General ARG60AH, ARG60AUAK, AOG60APAGT, ARG60RH, ARG60RUAK Technical Manual [ru]

...
Page 1
R22
5 . DUCT TYPE AR (60)
D2D007E/01
2005.04.22
Page 2
MODEL : AR60
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 01) -
Page 3
5-2. REMOTE CONTROLLER
5-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in one unit.
Wired
remote
controller
Built-in timers
Weekly
timer
Setback timerWeekly timer
Setback
timer
Possible to set ON/OFF time to operate twice each day of the week.
DUCT TYPE
AR60
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
DUCT TYPE
AR60
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is
Timer area
Operation area
needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
- (05 - 02) -
European switch box
JIS box
Page 4
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2 6
7 8 9
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETE SET
12 15 18 21
DAY
DAY OFF
SA
14
1 3
ENERGY
SAVE
THERMO SENSOR
4
5
2
Set Temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
10
11
12
13
6
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
7
Day (DAY OFF) button
Temporarily cancels of one day timer.
8
Display panel
15
SUMOTUWETH FR
DUCT TYPE
AR60
369
SA
12 15 18 21
16
1718 19
2021 2223
Set back button
pressed select the set back timer.
9
Set time button
Pessed to select the set back timer.
10
Delete button
The schedule of a weekly timer is deleted.
11
Set button
Sets the date, hour, minute and on-off time.
12
Horizontal air flow direction and swing button
Push for two seconds to change the swing mode.
DUCT TYPE
AR60
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT g 160
ACCESSORY 10m cable
13
Vertical air flow direction and swing button
Push for two seconds to change the swing mode
14
Operation lamp
Lights during operation and when the timer is on.
15
Timer and clock display
16
Operation mode display
17
Fan speed display
18
Central control display
19
Temperature display
20
Stand by display Indicates during the oil recovery and defrosting operation.
21
Vertical swing display
22
Horizontal swing display
23
Energy save display
- (05 - 03) -
Page 5
COOLING TYPE HEAT PUMP TYPE
AR*60AUAK AR*60RUAK
AO*60APAGT AO*60RPAGT
kW
BTU/h
kW - 17.8 - 18.2
BTU/h - 60700 - 62100
COOLING RATED 5.8 - 5.9 5.9 - 6.0
HEATING RATED - 5.05 - 5.25
COOLING RATED 9.8 - 9.8 9.8 - 9.8
HEATING RATED - 8.7 - 8.7
A
COOLING 2.83 - 2.88 2.78 - 2.83
HEATING - 3.52 - 3.47
l/h (pints/h)
High
Med
Low
Pa
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High
Med
Low
58.5 / - 58 / 59
Rows x Stages x Fin Pitch
mm
Coil Dimensions mm
- Corrosion resistant coating
Rows x Stages x Fin Pitch
mm 2 x 52 x 1.8 2 x 26 x 1.5
Coil Dimensions mm
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR 55 / 136 55 / 144
LIQUID
GAS
m
m
CHARGE kg 3.8 4.8
COOLING
HEATING
WIRED (AR-3TA2) WIRED (AR-3TA1)
mm
Simple remote controller
(UTB-YRB/UTB-GRB)
Simple remote controller
(UTB-YPB/UTB-GPB)
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 100 Pa. Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit) dimensions( )* are indicated the including flange,control box,safety drain pan.
460 x 1230 x 640
355.6x890x76.2
Plate fin coil
Fan motor thermal protector,Fuse
Plate fin coil
42 / 42
5040
400 x 1050(1150)* x 500(585)*
1355 x 940 x 370
660x975x38.1
Three Phase
Fan motor thermal protector,Fuse
Hydrophilic coating
4 x 14 x 1.80
540
63
49 / 49
45 / 45
100 to 250
Sirocco fan
Propeller fan
A
3600
3100
2600
5900
Coil
HEAT EXCHANGER TYPE
INDOOR
COP
Surface treatment
W/W
OUTDOOR
Coil
Surface treatment
0 to 43
R22
REMOTE CONTROLLER
TYPE
REFRIGERANT OIL
OPERATION(OUTDOOR)
°C
REFRIGERANT TYPE
-10 to 24
380 - 415V 50Hz
RATED
50 (chargeless:7.5m)
SCROLL
Hot-dipped galvanized steel sheet
Beige (10YR7.5/1.0NN)
RECOMMENDED STATIC PRESSURE @ high
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
OUTDOOR
AIR CIRCULATION
MODEL NAME
DUCTED MODELS
INDOOR
OUTDOOR
TYPE POWER SOURCE
DIMENSIONS H ×W ×D
INDOOR
OUTPUT
TYPE
OUTDOOR
COOLING
HEATING
CAPACITY COMPRESSOR
OPTIONS
FAN TYPE x Q'ty
FAN MOTOR OUTPUT
W
WEIGHT
NET
GROSS MAX HEIGHT
MAX LENGTH
RATED
INPUT POWER STARTING METHOD
m3/h
INDOOR
kW
CURRENT
dB(A)
STARTING CURRENT
MOISTURE REMOVAL
SAFETY DEVICES
NET / GROSS
CONNECTION METHOD
Synthetic (POE oil)
30
9.53(3/8 inc.)
19.05(6/8 inc.)
FLARE
CASING COLOR
mm
kg(lbs)
PIPE
SIZE
1485 x 1000 x 450
50 / 121
mm
Remote Sensor (UTD-RS100F/UTD-RS100G)
Long Life Filter (UTD-LF60K/UTB-LF60KA)
Wire Set (UTD-ECS5A)
-
OUTDOOR
INDOOR
DRAIN PIPE MATERIAL
Steel
SIZE
Outer diameter 25.4mm / Inner diameter 23.4mm
16.4 - 17.0
56000 - 58000
74
6.50
5-3. SPECIFICATIONS
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 04) -
Page 6
5-4. DIMENSIONS
5-4-1. OUTDOOR UNIT
MODEL : AO60
(Unit : mm)
370
1,355
23
425
DUCT TYPE
AR60
400
650 940
DUCT TYPE
AR60
- (05 - 05) -
Page 7
5-4-2. INDOOR UNIT
MODELS : AR60
(Unit : mm)
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 06) -
Page 8
MOUNTING POSITION
395 mm
155 mm
585 mm
500 mm
1,050 mm
1,000 mm
AIR
1,080 mm
85 mm
AIR
AIR
325 mm
14 mm
DUCT TYPE
AR60
27 mm
14 mm
26 mm
295 mm
865 mm
Intake port flange
Outlet port flange
850 mm
DUCT TYPE
AR60
- (05 - 07) -
Page 9
5-5. REFRIGERANT CIRCUIT
COOLING ONLY TYPE
MODELS : AR*60AUAK / AO*60APAGT
OUTDOOR UNIT INDOOR UNIT
MUFFLER
COMPRESSOR
CONDENSER
DRYER
ACCUMULATOR
Charging valve
CAPILLARY TUBE
Charging valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATOR
Refrigerant pipe
9.52mm(3/8")
DUCT TYPE
AR60
HEAT PUMP TYPE
DUCT TYPE
AR60
MODELS : AR*60RUAK / AO*60RPAGT
OUTDOOR UNIT INDOOR UNIT
HIGH PRESSURE SWITCH
4-Way Valve
MUFFLER
ACCUMULATOR
COMPRESSOR
Charging valve
Refrigerant pipe
19.05mm(3/4")
EVAPORATORCONDENSER
: Cooling : Heating
DRYER
STRAINER
EXPANSION VALVE
Charging valve
Refrigerant pipe
9.52mm(3/8")
- (05 - 08) -
Page 10
5-6. WIRING DIAGRAMS
5-6-1. OUTDOOR UNIT
MODEL : AO60A
DUCT TYPE
AR60
DUCT TYPE
AR60
MODEL : AO60R
- (05 - 09) -
Page 11
5-6-2. INDOOR UNIT
MODEL : AR60A
DUCT TYPE
AR60
DUCT TYPE
AR60
MODEL : AR60R
- (05 - 10) -
Page 12
AFR 58.3
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 18.48 1.19 3.58 19.18 3.40 3.63 20.65 3.73 3.75 21.30 2.44 3.82 22.45 1.17 3.93 22.99 0.40 3.97 23.39 3.17 3.99
5 17.58 1.87 3.99 18.24 4.15 4.04 19.64 4.62 4.16 20.38 2.86 4.23 21.49 1.14 4.40 22.14 0.58 4.46 22.66 3.49 4.50
10 16.68 2.57 4.42 17.30 4.92 4.47 18.65 5.51 4.60 19.33 3.86 4.67 20.50 1.78 4.87 21.07 1.23 4.96 21.67 4.25 5.01
15 15.74 3.31 4.86 16.34 5.72 4.92 17.60 6.49 5.05 17.29 3.92 5.12 19.42 2.92 5.35 19.96 2.33 5.47 20.56 5.43 5.53
20 14.79 4.07 5.30 15.34 6.57 5.37 16.54 7.48 5.51 17.17 5.97 5.59 18.26 4.32 5.86 18.81 3.72 5.98 19.38 6.83 6.05
25 15.91 3.17 4.79 16.60 5.50 4.82 18.03 6.09 4.89 18.79 4.39 4.93 19.93 2.92 5.12 20.59 2.43 5.17 21.09 5.36 5.20
30 14.93 3.96 5.25 15.57 6.37 5.29 16.95 7.10 5.37 17.66 5.49 5.41 18.80 4.12 5.64 19.45 3.58 5.69 19.97 6.56 5.73
35 13.90 4.81 5.72 12.63 5.44 5.76 15.83 8.17 5.85 16.50 6.94 5.93 17.57 5.59 6.17 18.22 5.07 6.23 18.72 8.07 6.27
40 12.75 5.77 6.19 13.37 8.30 6.24 14.66 9.33 6.34 15.20 8.60 6.48 16.35 7.34 6.70 16.92 6.80 6.76 17.34 9.79 6.81
43 12.01 6.41 6.47 14.50 10.83 6.52 13.84 10.37 6.68 14.39 9.71 6.82 15.56 8.51 7.02 16.07 7.91 7.08 16.48 10.88 7.13
21 °CDB
15 °CWB
26 °CDB
27 °CDB
16 °CWB
23 °CDB
Indoor temperature
30 °CDB
29 °CDB
32 °CDB
23 °CWB
18 °CWB
19 °CWB
22 °CWB
21 °CWB
Outdoor temperature
5-7. CAPACITY TABLE COOLING
AFR 58.3
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 16.59 3.18 4.57 16.92 5.65 4.60 17.51 6.92 4.65 17.81 5.75 4.67 18.35 3.49 4.70 18.60 2.37 4.70 18.88 4.68 4.72
5 14.78 4.47 4.80 15.01 7.09 4.82 15.43 8.70 4.86 15.70 7.66 4.89 16.03 5.79 4.88 16.27 4.79 4.89 16.40 7.37 4.87
10 14.31 4.81 5.33 14.62 7.40 5.38 15.08 9.01 5.46 15.26 8.07 5.48 15.67 6.16 5.52 15.85 5.40 5.54 15.95 7.86 5.52
15 15.71 3.80 4.92 16.04 6.31 4.94 16.73 7.58 4.98 17.16 6.34 5.02 17.70 4.12 5.03 18.10 2.88 5.05 18.30 5.30 5.05
20 15.26 4.10 5.45 15.61 6.63 5.48 16.31 7.94 5.55 16.66 6.79 5.58 17.28 4.54 5.63 17.60 3.40 5.65 17.90 5.74 5.67
25 16.75 3.16 5.08 17.24 5.57 5.10 19.59 8.13 5.13 18.72 5.43 5.15 19.71 2.83 5.17 20.22 1.68 5.18 20.69 3.88 5.18
30 15.93 4.15 5.62 16.38 6.67 5.65 17.32 7.97 5.70 17.80 6.81 5.73 18.73 4.51 5.77 19.19 3.39 5.79 20.98 7.19 5.81
35 14.86 4.41 6.54 15.28 6.88 5.96 16.11 8.12 0.67 16.50 6.94 6.06 17.32 4.80 6.13 17.69 3.71 6.14 18.05 6.11 6.17
40 13.75 5.23 6.35 14.12 7.79 6.40 14.84 9.22 6.49 15.20 8.13 6.53 15.85 6.05 6.60 16.18 5.12 6.63 16.47 7.64 6.67
43 12.48 6.19 5.92 12.89 8.78 6.59 13.68 10.25 6.04 14.06 9.19 6.70 14.54 7.31 6.77 14.77 6.38 6.80 14.98 8.93 6.83
23 °CDB
26 °CDB
27 °CDB
29 °CDB
32 °CDB
23 °CWB
Indoor temperature
22 °CWB
16 °CWB
18 °CWB
19 °CWB
21 °CWB
30 °CDB
21 °CDB
Outdoor temperature
15 °CWB
5-7-1. COOLING
MODEL : AR*60AUAK/AO*60APAGT
MODEL : AR*60RUAK/AO*60RPAGT
COOLING CAPACITY
DUCT TYPE
AR60
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
DUCT TYPE
AR60
- (05 - 11) -
Page 13
5-7-2. HEATING
58.3
( °CDB)
( °CWB)
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-10 -11 13.43 4.84 13.23 4.88 13.02 4.92 12.67 4.99 12.41 5.05 12.10 5.11 11.45 5.21
-4 -6 15.29 5.08 15.06 5.12 14.82 5.17 14.42 5.25 14.10 5.31 13.73 5.38 12.96 5.49
1 -1 17.41 5.21 17.11 5.27 16.79 5.33 16.21 5.43 15.73 5.50 15.17 5.59 13.98 5.73
5 3 19.04 5.27 18.65 5.34 18.20 5.41 17.40 5.54 16.70 5.63 15.83 5.73 14.35 5.87
7 6 20.30 5.36 19.97 5.45 19.50 5.54 18.53 5.67 17.72 5.76 16.76 5.86 15.23 6.00
12 10 21.86 5.44 21.49 5.56 21.06 5.68 20.02 5.83 19.06 5.93 17.97 6.02 16.34 6.16
15 13 21.44 5.38 21.09 5.50 20.57 5.60 19.40 5.75 18.44 5.86 17.43 5.96 15.77 6.08
20 15 22.15 5.42 21.76 5.54 21.31 5.66 20.04 5.81 19.04 5.92 17.99 6.01 16.13 6.12
24 18 23.11 5.45 22.64 5.59 22.12 5.72 20.99 5.89 19.92 5.98 18.81 6.07 16.66 6.14
16 °CDB
18 °CDB
20 °CDB
AFR
Indoor temperature
27 °CDB
30 °CDB
25 °CDB
23 °CDB
Outdoor temperature
MODEL : AR*60RUAK/AO*60RPAGT
HEATING CAPACITY
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 12) -
Page 14
5-8.
5 7.5 10 20 30 40 50
20 - - - - 0.857 0.823 0.788
15 - - - 0.892 0.857 0.823 0.788
10 - - 0.964 0.892 0.857 0.823 0.788
7.5 - 1.000 0.964 0.892 0.857 0.823 0.788
5 0.997 1.000 0.964 0.892 0.857 0.823 0.788
0 0.997 1.000 0.964 0.892 0.857 0.823 0.788
-5 0.989 0.992 0.956 0.885 0.851 0.816 0.781
-7.5 - 0.988 0.953 0.882 0.847 0.813 0.778
-10 - - 0.949 0.878 0.844 0.809 0.775
-15 - - - 0.871 0.837 0.803 0.769
-20 - - - - 0.830 0.796 0.763
Outdoor unit is
up-side
Outdoor unit is
bottom-side
COOLING
HEIGHT DIFFERENCE (m)
PIPE LENGTH (m)
5 7.5 10 20 30 40 50
20 - - - - 0.898 0.874 0.849
15 - - - 0.928 0.903 0.878 0.854
10 - - 0.979 0.932 0.908 0.883 0.858
7.5 - 0.993 0.982 0.935 0.910 0.885 0.860
5 1.005 0.995 0.984 0.937 0.912 0.887 0.862
0 1.010 1.000 0.989 0.942 0.917 0.892 0.867
-5 1.010 1.000 0.989 0.942 0.917 0.892 0.867
-7.5 - 1.000 0.989 0.942 0.917 0.892 0.867
-10 - - 0.989 0.942 0.917 0.892 0.867
-15 - - - 0.942 0.917 0.892 0.867
-20 - - - - 0.917 0.892 0.867
PIPE LENGTH (m)
HEATING
Outdoor unit is
bottom-side
Outdoor unit is
up-side
HEIGHT DIFFERENCE (m)
CAPACITY COMPENSATION FOR PIPE LENGTH
AND HEIGHT DIFFERENCE
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
COOLING
1.100
1.050
1.000
0.950
0.900
0.850
0.800
0.750
Coefficient of compensation
0.700
0 10 20 30 40 50
Pipe length (m)
1.200
1.150
1.100
1.050
1.000
0.950
0.900
0.850
Coefficient of compensation
0.800
0 10 20 30 40 50
HEATING
Pipe length (m)
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 13) -
Page 15
5-9. ADDITIONAL CHARGE CALCULATION
COOLING TYPE HEAT PUMP TYPE
AR*60AUAK AR*60RUAK
AO*60APAGT AO*60RPAGT
m 7.5 7.5
3800 4800 3800+100 4800 3800+500 4800 3800+900 4800+600
3800+1300 4800+1200 3800+1700 4800+1800
40 60
ADITIONAL charge
g/m
TYPE
DUCTED MODEL
MODEL NAME INDOOR
OUTDOOR
PRECHARGE REFREGERANT TYPE
R22
PIPE LENGTH
AMOUNT
20m
50m (max)
g
30m
40m
10m
REFRIGERANT CHARGE
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 14) -
Page 16
5-10. OPERATION RANGE
Model Name
Operation Range
Indoor unit Outdoor unit Mode Indoor unit Outdoor unit
AR*60AUAK
AOY60FMAYT
AOG60FMAYT
Cooling
Dry
Heating
18 to 32 °C 0 to 43 °C
- -
COOLING, DRY
40
30
20
10
Indoor temperature(°CDB)
0
-10 0 10 20 30 40 50 60
Outdoor temperature(°CDB)
DUCT TYPE
AR60
DUCT TYPE
AR60
HEATING
40
30
20
10
Indoor temperature(°CDB)
0
-10 0 10 20 30 40 50 60
Outdoor temperature(°CDB)
- (05 - 15) -
Page 17
Model Name
Operation Range
Indoor unit Outdoor unit Mode Indoor unit Outdoor unit
Cooling
AO*60RPAGTAR*60RUAK
Dry
Heating
18 to 32 °C 0 to 43 °C
10 to 30 °C -10 to 24 °C
COOLING, DRY
40
30
20
10
Indoor temperature(°CDB)
0
-10 0 10 20 30 40 50 60
Outdoor temperature(°CDB)
DUCT TYPE
AR60
DUCT TYPE
AR60
HEATING
40
30
20
10
Indoor temperature(°CDB)
0
-10 0 10 20 30 40 50 60
Outdoor temperature(°CDB)
- (05 - 16) -
Page 18
5-11. FAN PERFORMANCE CURVE
400V
Static pressure (Pa)
FAN SPEED
Hi
Med
Low
5-11-1. NORMAL MODE
MODEL : AR*60AUAK
400V
50 75 100 125 150 175 200 225 250
m3/h - - 3500 3315 3142 2932 2637 2339 2020.3
l/s - - 972 921 873 814 733 650 561
CFM - - 2060 1951 1849 1726 1552 1377 1189
m3/h - 3000 2892 2727 2541 2336 2116 1883 -
l/s - 833 803 758 706 649 588 523 -
CFM - 1766 1702 1605 1495 1375 1245 1108 -
m3/h 2460 2494 2418 2319 2199 2057 - - -
l/s 683 693 672 644 611 571 - - -
CFM 1448 1468 1423 1365 1294 1211 - - -
Q-h Characteris tic curve
300
250
Hi
Med
Low
200
150
DUCT TYPE
AR60
100
50
0
1,500 2,000 2,500 3,000 3,500 4,000
AIR FLOW (m3/h)
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0
1,500 2,000 2,500 3,000 3,500 4,000
Air temp
Capacity
COOLING
15.5
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
DUCT TYPE
AR60
°C)
Air tempreture(
AIR FLOW (m3/h)
- (05 - 17) -
Page 19
MODEL : AR*60AUAK
400V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
415V
54 78 100 125 150 175 200 227 250
m3/h - - 3564 3390 3193 2971 2689 2444 2092.4
l/s - - 990 942 887 825 747 679 581
CFM - - 2098 1995 1879 1748 1582 1439 1232
m3/h - 3179 3027 2850 2660 2448 2208 1956 -
l/s - 883 841 792 739 680 613 543 -
CFM - 1871 1781 1677 1565 1441 1300 1151 -
m3/h 2630 2525 2415 2274 2113 1929 - - -
l/s 731 701 671 632 587 536 - - -
CFM 1548 1486 1422 1339 1244 1136 - - -
Q-h Characteris tic curve
300
250
200
Hi
Med
Low
150
100
50
DUCT TYPE
AR60
0
1,500 2,000 2,500 3,000 3,500 4,000
AIR FLOW (m3/h)
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0
1,500 2,000 2,500 3,000 3,500 4,000
Air temp
Capacity
COOLING
15.5
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
DUCT TYPE
AR60
°C)
Air tempreture(
AIR FLOW (m3/h)
- (05 - 18) -
Page 20
MODEL : AR*60RUAK
415V
Static pressure (Pa)
FAN SPEED
Hi
Med
Low
400V
50 75 100 125 150 175 200 225 250
m3/h - - 3500 3315 3142 2932 2637 2339 2020.3
l/s - - 972 921 873 814 733 650 561
CFM - - 2060 1951 1849 1726 1552 1377 1189
m3/h - 3000 2892 2727 2541 2336 2116 1883 -
l/s - 833 803 758 706 649 588 523 -
CFM - 1766 1702 1605 1495 1375 1245 1108 -
m3/h 2460 2494 2418 2319 2199 2057 - - -
l/s 683 693 672 644 611 571 - - -
CFM 1448 1468 1423 1365 1294 1211 - - -
300
250
200
Q-h Characteris tic curve
Hi
Med
Low
150
100
50
DUCT TYPE
AR60
0
1,500 2,000 2,500 3,000 3,500 4,000
AIR FLOW (m3/h)
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0
1,500 2,000 2,500 3,000 3,500 4,000
COOLING
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
DUCT TYPE
AR60
°C)
Air tempreture(
AIR FLOW (m3/h)
HEATING
104.0
102.0
100.0
98.0
96.0
94.0
92.0
90.0
88.0
86.0
Heating capacity(%)
84.0
82.0
80.0 1,500 2,000 2,500 3,000 3,500 4,000
44.0
43.0
42.0
41.0
40.0
39.0
38.0
37.0
36.0
°C)
Air tempreture(
AIR FLOW (m3/h)
- (05 - 19) -
Page 21
MODEL : AR*60RUAK
Static pressure (Pa)
415V
FAN SPEED
Hi
Med
Low
415V
54 78 100 125 150 175 200 227 250
m3/h - - 3564 3390 3193 2971 2689 2444 2092.4
l/s - - 990 942 887 825 747 679 581
CFM - - 2098 1995 1879 1748 1582 1439 1232
m3/h - 3179 3027 2850 2660 2448 2208 1956 -
l/s - 883 841 792 739 680 613 543 -
CFM - 1871 1781 1677 1565 1441 1300 1151 -
m3/h 2630 2525 2415 2274 2113 1929 - - -
l/s 731 701 671 632 587 536 - - -
CFM 1548 1486 1422 1339 1244 1136 - - -
300
250
Q-h Characteris tic curve
200
150
100
50
DUCT TYPE
AR60
0
1,500 2,000 2,500 3,000 3,500 4,000
AIR FLOW (m3/h)
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Cooling capacity(%) STATIC PRESSURE(Pa)
88.0
86.0 1,500 2,000 2,500 3,000 3,500 4,000
COOLING
15.0
14.5
14.0
13.5
13.0
12.5
12.0
11.5
11.0
°C)
Air tempreture(
DUCT TYPE
AR60
AIR FLOW (m3/h)
HEATING
104.0
102.0
100.0
98.0
96.0
94.0
92.0
90.0
88.0
86.0
Heating capacity(%)
84.0
82.0
80.0 1,500 2,000 2,500 3,000 3,500 4,000
44.0
43.0
42.0
41.0
40.0
39.0
38.0
37.0
36.0
°C)
Air tempreture(
AIR FLOW (m3/h)
- (05 - 20) -
Page 22
5-12. NOISE LEVEL CURVE
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
NC-20
NC-40
NC-50
NC-60
NC-30
NC-15
NC-25
NC-35
NC-45
NC-55
NC-65
HIGH
LOW
5-12-1. OUTDOOR UNIT
MODELS : AO*60APAGT, AO*60RPAGT
Condition Fan speed : High Operation mode: FAN Voltage : 415V /50Hz Static pressure : 100Pa
COOLING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
HEATING
80
70
60
50
40
30
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
DUCT TYPE
AR60
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
5-12-2. INDOOR UNIT
MODELS : AR*60AUAK, AR*60RUAK
80
70
60
50
40
30
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
DUCT TYPE
AR60
20
Octave band sound pressure level, dB:(0dB=0.0002µbar)
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency,Hz
- (05 - 21) -
Page 23
SOUND LEVEL CHECK POINT
OUTDOOR UNIT
INDOOR UNIT (DUCT TYPE)
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 22) -
Page 24
5-13. ELECTRIC CHARACTERISTICS
AR 60AUAK
AR 60RUAK
AO 60APAGT
AO 60RPAGT
Mode
Rated Value Power Supply
Model Name
5050415
415
Full Load Charcteristics
202033334.0
4.0
* Wiring Spec Outdoor Fan Motor
0.394
0.394
1.7
1.7
Indoor Fan Motor
0.152
0.152
0.65
0.65
Voltage (V)
(Hz)
Cooling Heating Cooling Heating
Current (A) 9.8 - 9.8 8.7
Input (kW) 5.90 - 6.00 5.25
MCA (A) 14.4 - 14.4 13.4
MSC (A) 74 - 74 74
MFA (A)
Power Cable (mm2)
Limited wiring length*2
Input (kW)
(m)
FLA (A)
Input (kW)
FLA (A)
* Wiring Spec : Selected Sample (Selected based on Japan Electrotechnical Standard and
Codes Committee E0005)
DUCT TYPE
AR60
*2 Limited Wiring length :This is the wiring length in case voltage descent is less than 2%.
DUCT TYPE
AR60
When the wiring length becomes long, please select the wiring of a
more larger diameter. MCA : Min Circuit Amp = Max Operating Current (Full Load) MSC : Max Starting Current MFA : Main Fuse (Circuit breaker) Current FLA: Full Load Amp.
- (05 - 23) -
Page 25
5-14. SAFETY DEVICES
INDOOR UNIT
MODEL NAME PROTECTION FORM AR*60AUAK AR*60RUAK
PCB FUSE FAN MOTOR PROTECTOR THERMAL PROTECTOR
3.15A 250V
150°C±5°C OFF
OUTDOOR UNIT
MODEL NAME PROTECTION FORM AO*60APAGT AO*60RPAGT
FUSE (SIDE OF POWER SUPPLY
FUSE ON PCB 3.15A 250V 3.15A 250V FAN MOTOR PROTECTOR THERMAL PROTECTOR COMPRESSOR
HIGH PRESSURE PROTECTION
DISCHARGE THERMOSTAT
LOW PRESSURE PROTECTION FUSE IN SOFT STARTER
20°C(31A)~140°C(15A) OFF
OFF:130±5°C ON:100±15°C
5A 250V
150°C±5°C OFF
OFF:4.2±0.1MPa ON:3.2±0.15MPa
DUCT TYPE
AR60
DUCT TYPE
AR60
- (05 - 24) -
Page 26
5-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
TION
When the external input / output is used, connect the external signal wire as shown in the figure below.
CONTROL
INPUT
You can control air conditioner on/off by external control. You can select either Edge and Pulse.
CN106 (Black)
Indoor unit PCB
[Example]
+
Indoor unit
-
CN114
(White)
CN5
(Black)
PCB
Ch1
1
2
3
Field supply
DIP Switch (Indoor Unit)
NO.
DUCT TYPE
AR60
SW2
DIP-Switch
2
OFF
SW state
PulseEdge
ON
DUCT TYPE
AR60
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1 (Input)
Remote controller
Indoor unit
On
Off
On
Operation
Stop
2 Pulse
Ch1 (Input)
Remote controller
Indoor unit
Operation
Stop
200ms 200ms 200ms
On
- (05 - 25) -
Off
Page 27
OPERA
[Example]
TION DISPLA
Y
Operation indicator
Field supply
Operation
Ic
Vc
Vc : DC20V Ic : 10mA or less
or less
or
Indoor unit
(WHITE)
+
2
1
-
CN115
Indoor unit
Stop
SHORT
CN115
FRESH
(Output)
AIR OUTPUT SETTING
OPEN
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
DUCT TYPE
AR60
Indoor unit
+
1
2
Fuse
DUCT TYPE
AR60
-
CN14
(GREEN)
Indoor unit fan
CN14 (Output)
Field supplied
Operation
Stop
12V
0V
Power
Fan, other
- (05 - 26) -
Page 28
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation. When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON. When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode. 1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor unit
+
1
2
-
CN15
(ORANGE)
Indoor
Operation
Field supplied
unit
Heating
Indoor
Stop
Operation
unit fan
DUCT TYPE
AR60
Stop
12V
CN15 (Output)
0V
Power
CAUTION!
!
External Heater, other.
1min
DUCT TYPE
AR60
Please locate external a heater between the indoor unit and the ductwork. Please be sure to use delay control of a fan.
External Heater
Supply air
Indoor unit
Return air
- (05 - 27) -
Page 29
1
2
3
4
1 Room temperature correct coefficient of heating
2 External input select
3 Auto restart validity/invalidity
Rotary SW SW 3 Indoor unit number setting
JM1 Forbidden
JM2 Commercial mode setting
JM3 Fan delay setting
Jumper Wire
Forbidden
INDOOR UNIT
DIP SW
SW 1 SW 2
5-16. FUNCTION SETTING
5-16-1. INDOOR UNIT
SWITCH POSITION
Duct type Indoor unit control circuit board
POWER PCB
CN114
DUCT TYPE
AR60
CN106
CN115
MAIN PCB
CN4
CN5
CN16
CN14
CN15
SW1 SW2
SW3
JM1 JM2 JM3
CN16
DUCT TYPE
AR60
- (05 - 28) -
Page 30
5-16-2. SWITCH FUNCTION (INDOOR UNIT)
SW1-1 OFF
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
SW2-1 SW state
OFF Ceiling setting (+4 °C)
ON Room setting ( 0 °C)
SW2-2 SW state
OFF Edge
ON Pulse
SW2-3 SW state
OFF Validity
ON Invalidity
SW3 SW state
0 single
1-15 Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Dip SW 1-1,1-2,1-3,1-4 setting forbidden
( Factory setting)
2. SW2 setting
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature corrction
( Factory setting)
2-2 Control input setting
This switch is used to select the format of external input command as shown in the table below.
DUCT TYPE
AR60
( Factory setting)
DUCT TYPE
AR60
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
( Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
- (05 - 29) -
Page 31
JUMPER WIRE SETTING
JM1 SW state
Connect
Disconnect
Forbidden
JM2 SW state
Connect Residencial
Disconnect Commercial
JM3 SW state
Connect Invalidity
Disconnect Validity
Connector INPUT OUTPUT REMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115 - OPERATION DISPLAY
CN14 - FRESH AIR
CN15 - ELECTRICAL HEATER
See external
input/output settings
for details.
JM1 setting forbidden
( Factory setting)
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode. When you select "FAN:AUTO"mode fan goes in "HIGH"
( Factory setting)
Fan delay setting
This setting can be used when the auxiliary heater is mounted. When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,the fan operation continues one minutes.
( Factory setting)
DUCT TYPE
AR60
DUCT TYPE
AR60
EXTERNAL INPUT AND OUTPUT
- (05 - 30) -
Page 32
5-16-3. WIRED,SIMPLE REMOTE CONTROLLER CIRCUIT BOARD
Wired,Simple remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
OFF
DUCT TYPE
AR60
ON
1 2 3 4 5 6
DUCT TYPE
AR60
ON
DIP Switch
Simple remote controller
ON
ON
OFF
12345
6
DIP switches
- (05 - 31) -
Page 33
5-16-4. WIRED,SIMPLE REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
ON Multiple unit connection
1-3 Model setting
DUCT TYPE
AR60
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
DUCT TYPE
AR60
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (05 - 32) -