Glow-worm Envirosorb2 7, Envirosorb2 14, Envirosorb2 12 Installation And Servicing

Page 1
Envirosorb2 7 / 12 / 14
Installation and Servicing
Page 2
Page 3
- 1 -
1 Instructions guidance ................................................................................................................... 3
1.1 Product documentation .......................................................................................3
1.2 Associated documents .......................................................................................3
1.3 Explanation of symbols .......................................................................................3
1.4 Guarantee registration ........................................................................................3
2 Appliance description ................................................................................................................... 3
2.1 Safety devices ....................................................................................................3
2.2 Data label ...........................................................................................................4
2.3 Regulation and statutory requirements .................................................................4
2.4 Concept of operation ...........................................................................................4
2.5 Hydraulic and refrigerant schematic .....................................................................6
3 Safety instructions and regulations ............................................................................................... 7
3.1 Safety instructions ..............................................................................................7
3.2 Regulations .......................................................................................................8
4 Recycling ..................................................................................................................................... 8
4.1 Appliance ...........................................................................................................8
4.2 Packaging ..........................................................................................................8
4.3 Refrigerant .........................................................................................................8
5 Guarantee / Responsibility ........................................................................................................... 9
5.1 Detailed guarantee .............................................................................................9
5.2 Appliance use / manufacturer responsibility .........................................................9
TECHNICAL DATA
6 Envirosorb ................................................................................................................................. 10
INSTALLATION
7 Appliance location ..................................................................................................................... 12
7.1 Heat pump location ...........................................................................................12
7.2 Clearances .......................................................................................................13
7.3 Command unit location......................................................................................13
8 Installing the command unit ........................................................................................................ 14
9 Installing the heat pump ............................................................................................................ 14
9.1 Scope of delivery ..............................................................................................14
9.2 Recommendations before installation ................................................................15
9.3 Dimensions ......................................................................................................15
9.4 Mounting ........................................................................................................16
9.5 Positioning the appliance ..................................................................................17
10 Examples of installation ............................................................................................................. 18
10.1 Installation with hydraulic module, control by control unit ...................................18
10.2 Installation with hydraulic module, DHW tank, control by control unit ...................20
11 Hydraulic connection .................................................................................................................. 22
12 Discharge of condensate ............................................................................................................ 22
TABLE OF CONTENTS
Page 4
- 2 -
13 Electrical connection .................................................................................................................. 22
13.1 Access to main board ........................................................................................23
13.2 Cable passage .................................................................................................23
13.3 Electrical wiring ................................................................................................23
13.4 Wiring diagram .................................................................................................24
14 Commissioning .......................................................................................................................... 28
14.1 Filling the glycol circuit ......................................................................................28
14.2 Activating the heat pump ...................................................................................28
14.3 Activating the options .......................................................................................28
14.4 Heating system test ..........................................................................................28
15 Specifi c adjustment ................................................................................................................... 28
15.1 Adjusting the heating circuit ..............................................................................28
15.2 Settings for the command unit ...........................................................................29
16 User information ........................................................................................................................ 34
MAINTENANCE
17 Trouble-shooting ........................................................................................................................ 35
17.1 Fault diagnosis .................................................................................................35
17.2 Fault codes .......................................................................................................35
18 Servicing ................................................................................................................................... 36
19 Replacement of Parts .................................................................................................................. 36
20 Spare parts ................................................................................................................................ 36
TABLE OF CONTENTS
Page 5
0020117819_01 - 05/11 - Glow-worm
- 3 -
INTRODUCTION
1 Instructions guidance
1.1 Product documentation
The instructions are an integral part of the appliance and must be handed to the user on completion of the installation in order to comply with the current regulation.
Carefully read the manual, to understand all the information to enable safe installation, use and servicing. No liability can be accepted in the event of damage for not complying with the guidance in this instruction manual.
These instructions consist of, Installation, Servicing, Fault Finding and Replacement of Parts. The instructions are an integral part of the appliance and must be handed to the user on completion of the installation.
1.2 Associated documents
- 1 Instructions for user
- Instructions for other system components
1.3 Explanation of symbols
a
DANGER: Risk of injuries.
e
DANGER: Risk of electric shock.
b
ATTENTION: Risk of damage to the appliance or to its surroundings.
i
IMPORTANT: Important information.
1.4 Guarantee registration
Thank you for installing a new Glow-worm appliance in your home. Glow-worm appliances are manufactured to the very highest standard so we are pleased to off er our customers a Comprehensive Guarantee.
This product is guaranteed for 24 months from the date of installation or 30 months from the date of manufacture, whichever is the shorter, for parts and labour.
The second year of guarantee, from the beginning of the 13th month onwards after installation or manufacture, is conditional upon the heat pump having been serviced by a competent person approved at the time by the Health and Safety Executive, in accordance with the manufacturer’s recommendations. We strongly recommend regular servicing of your appliance, but where the condition is not met, any chargeable spare parts or components issued within the applicable guarantee period still benefi t from a 12 month warranty from the date of issue by the manufacturer.
We recommend you complete and return as soon as possible your guarantee registration card (delivered with the hydraulic module). If your guarantee registration card is missing you can obtain a copy or record your registration by telephoning the Glow-worm Customer Service number 01773 828100.
2 Appliance description
2.1 Safety devices
- This appliance is designed for use in heating with an external temperature of between -20°C and 30°C. Outside this range, the heat pump stops.
- A set of security devices based on measuring the temperature within the circuits and the current in the compressor protects it against excess pressure in the refrigerating fl uid.
- A fl ow detector protects the appliance as a whole.
- To prevent stagnation of the refrigerant fl uid when the compressor is stopped, a safety device is activated when the outside temperature lowers. The compressor is then heated by a low electrical current through the motor windings,
- A temperature sensor on exit from the compressor limits the functioning of the heat pump when the temperature measured by this sensor is greater than 100°C. From 117°C, the heat pump stops.
- A temperature sensor on the fi nned heat exchanger and a tachometer on the fan checks that the fan is working.
- A water fl ow sensor ensures the security of the water circulation. If the fl ow is too low (< 420 l/h), the appliance stops and re-starts when the fl ow comes within the normal functioning range (>500l/h).
INTRODUCTION
Page 6
0020117819_01 - 05/11 - Glow-worm
- 4 -
2.2 Data label
The data label certifi es the country where the appliance is intended to be installed.
Data label location:
1
Key 1 Data label
2.3 Regulation and statutory requirements
2.3.1 CE Mark
The CE mark indicates that the appliances described in this manual are in compliance with the following directives:
- European directive n°2004-108 from the European Parliament and Council relative to electromagnetic compatibility
- European directive n°2006-95 from the European Parliament and Council relative to low voltage
- European directive No. 97-23 of the European Parliament and the Council regarding pressure equipment
- European directive No. 2007-1494 of the Commission, dated December 17, 2007, determining, in accordance with Directive No. 2006-842 of the European Parliament and the Council, the label type and the additional requirements as regards the labelling of products and equipment containing certain uorinated greenhouse eff ect gas.
- European directive No. 2006-842 of the European Parliament and the Council of May 17, 2006 on certain fl uorinated greenhouse gasses (OJEU of June 14, 2006)
2.3.2 Local regulations
Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer’s instructions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.
Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.
Visit www.centralheating.co.uk for more information.
2.4 Concept of operation
A heat pump (HP) is a thermodynamic machine which transfers heat from one location to another. To do so, it employs the characteristics of a refrigerant fl uid.
The system is composed of the following circuits:
- The refrigeration circuit which transfers heat to the water circuit following the evaporation, compression, condensation and expansion of the fl uid.
- The heating circuit.
2.4.1 In heating mode
2
1
3 4
5
6
Key 1 Finned heat exchanger 2 Reverse cycle valve 3 Ventilating fan 4 Compressor 5 Pressure regulator 6 Exchanger with plates
INTRODUCTION
Page 7
0020117819_01 - 05/11 - Glow-worm
- 5 -
2.4.2 In defrosting and cooling mode
2
1
3 4
5
6
Key 1 Finned heat exchanger 2 Reverse cycle valve 3 Ventilating fan 4 Compressor 5 Pressure regulator 6 Exchanger with plates
2.4.3 Min. and Max. temperature settings in heating
60
50
70
40
45
30
20
10
0
-20 -10 0 10 20 30
A
B
Key A Water temperature B Air temperature
2.4.4 Min. and Max. temperature settings in cooling
12
14
16
18
20
10
8
6
4
2
0
01020304050
46
A
B
Key A Water temperature B Air temperature
2.4.5 Principle for controlling the heat pump
Control using the Glow Worm control unit. This confi guration is recommended in the case of an installation with the Glow Worm hydraulic unit. The Glow Worm system of active management of the heat pump using dry 12V contacts. The command unit is used only as a confi guration tool.
INTRODUCTION
Page 8
0020117819_01 - 05/11 - Glow-worm
- 6 -
2.5 Hydraulic and refrigerant schematic
9
10
11
12
14
15
16
17
19
20
22
23
21
18
24
1
3
2
4
5
6
7
A
C
13
8
B
Key 1 Fan (1 fan for the 7 kW model, 2 fans for the 12 and 14 kW models) 2 Outside air temperature sensor 3 Finned heat exchanger 4 Finned heat exchanger temperature sensor 5 4-way cycle inversion gate 6 Temperature sensor for compressor suction 7 Silencer 8 Expansion vessel (in this position for the 7 kW model) 9 Automatic purge vent for the heat pump circuit 10 Water fl ow detector for the heat pump circuit 11 Circulator for the heat pump circuit 12 Safety valve for the heat pump circuit 13 Expansion vessel (in this position for the 12 and 14 kW models) 14 Flow temperature sensor for the heat pump
15 Return temperature sensor for the heat pump 16 Draining valve for the heat pump circuit 17 Plate to plate exchanger 18 Pre-expansion temperature sensor 19 Anti-slugging bottle 20 Rotary compressor 21 Liquid tank 22 Silencer 23 Compressor discharge temperature sensor 24 Electronic expansion unit
A Heat pump return B Heat pump fl ow C Evacuation from the safety valve to a container for recovering glycol
water
INTRODUCTION
Page 9
0020117819_01 - 05/11 - Glow-worm
- 7 -
3 Safety instructions and regulations
3.1 Safety instructions
e
Incorrect installation can cause electric shock or appliance damage.
Never disable security devices and do not try to adjust them.
Be sure to consider the following handling techniques and
precautions:
Grip the appliance at its base
Use safety clothing where appropriate, e.g. gloves, safety
footwear.
Ensure safe lifting techniques are used:
Keep back straight.
Avoid twisting at the waist.
Avoid upper body/top heavy bending.
Always grip using the palm of the hand.
Use designated hand holds.
Keep load as close to body as possible.
Always use assistance if required.
Under no circumstances must the user interfere with or adjust
sealed parts.
When assembling the connections, correctly position the seals to avoid any leakage of water.
This appliance contains metal parts (components) and care should be taken when handling and cleaning, with particular regard to edges.
The basic safety instructions must be followed before attempting to maintain or replace spare parts:
Stop the appliance.
Electrically isolate the appliance from the power supply.
Hydraulically isolate the appliance using the isolation valves if
provided.
Should you need to replace hydraulic components, drain the appliance.
Protect all the electrical components from water while working on the appliance.
Use only original spare parts.
Use only new O-rings and gaskets.
After having completed work on water carrying components,
check for their tightness.
When work on the appliance is completed, perform an operational test and check for safety.
R410A Refrigerant
b
Important: any action carried out on the refrigerant circuit must be performed by qualifi ed personnel.
- Use only R410A refrigerant.
The tools used for charging, for measuring pressure, for
creating a vacuum and for the recovery of the fl uid must be compatible with and employed solely for R410A.
Welding is to be carried out with nitrogen and the circuit’s air­tightness is to be tested under pressure, with nitrogen.
Re lling must be e ected during the liquid phase.
In case of leakage, do not add uid: drain the remaining
uid from the circuit and eliminate, in accordance with the applicable regulations.
b
Evacuating refrigerant into the atmosphere is prohibited. The refrigerant must be properly recovered in a container suitable for recycling.
Create a vacuum in the circuit with a maximum pressure of 30 mbar (static pressure).
Bleed the circuit before any welding work.
a
Do not smoke or light fl ames during the emptying and fi lling of the circuit. The gases emitted during the combustion of the refrigerant are fl ammable.
INTRODUCTION
Page 10
0020117819_01 - 05/11 - Glow-worm
- 8 -
3.2 Regulations
3.2.1 Statutory requirements
IMPORTANT
Where no British Standards exists, materials and equipment should be fi t for their purpose and of suitable quality and workmanship.
The installation of this appliance must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
Standards
On installing and commissioning the appliance you must adhere to the technical rules, standards and provisions in eff ect at the time.
Reminder of existing regulatory acts
- EC regulation No. 20372000 from the 29th of June 2000 This European regulation repeals regulation No. 3093/94 and presents the elimination schedules of CFC and HCFC. It also deals with the collection of refrigerants, system leaks, particularly systems containing more than 3 kg of CFC or HCFC, as well as the minimum level of qualifi cation required by the technicians.
- EC regulation No. 0842/2006 from the 17th of May 2006 regarding the containment, use, collection and disposal of the uorinated greenhouse gases, the labelling and elimination of the products and equipment containing these gases, the restriction of use and banning of certain products from the market, as well as the training and certifi cation of personnel and companies operating in the activities targeted by this regulation: refrigeration, air-conditioning, heat pumps and fi re protection systems containing greenhouse gases.
3.2.2 Other regulations
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
The refrigerant used in this appliance is R410a the use of which is strictly controlled by F Gas regulation EN842/2006.
4 Recycling
i
The recycling of the packaging must be carried out by the qualifi ed professional who installed the appliance. The recycling of any refrigerant fl uid must be carried out by a suitably qualifi ed refrigerant engineer.
4.1 Appliance
Most of the appliance is made of recyclable materials.
This symbol indicates that this appliance must not be disposed of with household waste, that it should be selectively collected for energy recovery, reuse or recycling.
Take the appliance to an appropriate collection point for the treatment, evaluation and recycling. The collection point must accept appliances containing refrigerant fl uids for their recovery via recycling either within the elimination centre or by an authorised service provider.
i
By complying with this directive, you will contribute to the preservation of natural resources and the protection of human health.
4.2 Packaging
The competent person who installed the appliance must:
Sort the waste so as to separate those which can be recycled (cardboard, plastics...) from those that cannot.
Dispose of the waste in compliance with regulations in force.
4.3 Refrigerant
a
The appliance contains R410A refrigerant. The refrigerant should only be handled by an approved specialist. Avoid all contact with skin and eyes.
R410A fl uorinated greenhouse gases are contained within a fully sealed system (Kyoto Protocol PES 1975).
Under normal use and conditions, the refrigerant is not dangerous.
Degassing refrigerant fl uid into the atmosphere is prohibited, except when necessary to ensure personal safety.
Prior to disposing of the appliance, the refrigerant must be properly recovered in a container suitable for recycling.
The personnel approved for this recuperation must have an appropriate certifi cation according to the regulations in force.
INTRODUCTION
Page 11
0020117819_01 - 05/11 - Glow-worm
- 9 -
5 Guarantee / Responsibility
5.1 Detailed guarantee
Thank you for installing a new Glow-worm appliance in your home.
Glow-worm appliances are manufactured to the very highest standard so we are pleased to off er our customers a Comprehensive Guarantee.
This product is guaranteed for 24 months from the date of installation or 30 months from the date of manufacture, whichever is the shorter, for parts and labour.
The second year of the parts guarantee, from the beginning of the 13th month onwards after installation or manufacture, is conditional upon the heat pump having been serviced by a competent person approved at the time by the Health and Safety Executive, in accordance with the manufacturer’s recommendations. We strongly recommend regular servicing of your appliance, but where the condition is not met, any chargeable spare parts or components issued within the applicable guarantee period still benefi t from a 12 month warranty from the date of issue by the manufacturer.
5.2 Appliance use / manufacturer responsibility
b
The guarantee detailed above is applicable on the condition that:
- The appliance is installed by a competent person in accordance with installation instructions.
- The appliance is used for normal domestic purposes and in accordance with the manufacturer’s operating and maintenance instructions.
- The appliance is serviced, maintained, by a competent person.
- The repair or replacement of parts during the guarantee period does not have the eff ect of extending the period.
b
The manufacturer has no responsibility whatsoever for any damage resulting from:
- Any defects or damage resulting from incorrect or poor installation, inadequate servicing, or maladjustment.
- Any defects in the system to which the appliance is connected.
- Tout défaut résultant d’une protection antigel non adaptée.
- Any deterioration or maladjustment following changes in the nature or pressure of the water used, or a change in the characteristics of the electrical supply voltage.
For further details, refer to your Terms and Conditions.
a
This appliance is intended to be installed only within the designated countries displayed on the type plate.
This appliance is not designed to be used by persons (including children) with physical, sensory or mental restrictions, or a lack of experience or knowledge. To ensure the safety of these persons, they must seek help from and be guided by persons who are competent to explain the usage of this appliance.
Make sure that children do not play with this appliance.
INTRODUCTION
Page 12
0020117819_01 - 05/11 - Glow-worm
- 10 -
TECHNICAL DATA
i
This technical data is valid for a new appliance with its own heat exchangers.
6 Envirosorb
Description Unit 7 12 14
Min. operating outside temperature (in heating) °C -20 -20 -20
Max. operating outside temperature (in heating) °C 30 30 30
Specifi cations, with radiators
(fl ow : 45°C, return : 40°C, outside dry temperature (wet) 7 (6)°C)
Heating output kW 7.4 12.95 14
Power input kW 2.34 4.3 4.36
Rated electrical current A 10 18.7 19
COP* A7(6) W45-40 3.16 3.01 3.21
Specifi cations, with underfl oor heating
(fl ow : 35°C, return : 30°C, outside dry temperature (wet) : 7 (6)°C)
Heating output kW 7.2 11.9 14.5
Power input kW 1.84 3.04 3.57
Rated electrical current A 8 13.2 15.6
COP* A7(6) W35-30 3.91 3.91 4.06
Refrigerant circuit
Type of refrigerant
Quantity of refrigerant kg 1.81 2.485 3.385
Type of compressor Rotary
Type of oil Polyolester
Type of regulator Electronic
Fan speed rpm 1000 805 1050
Maximum operating pressure (PS)
bar454545
Pa 45 x 10
5
45 x 10
5
45 x 10
5
Heat pump circuit
Max. supply pressure.
bar333
Pa 3 x 10
5
3 x 10
5
3 x 10
5
Min. supply pressure
bar 0.5 0.5 0.5
Pa 50 x 10
3
50 x 10
3
50 x 10
3
Nominal water fl ow rate in heating mode l/h 1200 2100 2500
Flow rate detection threshold l/h 500 500 500
Min. volume of the installation l 28 42 49
Max volume of heat pump circuit, without auxiliary tank, for a water outlet temperature of 35°C
l659595
Minimum fl ow temperature setting (in heating) °C 20 20 20
Maximum fl ow temperature setting (in heating) °C 60 60 60
Volume of water in the heat pump l 1.2 2.3 2.3
TECHNICAL DATA
Page 13
0020117819_01 - 05/11 - Glow-worm
- 11 -
Description Unit 7 12 14
Electrical
Supply voltage/frequency V/Hz 1/N/PE 230V 50Hz
Fuse 15 type B 25 type D 25 type D
Maximum absorbed power (P max) kW 2.7 5.1 5.1
Maximum absorbed current (I max) A 14 23 20
Index of electrical protection IPX4 IPX4 IPX4
Electrical classifi cation 111
Description Unit 7 12 14
Dimensions
Height mm 821 1363 1363
Width mm 908 908 908
Depth mm 326 326 326
Ø Water circuit connections " 1 1 1
Nett total weight kg 71 105 130
Sound power level : overall exterior noise (according to EN 12102 and EN ISO 9614-1)
dBA 64 67 68
* Coeffi cient Of Performance (according to EN 14511) ** Energy Effi ciency Ratio (according to EN 14511)
i
Fluorinated greenhouse gases as identifi ed in the Kyoto protocol, are contained within a fully sealed system.
TECHNICAL DATA
Page 14
0020117819_01 - 05/11 - Glow-worm
- 12 -
Do not place near to stale air extraction fans.
Allow room for electricity cables (high and low voltage).
Explain these requirements to the appliance user.
7.1.2 Discharge of condensates
>100mm
Make allowance for a condensate discharge circuit.
7.1.3 Regulations
Please ensure that all correct permissions have been obtained from the local planning offi ce, prior to siting the appliance.
INSTALLATION
i
All the drawings dimensions are shown in mm.
7 Appliance location
7.1 Heat pump location
7.1.1 Instructions
Before choosing a site for the appliance, carefully read the safety warnings and installation manual.
Ensure there is suffi cient space available for the appliance, taking care that minimum clearances are adhered to ensure that the connections to the water, gas and fl ue can be accessed and inspected (see chapter Clearances).
Observe current regulations.
Install the appliance outside.
Do not install the appliance:
- near a heat source,
- near fl ammable materials,
- near the ventilation points of adjacent buildings
- beneath deciduous trees.
Take into account the following when installing the heat pump:
- prevailing winds,
- the noise generated by the fan and the compressor
- the visual impact on the surrounding neighbourhood.
Avoid areas exposed to strong winds directed against the appliance’s air outlet.
Set the appliance on one of the following supports:
- concrete slabs,
- crane beam,
- concrete blocks.
Do not install the fan facing the nearby windows. If necessary, install a noise barrier.
To avoid transmission of vibrations to the surrounding buildings:
- use hoses for water connections,
- install anti-vibration pads.
Ensure that the appliance is protected from water and from snow.
Do not expose the heat pump to corrosive or dusty atmospheres (near to dirt roads, for example).
INSTALLATION
Page 15
0020117819_01 - 05/11 - Glow-worm
- 13 -
7.2 Clearances
- Respect the minimum dimensions shown in the drawing above in order to ensure a correct air fl ow and to facilitate maintenance operations.
- Make sure that the available space is suffi cient for the installation of the water system piping.
7.3 Command unit location
Install the command unit in a room protected from frost
INSTALLATION
Page 16
0020117819_01 - 05/11 - Glow-worm
- 14 -
8 Installing the command unit
Make sure that the materials used for performing the installation are compatible with those of the appliance.
Determine the place of assembly. See the chapter "Location".
3
3
1
1
4
2
Key 1 Mounting screw 2 Wall support 3 Rawlplug 4 Electric terminal block
Separate the command unit from the wall support (3).
Pass the electrical connection cables through the hole on the
left of the connector and connect them onto terminal (4). See the chapter "Installation examples".
Position the support (3) on a wall.
Drill holes for the xing screws in accordance with the 2 xing
holes on the wall support (3).
Insert the rawlplugs (2) in the holes.
Fix the support (3) with the xing screws (supplied).
2
1
Key 1 Command unit 2 Wall support
Assemble the command unit (1) on the wall support (2).
9 Installing the heat pump
9.1 Scope of delivery
1
3
4
2
2.1
2.2
2.4
2.3
2.2
2.4
2.3
3.1
3.2
Key 1 Heat pump (x1)
2 Packet of accessories (x1)
2.1 Condensate connection (x1)
2.2 Leak-tight seal for passing mains and low-voltage cables
(x2)
INSTALLATION
Page 17
0020117819_01 - 05/11 - Glow-worm
- 15 -
2.3 Protection against the sharp edges of the sheet metal for the cable passage (if necessary)
(x1)
2.4 Leak-tight seal for the cable passage (if necessary) (x1)
3 Packet of documents (x1)
3.1 Installation manual (x1)
3.2 Instructions for use (x1)
4 Command unit (x1)
Check the contents of the package.
9.2 Recommendations before installation
9.2.1 Design of the heating circuit
The heat emitters may be either low temperature (underfl oor heating, etc.), or medium temperature (warm radiator, etc.).
b
We recommend that you provide suffi cient fl ow for the temperature diff erence between fl ow and return to be equal to 7 C for a underfl oor heating and 15 C for radiators.
The route of the piping will be designed to take all measures ne­cessary to avoid air pockets and facilitate the permanent venting of the installation. Vents must be provided at each high point of the pipes, and on all the radiators.
b
Always leave a radiator open.
We recommend installing a drainage valve at the lowest point of the installation.
In the case of the use of thermostatic valves, it is imperative not to fi t to all radiators, taking care to fi t these valves in rooms with high input and never in rooms where the room thermostats are installed.
- If it is an old installation, it is essential to rinse the radiator circuit before installing the new appliance and to add an anti­sludge fi lter.
- If a component of the system is not to be installed immediately, protect the various connections so plaster and paint cannot compromise the seal on the subsequent connection.
Install the following components on the heating circuit return:
- a heating fi lter,
- 2 quarter-turn shut-off valves (1 each side of the fi lter),
- an air separator (if necessary),
- an anti-sludge fi lter (if necessary).
In the case of a underfl oor heating, install a security device to prevent overheating, with manual reset (55°C) on the heating circuit fl ow. Connect the overheating security device to the glycol pump of the heat pump.
9.2.2 Design of the heat pump circuit
Installation pipework must be designed and installed to ensure venting of air from the system is possible.
b
Ensure that the water fl ow rate of the water circuit corresponds to the nominal water fl ow rate of the appliance (see ¨Technical data¨ chapter).
Install the following components on the rear section of the heat pump:
- a fi lter,
- a ¼ shut –off valve on each side of the fi lter,
- a drain valve,
- an air separator (if necessary)
- a sludge deposit (if necessary).
Install a ¼ turn shutoff valve in the fl ow of the heat pump.
i
In order to avoid the transmission of vibrations to surrounding structures, use fl exible hoses for the hydraulic connections at least 1 metre from the heat pump.
b
Insulate the pipes with a UV- and hightemperature­resistant insulation.
9.3 Dimensions
9.3.1 Envirosorb 7
150
150
600
908
326
821
INSTALLATION
Page 18
0020117819_01 - 05/11 - Glow-worm
- 16 -
9.3.2 Envirosorb 12, Envirosorb 14
150
150
600
908
326
1363
9.3.3 Command unit
1
2
3
4
5
6
7
132
27
132
9.4 Mounting
9.4.1 Unpacking the appliance
Carefully remove the packaging and protections without damaging the parts of the appliance.
1
1
2
3
Key 1 Transport pallet 2 Attachment screws 3 Heat pump
Remove the screws from the transport pallet at the front and rear of the unit.
INSTALLATION
Page 19
0020117819_01 - 05/11 - Glow-worm
- 17 -
9.4.2 Transportation of the appliance
i
With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift.
a
Warning! Two people at minimum are necessary to move the appliance.
b
Warning! Do not lean the appliance more than 45° during transportation as this may damage the refrigeration circuit which could lead to a complete system failure.
i
We recommend that you move the appliance with a trolley or with suitable handling equipment.
If you move the appliance with a two-wheeled trolley, respect the following regulations:
Only lift the appliance from the back.
Attach the appliance to the two-wheeled trolley with a strap.
Protect surfaces in contact with the trolley to avoid scratching
or damaging the appliance.
Use a suffi ciently solid ramp to lower the appliance from the pallet.
Move the appliance to the installation site.
9.5 Positioning the appliance
i
With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift.
1
1
1
2
Key 1 Concrete block 2 Mounting screw
Fix the heat pump onto the concrete blocks (1) using the fi xing screws.
INSTALLATION
Page 20
0020117819_01 - 05/11 - Glow-worm
- 18 -
10 Examples of installation
10.1 Installation with hydraulic module, control by control unit
A
B
H
E
F
230V
230V
L5
1
6
2
4
5
3
1
4
2
3
INSTALLATION
Page 21
0020117819_01 - 05/11 - Glow-worm
- 19 -
Key 1 Heat pump 2 Power supply and electrical protection for the heat pump (*) 3 Command unit for the heat pump 4 Glow Worm control unit (*) 5 Glow Worm hydraulic module (*) 6 Anti-sludge fi lter (*) A Flow heat pump circuit B Return heat pump circuit E Return heating circuit F Flow heating circuit H Discharge from the safety valve to a container for recovering glycol
water solution
(*) Not delivered with the appliance
Adjusting the heat pump's command unit
To fi nd out the description of each function, see the chapter "Specifi c adjustment".
i
The setting of codes 112, 114, 117, 122, 123, 124, 125, 126 must be identical on the heat pump command unit and the systempro control unit.
Menu Name of the function Value Factory setting
100 Type of system regulation 22 101 Confi guration of the command unit 00 112 External calibrated adjustment graphs 7 - 12 (*) 8 114 ECO heating mode 1 - 20°C (*) 5°C 117 External calibrated adjustment graphs for cooling 0 (*) 2
122 Maximum reference exterior temperature 24 - 46°C (*) 40°C 123 Exterior temperature from which the heat pump stops in cooling mode 0 - 30°C (*) 22°C 124 Minimum temperature of water in the installation in cooling mode 4 - 20°C (*) 4°C 125 Maximum temperature of water in the installation in cooling mode 4 - 20°C (*) 12°C 126 Confi gurations exterior sensor 22
146 Confi guration for stopping the heat pump if control by S1 contact input 1 2 147 Confi guration of the output between terminal channels 5 and N 1 1
148 Limit exterior temperature (T0) -20°C -20°C
155 Functioning of main circulator 01
(*) Refer to the system installation manual for pairing the settings of these codes.
Application conditions
- Command unit used as confi guration tool (see the chapter "Location of the appliance"),
- Installation with underfl oor heating (< 53°C) or low- temperature radiator (<60°C),
i
For the dimensioning of the cables and the electrical protection on the appliances, see the chapter "Electrical connection".
Envirosorb
71214 Minimum volume of the installation (l) 28 42 49 Max volume of heat pump circuit, without additional vessel, for a water outlet temperature of 35°C (l)
65 95 95
Volume of water in the heat pump
1.2 2.3 2.3
Nominal water ow rate (m³/h) 1.2 2.1 2.5
INSTALLATION
Page 22
0020117819_01 - 05/11 - Glow-worm
- 20 -
10.2 Installation with hydraulic module, DHW tank, control by control unit
A
B
H
E
F
230V
230V
L5
230V
1
9
8
2 3
6.1
6
6.2
7
5
1
4
6.2
8
2
5
230V
3
4
6.1
R6.1
INSTALLATION
Page 23
0020117819_01 - 05/11 - Glow-worm
- 21 -
Key 1 Heat pump 2 Power supply and electrical protection for the heat pump (*) 3 Power supply and electrical protection for the booster heating (*) 4 Glow Worm control unit (*) 5 Command unit for the heat pump 6 Domestic hot water tank (option) (*)
6.1 Electrical booster element
6.2 Temperature sensor for hot water tank 7 Glow Worm hydraulic module (*) 8 3-way valve (with return spring) for the domestic hot water tank (*) 9 Anti-sludge fi lter (*) R6.1 Additional electrical heater relay A Flow heat pump circuit B Return heat pump circuit E Return heating circuit F Flow heating circuit H Discharge from the safety valve to a container for recovering glycol
water solution
(*) Not delivered with the appliance
b
If the "Domestic hot water tank" option is chosen, it must be connected electrically to the systempro control unit (see the installation manual for the system).
Adjusting the heat pump's command unit
To fi nd out the description of each function, see the chapter "Specifi c adjustment".
i
The setting of codes 112, 117, 122, 123, 124, 125, 126 must be identical on the heat pump command unit and the systempro control unit.
Menu Name of the function Value Factory setting
100 Type of system regulation 22 101 Confi guration of the command unit 00 112 External calibrated adjustment graphs 7 - 12 (*) 8 117 External calibrated adjustment graphs for cooling 0 (*) 2
122 Maximum reference exterior temperature 24 - 46°C (*) 40°C 123 Exterior temperature from which the heat pump stops in cooling mode 0 - 30°C (*) 22°C 124 Minimum temperature of water in the installation in cooling mode 4 - 20°C (*) 4°C 125 Maximum temperature of water in the installation in cooling mode 4 - 20°C (*) 12°C 126 Confi gurations exterior sensor 22
146 Confi guration for stopping the heat pump if control by S1 contact input 1 2 147 Confi guration of the output between terminal channels 5 and N 1 1
148 Limit exterior temperature (T0) -20°C -20°C
153 Mode of activation hot-water demand contact S5 1 1 155 Functioning of main circulator 01
(*) Refer to the system installation manual for pairing the settings of these codes.
Application conditions
- Command unit used as confi guration tool (see the chapter "Location of the appliance"),
- Installation with underfl oor heating (< 53°C) or low- temperature radiator (<60°C),
- Control unit for the system not included.
i
For the dimensioning of the cables and the electrical protection on the appliances, see the chapter "Electrical connection".
Envirosorb
71214 Minimum volume of the installation (l) 28 42 49 Max volume of heat pump circuit, without additional vessel, for a water outlet temperature of 35°C (l)
65 95 95
Volume of water in the heat pump
1.2 2.3 2.3
Nominal water ow rate (m³/h) 1.2 2.1 2.5
INSTALLATION
Page 24
0020117819_01 - 05/11 - Glow-worm
- 22 -
11 Hydraulic connection
Take care to clean the pipes before assembly removing any debris or burrs. Grease and oils may need to be removed they are not possible to remove by cleansing and fl ushing. Foreign bodies in the system may enter the appliance and interrupt its operation.
Do not use any solvent products, due to the risk of damaging the circuit.
Only use original seals supplied with the appliance.
b
Make sure that mechanical connections are not overtightened.
b
Insulate the pipes (between the heat pump and the installation including those underground) with an UV­and high-temperature-resistant insulation.
1m min.
1
2
3
7
4
4
5
6
8
key 1 Heat pump fl ow circuit ¼ turn shut-off valve in the direction of the
building (not included) (*)
2 Return circuit ¼ turn shut-off valve in the direction of the heat pump
(not included) (*) 3 Return circuit hose in the direction of the heat pump (not supplied) 4 Cap 5 Return connection (Ø1 ") to the heat pump 6 Flow heat pump connection (Ø1 ") to the building 7 Flow heat pump circuit hose in the direction of the building (not
supplied)) 8 Insulation (not supplied) (*) To be installed as close as possible to the heat pump
Remove the protection caps (4) located on the connections.
Comply with the values given in the table below when making
the hydraulic connections of the heat pump circuit.
Max linear distance (without elbows or
additional pressure drops)
Tubes to be installed
20 m ¾" or Ø internal = 20 mm
30 m 1" or Ø internal = 26 mm
Connect a hose and a shut-off valve to the return connection to
the heat pump.
Connect a hose and a shut-off valve to the fl ow heat pump
connection in the direction of the building.
Install the fi lter on the heat pump return pipe. Install it between 2 shut-off valves in order to be able to remove if from the circuit and clean it periodically.
Insulate all exposed pipework.
12 Discharge of condensate
When the appliance is operational, it will produce condensation that needs to be drained off .
1
2
600150 150
430
400
363
37
Key 1 Evacuation bend for condensates 2 Holes pre-cut in the base of the heat pump
Install the bend (1) delivered with the appliance and connect it to an evacuation pipe with an internal diameter of 16 mm (not supplied).
Make sure that the condensates evacuation pipe does not freeze.
The discharge capacity of the condensate increases if the pre-cut holes (2) present in the base are open. Open the pre-cut holes using a hammer.
i
If you choose to open the pre-cut holes (2) present in the base, take the necessary precautions to recover the condensates and stop them freezing.
13 Electrical connection
e
Incorrect installation can cause electric shock or appliance damage. The electrical connection of the appliance must be made only by a qualifi ed engineer.
The appliance must be connected directly to an accessible, fi xed, switched, electrical outlet.
The manufacturer declines any responsibility for damages to persons or others caused by the incorrect installation of the appliance earthing. This includes failure to comply with current standards.
Electrical components have been tested to meet the equivalent requirements of BSEN 7671 and the BEAB regulations.
The cables connecting the installation's electrical panel and the heat pump must be:
- Suitable for a fi xed installation.
INSTALLATION
Page 25
0020117819_01 - 05/11 - Glow-worm
- 23 -
- weather resistant.
- equipped with wires adapted to appliance’s power rating.
Connect the heat pump to an electrical panel via an independent protection system (diff erential breaker with at least 3 mm between each contact). See the table below.
Additional protection may be required during installation to ensure buff er category II.
The power supply cut-off devices must allow complete disconnection of the power under the conditions required for over-voltage category III.
Description Unit 7 12 14
Electricity supply
V-ph-
Hz
230 - 1 - 50
Acceptable voltage range V 207/254 Maximum power absorbed kW 2.7 5.1 5.1 Maximum current A 14 23 20 Power fuse (gL) A 15 Type B 25 Type D 25 Type D Maximum current in glycol
pump
A2
13.1 Access to main board
B
A
A
A
C
2
1
Key 1 Terminal blocks for 230 V and 12 V connection 2 Front panel
Remove the fastening screws (A).
Slide the front panel (2) downwards (B) and pull it towards
yourself (B) using the handle.
To close the appliance, carry out the operations in reverse order.
13.2 Cable passage
e
The low and mains voltage cables must be inserted in diff erent sleeves.
2
1
Key 1 Mains-voltage cable passage 2 Low-voltage cable passage
Insert the electrical power cables in passages (1) and (2) provided for this purpose.
Make sure that the electrical cables are not in contact with the compressor and the hot pipes.
Fix the electrical cables with the clamps installed inside the heat pump.
13.4 Electrical wiring
3
2
4
1
Key Recommended cable section 1 230 V power cable H07RN-F 3 x 2.5 mm² 2 12 V cable 0.75 mm²
3
230 V cable (outputs 2A maximum)
0.75 mm²
4
Connection cable for the command unit
4 x 0.75 mm²
INSTALLATION
Page 26
0020117819_01 - 05/11 - Glow-worm
- 24 -
ʎPP
ʎPP
ʎPP
ʎPP
Attach the electrical cables using the cable pass-through located in the electrical box in order to ensure good resistance to pulling (for the 14kW model, use the anti-wrench connector supplied with the appliance).
13.5 Wiring diagram
13.5.1 Command board 7kW, 12kW, 14kW
1FS
1T
1TR
1PS
1LWT 1EWT
1PCB
Key 1PS Circulator 1LWT Flow temperature sensor for heat pump circuit 1TR Temperature sensor for detecting the end of defrost 1EWT Temperature sensor for fl ow of heat pump circuit 1FS Flow detector 1T Transformer 1PCB Command board
INSTALLATION
Page 27
0020117819_01 - 05/11 - Glow-worm
- 25 -
13.5.2 Board of power 7kW
R
R
W
W
C
C
Y
A
Y
Y
RWC
V
C
C
W
R
b
R
S
C
40CF
12
3
7CM
123
1R
41CF
21
8CM
21
12
P25
P24
P23
P22
P21
P20
P35
P34
P19
P18
P04
P05
P06
1P.C.BOARD
P11
P08
1MCC1530
42CF
123
43CF
12
3
CN805
1
1
P33 P32
44CF
21
9CM
21
P31 P30
CN701
45CF
123
1
F7 P03 P10 P02
CN806
1
CN300
CN700
CN503
CN502
CN501
CN500
1
6
1
1
1
1
1
46CF
3
2
1
47CF
6
5
4
3
2
1
48CF
3
2
1
49CF
2
1
50CF
3
2
1
51CF
2
1
C
W
W
R
Y/G
O
C
A
Y/G
R12
3R
1TB
1
N 3 L N PE
N
L
230V1~50Hz
/2.10/J4.1
/2.03/J3.1
/2.08/J1.1
1TD
1TS
2R
1R
1FM
6CM
1TE
1TO
1RV
1PMV
1F
Key 1FM Fan motor 1PMV Electronic expansion unit 1TS Temperature sensor for compressor suction 1TO Exterior temperature sensor 1TD Compressor discharge temperature sensor 1TE Temperature sensor for plate to plate exchanger 1RV 4-way cycle inversion gate 1R Filtering coil 1 2R Filtering coil 2 6CM Compressor engine 1F Fuse
INSTALLATION
Page 28
0020117819_01 - 05/11 - Glow-worm
- 26 -
13.5.3 Board of power 12kW
R
W
C
Y/G
WRW G
C
G
O
O
A
P R B
C
W C Y
YBB
O
O
C
W
R
R
R
W
W
C
C
B
A
PE
9bbabb+]
)
2
L
L
N
N
C)
2
3
C)
2
3
4
CN
CN02
CN03
PCBOAR'
2PCBOAR'
7CM
23
4C)
23
P08
CN700
CN02
42C)
234
43C)
234
44C)
2346
P09
R
CN3
CN0
CN702
8CM
23
4C)
23
P2 P3
R
46C)
2
47C)
2
CN0
CN04
P2
48C)
23
CN303
P24
49C)
234
0C)
234
+
CN800
CN06
P28 P29
C)
234
E'
CN302
2C)
23
3C)
2
3
P9
CN04
CN03
P20 P7 P8
CN600
4C)
23
C)
2
CN09
CN0
CN
CN30
6C)
2
3
CN600
7C)
234
CN300
8C)
2
CN60
9C)
2
CN604
60C)
2
7+ERMO67A7
)ORbCOMPRE66OR
CN00
2T
2
6C)
2
3
CN60
CN606
R
C
6
N 3
-4b/b/20
-3b/b/203
-b/b/208
1TD 1TS
1TH
1FM 2FM
1CM
1TE 1TO
1RV
1PVM
Key 1RV 4-way cycle inversion gate 1TH Temperature sensor for the fi nned heat exchanger 1TD Compressor discharge temperature sensor 1TS Temperature sensor for compressor suction 1TE Temperature sensor for plate to plate exchanger 1TO Exterior temperature sensor 1CM Compressor 1FM Fan 1 2FM Fan 2 1PVM Electronic expansion unit
INSTALLATION
Page 29
0020117819_01 - 05/11 - Glow-worm
- 27 -
13.5.4 Board of power 14kW
R
C
W
C
A
B
C
W
R
G
W
R
1TB
230V1~50Hz
L
N
2TB
1 2 3
J4.1//2.10
J3.1//2.03
J1.1//2.08
U V W
63CF
12
64CF
12
CN400
(WHITE)
CN300
(WHITE)
CN609
(BLUE)
CN610
(YELLOW)
CN604
(WHITE)
CN603
(WHITE)
CN602
(YELLOW)
CN601
(WHITE)
CN600
(WHITE)
CN710
(WHITE)
SW802
SW804
SW803
ONONON
432143214321
SW801
CN704
(BLUE)
SW800
RY704
P04
CN701
(WHITE)
P05
CONTROLP.C.BOARD
MCC1571
P06
CN04
(WHITE)
P07
CN200
F03
T10A,250V~
F01
T25A,250V~
CN201
P01
L/F
P02
CN202
P09
10CM
12
11CM
12
49C
12
L N
65CF
1
2
3
66CF
1
2
67CF
1
2
68CF
1
2
3
69CF
1
2
70CF
1
2
71CF
1
2
3
72CF
123456
73CF
1234
74CF
123456
75CF
1
2
3
1TD
1TS
1TL
1R 2R
2FM
1FM
1CM
1TE
1TO
1RV
1PVM
Key 1RV 4-way cycle inversion gate 1TL Temperature sensor for the fi nned heat exchanger 1TD Compressor discharge temperature sensor 1TS Temperature sensor for compressor suction 1TE Temperature sensor for plate to plate exchanger 1TO Exterior temperature sensor 1CM Compressor 1FM Fan 1 2FM Fan 2 1R Filtering coil 1 2R Filtering coil 2 1PVM Electronic expansion unit
INSTALLATION
Page 30
0020117819_01 - 05/11 - Glow-worm
- 28 -
14 Commissioning
i
At the time of commissioning, complete all relevant sections of the Benchmark Checklist located on the inside back pages of this document.
Check that the di erential breaker is installed.
Check that the hydraulic and electrical connections are correct.
Check that the lter on the heat pump return is installed.
Check the airtightness of the connections.
Open all the hydraulic circuits’ valves.
14.1 Filling the glycol circuit
b
Warning! Do not dispose of glycol into drains and the environment.
b
We recommend that you use propylene glycol enriched with corrosive inhibitors.
Mix 1 part propylene glycol with 2 parts water. This 30% mixture ensures antifreeze protection down to an exterior temperature of -15 °C.
Use an antifreeze test kit to ensure accurate dosing.
Make sure that the hydraulic circuit is purged.
In order to drain the glycol circuit after lling, use a ll pump.
Put the heat pump circuit under pressure between 1.5 and 2 bars.
i
The level of glycol may decrease during the fi rst month following the commissioning of the installation. It may also vary in accordance with the outdoor temperature.
Any residue of glycol solution should be kept in an appropriate container to be re-used for the next fi lling.
Ensure any leftover glycol solution is left with the end user and retained in a safe place.
14.2 Activating the heat pump
e
Make sure that all the electrical connections have been made.
b
Make sure that the setting for the maximum temperature at heating fl ow is compatible with the installation.
Position the circuit breaker located on the electrical circuit box and connected to the heat pump to the ON position.
The main screen for the command unit is displayed.
See the chapter "Example installation" to enter all the settings corresponding to your installation.
14.3 Activating the options
See the instructions for each option to activate them and enter their settings.
14.4 Heating system test
Ensure that there is a heating demand to the control unit. In the case of a multi-zone confi guration, perform the test zone by zone and ensure that the appropriate zone gets warmer.
Ensure that all the heating circuit’s thermostatic valves are open.
Balance the heat emitters, if necessary.
15 Specifi c adjustment
15.1 Adjusting the heating circuit
b
The maximum heating output temperature must be adjusted in accordance with the characteristics of your installation.
b
Ensure that the heating curve setting is compatible with the installation.
b
Make sure that the functioning mode for the boiler's circulator is not in permanent mode, but synchronised with heating demand (with the room thermostat).
2
4
3
1
Key 1 Speed I 2 Speed II 3 Speed III 4 Speed selector
Turn the circulator's speed selector to choose speed I.
Open all the thermostatic valves on the radiators to the
maximum.
Adjust the temperature to the maximum on all the room thermostats in your home.
Put your installation into service by forcing a heating request when the circulator should start.
Wait 10 to 15 min and measure the diff erence in temperature between fl ow and return of the heat pump (temperatures can be displayed using parameters 137 (return) and 138 (fl ow)). The diff erence should be between 5 and 6°C.
If the diff erence is greater than 6°C, select a higher pump speed or reduce the circuit pressure drops.
INSTALLATION
Page 31
0020117819_01 - 05/11 - Glow-worm
- 29 -
Envirosorb 7 fl ow/pressure curves
A
B
0
10
20
30
40
50
60
720 1440 2160 2880
1
2
3
Key 1 Speed I 2 Speed II 3 Speed III A Available pressure (kPa) B Flow in the circuit (l/h)
Envirosorb 12, Envirosorb 14 fl ow/pressure curves
A
B
0
10
20
30
40
50
60
70
80
720 1440 2160 2880
1
2
3
Key 1 Speed I 2 Speed II 3 Speed III A Available pressure (kPa) B Flow in the circuit (l/h)
15.2 Settings for the command unit
15.2.1 Overall view
1 2 3 4 5 6 7
14
1
2
3
7
6
5
4
10 9 8
13 12
11
Key 1 Selection of “standby” mode in the weekly programming 2 Hold the selected temperature or runs the scheduled program 3 Choice of functioning mode
4 Display 5 Scroll up 6 Scroll down 7 Validation 8 Temperature Night 9 Temperature Eco 10 Temperature Comfort 11 Setting day/time/minute 12 Programme: time when time interval begins 13 Programme: choice of time interval 14 Programme: group of days
15.2.2 Appliance confi guration parameters
i
If the parameters are changed, it is important to leave the control box connected for at least 10 seconds so that the change is properly saved.
Press simultaneously on the button (
) and (M) for 3
seconds. The parameter number is displayed and its value blinks.
Press the button (
) to access the parameter "302".
Press the button (M). The value of the parameter ashes.
Description of parameter 302
Setting
Factory
setting
Min Max
0 = Cooling only 1 = Heating + cooling 2 = Heating only
02 2
Press the buttons ( ) to modify the value.
Press the button (M) to con rm the parameter setting.
i
The other parameters 301, 303, 304, 305 and 306 must not be modifi ed.
Press the button (OK) to exit the menu and validate the settings.
15.2.3 Parameters set by the installer
This menu lets you enter the settings intended for the fi nal user.
Press simultaneously on buttons (
) and ( ) for 3 seconds. The parameter number is displayed and its value blinks.
Press the button (M) to access the parameter. The value of the
parameter fl ashes.
Press the buttons (
) to modify the value.
Press the button (M) to con rm the parameter setting.
Press the buttons (
) to move to the next parameter.
Perform the previous operations again for the other parameters.
Press the button (OK) to exit the menu and validate the settings.
INSTALLATION
Page 32
0020117819_01 - 05/11 - Glow-worm
- 30 -
Code Function Description
Setting
Factory
setting
Modifi able parameter
Min Max
1
Default functioning mode
Choose the default functioning mode for the heat pump: 0 = Stopped 2 = Cooling 3 = Heating
03 0 Yes
2 Protection against frost
Function to protect the installation against frost when the heat pump is stopped. 1 = Deactivated 2 = Activated
12 1 Yes
3
Temperature triggering protection against frost
Choose the ambient temperature of the dwelling from which the installation's protection against frost is activated.
6°C 12°C 6°C Yes
4
Correction of the ambient temperature
This parameter lets you correct the heat pump's temperature setting by increasing or reducing the temperature of the water in the installation to improve the adjustment of the ambient temperature of the room.
-5°C +5°C 0°C Yes
5 Silent mode
This mode lets you reduce the noise emitted by the heat pump (at night, for example), by reducing the frequency at which the compressor functions. 1 = Deactivated 2 = Activated
12 1 Yes
6
Compressor frequency reduction
This parameter defi nes the percentage reduction of the compressor frequency. 50% 100% 75% Yes
7
Temperature of the dwelling
This parameter displays the current temperature level: 1 = Temperature Comfort 2 = Temperature Night 3 = Temperature Eco
13 - No
8
Ambient temperature setting
This parameter displays the ambient temperature setting when you press one of the buttons "Comfort", "Night" and "Eco".
12°C 38°C - No
9 Ambient temperature
This parameter displays the ambient temperature of the room measured by the sensor installed in the command unit.
-20°C 50°C - No
10 Humidity rate
This parameter displays the rate of humidity of the room measured by the sensor installed in the command unit.
0 100 - No
11 Exterior temperature This parameter displays the exterior temperature measured by the heat pump. -30°C 90°C - No 12 Not used
13
Correction to the ambient temperature (command unit position)
This parameter corrects the measurement of the ambient temperature following an error in positioning the command unit.
-5°C +5°C 0°C Yes
14
Programme time intervals
Choose the number of time intervals available for weekly programming: 2 = 2 time intervals 4 = 4 time intervals 6 = 6 time intervals
24 6 Yes
15
"Comfort" heating temperature
Choose the ambient temperature in heating mode for the "Comfort" temperature. 12°C 38°C 20°C Yes
16
"Comfort" cooling temperature
Choose the ambient temperature in cooling mode for the "Comfort" temperature. 12°C 38°C 24°C Yes
17
"Night" heating temperature
Choose the ambient temperature in heating mode for the "Night" temperature. 12°C 38°C 18°C Yes
18
"Night" cooling temperature
Choose the ambient temperature in cooling mode for the "Night" temperature. 12°C 38°C 26°C Yes
19
"Eco" heating temperature
Choose the ambient temperature in heating mode for the "Eco" temperature. 12°C 38°C 15°C Yes
20
"Eco" cooling temperature
Choose the ambient temperature in cooling mode for the "Eco" temperature. 12°C 38°C 28°C Yes
21
Ambient temperature setting
This parameter displays the ambient temperature of the room where the command unit is installed.
12°C 38°C - No
22 Displaying fault codes This parameter displays the last occurring fault code. - - - No 23 Fault history Every 4 seconds, this parameter displays the latest fault codes that appear. - - - No
15.2.4 Reinitialisation of parameters
This function is used to reinitialise the control box parameters (factory settings).
b
The return to factory settings is irreversible. All the personalised settings of the control box will be lost.
Press the 2 buttons (
) and (M) for 10 seconds.
When selecting for the fi rst time, the fi gure 999 appears in the temperature display area and the fi gure 10 appears in the time display area.
Hold down the (
) button until 0 is displayed on the screen.
The message “FD” is displayed in the temperature area.
The control box then restores the factory default parameters.
Restart the entire system to complete the restore.
INSTALLATION
Page 33
0020117819_01 - 05/11 - Glow-worm
- 31 -
15.2.5 After-sales service parameters
This menu lets you make adjustments to the following functions according to the appliances connected, and reset all these parameters.
Press simultaneously on button (
) and ( ) for 3 seconds.
The parameter number is displayed and its value blinks.
Press the button (M) to access the parameter. The value of the parameter fl ashes.
Press the buttons (
) to modify the value.
Press the button (M) to con rm the parameter setting.
Press the buttons ( ) to move to the next parameter.
Perform the previous operations again for the other
parameters.
Press the button (OK) to exit the menu and validate the settings.
Code Function Description
Setting
Factory setting
Modifi able parameter
Min Max
100
Type of system regulation
1 = Not used 2 = Regulation with system of management by contact 3 = Not used 4 = Not used 5 = Not used 6 = Not used 7 = Not used
17 2 Yes
101
Confi guration of the command unit
0 = Command unit used as confi guration tool 1 = Not used 2 = Not used
02 0 Yes
102
Updates to the command unit software
This parameter displays the latest update to the software that is made on the heat pump's command unit.
-- - No
103
Version of the command unit's software
This parameter displays the version of the heat pump's command unit software - - - No
104 Test modes
By activating these various test modes, you can trigger special functions on the appliance. 0 = No test 1 = Force the circulator 2 = Force output between terminals 5 and N (code 147) 3 = Force output between terminals 4 and N (code 106) 4 = Force output between terminals 11 and N (code 108) 5 = Force output between terminals 12 and N (code 156) 6 = Force the 3-way gate 7 = Not used 8 = Not used
09 0 Yes
105
Reset the counter for the circulator functioning time
This parameter resets, to zero, the functioning time counter for the heat pump's circulator.
000 (no)
165
(yes)
000 (no)
Yes
106
Confi guration of the output between terminal channels 4 and N
Confi guration of the booster heating 1 = Command booster heating 2 = Not used
12 1 Yes
107
Humidity rate threshold
This parameter defi nes the humidity rate threshold from which the dehumidifi er is switched on.
20% 100% 50% Yes
108
Confi guration of the output between terminal channels 11 and N
Confi guration of dehumidifi er 1 = Not used 2 = Dehumidifi er command
12 2 Yes
109
Threshold for protection against frost
This parameter defi nes the temperature level of the installation's water from which protection against frost is activated. This threshold corresponds to the set temperature to which you should add 3°C.
0°C 6°C 0°C Yes
110
Reset the counter for the compressor's functioning time
This parameter resets, to zero, the functioning time counter for the heat pump's compressor.
000 (no)
165
(yes)
000 (no)
Yes
111
Status of water fl ow detector
This parameter lets you check the state of the water fl ow detector 1 = Suffi cient water fl ow detected 0 = No water fl ow or insuffi cient fl ow
-- - No
INSTALLATION
Page 34
0020117819_01 - 05/11 - Glow-worm
- 32 -
Predefi ned heating curves (code 112)
30
20
40
50
60
A
B
-20 -15 -10 -5 0 5 10 15 20
1211109
8
7
Key 7 Heating graph n°7 8 Heating graph n°8 (factory setting) 9 Heating graph n°9 10 Heating graph n°10 11 Heating graph n°11 12 Heating graph n°12 A Heating fl ow temperature (°C) B Exterior temperature (°C)
Code Function Description
Setting
Factory
setting
Modifi able parameter
Min Max
112
Predefi ned heating curves
0 = Personalised graph (see codes 118 to 121) 1 to 6 = Not used 7 to 12 = Pre-defi ned graphs (see above graphs)
112 8 Yes
114 ECO heating mode Reduction off set for the installation's water temperature setting in heating mode. 1°C 20°C 5°C Yes 116 ECO cooling mode Increase off set for the installation's water temperature setting in cooling mode. 1°C 10°C 5°C Yes 117 Not used
Personalised heating curves (codes 118, 119, 120, 121)
-20 -15 -10 -5 0 5 10 15 20
A
B
0
10
20
30
40
50
60
2
3
1
4
Key 1 Code 118 2 Code 119 3 Code 120 4 Code 121 A Heating fl ow temperature (°C) B Exterior temperature (°C)
Code Function Description
Setting
Factory setting
Modifi able
parameter
Min Max
Setting codes 118 to 121 is necessary only if code 112 = 0.
118
Minimum reference exterior temperature
Choose the minimum reference exterior temperature for the region where the heat pump is installed.
-20°C 10°C -7°C Yes
119
Exterior temperature from which the heat pump stops in heating mode
When the exterior temperature reaches the input value, heat pump stops. Choose the exterior temperature from which the heat pump must stop in heating mode.
10°C 30°C 20°C Yes
120
Minimum temperature of water in the installation in heating mode
Choose the minimum temperature of the water in the installation in heating mode.
20°C 60°C 40°C Yes
121
Maximum temperature of the water in the installation in heating mode
Choose the maximum temperature of the water in the installation in heating mode.
20°C 60°C 55°C Yes
122 Not used 123 Not used 124 Not used 125 Not used
INSTALLATION
Page 35
0020117819_01 - 05/11 - Glow-worm
- 33 -
Code Function Description
Setting
Factory setting
Modifi able
parameter
Min Max
126
Confi gurations exterior sensor
Choose the type of exterior-temperature sensor: 1 = Remote sensor (connected onto terminal block 23 and 24) 2 = Sensor installed on the heat pump.
12 2 Yes
127 Exterior temperature
This parameter displays the external temperature measured by the sensor installed in the heat pump.
-- - No
128
Temperature of the cooling circuit battery
This parameter displays the temperature of the heat pump's cooling circuit battery. - - - No
129
Compressor suction temperature
This parameter displays the compressor's suction temperature. - - - No
130
Compressor discharge temperature
This parameter displays the compressor's discharge temperature. - - - No
131
Functioning state of the heat pump
This parameter displays the functioning state of the heat pump: 0 = Stopped 2 = Cooling mode 3 = Heating mode 4 = Fault 5 = Defrost mode
-- - No
132
Maximum frequency of compressor
This parameter displays the maximum frequency of the compressor allowed by the heat pump's command board.
-- - No
133
Required compressor frequency
This parameter displays the compressor frequency required by the heat pump's command board.
-- - No
134
Real compressor frequency
This parameter displays the real frequency of the compressor variator. - - - No
135
Counter that times the functioning of the compressor
This parameter displays the number of hours during which the compressor has functioned since fi rst activation.
-- - No
136
Capacity of the heat pump
This parameter displays the capacity of the heat pump. - - - No
137
Return temperature of the heat pump circuit
This parameter displays the return temperature of the heat pump's circuit. - - - No
138
Flow temperature of the heat pump's circuit
This parameter displays the fl ow temperature of the heat pump's circuit. - - - No
139
Temperature of the cooling fl uid in the plate to plate exchanger
This parameter displays the temperature of the cooling fl uid in the plate to plate exchanger
-- - No
140
State of functioning of the system
This parameter displays the state of functioning of the system: 0 = Stopped 1 = Standby mode 2 = Cooling mode 3 = Heating mode 4 = Booster heating functioning 5 = Booster cooling functioning 4 = Nominal heating 5 = Nominal cooling 8 = Frost protection mode 9 = Defrost 10 = Protection against overheating 11 = Guard interval 12 = System fault
-- - No
141 Fault codes This parameter displays the fault codes for the heat pump. - - - No
142
Version of the heat pump's software
This parameter displays the version of the heat pump's software. - - - No
143
Update to the heat pump's software
This parameter displays the latest update made to the heat pump's software. - - - No
144
Counter that times the functioning of the circulator
This parameter displays the number of hours during which the circulator has functioned since fi rst activation.
-- - No
145
Temperature setting calculated for the installation's water
This parameter displays the temperature setting for the installation's water calculated by the command board according to climatic graphs.
-- - No
INSTALLATION
Page 36
0020117819_01 - 05/11 - Glow-worm
- 34 -
Code Function Description
Setting
Factory setting
Modifi able
parameter
Min Max
146
Confi guration for stopping the heat pump if control by S1 contact input
1 = Immediate halt (as soon as contact S1 moves into the open position, the heat pump stops). 2 = Gradual halt (as soon as contact S1 opens, the speed of the compressor gradually reduces. This confi guration is used to delay the shutdown of the compressor after contact S1 switches to the open position and to limit the number of compressor cycles per hour to 3.
12 2 Yes
147
Confi guration of the output between terminal channels 5 and N
1 = Unit alarm 2 = Ambient temperature setting reached
1 2 1 Yes
148
Limit exterior temperature (T0)
This parameter defi nes the exterior temperature that is the functioning limit and where the heat pump stops. In this confi guration, only the booster heating functions. See the chapter "Confi guring the booster heating".
-20°C 65°C -20°C Yes
149
Choice of display in the command unit's temperature zone
1 = Ambient temperature 2 = Temperature of water leaving the installation 3 = Temperature of water returning to the installation 4 = Temperature of the cooling fl uid in the plate to plate exchanger 5 = Compressor suction temperature 6 = Compressor discharge temperature 7 = Exterior temperature
17 1 Yes
150
Exterior temperature bivalence point (T1)
This temperature defi nes the external temperature from which the power of the heat pump alone is not suffi cient to meet the needs of the installation. Below this temperature, the booster heating and the heat pump can function together. See the chapter "Confi guring the booster heating".
30°C -20°C 0°C Yes
151
Delays for switching on booster heating
This parameter defi nes the period from which the booster heating is switched on when: T0 < exterior T° < T1.
160
20
minutes
Yes
152
Diff erential stop/ start booster heating
This parameter defi nes the diff erential between the installation's water temperature setting and the water temperature from which the booster heating switches on when: T0 < exterior T° < T1.
1°C 20°C 5°C Yes
153
Mode of activation hot-water demand contact S5
1 = Always active (demand for hot water is always met) 2 = Activated only in heating and cooling modes (demand for hot water is met only in heating or cooling mode)
12 1 Yes
154
Booster heating functioning
This parameter de
nes the functioning of the booster heating when: exterior T° < T0. 0 = Continuous functioning 1 = ON/OFF functioning depends on the ambient temperature. In case of a thermostat fault, switch to mode 3. 2 = ON/OFF functioning depends on the installation's water temperature.
12 1 Yes
155
Functioning of main circulator
This parameter defi nes the functioning mode for the main circulator for an external temperature < T0 (code 148) 0 = Stopped 1 = ON/OFF cycle identical to the booster heating 2 = Continuous operation
02 1 Yes
156
Confi guration of the output between terminals 12 and N
Confi guration of the output (connection between terminal channels 12 and N) 0 = Not used 1 = ON/OFF cycle identical to the main pump The water pump works continuously in case of demand for hot water. 2 = ON/OFF cycle identical to the main pump The pump is halted in case of demand for hot water.
02 2 Yes
157
Functioning of the additional circulator
This parameter defi nes the functioning mode for the additional circulator for an external temperature < T0 (code 148) 0 = Stopped 1 = ON/OFF cycle identical to the booster heating 2 = Continuous operation
02 1 Yes
158
Diff erential on the temperature setting from the ambient air
This parameter defi nes the diff erential on the ambient temperature setting in the case where the parameter 100 is confi gured to 4 (regulation with the command unit used as the room thermostat).
+/-
0.2°C
+/-
1°C
+/- 0.3°C No
- advise the user of the precautions necessary to prevent damage to the system, appliance and the building;
- remind the user to service the appliance annually.
- The user shall not interfere with or adjust sealed components.
- All servicing must be carried out by a competent person approved at the time by the Health and Safety Executive.
16 User information
At the end of the installation, the installer must:
- explain the operation of the appliance and its safety devices to the user, if necessary provide a demonstration and answer any questions;
- hand over to the user all the required documentation,
- fi ll in the documents where necessary;
INSTALLATION
Page 37
0020117819_01 - 05/11 - Glow-worm
- 35 -
MAINTENANCE
i
Any work carried out on the refrigerant circuit must be conducted by qualifi ed engineers.
The faults described in this chapter require the services of a qualifi ed professional and, if necessary, a Glow-worm Groupservice engineer.
17 Trouble-shooting
17.1 Fault diagnosis
The following checks should be performed before proceeding onto specifi c diagnostics:
Make sure that the electricity supply has not been interrupted and that the appliance is connected correctly.
Ensure that the isolating valves are open.
Check that all external controls are connected correctly.
17.2 Fault codes
i
The faults described in this chapter should be carried out by a qualifi ed engineer or a Glow-worm Groupservice engineer.
17.2.1 Fault codes accessible from the install menu
When the symbol “a” blinks at the bottom left of the control box, the appliance has a fault. You should access parameters 22 (last fault code) and 23 (history of last 4 faults) on the installer menu.
Simultaneously press the (
) and ( ) buttons for 3 seconds, the parameter number is displayed and its value blinks.
Press the buttons (
) until parameter 22 or 23 is displayed.
Press the (M) button to access the parameter, the value of the parameter blinks.
Press the (
) buttons to modify the value.
Press the (M) button to con rm the parameter setting.
Press the (OK) button to exit the menu and con rm the settings.
Refer to the “Hydraulic and refrigerant schematic” chapter to
identify the sensor positions.
Code Description
3 Heat pump return temperature sensor fault (n°15)
4 Pre-regulator temperature sensor fault (n°18)
5 Remote outside air temperature sensor fault
6 Loss of communication with the command unit
7 Control box ambient air temperature sensor fault
8 Power matching fault between the electronic control circuit board
and the appliance
9 Water fl ow rate (n°10) or circulator pump (n°11) sensor fault
Code Description
10 Outside air temperature greater than the maximum in heating
(parameter 119)
11 Air temperature higher than the maximum value for heating
12 Outside air temperature greater than the maximum in cooling
(parameter 123)
14 Loss of compressor signal
15 Heat pump outlet temperature sensor fault (n°14)
17 Outside air temperature sensor fault (n°2)
18
Protection against short-circuits in G-Tr variator
20
Error in controlling the position of the compressor rotor
21
Error in current variator sensor
22 Fin exchanger (n°4) or compressor intake (n°6) temperature
sensor fault
23 Compressor outlet temperature sensor fault (n°23)
24 Outside fan fault
26 Other outside faults
27 Compressor blocked
28 Compressor outlet temperature error
29 Compressor breakdown
30 Low pressure switch
31 Over-pressure valve
17.2.2 Specifi c faults shown on the control box main screen
The faults listed below are identifi ed directly on the control box main screen.
Fault Description
Control box ambient temperature sensor fault
In the case of an anomaly in the temperature sensor measurement, the temperature display is replaced by “--“.
Control box ambient humidity sensor fault
In the case of an anomaly in the humidity sensor measurement, the ambient humidity display is replaced by “--“.
Control box EEPROM fault
If the control box non-volatile memory (EEPROM) is defective, the code “E4” is displayed in the control box temperature display area. If the power is cut after this fault is displayed, the installer and after­sales parameters will be restored to their default values and the installation-specifi c parameters will be erased. This fault can result in poor operation of the installation. In the case of an “E4” fault, replace the control box.
Communications fault If communication between the control box
and the heat pump control circuit board is disturbed, error “E3” is displayed in the ambient temperature display area. In this case, check the communication cable between the control box and the heat pump.
MAINTENANCE
Page 38
0020117819_01 - 05/11 - Glow-worm
- 36 -
18 Servicing
To ensure the continued effi cient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage.
Servicing/maintenance should be carried out by a competent person approved at the time by the Health and Safety Executive in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Glow-worm’s own service organisation.
After servicing, complete the relevant Service Interval Record section of the Benchmark Checklist located on the inside back pages of this document.
b
IMPORTANT: any action carried out on the refrigerant circuit must be performed by qualifi ed authorised personnel.
The refrigerant fl uid contains gases that, when released into the atmosphere, may aff ect the environment by depleting the ozone layer, contributing to the greenhouse eff ect and an increase in temperature. The risk of leakage cannot be excluded for devices intended to operate for many years and subject to the eff ects of the environment.
See the "Safety instructions" chapter for a list of operations to be performed prior to the maintenance of the application.
Once the maintenance operations have been completed, consult the ¨Start Up¨ chapter to restart the appliance.
Annual Maintenance
Check the proper functioning of safety devices.
Check the pressure of the water system.
Check that there are no traces of rust or oil around the cooling
circuit’s components.
Ensure that the appliance’s components are neither worn nor broken.
Check that the wires are fi rmly attached to the electrical terminals.
Check the appliance’s earthing.
Check the starting temperature of the heat pump and the
adjustment points.
Check for any ice in the compressor.
Remove any dust from the power supply.
Clean the air / refrigerant battery and make sure that air
circulates between the fi ns and around the unit.
Check that the fan rotates freely.
Check the pressure of the expansion vessel.
19 Replacement of Parts
Do not use reconditioned or copy parts, only use original parts supplied by Glow-worm.
If a part is required, contact the Glow-worm service organisation.
Please quote the name and serial number of the appliance,
this information will be on the data plate on the side of the appliance.
If in doubt seek advice from the local gas company or Glowworm’s own service organisation.
a
Replacement of parts must be carried out by a competent person approved at the time by the Health and Safety Executive.
19.2.1 Mains supply cable
e
The main supply cable must be replaced by a qualifi ed and competent electrician.
If the main supply cable is damaged, replace it refering to the chapter "Electrical connection".
20 Spare parts
In order to guarantee the safe and prolonged life of the product, manufacturers genuine spare parts must be used.
i
This appliance displays a CE Mark of conformity. Only use the manufacturer’s genuine, new spare parts.
Ensure that spare parts are correctly mounted in the right position and direction. After fi tting any spare part or servicing, the appliance must be tested for its safe operation.
MAINTENANCE
Page 39
Notes: [1] Installers should be members of an appropriate Competent Persons Scheme. [2] All installations in England and Wales must be notified to Local Area Building Control (LABC) either directly or through a Competent Persons Scheme. A Building Regulations Compliance Certificate will then be issued to the customer. [3] May be required for systems covered by G3 Regulations
© Heating and Hotwater Industry Council (HHIC)
www.centralheating.co.uk
AIR TO WATER HEAT PUMP COMMISSIONING CHECKLIST
This Commissioning Checklist is to be completed in full by the competent person who commissioned the heat pump and associated equipment as a means of demonstrating compliance with the appropriate Building Regulations and then handed to the customer to keep for future reference.
Failure to install and commission this equipment to the manufacturer’s instructions will invalidate the warranty but does not affect statutory rights.
Customer Name
Address
Telephone Number
Heat Pump Make and Model
Heat Pump Serial Number
Commissioned by (print name) Certified Operative Reg. No.
[1]
Company Name & Address Commissioning Date
Telephone No.
Building Regulations Notification Number (if applicable)
[2]
Commissioning Engineer’s Signature
Customer’s Signature
(To confirm demonstration of equipment and receipt of appliance instructions)
ALL INSTALLATIONS
The heating, hot water and ventilation systems complies with the appropriate Building Regulations Yes
All electrical work complies with the appropriate Regulations Yes
The heat pump and associated products have been installed and commissioned in accordance with the manufacturer’s instructions Yes
The operation of the heat pump and system controls have been demonstrated to the customer Yes
The manufacturer’s literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
CENTRAL HEATING MODE
Heating Flow Temperature °C Heating Return Temperature °C
ALL SYSTEMS
The heating system has been filled and pressure tested Yes
Expansion vessel for heating is sized, fitted & charged in accordance with manufacturer’s instructions Yes
The heat pump is fitted on a solid/stable surface capable of taking its weight Yes
The system has been flushed and cleaned in accordance with BS7593 and heat pump manufacturer’s instructions Yes
What system cleaner was used?
What inhibitor was used? Qty litres
Is the system adequately frost protected? Yes
OUTDOOR UNIT
Are all external pipeworks insulated? Yes
Is the fan free from obstacles and operational? Yes
Has suitable consideration been made for waste water discharge? Yes
DOMESTIC HOT WATER MODE Measure and Record
Is the heat pump connected to a hot water cylinder? Unvented Vented Thermal Store Not Connected
Hot water has been checked at all outlets Yes Have Thermostatic Blending Valves been fitted? Yes Not required
ADDITIONAL SYSTEM INFORMATON
Additional heat sources connected: Gas Boiler Oil Boiler Electric Heater Solar Thermal Other
CONTROLS - SYSTEM AND HEAT PUMP Tick the appropriate boxes if applicable
1. Time & Temperature Room Thermostat & Programmable Load/Weather Optimum Start Control to Heating Programmer/Timer Roomstat Compensation Control
2. Time & Temperature Cylinder Thermostat & Combined with Heat Control to Hot Water Programmer/Timer pump main controls
3. Heating Zone Valves (including underfloor loops) Fitted Not Required
4. Hot Water Zone Valves Fitted Not Required
5. Thermostatic Radiator Valves Fitted Not Required
6. Heat Pump Safety Interlock
[3] Built In Provided
7. Outdoor Sensor Fitted Not Required
8. Automatic Bypass System Fitted Not Required
9. Buffer Vessel Fitted Yes No If YES, Volume Litres
Page 40
Service Record
It is recommended that your heating system is serviced regularly and that the appropriate Service Interval Record is completed.
Service Provider
Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the manufacturer’s instructions.
Always use the manufacturer’s specified spare part when replacing controls.
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Date:
Engineer Name:
Company Name:
Telephone No.
Operative ID No.
Comments:
Signature:
Service 1 Service 2
Service 3 Service 4
Service 5 Service 6
Service 7 Service 8
Service 9 Service 10
Page 41
Page 42
Page 43
Page 44
0020117819_01 - 05/11
GLOW-WORM
Nottingham Road, Belper, Derbyshire. DE56 1JT
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
www.glow-worm.co.uk
Subject to engineering changes
Loading...