GE Security 250-CO User Manual

Page 1
GE
Security
250-CO Carbon Monoxide Detector Installation Sheet
Description
The 250-CO Carbon Monoxide Detector monitors the levels of CO gas and gives early warning when potentially dangerous levels exist. It does not detect fire, smoke, or any other gas.
The 250-CO provides a multicolored LED and a sounder to indicate the detector status. Use Table 1 to determine the status of the detector. The detector automatically resets when CO is no longer detected.
The 250-CO Carbon Monoxide Detector is intended for indoor­dwelling unit applications in both residential and commercial occupancies, including single/multiple family residential occupancies, hotel rooms, dorm rooms, and other areas approved by the authority having jurisdiction (AHJ).
The 250-CO detector can connect to either UL 985 (Household Fire Warning) or UL 864 (Commercial Fire) control panels. It is not intended for use in industrial applications such as gasoline refineries or parking garages, which require different listings.
The 250-CO detector is not intended to meet the requirements of CAN/CSA-6.19 (Residential Carbon Monoxide Alarming Devices). Please check with the local codes concerning the applicability of this requirement for each installation.
The 250-CO detector has an optional adapter mounting plate. To purchase the plate order P/N 250-COPLT-5PKG.
The built-in sounder is a supplementary alarm notification device. The control panel is considered the primary alarm notification device.
WARNING: Use only with a UL Listed control panel that recognizes
different alarm types (fire, burglary, CO, etc.) and that provides a distinct notification for each type.
Sensor end of life indicator: The detector uses both a flashing
green LED and intermittent sounder chirps to indicated that the detector needs replacing. The detector also signals a trouble condition when the CO sensor reaches end-of-life. When connected to a UL Listed control panel, the trouble relay can report a trouble condition locally at the panel and optionally at the central station, if the system is monitored.
Common trouble relay: The trouble relay opens to indicate a
trouble condition upon lost power, CO sensor cell trouble, or cell end-of-life.
Figure 1: Recommended CO detector locations
Features
Test/hush button: Use the test/hush button to test the alarm and
silence an activated alarm. Pushing the test/hush button silences the integral sounder for five minutes. The red alarm light stays on, and if CO is still present after five minutes, the detector once again sounds in the temporal-four pattern. The hush feature does not operate at CO levels above 350 ppm (parts per million).
Distinct 85 dB temporal-four sounder alarm: The 85 dB
temporal-four sounder provides a distinctive alarm notification that is easy to differentiate from smoke alarm notification devices. The alarm beeps four times, pauses five seconds and then repeats the pattern.
© 2010 GE Security, Inc.
CO detector locations
P/N 1061018 • REV D • ISS 10FEB10
1 of 6
Page 2
Table 1: Detector status indications
Status LED Sounder Description
Safe air Green, 1 pulse every 15
seconds
Alarm Red, pulses with
sounder
Trouble Amber, pulses with
sounder
End of sensor life Amber, pulses with
sounder
Loss of power No LED No sounder Activates the trouble relay.
Detector locations
Selecting a suitable location is critical to the operation of CO detectors. Install the 250-CO in accordance with NFPA 720
Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment. Place wall-mounted detectors at least
No sound The detector has power and is functioning properly.
Sounds four rapid beeps every five seconds or every minute after five minutes in the alarm state
Sounds one rapid beep every 45 seconds
Sounds one rapid beep every 15 seconds
Dangerous levels of CO are present. Evacuate the premises.
Press the test/hush button to silence the sounder for five minutes.
Activates the alarm relay. If connected, the alarm panel activates.
There is a problem with the detector and the detector is not working properly. Contact the service company to correct the trouble and replace the detector, if necessary.
Press the test/hush button to silence the detector for nine hours.
Activates the trouble relay.
The sensor is no longer working. Replace the detector as soon as possible.
Press the test/hush button to silence the detector for 36 hours.
Activates the trouble relay.
Notes
Do not install CO detectors until after final construction cleanup (unless otherwise specified by the AHJ).
Leave this installation sheet with the owner/user of this carbon monoxide (CO) detection equipment.
5 ft. (1.5 m) up from the floor. For ceiling mounted applications, place the detector at least 1 ft. (0.3 m) from any wall.
The recommended CO detector locations are:
Within 10 ft. (3 m) of all sleeping areas, including areas such as hotel rooms and dorm rooms.
The 250-COPLT adapter plate
Use the 250-COPLT adapter plate when replacing a 240-COe with a 250-CO to cover the footprint of the 240-COe. For example, use the plate to cover different wall colors.
In a suitable environment: areas with a temperature range of 32 to 104°F (0 to 40°C) and with a relative humidity range of 0 to 90% noncondensing.
In residential dwellings, locate detectors in every bedroom, within 10 ft. (3 m) of sleeping areas, and on each level. At a minimum, place one detector outside the sleeping areas. See Figure 1 on page 1.
The recommended CO detector locations in commercial occupancies are:
On every habitable level of the building based on an engineering evaluation considering potential sources and
Installation
The 250-CO Carbon Monoxide Detector is a four-wire device designed to use a Class 2 output from a UL 985 or 864 Listed control panel or auxiliary power supply.
All wiring must conform to the NFPA 70 National Electric Code, UL 2075 Standard for Gas and Vapor Detectors and Sensors, NFPA 720
Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, and applicable codes. Use 14 to 22 AWG
wire.
migration of carbon monoxide
In any area required by local building codes, legislation, or authorities having jurisdiction
On a firm, permanent surface
Do not install the CO detector:
Within 10 ft. (3 m) of a fuel-burning appliance
Near air conditioners, heating registers, or any other
WARNINGS
Connect the CO detector only to a zone dedicated exclusively to CO detection and that is monitored 24 hours a day. Do not connect to an initiating circuit with fire or security devices.
Failure to properly install, test, and maintain a CO detector may cause it to fail, potentially resulting in loss of life.
ventilation source that may interfere with CO gas entering the detector
Where furniture or draperies may obstruct the airflow
In a recessed area
To install the detector (without the adapter plate):
1. Run the 250-CO detector wiring to the detector location.
2. Carefully remove the cover from the detector using a small, flat screwdriver blade in the slot on the left side of the detector cover.
2 of 6 P/N 1061018 • REV D • ISS 10FEB10
Page 3
3. The mounting hole pattern is for single-gang spacing. Use the base for a template to mark the two screw hole locations on the mounting surface or mount on a single-gang box (not provided).
4. Install two screws on the marks. If necessary, use wall anchors.
5. Line up the base with the screws, pull the wires through the square holes, and slide the base down the screws to the wall. For surface wiring, pull the wires through the wiring channel at the bottom of the base.
6. Strip 3/8 in. of insulation from each wire.
7. Determine the correct wiring (see "Wiring" and Figures 3 to 5 below) and insert the wires under the appropriate screw terminals.
8. Tighten both screws to secure the base to the wall.
9. Replace the detector cover.
10. Apply power. The LED should flash green for approximately four seconds and then pulse green.
11. Test per the testing instructions below.
To install the detector using the adapter plate:
1. Run the 250-CO detector wiring to the detector location.
2. Using the 250-COPLT wall plate for a template, trace the perimeter of the two square holes on the mounting surface. Also mark the two screw locations.
3. Cut out the two square holes.
4. Install two screws on the marks. If necessary, use wall anchors.
5. Mount the wall plate but do not fully tighten down the screws.
6. Carefully remove the cover from the detector using a small, flat screwdriver blade in the slot on the left side of the detector cover.
7. Pull the wires through the square holes on both the wall plate and the 250-CO base. Then slide the detector base over the screws.
8. Strip 3/8 in. of insulation from each wire.
9. Determine the correct wiring (see "Wiring" and Figures 3 to 5 below) and insert the wires under the appropriate screw terminals.
10. Tighten both screws to secure the base to the wall plate.
11. Replace the detector cover.
12. Apply power. The LED should flash green for approximately four seconds and then pulse green.
13. Test per testing instructions below.
Figure 2: Screw terminals
3
1 2
4
1. Sounder
2. Sensor
3. Alarm relay
4. Terminals ”” and “+” are for power; terminals “NC” and “C” are the common trouble relay shown in the normal state for this detector
Testing
Test the detector after installation and regularly to verify that it is functioning properly.
To test the CO detector:
1. To test the alarm and trouble relay panel connection, first notify all persons and facilities that receive an alarm and trouble signals (to prevent unnecessary response).
2. Momentarily press the test/hush button to start a test cycle. During the test cycle the detector should beep four times with a five second pause, then beep four more times. The LED should flash red at each sounder beep. At the end of the test cycle, the green LED illuminates for approximately four seconds.
3. Momentarily disconnect the power supply from the detector and verify that the common trouble relay opens.
4. Verify that the panel reacts correctly to the alarm relay activation.
5. If the detector fails the test, verify that the power leads are connected properly, wait briefly then try again. If the detector fails again, replace it.
Maintenance
Clean the detector as needed with a clean cloth (either dry or dampened with water) to keep openings free from dust and dirt. Test the detector regularly.
Do not paint the detector or expose it to cleaning solutions.
Notification
Notification of carbon monoxide detectors should be consistent with NFPA 720 and the local AHJ. Notification zones should be consistent with the emergency plan for the protected premises.
P/N 1061018 • REV D • ISS 10FEB10 3 of 6
Page 4
Wiring
There are three typical wiring configurations:
Single device and single zone (Figure 3)
Multiple devices in a single zone (Figure 4)
Multiple devices with separate alarm and trouble zones (Figure 5)
CO detector replacement
The 250-CO Carbon Monoxide Detector has a long-life carbon monoxide electrochemical sensor. Replace the detector with a new 250-CO detector after six years from the date of manufacture or when an audible and visible annunciation occurs signaling end­of-life.
To silence the detector, push the test/hush button
Figure 4: Multiple devices, single zone configuration
1
Figure 3: Single device, single zone configuration
1
PWR
PWR
1. Alarm IDC (NO)
2. End-of-line device (provided by the life safety system) Note: Relay is shown in the normal state for this detector
2
2
PWR
PWR
1. Alarm IDC (NO)
Note: Relay is shown in the normal state for this detector
Figure 5: Multiple devices, separate alarm, trouble zone configuration
1
2
PWR PWR
1. Alarm IDC (NO)
2. Supervisory IDC (NC)
Note: Relay is shown in the normal state for this detector
2. End-of-line device (supplied by life safety system)
3
3
3. End-of-line device (supplied by life safety system)
4 of 6 P/N 1061018 • REV D • ISS 10FEB10
Page 5
General limitations of CO detectors
CO detectors require a source of power to work. Verify that the green LED on the detector is flashing at all times. Since this unit is powered by a control panel, it may not operate during a power failure or if the control panel is disabled.
WARNING: This product is intended for use in ordinary indoor
locations of family living units. It is not designed to meet compliance with Occupational Safety and Health Administration (OSHA) commercial or industrial standards.
The 250-CO detector is not intended to meet the requirements of CAN/CSA-6.19 (Residential Carbon Monoxide Alarming Devices). Please check with the local codes concerning the applicability of this requirement for each installation.
People with special medical problems should consider using specialized detection devices with less than 30 ppm (parts per million) alarming capabilities.
This detector only indicates the presence of carbon monoxide gas at the detector. CO may be present in other areas. Anything preventing CO from reaching the detector, such as closed doors, could delay or prevent detector activation.
If the unit is in trouble or at the end of its life, it may not sense CO and cannot be relied upon to monitor carbon monoxide levels.
CO detectors are not smoke detectors: This detector is designed
to detect CO from any combustion source. It is not designed to detect smoke, fire, or any other gas.
CO detectors may not be heard: A sound sleeper, or someone
who has taken drugs or alcohol, may not awaken if the detector is installed outside a bedroom. Normal noise due to stereos, television, etc. may also prevent the detector from being heard if distance or closed or partly closed doors muffle the sounder. This unit is not designed for the hearing impaired.
CO detectors are not a substitute for life insurance: Though
these detectors will warn against increasing CO levels, we do not warrant or imply in any way that they will protect lives from CO poisoning. They should only be considered as an integral part of a comprehensive safety program.
Specifications
Input voltage 12 or 24 VDC supplied by control panel or
resettable auxiliary power supply
Current consumption Normal Alarm
Alarm relay Type UL rating
Common trouble relay Type
UL rating
CO alarm level 70 ppm/60 to 240 minutes
Sounder 85 dB
Compatible control panel UL 985 or UL 864 Listed
Compatible electrical box North American 2-1/2 in. (64 mm) deep single-
Wire size 14 to 22 AWG (0.25 to 2.0 mm²)
Dimensions (W x L x D) Detector Adapter plate
Weight Detector Adapter plate
Color White
Operating environment Temperature Relative humidity Altitude
20 mA 40 mA (75 mA in test)
150 mA at 33 VDC Form C Zone
150 mA at 33 VDC Normally opened held closed with power applied Common
gang
3.1 x 4.6 x 1.3 in. (7.8 x 11.7 x 3.2 cm)
4.5 x 6.5 x 0.2 in. (11.4 x 16.5 x 0.5 cm)
4.7 oz. (133 g)
1.6 oz (46 g)
32 to 104°F (0 to 40°C) 0 to 90%, noncondensing Less than 6,000 ft. above sea level
Regulatory information
Manufacturer GE Security, Inc.
HQ and regulatory responsibility: GE Security, Inc., 8985 Town Center Parkway, Bradenton, FL 34202, USA
Year of manufacture
UL rating 12 VDC, 24 VDC
North American standards
The first two digits of the product serial number (located on the product identification label) are the year of manufacture.
UL 2075 This detector has been evaluated to the CO alarm sensitivity limits of UL 2034.
Contact information
For contact information see our Web site: www.gesecurity.com
P/N 1061018 • REV D • ISS 10FEB10 5 of 6
Page 6
6 of 6 P/N 1061018 • REV D • ISS 10FEB10
Loading...