The action-related warnings are classified in
accordance with the severity of the possible
danger using the following warning signs and
signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of
severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental
damage
1.2Required personnel qualifications
▶ Secure against being switched back on
again.
▶ Wait for at least 3 minutes until the con-
densers have discharged.
▶ Check that there is no voltage.
▶ Cover or insulate adjacent live parts.
1.3.3 Risk of death due to lack of safety
devices
A lack of safety devices (e.g. expansion relief valve, expansion vessel) may lead to potentially fatal scalding and other injuries, e.g.
due to explosions. The schematic drawings
included in this document do not show all
safety devices required for correct installation.
▶ Install the necessary safety devices in the
system.
▶ Inform the operator about the function and
position of the safety devices.
▶ Observe the applicable national and inter-
national laws, standards and guidelines.
Improper work carried out on the product
may cause material damage to the complete
installation and, as a consequence, may even
cause personal injury.
▶ You should therefore only work on the
product if you are an authorised competent
person.
1.3General safety information
1.3.1 Danger caused by improper
operation
Improper operation may present a danger to
you and others, and cause material damage.
▶ Carefully read the enclosed instructions
and all other applicable documents, particularly the "Safety" section and the warnings.
1.3.2 Risk of death from electric shock
There is a risk of death from electric shock if
you touch live components.
1.3.4 Risk of being scalded by hot
drinking water
There is a risk of scalding at the hot water
draw-off points if the hot water temperatures
are greater than 50 °C. Young children and
elderly persons are particularly at risk, even
at lower temperatures.
▶ Select the temperature so that nobody is at
risk.
1.3.5 Risk of injury or material damage
due to incorrect handling of the
product
Using the fins on the front side of the product
as conductors may lead to injuries (due to
falling) or to material damage.
▶ Do not use the fins as conductors.
1.3.6 Risk of material damage due to
additional elements in the heating
water
Before commencing work on the product:
▶ Disconnect the product from the power
supply (electrical partition with a contact
opening of at least 3 mm, e.g. fuse or
power switch).
Unsuitable frost and corrosion protection
agents may damage seals and other components of the heating circuit and may therefore also lead to leaks in the water outlet.
1.3.7 Risk of material damage caused by
using an unsuitable tool
▶ Use the correct tool to tighten or loosen
screw connections.
1.3.8 Avoid environmental damage
caused by escaping coolant
The heat pump contains R410A coolant.
The coolant must not be allowed to escape
into the atmosphere. R410A is a fluorinated
greenhouse gas covered by the Kyoto Protocol, with a GWP of 1725 (GWP = Global
Warming Potential). If it escapes into the atmosphere, its impact is 1725 times stronger
than the natural greenhouse gas CO2.
Before the heat pump is disposed of, the
coolant it contains must be completely
drained into a suitable vessel so that it
can then be recycled or disposed of in
accordance with the regulations.
▶ Ensure that only officially certified com-
petent persons with appropriate protective
equipment carry out maintenance work on
the coolant circuit or access it.
▶ Arrange for the coolant contained in the
product to be recycled or disposed of by
accredited specialists in accordance with
regulations.
▶ Only use coolant R410A.
▶ Only use a suitable R410A tool for the
filling, pressure measurement, vacuum
generation and discharge.
▶ Solder the lines using shielding gas. Check
the lines for leak-tightness using nitrogen.
▶ In the event of a repair or maintenance
work, fill the coolant circuit with liquid
coolant.
▶ If the coolant circuit is not leak-tight, check
which component must be repaired or replaced.
▶ Lower the negative pressure in the coolant
circuit to max. 10 mbar (1000 Pa).
▶ When filling the coolant circuit, observe the
values in the "Technical data" section.
1.4Regulations (directives, laws,
standards)
As part of the installation, commissioning and
operation of the heat pump and the DHW
storage you must take into account the current versions of the following regulations or
standards, along with any local directives or
guidelines that may apply.
– Electricity at work act.
– Health and safety at work act.
– Relevant Utility supplier’s regulations.
– Water regulations and by-laws.
– Environment agency and local council re-
quirements regarding bore holes, water
courses, or noise levels.
– Gas safety installation and use regulations
concerning any associated gas fired heat
source used within the heating system.
– Building regulations part “L” and directives
concerning energy saving.
– Building regulations such as G3 covering
Hygiene and L8 Legieonella.
– COSHH regulations.
– Other relevant bodies such as HETAS and
OFTEC.
– BS7671 requirements for electrical installa-
tions.
1.5CE label
The CE label shows that the products comply
with the basic requirements of the applicable
directives as stated on the identification plate.
The declaration of conformity can be viewed
at the manufacturer's site.
1.6Approvals
This product has been fully tested in accordance with:
Benchmark places responsibilities on both
manufacturers and installers. The purpose is
to ensure that customers are provided with
the correct equipment for their needs, that it
is installed, commissioned and serviced in
accordance with the manufacturer’s instructions by a competent person approved at the
time by the Health and Safety Executive and
that it meets the requirements of the appropriate Building Regulations. The Benchmark
Checklist can be used to demonstrate compliance with Building Regulations and should be
provided to the customer for future reference.
Installers are required to carry out installation,
commissioning and servicing work in accordance with the Benchmark Code of Practice
which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
standards and provisions in eff ect at the
time.
1.8.3 Reminder of existing regulatory acts
– EC regulation No. 20372000 from the 29th
of June 2000 This European regulation repeals regulation No. 3093/94 and presents
the elimination schedules of CFC and
HCFC. It also deals with the collection of
refrigerants, system leaks, particularly systems containing more than 3 kg of CFC
or HCFC, as well as the minimum level of
qualifi cation required by the technicians.
– EC regulation No. 0842/2006 from the 17th
of May 2006 regarding the containment,
use, collection and disposal of the fl uorinated greenhouse gases, the labelling and
elimination of the products and equipment
containing these gases, the restriction of
use and banning of certain products from
the market, as well as the training and certifi cation of personnel and companies operating in the activities targeted by this regulation: refrigeration, air-conditioning, heat
pumps and fi re protection systems containing greenhouse gases.
Visit www.centralheating.co.uk for more information.
Planning consent and Building works notification should be submitted either to Building
Control or to a Competent Person Provider.
1.8Regulations
1.8.1 Statutory requirements
Where no British Standards exists, materials
and equipment should be fi t for their purpose
and of suitable quality and workmanship.
The installation of this appliance must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken
as overriding statutory requirements.
1.8.2 Standards
On installing and commissioning the appliance you must adhere to the technical rules,
1.9Other regulations
1.9.1 Control of Substances Hazardous to
Health
Under Section 6 of The Health and Safety at
Work Act 1974, we are required to provide information on substances hazardous to health.
The adhesives and sealants used in this appliance are cured and give no known hazard
in this state.
The refrigerant used in this appliance is
R410a the use of which is strictly controlled
by F Gas regulation EN842/2006.
1.10Intended use
There is a risk of injury or death to the user or
others, or of damage to the product and other
property in the event of improper use or use
for which it is not intended.
The heat pump is an air/water monoblock
system and uses the energy from the outside
air to supply heat to the building.
The heat pumps are intended exclusively for
domestic use as heat generators for closed
heating and hot water central heating systems and for hot water generation.
Intended use includes the following:
– observance of accompanying operating,
installation and servicing instructions for
the product and any other system components
– installing and fitting the product in accord-
ance with the product and system approval
– compliance with all inspection and main-
tenance conditions listed in the instructions.
Any other use that is not specified in these
instructions, or use beyond that specified in
this document, shall be considered improper
use. Any direct commercial or industrial use
is also deemed to be improper.
▶ You must observe all the operating and installation in-
structions included with the system components.
2.2Storing documents
▶ Pass these instructions and all other applicable docu-
ments on to the system operator.
2.3Applicability of the instructions
These instructions apply to units with the following type designations and article numbers only:
Type designationArt. no.
Envirosorb350010014421
Envirosorb380010011967
Envirosorb3110010011968
Envirosorb3150010014422
The seventh to sixteenth digits of the serial number on the
identification plate form the article number.
protection agent should be added to the heating water as
the heating water temperature may fall below the freezing point in the event of a power cut, which poses a risk
of frost to the heating installation.
Note
Operating the heat pump outside the application
limits results in the heat pump being switched off
by the internal control and safety devices.
3.2Functionality
The product comprises the following circuits:
– The coolant circuit releases heat into the heating circuit
by means of evaporation, compression, condensation
and expansion
– The heating circuit
3.2.1Heating mode
3System overview
3.1Safety devices
– The product can work at the following outside temperat-
ures:
Envirosorb
5
Heating mode−15 … 28 ℃−20 … 28 ℃
Cylinder charging mode−15 … 46 ℃−20 … 46 ℃
– If the product's coolant circuit pressure exceeds the max-
imum pressure of 4.15 MPa (41.5 bar), the high-pressure pressure switch switches the product off. Following a waiting period, the product attempts to start once
more. After three failed start attempts in succession, a
fault message is displayed.
– If the product is switched off, the crankcase housing
heating is switched on when the compressor outlet temperature reaches 7 °C in order to prevent possible damage caused by switching it back on.
– If the compressor inlet temperature and the compressor
outlet temperature are below 1 °C, the compressor does
not start up.
– A temperature sensor on the compressor outlet limits the
product's operation if the measured temperature exceeds
the maximum permissible temperature. The maximum
permissible temperature depends on the evaporation and
condensation temperature.
– The product measures the flow rate of the connected
heating circuit when starting up the product.
– If the heating circuit temperature falls below 3 °C, the
product's frost protection function is automatically activated as the heating pump is started. In addition, frost
1.Use the transportation belt to carry the product to the
final installation site.
2.Only lift the product from the back and side where the
hydraulic connections are located.
3.When transporting the product using a hand truck, secure the product using a belt.
4.In order to avoid scratches and damage, protect the
sides of the product that come into contact with the
hand truck.
5.1.1.2 Unpacking the product
Warning.
Risk of injury from lifting a heavy weight.
Lifting weights that are too heavy may cause
injury to the spine, for example.
▶ When transporting the product, two
people should lift it.
▶ Observe the product weight stated in the
technical data.
▶ When transporting heavy loads, observe
the applicable directives and regulations.
1.Remove the accessory (2).
2.Remove the documentation supplied (1).
3.Remove the transport belt (4).
4.Carefully remove the packaging and padding without
damaging the product (3).
5.Remove the screws from the pallet at the front and rear
of the product.
Caution.
Risk of material damage due to incorrect
transportation.
Regardless of the mode of transport, the heat
pump must never be tilted by more than 45°.
Otherwise, this may lead to malfunctions in
the coolant circuit during subsequent operation. In the worst case scenario, this may lead
to a fault in the whole system.
*Caution: If the minimum clearances are not maintained, the
output of the product may be affected.
▶ To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are
specified above.
▶ Ensure that there is sufficient room to install the hydraulic
lines.
▶ If the product is to be installed in areas where heavy
snow falls, ensure that the snow does not accumulate
around the product and that the minimum clearances
specified above are observed. If you cannot ensure this,
install an additional heat generator in the heating circuit.
2.Align the product horizontally so that condensate can
flow.
Note
The product must be installed with the vibration-isolating feet supplied. The product
is lifted by the vibration-isolating feet, which
simplifies the condensate-discharge process
and reduces vibrations.
3.Screw in the vibration-damping feet using the concrete
foundation.
Note
The concrete foundation must not be joined
to the house foundations.
5.3Hydraulics installation
In heating installations that are equipped primarily with thermostatic or electrically controlled valves, a constant and sufficient flow through the heat pump must be ensured. Irrespective of which heating installation is selected, the minimum volume of circulating heating water (40% of the nominal flow, see the technical data table) must be guaranteed.
5.3.1Carrying out the hydraulics installation
Caution.
Risk of damage caused by residue in the
heating flow and return.
Residue from the pipelines, such as welding
beads, scale, hemp, putty, rust and coarse
dirt, may be deposited in the product and
cause malfunctions.
1.Insulate the lines (including those running below
ground) with UV-resistant and high-temperature-resistant insulation between the product and the heating
installation.
2.In order to avoid transferring vibrations to the surrounding buildings, use flexible connection pipes on the
product that have a length of at least 0.75 m.
3.When the product is not installed at the highest point in
the heating circuit, install additional purging valves in
suitable places.
4.Install the following accessories in the heating return.
Installation without decoupling hydraulic module
– Drain cock
– Air separator (if required)
– Dirt filter
– An expansion vessel suitable for the complete hydraulic
When using a hydraulic
module without an expansion
vessel
Note
If you use glycol, you must collect it at the
expansion relief valve to prevent environmental pollution.
DN 26DN 28
50 m30 m
▶ Flush the heating installation thoroughly
before connecting the product in order to
remove any possible residue.
Caution.
Risk of material damage due to corrosion.
If plastic pipes that are not diffusion-tight are
used in the heating circuit, this may lead to
corrosion and deposits in the heating circuit
and in the product.
▶ Do not treat the water with corrosion pro-
tection agents if plastic pipes that are not
diffusion-tight are used.
Danger!
Risk of material damage caused by sol-
dering work.
Carrying out soldering work on lines that
have already been installed may damage the
seals.
▶ Solder the lines before installing the
product.
1 Connection hose in the
heating flow to the building
(on-site)
2 O-ring seal
3 Covering cap
4 Heating flow connection
(diameter 1 1/4") to the
building
5.Remove the covering caps (3) from the product's hydraulic connections.
6.Install a dirt filter in the heating circuit return between
two stop valves so that the filter can be cleaned regularly.
7.Install a flexible connection pipe (1) and (6) (to be
provided on-site) with an O-ring and a stop valve to
each of the connections for the heat pump heating flow
and return.
8.Check the connections for tightness.
5.3.2Connecting the swimming pool (optional)
Danger!
Risk of material damage due to a direct
connection to a swimming pool.
If the product is directly connected to a swimming pool, damage may be caused by corrosion.
▶ Do not connect the heat pump heating
circuit directly to a swimming pool.
▶ If you want to connect a swimming pool to the heating
circuit, note the components (expansion vessels, etc.)
that are required for the installation.
5.3.3Connecting the condensate drain pipework
Note
Observe all valid national regulations and rules.
1 Condensate drain pipe
2 Adaptor
3 Cable tie
1.Observe the various installation dimensions for the
products.
ProductDimensionValue
– Envirosorb35A70.0 mm
– Envirosorb38
– Envirosorb311
– Envirosorb315
2.Pull the heating wire in the condensate pan until the
elbow (4).
3.Connect the elbow (4) and adaptor (2) to the seal (5)
and secure them both using a cable tie (3).
4.Connect a condensate drain pipe to the elbow.
5.Install the heating wire in the condensate drain pipe (1)
in order to prevent the condensate from freezing in the
line.
6.Connect the adaptor (2) with the product's floor plate
and secure it with a 1/4 rotation.
Recommended cable dimension for
eBUS + limit thermostat
2 x 0.75 mm²
4 x 0.75 mm²
2.Connect the eBUS cable to the system controller.
3.If you install a limit thermostat (e.g. 50 °C) in the heating circuit flow, remove the bridge from terminal (2) and
connect the limit thermostat to this terminal.
5.4.4Installing the cable duct
Caution.
Risk of malfunction due to incorrect rout-
ing of the supply lines.
If you route the supply lines for the power
supply and the eBUS line through the same
cable duct, the signal will be disrupted.
1 eBUS line and limit ther-
mostat line cable duct
2 Power supply cable duct
1.Measure the diameter of the cable.
2.Drill a hole the same size as the cable diameter in the
cable duct.
3.Route the cable through the cable duct.
4.Tighten the cable duct with two open-end spanners.
▶ Route the supply lines for the power sup-
ply and the eBUS line through various
cable ducts in the product.
1Temperature sensor of the ribbed pipe heat exchanger
2Temperature sensor after the plate heat exchanger
3Coolant circuit pressure switch
4Compressor inlet temperature sensor
5Compressor outlet temperature sensor
1.Before starting up the product, read through the operating instructions.
2.Check that the electrical partition is installed.
3.Check that the hydraulic and electric connections are
correctly designed.
4.Check that a dirt filter is installed in the heat pump return.
5.Check whether an expansion relief valve, an expansion
vessel and a pressure gauge are installed.
6.Check the leak-tightness of the connections.
7.Open all the heating circuit valves.
6.2Filling the heating circuit
Note
We recommend using ethylene glycol with corrosion-inhibiting additives.
If no frost protection has been poured in, the
product will not be protected in the event of a
power cut when there is frost.
▶ To purge the heating circuit, open the purging valve by a
1/4 rotation (B) using an open-end spanner.
▶ Increase the operating pressure in the heat pump heat-
ing circuit.
– Operating pressure: 0.15 … 0.2 MPa (1.50
… 2.0 bar)
Note
The pressure level may fall in the first month
following start-up. It may also vary depending
on the outside temperature.
Conditions: If you are using glycol
▶ The glycol must not escape into the outflow or the envir-
onment.
▶ Prepare a mixture with suitable glycol (max. 50% ethyl-
ene glycol) in order to protect the heat pump against
frost according to the regional minimum temperatures.
Note
If no frost protection has been poured in, the
product will not be protected in the event of a
power cut when there is frost.
Conditions: SW10 open-end spanner
1 Heating circuit purging
valve
2 Open-end spanner (on-
site)
3 Hose
4 Collecting container (on-
site)
▶ To purge the heating circuit during the filling procedure,
use a filling pump.
▶ Connect one end of the hose (3) to the drain valve.
▶ When purging, insert the other end of the hose (3) into
the mixing container (4).
▶ Open the filling valve using an open-end spanner (2).
▶ Use a frost protection tester to ensure the correct
dosage.
6.3Treating the heating water
Caution.
Risk of material damage if the heating
water is treated with unsuitable frost and
corrosion protection agents.
Frost and corrosion protection agents may
cause changes in the seals, noises during
heating and may lead to further damage.
▶ Do not use any unsuitable frost and corro-
sion protection agents.
Mixing additives with the heating water may result in material
damage. However, no incompatibility with the units has been
detected to date with proper use of the following products.
▶ When using additives, follow the manufacturer's instruc-
tions without exception.
Note
Glow worm accepts no liability with respect to
the compatibility of any additive in the rest of
the heating system or its effectiveness.
Additives for cleaning measures (subsequent
flushing required)
– Fernox F3
– Sentinel X 300
– Sentinel X 400
Additives intended to remain permanently in the
system
Additives for frost protection intended to remain
permanently in the system
– Fernox HP 15 or HP15c
– Sentinel X 500
▶ Inform the operator about the measures required if you
have used these additives.
▶ Inform the operator about the measures required for frost
protection.
Permissible water hardness
Note
Contact the local water supply company for further
information on water quality.
▶ Observe all applicable national regulations and technical
standards when treating the filling and supplementary
water.
Provided the national regulations and technical standards
do not stipulate more stringent requirements, the following
applies:
You must treat the heating water in the following cases:
– If the entire filling and supplementary water volume dur-
ing the operating life of the system exceeds three times
the nominal volume of the heating installation,
– If the limit values shown in the following tables are not
observed.
Total heating
output
kW
< 50
> 50 to 2002 (200)1,5 (150)0,02 (2,0)
1) Of the specific system volume (nominal capacity in
litres/heating output; on systems with more than one boiler, the
lowest individual heating output must be set). These values only
apply up to three times the system volume for filling and supplementary water. If three times the system volume is exceeded,
the water must be treated in accordance with the specifications
from the VDI (softening, desalting, hardness stabilisation or
blowing down). This is exactly the same as if the limit values in
the table were exceeded
2) On systems with circulation water heaters and for systems
with electric heating elements
Permissible salt content
Heating water characteristics
Electrical conductivity
at 25 °C
Appearance—
Total hardness at smallest boiler heating
1)
surface
20 l/kW
mol/m³ (mg/l
CaCO₃)
No requirement
< 32)(3002))
UnitLow-saltSaline
μS/cm< 100100 … 1,500
> 20 l/kW
< 50 l/kW
mol/m³ (mg/l
CaCO₃)
2 (200)0,02 (2,0)
Free of sedimentary materials
> 50 l/kW
mol/m³ (mg/l
CaCO₃)
Heating water characteristics
pH value at 25 °C—
Oxygenmg/l< 0.1< 0.02
UnitLow-saltSaline
8,2 … 10,01)8,2 … 10,0
1)
6.4Filling the heating installation
Caution.
Risk of material damage due to heating
water that is extremely calciferous or corrosive or contaminated by chemicals.
Unsuitable tap water damages the seals
and diaphragms, blocks components in the
product and heating installation through
which the water flows and causes noise.
▶ Only fill the heating installation with suit-
able heating water.
Note
If a heat exchanger module is used, the heating
circuit must be topped up with heating water.
Conditions: System separation with a heat exchanger module
▶ Connect the filling cock with the heating water supply
using a cold water valve where possible.
▶ Open all radiator valves (thermostatic radiator valves) of
the heating installation.
▶ Open the cold water valve.
▶ Slowly open the filling cock.
▶ Fill it with water until the required filling pressure is
reached.
▶ Close the cold water valve.
▶ Purge all radiators.
▶ Then check the filling pressure on the display.
▶ Top up with more water if necessary.
▶ Close the filling cock.
6.5Activating the heat pump
1.Ensure the maximum flow temperature setting matches
the heating installation.
2.To fully activate the heating installation, observe the
installation instructions for the system controller.
3.Switch on the line protection switch in the fuse box
which is connected to the heat pump.
6.6Checking the product's operation
1.Ensure that the external control equipment (thermostats, external sensors, etc.) are sending a heating
demand to the heat pump. When configuring several
areas, test heating circuit by heating circuit and ensure
that the appropriate heating circuit gets warmer.
2.Ensure that all heating circuit thermostatic radiator
valves are open.
▶ Open the service valves on the back of the product.
▶ Remove the hose and the mixing container.
6.8.1.1 Available pressure in the heat pump
heating circuit
1 Envirosorb35 (water tem-
perature 20 °C)
2 Envirosorb38 (water tem-
perature 20 °C)
3 Envirosorb311 (water
temperature 20 °C)
4 Envirosorb315 (water
temperature 20 °C)
A Remaining feed head
(kPa)
B Flow rate (l/h)
C Remaining feed head
[mbar]
* Permanent operating
noises
The noises listed do not constitute a fault with the heat
pump.
In various operating modes, the noises come from the heat
pump (Start, Thawing, Stop).
6.8Adjusting the heating circuit
6.8.1Purging the heating circuit
Conditions: SW14 open-end spanner
▶ Connect one end of the hose to the purging valve.
▶ In order to collect the residual glycol when purging the
heating circuit, insert the other end of the hose into the
mixing container.
▶ Close the stop valves on the back of the product.
▶ Increase the pressure in the heating circuit.
▶ Open the purging valve with an open-end spanner.
▶ Open the lower stop valve on the back of the product.
▶ If liquid escapes from the pipe, close the purging valve.
▶ Check the pressure in the heating circuit. If necessary,
If the minimum flow rate is too low, the heat
exchanger may become damaged by frost.
▶ Operate the product with a sufficient flow
rate (see table).
The product is designed for operation between the minimum
flow rate and maximum flow rate, as specified in the table. If
the product is operated with the minimum flow rate, this results in a loss of energy and efficiency. The heating comfort is
still guaranteed but the energy savings are reduced.
Envirosorb
5
Minimum
flow rate
Maximum
flow rate
380 l/h380 l/h540 l/h1,200 l/h
860 l/h1,400 l/h1,900 l/h2,590 l/h
You can read the flow rate directly from the controller. Depending on the type of liquid in the heating circuit, the flow
rate displayed on the controller may be exaggerated.
Example: If you use a 30% mixture of propylene glycol and
the liquid temperature is 5 °C, you must subtract 400 l/h from
the value shown on the display.
▶ Use the following table to compare the various exaggera-
tion flow rate values depending on liquid type.
– Applies for: Envirosorb35,
3
Envirosorb
8
3
Envirosorb
11
3
Envirosorb
15
3
7 Maintenance
C
C
B
A
Envirosorb38,
Envirosorb311
Flow rate increase (l/h)Temper-
ature
5 °C
Water000
60% alcohol000
Liquid
type
30% propylene
glycol
50% propylene
glycol
30% ethylene
glycol
50% ethylene
glycol
400240120
650500400
12000
40014050
– Applies for: Envirosorb315
Flow rate increase (l/h)Temper-
ature
5 °C
Water000
60% alcohol000
Liquid
type
30% propylene
glycol
50% propylene
glycol
30% ethylene
glycol
50% ethylene
glycol
600440280
1050740580
520350300
880680540
Note
Insufficient purging may lead to deviations in the
flow rate.
Temperature
15 °C
Temperature
15 °C
6.9Installing the side cladding
Temperature
25 °C
Temperature
25 °C
▶ Install the side cladding.
6.10Instructing the operator
1.Explain the how the system operates to the operator.
2.Draw particular attention to the safety information,
which the operator must follow.
3.Make the operator aware of the need for regular maintenance (maintenance contract).
4.Explain to the operator how to check the system's water
volume/filling pressure.
7Maintenance
▶ If you cannot reach the minimum flow rate, install an ad-
ditional pump.
▶ If you cannot reach the recommended flow rate, adjust
the heating circuit pressure on the controller and, if necessary, use a bypass valve (item 50).
7.1Observing maintenance intervals
1.Only carry out maintenance work if you are a competent
person.
2.Carry out annual maintenance.
7.2Preparing for maintenance
7.2.1Procuring spare parts
The original components of the product were also certified
as part of the CE declaration of conformity. Information about
available original spare parts is available by contacting the
contact address provided on the reverse of this document.
▶ If you require spare parts for maintenance or repair work,
7.3Instructions before carrying out
maintenance work
Observe the basic safety rules before carrying out maintenance work or installing spare parts.
Danger!
Risk of injury due to unauthorised access
to the coolant circuit.
Escaping coolant may cause freezing if the
exit point is touched.
▶ Only carry out work on the coolant circuit if
you have been trained to do so and if you
have the required protective clothing.
▶ Avoid skin and eye contact with the
coolant.
▶ Switch the system off.
▶ Disconnect the system from the power supply.
▶ Where necessary, disconnect the heating circuit from the
product by using the stop valves.
▶ If you have to replace parts on the heating circuit, you
must first drain the product.
▶ When working on the product, protect all electric com-
ponents from spray water.
7.5Cleaning the product
7.5.1Cleaning the front
Warning.
Risk of injury due to sharp-edged casing.
The product's casing sections have sharp
edges.
▶ Wear gloves when installing or dismant-
ling the product's casing sections.
7.4Yearly maintenance
▶ Check that the safety devices are functioning properly.
▶ Check the heating circuit's fill pressure.
▶ Ensure that there are no traces of rust or oil on the
coolant circuit components.
▶ Ensure that the product components are neither worn nor
defective.
▶ Check that all wires sit securely in the connectors.
▶ Check the product's earthing.
▶ Check the heating pump's flow temperature and the set-
tings.
▶ Remove any dust from the electronics box and the in-
verter box.
▶ Clean the ribbed pipe heat exchanger and ensure that air
circulates between the fins and around the product.
▶ Check that the fan rotates freely.
▶ Check that condensate can escape freely from the heat
pump by removing the adaptor underneath the heat
pump.
▶ Clean the product as described in the operating instruc-
tions.
▶ Check that the vibration dampers are correctly seated on
the coolant lines.
1.Remove the side casing. (→ Page 14)
2.Remove both screws (1).
3.Lift off the cover.
4.Remove both screws (2) on the right front casing.
5.Remove the right front casing.
6.Lift the louvred grill (3) upwards.
7.Remover the fan grill casing (4).
8.Remove the nut (5) from the fan.
9.Remove the fan.
10. Clean the product and the ribbed pipe heat exchanger.
7.5.2Cleaning the back
Warning.
Risk of injury due to sharp-edged casing.
If necessary, you can drain the heating
installation using this drain cock by opening
the stop valves on the back of the heat
pump.
7.7Checking the product's status codes
You can check the product's status codes at any time to see
which operating condition the heat pump is in. These codes
can be read on the system's control module.
The status codes are described in the table in the appendix.
7.8Checking the electrical installation
▶ Check the electrical installation and take all relevant dir-
ectives into account.
Checking the cable
If the product's mains power cable is damaged, then, in order
to avoid danger, only the manufacturer, the Customer Service team or a similarly qualified person should replace the
mains power cable.
▶ To replace the mains power cable, see Carrying out the
electrical installation (→ Page 17).
1.Remove the side casing. (→ Page 14)
2.Remove both screws (1).
3.Lift off the cover.
4.Remove the four screws (2) and remove the mesh (3).
5.Clean the product.
7.6Draining the product
Conditions: SW10 open-end spanner
▶ Disconnect the product from the power supply.
1 Heating circuit drain cock2 Drain hose
1.Close the stop valves on the back of the heat pump.
2.To drain the heating circuit, connect a hose to the drain
cock or place a vessel underneath the drain cock.
3.Open the drain cock with an open-end spanner.
7.9Start-up following maintenance
1.After the maintenance work has been completed, start
up the product – see Start-up (→ Page 21).
2.If you have carried out work on load-bearing parts,
check that they are securely fitted.
3.When you have completed work on the product, carry
out an operational and safety test.
8Troubleshooting
8.1Troubleshooting
You should carry out the following tests before introducing
additional steps:
▶ Make absolutely sure that the power supply was not cut
and that the product is correctly connected.
▶ Ensure that the service valves are open.
▶ Check that all external controllers are correctly connec-
ted.
8.2Fault codes
The fault codes are described in a table in the Appendix.
Fault codes (→ Page 36)
In the event of a fault, a fault code number is shown in the
controller's display.
▶ Carry out all necessary repairs.
▶ Switch the product on/off using the partition.
4.Dispose of or recycle the product and its components.
10Customer service
For contact details for our customer service department, you
can write to the address that is provided on the back page,
or you can visit www.glow-worm.co.uk.
11Disposal
Decommissioning 9
11.1Recycling and disposal
▶ The competent person who installed your product is re-
sponsible for the disposal of the packaging.
If the product or any batteries that it contains are
marked with this symbol, they contain substances hazardous
to human health and to the environment.
▶ In this case, do not dispose of the product and any bat-
teries that it contains with your normal household waste.
▶ Instead, bring the product and any batteries to a collec-
tion centre for batteries and electrical or electronic appliances.
11.2Arranging disposal of coolant
Warning.
Risk of damage to the environment.
This heat pump contains R 410 A coolant.
The coolant must not be allowed to escape
into the atmosphere. R 410 A is a fluorinated
greenhouse gas covered by the Kyoto Protocol, with a GWP of 1725 (GWP = Global
Warming Potential).
▶ Before the product is disposed of, have
the coolant which it contains completely
drained into a suitable vessel so that it
can then be recycled or disposed of in
accordance with regulations.
The competent person who installed the heat pump must
dispose of the coolant.
Personnel who are approved for energy recovery must have
the relevant certification that corresponds to the valid regulations.
1Flow heating circuit temperature sensor
2Return heating circuit temperature sensor
3High-efficiency pump with flow sensor
4Expansion vessel
5Drain valve
6Purging valve
7Fan
8Air inlet temperature sensor
9Ribbed pipe heat exchanger
10Temperature sensor of the ribbed pipe heat exchanger
114-way valve
12Plate heat exchanger
13Temperature sensor after the plate heat exchanger
14Service valve for the high-pressure range of the coolant
circuit
15High-pressure pressure switch in the coolant circuit
16High-pressure sensor in the coolant circuit
17Compressor outlet temperature sensor
18Rotary piston compressor
19Filter
20Liquid separator
21Electronic expansion valve
22Compressor inlet temperature sensor
23Service valve for the low-pressure range of the coolant
1Flow heating circuit temperature sensor
2Return heating circuit temperature sensor
3High-efficiency pump with flow sensor
4Expansion vessel
5Drain valve
6Purging valve
7Fan
8Air inlet temperature sensor
9Ribbed pipe heat exchanger
10Temperature sensor of the ribbed pipe heat exchanger
114-way valve
12Plate heat exchanger
13Temperature sensor after the plate heat exchanger
14Service valve for the high-pressure range of the coolant
circuit
15High-pressure pressure switch in the coolant circuit
16High-pressure sensor in the coolant circuit
17Compressor outlet temperature sensor
18Rotary piston compressor
19Filter
20Liquid separator
21Electronic expansion valve
22Compressor inlet temperature sensor
23Service valve for the low-pressure range of the coolant
1Flow heating circuit temperature sensor
2Return heating circuit temperature sensor
3High-efficiency pump with flow sensor
4Expansion vessel
5Drain valve
6Purging valve
7Fan
8Air inlet temperature sensor
9Ribbed pipe heat exchanger
10Temperature sensor of the ribbed pipe heat exchanger
114-way valve
12Plate heat exchanger
13Temperature sensor after the plate heat exchanger
14Service valve for the high-pressure range of the coolant
circuit
15High-pressure pressure switch in the coolant circuit
16High-pressure sensor in the coolant circuit
17Compressor outlet temperature sensor
18Rotary piston compressor
19Filter
20Liquid separator
21Electronic expansion valve
22Compressor inlet temperature sensor
23Service valve for the low-pressure range of the coolant
1Flow heating circuit temperature sensor
2Return heating circuit temperature sensor
3High-efficiency pump with flow sensor
4Expansion vessel
5Drain valve
6Purging valve
7Fan
8Air inlet temperature sensor
9Ribbed pipe heat exchanger
10Temperature sensor of the ribbed pipe heat exchanger
114-way valve
12Plate heat exchanger
13Temperature sensor after the plate heat exchanger
BHeat pump setting parameters
Note
If repairs are carried out on the heat pump electronics (e.g. replacing the PCB), you must reset the parameters.
14Service valve for the high-pressure range of the coolant
circuit
15High-pressure pressure switch in the coolant circuit
16High-pressure sensor in the coolant circuit
17Compressor outlet temperature sensor
18Rotary piston compressor
19Filter
20Liquid separator
21Electronic expansion valve
22Compressor inlet temperature sensor
23Service valve for the low-pressure range of the coolant
LanguageSelect the required language here.02 English01 Deutsch
Contact
details
Max. remaining heating
circuit feed
head
Max. remaining hot water
feed head
As a competent person, you can enter your telephone number here. The end customer can read this number in the
menu → Information.
Limiting the remaining heating circuit feed head. If the value
is reduced, the pump speed is reduced as far as necessary
in order to prevent the remaining feed head from being
exceeded.
Limiting the remaining hot water circuit feed head. If the
value is reduced, the pump speed is reduced as far as necessary in order to prevent the remaining feed head from
being exceeded.
Maximum
value
Maximum
value
Adjustment
range
02 English
03 Français
04 Italiano
05 Dansk
07 Castellano
08 Türkçe
09 Magyar
11 Українська
15 Svenska
16 Norsk
18 Čeština
19 Hrvatski
20 Slovenčina
22 Slovenščina
≥ 100 mbar
≥ 100 mbar
Own setting
CTechnical data
Note
The following performance data is only applicable to new products with clean heat exchangers.
99Fault with the product: Take note of the fault codes.
EOverview of fault codes
CodeMeaningCause
37The fan speed is too low.– Obstruction in the product's air guiding
– Fan motor not connected or faulty
– Power supply to the fan PCB is faulty
42Fault: Coding resistance– The product's coding resistance is missing or is faulty
– Coding resistance value outside the permissible range
86Safety thermostat for the underfloor heating triggered – Underfloor heating temperature too high
– Heating circuit flow rate too low
– Underfloor heating circuit is closed
103Fault: Spare part detection–The main PCB that is fitted as a spare part or the inverter does
not match the product
514Sensor fault: Comp. inlet temp.
517Sensor fault: Comp. outlet temp.
519Sensor fault: Return temperature
520Sensor fault: Flow temperature
526Sensor fault: Heat exchanger temp.Sensor is faulty or incorrectly connected to the main PCB
532Building circuit: Flow rate too low– Pump faulty
– Sensor is faulty or incorrectly connected to the main PCB
Check the specific flow rate in forced mode
– Between 7000 and 7700 l/h: Alarm
– Between 7700 and 8200 l/h: The pump runs dry (no water in
the heating circuit; the heating circuit loses water)
– Between 8200 and 8700 l/h: Fault in the electronics
– Between 8700 and 9200 l/h: Pump blocked
– Between 9200 and 10,000 l/h: No PWM signal (cable faulty
or not connected; fault in the main PCB)
– Pump cabling has not been carried out correctly (PWM and sup-
ply)
– Low water pressure
– Dirt filter in the heating circuit return is missing or blocked
– Heating circuit not fully purged
– Pressure loss in the heating circuit too high
536Compressor outlet temperature too high (depends on
the compressor's operating range)
537Outlet pressure of the compressor too high– Coolant volume too high or too low
539Coolant pressure too low– Coolant quantity too low
546Sensor fault: Pressure sensor in the coolant circuit–Faulty cabling
554Coolant pressure not in operating range– Coolant volume too high or too low
582EEV fault– Cable insulation faulty
585Sensor fault: EEV building circuit temp.– Sensor is faulty or incorrectly connected to the main PCB
685Communication fault: eBUS– The product is not connected to the controller
750Compressor shut down– Cable insulation faulty
751Compressor overcurrent–Fault in the compressor
752Fault: Inverter– Inverter casing damaged
753Connection fault: Inverter not recognised–The connection between the main PCB and the inverter box is
754Fault: Fan PCB– The connection between the main PCB and the fan PCB is dam-
755Positioning fault: 4-way valveMechanical or electrical problem. Move the 4-way valve away from
774Sensor fault: Air inlet temperature– The temperature sensor is faulty or incorrectly connected to the
– Coolant quantity too low
– Sensor is faulty or incorrectly connected to the main PCB
– Pressure drop in the liquid line (pressure loss)
– Electronic expansion valve faulty
– Heat exchanger blocked
– Incorrect evacuation
– Incondensable particle in the coolant circuit
– Pressure switch or electrical connection faulty
– Pressure drop in the liquid line (pressure loss)
– Flow quantity too high (see defined maximum flow rate)
– Electronic expansion valve faulty
– Insufficient heat transfer in the heat exchanger
– Air flow too low
– No thawing
– The resistance heating in the condensate collecting container is
faulty.
– 4-way valve faulty
– Electronic expansion valve motor faulty, or connection faulty
– Sensor defective
– Incondensable particle in the coolant circuit
– Electronic expansion valve faulty
– Flow quantity too high (see defined maximum flow rate)
– Pressure drop in the liquid line (pressure loss)
– Insufficient heat exchange in the plate heat exchanger or the
ribbed pipe heat exchanger
– 4-way valve faulty
– Connection broken
– Polarity inverted
– Connection broken
– The product's voltage supply is too low
– The ribbed pipe heat exchanger or heat exchanger is dirty
– Cooler inverter box is dirty
– Faulty voltage supply
damaged or broken
– Inverter box is not switched on
aged or broken.
– The fan is faulty
– The fan PCB is faulty
– The power supply to the fan PCB is faulty
– The heat pump was switched on before the system's control sys-
tem (start up the control system before the heat pump or switch
on both components at the same time)
the controller. When moving it, check that the coil voltage is correct.