8
221917C
1.6 Precast Flues
• The appliance can be installed to a fireplace that has a properly
constructed precast concrete or clay flue block system
conforming to BS1289 or BS EN 1806. The appliance is suitable
for installations conforming to older versions of BS1289 as well
as the current standards. The flue blocks must have a minimum
width not less than 63mm and a cross-sectional area not less
than 13,000mm
2
.
Older editions of BS1289 required a cross-
sectional area of 13,000mm
2
. The current revision of the standard
requires 16,500mm
2
. This appliance is suitable in both cases.
• The chimney should be one or two storeys high but not less
than 3m vertical height and be correctly terminated. No mortar
fangs between the blocks should be extruded into the flueway.
If raking blocks are used, they must be fitted in accordance with
the manufacturer’s instructions. Mortar must not be allowed to
drop down and accumulate in the raked positions.
• The fireplace opening must be within the following dimensions:
Width Max. 440mm
Min. 305mm
Height Max. 610mm
1
Min. 610mm
2
1
Though the total height of the closure plate will accommodate
a maximum opening height of 650mm, heights above 610mm
will leave the closure plate and sealing tape visible above the
appliance.
2
Any opening visible below the appliance may be closed in.
1.7 Metal Flue Box
• The appliance can be installed to a metal flue box conforming
to BS715 Section 6 (For gas fires to BS5258:Part5) having a
minimum internal depth of 165mm.
• The opening must be within the following dimensions:
Width Max. 440mm
Min. 380mm
Height Max. 610mm
*
Min. 525mm
* Though the total height of the closure plate will accommodate
a maximum opening height of 650mm, heights above 610mm
will leave the closure plate and sealing tape visible above the
appliance.
1.8 Flue Requirements
The following flues are suitable:
• 225mm x 225mm conventional brick flue.
If a flue liner is used, it must be a minimum of 125mm diameter.
The liner must be sealed to the surrounding area above the
fireplace opening and to the top of the chimney. An approved
terminal must be fitted.
• A properly constructed precast flue conforming to B.S 1289 or
BS EN 1806.
• A flue pipe with a minimum diameter of 127mm. See B.S 6461
Part 1 for suitable materials. Metal flue pipes must comply with
B.S 715. See section 2.9.4 of this guide for flue box opening
sizes.
• The flue must conform to BS 5440: Part 1 in design and
installation.
• The flue, measured from the bottom of the fireplace opening
to the bottom of the terminal, shall be not less than 3m in actual
vertical height. When calculated in accordance with BS 5440:
Part 1 Annex A, the minimum equivalent height of the flue shall
be 2.0m of 125mm dia. flue pipe.
The flue must be clear of any obstruction and its base must be
clear of debris.
The flue must be completely sealed so that combustion products
do not come into contact with combustible materials outside the
chimney.
The flue must serve only one fireplace.
Proprietary terminals must comply with BS 715 or BS 1289. Any
terminal or termination must be positioned in accordance with
BS 5440 Part 1 to ensure that the products of combustion can
be safely dispersed into the outside atmosphere. Where the
appliance is connected to an unlined brick chimney it is generally
unnecessary for the chimney pot to be replaced or for a terminal
to be fitted unless the flue has a diameter smaller than 170mm.
If the appliance is intended to be installed to a chimney which
was previously used for solid fuel, the flue must be swept clean
prior to installation. All flues should be inspected for soundness
and freedom from blockages.
Any chimney dampers or restrictors should be removed. If
removal is not possible they must be fixed in the open position.
1.9 Ventilation
In the United Kingdom (GB) special ventilation bricks or vents
are not normally required in the room for this appliance.
In the Republic of Ireland (IE), permanent ventilation must
comply with the regulations currently in force.
An extractor fan may only be used in the same room as this
appliance, or in any area from which ventilation for the appliance
is taken, if it does not affect the safe performance of the
appliance. Note the spillage test requirements detailed further
on in this manual. If the fan is likely to affect the appliance, the
appliance must not be installed unless the fan is permanently
disconnected.
1.10 Appliance Clearances
Note that soft wall coverings (e.g. embossed vinyl, etc.) are
easily affected by heat. They may scorch or become discoloured
when close to a heating appliance. Please bear this in mind
when installing.
The minimum allowable distance from the outside of the
appliance case to a corner wall or other combustible surface
which projects beyond the front of the appliance is 12mm at
either side. See diagram 1.1.
Allow a minimum clearance of 110mm from the top surface of
the appliance case to the underside of any shelf whether it is
made from combustible or non-combustible materials. This
clearance is necessary to allow the case to be lifted off for
servicing and also allows the owner sufficient access to operate
the control knob.
A shelf made from wood or other combustible materials
deeper than 150mm must have a minimum clearance of
110mm + 12.5mm for every 25mm depth over 150mm. See
diagram 1.1.
The space between the fireplace front face and the back of the
outer case must not be filled in.
1.10 Room Restrictions
The appliance must not be installed in any room, which contains
a bath, or shower or where steam is regularly present.
1 Installation Requirements