Glow-worm Hideaway 80B FF Instructions For Use Installation And Servicing

2000225144B.09.03
Instructions for Use
Installation and Servicing
To be left with the user
80B FF
G.C. No. 41-047-35
Balanced
Fanned Flue Boiler
Hepworth Heating Ltd., Nottingham Road, Belper, Derbyshire. DE56 1JT
Guarantee Registration
Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances are manufactured to the very highest standard so we are pleased to offer our customers a Comprehensive First Year Guarantee.
We recommend you complete and return as soon as possible your guarantee registration return literature, supplied in the document envelope.
If your guarantee registration return literature is missing you can obtain a copy or record your registration by telephoning the Heatcall Customer Service number 01773 828100.
For customer service call:
(01773) 828100
Technical helpline: (01773) 828300
For General and Sales enquiries:
Tel. (01773) 824141
Fax: (01773) 820569
To register your Glow-worm appliance call:
2000225144B
0208 247 9857
2
Contents
The instructions consist of three parts, User, Installation and Servicing Instructions, which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
CONTENTS DESCRIPTION SECTION PAGE No.
Important Information 4
INSTRUCTIONS
FOR USE
INSTALLATION
INSTRUCTIONS
SERVICING
INSTRUCTIONS
Draining and Filling 5 Appliance Introduction 5 Appliance Safety Devices 5 Maintenance and Servicing 6 Instructions for Use 7
General Data 1 8 Water Systems 2 11 Flue and Ventilation 3 12 Installation 4 13 Electrical Wiring 5 20 Commissioning 6 21 Instructions to the User 7 23
Servicing 8 23 Fault Finding 9 26 Replacement of Parts 10 29 Spare Parts 11 31
3
2000225144B
Important Information
Gas safety (Installation and use) Regulations
In your interests and that of gas safety, it is the law that ALL gas appliances are installed and serviced by a competent person in accordance with the above regulations.
Testing and Certification
This boiler is tested and certificated for safety and performance. It is therefore important that no alteration is made to the boiler, without permission, in writing, from Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the certification, boiler warranty and may also infringe the current issue of the Statutory Requirements. The requirements are: The installation of this boiler must be carried out by a competent person in accordance with the current rules in force in the countries of destination at the time of installation. Manufacture's instructions supplied. Manufacture's instructions must not be taken as overriding statutory requirements.
CE Mark
This boiler meets the requirements of Statutory Instrument No. 3083 The boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes of Regulation 5 certified by: Notified body 0086.
Product/production certified by: Notified body 0086.
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to the electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Control of Substances Hazardous to Health
The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
INSULATION PADS/CERAMIC FIBRE
These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be suscepti­ble to irritation. High dust levels are usual only if the material is broken. Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention. The insulation is composed of non-combustible material.
Electrical Supply
WARNING: This boiler must be earthed.
All system components shall be of an approved type and shall be connected in accordance with the current issue of BS7671 and any applicable local regulations.
All external wiring between the appliance and the electrical supply and earthing requirements shall comply with the current IEE Regulations.
Connection of the boiler and system controls to the mains supply must be through a common isolator and must be fused 3A, maximum. This method of connection must be by a fused double pole isolating switch, with a minimum contact separation of 3mm on both poles. The switch should be readily accessible and preferably adjacent to the appliance. It should supply the appliance only and be easily identifiable as so doing.
Alternatively, an unswitched shuttered socket outlet and 3A fused 3 pin plug, both to the current issue of BS1363 may be used provided that they are not used in a room containing a bath or shower.
Wiring to the boiler must be PVC 85 than 0.75mm2 (24/0.20mm).
o
C insulated cable, not less
Gas leak or fault
WARNING: If a gas leak or fault exists or is suspected, turn the
boiler off and consult the local gas supply company or your installation/service company.
Sealed Components
WARNING: DO NOT interfere with any sealed components
within this appliance.
Manual Handling Guidance
During the appliance installation it will be necessary to employ caution and assistance whilst lifting as the appliance exceeds the recommended weight for a one man lift.
In certain situations it may be required to use a mechanical handling aid.
Take care to avoid trip hazards, slippery or wet surfaces.
Heating System Controls
The heating system should have installed: a programmer and room thermostat controlling the boiler.
Thermostatic radiator valves may be installed, however they must not be fitted in a room where the room thermostat is located.
Note: For further information, see the current issue of the Building Regulations, approved document L1, ( in the UK) and the references:
1) GIL 59, 2000: Central heating system specification (CheSS) and
2) GPG 302, 2001: Controls for domestic central heating system and hot water. BRECSU.
2000225144B
4
Important Information
Air in the heating system
Persistent air in the heating system may indicate leaks in the system or corrosion taking place. Call your Installation/Servicing company.
Boilers Installed in a Compartment
If the boiler is fitted in a compartment, cupboard etc., do not obstruct the purpose built compartment vents or the grill on the boiler.
Do not use the compartment for storage purposes.
Draining and Filling
Draining and filling
Caution: The boiler must only be drained and filled by a competent person.
If the boiler is to be out of use for any period of time during severe weather conditions we recommend the whole system including the boiler, be drained off to avoid the risk of freezing up. If an immersion heater is fitted to the hot water cylinder make sure it is switched off.
If in doubt, consult your servicing company.
Protection Against Freezing
If the boiler is to be out of use for any period of time during severe weather conditions we recommend the whole system including the boiler, be drained off to avoid the risk of freezing up. If an immersion heater is fitted to the hot water cylinder make sure it is switched off.
Appliance Introduction
Introduction
The Glow-worm Hideaway B FF series are Balanced fanned flue boilers. They provide heating and if required, an indirect domestic hot water supply.
The boiler is of the I as distributed in the United Kingdom.
The boiler is automatic in operation, having only one user control, the boiler temperature control.
category for use with Natural Gas (G20)
2H
Appliance Safety Devices
Air flow rate safety device
If the flue is obstructed, even partially, the built in safety system will turn the boiler OFF, the fan will continue to run. The boiler will be ready to operate when the fault has been cleared.
The installation of this boiler must be carried out by a competent person in accordance with the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
These instructions should be carefully followed for the safe and economical use of your boiler.
Note: The boiler serial number is marked on the data label attached to the heat shield under the control box. The 'Instructions for Use' section describes how to safely use the boiler.
Electrical supply failure
The boiler will not operate without an electrical supply. Normal operation of the boiler should resume when the electrical supply is restored.
Reset any central heating system controls, to resume normal operation.
If the boiler does not resume normal operation it is advisable to consult your installation / servicing company.
5
2000225144B
Maintenance and Servicing
Cleaning
WARNING: This appliance contains metal parts (components) and care should be taken when handling and cleaning with particular regard to edges of sheet metal parts to avoid any possibility of personal injury.
The boiler casing can be cleaned with a damp cloth, followed by a dry cloth to polish.
Do not use abrasive or solvent cleaners.
Maintenance and Servicing
To ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, refer to guarantee registration with this literature.
If this appliance is installed in a rented property in the UK there is a duty of care imposed on the owner of the property by the current issue of the Gas Safety (Installation and Use) Regulations, Section 35.
Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Heatcall (Glow­worm’s own service organisation) using the telephone number on the inside front cover of this literature.
Please be advised that the ‘Benchmark’ logbook should be completed by the installation engineer on completion of commissioning and servicing.
All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your benchmark Logbook. You can check your installer is CORGI registered by calling CORGI direct on: 01256 372300.
Spare Parts
Remember, when replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Hepworth Heating Ltd.
If a part is required contact Heatcall (Glow-worm’s own service organisation) using the telephone number on the inside front cover of this booklet.
Please quote the name of the appliance, this infomation will be on the name badge on the front of the appliance.
If in doubt seek advice from the local gas company or Heatcall (Glow-worm’s own service organisation) using the telephone number on the inside front cover of this booklet.
Boiler casing
CAUTION. Do not remove or adjust the casing in any way, as
incorrect fitting may result in faulty operation. If in doubt, consult your installation/service company.
2000225144B
6
Instructions for Use
To Turn the Appliance On
Turn the electrical supply on to the boiler and check that all remote controls are calling for heat.
Turn the boiler temperature control clockwise to any position between “0” and "Max", see diagram 1.
"Max" is approximately 82°C (180°F).
The boiler lighting operation is now automatic as follows:
The fan operates and after a short period of time, the spark ignition operates, the solenoid opens, then the burner will light shown by the burner ON indicator (green) on the control panel lighting up.
The burner will remain alight until switched off by the control thermostat or any remote control.
Note: If the boiler is turned OFF at the boiler temperature control, wait at least 30 seconds before switching on again.
When the boiler switches off, the burner will go out.
The automatic lighting sequence will operate again when heat is required.
It should be noted that this is a fanned flue appliance and fan operation may be heard.
If the reset/standby indicator lights, turn the boiler temperature control to "0" (off), wait 30 seconds, then repeat the lighting instructions.
BOILER TEMPERATURE CONTROL
9857
To Turn the Appliance Off
For short periods, turn the boiler temperature control fully anti­clockwise to “0” (off), the reset/standby indicator will be on.
To relight, turn the boiler temperature control to any position between “0” and “Max”.
For longer periods, turn the boiler temperature control fully anti­clockwise to “0” (off) and switch off the electrical supply to the boiler.
To relight follow the lighting sequence given above.
"OFF" POSITION
"BURNER ON" INDICATOR
RESET/STANDBY
INDICATOR
Diagram 1
7
2000225144B
1 General Data
GAS CONNECTION
1
Rc
1
/
(
/
2
in. B.S.P.T.)
2
WATER CONNECTIONS
Rc1 (1in. B.S.P.T.)
WATER CONNECTIONS Rc1 reduced with DISTRIBUTOR TUBE to
3
Rc
3
/
(
/
in. B.S.P.T.) (pumped return)
4
4
387
194
294
700
558
GENERAL DIMENSIONS - given in millimetres
Important Notice
This boiler is for use only on G20 gas.
The boiler is delivered in one pack and the flue pack is supplied separately.
Wherever possible, all materials, appliances and components to be used shall comply with the requirements of applicable British Standards.
Where no British Standard exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
Refer to Manual Handling Operations, 1992 Regulations.
Sheet Metal Parts
WARNING. When installing or servicing this boiler, care should be taken to avoid any possibility of personal injury when handling the edges of sheet metal parts.
1.1 Technical Data
See diagrams 1.1 and 1.2.
All dimensions are given in millimetres (except as noted)
Approximate weight of complete boiler and packaging :131.5kg (290lb)
Water content : 5.76 litre (1.27gallons)
Gas connection : Rc
Water connection : Rc1 (1in BSPT)
Electrical supply : 230V~50Hz, fused 3A
Burner : Aeromatic
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is 'D' 78.4%.
The value is used in the UK Governments Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by B.S.I.
1
/2 (1/2in BSPT)
1.2 Range Rating
See diagram 1.2.
.
NOTE: The boiler casing can be
set at two heights, MAX. and MIN.
555
300
MAX.
32
442
3
900
MIN.
860
364
Diagram 1.1
1.3 Statutory Requirements
The appliance is suitable only for installation in GB and IE and should be installed in accordance with the rules in force.
In GB the installation of the boiler must be carried out by a competent person as described in the following regulations:
The manufacturers instructions supplied.
The Gas Safety (Installation and Use) Regulations.
The appropriate Buildings Regulations either The Building Regulations, The Building Regulations (Scotland),The Building Regulations (Northern Ireland).
The Water Fittings Regulations or Water byelaws in Scotland.
The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH).
The Current I.E.E. Wiring Regulations.
Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.
In IE, the installation must be carried out by a competent person and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for Electrical Installation.
In GB the following Codes of Practice apply:
BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671.
In IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.
Manufacturers instructions must not be taken as overriding statutory requirements.
1.4 B.S.I Certification
This boiler is certificated by B.S.I., for safety and performance. It is, therefore, important that no alteration is made to the boiler unless agreed, in writing, by Hepworth Heating Ltd.
Any alteration not approved by Hepworth Heating Ltd., could invalidate the B.S.I. certification, boiler warranty and could infringe the current issue of the Statutory Requirements.
9921
2000225144B
8
1 General Data
1.5 Gas Supply
The gas installation shall be in accordance with the relevant standards.
In GB this is BS6891.
In IE this is the current edition of I.S.813 "Domestic Gas Installations".
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
On completion test the gas installation using the pressure drop method and suitable leak detection fluid, purge in accordance with the current issue of BS6891.
1.6 Electrical
WARNING. This boiler must be earthed.
The electrical installation must be carried out by a competent person. All external components shall be of the approved type and shall be connected in accordance with the current issue of BS7671 and any local regulations which apply.
External wiring must be correctly earthed, polarised and in accordance with the relevant standards.
In GB this is BS 6891.
In IE this is the current edition of I.S.813 "Domestic Gas Installations".
Connection of the boiler and any system controls to the mains supply through an unswitched shuttered socket outlet and 3A fused 3 pin plug, both to the current issue of BS1363. Alternatively, a 3A fused double pole isolating switch may be used, having a minimum double pole contact separation of 3mm, serving only the boiler and system controls.
Heat resistant cable of at least 0.75mm current issue of BS6500 Table 16, must be used for all connections within the boiler casing, to the control box, pump etc.
2
(24/0.20mm), to the
To floor level
MAX.900 MIN. 860
BOILER CASING ALTERNATIVE HEIGHT POSITIONS
MAX.
MIN.
FLOOR LEVEL
BOILER CASING HEIGHT(S)
WORKTOP
10
407 MIN.
BOILER
CUPBOARDS
MINIMUM CLEARANCES LEVEL WITH WORKTOP
10
9922
Diagram 1.3
407 MIN.
9923
5
BOILER
Diagram 1.4
Diagram 1.2
WORKTOP OR FIXTURE
10121
10
10 10
CUPBOARD
CUPBOARD
MINIMUM CLEARANCES UNDER WORKTOP, FIXTURES
9
10124
Diagram 1.5
2000225144B
1 General Data
1.7 Boiler Location
This boiler is not suitable for outside installation.
The boiler casing can be fitted at two heights. Refer to diagram 1.3.
The boiler is assembled at the factory with the control box and heat shield fitted in the lower position.
The boiler must stand on a level floor, conforming with local authority requirements and building regulations. The base temperature is within the requirements of the current issue of BS5258. The boiler may stand on a wooden floor but a metal base plate is required to protect plastic tiles and similar floor coverings.
Suitable installation clearance needs to be available at the sides of the boiler to facilitate direct connection of pipework and making good around the flue assembly. The actual clearance required will vary with site conditions.
When the boiler is to be installed level with work surfaces and the like, minimum clearances should be provided as shown in diagram 1.4. Work tops which overhang the cupboard sides, almost in contact with the casing top, require a larger minimum air gap. Flush sided fixtures require the same overall minimum space but can have a reduced air gap on one side.
Boilers to be installed under work tops or fixtures, should be positioned to provide minimum clearances as shown in diagram
1.5. To facilitate minimum clearances it may be necessary to modify kitchen units and fixtures.
A front access clearance for servicing of 700mm, should be provided.
The boiler can be installed within a cupboard, refer to minimum ventilation and clearances as shown in diagram 1.6.
If the boiler is to be installed in a cupboard or compartment, make sure that nothing will obstruct the openings/vents in the compartment.
A compartment used to enclose the boiler must be designed and constructed specifically for this purpose. An existing cupboard or compartment modified for the purpose may be used. Details of essential features of cupboard or compartment design are given in the current issue of BS6798.
The boiler may be installed in any room, although particular attention is drawn to the requirements of BS7671 with respect to the installation of a boiler in a room containing a bath or shower. Any electrical switch should be so positioned that it cannot be touched by a person using the bath or shower. The electrical provisions of the Building Standards (Scotland) Regulations apply to such installations in Scotland.
Where the installation of the boiler will be in an unusual location, special procedures are necessary the current issue of BS6798 gives detailed guidance on this aspect.
1.8 Heating System Controls
The heating system should have installed: a programmer and room thermostat controlling the boiler.
Thermostatic radiator valves may be installed, however they must not be fitted in a room where the room thermostat is located.
Note: For further information, see the current issue of the Building Regulations, approved document L1, and the references:
1) GIL 59, 2000: Central heating system specification (CheSS) and
2) GPG 302, 2001: Controls for domestic central heating system and hot water. BRECSU.
272cm2 FREE AREA
10mm
10mm
FOR VENTILATION
10mm
DOOR
CUPBOARD CUPBOARD
272cm2 FREE AREA FOR VENTILATION
IMPORTANT
A CLEARANCE OF 10mm IS REQUIRED BETWEEN THE FRONT OF THE APPLIANCE AND THE FITTED DOOR.
THE VENTILATION SLOTS ON THE FRONT OF THE APPLIANCE MUST BE KEPT CLEAR.
THE FREE AREA FOR VENTILATION MUST NOT BE REDUCED IF A GRILLE IS FITTED.
CUPBOARD MINIMUM VENTILATION & CLEARANCE Diagram 1.6
2000225144B
10
2 Water Systems
The installation of the boiler must comply with the requirements of the current issue of BS6798, in Ireland, refer also to the current edition of I.S.813 "Domestic Gas Installations".
In GB it is necessary to comply with the Water Supply (Water Fittings) Regulations 1999 (for Scotland, the Water Byelaws 2000, Scotland).
To comply with the Water regulations your attention is drawn to: The Water Regulations guide published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements.
In IE the requirements given in the current edition of I.S.813 "Domestic Gas Installations" and the current Building Regulations must be followed.
2.1 Water Pressure Head
The boiler shall only be connected to a cistern water supply with a minimum head of 1metre (3ft3in) and a maximum head of 27metres (90ft) which has an open vent in the system.
The working pressure must be within the range 0.1bar to 2.7bar (1.3 to 39lbftin
2
).
The boiler MUST NOT be connected to a sealed water system.
It is recommended that plastic pipes for primary pipework should not be used for this boiler.
2.2 Inhibitor
Attention is drawn to the current issue of BS5449 and BS7593 on the use of inhibitors in central heating systems.
If an inhibitor is to be used in the system, contact should be made with the inhibitor manufacturers so that they can recommend their most suitable product.
REFER TO BS 5546
22mm VENT 15mm COLD FEED
INDIRECT CYLINDER
(Shown with 27metres Max.
recommended
thermostat and valve).
When using in an existing system take special care to drain the entire system, including the radiators, then thoroughly clean out before fitting the boiler whether or not adding an inhibitor.
2.3 Gravity Domestic and Pumped Heating
It is recommended that a cylinder thermostat is used to prevent the stored water temperature becoming unnecessarily high when the central heating pump is off.
The domestic primary flow and return must be 28mm o.d. The installation must comply with the current issue of BS5546 and BS6700, see diagram 2.1.
If the above conditions cannot be met, it is suggested that a fully pumped system be used.
2.4 Pumped Heating and Hot Water
Where a single flow and return is taken from the boiler, a minimum static head of 1metre (3ft3in) must be provided between the water line of the feed tank and the centre of the waterway, see diagram 2.2.
2.5 Circulation Pump
Normally the pump should be set to give a temperature difference of 11oC (20oF) across the boiler. At the appropriate pumped flow rate the pressure loss through the boiler can be found from the graph, diagram 2.3.
Use a pump with integral valves or fit isolating valves as close to the pump as possible.
2.6. Cylinder
For all systems supplying domestic hot water the cylinder must be indirect.
2.7 Safety Valve
A safety valve need not be fitted to an open vented system.
0869
2.8 Draining Tap
A draining tap must be provided at the lowest points of the system which will allow the draining of the entire system, including the boiler and hot water cylinder.
Draining taps should be to the current issue of BS2879.
BOILER C
L
1 metre MIN. 27metres MAX.
BOILER C
L
DRAIN OFF COCK
15mm COLD FEED
DRAIN OFF COCK
28mm
PUMP
Distributor tube in pumped return connection
22mm VENT
PUMP
Distributor tube in pumped return connection
Heating Circuit
TO INDIRECT CYLINDER
Heating Circuit
Diagram 2.1
Diagram 2.2
2.9 Thermostatic Radiator Valves
If thermostatic radiator valves are fitted care must be taken to ensure that there is an adequate flow rate through the boiler when they close, refer to the current issue of BS7478 for guidance. If fitted to all radiators ensure a bypass is fitted and adjust to achieve a temperature difference no greater than 20°C between flow and return with the thermostatic valves closed.
FLOW RATE (GALLON/MINUTE) 0123456789
2.00
0870
1.75
1.50
1.25
1.00
0.75
0.50
WATER PRESSURE LOSS
(metre HEAD OF WATER)
0.25
0
6
0
12 18
FLOW RATE (LITRES/MINUTE)
24 30 36 42
1074
70
60
50
40
30
20
WATER PRESSURE LOSS
(INCHES HEAD OF WATER)
10
0
Diagram 2.3
11
2000225144B
3 Flue and Ventilation
The flue must be installed in accordance with the rules in force in the countries of destination.
3.1 Terminal Position
The minimum acceptable siting dimensions for the terminal from obstruction, other terminals and ventilation openings are shown in diagram 3.1. For Ireland the minimum distances for flue terminal positioning must be those detailed in I.S.813 "Domestic Gas Installations".
A
E
L
F
UNDER CAR PORT etc.
B,C
G
A
H,I
B,C
K
F
G
J
C
D
F
K
The terminal must be exposed to the external air, the position allowing free passage of air across it at all times.
Car ports or similar extensions of a roof only, or a roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if it is made of plastic sheeting. If the car port consists of a roof and two or more walls, seek advice from the local gas company before installing the boiler.
If the terminal is fitted within 600mm below plastic guttering or painted soffit an aluminium shield 1500mm long should be fitted immediately beneath the guttering or eaves. If the terminal is fitted within 450mm below painted eaves or a painted gutter, an aluminium shield 750mm long should be fitted immediately beneath the guttering or eaves.
3.2 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking or Hepworth Heating Ltd.
3.3 Terminal Guard
A terminal guard is required if persons come into contact with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide a minimum of 50mm clearance from any part of the terminal and
11508
be central over the terminal.
A suitable guard, reference Type “K3”, can be obtained from:
Tower Flue Components Ltd.,
Morley Road, Tonbridge,
Kent. TN9 1RA
MINIMUM SITING DIMENSIONS FOR FANNED FLUE TERMINALS POSITION MM
HORIZONTAL FLUES
A DIRECTLY BELOW, ABOVE OR
HORIZONTALLY TO AN OPENING, AIR BRICK, OPENING WINDOW, AIR VENT, OR ANY
OTHER VENTILATION OPENING 300 B BELOW GUTTER, DRAIN/SOIL PIPE 25 C BELOW EAVES 25 D BELOW A BALCONY OR CAR PORT 25 E FROM VERTICAL DRAIN PIPES AND
SOIL PIPES 25 F FROM INTERNAL/EXTERNAL CORNERS
OR TO A BOUNDARY ALONGSIDE THE
TERMINAL 25 G ABOVE ADJACENT GROUND OR
BALCONY LEVEL 300 H FROM SURFACE OR A BOUNDARY
FACING THE TERMINAL 600 I FACING TERMINALS 1200 J FROM OPENING (DOOR/WINDOW)
IN CAR PORT INTO DWELLING 1200 K VERTICAL FROM A TERMINAL 1500 L HORIZONTALLY FROM A TERMINAL 300
Diagram 3.1
3.4 Room Ventilation
The boiler is room sealed and does not require the room or space containing it to have permanent air vents.
3.5 Ventilation for Boilers installed in a Cupboard
For minimum ventilation and clearances for cupboard installation refer to section 1.7 and diagram 1.6.
3.6 Compartment Ventilation
Where the boiler is fitted in a compartment, the high and low level permanent air vents must have effective areas, see Compartment Air Vent Table.
Both the high and level air vents must communicate with the same room or must both be on the same wall to outside air.
COMPARTMENT AIR VENT TABLE
COMPARTMENT VENTILATION REQUIREMENTS
VENTILATION FROM ROOM OR SPACE
FROM OUTSIDE
HIGH LEVEL LOW LEVEL
VENT AREA VENT AREA
272cm2 42in2 272cm2 42in
136cm2 21in2 272cm2 42in
2
2
2000225144B
12
9867
4 Installation
* INCREASE TO 30mm IF A FLUE COLLAR IS ADDED
*
FLUE & AIR DUCT LENGTH = A + 15 + 3
General Installation Notes
The appliance pack contains :-
Boiler
Fan connector
Casing panels, packed seperately.
Loose items fittings pack, see list in pack.
The flue is supplied seperately.
NOTE: The rear flue option kit Part No. 425861 is available, which consists of wall cover plates, for replacement Hideaway balanced flue appliances.
Before installation of the boiler make sure that the location selected is in accordance with the requirements of Section 1.7.
FLUE
PACKS
REAR STD.
REAR 75 95 510
NOTE :
IF IT IS NECESSARY TO CUT THE DUCTS TO ACHIEVE THE "FLUE LENGTH" MAKE SURE THAT THE OVERLAPS ARE AS FOLLOWS :­THE OVERLAP FOR AIR DUCT = 25mm THE OVERLAP FOR FLUE DUCT = 50mm
MINIMUM
WALL
THICKNESS
MINIMUM
FLUE
LENGTH
MAXIMUM
FLUE
LENGTH
Diagram 4.1
4.2 Flue Position and Length
Select the boiler location, with due regard to the flue length and terminal position, see diagrams 3.1 and 4.1.
For a wall thickness up to 300mm, provided that the optional wall liner kit is used, the flue can be fully installed from the inside.
For a wall thickness of over 300mm the external flue hole will need to be made good from the outside, this also applies if you use the flue kit without the optional wall liner kit, irrespective of wall thickness.
387
9868
10051
4.1 Unpacking
The boiler casing panels are packed separately within the main carton and are designed to enable gas and water connections to be made before fitting the casing panels.
The casing brackets, flue restrictor, distributor tube and other loose items, are in the fittings pack.
NOTE:
To make a neat finish to the flue outlet a flue collar kit, part No. 900850, with instructions, is available, see diagram 4.4.
If required an optional wall liner kit, part no. 900862, is available complete with instructions.
All flue assemblies are designed for internal installation.
Make sure that the ductings do not slope down towards the boiler.
13
115
194
BOILER OUTLINE
700
FRONT VIEW
Diagram 4.2
2000225144B
4 Installation
4.3 Flue Hole Cutting
Mark out the flue centre, see diagram 4.2, then cut a hole for the flue using, preferably, a 115mm minimum core drill.
4.4 Rear Flue Option Kit - 425861
Fit the wall cover plates as described in the instructions supplied with the kit.
(if applicable)
4.5 Flue Preparation
Note: If the flue collar kit, see diagram 4.4, is to be used
increase the 15mm projection to 30mm.
Extend the telescopic flue to the required length, making sure that the minimum overlap is no less than 25mm, and that the flue terminal projects 15mm minimum beyond wall face, see diagram
4.1.
If it is necessary to cut the flue ensure that the overlap is as stated in diagram 4.1.
Carefully drill though air duct pilot hole and secure with self tapping screw provided in fittings pack, see diagram 4.3.
Seal the joint with the tape provided.
Note: Should any one of the flue sections require cutting to obtain desired flue system length make sure that the overlaps are as follows:-
The overlap for air duct = 25mm
The overlap for flue duct = 50mm.
Take the terminal restrictor and position the clamping bracket making sure the clamping bracket nib protrudes in the slot of the terminal restrictor and secure with locking screw, but do not tighten, see diagram 4.5.
Engage the terminal restrictor on the flue terminal by hooking it over the terminal end and engaging the clamping bracket behind the inner ring of the terminal securing it by tightening the locking screw, see diagram 4.5.
Fit the self adhesive foam seal provided in the flue pack around the air duct at the position shown in diagram 4.1.
Make sure that the ductings do not slope down towards the boiler.
Make good around the flue outside after installation of the boiler.
Important: If the wall liner kit is used, the self adhesive foam seal included in the wall liner kit must be used in place of the one supplied with the flue pack, see diagram 4.6 for position of self adhesive seal.
Push the flue assembly into and through the hole such that it is within the wall, and does not stick out into the room. Do not push the flue assembly too far into the hole as it has to be pulled back into the boiler and secured.
If the boiler is not to be fitted for some time cover the hole in the wall.
7148
OPTIONAL FLUE COLLAR
Diagram 4.4
STANDARD 510mm REAR
FLUE TERMINAL
CLAMPING BRACKET
7323
FLUE SPIGOT
2000225144B
BAYONET CONNECTION
SCREW AND TAPE
GASKET
SCREW (4)
FLUE
Diagram 4.3
9869
14
RESTRICTOR
7332
TERMINAL RESTRICTOR SHOWN FITTED
LOCKING SCREW
CLAMPING BRACKET NIB
Diagram 4.5
4 Installation
4.6 Water Connections - Gravity Domestic and Pumped Heating
Fit suitable fittings into the boiler tappings, see diagram 4.7. Make sure that all pipes are taken backwards and will clear the casings, see diagram 1.1.
NOTE: It is recommended that plastic pipes for primary pipework should not be used for this boiler.
Heating flow: Any one of the four upper connections may be used.
Domestic flow: Any one of the three remaining upper connections may be used.
Heating return: The water distributor tube must be fitted into either of the front lower connections on all installations, see diagram 4.8. This tube is in the fittings pack.
Domestic return: Any one of the three remaining lower connections may be used for the gravity domestic hot water return.
Fit plugs into any unused boiler tappings.
4.7 Water Connections - Fully Pumped Systems
Fit suitable fittings into the boiler tappings as required, see diagram 4.9. Make sure that all pipes are taken backwards and will clear the casings, see diagram 1.1.
NOTE: It is recommended that plastic pipes for primary pipework should not be used for this boiler.
It is important that all connections are made as shown in diagram 4.9.
Fit the water distributor tube into the return connection, see diagram 4.8. This tube is in the fittings pack.
Fit plugs into any unused boiler tappings.
WITH WALL LINER KIT ONLY
WALL THICKNESS­UP TO 300mm
SELF
ADHESIVE
FOAM SEAL
7102
9859
GRAVITY DOMESTIC RETURN TO ANY OF THE 3 REMAINING LOWER CONNECTIONS
WATER CONNECTIONS - GRAVITY DOMESTIC, PUMPED HEATING
UPPER MARKER must lie between the two outer NOTCHES
UPPER MARKER
DISTRIBUTOR TUBE
ALTERNATIVE HEATING OR DOMESTIC HOT WATER FLOW
ALTERNATIVE HEATING RETURN With distributor tube (not shown)
Diagram 4.7
1076
DISTRIBUTOR TUBE must be in pumped return connection
Diagram 4.8
Q
Q-35mm
WALL THICKNESS­OVER 300mm
15mm
SELF
ADHESIVE
FOAM SEAL
Q
Diagram 4.6
WATER CONNECTIONS FULLY PUMPED SYSTEMS
15
ALTERNATIVE FLOW POSITIONS
ALTERNATIVE RETURN POSITIONS With distributor tube (not shown)
Diagram 4.9
2000225144B
9859
4 Installation
4.8 Pipework
When the front tappings are used, it is essential that any pipework or fittings do not project more than shown in diagram
4.10.
When using a rear tapping with Rc (1in BSP) fitting for 28mm od pipework, it is recommended that a short nipple and an Rc thread (BSP) to copper elbow is used. If the pipework is required to run back to the wall, make sure that it will clear the boiler air duct and, if working to minimum clearance, does not project too far from the boiler, see diagram 4.11.
Do not route any pipework, water or gas, across the front of the combustion chamber cover.
The gas pipework must be along the left hand side of the boiler.
9860
4.9 Casing Brackets
Fit the two upper and two front casing brackets shown in diagram 4.12, using the No.8 screws provided.
NOTE: The screws will already be fitted.
Push the captive nuts, supplied loose, on to the casing brackets as shown in diagram 4.12.
PIPEWORK CASING CLEARANCES
REAR CONNECTION PIPEWORK (28mm)
Diagram 4.10
FOR MINIMUM CLEARANCE
Diagram 4.11
9861
UPPER CASING BRACKET
No.8 SCREW (4)
CAPTIVE NUT
No.8 SCREW (4)
FRONT
CAPTIVE NUT
CASING BRACKET
CASING BRACKETS FITTING
9858
Diagram 4.12
2000225144B
16
4 Installation
4.10 Side In-fill Panel (if required)
A side in-fill panel is supplied with the boiler, which can be fitted at the rear of the left or right hand side casing but can be discarded if the water connections are made on both sides of the boiler or if the boiler is screened by fixtures. The in-fill panel will usually be fitted on the side where there no pipework connections.
Insert the push fit plastic location peg, supplied, through the in­fill panel and side casing holes and secure with the spring clips, see diagram 4.13.
NOTE
The boiler is assembled at the factory with the control box and heat shield fitted in the lower casing height position.
SIDE CASING (R.H.SHOWN)
SPRING CLIP
IN-FILL PANEL
12082
4.11 Side Casings
Fit the side casings by locating their lugs into the appropriate slot in the boiler plinth, see diagram 4.13, depending on the required height, there are two options, see section 1.7.
Secure the casing sides to the front and rear upper casing brackets with self-tapping screws supplied, see diagrams 4.13 and 4.15.
FRONT CASING BRACKET
MAX.
MIN.
SIDE CASING (R.H.)
LOCATING SLOTS
No. 8 SCREW (4)
9863
UPPER VIEW
SIDE CASING (R.H. SHOWN)
IN-FILL PANEL
PLASTIC PEG
SPRING CLIP
PLASTIC PEG
LOWER VIEW
Diagram 4.13
BOILER PLINTH
SIDE CASINGS FITTING
SCREW
SIDE CASING (R.H. SHOWN)
Diagram 4.14
12081
UPPER CASING BRACKET
Diagram 4.15
17
2000225144B
4 Installation
4.12 Flue / Boiler Connection
Remove the three self-tapping screws from the lower part of the control box support bracket, see diagram 4.16.
Undo the wing nut that secures the top of the heat shield and carefully hinge down control box and heat shield, see diagram
4.16.
Release the two toggle latches that secure the boiler access door and remove, see diagram 4.17.
Remove the electrical connections from the fan by pulling the insulation boots onlyand disconnect the two air pressure tubes from the fan taking note of their positions, see diagram 4.18.
Remove the fan assembly from the flue hood by removing the securing screw, pull forward and lift up to release the 3 hooked securing lugs underneath the fan, see diagrams 4.18 and 4.19.
From the flue pack take the flue spigot,the gasket is supplied in the fittings pack.
Connect the flue spigot and gasket to the rear flue outlet of the boiler using the self tapping screws provided, see diagram 4.3.
IMPORTANT. With regards to the Manual Handling Operations, 1992 Regulations, the following operation, exceeds the recommended weight for one man lift.
Place the boiler in position taking care not to damage the casing panels.
With access to the flue system through the boiler, pull the flue on to the spigot bayonet connection, twist anti-clockwise to lock into position.
Take the flue duct extension from the boiler and slide on to the fan duct until it will go no further, see diagram 4.20.
Fit fan and engage the flue duct extension into the flue duct, secure fan, replace electrical connections and air pressure tubes.
The polarity of the electrical connections is not important.
Make sure that the air pressure tubes are fitted as before, see diagram 4.18 and that the fan duct engages fully into the flue duct extension piece.
10259
FAN ELECTRICAL CONNECTORS
AIR PRESSURE TUBE (RED)
TOGGLE LATCHES
FRONT AIR PRESSURE SWITCH TUBE (CLEAR)
12083
FAN ACCESS DOOR
Diagram 4.17
"LOW" position
"HIGH" position
"LOW" position
"HIGH" position
SELF TAPPING SCREWS (3)
WING NUT
(3) SELF TAPPING SCREWS (for height adjustment only)
CONTROL BOX SUPPORT BRACKET
Diagram 4.16
0886
FAN SECURING SCREW
REAR AIR PRESSURE SWITCH TUBE (RED)
Diagram 4.18
2000225144B
18
4 Installation
4.13 Water and Gas connections
Replace fan access door, heat shield and control box.
Note: When replacing the fan access door make sure the lip at the top of door fits into and behind the slotted bracket located at the top of the boiler.
As there are two casing height options, the control box height and the heat shield may have to be adjusted to suit your requirements.
Complete the water connections to the boiler.
Fill, vent and flush the system.
Check for any water leaks and put right.
Make the gas connection to the service cock, at the lower left hand side of the boiler, see diagram 1.1.
The whole of the gas installation, including the meter, should be inspected, tested for soundness and purged in accordance with the current issue of BS6891 and in IE the current edition of I.S. 813 "Domestic Gas Installations".
SECURING LUGS (3 OFF)
12084
Diagram 4.19
4.14 Top Casing
Refer to diagram 4.21.
Fit two plastic pegs, one on each side, in the holes on the top casing. The plastic pegs are a tight fit and are best pushed home with a flat faced tool.
Secure front of top casing with the screws provided.
FLUE DUCT EXTENSION PIECE
TOP CASING
10149
FAN
Diagram 4.20
9865
PLASTIC PEG (2)
19
SCREW (2)
Diagram 4.21
2000225144B
5 Electrical Wiring
SECURING SCREWS
TERMINAL BLOCK
CONTROL BOX
BOILER TEMPERATURE CONTROL
5.1 Control Box Access
Remove control box cover by undoing the four securing screws (two on control box, two on the heat shield) and lift off, see diagram 5.1.
5.2 Electrical Connections
WARNING. This boiler must be earthed.
Take care not to damage any internal wiring.
Using heat resistant (85oC) cable of at least 0.75mm2 (24/
0.2mm) and of a suitable length, route as shown in diagram 5.3. Thread through the grommet at the bottom rear of the control box, through the cable clamp and connect to appropriate terminals. Tighten cable clamp screws, see diagram 5.2.
Standard colours are, brown - live (L), blue - neutral (N) and green/yellow - earth
The mains cable outer insulation must not be cut back external to the cable clamp.
Make sure the cable is suitably secured.
When making connections make sure that the earth conductor is made of a greater length than the current carrying conductors, so that if the cable is strained the earth conductor would be the last to become disconnected.
.
CONTROL BOX COVER
CABLE CLAMP SCREW
MAINS INLET CONNECTOR
HEAT RESISTANT CABLE
9905
bk
TERMINAL BLOCK CONNECTIONS
Diagram 5.1
12086
CABLE CLAMP
Diagram 5.2
12085
5.3 Pump Connection
The pump must be connected to the external controls.
5.4 Testing - Electrical
Checks to ensure electrical safety must be carried out by a competent person.
After installation of the system, preliminary electrical system checks as below should be carried out.
1. Test insulation resistance to earth.
2. Test earth continuity and short circuit of all cables.
3. Test the polarity of the mains.
The installer is requested to advise and give guidance to the user of the controls scheme used with the boiler.
Replace the control box cover.
2000225144B
CABLE CLIPS
CABLE CLIPS
Diagram 5.3
20
6 Commissioning
IMPORTANT NOTE
The WARNING NOTICE attached to the front casing be removed by the user
Please ensure the “Benchmark” logbook is completed and left with the user, and the magnetic lighting instruction label is placed on the surface of the boiler casing.
must only
6.1 All Systems
Commissioning should be carried out by a competent person in accordance with the current issue of BS6798.
UNDER ALL CIRCUMTANCES the case must be correctly fitted and sealed, unless fault finding.
Make sure that the system has been thoroughly flushed out with cold water without the pump in place.
Refit the pump, fill the system with water, ensuring that all the air is properly vented from the system and pump.
6.2 Initial Lighting and Testing
CAUTION. This work must be carried out by a competent
person, in accordance with the current issue of BS6798.
Make sure that all naked lights and cigarettes are extinguished.
Refer to Instructions for Use and identify the controls.
Check that the boiler is isolated from the electrical supply.
Turn the gas service cock “On” , see diagram 6.1.
Purge in accordance with the current issue of BS6891.
WARNING. The multifunctional control and fan operate on mains voltage, terminals will become live.
If programmer control is fitted, make sure it is in the ON mode.
Make sure that any remote controls are calling for heat.
Turn the boiler temperature control clockwise to “Max”.
The control will conduct a purge before the ignition system will
operate to light the boiler. After a pre-set time if ignition has not taken place the boiler will shutdown.
To re-start the lighting sequence, turn the boiler temperature control to O, then fully clockwise to Max.
"Max" is approximately 82°C (180°F).
After the burner has lit, the Burner on indicator on the control panel will come on.
Isolate the boiler from the electrical supply.
Loosen the burner pressure test point screw and connect a suitable pressure gauge, see diagram 6.1.
Switch on the electrical supply to the boiler.
WARNING. The multifunctional control and fan operate on mains voltage, terminals will become live.
6.3 Testing - Electrical
Turn the boiler temperature control knob fully clockwise to the maximum setting, which is approx. 82oC (180oF).
The lighting sequence is automatic as follows:
The fan will operate for 10 seconds prior to the start of the ignition sparks, the gas valve solenoids will open and the burner will light. This is shown by the Burner On indicator on the control panel lighting up.
The burner will stay alight until switched off, either by the temperature control or remote system control. At this point the fan will overrun by 5 seconds.
To make sure that the flame supervision device is working correctly the following should be done.
With the burner alight, turn the gas service cock ‘OFF’, see diagram 6.1.
After a short period the burner will go out and fan will overrun for 5 seconds.
The correct working of the flame supervision device is shown by
12087
BOILER COMPONENTS
12163
A
10052
B
A
F
E
G
D
A CONTROL BOX B PHIAL POCKET C GAS SERVICE COCK D "BURNER ON" INDICATOR
J
E RESET/STANDBY INDICATOR
C
H
F TEMPERATURE CONTROL G BURNER PRESSURE TEST POINT H GAS PRESSURE ADJUSTMENT SCREW J DATA LABEL
Diagram 6.1
21
2000225144B
6 Commissioning
the Burner On indicator going out and the lighting sequence starting up, as follows:
1. Fan starts.
2. Spark ignition operates for 10 seconds.
3. Fan will overrun for 5 seconds.
4. The fan will start again.
5. After 10 seconds the spark ignition operates, this continues for a further 10 seconds.
6. Fan will overrun for 5 seconds.
This sequence is repeated TWICE more and the boiler will shut down. The following illumination will happen with the indicators on the front of the control panel, Reset/Standby indicator permanently ON and Burner On indicator flashing fast (8 Hz).
If the above lighting sequence fails, refer to section 9 - Fault Finding.
To continue, turn the gas service cock ‘On’, see diagram 6.1.
To restart the lighting sequence, turn the temperature control knob to ‘O’ then fully clockwise to ‘Max’.
During Normal Operation when the boiler switches ‘Off’, the burner will go out. The automatic lighting sequence will work again when heat is required.
6.4 Testing - Gas
With the boiler on proceed as follows:
Test for gas soundness around the boiler gas components using a suitable leak detection fluid, in accordance with the current issue of BS6891.
Check the burner gas pressure at least 10 minutes after boiler has lit, refer to Data Label, see diagram 1.2.
If necessary adjust the gas pressure to obtain the required setting turning screw clockwise, to decrease pressure, see diagram 6.1.
Should any doubt exist about the gas rate, check it using the gas meter test dial and stop watch at least 10 minutes after the burner has lit, making sure that all other gas burning appliances and pilot lights are off.
Gas rate: Hideaway 80B FF : 2.7m
is for guidance only, dependent on the heat setting.
Turn the boiler temperature control fully anti-clockwise to 0.
Isolate from the electrical supply.
Remove the pressure gauge from the test point and refit screw, making sure a gas tight seal is made.
When the boiler temperature control is turned to the “0” position, by hand, wait at least 30 seconds before turning On again.
There may be an initial smell given off from the boiler when new, this is quite normal and it will disappear after a short period of time.
3
/h (94ft3/h)
6.7 Adjustment - Fully Pumped Open Vented System
When commissioning the system the boiler should first be fired on full service, that is, central heating and domestic hot water. Adjust the pump to the system design setting, then balance the system, making adjustments as necessary.
6.8 Completion
Adjust the boiler temperature control and any system controls to their required settings. In addition it is necessary to complete the "Benchmark" logbook.
For IE, it is necessary to complete a "Declaration of Conformity" to indicate compliance to I.S.813. An example of this is given in the current edition of I.S.813.
Fit the bottom plinth panel and secure with two dog point screws, see diagram 6.2.
Finally fit the front panel by hooking under front of top panel locating on the two studs and securing at the bottom on to the bottom plinth panel with two screws, see diagram 6.3.
SECURING SCREWS
BOTTOM PLINTH PANEL
Diagram 6.2
LOCATE UNDER LIP
LOCATING STUDS
FRONT PANEL
12089
12164
6.5 Testing - All Water Systems
Allow the system to reach maximum working temperature and examine for water leaks.
There should be no undue noise in the system.
The boiler should then be turned off and the system drained off as rapidly as possible, whilst still hot.
Refill system.
6.6 Open Vented System
Ensure there is no pumping over of water or entry of air at the open vent above the feed and expansion cistern.
2000225144B
FRONT PANEL SECURING SCREWS
22
Diagram 6.3
7 Instructions to the User
Instruct and demonstrate the safe and efficient operation of the boiler, heating system and domestic hot water system.
Advise the user, that to ensure the continued efficient and safe operation of the boiler, it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough.
Draw attention, if applicable to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance in the UK.
It is the Law that servicing is carried out by a competent person.
Advise the user of the precautions necessary to prevent damage to the system and building in the event of the heating system being out of use during frost and freezing conditions.
Reminder - Leave these instructions and the “Benchmark” logbook with the user.
8 Servicing
REMEMBER, When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Hepworth Heating Ltd.
Products of Combustion Check
Note: To obtain a products of combustion reading, remove the front panel, see diagram 6.3 and remove the control box as descibed in the relevant paragraphs of section 4.12. Next, remove the cap from the sampling point, located on the top of the left hand side of the inner casing, see diagram 8.1.
Connect the analyser tube on to the nipple.
WARNING. The multifunctional control and fan operate on mains voltage, terminals will become live.
Switch on the electrical supply and gas supply then operate the boiler.
On completion of the test switch off the electrical supply and gas supply, remove analyser tube and replace sampling point cap.
Servicing
Before servicing turn off the gas and isolate the electrical supply to the boiler.
After completing a service always test for gas soundness, make electrical checks and carry out functional check on controls.
Unless stated otherwise all parts are replaced in the reverse order to removal.
8.1 Access
Remove the boiler front casing panel, refer to paragraph 6.8.
Remove the bottom plinth panel by unscrewing the two dog point screws securing the panel to the boiler plinth, see diagram
8.4.
Disconnect gas valve from gas service cock and unplug electrical plug from gas valve, firstly removing electrical plug securing screw, see diagram 8.2.
Unclip electrical wires from control box support bracket, see diagram 8.3.
Undo the four self-tapping screws that secure the combustion chamber front and carefully withdraw it together with the burner and gas valve assembly, taking care not to strain the ignition and earth wire, see diagram 8.5.
Note: When replacing burner in combustion chamber make sure it fits correctly on the guides.
Disconnect the ignition and earth leads from the burner and remove by drawing the leads though the grommet, see diagram
8.5.
Remove the three self-tapping screws from the lower part of the control box support bracket, see diagram 8.6.
Undo the wing nut that secures the top of the heat shield and carefully hinge down control box and heat shield, see diagram
8.6.
Release the two toggle latches that secure the boiler access door and remove, see diagram 4.17.
SAMPLE POINT
Diagram 8.1
ELECTRICAL PLUG
SECURING SCREW
GAS SERVICE COCK UNION
Diagram 8.2
12091
12088
23
2000225144B
8 Servicing
Note: When replacing the fan access door make sure the lip at the top of door fits into and behind the slotted bracket located at the top of the boiler.
Refer to diagram 8.7.
Remove the electrical connections from the fan by pulling the insulation boots only.
Disconnect the two air pressure tubes from the air pressure switch and the red air pressure tube from the fan taking note of their positions.
Remove the flue hood and fan assembly by sliding back to disengage the retaining lugs then lift up.
When replacing the flue hood ensure that it rests on the guides and that the rear of flue hood is located under the pegs at the rear and pushed down and back fully.
IMPORTANT: When re-fitting fan check that it fits fully into the flue duct extension piece.
GROMMET
COMBUSTION CHAMBER COVER
12029
IGNITION AND EARTH LEADS
Diagram 8.5
CONTROL BOX SUPPORT BRACKET
ELECTRICAL WIRE RETAINING CLIPS
SECURING SCREWS
Diagram 8.3
12159
12164
AIR PRESSURE TUB (RED)
WING NUT
SELF TAPPING SCREWS (3)
FAN ELECTRICAL CONNECTIONS
0886
CONTROL BOX SUPPORT BRACKET
Diagram 8.6
AIR PRESSURE SWITCH
2000225144B
BOTTOM PLINTH PANEL
Diagram 8.4
AIR PRESSURE TUB (RED)
24
AIR PRESSURE TUB (CLEAR)
10259
FLUE HOOD
Diagram 8.7
8 Servicing
8.2 Boiler Flueways
Remove flueway baffles noting that there are 2 centre and 2 side flueway baffles, see diagram 8.8.
Place a sheet of paper in the combustion chamber to catch any flue debris.
Thoroughly clean boiler flueways and fins with a suitable stiff brush.
Replace in reverse order, after completing the relevant instructions in sections 8.3 and 8.4.
8.3 Burner and Injector
Remove the two screws and nuts securing the burner support bracket to the combustion chamber cover, see diagram 8.9.
Remove the graphite coated nuts on the supply feed pipe at the rear of the burner to release the burner, see diagram 8.10.
Clean the burner. Use a vacuum cleaner or suitable stiff brush (not wire) to clean the burner thoroughly, making sure that all the burner ports are clear and unobstructed.
Check the burner injector for blockage or damage and replace if necessary, see diagram 8.11.
With the burner removed the injector can be inspected and cleaned as necessary.
For cleaning do not use a wire or sharp instrument on the hole.
If removed, use a little suitable sealant on the external thread when refitting to make sure a gas tight seal is made.
8.4 Service Checks
Inspect the spark electrode and clean and replace as necessary, see diagram 8.12.
Check the condition of the side and rear insulation panels in the combustion chamber.
Check the condition of the seals on the boiler access door and the combustion chamber cover.
Examine the flue hood and terminal to make sure they are clean and clear of obstructions.
Refit all parts.
Light the boiler and carry out functional tests as described in section 6.
BURNER SUPPORT BRACKET
SCREWS & NUTS (2)
12158
SIDE FLUEWAY BAFFLE
HEAT EXCHANGER
HEAT EXCHANGER
FLUEWAY BAFFLE
12157
12027
Diagram 8.9
12028
GRAPHITE COATED NUT(2)
MAIN BURNER
Diagram 8.8
25
SUPPLY FEED PIPE
Diagram 8.10
2000225144B
8 Servicing
ELECTRODE
SECURING SCREW
Diagram 8.12
GRAPHITE COATED NUT(2)
BURNER INJECTOR
Diagram 8.11
0939
SPARK GAP
+
= 3.6 1.1
-
9 Fault Finding
IMPORTANT. On completion of the Fault Finding task which has required the breaking and remaking of the electrical connections,
the continuity, polarity, short circuit and resistance to earth checks must be repeated using a suitable multimeter.
WARNING. The multifunctional control and fan operate on mains voltage, the terminal will be live.
Before carrying out fault finding, ensure that gas, electricity and water are available to the boiler. Ensure that any external controls are calling for heat and circuit water is cold. If Reset/Standby indicator is lit - check water system for overheating, reset by turning temperature control knob off and on. If the indicator coding is showing an ignition failure, reset the boiler by turning the control knob off and on. Do not operate the boiler without combustion chamber front fitted.
12062
12026
Control Knob at '0'
Ye s
Power ON at isolation switch
Ye s
Does the fan run for 10 seconds with RESET/STANDBY INDICATOR lit
Ye s
Apply heating demand (turn potentiometer clockwise)
Ye s
Does the fan start
Ye s
Does the unit begin to spark
Ye s
Does the burner light
Ye s
Correct Operation
No
Is there an INDICATOR sequence
Ye s
Refer to table
No
Are the HT & Earth connections made
Ye s
Refer to table
No
Ye s
Is there an INDICATOR sequence
Ye s
Refer to table
No
No
No
No
No
No
Replace fuse
Replace PCB
Switch OFF Remake connections Restart diagnosis
Replace PCB
Turn Gas ONIs the Gas turned ON
Replace PCB
ELECTRICAL FAULT FINDING
2000225144B
Diagram 9.1
26
9 Fault Finding
BOILER TEMPERATURE CONTROL
0900
Diagram 9.2
9.1 Electrical
Gain access to the control box, refer to the relevant paragraph in section 8.1, then remove the control box cover, refer to section 5.1.
Refer to: Boiler Fault Finding, see diagram 9.1, Fault Finding Wiring Diagram, see diagram 9.3, Pictorial Wiring Diagram, see diagram 9.4.
9.2 Electrical Supply Failure
Failure of the electrical supply will cause the burner to go out. Operation will normally resume on the restoration of the electrical supply.
If the burner does not relight after an electrical supply failure and the reset/standby indicator on the control panel is lit, turn the burner temperature control to “0”, wait 30 seconds, then fully clockwise to “Max.” see diagram 9.2.
SL
bk
FUSE
TYPE 3.15A
MAINS SUPPLY 230v ~ 50Hz
bk BLACK br BROWN b BLUE p PURLPLE
br
br
p
r
g
AIR PRESSURE SWITCH
br
bk
EV2
KEY
FAN
(N/O)
(N/C)
r RED y YELLOW g GREY
b
b
(C)
b
b
EV1
12001
N
9.3 INDICATOR Fault Coding
Refer to fault coding table below.
INDICATOR 1 INDICATOR 2 INDICATOR CONDITION REMARK (RESET) (BURNER LIT) STATUS
Reset O/H or in 'standby' mode
Correct operation
Transpose Live & Neutral
Check Earth
Check connection
& value
Check connection
& operation
Simultaneous
Simultaneous
Simultaneous
Alternating
Non - Volatile Lockout
Burner Lit
PCB Failure
Other Errors
Reversed Polarity
Lighting Sequence-Thermistor
Lighting Sequence-Fan/APS
Software Sequence Error
Software Error
Ignition Lockout
SPARK ELECTRODE
AIR PRESSURE SWITCH CONNECTIONS
MAIN TERMINAL STRIP CONNECTIONS
PRINTED CIRCUIT BOARD CONNECTIONS
Diagram 9.3
N
Slow Flashing (2Hz)
Fast Flashing (8Hz)
27
2000225144B
9 Fault Finding
12000
BOILER PILOT FAULT FINDING
2000225144B
Diagram 9.4
28
10 Replacement of Parts
IMPORTANT NOTES
REMEMBER, When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Hepworth Heating Ltd.
Replacement of parts must only be carried out by a competent person.
Before removing or replacing any parts, turn off the gas supply at the gas service cock, see diagram 8.2 and isolate the electrical supply to the appliance.
Unless stated otherwise, all parts are replaced in the reverse order to removal.
After replacing any parts always test for gas soundness and if necessary carry out functional check of controls.
10.1 Electrical Thermistor
Remove front panel to gain access, see section 6.8.
Remove control box cover by undoing the four securing screws (two on control box, two on the heat shield) and lift off, see diagram 10.1.
Remove thermistor lead from retaining clip, located on the control box support bracket, see diagram 8.3.
Release strain relief grommet securing thermistor lead at the side of control box.
SECURING SCREWS
CONTROL BOX COVER
Disconnect the thermistor electrical plug from the control board (P.C.B) slightly bending back the retaining latch to allow withdrawal, see diagram 10.2.
Withdraw the electrical thermistor from its phial, see diagram
10.3.
Draw the thermistor lead followed by the thermistor out though the control box case.
Re-assembly note. When fitting the thermistor make sure it is fully inserted into the phial and secured using the grommet moulded to the cable, see diagram 10.3.
10.2 Control Board (P.C.B)
Remove front panel to gain access, see section 6.8.
Remove control box lid by undoing the four securing screws (two on control box, two on the heat shield) and lift off, see diagram 10.1.
Carefully pull the boiler temperature control knob away from the P.C.B.
Disconnect the electrical plugs from the control board (PCB) slightly bending back the retaining latches to allow withdrawal, see diagram 10.2.
Disconnect ignition lead.
Carefully pull the board away from its supports bending back slightly the retaining latches.
When refitting refer to wiring diagram 9.4.
Take care when replacing the burner temperature control knob by supporting the potentiometer on the P.C.B.
NOTE: Ensure jumper is in position 'A', refer to wiring diagram
9.4.
9905
TERMINAL BLOCK
BOILER TEMPERATURE CONTROL
PCB
CONTROL BOX
Diagram 10.1
12100
ELECTRICAL PLUG
GAS SERVICE COCK UNION
SECURING SCREW
PHIAL
12099
POCKET
THERMISTOR
Diagram 10.3
12168
SHORT SCREWS (2)
LONG SCREWS (2)
EARTH LEAD
ELECTRICAL PLUGS
Diagram 10.2
29
SOLENOID ASSEMBLY
Diagram 10.4
2000225144B
10 Replacement of Parts
10.3 Electrode
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
To remove the electrode, unscrew from the retaining bracket, see diagram 8.12.
Take the electrode out from below and remove the ignition lead.
When removing and replacing the electrode take care not to damage it.
When refitting, check spark gap, see diagram 8.12.
10.4 Multifunctional Control
Remove front panel to gain access, see section 6.8.
Remove the securing screw and disconnect the electrical plug, see diagram 10.4.
Disconnect the gas cock, on the left hand side.
Support the multifunctional control, remove the four screws (2 long, 2 short) from the flanged connection at the right hand side.
Remove and discard the original “O” ring from the flanged connection and fit the new “O” ring supplied, into recess, before fitting the replacement multifunctional control.
After assembly test for gas soundness and purge in accordance with the current issue of BS6891 or IE, the current edition of I.S.813 "Domestic Gas Installations".
10.5 Solenoid
Remove the electrical plug from the multifunctional control and remove the securing screw and then the solenoid assembly, see diagram 10.4.
10.6 Burner
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
10.7 Injector
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
The injector can then be unscrewed from the manifold.
When replacing use a little jointing compound on the external thread only, to ensure a gas tight seal.
FRONT AIR PRESSURE SWITCH TUBE (CLEAR)
AIR PRESSURE SWITCH
10.8 Air Pressure Switch
Remove front panel to gain access, see section 6.8.
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
Remove the air pressure tubes and electrical connections from the switch, release the securing screws and remove the switch, see diagram 10.5.
When fitting the replacement make sure that the air pressure tubes are fitted with the clear tube from the air pressure switch to the front fan connection, as shown in diagram 10.5 and the electrical connections are made as shown in wiring diagram
9.4.
10.9 Fan
Remove front panel to gain access, see section 6.8.
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
Remove the electrical connections and air pressure tubes from the fan.
Note: Remove the electrical connections by pulling insulation boots only.
Undo the screw securing the fan to the flue hood and disengage fan from flue hood.
When re-assembling, make sure that the air pressure tubes are fitted as before and that the fan duct engages fully into the flue duct extension piece.
The polarity of the electrical connections is not important.
10.10 Insulation
Refer to the relevant paragraphs of Section 8 servicing to remove the burner from combustion chamber.
Sides
Undo the burner support bracket nuts and remove support bracket and insulation, see diagram 10.6.
Refit support bracket with new side insulation.
Rear
Bend forward rear insulation securing nibs, one on each side, to release insulation.
Fit new insulation and bend back securing nibs.
10259
BURNER SUPPORT BRACKET
NUTS
REAR INSULATION PANEL
12108
2000225144B
REAR AIR PRESSURE SWITCH TUBES (RED)
ELECTRICAL CONNECTORS
Diagram 10.5
SIDE INSULATION
30
Diagram 10.6
11 Spare Parts
11.1 Part Identification
The key number in diagram 11.1 and the first column of the list will help identify the spare part.
1
2
8
5
4
10
11.2 Ordering
When ordering any spare part please quote the part number and the description from the list together with the model name and serial number information from the data label.
The data label is positioned on the heat shield, see diagram 6.1.
12008
3
6
7
9
Diagram 11.1
Key No. Part No. Description GC Part No.
1 2000461752 Multifunctional control ******
2 227132 Fan ******
3 2000463496 Air pressure switch ******
4 2000461793 Electrical thermistor ******
5 202635 Spark electrode ******
6 2000461714 Boiler temperature control knob ******
7 2000461924 Injector ******
8 202240 Fuse ******
9 2000227134 Control board ******
10 205656 Burner ******
31
2000225144B
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
2000225144B
32