General ARG60AH, ARG60AUAK, AOG60APAGT, ARG60RH, ARG60RUAK Technical Manual [ru]

...
R22
5 . DUCT TYPE AR (60)
D2D007E/01
2005.04.22
MODEL : AR60
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 01) -
5-2. REMOTE CONTROLLER
5-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in one unit.
Wired
remote
controller
Built-in timers
Weekly
timer
Setback timerWeekly timer
Setback
timer
Possible to set ON/OFF time to operate twice each day of the week.
DUCT TYPE
AR60
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
DUCT TYPE
AR60
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is
Timer area
Operation area
needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
- (05 - 02) -
European switch box
JIS box
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2 6
7 8 9
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETE SET
12 15 18 21
DAY
DAY OFF
SA
14
1 3
ENERGY
SAVE
THERMO SENSOR
4
5
2
Set Temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
10
11
12
13
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Display panel
15
SUMOTUWETH FR
DUCT TYPE
AR60
369
SA
12 15 18 21
16
1718 19
2021 2223
Set back button
pressed select the set back timer.
9
Set time button
Pessed to select the set back timer.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Horizontal air flow direction and swing button
Push for two seconds to change the swing mode.
DUCT TYPE
AR60
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT g 160
ACCESSORY 10m cable
13
Vertical air flow direction and swing button
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display Indicates during the oil recovery and defrosting operation.
21
Vertical swing display
22
Horizontal swing display
23
Energy save display
- (05 - 03) -
COOLING TYPE HEAT PUMP TYPE
AR*60AUAK AR*60RUAK
AO*60APAGT AO*60RPAGT
kW
BTU/h
kW - 17.8 - 18.2
BTU/h - 60700 - 62100
COOLING RATED 5.8 - 5.9 5.9 - 6.0
HEATING RATED - 5.05 - 5.25
COOLING RATED 9.8 - 9.8 9.8 - 9.8
HEATING RATED - 8.7 - 8.7
A
COOLING 2.83 - 2.88 2.78 - 2.83
HEATING - 3.52 - 3.47
l/h (pints/h)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
58.5 / - 58 / 59
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
- Corrosion resistant coating
Rows x Stages x Fin Pitch
mm 2 x 52 x 1.8 2 x 26 x 1.5
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR 55 / 136 55 / 144
LIQUID
GAS
m
m
CHARGE kg 3.8 4.8
COOLING
HEATING
WIRED (AR-3TA2) WIRED (AR-3TA1)
mm
Simple remote controller
(UTB-YRB/UTB-GRB)
Simple remote controller
(UTB-YPB/UTB-GPB)
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 100 Pa. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) dimensions( )* are indicated the including flange,control box,safety drain pan.
460 x 1230 x 640
355.6x890x76.2
Plate fin coil
Fan motor thermal protector,Fuse
Plate fin coil
42 / 42
5040
400 x 1050(1150)* x 500(585)*
1355 x 940 x 370
660x975x38.1
Three Phase
Fan motor thermal protector,Fuse
Hydrophilic coating
4 x 14 x 1.80
540
63
49 / 49
45 / 45
100 to 250
Sirocco fan
Propeller fan
A
3600
3100
2600
5900
Coil
HEAT EXCHANGER TYPE
INDOOR
COP
Surface treatment
W/W
OUTDOOR
Coil
Surface treatment
0 to 43
R22
REMOTE CONTROLLER
TYPE
REFRIGERANT OIL
OPERATION(OUTDOOR)
°C
REFRIGERANT TYPE
-10 to 24
380 - 415V 50Hz
RATED
50 (chargeless:7.5m)
SCROLL
Hot-dipped galvanized steel sheet
Beige (10YR7.5/1.0NN)
RECOMMENDED STATIC PRESSURE @ high
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
OUTDOOR
AIR CIRCULATION
MODEL NAME
DUCTED MODELS
INDOOR
OUTDOOR
TYPE POWER SOURCE
DIMENSIONS H ×W ×D
INDOOR
OUTPUT
TYPE
OUTDOOR
COOLING
HEATING
CAPACITY COMPRESSOR
OPTIONS
FAN TYPE x Q'ty
FAN MOTOR OUTPUT
W
WEIGHT
NET
GROSS MAX HEIGHT
MAX LENGTH
RATED
INPUT POWER STARTING METHOD
m3/h
INDOOR
kW
CURRENT
dB(A)
STARTING CURRENT
MOISTURE REMOVAL
SAFETY DEVICES
NET / GROSS
CONNECTION METHOD
Synthetic (POE oil)
30
9.53(3/8 inc.)
19.05(6/8 inc.)
FLARE
CASING COLOR
mm
kg(lbs)
PIPE
SIZE
1485 x 1000 x 450
50 / 121
mm
Remote Sensor (UTD-RS100F/UTD-RS100G)
Long Life Filter (UTD-LF60K/UTB-LF60KA)
Wire Set (UTD-ECS5A)
-
OUTDOOR
INDOOR
DRAIN PIPE MATERIAL
Steel
SIZE
Outer diameter 25.4mm / Inner diameter 23.4mm
16.4 - 17.0
56000 - 58000
74
6.50
5-3. SPECIFICATIONS
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 04) -
5-4. DIMENSIONS
5-4-1. OUTDOOR UNIT
MODEL : AO60
(Unit : mm)
370
1,355
23
425
DUCT TYPE
AR60
400
650 940
DUCT TYPE
AR60
- (05 - 05) -
5-4-2. INDOOR UNIT
MODELS : AR60
(Unit : mm)
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 06) -
MOUNTING POSITION
395 mm
155 mm
585 mm
500 mm
1,050 mm
1,000 mm
AIR
1,080 mm
85 mm
AIR
AIR
325 mm
14 mm
DUCT TYPE
AR60
27 mm
14 mm
26 mm
295 mm
865 mm
Intake port flange
Outlet port flange
850 mm
DUCT TYPE
AR60
- (05 - 07) -
5-5. REFRIGERANT CIRCUIT
COOLING ONLY TYPE
MODELS : AR*60AUAK / AO*60APAGT
OUTDOOR UNIT INDOOR UNIT
MUFFLER
COMPRESSOR
CONDENSER
DRYER
ACCUMULATOR
Charging valve
CAPILLARY TUBE
Charging valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATOR
Refrigerant pipe
9.52mm(3/8")
DUCT TYPE
AR60
HEAT PUMP TYPE
DUCT TYPE
AR60
MODELS : AR*60RUAK / AO*60RPAGT
OUTDOOR UNIT INDOOR UNIT
HIGH PRESSURE SWITCH
4-Way Valve
MUFFLER
ACCUMULATOR
COMPRESSOR
Charging valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATORCONDENSER
: Cooling : Heating
DRYER
STRAINER
EXPANSION VALVE
Charging valve
Refrigerant pipe
9.52mm(3/8")
- (05 - 08) -
5-6. WIRING DIAGRAMS
5-6-1. OUTDOOR UNIT
MODEL : AO60A
DUCT TYPE
AR60
DUCT TYPE
AR60
MODEL : AO60R
- (05 - 09) -