GF Signet 7310 User Manual

Signet 7310 Switching Power Supplies
Features
• Universal AC input/Full range
• Protections: Short circuit/Overload/Over voltage
• Cooling by free air convection
• Install on DIN rail TS-35/7.5 or 15
• NEC class 2 / LPS compliant
• LED indicator for power on
• No load power consumption < 1W for 7310-7024 and < 0.75W for others
Signet 7310 Switching Power Supplies provide regulated output voltage in compact and lightweight plastic housings for DIN Rail mounting. The series includes five different output capacities from 0.42A to 4A (10W to 96W), all of which accept universal AC line voltage input and meet worldwide standards for performance and safety. These units meet the power requirements for a single system, multiple Signet instruments or other devices requiring 24 VDC operation.
• 100% full load burn-in test
CUS
Compatibility
• Signet Instruments
• Electromagnetic Flow Sensors
• Suitable for Electric Actuated Valves, including Solenoid
• Suitable for powering passive outputs and relays
Specifications
7310-1024 7310-2024 7310-4024 7310-6024 7310-7024
Output
DC Voltage 24V Rated Current 0.42A 1.0A 1.7A 2.5A 4.0A Current Range 0 ~ 0.42A 0 ~ 1A 0 ~ 1.7A 0 ~ 2.5A 0 ~ 4A Rated Power 10W 24W 40.8W 60W 96W Ripple & Noise (max.)
Note.2 Voltage Adj. Range N/A 21.6 ~ 26.4V 24 ~ 30V Voltage Tolerance Note.3 ±2.0% ±1.0% Line Regulation ±1.0% Load Regulation ±2.0% ±1.0% Setup, Rise Time Note.5
500ms, 30ms/230VAC,
1000ms, 30ms/115VAC at full load
Hold Up Time (Typ.) 120ms/230VAC,
25ms/115VAC at
full load
Input
Voltage Range 85 ~ 264VAC, 120 ~ 370VDC Frequency Range 47 ~ 63Hz Efficiency (Typ.) 84% 88% 88% 86% AC Current (Typ.) 0.33A/115VAC
0.21A/230VAC
Inrush Current (Typ.) Cold Start 35A/115VAC
70A/230VAC
0.55A/115VAC
0.35A/230VAC
Cold Start 20A/115VAC 40A/230VAC
Leakage Current
Protection
Overload
Above 105% rated
output power
105 ~ 160% rated
output power
Protection type Hiccup mode,
recovers automatically
after fault condition
is removed Over Voltage 27.6 ~ 32.4V 27.6 ~ 32.4V 31.2 ~ 36V Protection type Shut down o/p voltage, repower on to recover
Function
DC OK Active Signal (max.)
18 ~ 27V / 20mA 18 ~ 27V / 20mA Relay contact rating(max.): 30V/1A resistive
150mVp-p
500ms, 30ms/230VAC
500ms, 30ms/115VAC at full load
50ms/230VAC
20ms/115VAC at full load
1.1A/115VAC
0.7A/230VAC
1.8A/115VAC 1A/230VAC
Cold Start 30A/115VAC
60A/230VAC
<1mA / 240VAC
105 ~ 150% rated output power
Constant current limiting, recovers
automatically after fault condition is removed
3000ms, 50ms/
230VAC 3000ms,
50ms/115VAC
at full load
1.3A/115VAC
0.8A/230VAC
Dimensions
7310-1024 7310-2024
22.5
100
55
DC
-V
+V
OK
90
NL
55
Front View Side View Front View Side View
www.gfsignet.com
7310-4024 7310-6024
+V+V -V -V
90
+V ADJ
7.5
40
5
5555
+
NL
7.5
100