Thank you for purchasing this quality-built GE home generator. We’re pleased that you’ve placed your confidence in
Not
for
Reproduction
the GE brand. When operated and maintained according to the instructions in this manual, your home generator will
provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with home standby
generators and how to avoid them. Because we do not necessarily know all the applications this equipment could
be used for, it is important that you read and understand these instructions thoroughly before attempting to start or
operate this equipment. Save these instructions for future reference.
This home standby generator requires professional installation before use. Refer to the separate installation manual
for full information. Your installer should follow the instructions completely.
Where to Find Us
You never have to look far to find GE support and service for your generator. For quick service when you need it, keep
your original receipt with this manual. You may contact Customer Service at (888) 575-8226, or click on SERVICE &
SUPPORT at www.homestandbygeneratorsystems.com, which provides a list of authorized dealers.
Generator and engine model and serial numbers should be recorded in the installation manual.
important instructions that should be followed during
installation and maintenance of the generator and batteries.
Safety Symbols and Meanings
Explosion
Toxic Fumes
Lift Hazard
Fire
Rotating Parts
Read Manual
Electrical Shock
Hot Surface
Chemical BurnExplosive PressureAuto Start
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings
in this manual, and the tags and decals affixed to the unit
are, therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that it
is safe for you and others. You must also make sure that the
procedure, work method or operating technique that you
choose does not render the generator system unsafe.
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
The safety alert symbol indicates a potential personal
injury hazard. A signal word (DANGER, WARNING, or
CAUTION) is used with the alert symbol to designate a degree
or level of hazard seriousness. A safety symbol may be used
to represent the type of hazard. The signal word NOTICE is
used to address practices not related to personal injury.
DANGER indicates a hazard which, if not avoided, will
result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury.
CAUTION indicates a hazard which, if not avoided, could
result in minor or moderate injury.
NOTICE addresses practices not related to personal injury.
4
WARNING The engine exhaust from this product contains
chemicals known to the State of California to cause cancer, birth
defects, or other reproductive harm.
WARNING Certain components in this product and related
accessories contain chemicals known to the State of California
to cause cancer, birth defects, or other reproductive harm. Wash
hands after handling.
WARNING Storage batteries give off explosive hydrogen gas
Not
for
Reproduction
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• Install the fuel supply system according to NFPA 37 and other
applicable fuel-gas codes.
• Before placing the generator into service, the fuel system lines
must be properly purged and leak tested.
• After the generator is installed, you should inspect the fuel
system periodically.
• NO leakage is permitted.
• DO NOT operate engine if smell of fuel is present or other
explosive conditions exist.
• DO NOT smoke around the generator. Wipe up any oil spills
immediately. Ensure that no combustible materials are left in the
generator compartment. Keep the area near the generator clean
and free of debris.
WARNING Generator produces hazardous voltage.
Failure to properly ground generator could result
in electrocution.
Failure to isolate generator from utility power could result
in death or serious injury to electric utility workers due to
backfeed of electrical energy.
• When using generator for backup power, notify utility company.
• DO NOT touch bare wires or bare receptacles.
• DO NOT use generator with electrical cords which are worn,
frayed, bare or otherwise damaged.
• DO NOT handle generator or electrical cords while standing in
water, while barefoot, or while hands or feet are wet.
• If you must work around a unit while it is operating, stand on an
insulated dry surface to reduce the risk of a shock hazard.
• DO NOT allow unqualified persons or children to operate or
service generator.
• In case of an accident caused by electrical shock, immediately
shut down the source of electrical power and contact the local
authorities. Avoid direct contact with the victim.
• Despite the safe design of the residential generator, operating
this equipment imprudently, neglecting its maintenance or being
careless could cause possible injury or death.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• Before performing any maintenance on the generator, disconnect
the battery cable indicated by a NEGATIVE, NEG or (-) first. When
finished, reconnect that cable last.
• After your system is installed, the generator may crank and start
without warning any time there is a power failure. To prevent
possible injury, always set the generator’s system switch to OFF,
remove the service disconnect from the disconnect box AND
remove the 15 Amp fuse BEFORE working on the equipment.
WARNING Unintentional sparking could cause fire or electric
shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the
wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
5
WARNING Exhaust heat/gases could ignite combustibles or
Not
for
Reproduction
structures resulting in death, serious injury and/or
property damage.
Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
• DO NOT place weatherproof enclosure opposite exhaust side closer
than 18 inches (0.5m) from any structure.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5m) minimum clearance from any structure, shrubs, trees or
any kind of vegetation.
• Standby generator weatherproof enclosure must be at least 5 ft
from windows, doors, any wall opening, shrubs or vegetation over
12 inches (30.48cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 4 feet (1.2m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• Keep at least minimum distances shown in Generator Placement
to insure for proper generator cooling and maintenance
clearances.
• It is a violation of California Public Resource Code, Section 4442,
to use or operate the engine on any forest-covered, brushcovered, or grass-covered land unless the exhaust system is
equipped with a spark arrester, as defined in Section 4442,
maintained in effective working order. Other states or federal
jurisdictions may have similar laws.
Contact the original equipment manufacturer, retailer, or dealer to
obtain a spark arrester designed for the exhaust system installed
on this engine.
• Replacement parts must be the same and installed in the same
position as the original parts.
WARNING Starter and other rotating parts could entangle
hands, hair, clothing, or accessories resulting in
serious injury.
CAUTION Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
CAUTION Excessively high operating speeds could result in
minor injury and/or equipment damage.
Excessively low speeds impose a heavy load on generator.
• DO NOT tamper with governed speed. Generator supplies correct
rated frequency and voltage when running at governed speed.
• DO NOT modify generator in any way.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• Use generator only for intended uses.
• If you have questions about intended use, contact your
authorized dealer.
• Operate generator only on level surfaces.
• Adequate, unobstructed flow of cooling and ventilating air is
critical for correct generator operation.
• The access panels/door must be installed whenever the unit
is running.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• Remain alert at all times while working on this equipment.
Never work on the equipment when you are physically or
mentally fatigued.
• DO NOT start engine with air cleaner or air cleaner cover removed.
• DO NOT insert any objects through cooling slots.
• DO NOT use the generator or any of its parts as a step. Stepping
on the unit could cause stress and break parts. This may result in
dangerous operating conditions from leaking exhaust gases, fuel
leakage, oil leakage, etc.
• If connected devices overheat, turn them off and disconnect them
from generator.
• Shut off generator if:
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
-unit makes unusual noises.
• NEVER operate generator without protective housings, covers, or
guards in place.
• DO NOT wear loose clothing, jewelry or anything that could be
caught in the starter or other rotating parts.
• Tie up long hair and remove jewelry.
• Before servicing, remove 15 Amp fuse from control panel and
disconnect Negative (NEG or -) battery cable.
6
Installation
Not
for
Reproduction
We sincerely appreciate your patronage. For this reason, we
have made every effort to provide for a safe, streamlined
and cost-effective installation. Because each installation is
unique, it is impossible to know of and advise the trade of all
conceivable procedures and methods by which installation
might be achieved. Neither could we know of possible
hazards and/or the results of each method or procedure. For
these reasons,
For the Home Owner
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation in this
manual before contracting or starting your home
generator installation.
To arrange for proper installation, contact the store at which
you purchased your home generator, your dealer, a licensed
electrician or your utility power provider.
Only current licensed electrical and plumbing
professionals should attempt home generator system
installations. Installations must strictly comply with all
applicable codes, industry standards and regulations.
Your home generator is supplied with this “Operator’s
Manual” and a separate “Installation Manual”. These are
important documents and should be retained by the owner
after the installation has been completed.
The home generator warranty is VOID unless the system is
installed by licensed electrical and plumbing professionals.
Every effort has been made to ensure that information in this
manual is accurate and current. However, we reserve the
right to change, alter, or otherwise improve the product and
this document at any time without prior notice.
The Emission Control System for this generator is warranted
to standards set by the U.S. Environmental Protection Agency
and by the California Air Resources Board (CARB).
For the Installing Dealer/Contractor
For most applications, the installation manual contains all
the information required to properly install and start the
home generator. This operator’s manual describes routine
operation and owner maintenance procedures.
If you need more information in this matter, please call
888 575-8226 between 8:00 AM and 5:00 PM CT.
7
Owner Orientation
Not
for
Reproduction
This section provides home generator owners with the
information necessary to achieve the most satisfactory and
cost effective installation possible.
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available with
your home generator. A thorough understanding of these
options will provide fundamental control over the cost of
your installation, as well as ensure your final satisfaction
and security.
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional. Remember
that as the distance from the existing electrical service and
Fuel Factors
gaseous fuel supply increases, and the number of 90 degree
bends in the fuel supply increases; compensations in piping
and wiring materials must be made. This is necessary to
comply with local codes and overcome electrical voltage
drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your home generator installation.
In some areas you may need to acquire electrical permits for
installing the home generator, building permits for installing
gas lines, and permits for noise allowances. Your installer
should check your local codes AND obtain the permits before
installing the system.
An important consideration affecting the entire installation
is the type of fuel used by your home generator. The system
was factory tested and adjusted using natural gas, but can
be converted to use LP vapor. For proper engine function,
factors that are inherent to each of these fuels, your
location and the duration of possible utility interruptions are
important considerations in the following fuel guidelines:
• Use clean, dry fuel, free of moisture or any
particulate material. Using fuels outside the
following recommended values may cause
performance problems.
• In engines set up to run on propane (LP), commercial
grade HD5 propane with a minimum fuel energy of
2500 BTUs/ft3 with maximum propylene content of
5% and butane and heavier gas content of 2.5% and
minimum propane content of 90%.
Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.
Natural gas or LP engines are certified to operate on natural
or liquid propane gas. The emissions control system for this
engine is EM (Engine Modifications).
WARNING Propane and Natural Gas are extremely flammable
and explosive, which could cause burns, fire or
explosion resulting in death, serious injury and/or
property damage.
• The residential generator is equipped with an automatic safety
gas “fuel shut-off” valve.
• DO NOT operate the equipment if the “fuel shut-off” valve is
missing or inoperative.
Power Decrease at High Altitude or
High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1%
for each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
8
Generator Location
Not
for
Reproduction
The actual physical location of your home generator has a
direct affect on:
1. The amount of plumbing required to fuel
your generator.
2. The amount of wiring required to control and connect
your generator.
Specific location guidelines are discussed in the installation
manual. Acquaint yourself with that information and confer
with your installer. Be sure to ask how your site might
affect installation costs and compliance with local codes
and standards.
• Install generator outdoors in an area that will not
accumulate deadly exhaust gas.
• DO NOT install generator where exhaust gas could
accumulate and enter inside or be drawn into a
potentially occupied building or structure.
• By law it is required in many states to have a Carbon
Monoxide (CO) detector in operating condition in
your home. Carbon monoxide detector(s)
be installed and maintained indoors according to
the manufacturer’s instructions/ recommendations.
A CO monitor is an electronic devise that detects
hazardous levels of CO. When there is a buildup of
CO, the monitor will alert the occupants by flashing
visual indicator light and alarm. Smoke alarms cannot
detect CO gas.
A
A
MUST
WARNING Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide could result in death, serious
injury, headache, fatigue, dizziness, vomiting, confusion,
seizures, nausea or fainting.
• Operate this product ONLY outdoors in an area that will not
accumulate deadly exhaust gas.
• Keep exhaust gas away from any windows, doors, ventilation
intakes, soffit vents, crawl spaces, open garage doors or other
openings that can allow exhaust gas to enter inside or be drawn
into a potentially occupied building or structure.
• Carbon monoxide detector(s) MUST be installed and maintained
indoors according to the manufacturer’s instructions/
recommendations. Smoke alarms cannot detect carbon
monoxide gas.
WARNING Exhaust heat/gases could ignite combustibles or
structures resulting in death, serious injury and/or property
damage.
• DO NOT place weatherproof enclosure opposite exhaust side closer
than 18 inches (0.5 m) from any structure.
• Exhaust outlet side of weatherproof enclosure must have at least
5 ft (1.5 m) minimum clearance from any structure, shrubs, trees or
any kind of vegetation.
• Standby generator weatherproof enclosure must be at least
5 ft (1.5 m) from windows, doors, any wall opening, shrubs or
vegetation over 12 inches (30.5 cm) in height.
• Standby generator weatherproof enclosure must have a minimum
of 4 feet (1.2 m) overhead clearance from any structure, overhang
or trees.
• DO NOT place weatherproof enclosure under a deck or other type
of structure that may confine airflow.
• USE ONLY flexible steel fuel line provided. Connect provided fuel
line to generator, DO NOT use with or substitute any other flexible
fuel line.
• Smoke detector(s) MUST be installed and maintained indoors
according to the manufacturer’s instructions/ recommendations.
Carbon monoxide alarms cannot detect smoke.
• DO NOT place weatherproof enclosure in manner other than shown
in illustrations.
• Ensure exhaust gas is kept away from any windows,
doors, ventilation intakes, soffit vents, crawl spaces,
open garage doors or other openings that can
allow exhaust gas to enter inside or be drawn into
a potentially occupied building or structure. Your
neighbor(s) home may be exposed to the engine
exhaust from your standby generator and must be
considered when installing your standby generator.
• Wind and air currents should be taken into
consideration when positioning generator.
See the installation manual for full details on safe generator
location.
9
Delivery Inspection
Not
for
Reproduction
Carefully inspect the home generator for any damage that
may have occurred during shipment.
If loss or damage is noted at time of delivery, have the
person(s) making delivery note all damage on the freight bill
and affix his signature under the consignor’s memo of loss or
damage. If loss or damage is noted after delivery, separate
the damaged materials and contact the carrier and your
installer for claim procedures. Missing or damaged parts are
not warranted.
The home generator system is supplied with:
• Pre-attached mounting pad
• Fully-serviced oil/lubricating system
• Flexible steel fuel line
• Installation and start-up manual
• Operator’s manual
• Spare access door keys
• Spare 15 Amp ATO-type fuse
• Two pin control panel connector
• Ten pin control panel connector
• Lifting hole plugs (4)
• LP conversion jet
Not included:
• Carbon monoxide detector(s)
• Starting battery
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Crane, lifting straps, chains or cables
• Two 48” lengths of 1” pipe (NOT conduit)
• Torque screwdriver, 5 to 50 inch-pound range
• Voltage/frequency meter
10
Controls
Not
for
Reproduction
Home Generator
Read this operator’s manual and Important Safety Instructionsbefore operating your generator.
Compare the illustration with your generator to familiarize yourself with the locations of various
controls and adjustments. Save this manual for future reference.
E
D
C
B
A
F
G
H
J
K
L
Generator is shown with roof and access covers removed
for clarity.
A
- Lifting Holes ― Provided at each corner for
lifting generator.
B
- Fuel Inlet ― Attach appropriate fuel supply to
generator here.
C
- Oil Filter ― Filters engine oil to prolong generator life.
D
- Exhaust Port ― High-performance muffler lowers engine
noise to comply with most residential codes.
E
- Air Cleaner ― Uses a dry type filter element and foam
precleaner to protect engine by filtering dust and debris
out of intake air.
F
- Engine Label ― Identifies engine model and type.
G
- Oil Fill Cap/Dipstick ― Check and fill engine with
recommended oil here.
H
- Control Panel ― Used for various test, operation and
maintenance functions. See System Control Panel.
J
- Oil Drain Hose ― Located inside access cover on side
panel. Provided to facilitate oil changing.
K
- Unit Identification Label ― Identifies unit by serial
number.
L
- Battery (installer supplied) ― 12 Volt DC, sealed battery
provides power to start the engine.
11
System Control Panel
Not
for
Reproduction
Compare this control panel illustration with your generator to
familiarize yourself with the location of these important controls:
CD
B
A
E
F
A
- SET EXERCISE― Used to set the exercise cycle start
time and day-of-the-week. Exercise cycle only occurs in
AUTO mode.
B
- Circuit Breaker ― Pr
and other over-current conditions. Must be ON to
supply power to the automatic transfer switch.
C
- 15 Amp Fuse ― Protects the home generator DC
control circuits. If the fuse has ‘blown’ (melted open)
or was removed, the engine cannot crank or start.
Replace the fuse using only an identical ATO 15A fuse.
D
- System Switch ― This two-position switch is the most
important control on the system and is used as follows:
• “AUTO” position is the normal operating position. If a
utility power outage is sensed, the system will start the
generator. When utility power is restored, AUTO lets
the engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.
otects the generator from shorts
12
• “OFF” position turns off running generator, prevents
unit from starting and resets any detected faults.
E
– MANUAL OVER-RIDE― W
position, push the manual over-ride switch to start the
generator. To turn off the generator, push and hold the
manual over-ride switch again until engine stops.
F
- Digital Display ― Displays the total number of hours
the generator has been running and fault codes. Used
to schedule maintenance tasks and for troubleshooting
operational problems with the residential generator. A
constant number displayed indicates the total hours of
operation. Fault conditions will flash “FC” followed by a
fault code number. All fault conditions are described in
Fault Detection System.
ith system switch in AUTO
Access Ports
Not
for
Reproduction
Each home generator is supplied with a set of identical keys.
These keys fit the lock that secures the control panel access
door.
To open access door:
1. Insert key into lock of access door and turn key one
quarter turn counterclockwise.
2. Remove key.
To close access door:
1. Close control panel door and insert key into lock and
turn key one quarter turn clockwise.
2. Remove key.
The home generator is equipped with a removable roof and
removable side panels to permit simple servicing.
To remove roof and divider:
1. Open the control panel access door.
2. Set generator’s circuit breaker to OFF position.
3. Set control panel system switch to OFF.
4. Remove 15 Amp fuse from control panel.
5. Move roof latch to the left until roof pops up slightly.
7. Rotate 4 knobs 1/4 turn and lift divider off.
8. Replace divider and roof in reverse order.
To remove side panels:
1. Open the control panel access door.
2. Set generator’s circuit breaker to OFF position.
3. Set control panel system switch to OFF.
4. Remove 15 Amp fuse from control panel.
5. Remove roof and divider.
6. Lift latches
A
up on both sides of panel to release.
6. Lift roof off of generator.
A
7. Pull panel upward and out of grooves.
13
To remove exhaust panel:
Not
for
Reproduction
1. Remove roof and divider.
2. Remove side panels.
WARNING Contact with muffler area could cause burns
resulting in serious injury.
• DO NOT touch hot parts and AVOID hot exhaust gases.
• Allow equipment to cool before touching.
3. Remove 6 screws
A
from exhaust panel.
To install side panels:
1. Place panel in grooves and slide down in place.
A
A
A
A
4. Pull exhaust panel up and out of base.
5. Remove two screws B and pull muffler cover off.
B
2. Push latches
into place.
A
A
3. Replace divider and rotate knobs 1/4 turn to
lock in place.
B
C
down on both sides of panel to lock
C
6. Replace muffler cover and exhaust panel in reverse
order.
14
4. Replace roof.
Operation
Not
for
Reproduction
Important Owner’s Considerations
Engine Oil
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
• DO NOT attempt to crank or start the engine before it has been
properly serviced with the recommended oil. This may result in an
engine failure.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
This engine is shipped from the factory pre-run and filled
with synthetic oil (API SJ/CF 5W-30). This allows for system
operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level as
described in Maintenance.
Battery
The installer must supply a valve-regulated, rechargeable
12 volt DC starting battery. See Battery in Final Installation Considerations in the installation manual.
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
With the battery installed, all wiring to transfer switch and
home generator completed, utility power supplied to the
automatic transfer switch, and the unit in AUTO mode, the
battery receives a trickle charge while the engine is not
running. The trickle charge cannot be used to recharge a
battery that is completely discharged.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. The 15 Amp fuse was removed at the factory to
prevent the unit from starting during shipping. Your installer
will ensure the fuse is properly installed upon completion of
the installation.
Automatic Operation
To select automatic operation, do the following:
1. Confirm 15 Amp fuse is installed in control panel.
2. Set the main distribution panel circuit breaker that
sends utility voltage to the transfer switch to ON.
3. Set the generator’s main circuit breaker to its
ON position.
4. Set the control panel system switch to AUTO.
CAUTION With the system switch set to AUTO, the engine could
crank and start at any time without warning, resulting in
minor or moderate injury.
• To prevent possible injury that could be caused by such sudden
starts, always set the system switch to OFF if performing
maintenance on the system.
• Remove the 15 Amp fuse before working on or around the
generator or transfer switch.
15
Checking Automatic Operation
Not
for
Reproduction
To check the system for proper automatic operation,
proceed as follows:
1. Confirm the control panel system switch to AUTO.
2. Turn OFF the main distribution panel circuit breaker
sending power to the automatic transfer switch.
When utility voltage is lost and the sensor has timed
out, the engine will crank and start. Let the system go
through its entire automatic operation sequence.
3. With generator output supplying its loads, turn ON the
service disconnect or main distribution panel circuit
breaker that supplies utility power to the automatic
transfer switch.
Setting Exercise Timer
4. The automatic transfer switch will transfer loads back
to utility power after a 5 minute minimum run time
and utility power is available.
5. The generator will run for one additional minute for
engine cool down, then will shut down.
If utility is restored and generator does not shut down after
10 minutes, set system switch to OFF and contact your
installer or local service center.
This completes the test procedures for automatic operation.
The home generator will now start automatically and will
supply power to the transfer switch when utility power is lost.
The home generator is equipped with an exercise timer that
will start and exercise the system once every seven days.
During this exercise period, the unit runs for approximately
20 minutes and then shuts down. Electrical load transfer
DOES NOT occur during the exercise cycle (unless an utility
power outage occurs).
A button on the control panel is labeled “SET EXERCISE”
(see System Control Panel). The specific day and the specific
time of day this button is pressed is programmed into the
control board memory. This date and time is then used to
automatically initiate the system exercise cycle. The “SET
EXERCISE” legend on the control panel will flash until the set
exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your home
generator to exercise.
2. On that day and time, press and hold “SET EXERCISE”
for three seconds.
The “Set Exercise” display will illuminate then turn off
to confirm that the exercise timer has been set. Then
release the button.
The unit will crank and run the exercise cycle. During
the cycle, “Set Exercise” will illuminate.
Once the exercise cycle is complete, the unit will turn
off and “Set Exercise” will no longer be displayed.
The exercise cycle may be discontinued at anytime by
turning the System Switch to OFF.
3. The unit will then start and run it’s 20 minute exercise
cycle weekly.
For example, if you press SET EXERCISE on Sunday morning
at 10:00 AM, the unit will run an immediate exercise cycle
and an exercise cycle every following Sunday at 10:00 AM
(+/- 1/2 hour).
“Set Exercise” will only work if the unit is in the AUTO mode
and this exact procedure is followed. The exerciser will need
to be re-set if the 15 Amp fuse is removed or changed, or if
the starting battery is disconnected.
If you want to change the day and time the unit exercises,
simply perform the “Set Exercise” procedure at the exact
weekday and time you want it to take place.
Generator will not exercise if timer is not set.
16
Maintenance
Not
for
Reproduction
Servicing the System
Before performing any generator maintenance, always
perform the following steps:
1. Set generator’s circuit breaker to its OFF position.
2. Set control panel system switch to OFF.
3. Remove 15 Amp fuse from control panel.
Fault Detection System
The generator may have to run for long periods of time
with no operator present. For that reason, the system is
equipped with sensors that automatically shut down the
generator in the event of potentially damaging conditions,
such as low oil pressure, high temperature, over speed, and
other conditions.
The generator’s control panel has a digital display that
shows fault codes, like “FC_1”. The table below lists the
detected fault, the fault code as displayed on the control
panel.
Fault DescriptionFault Codes
Low battery voltageFC_1
Low oil pressureFC_2
Low voltageFC_3
Engine does not startFC_4
Low frequencyFC_5
Engine overspeedFC_6
High temperatureFC_7
Transfer switch faultFC_8
4. Utility voltage is present at generator control panel.
Disconnect power before servicing control panel by
removing the fuses from the transfer switch.
5. After all servicing has been completed, replace fuses
in transfer switch, replace 15 Amp fuse in control
panel, set system switch and circuit breaker ON
and reset exercise timer. See Setting Exercise Timer
in Operation.
Reset Fault Detection System
The operator must reset the fault detection system each time
it activates. To do so, place the control panel system switch
in the OFF position for 30 seconds or more. Remedy the fault
condition, then return the home generator to service by
placing the system switch in the AUTO position, installing the
15 Amp fuse (if removed), and resetting the exercise timer.
See Setting Exercise Timer in Operation.
Low Battery Voltage (FC_1)
This fault is indicated by fault code FC_1. This condition
occurs if the generator cannot start because the starting
battery output power is below that needed to crank the
engine. Causes for this problem may be a faulty battery or
battery charge circuit.
Remove the 15 Amp fuse and disconnect the battery from
the generator. Take the battery to a local battery store for
analysis. Or contact your local service center for assistance.
Reinstall the battery (replace if necessary - see Battery in Final Installation Considerations in the installation manual).
Then reset the fault detection system, as described earlier.
17
Low Oil Pressure (FC_2)
Not
for
Reproduction
This fault is indicated by fault code FC_2. The unit is equipped
with an oil pressure switch that uses normally closed
contacts held open by engine oil pressure during operation.
Should oil pressure drop below the 8 psi range, switch
contacts close and the engine is shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down again. The fault code will appear. In
this case, contact an authorized dealer.
Low Voltage (Generator, FC_3)
This fault is indicated by fault code FC_3. This condition
is caused by a restriction in the fuel flow, a broken or
disconnected signal lead, a failed alternator winding, the
control panel circuit breaker is open, or the generator is
overloaded.
To remedy the problem, contact your installer or an
authorized dealer.
Engine Does Not Start (FC_4)
This fault is indicated by fault code FC_4. This feature
prevents the generator from damaging itself if it continually
attempts to start in spite of another problem, such as no fuel
supply. Each time the system is directed to start, the unit
will crank for 10 seconds, pause for 10 seconds, and repeat.
If the system does not begin producing electricity after
approximately 2 minutes, the unit will stop cranking.
Check to make sure the generator’s main circuit breaker is in
the ON position in order for the sensing leads to verify that
the unit is running.
The most likely cause of this problem is no fuel supply. Check
the internal and external fuel shut off valves to ensure they
are fully open. Other causes could be failed spark plug(s),
failed engine ignition, or the engine air filter is clogged. You
may need to contact your installer for assistance if you can’t
remedy these problems.
Low Frequency (FC_5)
This fault is indicated by fault code FC_5. This feature
protects devices connected to the transfer switch by shutting
the generator down if the engine runs slower than 55 Hz for
three seconds.
This condition is caused by a failed engine component or by
excessive loads on the generator. To remedy the problem,
contact your installer or an authorized dealer.
Engine Overspeed (FC_6)
This fault is indicated by fault code FC_6. This feature
protects devices connected to the transfer switch by shutting
the generator down if the engine happens to run faster than
the preset limit.
The overspeed fault is detected as follows:
• If the generator output frequency is 65-70 Hz, after
three seconds, the generator will shut down.
• If the generator output frequency is greater than
70 Hz, the generator will shut down immediately.
This condition is caused by a failed engine component.
To remedy the problem, contact your installer or an
authorized dealer.
High Temperature (FC_7)
This fault is indicated by fault code FC_7. The contacts of
the temperature switch are normally open. If the engine
temperature exceeds approximately 149°C (300°F), the fault
is detected and the engine shuts down.
Common causes for this condition include running the unit
with access panels removed, obstructed air inlet or exhaust
port, low oil level, or debris in the engine cylinder cooling fins.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that all
access panels are installed whenever the unit is running.
Transfer Switch Fault (FC_8)
This fault is indicated by fault code FC_8 (if transfer switch is
equipped with fault detection).
The most likely cause of this fault is a blown fuse in the
transfer switch. To remedy the problem, contact your
installer or an authorized dealer.
18
Maintenance Schedule
Not
for
Reproduction
Follow the hourly or calendar intervals of operation,
whichever occurs first.
First 5 Hours
Change Engine Oil
Every 8 Hours or Daily
Clean Debris
Check Engine Oil Level
Every 100 Hours or Annually
Change Air Filter
Change Engine Oil and Filter
Replace Spark Plugs
Check Valve Clearance
Annually
Clean Air Cooling System
Clean Oil Cooler Fins
Generator Maintenance
Regular maintenance will improve the performance and
extend the life of the generator. See any authorized dealer
for service.
NOTICE Once a year you should replace the spark plugs and
air filter. A new spark plug and clean air filter assure proper
fuel-air mixture and help your engine run better and last
longer. Also check fuel lines for leaks.
Emissions Control
Maintenance, replacement, or repair of the emissions
control devices and systems may be performed by any
non-road engine repair establishment or individual.
However, to obtain ”no charge” emissions control service, the
work must be performed by a factory authorized dealer. See
the Emissions Warranty.
The generator’s warranty does not cover items that have
been subjected to operator abuse or negligence. To receive
full value from the warranty, the operator must maintain the
generator as instructed in this manual.
Some adjustments will need to be made periodically to
properly maintain your generator.
All service and adjustments should be made at least once
each season. Follow the requirements in the Maintenance
Schedule chart.
Generator maintenance consists of keeping the unit
clean. Operate the unit in an environment where it will
not be exposed to excessive dust, dirt, moisture or any
corrosive vapors. Cooling air louvers on the enclosure
must not become clogged with snow, leaves, or any other
foreign material. To prevent generator damage caused by
overheating, keep the enclosure cooling inlets and outlets
clean and unobstructed at all times.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are visible
on its exterior/interior surface. Inspect the air inlet and outlet
openings inside and outside the enclosure to ensure air flow
is not blocked.
DO NOT use direct spray from a garden hose to clean
generator. Water can enter the engine and generator and
cause problems.
NOTICE Improper treatment of generator could damage it and
shorten its life.
• DO NOT expose generator to excessive moisture, dust, dirt, or
corrosive vapors.
• DO NOT insert any objects through cooling slots.
Clean the generator as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Clean generator as desired.
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft, bristle brush to loosen caked on dirt, etc.
• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean
and unobstructed.
4. Reinstall 15 Amp fuse in control panel.
5. Set generator’s system switch to AUTO.
6. Reset exercise timer. See Setting Exercise Timer.
19
Battery
Not
for
Reproduction
Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel away
from batteries.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required. See Battery
in Final Installation Considerations in the installation
manual for specific battery needed.
4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable from negative
battery terminal (indicated by NEGATIVE, NEG, or (-)).
NOTICE Failure to disconnect negative battery cable could result in
equipment failure.
• DO NOT attempt to jump start the generator.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts. DO NOT exceed 13.7 volts
when charging.
WARNING Battery posts, terminals and related accessories
contain lead and lead compounds, chemicals known to the State
of California to cause cancer and reproductive harm. Wash hands
after handling.
5. Connect black negative battery cable to negative
battery terminal (indicated by NEGATIVE, NEG, or (-).
6. Ensure hardware on both positive and negative
battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
DON’T POLLUTE. CONSERVE RESOURCES, RETURN
USED BATTERY TO RECYCLING COLLECTION CENTER.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative
battery terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
CAUTION With the system switch set to AUTO, the engine could
crank and start at any time without warning, resulting in
minor or moderate injury.
• To prevent possible injury that could be caused by such sudden
starts, always set the system switch to OFF if performing
maintenance on the system.
• Remove the 15 Amp fuse before working on or around the
generator or transfer switch.
WARNING Storage batteries give off explosive hydrogen gas
during recharging.
Slightest spark will ignite hydrogen and
cause explosion, resulting in death, serious
injury and/or property damage.
Battery electrolyte fluid contains acid and is extremely caustic.
Contact with battery contents could cause severe chemical burns.
A battery presents a risk of electrical shock and high short
circuit current.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit cigarette during
and for several minutes after charging a battery.
9. Reset exercise timer. See Setting Exercise Timer.
Engine Maintenance
Not
for
Reproduction
WARNING Unintentional sparking could cause fire or electric
shock resulting in death or serious injury.
WHEN ADJUSTING OR MAKING REPAIRS TO YOUR GENERATOR
• Disconnect the spark plug wire from the spark plug and place the
wire where it cannot contact spark plug.
WHEN TESTING FOR ENGINE SPARK
• Use approved spark plug tester.
• DO NOT check for spark with spark plug removed.
Engine Oil
The engine is filled with synthetic oil (API SJ/CF 5W-30).
This allows for system operation in the widest range of
temperature and climate conditions.
We recommend the use of Briggs & Stratton Warranty
Certified oils for best performance. Other high-quality
detergent oils are acceptable if classified for service SF, SG,
SH, SJ or higher. DO NOT use special additives.
Outdoor temperatures determine the proper oil viscosity for
the engine. Use the chart to select the best viscosity for the
outdoor temperature range expected.
NOTICE Synthetic oil meeting ILSAC GF-2, API
certification mark and API service symbol with “SJ/
CF ENERGY CONSERVING” or higher, is an acceptable
oil at all temperatures. Use of synthetic oil does not
alter required oil change intervals.
When all engine servicing is complete, replace 15 Amp fuse
in control panel and reset exercise timer. See Setting Exercise Timer in Operation.
* Below 40°F (4°C) the use of SAE 30 will result in hard
starting.
** Above 80°F (27°C) the use of 10W30 may cause increased
oil consumption. Check oil level more frequently.
Checking/Adding Engine Oil
1. Remove roof and divider.
2. Clean the oil fill area of any debris.
3. Remove the dipstick and wipe with a clean cloth.
4. Fully insert dipstick into oil fill.
5. Remove dipstick and check oil level. Verify oil is at Full
mark (top hole) on dipstick.
Full
Add
6. If needed, slowly pour recommended oil into oil fill
opening. DO NOT overfill. After adding oil, wait one
minute and recheck oil level.
NOTICE Overfilling with oil could cause the engine to not start, or
hard starting.
• DO NOT overfill.
• If over the FULL mark on dipstick, drain oil to reduce oil level to
FULL mark on dipstick.
7. Replace and tighten oil dipstick.
8. Reattach roof and divider.
21
Changing Engine Oil and Oil Filter
Not
for
Reproduction
Remove roof, divider and side panel to change engine oil and
filter.
Changing Engine Oil
CAUTION Avoid prolonged or repeated skin contact with used
motor oil.
• Used motor oil has been shown to cause skin cancer in certain
laboratory animals.
• Thoroughly wash exposed areas with soap and water.
KEEP OUT OF REACH OF CHILDREN. DON’T POLLUTE.
CONSERVE RESOURCES. RETURN USED OIL TO
COLLECTION CENTERS.
Change the oil while the engine is still warm from running, as
follows:
1. Set control board system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Place oil drain hose into an approved container.
Changing Oil Filter
1. Place an approved container under oil filter.
2. Remove oil filter and dispose of properly.
3. Before installing a new oil filter, lightly lubricate the oil
filter gasket with fresh, clean oil.
4. Install the oil filter by hand until the gasket contacts
the oil filter adapter, then tighten the oil filter 1/2 to
3/4 turn.
5. Add oil as described in Checking/Adding Engine Oil.
6. Remove container from under oil filter and clean up
any spilled oil.
4. Remove brass fitting from end of drain hose and drain
oil into an approved container.
5. When oil has drained, replace brass fitting on hose.
6. Add oil if not changing oil filter. See Checking/Adding
Engine Oil.
7. Start and run engine. As engine warms up, check for oil
leaks.
8. Stop engine, wait for oil to settle, check oil level and
add if necessary as described in Checking/Adding
Engine Oil.
NOTICE Any attempt to crank or start the engine before it has
been properly serviced with the recommended oil will result in
equipment failure.
• DO NOT attempt to crank or start the engine before it has been
properly serviced with the recommended oil. This may result in an
engine failure.
• Damage to equipment resulting from failure to follow this
instruction will void engine and generator warranty.
22
Service Air Cleaner
Not
for
Reproduction
Your engine will not run properly and may be damaged if you
run it with a dirty air cleaner. Clean or replace more often if
operating under dusty or dirty conditions.
To service the air cleaner, follow these steps:
1. Loosen knobs and remove cover. Remove air cleaner
by lifting the end up and out.
2. To loosen debris, gently tap air cleaner on a hard
surface. If air cleaner is excessively dirty, replace with
a new air cleaner.
3. Install clean (or new) air cleaner inside base and
push down until air cleaner snaps in place. See
Specifications.
4. Reinstall cover and tighten knobs.
Service Spark Plugs
Changing the spark plugs will help your engine to start easier
and run better.
1. Clean area around spark plugs.
2. Remove and inspect spark plugs.
3. Check electrode gap with wire feeler gauge and reset
spark plug gap to recommended gap if necessary
(see Specifications).
4. Replace spark plugs if electrodes are pitted, burned
or porcelain is cracked. Use the recommended
replacement spark plugs. See Specifications.
5. Install spark plugs and tighten to 180 in/lbs (20Nm).
Clean Air Cooling System and Oil Cooler Fins
Over time debris may accumulate in cylinder cooling fins
and cannot be observed without partial engine disassembly.
Unobstructed air flow is critical for correct generator
operation. For this reason, we recommend you have an
authorized service dealer clean the cooling system per
recommended intervals (see Maintenance Schedule in the
Maintenance section). Equally important is to keep top of
engine free from debris. Make sure the oil cooler fins are free
of dirt and debris. Also see Cleaning.
23
Check Valve Clearance
Not
for
Reproduction
Regular valve clearance check and adjustment will improve
performance and extend engine life. This procedure cannot
be done without partial engine disassembly and the use
of special tools. For this reason we recommend that you
have an authorized Service Dealer check and adjust valve
clearance at recommended intervals (see Maintenance Schedule in the Maintenance section).
When Calling for Assistance
You must have the following information at hand if it is
necessary to contact a local service center regarding
service or repair of this unit:
1. Obtain the unit Model Number and Serial Number
from the unit ID label. See Controls for location of
the label or refer to the information recorded on the
inside front cover of the installation manual.
2. Obtain the engine identification numbers from the
engine label. See Controls for location of the label or
refer to the information recorded on the inside front
cover of the installation manual.
Storage
The home generator system is designed for long term service
as a backup generator. There is no need to take any storage
precautions. However, if it becomes necessary to take the
system out of service for an extended period, call Technical
Services at 888 575-8226, between 8:00 AM and 5:00 PM CT
for specific recommendations.
24
Troubleshooting
Not
for
Reproduction
ProblemCauseCorrection
1. Circuit breaker open or defective.
Eng ine is running, but no AC output
is available.
Eng ine runs good at no-load but “bogs
down” when loads are connected.
Eng ine will not start; or starts and runs
rough.
Engine shuts down during operation.
2. Fault in generator control panel.
3. Poor wiring connections or defective
transfer switch.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
4. Fuel pressure or mixture is incorrect.
5. Kinked fuel line between regulator
and engine.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
4. Clogged air filter.
1. Fuel supply turned off or depleted.
2. Control panel digital display shows a
fault code.
1. Reset or replace circuit breaker.
2. Contact local service facility.
3. Check and repair or contact local
service facility.
1. Disconnect shorted electrical load.
2. Turn off one or more loads.
3. Contact local service facility.
4. See Gaseous Fuel System in the
installation manual.
5. Remove kink. Replace
if necessary.
1. Install (new) 15 Amp fuse.
See System Control Panel.
2. Open fuel valve(s); check propane
tank.
3. Replace battery.
4. Clean or replace air filter.
1. Check fuel valves, fill
propane tank.
2. Refer to Fault Detection System.
Loss of power on circuits.
Unit will not exercise weekly.
Excessive Vibration
Odor of fuel
Utility power returns, unit does not stop
1. Generator circuit breaker is open.
2. Transfer switch problems.
1. System Switch not on AUTO.
2. Exercise timer not set.
3. Failed battery.
4. 15 Amp fuse missing or blown.
1. Lose mechanical fastener.1. Check and repair or contact local
1. Fuel leak.1. Turn off manual shutoff fuel valve.
1. Blown fuses in transfer switch.
2. 5 minute minimum runtime not
lapsed.
3. Poor wire connection or defective
controllers.
1. Reset circuit breaker.
2. See transfer switch manual.
1. Set system switch to AUTO.
2. Set exercise timer.
3. Replace battery.
4. Install (new) 15 Amp fuse.
See System Control Panel.
service facility.
Contact local service facility.
1. Install (new) fuses.
2. Wait 5 minutes.
3. Check and repair or contact local
service facility.
25
California, U.S. EPA,
Not
for
Reproduction
and Briggs & Stratton Corporation Emissions Control Warranty Statement
Your Warranty Rights And Obligations
The California Air Resources Board, U.S. EPA, and Briggs &
Stratton (B&S) are pleased to explain the emissions control
system warranty on your Model Year 2011-2012 engine/
equipment. In California, new small off-road engines and
large spark ignited engines less than or equal to 1.0 liter
must be designed, built, and equipped to meet the State’s
stringent anti-smog standards. B&S must warrant the
emissions control system on your engine/equipment for
the periods of time listed below provided there has been no
abuse, neglect, or improper maintenance of your engine or
equipment.
Your emissions control system may include parts such as
the carburetor or fuel injection system, fuel tank, ignition
system, and catalytic converter. Also included may be hoses,
belts, connectors, sensors, and other emissions-related
assemblies. Where a warrantable condition exists, B&S will
repair your engine/equipment at no cost to you including
diagnosis, parts, and labor.
Manufacturer’s Warranty Coverage:
Small off-road engines and large spark ignited engines
less than or equal to 1.0 liter are warranted for four years.
If any emissions-related part on your engine/equipment is
defective, the part will be repaired or replaced by B&S.
Owner’s Warranty Responsibilities:
• As the engine/equipment owner, you are responsible
for the performance of the required maintenance
listed in your owner’s manual. B&S recommends that
you retain all receipts covering maintenance on your
engine/equipment, but B&S cannot deny warranty
solely for the lack of receipts or your failure to ensure
the performance of all scheduled maintenance.
• As the engine/equipment owner, you should however
be aware that B&S may deny you warranty coverage
if your engine/equipment or a part has failed due to
abuse, neglect, improper maintenance, or unapproved
modifications.
• You are responsible for presenting your engine/
equipment to a B&S distribution center, servicing
dealer, or other equivalent entity, as applicable, as
soon as a problem exists. The warranty repairs should
be completed in a reasonable amount of time, not to
exceed 30 days. If you have any questions regarding
your warranty rights and responsibilities, you should
contact B&S at 414 259-5262.
Briggs & Stratton Emissions Control Warranty Provisions
The following are specific provisions relative to your
Emissions Control Warranty Coverage. It is in addition to the
B&S engine warranty for non-regulated engines found in the
Operator’s Manual.
1. Warranted Emissions Parts
Coverage under this warranty extends only to the parts
listed below (the emissions control systems parts) to
the extent these parts were present on the engine
purchased.
a. Fuel Metering System
• Cold start enrichment system (soft choke)
• Carburetor and internal parts
• Fuel pump
• Fuel line, fuel line fittings, clamps
• Fuel tank, cap and tether
• Carbon canister
b. Air Induction System
• Air cleaner
• Intake manifold
• Purge and vent line
c. Ignition System
• Spark plug(s)
• Magneto ignition system
d. Catalyst System
• Catalytic converter
• Exhaust manifold
• Air injection system or pulse valve
e. Miscellaneous Items Used in Above Systems
• Vacuum, temperature, position, time sensitive
valves and switches
• Connectors and assemblies
2. Length of Coverage
For a period of four years from date of original
purchase, B&S warrants to the original purchaser
and each subsequent purchaser that the engine
is designed, built, and equipped so as to conform
with all applicable regulations adopted by the Air
Resources Board; that it is free from defects in material
and workmanship that could cause the failure of a
warranted part; and that it is identical in all material
respects to the engine described in the manufacturer’s
application for certification. The warranty period begins
on the date the engine is originally purchased.
26
The warranty on emissions-related parts is as follows:
Not
for
Reproduction
• Any warranted part that is not scheduled for
replacement as required maintenance in the
owner’s manual supplied, is warranted for the
warranty period stated above. If any such part fails
during the period of warranty coverage, the part will
be repaired or replaced by B&S at no charge to the
owner. Any such part repaired or replaced under
the warranty will be warranted for the remaining
warranty period.
• Any warranted part that is scheduled only for
regular inspection in the owner’s manual supplied, is
warranted for the warranty period stated above. Any
such part repaired or replaced under warranty will
be warranted for the remaining warranty period.
• Any warranted part that is scheduled for
replacement as required maintenance in the
owner’s manual supplied, is warranted for the period
of time prior to the first scheduled replacement
point for that part. If the part fails prior to the first
scheduled replacement, the part will be repaired
or replaced by B&S at no charge to the owner. Any
such part repaired or replaced under warranty will
be warranted for the remainder of the period prior
to the first scheduled replacement point for the part.
• Add on or modified parts that are not exempted by
the Air Resources Board may not be used. The use
of any non exempted add on or modified parts by
the owner will be grounds for disallowing a warranty
claim. The manufacturer will not be liable to warrant
failures of warranted parts caused by the use of a
non exempted add on or modified part.
3. Consequential Coverage
Coverage shall extend to the failure of any engine
components caused by the failure of any warranted
emissions parts.
4. Claims and Coverage Exclusions
Warranty claims shall be filed according to the
provisions of the B&S engine warranty policy. Warranty
coverage does not apply to failures of emissions
parts that are not original equipment B&S parts or
to parts that fail due to abuse, neglect, or improper
maintenance as set forth in the B&S engine warranty
policy. B&S is not liable for warranty coverage of
failures of emissions parts caused by the use of add-on
or modified parts.
Look For Relevant Emissions Durability Period and Air
Index Information On Your Small Off-Road Engine
Emissions Label
Engines that are certified to meet the California Air
Resources Board (CARB) small off-road Emissions Standard
must display information regarding the Emissions Durability
Period and the Air Index. Briggs & Stratton makes this
information available to the consumer on our emissions
labels. The engine emissions label will indicate certification
information.
The Emissions Durability Period describes the number of
hours of actual running time for which the engine is certified
to be emissions compliant, assuming proper maintenance in
accordance with the Operating & Maintenance Instructions.
The following categories are used:
Moderate:
Engine is certified to be emissions compliant for 125 hours
of actual engine running time.
Intermediate:
Engine is certified to be emissions compliant for 250 hours
of actual engine running time.
Extended:
Engine is certified to be emissions compliant for 500 hours
of actual engine running time.
For example, a typical walk-behind lawn mower is used 20
to 25 hours per year. Therefore, the Emissions Durability
Period of an engine with an intermediate rating would
equate to 10 to 12 years. Briggs & Stratton engines are
certified to meet the United States Environmental Protection
Agency (USEPA) Phase 2 emissions standards. For Phase 2
certified engines, the Emissions Compliance Period referred
to on the Emissions Compliance label indicates the number
of operating hours for which the engine has been shown to
meet Federal emissions requirements.
For engines less than 225 cc displacement.
Category C = 125 hours
Category B = 250 hours
Category A = 500 hours
For engines of 225 cc or more displacement.
Category C = 250 hours
Category B = 500 hours
Category A = 1000 hours
27
Warranty
Not
for
Reproduction
Limited Warranty
Briggs & Stratton Power Products Group, LLC will repair or
replace, free of charge, any part(s) of the equipment that
is defective in material or workmanship or both. Travel
expenses are reimbursed as specified under the Briggs
& Stratton Warranty Guidelines document to authorized
Briggs & Stratton dealers for performing applicable warranty
repair work. This warranty is effective for the time periods
and subject to the conditions stated below. For all warranty
service, find the nearest Authorized Service Dealer in our
dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED
WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND
Warranty Period
Consumer Use
Commercial Use 2None
Rental Use
Prime Power
1
4 years or 1,600 hours, whichever comes first
3
None
4
None
FITNESS FOR A PARTICULAR PURPOSE, ARE LIMITED TO ONE
YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY
LAW. ANY AND ALL IMPLIED WARRANTIES ARE EXCLUDED.
LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES
IS EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED
BY LAW. Some states or countries do not allow limitations
on how long an implied warranty lasts, and some states
or countries do not allow the exclusion or limitation of
incidental or consequential damages, so the above limitation
and exclusion may not apply to you. This warranty gives
you specific legal rights and you may also have other rights
which vary from state to state or country to country.
The warranty period begins on the date of purchase by the
first retail consumer or commercial end user, and continues
for the period of time stated in the table above.
1
“Consumer” means personal residential household use by
a retail consumer.
2
“Commercial” means all other uses, including use for
commercial, income producing or rental purposes. Once
equipment has experienced commercial use, it shall
thereafter be considered as commercial use for purposes
of this warranty.
3
“Rental use” means any use of this product in a temporary
or semi-permanently installed rental application. Once
equipment has experienced rental use, it shall thereafter
be considered rental use for purposes of this warranty.
is a trademark of General Electric Company
and is under license by Briggs & Stratton
Power Products Group, LLC.
28
4
For purposes of this warranty, “Prime Power” is defined
where the generator is a source of power where no
electrical power is available from the UTILITY POWER GRID.
If no UTILITY power is available, the generator is considered
the prime power source.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN
WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR
PROOF OF PURCHASE RECEIPT. IF YOU DO NOT PROVIDE
PROOF OF THE INITIAL PURCHASE DATE AT THE TIME
WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING
DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE
WARRANTY PERIOD.
We welcome warranty repair and apologize to you for
being inconvenienced. Any Authorized Service Dealer may
perform warranty repairs. Most warranty repairs are handled
routinely, but sometimes requests for warranty service
may not be appropriate. For example, warranty service
would not apply if equipment damage occurred because
of misuse, lack of routine maintenance, shipping, handling,
warehousing or improper installation. Similarly, the warranty
is void if the manufacturing date or the serial number on
the equipment has been removed or the equipment has
been altered or modified. During the warranty period, the
Authorized Service Dealer, at its option, will repair or replace
any part that, upon examination, is found to be defective
under normal use and service. This warranty will not cover
the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment and
engines, like all mechanical devices, needs periodic
parts and service to perform well. This warranty does
not cover repair when normal use has exhausted the
life of a part or the equipment.
• Installation and Maintenance: This warranty does
not apply to equipment or parts that have been
subjected to improper or unauthorized installation
or alteration and modification, misuse, negligence,
accident, overloading, overspeeding, improper
maintenance, repair or storage so as, in our
judgment, to adversely affect its performance and
reliability. This warranty also does not cover normal
maintenance such as adjustments, fuel system
cleaning and obstruction (due to chemical, dirt,
carbon, lime, and so forth).
• Other Exclusions: This warranty excludes starting
battery, accessory parts, wear items such as oil
gauges, o-rings, filters, fuses, or spark plugs, etc., or
damage or malfunctions resulting from accidents,
abuse, modifications, alterations, or improper
servicing or freezing or chemical deterioration.
This warranty excludes failures due to acts of
God and other force majeure events beyond the
manufacturers control. And this warranty excludes
used, reconditioned, and demonstration equipment;
equipment used for prime power in place of
utility power, equipment used in mobile or rental
applications, and equipment used in life support
applications.
Enclosure is warranted against surface rust and
corrosion for the first year of the warranty period.
Surface rust and corrosion is defined as any rust or
corrosion that has penetrated the paint but has not
penetrated through the metal substructure.
Enclosure is warranted against rust-through for the
first three years of the warranty period.
Rust-through is defined as rust or corrosion that
has penetrated completely through the paint and
metal substructure.
Enclosure is not warranted for surface rust or
corrosion or complete rust-through that may result
due to improper installation, damage to painted
surfaces that compromise the paint’s corrosion
prevention properties, or if the unit is installed in
environments that expose the generator to high levels
of corrosive agents.
Warranty terms effective October 1, 2010 - replaces all undated Warranties and
Warranties dated before October 1, 2010.
313771E, Rev. -, 10 September 2010
29
Loading...
+ 67 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.