General ARG60A, ARG60ALA3, AOG60ABA3L, ARG60R, ARG60RLA3 Installation Manual

...
SPLIT TYPE AIR CONDITIONER
Duct Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9362590013)
For authorized service personnel only.
WARNING
(1) For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(3) Do not turn on the power until all installation work is complete.
Be careful not to scratch the air conditioner when handling it.
After installation, explain correct operation to the customer, using the operating manual.
Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation cannot be guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as requred.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Installation template
Special nut A (large flange)
Special nut B (small flange)
Coupler heat insulation (large)
Coupler heat insulation (small)
Nylon fastener For fixing the drain hose
Remote controller
Remote controller cord clamp
Tapping screw (flush heads)
Auxiliary pipe assembly
Drain hose insulation
Drain pipe insulation
OUTDOOR UNIT ACCESSORIES
Power cap
For positioning the indoor unit
1
For suspending the indoor unit from ceiling
4
4
For indoor side pipe joint (large pipe)
2
For indoor side pipe joint (small pipe)
1
1
1
For installing the remote controller cord
10
For installing the remote controller cord clamp
10
For wiring conduit (gas side) connection
1
Insulates the drain pipe and drain hose connection
1
For insulating the drain pipe
1
For power supply cord installation
1
SELECTING THE MOUNTING POSITION
Decide the mounting position together with the customer as follows:
INDOOR UNIT
(1)
Install the indoor unit on a place having a sufficient strength so that it withstand against the weight of the indoor unit.
(2)
The inlet and outlet parts should not be obstructed; the air should be able to blow all over the room.
(3)
Leave the space required to service the air conditioner (Fig. 1).
Fig. 1
Strong and durable ceiling
INDOOR UNIT
Left
side
150 mm or more
Install the unit where the drain pipe can be easily installed.
(4)
Providing as much space as possible between the indoor unit and
(5)
the ceiling will make work much easier.
OUTDOOR UNIT
Install the unit where it will not be tilted by more than 5°.
(1)
When installing the outdoor unit where it may
(2)
exposed to strong wind, fasten it securely.
Leave the space indicated for good air flow. (Fig. 2)
(1)
Fig. 2
(2)
If possible, do not install the unit where it will exposed to direct sun­light. (If necessary, install a blind that does not interfere with the air flow.)
(3)
Do not install the unit near a source of heat, steam, of flammable gas.
(4)
During heating operation, drain water flows from the outdoor unit. Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Reverse cycle model only)
(5)
Do not install the unit where a strong wind blows or where it is very dusty.
(6)
Do not install the unit where people pass.
(7)
Install the outdoor unit in a place where it will be free from being dir­ty or getting wet by rain as much as possible.
(8)
Install the unit when connection to the indoor unit is easy.
100 mm or more
AIR FLOW
500 mm or more
WARNING
300 mm or more
600 mm or more
Right
side
10 mm or more
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
INDOOR UNIT INSTALLATION
1. PIPING CONNECTION DIRECTION AND PREPARATION
Select piping directions.(Fig. 3)
Fig. 3
To top
Auxiliary pipe assembly
To rear
To side
To bottom
When bending the piping is difficult, use the auxiliary pipe assembly.
2. DRILLING HOLES FOR BOLTS AND INSTALLING THE BOLTS
Using the installation template, drill holes for bolts (four holes). (Fig. 4)
Fig. 4
Installation template
3. INSTALLING THE HANGERS
Installation method
Fasten the hanging bolts to the ceiling and install special nuts A and B.
Fig. 5
Install the hangers to the unit.
Fig. 6
Air
Right side
Hang the unit.
Pass the hanging bolts through the hangers. (Four places)
Fig. 7
Hanger bolt
Hanger
Hanger
Drilling position for bolts
Hanging bolt
Special nut A
Special nut B
Unit
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 9
B
Ceiling
Level
CAUTION
The side of the unit that holds the drain port (A) should be slightly lower than the opposite side of the unit (B). The slant should allow from 0 to 20 mm of difference between (A) and (B).
Base vertical direction leveling on the unit (right and left).
Fig. 10
Air
Level
5. SERVICE HOLE DIMENSIONS
Open a service hole with the dimensions shown below.
Fig. 11
Unit
100 mm
or more
Service hole
500 mm or more
2
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
(1)
When the outdoor unit will be exposed to strong wind, fasten it with bolts or wire at the four places indicated by the arrows. (Fig. 12)
(2)
Since the drain water flows out of the outdoor unit during heating operation, install the drain pipe and connect it to an commercial 16 mm hose. (When heating when the outdoor temperature is 0°C or less, construct so that the drain water drained from the outdoor unit will not freeze in the drain pipe.) (Reverse cycle model only)
(3)
When installing the drain pipe, plug all the holes other than the drain pipe mounting hole in the bottom of the outdoor unit with put­ty so there is no water leakage. (Fig. 12) (Reverse cycle model only)
Fig. 12
Drain cap
Drain pipe or drain cap
Always use a drain pipe at two places.
(4)
2. OUTDOOR UNIT CONNECTION CORD AND PIPE CONNECTION PREPARATIONS
(1)
Piping and connection cord mounting direction (4-way mounting possible).
Fig. 13
Plug the holes.
A
Control box
Open the piping and connection cord knockout holes of the desired
(3)
direction with nippers, etc. After opening the knockout holes, install the accessory edge cover and power cap to protect the opened places.
Fig. 15
Connect the piping and power supply cord from the mounting
(4)
holes.
When pipe bending work is
*
difficult inside the outdoor unit, use the accessory auxiliary pipe assembly.
3
Fig. 16
CONNECTING THE PIPING
1. FLARE PROCESSING
(1)
Cut the connection pipe with pipe cutters so that the pipe is not deformed.
(2)
Holding the pipe downward so that cuttings cannot enter the pipe, remove the burrs.
(3)
Remove the flare nut from the indoor unit pipe and outdoor unit and assemble as shown in (Table 3) and insert the flare nut onto the pipe, and flare with a flaring tool.
(4)
Check if the flared part “L” (Fig. 17) is spread uniformly and that there are no cracks.
Table 3
Flare nut
L dimension Small pipe (9.53 mm dia)
1.8 to 2.0 mm Large pipe (19.05 mm dia)
2.6 to 3.0 mm
Small pipe
Large pipe
Fig. 17
Pipe
Small (width across flats 22 mm)
Large (width across flats 36 mm)
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 18
Do not bend the pipes in an angle less than 90°. When the pipes are bent and stretched repeatedly, the material will be hardened, causing the pipes no longer be sent or stretched. Be sure to limit number of bending and stretchings to three times.
When bending the pipe, do not bend it as is. The pipe will be collapsed. In this case, cut the heat insulating pipe with a sharp cutter as shown in Fig. 19, and bend it after exposing the pipe. After bending the pipe as you want, be sure to put the heat insulat­ing pipe back on the pipe, and secure it with tape.
Fig. 19
3. CONNECTION PIPES
Indoor unit side
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare nut cannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.
CAUTION
Be sure to connect the large pipe after connecting the small pipe completely.
Outdoor unit side
(1)
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method is the same as that as at the indoor side.
(2)
Seal with the accessory putty so that water does not enter at the top of the pipe insulation installed to the connection pipe (large pipe and small pipe).
Fig. 22
Valve A (small)
Putty
(Small pipe)
(Large pipe)
4.
CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING
For both the indoor and outdoor unit sides, check the joints for gas leaking by the use of a gas leakage detector without fail when the pipes are connected.
Valve B (large)
Flare nut
Connection pipe
5. HEAT INSULATION ON THE PIPE JOINTS (INDOOR SIDE ONLY)
Stick coupler heat insulation (large and small) to the place where
connecting pipes. When using auxiliary piping with large pipe, stick coupler heat insu-
lation (large) to the pipe at the two places shown below.
Fig. 23
Coupler heat insulation (small) on the pipe
Rear
Small pipe
Coupler heat insulation (large) on the pipe.
Large pipe
Cover this portion with heat insulating material also without fail.
Heat insulating pipe
CAUTION
No gap should remain.
4
VACUUMING AND
ADDITIONAL CHARGE
VACUUM
1.
Vacuum inside the indoor unit and the piping to a pressure of 1.5 mmHg
(1)
abs or less from the charging valve with a vacuum pump. After vacuuming inside the indoor unit and the piping, remove the cap
(2)
of the two valves. Open the spindle(handle) of the two valves from the closed state. (Table 6)
(3)
Tighten the cap of the two valves to the specified torque.
(4)
Table 5
Tightening torque
Large valve Small valve
25 kgf
Spindle (TYPE A)
Handle (TYPE B)
Cap
TYPE A
150 to 200 kgf
Open valve stateValve
15 kgf
Table 6
cm (2.45 N
cm (1.47 N
m) or less
m) or less
cm (14.7 to 19.6 N
Closed valve state
m)
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 5 m (36/45 TYPE), 20 m (60 TYPE) is charged in the outdoor unit at the factory. When the piping is longer than 5 m (36/45 TYPE), 20 m (60 TYPE) addi­tional charging is necessary. For the additional amount, see the table below.
Table 7
Additional refrigerant
(Cooling model)
(Reverse cycle model)
Pipe length
36/45 TYPE
36/45 TYPE
60 TYPE 1200 g 1800 g 60 g/m
5 m 10 m 20 m 30 m 40 m 50 m g/m
None 175 g 525 g 875 g 1225 g 1575 g 35 g/m
None 200 g 600 g 1000 g 1400 g 1800 g 40 g/m
None 600 g
CAUTION
When charging the refrigerant, always use a measuring
(1)
cylinder.
Add refrigerant from the charging valve after the com-
(2)
pletion of the work.
5
INSTALLING DRAIN HOSE
NOTE : INSTALL THE DRAIN HOSE
Install the drain hose so that there is a trap. The position of the
••
installed drain hose should have a downward gradient of (1/50 to 1/100). Make sure that the drain hose is installed without rises. Make the trap near to the indoor unit.
Use general hard polyvinyl chloride pipe (VP25) [outside diameter
38 mm] and connect it with adhesive (polyvinyl chloride) so that there is no leakage. When the hose is long, install supporters.
Do not perform air bleeding.
Always heat insulate the indoor side of the drain hose.
Fig. 25
1
= 100 mm (approx.)
Outlet air flow
1
H
2
H
The outside diameter of the drain port is 38 mm. Use a suitable
••
drain hose. Stick the large drain hose insulation at the drain hose installation
side. (Fig. 26-(1))
Fig. 26-(1)
Drain pipe
Drain hose
Fig. 26-(2)
As required.
••
Drain hose insulation
Drain hose
Rise
1.5 to 2 m
Air bleeding
H H
Unit side
2
= 50~100 mm
Drain hose insulation
0 mm
Supporter
Drain hose
Auxiliary pipe assembly
1
Edge cover
1
Tapping screw
2
Binder
1
Putty
1
Coupler heat insulation
1
Pipe (drain)
2
Flexible tube
2
Cap (drain)
2
For wiring conduit (gas side) connection (May not be supplied, depending on the model)
For wiring conduit installa­tion hole edge protection
For cabinet A and cabinet D mounting (1)
Spare (1)
For power supply cord binding
For sealing
For outdoor side pipe joint
For outdoor unit drain piping work (May not be supplied, depending on the model.)
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
9.53 mm 19.05 mm
Use 0.7 mm to 1.2 mm thick pipe.
Use pipe with water-resistant heat insulation.
Maximum
length
50 m 30 m
Maximum height
(between indoor
and outdoor)
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 2
Power
supply
cord
2
(mm
)
Connection
cord
2
(mm
)
Fuse capacity (A)
Install all electrical works in accordance to local regulation. Use H07RN-F or equivalent as the connection cord. (Europe area only)
Install the disconnect device with a contact gap of at least 3 mm
nearby the units. (Both indoor unit and outdoor unit)
MAX
MIN
MAX
MIN
3.5
2.5
2.5
1.0
20
CAUTION
Fasten the unit securely with special nuts A and B.
Hanging bolt installation diagram
Fig. 8
1,300 mm
1,250 mm
1,063 mm
800 mm
710 mm
1,063 mm
Control box
(2)
Remove outdoor unit cabinet A and cabinet D.
Fig. 14
After removing the screws, remove
*
cabinet A by pushing it down.
Centering the pipe against port on the indoor unit, turn the flare nut with your hand.
CAUTION
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 21, in order to tighten the flare nut correctly.
When the flare nut is tightened properly by your hand, use a torque wrench to finally tighten it.
Fig. 20
Holding spanner
Small pipe
Large pipe
Pipe
Torque wrench
Table 4 : Flare nut tightening torque
Tightening torque
310 to 350 kgf
800 to 1,000 kgf
Fig. 21
Unit side
cm (30.4 to 34.3 N
cm (78.4 to 98 N
90°
m)
m)
Fig. 24
Valve A (small)
Screwdriver
Charging valve
Valve A (small)
Charging valve
TYPE B
* If the spindle (handle) is not fully open, performance will drop and an abnormal sound will be generated.
[TYPE A]
Small pipe
Spindle
[TYPE B]
Small pipe
Handle
Large pipe
Valve B (large)
Cap
Valve B (large)
Large pipe
Cap
Gauge manifold
Vacuum pump
Service hose
6
Drain pipe insulation
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1)
Cut the wire and with a wire cutter or wire-cutting pliers, then strip the insulation to about 15/16” (25 mm) of expose the solid wire.
(2)
Using a screwdriver, remove the terminal screw(s) on the terminal board.
(3)
Using pliers, bend the solid wire to form a loop suitable for the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal board and tighten securely with the terminal screw using a screw­driver.
B. For strand wiring
Cut the wire and with a wire cutter or wire-cutting pliers,
(1)
then strip the insulation to about 3/8” (10 mm) of expose the strand wiring. Using a screwdriver, remove the terminal screw(s) on the
(2)
terminal board. Using a round terminal fastener or pliers, securely clamp a
(3)
round terminal to each stripped wire end. Position the round terminal wire, and replace and tighten
(4)
the terminal screw with a screwdriver.
- Continued on back -
Fig. 27
2. OUTDOOR UNIT SIDE
(1)
Remove outdoor unit cabinet A and connect the power supply cord and the outdoor unit connection cord wired at the indoor unit.
(2)
Fasten the power supply cord and connection cord with cable clips and binders as shown in (Fig. 31).
Fig. 30
Cabinet A
8
REMOTE CONTROLLER
INSTALLATION
Insert the end of a flat blade screwdriver at the arrow parts of the
groove at the side of the remote controller case and remove the remote controller case top by turning the screwdriver. Disconnect the remote controller cord from the remote controller
terminal board.
Fig. 34
When EE: EE blinks at the current time display, there is an error
inside the air conditioner. If the ZONE CONTROL button and ENERGY SAVE button are pressed simultaneously for more than three seconds, the self diagnosis check will start and the error contents will be displayed at the current time display. (Fig. 39) When the operation lamp lights, press the START/STOP button and after operation lamp goes off, perform the same operation. (Fig. 39) Process the error contents by referring to (Table 8).
Fig. 39
45 TYPE
(mmAq)
EXTERNAL STATIC PRESSURE
Round flange dimensions
RECOMMENDED RANGE
444333278222167 500 556 611 667 722 833 889 944 1000
20
HIGH
LOW
(L/Sec)
294
196
Unit : (mm)
(Pa)30
1. INDOOR UNIT SIDE
Attaching and removing the control box cover.
(1)
Fig. 28
Control box cover
Screw
Side view
Control box
Fig. 31
Terminal board
Cord clamp
Power supply cord
Remove the four screws and slide cabinet A down.
Electric box
Power supply cord
Earth
Connection cord (indoor unit and outdoor unit connection cord)
(1)
When remote controller exposed
1)
Make a notch in the thin part ( part of Fig. 34) at the rem­ote controller case top and bottom with nippers, file, etc.
2)
Connect the remote controller cord to the remote controller terminal board specified in (Fig. 35)
3)
Clamp the remote controller cord sheath with the binder (small) as shown in Fig. 35.
4)
Cut off the excess binder.
5)
Clamp the remote controller cord to a wall, etc. with the rem­ote controller cord clamp furnished. (Fig. 36)
Fig. 35
Remote controller cord
Binder (small)
Red
White
Black
Remote controller terminal board
Error cord
E0:00
E1:00
E2:00
E3:00
E4:00
E5:00
E6:00
E7:00
EA:00
Eb:00
EC:00
Ed:00
EF:00
Stop operation
Table 8
Error contents
Communication error (indoor unit remote controller)
Communication error (indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor shorted
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor shorted
Outdoor heat exchanger temperature sensor open
Outdoor heat exchanger temperature sensor shorted
Outdoor temperature sensor open
Outdoor temperature sensor shorted
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shorted
Discharge pipe temperature abnormal
11
10
0
1600140012001000800600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600
AIR FLOW (m
36 TYPE
(mmAq)
EXTERNAL STATIC PRESSURE
RECOMMENDED RANGE
444389278222167 500 556 611 667 722 778 833 889
20
10
0
1600140012001000800600 1800 2000 2200 2400 2600 2800 3000 3200
HIGH
LOW
AIR FLOW (m
(L/Sec)
APPEARANCE OF OUTDOOR UNIT
98
Flexible duct
Model name : UTD-RD202 (P/N 9074165004)
0
3
/H)
ø200 mm L 2 m
(Pa)30
294
196
98
0
3
/H)
12
Connection cord and remote controller cord connections.
(2)
Clamp the connection cord with the cord clamp and the remote
controller cord with the nylon clamp. (Fig. 29)
Fig. 29
1
Remote controller cord
Nylon clamp
23
RED
WHITE BLACK
REMOTE
CONTROL UNIT
RED
WHITE
G
Earth
BLACK
(N)
2
1
OUTDOOR UNIT
Cord clamp
3
Hi Me Lo
FAN MOTOR
Connection cord
Hi Me Lo
FAN MOTOR
Fan motor cord (Already connected)
Fig. 32
Fig. 33
Coupler holder
7
After passing the connection cord through the insulation tube, fasten it with the cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Cable clip
Binder
Compressor
Power supply cord and connection cord (indoor unit and outdoor unit connection cord)
Outdoor unit
100 mm or less
Cabinet D
POWER
WARNING
The rated voltage of this product is 3ø 4W 380-415V
(1)
50Hz.
Before turning on verify that the voltage is within the
(2)
342 to 457V range.
Fig. 36
Remote controller cord
Tapping screw (flush heads)
(2)
When remote controller cord embedded
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the remote
Remote controller cord clamp
controller case bottom and install the cord to the box. (Fig. 37)
3)
Connect the remote controller cord to the remote controller terminal board specified in (Fig. 35).
Fig. 37 [Example]
Remote controller case top
Remote controller cord
Remote controller case bottom
After wiring work is complete, return the remote controller case
top to its original state.
CAUTION
Do not bundle the remote controller cord, or wire
(1)
the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and the power supply cord. It may cause erroneous operation.
When installing the remote controller and cord near
(2)
a source of electromagnetic waves, separate the rem­ote controller from the source of the electromagnet­ic waves and use shielded cord.
Do not touch the remote controller PC board and PC
(3)
board parts directly with your hands.
To stop test running, press the START/STOP button.
For the operation method, refer to the operating manual and per­form operation check.
Check that there are no abnormal sounds or vibration sounds dur­ing test running.
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may switch to low speed, or one of the fans may stop intermittently.
ERROR
The LED lamps operate as follows (Table 9) according to the error contents. The LED lamps are on the outdoor unit board.
Table 9
Error display Error contents
Lighting continued
Single quick flashes repeated
Two quick flashes repeated
Three quick flashes repeated
Lighting continued
LED
No. 1
Lamp
LED No. 2 Lamp
ON
OFF
0.5 sec
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5 sec
0.5 sec 0.5 sec
5 sec
0.5 sec 0.5 sec
5 sec
When the fault is cleared, the LED lamp goes off. However, for discharge pipe temperature abnormal and high pres­sure abnormal, the LED lamp lights continuously for 24 hours, as long as the power is not turned off.
Discharge pipe temperature abnomal
Outdoor heat exchanger tem­perature sensor abnormal
Outdoor tem­perature sensor abnormal
Discharge pipe temperature sensor abnormal
High pressure abnormal
12
Fig. 41
60 TYPE
36/45 TYPE
CONNECTION FLANGE DIMENSIONS
(INTAKE AND OUTLET)
Fig. 42
Rectangular flange
Connection cord
Remote controller cord
CAUTION
(1)
Tighten the indoor unit connection cord (to the out­door unit) and power supply indoor and outdoor unit terminal board connections firmly with the terminal board screws. Faulty connection may cause a fire.
(2)
If the indoor unit connection cord (to the outdoor unit) and power supply are wired incorrectly, the air conditioner may be damaged.
(3)
Wire the indoor unit connection cord (to the outdoor unit) by matching the numbers of the outdoor and indoor units terminal board numbers as shown in (Fig. 29).
(4)
Ground both the indoor and outdoor units by attach­ing a ground wire.
(5)
Unit shall be grounded in compliance with the appli­cable local and national codes.
Always use a special branch circuit and install a special
(3)
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
(4)
matched to the capacity of the air conditioner. (Install in accordance with standard.)
The special branch circuit breaker is installed in the per-
(5)
manent wiring.
Always use a circuit that can trip all the poles of the wiring and has an isolation distance of at least 3mm between the contacts of each pole.
Perform wiring work in accordance with standards so
(6)
that the air conditioner can be operated safely and positively.
Install a leakage special branch circuit breaker in
(7)
accordance with the related laws and regulations and electric company standards.
CAUTION
When the voltage is low and the air conditioner is diffi­cult to start, contact the power company the voltage raised.
9
1. REMOTE CONTROLLER
Supply power to the crankcase heater 12 hours before the start
of operation in the winter. For test running, when the remote controller FAN CONTROL but-
ton and MASTER CONTROL button are pressed simultaneously for more than three seconds when the air conditioner is not run­ning, the air conditioner starts and TEST is displayed on the rem­ote controller display. However, the SET TEMP. setting button does not function, but all other buttons, displays, and protection functions operate. (Fig. 38)
Fig. 38
TEST RUNNING
10
Fig. 40
60 TYPE
(mmAq)
EXTERNAL STATIC PRESSURE
STATIC PRESSURE
CHARACTERISTIC
FAN PERFORMANCE AND AIR FLOW
EXTERNAL STATIC PRESSURE
RECOMMENDED RANGE
444 500 556 611 667 722 778 833 889 944 1000 1056 1111
30
HIGH
20
LOW
10
0
1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000
AIR FLOW
(L/Sec)
(m3/H)
(Pa)
294
196
98
0
Rectangular flange dimensions
40
295
1,063
Unit : (mm)
OPTIONAL PARTS
When connecting the square duct and round duct, use the optional square flange or round flange and flexible duct.
Fig. 43
Outlet chamber
Model name : UTD-BC200 (P/N 9085835002)
PART NO. 9362590013
Loading...