GE Security 1200C, 2000C User Manual

Page 1
GE
Security
P/N 1068369 • REV 7.0 • ISS 03JUN09
1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Page 2
Copyright © 2009 GE Security, Inc.
This document may not be copied in whole or in part or otherwise reproduced without prior written consent from GE Security, Inc., except where specifically permitted under US and international copyright law.
Disclaimer The information in this document is subject to change without notice. GE Security, Inc.
(“GE Security”) assumes no responsibilit
y
for inaccuracies or omissions and specifically disclaims any liabilities, losses, or risks, personal or otherwise, incurred as a consequence, directly or indirectly, of the use or application of any of the contents of this document. For the latest documentation, contact your local supplier or visit us online at www.gesecurity.eu.
This publication may contain examples of screen captures and reports used in daily operations. Examples may include fictitious names of individuals and companies. Any similarity to names and addresses of actual businesses or persons is entirely coincidental.
Trademarks and patents GE and the GE monogram are trademarks of General Electric Company.
Other trade names used in this document may be trademarks or registered trademarks of the manufacturers or vendors of the respective products.
Intended use Use this product only for the purpose it was designed for; refer to the data sheet and user
documentation for details. For the latest product information, contact your local supplier or visit us online at www.gesecurity.eu.
Certification and compliance
European Union directives
2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as
unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
2004/108/EC (EMC directive): Non-European manufacturers must designate an authorized
representative in the Community. Our authorized manufacturing representative is:
GE Security B.V., Kelvinstraat 7, 6003 DH Weert, The Netherlands.
2006/66/EC (battery directive): This product contains a battery that cannot be disposed of as
unsorted municipal waste in the European Union. See the product documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling, return the battery to your supplier or to a designated collection point. For more information see: www.recyclethis.info.
Contact information
For contact information see our Web site: www.gesecurity.eu.
Page 3
1200C-2000C Fire Alarm Control Panel and Repeater User Manual i
Content
Important information ii
Introduction ii Product compatibility ii Support ii Limitation of liability ii
Controls and indicators 1
The control panel interface 1 User interface controls 2 General indicators 4 Controls buttons and indicators 6 Sounder buttons and indicators 7 Fire brigade buttons and indicators 8 Repeater buttons and indicators 9 Zone indicators 10
Operation 11
Panel operation in standby 11 Panel operation in fire alarm 12 Panel operation in pre-warning 13 Panel operation in fault 14
Maintenance 15
Fire alarm system maintenance 15 Battery maintenance 16
Product compliance 17
Page 4
ii 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Important information
Introduction
This is the installation manual for GE Security 1200C-2000C addressable fire alarm control panels and repeaters. Read these instructions and all related documentation entirely before operating this product.
Product compatibility
All models are compatible with GE Security Aritech fire detectors and manual call points. Compatibility with third-party products cannot be guaranteed. Consult your local supplier for further information.
Support
For assistance operating and maintaining this product, contact your installation or maintenance contractor.
Limitation of liability
Installation in accordance with this manual, applicable codes, and the instructions of the authority having jurisdiction is mandatory. GE Security shall not under any circumstances be liable for any incidental or consequential damages arising from loss of property or other damages or losses owing to the failure of GE Security products beyond the cost of repair or replacement of any defective products. GE Security reserves the right to make product improvements and change product specifications at any time.
While every precaution has been taken during the preparation of this manual to ensure the accuracy of its contents, GE Security assumes no responsibility for errors or omissions.
Page 5
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 1
Controls and indicators
This chapter describes the control panel interface, indicators, and controls.
The control panel interface
Figure 1: The control panel interface
1. LCD screen
2. Alphanumeric keypad
3. Fire brigade buttons and indicators
4. Key switch
5. Sounder buttons and indicators
6. Repeater buttons and indicators
7. Controls buttons and indicators
8. Zone indicators
9. General indicators
Page 6
2 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
User interface controls
Key switch operation
The key switch is used to restrict the operation of the fire panel controls.
Table 1: Key switch enable/disable
Position Status Description
Disabled Panel operation is restricted.
Enabled Panel operation is not restricted.
The Silence Buzzer and Test buttons operate with the key switch in any position.
User interface controls
The user interface has 20 buttons, 10 of which are alphanumeric. The remaining 10 are described below.
Table 2: Description of the control panel user interface controls
Button Description
Alpha selection (when using the alphanumeric buttons)
Display the most recent alarm
Print the current screen
Scroll between Alarm, Fault and Conditions. View additional information when the "MORE" prompt appears on the LCD screen.
Exit a menu
Enter or confirm a value or selection
Move to the next field on the LCD screen
Move to the previous field on the LCD screen
Page 7
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 3
Button Description
Increase a value
Decrease a value
Page 8
4 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
General indicators
Figure 2: General indicators
1. Fire Alarm LEDs
2. Fault LED
3. Disable LED
4. Supply fault LED
5. System fault LED
6. Processor running LED
7. Supply On LED
Table 3: Description of general indicators
LED indicator Description
Fire Alarm Two red LEDs indicate a fire alarm.
Fault A yellow LED indicates one or more of the following general faults:
• Device fault·
• Supply fault
• Processor fault
• Bell fault
• Communications fault
Fire brigade fault·
• Any test mode·
• Any disablement
Page 9
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 5
LED indicator Description
Disable A yellow LED indicates that one or more of the following is disabled:
Devices on the loop
• Area
• Zone
• Sounders
• Fire brigade·
• Any delays ON
Supply fault A yellow LED indicates one or more of the following supply faults:
A mains failure
A battery problem (battery disconnected or not charging)
An earth fault
A yellow LED indicates one or more of the following: System fault
Internal memory failure
• Clock failure
Watchdog time out
• Tamper switch
• Service switch
• Logic error
• Memory lock
No checksums calculated
Hardware test fault
Fireman’s' panel down
• Repeater down
• Panel down
Global repeater down
• Input fault
• Output fault
• Configuration fault
• Checksum fault
Protected memory overwritten
• Time date wrong
• Access fault
• FEP fault
• Watchdog time-out
Processor running A flashing green LED indicates normal operation
Supply on A steady green LED indicates that the control panel is powered up
Page 10
6 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Controls buttons and indicators
Figure 3: Control buttons and indicators
1. Silence Buzzer
2. Reset
3. Disable
4. Test
5. Test Third Source (2000C control panels only)
Note: Some features can only be accessed if the key switch is enabled (see “Key
switch operation” on page 2).
Table 4: Description of controls LED indicators
LED indicator Key switch position Description
Silence Buzzer Enabled or disabled The control panel internal buzzer activates for any
new condition.
The buzzer sound is:
Constant for a fire alarm
Fast intermittent for a fault warning
Slow intermittent for a condition warning Press the Silence Buzzer button to silence the buzzer.
A steady yellow LED indicates that the buzzer has been silenced.
Reset Enabled Press this button to reset the fire panel.
Disable Enabled Press this button to display the Disable menu on the
LCD screen. The yellow LED indicates a disablement.
Test Enabled Press this button to display the Test menu on the LCD
screen. The yellow LED indicates that a feature or device is being tested.
Test Third Source Enabled or disabled Press this button to test the third source battery. The
yellow LED is steady and the internal buzzer sounds intermittently.
Page 11
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 7
Sounder buttons and indicators
Figure 4: Sounder buttons and indicators
1. Sound
2. Delay ON/OFF
3. Fault/Disable
4. Silence
Note: Some features can only be accessed if the key switch is enabled (see “Key
switch operation” on page 2).
Table 5: Description of sounders LED indicators
LED indicator Key switch position Description
Sound A red LED indicates that the sounders are activate
(sounding).
Delay ON/OFF A single LED indicates that the sounder delay has been
toggled ON or OFF.
Fault/Disable Enabled Press the Fault/Disable button to disable the sounders.
The LED flashes when a fault is detected and is steady when the sounders are disabled.
Silence Enabled A yellow LED indicates that the sounders have been
silenced.
Note: Functionality of the Sound and Silence buttons is defined by the control panel
operating mode.
Page 12
8 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Fire brigade buttons and indicators
Figure 5: Fire brigade buttons and indicators
1. Signal
2. Delay ON/OFF
3. Fault/Disable
4. Stop fire brigade
Note: Some features can only be accessed if the key switch is enabled (see “Key
switch operation” on page 2).
Table 6: Description of fire brigade LED indicators
LED indicator Key switch position Description
Signal Enabled Push this button to activate the fire brigade notification.
A red LED indicates that a signal has been sent.
Delay ON/OFF The LED indicates that the fire brigade delay has been
toggled ON or OFF.
Fault/Disable Enabled Push this button to disable the fire brigade notification.
The LED is steady when the feature is disabled and flashes when a fault is detected.
Stop Fire brigade Enabled Push this button to stop the fire brigade notification A
yellow LED indicates that the signal has been stopped.
Note: Functionality of the Signal and Stop Fire Brigade buttons is defined by the
control panel operating mode.
Page 13
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 9
Repeater buttons and indicators
Figure 6: Repeater buttons and indicators
1. Panel
2. All
Table 7: Description of repeater LED indicators
LED indicator Key switch position Description
Panel Enabled or disabled This indicator is used by global and local repeaters for
panel emulation. The yellow LED indicates that a control panel is being emulated.
Global repeater
To start emulation:
1. Press the Panel button.
2. Enter the number of the panel to be emulated
3. Press the Enter button
To stop emulation:
1. Press the Panel button.
2. Press "0".
3. Press the Enter button.
When a global repeater is emulating a panel it is not necessary to stop emulation before emulating another panel. The global repeater will automatically stop the emulation before trying to emulate another panel.
Local repeater:
Press the Panel button to start emulating the panel. Emulation will stop when the button is pressed again.
All Enabled or disabled Press this button for the global repeater panel to send a
command to all control panels that the global repeater communicates with. The command from the next command button to be pressed is then sent to all corresponding panels.
Page 14
10 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Zone indicators
Each zone has two LED indicators. A red LED indicates a fire alarm and a yellow LED indicates a fault. The zone fault LED flashes when there is a fault and remains steady if the entire zone has been disabled.
Figure 7: Zone fire and fault indicators
Page 15
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 11
Operation
Panel operation in standby
Normal operation (standby) is indicated as shown below.
Table 8: Normal operation
LED indicator Status
Supply ON The green LED is steady
Processor running The green LED is flashing
Sounder indicators: Delay ON or Delay OFF
The yellow Delay ON LED is steady when a delay is running. This is logged as a condition. Press the SILENCE BUZZER button to silence the internal buzzer.
Fire brigade indicators: Delay ON or Delay OFF
The yellow Delay ON LED is steady when a delay is running. This is logged as a condition. Press the SILENCE BUZZER button to silence the internal buzzer.
All other LEDs OFF
Figure 8: System Status menu (normal operation)
X Î
SYSTEM STATUS Fri 12/10/04 09:17:37
(Site text – up to 40 characters)
Y Î
(Site text – up to 40 characters)
Z Î
Scanning Day Mode Zones on E
[ Î \ Î
Alarm: 0 Faults: 0 Cond.: 0 P: 1 SDZ
1. Menu title, date, and time
2. Site text (up to 40 characters)
3. Operations status line (operations are displayed in full here)
4. User keys (none shown in this screen)
5. System status. The current number of fire alarms, faults, and conditions are displayed here as well as repeater information (P is global with panel number shown, L is local) and a summary of the operations (eg, SDZ).
Page 16
12 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Panel operation in fire alarm
The Fire Alarm LEDs are lit and the internal buzzer sounds constantly to indicate a fire alarm. Sounders are also activated.
Figure 9: System Status menu screen in normal operation
ALARM: 1 Event: 79 Active Zone: 6 Area: 1 ALMLVL Address: 1/12 Fire MCP 06/02/05 09:39:34
(Site text – up to 40 characters) ¿À X Alarm: 1 Faults: 0 Cond.: 0 P: 1 SDZ
1. Look at the screen to see where the fire is located. In the example above, the fire is in zone 6, area 1 at address 12 in loop 1.
2. Press Display alarm to view the most recent alarm.
3. If more than one fire alarm exists, use the up and down arrows to view each alarm.
4. Press Silence Buzzer to silence the internal buzzer and to acknowledge the alarm.
5. Once the evacuation of the building is complete, silence the sounders by turning the enable/disable key switch to enable (see “Key switch” on page 2).
6. Press the Silence button. The yellow Silence LED is steady.
7. If you need to restart the evacuation, press the Sound button.
8. When the fire situation is under control, the fire panel may be returned to normal condition by turning the enable/disable key switch to enable.
9. Press the Reset button.
If the fire alarm continues, then one of the following is true:
• The fire is not under control (perform the above checks again).
• The cover glass of a manual call point is broken (repair or disable the manual call point).
Page 17
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 13
Panel operation in pre-warning
The internal buzzer sounds with a short intermittent tone to indicate a pre-warning.
Figure 10: The alarm screen (pre-warning)
ALARM: 1 Event: 79 Active Zone: 6 Area: 1 ALMLVL Address: 1/12 Pre-Warning MCP 06/02/05 09:39:34
(Site text – up to 40 characters) ¿À X Alarm: 0 Faults: 0 Cond.: 0 P: 1 SDZ
1. Look at the screen to see the location of the detector in pre-warning. In the example shown above, the pre-alarm is in zone 6, area 1 at address 12 in loop 1.
2. If more than one pre-warning exists, use the up and down arrows to view each pre-warning condition.
3. Press Silence Buzzer to silence the internal buzzer and to acknowledge the pre­warning.
4. Investigate the cause of the pre-warning condition.
5. When the pre-warning condition is under control, turn the enable/disable key switch to enable to return the fire panel to normal condition.
6. Press the Reset button.
If the pre-warning continues, then one of the following is true:
• The event is not under control (return step 3 above).
• The detectors are contaminated with smoke (clean the detectors).
Page 18
14 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Panel operation in fault
The internal buzzer sounds to indicate a fault.
1. Press the Silence Buzzer button to silence the internal buzzer.
2. The yellow Fault LED is steady to indicate a fault in the fire system.
3. The yellow fault LED for the corresponding feature or device is also steady.
Table 9: Fault LED indications
LED indication Action required
A specific zone Call the maintenance engineer.
Disable A zone, loop, or device has been disabled.
Supply fault Check the mains supply and battery.
System fault Call the maintenance engineer.
Test (Controls) A specific zone has been placed in test mode. The fault remains until
the test is complete.
Fault/Disable (Sounders) The sounders are disabled or there is a fault with the connection.
Enable the sounders. If the fault continues, check the connections.
Fault/Disable (Fire brigade) The fire brigade notification has been disabled or there is a fault with
the connection, Enable the Fire brigade notification. If the fault continues, check the connections.
Fault details are also displayed on the LCD screen. The figure below shows a communication fault in zone 6, area 1 at address 12 in loop 1 (the fault is in a specific zone).
Figure 11: The alarm screen (fault)
ALARM: 1 Event: 79 Active Zone: 6 Area: 1 ALMLVL Address: 1/12 Communication fault MCP 06/02/05 09:39:34
(Site text – up to 40 characters) ¿À X Alarm: 0 Faults: 1 Cond.: 0 P: 1 SDZ
Page 19
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 15
Maintenance
This section provides information to help you maintain your GE Security product.
Caution: This product must be installed and maintained by qualified personnel
adhering to all applicable standards and local authority laws.
Fire alarm system maintenance
Your fire alarm system must be regularly tested and serviced in order to ensure its reliable operation. The following maintenance routine is recommended:
Daily
• Check that the panel indicates normal operation. If it does not, check that any fault indicated is recorded in the log book and reported to the maintenance personnel.
• Check that any fault warning recorded the previous day has received attention.
Quarterly
• Check the log book entries and ensure that any necessary action has been taken.
• Check the state of the batteries and corresponding connections.
• Visually inspect the control panel for signs of moisture and other deterioration.
• Test the alarm, fault, and ancillary functions of the fire panel.
Yearly
• Carry out the recommended daily and quarterly inspection and test routines.
• Check each detector for correct operation in accordance with the manufacturer's recommendations.
• Visually inspect all cable fittings and equipment to ensure that no damage has taken place.
• Visually inspect all electrical connections to make sure that they are securely fastened, that they have not been damaged and that they are appropriately protected.
• Visually inspect the manual call points, detectors, and sounders to ensure that no structural or occupancy changes have affected their location requirements.
Page 20
16 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Battery maintenance
Batteries must be replaced periodically as recommended by the manufacturer. The useful life of the battery is approximately 4 years. Avoid the total discharge of the batteries.
Battery test fail
When the control panel indicates that the battery test has failed, check the following:
• That the battery leads are in good condition
• That the battery leads are connected securely and correctly at the battery and at the panel
• That the control panel event log does not indicate a mains failure in the last twenty-four hours
If the leads are in good condition, all connections are correct, and the control panel continues to report that the test has failed twenty-four hours after the last mains failure, then the batteries should be replaced immediately.
Replacing batteries
To replace the batteries:
1. Disconnect and remove the existing batteries from the cabinet.
2. Install and connect the replacement batteries using the bridge provided. Observe correct polarity.
Always use the recommended replacement batteries. Dispose of used batteries according the European regulations and/or instructions from local authorities.
Page 21
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 17
Product compliance
All 1200C-2000C control panels are designed to comply with the requirements of European standards EN 54-2 for control and indicating equipment, and EN 54-4 for power supply equipment).
EN 54-2 compliance for control panels with the SD2000 module
Control panels with the SD2000 module installed have the following options with requirements according to EN 54-2:
Table 10: EN 54-2 options with requirements with the SD2000 module
Clause Description
7.8 Output to fire alarm devices
7.9 Output to fire routing equipment
7.10 Output to fire protection equipment
7.11 Delay to output
7.12 Dependency on more than one alarm signal
7.13 Alarm counter
8.4 Total loss of the power supply
9.5 Disablement of addressable points
10 Test
EN 54-2 compliance for control panels with the VDS2000 module
Control panels with the VDS2000 module installed have the following options with requirements according to EN 54-2:
Table 11: EN 54-2 options with requirements with the VDS2000 module
Clause Description
7.8 Output to fire alarm devices
7.9 Output to fire routing equipment (+ VDE0833)
7.10 Output to fire protection equipment (+ VdS requirements)
7.11 Delay to output
7.12 Dependency on more than one alarm signal (+ VDE0833)
7.13 Alarm counter
8.4 Total loss of the power supply
8.9 Output to fault routing equipment
9.5 Disablement of addressable points
10 Test
Page 22
18 1200C-2000C Fire Alarm Control Panel and Repeater User Manual
Control panels with the VDS2000 module also allow for:
• Interface to FBF
• Interface to FAT
• interface to FSK
• interface to Hauptmelder
• interface to EMZ
Construction Products Directive (CPD)
Details of the CPD certification for 1200C-2000C fire panels and global repeaters are shown below.
Table 12: CPD certification for 1200C-2000C series fire panels and global repeaters
Certification
Certification body 1134
Certificate number 1134-CPD-069
Manufacturer GE Security B.V., Kelvinstraat 7,6003 DH Weert, The Netherlands.
Page 23
1200C-2000C Fire Alarm Control Panel and Repeater User Manual 19