- (01 - 01) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
MODEL : AS B24LDC
FEATURES
1. FEATURE
Energy saving Rank A
Original plasma air cleaning unit effectively cleans the air in the room.
Super quiet
ALL DC
Large air flow and quiet
operation by new air
flow path
V-PAM technology makes a compressor more powerful.
V P
More compact compared with conventional model
Front view
Back view
Air flow mode can be set in 4 steps and more detailed air flow setting is possible.
High efficiency
layout
New 3-row heat
exchange system
V-P
V-PAM control
b
DC scroll compressor
c
a
DC fan motor
DC fan motor
b
a
c
1
2
3
Dirty Air
Clean Air
Pet odor and the smell of
cigarette smoke are
removed by decomposition
by weak ozone O3.
Clean Air
Activated charcoal
bacteria eliminating &
deodorizing filter
Polyphenol filter
(Grapefruit seed extract)
Earth conductor
Plasma filter generates
ions and ozone.
Electric pole
Electrostatic
filter
Dirty Air
Negatively-charged dust, etc. are attracted
to the earth section and are collected by a
bacteria eliminating & deodorizing filter.
Plasma air filter mechanism
Washable filter
Restored to the same performance
as when new each time it is washed.
Plasma unit
Mounts a plasma air cleaning unit.Minute dust
particles are collected by an electrostatic filter and odor
is suppressed by decomposition of foul odors by very
weak ions. Since a filter with a lower ventilation
resistance than in the past is used, high dust collection
design simultaneously cleans in the air in the room.
Europe energy saving Rank A achieved

- (01 - 02) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
Easy maintenance
Easy maintenance and always clean. Troublesome maintenance has been made easy.
Since the front panel is easy to remove, maintenance is also easy.
Inner drying operation and plasma effect
This model is equipped with an inner drying function. After the power is turned off, the dry operation starts
inside the air conditioner. The plasma air cleaning unit eliminates bacteria, deodorizes, and keeps
the interior of the air conditioner clean by generating ozone and ions.
Power diffuser
Adoption of large power diffuser
Compact design
998mm width compact design
Low outdoor air temperature cooling correspondence
Corresponds to cooling operation at -10°Coutdoor air temperature
New model
(unit:mm)
H320 x W998 x D228
2.52.5
5
0 3 6 9 12(m)
Outside air conditions: 2 oC 60%
( C)
Operation contents: Heating,
Set temperature (Max set temp)
30
o
o
C, Air flow Hi,
Air direction downward and front
“Strong vertical air flow” provides
powerful floor level heating.
Power diffuser
Power diffuser
(full open)
“Healthy horizontal air flow” does not blow
cool air directly at the occupants in the room.
5
2.5
0 3 6 9 12(m)
Corresponds to maximum 30m long piping
2933 32 31 30
Outside air conditions: 35 oC 40%
( C)
Operation contents: Cooling,
Set temperature (Min set temp)
18
o
o
C, Air flow Hi,
Air direction downward and front
1815 16 17
2.5
10kWNo.1 attainedmaximum heating capacity
Adoption of large power diffuser
powerful floor level heating.
Bacteria grows in beading,
and it causes bad odor.
Drying operation for
approx. fifteen minutes.
Ozone bacteria eliminating operation
for approx. fifteen minutes.
“Inner drying operation” and
“ozone bacteria eliminating
operation” keep the inside
of the air conditioner clean
at all times. That ’s why air
from the air conditioner is
always clean and high
efficiency is realized.
After operation ends,
start approximately
30 minutes speed
cleaning operation
by merely pressing
the COIL DRY
button.
Removes moisture.
Bacteria elimination
Covered with beading.

- (01 - 03) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
FEATURES
Four kinds of timer setup (ON / OFF / PROGRAM / SLEEP) are possible.
Four kinds of timers. Easy operation.
Select from four different timer programs (On/Off/Program/Sleep).
Built-in timers
The program timer operates the ON and OFF timer once within a 24 hour period.
Program timer
The sleep timer function automatically corrects the temperature thermostat setting according to the
time setting to prevent excessive cooling and heating while sleeping.
Sleep timer
2-1. WIRELESS REMOTE CONTROLLER
2.
REMOTE CONTROLLER
Cooling operation/dry operation
60min.
1 °C
2 °C
When the sleep timer is set, the set temperature
automatically rises 1 °C every hour. The set
temperature can rise up to a maximum of 2 °C.
Heating operation
When the sleep timer is set, the set temperature
automatically drops 1 °C every 30 minutes. The
set temperature can drop to a maximum of 4 °C.
1 °C
30min.
60min.
90min.
2 °C
3 °C
4 °C
Timer setting
Timer setting

- (01 - 04) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
Display panel
FUNCTIONS
SPECIFICATION
SIZE (H x W x D mm) 176 x 56 x 18
WEIGHT ( g ) 110
ACCESSORY Holder
TIMER SET ( / ) button
SET button (Horizontal)
TEST RUN button
This button is used when installing the
conditioner, and should not be used under normal conditions, as it will cause the
air conditioner’s thermostat function to operate incorrectly.
If this button is pressed during normal operation, the unit will switch to test operation mode, and the Indoor Unit’s OPERATION Indicator Lamp and TIMER Indicator
Lamp will begin to flash simultaneously.
To stop the test operation mode, press the
START/STOP button to stop the air conditioner.
CLOCK ADJUST button
Remote Control Unit Display
Transmit Indicator
Clock Display
Operating Mode Display
Timer Mode Display
Fan Speed Display
Temperature SET Display
SLEEP button
MASTER CONTROL button
/ )
SET TEMP. button (
COIL DRY button
Signal Transmitter
TIMER MODE button
FAN CONTROL button
START/STOP button
SET button (Vertical)
SWING button
RESET button
AIR CLEAN Display
SLEEP Display
SWING Display
4
6
7
8
9
10
19
21
22
23
24
26
27
COIL DRY Display
25
20
18
2
3
11
13
12
16
17
15
1
14
AIR CLEAN button
5
2
4
10
3
1
16
6
18
19
20
22
26
25
23
27
11
14
12
13
15
9
8
7
21
5
24
17

- (01 - 05) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
3. SPECIFICATIONS
WALL MOUNTED
INVERTER HEAT PUMP
Cooling A
Heating A
kW 7.10
BTU/h 24,200
kW 0.9 - 8.0
BTU/h 3,100 - 27,300
kW 8.10
BTU/h 27,600
kW 0.9 - 10.6
BTU/h 3,100 - 36,200
2.21
0.11 - 2.62
2.24
0.11 - 3.68
9.7
12
9.8
17.5
3.21
3.62
kW 5.54
99
99
l/h (pints/h) 3.0 (5.3)
High 1170
Med 970
Low 785
Quiet 685
High 1170
Med 970
Low 785
Quiet 685
Cross flow fan × 1
W 42
High 49
Med 43
Low 38
Quiet 33
High 48
Med 42
Low 37
Quiet 33
Dimensions (H × W × D)
Main : 378 × 832 × 26.6
Sub : 84 × 832 × 13.3
Main : 1.2, Sub : 1.4
Main : 2 × 18, Sub : 1 × 4
Copper
Aluminium
Polystyrene
White
320 × 998 × 228
319 × 1090 × 429
14 (30.8)
18 (39.6)
Flare
°C 18 to 32
%RH 80 or less
°C 30 or less
Wireless
PVC
mm Outer diameter : 28 / Inner diameter : 16
Note :
Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB/19°CWB. and outdoor temperature of 35°CDB/24°CWB.
Heating : Indoor temperature of 20°CDB/15°CWB. and outdoor temperature of 7°CDB/6°CWB.
Pipe length : 7.5 m, Height difference : 0 m. (Outdoor unit - Indoor unit)

- (01 - 07) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
5. WIRING DIAGRAMS
MODEL : AS B24LD
TO OUTDOOR UNIT
BLUE
YELLOW
WHITE
BLACK
RED
PINK
BLUE
YELLOW
ORANGE
RED
PINK
BLUE
YELLOW
ORANGE
RED
PINK
BLUE
YELLOW
ORANGE
RED
WHITE
RED
WHITE
WHITE
WHITE
WHITE
WHITE
BLACK
BLACK
BLACK
RED
WHITE
BLACK
BLACK
WHITE
BLACK
RED
BLUE
RED
YELLOW
WHITE
WHITE
YELLOW
GREEN
RED
BLUE
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
7
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
1
2
3
4
5
1
2
3
4
5
1
2
3
4
1
2
3
4
1
2
3
4
5
1
2
3
1
2
3
1
2
1
2
6
5
4
3
2
1
6
5
4
3
2
1
5
4
3
2
1
54
3
2
1
5
4
3
2
1
CN19
W5
AIR CLEAN UNIT
SWITCH
TM2
TM1
TM4
CN11
CN6
CN1
CN2
CN5
CN201
CN8
CN3
CN13
CN10
THERMAL
FUSE 102
1 2 3
TERMINAL
M
M
STEP MOTOR
( UP / DOWN )
STEP MOTOR
( DIFFUSER )
FAN MOTOR
M
F M
TEST
PIPE TEMP.
THERMISTOR
ROOM TEMP.
THERMISTOR
INDICATO
PCB ASSY
REMOTE CONTROL
UNIT (OPTION)
WHITE
RED
1
2
3
STEP MOTOR
( RIGHT / LEFT )

- (01 - 08) -
WALL MOUNTED TYPE
AS B24LD
WALL MOUNTED TYPE
AS B24LD
6. CAPACITY TABLE
6-1. COOLING CAPACITY
MODEL : AS B24LD
°CDB
°CWB
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
5.26 4.97 1.05 5.86 5.00 1.07 6.06 5.43 1.07 6.46 5.45 1.09 6.66 5.88 1.09 7.05 5.86 1.10 7.45 6.24 1.11
6.26 5.61 1.75 6.98 5.64 1.78 7.22 6.13 1.79 7.69 6.15 1.80 7.93 6.65 1.81 8.41 6.62 1.83 8.88 7.05 1.85
6.00 5.21 1.94 6.68 5.24 1.97 6.91 5.70 1.98 7.36 5.71 2.00 7.59 6.17 2.01 8.05 6.15 2.03 8.50 6.55 2.05
5.61 4.67 2.13 6.25 4.70 2.17 6.46 5.11 2.18 6.89 5.13 2.20 7.10 5.54 2.21 7.53 5.51 2.23 7.95 5.87 2.25
5.06 4.08 2.15 5.64 4.10 2.18 5.83 4.46 2.19 6.22 4.47 2.21 6.41 4.83 2.22 6.79 4.81 2.25 7.18 5.13 2.27
4.73 3.72 2.16 5.27 3.74 2.20 5.45 4.07 2.21 5.81 4.08 2.23 5.99 4.41 2.24 6.35 4.39 2.27 6.71 4.67 2.29
AFR : Air Flow Rate (m3/min)
TC : Total Capacity (kW)
SHC : Sensible Heat Capacity (kW)
PI : Power Input (kW)