Glow-worm Envirosorb3 User Manual

The energy you need
Installation instruc­tions
Envirosorb
GB

Contents

1 Safety .................................................................... 3
1.1 Action-related warnings ......................................... 3
1.2 Required personnel qualifications ......................... 3
1.3 General safety information .................................... 3
1.4 Regulations (directives, laws, standards).............. 4
1.5 CE label ................................................................. 4
1.6 Approvals............................................................... 4
1.7 Local regulations.................................................... 5
1.8 Regulations............................................................ 5
1.9 Other regulations ................................................... 5
1.10 Intended use .......................................................... 5
2 Notes on the documentation .............................. 7
2.1 Observing other applicable documents ................. 7
2.2 Storing documents................................................. 7
2.3 Applicability of the instructions .............................. 7
3 System overview.................................................. 7
3.1 Safety devices ....................................................... 7
3.2 Functionality........................................................... 7
3.3 Permitted hydraulic configurations ........................ 8
3.4 System diagram (Envirosorb35)............................ 8
3.5 System diagram (Envirosorb38, Envirosorb311,
Envirosorb315) ...................................................... 9
4 Overview of the equipment................................. 9
4.1 Type designation and serial number ..................... 9
4.2 Information on the identification plate.................... 9
5 Assembly and installation ................................ 10
5.1 Preparing for fitting and installation ..................... 10
5.2 Carrying out the installation ................................. 14
5.3 Hydraulics installation.......................................... 15
5.4 Carrying out the electrical installation.................. 17
5.5 Connection diagrams........................................... 19
6 Start-up ............................................................... 21
6.1 Run the start-up................................................... 21
6.2 Filling the heating circuit ...................................... 21
6.3 Treating the heating water................................... 21
6.4 Filling the heating installation .............................. 22
6.5 Activating the heat pump ..................................... 22
6.6 Checking the product's operation ........................ 22
6.7 Operating noises.................................................. 23
6.8 Adjusting the heating circuit................................. 23
6.9 Installing the side cladding .................................. 24
6.10 Instructing the operator........................................ 24
7 Maintenance....................................................... 24
7.1 Observing maintenance intervals ........................ 24
7.2 Preparing for maintenance .................................. 24
7.3 Instructions before carrying out maintenance
work ..................................................................... 25
7.4 Yearly maintenance............................................. 25
7.5 Cleaning the product............................................ 25
7.6 Draining the product ............................................ 26
7.7 Checking the product's status codes ................... 26
7.8 Checking the electrical installation ...................... 26
7.9 Start-up following maintenance ........................... 26
8 Troubleshooting ................................................ 26
8.1 Troubleshooting................................................... 26
8.2 Fault codes .......................................................... 26
9 Decommissioning.............................................. 27
9.1 Temporary decommissioning .............................. 27
9.2 Permanently decommissioning............................ 27
10 Customer service............................................... 27
11 Disposal.............................................................. 27
11.1 Recycling and disposal ........................................ 27
11.2 Arranging disposal of coolant .............................. 27
Appendix ............................................................................28
A Heat pump schematic........................................ 28
A.1 Heat pump schematic drawing (Envirosorb
3
5).......................................................................... 28
A.2 Heat pump schematic drawing (Envirosorb
3
8).......................................................................... 29
A.3 Heat pump schematic drawing (Envirosorb
3
11)........................................................................ 30
A.4 Heat pump schematic drawing (Envirosorb
3
15)........................................................................ 31
B Heat pump setting parameters......................... 31
C Technical data.................................................... 32
D Status codes ...................................................... 34
E Overview of fault codes .................................... 36
Index ...................................................................................39
2 Installation instructions Envirosorb0020154078_03
Safety 1

1 Safety

1.1 Action-related warnings

Classification of action-related warnings
The action-related warnings are classified in accordance with the severity of the possible danger using the following warning signs and signal words:
Warning symbols and signal words
Danger!
Imminent danger to life or risk of severe personal injury
Danger!
Risk of death from electric shock
Warning.
Risk of minor personal injury
Caution.
Risk of material or environmental damage

1.2 Required personnel qualifications

Secure against being switched back on
again.
Wait for at least 3 minutes until the con-
densers have discharged.
Check that there is no voltage.Cover or insulate adjacent live parts.

1.3.3 Risk of death due to lack of safety devices

A lack of safety devices (e.g. expansion re­lief valve, expansion vessel) may lead to po­tentially fatal scalding and other injuries, e.g. due to explosions. The schematic drawings included in this document do not show all safety devices required for correct installa­tion.
Install the necessary safety devices in the
system.
Inform the operator about the function and
position of the safety devices.
Observe the applicable national and inter-
national laws, standards and guidelines.
Improper work carried out on the product may cause material damage to the complete installation and, as a consequence, may even cause personal injury.
You should therefore only work on the
product if you are an authorised competent person.

1.3 General safety information

1.3.1 Danger caused by improper operation

Improper operation may present a danger to you and others, and cause material damage.
Carefully read the enclosed instructions
and all other applicable documents, par­ticularly the "Safety" section and the warn­ings.

1.3.2 Risk of death from electric shock

There is a risk of death from electric shock if you touch live components.

1.3.4 Risk of being scalded by hot drinking water

There is a risk of scalding at the hot water draw-off points if the hot water temperatures are greater than 50 °C. Young children and elderly persons are particularly at risk, even at lower temperatures.
Select the temperature so that nobody is at
risk.

1.3.5 Risk of injury or material damage due to incorrect handling of the product

Using the fins on the front side of the product as conductors may lead to injuries (due to falling) or to material damage.
Do not use the fins as conductors.

1.3.6 Risk of material damage due to additional elements in the heating water

Before commencing work on the product: Disconnect the product from the power
supply (electrical partition with a contact opening of at least 3 mm, e.g. fuse or power switch).
Unsuitable frost and corrosion protection agents may damage seals and other com­ponents of the heating circuit and may there­fore also lead to leaks in the water outlet.
Only add approved frost and corrosion
protection agents to the heating water.
0020154078_03 EnvirosorbInstallation instructions 3
1 Safety

1.3.7 Risk of material damage caused by using an unsuitable tool

Use the correct tool to tighten or loosen
screw connections.

1.3.8 Avoid environmental damage caused by escaping coolant

The heat pump contains R410A coolant. The coolant must not be allowed to escape into the atmosphere. R410A is a fluorinated greenhouse gas covered by the Kyoto Pro­tocol, with a GWP of 1725 (GWP = Global Warming Potential). If it escapes into the at­mosphere, its impact is 1725 times stronger than the natural greenhouse gas CO2.
Before the heat pump is disposed of, the coolant it contains must be completely drained into a suitable vessel so that it can then be recycled or disposed of in accordance with the regulations.
Ensure that only officially certified com-
petent persons with appropriate protective equipment carry out maintenance work on the coolant circuit or access it.
Arrange for the coolant contained in the
product to be recycled or disposed of by accredited specialists in accordance with regulations.
Only use coolant R410A.Only use a suitable R410A tool for the
filling, pressure measurement, vacuum generation and discharge.
Solder the lines using shielding gas. Check
the lines for leak-tightness using nitrogen.
In the event of a repair or maintenance
work, fill the coolant circuit with liquid coolant.
If the coolant circuit is not leak-tight, check
which component must be repaired or re­placed.
Lower the negative pressure in the coolant
circuit to max. 10 mbar (1000 Pa).
When filling the coolant circuit, observe the
values in the "Technical data" section.

1.4 Regulations (directives, laws, standards)

As part of the installation, commissioning and operation of the heat pump and the DHW storage you must take into account the cur­rent versions of the following regulations or standards, along with any local directives or guidelines that may apply.
Electricity at work act.Health and safety at work act.Relevant Utility supplier’s regulations.Water regulations and by-laws.Environment agency and local council re-
quirements regarding bore holes, water courses, or noise levels.
– Gas safety installation and use regulations
concerning any associated gas fired heat source used within the heating system.
– Building regulations part “L” and directives
concerning energy saving.
– Building regulations such as G3 covering
Hygiene and L8 Legieonella.
COSHH regulations.Other relevant bodies such as HETAS and
OFTEC.
– BS7671 requirements for electrical installa-
tions.

1.5 CE label

The CE label shows that the products comply with the basic requirements of the applicable directives as stated on the identification plate.
The declaration of conformity can be viewed at the manufacturer's site.

1.6 Approvals

This product has been fully tested in accord­ance with:
– BS EN 14511:2011
4 Installation instructions Envirosorb0020154078_03
Safety 1

1.7 Local regulations

Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instruc­tions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appro­priate Building Regulations. The Benchmark Checklist can be used to demonstrate compli­ance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accord­ance with the Benchmark Code of Practice which is available from the Heating and Hot­water Industry Council who manage and pro­mote the Scheme.
standards and provisions in eff ect at the time.

1.8.3 Reminder of existing regulatory acts

– EC regulation No. 20372000 from the 29th
of June 2000 This European regulation re­peals regulation No. 3093/94 and presents the elimination schedules of CFC and HCFC. It also deals with the collection of refrigerants, system leaks, particularly sys­tems containing more than 3 kg of CFC or HCFC, as well as the minimum level of qualifi cation required by the technicians.
– EC regulation No. 0842/2006 from the 17th
of May 2006 regarding the containment, use, collection and disposal of the fl uorin­ated greenhouse gases, the labelling and elimination of the products and equipment containing these gases, the restriction of use and banning of certain products from the market, as well as the training and cer­tifi cation of personnel and companies op­erating in the activities targeted by this reg­ulation: refrigeration, air-conditioning, heat pumps and fi re protection systems con­taining greenhouse gases.
Visit www.centralheating.co.uk for more in­formation.
Planning consent and Building works notific­ation should be submitted either to Building Control or to a Competent Person Provider.

1.8 Regulations

1.8.1 Statutory requirements

Where no British Standards exists, materials and equipment should be fi t for their purpose and of suitable quality and workmanship.
The installation of this appliance must be car­ried out by a competent person in accord­ance the rules in force in the countries of des­tination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.

1.8.2 Standards

On installing and commissioning the appli­ance you must adhere to the technical rules,

1.9 Other regulations

1.9.1 Control of Substances Hazardous to Health

Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide in­formation on substances hazardous to health. The adhesives and sealants used in this ap­pliance are cured and give no known hazard in this state.
The refrigerant used in this appliance is R410a the use of which is strictly controlled by F Gas regulation EN842/2006.

1.10 Intended use

There is a risk of injury or death to the user or others, or of damage to the product and other property in the event of improper use or use for which it is not intended.
The heat pump is an air/water monoblock system and uses the energy from the outside air to supply heat to the building.
The heat pumps are intended exclusively for domestic use as heat generators for closed
0020154078_03 EnvirosorbInstallation instructions 5
1 Safety
heating and hot water central heating sys­tems and for hot water generation.
Intended use includes the following: – observance of accompanying operating,
installation and servicing instructions for the product and any other system compon­ents
– installing and fitting the product in accord-
ance with the product and system approval
– compliance with all inspection and main-
tenance conditions listed in the instruc­tions.
Any other use that is not specified in these instructions, or use beyond that specified in this document, shall be considered improper use. Any direct commercial or industrial use is also deemed to be improper.
Caution.
Improper use of any kind is prohibited.
6 Installation instructions Envirosorb0020154078_03
Notes on the documentation 2
1
2
3
4
5
6
1
2
3
4
5
6

2 Notes on the documentation

2.1 Observing other applicable documents

You must observe all the operating and installation in-
structions included with the system components.

2.2 Storing documents

Pass these instructions and all other applicable docu-
ments on to the system operator.

2.3 Applicability of the instructions

These instructions apply to units with the following type des­ignations and article numbers only:
Type designation Art. no.
Envirosorb35 0010014421
Envirosorb38 0010011967
Envirosorb311 0010011968
Envirosorb315 0010014422
The seventh to sixteenth digits of the serial number on the identification plate form the article number.
protection agent should be added to the heating water as the heating water temperature may fall below the freez­ing point in the event of a power cut, which poses a risk of frost to the heating installation.
Note
Operating the heat pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.

3.2 Functionality

The product comprises the following circuits:
– The coolant circuit releases heat into the heating circuit
by means of evaporation, compression, condensation and expansion
– The heating circuit

3.2.1 Heating mode

3 System overview

3.1 Safety devices

– The product can work at the following outside temperat-
ures:
Envirosorb 5
Heating mode 15 … 28 20 … 28
Cylinder charging mode 15 … 46 20 … 46
– If the product's coolant circuit pressure exceeds the max-
imum pressure of 4.15 MPa (41.5 bar), the high-pres­sure pressure switch switches the product off. Follow­ing a waiting period, the product attempts to start once more. After three failed start attempts in succession, a fault message is displayed.
– If the product is switched off, the crankcase housing
heating is switched on when the compressor outlet tem­perature reaches 7 °C in order to prevent possible dam­age caused by switching it back on.
– If the compressor inlet temperature and the compressor
outlet temperature are below 1 °C, the compressor does not start up.
– A temperature sensor on the compressor outlet limits the
product's operation if the measured temperature exceeds the maximum permissible temperature. The maximum permissible temperature depends on the evaporation and condensation temperature.
– The product measures the flow rate of the connected
heating circuit when starting up the product.
– If the heating circuit temperature falls below 3 °C, the
product's frost protection function is automatically ac­tivated as the heating pump is started. In addition, frost
Envirosorb
3
8, Envirosorb 11, Envirosorb 15
3
1 Evaporator 2 4-way valve
3
3 Fan
3
4 Compressor 5 Electronic expansion valve 6 Plate heat exchanger

3.2.2 Thawing

1 Evaporator 2 4-way valve 3 Fan
4 Compressor 5 Electronic expansion valve 6 Plate heat exchanger

3.2.3 Application limits

Operation of the pump outside the application limits results in the heat pump being switched off by the internal control and safety devices.
0020154078_03 EnvirosorbInstallation instructions 7
3 System overview
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-15;22]
[-15;45]
[46;22]
[46;58]
[35;60]
[28;60]
[2;60]
[-10;55]
1
2
[28;22]
[35;22]
A
B
60
50
70
40
30
20
10
0
-20 -10 0 10 20 30 40 50
[-20;22]
[-20;43]
[46;22]
[46;58]
[35;63]
[28;63]
[2;63]
[-10;55]
1
2
[28;22]
[35;22]
A
B
e
1 3 12161719
24
1521
14
11
4
23
20222
5 13 8 9
6
7
10
A
B
18
3.2.3.1 Application limits in heating mode (Envirosorb35)
1 Heating mode application
limits
2 Hot water generation
application limits
A Water temperature B Air temperature
3.2.3.2 Application limits in heating mode (Envirosorb38, Envirosorb311, Envirosorb
15)

3.3.2 Indirect connection to a heating installation via a hydraulic module

3.4 System diagram (Envirosorb35)

3
1 Heating mode application
limits
2 Hot water generation
application limits

3.3 Permitted hydraulic configurations

3.3.1 Direct connection to a heating installation

8 Installation instructions Envirosorb0020154078_03
A Water temperature B Air temperature
1 Fan 2 Air inlet temperature
sensor
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex­changer
5 4-way valve 6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow rate sensor
8 Purging valve 9 Flow heating circuit tem-
perature sensor
10 Drain valve 11 Plate heat exchanger 12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
14 High-pressure pressure
switch in the coolant cir­cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor 18 Filter 19 Liquid separator 20 Electronic expansion valve 21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the coolant circuit
23 Filter 24 Fluid collector A Heating return B Heating flow
pressure range of the coolant circuit
Overview of the equipment 4
e
1 3 12161719
25
23
1521
14
11
4
24
20222
5 13 8 9
6
7
10
A
B
18
1
1

3.5 System diagram (Envirosorb38, Envirosorb311, Envirosorb315)

1 Fan 2 Air inlet temperature
sensor
3 Ribbed pipe heat ex-
changer
4 Temperature sensor of
the ribbed pipe heat ex­changer
5 4-way valve 6 Return heating circuit
temperature sensor
7 High-efficiency pump with
flow sensor
8 Purging valve 9 Flow heating circuit tem-
perature sensor
10 Drain valve 11 Plate heat exchanger 12 Temperature sensor after
the plate heat exchanger
13 Service valve for the high-
pressure range of the coolant circuit
14 High-pressure pressure
switch in the coolant cir­cuit
15 High-pressure sensor in
the coolant circuit
16 Compressor outlet temper-
ature sensor
17 Rotary piston compressor 18 Filter 19 Liquid separator 20 Electronic expansion valve 21 Compressor inlet temper-
ature sensor
22 Service valve for the low-
pressure range of the coolant circuit
23 Flow rate limiter (cooling
mode) on Genia Air 8/1 only
24 Filter 25 Gas buffer A Heating return B Heating flow

4 Overview of the equipment

4.1 Type designation and serial number

The type designation and serial number are on the identifica­tion plate (1).

4.2 Information on the identification plate

Information on the identi­fication plate
Serial no. Unique unit identification number
P max Maximum rated power
I Max. operating current
I max Maximum start-up current
R410A Coolant type and fill quantity
PSR_LP PSR_HP
PSHmin PSHmax
COP (Ax/Wxx) Output figure (coefficient of
(Ax/Wxx)
Volt Compressor, pump and control-
Hz Power frequency
IP Protection class
Meaning
Min. and max. operating pres­sure in the coolant circuit
Minimum and maximum operat­ing pressure in the heating circuit
performance) at an air inlet temperature of xx °C and a heating flow temperature of xx °C
Heating output at an air inlet temperature of xx °C and a heating flow temperature of xx °C
ler mains voltage
0020154078_03 EnvirosorbInstallation instructions 9

5 Assembly and installation

13mm
1
2
3
4
B
A
D
E
C
5 Assembly and installation

5.1 Preparing for fitting and installation

5.1.1 Delivery, transport and positioning

5.1.1.1 Transporting the product
During transport, do not tilt the heat pump
by any more than the maximum angle of 45°.
1. Use the transportation belt to carry the product to the final installation site.
2. Only lift the product from the back and side where the hydraulic connections are located.
3. When transporting the product using a hand truck, se­cure the product using a belt.
4. In order to avoid scratches and damage, protect the sides of the product that come into contact with the hand truck.
5.1.1.2 Unpacking the product
Warning. Risk of injury from lifting a heavy weight.
Lifting weights that are too heavy may cause injury to the spine, for example.
When transporting the product, two
people should lift it.
Observe the product weight stated in the
technical data.
When transporting heavy loads, observe
the applicable directives and regulations.
1. Remove the accessory (2).
2. Remove the documentation supplied (1).
3. Remove the transport belt (4).
4. Carefully remove the packaging and padding without damaging the product (3).
5. Remove the screws from the pallet at the front and rear of the product.
Caution. Risk of material damage due to incorrect
transportation.
Regardless of the mode of transport, the heat pump must never be tilted by more than 45°. Otherwise, this may lead to malfunctions in the coolant circuit during subsequent opera­tion. In the worst case scenario, this may lead to a fault in the whole system.
10 Installation instructions Envirosorb0020154078_03
5.1.1.3 Checking the scope of delivery
120
120
740
980
360
800*
386
11
Envirosorb 5
3
162
162
778
1103
415
942*
437
11
Envirosorb 8
3
Envirosorb 11
3
Check the contents of the packaging units
Quant­ity
1 Condensate discharge
1 Bag with seals
4 Vibration-isolating feet
1 Purge hose
5.1.2 Complying with clearances and installation
5.1.2.1 Unit dimensions and connection
Description
clearances
dimensions
Assembly and installation 5
* Size increases by 45 mm
when using the vibration dampers supplied.
* Size increases by 45 mm
when using the vibration dampers supplied.
0020154078_03 EnvirosorbInstallation instructions 11
5 Assembly and installation
162
162
778
1103
415
1340*
437
11
Envirosorb 15
3
C
B
D
A
A
E
5.1.2.2 Installation clearance
* Size increases by 45 mm
when using the vibration dampers supplied.
Clearance For heating mode
A > 250 mm
B > 1000 mm
C > 120 mm*
D > 600 mm
E > 300 mm
*Caution: If the minimum clearances are not maintained, the output of the product may be affected.
To guarantee sufficient air flow and to facilitate mainten-
ance work, observe the minimum clearances that are specified above.
Ensure that there is sufficient room to install the hydraulic
lines.
If the product is to be installed in areas where heavy
snow falls, ensure that the snow does not accumulate around the product and that the minimum clearances specified above are observed. If you cannot ensure this, install an additional heat generator in the heating circuit.
12 Installation instructions Envirosorb0020154078_03
5.1.2.3 Selecting the installation site
dB(A)
dB(A)
Observe all valid regulations.Install the product outside the building.Do not install the product:
Near a heat source,Near flammable materials,Near ventilation openings for adjacent buildings,Under deciduous trees.
Note the following points when installing the product:
Prevailing winds,The visual impression on the environment
Avoid places where strong winds blow on the product's
air outlet.
Point the fan away from nearby windows. Install noise
protection if necessary.
Install the product on one of the following supports:
Concrete slab,Steel T-beam,Concrete block,Elevating socket (accessory),Wall bracket (permitted accessory for Envirosorb35,
Envirosorb38 and Envirosorb311).
Do not expose the product to dusty or corrosive air (e.g.
near unsecured streets).
Do not install the product near ventilation shafts.Prepare the routing for the electrical lines.
Assembly and installation 5
Note any noise emissions from the fan and compressor.
0020154078_03 EnvirosorbInstallation instructions 13
5 Assembly and installation
>100mm
B
A
A
C
5.1.2.4 Installing the heat pump
1. Note the safety information in this manual and in the operating instructions before installing the product.
2. Install the product on steel beams, concrete blocks or using a wall holder (accessory).
3. Ensure that no water collects under the product.
4. In order to avoid ice formation, ensure that the ground in front of the product can absorb water well.
5.1.2.5 Preparing the condensate discharge

5.2 Carrying out the installation

5.2.1 Removing the side casing

Danger! Risk of injury due to frozen condensate.
Frozen condensate on paths may cause falls.
Ensure that condensate does not dis-
charge onto paths and that ice cannot build up there.
The condensate is discharged centrally underneath the product.
Prepare the condensate discharge using a drain line or in
a gravel bed.
1. Remove both screws (A).
2. Pull the side casing downwards and then forwards.
Note
Note that the required tool is not included in the scope of delivery.

5.2.2 Aligning the product

1. Only use bolts of a specific length.
14 Installation instructions Envirosorb0020154078_03
Assembly and installation 5
0.75 m min.
1
4
5
6
7
3
2
– Maximum length: 8 mm
2. Align the product horizontally so that condensate can flow.
Note
The product must be installed with the vi­bration-isolating feet supplied. The product is lifted by the vibration-isolating feet, which simplifies the condensate-discharge process and reduces vibrations.
3. Screw in the vibration-damping feet using the concrete foundation.
Note
The concrete foundation must not be joined to the house foundations.

5.3 Hydraulics installation

In heating installations that are equipped primarily with ther­mostatic or electrically controlled valves, a constant and suf­ficient flow through the heat pump must be ensured. Irre­spective of which heating installation is selected, the min­imum volume of circulating heating water (40% of the nom­inal flow, see the technical data table) must be guaranteed.

5.3.1 Carrying out the hydraulics installation

Caution. Risk of damage caused by residue in the
heating flow and return.
Residue from the pipelines, such as welding beads, scale, hemp, putty, rust and coarse dirt, may be deposited in the product and cause malfunctions.
1. Insulate the lines (including those running below ground) with UV-resistant and high-temperature-res­istant insulation between the product and the heating installation.
2. In order to avoid transferring vibrations to the surround­ing buildings, use flexible connection pipes on the product that have a length of at least 0.75 m.
3. When the product is not installed at the highest point in the heating circuit, install additional purging valves in suitable places.
4. Install the following accessories in the heating return.
Installation without decoupling hydraulic module
Drain cockAir separator (if required)Dirt filterAn expansion vessel suitable for the complete hydraulic
installation
Expansion relief valve 0.3 MPa (3 bar)Pressure gauge (recommended)
Maximum length of the heating circuit
When using a hydraulic module without an expansion vessel
Note
If you use glycol, you must collect it at the expansion relief valve to prevent environ­mental pollution.
DN 26 DN 28
50 m 30 m
Flush the heating installation thoroughly
before connecting the product in order to remove any possible residue.
Caution. Risk of material damage due to corrosion.
If plastic pipes that are not diffusion-tight are used in the heating circuit, this may lead to corrosion and deposits in the heating circuit and in the product.
Do not treat the water with corrosion pro-
tection agents if plastic pipes that are not diffusion-tight are used.
Danger! Risk of material damage caused by sol-
dering work.
Carrying out soldering work on lines that have already been installed may damage the seals.
Solder the lines before installing the
product.
1 Connection hose in the
heating flow to the building (on-site)
2 O-ring seal 3 Covering cap 4 Heating flow connection
(diameter 1 1/4") to the building
5. Remove the covering caps (3) from the product's hy­draulic connections.
6. Install a dirt filter in the heating circuit return between two stop valves so that the filter can be cleaned regu­larly.
5 Heating return connection
(diameter 1 1/4") to the heat pump
6 Connection hose in the
heating return to the heat pump (on-site)
7 Insulation (on-site)
0020154078_03 EnvirosorbInstallation instructions 15
5 Assembly and installation
B
A
365
Ø25
1
2
3
4
5
7. Install a flexible connection pipe (1) and (6) (to be provided on-site) with an O-ring and a stop valve to each of the connections for the heat pump heating flow and return.
8. Check the connections for tightness.

5.3.2 Connecting the swimming pool (optional)

Danger! Risk of material damage due to a direct
connection to a swimming pool.
If the product is directly connected to a swim­ming pool, damage may be caused by corro­sion.
Do not connect the heat pump heating
circuit directly to a swimming pool.
If you want to connect a swimming pool to the heating
circuit, note the components (expansion vessels, etc.) that are required for the installation.

5.3.3 Connecting the condensate drain pipework

Note
Observe all valid national regulations and rules.
1 Condensate drain pipe 2 Adaptor 3 Cable tie
1. Observe the various installation dimensions for the products.
Product Dimension Value
Envirosorb35 A 70.0 mm
Envirosorb38 – Envirosorb311 – Envirosorb315
2. Pull the heating wire in the condensate pan until the elbow (4).
3. Connect the elbow (4) and adaptor (2) to the seal (5) and secure them both using a cable tie (3).
4. Connect a condensate drain pipe to the elbow.
5. Install the heating wire in the condensate drain pipe (1) in order to prevent the condensate from freezing in the line.
6. Connect the adaptor (2) with the product's floor plate and secure it with a 1/4 rotation.
4 Elbow 5 Seal
B 490.0 mm
A 102.5 mm
B 550.0 mm
16 Installation instructions Envirosorb0020154078_03
Assembly and installation 5
30 mm max.
1
2
X4
X9
EBUS
X7
FLOOR H
X2
21
2
1
7. Make sure that the condensate drain pipe ends in a gravel bed.
Note
The condensate drain pipe must not be longer than 365 mm, otherwise it may freeze over.
8. Route the condensate drain pipework with a downward gradient.

5.4 Carrying out the electrical installation

1 Connecting wires 2 Insulation
Danger! Risk of death from electric shock as a res-
ult of an improper electrical connection!
An improper electrical connection may neg­atively affect the operational safety of the product and result in material damage or per­sonal injury.
The electrical installation must be carried
out by a suitably qualified competent per­son who is responsible for complying with the existing standards and directives.
1. Only strip a maximum of 3 cm from the outer sheathing of the flexible lines.
2. Secure the conductors in the connection terminals.

5.4.1 Establishing the power supply

The external mains connection cable must be earthed and connected with the correct polarity and in accordance with the valid regulations.
Check that the mains connection cable is connected cor-
rectly.
The cables that connect the product to the fuse box must:
Be suitable for fixed installation,Be weatherproof,Be equipped with a wire cross-section that is necessary
for the product performance.
Connect the product using a fixed connection and a parti-
tion with a contact opening of at least 3 mm (e.g. fuses or power switches).
In order to meet the overvoltage category II requirements, further fuse protection may be required.
To meet the overvoltage category III conditions, the parti­tions must ensure a complete separation of the power sup­ply.

5.4.2 Standard tariff

5.4.2.1 230 V connection
1 Mains connection terminal
in the product
2 Partition
Caution. Risk of material damage due to high con-
nected voltage.
At mains voltages greater than 253 V, elec­tronic components may be damaged.
Ensure that the rated voltage of the mains
is 230 V.
Connect the mains connection cable to the product's
power supply connection.
En­virosorb 5
Power supply 1/N/PE
230 V 50 Hz
Fuse 16 A -
type C or D
Recommended cable dimension
3G x
2.5 mm²
To ensure that people are safe, install a separate 30 mA
residual-current-operated circuit-breaker for the heat pump.
Guide the mains connection cable through the product's
cable duct (PEG screwed connection).
En­virosorb
3
8
1/N/PE 230 V 50 Hz
16 A ­type C or D
3G x
2.5 mm²
En­virosorb
3
11
1/N/PE 230 V 50 Hz
20 A ­type C or D
3G x
2.5 mm²
En­virosorb
3
15
1/N/PE 230 V 50 Hz
20 A ­type C or D
3G x
2.5 mm²
3
0020154078_03 EnvirosorbInstallation instructions 17
5 Assembly and installation
X4
X9
EBUS
X7
FLOOR H
3
1
2
123456789101112131415
16
1
2
3
4
ØA
ØA
1
2

5.4.3 Laying the 24 V cabling

1 eBUS connection in the
heat pump (observe the polarity)
2 Limit thermostat connec-
tion (underfloor protective circuit)
3 eBUS connection in the
heat pump control module
1. Feed the cable through the cable duct.
Envirosorb35
Envirosorb38 Envirosorb311 Envirosorb315
Recommended eBUS cable dimen­sion
Recommended cable dimension for eBUS + limit thermostat
2 x 0.75 mm²
4 x 0.75 mm²
2. Connect the eBUS cable to the system controller.
3. If you install a limit thermostat (e.g. 50 °C) in the heat­ing circuit flow, remove the bridge from terminal (2) and connect the limit thermostat to this terminal.

5.4.4 Installing the cable duct

Caution. Risk of malfunction due to incorrect rout-
ing of the supply lines.
If you route the supply lines for the power supply and the eBUS line through the same cable duct, the signal will be disrupted.
1 eBUS line and limit ther-
mostat line cable duct
2 Power supply cable duct
1. Measure the diameter of the cable.
2. Drill a hole the same size as the cable diameter in the cable duct.
3. Route the cable through the cable duct.
4. Tighten the cable duct with two open-end spanners.
Route the supply lines for the power sup-
ply and the eBUS line through various cable ducts in the product.
18 Installation instructions Envirosorb0020154078_03

5.5 Connection diagrams

X8
X1
X6
X4
X7
X60DA
X14
X700
X16
X11
F1
X1
X15
X13
X26
X23
X21
X22
X30 X25
X24
X25
X5
X10CA
X9
X2
RL1
X3
15
16
17
12
18
19
20
21
22
23
24
25
11
9
8
7
6
5
4
3
1
2
13
14
10

5.5.1 Connection diagram

Assembly and installation 5
1 Temperature sensor of the ribbed pipe heat exchanger 2 Temperature sensor after the plate heat exchanger 3 Coolant circuit pressure switch 4 Compressor inlet temperature sensor 5 Compressor outlet temperature sensor
0020154078_03 EnvirosorbInstallation instructions 19
6 Coolant circuit temperature sensor 7 Heat pump heating flow temperature sensor 8 Heat pump heating return temperature sensor 9 Air inlet temperature sensor 10 Electronic expansion valve
5 Assembly and installation
11 Main PCB 12 Coding resistance 13 Diagnosis software connection 14 Fan 1 15 Fan 2 (with 15 kW only) 16 Fan PCB 17 Crankcase heating 18 Drain pan electrical heating rod
19 LED status display 20 Heating circuit high-efficiency pump with flow sensor 21 4-way valve 22 PCB installation 23 Rotary piston compressor 24 Inverter box 25 Temperature sensor for ribbed pipe heat exchanger
20 Installation instructions Envirosorb0020154078_03
Start-up 6
A
B
10mm
2
1
3
4

6 Start-up

6.1 Run the start-up

1. Before starting up the product, read through the operat­ing instructions.
2. Check that the electrical partition is installed.
3. Check that the hydraulic and electric connections are correctly designed.
4. Check that a dirt filter is installed in the heat pump re­turn.
5. Check whether an expansion relief valve, an expansion vessel and a pressure gauge are installed.
6. Check the leak-tightness of the connections.
7. Open all the heating circuit valves.

6.2 Filling the heating circuit

Note
We recommend using ethylene glycol with corro­sion-inhibiting additives.
If no frost protection has been poured in, the product will not be protected in the event of a power cut when there is frost.
To purge the heating circuit, open the purging valve by a
1/4 rotation (B) using an open-end spanner.
Increase the operating pressure in the heat pump heat-
ing circuit. – Operating pressure: 0.15 … 0.2 MPa (1.50
… 2.0 bar)
Note
The pressure level may fall in the first month following start-up. It may also vary depending on the outside temperature.
Conditions: If you are using glycol
The glycol must not escape into the outflow or the envir-
onment.
Prepare a mixture with suitable glycol (max. 50% ethyl-
ene glycol) in order to protect the heat pump against frost according to the regional minimum temperatures.
Note
If no frost protection has been poured in, the product will not be protected in the event of a power cut when there is frost.
Conditions: SW10 open-end spanner
1 Heating circuit purging
valve
2 Open-end spanner (on-
site)
3 Hose
4 Collecting container (on-
site)
To purge the heating circuit during the filling procedure,
use a filling pump.
Connect one end of the hose (3) to the drain valve.When purging, insert the other end of the hose (3) into
the mixing container (4).
Open the filling valve using an open-end spanner (2).
Use a frost protection tester to ensure the correct
dosage.

6.3 Treating the heating water

Caution. Risk of material damage if the heating
water is treated with unsuitable frost and corrosion protection agents.
Frost and corrosion protection agents may cause changes in the seals, noises during heating and may lead to further damage.
Do not use any unsuitable frost and corro-
sion protection agents.
Mixing additives with the heating water may result in material damage. However, no incompatibility with the units has been detected to date with proper use of the following products.
When using additives, follow the manufacturer's instruc-
tions without exception.
Note
Glow worm accepts no liability with respect to the compatibility of any additive in the rest of the heating system or its effectiveness.
Additives for cleaning measures (subsequent flushing required)
Fernox F3Sentinel X 300Sentinel X 400
Additives intended to remain permanently in the system
– Fernox F1
0020154078_03 EnvirosorbInstallation instructions 21
6 Start-up
Fernox F2Sentinel X 100Sentinel X 200
Additives for frost protection intended to remain permanently in the system
Fernox HP 15 or HP15cSentinel X 500
Inform the operator about the measures required if you
have used these additives.
Inform the operator about the measures required for frost
protection.
Permissible water hardness
Note
Contact the local water supply company for further information on water quality.
Observe all applicable national regulations and technical
standards when treating the filling and supplementary water.
Provided the national regulations and technical standards do not stipulate more stringent requirements, the following applies:
You must treat the heating water in the following cases:
– If the entire filling and supplementary water volume dur-
ing the operating life of the system exceeds three times the nominal volume of the heating installation,
– If the limit values shown in the following tables are not
observed.
Total heating output
kW
< 50
> 50 to 200 2 (200) 1,5 (150) 0,02 (2,0)
1) Of the specific system volume (nominal capacity in litres/heating output; on systems with more than one boiler, the lowest individual heating output must be set). These values only apply up to three times the system volume for filling and supple­mentary water. If three times the system volume is exceeded, the water must be treated in accordance with the specifications from the VDI (softening, desalting, hardness stabilisation or blowing down). This is exactly the same as if the limit values in the table were exceeded
2) On systems with circulation water heaters and for systems with electric heating elements
Permissible salt content
Heating water char­acteristics
Electrical conductivity at 25 °C
Appearance
Total hardness at smallest boiler heating
1)
surface
20 l/kW
mol/m³ (mg/l CaCO)
No require­ment
< 32)(3002))
Unit Low-salt Saline
μS/cm < 100 100 … 1,500
> 20 l/kW < 50 l/kW
mol/m³ (mg/l CaCO)
2 (200) 0,02 (2,0)
Free of sedimentary materi­als
> 50 l/kW
mol/m³ (mg/l CaCO)
Heating water char­acteristics
pH value at 25 °C
Oxygen mg/l < 0.1 < 0.02
Unit Low-salt Saline
8,2 … 10,01)8,2 … 10,0
1)

6.4 Filling the heating installation

Caution. Risk of material damage due to heating
water that is extremely calciferous or cor­rosive or contaminated by chemicals.
Unsuitable tap water damages the seals and diaphragms, blocks components in the product and heating installation through which the water flows and causes noise.
Only fill the heating installation with suit-
able heating water.
Note
If a heat exchanger module is used, the heating circuit must be topped up with heating water.
Conditions: System separation with a heat exchanger module
Connect the filling cock with the heating water supply
using a cold water valve where possible.
Open all radiator valves (thermostatic radiator valves) of
the heating installation.
Open the cold water valve.Slowly open the filling cock.Fill it with water until the required filling pressure is
reached.
Close the cold water valve.Purge all radiators.Then check the filling pressure on the display.Top up with more water if necessary.Close the filling cock.

6.5 Activating the heat pump

1. Ensure the maximum flow temperature setting matches the heating installation.
2. To fully activate the heating installation, observe the installation instructions for the system controller.
3. Switch on the line protection switch in the fuse box which is connected to the heat pump.

6.6 Checking the product's operation

1. Ensure that the external control equipment (thermo­stats, external sensors, etc.) are sending a heating demand to the heat pump. When configuring several areas, test heating circuit by heating circuit and ensure that the appropriate heating circuit gets warmer.
2. Ensure that all heating circuit thermostatic radiator valves are open.
3. If necessary, balance the heat generator.
22 Installation instructions Envirosorb0020154078_03
Start-up 6
"Hhmmm..." (*)
"Ttsheeh...!"
"Eeee..."
“Clink!"
"Chug, chug, chug,..."
"Whirr..." (*)
1
2
3
4
5
6
A
B
0
10
20
30
40
50
60
70
80
5000 1000 1500 2000
C
100
200
300
400
500
600
700
800
90 900
2500
3
2
1
4

6.7 Operating noises

– Operating pressure: 0.15 … 0.2 MPa (1.50
… 2.0 bar)
Open the service valves on the back of the product.Remove the hose and the mixing container.
6.8.1.1 Available pressure in the heat pump heating circuit
1 Envirosorb35 (water tem-
perature 20 °C)
2 Envirosorb38 (water tem-
perature 20 °C)
3 Envirosorb311 (water
temperature 20 °C)
4 Envirosorb315 (water
temperature 20 °C)
A Remaining feed head
(kPa)
B Flow rate (l/h) C Remaining feed head
[mbar]
* Permanent operating
noises
The noises listed do not constitute a fault with the heat pump.
In various operating modes, the noises come from the heat pump (Start, Thawing, Stop).

6.8 Adjusting the heating circuit

6.8.1 Purging the heating circuit

Conditions: SW14 open-end spanner
Connect one end of the hose to the purging valve.In order to collect the residual glycol when purging the
heating circuit, insert the other end of the hose into the mixing container.
Close the stop valves on the back of the product.Increase the pressure in the heating circuit.Open the purging valve with an open-end spanner.Open the lower stop valve on the back of the product.If liquid escapes from the pipe, close the purging valve.Check the pressure in the heating circuit. If necessary,
increase it.
0020154078_03 EnvirosorbInstallation instructions 23

6.8.2 Adjusting the heating circuit flow rate

Caution. Risk of material damage due to frost
If the minimum flow rate is too low, the heat exchanger may become damaged by frost.
Operate the product with a sufficient flow
rate (see table).
The product is designed for operation between the minimum flow rate and maximum flow rate, as specified in the table. If the product is operated with the minimum flow rate, this res­ults in a loss of energy and efficiency. The heating comfort is still guaranteed but the energy savings are reduced.
En­virosorb 5
Minimum flow rate
Maximum flow rate
380 l/h 380 l/h 540 l/h 1,200 l/h
860 l/h 1,400 l/h 1,900 l/h 2,590 l/h
You can read the flow rate directly from the controller. De­pending on the type of liquid in the heating circuit, the flow rate displayed on the controller may be exaggerated.
Example: If you use a 30% mixture of propylene glycol and the liquid temperature is 5 °C, you must subtract 400 l/h from the value shown on the display.
Use the following table to compare the various exaggera-
tion flow rate values depending on liquid type.
– Applies for: Envirosorb35,
3
En­virosorb 8
3
En­virosorb 11
3
En­virosorb 15
3

7 Maintenance

C
C
B
A
Envirosorb38, Envirosorb311
Flow rate increase (l/h) Temper-
ature 5 °C
Water 0 0 0
60% alcohol 0 0 0
Liquid type
30% propylene glycol
50% propylene glycol
30% ethylene glycol
50% ethylene glycol
400 240 120
650 500 400
120 0 0
400 140 50
– Applies for: Envirosorb315
Flow rate increase (l/h) Temper-
ature 5 °C
Water 0 0 0
60% alcohol 0 0 0
Liquid type
30% propylene glycol
50% propylene glycol
30% ethylene glycol
50% ethylene glycol
600 440 280
1050 740 580
520 350 300
880 680 540
Note
Insufficient purging may lead to deviations in the flow rate.
Temper­ature 15 °C
Temper­ature 15 °C

6.9 Installing the side cladding

Temper­ature 25 °C
Temper­ature 25 °C
Install the side cladding.

6.10 Instructing the operator

1. Explain the how the system operates to the operator.
2. Draw particular attention to the safety information, which the operator must follow.
3. Make the operator aware of the need for regular main­tenance (maintenance contract).
4. Explain to the operator how to check the system's water volume/filling pressure.
7 Maintenance
If you cannot reach the minimum flow rate, install an ad-
ditional pump.
If you cannot reach the recommended flow rate, adjust
the heating circuit pressure on the controller and, if ne­cessary, use a bypass valve (item 50).

7.1 Observing maintenance intervals

1. Only carry out maintenance work if you are a competent person.
2. Carry out annual maintenance.

7.2 Preparing for maintenance

7.2.1 Procuring spare parts

The original components of the product were also certified as part of the CE declaration of conformity. Information about available original spare parts is available by contacting the contact address provided on the reverse of this document.
If you require spare parts for maintenance or repair work,
use only original spare parts.
24 Installation instructions Envirosorb0020154078_03
Maintenance 7
3
4
5
3.
6.
5.
1
2

7.3 Instructions before carrying out maintenance work

Observe the basic safety rules before carrying out mainten­ance work or installing spare parts.
Danger! Risk of injury due to unauthorised access
to the coolant circuit.
Escaping coolant may cause freezing if the exit point is touched.
Only carry out work on the coolant circuit if
you have been trained to do so and if you have the required protective clothing.
Avoid skin and eye contact with the
coolant.
Switch the system off.Disconnect the system from the power supply.Where necessary, disconnect the heating circuit from the
product by using the stop valves.
If you have to replace parts on the heating circuit, you
must first drain the product.
When working on the product, protect all electric com-
ponents from spray water.

7.5 Cleaning the product

7.5.1 Cleaning the front

Warning. Risk of injury due to sharp-edged casing.
The product's casing sections have sharp edges.
Wear gloves when installing or dismant-
ling the product's casing sections.

7.4 Yearly maintenance

Check that the safety devices are functioning properly.Check the heating circuit's fill pressure.Ensure that there are no traces of rust or oil on the
coolant circuit components.
Ensure that the product components are neither worn nor
defective.
Check that all wires sit securely in the connectors.Check the product's earthing.Check the heating pump's flow temperature and the set-
tings.
Remove any dust from the electronics box and the in-
verter box.
Clean the ribbed pipe heat exchanger and ensure that air
circulates between the fins and around the product.
Check that the fan rotates freely.Check that condensate can escape freely from the heat
pump by removing the adaptor underneath the heat pump.
Clean the product as described in the operating instruc-
tions.
Check that the vibration dampers are correctly seated on
the coolant lines.
1. Remove the side casing. (Page 14)
2. Remove both screws (1).
3. Lift off the cover.
4. Remove both screws (2) on the right front casing.
5. Remove the right front casing.
6. Lift the louvred grill (3) upwards.
7. Remover the fan grill casing (4).
8. Remove the nut (5) from the fan.
9. Remove the fan.
10. Clean the product and the ribbed pipe heat exchanger.

7.5.2 Cleaning the back

Warning. Risk of injury due to sharp-edged casing.
The product's casing sections have sharp edges.
Wear gloves when installing or dismant-
ling the product's casing sections.
0020154078_03 EnvirosorbInstallation instructions 25

8 Troubleshooting

1
2
3
10mm
2
1
Note
If necessary, you can drain the heating installation using this drain cock by opening the stop valves on the back of the heat pump.

7.7 Checking the product's status codes

You can check the product's status codes at any time to see which operating condition the heat pump is in. These codes can be read on the system's control module.
The status codes are described in the table in the appendix.

7.8 Checking the electrical installation

Check the electrical installation and take all relevant dir-
ectives into account.
Checking the cable
If the product's mains power cable is damaged, then, in order to avoid danger, only the manufacturer, the Customer Ser­vice team or a similarly qualified person should replace the mains power cable.
To replace the mains power cable, see Carrying out the
electrical installation (Page 17).
1. Remove the side casing. (Page 14)
2. Remove both screws (1).
3. Lift off the cover.
4. Remove the four screws (2) and remove the mesh (3).
5. Clean the product.

7.6 Draining the product

Conditions: SW10 open-end spanner
Disconnect the product from the power supply.
1 Heating circuit drain cock 2 Drain hose
1. Close the stop valves on the back of the heat pump.
2. To drain the heating circuit, connect a hose to the drain cock or place a vessel underneath the drain cock.
3. Open the drain cock with an open-end spanner.

7.9 Start-up following maintenance

1. After the maintenance work has been completed, start up the product – see Start-up (Page 21).
2. If you have carried out work on load-bearing parts, check that they are securely fitted.
3. When you have completed work on the product, carry out an operational and safety test.
8 Troubleshooting

8.1 Troubleshooting

You should carry out the following tests before introducing additional steps:
Make absolutely sure that the power supply was not cut
and that the product is correctly connected.
Ensure that the service valves are open.Check that all external controllers are correctly connec-
ted.

8.2 Fault codes

The fault codes are described in a table in the Appendix. Fault codes (Page 36) In the event of a fault, a fault code number is shown in the
controller's display.
Carry out all necessary repairs.Switch the product on/off using the partition.
26 Installation instructions Envirosorb0020154078_03

9 Decommissioning

9.1 Temporary decommissioning

1. Switch the product off.
2. Disconnect the product from the power supply.

9.2 Permanently decommissioning

1. Switch the product off.
2. Disconnect the product from the power supply.
3. Drain the product. (Page 26)
4. Dispose of or recycle the product and its components.

10 Customer service

For contact details for our customer service department, you can write to the address that is provided on the back page, or you can visit www.glow-worm.co.uk.

11 Disposal

Decommissioning 9

11.1 Recycling and disposal

The competent person who installed your product is re-
sponsible for the disposal of the packaging.
If the product or any batteries that it contains are marked with this symbol, they contain substances hazardous to human health and to the environment.
In this case, do not dispose of the product and any bat-
teries that it contains with your normal household waste.
Instead, bring the product and any batteries to a collec-
tion centre for batteries and electrical or electronic appli­ances.

11.2 Arranging disposal of coolant

Warning. Risk of damage to the environment.
This heat pump contains R 410 A coolant. The coolant must not be allowed to escape into the atmosphere. R 410 A is a fluorinated greenhouse gas covered by the Kyoto Pro­tocol, with a GWP of 1725 (GWP = Global Warming Potential).
Before the product is disposed of, have
the coolant which it contains completely drained into a suitable vessel so that it can then be recycled or disposed of in accordance with regulations.
The competent person who installed the heat pump must dispose of the coolant.
Personnel who are approved for energy recovery must have the relevant certification that corresponds to the valid regula­tions.
0020154078_03 EnvirosorbInstallation instructions 27

Appendix

PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
3
Appendix

A Heat pump schematic

A.1 Heat pump schematic drawing (Envirosorb35)

1 Flow heating circuit temperature sensor 2 Return heating circuit temperature sensor 3 High-efficiency pump with flow sensor 4 Expansion vessel 5 Drain valve 6 Purging valve 7 Fan 8 Air inlet temperature sensor 9 Ribbed pipe heat exchanger 10 Temperature sensor of the ribbed pipe heat exchanger 11 4-way valve 12 Plate heat exchanger 13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit 16 High-pressure sensor in the coolant circuit 17 Compressor outlet temperature sensor 18 Rotary piston compressor 19 Filter 20 Liquid separator 21 Electronic expansion valve 22 Compressor inlet temperature sensor 23 Service valve for the low-pressure range of the coolant
circuit
24 Filter 25 Fluid collector
28 Installation instructions Envirosorb0020154078_03

A.2 Heat pump schematic drawing (Envirosorb38)

PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
26
3
Appendix
1 Flow heating circuit temperature sensor 2 Return heating circuit temperature sensor 3 High-efficiency pump with flow sensor 4 Expansion vessel 5 Drain valve 6 Purging valve 7 Fan 8 Air inlet temperature sensor 9 Ribbed pipe heat exchanger 10 Temperature sensor of the ribbed pipe heat exchanger 11 4-way valve 12 Plate heat exchanger 13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit 16 High-pressure sensor in the coolant circuit 17 Compressor outlet temperature sensor 18 Rotary piston compressor 19 Filter 20 Liquid separator 21 Electronic expansion valve 22 Compressor inlet temperature sensor 23 Service valve for the low-pressure range of the coolant
circuit
24 Filter 25 Gas buffer 26 Flow rate limiter (cooling mode)
0020154078_03 EnvirosorbInstallation instructions 29
Appendix
PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
4
5
13
19
21
24
10
25
11
20+
2
3

A.3 Heat pump schematic drawing (Envirosorb311)

1 Flow heating circuit temperature sensor 2 Return heating circuit temperature sensor 3 High-efficiency pump with flow sensor 4 Expansion vessel 5 Drain valve 6 Purging valve 7 Fan 8 Air inlet temperature sensor 9 Ribbed pipe heat exchanger 10 Temperature sensor of the ribbed pipe heat exchanger 11 4-way valve 12 Plate heat exchanger 13 Temperature sensor after the plate heat exchanger
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit 16 High-pressure sensor in the coolant circuit 17 Compressor outlet temperature sensor 18 Rotary piston compressor 19 Filter 20 Liquid separator 21 Electronic expansion valve 22 Compressor inlet temperature sensor 23 Service valve for the low-pressure range of the coolant
circuit
24 Filter 25 Gas buffer
30 Installation instructions Envirosorb0020154078_03

A.4 Heat pump schematic drawing (Envirosorb315)

PZHH
-
TI
-
TCE
TI
-
TI
-
PT
-
TI
-
TI
-
TI
-
TI
-
7
9
8
23
22
18
15
16
17
14
12
6
1
3
4
5
13
19
21
24
10
25
11
20+
2
Appendix
1 Flow heating circuit temperature sensor 2 Return heating circuit temperature sensor 3 High-efficiency pump with flow sensor 4 Expansion vessel 5 Drain valve 6 Purging valve 7 Fan 8 Air inlet temperature sensor 9 Ribbed pipe heat exchanger 10 Temperature sensor of the ribbed pipe heat exchanger 11 4-way valve 12 Plate heat exchanger 13 Temperature sensor after the plate heat exchanger

B Heat pump setting parameters

Note
If repairs are carried out on the heat pump electronics (e.g. replacing the PCB), you must reset the parameters.
14 Service valve for the high-pressure range of the coolant
circuit
15 High-pressure pressure switch in the coolant circuit 16 High-pressure sensor in the coolant circuit 17 Compressor outlet temperature sensor 18 Rotary piston compressor 19 Filter 20 Liquid separator 21 Electronic expansion valve 22 Compressor inlet temperature sensor 23 Service valve for the low-pressure range of the coolant
circuit
24 Filter 25 Gas buffer
0020154078_03 EnvirosorbInstallation instructions 31
Appendix
Parameter Explanation Default
setting
Language Select the required language here. 02 English 01 Deutsch
Contact details
Max. remain­ing heating circuit feed head
Max. remain­ing hot water feed head
As a competent person, you can enter your telephone num­ber here. The end customer can read this number in the menu Information.
Limiting the remaining heating circuit feed head. If the value is reduced, the pump speed is reduced as far as necessary in order to prevent the remaining feed head from being exceeded.
Limiting the remaining hot water circuit feed head. If the value is reduced, the pump speed is reduced as far as ne­cessary in order to prevent the remaining feed head from being exceeded.
Maximum value
Maximum value
Adjustment range
02 English 03 Français 04 Italiano 05 Dansk 07 Castellano 08 Türkçe 09 Magyar 11 Українська 15 Svenska 16 Norsk 18 Čeština 19 Hrvatski 20 Slovenčina 22 Slovenščina
100 mbar
100 mbar
Own setting

C Technical data

Note
The following performance data is only applicable to new products with clean heat exchangers.
Technical data – General
Heat pump type
Flow/return heating con­nections, boiler side
Product dimensions, width
Product dimensions, height
Product dimensions, depth
Net weight
Hydraulic lines material
Hydraulic connections material
Hydraulic seals material
Plate heat exchanger ma­terial
Pump casing material
Pollution rating
Envirosorb35 Envirosorb38 Envirosorb
11-1 ph
Monoblock
air/water heat
pump
1 1/4" 1 1/4" 1 1/4" 1 1/4"
980 mm 1,103 mm 1,103 mm 1,103 mm
800 mm 942 mm 942 mm 1,340 mm
360 mm 415 mm 415 mm 415 mm
90 kg 106 kg 126 kg 165 kg
Copper Copper Copper Copper
Brass Brass Brass Brass
EPDM EPDM EPDM EPDM
AISI 304
stainless steel
Painted cast
iron
2 2 2 2
Monoblock
air/water heat
pump
AISI 304
stainless steel
Painted cast
iron
Monoblock
air/water heat
pump
AISI 304
stainless steel
Painted cast
iron
Envirosorb
3
Monoblock
air/water heat
stainless steel
Painted cast
15-1 ph
AISI 304
3
pump
iron
32 Installation instructions Envirosorb0020154078_03
Appendix
Electric connection
Fuse type
Inverter controller fuse
Level of protection
Maximum start-up cur­rent
Maximum current con­sumption
Pump power consump­tion
Fan power consumption
Electrical classification
Overvoltage category
Fan rotational speed
Sound power level for A7W35 according to EN 12102 and EN ISO 9614-1
Sound power level for A7W45 according to EN 12102 and EN ISO 9614-1
Sound power level for A7W55 according to EN 12102 and EN ISO 9614-1
Maximum cylinder tem­perature
Minimum air temperature (heating and cylinder charging)
Maximum air temperature (heating)
Maximum air temperature (hot water generation)
Max. air flow
Envirosorb35 Envirosorb38 Envirosorb
11-1 ph
3
Envirosorb
15-1 ph
230 V/50 Hz 230 V/50 Hz 230 V/50 Hz 230 V/50 Hz
T4A T4A T4A T4A
HRC 20 A 550VHRC 20 A 550VHRC 32 A 550VHRC 32 A 550
V
IP 25 IP 25 IP 25 IP 25
16 A 16 A 20 A 25 A
16 A 16 A 20 A 25 A
15 … 70 W 15 … 70 W 15 … 70 W 6 … 87 W
15 … 42 W 15 … 42 W 15 … 76 W 15 … 76 W
Note
2 x
I I I I
II II II II
550 rpm 550 rpm 675 rpm 600 rpm
58 dB(A) 60 dB(A) 65 dB(A) 65 dB(A)
59 dB(A) 60 dB(A) 65 dB(A) 65 dB(A)
61 dB(A) 61 dB(A) 66 dB(A) 66 dB(A)
60 63 63 63
15 20 20 20
28 28 28 28
46 46 46 46
2,000 m³/h 2,700 m³/h 3,400 m³/h 5,500 m³/h
3
Technical data – Heating circuit
Envirosorb35 Envirosorb38 Envirosorb
11-1 ph
Minimum operating pres­sure
Maximum operating pres­sure
Heating circuit water con-
0.1 MPa
(1.0 bar)
0.3 MPa (3.0 bar)
0.1 MPa (1.0 bar)
0.3 MPa (3.0 bar)
0.1 MPa (1.0 bar)
0.3 MPa (3.0 bar)
1.1 l 1.6 l 2.1 l 2.7 l
tents in the heat pump
Minimum heating circuit
17 l 21 l 35 l 60 l
water contents
Min. volume flow rate
Nominal volume flow
380 l/h 380 l/h 540 l/h 1,200 l/h
860 l/h 1,400 l/h 1,900 l/h 2,590 l/h
rate, max. volume flow rate
Hydraulic pressure differ-
640 mbar 450 mbar 300 mbar 370 mbar
ence
Expansion vessel capa-
2.0 l 2.0 l 2.0 l 2.0 l
city
0020154078_03 EnvirosorbInstallation instructions 33
3
Envirosorb
15-1 ph
0.1 MPa (1.0 bar)
0.3 MPa (3.0 bar)
3
Appendix
Technical data – Coolant circuit
Envirosorb35 Envirosorb38 Envirosorb
Coolant type
Coolant contents
Maximum permissible operating overpressure
Compressor type
Oil type
Coolant circuit control system
Technical data – Heat pump system performance data
Heating output A-7/W35
A-7/W35 output figure/EN 14511 coefficient of per­formance
A7/W35 heating output
A7/W35 output figure/EN 14511 coefficient of per­formance
Power consumption ef­fective at A7/W35
Input current at A7/W35
A7/W45 heating output
A7/W45 output figure/EN 14511 coefficient of per­formance
Power consumption ef­fective at A7/W45
Input current at A7/W45
A7/W55 heating output
A7/W55 output figure/EN 14511 coefficient of per­formance
Power consumption ef­fective at A7/W55
Input current at A7/W55
R410A R410A R410A R410A
1.80 kg 1.95 kg 3.53 kg 4.40 kg
4.15 MPa
(41.50 bar)
Rotary piston Rotary piston Rotary piston Rotary piston
Specific
polyvinyl ether
(PVE)
Electronic Electronic Electronic Electronic
Envirosorb35 Envirosorb38 Envirosorb
4.90 kW 6.20 kW 7.60 kW 11.80 kW
2.40 2.40 2.40 2.60
4.70 kW 7.60 kW 10.60 kW 14.60 kW
4.70 4.50 4.30 4.50
1.10 kW 1.69 kW 2.47 kW 3.40 kW
4.80 A 8.28 A 12.04 A 14.80 A
4.40 kW 7.20 kW 10.20 kW 13.40 kW
3.40 3.50 3.35 3.40
1.30 kW 2.06 kW 3.05 kW 4.10 kW
5.70 A 9.61 A 14.13 A 17.80 A
4.20 kW 6.60 kW 9.40 kW 11.20 kW
2.70 2.70 2.60 2.30
1.60 kW 2.44 kW 3.61 kW 5.00 kW
7.00 A 10.86 A 16.49 A 21.70 A
4.15 MPa
(41.50 bar)
Specific
polyvinyl ether
(PVE)
4.15 MPa
(41.50 bar)
polyvinyl ether
11-1 ph
Specific
(PVE)
11-1 ph
Envirosorb
3
4.15 MPa
(41.50 bar)
polyvinyl ether
Envirosorb
3
15-1 ph
3
Specific
(PVE)
3
15-1 ph

D Status codes

Code Meaning
0 Product in standby mode
1 Heating mode: Pump pre-run
2 Pump pre-run OK
3 Water temperature/setting compatibility test
4 Heating mode start phase activated
5 Heating mode: Pump pre-run to max. speed
6 Heating mode: Fan pre-run
7 Heating mode: Move 4-way valve into position
8 Heating mode: Move electronic expansion valve into
position
34 Installation instructions Envirosorb0020154078_03
Code Meaning
9 Heating mode: Start command for the compressor
10 Product in heating mode
11 Product in hot water handling mode
12 Heating mode: Water temperature exceeded
13 Hot water handling mode: Water temperature exceeded
14 Heating mode: Pump overrun
15 Thawing mode: Pump pre-run
16 Product in thawing mode
17 Thawing mode: Pump overrun
18 Pump operated by remote control (auxiliary)
19 Compressor's oil temperature too low for operation
30 Cooling mode: Pump pre-run
31 Cooling mode: Pump pre-run OK
32 Water temperature/setting compatibility test in cooling
mode 33 Cooling mode start phase activated
34 Pump pre-run to max. speed
35 Fan pre-run
36 Cooling mode: 4-way valve into position
37 Cooling mode: Electronic expansion valve into position
38 Cooling mode: Start command for the compressor in
cooling mode 39 Heat pump in cooling mode
40 Cooling mode: Water temperature exceeded
41 Cooling mode: Pump overrun
50 Fault: Pressure compensation
51 Fault: Pressure regulator
52 Pressure envelope fault detected
53 Fault in the compressor starter
54 Loss of "special tariff" power source
55 Coolant circuit pressure not in the permissible range/high
pressure : low pressure ratio too low 56 Coolant circuit pressure not in the permissible
range/condensation rate too low 57 Coolant circuit pressure not in the permissible
range/evaporation rate too high 58 Coolant circuit pressure not in the permissible
range/condensation rate too high 59 Coolant circuit pressure too low
60 Compressor outlet overheated
61 Fault: Compressor inlet temperature
62 Fault: Compressor outlet temperature
63 Fault: Plate heat exchanger temperature sensor
64 Fault: Fin-type heat exchanger temperature sensor
65 Fault: Outside temperature sensor
66 Fault: Heating flow temperature sensor
67 Fault: Heating return temperature sensor
68 Fault: Coolant circuit high-pressure sensor
69 Fault: Inverter low-voltage bus
70 Fault: Inverter switched off
71 Fault: Inverter overheated
Appendix
0020154078_03 EnvirosorbInstallation instructions 35
Appendix
Code Meaning
72 Fault: Inverter overcurrent
73 Fault: Inverter voltage too low
74 Fault: Inverter voltage too high
75 Internal inverter fault message
76 Fault: Inverter heat sensor
77 Fault: Inverter overload
78 Fault: Fan Management Unit PCB
79 eBUS communication error
80 Fault: Flow rate
81 Communication error with inverter
82 Fault: Maximum compressor current
84 Fault: Electronic expansion valve
85 Fan speed too low
88 Coding resistance fault
89 Fault: Underfloor protective circuit
90 Fault: 4-way valve
99 Fault with the product: Take note of the fault codes.

E Overview of fault codes

Code Meaning Cause
37 The fan speed is too low. Obstruction in the product's air guiding
Fan motor not connected or faultyPower supply to the fan PCB is faulty
42 Fault: Coding resistance The product's coding resistance is missing or is faulty
Coding resistance value outside the permissible range
86 Safety thermostat for the underfloor heating triggered Underfloor heating temperature too high
Heating circuit flow rate too lowUnderfloor heating circuit is closed
103 Fault: Spare part detection The main PCB that is fitted as a spare part or the inverter does
not match the product 514 Sensor fault: Comp. inlet temp.
517 Sensor fault: Comp. outlet temp.
519 Sensor fault: Return temperature
520 Sensor fault: Flow temperature
526 Sensor fault: Heat exchanger temp. Sensor is faulty or incorrectly connected to the main PCB
532 Building circuit: Flow rate too low – Pump faulty
– Sensor is faulty or incorrectly connected to the main PCB
Check the specific flow rate in forced mode
Between 7000 and 7700 l/h: Alarm
Between 7700 and 8200 l/h: The pump runs dry (no water in
the heating circuit; the heating circuit loses water)
Between 8200 and 8700 l/h: Fault in the electronics
Between 8700 and 9200 l/h: Pump blocked
Between 9200 and 10,000 l/h: No PWM signal (cable faulty
or not connected; fault in the main PCB)
– Pump cabling has not been carried out correctly (PWM and sup-
ply)
Low water pressureDirt filter in the heating circuit return is missing or blockedHeating circuit not fully purgedPressure loss in the heating circuit too high
36 Installation instructions Envirosorb₃ 0020154078_03
Appendix
Code Meaning Cause
536 Compressor outlet temperature too high (depends on
the compressor's operating range)
537 Outlet pressure of the compressor too high – Coolant volume too high or too low
539 Coolant pressure too low – Coolant quantity too low
546 Sensor fault: Pressure sensor in the coolant circuit Faulty cabling
554 Coolant pressure not in operating range – Coolant volume too high or too low
582 EEV fault – Cable insulation faulty
585 Sensor fault: EEV building circuit temp. – Sensor is faulty or incorrectly connected to the main PCB
685 Communication fault: eBUS – The product is not connected to the controller
750 Compressor shut down – Cable insulation faulty
751 Compressor overcurrent Fault in the compressor
752 Fault: Inverter – Inverter casing damaged
753 Connection fault: Inverter not recognised The connection between the main PCB and the inverter box is
754 Fault: Fan PCB – The connection between the main PCB and the fan PCB is dam-
755 Positioning fault: 4-way valve Mechanical or electrical problem. Move the 4-way valve away from
774 Sensor fault: Air inlet temperature – The temperature sensor is faulty or incorrectly connected to the
Coolant quantity too lowSensor is faulty or incorrectly connected to the main PCBPressure drop in the liquid line (pressure loss)Electronic expansion valve faultyHeat exchanger blocked
Incorrect evacuationIncondensable particle in the coolant circuitPressure switch or electrical connection faultyPressure drop in the liquid line (pressure loss)Flow quantity too high (see defined maximum flow rate)Electronic expansion valve faultyInsufficient heat transfer in the heat exchanger
Air flow too lowNo thawingThe resistance heating in the condensate collecting container is
faulty.
4-way valve faultyElectronic expansion valve motor faulty, or connection faulty
Sensor defective
Incondensable particle in the coolant circuitElectronic expansion valve faultyFlow quantity too high (see defined maximum flow rate)Pressure drop in the liquid line (pressure loss)Insufficient heat exchange in the plate heat exchanger or the
ribbed pipe heat exchanger
4-way valve faulty
Connection broken
Polarity inverted
Connection broken
The product's voltage supply is too lowThe ribbed pipe heat exchanger or heat exchanger is dirty
Cooler inverter box is dirtyFaulty voltage supply
damaged or broken
– Inverter box is not switched on
aged or broken.
The fan is faultyThe fan PCB is faultyThe power supply to the fan PCB is faultyThe heat pump was switched on before the system's control sys-
tem (start up the control system before the heat pump or switch on both components at the same time)
the controller. When moving it, check that the coil voltage is correct.
main PCB.
0020154078_03 EnvirosorbInstallation instructions 37
Appendix
For further technical information, please call 0844 6933 133.
38 Installation instructions Envirosorb0020154078_03

Index

B
Back
Cleaning.........................................................................25
C
Cable duct ...........................................................................18
CE label.................................................................................4
Connection diagram ............................................................ 19
D
Documents ............................................................................ 7
E
Electrical diagram................................................................ 19
Electricity ...............................................................................3
F
Filling ...................................................................................22
Front
Cleaning.........................................................................25
H
Heating water
Preparing .......................................................................21
Hot water temperature...........................................................3
I
Identification plate .................................................................9
M
Manual
Applicability...................................................................... 7
P
Product
Unpacking......................................................................10
R
Regulations ...........................................................................4
Risk of scalding ..................................................................... 3
S
Safety devices ..................................................................... 7
Expansion relief valve......................................................3
Expansion vessel.............................................................3
Side casing
Removing.......................................................................14
Spare parts..........................................................................24
T
Terminal connection diagram .............................................. 19
Tool .......................................................................................4
V
Voltage ..................................................................................3
Index
0020154078_03 EnvirosorbInstallation instructions 39
GLOW-WORM
0020154078_03 - 30.04.2014
Nottingham Road, Belper, Derbyshire. DE56 1JT
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
www.glow-worm.co.uk
© These instructions, or parts thereof, are protected by copyright and may be repro­duced or distributed only with the manufacturer's written consent.
The energy you need
Loading...