1.Low static pressure mode 1 air volume at 85Pa (fan speed:high)
2.Normal Mode Air volume at 100Pa (fan speed:high)
When installed, normal middle static pressure mode, and low static
pressure mode can be selected by switching over using DIP switch
on the board in the control box. Therefore, these models can be operated under the wide range of conditions.
(230V)
/h)
3
Air volume (m
085 100
Static pressure (Pa)
12
DUCT TYPE
AR45
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape
is now united with main unit (DIP Switch is
located on the internal substrate.)
One-touch operating and easy-to-install
long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further compactification is attained by reducing 65 mm from the width with the flanking
control box embedded inside the chassis.
- (04 - 01) -
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and
rear, and the internal fan casing is also made dismountable in two pieces namely,
upper and lower ones.
DUCT TYPE
AR45
The motor and fan maintenance and dismounting can be made easily by removing
the rear panel and lower part of the casing with the main chassis installed.
DUCT TYPE
AR45
- (04 - 02) -
Page 4
4-2. REMOTE CONTROLLER
4-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible.
Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature
setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16)
Error indication.(A maximum of 16 error histories are memorizable.)
Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible.
Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature
accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
DUCT TYPE
AR45
Wired
remote
controller
Weekly
timer
Setback
timer
DUCT TYPE
AR45
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day
of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example
(Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen
after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer
area
Operation
area
Possible to set temperature for two time spans and
for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example
(Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard
switch boxes. Flat back construction allows
equipment to be installed wherever it is
needed.
[
Variable timer control
]
The operation/display sections are zoned according to time and operation, enabling variable programming to match application.
- (04 - 03) -
European
switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2
7
8
9
10
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETESET
12 15 18 21
DAY
DAY OFF
SA
13
1
3
ENERGY
SAVE
THERMO
SENSOR
4
6
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
11
12
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER)
Set the current time.
8
Day (DAY OFF) button
Display panel
DUCT TYPE
AR45
14
15
1617 18
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
10
Set time button
DUCT TYPE
AR45
Pessed to select the set back timer.
SUMOTUWETH FR
SA
11
Delete button
The schedule of a weekly timer is deleted.
369
12 15 18 21
1920
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETESET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm)120 x 120 x 17
WEIGHT( g )160
CABLE LENGTH( m )
POWER( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display
Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (04 - 04) -
Page 6
4-3. SPECIFICATIONS
AR 45LUAN
AO 45LJBYL
230V 50Hz
198-264V
Rows x Stagesmm4 x 14
Fin Pitch1.4
Rows x Stagesmm2 x 60
Fin Pitch1.3
FAN MOTOR THERMAL PROTECTOR
PCB FUSE
FAN MOTOR THERMAL PROTECTOR
PCB FUSE
9.52(3/8 inc.)
15.88(5/8 inc.)
Steel
Outer diameter 38.0
Inner diameter 36.0
AVAILABLE VOLTAGE RANGE
PIPE
MAX HEIGHT
CONNECTION METHOD
SIZE
mm
kg(lbs)
DIMENSIONS
H × W × D
NET
GROSS
TYPE
OUTDOOR
CASING COLOR
STARTING METHOD
Surface treatment
NET /
GROSS
WEIGHT
mm
MAX LENGTH
REMOTE CONTROLLER
DRAIN PIPE
MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
REFRIGERANT OIL
kW
SAFETY DEVICES
OUTDOOR
AIR
CIRCULATION
INPUT POWER
TYPE
COMPRESSOR
HEAT
EXCHANGER
TYPE
MOISTURE REMOVAL
CURRENT
kW/kW
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
A
STARTING CURRENT
INDOOR
m3/h
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
INDOOR
COOLING
HEATING
CAPACITY
RATED/MAX
RATED/MAX
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL
(SOUND
PRESSURE)
COOL/HEAT
Surface treatment
Coil
INDOOR
Coil
dB(A)
INDOOR
COOLINGRATED/MAX4.45/5.15
HEATINGRATED/MAX3.95/5.15
COOLINGRATED/MAX19.5/22.6
HEATINGRATED/MAX17.3/22.5
EER COOLING2.81
COP HEATING3.54
High2290
Med2150
Low2000
INDOORSirocco x 2
OUTDOORPropeller x 2
INDOOR275
DUCT TYPE
AR45
OUTPUTW2500
OUTDOOR103 × 2
High44.0/44.0
Med42.0/42.0
Low40.0/40.0
DUCTED MODELS
REVERSE CYCLE TYPE
kW12.5/14.0
BTU/h42700/47800
kW14.0/17.0
BTU/h47800/61500
A15
l/h (pints/h)4.0(8.5)
6600
Pa30 to 150
52.0/53.0
DC SCROLL(INVERTER)
Inverter Method
Plate fin coil
Hydrophilic coating
DUCT TYPE
AR45
Coil Dimensionsmm294 x 1000 x 53.2
Plate fin coil
Corrosion resistant coating
Coil Dimensionsmm1260 x 900 x 36.38
INDOOR
OUTDOOR
INDOORGalvanized steel sheet
OUTDOORBeige(10YR7.5/1.0NN)
INDOOR270 x 1135 x 700
OUTDOOR1290 x 900 x 330
INDOOR300 x 1300 x 790
OUTDOOR1430 x 1050 x 445
INDOOR45/52(99/115)
OUTDOOR105/112(231/247)
FLARE
LIQUID
GAS
m70(chargeless:20m)
m30
R410A
CHARGEkg3.4
Synthetic (POE oil)
COOLING-15 to 43
HEATING-15 to 24
WIRED(AR-3TA1)
Note:Specifications are based on the following conditions.
Cooling:Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB.
Heating:Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB.
Standard static pressure : 30Pa
Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (04 - 05) -
Page 7
4-4. DIMENSIONS
4-4-1. OUTDOOR UNIT
MODEL : AO 45L
(Unit : mm)
Top view
900
1290
DUCT TYPE
AR45
21
7731
12330
DUCT TYPE
AR45
Front view
370
Drain cap
mounting places
Drain cap
mounting place
Bottom view
MOUNTING POSITION
When there are
obstacles at the
back or front side.
When there are obstacles
at the back and front sides.
9
Air flow
Side view
4-Ø12mm hole
When there are obstacles at
the back, side(s), and top.
400
151
170
196
99
When there are obstacles
at the back side with the
installation of more than
one unit.
100 mm
or more
600 mm
or more
100 mm
or more
100 to 300 mm *
* If the space is larger than that is stated, the condition
will be the same as that there are no obstacles.
25
0
(
Se
m
m
r
v
or
i
c
e
mor
s
pac
e
e
)
- (04 - 06) -
600 to 1000 mm
300 mm
or more
250 mm
or more
250 mm
or more
300 mm
or more
Page 8
4-4-2. INDOOR UNIT
MODEL :
AR45L
(Unit : mm)
Front view
DUCT TYPE
DUCT TYPE
AR45
AR45
Side view (L)
Top view
Side view (R)
Rear view
Refrigerant piping flare connection (Gas)
Refrigerant piping flare connection (Liquid)
Drain piping connection (Drain pipe : I.D. 36 O.D. 38)
Drain piping connection with cap.
Knock out hole for fresh air.
- (04 - 07) -
Page 9
MOUNTING POSITION
300mm
or more
150mm
or more
MAINTENANCE HOLE
It shall be possible to install and remove
the control box.
DUCT TYPE
AR45
When using a square duct
It shall be possible to install and remove
the control box, fan units and filter.
AFR: Air flow rate (m3/min)
TC : Total capacity (kW)
SHC: Sensible Heat capacity (kW)
PI : Power Input (kW)
DUCT TYPE
AR45
AR
45L / AO
TCPITCPITCPITCPITCPITCPITCPI
45L
DUCT TYPE
AR45
- (04 - 13) -
Page 15
4-8. CAPACITY COMPENSATION FOR PIPE LENGTH
Pipe length (m)
Pipe length (m)
COOLING
PIPE LENGTH (m)
PIPE LENGTH (m)
Outdoor unit is
bottom-side
Outdoor unit is
bottom-side
Outdoor unit is
up-side
HEIGHT DIFFERENCE (m)
HEIGHT DIFFERENCE (m)
HEATING
Outdoor unit is
up-side
AND HEIGHT DIFFERENCE
AR
MODELS:
45L / AO
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
COOLINGHEATING
1.200
1.150
1.100
1.050
1.000
0.950
0.900
0.850
Coefficient of compensation
0.800
010203040506070
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
45L
1.200
1.150
1.100
1.050
1.000
0.950
0.900
Coefficient of compensation
0.850
0.800
010203040506070
DUCT TYPE
DUCT TYPE
AR45
AR45
57.510203040506070
30----0.9070.8800.8580.8370.817
20---0.9400.9070.8800.8580.8370.817
10--0.9850.9400.9070.8800.8580.8370.817
7.5-1.0000.9850.9400.9070.8800.8580.8370.817
51.0001.0000.9850.9400.9070.8800.8580.8370.817
01.0001.0000.9850.9400.9070.8800.8580.8370.817
-50.9920.9920.9770.9320.9000.8730.8510.8300.811
-7.5-0.9880.9730.9290.8960.8690.8470.8270.808
-10--0.9690.9250.8920.8660.8440.8230.804
-20---0.9100.8780.8520.8300.8100.791
-30----0.8630.8380.8170.7970.778
57.510203040506070
30---0.9230.9120.8990.8860.874
20---0.9490.9330.9210.9080.8960.883
10--0.9800.9580.9420.9310.9170.9050.892
7.5-0.9930.9830.9610.9450.9330.9200.9070.894
50.9950.9950.9850.9630.9470.9360.9220.9090.896
01.0001.0000.9900.9680.9520.9400.9270.9140.901
-51.0001.0000.9900.9680.9520.9400.9270.9140.901
-7.5-1.0000.9900.9680.9520.9400.9270.9140.901
-10--0.9900.9680.9520.9400.9270.9140.901
-20---0.9680.9520.9400.9270.9140.901
-30----0.9520.9400.9270.9140.901
- (04 - 14) -
Page 16
4-9. ADDITIONAL CHARGE CALCULATION
DUCTED MODEL
HEAT PUMP TYPE
AR*45L
AO*45L
R410A
m20
3400
3400
3400+400
3400+800
3400+1200
3400+1600
3400+2000
40
60m
50m
70m
TYPE
MODEL NAME
INDOOR
OUTDOOR
g/m
ADDITIONAL CHARGE
PRECHARGE
REFREGERANT TYPE
PIPE LENGTH
g
20m
40m
AMOUNT
30m
MODELS : AR
45L / AO
45L
REFRIGERANT CHARGE
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 15) -
Page 17
4-10. OPERATION RANGE
Indoor unitOutdoor unitIndoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32
℃
About 80% or less-15 to 43
℃
Heating16 to 30
℃
--15 to 24
℃
Operation Range
Model
AO*45L
AR*45L
Mode
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 16) -
Page 18
4-11. FAN PERFORMANCE AND AIR FLOW
m3/h
2290218019601800160013301120
m3/h
215020301840168014901230-
m3/h
20001870169015501370--
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
4-11-1. NORMAL MODE
MODEL : AR
45L
230V
305080100120140150
l/s636606544500444369311
CFM1348128311541059942783659
l/s597564511467414342-
CFM126511951083989877724-
l/s556519469431381--
CFM11771101995912806--
Q-h Characteris tic curve
160
DUCT TYPE
AR45
140
120
100
COOLING
Hi
Med
Low
DUCT TYPE
AR45
80
60
40
20
0
1000150020002500
COOLING
105.0
Air temp
100.0
95.0
90.0
85.0
Capacity
Cooling capacity(%)STATIC PRESSURE(Pa)
80.0
1,0001,5002,0002,500
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
6.0
°C)
Air temperature(
HEATING
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0
1,0001,5002,0002,500
Air temp
Capacity
55.0
53.0
51.0
49.0
47.0
45.0
43.0
41.0
39.0
°C)
Air temperature(
AIR FLOW (m3/h)
Testcondition:NofilterandFanmode.
- (04 - 17) -
Page 19
4-11-2. LOW STATIC MODE
m3/h
2140203019101680
m3/h
196018701750-
m3/h
178016901580-
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
MODEL : AR
45L
230V
305070100
l/s594564531467
CFM126011951124989
l/s544519486-
CFM115411011030-
l/s494469439-
CFM1048995930-
Q-h Characteris tic curve
120
DUCT TYPE
AR45
100
80
Hi
Med
Low
DUCT TYPE
AR45
60
40
20
0
1000150020002500
105.0
100.0
95.0
90.0
85.0
Cooling capacity(%)STATIC PRESSURE(Pa)
80.0
1,0001,5002,0002,500
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0
1,0001,5002,0002,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (04 - 18) -
COOLING
HEATING
Air temp
Capacity
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
6.0
55.0
53.0
51.0
49.0
47.0
45.0
43.0
41.0
39.0
°C)
Air temperature(
°C)
Air temperature(
Page 20
4-12. NOISE LEVEL CURVE
4-12-1. OUTDOOR UNIT
MODEL : AO 45L
Condition
Voltage : 230V /50Hz
Static pressure : 30Pa
COOLING
80
70
NC-65
60
50
40
DUCT TYPE
AR45
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR45
0
631252505001,0002,0004,0008,000
Octave band center frequency, Hz
0
631252505001,0002,0004,0008,000
Octave band center frequency, Hz
- (04 - 19) -
Page 21
4-12-2. INDOOR UNIT
HIGH
HIGH
LOW
MODEL : AR 45L
Condition
Voltage : 230V /50Hz
Static pressure : 30Pa
COOLING
80
70
NC-65
60
50
40
DUCT TYPE
AR45
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
LOW
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR45
0
631252505001,0002,0004,0008,000
Octave band center frequency, Hz
0
631252505001,0002,0004,0008,000
Octave band center frequency, Hz
- (04 - 20) -
Page 22
SOUND LEVEL CHECK POINT
INDOOR UNIT (DUCT TYPE)
DUCT TYPE
DUCT TYPE
AR45
AR45
OUTDOOR UNIT
- (04 - 21) -
Page 23
4-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker)
Current
AR45L
AO45L
50
15
230
0.34 x 2
6.03027
0.067 × 2
0.150
0.670
Outdoor Fan Motor
Indoor Fan Motor
*1) Wiring Spec
Starting Current
Model Name
Indoor unit
Outdoor unit
Mode
Rated Value
Power Supply
MODELS : AR 45L / AO 45L
VoltageV
Frequency
Hz
CoolingHeating
CurrentA19.517.3
InputkW4.453.95
Max Operating CurrentA22.622.5
A
A
Power Cable
mm
2
*2)Limited wiring lengthm
DUCT TYPE
AR45
InputkW
DUCT TYPE
AR45
Full Load Amp.A
InputkW
Full Load Amp.A
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger
- (04 - 22) -
Page 24
4-14. SAFETY DEVICE
PROTECTION FORM
AR45L
PROTECTION FORM
AO45L
FUSE
(SIDE OF INDOOR UNIT TERMINAL)
3.15A 250V
5A 250V
165°C±5°C OFF
OUTDOOR UNIT
MODEL NAME
-10A 250V
FUSE ON MAIN PCB-
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C±5°C OFF
COMPRESSOR -
HIGH PRESSURE PROTECTION -4.2MPa
TERMINAL FUSETHERMAL FUSE-
INDOOR UNIT
MODEL NAME
DUCT TYPE
PCB FUSE-3.15A 250V
AR45
FAN MOTOR PROTECTORTHERMAL PROTECTOR150°C±5°C OFF
DUCT TYPE
AR45
- (04 - 23) -
Page 25
4-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
TION
When the external input / output is used,
connect the external signal wire as shown
in the figure below.
CONTROL
INPUT
[Example]
You can control air conditioner on/off by
external control. You can select either
Edge and Pulse.
Indoor
unit
+
1
2
3
Ch1
-
CN114
DUCT TYPE
AR45
(White)
Field supply
DUCT TYPE
AR45
DIP Switch (Indoor Unit)
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1
(Input)
Remote
controller
Indoor
unit
On
Off
On
Operation
Stop
2 Pulse
Ch1
(Input)
Remote
controller
Indoor
unit
Operation
Stop
200ms200ms200ms
On
- (04 - 24) -
Off
Page 26
OPERA
[Example]
TION DISPLA
Y
Operation
indicator
Field
supply
Operation
Ic
Vc
or
Vc : DC20V or less
Ic : 10mA or less
Indoor
unit
CN115
(WHITE)
+
2
1
-
Indoor
unit
Stop
SHORT
CN115
(Output)
DUCT TYPE
AR45
FRESH
AIR OUTPUT SETTING
OPEN
DUCT TYPE
AR45
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
Indoor
unit
-
CN14
(GREEN)
1
2
Indoor
unit fan
CN14
(Output)
Field supplied
Operation
Stop
14V
0V
Fuse
Power
Fan, other
- (04 - 25) -
Page 27
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation.
When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON.
When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode.
1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor
unit
+
1
2
-
CN15
(ORANGE)
DUCT TYPE
AR45
Indoor
unit
Heating
Indoor
Operation
Stop
Operation
Field supplied
unit fan
Stop
14V
CN15
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Power
External Heater, other.
1min
DUCT TYPE
AR45
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork.
Please be sure to use delay control of a fan.
Press the this push-button switch, and "PUMP DOWN OPERATION" is starting.
AR45
AR45
- (04 - 28) -
Page 30
4-16-3. INDOOR UNIT
INDOOR UNIT
1
Low static pressure function setting
SW 1
DIP SW
SW 2
Rotary SWSW 3Indoor unit number setting
Jumper Wire
SWITCH POSITION
Duct type Indoor unit control circuit board
2
Forbidden
3
4
1Room temperature correct coefficient of heating
2External input select
3Auto restart validity/invalidity
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
DUCT TYPE
DUCT TYPE
AR45
POWER PCB
CN114
CN106
CN115
MAIN PCB
ON
OFF
CN4
CN5
CN16
CN14
CN15
SW1SW2
1 2 31 2 34
SW1 SW2
SW3
ON
OFF
JM1
JM2
JM3
AR45
- (04 - 29) -
CN16
Page 31
4-16-4. SWITCH FUNCTION (INDOOR UNIT)
SW1-1SW state
OFFNormal
ONLow static pressure
SW1-2OFF
SW1-3OFF
SW1-4OFF
SW2-1SW state
OFF +4 deg (Ceiling setting)
ON0 deg (Room setting)
SW2-2SW state
OFFEdge
ONPulse
SW2-3SW state
OFFValidity
ONInvalidity
SW3SW state
0single
1-15Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
(Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
(Factory setting)
2-1 Room temperature correct coefficient of heating.
DUCT TYPE
AR45
Decide the heating temperature correct coefficient vale of heating.
DUCT TYPE
AR45
Heat temperature correction
(Factory setting)
2-2 External input select edge/pulse
This switch is used to select the format of external input command as shown in the table below.
(Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
(Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
(Factory setting)
- (04 - 30) -
Page 32
JUMPER WIRE SETTING
JM2JM state
ConnectResidencial
DisconnectCommercial
JM3JM state
ConnectInvalidity
DisconnectValidity
ConnectorINPUTOUTPUTREMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115-OPERATION DISPLAY
CN14-FRESH AIR
CN15-ELECTRICAL HEATER
See external
input/output settings
for details.
JM1JM state
Connect0 deg
Disconnect+ 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
(Factory setting)
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode.
When you select "FAN:AUTO"mode fan goes in "HIGH"
(Factory setting)
DUCT TYPE
Fan delay setting
AR45
DUCT TYPE
AR45
This setting can be used when the auxiliary heater is mounted.
When the fan operation is stopped when the indoor unit is operating
with an auxiliary heater,the fan operation continues one minutes.
Set the remote controller DIP switch No.1 and 2 according to the following table.
(Factory setting)
Number of
remote
controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple)
This is switched according to the number of connected indoor units.
DIP-SW
DUCT TYPE
AR45
No.3
OFF
Master unitSlave unit
DIP-SW
No.1
DIP-SW
No.2
ON
OFF
(Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW
No.1
ONON
DIP-SW
No.2
DUCT TYPE
AR45
ONMultiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
(Factory setting)
DIP-SW
No.4
OFF
ONCooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
(Factory setting)
DIP-SW
No.5
OFF
ONValidity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used,
all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
(Factory setting)
DIP-SW
No.6
OFF
ONValidity
Memory backup
Invalidity
- (04 - 33) -
Page 35
4-17. OPTIONAL PARTS
SIMPLE REMOTE CONTROLLERS
UTB - YPB : FUJITSU BRAND
UTB - GPB : GENERAL BRAND
UTB - TPB : Australia only
Remote controller which gives priority to ease-of-use and allows operation
of the necessary functions only.
REMOTE SENSOR UNIT
UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller.
Because the remote controller has the switching function, the user can select the position of the
sensor. (Room temperature sensor selection)
DUCT TYPE
AR45
Example of room temperature
sensor selection
Simple remote
controllers
Remote Sensor
in the bed room (effective at night)
DUCT TYPE
AR45
Sensor part
Wired Remote Controller
THERMO
Day
The detecting point can be freely changed.
SENSOR
Night
Remote Controller
in the living room (effective during the day)
Remote Sensor (Optional Parts)
LONG LIFE FILTER
UTD - LF25NA
Intake air filter can be mounted to the indoor unit.
- (04 - 34) -
Page 36
SQUARE FLANGE (UTD - SF045T)
ROUND FLANGE (UTD - RF204)
Round flange is used when the fresh air duct is installed.
DUCT TYPE
DUCT TYPE
AR45
AR45
Air intake hole
Round flange
- (04 - 35) -