SPLIT TYPE AIR CONDITIONER
Duct Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9362590013)
For authorized service personnel only.
WARNING
(1) For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.
(2) Installation work must be performed in accordance with national wiring standards by authorized personnel only.
(3) Do not turn on the power until all installation work is complete.
•
Be careful not to scratch the air conditioner when handling it.
•
After installation, explain correct operation to the customer, using the operating manual.
•
Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved.
•
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation cannot be
guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as requred.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Installation
template
Special nut A
(large flange)
Special nut B
(small flange)
Coupler heat
insulation
(large)
Coupler heat
insulation
(small)
Nylon fastener For fixing the drain hose
Remote
controller
Remote
controller
cord clamp
Tapping screw
(flush heads)
Auxiliary pipe
assembly
Drain hose
insulation
Drain pipe
insulation
OUTDOOR UNIT ACCESSORIES
Power cap
For positioning the indoor
unit
1
For suspending the indoor
unit from ceiling
4
4
For indoor side pipe joint
(large pipe)
2
For indoor side pipe joint
(small pipe)
1
1
1
For installing the remote
controller cord
10
For installing the remote
controller cord clamp
10
For wiring conduit
(gas side) connection
1
Insulates the drain pipe
and drain hose connection
1
For insulating the drain
pipe
1
For power supply cord
installation
1
SELECTING THE MOUNTING POSITION
Decide the mounting position together with the customer as follows:
INDOOR UNIT
(1)
Install the indoor unit on a place having a sufficient strength so that
it withstand against the weight of the indoor unit.
(2)
The inlet and outlet parts should not be obstructed; the air should
be able to blow all over the room.
(3)
Leave the space required to service the air conditioner (Fig. 1).
Fig. 1
Strong and durable ceiling
INDOOR UNIT
Left
side
150 mm
or more
Install the unit where the drain pipe can be easily installed.
(4)
Providing as much space as possible between the indoor unit and
(5)
the ceiling will make work much easier.
OUTDOOR UNIT
Install the unit where it will not be tilted by more than 5°.
(1)
When installing the outdoor unit where it may
(2)
exposed to strong wind, fasten it securely.
Leave the space indicated for good air flow. (Fig. 2)
(1)
Fig. 2
(2)
If possible, do not install the unit where it will exposed to direct sunlight. (If necessary, install a blind that does not interfere with the air
flow.)
(3)
Do not install the unit near a source of heat, steam, of flammable
gas.
(4)
During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (Reverse cycle model only)
(5)
Do not install the unit where a strong wind blows or where it is very
dusty.
(6)
Do not install the unit where people pass.
(7)
Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible.
(8)
Install the unit when connection to the indoor unit is easy.
100 mm
or more
AIR FLOW
500 mm
or more
WARNING
300 mm
or more
600 mm
or more
Right
side
10 mm
or more
INSTALLATION PROCEDURE
Install the air conditioner as follows:
1
INDOOR UNIT INSTALLATION
1. PIPING CONNECTION DIRECTION AND
PREPARATION
Select piping directions.(Fig. 3)
•
Fig. 3
To top
Auxiliary pipe assembly
To rear
To side
To bottom
When bending the piping is difficult, use the auxiliary pipe assembly.
•
2. DRILLING HOLES FOR BOLTS AND
INSTALLING THE BOLTS
•
Using the installation template, drill holes for bolts (four holes).
(Fig. 4)
Fig. 4
Installation
template
3. INSTALLING THE HANGERS
Installation method
Fasten the hanging bolts to the ceiling and install special nuts A and B.
•
Fig. 5
Install the hangers to the unit.
•
Fig. 6
Air
Right side
Hang the unit.
•
Pass the hanging bolts through the hangers. (Four places)
Fig. 7
Hanger bolt
Hanger
Hanger
Drilling position
for bolts
Hanging bolt
Special nut A
Special nut B
Unit
4. LEVELING
Base horizontal direction leveling on top of the unit.
Fig. 9
B
Ceiling
Level
CAUTION
The side of the unit that holds the drain port (A) should be
slightly lower than the opposite side of the unit (B). The
slant should allow from 0 to 20 mm of difference between
(A) and (B).
Base vertical direction leveling on the unit (right and left).
Fig. 10
Air
Level
5. SERVICE HOLE DIMENSIONS
Open a service hole with the dimensions shown below.
Fig. 11
Unit
100 mm
or more
Service hole
500 mm
or more
2
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
(1)
When the outdoor unit will be exposed to strong wind, fasten it with
bolts or wire at the four places indicated by the arrows. (Fig. 12)
(2)
Since the drain water flows out of the outdoor unit during heating
operation, install the drain pipe and connect it to an commercial
16 mm hose. (When heating when the outdoor temperature is 0°C
or less, construct so that the drain water drained from the outdoor
unit will not freeze in the drain pipe.) (Reverse cycle model only)
(3)
When installing the drain pipe, plug all the holes other than the
drain pipe mounting hole in the bottom of the outdoor unit with putty so there is no water leakage. (Fig. 12) (Reverse cycle model only)
Fig. 12
Drain cap
Drain pipe or
drain cap
Always use a drain pipe at two places.
(4)
2. OUTDOOR UNIT CONNECTION CORD AND PIPE
CONNECTION PREPARATIONS
(1)
Piping and connection cord mounting direction (4-way mounting
possible).
Fig. 13
Plug the holes.
A
Control box
Open the piping and connection cord knockout holes of the desired
(3)
direction with nippers, etc. After opening the knockout holes, install
the accessory edge cover and power cap to protect the opened places.
Fig. 15
Connect the piping and power supply cord from the mounting
(4)
holes.
When pipe bending work is
*
difficult inside the outdoor
unit, use the accessory
auxiliary pipe assembly.
3
Fig. 16
CONNECTING THE PIPING
1. FLARE PROCESSING
(1)
Cut the connection pipe with pipe cutters so that the pipe is not
deformed.
(2)
Holding the pipe downward so that cuttings cannot enter the pipe,
remove the burrs.
(3)
Remove the flare nut from the indoor unit pipe and outdoor unit
and assemble as shown in (Table 3) and insert the flare nut onto
the pipe, and flare with a flaring tool.
(4)
Check if the flared part “L” (Fig. 17) is spread uniformly and that
there are no cracks.
Table 3
Flare nut
L dimension
Small pipe (9.53 mm dia)
1.8 to 2.0 mm
Large pipe (19.05 mm dia)
2.6 to 3.0 mm
Small pipe
Large pipe
Fig. 17
Pipe
Small (width across flats 22 mm)
Large (width across flats 36 mm)
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 18
Do not bend the pipes in an angle less than 90°.
When the pipes are bent and stretched repeatedly, the material will be
hardened, causing the pipes no longer be sent or stretched. Be sure to
limit number of bending and stretchings to three times.
When bending the pipe, do not bend
it as is. The pipe will be collapsed. In
this case, cut the heat insulating pipe
with a sharp cutter as shown in Fig.
19, and bend it after exposing the
pipe. After bending the pipe as you
want, be sure to put the heat insulating pipe back on the pipe, and secure
it with tape.
Fig. 19
3. CONNECTION PIPES
Indoor unit side
Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the indoor
unit correctly. If the centering is improper, the flare nut
cannot be tightened smoothly. If the flare nut is forced to
turn, the threads will be damaged.
CAUTION
Be sure to connect the large pipe after connecting the
small pipe completely.
Outdoor unit side
(1)
Tighten the flare nut of the connection pipe at the outdoor unit
valve connector. The tightening method is the same as that as at
the indoor side.
(2)
Seal with the accessory putty so that water does not enter at the
top of the pipe insulation installed to the connection pipe (large
pipe and small pipe).
Fig. 22
Valve A
(small)
Putty
(Small pipe)
(Large pipe)
4.
CHECKING THE PIPE CONNECTIONS FOR GAS LEAKING
For both the indoor and outdoor unit sides, check the joints for gas
leaking by the use of a gas leakage detector without fail when the
pipes are connected.
Valve B
(large)
Flare nut
Connection pipe
5. HEAT INSULATION ON THE PIPE JOINTS
(INDOOR SIDE ONLY)
Stick coupler heat insulation (large and small) to the place where
•
connecting pipes.
When using auxiliary piping with large pipe, stick coupler heat insu-
•
lation (large) to the pipe at the two places shown below.
Fig. 23
Coupler heat insulation
(small) on the pipe
Rear
Small pipe
Coupler heat insulation
(large) on the pipe.
Large pipe
Cover this portion with heat
insulating material also without fail.
Heat insulating pipe
CAUTION
No gap should remain.
4
VACUUMING AND
ADDITIONAL CHARGE
VACUUM
1.
Vacuum inside the indoor unit and the piping to a pressure of 1.5 mmHg
(1)
abs or less from the charging valve with a vacuum pump.
After vacuuming inside the indoor unit and the piping, remove the cap
(2)
of the two valves.
Open the spindle(handle) of the two valves from the closed state. (Table 6)
(3)
Tighten the cap of the two valves to the specified torque.
(4)
Table 5
Tightening torque
Large valve Small valve
25 kgf
•
Spindle (TYPE A)
Handle (TYPE B)
Cap
TYPE A
150 to 200 kgf
Open valve stateValve
15 kgf
Table 6
cm (2.45 N
•
cm (1.47 N
•
•
m) or less
•
m) or less
cm (14.7 to 19.6 N
Closed valve state
•
m)
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 5 m (36/45 TYPE), 20 m (60
TYPE) is charged in the outdoor unit at the factory.
When the piping is longer than 5 m (36/45 TYPE), 20 m (60 TYPE) additional charging is necessary.
For the additional amount, see the table below.
Table 7
Additional
refrigerant
(Cooling model)
(Reverse cycle model)
Pipe length
36/45 TYPE
36/45 TYPE
60 TYPE 1200 g 1800 g 60 g/m
5 m 10 m 20 m 30 m 40 m 50 m g/m
None 175 g 525 g 875 g 1225 g 1575 g 35 g/m
None 200 g 600 g 1000 g 1400 g 1800 g 40 g/m
None 600 g
CAUTION
When charging the refrigerant, always use a measuring
(1)
cylinder.
Add refrigerant from the charging valve after the com-
(2)
pletion of the work.
5
INSTALLING DRAIN HOSE
NOTE : INSTALL THE DRAIN HOSE
Install the drain hose so that there is a trap. The position of the
••
installed drain hose should have a downward gradient of (1/50 to
1/100). Make sure that the drain hose is installed without rises.
Make the trap near to the indoor unit.
•
Use general hard polyvinyl chloride pipe (VP25) [outside diameter
•
38 mm] and connect it with adhesive (polyvinyl chloride) so that
there is no leakage.
When the hose is long, install supporters.
•
Do not perform air bleeding.
•
Always heat insulate the indoor side of the drain hose.
•
Fig. 25
1
= 100 mm (approx.)
Outlet air
flow
1
H
2
H
The outside diameter of the drain port is 38 mm. Use a suitable
••
drain hose.
Stick the large drain hose insulation at the drain hose installation
•
side. (Fig. 26-(1))
Fig. 26-(1)
Drain pipe
Drain hose
Fig. 26-(2)
As required.
••
Drain hose
insulation
Drain hose
Rise
1.5 to 2 m
Air bleeding
H
H
Unit
side
2
= 50~100 mm
Drain hose
insulation
0 mm
Supporter
Drain hose
Auxiliary pipe assembly
1
Edge cover
1
Tapping screw •
2
Binder
1
Putty
1
Coupler heat insulation
1
Pipe (drain)
2
Flexible tube
2
Cap (drain)
2
For wiring conduit
(gas side) connection
(May not be supplied,
depending on the model)
For wiring conduit installation hole edge protection
For cabinet A and
cabinet D mounting (1)
•
Spare (1)
For power supply cord
binding
For sealing
For outdoor side pipe joint
For outdoor unit drain
piping work (May not be
supplied, depending on
the model.)
CONNECTION PIPE REQUIREMENT
Table 1
Diameter
Small Large
9.53 mm 19.05 mm
•
Use 0.7 mm to 1.2 mm thick pipe.
•
Use pipe with water-resistant heat insulation.
Maximum
length
50 m 30 m
Maximum height
(between indoor
and outdoor)
ELECTRICAL REQUIREMENT
•
Electric wire size and fuse capacity:
Table 2
Power
supply
cord
2
(mm
)
Connection
cord
2
(mm
)
Fuse capacity (A)
•
Install all electrical works in accordance to local regulation.
Use H07RN-F or equivalent as the connection cord. (Europe area only)
•
Install the disconnect device with a contact gap of at least 3 mm
•
nearby the units. (Both indoor unit and outdoor unit)
MAX
MIN
MAX
MIN
3.5
2.5
2.5
1.0
20
CAUTION
Fasten the unit securely with special nuts A and B.
Hanging bolt installation diagram
Fig. 8
1,300 mm
1,250 mm
1,063 mm
800 mm
710 mm
1,063 mm
Control box
(2)
Remove outdoor unit cabinet A and cabinet D.
Fig. 14
After removing the screws, remove
*
cabinet A by pushing it down.
Centering the pipe against port on the indoor unit, turn the flare nut
with your hand.
CAUTION
Hold the torque wrench at its grip, keeping it in the right
angle with the pipe as shown in Fig. 21, in order to tighten
the flare nut correctly.
When the flare nut is tightened properly by your hand, use a torque
wrench to finally tighten it.
Fig. 20
Holding
spanner
Small pipe
Large pipe
Pipe
Torque wrench
Table 4 : Flare nut tightening torque
Tightening torque
310 to 350 kgf
800 to 1,000 kgf
Fig. 21
Unit
side
•
cm (30.4 to 34.3 N
•
cm (78.4 to 98 N
90°
•
m)
•
m)
Fig. 24
Valve A
(small)
Screwdriver
Charging valve
Valve A
(small)
Charging valve
TYPE B
* If the spindle (handle) is not fully open, performance will
drop and an abnormal sound will be generated.
[TYPE A]
Small pipe
Spindle
[TYPE B]
Small pipe
Handle
Large pipe
Valve B (large)
Cap
Valve B (large)
Large pipe
Cap
Gauge manifold
Vacuum pump
Service hose
6
Drain pipe insulation
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1)
Cut the wire and with a wire cutter or wire-cutting pliers,
then strip the insulation to about 15/16” (25 mm) of expose
the solid wire.
(2)
Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3)
Using pliers, bend the solid wire to form a loop suitable for
the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal board
and tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
Cut the wire and with a wire cutter or wire-cutting pliers,
(1)
then strip the insulation to about 3/8” (10 mm) of expose
the strand wiring.
Using a screwdriver, remove the terminal screw(s) on the
(2)
terminal board.
Using a round terminal fastener or pliers, securely clamp a
(3)
round terminal to each stripped wire end.
Position the round terminal wire, and replace and tighten
(4)
the terminal screw with a screwdriver.
- Continued on back -
Fig. 27
2. OUTDOOR UNIT SIDE
(1)
Remove outdoor unit cabinet A and connect the power supply
cord and the outdoor unit connection cord wired at the indoor
unit.
(2)
Fasten the power supply cord and connection cord with cable
clips and binders as shown in (Fig. 31).
Fig. 30
Cabinet A
8
REMOTE CONTROLLER
INSTALLATION
Insert the end of a flat blade screwdriver at the arrow parts of the
•
groove at the side of the remote controller case and remove the
remote controller case top by turning the screwdriver.
Disconnect the remote controller cord from the remote controller
•
terminal board.
Fig. 34
When EE: EE blinks at the current time display, there is an error
•
inside the air conditioner. If the ZONE CONTROL button and
ENERGY SAVE button are pressed simultaneously for more than
three seconds, the self diagnosis check will start and the error
contents will be displayed at the current time display. (Fig. 39)
When the operation lamp lights, press the START/STOP button
and after operation lamp goes off, perform the same operation.
(Fig. 39) Process the error contents by referring to (Table 8).
Fig. 39
45 TYPE
(mmAq)
EXTERNAL
STATIC
PRESSURE
•
Round flange dimensions
RECOMMENDED RANGE
444333278222167 500 556 611 667 722 833 889 944 1000
20
HIGH
LOW
(L/Sec)
294
196
Unit : (mm)
(Pa)30
1. INDOOR UNIT SIDE
Attaching and removing the control box cover.
(1)
Fig. 28
Control box
cover
Screw
Side view
Control box
Fig. 31
Terminal board
Cord clamp
Power supply cord
Remove the four screws and
slide cabinet A down.
Electric box
Power supply
cord
Earth
Connection cord
(indoor unit and outdoor
unit connection cord)
(1)
When remote controller exposed
1)
Make a notch in the thin part ( part of Fig. 34) at the remote controller case top and bottom with nippers, file, etc.
2)
Connect the remote controller cord to the remote controller
terminal board specified in (Fig. 35)
3)
Clamp the remote controller cord sheath with the binder
(small) as shown in Fig. 35.
4)
Cut off the excess binder.
5)
Clamp the remote controller cord to a wall, etc. with the remote controller cord clamp furnished. (Fig. 36)
Fig. 35
Remote controller cord
Binder (small)
Red
White
Black
Remote controller
terminal board
Error cord
E0:00
E1:00
E2:00
E3:00
E4:00
E5:00
E6:00
E7:00
EA:00
Eb:00
EC:00
Ed:00
EF:00
Stop operation
Table 8
Error contents
Communication error
(indoor unit remote controller)
Communication error
(indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor shorted
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor
shorted
Outdoor heat exchanger temperature sensor
open
Outdoor heat exchanger temperature sensor
shorted
Outdoor temperature sensor open
Outdoor temperature sensor shorted
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shorted
Discharge pipe temperature abnormal
11
10
0
1600140012001000800600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600
AIR FLOW (m
36 TYPE
(mmAq)
EXTERNAL
STATIC
PRESSURE
RECOMMENDED RANGE
444389278222167 500 556 611 667 722 778 833 889
20
10
0
1600140012001000800600 1800 2000 2200 2400 2600 2800 3000 3200
HIGH
LOW
AIR FLOW (m
(L/Sec)
APPEARANCE OF OUTDOOR UNIT
98
Flexible duct
Model name : UTD-RD202
(P/N 9074165004)
0
3
/H)
ø200 mm L 2 m
(Pa)30
294
196
98
0
3
/H)
12
Connection cord and remote controller cord connections.
(2)
Clamp the connection cord with the cord clamp and the remote
•
controller cord with the nylon clamp. (Fig. 29)
Fig. 29
1
Remote
controller
cord
Nylon clamp
23
RED
WHITE BLACK
REMOTE
CONTROL UNIT
RED
WHITE
G
Earth
BLACK
(N)
2
1
OUTDOOR
UNIT
Cord clamp
3
Hi Me Lo
FAN MOTOR
Connection cord
Hi Me Lo
FAN MOTOR
Fan motor cord
(Already
connected)
Fig. 32
•
Fig. 33
Coupler holder
7
After passing the connection
cord through the insulation
tube, fasten it with the cord
clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
Cable clip
Binder
Compressor
Power supply cord and connection cord
(indoor unit and outdoor unit
connection cord)
Outdoor unit
100 mm or less
Cabinet D
POWER
WARNING
The rated voltage of this product is 3ø 4W 380-415V
(1)
50Hz.
Before turning on verify that the voltage is within the
(2)
342 to 457V range.
Fig. 36
Remote controller cord
Tapping screw (flush heads)
(2)
When remote controller cord embedded
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the remote
Remote controller
cord clamp
controller case bottom and install the cord to the box. (Fig. 37)
3)
Connect the remote controller cord to the remote controller
terminal board specified in (Fig. 35).
Fig. 37 [Example]
Remote controller
case top
Remote
controller
cord
Remote controller case bottom
After wiring work is complete, return the remote controller case
•
top to its original state.
CAUTION
Do not bundle the remote controller cord, or wire
(1)
the remote controller cord in parallel, with the
indoor unit connection wire (to the outdoor unit)
and the power supply cord. It may cause erroneous
operation.
When installing the remote controller and cord near
(2)
a source of electromagnetic waves, separate the remote controller from the source of the electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and PC
(3)
board parts directly with your hands.
•
To stop test running, press the START/STOP button.
•
For the operation method, refer to the operating manual and perform operation check.
•
Check that there are no abnormal sounds or vibration sounds during test running.
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may
switch to low speed, or one of the fans may stop intermittently.
ERROR
The LED lamps operate as follows (Table 9) according to the error
contents.
The LED lamps are on the outdoor unit board.
Table 9
Error display Error contents
Lighting
continued
Single quick
flashes
repeated
Two quick
flashes
repeated
Three quick
flashes
repeated
Lighting
continued
LED
No. 1
Lamp
LED
No. 2
Lamp
ON
OFF
0.5 sec
ON
OFF
ON
OFF
ON
OFF
ON
OFF
5 sec
0.5 sec 0.5 sec
5 sec
0.5 sec 0.5 sec
5 sec
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as
long as the power is not turned off.
Discharge pipe
temperature
abnomal
Outdoor heat
exchanger temperature sensor
abnormal
Outdoor temperature sensor
abnormal
Discharge pipe
temperature
sensor abnormal
High pressure
abnormal
12
Fig. 41
60 TYPE
36/45 TYPE
CONNECTION FLANGE DIMENSIONS
(INTAKE AND OUTLET)
Fig. 42
Rectangular flange
Connection cord
Remote controller
cord
CAUTION
(1)
Tighten the indoor unit connection cord (to the outdoor unit) and power supply indoor and outdoor unit
terminal board connections firmly with the terminal
board screws. Faulty connection may cause a fire.
(2)
If the indoor unit connection cord (to the outdoor
unit) and power supply are wired incorrectly, the air
conditioner may be damaged.
(3)
Wire the indoor unit connection cord (to the outdoor
unit) by matching the numbers of the outdoor and
indoor units terminal board numbers as shown in
(Fig. 29).
(4)
Ground both the indoor and outdoor units by attaching a ground wire.
(5)
Unit shall be grounded in compliance with the applicable local and national codes.
Always use a special branch circuit and install a special
(3)
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
(4)
matched to the capacity of the air conditioner.
(Install in accordance with standard.)
The special branch circuit breaker is installed in the per-
(5)
manent wiring.
Always use a circuit that can trip all the
poles of the wiring and has an isolation distance of at
least 3mm between the contacts of each pole.
Perform wiring work in accordance with standards so
(6)
that the air conditioner can be operated safely and
positively.
Install a leakage special branch circuit breaker in
(7)
accordance with the related laws and regulations
and electric company standards.
CAUTION
When the voltage is low and the air conditioner is difficult to start, contact the power company the voltage
raised.
9
1. REMOTE CONTROLLER
Supply power to the crankcase heater 12 hours before the start
•
of operation in the winter.
For test running, when the remote controller FAN CONTROL but-
•
ton and MASTER CONTROL button are pressed simultaneously
for more than three seconds when the air conditioner is not running, the air conditioner starts and TEST is displayed on the remote controller display.
However, the SET TEMP. setting button does not function, but all
other buttons, displays, and protection functions operate. (Fig. 38)
Fig. 38
TEST RUNNING
10
Fig. 40
60 TYPE
(mmAq)
EXTERNAL
STATIC
PRESSURE
STATIC PRESSURE
CHARACTERISTIC
FAN PERFORMANCE AND AIR FLOW
EXTERNAL STATIC PRESSURE
RECOMMENDED RANGE
444 500 556 611 667 722 778 833 889 944 1000 1056 1111
30
HIGH
20
LOW
10
0
1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600 3800 4000
AIR FLOW
(L/Sec)
(m3/H)
(Pa)
294
196
98
0
•
Rectangular flange dimensions
40
295
1,063
Unit : (mm)
OPTIONAL PARTS
When connecting the square duct and round duct, use the optional
square flange or round flange and flexible duct.
Fig. 43
Outlet chamber
Model name : UTD-BC200
(P/N 9085835002)
PART NO. 9362590013