Glow Worm Betacom 24a/28a INSTALLATION AND SERVICING (0020105022_01 - 12/10)

Page 1

Glow-worm

Installation and Servicing

Betacom 24a G.C. No. 47-019-13

Betacom 28a G.C. No. 47-019-14

Page 2

Page 3

TABLE OF CONTENTS

INTRODUCTION

1 Instructions guidance 3
1.1
1.2
1.3
1.4
Product documentation
Associated documents
Explanation of symbols
Guarantee registration
3
3
3
2 Appliance description 3
2.1
2.2
2.3
2.4
2.5
Safety devices
Data label
Gas category
Regulation and statutory requirements
Hydraulic schematic
3
4
4
4
5
3 Safety instructions and regula itions 6
3.1
3.2
Safety instructions
Regulations
6
6
4 Recycling 7
4.1
4.2
Appliance
Packaging
7
7

TECHNICAL DATA

INSTALLATION

6 Appliance location 9
6.1
6.2
6.3
Location
Clearances
Ventilation
7 Appliance installation 10
7.1
7.2
7.3
7.4
Scope of delivery
Recommendations before installing
Dimensions
Mounting
8 Hydraulic connection - 14
8.1
8.2
8.3
Gas and water connections
Safety Discharge Valve
Connection to the condensate trap
9 Evacuation of combustion n gas 17
9.1
9.2
Regulation
Flue configuration description
17
17
10 Remove the front panel 19
11 Electrical connections
11.1
11.2
11.3
11.4
11.5
11.6
Access to main board
Main board
Electrical wiring
External accessories
Testing the electrical connections
Wiring diagram
20
20
20
21
21
21
22
Page 4

TABLE OF CONTENTS

12 Commissioning 23
- 12.1 Switching on 23
12.2 Filling the CH system (Central heating)
12.3 Filling DHW Circuit
12.4 Filling the Condensate Trap
12.5 Initial lighting
12.6 Gas rates
12.7 Testing heating system 25
12.8 Testing domestic hot water system.
12.9 Completion 25
13 Specified Adjustment
13.1 Heating circuit adjustment
14 Installation settings
14.1 CO. measurement
14.2 Re-check and restart
15 User information

MAINTENANCE

16 Trouble-shooting
16.1 Fault diagnosis
16.2 Fault memory 31
16.3 Fault codes
16.4 Functional flow diagram
17 Gas conversion adjustments 34
17.1 Settings
17.2 Restart - re-check commissioning 35
18 Draining
18.1 Heating circuit 36
18.1 Domestic Hot water circuit
10 Servicing 36
13
19.1 Annual Maintenance
19.2 Casing removing
19.3 Compussion check and setting the air/gas ratio valve
19.4 Servicing
19.5
19.0 Condonsato tran
19.7 Compustion block
19.0 Service completion
19.9
20 Replacement of Parts 42
20.1 General 43
20.2 Boiler Access 43
20.3 Viewing window 43
20.4 Hydraulic block 44
20.5 Combustion block 46
20.6 Condensate trap 48
20.7 PCB 48
21 Spare parts 49
21.1 Short List of Parts
21.2 Short List of Parts
22 Manual Handling
-
23 Declaration of Conformity
Page 5

INTRODUCTION

1 Instructions guidance

1.1 Product documentation

The instructions are an integral part of the appliance and must be handed to the user on completion of the installation in order to comply with the current regulation.

• Carefully read the manual, to understand all the information to enable safe installation, use and servicing. No liability can be accepted in the event of damage for not complying with the guidance in this instruction manual.

These instructions consist of, Installation, Servicing, Fault Finding, Replacement of Parts and Spares. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.

1.2 Associated documents

  • 1 Instructions for use
  • 1 magnetic lighting instruction label
  • 1 flue guide
  • 1 extended guarantee leaflet
  • 1 guarantee envelope pack
  • 1 wall template
  • 1 gas conversion label
1.3 Explanation of symbols

DANGER: Risk of injuries.

DANGER: Risk of electric shock.

ATTENTION: Risk of damage to the appliance or to its surroundings.

IMPORTANT: Important information

1.4 Guarantee registration

Thank you for installing a new Glow-worm appliance in your home. Glow-worm appliances are manufactured to the very highest standard so we are pleased to offer our customers a Comprehensive 12 month Guarantee.

We recommend you complete and return as soon as possible your guarantee registration card. If your guarantee registration card is missing you can obtain a copy or record your registration by telephoning the Glow-worm Customer Service number 01773 828100.

2 Appliance description

2.1 Safety devices
2.1.1 Overheating safety

The appliance is designed to recognise the potential for an overheat lockout and will shutdown before this happens.

2.1.2 Safety discharge valve

A safety discharge valve and discharge pipe are fitted to the boiler. This valve must not be touched.

  • The heating safety valve opens when the pressure in the heating circuit exceeds 3 bars.
  • Should there be any discharge from the pipe, isolate the boiler electrical supply and call your installer or Glow-worm's own service organisation.
2.1.3 Frost protection

The frost protection system operates the pump to start as soon as the temperature in the heating circuit falls below 12°C. The pump stops as soon as the temperature of the water contained in the heating circuit reaches 15°C.

If the temperature in the heating system falls below 7°C, the burner ignites until it reaches 35°C.

The frost-protection system is active when the appliance is switched on.

The system alone cannot ensure that the installation is protected against frost. An separate frost thermostat is necessary to control the temperature of the system.

Your domestic water circuit (hot or cold) is not protected by the boiler.

2.1.4 Condensate drain blockage

During freezing conditions this may be due to the forming of ice in the condense drain external to the house. In this case, a safety device shuts down the appliance.

Page 6
22 Data label

The data label certifies the country where the appliance is intended to be installed

Data label location

Data label

The data label contains the following data:

  • The name of the manufacture
  • The country of intended destination
  • The commercial name of the appliance and its serial number
  • The types of flues installations authorised
  • The appliance's gas category
  • The gas type group and pressure set in the factory
  • The DHW specific flow rate (D)
  • The maximum pressure in the heating circuit (PMS)
  • The maximum pressure in the domestic water circuit (PMW)
  • The NOx class of the appliance
  • The type and voltage of electricity supply
  • The maximum power rating
  • The electrical protection class
  • The minimum and maximum heat input (Q)
  • The minimum and maximum power output (P)
  • The CE number and logo

The appliance shall only be connected to the gas type(s) indicated on the data label.

Gas category

This boiler is for use only on G20, but can be converted for use on C31

• To adapt the appliance to another type of gas, see the chapter "Gas conversion".

24 Regulation and statutory requirements
241 CE Mark

This boiler meets the requirements of Statutory Instrument. No. 3083 The Boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.

Type test for purposes of Regulation 5 certified by: Notified body 1312

Product/production certified by: Notified body 0086.

The CE mark indicates that the appliances described in this manual are in compliance with the following directives:

  • European directive n°2009-142 relative to gas appliances
  • European directive n°2004-108 from the European Parliament and Council relative to electromagnetic compatibility
  • European directive n°2006-95 from the European Parliament and Council relative to low voltage
  • European directive n°92-42 relative to the yield of boilers
242 Local regulations

Benchmark places responsibilities on both manufacturers and installers. The purpose is to ensure that customers are provided with the correct equipment for their needs, that it is installed, commissioned and serviced in accordance with the manufacturer's instructions by a competent person approved at the time by the Health and Safety Executive and that it meets the requirements of the appropriate Building Regulations. The Benchmark Checklist can be used to demonstrate compliance with Building Regulations and should be provided to the customer for future reference.

Installers are required to carry out installation, commissioning and servicing work in accordance with the Benchmark Code of Practice which is available from the Heating and Hotwater Industry Council who manage and promote the Scheme.

Visit www.centralheating.co.uk for more information.

Page 7
2.5 Hvdraulic schematic

Key

  • Gas isolating valve
  • 2 Heating flow isolating valve
  • Heating safety valve 3 4 Filter on cold water inlet
  • 5 DHW flow sensor 6 Water pressure sensor
  • Domestic plate to plate heat exchanger 8
  • Three way valve
  • 9 By-pass
  • 10 Heating return thermistor
  • 11 Condensate trap 12 Ignition and control electrode
  • 13 Burner
  • 14 Main heat exchanger 15 Thermal fuse
  • 16 Flue outlet
  • 17 Silencer

  • 18 Heating expansion vessel
  • 19 Fan
  • 20 Gas control valve
  • 21 Ignition module
  • 22 Heating flow thern
  • 23 Air vent
  • 24 Pump
  • 25 Heating return isolating valve
  • 26 Domestic cold water isolating valve
  • Heating flow Α
  • B Pipe for heating safety valve
  • c Domestic hot water outlet
  • Gas
  • E Cold water inlet Heating return
  • F
  • G Condensate drain
Page 8

3 Safety instructions and regulations

3.1 Safety instructions

If the gas pressure at the input of the appliance is outside the range specified, the appliance must not be put into operation.

Incorrect installation can cause electric shock or appliance damage.

• Never disable security devices and do not try to adjust them.

With regards to the "Manual Handling Operations, 1992 Regulations", the appliance exceeds the recommended weight for a one person lift.

The handling of the boiler may involve lifting, pushing and pulling, the use of a sack truck may be required.

  • Be sure to consider the following handling techniques and precautions:
  • Grip the appliance at its base
  • Use safety clothing where appropriate, e.g. gloves, safety footwear.
  • Ensure safe lifting techniques are used:
  • Keep back straight.
  • Avoid twisting at the waist.
  • Avoid upper body/top heavy bending
  • Always grip using the palm of the hand.
  • Use designated hand holds.
  • Keep load as close to body as possible
  • Always use assistance if required.
  • Under no circumstances must the user interfere with or adjust sealed parts.
  • When assembling the connections, correctly position the seals to avoid any leakage of gas or water.
  • This appliance contains metal parts (components) and care should be taken when handling and cleaning, with particular regard to edges.

The basic safety instructions must be followed before attempting to maintain or replace spare parts:

  • · Stop the appliance.
  • Electrically isolate the appliance from the power supply.
  • Turn off the appliance gas isolation valve.
  • Hydraulically isolate the appliance using the isolation valves if provided.
  • Should you need to replace hydraulic components, drain the appliance.
  • Protect all the electrical components from water while working on the appliance.
  • Use only original spare parts.

  • Use only new O-rings and gaskets.
  • After having completed work on gas or water carrying components, check for their tightness.
  • When work on the appliance is completed, perform an operational test and check for safety.
3.2 Regulations
3.2.1 Statutory requirements
IMPORTANT

Where no British Standards exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.

The installation of this boiler must be carried out by a competent person approved at the time by the Health and Safety Executive and in accordance with the rules in force in the countries of destination.

Manufacturer's instructions must not be taken as overriding statutory requirements.

Statutory Requirements

In GB, the installation of the boiler must comply with the requirements of the current issue of BS6798 and be carried out by a competent person approved at the time by the Health and Safety Executive and as described in the following regulations:

  • The manufacturer's instructions supplied.
  • The Gas Safety (Installation and Use) Regulations.
  • The appropriate Buildings Regulations either The Building

Regulations, The Building Regulations (Scotland), The Building Regulations (Northern Ireland).

- The Water Supply (water fittings) Regulations 1999 and water byelaws 2000, Scotland.

- The Health and Safety at Work Act, Control of Substances Hazardous to Health (COSHH).

- Any electrical work must conform to BS7671 and part P of the building regulations where applicable.

Where no specific instructions are given, reference should be made to the relevant British Standard Code of Practice.

In IE, the installation must be carried out by a competent person approved at the time by the Health and Safety Executive and installed in accordance with the current edition of I.S.813 "Domestic Gas Installations", the current Building Regulations and reference should be made to the current ETCI rules for Electrical Installation.

GB: the following Codes of Practice apply: BS4814, BS6798, BS5440 Part 1 and 2, BS5546 Part 1, BS5449, BS6891, BS6700, BS7074 Part 1 and 2, BS7593, BS7671. IE: I.S.813, BS5546, BS 5449, BS 7074, BS 7593.

NOTE: For further information, see the current issue of the Building Regulations, approved document L1 ( in the UK) and the following current issues of:

Central heating system specification (CheSS) and Controls for domestic central heating system and hot water. BRECSU.

Page 9

Gas Supply

The gas installation must be in accordance with the relevant standards.

In GB. this is BS6891.

In IE, this is the current edition of I.S.813 "Domestic Gas Installations".

The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler. On completion, test the gas installation for tightness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.

Domestic Hot Water

All domestic hot water circuits, connections, fittings must be in accordance with the relevant standards and water supply regulations.

GB: Guidance G17 to G24 and recommendation R17 to R24 of the Water Regulations Guide.

IE: The current edition of I.S.813 "Domestic Gas Installations".

Heating System

In GB, it is necessary to comply with the Water Supply (Water Fittings) Regulations 1999 (for Scotland, the Water Byelaws 2000, Scotland). To comply with the Water regulations your attention is drawn to: The Water Regulations guide published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements.

In IE, the requirements given in the current edition of I.S.813 "Domestic Gas Installations" and the current Building Regulations must be followed

Electrical Supply

The boiler MUST be earthed. All system components shall be of an approved type and all wiring to current I.E.E. wiring regulations. External wiring must be correctly earthed, polarised and in accordance with the relevant standards.

In GB. this is BS 7671.

In IE, this is the current edition of ETCI rules.

The boiler MUST be connected to a permanent 230V ac, 50Hz supply.

Connection of the whole electrical system of the boiler, including any heating controls, to the electrical supply MUST be through one common isolator and must be fused 3 Amp maximum.

Isolation should be by a double pole switched fused spur box, with a minimum gap of 3mm for both poles. The fused spur box should be readily accessible and preferably adjacent to the appliance. It should be identified as to its use.

Alternatively connection can be made through an unswitched shuttered socket and 3A fused 3-pin plug both to the current issue of BS 1363, provided they are not used in a room containing a bath or shower.

Wiring to the boiler must be PVC 85OC insulated cable, not less than 0.75mm2 (24/0.20mm).

3.2.2 Other regulations
Gas Safety (Installation and Use) Regulations

In your own interests and that of safety, it is the Law that ALL gas appliances are installed by a competent person approved at the time by the Health and Safety Executive in accordance with the current issue of these regulations.

Control of Substances Hazardous to Health

Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.

Insulation Pads

These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken.

Normal handling should not cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory.

• If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.

4 Recycling

The recycling of the packaging must be carried out by the qualified professional who installed the appliance.

4.1 Appliance

Most of the appliance is made of recyclable materials.

This symbol indicates that this appliance must not be disposed of with household waste, that it should be selectively collected for energy recovery, reuse or recycling.

Take the appliance to an appropriate collection point.

By complying with this directive, you will contribute to the preservation of natural resources and the protection of human health.

4.2 Packaging

We recommend that you recycle the packaging of the appliance in a responsible fashion.

  • Sort the waste in order to separate those elements which can be recycled (cardboard, plastics ...) and those which cannot be recycled.
  • Dispose of waste in accordance with existing regulations.
Page 10

TECHNICAL DATA

5 Betacom a

Boiler, type C13, C33, C43

Description Unit 24 a 28 a
Gas category II 2H3P II 2H3P
SEDBUK rating 2009 % 89.0% 89.2%
SEDBUK rating 2005 % 90.0% 90.1%
Heating
Maximum heating input power kW 18.5 25
Minimum heating output
power at 80/60°C (P min.)
kW 7.7 9.3
Maximum heating output
power at 80/60°C (P max.)
kW 18.0 24.5
Minimum heating output
power at 50/30°C (P min.)
kW 8.5 9.9
Maximum heating output
power at 50/30°C (P max.)
kW 19.6 26.7
Minimum heating temperature °C 10 10
Maximum heating temperature °C 80 80
Minimum heating flow rate l/h 400 400
Content of heating expansion 8 8
vessel gallons 1.76 1.76
Heating expansion vessel bar 0.75 0.75
preset pressure psi 10.9 10.9
Maximum heating system volume (approx) Ι 160 160
Heating safety valve preset bar 3 3
pressure (PMS) lbf/in 2 36/3 36/3
Domestic Hot Water
Minimum DHW output power
(P min.)
kW 8 9.3
Maximum DHW output power
(P max.)
kW 24 28
Maximum DHW temperature °C 60 60
Specific flow rate ( \Delta T of 35 K) l/min 9.8 11.2
Minimum inlot water prossure bar 0.3 0.3
psi 4.3 43
Maximum inlet water pressure bar 10 10
psi 145 145
Combustion
Appliance NOx class 5 5
Electrical
Electrical supply V/Hz 230∨
50Hz
230V
50Hz
Standby mode electrical
power
W 6 6
Operational mode electrical
power (Max)
W 151 151
Internal fuse rating on main PCB А 2 2
Index of electrical protection
(EN 60529)
IPX4D IPX4D
Description Unit 24 a 28 a
Gas connection Ø O.D. mm 15 (copper) 15 (copper)
Heating flow and return connection Ø O.D. mm 22 (copper) 22 (copper)
Domestic Hot Water
connection Ø O.D.
mm 15 (copper) 15 (copper)
Condensate connection Ø I.D. mm Pushfit
Plastic
Pushfit
Plastic
Safety valve discharge
connection Ø O.D.
mm 15 (copper) 15 (copper)
Lift weight kg 37 38
lb 82 84.8
Total weight (installed) kg 42 43
Number of CE certificate 1312 BU
5334
1312 BU
5335
Description Unit 24 a 28 a
Natural Gas G 20 (15 °C, 1013 .25 mbar)
Maximum DHW gas flow rate m³/h 2.54 2.96
Maximum heating gas flow rate m³/h 1.96 2.64
Minimum gas flow rate m³/h 0.85 0.98
CO 2 at Qmax DHW +
"tolerance case ON"
% 9.2 ± 0.3% 9.2 ± 0.3%
CO 2 at Qmax DHW +
"tolerance case OFF"
% 9.0 ± 0.2% 9.0 ± 0.2%
CO 2 at Qmin +
"tolerance case ON"
% 8.9 ± 0.3% 8.9 ± 0.3%
CO 2 at Qmin +
"tolerance case OFF"
% 8.7 ± 0.2% 8.7 ± 0.2%
Inlet pressure mbar 20 20
Propane Gas G 31 (15 °C, 101 3.25 mbar) -
Maximum DHW gas flow rate kg/h 1.87 2.17
Maximum heating gas flow rate kg/h 1.44 1.94
Minimum gas flow rate kg/h 0.62 0.72
CO 2 at Qmax DHW +
"tolerance case ON"
% 10.3 ±
0.3%
10.3 ±
0.3%
CO 2 at Qmax DHW +
"tolerance case OFF"
% 10.1 ±
0.3%
10.1 ±
0.3%
CO 2 at Qmin +
"tolerance case ON"
% 9.8 ± 0.3% 9.8 ± 0.3%
CO 2 at Qmin +
"tolerance case OFF"
% 9.6 ± 0.2% 9.6 ± 0.2%
Inlet pressure mbar 37 37
Page 11

INSTALLATION

INSTALLATION

All the drawings dimensions are shown in mm.

6 Appliance location

6.1 Location

6.1.1 Instructions

Before choosing a site for the appliance, carefully read the safety warnings and installation manual.

  • Ensure that wall to which the appliance will be mounted on is structurally safe in order to support the weight of the appliance.
  • Ensure that the space that the appliance is to be installed within allows the appliance to be installed and the clearances maintained. This will ensure that the connections to the water, gas and flue can be accessed and inspected (see chapter Clearances).
  • Explain these requirements to the appliance user.
  • Do not install the appliance above another appliance that could damage it (for example, above a cooker that might emit steam or grease) or in a room, which has a lot of dust in the atmosphere which is corrosive.
  • The boiler must be fitted inside the property and exposed pipe work may need to be protected from frost by fitting a frost thermostat.
6.1.2 Regulations
Location

This boiler is not suitable for outdoor installation. This boiler is suitable for installation in bathroom zones 2 and 3. In GB this is the current I.E.E. WIRING REGULATIONS and BUILDING REGULATIONS.

In IE reference should be made to the current edition of I.S.813 "Domestic Gas Installations" and the current ETCI rules.

Timber Frame Buildings

If the boiler is to be installed in a timber frame building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from local gas undertaking or Glow-worm.

6.2 Clearances

• To allow periodic maintenance, ensure the distances indicated on the diagram.

Additional clearances may be beneficial around the boiler for installation and servicing.

For flue installations where external access is not practicable, consideration should be given for the space required to insert the flue from inside the property, which may necessitate clearance larger than those specified in diagram below.

Key

A removable compartment door can be placed a minimum 5 mm in front of appliance. A clearance of 600 mm is required from a fixed surface.

The boiler and flue are suitable for installation onto and through combustible materials provided that:

  • Minimum 5mm clearance is maintained around the circumference of the flue (air intake).
  • The combustible surface and fixings are suitable for supporting the load.
  • The minimum clearances from the boiler case are maintained.

6.3 Ventilation

6.3.1 Room Ventilation

The boiler is room sealed so a permanent air vent is not required.

6.3.2 Cupboard or Compartment Ventilation

Due to the high efficiency and low casing temperature of this boiler, cupboard or compartment ventilation is not necessary.

• Existing ventilation should be investigated for its purpose before removing.

Page 12

7 Appliance installation

7.1 Scope of delivery

The appliance is delivered in a single carton with a document pack and fittings.

The flues package will be ordered according to the configuration of the installation.

• Please check the contents.

7.2 Recommendations before installing

7.2.1 Domestic hot water circuit design
Water pressure

The minimum working pressure to obtain the maximum domestic flow is 1,0 bar.

The maximum working pressure of the domestic hot water circuit is 10 bar. If the cold water supply pressure exceeds this, then a pressure-reducing valve must be fitted in the supply to the boiler.

'Hard' water areas

The temperatures within the heat exchanger are limited by the boiler control system to minimise scale formation within the hot water pipework. However, in areas where the water is 'hard' (i.e. more than 200 mg/L of calcium carbonate), it is recommended that the hot water setting is reduced and that a scale reducer is fitted, refer to the manufacturer's instructions or consult the local water company for additional advice.

Domestic water flow rate

The domestic hot water flow has a restrictor, factory fitted, which reduces the flow to a maximum of:

  • 24a ► 8/min,
  • 28a ► 10/min,
Central Heating water flow rate

If it is necessary to alter the flow rate, the system can be fitted with a lockable balancing valve in the main flow or return pipes.

- Heating circuit design

Page 13

  • Additional expansion vessel (if required)
  • Heating return circuit
  • Heating flow circuit ä
  • Optional balancing valve
General

This boiler is designed for use as part of a sealed water central heating system with fully pumped circulation. The pump. expansion vessel and associated safety devices are all fitted within the boiler.

Safety valve

The safety valve is an integral part of the boiler and it cannot be adjusted. The pipe from the safety discharge valve must discharge safely in accordance with standards.

Expansion vessel

The boiler has an integral expansion vessel with a capacity of 8 litres (1.76 gallons) with a charge pressure of 0.75bar

The heating system volume should be calculated to ensure that the expansion vessel is suitable, it may be necessary to add an additional vessel.

  • In GB. Guidance on vessel sizing is also given in the current issue of BS5449 and BS7074 Part 1.
  • In IE, current edition of I.S.813 "Domestic Gas Installations".
Bypass

The boiler is fitted with an automatic bypass

Ensure that under no circumstances does the flow rate drop below the figure specified, refer to chapter "Technical data".

Filling the sealed system

i

The boiler does not contain any filling loop, an external one must be fitted.

Suitable external filling systems are shown diagrammatically see diagram below.

  • ng flow circuit
  • Heating return circuit
  • 4 ible check valve assembly
  • 5 mestic cold water supply in
  • 6 mporary filling loop (remove immediately after filling)
  • Drain noint
  • 8 ack flow prevention device

The system should be pressurised to 0.8bar indicated on the digital display with no heating demand.

Drain points

Drain taps must be provided at all low points of the system. which will allow the entire system to be drained.

Drain taps shall be to the current issue of BS2879

Water treatment

Existing system- It is essential that prior to installing the new boiler the system is thoroughly flushed.

New system - For optimum performance after installation the boiler and its associated central heating system should also be fluchod

Flushing shall be carried out in accordance with BS 7593, a chemical cleanser can be used either Sentinel X300, X400 or Fernox F3 are suitable.

It is recommended to flush existing systems first before fitting the new boiler

Ensure all cleanser is removed from the whole system before adding an inhibitor.

For long-term corrosion protection after flushing, an inhibitor suitable for stainless steel heat exchangers can be used. Fither Sentinel X100 or Fernox F1 inhibitor can be used

The boiler is suitable for use on systems using softened water.

Page 14
7.3 Dimensions

7.4 Mounting

  • Make sure that the equipment used for implementing the installation is compatible with that of the appliance.
  • Determine the assembly location. See the "Appliance location" chapter.

  • 80/125 flue ► Ø150mm 80/125 flue ► Ø130mm 80/125 flue ► 156mm
  • ***
  • Take the wall template and place in the desired position on the wall, giving due consideration to the required boiler clearances, see chapter "Appliance location ► Clearances", and the flue you are fitting.
Page 15
7.4.1 Fixing to the wall

i

The flue is designed with an internal fall of 44mm/ metre (2.5°), therefore the hole can be drilled horizontally.

  • Use a 105mm diameter core drill for external access flue installation (60/100 flue) (80/125 flue ► Ø130mm).
  • Use a 125mm diameter core drill for internal access only flue installation (60/100 flue) (80/125 flue ► Ø150mm).

If flue extension pipes are to be used then a core drill size of 125mm is required. This will allow the extension pieces to slope at 44mm/metre (2.5°) towards the boiler.

  • If fitting a side flue, extend the flue centre line into the corner then 130mm along the adjacent wall.
  • If fitting an extended side flue, determine the flue hole centre by extending the dashed inclined line on the template to the side wall. This dashed line is drawn at 44mm/metre (2.5°) rise from the boiler. Where this line reaches the side wall, a horizontal line should be marked. The vertical centre line of the flue should then be marked at 130mm from the back wall. To allow for the flue passing through the wall at this angle a 125mm hole should be drilled irrespective of internal or external installation.
Hanging bracket fixing

Due to the varied site conditions the fixings supplied may not be suitable, please make sure that those used are.

  • Drill the holes for the fixing screws in accordance with the wall template.
  • Fix the hanging bracket on the wall.
7.4.2 Boiler hanging

With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one person lift, refer to chapter "Manual Handling".

1 Boller

  • 2 Hanging brack
  • Lifting the boiler into position, lean the top of the boiler slightly to the wall and position just above the hanging bracket.
  • Lower the boiler slowly and engage onto the hanging bracket
Page 16
Hydraulic connection
8 1 Gas and water connections

The whole of the gas installation including the meter should be inspected, tested for tightness and purged in accordance with the current issue of BS6891 and in IE the current edition of I.S.813 "Domestic Gas Installations"

The appliance may contain a small amount of water. place a water container beneath the boiler connections

  • Take care to clean the pipes before assembly removing any debris or burrs. Grease and oils may need to be removed they are not possible to remove by cleansing and flushing. Foreign bodies in the system may enter the appliance and interrupt its operation.
  • Do not use any solvent products, due to the risk of damaging the circuit

Do not perform any 'hot work' directly under the appliance, this may cause damage to the appliance base. Heat may also damage the isolation valves

Always pre-assemble pipes before fitting them to the boiler

  • Only use original seals supplied with the appliance.
  • Check that there are no leaks. Repair if necessary.
  • Check the cold water inlet filter is fitted ( located in the appliance cold water inlet pipe).

  • Kev
  • Heating return isolating valve + sealing washer 3/4"
  • Cold water inlet isolating valve + sealing washer 1/2"
  • 3 Gas service isolating valve with pressure test point + sealing sher 1/3"
  • Domestic hot water outlet isolating valve + sealing washer 1/2"
  • Heating flow isolating valve + sealing washer 3/4 Connection Ø O D 22 mm
  • Connection Ø O.D. 15 mm
  • Gas connection Ø O.D. 15 mm
  • Use only the original gas cock GER/1 DN15, CE-0085 CL
  • Use only the olive and flat seal washer supplied with the gas cock

  • Remove the protective caps from the boiler connections.
  • Flush out the domestic hot water and the heating systems.

i

Before turning on the cold mains supply to the boiler turn off the cold water inlet to the boiler. lock the filling loop in the closed position and close its filling taps.

82 Safety Discharge Valve

  • Discharge pipe 15mm o.d.
  • ressure relief valve PRV
  • aining outlet
  • PRV outlet to outside

This must be extended, using not less than 15mm o.d. pipe, to discharge, in a visible position, outside the building, facing downwards preferably over a drain

To ease future servicing it is advisable to use a compression type fitting to extend the safety discharge valve tube.

The nine must have a continuous fall and be routed to a position so that any discharge of water possibly boiling or steam cannot create any danger to persons, damage to property or external electrical components and wiring.

Page 17
8.3 Connection to the condensate trap

Condensate produced by the appliance is mildly acidic (pH 3.5 - 5.0). Use protective gloves

Condensate must only be discharged in accordance with these instructions.

The volume of condensates evacuated can reach about 15 litres per day for a detached house. This volume is negligible compared to the volume of waste water discharged by a house, because the condensates are diluted in this water.

Refer to BS5546 and BS6798 for advice on disposal of boiler condensate

Key

  • 1 Condensate pipe
  • 2 Condensate outlet pushfit

Make sure there is no protective plug fitted. Connect the condensate pipe (1) to the condensate outlet (2).

The pipe should have a fall of a least 2.5° 44mm/ metre away from the boiler.

Condensate should, if possible be discharged into the household internal drainage system.

If this is not practicable, discharge can be allowed into the external household drains or a purpose designed soak away, refer to diagram overleaf.

It is recommended that any external condensate drain pipe is protected and also preferably of 32mm diameter, to prevent freezing in adverse weather conditions.

• Always ensure the pipe is installed with the correct fall

Connect the boiler condensate drain (1) to a condensate discharge pipe which should be minimum of 19 mm internal diameter and be made of an acid resistant material (e.g. plastic overflow pipe). Do not use metal pipes. It is permissible to use a condensate neutraliser providing that it is checked for correct operation.

External Termination to a Gulley or Hopper

Page 18

9 Evacuation of combustion gas
9.1 Regulation

Only flue accessories supplied by Glow-worm must be used.

Different flue outlet configurations can be carried out

Consult your supplier for more information about the other possibilities and associated accessories.

Standard flue terminal kits have an in-built fall back to the boiler to drain the condensate. These can be fitted level between the appliance and the termination position. All other extended flues must have a fall of at least 44mm/m

The maximum length of the flue outlet is defined according to its type (for example C13).

  • Whatever the kind of flue system chosen, observe the minimum distances indicated in the chart below to position the flue terminals.
  • To install the flue, refer to the separate flue instruction supplied with your appliance.
  • Explain these requirements to the user of the appliance.

If necessary, you must install a flue terminal guard.

Ĩ

Caution! The connection between the flue elbow and the flue outlet must be sealed.

In GB the minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in diagram overleaf.

In IE the minimum distances for flue terminal positioning must be those detailed in I.S.813 "Domestic Gas Installations".

The terminal must be exposed to the external air, allowing free passage of air across it at all times.

Being a condensing boiler some pluming may occur from the flue outlet. This should be taken into consideration when selecting the position for the terminal.

Carports or similar extensions of a roof only, or a roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if made of plastic sheeting. If the carport comprises of a roof and two or more walls.

Page 19

If the flue terminal is positioned near a light source insects may enter the flue system. Where safe and practical to do so advise the

homeowner to check the flue outlet and clear visible insects from the terminal end.

Position Position of the flue terminal mm
Horizontal flues
А directly below an opening, air brick, opening windows 300
В above an opening, air brick, opening windows 300
С horizontally to an opening, air brick, opening windows 300
D below gutter, drain/soil pipe 25
Е below eaves 25
F below a balcony or car port 25
G from vertical drain pipes and soil pipes 25
Н from internal/external corners 25
H* to a boundary alongside the terminal 300
Ι above adjacent ground or balcony level 300
J* from surface or a boundary facing the terminal 600
L from opening (door/window) in car port into dwelling 1200
М vertical from a terminal 1500
N horizontally from a terminal 300
Vertical flues
Р from another terminal 600
Q above roof level 300
R from adjacent opening window 1000
S from adjacent wall to flue 300

(*) These dimensions comply with the building regulations. but they may need to be increased to avoid wall staining and nuisance from pluming depending on site conditions.

  • 9.2 Flue configuration description
  • 9.2.1 Horizontal concentric flue Ø 60/100 mm or Ø 80/125 mm (C13 type installation)

If necessary, you must install a terminal protection kit.

et (fitte

Key

1 Gasket (fitted)

Туре Max length
Ø 60/100 6 m
Ø 80/125 10 m
Each time an additional 90° bend is necessary (or 2 at 45°), the
length (L) must be reduced by 1 m

0020105022 01 - 12/10 - Glow-worm

Page 20

922 Vertical concentric flue Ø 60/100 mm or Ø 80/125 mm (C33 type installation)

Туре Max length (L)
Ø 60/100 6 m
Ø 80/125 10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the length (L) must be reduced by 1 m.

9.2.3 Multiple boiler chimney flue Ø 60/100 mm (C43 type installation)

The flue connecting from the appliance to the flue system must be supplied from the manufacturer of the boiler.

C43 flue systems must not be a 'pressurised system' but act under natural draught principles

C43 type flue systems must have their own condensate drain fitted and not allow condensate to mix into other appliances

Ke

  • ure balancing system
  • 2
  • 3 Collector pipe
  • 4
  • Final storey ound floo
Туре Max length (L)
Ø 60/100 10 m

Each time an additional 90° bend is necessary (or 2 at 45°), the length (L) must be reduced by 1 m.

Model 24a 28a
Exhaust mass rate (g/s)
At min thermal load (40°C/30°C) 2.4 2.9
At max thermal load (80°C/60°C) 8.3 11.3
Exhaust temperature (°C)
At min thermal load (40°C/30°C) 45 37
At max thermal load (80°C/60°C) 65.7 63.4
Page 21

10 Remove the front panel

  • Front panel retaining screw
  • Undo the two screws (2) on the underside of the front panel and remove the front panel (1).

11 Electrical connections

Incorrect installation can cause electric shock or appliance damage. The electrical connection of the appliance must be made only by a qualified engineer.

The appliance must be connected directly to an accessible. fixed, switched, electrical outlet.

The external wiring must be earthed with correct polarity and in accordance with current standards.

The manufacturer declines any responsibility for damages to persons or others caused by the incorrect installation of the appliance earthing. This includes failure to comply with current standards

Electrical components have been tested to meet the equivalent requirements of the BEAB.

• Do not use cable greater than 10 mm in diameter for the electrical connections.

All system components must be of an approved type.

Do not interrupt the mains supply with a time switch or programmer.

The boiler is suitable for installation in bathroom zones 2 and 3.

11.1 Access to main board

Kev

  • 24 V access cove
  • minal blocks for 24 V connection
  • ninal blocks for 230 V connection
  • 220 V access COVer
11.2 Main board

  • Insulation

When you connect the electrical wires to a connector on the electronic board:

  • Keep a distance of a maximum of 30 mm between connector (1) and the start of the insulation (3).
  • If using single core wires are used(2) ensure that the are wrapped together in an insulating sheath.
  • Fix the cables in the cable-clamp on the eBox.
Page 22
11.3 Electrical wiring

Connection of the whole electrical system and any heating system controls to the electrical supply must be through a common isolator.

Isolation should preferably be by a double pole switched fused spur box having a minimum contact separation of 3mm on each pole. The fused spur box should be readily accessible and preferably adjacent to the boiler. It should be identified as to its use.

A fused three pin plug and shuttered socket outlet may be used instead of a fused spur box provided that it is not used in a room containing a fixed bath or shower.

Key

1 Power supply cable

  • Connect the appliance's power cable to the 230 V singlephase network + earth.
  • Connect the appliance in accordance with the live and neutral connections.
11.3.1 230V permanent supply

All cables connected to the appliance should be permanently fixed to the wall.

i This appliance will not operate without a link or system controls fitted.

Key

  • 1 230V permanent supply 2 Main board terminal bloc
  • () = Mains earth N = Mains peutra
  • L = Mains live
  • 3 Fuso
  • 4 Double pole connector
  • · Connect mains supply as described.
Page 23
11 3 2 230V permanent supply + 230V system controls

  • 230V permanent supply
  • 2 System controls
  • Frost stat
  • ain board terminal block 4 FP = Frost stat 230V (switchable)
    • T = Switch live (230V) (1) = Mains earth
    • = Mains neutra
    • I = Mains live
  • Junction box Fuse
  • Double pole connector
  • Connect the mains supply and system heating controls e.g. room thermostat as described
  • When installing a 230v controller, the link fitted to the 24v terminals (RT/24v) must be removed.

11.4 External accessories

Under no circumstances must any mains voltage be applied to any of the terminals on the 24v nection plug

  • 24V room thermostat conne
  • Ebus room thermostat con or Ebus radio receiver
  • Fit external controls in accordance with the rules in force
  • When installing a non eBus controller, the link fitted to the 24V terminals (RT/24V) must be removed.
11.5 Testing the electrical connections

Carry out preliminary electrical system checks as below:

  • Resistance to earth (<1 Ohm)
  • Short circuit test (L-N)
  • Resistance to earth (L-E)
  • Polarity check
Page 24

11.6 Wiring diagram

Page 25

12 Commissioning

i

At the time of commissioning, complete all relevant sections of the Benchmark Checklist located in the centre pages of this document.

The commissioning should be carried out by a competent person approved at the time by the Health and Safety Executive and in accordance with the current issue of BS6798.

12.1 Switching on

  • Do not operate the boiler without water.
  • Make sure that the system has been thoroughly flushed out with cold water and that all cleanser if used has been removed.
  • With the gas service isolation valve closed, with no demand from any external controls and the power supply to the boiler switched off.
  • Test for gas soundness and purge air from the gas supply.
  • Switch on the power supply to the appliance.
  • Make sure that the domestic hot water and heating functions on your appliance are not activated.
12.2 Filling the CH system (Central heating)

  • Make sure that the installation's cold water inlet isolating valve is open.
  • Open the isolating valves located on the connections: they must be positioned in the direction of the flow.

Key

  • 1 Air ven
  • 2 Pump
  • 3 Screw for the pump shaft
  • Open the plug on the air vent located on the pump and automatic air vents on the installation.

If the (CH.) pressure falls below 0.4 bar, the display will flash the current pressure and the boiler will not operate. To increase the pressure, the CH circuit requires "Topping up".

i When turning the 230Vac supply on to the boiler should the water pressure be less than 0.5 bar an automatic air vent function will be activated for a period of 5 minutes. During this time the pressure should be increased and air vented from the system. Note that the burner will not fire in either the CH or DHW mode and the display will blink displaying the current water pressure.

  • Vent air from each radiator until the water flows normally, then close the vents.
  • Leave the pump's air vent open

The following two operations will unblock the pump' s engine after a prolonged storage period and will purge the air from the pumps circuit.

  • Remove the screw from the pump shaft and introduce a flat screwdriver. A trickle of water, under no pressure should normally come out of the pump.
  • Rotate the pump's shaft through several turns, then replace the screw.
12.3 Filling DHW Circuit

• Open the various hot water taps to fill the DHW circuit.

12.4 Filling the Condensate Trap

Key

  • 1 Filling trap
  • 2 Condensate trap
Page 26

  • Fill the trap with water (1)
  • Activate the Heating and Domestic Hot Water functions
  • Run the appliance for at least 15 minutes, with a heating temperature set to greater than or equal to 50°C (not applicable for an installation with underfloor heating).
  • · Vent air from each radiator again until the water flows normally then close the vents
  • If you have difficulties in removing the air. launch the airremoval programs in the heating circuit (see the chapter ("Technical settings for the appliance and list of parameters").
  • Make sure that the pressure indicator shows a value of 0.8 bars: otherwise, fill the appliance again.
12.5 Initial lighting
12.5.1 Control

The combustion for this appliance has been i checked, adjusted and preset at the factory for operation on natural gas (G20) as defined on the appliance data label No measurement of the combustion is necessary. Should the appliance require to be converted to LPG

gas ensure you follow the gas conversion section before lighting the boiler

  • Check that the appliance has been installed in accordance with the instructions.
  • Check the integrity of the flue system and flue seals
  • Check the integrity of the appliance combustion circuit and relevant seals.
  • Check that all internal/external controls are calling for heat.
  • Check that the gas service isolation is open
  • To adapt the appliance to another type of gas, see chapter "LPG conversion".
12.5.2 Adjusting the temperature

  • loque cloc
  • 2 Reset button 3
  • ction of functionina mode ure adjustment
12 5 3 Display

  • Light the appliance by following the procedure below
  • Select the "Heating + domestic hot water" function by pressing the "Mode" button repeatedly to scroll through your options until 🎹 🖌 are shown

The appliance will enter a self checking routine, then the fan will start and the ignition sequence commence. The boiler, if necessary, will automatically repeat the ignition sequence a further 4 times.

If the burner fails to ignite "F28" will be displayed, initially, this may be due to air in the gas supply line. Press the reset button. Do not use the reset button to purge the installation - never press reset more than 3 times.

  • Select the heating function only by pressing the "mode" button repeatedly (IIII is shown only).
  • Press (+) or (-) buttons to adjust
  • Select the hot water function only by pressing the "mode" button repeatedly ( 6 is shown only).
  • Press (+) or (-) buttons to adjust
  • Check that hot water is available at all taps, then close.
  • Return the appliance to the correct mode by pressing "mode" button unit the desired functions are activated.

12.6 Gas rates

The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler

On completion, test the gas installation for tightness using the pressure drop method and suitable leak detection fluid. purge in accordance with the above standard.

D
n
th
fc

Due to the modulating operation of the boiler and the eed to check the gas inlet pressure and measure he gas rate at maximum rate, it will be necessary to orce it to maximum.

Activate the test mode "P.01" and set the value to HI in order to force the burner at P. max. See chapter "Specific adjustment Appliance technical settings and parameter list ► Test modes".

Page 27
12.6.1 Operational Gas Inlet Pressure

Key

  • 1 Gas service isolation valve
  • 2 Test point
  • With all other gas appliances operating, check the operational supply pressure at the gas service isolation valve test point.

The nominal supply pressure for Natural Gas (G20) is 20mbar. The nominal supply pressure for LPG (G31) is 37mbar.

• Turn the taps and appliances off, then disconnect the pressure gauge.

Additionally the safe nominal maximum heat input of the appliance can be achieved at an inlet pressure down to 15mbar.

The burner pressure cannot be measured and is not used to measure the gas rate.

12.6.2 Gas Rate

  • Make sure that all other gas burning appliances and pilot lights are off.
  • Check the gas rate using the gas meter test dial and stop watch, at least 10 minutes after the burner has lit, see table below for approximate rates.
Gas rates (G20) Gas rate es (G31)
(approx) after 10 mins from cold
Madal MIN MAX MIN MAX
Model m³/h ft³/h m³/h ft³/h kg/h kg/h
24a 0.85 30 2.54 89.7 0.62 1.87
28a 0.98 34.6 2.96 104.05 0.72 2.17

In communal or LPG installations where the gas rate cannot be measured it is acceptable to measure the combustion rate as described in the servicing section.

  • On completion, press the "reset" button to reset the boiler.
  • Gas rates for both central heating and hot water can be verified using the test program P.03 and P.01 respectively.
12.7 Testing heating system

  • Ensure that the external controls and programmer are calling for heat.
  • Fully open all radiator valves, see chapter "Appliance installation ► Recommendations before installing ► Heating circuit design".
  • Activate the C.H. function on the appliance's control panel.
  • Balance the radiators as required to give the required system differential.
  • Turn off all radiators that can be shut off by the user and check to see if less than the maximum differential allowed of 20°C can be achieved across flow and return.

i Should the appliance require adjustment refer to the "Specific adjustment" section overleaf.

  • Allow the system to reach maximum temperature then switch off the boiler by isolating from the electrical supply.
  • Drain the entire system rapidly whilst hot, using the drain taps at all the low points of the system. Fill and vent the system as described previously in chapter "Commissioning Filling the CH system (Central heating)".
  • Adjust the boiler temperature controls and any system controls to their required settings.
12.8 Testing domestic hot water system

  • Open a hot-water tap.
  • Check that the temperature obtained is compliant with the setting on the appliance.
12.9 Completion

• Ensure that the magnetic lighting instruction label is placed on the surface of the boiler casing.

GB: It is a requirement that the "Benchmark" Installation, Commissioning and Service Record is completed and left with the user.

IE: it is necessary to complete a "Declaration of Conformity" to indicate compliance to I.S.813. An example of this is given in the current edition of I.S.813.

Page 28

13 Specified Adjustment

13.1 Heating circuit adjustment

By pass operation is automatic and not adjustable.

If necessary, fit an external by-pass.

Key

A Available pressure between heating flow and return (kPa)

B Heating circuit flow rate (I/h)

Key

A Available pressure between heating flow and return (kPa)

B Heating circuit flow rate (I/h)

14 Installation settings

  • Push in and hold the mode button for more than 7 seconds to access the configuration menu. The screen displays "0".
  • Press the button 4 times. The screen displays "96". This is the installer's password.
  • Press mode to validate. The screen displays a flashing and alternating "d." and "00".
  • Press ⊕ or ⊖ button to access the parameter to modify.
  • Press mode button to modify the value of the parameter and select with the ⊕ or ⊙ keys.
  • Press (mode) button to confirm and save the changes.
  • Press and hold the mode button for more than 7 seconds to exit.
Page 29
Code Parameter Unit Description Factory setting Modifiable
parameter
d.00 Maximum heating power kW Choose a value 24a > 8 to 18 and 28a > 9 to 24. 18 (24a)
24 (28a)
yes
d.01 Pump over-run time - heating min Choose a value between 2 and 60 5 yes
d.20 Maximum temperature setting for domestic hot water °C The recommended maximum temperature setting for DHW is 60°C. Choose a value suitable for your needs. 60 yes
d.34 Speed of fan rpm Fan speed is displayed between 0 and 99.
Multiply the display value by 100.
- no
d.36 Domestic hot water flow l/min. Display domestic hot water flow. - no
d.40 Heating flow temperature °C Display the heating flow temperature. - no
d.41 Heating return temperature °C Display the heating return temperature. - no
d.43 Heating curve к See the instructions for the external sensor connected to the appliance. 1.2 yes
d.47 Exterior temperature °C Display the temperature measured by the external sensor. - no
d.67 Time remaining before the end of the anti-cycle in heating mode. min. Display the time remaining before the end of the anti-cycle - no
d.71 Maximum temperature setting for heating outlet °C Select a value between 50°C and 80°C. 75 yes
d.90 Detection of eBUS controller - 0 = Not detected
1 = Detected
- no
14.1.1 After Sales Service settings

  • Press and hold the (mode) button for more than 7 seconds to access the configuration menu. The screen displays "0".
  • Press ⊕ or ⊙ button and enter the After Sales Service password.
  • Press mode to validate. The screen displays a flashing and alternating "d." and "00".
  • Press ⊕ or ⊖ button to access the parameter to modify.
  • Press mode button to modify the value of the parameter and select with the ⊕ or ⊙ keys.
  • Press (mode) button to confirm and save the changes.
  • Press and hold the mode button for more than 3 seconds to exit the configuration menu.
Code Parameter Unit Description Factory setting Modifiable
parameter
d.08 Current state of the 230V room thermostat - 230V room thermostat :
0 = open (no heating),
1 = closed (heating mode).
- no
d.09 Flow temperature set point from external eBus control °C External eBus set value. - no
d.10 Heating pump status - 0 = off
1 = on
- no
d.16 Current state of the 24V room thermostat °C 0 = open (no heating),
1 = closed (heating mode)
- no
d.17 Flow or Return temperature control °C Temperature regulation on flow (radiator) or return (under-floor heating) temperature sensor. 0 yes
d.22 DHW demand active (tapping) - 0 = off
1 = on
- no
d.23 Central heating mode - 0 = CH not available (summer mode)
1 = CH available (winter mode)
- no
d.33 Speed setpoint of fan rpm Fan speed is displayed between 0 and 99.
Multiply the displayed value by 100.
- no
d.44 Digitalized ionisation voltage V Display the digitalized ionisation voltage. Multiply the displayed value by 100. - no
Page 30
Code Parameter Unit Description Factory setting Modifiable
parameter
d.68 Unsuccessfull ignitions at first attempt - Display the number of unsuccessfull ignitions at first attempt. - no
d.69 Unsuccessfull ignitions at second attempt - Display the number of unsuccessfull ignitions at second attempt. - no
d.80 Operating hours in heating mode h Display the number of operating hours in heating mode. Multiply the displayed value by 100. - no
d.81 Operating hours in domestic hot water mode h Display the number of operating hours in domestic hot water mode. Multiply the displayed value by 100. - no
d.82 Number of burner starts in heating mode - Display the number of burner starts in heating mode. Multiply the displayed value by 100. - no
d.83 Number of burner starts in DHW mode - Display the number of burner starts in DHW mode.
Multiply the displayed value by 100.
- no
d.93 Device Specific Number - Select the product code of the appliance: 24a -> 3
28a -> 4
yes
d.96 Factory reset - All parameters stored in EEPROM (main board +
appliance interface) are reset to factory settings if
this function is activated.
0 = deactivated
1 = activated
0 yes
14.1.2 Status of the appliance

Press button for more than 3 seconds to learn the current state of functioning of the appliance.

The screen displays "S" and the state of the appliance.

Press and hold the mode button for more than 3 seconds to exit this menu.

Status Heating Mode
S.00 No request for heating
S.01 Pre-run fan
S.02 Pre-run pump
S.03 Ignition
S.04 Burner lit
S.05 Post run pump/fan
S.06 Post run fan
S.07 Post run pump
S.08 Time delay anti short-cycles after heating
Status Domestic hot water mode
S.10 Request for domestic hot water
S.11 Pre-run fan
S.13 Ignition
S.14 Burner lit
S.15 Post run pump/fan
S.16 Post run fan
S.17 Post run pump
Status Specific messages
S.30 Default status, no request for heating or domestic water. If
an EBUS controller is connected to the boiler, check that
a wiring link is present on terminals 3 and 4 of the boiler's
main board.
S.31 "Hot water only" mode
S.32 Control cycle: the speed of the fan in the functioning phase is outside tolerance.
S.34 "Frost protection" mode
S.41 Water pressure too high
S.53 Waiting cycle: temperature differential between heating flow and return is too high. If ∆T > 30, forcing to Pmin.
S.54 Waiting cycle: lack of water in the installation/temperature rise between heating flow and return is too high.
S.96 Test temperature sensor for heating return.
S.98 Test temperature sensors for heating flow and return, or the appliance has a fault
14.1.3 Test modes

By activating these various test modes, you can enable special functions on the appliance.

  • Press the on/off button to switch off the appliance.
  • While keeping the button (mode) pressed for more than 5 seconds, press the on/off button. The screen displays the first test mode "P1" and "Off".
  • Press ⊕ or ⊙ button to choose the test mode that you wish to launch.
  • Test mode "P1" :
  • Press mode button to display the burner forcing setting. The screen displays "P1" and "Lo".
  • Press on ⊕ or ⊖ button to modify the value of the setting from "Lo" (0%) to "Hi" (100%).
  • Press on mode button for 1 second to exit the submenu or for more than 7 seconds to access the configuration menu.
  • Test mode "P.02" to "P.07" :
  • Press (mode) to launch the test mode. The screen displays "PX" and "On".
  • The test mode will be automatically stop after 15 minutes.
  • When you have finished, press the reset button -||- to exit the test modes.
Page 31
Code Parameter Description
P.01 Forcing the
adjustable-
power burner
when heating
The appliance functions at a power
adjustable from "Lo" (Lo = Pmin.) to "Hi"
(Pmax.) by using buttons ⊕ or ⊙ Ⅲ
after successful ignition.
P.02 Forcing the
burner to
heating ignition
power
The appliance functions at ignition power after successful ignition.
P.03 Forcing the
burner to
Heating Pmax.
The appliance functions at its maximum power after successful ignition.
P.06 Venting the installation The function is activated for a period of 5
minutes on the heating circuit.
Make sure that the air vent is open.
P.07 Venting the appliance The function is activated for a period of 5
minutes on the short circuit.
Make sure that the air vent is open.
14.1 CO, measurement

The combustion for this appliance has been pre-set at the factory for operation on Natural Gas G20 as defined on the appliance data label.

No adjustment of the combustion is necessary.

If you wish to check the combustion then follow the instructions in the Servicing section.

14.2 Re-check and restart

  • Once the appliance is installed, check the operation of the appliance.
  • Start the appliance to ensure that any adjustments operate correctly and check that the appliance operates safely.
  • Check the gas-tightness and water-tightness of the appliance and eliminate any leaks.
  • Check that the flue joints are tested for tightness and fitted in accordance with the instructions.
  • Check the entire control and safety system, its settings and its operation.

15 User information

At the end of the installation, the installer must:

  • explain the operation of the appliance and its safety devices to the user, if necessary provide a demonstration and answer any questions;
  • hand over to the user all the required documentation,
  • fill in the documents where necessary;
  • advise the user of the precautions necessary to prevent damage to the system, appliance and the building;
  • remind the user to service the appliance annually.
  • Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35, which imposes a duty of care on all persons who let out any property containing a gas appliance in the UK.

The user shall not interfere with or adjust sealed components.

It is the Law that any servicing is carried out by a competent person approved at the time by the Health and Safety Executive.

  • Advise the user that, like all condensing boilers this appliance will produce a plume of condensation from the flue terminal in cool weather. This is due to the high efficiency and low flue gas temperature of the boiler.
  • Advise the user that the permanent mains electrical supply should not be switched off, as the built in frost protection and pump exercise program will not operate.
  • Advise the User if the mains electricity and gas are to be turned off for any long periods during severe weather, it is recommended that the whole system, including the boiler, should be drained to avoid the risk of freezing.

Sealed system: The system must be refilled and to the correct pressure as indicated in these instructions

• Leave these instructions and the 'Benchmark' Installation, Commissioning and Service Record with the user.

Page 32

MAINTENANCE

To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough

It is the Law that any servicing is carried out by a competent person approved at the time by the Health and Safety Executive

  • · Before commencing with a service or replacement of parts isolate the boiler from the electrical supply and turn off the gas supply at the gas isolation valve
  • When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Glow-worm.
  • If any electrical connections have been disconnected and after their connection, checks to the earth continuity, polarity short circuit and resistance to earth must be repeated using a suitable multimeter, as described in chapter "Trouble-shooting ► Fault diagnosis ► Check the electrical installation"
  • After servicing complete the relevant Service Interval Record section of the Benchmark Checklist located in the back pages of this document

16 Trouble-shooting

16.1 Fault diagnosis

The following checks should be performed before proceeding onto specific diagnostics:

  • Make sure that the electricity supply has not been interrupted and that the appliance is connected correctly (See chapter "Trouble-shooting Fault diagnosis Check the electrical installation")
  • Check the appliance's gas supply (See chapter "Troubleshooting ► Fault diagnosis ► Check the gas supply")
  • Ensure that the isolating valves are open
  • Ensure that the pressure indicator displays a value of 0.8 bar (if the pressure falls below 0.4 bar, the air vent function will run automatically for a period of 5 minutes until you see 0.5 bar on the pressure indicator). If not, fill the appliance.
  • Check that all external controls are connected correctly.
  • If the symbol -"- is displayed on the screen, display the fault code memory (see chapter " Trouble-shooting ► Fault memorv").
  • Press the reset button -!!- to restart the appliance
  • Check the functional flow diagram

16 1 1 Check the electrical installation

  • Neutral
  • Remove the front casing panel
  • Check the external electrical supply to the boiler is on and a supply of 230V is present at the 'L' and 'N' terminals on the main board
  • Check the electrical installation and appliance, carry out tests for earth continuity, polarity, short circuit and resistance to earth using a suitable multimeter
  • Bare metal points such as screws or rivets will act as suitable earth check points on the appliance.
Page 33
16.1.2 Check the gas supply

Key

  • 1 Gas service isolation valve
  • 2 Test point
  • Check that there is a gas supply to the boiler and the gas service isolation valve is turned on.
  • Check pressure at the gas service isolation valve.
16.2 Fault memory

  • This menu allows you to display the 10 most recent failure codes registered by the appliance.
  • In order to display the fault code memory, simultaneously press the buttons ⊕ and ⊝ for more than 7 seconds.
  • The screen will display the first fault "1." (record) and after "XX" (fault code).
  • To display the other faults registered by the appliance, press the button ⊕ or ⊙.
  • Press button mode for more than 3 seconds to exit this menu.
Record Fault code Description
1. ХХ Consult the "Fault codes" chapter.
2. ХХ Consult the "Fault codes" chapter.
3. ХХ Consult the "Fault codes" chapter.
4. XX Consult the "Fault codes" chapter.
5. ХХ Consult the "Fault codes" chapter.
6. ХХ Consult the "Fault codes" chapter.
7. XX Consult the "Fault codes" chapter.
8. XX Consult the "Fault codes" chapter.
9. ХХ Consult the "Fault codes" chapter.
10 ХХ Consult the "Fault codes" chapter.

• To erase the fault memory registered by the appliance, consult the "Installation adjustments" chapter and use code "d.94".

Page 34

16.3 Fault codes

i

The faults described in this chapter should be

carried out by a qualified engineer and if needed by

the After Sales Service.

Fault codes Description Cause Solution
F00 Flow heating temperature sensor fault Sensor open circuit
F01 Return heating temperature sensor fault Return heating temperature sensor
disconnected
Check the sensor's connections.
F10 Flow heating temperature sensor fault Sensor short-circuit Check the wiring namess. Check the sensor.
F11 Return heating temperature sensor fault Return heating temperature sensor shorted.
F20 Overheating fault Overheating safety device activated (97°C)
  • Check the operation of the pump.
  • Check the wiring harness.
  • Check that the flow and return heating isolation valves are open.
F22 Water pressure of the installation (<0.3 bar) Return water valve closed
Pump disconnected
Leak in the installation
  • Fill the installation.
  • Purge the installation.
  • Check the pump connections.
  • Check the flow and return heating sensor connections.
  • Check that there are no leaks.
F23 Maximum temperature difference reached between return and flow heating Water circulation fault
  • Check the flow and return heating sensor connection.
  • Check the pump speed.
F24 Water circulation fault Malfunction of the pump (excessively rapid temperature increase) Check that the flow and return heating isolation valves are open.
F26 Fault in gas valve motor. Disconnected or defective cables
  • Check the gas valve connections.
  • Check the operation of the gas valve.
  • Check the operation of the condensate pump (option).
F27 Flame detection fault. Abnormal flame detection
  • Check the flame detection electrode.
  • Check the main board.
  • Check the igniter unit.
F28 Ignition fault No return gas / Insufficient gas flow
Gas valve incorrectly adjusted
  • Check the return gas circuit (gas valve open).
  • Check the observe the flame picture and check the CO 2 setting.
F29 Loss of flame during operation Defective firing electrode and flame
control / Defective igniter unit
Check the igniter unit connections. Check the state of the electrode (corrosion).
F32 Incorrect air pressure Incorrect fan speed.
  • Check the entire flue system.
  • Check the fan's electrical connections.
F49 EBUS voltage fault Fault in EBUS line
Short circuit in EBUS connector
Check that the eBus controls are fitted and wired correctly.
F61 Gas valve command fault
F62 Gas valve closure fault
F63 Fault in the main board memory Check the main boards connections. Check the main board
F64 Fault in the main board Rapid fluctuation of return or flow heating sensor. Check the appliance DSN number is correct. Reset the appliance.
F65 Excessive main board temperature
F67 Flame signal fault in the main board
F68 Fluctuation of flame signal No return gas / Insufficient gas flow
Gas valve incorrectly adjusted
Defective firing electrode and flame
control / Defective igniter unit
  • Check the return gas circuit (gas valve open).
  • Check the observe the flame picture and check the CO 2 setting.
  • Check the igniter unit connections.
  • Check the state of the electrode (corrosion).
F70 User interface incompatible with the main board Incorrect product code
  • Check that the appliance DSN code on the screen
    matches the product code of the nameplate (in the
    event of a fault and the appliance DSN does not
    appear, consult menu.d.93 reserved for the code).
  • Check the boards reference.
F71 Flow heating temperature sensor fault Flow heating temperature sensor
unclipped or defective (no
temperature variation)
  • Check the sensor connections.
  • Make sure that the sensor is clipped to the tube.
Page 35
Fault codes Description Cause Solution
F72 Permanent temperature difference between flow and return heating sensors Mismatch between the flow and return heating temperatures (permanent difference)
  • Check temperature sensors connections.
  • Replace faulty sensors.
F73 Heating circuit pressure sensor fault The sensor is shorted or disconnected. Check the sensor's connections.
F74 Heating circuit pressure sensor fault Fault in pressure sensor Check the sensor.
F76 Thermal fuse fault Thermal fuse disconnected
Defective thermal fuse
  • Check the fuses connections.
  • Replace the heat exchanger.
F77 Fault in gas valve motor. Defective gas valve.
Defective condensate pump (option)
  • Check the gas valve connections.
  • Check the operation of the gas valve.
  • Check the operation of the condensate pump (option).
F83 No water in the installation : the temperature does not increase when the burner is lit Return water valve closed
Pump disconnected
Leak in the installation
  • Fill the installation.
  • Purge the installation.
  • Check the pump connections.
  • Check the flow and return heating sensor connections.
  • Check that there are no leaks.
F84 Permanent temperature difference between flow and return heating sensors Inverted or disconnected flow and
return heating temperature sensors
Defective temperature sensors
  • Check temperature sensors connections.
  • Replace faulty sensors.
F85 Flow and return heating sensors fault Flow and return heating temperature sensor connected to same tube Check temperature sensors connections.
F86 Underfloor heating contact fault Floor heating contact open
Sensor disconnected or defective
  • Check the sensor connections.
  • Check that the sensor is connected to the main
    board and the shunt is removed.
Err User interface fault Defective user interface
  • Check connection from user interface PCB to main
    PCB.
  • Replace user interface.

16.4 Functional flow diagram

16.4.1 Central Heating

Page 36

16.4.2 Domestic Hot Water

17 Gas conversion adjustments

In order to operate with a gas other than that provided from the factory, it is necessary to some adjustments to the gas valve.

This conversion should only be carried out by a competent person approved at the time by the Health and Safety Executive.

• During the conversion to Propane, use of a suitable flue gas analyser is necessary.

The person carrying out a combustion measurement should have been assessed as competent in the use of a flue gas analyser and the interpretation of the results.

The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN50379-3 and be calibrated in accordance with the analyser manufacturers' requirements.

Competence can be demonstrated by satisfactory completion of the CPA1 ACS assessment, which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, parts 1 to 4.

17.1 Settings

i

Steps "Switching on" to "Re-pressurising System" will need to be completed before the appliance can be converted (See chapter "Commissioning").

Tools required to make the conversion are a 4mm Allen key and an electricians screwdriver.

Having checked :

  • the appliance and system have been installed in accordance with the instructions.
  • the integrity of the flue system and flue seals ....
  • the integrity of the appliance combustion circuit and relevant seals....
  • that all internal/external controls are calling for heat.
  • the gas service isolation valve is opened.
Page 37

Key

  • ть
  • analyser sample point
  • 2A Flue elbow
  • Vertical flue adaptor 2B Cap
  • 3
  • Remove the front panel first
  • Remove the cap (3) and connect a CO2 analyser to effect the measurement (2)
17.1.1 Adjusting the gas valve

  • Press the on/off button to turn the appliance off.
  • Turn the screw in the direction and the number of times indicated in the following table.
Gas adjustment Model G20 ► G31 G31 ► G20
24a 2 turns
28a 3 turns
24a 2 turns
28a 3 turns
1712 Adjusting the maximum power setting

  • Activate the test mode "P.01" and set the value to HI in order to force the burner at P. max. See chapter "Specific adjustment ► Appliance technical settings and parameter list ► Test modes".
  • Wait approximately 5 minutes to read a stabilized CO, value.
  • Compare the value measured with the values indicated in the table below.
Gas adjustment G20 G31
CO 2 case ON 9 ± 0.2 % 10.1 ± 0.2 %
CO 2 case OFF 9.2 ± 0.3 % 10.3 ± 0.3 %

Safe compustion can only be verified by measuring i CO/CO ratio. This must not exceed the value shown in the table under the section "Maximum Rate and Adjustment"

1713 Restarting

  • Replace the cap
  • Replace the appliance front panel

Note: following the replacement of the front panel, the CO value will change: you can check that the value "case on" is correct by the values in the previous table.

  • al ni
  • Firmly attach the gas replacement label to the appliance in the corresponding location (1) on the electrical box.
17.2 Restart - re-check commissioning

Before putting the appliance into operation, follow the instructions within the chapter Specific adjustment.

Page 38

18 Draining

18.1 Heating circuit

Kev

  • 1 Length of hose (not supplied)
  • 2 Drain valv
  • Drain down the heating circuit of the boiler only, by closing the heating flow and return isolating valves. See chapter "Hydraulic connection Gas and water connections"
  • Open the drain point (2). Attach a length of hose (1) if required.
  • After draining, close the drain valve (2) and remove the hose.
18.2 Domestic Hot water circuit

  • Drain the Domestic Hot Water circuit by closing the coldwater isolation valve.
  • Open one or more hot water taps to drain the hot water circuit.

19 Servicing

• To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced as necessary at regular intervals.

The frequency of servicing will depend upon the particular installation conditions and usage. However it is recommended that the boiler is inspected as part of a service at least once a year.

If this appliance is installed in a rented property there is a duty of care imposed on the owner of the property by the current issue of the Gas Safety (Installation and Use) Regulations, Section 35.

Servicing/maintenance should be carried out by a competent person approved at the time by the Health and

Safety Executive in accordance with the rules in force in the countries of destination.

• To obtain service, please call your installer or Glow-worm's own service organisation.

PLEASE NOTE: During routine servicing, and after any maintenance, we recommend that the following must be checked:

  • The integrity of the flue system and the flue seals,
  • The integrity of the boiler combustion circuit and the relevant seals,
  • The operational (working) gas inlet pressure at maximum rate,
  • The gas rate,
  • The combustion performance.
  • See the "Safety instructions" chapter for a list of operations to be performed prior to the maintenance of the application.
  • Once the maintenance operations have been completed, consult the "Start Up" chapter to restart the appliance.
19.1 Annual Maintenance
19.1.1 Verification of components

  • Check that the flow sensor is working properly. See chapter "Specific adjustment ► Appliance technical settings and parameter list ► Installation settings" and use code "d.36".
  • Check that the fan is working properly. See chapter "Specific adjustment ► Appliance technical settings and parameter list ► Installation settings" and use code "d.34".
  • Check that the temperature sensors are working properly. See chapter "Specific adjustment ► Appliance technical settings and parameter list ► Installation settings" and use code "d.3, d.4, d.40, d.41".
  • Check the ionisation quality.
  • Check that the thermal fuse protects the appliance against dry fire. Disconnect the thermal fuse and check if "F76" fault code is displayed on the screen.
  • Check that the pressure sensor is working properly. The pressure must be displayed on the screen.
  • · Check the pressure of the expansion vessel.
19.1.2 Other checks

  • Check the CO2 rate in the fuel and compare with the values indicated in the chapter "CO2 Measurement".
  • Check that there are no leaks in the joints and the safety valves.
  • Check that there are no gas leaks.
  • Verify that the flue system is sound and complete.
  • Check the appliance's electrical safety.
Page 39
1913 Cleaning of the components

  • Clean the following components:
  • The condensate tran
  • The heat exchanger.
  • The burner
  • The fan
Corrosion and anti-sludge protection 10 1 1

In order to avoid corrosion, the addition of a corrosion inhibiter to the heating circuit water is recommended. The inhibiter will stop electrolytic reaction and bacterial growth between the different metals used in the installation

It will also avoid the formation of gas which could be produced following the chemical reactions.

It is especially important to treat the water in underfloor heating systems, as low temperatures favour bacterial growth. This can lead to the formation of sludge, which in turn may block some or all of the circuits

In order to add the correct dosage of these products, you must know the volume of water contained in the installation. It is recommended that you note down the volume for future needs.

The inhibitors must be compatible with the materials employed in the installation.

19.2 Casing removing
19.2.1 Front panel

  • Front panel retaining screw

• Undo the two screws (2) on the underside of the front panel and remove the front panel (1).

19.2.2 Control box

• Position the control box (1) into the service position.

19.3 Combustion check and setting the air/gas ratio valve
1931 Competency to carry out the check of combustion performance

  • BS 6798: 2009 Specification for installation and i maintenance of gas-fired boilers of rated input not exceeding 70kW net advises that:
  • The person carrying out a combustion measurement must be assessed as competent in the use of a flue gas analyser and the interpretation of the results
  • The flue gas analyser used should be one meeting the requirements of BS7927 or BS-EN50379-3 and be calibrated in accordance with the analyser manufacturers' requirements.
  • Competence can be demonstrated by satisfactory completion of the CPA1 ACS assessment, which covers the use of electronic portable combustion gas analysers in accordance with BS 7967, parts 1 to 4.
  • Ensure that the gas analyser is set to the correct fuel setting.
  • Select the " f + ", constant central heating with DHW function by pressing the "(mode)" button repeatedly, refer to commissioning section. The boiler should fire automatically.

Safe combustion can only be verified by measuring CO/CO, ratio. This must not exceed the value shown in the table opposite

10 2 2 Preliminaries

Prior to, during servicing and after any maintenance or changed parts, the following inspection must be carried out.

  • The integrity of the flue system and flue seals.
  • The integrity of the appliance combustion circuit and relevant seals
  • A visual inspection of the flame quality.
Page 40

MAINTENANCE

  • Electrical, gas and water connections.
  • · System pressure.
  • The combustion performance, refer to the following procedure.
  • The operational gas inlet pressure and gas rates, refer to the commissioning section paragraph 12.5. Correct any fault before continuing.
Combustion check and setting the air/gas ratio

  • Remove the front casing panel and hinge down the control box. Taking care not to touch any internal components, proceed as follows:
  • Connect the CO2 combustion analyser to the relevant test point.

Key

  • 1 Throttle
  • 2 Combustion analyser sample point
  • 2A Flue elbow
  • 2B Vertical flue adapt
  • 3 Cap

19.3.3 Maximum rate check and adjustment

To verify the maximum gas rate CO2 setting the appliance must be checked at the maximum rate.

  • Activate the test mode "P.01" and set the value to HI in order to force the burner at P. max. See chapter "Specific adjustment ► Appliance technical settings and parameter list ► Test modes".
  • Wait approximately 5 minutes to read a stabilised CO, value.
  • Check that the value is within the range specified in table in the "check" column.
G20 Burner % CO 2
Model Check (case on) Setting (case off) CO/CO 2 ratio
24a 9.2 ± 0.3% 9 ± 0.2% 0.004
28a 9.2 ± 0.3% 9 ± 0.2% 0.004
G31 B urner % CO 2
Model Check (case on) Setting (case off) CO/CO 2 ratio
24a 10.3 ± 0.3% 10.1 ± 0.2% 0.004
28a 10.3 ± 0.3% 10.1 ± 0.2% 0.004

If the combustion reading is not within the acceptable values and the integrity of the complete flue system and combustion circuit seals have been verified and the inlet gas pressure (and gas rate) have been verified, then, it will necessary to adjust the combustion rate of the appliance.

  • Remove the sticker covering the "throttle" adjustment screw, if fitted.
  • Rotate the "throttle" (1) (anti-clockwise to increase), to the required CO2, refer to previous diagram and the "Setting" column in the table.
  • When you have finished, press the On/Off button to exit the test modes.
  • Remove the analyser probe and replace the cap on the sampling point, replace the controls fascia, and the front casing panel.

Remember to replace the sample point cap on

i

1934 Gas rate check

completion of the test.

Check the gas rates as described in the commissioning section.

19.3.5 Completion

If it is not possible to achieve the required results for either the combustion or gas rates, it will be necessary to complete a full service of the appliance and then repeat the combustion check procedure.

If after servicing and adjustment of the appliance the combustion values are still unacceptable and after further remedial work has been carried out, the appliance must be disconnected until the CO/CO2 ratio is acceptable.

Advice can be sought from the Glow-worm Technical Helpline.

Page 41
19.4 Servicing

If the annual check of combustion CO2, CO/ CO2 ratio checks did not require adjustment and the inspections described in "Preliminaries" were satisfactory then it will not be necessary to complete a full service. In any case, a full service must be carried out at least once every 5 years including the replacement of the burner door seal.

All routine servicing requirements can be achieved by the removal of the front panel.

  • Position the control box into the service position.
  • Before commencing with a service or replacement of parts, isolate the boiler from the electrical and gas supplies.
19.4.1 Service interval record

Refer to benchmark Service Interval Record at the rear of this manual.

19.5 Silencer

Key

  • 1 Silencer retaining screw
  • 2 Fixed silencer
  • 3 Removable silencer
  • Remove the silencer retaining screws (1) and remove the silencer (3).
  • Clean the interior of the silencer with a dry cloth if necessary, taking care not to damage the internal foam.
  • Repeat the operation in reverse order to replace the silencer.
19.6 Expansion vessel

  • Kev
  • 1 Expansion vess
  • 2 Expansion vessel pressure inlet
  • Check the expansion vessel's supply pressure (see « Technical Data » chapter) by means of the pressure inlet located on the expansion vessel. Adjust the pressure if necessary.
  • Following the installation of a new expansion vessel, fill and purge the appliance or installation, if necessary.
Page 42

19.7 Condensate trap

Warning: condensate is mildly acidic. Use protective gloves.

Key

  • 1 Condensate cleaning cap
  • 2 Condensate pipe 3 Condensate outlety
  • 3 Condensate outletv4 Condensate retaining screw
  • 5 Condensate trap
  • Place a container under the condensate trap (5).
  • Remove the condensate from the reservoir (1).
  • Disconnect the condensation discharge (2).
  • Disconnect the heat exchanger hose (6).

The condense trap will contain water, lift taking care not to spill the water.

  • Remove the condensate trap (5) using the retaining screw (4).
  • Clean the hose, the trap and the siphon, remove any accumulated dirt.
  • Reassemble the components, taking care to position the gaskets correctly.
  • Start the siphon (3) and fill with water.
Page 43

19.8 Combustion block

  • valve co
  • Inding cabl
  • 23 ctrode in
  • ng screw
  • k electrode a
  • 4 5 6 7
  • etaining r
  • 7 8 9 er retaining scre
  • rmal fuse connectio

  • 10
  • 11
  • 12
  • 13
  • 14 14 Gd5
  • 16 Fan o
  • 17 Gas pipe
Page 44
19.8.1 Spark electrode

  • Disconnect the electrode inlet (3) and the grounding cable (2).
  • Remove the 2 spark electrode retaining screws (4)
  • Carefully remove the electrode from the combustion chamber.
  • Check that the extremes of the electrode (6) are not damaged.
  • Clean away any accumulation of dirt and check that the distance between the two electrodes is between 3.5 and 4.5 mm.
  • Check that the gasket (5) is not damaged. Replace if necessary.
19.8.2 Dismantling the burner

Warning: The gasket (12) must be replaced each time the burner is dismantled.

  • Disconnect the spark electrode connector (6) from the igniter unit.
  • Remove the gas pipe (17).
  • Remove the connectors from the gas valve (1) and the fan (15).
  • Remove the retaining screw of the silencer.
  • Loosen the 4 nuts (7).
  • Remove the burner group from the heat exchanger (11).
  • The studs (8) fixed to the heat exchanger must not be damaged. Should it be damaged, replace the heat exchanger.
  • The burner gate insulation should not be damaged. Replace if damaged.
19.8.3 Cleaning the heat exchanger

• Clean the coil (19) in the heat exchanger (11) with water.

19.8.4 Burner control

  • The burner (13) does not require maintenance and should not be cleaned.
  • Check that its surface is not damage. Replace the burner if necessary.
  • Following the verification or replacement of the burner, assemble the burner group as described in the following chapter.
19.8.5 Re-assembling the burner group

  • Place the burner group on the heat exchanger (11).
  • Progressively tighten the 4 nuts (7) in an alternate order.
  • Reassemble the silencer.

  • Connect the gas tube (17) with a new gasket to the burner group.
  • Connect the spark electrode connector (6) to the igniter unit.
  • Connect the connector to the gas valve (1) and the fan (15).
  • Open the appliance gas input.
  • Check the watertightness of the gas connection.
19.9 Service completion

• Re-check the combustion, see chapter "Combustion check".

On completion of the service, the "Benchmark" Service Record sould be completed.

20 Replacement of Parts

  • Do not use reconditioned or copy parts, only use original parts supplied by Glow-worm.
  • If a part is required, contact the Glow-worm service organisation.
  • Please quote the name of the appliance, this information will be on the name badge on the front of the appliance.
  • If in doubt seek advice from the local gas company or Glowworm's own service organisation.

Replacement of parts must be carried out by a competent person approved at the time by the Health and Safety Executive.

PLEASE NOTE: During change of part of the combustion circuit, we recommend that the following is the following must be checked:

  • The integrity of the flue system and the flue seals,
  • The integrity of the boiler combustion circuit and the relevant seals,
  • The operational (working) gas inlet pressure at maximum rate,
  • The gas rate,
  • The combustion performance
Page 45

20.1 General

The replacement of parts described in sections "Combustion block" will require the removal of the burner module assembly and the replacement of seal and self locking nuts.

Replacement parts that have associated components that need to be replacing on removal, i.e. 'O' ring, seals, gasket, etc., will be supplied and should be fitted.

· Before replacing any parts of the boiler, isolate from the mains electric supply and turn off the gas at the gas service isolation valve on the boiler.

Unless stated otherwise parts are replaced in the reverse order to removal.

After replacing any parts, always test for gas soundness and if necessary carry out functional test of the controls.

20.2 Boiler Access

For replacement of parts, the front casing panel of the boiler will need to be removed.

• To remove undo the two screws on the underside of the front casing and lift off.

20.3 Viewing window

  • Fibre washe 2 Steel weeks
  • Glass
  • Circlip
  • Remove the circlip (5)
  • Remove the steel washer (4).
  • Remove fibre washer (1)
  • Remove the glass (3)
20 3 1 Expansion vessel

Кеу

  • er support bra aining screw
  • 5 Gaskot

Drain the boiler heating circuit as described in the appropriate chapter "Draining".

  • Remove the two screws (4).
  • Undo the connector (1) at the base of the vessel
  • Remove upper support bracket (3).
  • Remove the expansion vessel (2).
  • Fit a new gasket between the expansion vessel and connector
  • Refill, vent and pressurise the boiler.
Page 46

20.4 Hvdraulic block

Key

  • Three-way valve
  • 2
  • Three-way valve Three-way valve electrical plug Three-way valve electrical plug retaining clip 3
  • 4 Low water pressure sensor connector
  • 5 Low water pressure sensor
  • 6 Low water pressure sensor retaining clip
  • Heating flow pipe retaining clip
  • 8 Heating flow pipe
  • 9 Heating flow pipe
  • 10 Heating flow nine retaining clin
  • 11 Gas pipe
  • 12 Flow sensor electrical plug
  • 13 Flow sensor
  • 14 Heating return pipe 15 Expansion vessel pipe

  • 16 Plate-to-plate heat exchanger
  • 17 Automatic air vent
  • 18 Expansion vessel nine clin
  • 19 Automatic air vent retaining clip
  • 20 Pump head retaining screws
  • 21 Pump housing
  • Pump head connector Plate-to-plate heat exchanger retaining screw
  • 24 Safety Discharge Valve
  • 25 Bypass Valve
  • 26 Bypass Valve retaining nut
  • 27 Bypass Valve retaining nut 27 Bypass Valve retaining nut
  • 28 Impeller housing
  • 29 Safety discharge valve plastic housing
  • 30 Retaining clip
Page 47
20.4.1 Pump (head only)

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Disconnect the electrical plug (22) from the main board.
  • Remove the four cap head screws (20).
  • Carefully remove the pump head (21) together with cable. Do not strain cable.
  • Reconnect wiring to new pump head and fit cover.
  • Fit the new pump head by repeating the operations in reverse.

20.4.2 Automatic air vent

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Remove the retaining clip (19).
  • Remove the automatic air vent (18).
  • Fit the new automatic air vent and 'O' ring ensuring the vent cap is left loose.
  • Refill, vent and pressurise the boiler.

20.4.3 Low water pressure sensor

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Disconnect the electrical lead (4).
  • Remove the retaining clip (6), remove the low water pressure sensor (5).
  • Fit the new low water pressure sensor.
  • Refill vent and pressurise the boiler.

20.4.4 Safety discharge valve

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Remove the low water pressure sensor as described in the previous section.
  • Undo the safety discharge valve union and remove the pipe.
  • Disconnect the Central Heating isolation valve.
  • Remove the securing clips and withdraw the safety discharge valve plastic housing (29).
  • Remove the safety discharge valve.
  • Fit new 'O' ring. Refill, vent and pressurise the boiler.

20.4.5 Flow sensor and impeller

  • Remove the the electrical connection (12).
  • Unclip the flow sensor (13).
  • Unscrew the impeller housing (28) and remove the impeller.

20.4.6 Bypass

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Remove the bypass valve retaining nut (26) to remove the bypass from its housing (25).
  • After replacing the bypass, refill, vent and pressurise the boiler.

20.4.7 3 way valve motor and diverter valve

  • Drain the boiler heating circuit as described in the appropriate chapter "Draining".
  • Disconnect the electrical plug (2).
  • Remove the retaining clip (3).
  • Remove the three way valve motor (1)
  • Remove the diverter valve retaining nut.
  • Remove the diverter valve.
  • Fit new three way valve motor and diverter valve assembly.
  • Refill, vent and pressurise the boiler.

20.4.8 Plate-to-plate heat exchanger

  • Drain the boiler heating and domestic hot water circuits as described in the appropriate chapter "Draining".
  • Remove the two securing screws (23).
  • Remove the plate-to-plate heat exchanger (17).
  • When replacing the plate-to-plate heat exchanger, ensure that the four rubber sealing washers are fitted into the hydroblock.

NOTE: The plate-to-plate heat exchanger only fits one way.

• Refill, vent and pressurise the boiler.

Page 48

20.5 Combustion block

Legend

  • Igniter unit retaining bracket
  • 2 Igniter unit
  • Igniter unit retaining screw Igniter unit electrical connector 4
  • 5 Electrode / igniter unit connection cable
  • 6 Earth cable
  • Spark electrode cap
  • 8 Spark electrode retaining screw
  • 9 Spark electrode gasket
  • 10 Spark electrode
  • 11 Combustion burner door assembly
  • 12 Combustion burner door assembly nut
  • 13 Combustion burner door assembly gasket 14 Burner gasket
  • 15 Burner
  • 16 Burner retaining screw
  • Burner retaining screw Heat exchanger retaining screw Heat exchanger retaining bracket
  • 19 Burner gate retaining screw

  • 20 Thermal fuse conne
  • 21 Heat exchanger
  • 22 Heat exchanger retaining bracket Heat exchanger retaining screw
  • 23 Heating return nine
  • 25 Heating return pipe retaining clip
  • 26 Return heating temperature sensor
  • 27 Heating flow pipe
  • 28 Flow heating temperature sensor29 Heating flow pipe retaining clip
  • 30 Gas valve retaining screw
  • 31 Gas valve
  • 32 Gas valve gasket
  • 33 Fan
  • 34 Fan electrical connection
  • 35 Fan/burner gasket
  • 36 Gas pipe
  • 37 Gas valve electrical connection
  • 38 Fan retaining screw
Page 49
20 5 1 Spark electrode

  • Disconnect the electrode cap (7) and the earthing cable (6).
  • Remove the 2 spark electrode retaining screws (8).
  • Carefully remove the electrode (10) from the combustion chamber
  • Remove the gasket (9).
  • Check that the distance between the 2 electrodes is between 3.5 and 4.5 mm.
  • Install the electrode and a new gasket
laniter unit 20 5 2

  • Remove the ignition lead (2)
  • Remove electrical connections (4).
  • Loosen the screws (3) located on the igniter unit (2).
  • Remove the igniter unit (2).
20 5 2 Removing the combustion/burner door assembly
Warning: The gasket (13) must be replaced each time the combustion/burner door assembly is removed.

  • Disconnect the spark electrode cap (7) from the igniter unit.
  • Disconnect the gas supply pipe (36) at the gas valve
  • Remove the electrical connectors from the gas valve (37) and the fan (34).
  • Remove the retaining screw of the silencer
  • Loosen the 4 nuts (12).
  • Remove the combustion/burner door assembly from the heat exchanger (11)
  • The studs (19) must not be damaged. If damaged you will need to replace the heat exchanger.
  • The combustion/burner door assembly insulation should be inspected and replaced if damaged.
20 5 4 Burner

  • Remove the 3 burner retaining screws (16)
  • Remove the burner (15) and the gasket (14).
  • Fit the new burner and the new gasket.
20.5.5 Heat exchanger

There will be water in the heat exchanger. Carefully ease heat exchanger out.

Drain the boiler heating and hot water circuits as described in the appropriate chapter "Draining".

  • Remove the flue connection
  • Undo the two screws located on the top of each side panel.
  • Remove the thermal fuse connector (20)
  • Remove the 2 heating pipe retaining clips (25) and (29).
  • Release the heating pipes (24) and (27) from the heat exchanger
  • Release the condensate trap pipe from the heat exchanger.
  • Remove the combustion/burner door assembly (11) refering to chapter "Removing the combustion/burner door assembly".
  • Unscrew the 4 retaining screws (17) and (23) and remove the 2 retaining plates (18) and (22) from the heat exchanger.
  • Pull the heat exchanger towards you to extract it from its 2
20.5.6 Re-assembling the burner group

  • Place the burner assembly on the heat exchanger (21).
  • Progressively tighten the 4 nuts (12) in an alternate order.
  • Reassemble the silencer
  • Connect the gas pipe (36) with a new gasket to the burner group.
  • Connect the spark electrode connector (5) to the igniter unit
  • Connect the connector to the gas valve (37) and the fan (34).
  • Open the appliance's gas input
  • Check the tightness of the gas connection.
20.5.7 Heating Flow Thermistor

  • Remove the electrical connections from the thermistor (28).
  • Remove the retaining clip from the flow pipe (27).

i

When reconnecting, the polarity of the wiring to thermistors is not important.
20.5.8 Heating Return Thermistor

  • Remove the electrical connections from the thermistor (26)
  • Remove the retaining clip from the return pipe (24).

20.5.9 Gas valve

  • Remove the burner door (11) refering to chapter "Dismantling the humer door"
  • Remove the two gas valve retaining screws (30).
  • Remove the gas valve (31) and the gasket (32)
Page 50

  • Fit the new gas valve and the new gasket by repeating the operations in reverse.
  • After assembly test for gas tightness and purge in accordance with the current issue of BS6891or in IF the current edition of LS 813 "Domestic Gas Installations".
  • Check the combustion COa.
20.5.10 Fan

  • Remove the burner door (11) refering to chapter "Dismantling the burner door"
  • Remove the gas valve (31) (see previous paragraph).
  • Loosen the 3 screws (38) located on the burner door (11).
  • Remove the fan (33) and the gasket (35).
  • Fit the new gasket (35)
  • Screw the new fan to the burner door (11).
  • After assembly test for gas tightness and purge in accordance with the current issue of BS6891or in IF. the current edition of I.S.813 "Domestic Gas Installations".
20.6 Condensate trap

Warning: condensate is mildly acidic. Wear protective gloves

  • nsate reservoi Condensate discharge
  • ensate outlet
  • nsate retaining screw sate trap

  • Place a container under the condensate trap (5).
  • Remove the condensate from the reservoir (1).
  • Disconnect the condensation discharge (2)
  • Disconnect the heat exchanger hose (6)

The condense trap will contain water, lift taking care not to spill the water

  • Remove the condensate trap (5) using the retaining screw (4).
  • IMPORTANT: Partially fill the condensate trap with water before replacing. Start the siphon (3) and fill with water.

20.7 PCB

20.7.1 Main PCB

  • Key
  • Remove the 24V and 230V connections.
  • Remove the rear panel (2)
  • Ease back the two PCB retaining clips (3) and withdraw the PCB from the retaining lugs.
  • Remove the electrical connections to the PCB (appliance) interface cable).
  • When refitting the rear panel, ensure the leads are not trapped.
Page 51
20.7.2 2A Fuse Rating

  • For access, refer to chapter "Main PCB".
  • The fuse is located at top right hand side of the PCB, see chapter "Electrical connection ► Wiring diagram".
20.7.3 User interface PCB

  • кеу
  • 1 User interface
  • 2 Retaining slots
  • 3 User interface PCB
  • 4 Retainings clips
  • 5 Control Panel
  • Remove the user interface (1) easing back the two retaining slots (2).
  • Ease back the two PCB retaining clips (4) and withdraw the PCB from the retaining lugs.
  • Remove the electrical connections to the PCB.
  • When refitting the user interface, ensure the leads are not trapped.
20.7.4 Mains supply cable

The main supply cable must be replaced by a qualified and competent electrician.

If the main supply cable is damaged, replace it referring to the chapter "Electrical connection".

21 Spare parts

In order to guarantee the safe and prolonged life of the product, manufacturers genuine spare parts must be used.

This a
Only
parts.

This appliance displays a CE Mark of conformity. Only use the manufacturer's genuine, new spare parts

Ensure that spare parts are correctly mounted in the right position and direction. After fitting any spare part or servicing, the appliance must be tested for its safe operation.

21.1 Short List of Parts

  • When ordering spare parts, contact Glow-worm's own service organisation.
  • Please quote the name of the appliance and serial number, to be found on the data label. If ordering from British Gas also quote the G.C. number of the part.
Key
No.
Part No. Description GC Part No.
1 0020097277 Fan
2 A000035144 Spark igniter
3 2000801935 Thermistor (flow and return)
0020097279 Gas valve 24a
4 0020097278 Gas valve 28a
5 0020038441 Electrode assembly
6 0020118159 User interface PCB
7 0020118165 Plate to plate heat exchanger 24a
L ' 0020118166 Plate to plate heat exchanger 28a
8 2000801912 3 way valve motor
9 0020118139 Pump 24a / 28a
10 0020118178 Water flow sensor
11 0020061608 Water flow sensor
12 0020118138 Main PCB
13 0020079644 Low water pressure sensor
14 801635 Burner Door Seal Kit
16 002011896 Diverter valve
Page 52

21.2 Short List of Parts

Page 53

Page 54

Manual Handling

IMPORTANT. With regards to the Manual Handling Operations, 1992 Regulations, the following lift operation exceeds the recommended weight for a one man lift.

General recommendations when handling

Clear the route before attempting the lift.

Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Do not twist – reposition feet instead. If 2 persons performing lift, ensure co-ordinated movements during lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip. Always use assistance if required.

Removal of carton from delivery van

Recommend 2 person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Always use assistance if required.

Carriage of carton from point of delivery to point of installation – ground floor.

Recommend 2 person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Clear the route before attempting the lift. If removing boiler from truck straddle the load and tilt forwards to facilitate secure grip. Ensure safe lifting techniques are used – keep back straight – bend using legs. Do not twist – reposition feet instead. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required.

Carriage of carton from point of delivery to point of installation –

first or higher floor, cellar. Recommend 2-person lift or 1 person with use of sack truck. If 1 person is performing lift, straddle the load, tilt and place carton into position on truck. Recommend secure appliance onto truck with suitable straps. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. If 2 persons performing lift, ensure co-ordinated movements during lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Clear the route before attempting the lift. If removing boiler from truck straddle the load and tilt forwards to facilitate secure grip. Ensure safe lifting techniques are used – keep back straight – bend using legs. Do not twist – reposition feet instead. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. Always use assistance if required.

Carriage of carton from point of delivery to point of installation – roofspace.

Recommend 2-person lift. Ensure co-ordinated movements during lift. Avoid upper body/top heavy bending - do not lean forward/sideways. Clear the route before attempting the lift. Take care to avoid trip hazards, slippery or wet surfaces and when climbing steps and stairs. When transferring appliance into roofspace, recommend 1 person to be in roofspace to receive the appliance and other person to be below to pass up and support appliance. Ensure safe lifting techniques are used – keep back straight – bend using legs. Keep load as close to body as possible. Always use assistance if required. It is assumed safe access, flooring and adequate lighting are provided in the roof space. It is recommended a risk assessment of the roof space area be carried out before moving the appliance into the area to take into account access, stability of flooring, lighting and other factors, and appropriate measures taken.

Unpacking of appliance from carton.

Recommend 2 persons unpack appliance from carton. Always keep working area clear. Cut the carton straps, lift carton up and slide over polystyrene end packs. Remove top polystyrene pack with fittings.

Positioning of Appliance for Final Installation – no obstructions. Recommend 2 persons lift appliance to position into place. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to position in place on bracket. Ensure safe lifting techniques are used – keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Ensure co-ordinated movements to ensure equal spread of weight of load. Always use assistance if required.

Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.

Positioning of Appliance for Final Installation – above worktop, foreseeable obstructions etc.

Recommend 2 persons lift appliance to position into place. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, onto worktop if practicable. Ensure stable balance achieved and lift upwards to position in place on bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. Ensure safe lifting techniques are used – keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Avoid upper body/top heavy bending - do not lean forward/sideways. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.

Positioning of Appliance for Final Installation – within compartment etc. restricting installation.

Recommend 2 persons lift appliance to position into place, space permitting. Fit bracket securely onto wall before lifting appliance into position. Obtain firm grip on front and sides of appliance, lift upwards, onto worktop if practicable. Ensure stable balance achieved and lift upwards to drop into place onto bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. If 1 person positioning onto bracket recommend obtain firm grip supporting base of boiler. Ensure safe lifting techniques are used – keep back straight – bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Always use assistance if required. Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance.

Positioning of Appliance for Final Installation – in roof space restricting installation.

Recommend 2 persons lift appliance to position into place, space permitting. Fit bracket securely onto wall before lifting appliance into position Obtain firm grip on front and sides of appliance, lift upwards, ensure stable balance achieved and lift upwards to drop into place onto bracket. If 2 persons positioning onto bracket obtain firm grip at front and sides/base of boiler. Ensure co-ordinated movements during 2 person lifts to ensure equal spread of weight of load. If 1 person positioning onto bracket recommend obtain firm grip supporting base of boiler. Ensure safe lifting techniques are used - keep back straight - bend using legs - when lifting load from floor level. Do not twist – reposition feet instead. Keep boiler as close as possible to body throughout lift to minimise strain on back. Always use assistance if required Recommend wear suitable cut resistant gloves with good grip to protect against sharp edges and ensure good grip when handling appliance. It is recommended a risk assessment of the roof space area be carried out before moving the appliance into the area to take into account access stability of flooring lighting and other factors and appropriate measures taken

Page 55

Declaration of Conformity

Installation, Commissioning and Service Record

Page 56

Please affix the label positioned on the top panel of your boiler over this area.

COMMISSIONING CHECKLIST GAS BOILER SYSTEM

This Commissioning Checklist is to be completed in full by the competent persor
compliance with the appropriate Building Regulations and then handed to the cu
n who commissioned the boiler as a m
stomer to keep for future reference.
eans of demonstrating
Failure to install and commission this equipment to the manufacturer's instruction ns will invalidate the warranty but doe es not affect statutory ri ghts.
Customer Name Telephone Number
Address
Commissioned by (print name) Engineer ID Number Engineer ID Number
Company Name Telephone Number
Company Address
To be completed by the suptemer on receipt of a Building Regulations Compliance Co Commissioning Date
Building Regulations Notification Number ( if applicable )
CONTROLS Tick the appropriate boxes
Time and Temperature Control to Heating Room Thermostat and Program nmable Load/Weather Compensation Optimum Start
Control
Time and Temperature Control to Hot Water Cylinde er Thermostat and Programmer/Timer nostat and Programmer/Timer Combination Boiler
ng Zone Valves Fitted Not Required
Hot Water Zone Valves Fitted Fitted Not Required
Thermostatic Radiator Valves Fitted Not Required
Automatic Bypass to System Fitted ] Not Required
Boiler Interlock Provided
ALL SYSTEMS
The system has been flushed and cleaned in accordance with BS7593 and boiler manufacturer's instructions Yes
What system cleaner was used?
What inhibitor was used? Quantity
ft3/br
Is the installation in a hard water area (above 200ppin): the installation in a hard water area (above 200ppm)? Yes No
Gas Rate ft³/hr
Burner Operating Pressure (at maximum rate) mbar OR Gas Inlet Pressure (at maximum rate) mbar
Ves 0.0
Water Flow Rate
The condensate drain has been installed in accordance with the manufacturer's instructions and/or BS5546/BS6798 Yes
ALL INSTALLATIONS
If required by the manufacturer, record the following CO 2
The heating and hot water system complies with the appropriate Building Regulations Yes
The boiler and associated products have been installed and commissioned in accordance with the manufacturer's instructions Yes
The operation of the boiler and system controls have been demonstrated to and understood by the customer Yes
The manufacturer's literature, including Benchmark Checklist and Service Record, has been explained and left with the customer Yes
Commissioning Engineer's Signature
Customer's Signature
(To confirm satisfactory demonstration and receipt of manufacturer's literature)
II installations in England and Wales must be notified to Local Authority Building Control (LABC) either direct ly or through a Competent Persons Scheme -

*All installations in England and Wales must be notified to Local Authority Building C A Building Regulations Compliance Certificate will then be issued to the customer. ©Heating and Hotwater Industry Council (HHIC)

www.centralheating.co.uk

Page 57

SERVICE INTERVAL RECORD

It is recommended that your heating system is serviced regularly

and that you complete the appropriate Service Interval Record Below .

Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service as described in the boiler manufacturer's instructions. Always use the manufacturer's specified spare part when replacing all controls.

SERVICE 1 Date SERVICE 2 Date
Energy Efficiency Checklist completed? Yes No Energy Efficiency Checklist completed? Yes No
Engineer Name Engineer Name
Company Name Company Name
Telephone Number Telephone Number
Engineer ID Number Engineer ID Number
Comments Comments
Signature Signature
SERVICE 3 Date SERVICE 4 Date
Energy Efficiency Checklist completed? Yes No Energy Efficiency Checklist completed? Yes No
Engineer Name Engineer Name
Company Name Company Name
Telephone Number Telephone Number
Engineer ID Number Engineer ID Number
Comments Comments
Signature Signature
SERVICE 5 Date SERVICE 6 Date
Energy Efficiency Checklist completed? Yes No Energy Efficiency Checklist completed? Yes No
Engineer Name Engineer Name
Company Name Company Name
Telephone Number Telephone Number
Engineer ID Number Engineer ID Number
Comments Comments
Signature Signature
SERVICE 7 Date SERVICE 8 Date
Energy Efficiency Checklist completed? Yes No Energy Efficiency Checklist completed? Yes No
Engineer Name Engineer Name
Company Name Company Name
Telephone Number Telephone Number
Engineer ID Number Engineer ID Number
Comments Comments
Signature Signature
SERVICE 9 Date SERVICE 10 Date
Energy Efficiency Checklist completed? Yes No Energy Efficiency Checklist completed? Yes No
Engineer Name Engineer Name
Company Name Company Name
Telephone Number Telephone Number
Engineer ID Number Engineer ID Number
Comments Comments
Signature Signature
Page 58

Page 59

Page 60

GLOW-WORM

Nottingham Road, Belper, Derbyshire. DE56 1IT

www.glow-worm.co.uk

Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.

Glow-worm

Loading...