5-2. REMOTE CONTROLLER
5-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
one unit.
Wired
remote
controller
Built-in timers
Weekly
timer
Setback timerWeekly timer
Setback
timer
Possible to set ON/OFF time to operate twice each day
of the week.
DUCT TYPE
AR60
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen
after setup
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
DUCT TYPE
AR60
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
Timer
area
Operation
area
needed.
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (05 - 02) -
European
switch box
JIS box
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2
6
7
8
9
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETE SET
12 15 18 21
DAY
DAY OFF
SA
14
1
3
ENERGY
SAVE
THERMO
SENSOR
4
5
2
Set Temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
10
11
12
13
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Display panel
15
SUMOTUWETH FR
DUCT TYPE
AR60
369
SA
12 15 18 21
16
1718 19
2021 2223
Set back button
pressed select the set back timer.
9
Set time button
Pessed to select the set back timer.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Horizontal air flow direction and swing button
Push for two seconds to change the swing mode.
DUCT TYPE
AR60
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT g 160
ACCESSORY 10m cable
13
Vertical air flow direction and swing button
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display
Indicates during the oil recovery and defrosting operation.
21
Vertical swing display
22
Horizontal swing display
23
Energy save display
- (05 - 03) -
COOLING TYPE HEAT PUMP TYPE
AR*60AUAK AR*60RUAK
kW
BTU/h
kW - 17.8 - 18.2
BTU/h - 60700 - 62100
COOLING RATED 5.8 - 5.9 5.9 - 6.0
HEATING RATED - 5.05 - 5.25
COOLING RATED 9.8 - 9.8 9.8 - 9.8
HEATING RATED - 8.7 - 8.7
A
COOLING 2.83 - 2.88 2.78 - 2.83
HEATING - 3.52 - 3.47
l/h (pints/h)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
58.5 / - 58 / 59
Rows x Stages x
Fin Pitch
mm
Coil Dimensions mm
- Corrosion resistant coating
Rows x Stages x
Fin Pitch
mm 2 x 52 x 1.8 2 x 26 x 1.5
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR 55 / 136 55 / 144
LIQUID
GAS
m
m
CHARGE kg 3.8 4.8
COOLING
HEATING
WIRED (AR-3TA2) WIRED (AR-3TA1)
mm
Simple remote controller
(UTB-YRB/UTB-GRB)
Simple remote controller
(UTB-YPB/UTB-GPB)
Note: Specifications are based on the following conditions.
Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
dimensions( )* are indicated the including flange,control box,safety drain pan.
Fan motor thermal protector,Fuse
400 x 1050(1150)* x 500(585)*
Fan motor thermal protector,Fuse
Hot-dipped galvanized steel sheet
RECOMMENDED STATIC PRESSURE @ high
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
INPUT POWER
STARTING METHOD
Remote Sensor (UTD-RS100F/UTD-RS100G)
Long Life Filter (UTD-LF60K/UTB-LF60KA)
Wire Set (UTD-ECS5A)
Outer diameter 25.4mm / Inner diameter 23.4mm
5-3. SPECIFICATIONS
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 04) -
5-5. REFRIGERANT CIRCUIT
COOLING ONLY TYPE
MODELS : AR*60AUAK / AO*60APAGT
OUTDOOR UNIT INDOOR UNIT
MUFFLER
COMPRESSOR
CONDENSER
DRYER
ACCUMULATOR
Charging valve
CAPILLARY TUBE
Charging valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATOR
Refrigerant pipe
9.52mm(3/8")
DUCT TYPE
AR60
HEAT PUMP TYPE
DUCT TYPE
AR60
MODELS : AR*60RUAK / AO*60RPAGT
OUTDOOR UNIT INDOOR UNIT
HIGH
PRESSURE
SWITCH
4-Way
Valve
MUFFLER
ACCUMULATOR
COMPRESSOR
Charging
valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATORCONDENSER
: Cooling
: Heating
DRYER
STRAINER
EXPANSION
VALVE
Charging valve
Refrigerant pipe
9.52mm(3/8")
- (05 - 08) -