Signet 2850 Conductivity/Resistivity Sensor Electronics (PVDF)
*3-2850.090-1*
3-2850.090-2 Rev. C 03/15
Operating Instructions
English
3-2850-51, 3-2850-52
with ¾-in. adapter
3-2850-61, 3-2850-62, 3-2850-63
with Universal adapter
3-2850-51-XXV(D), 3-2850-52-XXV(D)
PVDF Integral System
Description
• Signet 2850 Conductivity/Resistivity Sensor Electronics provides either a two-wire
4 to 20 mA output or Digital (S3L) format.
• The 4 to 20 mA output models provide eight ranges for each electrode cell constant,
plus the ability to invert each range.
• The EasyCal feature allows the devices to automatically recognize standard
conductivity test solution values for simple fi eld calibration.
• The Conductivity Sensor provided with integral systems will have its custom cell
constant information programmed into the electronics at the factory to provide a
2% sensor accuracy. See page 6 for details.
Table of Contents
Description ............................................................................................ 1
Dimensions ........................................................................................... 1
Warranty Information ............................................................................ 2
Product Registration ............................................................................. 2
Safety Information................................................................................. 2
Specifi cations........................................................................................ 2
Conductivity Sensor Dimensions .......................................................... 3
Operating Range Chart......................................................................... 3
In-Line Installation................................................................................. 4
Tank Installation .................................................................................... 4
4 to 20 mA Wiring ................................................................................. 5
Digital (S3L) Wiring ................................................................................ 5
Dual Input Wiring (Dual Digital (S3L) Output) ........................................ 5
Cell Constant Selection ........................................................................ 6
Range Selection for 4 to 20 mA Output ................................................ 7
Calibration............................................................................................. 8
EasyCal ................................................................................................ 8
Dual Input Calibration ........................................................................... 8
Maintenance ......................................................................................... 9
Troubleshooting .................................................................................... 9
Electronic Certifi cation ........................................................................ 10
Ordering Information ........................................................................... 12
• English
• Deutsch
• Français
• Español
• Italiano
Dimensions
2850-51, -52 Integral mount 2850-61, -62, -63 Universal mount
95 mm
3.74 in.
85 mm
3.34 in.
95 mm
3.74 in.
82 mm
3.24 in.

Warranty Information
Specifi cations
Refer to your local Georg Fischer Sales offi ce for the most
current warranty statement.
All warranty and non-warranty repairs being returned must
include a fully completed Service Form and goods must be
returned to your local GF Sales offi ce or distributor.
Product returned without a Service Form may not be
warranty replaced or repaired.
Signet products with limited shelf-life (e.g. pH, ORP, chlorine
electrodes, calibration solutions; e.g. pH buffers, turbidity
standards or other solutions) are warranted out of box but not
warranted against any damage, due to process or application
failures (e.g. high temperature,
mishandling (e.g. broken glass,
chemical poisoning, dry-out) or
damaged membrane, freezing
and/or extreme temperatures).
Product Registration
Thank you for purchasing the Signet line of Georg Fischer
measurement products.
If you would like to register your product(s), you can now
register online in one of the following ways:
• Visit our website www.gfsignet.com.
Under Service and Support click on
Product Registration Form
• If this is a pdf manual (digital copy),
click here
Safety Information
1. Depressurize and vent system prior to installation or removal.
2. Confi rm chemical compatibility before use.
3. Do not exceed maximum temperature/pressure specifi cations.
4. Wear safety goggles or faceshield during installation/service.
5. Do not alter product construction.
6. When using chemicals or solvents, care should be taken
and appropriate eye, face, hand, body, and/or respiratory
protection should be used.
Caution / Warning / Danger
Indicates a potential hazard. Failure to follow all warnings
may lead to equipment damage, injury, or death
Electrostatic Discharge (ESD) / Electrocution Danger
Alerts user to risk of potential damage to product by ESD,
and/or risk of potential of injury or death via electrocution.
Personal Protective Equipment (PPE)
Always utilize the most appropriate PPE during
installation and service of Signet products.
Pressurized System Warning
Sensor may be under pressure, take caution to vent
system prior to installation or removal. Failure to do so
may result in equipment damage and/or serious injury.
Note / Technical Notes
Highlights additional information or detailed procedure.
General
Compatible Electrodes ............. Any Signet Conductivity/
Resisitivity electrode
(2818-2823, 2839-2842)
Temperature Compensation .....PT-1000 RTD (2% per °C)
Pure Water Compensation ....... Auto-switching when using
0.01 cell and raw conductivity
value < 0.5 S
EasyCal
Automatic recognition of the following conductivity values:
• 146.93 S, 1408.8 S, 12856 S (@ 25 °C)
(Test solutions per ASTM D1125-95)
• 10 S, 100 S, 200 S, 500 S, 1000 S, 5000 S, 10,000 S,
50,000 S, 100,000 S (@ 25 °C)
Power
• 12 to 24 VDC (4 to 20 mA output)
• 5 VDC ±5% regulated, 3.0 mA max. for Digital (S
3
L) output
(Reverse polarity and short circuit protected)
Digital (S
3
L) Output ................. Serial ASCII, TTL level 9600 bps
Accuracy
• Conductivity ..........................±2% of reading
• Temperature ..........................±0.5 °C
Resolution
• Conductivity ..........................0.1% of reading
• Temperature ..........................< 0.2 °C
Update Rate
• Single Input models ..............< 600 ms
• Dual Input models .................< 1.2 s
Current Output
Field-selectable ranges. Factory set span:
• 0.01 cell
(2818, 2819, 2839)
.. 4 to 20 mA = 0 to 100 S
• 0.10 cell (2820, 2840) ........... 4 to 20 mA = 0 to 1000 S
• 1.0 cell (2821, 2841) ............. 4 to 20 mA = 0 to 10,000 S
• 10.0 cell (2822, 2842) ........... 4 to 20 mA = 0 to 200,000 S
• 20.0 cell (2823) ..................... 4 to 20 mA = 0 to 400,000 S
Max. Loop Resistance .............. 50 @ 12 VDC
325 @ 18 VDC
600 @ 24 VDC
Accuracy ................................... ±2% of output span
Resolution.................................7 A
Update Rate .............................<600 ms
Error Indication ......................... 22 mA
3
Available data via Digital (S
L) Output
• Raw conductivity
• Calibrated conductivity
• Calibrated temperature-compensated conductivity
• Temp. Error Indication ........... Open input and out-of-range
diagnostics for temperature or
internal electronic error.
Environmental
Material ..................................... PBT
Enclosure Rating ...................... NEMA 4X/IP65
Operating Temperature .............-10 to 85 °C (14 to 185 °F)
Storage Temperature ................-20 to 85 °C (-4 to 185 °F)
Relative Humidity......................0 to 95%, non-condensing
Shipping Weight .......................0.75 kg (1.75 lb.)
Standards and Approvals
• CE, RoHS Compliant
• Manufactured under ISO 9001 for Quality,
ISO 14001 for Environmental Management and
OHSAS 18001 for Occupational Health and Safety.
China RoHS (Go to www.gfsignet.com for details)
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference, and
(2) This device must accept any interference received,
including interference that may cause undesired operation.
2
2850 Conductivity/Resistivity Sensor Electronics

In-Line Installation Tank Installation
While the 2850-5X and 2850-6X electronics cannot be
submerged, either model will accommodate tank installation.
Select any electrode with a 5 m (15 ft) cable. The cable may
be cut to length, but it CANNOT BE EXTENDED.
Most of the Conductivity/Resistivity electrodes
used with the 2850 can be installed into
standard 3/4 in. (NPT or ISO 7-R3/4) fi ttings.
The 2850-5X models are designed for
integral systems, where the electronics
are attached directly to the sensor.
The preferred installation for in-line applications directs fl ow
straight into the electrode. This confi guration reduces the
probability of entrapped air bubbles, and provides the best
continuous sampling of the fl uid content.
The universal adapter included with 2850-6X models can
be attached to the top of a tank or mounted to a surface near
the tank.
Adapt the 2850-5X models to tank installations by attaching a
clamp to the conduit.
If the electrode is mounted vertically in a tee, do not recess
the electrode orifi ces inside the tee. Mounting upside down
may help prevent air entrapment.
An oversized tee or fl ow cell may be helpful for inline
installations.
At least 4 threads (ANSI B1.20.1) must be engaged to meet
the pressure rating as published in the specifi cations.
Use the 2850-6X models for in-line installations where the
electronics must be separated from the electrode.
Conductivity electrodes with sanitary fl ange fi ttings must be
installed using this option.
4