Glow-worm 56-3e Back Boiler User Manual

221725B.10.00
Installation & Servicing Instructions
To be left with the user
Glow-worm 56/3e
Back Boiler Unit
G.C. No. 44 047 04A
This Back Boiler Unit Is To Be Used Only With The Glow-worm Mk.3 Fire Front Range
6836
One Contact Local Service
This is a Cat I2H Appliance
Customer Services: Tel: (01773) 828100 Fax: (01773) 828070
Nottingham Road, Belper, Derbyshire. DE56 1JT
Tel: (01773) 824141 Fax: (01773) 820569
Hepworth Heating Ltd.,
General/Sales enquiries:
1 General
1 General
The instructions consist of three parts, Installation and Servicing Instructions for the Back Boiler Unit, Installation and Servicing Instructions for the Fire Front and Instructions for Use, which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
This boiler is for use only with a specially designed Glow-worm Gas Fire Front, see Table 1.
This boiler is NOT suitable for fitting to a precast flues. The boiler is delivered in one pack which contains all the parts
necessary for the installation. If installing the back boiler unit and fire front at the same time
please read both sets of instructions before starting.
1 General Notes and Information
IMPORTANT NOTICE The back boiler is fitted with a safety device which will shut it
down if there is a lack of oxygen. If the back boiler shuts down frequently for no apparent reason. The first things to be checked are the chimney and air inlets into the room. Any problems found must be put right, by a competent person, before the back boiler is used again.
This back boiler is for use only on G20 gas. Wherever possible, all materials, appliances and components
to be used shall comply with the requirements of applicable British Standards.
Where no British Standard exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship.
Sheet Metal Parts
WARNING. When installing or servicing this back boiler care should be taken when handling the edges of sheet metal parts to avoid any possibility of personal injury.
1.1 Statutory Requirements
The installation of this back boiler unit must be carried out by a competent person in accordance with the current issue and relevant requirements of:
Manufacturer’s instructions, supplied. The Gas Safety (Installation and Use) Regulations, The
Building Regulations, The Building Standards (Scotland) Regulations (applicable in Scotland), Local Gas Undertaking, Bye-laws of the Local Water Company, The Health and Safety at Work Act, Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations.
Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice,
BS6891, BS5449, BS5546, BS6700, BS5871, BS5440 Part 1 and 2, BS6798, BS1251, BS7478, BS7593, BS7671.
Manufacturer’s notes must not be taken as overriding statutory requirements.
1.2 Data
Gas connection Rc1/2 (1/2inBSPT) Water connection Supplied in fittings pack Electrical supply 230V~50Hz fused 3A Weight, about 35kg Water content 3.11Litres Injector 3.6mm Dimensions are given in millimetres (except as noted). Data Label: Front, centre on base. The Seasonal Efficiency Domestic Boilers UK (SEDBUK)
is 78.6%. The value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated have been certified by B.S.I.
1.3 Gas Supply
The gas installation shall be in accordance with the current issue of BS6891.
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the back boiler.
On completion test the gas installation using the pressure drop method and suitable leak detection fluid, purge in accordance with the current issue of BS6891.
1.4 Electrical Supply
WARNING. This back boiler must be earthed. All system components shall be of an approved type and shall
be connected in accordance with the current issue of BS7671 and any applicable local regulations.
Connection of the back boiler and system controls to the mains supply should be through a double pole isolating switch, fused 3A having a minimum contact separation of 3mm in both poles.
Alternatively, a fused 3A 3 pin plug and unswitched socket outlet to the current issue of BS1363 may be used.
o
Wiring to the back boiler must be PVC (85 the current issue of BS6500 Table 16, not less than 0.75mm (24/0.20mm).
C) insulated type to
1.5 Site Requirements
Refer to diagram 1.1 for dimensions appropriate to the back boiler.
For all types of installation a standard sized builder’s opening is required, see diagram 1.2.
It is important that the opening is cleared of debris and mortar.
It is recommended that the access hole for pipework into the fireplace or builder’s opening is either at the left hand or right hand side of the chimney breast. If access is required at both sides then it may be necessary to prepare some of the connections before fitting the back boiler into the builder’s opening.
The prepared base for the back boiler must be level. NOTE: For wider openings corner infills may be required when
fitting some fire fronts. The infills are for cosmetic reasons only, see diagram 1.3.
Refer to Table 2 for dimensions of fire front fixing wall face which must be true.
2
221725B
2
1 General
INSIDE DIAMETER
FIRE FIXING WALL FACE
C
L
E
T
G
FLUE
R
N
F
S
D
OF SOCKET FOR 125mm (5in) NOMINAL DIAMETER FLUE
P
B
H
C
L of Flue
WATER CONNECTIONS 22mm COPPER PIPE
GAS CONNECTION RC (1/2 in BSPT)
A
L
6837
C
M
SIDE ELEVATION
OVERALL DIMENSIONS
Dimension A B C D E F G H J K L M N P R S T
56/3e 550 400 338 337 245 130 3 146 177 174 60 457 65 530 80 50 490
RANGE RATING TABLE
Minimum Medium Maximum Maximum
RANGE RATING
Brown Ember 3 Miami 3
J
FRONT ELEVATION
Black Ash 3 Melody 3 Saxony 3
HEAT INPUT (NETT)
HEAT OUTPUT
HOT BURNER PRESSURE
kW
Btu/h kW
Btu/h mbar
in.w.g
10.8 14.5 17.6 18.2
36,950 49,550 59,900 62,150
9.4 12.9 15.8 16.4
32,000 44,000 54,000 56,000
5.0 9.0 13.7 14.8
2.0 3.6 5.5 5.9
K
J
Diagram 1.1
INJECTOR MARKING
3.6 Pt. No. 230208
3
221725B
1 General
1.6 Water System - Open Vented
This back boiler can be used on an unrestricted open vented system with the water supply taken from a feed and expansion cistern, having a head between 1m (3ft3in) minimum and 27m (90ft) maximum.
Diagrammatic layouts of systems are shown in diagram 1.4 and
1.5.
1.7 Sealed Water System
A kit and instructions, part number 459033, is available to enable the back boiler to be used on a sealed water system.
Please give the serial number of the back boiler when ordering the kit.
1.8 Hot Water Cylinder
The back boiler is suitable for open vented systems using an indirect cylinder (including single feed self priming type). The indirect cylinder must be fitted to the manufacturer’s recommendations and the system must conform to the requirements of the current issue of BS5546 and BS6700.
It is recommended that the indirect cylinder be fitted with some form of temperature control.
1.9 Frost Protection
If the position of the back boiler is such that it may be vulnerable to freezing it should be protected as specified in the current issue of BS5422.
It is also recommended that a frost protection thermostat is fitted.
1.10 Draining Tap
A draining tap must be provided at the lowest point of the system which will allow the entire system, the back boiler and hot water cylinder to be drained.
Draining taps shall be to the current issue of BS2879.
1.12 Back Boiler Location
This back boiler MUST NOT be installed in a private garage or in a room containing a bath or shower or in a room used or intended to be used as sleeping accommodation.
TABLE 2
Dimensions for minimum
FIRE TYPE
flat area (no fixtures)
X Y X Y
Miami 3 BBU 642 698 750 836 Melody 3 BBU 642 698 750 836 Black Ash 3 BBU 700 660 840 890 Brown Ember 3 BBU 795 707 905 892 Saxony 3 BBU 700 625 840 860
ALL DIMENSIONS IN MM
Y
C
L
PREPARED BASE
FRONT
OPENING
Dimensions for fixture or surround protection clearance
3013
X
1.11 Safety Valve
A safety valve need not be fitted to an open vented system.
TABLE 1
FIRE TYPE
Miami 3 BBU 37-047-04A 37-047-07A Melody 3 BBU 37-047-06A Black Ash 3 BBU 37-047-08 Brown Ember 3 BBU 37-047-02A Saxony 3 BBU 37-047-09
G.C No.
Teak Mahogany
C
PREPARED BOILER BASE
A B C Miami 3 BBU 350 405 to 580 560 to 590 Melody 3 BBU 350 405 to 580 560 to 590 Black Ash 3 BBU 350 406 to 460 560 to 590
*Brown Ember 3 BBU 350 406 to 580 560 to 590
Saxony 3 BBU 350 406 to 460 560 to 590
FRONT OPENING
A
B 405 min.
Diagram 1.2
6302
221725B
4
1 General
* CORNER IN-FILL
OPENING
(not required to be full depth of opening)
405 mm. MIN.
Diagram 1.3
1.13 BSI Certification
FRONT
This appliance is certificated to the current issue of BS6332 Part 1 invoking the current issue of BS5258 Part 8 for safety and performance. It is, therefore, important that no alteration is made to it without permission, in writing, from Hepworth Heating Ltd.
Any alteration that is not approved by Hepworth Heating Ltd., could invalidate the BSI Certification of the boiler, warranty and could infringe the current issue of the Statutory Requirements.
CE Mark
The CE mark on this appliance shows compliance with:
1. Directive 90/396/EEC on the approximation of the Laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on the harmonization of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on the approximation of the Laws of the Member States relating to electromagnetic compatibility.
This boiler meets the requirements of Statutory Instrument, No. 3083, The Boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels.
Type test for purposes for Regulation 5 certified by: Notified body 0086.
Product/production certified by: Notified body 0086.
1.14 Inhibitor
Attention is drawn to the current issue of BS5499 and BS7593 on the use of inhibitors in central heating systems.
If an inhibitor is to be used, contact a manufacturer for their recommendations as to the best product to use.
If using in an existing system take special care to drain the entire system, including the radiators, then thoroughly cleaning out before fitting the boiler whether or not adding an inhibitor.
6408
1 metre MIN 27 metres MAX
28mm
IMPORTANT DIMENSION NOT LESS THAN 145mm
FLOW
DISTRIBUTOR TUBE IN RETURN CONNECTION
RETURN
INDIRECT
CYLINDER
22mm CENTRAL HEATING RETURN
BOILER
22mm CENTRAL HEATING FLOW
27 METRES
C
L
PUMPED HEATING & GRAVITY DOMESTIC HOT WATER (DIAGRAMMATIC)
Diagram 1.4
22mm MIN OPEN VENT
MANUAL AIR VENT
INDIRECT CYLINDER
15mm COLD FEED
PUMP
150mm MAX
BOILER
The COLD FEED PIPE may be connected to the flow pipe, adjacent to the open vent pipe as shown . (THERE MUST ALWAYS BE A COLD WATER PATH TO THE RETURN CONNECTION Of THE BOILER.)
C
L
HEATING CIRCUIT
FULLY PUMPED SYSTEM (DIAGRAMMATIC)
Diagram 1.5
6242
MAXIMUM
7218
5
221725B
2 Types of Installation
2.1 With Non-combustible Hearth
The back boiler must be installed level with the hearth or above it, see diagram 2.1.
For minimum dimensions of a hearth see diagram 2.1.
2.2 Combustible Hearth
If the hearth is existing and made of a combustible material the back boiler must be installed to the dimensions in diagram 2.2.
2.3 With Surround
The combined thickness of the surround and lintel must be checked, to make sure that the back boiler can be positioned
Dimensions X, Y, and Z refer to Fire Installation Instructions
PREPARED BOILER BASE
'X' mm MIN
HEARTH
within the opening to allow easy connection of the flue into the back boiler flue socket, see diagram 2.3.
The surround requires a minimum opening for access as shown in diagram 1.2.
2.4 Wall Mounted - that is - Without Surround or Hearth
If there is to be any combustible material beneath the fire front, for example, carpet then the base of the builder’s opening must not be less than 75mm above the floor covering as shown in diagram 2.2.
The builders opening, with lintel must have minimum dimensions as shown in diagram 1.2 and 2.3.
FIRE FIXING
5423
350mm
MIN.
WALL FACE
N.B. *Minimum dimension.
This dimension refers to minimum clearance after carpet or any floor covering has been fitted.
PREPARED BASE
TOP OF CARPET, FLOOR COVERING OR COMBUSTIBLE HEARTH
1590
'Y' mm
165mm MAX
350mm MIN
'Z' mm
FIRE FIXING WALL FACE
PREPARED BASE
TOPS OF HEARTH MUST NOT BE ABOVE PREPARED BASE
13mm MIN NON-COMBUSTIBLE MATERIAL
Diagram 2.1
50mm MIN
COMBUSTIBLE HEARTH / WALL MOUNTED INSTALLATIONS
350mm MIN
FIRE FIXING WALL FACE
FLUE PIPE
*165mm MAX
*NOTE This dimension can be increased up to 190mm if builder’s opening depth is at least 375mm deep
*75mm
Diagram 2.2
6838
Diagram 2.3
221725B
6
3 Flue and Ventilation
3.1 General
The general recommendations of the current issue of BS5440 Part 1 should be followed.
In all cases the flue should be lined, preferably with a flexible liner.
It is essential that the flue has an equivalent height of at least
2.5m (8.2ft) measured from the flue connection on the appliance. The first 600mm, at least, above the draught diverter must be vertical.
The flue socket is designed to take flue pipe to BS567. If flue pipe conforming to a different standard is used a suitable adapter must be fitted and secured to the flue socket. A flexible flue liner may be used, with connection to the back boiler flue socket made with a short vertical piece of flexible liner, see diagram 3.2.
The existing flue may not be completely sound. To prevent any possibility of leakage, additional sealing MUST be carried out between the base of the chimney and the flue liner.
The end of the liner at the chimney top must be adequately sealed and clamped, using proprietary fittings suitable for the flue liner used, see diagram 3.1.
The flue should, preferably, end above ridge height but at least above the eaves of a pitched roof. Use a certificated terminal.
If the flue is to pass through or near any combustible material it should be installed in accordance with the current issue of BS5440 Part 1. If in doubt seek advice from the local gas undertaking or Hepworth Heating Ltd.
SEALING AND CLAMPING PLATE
AIR SPACE
150mm (6in) plug of Mineral Wool or similar
SEALING PLATE
600mm
6197
3.2 Existing Chimney
An existing brick chimney must be thoroughly swept and all debris cleared away before lining.
Remove any register plates, dampers and the like. Alternatively it may be locked in the open position.
A flexible flue liner is preferred but a rigid liner may be used, with connection to the back boiler flue socket made with a short vertical piece of flexible liner, see diagram 3.2.
Any air supply that enters the builders opening other than by the front opening, that is underdraught openings and the like must be completely sealed off.
The sealing plate also prevents debris falling and gives the flue better insulation, reducing the possibility of condensation, see diagram 3.1.
Check the flue system efficiency before installing the back boiler.
3.3 New Chimney
A newly built chimney can be lined with a moisture resistant lining, such as salt glazed pipe, of an appropriate diameter as specified in the Building Regulations
In the case of a salt glazed lined flue, it is recommended that a short vertical length of flue pipe, preferable flexible metallic be used, fixed and sealed to the back boiler flue socket, made good with approved packing and parged with fire cement, see diagram
3.2.
BACK
BOILER
UNIT
Existing Flue Fitted with Approved Lining
FLEXIBLE LINER
Diagram 3.1
RIGID FLUE LINER
APPROVED SEAL
7194
BACK BOILER
Diagram 3.2
7
221725B
3 Flue and Ventilation
If a flue and false chimney breast are to be constructed all openings for pipework to upper floors etc., must be sealed. The only opening for the back boiler must be at the front, being of the dimensions as shown in diagram 1.2.
If a specially built compartment is constructed for the back boiler, it must conform to the requirements of the current issue of BS5440 Part 1 and BS5871.
The flue should, preferably, end above ridge height but at least above the eaves of a pitched roof. Use a certificated terminal.
3.4 Ventilation - Back Boiler and Fire Front
It is important that the room in which the back boiler unit is installed has adequate air inlets to ensure correct operation as specified in the current issue of BS5440 Part 2.
Ventilation requirement for this back boiler is:
2
(13.5in2)
87cm
This ventilation area takes into account the total requirement of the back boiler unit and any of the specially designed gas fire fronts.
The ventilation openings may communicate direct with outside air or with an internal room or space (such as a hall) which itself is provided with a permanent air vent of the same effective area. The permanent air vent should be in a position which minimizes nuisance to occupants due to draughts.
This vent must NOT be placed in the builders opening. If the appliance is to be installed in a room already containing
another fuel burning unit, the air supply required for this other unit MUST be added to the figure above.
Any air vent taken through a cavity wall must be ducted.
3.5 Extract Fans
If an extract fan is fitted in the premises, there is a possibility that if adequate air inlet openings are not provided spillage of the products of combustion could occur.
When openings are fitted in accordance with the recommendations of the current issue of BS5440 Part 2, extract fans should not cause spillage.
Where such a fan installation is found, a clearance of products test must be conducted as described in the fire front Installation Instructions.
This test must be carried out with the back boiler fitted with its fire front.
See also Section 6.3 of these instructions.
221725B
8
4 Installation
4.1 Preparation
Remove draught diverter assembly, flueway baffles and fittings pack from carton.
Check contents of fittings pack against packed list. Remove back boiler body assembly from carton.
4.2 Water Connections
IT IS EXTREMELY IMPORTANT THAT NO SERVICE PIPES ARE ROUTED IN FRONT OF THE BOILER. If the builder’s opening was previously used for solid fuel all pipework within should be protected with PVC tape or equal. Pipework passing through walls of the opening should be sleeved and made good.
The two heat exchanger connections are supplied in the fittings pack and MUST be used, see diagram 4.1.
NOTE: Take care when soldering the copper connections not to damage the sealing washers.
4.3 Pumped Heating with Gravity Domestic Hot Water
NOTE: The draught diverter assembly and capillaries are shown to aid plumbing, but would not be fitted at this stage.
All pipework must comply with the current issue of BS5546. The domestic hot water flow and return pipes must be 28mm. Refer to diagrams 1.3 and 1.4 for a diagrammatic layout. If it is necessary to route pipework from both sides of the
builders opening, it is recommended that the heat exchanger is positioned on the combustion chamber so that the gravity circuits exit on the same side as the boiler connections.
If the heat exchanger connections are opposite hand to that required, the heat exchanger can be turned, as follows, remove the four screws securing the heat exchanger to combustion chamber, see diagram 4.2. Turn heat exchanger, refit the four screws.
It is recommended that pumped heating connections are pre­piped as in diagram 4.4.
Note: The diagram 4.4 shows two methods “A” and “B” of plumbing the flow pipe.
The central heating return must have the injector fitted on both methods A and B, see diagram 4.4 for fitting the injector.
22mm COPPER PIPE SUPPLIED WITH APPLIANCE (Do not cut)
SEALING WASHERS
HEAT EXCHANGER
SECURING SCREWS (4)
INJECTOR
UNEQUAL TEE PIECE
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
COMBUSTION CHAMBER
6254
Diagram 4.1
6839
Diagram 4.2
4.4 Pumped Heating and Hot Water
NOTE: The draught diverter assembly and capillaries are shown to aid plumbing, but would not be fitted at this stage.
Refer to diagram 1.5 for a diagrammatic layout. If it is necessary to route pipework from both sides of the
builders opening it is recommended that the heat exchanger is positioned on the combustion chamber such that the flow pipe exits on the same side as the boiler connections.
It is recommended that the pumped return is pre-piped as in diagram 4.3.
If the heat exchanger connections are opposite hand to that required, turn in the same manner as described in Section 4.3 paragraph 6.
22mm COPPER PIPE SUPPLIED WITH APPLIANCE (Do not cut)
Pumped Heating and Hot Water
9
22mm RETURN
22mm FLOW
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
Diagram 4.3
221725B
6840
4 Installation
FITTING THE INJECTOR
6842
145 mm MINIMUM
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
METHOD A
28mm DOMESTIC HOT WATER FLOW
(Must rise to allow air to escape from the system)
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
6843
22mm COPPER PIPE SUPPLIED WITH APPLIANCE (Do not cut)
22mm
22mm CENTRAL HEATING RETURN
28mm
22mm CENTRAL HEATING FLOW
(Must run down to allow air in system to escape)
145 mm MINIMUM
22mm CENTRAL HEATING RETURN
INJECTOR (Supplied)
UNEQUAL TEE (supplied)
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
28mm DOMESTIC HOT WATER FLOW
22mm CENTRAL HEATING RETURN
6841
28mm DOMESTIC HOT WATER RETURN
145 mm MINIMUM
221725B
28mm COPPER PIPE
28mm DOMESTIC HOT WATER RETURN
22mm COPPER PIPE SUPPLIED WITH APPLIANCE
(Do not cut)
10
METHOD B
22mm CENTRAL HEATING FLOW
Note: If the tee piece is fitted away from the boiler, the central heating flow pipe must be increased to 28mm as shown.
Diagram 4.4
Loading...
+ 22 hidden pages