Glow-worm hxi and Gas Valve User Manual

0020008153-05 11.05
Instructions for Use
Installation and Servicing
To be left with the user
12hxi 15hxi
G.C. No. 41-047-73
G.C. No. 41-047-74
18hxi 24hxi
G.C. No. 41-047-63
G.C. No. 41-047-69
30hxi 38hxi
G.C. No. 41-047-64
High Efficiency
Condensing Boilers
G.C. No. 41-047-71
Glow-worm, Nottingham Road, Belper, Derbyshire. DE56 1JT
www.glow-worm.co.uk
Guarantee Registration
Thank you for installing a new Glow-worm appliance in your home. Glow-worm appliances are manufactured to the very highest standard so we are pleased to offer our customers a Comprehensive Guarantee. This product is guaranteed for 24 months from the date of installation or 30 months from the date of manufacture, whichever is the shorter, for parts. In addition this product is guaranteed for 12 months from the date of installation or 18 months from the date of manufacture, whichever is the shorter, for labour. The second year of the parts guarantee, from the beginning of the 13th month onwards after installation or manufacture, is conditional upon the boiler having been serviced by a CORGI registered gas installer, in accordance with the manufacturer's recommendations. We strongly recommend regular servicing of your gas appliance, but where the condition is not met, any chargeable spare parts or components issued within the applicable guarantee period still benefit from a 12 month warranty from the date of issue by the manufacturer.
We recommend you complete and return as soon as possible your guarantee registration card.
If your guarantee registration card is missing you can obtain a copy or record your registration by telephoning the Glow-worm Customer Service number 01773 828100.
For customer service call:
01773 828100
Technical helpline: 01773 828300
For General and Sales enquiries:
Tel. 01773 824639
Fax: 01773 820569
To register your Glow-worm appliance call:
0800 073 2142
0020008153-05
2
Contents
The instructions consist of three parts, User, Installation and Servicing Instructions.The
instructions are an integral part of the appliance and must, to comply with the current issue
of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion
of the installation.
CONTENTS DESCRIPTION SECTION PAGE No.
Important Information 4
INTRODUCTION
General Information 5 Manual Handling 5
INSTRUCTIONS
FOR USE
INSTALLATION
INSTRUCTIONS
SERVICING
INSTRUCTIONS
Appliance Safety Devices 7 Maintenance and Servicing 7 Operating the Boiler 8
Technical Information 1 9 Boiler Location and Ventilation 2 13 Flue Location and Ventilation 3 14 Water System 4 16 Installation Preparation 5 20 Boiler Fixing 6 21 Gas, Water and Condensate Conns. 7 22 Flue Preparation Telescopic and Standard Flue 8 24 Electrical Connections 9 27 Commissioning 10 28
Servicing 11 31 Fault Finding 12 35 Replacement of Parts 13 39 Spare Parts 14 44
3
0020008153-05
Important Information
WARNINGS
Gas Leak or Fault
Turn off the gas emergency control valve immediately. Eliminate all sources of ignition, i.e.smoking, blowlamps, hot air guns
etc. Do not operate electrical lights or switches either on or off. Open all doors and windows, ventilate the area.
Sheet Metal Parts
This boiler contains metal parts (components) and care should be taken when handling and cleaning,
Under no circumstances must the User interfere with or adjust sealed parts.
with particular regard to edges.
Sealed Components
Gas Category
This boiler is for use only on G20 natural gas, but the 30hxi may be converted for use on G31 gas (Propane L.P.G.).
Gas Safety (Installation and Use) Regulations
In your own interests and that of safety, it is the Law that ALL gas appliances are installed by a competent person in accordance with the current issue of the above regulations.
Testing and Certification
The boiler is tested and certificated for safety and performance. It is, therefore, important that no alteration is made to the boiler unless approved, in writing, by Glow-worm.
Any alteration not approved by Glow-worm, could invalidate the certification, boiler warranty and may also infringe the current issue of the statutory requirements.
CE Mark
This boiler meets the requirements of Statutory Instrument, No. 3083 The Boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body
0087.
Product/production certified by: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonisation of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation Pads / Ceramic Fibre
These can cause irritation to skin, eyes and the respiratory tract.
If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken.
Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory.
If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Electrical Supply
The boiler must be earthed.
All system components shall be of an approved type and all wiring to current I.E.E. wiring regulations.
External wiring must be correctly earthed, polarised and in accordance with the relevant standards.
In GB this is BS 7671.
In IE this is the current edition of I.S.813 "Domestic Gas Installations".
The boiler must be connected to a permanent 230V ac, 50Hz supply.
Connection of the whole electrical system of the boiler, including any heating controls, to the electrical supply must be through one common isolator and must be fused 3 Amp maximum.
Isolation should be by a double pole switched fused spur box, with a minimum gap of 3mm for both poles. The fused spur box should be readily accessible and preferably adjacent to the appliance. It should be identified as to its use.
Alternatively connection can be made through an unswitched shuttered socket and 3A fused 3-pin plug both to the current issue of BS 1363 may be used, provided they are not used in a room containing a bath or shower.
The colours of three core flexible cable are, blue - neutral, brown
- live, green and yellow - earth.
0020008153-05
4
General Information
General Note
This boiler is designed to provide central heating from a fully pumped open-vented or sealed water system with a fully indirect cylinder.
Once the controls are set the boiler operates automatically.
Please read these instructions and follow them carefully for the correct installation and economical use of your boiler.
Water Treatment
In the case of an existing installation, it is ESSENTIAL that prior to installing the new boiler the system is thoroughly flushed. For optimum performance after installation of a new system, the boiler and its associated central heating system should also be flushed. Flushing should be carried out in accordance with BS7593: 1992 using a cleanser such as Sentinel X300 or X400, Fernox Superfloc or Salamander corrosion guard cleaner.
For long-term corrosion protection, after flushing, an inhibitor suitable for stainless steel exchangers should be used, refer to the current issue of BS 5449 and BS 7593 on the use of inhibitors in central heating systems. Examples are Sentinel X100 Fernox or Salamander corrosion guard inhibitor.
Compartment or Cupboard Installations
If the boiler is fitted into a compartment or cupboard it does not require ventilation openings.
Do not use the compartment or cupboard for storage.
Condensate Drain
The condensate drain, see section 7.3, must not be modified or blocked.
Pluming from flue terminal
Like all condensing boilers this appliance will produce a plume of condensation from the flue terminal in cool weather. This is due to the high efficiency and hence low flue gas temperature of the boiler. It is normal and not a fault indication.
Cleaning
The boiler casing can be cleaned using a mild liquid detergent with a damp cloth, then a dry cloth to polish.
Do not use any form of abrasive or solvent cleaner as you may damage the paintwork.
Electrical Supply
If the mains electricity and gas are to be turned off for any long periods during severe weather, it is recommended that the whole system, including the boiler, should be drained to avoid the risk of freezing. Make sure that, if fitted, the immersion heater in the cylinder is switched off.
NOTE: If you have a sealed water system contact your installation/servicing company as draining, refilling and pressurising MUST be carried out by a competent person.
Clearances
If fixtures are positioned close to the boiler, space must be left as shown in diagram 2.1. Enough space must also be left in front of the boiler to allow for servicing.
Manual Handling
IMPORTANT. With regards to the Manual Handling Operations,
1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift.
General recommendations when handling
Clear the route before attempting the lift.
Ensure safe lifting techniques are used – keep back straight – bend using legs.
Keep load as close to body as possible.
Do not twist – reposition feet instead.
If 2 persons performing lift, ensure co-ordinated movements during lift.
Avoid upper body/top heavy bending - do not lean forward/ sideways.
Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip.
Always use assistance if required.
Removal of carton from delivery van
Recommend 2 person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co­ordinated movements during lift. Always use assistance if required.
Carriage of carton from point of delivery to point of installation – ground floor
Recommend 2 person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co­ordinated movements during lift. Clear the route before attempting the lift. If removing boiler from truck straddle the load and tilt forwards to facilitate secure grip. Ensure safe lifting techniques are used – keep back straight – bend using legs. Do not twist – reposition feet instead. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required.
5
0020008153-05
Manual Handling
Carriage of carton from point of delivery to point of installation – first or higher floor, cellar.
Recommend 2-person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co­ordinated movements during lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Clear the route before attempting the lift. If removing boiler from truck straddle the load and tilt forwards to facilitate secure grip. Ensure safe lifting techniques are used – keep back straight – bend using legs. Do not twist – reposition feet instead. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required.
Carriage of carton from point of delivery to point of installation – roofspace.
Recommend 2-person lift. Ensure co-ordinated movements during lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Clear the route before attempting the lift. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. When transferring appliance into roofspace, recommend 1 person to be in roofspace to receive the appliance and other person to be below to pass up and support appliance. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Always use assistance if required. It is assumed safe access, flooring and adequate lighting are provided in the roof space. It is recommended a risk assessment of the roof space area be carried out before moving the appliance into the area to take into account access, stability of flooring, lighting and other factors, and appropriate measures taken.
Unpacking of appliance from carton.
Recommend 2 persons unpack appliance from carton. Always keep working area clear. Recommend cut base end of carton and open carton flaps, then tilt boiler forwards from its side onto its base and remove carton by sliding up over the boiler. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Always use assistance if required. Dispose of packaging in a responsible manner. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance outside packaging.
Positioning of Appliance for Final Installation – no obstructions.
Recommend 2 persons lift appliance to position into place. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to position in place on bracket. Ensure safe lifting techniques are used – keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Ensure co-ordinated movements to ensure equal spread of weight of load. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.
Positioning of Appliance for Final Installation – above worktop, foreseeable obstructions etc.
Recommend 2 persons lift appliance to position into place. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, onto worktop if practicable. Ensure stable balance achieved and lift upwards to position in place on bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. Ensure safe lifting techniques are used – keep back straight – bend using legs ­when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Avoid upper body/top heavy bending - do not lean forward/sideways. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.
Positioning of Appliance for Final Installation – within compartment etc. restricting installation.
Recommend 2 persons lift appliance to position into place, space permitting. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, onto worktop if practicable. Ensure stable balance achieved and lift upwards to drop into place onto bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. If 1 person positioning onto bracket recommend obtain firm grip supporting base of boiler. Ensure safe lifting techniques are used – keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.
Positioning of Appliance for Final Installation – in roof space restricting installation.
Recommend 2 persons lift appliance to position into place, space permitting. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to position into place onto bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. If 1 person positioning onto bracket recommend obtain firm grip supporting base of boiler. Ensure safe lifting techniques are used - keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance. It is recommended a risk assessment of the roof space area be carried out before moving the appliance into the area to take into account access, stability of flooring, lighting and other factors, and appropriate measures taken.
0020008153-05
6
Appliance Safety Devices - User Instructions
Electrical Supply Failure Reset Switch
The boiler will not work without an electrical supply.
Normal operation of the boiler should resume when the electrical supply is restored.
Reset any external controls, to resume normal operation of the central heating.
If the boiler does not resume normal operation turn the mains reset switch off and on. If the boiler does not resume normal operation after this the overheat stat may have operated.
Overheating Safety
In the event of the boiler overheating the safety devices will cause a safety shutdown. If this happens, call your Installation/ Servicing company.
Frost Protection
The appliance has a built in frost protection programme as long as the electricity and gas are left switched on.
This device operates the burner and system pump when the temperature inside the boiler falls to 30C.
Any other exposed areas of the system should be protected by a separate frost thermostat.
Condensate Drain Blockage
As a safety feature the boiler will stop working if the condensate drain becomes blocked. During freezing conditions this may be due to the forming of ice in the condense drain external to the house. Release an ice blockage by the use of warm cloths on the pipe. The boiler should then restart. Contact your installation/ servicing company if the fault persists.
Maintenance and Servicing - User Instructions
For the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the installation conditions and usage, but in general, once a year should be enough.
If this appliance is installed in a rented property in the UK there is a duty of care imposed on the owner of the property by the current issue of the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Glow-worm’s own service organisation using the telephone number on the inside front cover of this booklet.
Please be advised that the installation engineer on completion of commissioning and servicing should complete the ‘Benchmark’ logbook.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Logbook. You can check your installer is CORGI registered by calling CORGI direct on: - 01256 372300.
Spare Parts
REMEMBER, When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Glow-worm.
If replacement parts are required contact Glow-worm’s own service organisation using the telephone number on the inside front cover of this booklet.
Please quote the name of the appliance, this infomation will be on the name badge on the front of the appliance.
If in doubt seek advice from the local gas company or Glow­worm’s own service organisation using the telephone number on the inside front cover of this booklet.
7
0020008153-05
Operating the Boiler - User Instructions
CONTROLS FASCIA
CONTROL LIGHT
MAINS RESET SWITCH
CENTRAL HEATING WATER TEMPERATURE CONTROL
DIGITAL DISPLAY
OPERATION OF THE BOILER
1. Check that all isolating valves on the boiler are open and that water flows from the hot water tap.
2. If you are in any doubt about the boiler being filled with water contact your installer or Glow-worm's own service
organisation using the telephone number on the inside front cover of this booklet. Do not operate the boiler
without water.
3. Check that the electrical supply to the boiler is ON and set any remote controls as required.
4. With the Central Heating Water Temperature Control in its "OFF" (0) position, turn the Mains Reset Switch to the ON (1) position, the running lamp will initially illuminate (green) then go off, the system pressure will be displayed and should read on the digital display, at least 0.7bar (recommended 1.0bar), if less you MUST contact your installation / servicing company.
9239
Diagram 1
USER CONTROLS
CENTRAL HEATING CONTROL
1. Turn the central heating water temperature control "ON", the lighting sequence will begin, the running lamp will illuminate (green) to indicate the boiler has lit, the system temperature will now be displayed instead of system pressure.
The temperature of the central heating water can be adjusted by turning the central heating water temperature control to desired setting between 1 'Min' and
Set the control to
If the boiler fails to light, reset the controls, see paragraph below, TO RESET
If a fault occurs the running lamp will flash red and a fault code will appear on the digital display.
TO RESET
2. Turn the Mains Reset Switch to 0, wait for 5 seconds, turn Mains Reset Switch to 1, the boiler is reset.
If the fault persists contact your installer/service provider using the telephone number on the inside font cover of this booklet.
TO TURN THE BOILER OFF
3. Turn the Mains Reset Switch to the OFF (0) position.
Turn the gas supply OFF at the gas service cock if the boiler is to be out of use for some time.
'0' to switch off heating.
'Max'. Maximum setting is appoximately 82°C.
0020008153-05
8
1 Technical Information
1.1 IMPORTANT NOTICE
The boiler is supplied in one carton, which includes a fittings and documentation pack.
This boiler is for use only on G20 natural gas, but the 30hxi may be converted for use on G31 gas (Propane L.P.G.).
Where no British Standards exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
The installation of this boiler must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
1.2 Statutory Requirements
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB the installation of the boiler must be carried out by a competent person as described in the following regulations:
The manufacturer’s instructions supplied.
The Gas Safety (Installation and Use) Regulations.
The appropriate Buildings Regulations either The Building Regulations, The Building Regulations (Scotland),The Building Regulations (Northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for Electrical Installation.
In GB the following Codes of Practice apply:
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671.
In IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
NOTE: For further information, see the current issue of the Building Regulations, approved document L1 ( in the UK) and the following current issues of:
1) Central heating system specification (CheSS) and
2) Controls for domestic central heating system and hot water. BRECSU.
Certification
This boiler certificated to the current issue of EN 483 for performance and safety.
It is important that no alteration is made to the boiler, without permission, in writing, from Glow-worm.
Any alteration that is not approved by Glow-worm, could invalidate the warranty and could also infringe the current issue of the Statutory Requirements.
9
0020008153-05
600
MAX.
87
MIN.
1 Technical Information
334
176
48
66
12856
113.5
53
INSIDE WALL FIXING FACE
CONDENSATE DRAIN
48
73
TABLE 1
12 hxi = 30kg
TOTAL WEIGHT
GAS CONNECTION Rc1/2 (1/2in BSPT)
WATER CONNECTION 22mm. copper
15 hxi = 30kg 18 hxi = 30kg 24 hxi = 33kg 30 hxi = 33kg 38 hxi = 33kg
33
GAS
600
CONDENSATE DRAIN
133
30
13
54
375
Diagram 1.1
1.3 Gas Supply
The gas installation shall be in accordance with the relevant standards.
In GB this is BS6891.
In IE this is the current edition of I.S.813 "Domestic Gas Installations".
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) (Propane G31, 37mbar) at the boiler.
On completion, test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
ELECTRICITY SUPPLY 230V~50Hz fused 3A
ELECTRICAL RATING 60W
INTERNAL FUSE RATE Main PCB 630mAT
0020008153-05
10
1 Technical Information
12 hxi
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
Case Off 9.1 +0.2 -0.5
Case On 9.3 +0.3 -0.5
2
15 hxi
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
Case Off 9.1 +0.2 -0.5
2
Case On 9.3 +0.3 -0.5
18 hxi
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
Case Off 9.1 +0.2 -0.5
2
Case On 9.3 +0.3 -0.5
24 hxi
TABLE 2
MIN MAX
m3/h
ft3/h
m3/h
ft3/h
m3/h
ft3/h
0.53 1.29
18.7 45.6
MIN MAX
0.53 1.61
18.7 57.0
MIN MAX
0.53 2.00
18.7 70.6
TABLE 2 (cont'd)
30 hxi
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
Case Off 9.1 +0.2 -0.5
Case On 9.3 +0.3 -0.5
2
MIN MAX
m3/h
ft3/h
0.56 3.02
19.8 107
38 hxi
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
1.4 Technical Data
All dimensions are given in millimetres (except as noted).
See diagram 1.1 and Tables 1 and 2.
The data label is positioned on the inner door, refer to diagram 1.2.
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is: All hxi boilers: Class 'A'.
The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated has been certified by B.S.I.
Case Off 8.8 +0.2 -0.5
2
Case On 9.0 +0.3 -0.5
MIN MAX
m3/h
ft3/h
0.67 4.06
23.8 143
BURNER
%CO
APPROXIMATE
GAS RATE
(after 10 mins.
from cold)
Case Off 9.1 +0.2 -0.5
2
Case On 9.3 +0.3 -0.5
m3/h
ft3/h
MIN MAX
0.56 2.58
19.8 91.1
1.5 Condensate Drain
A plastic drain pipe must be fitted to allow discharge of condensate to a drain.
Condensate should, if possible, be discharged into the internal household draining system. If this is not practical, discharge can be made externally into the household drainage system or a purpose designed soak away, see Section 7.3 for more details.
11
0020008153-05
1 Technical Information
12334
12335
12336
12327
11975
12330
Diagram 1.2
0020008153-05
12
2 Boiler Location and Ventilation
2.1 Boiler Location
This boiler is not suitable for outdoor installation.
This boiler may be installed in any room, although particular attention is drawn to the installation of a boiler in a room containing a bath or shower where reference must be made to the relevant requirements.
This boiler is suitable for installation in bathroom zones 2 and 3.
In GB this is the current I.E.E. WIRING REGULATIONS and BUILDING REGULATIONS.
In IE reference should be made to the current edition of I.S.813 "Domestic Gas Installations" and the current ETCI rules.
The boiler must be mounted on a flat wall, which is sufficiently robust to take its total weight, see Table 1. Section 1.
2.2 Clearances
The boiler should be positioned so that at least the minimum operational and servicing clearances are provided, see diagram
2.1.
Additional clearances may be beneficial around the boiler for installation and servicing.
For flue installations where external access is not practicable, consideration should be given for the space required to insert the flue internally, which may necessitate clearance larger than those specified in diagram 2.1.
12344
5
5
600
150
5
2.3 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998 and BG Operational Procedures, Part 19 Building and Kitchen Work, Section 7 - Timber Frame Constructions. If in doubt seek advice from the local gas undertaking or Glow-worm.
2.4 Room Ventilation
The boiler is room sealed, so when it is installed in a room or space, a permanent air vent is not required.
2.5 Compartment Ventilation
Due to the high efficiency and hence low casing temperature of this boiler, cupboard or compartment ventilation is not necessary.
Leave existing air vents.
20
200
† A removable compartment door can be placed at least 5mm in front of the appliance.
MINIMUM CLEARANCE FROM PERMANENT SURFACES
Diagram 2.1
20
13
0020008153-05
3 Flue Location and Ventilation
3.1 Flue Options
This boiler is suitable for concentric Horizontal and Vertical flues, elevated horizontal and vertical twin, all are fitted onto the top of the boiler.
The Glow-worm Flue Options Guide, available on request or through the web site, describes in detail the necessary accessories.
These instructions describe the use of the standard and telescopic horizontal flues.
The instructions for all other flues will be contained in those packs.
75 min. to 540 max.
WALL THICKNESS
87min
112
3.2 Flue Length
The maximum permissable horizontal flue length is 10 metres plus the flue terminal, this can be achieved by use of the accessories, however should an additional 90 be used then the length MUST be reduced by 1metre.
When extension pipes are used the flue system must be designed to have a continuous fall to the boiler of at least 2.5 44mm/metre, to allow condensate to run back into the boiler and out via the drain.
The flue can be installed from inside the building, when access to the outside wall face is not practicable.
The diagrams 3.1 to 3.4 describe the lengths achievable without the use of extensions or elbows.
208 min. to 413 max.
12839
87min
WALL THICKNESS
112
o
or 2 x 45o elbows
o
12837
176
OUTSIDE WALL FACE
NOTE. If necessary, it is permitted to increase this dimension to 600mm max.
BOILER MOUNTING WALL
TOP REAR FLUE - STANDARD
NOTE. If necessary, it is permitted to increase this dimension to 600mm max.
87min
Max flue length 717mm
20mm min. clearance
A
Diagram 3.1
136239
C
L
FLUE
12855
176
OUTSIDE WALL FACE
NOTE. If necessary, it is permitted to increase this dimension to 600mm max.
BOILER MOUNTING WALL
TOP REAR FLUE - TELESCOPIC
NOTE. If necessary, it is permitted to increase this dimension to 600mm max.
87min
Max flue length 589mm
20mm min. clearance
A
Diagram 3.3
136239
C
L
FLUE
12854
OUTSIDE WALL FACE
INTERNAL SURFACE
A
Max. distance from outside
wall face to min clearance. LH - 458mm RH - 561mm
TOP SIDE FLUE - STANDARD
0020008153-05
Min. distance from outside wall face to min clearance. LH/RH - 75mm
Diagram 3.2 Diagram 3.4
OUTSIDE WALL FACE
Max. distance from outside wall face to min clearance. LH - 330mm RH - 433mm
INTERNAL SURFACE
TOP SIDE FLUE - TELESCOPIC
14
A
Min. distance from outside
wall face to min clearance. LH - 125mm RH - 228mm
3 Flue Location and Ventilation
MINIMUM SITING DIMENSIONS FOR FANNED FLUE TERMINALS POSITION MM
HORIZONTAL FLUES
A DIRECTLY BELOW AN OPENING, AIR BRICK,
OPENING WINDOWS 300
B ABOVE AN OPENING, AIR BRICK,
OPENING WINDOWS 300
C HORIZONTALLY TO AN OPENING,
AIR BRICK, OPENING WINDOWS 300
D BELOW GUTTER, DRAIN/SOIL PIPE 25
E BELOW EAVES 25
F BELOW A BALCONY OR CAR PORT 25
G FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 25
H FROM INTERNAL/EXTERNAL CORNERS 25
H TO A BOUNDARY ALONGSIDE THE
*
TERMINAL 300
I ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300
J FROM SURFACE OR A BOUNDARY
*
FACING THE TERMINAL 600
K FACING TERMINALS 1200
L FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING 1200
M VERTICAL FROM A TERMINAL 1500
N HORIZONTALLY FROM A TERMINAL 300
3.3 Terminal Position
The minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in diagram 3.5. For Ireland the minimum distances for flue terminal positioning must be those detailed in I.S.813 "Domestic Gas Installations".
The terminal must be exposed to the external air, allowing free passage of air across it at all times.
Being a condensing boiler some pluming may occur from the flue outlet. This should be taken into consideration when selecting the position for the terminal.
H
* and J* See diagram 3.5 . These dimensions comply with
the building regulations, but they may need to be increased to avoid wall staining and nuisance from pluming depending on site conditions.
Increased siting flexibility can be achieved by using the Glow­worm Plume Management Kit, A2044000 (black) or A2044100 (white).
NOTE: If necessary it is permitted to increase the terminal protrusion through the outside wall to greater than the minimum dimension of 87mm but no more than 600mm, see diagram 1.1.
Carports or similar extensions of a roof only, or a roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if made of plastic sheeting. If the carport comprises of a roof and two or more walls, seek advice from the local gas supply company before installing the boiler.
3.4 Terminal Guard
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide minimum of 50mm clearance from any part of the terminal and be central over the terminal.
The guard should be similar to that shown in diagram 2.6.
A suitable guard is manufactured by: -
Tower Flue Components
Morley Rd.
Tonbridge
Kent
TN9 1RA.
Size: 280mm x 280mm x 270mm.
TERMINAL GUARD
12325
VERTICAL FLUES
P FROM ANOTHER TERMINAL 600
Q ABOVE ROOF LEVEL 300
R FROM ADJACENT OPENING WINDOW 1000
S FROM ADJACENT WALL TO FLUE 300
Diagram 3.5
15
Diagram 3.6
0020008153-05