Refrigerant
Drain
hose
Outlet air
flow
Arrange the drain hose lower
than this portion
Trap
OK
NO
Unit
Air Outlet Grille Air inlet Grille
(Room)
740 mm
1135
mm
1177
mm
270 mm
AIR
AIR
477 mm
R410A
Duct Type
SPLIT TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION
SHEET
(PART NO. 9374536047)
Indoor unit is an appliance not accessible to the general public.
For authorized service personnel only.
WARNING
CAUTION
This air conditioner uses new refrigerant HFC (R410A).
The basic installation work procedures are the same as conventional refrigerant models.
However, pay careful attention to the following points:
Since the working pressure is 1.6 times higher than that of conventional refrigerant models, some of the
piping and installation and service tools are special. (See the table below.)
Especially, when replacing a conventional refrigerant model with a new refrigerant R410A model, always
replace the conventional piping and flare nuts with the R410A piping and flare nuts.
Models that use refrigerant R410A have a different charging port thread diameter to prevent erroneous
charging with conventional refrigerant and for safety. Therefore, check beforehand. [The charging port thread
diameter for R410A is 1/2 UNF 20 threads per inch.]
Be more careful that foreign matter (oil, water, etc.) does not enter the piping than with refrigerant models.
Also, when storing the piping, securely seal the openings by pinching, taping, etc.
When charging the refrigerant, take into account the slight change in the composition of the gas and liquid
phases, and always charge from the liquid phase side whose composition is stable.
When moving, if the compressor stops during pump down, close the valve immediately. (45 type only.)
This mark indicates procedures which, if improperly performed, might lead to the death or
serious injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in
personal harm to the user, or damage to property.
ELECTRICAL REQUIREMENT
• Electric wire size and breaker capacity:
2
Power supply cord (mm
45,000 BTU/h class (3 phase TYPE)
36,000 BTU/h class (3 phase TYPE)
36,000 BTU/h class (1 phase TYPE)
• Always use H07RN-F or equivalent to the connection cord.
• Install all electrical works in accordance to the standard.
• Install the disconnect device with a contact gap of at least 3 mm in all poles nearby the units. (Both indoor unit and outdoor unit)
• Install the circuit breaker nearby the units.
4.0
6.0 4.0 30
)
MIN.MAX.
2.5
Connection cord (mm2)
MAX. MIN.
2.5 1.0
Breaker capacity (A)
20
SELECTING THE MOUNTING POSITION
Decide the mounting position with the customer as follows:
WARNING
Select installation locations that can properly support the weight of the indoor and outdoor units. Install the
units securely so that they do not topple or fall.
CAUTION
Do not install where there is the danger of combustible gas leakage.
Do not install the unit near heat source of heat, steam, or flammable gas.
If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
INDOOR UNIT
(1) Install the indoor unit on a place having a sufficient strength so that it withstand against
the weight of the indoor unit.
(2)
The inlet and outlet ports should not be obstructed; the air should be able to blow all over the room.
(3) Leave the space required to service the air conditioner.
(4) Install the unit where the drain pipe can be easily installed.
(5)
Providing as much space as possible between the indoor unit and the ceiling will make work much easier.
(6)
If installing in a place where its humidity exceeds 80%, use heat insulation to prevent condensation.
300 mm
or more
Maintenance hole dimension
It shall be possible to install and remove the control box. It shall be possible to install and remove the control box, fan
units and filter.
150 mm
or more
INSTALLATION
PROCEDURE
Install the air conditioner as follows:
INDOOR UNIT
1
INSTALLATION
RECOMMENDED RANGE OF
EXTERNAL STATIC PRESSURE
30Pa~150Pa
WARNING
Install the air conditioner in a location which can
withstand a load of at least five times the weight
of the main unit and which will not amplify sound
or vibration.
If the installation location is not strong enough,
the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there
is a risk that the unit will come loose. Please
take care.
CAUTION
For installation, refer to the technical data.
1. INSTALLING THE HANGERS
WARNING
When fastening the hangers, make the bolt positions uniform.
Hanging bolt installation diagram.
(Example)
(Top side)
Slide the unit in the arrow direction and fasten it.
Hanging bolt M10
(Obtained locally)
Bolt Strength 9.81 to 14.71 N·m (100 to 150 kgf·cm)
Special nut A
Washer
(Obtained locally)
Special nut B
Hanger
WARNING
Fasten the unit securely with special nuts A and B.
2. LEVELING
Base vertical direction leveling on the unit (right and left).
(Left side)
Base horizontal direction leveling on top of the unit.
0 – 5 mm
Give a slight tilt to the side to which the drain hose is connected.
The tilt should be in the range of 0 mm to 5 mm.
Drain hose
3. INSTALLING DRAIN HOSE
Install the drain hose according to the measurements given in the
following figure.
240 mm
CAUTION
Install the drain hose in accordance with the instructions in this installation instruction sheet and keep
the area warm enough to prevent condensation.
Problems with the piping may lead to water leaks.
NOTE: INSTALL THE DRAIN HOSE
• Install the drain hose with downward gradient (1/50 to
1/100) and so there are no rises or traps in the hose.
• Use general hard polyvinyl chloride pipe (VP25) [outside diameter 38 mm] and connect it with adhesive (polyvinyl chloride)
so that there is no leakage.
• When the hose is long, install supporters.
• Do not perform air bleeding.
• Always heat insulate the indoor side of the drain hose.
Rise
Supporter
1.5 to 2 m
Air bleeding
• When the unit is shipped from the factory, the drain port is on
the left side (control box side).
• When using the drain port on the right side of the unit, reinstall
the drain cap to the left side drain port.
Drain port
Drain cap Nylon fastener
• Cut the drain hose insulation at a position approximately 30 mm
from the end with cutters, etc.
• Stick the large drain hose insulation at the drain hose installation
side.
• Stick the small drain hose insulation at the drain cap side.
450 mm
Cut line
170 mm
Drain hose
insulation
(large)
unit
Drain hose
Drain hose insulation (small)
Unit
30 mm
Drain cap
420 mm
170 mm
unit
0 mm
Unit
30 mm
170 mm
Drain hose
insulation
(large)
Drain hos
Drain hose
insulation
(small)
0 mm
4. INTAKE DUCT CONNECTION
Follow the procedure in the following figure to the ducts.
1015 mm
240 mm
The air inlet duct can be changed by replacing the intake grille and
flange.
Special tools for R410A
Tool name
Pressure is high and cannot be measured with a conventional gauge. To prevent erroneous mixing of
Gauge manifold
Charge hose
Vacuum pump
Gas leakage detector
other refrigerants, the diameter of each port has been changed.
It is recommended the gauge with seals –0.1 to 5.3 MPa (–76 cmHg to 53 kgf/cm2) for high pressure.
–0.1 to 3.8 MPa (–76 cmHg to 38 kgf/cm2) for low pressure.
To increase pressure resistance, the hose material and base size were changed.
A conventional vacuum pump can be used by installing a vacuum pump adapter.
Special gas leakage detector for HFC refrigerant R410A.
Copper pipes
It is necessary to use seamless copper pipes and it is desirable that the amount
of residual oil is less than 40 mg/10m. Do not use copper pipes having a
collapsed, deformed or discolored portion (especially on the interior surface).
Otherwise, the expansion valve or capillary tube may become blocked with
contaminants.
As an air conditioner using R410A incurs pressure higher than when using
conventional refrigerant, it is necessary to choose adequate materials.
Thicknesses of copper pipes used with R410A are as shown in the table.
Never use copper pipes thinner than that in the table even when it is available
on the market.
Contents of change
Thicknesses of Annealed Copper Pipes (R410A)
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Thickness
0.80 mm
0.80 mm
0.80 mm
1.00 mm
1.20 mm
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Hanger
Special nut A
(large flange)
Special nut B
(small flange)
Coupler heat
insulation (large)
Coupler heat
insulation (small)
Q’ty Application
For suspending the indoor
unit from ceiling
4
For suspending the indoor
4
unit from ceiling
4
For indoor side pipe joint
(gas pipe)
1
For indoor side pipe joint
1
(liquid pipe)
Name and Shape Q’ty Application
Binder
Remote
controller
Tapping screw
(flush heads)
Remote
controller cord
Drain hose
insulation
1
(large)
1
(small)
1
2
1
1
For fixing the drain hose
For fixing the remote
controller cord
For installing the remote
controller
For connecting the remote
controller
Insulates the drain hose
and vinyl hose
OUTDOOR UNIT ACCESSORIES
Drain pipe
Drain cap
For outdoor unit drain
1
piping work
[Heat & Cool model
2
(Reverse cycle) only]
Insulation (seal)
For filling in a gap at the
entrance of connection
1
cords
OPTIONAL PARTS
When connecting the square duct and round duct, use the optional square flange or round flange.
Square flange Round flange
Model name : UTD–SF045T (P/N 9098180007) Model name : UTD–RF204 (P/N 9093160004)
40 mm
ø205 mm
204 mm
1065 mm
ø195 mm
85 mm
Long-life filter Remote sensor
Model name : UTD–LF25NA (P/N 9079892004) Model name : UTD–RS100 (P/N 9072619004)
External control wire set
239 mm
507 mm
Model name : UTD–ECS5A (P/N 9077359004)
CONNECTING PIPE REQUIREMENT
CAUTION
The maximum lengths of this product are shown in the following table. If the units are further apart than this,
correct operation cannot be guaranteed.
45,000 BTU/h class
36,000 BTU/h class
• Use pipe with water-resistant heat insulation.
Liquid
9.52 mm (3/8 in.)
Diameter
Gas
19.05 mm (3/4 in.)
15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above 120 °C. (Reverse cycle model only)
In addition, if the humidity level at the installation location of the refrigerant piping is expected to exceed 70%,
install heat insulation around the refrigerant piping. If the expected humidity level is 70-80%, use heat insulation
that is 15 mm or thicker and if the expected humidity exceeds 80%, use heat insulation that is 20 mm or thicker.
If heat insulation is used that is not as thick as specified, condensation may form on the surface of the insulation.
In addition, use heat insulation with heat conductivity of 0.045 W/(m·K) or less (at 20 °C).
Pipe length
MAX. MIN.
50 m 5 m
Maximum height
(between indoor and outdoor)
30 m
300 mm
500 mm
500 mm
Maintenance hole
Control box
100 mm
300 mm
500 mm
Control box
Maintenance hole
Intake panel
1550 mm
OUTDOOR UNIT
WARNING
Install the unit where it will not be tilted by more than 3˚. However, do not install the unit with it tilted towards
the side containing the compressor.
When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
(1) Install the outdoor unit in a location which can withstand the weight of the unit and vibration, and which can install horizontally.
(2) Provide the indicated space to ensure good airflow.
(3) If possible, do not install the unit where it will be exposed to direct sunlight.
(If necessary, install a blind that does not interfere with the airflow.)
(4) Do not install the unit near a source of heat, steam, or flammable gas.
(5) During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water flow will not be obstructed. (Reverse cycle model only)
(6) Do not install the unit where strong wind blows or where it is very dusty.
(7) Do not install the unit where people pass.
(8) Install the outdoor unit in a place where it will be free from being dirty or getting wet by rain as much as possible.
(9) Install the unit where connection to the indoor unit is easy.
• When there are obstacles at the back side.
100 mm
or more
• When there are obstacles at the back, side(s), and top.
*
600 – 1000 mm
100 – 300 mm
*
250 mm or more
(Service space)
300 mm
or more
* If the space is larger than that is stated, the condition will
be the same as that there are no obstacles.
or more
• When there are obstacles at the back and front sides.
AIR
600 mm
or more
• When there are obstacles at the back side with the installation of
more than one unit.
250 mm
250 mm
or more
100 mm
100 mm
or more
300 mm
or more
(Left side)
The distance of
hanging bolts.
(MAX : 550 mm, MIN : 410 mm)
is adjustable according to the place of the
CAUTION
If an intake duct is installed, take care not to
damage the temperature sensor (the tempera-
ture sensor is attached to the intake port flange).
Be sure to install the air inlet grille and the air
outlet grille for air circulation. The correct tem-
perature cannot be detected.
Grills must be fixed so that man cannot touch
indoor unit fan, and cannot be removed by only
hand operation without tool.
Be sure to install the air filter in the air inlet. If the
air filter is not installed, the heat exchanger may
be clogged and its performance may decrease.
5. OUTLET DUCT CONNECTION
Duct installation pattern ( CUT PART)
(1) Square duct
(2) Round duct outlet ×4
(This is the factory setting.)
When using as a square duct
(1) Cut the slit seam with a cutter.
(2) Turn up the insulation around the points to be cut according
to the outlet port shape working points so that the insulation
does not stick out at the
Cut Cut
Cut
(3) Cut with nippers and remove the sheet metal.
part.
Cut
(Left side)
Liquid pipe
66 mm
Drain pipe
ø 38 mm (O.D.)
240 mm
(Right side)
32 mm
(4) Since there is a slit in the insulation, use radio pliers, tweezers,
etc. to stretch the screw hole part used when installing the round
flange and square flange when connecting the duct.
Gas pipe
Drain pipe
ø 38 mm (O.D.)
The drain cap is attached
at the factory setting.
32 mm
114 mm
6. FRESH AIR INTAKE
(Processing before use)
(1) When taking in fresh air, cut a slit shaped cabinet in the left side
of the outer case with nippers.
Cut
Cut
Square holeCabinet (iron plate)
CAUTION
When removing the cabinet (iron plate), be careful not to damage the indoor unit internal parts
and surrounding area (outer case).
When processing the cabinet (iron plate), be careful not to injure yourself with burrs, etc.
(2) Install the round flange (option parts) to the fresh air intake.
Round duct
(3) Connect the duct to the round flange.
(4) Seal with a band and vinyl tape, etc. so that air does not leak
from the connection.
Duct
CAUTION
Always check that the drain cap is installed to the
unused drain port and is fastened with the nylon
fastener.
If the drain cap is not installed, or is not sufficiently
fastened by the nylon fastener, water may drip during the cooling operation.
2
OUTDOOR UNIT
INSTALLATION
1. OUTDOOR UNIT PROCESSING
(1) Outdoor unit to be fastened with bolts at the four places indi-
cated by the arrows without fail.
Drain cap
Bottom side
650 mm
Drain pipe
mounting place
(2) Fix securely with bolts on a solid block. (Use 4 sets of com-
mercially available M10 bolt, nut and washer.)
(3) Since the drain water flows out of the outdoor unit during
heating operation, install the drain pipe and connect it to a
commercial 16 mm hose.
(Reverse cycle model only)
(4) When installing the drain pipe, plug all the holes other than
the drain pipe mounting hole in the bottom of the outdoor unit
with putty so there is no water leakage.
(Reverse cycle model only)
CAUTION
When the outdoor temperature is 0°C or less, do
not use the accessory drain pipe and drain cap.
If the drain pipe and drain cap are used, the drain
water in the pipe may freeze in extremely cold
weather.
(Reverse cycle model only)
Drain pipe mounting hole
mounting place
Bolt
Nut
Drain pipe
370 mm
4-ø12 mm hole
Block
Base
For the bottom air intake, follow the procedure of → for
installation.
(The factory setting is back air intake.)
CAUTION
When air is taken in from the bottom side, the operating sound of the product will easily enter the room.
Install the product and intake grilles where the affect
of the operating sound is small.
3
CONNECTING THE
PIPE
CAUTION
Do not use mineral oil on flared part. Prevent mineral oil from getting into the system as this would
reduce the lifetime of the units.
While welding the pipes, be sure to blow dry nitrogen gas through them.
The maximum lengths of this product are shown
in the table. If the units are further apart than this,
correct operation cannot be guaranteed.
1. FLARING
(1)
Cut the connection pipe to the necessary length with a pipe cutter.
(2) Hold the pipe downward so that cuttings will not enter the pipe
and remove the burrs.
(3) Insert the flare nut (always use the flare nut attached to the
indoor and outdoor units respectively) onto the pipe and perform the flare processing with a flare tool.
Use the special R410A flare tool, or the conventional (for R22)
flare tool.
Check if [L] is flared uniformly
and is not cracked or scratched.
Die
L
Pipe outside diameter
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Pipe outside diameter Dimension B (mm)
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
When using conventional flare tools to flare R410A pipes, the dimension A should be approximately 0.5 mm more than indicated in
the table (for flaring with R410A flare tools) to achieve the specified
flaring. Use a thickness gauge to measure the dimension A.
Width across flats
6.35 mm (1/4 in.)
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Flare tool for R410A, clutch type
Pipe outside
diameter
A
Pipe
Dimension A (mm)
0 to 0.5
9.1
13.2
16.6
19.7
24.0
Width across flats
of Flare nut
(Continued to the next page)
0
-0.4
17 mm
22 mm
26 mm
29 mm
36 mm
B
9374536047_B2_front 24/11/2005, 9:14 AM1
CONNECTING THE PIPE
Be sure to overlap
the insulation.
Coupler heat insulation
Indoor unit side
(Gas and liquid pipes)
No gaps
DAY OFF
DELETE SET
ENERGY
SAVE
THERMO
SENSOR
SET BACK
DAY
CLOCK ADJUST
1 2 3 1 2 3 1 2 3
1 2 3
1 2 3
1 2 31 2 3
1 2 3
Remote
controller
wire
Remote
controller
Indoor unit
Master unit Slave unit
Red
White
Power line
Black
Red
White
Black
Power line
3
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse
them.
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched, the material will
harden, making it difficult to bend or stretch them any more.
Do not bend or stretch the pipes more than three times.
CAUTION
To prevent breaking of the pipe, avoid sharp
bends.
Bend the pipe with a radius of curvature of 150
mm or over.
If the pipe is bent repeatedly at the same place, it
will break.
3. CONNECTION PIPES
Indoor unit
(1) Detach the caps and plugs from the pipes.
CAUTION
Be sure to apply the pipe against the port on the
indoor unit correctly. If the centering is improper,
the flare nut cannot be tightened smoothly. If the
flare nut is forced to turn, the threads will be
damaged.
Do not remove the flare nut from the indoor unit
pipe until immediately before connecting the
connection pipe.
(2) Centering the pipe against port on the indoor unit, turn the
flare nut with your hand.
To prevent gas leakage, coat the flare
surface with alkylbenzene oil (HAB).
Do not use mineral oil.
When the flare nut is tightened properly by your hand, use a torque
wrench to finally tighten it.
Holding
spanner
Hold the torque wrench at its grip, keeping it in the
right angle with the pipe , in order to tighten the flare
nut correctly.
Torque wrench
Unit
side
90°
CAUTION
Flare nut
6.35 mm (1/4 in.) dia.
9.52 mm (3/8 in.) dia.
12.70 mm (1/2 in.) dia.
15.88 mm (5/8 in.) dia.
19.05 mm (3/4 in.) dia.
Tightening torque
16 to 18 N·m (160 to 180 kgf·cm)
30 to 42 N·m (300 to 420 kgf·cm)
49 to 61 N·m (490 to 610 kgf·cm)
63 to 75 N·m (630 to 750 kgf·cm)
90 to 110 N·m (900 to 1100 kgf·cm)
Outdoor unit
Tighten the flare nut of the connection pipe at the outdoor unit
valve connector. The tightening method is the same as that as at
the indoor side.
3-way valve
(liquid)
Flare nut
Connection pipe
(liquid)
3-way valve
(gas)
Flare nut
Connection pipe
(gas)
4. VACUUM
(1) Remove the cap, and connect the gauge manifold and the
vacuum pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the
pressure gauge indicates –0.1 MPa (–76 cmHg).
(3) When –0.1 MPa (–76 cmHg) is reached, operate the vacuum
pump for at least 60 minutes.
(4) Disconnect the service hoses and fit the cap to the charging
valve to the specified torque.
(5) Remove the blank caps, and fully open the spindles of the 2-
way and 3-way valves with a hexagon wrench [Torque: 6~7
N·m (60 to 70 kgf·cm)].
(6) Tighten the blank caps of the 2-way valve and 3-way valve to
the specified torque.
Tightening torque
6.35 mm (1/4 in.)
Blank
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
cap
15.88 mm (5/8 in.)
19.05 mm (3/4 in.)
Charging port cap
20 to 25 N·m (200 to 250 kgf·cm)
20 to 25 N·m (200 to 250 kgf·cm)
28 to 32 N·m (280 to 320 kgf·cm)
30 to 35 N·m (300 to 350 kgf·cm)
35 to 40 N·m (350 to 400 kgf·cm)
12.5 to 16 N·m (125 to 160 kgf·cm)
Connecting pipe
Blank cap
Hexagon wrench
Service hose
with valve core
Cap
Gauge manifold
Service hose
3-way valve
Charging port
Vacuum pump
Use a 4 mm
hexagon wrench.
CAUTION
Do not purge the air refrigerants but use a vacuum
pump to vacuum the installation! There is no ex-
tra refrigerant in the outdoor unit for air purging!
Use a vacuum pump and gauge manifold and
charging hose for R410A exclusively. Using the
same vacuum for different refrigerants may
damage the vacuum pump or the unit.
5. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 20 m is charged in the
outdoor unit at the factory.
When the piping is longer than 20 m, additional charging is
necessary.
For the additional amount, see the table below.
Pipe length
Model type
36,000 BTU/h class
45,000 BTU/h class
20 m
(66 ft)
None
None
30 m
(99 ft)
300g
(10.6 oz)
400g
(14.1 oz)
40 m
(132 ft)
600g
(21.2 oz)
800g
(28.2 oz)
50 m
(164 ft)
900g
(31.8 oz)
1200g
(42.3 oz)
g/m
(oz/ft)
30 g/m
(1.06 oz
/3.3 ft)
40 g/m
(1.41 oz
/3.3 ft)
CAUTION
When moving and installing the air conditioner,
do not mix gas other than the specified refrigerant (R410A) inside the refrigerant cycle.
When charging the refrigerant R410A, always use
an electronic balance for refrigerant charging (to
measure the refrigerant by weight).
When charging the refrigerant, take into account the
slight change in the composition of the gas and liquid
Gas
R410A
phases, and always charge
from the liquid phase side
Liquid
whose composition is stable.
Add refrigerant from the charging valve after the
completion of the work.
The maximum length of piping is 50 m. If the units
are further apart than this, correct operation can
not be guaranteed.
6. GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the all joints
for gas leakage with gas leak detector.
When inspecting gas leakage, always use the
vacuum pump for pressure. Do not use nitrogen gas.
7. HEAT INSULATION ON THE PIPE JOINTS
(INDOOR SIDE ONLY)
CAUTION
There should be no gaps between the insulation
and the product.
4
POWER
WARNING
[45,000 BTU/h class (3 phase TYPE) ]
[36,000 BTU/h class (3 phase TYPE) ]
The rated voltage of this product is 400 V 3N ~ 50 Hz.
Before turning on, verify that the voltage is within
the 342 V to 457 V range.
[36,000 BTU/h class (1 phase TYPE) ]
The rated voltage of this product is 230 V ~ 50 Hz.
Before turning on, verify that the voltage is within
the 198 V to 264 V range.
Always use a special branch circuit and install a special
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
matched to the capacity of the air conditioner.
(Install in accordance with standard.)
Perform wiring work in accordance with standards so
that the air conditioner can be operated safely and
positively.
Install a leakage special branch circuit breaker in
accordance with the related laws and regulations and
electric company standards.
CAUTION
The power source capacity must be the sum of the
air conditioner current and the current of other elec-
trical appliances. When the current contracted
pacity is insufficient, change the contracted capacity.
When the voltage is low and the air conditioner is
difficult to start, contact the power company the
voltage raised.
This air conditioner must be connected to a power
source that has an electrical impedance of 0.11 Ω
or less or has a supply current of 100 A or greater.
If the power supply does not meet the specifications, contact the power company.
5
ELECTRICAL WIRING
WARNING
Before starting work, check that power is not being supplied to the indoor unit and outdoor unit.
Match the terminal board numbers and connection cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
Connect the connection cords firmly to the terminal board. Imperfect installation may cause a fire.
Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed, electric leakage may occur.)
Always connect the ground wire.
ca-
HOW TO CONNECT WIRING
TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1) Cut the wire end with a wire cutter or wire-cutting pliers, then
strip the insulation to about 25 mm to expose the solid wire.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using pliers, bend the solid wire to form a loop suitable for
the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal board and
tighten securely with the terminal screw using a screwdriver.
B. For strand wiring
(1)
Cut the wire end with a wire cutter or wire-cutting pliers, then
strip the insulation to about 10 mm to expose the strand wiring.
(2) Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3) Using a round terminal fastener or pliers, securely clamp a
round terminal to each stripped wire end.
(4) Position the round terminal wire, and replace and tighten
the terminal screw using a screwdriver.
A. Solid wire B. Strand wire
Loop
Strip 25 mm
Wire
Insulation
Screw with
special washer
Round terminal
Terminal
board
Terminal block
Strip 10 mm
Wire
Round
terminal
Screw with
special washer
Round
terminal
CAUTION
Do not bundle the remote controller cord, or wire the
remote controller cord in parallel, with the indoor unit
connection wire (to the outdoor unit) and the power
supply cord. It may cause erroneous operation.
1. CONNECTION DIAGRAMS
[45,000 BTU/h class (3 phase TYPE) ]
[36,000 BTU/h class (3 phase TYPE) ]
Remote controller
Indoor unit
side terminal
[36,000 BTU/h class (1 phase TYPE) ]
Remote controller
Indoor unit
side terminal
Power supply
Outdoor unit
side terminal
Power supply
Outdoor unit
side terminal
EARTH
(L1)
(L2)
(L3)
EARTH
2. CONNECTION CORD PREPARATION
Keep the earth wire longer than the other wires.
30 mm
Earth wire
40 mm or more
Power supply cord
or connection cord
3. INDOOR UNIT
CAUTION
Use care not to mistake the power supply cord
and connection wires when installing.
Install so that the wires for the remote controller will not come in contact with other connection wires.
If there is a risk of entering insects and small
animals into the hole for cords, fill in the gap
with putty.
(1)
Remove the control box cover and install each connection wire.
Control box cover
Screw
(2) After wiring is complete, secure the remote controller cord
and connection cord with the cord clamps.
Connection cord
(to outdoor unit)
Cord clamp
40 mm or more
Cord clamp
Remote
controller cord
12
Remote controller
3
Connection cord
31
2
(3) Install control box cover.
Adjust the position of the screws for control box cover according
to the installation.
Outdoor unit
4. OUTDOOR UNIT
CAUTION
When connecting the power supply cord, make sure
that the phase of the power supply matches with
the phase of the terminal board. If the phases do
not match, the compressor will rotate in reverse and
will not be able to compress.
(1) Service cover removal
• Remove the two mounting screws.
• Remove the service cover by pushing downwards.
Hook
(3 places)
Direction of the service
cover removal
Service cover
(2) Valve cover removal.
• Remove the one mounting screw.
• Remove the valve cover by sliding upward.
Hook (4 places)
(3)
Connect the power supply cord and the connection cord to terminal.
(4)
Fasten the power supply cord and connection cord with cord clamp.
[45,000 BTU/h class (3 phase TYPE) ]
[36,000 BTU/h class (3 phase TYPE) ]
Power supply cord
Power supply cord
EARTH
[36,000 BTU/h class (1 phase TYPE) ]
Power supply cord
Power supply cord
EARTH
Connection cord
(indoor unit and outdoor
unit connection cord)
Indoor unit
Connection cord (indoor
unit and outdoor unit
connection cord)
Indoor unit
Valve cover
Control box
Terminal
Cord clamp
Connection cord
Control box
Terminal
Cord clamp
Connection cord
(5) Power supply cord and connection cord should be fixed with cable
clip as shown in the figure.
Fill in a gap at the entrance of the cords with insulation (seal).
[45,000 BTU/h class ]
[36,000 BTU/h class (Reverse cycle model) ]
Power supply cord and connection cord
Cable clip
(2 places)
[36,000 BTU/h class (Cooling model) ]
Power supply cord and connection cord
Compressor
Cable clip
CAUTION
Do not make power supply cord and connection
cord come in contact with valve (Gas).
Power supply cord
and connection cord
Gap
Valve
(Gas)
(6) Put the service cover and valve cover back after completion
of the work.
6
REMOTE CONTROLLER
SETTING
CAUTION
In order to detect the room temperature correctly when using the
temperature sensor of the remote
controller, do not install the remote
controller in a place where it will be
exposed to direct sunlight or
directly below the air outlet of the
indoor unit.
When installing the remote controller and cord
near a source of electromagnetic waves, separate the remote controller from the source of the
electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and
PC board parts directly with your hands.
Temperature
sensor
1. INSTALLING THE REMOTE CONTROLLER
(1) Open the operation panel on the front of the remote controller,
remove the two screws indicated in the following figure, and
then remove the front case of the remote controller.
Screws
When installing the remote controller, remove the connector from
the front case. The wires may break if the connector is not
removed and the front case hangs down.
When installing the front case, connect the connector to the
front case.
(2) Install the rear case to the wall, etc. with the two tapping screws.
Refer to the following information to install the remote controller wires.
Front case
Connector
Install the remote controller wires so as not to be direct touched
with your hand.
Front case
(back side)
Rear case
Connector
Remote controller
wires
Rear case
2. ROUTING THE REMOTE CONTROLLER
WIRES
(1) Install the remote controller wires to the terminals on the top of
the rear case as shown in the following figure.
(2) Fasten the wires with the binder.
(Example)
1. Red
Binder
2. White
3. Black
3. SETTING THE DIP SWITCHES
When using a battery (memory backup)
ON
OFF
1
2
3
4
5
6
DIP Switch
Change the DIP switch setting to use batteries. (The DIP switch is
not set to use batteries at the factory.)
Change DIP switch No. 6 from OFF to ON.
If batteries are not used, all of the settings stored in memory will be
deleted if there is a power failure.
ON
4. SETTING THE ROOM TEMPERATURE
DETECTION LOCATION
The detection location of the room temperature can be selected
from the following three examples. Choose the detection location
that is best for the installation location.
A. Indoor unit setting (factory setting)
The room temperature is detected by the indoor unit temperature
sensor.
(1)
When the THERMO SENSOR button is pressed, the lock display
flashes because the function is locked at the factory.
B. Remote controller setting
The room temperature is detected by the remote controller temperature sensor.
B
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and then
disappears when the function is unlocked.
(2) Press the THERMO SENSOR button.
The thermo sensor display appears.
(3) Press the THERMO SENSOR button again for 5 seconds or
more to lock the function. The thermo sensor display flashes
and then remains on when the function is locked.
(4) Make sure that the function is locked.
C. Indoor unit/remote controller setting
(room temperature sensor selection)
The temperature sensor of the indoor unit or the remote controller
can be used to detect the room temperature.
C
Indoor unit
(1) Press the THERMO SENSOR button for 5 seconds or more to
unlock the function. The thermo sensor display flashes and then
disappears when the function is unlocked.
(2) Press the THERMO SENSOR button to select the temperature
sensor of the indoor unit or the remote controller.
NOTES
If the function to change the temperature sensor is used as shown
in examples A and B (other than example C), be sure to lock the
detection location. If the function is locked, the lock display
will flash when the THERMO SENSOR button is pressed.
7
TEST RUN
CAUTION
Supply power to the crankcase heater for at least 12
hours before the start of operation in winter.
(1) Stop the air conditioner operation.
(2) Press the master control button and the fan control button si-
multaneously for 2 seconds or more to start the test run.
Test run display
(3) Press the start/stop button to stop the test run.
[SELF-DIAGNOSIS]
When the error indication “E:EE” is displayed, follow the following
items to perform the self-diagnosis. “E:EE” indicates an error has
occurred.
1. REMOTE CONTROLLER DISPLAY
(1) Stop the air conditioner operation.
(2) Press the set temperature buttons simultaneously for 5
seconds or more to start the self-diagnosis.
Refer to the following tables for the description of each error
code.
Unit number (usually 0)
EX. Self-diagnosis
(3) Press the set temperature buttons simultaneously for 5
seconds or more to stop the self-diagnosis.
Error code
00
01
02
03
04
05
06
07
Communication error
(indoor unit
Communication error
(indoor unit
Room temperature sensor open
Room temperature sensor short-circuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor
short-circuited
Outdoor heat exchanger temperature sensor
open
Outdoor heat exchanger temperature sensor
short-circuited
Power source connection error
Error contents
remote controller)
outdoor unit)
Error code
08
09
0A
0b
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor short-circuited
Error code Error contents
0c
0d
0E
0F
Discharge pipe temperature sensor or
compressor temperature sensor open
Discharge pipe temperature sensor or
compressor temperature sensor short-circuited
Outdoor high pressure abnormal
Discharge pipe temperature or compressor
temperature abnormal
Model abnormal
11
12
Indoor fan abnormal
13
Outdoor signal abnormal
14
Outdoor EEPROM abnormal
2. OUTDOOR UNIT LEDS
Heat & Cool model (reverse cycle) only
When a malfunction occurs in the outdoor unit, the LEDs on the circuit board
light to indicate the error. Refer to the
following table for the description of
each error according to the LEDs.
LED1 LED2 Error contents
flash
1flash
2 flash
3 flash
4 flash
5 flash
6 flash
7 flash
8 flash
9 flash
10 flash
Dislighting
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as
long as the power is not turned off.
flash
Lighting
Lighting
Lighting
Lighting
Lighting
Lighting
Lighting
Lighting
Lighting
Lighting
Model abnormal or EEPROM abnormal
Power source connection error
Discharge temp. sensor error
Heat exchanger temp. sensor error
Outdoor temp. sensor error
Communication signal error
Indoor unit error
Discharge temp. abnormal
High pressure abnormal
Compressor temp. abnormal
Compressor temp. sensor error
No error. Protect operation
LED layout
LED2
LED1
8
SPECIAL INSTALLATION
METHODS
CAUTION
When setting the rotary switch and DIP
switches, do not touch any other parts on the
circuit board directly with your bare hands.
Be sure to turn off the main power.
1. GROUP CONTROL SYSTEM
A number of indoor units can be operated at the same time using
a single remote controller.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
No. 0
Remote
controller
wire
(2) Rotary switch setting (indoor unit)
Set the unit number of each indoor unit using the rotary switch
on the indoor unit circuit board.
The rotary switch is normally set to 0.
(3) DIP switch setting (remote controller)
Change DIP switch No. 3 on the remote controller from OFF
to ON.
2. DUAL REMOTE CONTROLLERS
(OPTIONAL)
Two separate remote controllers can be used to operate the
indoor units.
(1) Wiring method (indoor unit to remote controller)
Indoor unit
No. 1
Remote
controller
Indoor unit
SW3
Rotary Switch
Indoor unit
No. 2
Indoor unit
No. 3
Remote controller
DIP Switch
(2) DIP switch setting (remote controller)
Set the remote controller DIP switch Nos. 1 and 2 according
to the following table.
Number of
remote
controllers
1 (Normal)
2 (Dual)
Number of
remote
controllers
1 (Normal)
2 (Dual)
Master unit
DIP-SW
No. 1
ON
OFF
DIP-SW
No. 1
–
ON
Slave unit
DIP-SW
No. 2
OFF
OFF
DIP-SW
No. 2
–
ON
Remote
controller
DIP Switch
3. CANCELING AUTO RESTART
The auto restart function can be canceled.
(1) DIP switch setting (indoor unit)
Change the DIP switch (SW2-3) on the indoor unit circuit board
from OFF to ON. The auto restart function will be canceled.
Indoor unit
DIP Switch
[DIP-SWITCH SETTING]
• Indoor unit
NO.
SW2
Switch
1 – ✽ – Remote sensor setting
DIP-
2 Edge ✽ Pulse Control input setting
3 Validity ✽ Invalidity Auto restart setting
• Remote controller
NO.
1 ✽
2 ✽
3 One unit ✽ Multiple unit
DIP-
Switch
4
5 Invalidity Validity ✽
6 Invalidity ✽ Validity
SW state
OFF ON
SW state
OFF ON
Heat &Cool model
(Reverse cycle model)
Cooling only
model
Detail
Detail
Dual remote
controller setting
Group control
setting
Model setting
Auto changeover
setting
Memory backup
setting
✽: Factory setting
9374536047_B2_back 24/11/2005, 9:11 AM1