Georg Fischer 2819-2823, 2850 User Manual

Page 1
CSA is cross sectional area.
*
www.gfsignet.com
Technical Reference Section: Conductivity/ Resistivity
Principle of operation
AC
+
Half Cells
Voltage
+
z
+
+
+
+
+
+
+
+
+
+
+
+
+
+
1cm
1cm
+
+
2
-1
Graphs
221
Most conductivity electrodes consist of two measuring half-cells. The geometry of the half-cells can be tai­lored to provide highly accurate mea­surements over a specific conduc­tivity range. Cell constants
help to
describe electrode geometry for the purpose of selecting the appropriate
x
electrode for a given application. A cell constant is defined as the length
y
between the two half-cells divided by the area of the cells.
Conductivity Cell Constant = =
Length
CSA*
z
xy
As an example, When x = y = z = 1cm the cell constant becomes = 1cm
Solutions of very low conductivity (high resistivity) such as ultra-pure water are best measured with half-cells that are very close together (i.e., cell constant =
-1
0.01cm
). Highly conductive solutions should be measured with half-cells that
are farther apart and that have relatively little cross sectional area between
-1
them (i.e., cell constant = 20.0cm
Temperature Compensation
The conductivity of a solution is highly dependent upon temperature. Therefore, conductivity measure­ments are almost always converted to an equivalent conductivity at the common reference temperature of 25°C (77°F). This is accomplished by means of temperature compensa­tion algorithms in the instruments, which require temperature as well as conductivity measurement input. To simplify and facilitate this require­ment all Signet conductivity elec­trodes contain high-quality tempera­ture sensing elements intelligently positioned for quick and accurate response.
).
siderably with the ionic composition of the solution and can range from less than 1% to more than 3% per °C. This is true of regional ground water sources as well as for other solutions such as brackish water, acids and bases. Signet instruments allow the entry of custom linear compensation coefficients for these applications. See the instruction manual of any Signet conductivity instrument for details. The conductivity or resistivity of pure water is not a linear function with respect to temperature. In fact, the latest Signet conductivity instru­ments utilize a sophisticated polyno­mial to compensate for the peculiar
effects. For seamless measurement Temperature effects on conductivity are more or less linear for normal water-based solutions, hovering around 2% per °C. However, the actual linear relationship varies con-
accuracy all current Signet conduc-
tivity instruments switch automati-
cally between linear and pure-water
compensation as certain measure-
ment thresholds are crossed. Temperature Compensation Exception
One exception to the requirement for temperature compensation has been estab­lished by USP (United States Pharmacopeia), which prescribes limits of accept­ability for ultra-pure water quality based upon non-compensated measurements. This methodology is used to eliminate measurement variances that may result from differences in the pure-water temperature compensation algorithms used by different manufacturers of conductivity measurement equipment. A more thor­ough treatment of the USP standard and instrument functionality can be found in the instruction manuals of the following Signet conductivity instruments: Model 8900 Multi-Channel, Multi-Parameter Controller (Appendix D), model 8860 Dual Channel Conductivity/Resistivity Controller.
Choosing
Products
Instrument
Multi-Pa-
rameter
Flow
pH/ORP
Conductivity/
Resistivity
Temperature,
Products
Other
Installation
Wiring &
Reference
Technical
Temperature/
Pressure
of Terms
Glossary
Reference
Part No.
Index
Page 2
p
p
Relay Information
The two most common methods of controlling a process are “on/off” and “pro­portional” control. In on/off control, relay setpoints are defined as either high or low limits on the process variable. When the measurement value reaches a limit the relay is energized, typically for the purpose of opening a valve or start­ing a pump to introduce a chemical reagent to the process. This should cause the measurement value to change in the direction of the setpoint as shown in these on/off control diagrams:
High limit on/off relay control
= HI setpoint
= Hysteresis
= Relay energized
= Relay de-energized
pH
Notice the relay will not de-energize until the setpoint is exceeded by the hysteresis value. This is a program­mable value and is primarily used to prevent ”relay chatter”, which occurs if a relay is set to energize and de­energize at the same value. Because of hysteresis, and because reagent delivery is fairly constant while the relay is energized, a condition known as “overshoot” is inherent to the on/ off control method. Overshoot refers to the introduction of more chemical reagent than is absolutely necessary for achieving a desired adjustment to the process value, and can be expen­sive over time.
Proportional control is a popular alternative to the on/off control method. This method typically makes use of variable-rate metering pumps to reduce overshoot and improve precision. Establishing a propor­tional control scenario requires the selection of setpoint(s), deviation
Low limit on/off control
pH
= LO setpoint
= Hysteresis
= Relay energized
= Relay de-energized
range(s) and maximum pulse rates. The example shown here illustrates how two relays in ”pulse mode” can be used to proportionally control pH within a desired range, or to a single setpoint. This is called “Dual Propor­tional Control”. Of course, a single relay in proportional pulse mode can be used to establish a high or low limit and will also reduce overshoot.
Metering pumps are idle at and be­tween setpoints. When a setpoint is exceeded, the pump begins delivering reagent at a rate proportional to the difference between the measurement value and the setpoint. The larger the difference, the faster the deliv­ery. The programmed deviation value defines how quickly the maximum pulse rate is reached. Depending on the input requirements of the meter­ing pump, proportional control can also be accomplished with scaleable 4 to 20 mA outputs instead of pulsing relays or open collectors.
Dual proportional pulse relay control
Maximum Pulse Rate
0 pH
Deviation=
5.30 pH
LO
5.30 H
HI
7.50 H
Deviation=
3.50 pH
11.00 pH
222
14 pH
pH
Maximum Pulse Rate
Deviation=
5.20 pH
0
2.10 pH
LO and HI
7.30 pH
Deviation=
4.90 pH
12.20 pH
14 pH
www.gfsignet.com
Page 3
Open Collector Output
Many Signet instruments and sensors feature “Open Collector Outputs” for purposes of signal transmission, alarming, control signal output, etc. Although such outputs allow for a lot of wiring flexibility, care must be taken not to destroy the circuits via incorrect polarity, over-voltage, transients or current overload. Below is an explanation of proper wiring and dimensioning of related circuit components. Please note that the following recommendations may or may not apply to other manufacturer’s equipment.
1. Function
Open Collector (“OC”) outputs are low powered, solid state switches.
Although the term “Open Collector” stipulates the use of bipolar transistors (NPN-type or PNP-type) as a switch, nowadays Field Effect Transistors (FET or MOSFET) are used. Unlike electromechnical switches (e.g. pushbuttons or dry contact relays) these OC switches are very fast, use little power, are inexpensive, do not bounce and do not wear. However, OC’s are also more limited in terms of voltage and current rating as well as being polarized (i.e. they have a “plus” and “minus” terminal and thus DC only switching capability). They are less tolerant to overload abuse than electromechanical devices. Usually these switches have higher resistance and voltage drop.
2. Sensor Wiring
A typical example of the need for high speed switching capability is the
OC frequency output of Signet flow sensors like 3-2536 or 3-2540. Signal frequencies can reach several hundred pulses per second while voltage and current requirements are small enough, allowing the use of a transistor switch. For each output pulse this switch connects the signal output to the negative supply or ground terminal of the sensor and is therefore an “NPN” style output. Signet does not produce sensors with PNP style outputs (which connect the signal output internally to the positive supply terminal).
Choosing
Products
Instrument
Multi-Pa-
rameter
Flow
pH/ORP
Conductivity/
Resistivity
Temperature,
Products
Other
Do not exceed the absolute maximum voltage rating of the OC output as listed in the sensor specifications, normally 27 or 30 Volt, DC only. This includes changes to power line fluctuations, transients or power supply instability, otherwise dam­age to the OC will occur.
Most indicating instruments or control system inputs require a signal
voltage of 0 to 5V (TTL or CMOS logic levels) or 0 to 24V. Therefore, Open Collector output circuits must be complemented with a “Pull-Up-Resistor” to function properly. Please see the following example diagram for wiring with a PLC input:
+5V to
Gnd
+24V
Power Supply
V+
Signet
Sensor/Instrument
Signal OC­Switch
Gnd
Pull-Up­Resistor
Input
Gnd
PLC
Please note that the voltage connected to the positive sensor supply (V+)
must correspond to the required high-level PLC input voltage (i.e. if the high-input voltage of the PLC is 24V, then the pull-up must be supplied with 24V). If the input is “TTL-Level” or “CMOS-Level”, that means 5V for high level, then the pull-up should not be connected with a supply higher than 5V.
Signet instruments already have the pull-up-resistor and the sensor power
supply built into the instrument. No external pull-up-resistors are required.
Installation
Wiring &
Reference
Technical
Temperature/
Pressure
Graphs
of Terms
Glossary
Reference
Part No.
Index
www.gfsignet.com
223
Page 4
Open Collector Output (continued)
3. Instrument Output Wiring
Open collector control and alarm outputs on Signet instruments (i.e.
ProcessPro instrument’s power supply. That means these can be used in the above mentioned NPN configuration as well as in PNP configuration, if required. Below are a few sample circuits:
• PLC Wiring “NPN” style
Signet
Instrument/Sensor
OC­Switch
• Alarm circuit or alarm lamp wiring to a single Signet instrument
®
or ProPoint™ series) are electrically isolated from the
+5V to
+24V
OC+
OC-
Pull-Up­Resistor
Input
Gnd
PLC
Gnd
Power Supply
Signet
Instrument
OC­Switch
OC+
Alarm
Circuit
V+
Gnd
Power Supply
• Alarm circuit or alarm lamp wiring to serve multiple Signet instruments
- Triggers the alarm if any one of the instruments open collector outputs are on.
Signet
Instrument
OC­Switch
OC+
Signet
Instrument
OC­Switch
OC+
Signet
Instrument
OC­Switch
OC+
Alarm
Circuit
V+
Gnd
Power Supply
224
www.gfsignet.com
Page 5
Open Collector Output (continued)
4. Voltage and Current Limitation
As mentioned before, the supply voltage in the OC output circuit MUST
be limited to the specified maximum OC voltage (see operating manual for specific instrument). The use of a quality regulated 5V, 12V or 24V (depending on the application) power supply is recommended.
The current through the Open Collector switch must be limited. Typical OC
outputs allow only for 10 to 50mA switch current (please consult manual). Exceeding this current limit can burn out the OC output components immediately. Please see the following section on how to dimension the loads.
5. Load and Pull-Up/Down Resistor Considerations
By utilizing basic arithmetic and Ohm’s law, one can determine the safe
limits of load resistance. When the OC switch is closed, almost the entire supply voltage is applied to the load, (i.e. the pull-up or pull-down resistor, the alarm horn input, a potential power relay coil or annunciator lamp). The resulting current through the load and through the OC switch, as well, can be calculated as:
(Current) = (Supply Voltage)/(Load Resistance)
Choosing
Products
Instrument
Multi-Pa-
rameter
Flow
pH/ORP
Conductivity/
Resistivity
Temperature,
• Example 1: The supply voltage is 24V and a
pull-up-resistor of 10kΩ is used. Current is 24/10,000 = 2.4mA
(If the OC current rating is 10mA, then in this example, it would be considered safe.)
• Example 2: The supply voltage is 12V and a horn
with a resistance of 100Ω is used
Current is 12/100 = 120mA
(Even if the OC current rating is 50mA, this load will damage the instrument)
6. Transient Protection
There are several “difficult” load cases that must be considered:
• Inductive loads: These can be power relay
or other solenoids, motors, alarm horn coils, etc. Such loads generate very high voltage spikes everytime the load switches. If such a load is unavoidable, the use of transient suppression
• Capacitive loads: This type of load should be
rare but can occur if the load contains an internal power supply/regulator that is fed from the output circuit. In such a case, it must be assured that the in-rush current does not
exceed the OC current rating. components, or Signet RC­Filters (3-8050.396), or snubbers, wired parallel to the load is required. This is critical, as a single transient pulse may destroy the output.
• Incandescent lamps: Such lamps have a very high
start-up current until the
filament glows and the current
settles to the specified value.
The use of incandescent
lamps on an OC output is not
recommended. An LED type
annunciator should be used
instead.
Products
Other
Installation
Wiring &
Reference
Technical
Temperature/
Pressure
Graphs
of Terms
Glossary
Reference
Part No.
www.gfsignet.com
Index
225
Page 6
Open Collector Output (continued)
7. “Active High” and “Active Low” Setting
Depending on the desired function of the circuit attached to the OC output, it
may be necessary to have the OC output switch turned “on” or “off” when the criteria for the activation of this output are met.
By default, Signet instruments are set to operate in “active low” mode.
This means when the user-defined condition for the activation is met (e.g. exceeding of an alarm limit) the OC switch is turned “on”. If wired as standard “NPN-style” output (see previous page) the logic level of the attached control system or PLC input consequently becomes “low” logic level.
If a high input logic level is required for activation, it can be accomplished by
changing the OC output function to “active high” in the menu system of the instrument. Most Signet instruments allow for this option.
8. Fail-Safe Behavior
No matter what the setting, most OC outputs of Signet instruments turn off
when the instrument loses power. This must be taken into account when evaluating system failure consequences. If the system layout requires a “closed” or “on” condition for the output in case of power loss, a mechanical dry contact relay (NC contacts) must be used instead of the OC output.
226
www.gfsignet.com
Loading...