AU A12LALAO A12LACLAO B12LACL
AU F12LALAO A12LALLAO B12LALL
AU A14LALAO A14LACLAO B14LACL
AU F14LALAO A14LALLAO B14LALL
FEATURES
ENERGY SAVING (AO A12LACL, AO A12LALL, AO A14LACL, AO A14LALL connection model)
• ALL DC DESIGN
• Heat exchange efficiency increased and larger air flow by adoption of new type turbo fan
ADVANCEMENT IN COMFORT
• Quiet operation was realized by adoption of new type turbo fan
• Improvement of air stream
IMPROVEMENT IN AIRFLOW RANGE (14 TYPE)
Wind velocity at maximum point of airflow range is 0.5m/s
CASSETTE TYPE
AU A12-14L
Conventional type
New type
EXPANSION OF AIR OUTLET ADJUSTMENT RANGE (14 TYPE)
Auto airflow direction and auto swing
Expanded air outlet range provides more comfortable space
2.5 m
3.7 m
IMPROVEMENT OF INSTALLATION & MAINTENANCE
• COMPACT DESIGN
Fits the European size ceiling.
590
590
18kg18kg
570
570
- (01 - 01) -
CASSETTE TYPE
AU A12-14L
• EASY MAINTENANCE
Maintenance of fan motor and fan
Maintenance of fan motor and fan can be done
easily after taking off the panel,
since bell-mouth can be removed easily
A : Fan motor
B : 2 stage turbo fan
C : Bell-mouth
D : Panel
Long life filter
Standard equipment
CASSETTE TYPE
AU A12-14L
A
B
C
D
Adaptation of transparent drainage parts
Easy check of operation of drain-up kit
When you install
EASY INSTALLATION
Easy setting by wireless or wired remote controller.
FUNCTION SETTING
OTHER FUNCTIONS
• The number of air outlet can be selected.
4-way direction3-way direction
Grille cover
• High ceiling mode
Air reaches sufficiently up to 3.5m height, even it is compact cassette type.
High ceiling
3.5m
• Setting the filter sign
The indoor unit has sign to inform the user that it is time to clean the filter
• Setting the cooler room temperature correction
• Setting the heater room temperature correction
• Auto restart
- (01 - 02) -
12
2. REMOTE CONTROLLER
WIRELESS REMOTE CONTROLLER
CASSETTE TYPE
AU A12-14L
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
Easy to change transmission code (4 patterns) by button operation.
Simple function setting
Setting of the air conditioner selection function is performed by remote controller.
Built-in timers
Select from four different timer programs (On/Off/Program/Sleep).
CASSETTE TYPE
AU A12-14L
Program timer
The program timer operates the ON and OFF timer once within a 24 hour period.
Sleep timer
The sleep timer function automatically corrects the temperature thermostat setting according to the
time setting to prevent excessive cooling and heating while sleeping.
Cooling operation/dry operation
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Timer setting
60min.
1 °C
2 °C
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The
set temperature can drop to a maximum of 4 °C.
1 °C
2 °C
3 °C
4 °C
30min.
60min.
90min.
Timer setting
Simultaneously operation
After code change
Mixed-up
• Code selector switch eliminates unit
being wrongly switched.
(Up to 4 codes can be set.)
ABCD
AB
C
1. Press the MODE button for
more than five seconds
to start the code change.
D
•Wide and precise
transmitting range.
- (01 - 03) -
2. Press the or button to
select the desired code.
A B C D
3. Press the MODE button
again to end the code change.
CASSETTE TYPE
AU A12-14L
FUNCTIONS
1
3
2
4
5
11
13
16
10
14
12
15
CASSETTE TYPE
1
MODE button
Selects the operating mode (AUTO, HEAT, FAN, COOL, DRY).
/Start / end R.C. custom code change. (Max 4 types)
2
Economy button
3
Set temp. button ( / )
AU A12-14L
Set remote controller custom code buttons
Sets the indoor temp./ Sets R.C. custom code.
4
Filter reset button
5
Sleep button
Pressed to select sleep timer.
6
6
7
8
9
Fan button
Selects the fan speed (AUTO, QUIET, LOW, MED, HIGH).
7
START/STOP button
Pressed to start and stop operation.
8
Set button (Vertical)
Air flow direction vertical set button.
9
Set button (Horizontal)*
Air flow direction horizontal set button.
10
Swing button
Air flow direction swing button.
11
Timer mode button
Pressed to select the timer mode. (OFF TIMER, ON TIMER,
PROGRAM TIMER, TIMER RESET)
Display panel
17
18
19
20
21
22
23
24
25
12
Timer set ( / ) button
Sets the current time and on-off time.
13
Clock adjust button
Sets the current time.
14
Reset button
Used when replacing batteries.
15
Test run button
Used when testing the air conditioner after installation.
16
Signal transmitter
17
Temperature set display
18
Economy display
19
Operating mode display
20
Sleep display
21
Transmit indicator
22
Fan speed display
23
Swing display
24
Timer mode display
25
Clock display
* These functions are not available.
SPECIFICATION
SIZE (H x W x D mm)170 x 56 x 19
WEIGHT ( g )85 (w/o batteries)
ACCESSORYHolder
- (01 - 04) -
3. SPECIFICATIONS
CASSETTE TYPE
AU A12-14L
Type
Model name
Power source
Available voltage range
European energy label
Cooling
Capacity
Heating
Input power
Current
EER3.333.21
COP3.693.71
Moisture removal
Fan
Sound pressure level
Heat exchanger type
Enclosure
Dimensions
( H×W×D)
Weight
Connection pipe
Operation range
Remote controller type
Drain pipe
Cooling
Heating
Cooling
Heating
Airflow
rate
Type × Q'ty
Motor outputW
Net
Gross
Net
Gross
Sizemm
Method
Material
Size
Rated
Min.-Max.
Rated
Min.-Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Rated
*Max.
Cooling
Heating
Cooling
Heating
Cooling
Heating
Dimensions (H × W × D)
Fin pitch1.201.20
Rows x Stages2X102X10
Pipe type
Fin type
Material
Colour
Unit
Panel
Unit
Panel
Unit15 (33)15 (33)
Panel
Unit18 (40)18 (40)
Panel
Liquid
Gas9.52( 3/8 in.)12.70( 1/2 in.)
Cooling
Heating°C
CoolingAA
HeatingAA
kW3.504.30
BTU/h1195014650
kW0.90 - 4.400.90 - 5.40
BTU/h3100 - 150003100 - 18400
kW4.105.00
BTU/h1400017050
kW0.90 - 5.700.90 - 6.50
BTU/h3100 - 194003100 - 22100
kW
A
kW/kW
l/h (pints/h)1.2 ( 2.1 )1.5 ( 2.6 )
High600680
Med530580
Low470490
Quiet410410
High600800
Med530680
Low470580
Quiet410450
High3738
Med3434
Low3030
Quiet2727
High3743
Med3438
Low3134
Quiet2930
m3/h
dB(A)
mm
mm
kg(lb.)
°C
%RH
mm
AU A12LAL, AU F12LALAU A14LAL, AU F14LAL
AO A12LACL, AO A12LALLAO A14LACL, AO A14LALL
1.051.33
1.732.07
1.111.34
2.302.88
4.65.8
7.59.0
4.95.9
10.012.5
210 × 1310 × 13.3
210 × 1250 × 13.3
Outer diameter : 25.4 / Inner diameter : 19.4
CASSETTE MODEL
INVERTER HEATPUMP
230V50Hz
198-264V 50Hz
Turbo × 1
54
210 × 1310 × 13.3
210 × 1250 × 13.3
Copper tube
Aluminium
PS
WHITE
245 × 570 × 570
49 x 700 x 700
265 x 730 x 625
120 x 765 x 755
2.6 (5.7)
4.5 (10.0)
6.35 ( 1/4 in.)
Flare
18 to 32
80 or less
30 or less
WIRELESS
ABS
CASSETTE TYPE
AU A12-14L
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Ceiling mode : Standard
*The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27 °CDB / 19 °CWB.and outdoor temperature of 35 °CDB/24 °CWB.
Heating : Indoor temperature of 20 °CDB / 15 °CWB.and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
Ceiling mode : Standard
*The maximum current and the maximum input value are the maximum values when operated within the operation range (temperature).
To set “3-way directions”, the air outlet shutter plate (UTR-YDZ ) sold separately
must be installed and “outlet-direction” switched to “3-way” by remote controller.