Technical Specifications Electric Actuator EA04
EA 04
Nominal torque Mdn
Peak torque
Control time
Actuating angle
L/ W/H (Actuautor only)
Housing materials
Position indicator
Emergency manual override
Rated voltage
Rated output
Duty cycle ED
Protection class
Electrical connections
Weight
Limit switches
Operating temper ature
10 Nm
12 Nm
18 seconds/90º at Mdn 10% without load
90°-180°
178/103/130
Polyamide
optical, integrated
integrated, standard
80-240V, 50/60 Hz AC
21 Watts
35% at 77°F/15 min
IP 65
Power - Connector plug 3 P+ E per DIN EN 175301-0 3, Limit switches DIN 3 337
(mini DIN)
3.3 Pounds
Two SPST 5A 250V
14° to 110°F
Important Note: Some residual voltage may be present on the closed terminal when the valve is in the open state and on the open
terminal when in the closed state. For position indication the auxiliary limit switches should be used. The power terminals should