5 . DUCT TYPE :
AR 36FUAN, AR 36UUAN
AR 45FUAN, AR 45UUAN
D2D009E/03
2006.05.30
Page 2
5-1. FEATURE
MODELS :
AR 36FUAN / AO 36FNAXT
AR 36UUAN / AO 36UNAXT
AR 45FUAN / AO 45FMAXT
AR 45UUAN / AO 45UMAXT
FEATURES
Installation styles
Embedded in Ceiling
Hanging from Ceiling
Low static pressure mode function
When installed, normal middle static pressure mode, and low static
pressure mode can be selected by switching over using DIP switch
on the board in the control box. Therefore, these models can be operated under the wide range of conditions.
DUCT TYPE
AR36X - AR45X
DUCT TYPE
AR36X - AR45X
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape
is now united with main unit (DIP Switch is
located on the internal substrate.)
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further compactification is attained by reducing 65 mm from the width with the flanking
control box embedded inside the chassis.
- (05 - 01) -
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and
rear, and the internal fan casing is also made dismountable in two pieces namely,
upper and lower ones.
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
DUCT TYPE
AR36X - AR45X
DUCT TYPE
AR36X - AR45X
- (05 - 02) -
Page 4
5-2. REMOTE CONTROLLER
5-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
one unit.
Wired
remote
controller
Built-in timers
Weekly
timer
Setback timerWeekly timer
Setback
timer
Possible to set ON/OFF time to operate twice each day
of the week.
DUCT TYPE
AR36X - AR45X
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen
after setup
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
DUCT TYPE
AR36X - AR45X
At "Weekly timer" + "Set back timer" setup
24°C
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
28°C
Easy-to-understand operationSimple installation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
Timer
area
Operation
area
needed.
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (05 - 03) -
European
switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2
7
8
9
10
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETESET
12 15 18 21
DAY
DAY OFF
SA
13
1
3
ENERGY
SAVE
THERMO
SENSOR
4
6
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
11
12
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Display panel
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
14
15
1617 18
10
Set time button
Pessed to select the set back timer.
SUMOTUWETH FR
SA
11
Delete button
The schedule of a weekly timer is deleted.
369
DUCT TYPE
AR36X - AR45X
12 15 18 21
DUCT TYPE
12
Set button
1920
Sets the date, hour, minute and on-off time.
13
Operation lamp
AR36X - AR45X
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETESET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH( m )
POWER( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (05 - 04) -
Page 6
- (05 - 05) -
DUC
T TYPE
AR36
X -
A
R45
X
D
UCT TYPEAR36X - AR45X
5-3. SPECIFICATIONS
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CW B.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 100 Pa.
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
COOLING TYPEHEAT PUMP TYPECOOLING TYPEHEAT PUMP TYPE
*1) Wiring Spec : Selected Sample (Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2 Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
DUCT TYPE
When the wiring length becomes long, please select the wiring of a more larger diameter.
When the external input / output is used,
connect the external signal wire as shown
in the figure below.
CONTROL
INPUT
You can control air conditioner on/off by
external control. You can select either
Edge and Pulse.
CN106
(Black)
Indoor unit
PCB
[Example]
+
Indoor
unit
-
CN114
(White)
CN5
(Black)
PCB
Ch1
1
2
3
Field supply
DIP Switch (Indoor Unit)
NO.
DUCT TYPE
AR36X - AR45X
SW2
DIP-Switch
2
OFF
SW state
PulseEdge
ON
DUCT TYPE
AR36X - AR45X
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1
(Input)
Remote
controller
Indoor
unit
On
Off
On
Operation
Stop
2 Pulse
Ch1
(Input)
Remote
controller
Indoor
unit
Operation
Stop
200ms200ms200ms
On
- (05 - 32) -
Off
Page 34
OPERA
[Example]
TION DISPLA
Y
Operation
indicator
Field supply
Operation
Ic
Vc
Vc : DC20V or less
Ic : 10mA or less
or
Indoor
unit
(WHITE)
+
2
1
-
CN115
Indoor
unit
Stop
SHORT
CN115
FRESH
(Output)
AIR OUTPUT SETTING
OPEN
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
DUCT TYPE
AR36X - AR45X
Indoor
unit
+
1
2
Fuse
DUCT TYPE
AR36X - AR45X
-
CN14
(GREEN)
Indoor
unit fan
CN14
(Output)
Field supplied
Operation
Stop
14V
0V
Power
Fan, other
- (05 - 33) -
Page 35
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor
unit
+
1
2
-
CN15
(ORANGE)
Indoor
Operation
Field supplied
unit
Heating
Indoor
Stop
Operation
unit fan
Stop
DUCT TYPE
AR36X - AR45X
14V
CN15
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Power
External Heater, other.
1min
DUCT TYPE
AR36X - AR45X
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
External
Heater
Supply air
Indoor unit
Return air
- (05 - 34) -
Page 36
1
2
3
4
1Room temperature correct coefficient of heating
2External input select
3Auto restart validity/invalidity
Rotary SWSW 3Indoor unit number setting
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
Jumper Wire
INDOOR UNIT
DIP SW
SW 1
SW 2
5-16. FUNCTION SETTING
5-16-1. INDOOR UNIT
Low static pressure function setting
Forbidden
SWITCH POSITION
Duct type Indoor unit control circuit board
MAIN PCBPOWER PCB
CN114
SW1SW2
1 2 31 2 34
DUCT TYPE
AR36X - AR45X
CN106
CN115
CN16
CN14
CN15
ON
OFF
SW1 SW2
SW3
CN4
CN5
ON
OFF
JM1
JM2
JM3
DUCT TYPE
AR36X - AR45X
CN16
- (05 - 35) -
Page 37
5-16-2. SWITCH FUNCTION (INDOOR UNIT)
SW1-1SW state
OFFNormal
ONLow static pressure
SW1-2OFF
SW1-3OFF
SW1-4OFF
SW2-1SW state
OFF +4 deg (Ceiling setting)
ON0 deg (Room setting)
SW2-2SW state
OFFEdge
ONPulse
SW2-3SW state
OFFValidity
ONInvalidity
SW3SW state
0single
1-15Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
(Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
(Factory setting)
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature correction
DUCT TYPE
AR36X - AR45X
(Factory setting)
DUCT TYPE
AR36X - AR45X
2-2 External input select edge/pulse
This switch is used to select the format of external input command as shown in the table below.
(Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
(Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
(Factory setting)
- (05 - 36) -
Page 38
JUMPER WIRE SETTING
ConnectorINPUTOUTPUTREMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115-OPERATION DISPLAY
CN14-FRESH AIR
CN15-ELECTRICAL HEATER
See external
input/output settings
for details.
JM2JM state
ConnectResidencial
DisconnectCommercial
JM3JM state
ConnectInvalidity
DisconnectValidity
JM1JM state
Connect0 deg
Disconnect+ 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
(Factory setting)
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode.
When you select "FAN:AUTO"mode fan goes in "HIGH"
(Factory setting)
Fan delay setting
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating
with an auxiliary heater,the fan operation continues one minutes.
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
ONMultiple unit connection
1-3 Model setting
DUCT TYPE
AR36X - AR45X
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( )
( )
(
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Factory setting)
Model
DUCT TYPE
AR36X - AR45X
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
Invalidity
- (05 - 39) -
Page 41
5-17. OPTIONAL PARTS
SIMPLE REMOTE CONTROLLERS
UTB - YPB : FUJITSU BRAND
UTB - GPB : GENERAL BRAND
UTB - TPB : Australia only
Remote controller which gives priority to ease-of-use and allows operation
of the necessary functions only.
REMOTE SENSOR UNIT
UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller.
Because the remote controller has the switching function, the user can select the position of the
sensor. (Room temperature sensor selection)
Remote Sensor
in the bed room (effective at night)
Simple remote
controllers
Example of room temperature
sensor selection
Sensor part
DUCT TYPE
AR36X - AR45X
Remote Controller
in the living room (effective during the day)
THERMO
Day
Wired Remote Controller
The detecting point can be freely changed.
SENSOR
Night
Remote Sensor (Optional Parts)
DUCT TYPE
AR36X - AR45X
LONG LIFE FILTER
UTD - LF25NA
Intake air filter can be mounted to the indoor unit.
- (05 - 40) -
Page 42
SQUARE FLANGE (UTD - SF045T)
ROUND FLANGE (UTD - RF204)
Round flange is used when the fresh air duct is installed.
DUCT TYPE
AR36X - AR45X
Air intake hole
Round flange
DUCT TYPE
AR36X - AR45X
- (05 - 41) -