Glow-worm Envirosorb3 User Manual

The energy you need
Installation instruc­tions
Envirosorb
GB

Contents

1 Safety .................................................................... 3
1.1 Action-related warnings ......................................... 3
1.2 Required personnel qualifications ......................... 3
1.3 General safety information .................................... 3
1.4 Regulations (directives, laws, standards).............. 4
1.5 CE label ................................................................. 4
1.6 Approvals............................................................... 4
1.7 Local regulations.................................................... 5
1.8 Regulations............................................................ 5
1.9 Other regulations ................................................... 5
1.10 Intended use .......................................................... 5
2 Notes on the documentation .............................. 7
2.1 Observing other applicable documents ................. 7
2.2 Storing documents................................................. 7
2.3 Applicability of the instructions .............................. 7
3 System overview.................................................. 7
3.1 Safety devices ....................................................... 7
3.2 Functionality........................................................... 7
3.3 Permitted hydraulic configurations ........................ 8
3.4 System diagram (Envirosorb35)............................ 8
3.5 System diagram (Envirosorb38, Envirosorb311,
Envirosorb315) ...................................................... 9
4 Overview of the equipment................................. 9
4.1 Type designation and serial number ..................... 9
4.2 Information on the identification plate.................... 9
5 Assembly and installation ................................ 10
5.1 Preparing for fitting and installation ..................... 10
5.2 Carrying out the installation ................................. 14
5.3 Hydraulics installation.......................................... 15
5.4 Carrying out the electrical installation.................. 17
5.5 Connection diagrams........................................... 19
6 Start-up ............................................................... 21
6.1 Run the start-up................................................... 21
6.2 Filling the heating circuit ...................................... 21
6.3 Treating the heating water................................... 21
6.4 Filling the heating installation .............................. 22
6.5 Activating the heat pump ..................................... 22
6.6 Checking the product's operation ........................ 22
6.7 Operating noises.................................................. 23
6.8 Adjusting the heating circuit................................. 23
6.9 Installing the side cladding .................................. 24
6.10 Instructing the operator........................................ 24
7 Maintenance....................................................... 24
7.1 Observing maintenance intervals ........................ 24
7.2 Preparing for maintenance .................................. 24
7.3 Instructions before carrying out maintenance
work ..................................................................... 25
7.4 Yearly maintenance............................................. 25
7.5 Cleaning the product............................................ 25
7.6 Draining the product ............................................ 26
7.7 Checking the product's status codes ................... 26
7.8 Checking the electrical installation ...................... 26
7.9 Start-up following maintenance ........................... 26
8 Troubleshooting ................................................ 26
8.1 Troubleshooting................................................... 26
8.2 Fault codes .......................................................... 26
9 Decommissioning.............................................. 27
9.1 Temporary decommissioning .............................. 27
9.2 Permanently decommissioning............................ 27
10 Customer service............................................... 27
11 Disposal.............................................................. 27
11.1 Recycling and disposal ........................................ 27
11.2 Arranging disposal of coolant .............................. 27
Appendix ............................................................................28
A Heat pump schematic........................................ 28
A.1 Heat pump schematic drawing (Envirosorb
3
5).......................................................................... 28
A.2 Heat pump schematic drawing (Envirosorb
3
8).......................................................................... 29
A.3 Heat pump schematic drawing (Envirosorb
3
11)........................................................................ 30
A.4 Heat pump schematic drawing (Envirosorb
3
15)........................................................................ 31
B Heat pump setting parameters......................... 31
C Technical data.................................................... 32
D Status codes ...................................................... 34
E Overview of fault codes .................................... 36
Index ...................................................................................39
2 Installation instructions Envirosorb0020154078_03
Safety 1

1 Safety

1.1 Action-related warnings

Classification of action-related warnings
The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental damage

1.2 Required personnel qualifications

Secure against being switched back on
again.
Wait for at least 3 minutes until the con-
densers have discharged.
Check that there is no voltage.Cover or insulate adjacent live parts.

1.3.3 Risk of death due to lack of safety devices

A lack of safety devices (e.g. expansion re­lief valve, expansion vessel) may lead to po­tentially fatal scalding and other injuries, e.g. due to explosions. The schematic drawings included in this document do not show all safety devices required for correct installa­tion.
Install the necessary safety devices in the
system.
Inform the operator about the function and
position of the safety devices.
Observe the applicable national and inter-
national laws, standards and guidelines.
Improper work carried out on the product may cause material damage to the complete installation and, as a consequence, may even cause personal injury.
You should therefore only work on the
product if you are an authorised competent person.

1.3 General safety information

1.3.1 Danger caused by improper operation

Improper operation may present a danger to you and others, and cause material damage.
Carefully read the enclosed instructions
and all other applicable documents, par­ticularly the "Safety" section and the warn­ings.

1.3.2 Risk of death from electric shock

There is a risk of death from electric shock if you touch live components.

1.3.4 Risk of being scalded by hot drinking water

There is a risk of scalding at the hot water draw-off points if the hot water temperatures are greater than 50 °C. Young children and elderly persons are particularly at risk, even at lower temperatures.
Select the temperature so that nobody is at
risk.

1.3.5 Risk of injury or material damage due to incorrect handling of the product

Using the fins on the front side of the product as conductors may lead to injuries (due to falling) or to material damage.
Do not use the fins as conductors.

1.3.6 Risk of material damage due to additional elements in the heating water

Before commencing work on the product: Disconnect the product from the power
supply (electrical partition with a contact opening of at least 3 mm, e.g. fuse or power switch).
Unsuitable frost and corrosion protection agents may damage seals and other com­ponents of the heating circuit and may there­fore also lead to leaks in the water outlet.
Only add approved frost and corrosion
protection agents to the heating water.
0020154078_03 EnvirosorbInstallation instructions 3
1 Safety

1.3.7 Risk of material damage caused by using an unsuitable tool

Use the correct tool to tighten or loosen
screw connections.

1.3.8 Avoid environmental damage caused by escaping coolant

The heat pump contains R410A coolant. The coolant must not be allowed to escape into the atmosphere. R410A is a fluorinated greenhouse gas covered by the Kyoto Pro­tocol, with a GWP of 1725 (GWP = Global Warming Potential). If it escapes into the at­mosphere, its impact is 1725 times stronger than the natural greenhouse gas CO2.
Before the heat pump is disposed of, the coolant it contains must be completely drained into a suitable vessel so that it can then be recycled or disposed of in accordance with the regulations.
Ensure that only officially certified com-
petent persons with appropriate protective equipment carry out maintenance work on the coolant circuit or access it.
Arrange for the coolant contained in the
product to be recycled or disposed of by accredited specialists in accordance with regulations.
Only use coolant R410A.Only use a suitable R410A tool for the
filling, pressure measurement, vacuum generation and discharge.
Solder the lines using shielding gas. Check
the lines for leak-tightness using nitrogen.
In the event of a repair or maintenance
work, fill the coolant circuit with liquid coolant.
If the coolant circuit is not leak-tight, check
which component must be repaired or re­placed.
Lower the negative pressure in the coolant
circuit to max. 10 mbar (1000 Pa).
When filling the coolant circuit, observe the
values in the "Technical data" section.

1.4 Regulations (directives, laws, standards)

As part of the installation, commissioning and operation of the heat pump and the DHW storage you must take into account the cur­rent versions of the following regulations or standards, along with any local directives or guidelines that may apply.
Electricity at work act.Health and safety at work act.Relevant Utility supplier’s regulations.Water regulations and by-laws.Environment agency and local council re-
quirements regarding bore holes, water courses, or noise levels.
– Gas safety installation and use regulations
concerning any associated gas fired heat source used within the heating system.
– Building regulations part “L” and directives
concerning energy saving.
– Building regulations such as G3 covering
Hygiene and L8 Legieonella.
COSHH regulations.Other relevant bodies such as HETAS and
OFTEC.
– BS7671 requirements for electrical installa-
tions.

1.5 CE label

The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate.
The declaration of conformity can be viewed at the manufacturer's site.

1.6 Approvals

This product has been fully tested in accord­ance with:
– BS EN 14511:2011
4 Installation instructions Envirosorb0020154078_03
Safety 1

1.7 Local regulations

Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instruc­tions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appro­priate Building Regulations. The Benchmark Checklist can be used to demonstrate compli­ance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accord­ance with the Benchmark Code of Practice which is available from the Heating and Hot­water Industry Council who manage and pro­mote the Scheme.
standards and provisions in eff ect at the time.

1.8.3 Reminder of existing regulatory acts

– EC regulation No. 20372000 from the 29th
of June 2000 This European regulation re­peals regulation No. 3093/94 and presents the elimination schedules of CFC and HCFC. It also deals with the collection of refrigerants, system leaks, particularly sys­tems containing more than 3 kg of CFC or HCFC, as well as the minimum level of qualifi cation required by the technicians.
– EC regulation No. 0842/2006 from the 17th
of May 2006 regarding the containment, use, collection and disposal of the fl uorin­ated greenhouse gases, the labelling and elimination of the products and equipment containing these gases, the restriction of use and banning of certain products from the market, as well as the training and cer­tifi cation of personnel and companies op­erating in the activities targeted by this reg­ulation: refrigeration, air-conditioning, heat pumps and fi re protection systems con­taining greenhouse gases.
Visit www.centralheating.co.uk for more in­formation.
Planning consent and Building works notific­ation should be submitted either to Building Control or to a Competent Person Provider.

1.8 Regulations

1.8.1 Statutory requirements

Where no British Standards exists, materials and equipment should be fi t for their purpose and of suitable quality and workmanship.
The installation of this appliance must be car­ried out by a competent person in accord­ance the rules in force in the countries of des­tination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.

1.8.2 Standards

On installing and commissioning the appli­ance you must adhere to the technical rules,

1.9 Other regulations

1.9.1 Control of Substances Hazardous to Health

Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide in­formation on substances hazardous to health. The adhesives and sealants used in this ap­pliance are cured and give no known hazard in this state.
The refrigerant used in this appliance is R410a the use of which is strictly controlled by F Gas regulation EN842/2006.

1.10 Intended use

There is a risk of injury or death to the user or others, or of damage to the product and other property in the event of improper use or use for which it is not intended.
The heat pump is an air/water monoblock system and uses the energy from the outside air to supply heat to the building.
The heat pumps are intended exclusively for domestic use as heat generators for closed
0020154078_03 EnvirosorbInstallation instructions 5
1 Safety
heating and hot water central heating sys­tems and for hot water generation.
Intended use includes the following: – observance of accompanying operating,
installation and servicing instructions for the product and any other system compon­ents
– installing and fitting the product in accord-
ance with the product and system approval
– compliance with all inspection and main-
tenance conditions listed in the instruc­tions.
Any other use that is not specified in these instructions, or use beyond that specified in this document, shall be considered improper use. Any direct commercial or industrial use is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
6 Installation instructions Envirosorb0020154078_03
Notes on the documentation 2
1
2
3
4
5
6
1
2
3
4
5
6

2 Notes on the documentation

2.1 Observing other applicable documents

You must observe all the operating and installation in-
structions included with the system components.

2.2 Storing documents

Pass these instructions and all other applicable docu-
ments on to the system operator.

2.3 Applicability of the instructions

These instructions apply to units with the following type des­ignations and article numbers only:
Type designation Art. no.
Envirosorb35 0010014421
Envirosorb38 0010011967
Envirosorb311 0010011968
Envirosorb315 0010014422
The seventh to sixteenth digits of the serial number on the identification plate form the article number.
protection agent should be added to the heating water as the heating water temperature may fall below the freez­ing point in the event of a power cut, which poses a risk of frost to the heating installation.
Note
Operating the heat pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.

3.2 Functionality

The product comprises the following circuits:
– The coolant circuit releases heat into the heating circuit
by means of evaporation, compression, condensation and expansion
– The heating circuit

3.2.1 Heating mode

3 System overview

3.1 Safety devices

– The product can work at the following outside temperat-
ures:
Envirosorb 5
Heating mode 15 … 28 20 … 28
Cylinder charging mode 15 … 46 20 … 46
– If the product's coolant circuit pressure exceeds the max-
imum pressure of 4.15 MPa (41.5 bar), the high-pres­sure pressure switch switches the product off. Follow­ing a waiting period, the product attempts to start once more. After three failed start attempts in succession, a fault message is displayed.
– If the product is switched off, the crankcase housing
heating is switched on when the compressor outlet tem­perature reaches 7 °C in order to prevent possible dam­age caused by switching it back on.
– If the compressor inlet temperature and the compressor
outlet temperature are below 1 °C, the compressor does not start up.
– A temperature sensor on the compressor outlet limits the
product's operation if the measured temperature exceeds the maximum permissible temperature. The maximum permissible temperature depends on the evaporation and condensation temperature.
– The product measures the flow rate of the connected
heating circuit when starting up the product.
– If the heating circuit temperature falls below 3 °C, the
product's frost protection function is automatically ac­tivated as the heating pump is started. In addition, frost
Envirosorb
3
8, Envirosorb 11, Envirosorb 15
3
1 Evaporator 2 4-way valve
3
3 Fan
3
4 Compressor 5 Electronic expansion valve 6 Plate heat exchanger

3.2.2 Thawing

1 Evaporator 2 4-way valve 3 Fan
4 Compressor 5 Electronic expansion valve 6 Plate heat exchanger

3.2.3 Application limits

Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
0020154078_03 EnvirosorbInstallation instructions 7
3 System overview
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-15;22]
[-15;45]
[46;22]
[46;58]
[35;60]
[28;60]
[2;60]
[-10;55]
1
2
[28;22]
[35;22]
A
B
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-20;22]
[-20;43]
[46;22]
[46;58]
[35;63]
[28;63]
[2;63]
[-10;55]
1
2
[28;22]
[35;22]
A
B
e
1 3 12161719
24
1521
14
11
4
23
20222
5 13 8 9
6
7
10
A
B
18
3.2.3.1 Application limits in heating mode (Envirosorb35)
1 Heating mode application
limits
2 Hot water generation
application limits
A Water temperature B Air temperature
3.2.3.2 Application limits in heating mode (Envirosorb38, Envirosorb311, Envirosorb
15)

3.3.2 Indirect connection to a heating installation via a hydraulic module

3.4 System diagram (Envirosorb35)

3
1 Heating mode application
limits
2 Hot water generation
application limits

3.3 Permitted hydraulic configurations

3.3.1 Direct connection to a heating installation

8 Installation instructions Envirosorb0020154078_03
A Water temperature B Air temperature
1 Fan 2 Air inlet temperature
sensor
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex­changer
5 4-way valve 6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow rate sensor
8 Purging valve 9 Flow heating circuit tem-
perature sensor
10 Drain valve 11 Plate heat exchanger 12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
14 High-pressure pressure
switch in the coolant cir­cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor 18 Filter 19 Liquid separator 20 Electronic expansion valve 21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the coolant circuit
23 Filter 24 Fluid collector A Heating return B Heating flow
pressure range of the coolant circuit
Overview of the equipment 4
e
1 3 12161719
25
23
1521
14
11
4
24
20222
5 13 8 9
6
7
10
A
B
18
1
1

3.5 System diagram (Envirosorb38, Envirosorb311, Envirosorb315)

1 Fan 2 Air inlet temperature
sensor
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex­changer
5 4-way valve 6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow sensor
8 Purging valve 9 Flow heating circuit tem-
perature sensor
10 Drain valve 11 Plate heat exchanger 12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
pressure range of the coolant circuit
14 High-pressure pressure
switch in the coolant cir­cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor 18 Filter 19 Liquid separator 20 Electronic expansion valve 21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the coolant circuit
23 Flow rate limiter (cooling
mode) on Genia Air 8/1 only
24 Filter 25 Gas buffer A Heating return B Heating flow

4 Overview of the equipment

4.1 Type designation and serial number

The type designation and serial number are on the identifica­tion plate (1).

4.2 Information on the identification plate

Information on the identi­fication plate
Serial no. Unique unit identification number
P max Maximum rated power
I Max. operating current
I max Maximum start-up current
R410A Coolant type and fill quantity
PSR_LP PSR_HP
PSHmin PSHmax
COP (Ax/Wxx) Output figure (coefficient of
(Ax/Wxx)
Volt Compressor, pump and control-
Hz Power frequency
IP Protection class
Meaning
Min. and max. operating pres­sure in the coolant circuit
Minimum and maximum operat­ing pressure in the heating circuit
performance) at an air inlet temperature of xx °C and a heating flow temperature of xx °C
Heating output at an air inlet temperature of xx °C and a heating flow temperature of xx °C
ler mains voltage
0020154078_03 EnvirosorbInstallation instructions 9

5 Assembly and installation

13mm
1
2
3
4
B
A
D
E
C
5 Assembly and installation

5.1 Preparing for fitting and installation

5.1.1 Delivery, transport and positioning

5.1.1.1 Transporting the product
During transport, do not tilt the heat pump
by any more than the maximum angle of 45°.
1. Use the transportation belt to carry the product to the final installation site.
2. Only lift the product from the back and side where the hydraulic connections are located.
3. When transporting the product using a hand truck, se­cure the product using a belt.
4. In order to avoid scratches and damage, protect the sides of the product that come into contact with the hand truck.
5.1.1.2 Unpacking the product
Warning. Risk of injury from lifting a heavy weight.
Lifting weights that are too heavy may cause injury to the spine, for example.
When transporting the product, two
people should lift it.
Observe the product weight stated in the
technical data.
When transporting heavy loads, observe
the applicable directives and regulations.
1. Remove the accessory (2).
2. Remove the documentation supplied (1).
3. Remove the transport belt (4).
4. Carefully remove the packaging and padding without damaging the product (3).
5. Remove the screws from the pallet at the front and rear of the product.
Caution. Risk of material damage due to incorrect
transportation.
Regardless of the mode of transport, the heat pump must never be tilted by more than 45°. Otherwise, this may lead to malfunctions in the coolant circuit during subsequent opera­tion. In the worst case scenario, this may lead to a fault in the whole system.
10 Installation instructions Envirosorb0020154078_03
5.1.1.3 Checking the scope of delivery
120
120
740
980
360
800*
386
11
Envirosorb 5
3
162
162
778
1103
415
942*
437
11
Envirosorb 8
3
Envirosorb 11
3
Check the contents of the packaging units
Quant­ity
1 Condensate discharge
1 Bag with seals
4 Vibration-isolating feet
1 Purge hose
5.1.2 Complying with clearances and installation
5.1.2.1 Unit dimensions and connection
Description
clearances
dimensions
Assembly and installation 5
* Size increases by 45 mm
when using the vibration dampers supplied.
* Size increases by 45 mm
when using the vibration dampers supplied.
0020154078_03 EnvirosorbInstallation instructions 11
5 Assembly and installation
162
162
778
1103
415
1340*
437
11
Envirosorb 15
3
C
B
D
A
A
E
5.1.2.2 Installation clearance
* Size increases by 45 mm
when using the vibration dampers supplied.
Clearance For heating mode
A > 250 mm
B > 1000 mm
C > 120 mm*
D > 600 mm
E > 300 mm
*Caution: If the minimum clearances are not maintained, the output of the product may be affected.
To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are specified above.
Ensure that there is sufficient room to install the hydraulic
lines.
If the product is to be installed in areas where heavy
snow falls, ensure that the snow does not accumulate around the product and that the minimum clearances specified above are observed. If you cannot ensure this, install an additional heat generator in the heating circuit.
12 Installation instructions Envirosorb0020154078_03
Loading...
+ 28 hidden pages