PROCEEDING.
Refer to the relevant diagrams in Section 4.
For wall thickness of less than 300mm the boiler can be fully installed from inside.
For a wall thickness of over 300mm the cut hole will need to be made good from the outside.
The rear and side flue assemblies are designed for internal installation, but should it be necessary due to insufficient clearances or boiler location they can be installed from the outside.
2876
R
Rear Flue Lengths
Distance 'R'
S T D 75mm to 692mm
1m 692mm to 1022mm
2m 1022mm to 2022mm
REAR FLUE APPLICATION
FOLLOW
FLUE INSTALLATION
step
1
step
11
SIDE FLUE APPLICATION
FOLLOW
FLUE INSTALLATION
step
6
t o
&
t o
t o
step
5
step
16
step
16
2877
S
Side Flue Lengths
Distance 'S'
S T D 75mm to 692mm
1m 692mm to 1022mm 2m 1022mm to 2022mm
14
220692C
14
Supplied By www.heating spares.co Tel. 0161 620 6677
Flue Installation
5
Rear Flue Application
Having selected the boiler location with due regard to the terminal position;
Using an adhesive tape temporarily position the wallplate/template on the wall.
Mark out the centre and cut the hole for the flue using, preferably, a 115mm minimum core drill.
If the wall thickness “Q” is less than 300mm cut the wall sleeve to the required length.
step
2892
1
WALLPLATE/ TEMPLATE
SECTION
115mm MINIMUM HOLE
step
2
Fit the wall sleeve. Make good around the wall sleeve at
both internal and external wall faces (through the wall sleeve if internal access only is available).
If the wall thickness “Q” is greater than 300mm the wall sleeve must be fitted flush with the INSIDE wall face. If the inner end of the sleeve sticks out into a cavity then, if desired, the wall sleeve can be trimmed back to the depth of the inner skin of the brickwork. Make good at the internal wall face, leave the external wall face until later.
Reposition the wallplate/template ensuring alignment with the flue hole. Mark the top and bottom boiler mounting hole positions.
step
3
WALLPLUG
Q
No. 10x11/2in SCREW
Q
300mm MAX LENGTH
Remove wallplate/template, drill holes and then secure wallplate/template to the wall with the fittings provided in the loose items pack.
15
5.5mm DRILL SIZE
15
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
5
Flue Installation
Flue Duct (Standard or Long)
Mark the duct to the length “Q”+11mm then cut square and remove any burrs.
SECTION
Air Duct/Terminal (Standard or Long)
step
4
step
5
2893
Q+11mm
Q
Mark the duct to the length “Q”+13mm then cut square and remove any burrs.
STANDARD, 1 METRE AND 2 METRE FLUE TERMINAL KFB 70 ONLY. 1 METRE AND 2 METRE FLUE TERMINAL KFB 60 ONLY
1m 2m FLUE TERMINAL
STANDARD FLUE TERMINAL
Q+13mm
Continue at
step
11
16
220692C
16
Q
Supplied By www.heating spares.co Tel. 0161 620 6677
Flue Installation
5
Side Flue Application
Having selected the boiler location, with due regard to boiler clearances and the terminal position.
Position the wallplate/template on the wall. Mark the top and bottom boiler mounting hole positions.
Remove the wallplate/template, drill the holes and then secure the wallplate/ template with the fittings provided.
Mark and extend the flue horizontal centre line to the corner of the adjacent surface.
step
6
step
7
WALLPLUG
2894
No. 10x11/2in SCREW
SECTION
5.5mm DRILL SIZE
125mm
Mark out and cut the hole for the flue using, preferably, a 115mm minimum core drill.
If the wall thickness “Q” is less than 300mm cut the wall sleeve to the required length.
Fit the wall sleeve. Make good around the wall sleeve at
both the internal and external wall faces (through the wall sleeve if internal access only is available).
If the wall thickness “Q” is greater than 300mm the wall sleeve must be fitted flush with the internal wall face.
step
8
115mm MINIMUM HOLE
Q
Q
Make good at the internal wall face, leave the external wall face until later.
If the inner end of the sleeve sticks out into the cavity then, if desired, the wall sleeve can be trimmed back to the depth of the inner skin of the brickwork.
17
300mm MAX LENGTH
17
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
5
Flue Installation
Flue Duct (Standard or Long)
Mark the duct to length “S”+11mm then cut square and remove any burrs.
SECTION
step
2895
9
S+11mm
WALLPLATE /TEMPLATE
S
Terminal/Air Duct (Standard or Long)
Mark the duct to the length “S”+13mm then cut square and remove any burrs.
STANDARD 1METRE AND 2 METRE FLUE TERMINAL KFB 70 ONLY. 1 METRE AND 2 METRE FLUE TERMINAL KFB 60 ONLY
step
10
1m 2m FLUE TERMINAL
STANDARD FLUE TERMINAL KFB 60
S+13mm
18
220692C
18
WALLPLATE /TEMPLATE
S
Supplied By www.heating spares.co Tel. 0161 620 6677
Flue Installation
5
Air Duct/Terminal and Flue Duct Assembly
Locate the flue duct into the air duct/ terminal.
Place the sealant from the loose items pack onto the flue manifold.
Fully locate the flue manifold into the air duct/terminal and flue duct assembly as shown, ensuring correct alignment of the “TOP”s.
step
11
step
12
2896
SECTION
FLUE DUCT
AIR DUCT/TERMINAL ASSEMBLY
SEALANT
Drill two 3mm diameter holes through the air duct/terminal and flue manifold.
Secure the air duct/terminal to the flue manifold with the two self tapping screws supplied in the loose items pack.
It should now not be possible to remove the manifold.
step
13
AIR DUCT/TERMINAL AND FLUE DUCT ASSEMBLY
FLUE MANIFOLD
5mm
3mm DRILL SIZE
19
19
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
5
Flue Installation
Wall Thickness up to 300mm
Fit the self adhesive foam seal provided in the loose items pack around the air duct/terminal at the position shown.
SECTION
Wall Thickness over 300mm
step
14
step
15
FOAM SEAL
10mm
3039
Q
FOAM SEAL
Fix the self adhesive foam seal around the air duct/terminal such that, when installed, the seal will be within the wall sleeve.
If the boiler is not to be fitted for sometime cover the hole in the wall.
On all installations push the flue assembly into and through the wall sleeve and hole such that it is within the wall sleeve and does not stick out into the room. Do not push the flue assembly too far into the hole as it has to be pulled back into the boiler and secured to the keyhole fixings.
step
16
Q-25mm
Q
WALL SLEEVE
Note: That the foam seal is a tight fit in the wall sleeve, so either the wall sleeve will need to be rigidly fixed in the wall, that is, the cement has fully set or it can be held from the other side
20
whilst inserting the flue assembly.
220692C
20
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation
6
Boiler Preparation
Remove the front panel and place it on one side until required.
Remove and discard internal packing piece.
Remove the inner case by releasing the screws at the bottom and unhooking at the top, place on one side until required.
step
1
step
2
FRONT PANEL
3040
SECTION
Remove the violet and red electrical connections from the fan.
Break the air pressure switch tubes connections.
Remove the fan/flue hood assembly by removing the two screws one at each side.
WHEN FITTING A REAR FLUE
FOLLOW STEPS
step
4
step
t o t o&
8
step
17
step
step
21
INNER CASE
SCREW (3)
3
AIR PRESSURE SWITCH TUBES
RESET BUTTON
CLEAR
RED
WHEN FITTING A SIDE FLUE
FOLLOW STEPS
step
9
t o
step
21
ELECTRICAL CONNECTIONS
21
FAN/FLUE HOOD SCREW (2)
21
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
6
Rear Flue Boiler Installation
THE BOILER IS SUPPLIED FOR REAR FLUE OUTLET.
Installation
step
3041
4
TOP MOUNTING BRACKET
SECTION
Note: To reduce the total lifting weight remove the electrical control box and combustion chamber assembly by following the instructions in Section 6, step 18 and Section 10, steps 3,5,6,7,8 and 9.
Lift the boiler into position above the top mounting bracket, allow the boiler to slide down the wall onto the top and bottom wall mounting brackets.
Check the engagement by pulling the boiler forward at its base, there should be no forward movement.
When the boiler is correctly located secure it with the two screws.
BOTTOM MOUNTING BRACKET
step
5
22
Secure the flue assembly to the boiler, using the previously fitted dogpoint screws noting that these are keyhole fixings.
Make sure of the correct location of the flue to the boiler.
220692C
step
6
LOCATION LUG
KEYHOLE
22
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation
6
Fit fan/fluehood assembly by engaging the fan outlet extension over the flue manifold spigot.
Secure the fluehood assembly to the heat exchanger with the screws previously removed.
step
7
FAN OUTLET EXTENTION
3042
FLUE MANIFOLD SPIGOT
SECTION
If removed, refit the control box/ combustion chamber by reversing the instructions in Section 6, step 18 and Section 10, steps 3,5,6,7,8 and 9.
Reconnect the violet and red electrical connections to the fan, the polarity of the connections is not important.
Reconnect the air pressure switch tubes as shown.
step
8
ELECTRICAL CONNECTIONS
WHITE
RED
RED
AIR PRESSURE SWITCH TUBES
Continue at
step
17
23
23
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
6
Installation
Side Flue Boiler Installation
Remove the appropriate blanking plate on the casing and fit it to the rear flue
SECTION
outlet.
Remove the fan assembly from the fluehood assembly, by removing the two screws.
Partially refit the securing screws into the fan.
Turn the fan assembly to the required flue outlet direction.
step
9
step
10
REAR VIEW
GASKET
FAN REAR OUTLET EXTENTION
3043
BLANKING PLATE
FAN SECURING SCREW
FLUE HOOD ASSEMBLY
Fit the flue hood over the partially fitted securing screws in the special key hole slot sandwiching the gaskets and spacer between, take care not to damage the gaskets.
Turn the flue hood in the direction shown.
Remove and discard the fan rear outlet extension from the fan by releasing the clip.
Fit the fan side outlet extension, supplied in the loose items pack.
Secure with the clip previously removed.
step
11
GASKET
SPACER
GASKET
RIGHT HAND FLUE HOOD ASSEMBLY
FAN SECURING SCREW (4)
KEYHOLE SLOT
24
220692C
24
GASKETS AND SPACER
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation
6
Note: To reduce the total lifting weight remove the electrical control box and combustion chamber assembly by following the instructions in Section 6, step 18 and Section 10, steps 3,5,6,7,8 and 9.
Lift the boiler into position above the top mounting bracket, allow the boiler to slide down the wall onto the top and bottom wall mounting brackets.
Check the engagement by pulling the boiler forwards at its base, there should be no forwards movement.
step
12
FAN SIDE OUTLET EXTENSION
THIS END TO FAN
3044
RIGHT HAND FLUE HOOD ASSEMBLY
SECTION
LEFT HAND FLUE HOOD ASSEMBLY
When the boiler is correctly located secure it with the two screws.
step
13
TOP MOUNTING BRACKET
BOTTOM MOUNTING BRACKET
25
25
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
6
Installation
Secure the flue assembly to the boiler, using the previously fitted dogpoint screws noting that these are keyhole fixings.
Take the beige/grey sealant from the
SECTION
loose items pack and place firmly around the internal spigot of the flue manifold.
Make sure of the correct location of the flue and boiler.
If removed, refit the control box/ combustion chamber by reversing the instructions in Section 6, step 18 and Section 10, steps 3,5,6,7,8 and 9.
Loosely fit one extended brass fluehood/fan assembly screw to the heat exchanger on the side that the flue exits. Slide the fluehood/fan assembly flange under this extended brass screw whilst turning the assembly to enable engagement of the fan outlet extension onto the flue manifold spigot.
step
14
step
15
3045
BEIGE/GREY SEALANT
FAN OUTLET EXTENTION
EXTENDED BRASS FLUE HOOD FAN ASSEMBLY SCREW
26
After fitting the fan outlet extension to the spigot smooth the sealant over the joint.
When correctly located, secure the assembly by fitting the other extended brass screw and tighten both down.
Reconnect the violet and red electrical connections to the fan, the polarity of the connections is not important.
Reconnect the air pressure switch tubes.
step
16
FLUE HOOD/ FAN ASSEMBLY
FLUE MANIFOLD SPIGOT
ELECTRICAL CONNECTION(S)
RED
AIR PRESSURE SWITCH TUBES
CLEAR
FAN OUTLET EXTENSION
220692C
26
Supplied By www.heating spares.co Tel. 0161 620 6677
Installation
6
Water System Connection
Connect the boiler to the water system using the fittings provided in the loose items pack.
The flow connection is on the right.
Gas Supply Connection
Remove the electrical controls box cover.
step
17
step
18
RETURN
ELECTRICAL CONTROL BOX COVER
SECURING SCREW (4)
UNION NUT
OLIVE
FLOW
3046
SECTION
Connect the gas supply to the gas service cock on the boiler making sure it is turned off.
Check for gas soundness up to the cock, in accordance with the current issue of BS6891.
step
19
27
INDICATOR SLOT (SHOWN OFF)
27
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
6
Installation
Electrical Connection and System Controls
SECTION
Cable Connection
The boiler must be earthed. The incoming cables should be routed
from the right hand side of the boiler. Remove the terminal connection plug
as shown.
Connect the incoming supply and remote controls cables through the restraining glands.
step
20
step
21
The electrical installation must comply with the current
issue of BS7671 and any local regulations which apply.
All controls and connections must be of the approved type.
PUMP STRAIN RELIEF GLAND
TERMINAL PLUG CONNECTION
TERMINAL CONNECTION PLUG MAINS AND REMOTE CONTROLS WIRING
RED LINK
LONGER EARTH LEADS
MAINS AND SWITCH LIVE STRAIN RELIEF GLAND
2905
The earth conductor must be of a greater length so that if the cable is strained the earth is the last to become disconnected.
Test the insulation resistance of the mains cable to earth.
Test for polarity of the mains cables. Check earth continuity and short circuit
of cables. Replace the terminal connection plug. Secure the cables in the plastic clips.
SL
RED LINK
5 6
7 8 9
10
N
11
L
12
G/Y
G/Y
BLUE
BROWN
BLUE
BROWN
G/Y
CIRCULATION PUMP
E N
240V ~ 50Hz PERMANENT
L
MAIN SUPPLY
N
FUSED AT 3AMP
L
E
Remove RED link between 7 and 12 (switch live) when fitting a time control etc.(if no switch is fitted the pump will run continuously)..
28
220692C
28
RED LINK
Supplied By www.heating spares.co Tel. 0161 620 6677
Completion and Commissioning
7
System Commissioning - All Systems
Sealed Water Systems Only
Commissioning should be carried out by a competent person in accordance with the current issue of BS6798. Make sure that the system has been thoroughly flushed out with cold water without the pump in place. Refit the pump, fill the system with water, making sure that all air is properly vented from the system and pump.
Clear any airlocks and check for water soundness.
Flush the whole system without the pump in place. Refit the pump and fill the system until the pressure gauge registers 1.5bar (21.5lbf/in2). Clear any airlocks and check for water soundness.
Check the operation of the safety valve, by allowing the water pressure to rise until the valve opens. The valve should open within +/-0.3bar (+/-4.3lbf/in2) of 3bar (42.6lbf/in2). Where this is not possible conduct a manual check and test.
Release cold water to initial system design pressure.
SECTION
The set pointer on the pressure gauge should be set to the initial design pressure.
If air is present in the system, this may, in certain circumstances, cause the overheat thermostat to trip. If this occurs advise the user to operate the control thermostat on a low setting until all air has been expelled.
29
29
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
7
Completion and Commissioning
Initial Lighting and Testing and Adjustment
Refit the inner case, by hooking it over
SECTION
at the top and securing with the screws previously removed, at the bottom.
Make sure that the case is correctly fitted and sealed.
Identify the controls by reference to the diagram.
Check that the boiler is isolated from the electrical supply.
Make sure that the boiler thermostat is turned to the “Off” position.
Turn the gas service cock “On”, the indicator slot to be horizontal.
The pilot gas rate is preset and MUST NOT be adjusted, see Servicing, Step
15.
BOILER THERMOSTAT CONTROL KNOB (Shown in the OFF position)
VIEWING WINDOW
GAS SERVICE COCK
3047
INDICATOR SLOT (SHOWN OFF)
NOTE: Do not adjust any other setting screws.
For future reference stick the self adhesive arrow indicator from the loose items pack, to the data label against the rating that the boiler is going to be set to.
Loosen the main burner pressure test point screw and fit a suitable pressure gauge.
Make sure that any remote controls are calling for heat.
Switch on or connect the electrical supply to the boiler and heating system.
Warning. The gas valve and fan operate on MAINS voltage, terminals will become “LIVE”.
PRESSURE TEST POINT
30
220692C
30
Supplied By www.heating spares.co Tel. 0161 620 6677
Completion and Commissioning
7
Testing - Electrical
Checks to ensure electrical safety should be carried out by a competent person.
In the event of an electrical fault after installation of the system, preliminary electrical system checks as below should be carried out.
1. Test insulation resistance to earth of mains cables.
2. Test the earth continuity and short circuit of all cables.
3. Switch on the electrical supply to the boiler and test the polarity of the mains supply.
Turn the boiler thermostat knob fully clockwise to the maximum setting.
The lighting sequence is automatic, as follows:
The fan operates The spark ignition operates The pilot solenoid opens
SECTION
The pilot burner lights The ignition spark stops The main solenoid opens -
and after a short period of time the main burner will light, view through window.
The main burner will remain alight until switched off, either by the boiler thermostat or a remote system control.
(When the boiler switches “Off”, both the pilot and main burner go out. The automatic lighting sequence will operate again when heat is required).
31
31
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
7
Completion and Commissioning
Testing - Gas
With the boiler on proceed as follows: Test for gas soundness around the boiler
gas components using a suitable leak detection fluid, in accordance with the current issue of BS6891.
SECTION
Check the main burner gas pressure at least 10 minutes after the burner has lit, refer to Data Label.
If necessary, adjust the gas pressure to obtain the required setting (screw at rear of the gas valve) turning anti-clockwise, viewed from the front, to decrease the pressure.
Should any doubt exist about the gas rate, check it using the gas meter test dial and a stop watch, at least 10 minutes after the burner has lit, making sure that all other gas burning appliances and pilot lights are off.
Space Saver K.F.B 60 Approx. Gas Rate
min med max
m3/h 1.8 1.95 2.1 ft3/h 64 69 74
3048
MAIN BURNER ADJUSTMENT SCREW (8mm ACROSS FLATS)
Space Saver K.F.B 70 Approx. Gas Rate
min med max
m3/h 2.2 2.4 2.5 ft3/h 78 83 89
The gas rates are for guidance only, dependent on the heat setting.
Turn the boiler thermostat knob fully anti-clockwise to “Off”. Remove the pressure gauge from the test point and refit the screw, making sure that a gas tight seal is made.
When the boiler thermostat is turned to the “Off” position, by hand, wait at least 30 seconds before turning “On” again.
There may be an initial smell given off from the boiler when new, this is quite normal and it will disappear after a short period of time.
Refit the electrical controls box cover with the four screws previously removed.
8mm SPANNER
DO NOT ADJUST
Note: The neon indicator lights on the printed circuit board are an aid to fault finding, for details refer to Section 11.
32
220692C
32
Supplied By www.heating spares.co Tel. 0161 620 6677
Completion and Commissioning
7
Heating System
Check that all remote controls are working as required.
Allow the system to reach maximum working temperature and examine for water leaks. The boiler should then be turned off and the system drained off as rapidly as possible whilst still hot.
SECTION
Refill the system, vent and again check for water soundness.
For sealed systems adjust to initial design pressure. Any set pointer on the pressure gauge should be set to coincide with the indicating pointer.
The overrun thermostat will keep the pump running when the boiler shuts down, so long as the temperature within the boiler is above a predetermined level, providing the control thermostat is set at maximum.
When commissioning the system the boiler should be fired with the bypass fully closed on full service, that is, central heating and domestic hot water. The system should then be balanced, adjusting the pump and lockshield valve as necessary. Having achieved a satisfactory condition, operate the boiler with the bypass closed on minimum load, normally central heating only with one radiator operating in the main living area. The valve should be opened gradually to achieve the appropriate flow rate as quoted in Section 2. If necessary readjust the pump.
Operational Checks
Under NO circumstances should this valve be left in the FULLY CLOSED position.
Adjust the boiler thermostat and any system controls to their required settings.
Do not attempt to adjust the thermostat calibration. Operate the boiler again on full service and check
that the balancing is satisfactory, making further adjustments as necessary to the system, radiator valves and bypass.
On open vented systems there must be no pumping over of water or entry of air at the vent above the feed and expansion cistern.
If thermostatic radiator valves are fitted care must be taken to ensure that there is an adequate flow rate when the valves are closed. Refer to the current issue of BS7478 on the use of thermostatic radiator valves.
33
33
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
8
Front Panel Assembly
Note. The front panel assembly has been designed with a variable adjustment to suit a range of available kitchen furniture, 700mm-728mm high by 285mm-315mm deep and will also suit installations in a cupboard.
SECTION
It is delivered preset to 700mm high by 285mm deep.
Measure the height of the cupboard or compartment, “H”.
Adjust the front panel height “H” as necessary.
step
1
step
2
H = 700 to 728mm
W = 470mm
TOP HOLE FIXING 700 to 714mm
W
D = 285 to 315mm
3059
H
BOTTOM HOLE FIXING 714 to 728mm
Measure the depth of the cupboard or compartment, “D”.
Adjust the front panel top mounting bracket as necessary.
Slide the right hand side cover plate (supplied in the fittings pack) into position.
step
3
BOILER MOUNTING WALL
ADJUSTMENT SCREW
H
D
'MINUS' 1mm
34
220692C
34
FRONT PANEL TOP MOUNTING BRACKET
Supplied By www.heating spares.co Tel. 0161 620 6677
Front Panel Assembly
8
Locate the front panel assembly.
Engage the bottom front panel assembly slide/catch and adjust as necessary.
step
4
step
5
2908
SECTION
ADJUSTMENT SCREW
User Information
User Information
Instruct and demonstrate the efficient and safe operation of the boiler, heating system and if fitted, the domestic hot water system.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Advise the user, to ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough.
It is the law that servicing must be carried out by a competent person.
SLIDE ASSEMBLY
CATCH
9
SECTION
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
Reminder, leave these instructions with the user.
35
35
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
10
Servicing
To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in
SECTION
general once a year should be enough. It is the Law that servicing must be
carried out by a competent person. BEFORE STARTING A SERVICE
REMOVE THE FRONT PANEL as shown, for Access, ISOLATE THE BOILER FROM THE ELECTRICAL SUPPLY AND TURN THE GAS SUPPLY OFF AT THE GAS SERVICE COCK, INDICATOR SLOT TO BE VERTICAL.
Unless stated otherwise, all parts are replaced in the reverse order to removal.
After completing any servicing always test for gas soundness and if necessary carry out functional checks of controls.
step
1
step
2
step
3
SECURING SCREW(4)
3049
FRONT PANEL
ELECTRICAL CONTROLS BOX COVER
INDICATOR SLOT (SHOWN OFF)
36
Access
Remove the electrical control box cover by removing the four screws.
Note: As an aid to Servicing the air pressure switch tube connection can be used to obtain a products of combustion reading.
Follow Steps 1, 2 and 4. Remove the RED tube from the
connection on the air pressure switch and insert the analyser probe into the tube.
Switch on the electrical supply to operate the fan and turn on the gas supply.
On completion of the test switch off the electrical and gas supplies and reconnect the red tube to the air pressure switch.
Remove the inner case, by unscrewing at the bottom and unhooking at the top.
step
4
GAS SERVICE COCK
INNER CASE
SCREW (3)
step
5
220692C
36
Supplied By www.heating spares.co Tel. 0161 620 6677
Servicing
10
Cleaning the Heat Exchanger
Slacken the flue hood by loosening the extended brass screws at the left and right hand sides.
Remove the split pin and thermostat phials from the pocket, taking care not to kink the capillaries.
When replacing the phials make sure that they are still covered with heat sink compound.
step
6
step
7
FAN/FLUE HOOD SCREW (2)
PHIAL POCKET
3050
SECTION
SPLIT PIN
OVERHEAT CUT-OFF PHIAL
Disconnect the air pressure switch tubes.
step
8
THERMOSTAT PHIAL
RED
AIR PRESSURE SWITCH TUBES
WHITE
37
37
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
10
Servicing
Disconnect the gas service cock at the union connection.
Disconnect the electrical connection plug by pulling it out from the right hand side of the control box.
SECTION
Remove the violet and red electrical connections on the fan and cable from the securing clips.
Remove the electrical control box/ combustion chamber cover assembly by removing the ten securing screws, withdraw the complete assembly.
Slacken the air pressure pipe union and turn through 90o.
step
9
CLIPS
FAN ELECTRICAL CONNECTIONS
AIR PRESSURE PIPE UNION
SECURING SCREWS (10)
ELECTRICAL CONNECTIONS PLUG
3051
Remove the rear flueway cleaning plate.
Remove the heat exchanger front cover, by removing the eight securing screws.
Place a sheet of paper in the base of the combustion chamber.
Remove the three baffles.
step
10
step
11
GAS SERVICE COCK UNION CONNECTION
REAR FLUEWAY CLEANING PLATE
SECURING SCREW (6)
HEAT EXCHANGER FRONT COVER
38
220692C
38
BAFFLES (3)
Supplied By www.heating spares.co Tel. 0161 620 6677
Servicing
10
The heat exchanger can now be cleaned with a suitably sized semi­stiff brush, using the cleaning plate, as shown to protect the rear insulation panel.
DO NOT USE A BRUSH WITH METALLIC BRISTLES.
Remove the paper and debris from the combustion chamber.
Correctly refit the baffles previously removed, each is marked TOP on its upper face.
Refit the heat exchanger front cover. Tighten down the fan flue screws. Refit the cleaning plate.
Main Burner
Remove the main burner by releasing the two securing nuts as shown. Brush or vacuum away any deposits, ensure that the flame ports are clean.
step
12
step
13
3108
50mm
SECTION
380mm MIN.
20mm
40mm
SEMI-STIFF NYLON BRISTLES CLEANING BRUSH
CLEANING PLATE
PILOT BURNER SHIELD
DO NOT USE A BRUSH WITH METALLIC BRISTLES.
Make sure that the pilot burner shield is located between the burner bracket as shown.
Main Injector
The main injector can be removed and cleaned.
When cleaning the injector do not use a wire or sharp instrument on the hole.
BURNER BRACKET
INJECTOR
step
14
VIEW OF MAIN BURNER INJECTOR WITH BURNER REMOVED
39
SECURING NUTS
220692C
39
Supplied By www.heating spares.co Tel. 0161 620 6677
10
Servicing
Pilot Burner, Ignition Electrode and Pilot Injector
SECTION
Pull off the ignition lead at the electrode (covered with a silicone rubber sleeve).
Unscrew the tubing nuts at both ends releasing the pilot pipe.
Remove the pilot burner securing screws to release the pilot burner and electrode assembly.
Clean the pilot burner and electrode. Remove the pilot injector by
unscrewing it from the pilot burner, clean it by blowing through it.
When refitting take care not to damage the electrode and check that the spark gap is as shown.
step
15
IGNITION LEAD
SILICONE RUBBER SLEEVE
PILOT TUBING NUT
4781
PILOT BURNER ASSEMBLY SECURING SCREW (2)
PILOT PIPE
PILOT TUBING NUT
15-20mm
SPARK GAP
3.5-4.5mm
PILOT BURNER
40
220692C
40
PILOT INJECTOR
Supplied By www.heating spares.co Tel. 0161 620 6677
Fault Finding
11
Electrical
Important. On completion of the service/fault finding task which has required the breaking and remaking of the electrical connections the earth continuity, polarity, short circuit and resistance to earth checks must be repeated using a suitable multimeter.
Refer to Fault Finding, Wiring and Functional Flow diagrams.
Electrical Supply Failure
Failure of the electrical supply will cause the burner to go out. Operation will normally resume on restoration of the electrical supply. If the boiler does not relight after an electrical supply failure the overheat device may need resetting.
Remove the front panel as Section 1, Step 1 and press the reset button on top of the electrical controls box cover, see diagram at Step 3. If the cut off operates at any other time press the reset button and the burner should relight. If the fault persists refer to Fault Finding Chart.
L
THERMOSTAT
SPARK ELECTRODE
FUSE TYPE F1 1 AMP
KEY
bk BLACK br BROWN b BLUE v VIOLET p PURPLE
PUMP
OVERRUN
(L)
11
7
p
9
w
rv
AIR PRESSURE SWITCH
brbr
9
8
br b
PUMP
br
b
O/H CUTOFF
y
CONTROL STAT
FAN
r
bk
y
w WHITE r RED y YELLOW
br
7
LINK
6
2
*
12
3
3
(N/C)
r
(N/O) (C)
1
RED
(SL)
2914
SECTION
8
b
10
(N)
10
b
(N)
b
y
RED LINK may have been removed
to fit remote controls.
*
41
br
PILOT SOLENOID
bk
MAIN SOLENOID
AIR PRESSURE SWITCH CONNECTIONS MAIN TERMINAL STRIP CONNECTIONS CONTROL THERMOSTAT CONNECTIONS PRINTED CIRCUIT BOARD CONNECTIONS
b
b
10
10
(N)
b
(N)
N
41
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
11
Fault Finding
SECTION
AIR PRESSURE
SWITCH
C
NC NO
123
FAN
g/y
CHASSIS
EARTH
KEY:
b - BLUE bk - BLACK br - BROWN
v
r
r - RED g/y - GREEN/YELLOW
- MAIN TERMINAL STRIP
- CONTROL THERMOSTAT AIR PRESSURE SWITCH
-
NUMBER = BECK LETTER = YAMATAKE
p - PURPLE v - VIOLET w - WHITE y - YELLOW
3109
OVERHEAT
CUT-OFF
CONTROL
THERMOSTAT
y
p
7
w
986
3
br
r
y
CHASSIS
EARTH
r
v
g/y
POST
42
r
y
PRINTED CIRCUIT
BOARD
SPARK
ELECTRODE
FUSE
TYPE F1
1 AMP
bk
GAS
VALVE
bk
br
g/y
b
g/y
CIRCULATION
5 6 7 8
9 10 11 12
b
br
g/y
SWITCHED
LIVE
PUMP
g/y
b
br
b
br
g/y
240V~50Hz
PERMANENT
E N
L
N
L
E
MAINS SUPPLY
Remove RED link
FUSED 3 AMP
between 7 and 12
when fitting a time
control etc. (If no
switch is fitted the
pump will run
continuously).
220692C
42
Supplied By www.heating spares.co Tel. 0161 620 6677
Fault Finding
Neon Indicators - An Aid to Fault Finding
THE NEON INDICATORS ARE AN AID TO FAULT FINDING ONLY. FAILURE OF ANY OF THE NEON INDICATORS DOES NOT
WARRANT THE REPLACEMENT OF AN OTHERWISE SATISFACTORY PRINTED CIRCUIT BOARD (PCB)
Is neon 1 lit? Fault with mains supply or PCB fuse.
Overheat cut off device tripped or thermostat, overheat cut off device faulty - see detailed fault finding chart.
Air flow proving fault ­that is fan or air pressure switch ­see detailed fault finding chart.
Ignition, pilot or flame proving fault ­see detailed fault finding chart.
Gas valve / harness problem - see detailed working? fault finding chart.
Is neon 2 lit?
Is neon 3 lit?
Is neon 4 lit?
Is main burner operating?
System satisfactory
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
11
4754
SECTION
43
NEON INDICATORS (4)
3054
43
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
11
Before detailed checking of electrical components ensure that remote controls are calling for heat. Check the gas supply is free of obstructions and
purged of air. Check the overheat cutoff has not operated. Isolate the electrical supply and physically check ALL cables, connections and the printed
Is neon 1 lit?
YES
SECTION
Is neon 2 lit?
YES
Fault Finding
circuit board fuse. Check the air tubes to the air pressure switch. Switch on the electrical supply and check for correct polarity.
NO
NO
YES
Turn the boiler thermostat to its maximum setting. Also check fuses.
Is there 240V~ between 12 and 10 and between 11 and 10 ?
NO
YES
Is there 240V~ between yellow connection on overheat device and 10 ?
NO
YES
Is there 240V~ between 6 on thermostat and 10 ?
NO
Correct power supply problem.
Check overheat reset. If satisfactory replace overheat device.
Replace thermostat.
4780
Is neon 3 lit?
YES
Is neon 4 lit?
YES
NO
NO
Is there 240V~ between 1 on air pressure switch and 10 ?
NO
Check yellow cable between printed circuit board and air pressure switch. If satisfactory replace printed circuit board.
YES
Is there 240V~ between 3 on air pressure switch and 10 ?
NO
Replace air pressure switch.
YES
NO
Does fan run?
YES
Replace fan.
Is there 240V~ between motor connections on fan?
YES
Isolate electrical supply test fan harness continuity. If satisfactory replace printed circuit board.
YES
Does fan Hunt? Replace printed circuit board.
NO
Is there 240V~ between 2 on air pressure switch and 10 ?
NO
Inspect air tubes for leaks, kinks and correct fitting. If satisfactory replace faulty air pressure switch.
YES
Is there 240V~ between pilot gas valve solenoid blue and brown connections?
NO
Isolate supply, test harness continuity. If satisfactory replace printed circuit board.
YES
NO
Is there a spark at pilot burner?
YES
Does pilot light?
YES
With pilot lit does spark stop?
YES
Does main burner light?
YES
44
220692C
Is there 240V~ between main gas valve solenoid black and blue cables?
NO
YES
Replace gas valve.System satisfactory.
44
NO
NO
NO
NO
Check lead continuity and inspect electrode and lead for damage.
Check for pilot jet blockage, incorrect electrode adjustment. If satisfactory replace gas valve.
Inspect electrode lead / connection for poor contact. Check electrical supply polarity and correct if necessary. If satisfactory replace printed circuit board
Isolate supply, test harness and replace as required.
AIR PRESSURE SWITCH
MAIN TERMINAL STRIP
CONTROL THERMOSTAT
Supplied By www.heating spares.co Tel. 0161 620 6677
Fault Finding
11
Pump overrun Operation
the pump overrun will keep the pump running to allow the boiler to cool down after which it will stop, providing the remote controls are NOT
The Control Thermostat has a pump overrun facility built into it, when the Control Thermostat is set at maximum only,
calling for heat.
Fault Finding
Turn boiler Control Thermostat to maximum, with the remote controls calling for heat,
does the pump continue to run after the appliance has shut down on boiler control thermostat?
YES
Turn off remote controls, does the pump stop after a short period of time
YES
NO NO
Is there 240V~ on 11 ?
Faulty Pump overrun. Replace Control Thermostat
NO
Faulty permanent live feed. Replace.
YES
4756
SECTION
Pump overrun in order.
Is there 240V~ on 9 connection on thermostat?
YES
Is there 240V~ on 9 for pump?
YES
NO
NO
Faulty connections between thermostat and terminal strip. Repair.
Faulty internal wiring between terminal block and thermostat. Repair.
Faulty pump / wiring ? Replace or repair as necessary.
45
45
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
12
Replacement of Parts
Replacement of parts must only be carried out by a competent person.
BEFORE REPLACING ANY PARTS ISOLATE THE BOILER FROM THE ELECTRICAL SUPPLY
AND TURN THE GAS SUPPLY OFF AT THE GAS COCK INDICATOR SLOT TO BE VERTICAL.
Unless stated otherwise, all parts are replaced in the reverse order to removal.
After replacing any parts always test for gas soundness and if necessary carryout functional checks of controls.
SECTION
Pilot Burner/Injector and Ignition Lead
Gain access as Section 10, steps 1 to 4. Pull off the ignition lead at the
electrode (covered with a silicone rubber sleeve) and printed circuit board.
Unscrew the tubing nuts at both ends releasing the pilot pipe.
Remove the pilot burner by unscrewing the two securing screws as shown.
The pilot burner or injector can now be replaced.
Electrode
IGNITION LEAD
ELECTRODE SECURING SCREW
SILICONE RUBBER SLEEVE
ELECTRODE
PILOT TUBING NUT
PILOT PIPE
PILOT BURNER INJECTOR
PILOT BURNER ASSEMBLY SECURING SCREW (2)
3055
46
Gain access as Section 10, steps 1 to 4. Pull off the ignition lead at the
electrode. Remove the electrode securing screw. The electrode can now be replaced.
Printed Circuit Board (PCB)
Gain access as Section 10, steps 1 to 4. Do not disturb the heat shield earth
connector. Disconnect the three electrical plugs,
ignition lead, the earth and mains cables.
Pull the board away from the supports. When fitting the replacement make
sure that it is correctly located on to the securing posts and make sure that all the connections are remade.
IGNITION LEAD
PILOT TUBING NUT
HEAT SHIELD EARTH LEAD
ELECTRICAL PLUGS (3)
SECURING POST
220692C
46
Supplied By www.heating spares.co Tel. 0161 620 6677
Replacement of Parts
12
Control Thermostat and Overheat Cutoff
Gain access as Section 10, steps 1 to 5.
Control Thermostat:
Pull off the control thermostat knob, remove the two screws securing the thermostat to the control box.
Remove the electrical connections from the thermostat body.
Overheat Cutoff:
Remove the nut securing the overheat cutoff, withdraw the assembly.
Control Thermostat/ Overheat Cutoff
PHIAL POCKET
SECURING SCREW(2)
SPLIT PIN
OVERHEAT CUTOFF PHIAL
YELLOW
PURPLE
BROWN
RED
YELLOW
CONTROL KNOB
WIRING DIAGRAM
7
689
3
3056
SECTION
Now remove the split pin and then the thermostat phials from the pocket.
Make sure that the thermostat capillaries are correctly routed and the phials are securely fitted into the pocket.
Note: The position of the two phials should be as shown when replacing in the pocket.
Reconnect the electrical leads as shown.
When replacing either of these thermostats make sure that the phial is smeared with the heat sink compound supplied with the replacement.
THERMOSTAT PHIAL
SEAL
CUT OUT
SECURING NUT
WIRING
DIAGRAM OVERHEAT CUTOFF
YELLOW
PURPLE
47
OVERHEAT CUTOFF
WHITE
BROWN
RED
YELLOW
47
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
12
Replacement of Parts
Air Pressure Switch
Note: Alternative types of Air Pressure Switches may be fitted.
Gain access as Section 10 steps 1 to 4.
SECTION
Remove the air pressure tubes and electrical connections, release the screws and nuts, remove the switch.
When fitting the replacement make sure that all the plastic tubes and electrical connections are made as shown.
SECURING SCREW (2)
RED
SECURING SCREW (2)
BLACK
YELLOW
RED AIR PRESSURE TUBE
CLEAR AIR PRESSURE TUBE
YAMATAKE
BECK
RED AIR PRESSURE TUBE
3057
Gas V alve
Gain access as Section 10, steps 1 to 4. Disconnect all electrical leads from the
gas valve. Disconnect the pilot pipe at the pilot
burner. Undo the four screws at the outlet
manifold and disconnect the gas service cock union.
Transfer the half union of the gas service cock to the inlet of the replacement gas valve. Also transfer the pilot supply pipe. Use a little thread sealant on the external threads to ensure gas soundness.
Fit the new valve, take care not to damage the “O” ring.
BLACK
PILOT BURNER
PILOT PIPE
SECURING SCREW (4)
YELLOW
EARTH
CONNECTOR
RED
GAS SERVICE COCK UNION
BLUE
BLACK
G/Y
CLEAR AIR PRESSURE TUBE
ELECTRICAL LEADS
BROWN
It will be necessary to purge the pipework and valve before relighting, check gas pressure settings, refer to Section 7.
48
220692C
48
WIRING DIAGRAM
"O" RING
Supplied By www.heating spares.co Tel. 0161 620 6677
Replacement of Parts
12
Fan
Gain access as Section 10, steps 1, 2 and 5.
Remove the electrical connections and disconnect the air tubes.
Remove the fluehood/fan assembly screws and withdraw the assembly.
Turn the flue hood over and release the two securing screws as shown.
Remove the sealant from the fan outlet and manifold.
Take the beige/grey sealant supplied with the replacement fan and place firmly around the internal spigot of the flue manifold.
After fitting the fan outlet to the spigot smooth the sealant over the joint.
step
1
3058
ELECTRICAL CONNECTIONS
SECTION
EARTH
CONNECTION
AIR PRESSURE SWITCH TUBES
FAN/FLUEHOOD SCREW (2)
Make sure that when fitting the replacement fan to the flue hood that it is the correct way round for connection to the flue, refer to the diagram in Section 6, also steps 10 and 11.
Make sure that the earth connection is remade onto the new fan assembly.
The polarity of the other connections is not important.
step
2
SECURING SCREW (2)
Main Burner
Main Burner Injector
Gain access as Section 10, steps 1 to 5 and 9. Remove burner as in Section 10, step 13.
Gain access as Section 10, steps 1 to 5 and 9. Remove the injector as in Section 10, steps 13 and 14.
49
49
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
12
Replacement of Parts
Insulation
Gain access as Section 10, steps 1 to
10.
SECTION
Combustion Chamber Sides and Rear:
Remove the baffles. Remove the insulation and fit the
replacement parts making sure they are fitted as shown.
COMBUSTION CHAMBER SIDE
step
1
COMBUSTION CHAMBER REAR
3107
SECURING SCREW (2)
BAFFLE
70 ILLUSTRATED
Heat Exchanger Front Cover Panel:
Remove panel, Section 10, step 10. Upper Insulation: push up and pull out
to remove. Lower insulation: remove the securing
screws and angle and remove the insulation.
When refitting either, make sure that it is fitted as shown.
Viewing Window
step
2
COMBUSTION CHAMBER FRONT PANELS
SECURING SCREW (2)
Gain access as Section 10, steps 1 to 4.
SECURING SCREW (2)
Remove the two screws and then the window.
50
220692C
When replacing take care not to damage the gasket.
50
Supplied By www.heating spares.co Tel. 0161 620 6677
Spare Parts
13
Part Identification
The key number in the diagram and the list will help to identify the part.
Ordering
When ordering any spare parts please quote the part number and description from the list together with the model name and serial number.
If ordering from the local gas undertaking also quote the GC number of the appliance and part.
8
7
14
12
5 6B
4760
1
2
10
11
3
SECTION
9
4
6A
13
Key Glow-worm Description GC No.
No Part No
1 800165 Gas valve assembly, inc item11 313 300 2 202539 Thermostat 397 893 3 202538 Overheat thermostat 397 894 4 900817 Printed circuit board 313 301 5 440073 Fan assembly (60) - special 397 987 5 800238 Fan assembly (70) - special 313 397
6A 202135 Air pressure switch - Yamatake 313 303
6B 440165 Air pressure switch - special 313 391
7 203428 Pilot assembly - inc. 8 and 14 313 304 8 800187 Pilot injector - special 313 392 9 205701 Main injector (60) - special 313 393
9 205702 Main injector (70) - special 313 394 10 440108 Control knob - thermostat - assembly 313 306 11 208040 “O” ring - gas valve 334 592 12 202015 Fuse to BS4265 sheet 2. type F1A 334 750 13 WX1800 Ignition lead 313 307
14 800188 Electrode - special 313 395
51
51
220692C
Supplied By www.heating spares.co Tel. 0161 620 6677
SECTION
52
Because of our constant endeavour for improvement details may vary slightly from those given in these instructions.
220692C
52
Loading...