General ARH45L, ARH45LUAN, AOH45LJBYL Technical Manual

Page 1
R410A
4 . DUCT TYPE :  AR 45LUAN
D2D_AR003E/03
2006.05.30
Page 2
MODEL : AR 45LUAN / AO 45LJBYL
FEATURES
Installation styles
Embedded in Ceiling
Hanging from Ceiling
DUCT TYPE
AR45
Low static pressure mode function
1.Low static pressure mode 1 air volume at 85Pa (fan speed:high)
2.Normal Mode Air volume at 100Pa (fan speed:high)
When installed, normal middle static pressure mode, and low static pressure mode can be selected by switching over using DIP switch on the board in the control box. Therefore, these models can be op­erated under the wide range of conditions.
(230V)
/h)
3
Air volume (m
0 85 100
Static pressure (Pa)
1 2
DUCT TYPE
AR45
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape is now united with main unit (DIP Switch is located on the internal substrate.)
One-touch operating and easy-to-install long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further com­pactification is attained by reducing 65 mm from the width with the flanking control box embedded inside the chassis.
- (04 - 01) -
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and rear, and the internal fan casing is also made dismountable in two pieces namely, upper and lower ones.
DUCT TYPE
AR45
The motor and fan maintenance and dismounting can be made easily by removing the rear panel and lower part of the casing with the main chassis installed.
DUCT TYPE
AR45
- (04 - 02) -
Page 4
4-2. REMOTE CONTROLLER
4-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in
DUCT TYPE
AR45
Wired
remote
controller
Weekly
timer
Setback
timer
DUCT TYPE
AR45
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer area
Operation area
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
- (04 - 03) -
European switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2 7 8
9
10
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETE SET
12 15 18 21
DAY
DAY OFF
SA
13
1 3
ENERGY
SAVE
THERMO SENSOR
4
6
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
11
12
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Display panel
DUCT TYPE
AR45
14
15
1617 18
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
10
Set time button
DUCT TYPE
AR45
Pessed to select the set back timer.
SUMOTUWETH FR
SA
11
Delete button
The schedule of a weekly timer is deleted.
369
12 15 18 21
1920
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display Indicates during the oil recovery and defrosting operation.
20
Energy save display
- (04 - 04) -
Page 6
4-3. SPECIFICATIONS
AR 45LUAN
AO 45LJBYL
230V 50Hz
198-264V
Rows x Stages mm 4 x 14
Fin Pitch 1.4
Rows x Stages mm 2 x 60
Fin Pitch 1.3
FAN MOTOR THERMAL PROTECTOR
PCB FUSE
FAN MOTOR THERMAL PROTECTOR
PCB FUSE
9.52(3/8 inc.)
15.88(5/8 inc.)
Steel
Outer diameter 38.0
Inner diameter 36.0
AVAILABLE VOLTAGE RANGE
PIPE
MAX HEIGHT
CONNECTION METHOD
SIZE
mm
kg(lbs)
DIMENSIONS H × W × D NET
GROSS TYPE
OUTDOOR
CASING COLOR STARTING METHOD
Surface treatment
NET / GROSS
WEIGHT
mm
MAX LENGTH
REMOTE CONTROLLER
DRAIN PIPE MATERIAL
REFRIGERANT
SIZE
TYPE
OPERATION(OUTDOOR)
°C
REFRIGERANT OIL
kW
SAFETY DEVICES
OUTDOOR
AIR CIRCULATION INPUT POWER
TYPE
COMPRESSOR
HEAT EXCHANGER TYPE
MOISTURE REMOVAL
CURRENT
kW/kW
RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
A
STARTING CURRENT
INDOOR
m3/h
TYPE
MODEL NAME
OUTDOOR
POWER SOURCE
INDOOR
COOLING
HEATING
CAPACITY
RATED/MAX
RATED/MAX
FAN MOTOR OUTPUT
W
OUTDOOR
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
Surface treatment
Coil
INDOOR
Coil
dB(A)
INDOOR
COOLING RATED/MAX 4.45/5.15
HEATING RATED/MAX 3.95/5.15
COOLING RATED/MAX 19.5/22.6
HEATING RATED/MAX 17.3/22.5
EER COOLING 2.81
COP HEATING 3.54
High 2290
Med 2150
Low 2000
INDOOR Sirocco x 2
OUTDOOR Propeller x 2
INDOOR 275
DUCT TYPE
AR45
OUTPUT W 2500
OUTDOOR 103 × 2
High 44.0/44.0
Med 42.0/42.0
Low 40.0/40.0
DUCTED MODELS
REVERSE CYCLE TYPE
kW 12.5/14.0
BTU/h 42700/47800
kW 14.0/17.0
BTU/h 47800/61500
A 15
l/h (pints/h) 4.0(8.5)
6600
Pa 30 to 150
52.0/53.0
DC SCROLL(INVERTER)
Inverter Method
Plate fin coil
Hydrophilic coating
DUCT TYPE
AR45
Coil Dimensions mm 294 x 1000 x 53.2
Plate fin coil
Corrosion resistant coating
Coil Dimensions mm 1260 x 900 x 36.38
INDOOR
OUTDOOR
INDOOR Galvanized steel sheet
OUTDOOR Beige(10YR7.5/1.0NN)
INDOOR 270 x 1135 x 700
OUTDOOR 1290 x 900 x 330
INDOOR 300 x 1300 x 790
OUTDOOR 1430 x 1050 x 445
INDOOR 45/52(99/115)
OUTDOOR 105/112(231/247)
FLARE
LIQUID
GAS
m 70(chargeless:20m)
m 30
R410A
CHARGE kg 3.4
Synthetic (POE oil)
COOLING -15 to 43
HEATING -15 to 24
WIRED(AR-3TA1)
Note: Specifications are based on the following conditions. Cooling: Indoor temperature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CWB. Standard static pressure : 30Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
- (04 - 05) -
Page 7
4-4. DIMENSIONS
4-4-1. OUTDOOR UNIT
MODEL : AO 45L
(Unit : mm)
Top view
900
1290
DUCT TYPE
AR45
21
77 31
12330
DUCT TYPE
AR45
Front view
370
Drain cap mounting places
Drain cap mounting place
Bottom view
MOUNTING POSITION
When there are obstacles at the back or front side.
When there are obstacles at the back and front sides.
9
Air flow
Side view
4-Ø12mm hole
When there are obstacles at the back, side(s), and top.
400
151
170
196
99
When there are obstacles at the back side with the installation of more than one unit.
100 mm
or more
600 mm
or more
100 mm or more
100 to 300 mm *
* If the space is larger than that is stated, the condition
will be the same as that there are no obstacles.
25
0
(
Se
m
m
r
v
or
i
c
e
mor
s
pac
e
e
)
- (04 - 06) -
600 to 1000 mm
300 mm or more
250 mm or more
250 mm or more
300 mm or more
Page 8
4-4-2. INDOOR UNIT
MODEL :
AR 45L
(Unit : mm)
Front view
DUCT TYPE
DUCT TYPE
AR45
AR45
Side view (L)
Top view
Side view (R)
Rear view
Refrigerant piping flare connection (Gas) Refrigerant piping flare connection (Liquid) Drain piping connection (Drain pipe : I.D. 36 O.D. 38) Drain piping connection with cap. Knock out hole for fresh air.
- (04 - 07) -
Page 9
MOUNTING POSITION
300mm
or more
150mm or more
MAINTENANCE HOLE
It shall be possible to install and remove the control box.
DUCT TYPE
AR45
When using a square duct
It shall be possible to install and remove the control box, fan units and filter.
(Unit : mm)
DUCT TYPE
AR45
- (04 - 08) -
Page 10
4-5. REFRIGERANT CIRCUIT
MODELS : AR 45L / AO 45L
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 09) -
Page 11
4-6. WIRING DIAGRAMS
4-6-1. OUTDOOR UNIT
MODEL : AO 45L
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 10) -
Page 12
4-6-2. INDOOR UNIT
MODEL : AR 45L
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 11) -
Page 13
4-7. CAPACITY TABLE
32 °CDB
21 °CWB
22 °CWB
23 °CWB
21 °CDB
23 °CDB
15 °CWB
16 °CWB
Outdoor temperature
Indoor temperature
26 °CDB
27 °CDB
29 °CDB
18 °CWB
19 °CWB
30 °CDB
4-7-1. COOLING (Maximum)
COOLING CAPACITY
MODELS :
AFR 38.2
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
-15 10.59 9.24 2.06 11.13 10.01 2.08 12.07 11.33 2.11 12.55 11.35 2.13 13.50 11.39 2.17 13.99 11.41 2.19 14.49 12.31 2.20
-10 12.64 10.10 2.45 12.97 11.00 2.46 13.63 11.79 2.49 13.95 11.70 2.51 14.57 11.48 2.53 14.86 11.35 2.54 15.12 12.12 2.55
0 11.59 9.20 3.05 11.86 10.08 3.07 12.42 10.85 3.11 12.69 10.76 3.13 13.23 10.57 3.15 13.48 10.47 3.16 13.73 11.27 3.17
10 11.02 8.95 3.36 11.30 9.84 3.38 11.85 10.63 3.42 12.13 10.55 3.43 12.66 10.37 3.46 12.94 10.28 3.48 13.19 11.09 3.49
20 13.27 9.96 3.53 13.69 10.88 3.53 14.54 11.76 3.52 14.99 11.72 3.52 15.91 11.67 3.50 16.33 11.62 3.48 16.78 12.48 3.47
30 11.71 9.26 4.24 12.12 10.19 4.25 12.95 11.06 4.26 13.37 11.03 4.27 14.23 10.93 4.27 14.66 10.88 4.27 15.06 11.73 4.27
35 11.68 9.25 5.13 12.09 10.18 5.16 12.86 11.04 5.13 14.00 11.00 5.15 14.02 11.14 5.18 14.43 10.79 5.13 14.82 11.64 5.15
40 10.12 8.41 5.00 10.37 9.27 5.00 10.97 10.08 5.00 11.34 10.09 5.00 12.55 10.00 5.00 12.29 9.99 5.00 12.63 10.83 5.00
43 9.28 8.05 5.00 9.62 8.95 5.00 10.26 9.79 5.00 10.63 9.76 5.00 11.18 9.63 5.00 11.51 9.58 5.00 11.84 10.40 5.00
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
DUCT TYPE
AR45
AR 45L / AO 45L
DUCT TYPE
AR45
- (04 - 12) -
Page 14
4-7-2. HEATING (Maximum)
(°CWB)
Outdoor temperature
Indoor temperature
16°CDB
18°CDB
25°CDB
27°CDB
30°CDB
20°CDB
23°CDB
HEATING CAPACITY
MODELS :
AFR 38.2
(°CDB)
-15 -16 7.98 3.64 7.81 3.71 7.66 3.76 7.01 3.82 6.92 3.90 6.79 3.98 6.61 4.06
-10 -11 10.41 4.24 10.18 4.31 9.95 4.38 9.59 4.50 9.47 4.74 9.09 4.70 8.64 4.72
-4 -6 11.99 4.43 11.72 4.51 11.46 4.59 10.98 4.69 10.65 4.71 10.31 4.73 9.74 4.74
1 -1 13.80 4.69 13.44 4.70 13.09 4.73 12.45 4.73 11.98 4.70 11.59 4.72 10.93 4.72
7 6 18.00 5.15 17.60 5.15 17.00 5.15 16.00 5.15 14.79 5.15 14.12 5.15 13.24 5.15
12 10 19.07 5.15 18.50 5.15 17.91 5.15 17.16 5.15 16.43 5.15 15.85 5.15 14.82 5.15
18 13 19.94 5.15 19.52 5.15 18.91 5.15 18.03 5.15 17.43 5.15 16.76 5.15 15.64 5.15
20 15 19.65 5.15 19.11 5.15 18.71 5.15 17.84 5.15 17.08 5.15 16.49 5.15 15.46 5.15
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
DUCT TYPE
AR45
AR
45L / AO
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
45L
DUCT TYPE
AR45
- (04 - 13) -
Page 15
4-8. CAPACITY COMPENSATION FOR PIPE LENGTH
Pipe length (m)
Pipe length (m)
COOLING
PIPE LENGTH (m)
PIPE LENGTH (m)
Outdoor unit is
bottom-side
Outdoor unit is
bottom-side
Outdoor unit is
up-side
HEIGHT DIFFERENCE (m)
HEIGHT DIFFERENCE (m)
HEATING
Outdoor unit is
up-side
AND HEIGHT DIFFERENCE
AR
MODELS:
45L / AO
COEFFICIENT OF COMPENSATION FOR PIPE LENGTH
COOLING HEATING
1.200
1.150
1.100
1.050
1.000
0.950
0.900
0.850
Coefficient of compensation
0.800
0 10 20 30 40 50 60 70
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
45L
1.200
1.150
1.100
1.050
1.000
0.950
0.900
Coefficient of compensation
0.850
0.800
0 10 20 30 40 50 60 70
DUCT TYPE
DUCT TYPE
AR45
AR45
5 7.5 10 20 30 40 50 60 70
30 - - - - 0.907 0.880 0.858 0.837 0.817
20 - - - 0.940 0.907 0.880 0.858 0.837 0.817
10 - - 0.985 0.940 0.907 0.880 0.858 0.837 0.817
7.5 - 1.000 0.985 0.940 0.907 0.880 0.858 0.837 0.817
5 1.000 1.000 0.985 0.940 0.907 0.880 0.858 0.837 0.817
0 1.000 1.000 0.985 0.940 0.907 0.880 0.858 0.837 0.817
-5 0.992 0.992 0.977 0.932 0.900 0.873 0.851 0.830 0.811
-7.5 - 0.988 0.973 0.929 0.896 0.869 0.847 0.827 0.808
-10 - - 0.969 0.925 0.892 0.866 0.844 0.823 0.804
-20 - - - 0.910 0.878 0.852 0.830 0.810 0.791
-30 - - - - 0.863 0.838 0.817 0.797 0.778
5 7.5 10 20 30 40 50 60 70
30 - - - 0.923 0.912 0.899 0.886 0.874
20 - - - 0.949 0.933 0.921 0.908 0.896 0.883
10 - - 0.980 0.958 0.942 0.931 0.917 0.905 0.892
7.5 - 0.993 0.983 0.961 0.945 0.933 0.920 0.907 0.894
5 0.995 0.995 0.985 0.963 0.947 0.936 0.922 0.909 0.896
0 1.000 1.000 0.990 0.968 0.952 0.940 0.927 0.914 0.901
-5 1.000 1.000 0.990 0.968 0.952 0.940 0.927 0.914 0.901
-7.5 - 1.000 0.990 0.968 0.952 0.940 0.927 0.914 0.901
-10 - - 0.990 0.968 0.952 0.940 0.927 0.914 0.901
-20 - - - 0.968 0.952 0.940 0.927 0.914 0.901
-30 - - - - 0.952 0.940 0.927 0.914 0.901
- (04 - 14) -
Page 16
4-9. ADDITIONAL CHARGE CALCULATION
DUCTED MODEL
HEAT PUMP TYPE
AR*45L
AO*45L
R410A
m 20
3400
3400
3400+400
3400+800
3400+1200
3400+1600
3400+2000
40
60m
50m
70m
TYPE
MODEL NAME INDOOR
OUTDOOR
g/m
ADDITIONAL CHARGE
PRECHARGE
REFREGERANT TYPE
PIPE LENGTH
g
20m
40m
AMOUNT
30m
MODELS : AR
45L / AO
45L
REFRIGERANT CHARGE
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 15) -
Page 17
4-10. OPERATION RANGE
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
Cooling
Dry
18 to 32
About 80% or less -15 to 43
Heating 16 to 30
- -15 to 24
Operation Range
Model
AO*45L
AR*45L
Mode
DUCT TYPE
DUCT TYPE
AR45
AR45
- (04 - 16) -
Page 18
4-11. FAN PERFORMANCE AND AIR FLOW
m3/h
2290 2180 1960 1800 1600 1330 1120
m3/h
2150 2030 1840 1680 1490 1230 -
m3/h
2000 1870 1690 1550 1370 - -
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
4-11-1. NORMAL MODE
MODEL : AR
45L
230V
30 50 80 100 120 140 150
l/s 636 606 544 500 444 369 311
CFM 1348 1283 1154 1059 942 783 659
l/s 597 564 511 467 414 342 -
CFM 1265 1195 1083 989 877 724 -
l/s 556 519 469 431 381 - -
CFM 1177 1101 995 912 806 - -
Q-h Characteris tic curve
160
DUCT TYPE
AR45
140
120
100
COOLING
Hi
Med
Low
DUCT TYPE
AR45
80
60
40
20
0 1000 1500 2000 2500
COOLING
105.0
Air temp
100.0
95.0
90.0
85.0
Capacity
Cooling capacity(%) STATIC PRESSURE(Pa)
80.0 1,000 1,500 2,000 2,500
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
6.0
°C)
Air temperature(
HEATING
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0
1,000 1,500 2,000 2,500
Air temp
Capacity
55.0
53.0
51.0
49.0
47.0
45.0
43.0
41.0
39.0
°C)
Air temperature(
AIR FLOW (m3/h)
Testcondition:NofilterandFanmode.
- (04 - 17) -
Page 19
4-11-2. LOW STATIC MODE
m3/h
2140 2030 1910 1680
m3/h
1960 1870 1750 -
m3/h
1780 1690 1580 -
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
MODEL : AR
45L
230V
30 50 70 100
l/s 594 564 531 467
CFM 1260 1195 1124 989
l/s 544 519 486 -
CFM 1154 1101 1030 -
l/s 494 469 439 -
CFM 1048 995 930 -
Q-h Characteris tic curve
120
DUCT TYPE
AR45
100
80
Hi
Med
Low
DUCT TYPE
AR45
60
40
20
0
1000 1500 2000 2500
105.0
100.0
95.0
90.0
85.0
Cooling capacity(%) STATIC PRESSURE(Pa)
80.0 1,000 1,500 2,000 2,500
105.0
100.0
95.0
90.0
85.0
Heating capacity(%)
80.0 1,000 1,500 2,000 2,500
Testcondition:NofilterandFanmode.
Air temp
Capacity
AIR FLOW (m3/h)
- (04 - 18) -
COOLING
HEATING
Air temp
Capacity
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
6.0
55.0
53.0
51.0
49.0
47.0
45.0
43.0
41.0
39.0
°C)
Air temperature(
°C)
Air temperature(
Page 20
4-12. NOISE LEVEL CURVE
4-12-1. OUTDOOR UNIT
MODEL : AO 45L
Condition Voltage : 230V /50Hz Static pressure : 30Pa
COOLING
80
70
NC-65
60
50
40
DUCT TYPE
AR45
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR45
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
- (04 - 19) -
Page 21
4-12-2. INDOOR UNIT
HIGH
HIGH
LOW
MODEL : AR 45L
Condition Voltage : 230V /50Hz Static pressure : 30Pa
COOLING
80
70
NC-65
60
50
40
DUCT TYPE
AR45
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
LOW
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
HEATING
80
70
60
50
40
30
20
10
Octave-band sound-pressure level dB : (0dB=0.0002µbar)
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
NC-20
NC-15
DUCT TYPE
AR45
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
- (04 - 20) -
Page 22
SOUND LEVEL CHECK POINT
INDOOR UNIT (DUCT TYPE)
DUCT TYPE
DUCT TYPE
AR45
AR45
OUTDOOR UNIT
- (04 - 21) -
Page 23
4-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
AR 45L
AO 45L
50
15
230
0.34 x 2
6.03027
0.067 × 2
0.150
0.670
Outdoor Fan Motor
Indoor Fan Motor
*1) Wiring Spec
Starting Current
Model Name Indoor unit
Outdoor unit
Mode
Rated Value Power Supply
MODELS : AR 45L / AO 45L
Voltage V
Frequency
Hz
Cooling Heating
Current A 19.5 17.3
Input kW 4.45 3.95
Max Operating Current A 22.6 22.5
A
A
Power Cable
mm
2
*2)Limited wiring length m
DUCT TYPE
AR45
Input kW
DUCT TYPE
AR45
Full Load Amp. A
Input kW
Full Load Amp. A
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger
- (04 - 22) -
Page 24
4-14. SAFETY DEVICE
PROTECTION FORM
AR 45L
PROTECTION FORM
AO 45L
FUSE (SIDE OF INDOOR UNIT TERMINAL)
3.15A 250V 5A 250V
165°C±5°C OFF
OUTDOOR UNIT
MODEL NAME
- 10A 250V
FUSE ON MAIN PCB -
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C±5°C OFF
COMPRESSOR -
HIGH PRESSURE PROTECTION - 4.2MPa
TERMINAL FUSE THERMAL FUSE -
INDOOR UNIT
MODEL NAME
DUCT TYPE
PCB FUSE - 3.15A 250V
AR45
FAN MOTOR PROTECTOR THERMAL PROTECTOR 150°C±5°C OFF
DUCT TYPE
AR45
- (04 - 23) -
Page 25
4-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
TION
When the external input / output is used, connect the external signal wire as shown in the figure below.
CONTROL
INPUT
[Example]
You can control air conditioner on/off by external control. You can select either Edge and Pulse.
Indoor unit
+
1
2
3
Ch1
-
CN114
DUCT TYPE
AR45
(White)
Field supply
DUCT TYPE
AR45
DIP Switch (Indoor Unit)
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1 (Input)
Remote controller
Indoor unit
On
Off
On
Operation
Stop
2 Pulse
Ch1 (Input)
Remote controller
Indoor unit
Operation
Stop
200ms 200ms 200ms
On
- (04 - 24) -
Off
Page 26
OPERA
[Example]
TION DISPLA
Y
Operation indicator
Field supply
Operation
Ic
Vc
or
Vc : DC20V or less Ic : 10mA or less
Indoor unit
CN115
(WHITE)
+
2
1
-
Indoor unit
Stop
SHORT
CN115 (Output)
DUCT TYPE
AR45
FRESH
AIR OUTPUT SETTING
OPEN
DUCT TYPE
AR45
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
Indoor unit
-
CN14
(GREEN)
1
2
Indoor unit fan
CN14 (Output)
Field supplied
Operation
Stop
14V
0V
Fuse
Power
Fan, other
- (04 - 25) -
Page 27
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation. When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON. When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode. 1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor unit
+
1
2
-
CN15
(ORANGE)
DUCT TYPE
AR45
Indoor unit
Heating
Indoor
Operation
Stop
Operation
Field supplied
unit fan
Stop
14V
CN15 (Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Power
External Heater, other.
1min
DUCT TYPE
AR45
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork. Please be sure to use delay control of a fan.
External Heater
Supply air
Indoor unit
Return air
- (04 - 26) -
Page 28
4-16. FUNCTION SETTING
Change current capacity No use (OFF)
1
OUTDOOR UNIT
2
3
DIP SW 1
PUSH SW
4-16-1. OUTDOOR UNIT
Pump down switch
SWITCH POSITION
Outdoor unit control circuit board
DUCT TYPE
DUCT TYPE
AR45
DIP SW 1
OFF ON
1
2
3
PUSH SW
AR45
- (04 - 27) -
Page 29
4-16-2.
18.0A
15.5A
DIP-SW1
CURRENT
(MAX.)
23.5A *1
20.0A *2
OFF
OFF
OFFONON
OFF
ON
OFF
1
OFFON23OFF
OFF
P
I
D
Current capacity setting
*1=54000BTU model's factory setting *2=45000BTU model's factory setting
S
U
P
SW2 setting
SWITCH FUNCTION (OUTDOOR UNIT)
G
N
TTI
E
S
H
TC
I
W
S
G
N
TI
T
E
S
H
C
T
I
W
S
H
DUCT TYPE
DUCT TYPE
Press the this push-button switch, and "PUMP DOWN OPERATION" is starting.
AR45
AR45
- (04 - 28) -
Page 30
4-16-3. INDOOR UNIT
INDOOR UNIT
1
Low static pressure function setting
SW 1
DIP SW
SW 2
Rotary SW SW 3 Indoor unit number setting
Jumper Wire
SWITCH POSITION
Duct type Indoor unit control circuit board
2
Forbidden
3
4
1 Room temperature correct coefficient of heating
2 External input select
3 Auto restart validity/invalidity
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
DUCT TYPE
DUCT TYPE
AR45
POWER PCB
CN114
CN106
CN115
MAIN PCB
ON
OFF
CN4
CN5
CN16
CN14
CN15
SW1 SW2
1 2 3 1 2 34
SW1 SW2
SW3
ON
OFF
JM1 JM2 JM3
AR45
- (04 - 29) -
CN16
Page 31
4-16-4. SWITCH FUNCTION (INDOOR UNIT)
SW1-1 SW state
OFF Normal
ON Low static pressure
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
SW2-1 SW state
OFF +4 deg (Ceiling setting)
ON 0 deg (Room setting)
SW2-2 SW state
OFF Edge
ON Pulse
SW2-3 SW state
OFF Validity
ON Invalidity
SW3 SW state
0 single
1-15 Indoor unit address
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
( Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
( Factory setting)
2-1 Room temperature correct coefficient of heating.
DUCT TYPE
AR45
Decide the heating temperature correct coefficient vale of heating.
DUCT TYPE
AR45
Heat temperature correction
( Factory setting)
2-2 External input select edge/pulse
This switch is used to select the format of external input command as shown in the table below.
( Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AUTORESTART SETTING
( Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
- (04 - 30) -
Page 32
JUMPER WIRE SETTING
JM2 JM state
Connect Residencial
Disconnect Commercial
JM3 JM state
Connect Invalidity
Disconnect Validity
Connector INPUT OUTPUT REMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115 - OPERATION DISPLAY
CN14 - FRESH AIR
CN15 - ELECTRICAL HEATER
See external
input/output settings
for details.
JM1 JM state
Connect 0 deg
Disconnect + 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
( Factory setting)
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode. When you select "FAN:AUTO"mode fan goes in "HIGH"
( Factory setting)
DUCT TYPE
Fan delay setting
AR45
DUCT TYPE
AR45
This setting can be used when the auxiliary heater is mounted. When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,the fan operation continues one minutes.
( Factory setting)
EXTERNAL INPUT AND OUTPUT
- (04 - 31) -
Page 33
4-16-5. WIRED, SIMPLE REMOTE CONTROLLER CIRCUIT BOARD
Wired,Simple remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
DUCT TYPE
AR45
OFF
ON
1 2 3 4 5 6
DUCT TYPE
AR45
ON
DIP Switch
Simple remote controller
ON
ON
OFF
12345
6
DIP switches
- (04 - 32) -
Page 34
4-16-6. WIRED, SIMPLE REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DIP-SW
DUCT TYPE
AR45
No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
DUCT TYPE
AR45
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
- (04 - 33) -
Page 35
4-17. OPTIONAL PARTS
SIMPLE REMOTE CONTROLLERS UTB - YPB : FUJITSU BRAND UTB - GPB : GENERAL BRAND UTB - TPB : Australia only
Remote controller which gives priority to ease-of-use and allows operation of the necessary functions only.
REMOTE SENSOR UNIT UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller. Because the remote controller has the switching function, the user can select the position of the sensor. (Room temperature sensor selection)
DUCT TYPE
AR45
Example of room temperature sensor selection
Simple remote
controllers
Remote Sensor in the bed room (effective at night)
DUCT TYPE
AR45
Sensor part
Wired Remote Controller
THERMO
Day
The detecting point can be freely changed.
SENSOR
Night
Remote Controller in the living room (effective during the day)
Remote Sensor (Optional Parts)
LONG LIFE FILTER UTD - LF25NA
Intake air filter can be mounted to the indoor unit.
- (04 - 34) -
Page 36
SQUARE FLANGE (UTD - SF045T)
ROUND FLANGE (UTD - RF204)
Round flange is used when the fresh air duct is installed.
DUCT TYPE
DUCT TYPE
AR45
AR45
Air intake hole
Round flange
- (04 - 35) -