Glow-worm Opulence 2 BBU, Opus 2 BBU Installation & Servicing Instructions Manual

Page 1
Supplied By www.heating spares.co Tel. 0161 620 6677
221098C.01.99
Installation and Servicing
Instructions
T o be left with the user
3914 S
G.C.37 314 15
a specially designed
G.C.37 314 14
For use with
3915 S
References in these instructions to British Standards and Statutory
Regulations/Requirements apply only to the United Kingdom.
One Contact Local Service
For Ireland the rules in force must be used.
This is a Cat I
Customer Services: Tel: (01773) 828100 Fax: (01773) 828070
Appliance
2H
BS 6332 BS 5258
Hepworth Heating Ltd.,
Nottingham Road, Belper, Derbyshire. DE56 1JT
General/Sales enquiries :
Tel: (01773) 824141 Fax: (01773) 820569
Page 2
Supplied By www.heating spares.co Tel. 0161 620 6677
1 G e n e r a l
If this fire front is to be fitted to a Glow-worm back boiler WITHOUT a combustion products discharge safety device please read the supplementary instructions at the back of this booklet.
The instructions consist of three parts, Installation and Servicing Instructions for the Back Boiler Unit, Installation and Servicing Instructions for the Fire Front and Instructions for Use, including the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
1 General Notes and Information
This Glow-worm gas fire front is to be used with a specially designed Glow-worm Back Boiler Unit only.
This fire front and back boiler are NOT suitable for fitting to a precast flue.
The fire front is delivered packed in two cardboard cartons, which together contain all the parts necessary for the installation of the fire front.
If the back boiler and fire front are to be installed at the same time please read both sets of installation instructions before starting.
Wherever possible, all materials, appliances and components to be used shall comply with the requirements of applicable British Standards.
Where no British Standards exist, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
1.1 Important Notice
This fire front is for use only on G20 gas. This fire front is fitted with a safety device which will
shut it down if there is a lack of oxygen. If the fire shuts down frequently for no apparent reason the first things to be checked are the chimney and the air inlets into the room. An additional cause could be that the filter, in the gas tap has become blocked. Any problems found must be put right, by a competent person, before the fire is used again.
Sheet Metal Parts
WARNING. When installing or servicing this fire front care should be taken when handling metal parts (components), to avoid any possibility of personal injury.
1.2 Statutory Requirements
The installation of this fire front must be carried out by a competent person, in accordance with the current issue and relevant requirements of:-
Manufacturer’s instructions, supplied. The Gas Safety (Installation and Use) Regulations, as
amended, The Building Regulations, the Local Gas Undertaking, The Building Standards (Scotland) Regulations (applicable in Scotland), The Health and Safety at Work Act, Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice:-
BS1251, BS5440 Part 1 and 2, BS5871, BS6891, BS7671.
Manufacturer’s notes must not be taken as overriding statutory requirements.
CE Mark
The CE mark on this appliance shows compliance with:-
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
2221098C
Page 3
Supplied By www.heating spares.co Tel. 0161 620 6677
289mm
1 G e n e r a l
FLAT AREA
FIRE FIXING FACE
C
L
327mm
327mm
3916 BBU S
289mm
690mm
339mm 351mm 351mm 339mm
1.3 Data
Gas connection- from the service cock Total weight - 49kg Injector - upper Bray 18/180
- lower Bray 18/320
Burner pressure setting
- cold 13.0mbar 5.18in wg
- hot 13.2mbar 5.28in wg Heat input - gross - 6.7kW 22,750Btu/h Heat output - nominal - 4.03kW 13,670Btu/h Fire serial No. - On chassis - visible when front
casting is removed
Data label - Inside of right hand side panel The fire front burner is lit by means of an electronic
spark generator unit.
Diagram 1.1
All dimensions are given in millimetres (except as noted).
3
221098C
Page 4
Supplied By www.heating spares.co Tel. 0161 620 6677
150mm
1 G e n e r a l
C
L
445mm 445mm
150mm 150mm
MAXIMUM SHELF DEPTH
3917 S
150mm
840mm
FLAT AREA FIRE FIXING FACE
1.4 Fire Front Location
This fire front can only be fitted to a Glow-worm 45/2 or 56/2 back boiler unit which itself has been installed in accordance with the Glow-worm Installation and Servicing Instructions.
The back boiler air duct acts as a support for the fire front.
The top of the fire front must be secured to the vertical fire front fixing wall face. This wall face may be a chimney breast or surround, see diagram 1.2.
840mm
Diagram 1.2
1.5 Clearances
Restrictions must not be placed around the assembled fire front, see diagram 1.2.
A shelf or surround of a maximum depth of 150mm may be fitted, provided clearances are as shown in diagram 1.2. However, for every additional 25mm extra above the fire front the depth of the shelf may be increased by 25mm.
Combustible furniture or materials must not be placed closer than 1metre in front of the fire front.
The fire front flue spigot projects into the back boiler flue collector assembly.
The gas supply is taken from the back boiler gas service cock.
The back boiler must be correctly positioned in the builder’s opening as the fire front is located by connection to it.
4221098C
Page 5
Supplied By www.heating spares.co Tel. 0161 620 6677
2 T y p e s o f I n s t a l l a t i o n a n d F l u e
Note. Refer to Section 2 in the Back Boiler Installation Book before starting.
2.1 With Hearth
A fireproof hearth under the fire front must have the minimum dimensions as shown in diagram 2.1.
2.2 With Surround
See diagram 2.2. The fire front casing should cover the opening.
A wider opening will require any opening left to be covered with a non-combustible finished material, see diagram 2.3.
The surround must have a minimum clear, flat area as shown in diagram 1.2. Any projection on the surround must be outside this area.
Any combustible material on the fire front fixing face area of the surround must be removed, see diagram 2.3. This area, to the depth removed, should then be rendered with a sand/cement mixture.
2.4 Flue
The back boiler flue collector assembly accepts the fire front flue spigot.
Note: Provision must be made during the installation of the back boiler for total ventilation requirement for the combined appliance. See relevant section in back boiler installation instructions.
INSTALLATION CENTRE LINE
406mm
to
460mm
560mm
to
C
L
590mm
3919 S
2.3 Without Surround or Hearth
The fire front fixing wall face must be flat over an area as shown in diagram 1.2. This also shows the minimum clearances for shelves or projections on the fire front fixing wall face.
The information in the last two paragraphs of “With Surround” should now be followed.
Under no account must carpet or other combustible material be laid directly under the fire front, unless the minimum clearances shown in diagram 1.2 is achieved.
The dimension is taken from the bottom of the fire front plinth to the top of the carpet pile or other floor covering.
Opus illustrated
1
/2in. 12mm
50mm MIN.
2in.
760mm 30in.
Non-
combustible
material
1
/2in
340mm 131/2in.
3918 S
REMOVE COMBUSTIBLE MATERIAL FROM THIS AREA
FRONT OPENING
280mm
BUILDERS
INSTALLATION
220mm220mm
OPENING
C
L
CENTRE
LINE
PREPARED BASE
280mm
135mm
PREPARED BASE
Diagram 2.2
680mm
560mm
3920 S
Diagram 2.1
5
Diagram 2.3
221098C
Page 6
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F i r e F r o n t P r e p a r a t i o n
FIRE BODY PACK
FIRE BODY ASSEMBLY
FLUE SPIGOT
LITERATURE
COMBUSTION
FUEL EFFECT BED
CHAMBER BOTTOM PLATE
OPULENCE CASING PACK OPUS CASING PACK
4337 S
WALL SEALING PLATE
L.H. SIDE PANEL
L.H. SIDE CASTING
FRONT CASTING
PLINTH
CANOPY
R.H. SIDE PANEL
R.H. SIDE CASTING
CANOPY
L.H. SIDE CASTING
L.H. SIDE PANEL
R.H. SIDE PANEL
FRONT CASTING
PLINTH
R.H. SIDE CASTING
R.H. LEG
L.H. LEG
6221098C
L.H. LEG
R.H. LEG
Diagram 3.1
Page 7
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F i r e F r o n t P r e p a r a t i o n
A
B
C
D
E
F
G
H
KEY
SCREW FRONT LEG
M5x30 LEVELLING SCREW
SCREW SIDE
M5x14 CASTINGS
SCREW UPPER WALL
M5x40 MOUNTING
ANCHOR UPPER WALL
NUT MOUNTING
SCREW FRONT LEG
M5x8 FIXING
SCREW WALL SEALING
No. 10 x 1 1/2in. PLATE FIXING
WALL WALL SEALING PLUG PLATE FIXING
SCREW UPPER SIDE
RETAINING
6135
J
K
L
SENSING TUBE MOUNTING BRACKET ASSEMBLY
BBU SENSING TUBE
SCREW FLUE SPIGOT FIXING
No. 8 x 3/8in.
SCREW SENSING TUBE
M4x10 FIXING SCREW
TAPTITE SCREW SENSING TUBE MOUNTING
M4x6 BRACKET SCREW
FILTER
BATTERY
FIRE FRONT SENSING TUBE
LIQUID COAL
OLIVE (2)
GAS SUPPLY PIPE
CONTROL KNOB
FIBRE WASHER (2)
TUBING NUT (2)
7
SIDE EXTENSION (2)
Diagram 3.1
221098C
Page 8
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F i r e F r o n t P r e p a r a t i o n
3.1 Unpacking
The fire front is delivered in two packs, one contains the body assembly, fuel effect pieces and supply tube pack.
The other contains the fire front castings, side panels, plinth and loose items pack. Refer to diagram 3.1. to identify the parts.
To unpack carton 1, lift out the top fitting containing the fire spigot and combustion chamber bottom plate, lift out the cardboard front fitting, the supply tube pack and the two boxes containing the fuel effect pieces.
Lift the outer carton clear to leave the fire front sitting in the base tray.
To unpack carton 2, lift out the cardboard tray containing the plinth and side panels. Lift out the loose items pack, legs box and canopy. Remove the internal cardboard fitting and lift out the lower front and side castings.
Put these items on one side until required. Check contents of loose items pack against list.
Remove the glass front panel, see diagram 3.2. It is suggested that the side extensions, from the castings
pack, be fitted at this time to the left and right hand side panels.
NOTE: These are a slide fit onto the louvres.
3.2 Flue Spigot Assembly
Note. This is marked “Homeglow BBU” Leave the fire front sitting in the base tray. Remove the two plastic transit studs securing the wall
sealing plate to the rear of the fire front and put it on one side until required.
Secure the spigot assembly to the fire front back with the self taping screws provided, in the loose items pack, see diagram 3.3.
Note. There are eight self tapping screws in the pack, one spare.
5171
GLASS RETAINING BRACKET
PULL FORWARDS AND UP
GLASS FRONT PANEL
Diagram 3.2
3923 S
FLUE SPIGOT ASSEMBLY
3.3 Gas Supply Tube and Sensing Tubes Preparation
Remove the plastic ferrule from the bulkhead connector on the air duct and discard.
Fix the flared end of the back boiler sensing tube to the bulkhead connection on the boiler air duct with the tubing nut provided. Slide the sensing tube mounting bracket assembly over the back boiler sensing tube and fix to the casing with the screw provided, see diagram 4.2.
Important. Make sure that the mounting bracket assembly is pushed back to the fire front face of the boiler casting and check 3mm distance is achieved and the back boiler sensing tube does not extend above the sensing tube bracket assembly, see diagram 4.2.
Note: After fitting the combustion products discharge safety device sensing tube please refer to the ‘commisioning’ section of the back boiler unit and relight the boiler to test the device.
Check that the gas service cock is in the Off position, see diagram 3.4.
The inlet supply tube, back boiler sensing tube assembly and fire front sensing tube are packed in the supply tube pack, see diagram 3.1.
This supply tube and fire front sensing tube may need to be cut, at the plain end, dependent on the model and position of the back boiler in the opening.
SECURING
J
SCREW (7)
Diagram 3.3
Gas Supply Tube
Measure the distance “C”, see diagram 3.5, from the front mark “P” on the air duct to the fire front fixing wall face.
Use a straight edge across the opening. Shorten the plain end of the gas supply tube by the
distance “C”. No shortening is required when mark “P” is level with the fire front fixing wall face, “C” being zero.
The maximum distance for “C” will be 67mm (25/8in).
8221098C
Page 9
Supplied By www.heating spares.co Tel. 0161 620 6677
3 F i r e F r o n t P r e p a r a t i o n
Firefront sensing tube
Shorten the plain end of the fire front sensing tube by distance “D”, no shortening of the tube is required when 45/2 back boiler is fitted and point “P” is level with the fire fixing wall face. Similarly when a 56/2 back boiler is fitted no shortening is required when point “N” is level with the fire fixing wall face. In both cases “D” is zero the maximum distance of “D” for both the 45/2 and 56/2 back boiler will be 25mm, see diagram 3.6.
Deburr the tube end inside and out.
3.4 Battery
Remove the fire front from the base tray. Take the battery from the fittings pack and fit as shown
in diagram 4.1, make sure that the terminals are correctly fitted.
GAS SERVICE COCK UNION
*'C' = Distance from fire fixing wall face to datums on back boiler air duct. This represents the length of pipe that requires cutting off.
'P'
BACK BOILER AIR DUCT
*'C'
GAS FIRE SUPPLY TUBE
*'C'
FIRE FIXING WALL FACE
Diagram 3.5
5078
BACK BOILER ONLY 'ON' TURNED FULLY CLOCKWISE
BACK BOILER & FIRE 'ON' TURNED TO MID POSITION
'OFF' TURN FULLY ANTI­CLOCKWISE
90˚
180˚
Diagram 3.4
*'D' = Distance from fire fixing wall face to datums on back boiler air duct. This represents the length of pipe that requires cutting off.
*'D'
56/2
BBU
N
45/2
BBU
P
BACK BOILER AIR DUCT
5245
FIRE FRONT SENSING TUBE
56 BBU/2 FIRE FIXING WALL FACE
*'D'
45 BBU/2 FIRE FIXING WALL FACE
*'D'
Diagram 3.6
9
221098C
Page 10
Supplied By www.heating spares.co Tel. 0161 620 6677
4 I n s t a l l a t i o n
4.1 Battery
Remove the fire front from the base tray. Take the battery from the fittings pack and fit as shown in
diagram 4.1, make sure the terminals are correctly fitted.
SECURING SCREW
5283
9V ALKALINE BATTERY
4.2 Positioning the Fire Front
Remove and discard the plastic ferrule from the bulkhead connector.
Fix the flared end of the back boiler sensing tube to the bulkhead connection on the boiler air duct with the tubing nut provided. Slide the sensing tube mounting bracket assembly over the back boiler sensing tube and fix to the casting with the screw provided, see diagram 4.2. Fit the sensing tube filter onto the fitting assembly, see diagram
4.2. Take care not to damage the filter. Important. Make sure that the mounting bracket assembly
is pushed back to the front face of the boiler casting and check 3mm distance is achieved and back boiler sensing tube does not extend above sensing tube fitting, see diagram 4.2.
Place the wall sealing plate onto the back boiler air duct, mark the fixing holes, remove the plate and drill the holes to suit the plugs and screws provided, from supply tube pack, leave sufficient screw proud to accept the wall sealing plate keyholes, see diagram 4.3.
Fit the wall sealing plate and tighten the screws, making sure that the “wings” are flush with the fire fixing wall face, see diagram 4.3.
Place the fire front onto the back boiler air duct, check that the fire front spigot is central in the flue collector assembly, push back into contact with the fire front fixing wall face, see diagram 4.4.
Mark the fire front fixing points through the mounting bracket holes at the top, see diagram 4.4.
Pull the fire front forwards and remove.
SPARK GENERATOR
ELECTRICAL CONNECTIONS
SENSING TUBE MOUNTING BRACKET ASSEMBLY
3mm
TUBING NUT
BACK BOILER SENSING TUBE
BULKHEAD CONNECTION
BOILER AIR DUCT
SECURING SCREW
IGNITION LEAD
Diagram 4.1
L
MOUNTING BRACKET SCREW
SENSING TUBE MOUNTING BRACKET ASSEMBLY
FRONT FACE OF BOILER CASTING
Diagram 4.2
6171
6171
Drill the fire front fixing face using a 10mm masonry drill to a minimum depth of 40mm to accept the anchor nuts and screws provided.
Place the anchor nuts and screws into the holes, screw up, but leave sufficient screw thread proud to accept the fire front.
Note, if the fire front fixing wall face is not of a solid construction, to a minimum depth of 40mm, for example, hollow brick or metal an alternative and rigid form of fastening for the fire front must be used and extra care taken.
Fit the fire front sensing tube to the flue collector with the two securing screws, see diagram 4.5.
10221098C
5166
G
F
NOTE: WINGS FLUSH WITH WALL
Diagram 4.3
Page 11
Supplied By www.heating spares.co Tel. 0161 620 6677
4 I n s t a l l a t i o n
MARK FRONT FIXING HOLES
FLUE COLLECTOR ASSEMBLY
SPIGOT
FIRE FRONT
52575072
FRONT FIXING SCREW
FLUE COLLECTOR ASSEMBLY
5258
SPIGOT
BACK BOILER AIR DUCT
FIRE FRONT
SECURING SCREW (2)
FLUE COLLECTOR
TUBING NUT
OLIVE
Diagram 4.4
FIRE FRONT SENSING TUBE
SENSING TUBE
TUBING
OLIVE
NUT
Diagram 4.6
Note, place the tubing nut and olive from the loose items pack onto the prepared end of the sensing tube, see diagram 4.5.
Offer the appliance up to the back boiler air duct and push into position taking care not to damage fire front sensing tube and filter, lift slightly to engage mounting brackets onto screws, engage sensing tube into bulk head connection, see diagram 4.6.
Tighten the fire securing screws, see diagram 4.7. Tighten the sensing tube nut onto the bulkhead, see
diagram 4.8.
Diagram 4.5
11
221098C
Page 12
Supplied By www.heating spares.co Tel. 0161 620 6677
4 I n s t a l l a t i o n
MOUNTING BRACKET
C
SECURING SCREW (2)
SECURING SCREW (2) M5 X 40mm
ANCHOR NUT
D
FIRE FRONT SENSING
5167
3928 S
TUBE NUT
TUBE
TUBE NUT
C
Diagram 4.8
LOCK NUT (A)
3929 S
Diagram 4.7
4.3 Gas Connection
Place the tubing nut and olive, from the loose items pack, onto the prepared end of the gas supply tube, see diagram 4.9.
Connect the gas supply, as diagram 4.9 tighten the nut and olive at the gas service cock.
To tighten the other end use a spanner to hold the locknut (A) at the bulkhead fitting and ensure that it does not turn, tighten the union nut (B) on the supply tube in the usual manner, see diagram 4.9.
Make sure that joint (B) is checked for gas soundness, by checking it when carrying out the other gas soundness checks in Section 5.1.
Fit the left hand side panel, see diagram 4.10.
UNION NUT (B)
JOINT (C)
GAS SUPPLY PIPE
GAS SERVICE COCK
TUBING NUT
OLIVE
Diagram 4.9
12221098C
Page 13
Supplied By www.heating spares.co Tel. 0161 620 6677
4 I n s t a l l a t i o n
FIBRE WASHER
L.H. SIDE PANEL
UPPER SIDE RETAINING SCREW
H
LOCATING PIN AND HOLE
UPPER SIDE RETAINING SCREW
H
FIBRE WASHER
LOCATING PIN AND HOLE
R.H. SIDE PANEL
GAS CONTROL KNOB
R.H. SIDE PANEL
3930 S
LOCATING PIN AND HOLE
Diagram 4.10
13
221098C
Page 14
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
5.1 Lighting and Testing
Make sure that the electrical supply to the back boiler is isolated.
The fire front is fitted with a combustion products discharge safety device which will shut it down if there is a lack of oxygen. If the fire shuts down frequently for no apparent reason the first things to be checked are the chimney and air inlets into the room. An additional cause could be that the filter in the gas tap is blocked. Any problems found must be put right, by a competent person before the fire is used again.
The combustion products discharge safety device MUST NOT be adjusted or disconnected. If replacing use only the correct and approved parts.
Remove the pressure test nipple screw and fit a suitable pressure gauge, see diagram 5.1.
Place the right hand side panel onto the pins, see diagram 4.10, but do not secure at this time.
Turn the gas service cock to back boiler and fire ON, see diagram 3.4.
To check for gas soundness use the pressure drop method and apply suitable leak detection fluid to all joints, replace glass panel, see diagram 3.2.
GAS TAP
VERTICAL
PRESSURE TEST POINT
Diagram 5.1
5081
5082
Fit the control knob to the tap spindle, see diagram 5.2. IMPORTANT. If the burner does not light within three
seconds, release the tap, wait ten seconds and repeat the lighting operation.
Push the control knob fully in and turn it anti-clockwise to 1 - ignition, see diagram 5.2, clicking of the ignition will be heard and the burner will light.
Keep the knob pushed in for ten seconds, to energise the flame supervision device, during this time the ignition system will continue to operate, indicated by the clicking.
Air may be present in the supply to the fire front so that the initial lighting operation may need to be repeated.
With the burner lit, visually check for leaks whilst changing tap settings.
To change settings: 0 - 1 Push in and turn 1 - 2 Push in and turn 2 - 3 Push in and turn 3 - 4 Push in and turn
GAS CONTROL KNOB
APPLIANCE
OFF
FLAT DOWN POSITION
IGNITION & POSITION 1
POSITION 4POSITION 3
POSITION 2
Diagram 5.2
If the burner goes out, wait three minutes before relighting, for any other reason wait for two minutes.
Check that the gas pressure is as stated in the Data Section 1.3 or on the Data Label. (Right hand side panel)
If there is any doubt about the gas rate, check at the meter, having first turned off all other gas appliances and pilots.
14221098C
Page 15
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
BOTTOM PLATE
Diagram 5.3
5.2 Internal Parts - Fitting
CAUTION: If any of the internal fire front parts are damaged DO NOT light or further test the fire front until replacement parts are fitted.
Refit gas tap control knob. Swing the side panels out by about 5mm, to their stops. WARNING: The glass panel can be hot. Remove the glass panel, see diagram 3.2.
FUEL EFFECT PIECES LOCATIONS
5174
4
5
2
2
4
2
1
5
1
FUEL EFFECT PIECES 1 to 5 Diagram 5.4
Left Side
FUEL
EFFECT
BASE
(see note)
3
FUEL EFFECT BASE
3
Right
Side
4329 S
5088
Follow sequence in diagram 5.3 to 5.11 to fit the combustion chamber bottom plate (inside base tray) and internal fire front parts.
Note. The fuel effect pieces are marked on their backs. Replace front glass panel.
FUEL EFFECT BASE
NOTE:
Fuel Effect Base seats behind retaining brackets
RETAINING BRACKETS
SUPPORT ANGLE FOR FUEL EFFECT PIECES 1, 2 AND 3
Diagram 5.5
15
221098C
Page 16
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
FUEL EFFECT PIECE POSITION 1 FUEL EFFECT PIECE POSITION 4
4331 S
4334 S
LOCATION
RECESS 4
RECESS 1
NOTE: FUEL EFFECT PIECE MUST
SIT ON SUPPORT ANGLE
Diagram 5.6
FUEL EFFECT PIECE POSITION 2 FUEL EFFECT PIECE POSITION 5
LOCATION
4332 S
LOCATION
LOCATION
RECESS 5
RECESS 2
Diagram 5.9
4335 S
NOTE: FUEL EFFECT PIECE MUST
SIT ON SUPPORT ANGLE
Diagram 5.7
FUEL EFFECT PIECE POSITION 3
LOCATION LUG 3
NOTE: FUEL EFFECT PIECE MUST
SIT ON SUPPORT ANGLE
Diagram 5.8
4333 S
COMPLETED FUEL EFFECT BED
Ensure corners of fuel effect pieces 4 and 5 are seated on flat areas of fuel effect pieces 1, 2 and 3
Diagram 5.11
Diagram 5.10
3943 S
16221098C
Page 17
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
5.3 Decorative Castings
Fit the front casting as diagram 5.12, decorative side castings as diagram 5.13, front legs and feet as diagram
5.14 and canopy as diagram 5.15.
3944 S
LOCATION PIN
LOCATION SLOT
VIEWED FROM REAR
FRONT CASTING
SIDE CASTING
Diagram 5.12
LEG
VIEWED FROM REAR
CANOPY
3945 S
SECURING SCREW (2)
E
Diagram 5.14
LOCATING
PIN
3946 S
3947 S
SECURING SCREW (3)
B
M5 x 14mm
Diagram 5.13
17
LOCATING
HOLE
Diagram 5.15
221098C
Page 18
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
5.4 Heat Settings
Light the fire front burner as the relevant part of Section 5.1.
Refer to diagram 5.16.
5154
At tap position 1 - centre section flame effect. At tap position 2 - centre section flame effect with outer
sections fuel bed glow.
At tap position 3 - centre and outer sections flame effect
with fuel bed glow.
At tap position 4 - (full on) full flame effect and fuel bed
glow.
In the unlikely event of the flame going out when the fire front burner is on, then turn off. Wait 3 minutes before relighting.
If relighting for any other reason, wait 2 minutes before doing so.
APPLIANCE OFF
IGNITION POSITION AND CENTRE SECTION FLAME EFFECT
CENTRE SECTION FLAME EFFECT WITH OUTER SECTIONS FUELBED GLOW
CENTRE AND OUTER SECTIONS FLAME EFFECT WITH FUELBED GLOW
FULL FLAME EFFECT WITH FUELBED GLOW
Diagram 5.16
18221098C
Page 19
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
5.5 Test for Clearance of Products
Notes: WARNING: Take care, the appliance will get hot
during tests. For the test you will need a smoke match, extension and
a torch. IN ALL CASES, if spillage continues after the specified
test periods steps must be taken to rectify the fault(s). Possible causes include, flue obstruction, down draught
or restricted fresh air supply into the room. If the problem cannot be put right the appliance must be
disconnected and expert advice sought.
Test Where No Fan is Present
Close all outside doors and windows in the room where the appliance is installed.
Light the fire front only and set to tap position 4. After 5 minutes apply a spillage test as shown in diagram
5.17 and 5.18. During tests smoke should be drawn into the fire draught diverter and the boiler draught diverter.
If spillage occurs, leave fire front alight for up to a further 10 minutes and repeat test. Turn the fire front off.
L.H. SIDE PANEL
SMOKE MATCH EXTENSION
TORCH
5175
DRAUGHT DIVERTER
Next light the back boiler only. After 10 minutes apply spillage test as shown in diagram 5.17 and 5.18. During tests smoke should be drawn into the fire front draught diverter and boiler draught diverter.
If spillage occurs, leave the back boiler alight for up to a further 5 minutes and repeat tests.
Leave the back boiler alight. Now light fire front. After 10 minutes apply spillage
tests as shown in diagram 5.17 and 5.18. During tests smoke should be drawn into the fire draught diverter and boiler draught diverter.
If spillage occurs leave back boiler and fire front alight for up to a further 5 minutes and repeat tests.
Test Where a Fan is Present
(A fan means an extract fan or a fan for other open flued appliances or a circulating fan for a warm air unit, whether or not gas fired). With the fan switched off carryout the appropriate spillage test with all doors and windows closed, as above.
If the above spillage test is satisfactory continue as follows:-
Open all doors connecting the room containing the appliance and the room in which the fan is fitted.
MATCH EXTENSION
SIDE VIEW
560 SMOKE MATCH EXTENSION
10
25mm
10
DIVERTER
25mm
PLATE
Diagram 5.17
5176
10
FRONT VIEW
Close all other doors and windows in the premises. If the fan is in the same room as the appliance, close all
doors and windows in that room. Switch the fan on and repeat the spillage test as above.
19
FIRE SPIGOT NOT SHOWN FOR CLARITY
Diagram 5.18
221098C
Page 20
Supplied By www.heating spares.co Tel. 0161 620 6677
5 L i g h t i n g , T e s t i n g a n d F i t t i n g o f I n t e r n a l P a r t s
5.6 Plinth Fitting
Fit the controls cover plinth onto the guides and push it back as far as it will go, see diagram 5.19.
6 I n s t r u c t i o n s t o U s e r
Hand the Instructions for Use to the user and instruct in the safe and economical use of the fire front and back boiler.
Advise the customer that they should read their Users instructions before operating the fire and always follow the advice in the Section headed “Cleaning your Fire”.
Advise that any smell which may be apparent on initial lighting is quite normal and it will quickly disappear.
Important: Advise that soft wall coverings, for example, blown vinyl wallpaper, are easily affected by heat, they may, therefore, scorch or become discoloured when close to a heating appliance. This should be borne in mind when having a heating appliance installed and when redecorating.
3951 S
PLINTH
Diagram 5.19
If the burner should go out repeat the above operation, but now keep the knob pushed in for a little longer.
Once lit operate the gas tap normally. This is a temporary measure only and the fault must be
put right as soon as possible. Advise the user of the precautions necessary to prevent
damage to the system, boiler and the building, in the event of the heating system being out of use during frost or freezing conditions.
Advise that the fire front is fitted with a safety device and refer to the instructions for use.
Reminder, leave these instructions with the user.
Advise the user, to ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance.
It is the Law that servicing is carried out by a competent person.
Show how to light the fire front, in the event of a power or ignition system failure, with a spill or long match, see diagram 6.1.
Remove the front casting. Hold a lighted spill or long match and insert it beneath
the front lighting assembly, position the spill so that the flame is over the burner.
Keep the spill in position, push in and turn the gas tap to position 1 and the burner will light keep knob pushed in for about 10 seconds and the burner will stay light.
5338
MATCH EXTENSION
BURNER
MATCH OR SPILL
20221098C
Diagram 6.1
Page 21
Supplied By www.heating spares.co Tel. 0161 620 6677
7 S e r v i c i n g
LOWER
FRONT
BAFFLE
SECURING SCREWS (3)
SECURING SCREWS (2)
BURNER BAFFLE
Notes
(a) To ensure the continued efficient and safe operation
of the appliance it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
(b) It is the Law that servicing is carried out by a
competent person.
(c) Make sure the fire is cold before carrying out any
servicing.
(d) Before servicing isolate the gas and electrical
supplies.
(e) After servicing (or replacing parts) always test for
gas soundness with a suitable leak detection fluid. (To test the gas tap, refix the fire front and apply leak detection fluid to all joints, replace the glass panel, light the burner and visually check all the joints for leakage whilst changing tap settings).
(f) Carryout functional check on controls, see Section 4
and 5.
(g) Other than for replacing the glass panel, internal fire
front parts and lighting the fire front should be removed from its fixings by reversing the instructions in Section 4 and 5. Make sure that the side panels and feet are removed. Refit controls cover plinth so that the fire can stand upright.
(h) Unless stated otherwise reassemble all parts in the
reverse order to removal.
(i) The back boiler should be serviced at this time, refer
to Back Boiler Installation and Servicing Instructions.
(j) The combustion products discharge safety device
MUST NOT be adjusted or disconnected. If replacing use only the correct and approved parts.
3953 S
5mm
5mm
Diagram 7.1
4854B
7.1 Glass Panel
Lift canopy off. Swing open side panels to their stops, about 5mm, as
diagram 7.1. To remove the glass panel, refer to diagram 3.2.
7.2 Internal Fire Front Parts
Remove internal fire front parts as diagram 5.10 to 5.3. Examine these parts and replace as necessary.
7.3 Burner and Injectors
Remove the front casting, see diagram 5.12. Remove the lower front baffle, see diagram 7.2. Remove the burner baffle, see diagram 7.2. Remove the side castings, see diagram 5.13. Remove right hand leg, see diagram 5.14. Remove right hand leg support bracket, see diagram 7.4.
21
Diagram 7.2
221098C
Page 22
Supplied By www.heating spares.co Tel. 0161 620 6677
4855
L.H. BURNER
SECURING SCREW
R.H. BURNER
SECURING SCREW
BURNER
UNION CONNECTION
UNION CONNECTION
7 S e r v i c i n g
Disconnect the supply pipe unions at the injectors also the union connection at front, see diagram 7.5.
Remove the two burner securing screws, see diagram 7.5.
Swing burner out for access, see diagram 7.6. Unscrew the injectors, inspect, clean or replace as
necessary, see diagram 7.7. Do not clean the holes with a wire or sharp instrument. Remove the injector box cover screw and plate, see
diagram 7.7, clean out dust and debris. Brush away any lint and dust from the burner and surrounds.
Using a soft brush or vacuum cleaner. Do not use a brush with wire bristles.
BURNER BAFFLE
SECURING SCREW (2)
BURNER
Diagram 7.3
5080
3955 S
INJECTOR BOX COVER
Diagram 7.5
5172
BURNER
PULL FORWARDS
Diagram 7.6
3958 S
SECURING SCREW (4)
R.H. LEG SUPPORT BRACKET
Diagram 7.4
22221098C
SECURING SCREW
INJECTORS Diagram 7.7
Page 23
Supplied By www.heating spares.co Tel. 0161 620 6677
7 S e r v i c i n g
7.4 Combustion Products Discharge Safety Device
Remove the burner refer to Section 7.3. Check the condition of the electrode and thermocouple,
with a soft brush, see diagram 7.8. Make sure the electrode is in line with the earth post and
spark gap is as in diagram 7.9.
7.5 Ignition Lead
Remove the burner refer to Section 7.3. Disconnect the union connections, remove the mounting
bracket securing screws and combustion products discharge safety device, see diagram 7.8.
Check the ignition lead, see diagram 7.8. Replace if required, refer to Section 9.5.
TUBE NUT
5075
5075
Note. When refitting the combustion products discharge safety device, take care not to trap the ignition lead under the mounting bracket.
7.6 Gas Tap and Micro Switch Assembly
Note: This item need not be serviced annually. Remove micro switch electrical connections, see
diagram 7.10. Disconnect all union connections and remove the tubes
in the order shown diagram 7.11. Disconnect the thermocouple nut, see diagram 7.12.
When replacing only tighten the nut a quarter turn beyond finger tight.
Remove the gas tap bracket securing screws, see diagram 7.12.
Remove the gas tap assembly. To service the gas tap remove the gas tap niting plate
assembly securing screws, see diagram 7.13. Take care as there is a spring beneath the niting plate. Remove the plug, pin, spring washer, plain washer and “O” ring, see diagram 7.13.
TUBE NUT
COMBUSTION PRODUCTS DISCHARGE SAFETY DEVICE
MOUNTING BRACKET
SECURING SCREW (2)
Clean and relubricate using a suitable grease. When replacing make sure the operating disc, with
retaining washer and micro switch and leads are correctly located, see diagram 7.13 and 7.10.
23
SECURING SCREW (2)
TUBE NUT
IGNITION LEAD
Diagram 7.7
221098C
Page 24
Supplied By www.heating spares.co Tel. 0161 620 6677
EARTH POST
ELECTRODE
ELECTRODE
C
L
SPARK GAP
+ 1.0
3
- 0.5
EARTH POST
7 S e r v i c i n g
5248
GAS TAP MOUNTING BRACKET SECURING SCREW
MICRO SWITCH
ELECTRICAL CONNECTIONS
INSULATION
3960 S
MICRO SWITCH
ELECTRODE
67
TOP VIEW
18
EARTH POST
Diagram 7.9
NUT (2)
INSULATION
SECURING SCREW (2)
GAS TAP MOUNTING BRACKET
Diagram 7.10
24221098C
Page 25
Supplied By www.heating spares.co Tel. 0161 620 6677
7 S e r v i c i n g
1
8
6
4
5089
2
GAS TAP SECURING SCREWS
5090
9
5
7
3
9
5
THERMOCOUPLE NUT
7
Diagram 7.12
5091
GAS TAP
Diagram 7.11
GAS TAP BODY
BRACKET AND NITING PLATE ASSEMBLY
'O' RING
PLUG
WASHER
SPRING
SECURING SCREW
25
Diagram 7.13
221098C
Page 26
Supplied By www.heating spares.co Tel. 0161 620 6677
8 F a u l t F i n d i n g
ELECTRODE
RED
RED
SPARK GENERATOR
MICRO SWITCH
5251
ELECTRODE
MICRO SWITCH
SPARK GENERATOR
8.1 Fire Front Ignition
Remove decorative castings, glass panel and fuel bed, refer to appropriate parts of Section 7.
Refer to diagram 8.3.
8.2 Electrical
5252
RED RED
Diagram 8.2
Diagram 8.1
Refer to pictorial wiring diagram 8.1 and functional flow diagram 8.1.
Refer to pictorial wiring diagram 8.1 and functional flow diagram 8.2.
26221098C
Page 27
Supplied By www.heating spares.co Tel. 0161 620 6677
8 F a u l t F i n d i n g
5478
START HERE
YES
Turn off appliance tap, turn on appliance tap. Does the fire light ?
NO
Ensure gap is within specified tolerance, refer to SERVICING. turn tap to energise ignition. Does the fire light ?
YES
NO
Disconnect ignition lead from electrode, place connector within 4mm of burner and turn tap to energise igniter. Is there a spark at the gap ?
YES
Replace faulty electrode and reassemble ignition system. Turn tap to energise igniter. Does the fire light ?
FIRE WILL NOT LIGHT
Check that gas is available Does the pilot light using a match ?
YES
NO
Change pilot filter
Check that gas is available at burner, using a match, ensuring correct functioning of burner on all setting positions. Check that electrode, micro switch and ignition unit connections are satisfactory. Check that burner pressure is as specified - correct any fault found.
NO
Remove ignition lead from ignition unit and place screw driver between appliance chassis earth and ignition unit, leaving 4mm gap between blade and spade connector. Turn tap to energise ignition. Is there a spark at gap ?
NO
YES
NO
YES
Disconnect red leads from ignition unit. Turn tap to energise ignition. Is there continuity between red leads ?
Change the ignition unit battery. Turn tap to energise ignition. Does the fire light ?
YES
Change ignition unit.
Check several times that ignition is satisfactory.
YES
NO
Renew ignition lead and reassemble ignition system.
NO
Rectify faulty leads or replace micro switch.
Diagram 8.3
27
221098C
Page 28
Supplied By www.heating spares.co Tel. 0161 620 6677
8 F a u l t F i n d i n g
Disconnect appliance thermocouple from the gas tap. Check that all connections are clean and in good condition. Fit test meter interrupter into the magnet unit. Fit appliance thermocouple into the test meter interrupter.
Hold down control tap in ignition position. Ignite burner, allowing thermocouple to attain operating temperature. Measure the OPEN CIRCUIT voltage.
5243
Is voltage greater
Is voltage greater
than 15mV?
than 15mV?
Note the open circuit reading then measure the CLOSED CIRCUIT voltage. Note this voltage. Referring to the diagnosis graph, mark the open circuit voltage on the VERTICAL axis, and the closed circuit voltage on the HORIZONTAL axis. Note the point where these two values intersect on the graph.
THERMOCOUPLE CIRCUIT IS SATISFACTORY
In which area of the graph is the intersect
B
Faulty magnet unit in gas tap. Replace gas tap
NO
YES
A
C
Faulty thermocouple. Replace combustion products discharge safety device.
Faulty thermocouple. Replace combustion products discharge safety device.
Diagram 8.4
28221098C
Page 29
Supplied By www.heating spares.co Tel. 0161 620 6677
8 F a u l t F i n d i n g
8.3 Thermocouple
To test a thermocouple, a meter with a range of 0 to 30mV is required together with a thermocouple interrupter test unit, similar to a British Gas Multimeter 6 unit.
Refer to fault finding diagram 8.4 and diagnosis graph, diagram 8.5.
8.4 Combustion Products Discharge Safety Device
If the device operates it indicates there could be a problem with the chimney or, the pilot filter in the gas tap is blocked. First make sure air vents are free from obstructions, by carrying out spillage checks as Section 5.5. If all is in order refer to diagram 8.3 to check if the pilot filter is blocked.
17 16 15 14 13 12
11
10
9 8
Open Circuit Voltage (millivolts)
7
01234567891011
Closed Circuit Voltage (millivolts) DIAGNOSIS GRAPH FOR FIRE
THERMOCOUPLE CIRCUIT
ABC
Diagram 8.5
0065M
29
221098C
Page 30
Supplied By www.heating spares.co Tel. 0161 620 6677
9 R e p l a c e m e n t o f P a r t s
Notes: (a) Make sure that the fire is cold before replacing any
parts.
(b) Replacement of parts must be carried out by a
competent person.
(c) Remove the internal fire front parts as the relevant
part of Section 5.2.
(d) Before removing or replacing any fire front parts
turn the gas supply service cock to “Back Boiler Only On”, see diagram 3.4.
(e) Isolate the electrical supply to the back boiler and
fire front.
(f) Other than for replacing the burner, injectors and
internal fire front parts the fire front should be removed from its fixings be reversing the instructions in Section 4 and 5. Make sure that the side panels and legs are removed. Refit controls cover so that the fire front can stand upright.
(g) After replacing or disconnecting any gas carrying
component, always test for gas soundness, using a suitable leak detection fluid and carry out functional check of controls.
SECURING SCREW
SPARK GENERATOR
ELECTRICAL CONNECTIONS
5283
9V ALKALINE BATTERY
SECURING SCREW
IGNITION LEAD
Diagram 9.1
(h) To test the gas tap apply leak detection fluid to all
joints, light the burner and check all the joints for leakage at all tap settings.
(j) Unless stated otherwise reassembly of all parts is in
the reverse order to removal.
(k) The combustion products discharge safety device
MUST NOT be adjusted or disconnected.
30221098C
Page 31
Supplied By www.heating spares.co Tel. 0161 620 6677
9 R e p l a c e m e n t o f P a r t s
GAS TAP BRACKET AND NITING PLATE ASSEMBLY
9.1 Burner
Refer to Section 7.3.
9.2 Injectors
Refer to Section 7.3.
9.3 Gas Tap and Micro Switch Assembly
Refer to Section 7.5, and diagram 7.10 to remove the micro switch.
9.4 Combustion Products Discharge Safety Device
Remove canopy. Refer to Section 7.3 to remove the burner. Disconnect the union connections, remove the mounting
bracket securing screws and combustion products discharge safety device, see diagram 7.8.
Pull off the lower sensing tube. When replacing take care not to damage the “O” ring seals.
Remove right hand side panel, see diagram 4.10. Remove the thermocouple nut, see diagram 7.12. Remove the ignition lead, see diagram 9.1.
FILTER
GAS TAP
CROSS SECTION VIEW
FILTER
Diagram 9.2
9.5 Ignition Lead
Refer to Section 7.3 to remove the burner. Disconnect the tube nuts, remove the mounting bracket
securing screws, remove the ignition lead (black end), see diagram 7.8.
Remove side panel securing stop screw and open panel, see diagram 4.10.
Remove the ignition lead (clear end), see diagram 9.1. Note. When refitting the combustion products discharge
safety device, take care not to trap the ignition lead under the mounting bracket.
9.6 Spark Generator
Remove right hand side panel, see diagram 4.10. Remove the right hand side casting, see diagram 5.13.
Remove retaining screw, disconnect the electrical leads and then release the spark generator from the location tab at the rear, see diagram 9.1.
9.7 Gas Tap Pilot Filter
Gain access to the gas tap as Section 7.6. The filter, which is very small, is in the pilot port of the
gas tap, to remove use a small non-metallic tool.
5477
Note. When refitting the combustion products discharge safety device, take care not to trap the ignition lead under the mounting bracket.
When refitting make sure that the spark gap is as shown in diagram 7.9.
When fitting the replacement it is important that the filter is seated correctly as shown in diagram 9.2.
31
221098C
Page 32
Supplied By www.heating spares.co Tel. 0161 620 6677
10 S p a r e P a r t s
When replacement parts are required please apply to your local supplier.
Please quote the name of the fire front, “Opus” or “Opulence”.
The GC No.37 314 14, Opus, 37 314 15 Opulence, and the serial number, to be found on the chassis, visible when front casting is removed.
Refer to diagram 10.1 for the illustration of the replacement parts.
Key No. Part No. G.C. Part No. Description
1 210213 136 918 Rear fuel effect piece 2 210214 136 919 Fuel effect piece - 1 3 210215 136 920 Fuel effect piece - 2 4 210216 136 921 Fuel effect piece - 3 5 210217 136 922 Fuel effect piece - 4 6 210218 136 923 Fuel effect piece - 5 7 448093 136 924 Glass panel assembly 8 230169 398 444 Injector - upper 9 230201 398 422 Injector - lower 10 203437 162 100 Combustion products discharge safety device 12 202014 360 188 Microswitch 13 WW4617 312 997 Ignition lead 14 448103 136 925 Gas tap control knob - Opus 2 14 448235 136 926 Gas tap control knob - Opulence 2 15 800449 136 927 Gas tap 16 202179 152 949 Spark generator 17 208673 162 208 Filter
32221098C
Page 33
Supplied By www.heating spares.co Tel. 0161 620 6677
10 S p a r e P a r t s
5178
7
10
1
5
3
6
2
4
8
9
15
13
17
12
16
14
33
Diagram 10.1
221098C
Page 34
Supplied By www.heating spares.co Tel. 0161 620 6677
11 S u p p l e m e n t a r y I n s t a l l a t i o n I n s t r u c t i o n s
These fire fronts are fitted with combustion products safety devices
As these fire fronts may be fitted to Glow-worm 45, 56, 45R and 56R back boiler units WITHOUT a combustion products discharge safety device, the following instructions must be read and followed in place of those in the main Installation and Servicing Instructions.
To check if a combustion products discharge safety device, refer to inset in diagram 11.1, if one is fitted this supplement MUST be ignored.
11.1 General
To fit the fire front to one of the above EXISTING GLOW-WORM BACK BOILER UNITS follow the instructions below.
NOTE: Kit No. 451484 will be required.
1. Replace the existing draught diverter front with the
new part supplied in Kit No. 451484. To fit follow the instructions supplied with the kit.
11.2 Installation
2. Do not fit the back boiler sensing tube as required in
the main installation and servicing instructions.
3. If necessary isolate the power supply to the back
boiler unit and remove the existing wiring used previously for a fire front with lights.
Turn the thermostat control knob “B” to “Off” position, that is, fully anticlockwise, “Off” to be against the pointer.
Push in and slightly turn gas control knob “A” clockwise until “ ” is against its setting point, that is, set to “Off”.
Push in slightly and turn gas control knob “A” anticlockwise until “ ” is against its setting point, then push fully in and hold in. At the same time press and release piezo button “D” until pilot burner “E” lights. Look at flame through viewing window “F”.
At initial lighting of the boiler air may be present and several attempts may be needed to light the pilot. Keep the control knob “A” pushed in whilst operating the ignition button.
When the pilot is alight and stable, keep knob “A” fully pushed in for about 15 seconds then release. Check that the pilot is still alight, look through window “F”.
If the pilot burner fails to stay alight turn gas control knob “A” “Off”. that is, fully clockwise. Wait three minutes. Repeat the lighting operation, only now keep the control knob “A” pushed in for a little longer than before after the pilot has lit.
NOTE. Always wait three minutes before attempting to relight the pilot after it has gone out for any reason.
Push control knob “A” in slightly and turn anticlockwise
4. Any reference in the installation and servicing
instructions to the back boiler combustion products discharge safety device must be ignored.
Lighting the Boiler
The boiler controls are placed behind the fire front plinth.
To remove the plinth, pull it gently forwards until it is free.
Refer to diagram 11.1 to identify controls. Turn off the electrical supply at the mains supply outside
the appliance. Check that all controls are calling for heat. The clock, room thermostat and programmer, if fitted,
will be away from the unit, see manufacturer’s instructions supplied with them.
34221098C
Page 35
Supplied By www.heating spares.co Tel. 0161 620 6677
11 S u p p l e m e n t a r y I n s t a l l a t i o n I n s t r u c t i o n s
SETTING POINT
'B' THERMOSTAT CONTROL KNOB
BOILER CONTROLS
INSET: Showing a Combustion Products Discharge
Safety Device fitted.
'E' PILOT BURNER
'F' VIEWING WINDOW
'A' GAS VALVE
'D' PIEZO UNIT BUTTON
CONTROL KNOB
5342
SETTING POINT
OFF
PILOT/IGNITION MAIN BURNER
Diagram 11.1
35
221098C
Page 36
Supplied By www.heating spares.co Tel. 0161 620 6677
C o n t r o l o f S u b s t a n c e s H a z a r d o u s t o H e a l t h
Information for the Installer and Service Engineer.
Under Section 6 of the Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The Adhesives and sealants used in this appliance are cured and give no known hazard in this state. FUELBEDS, ARTIFICIAL FUEL This product uses fuel effect Pieces containing Refractory Ceramic Fibre (RCF), which are man-
made vitreous silicate fibres. Excessive exposure to these materials may cause temporary irritation to eyes, skin and respiratory tract, consequently, it makes sense to take care when handling these articles to ensure that the release of dust is kept to a minimum.
To ensure that the release of fibres from these RCF articles is kept to a minimum, during installation and servicing we recommend that you use a HEPA filtered vacuum to remove any dust and soot accumulated in and around the fire before and after working on the fire. When replacing these articles we recommend that the replaced items are not broken up, but are sealed within heavy duty polythene bags, clearly labelled as RCF waste. This is not classified as “hazardous waste” and may be disposed of at a tipping site licensed for the disposal of industrial waste. Protective clothing is not required when handling these articles, but we recommend you follow the normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking.
INSULATION and SEALS Ceramic fibre and glass fibre used in insulation panels rope and gaskets. These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are
usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands
before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Because of our constant endeavour for improvement details may vary slightly from those in the instructions.
36221098C
Loading...