Refrigerant
R407C
MUlTI TYPE AIR CONDITIONER
INSTALLATION INSTRUCTION
SHEET
(PART NO. 9370823011)
This air conditioner uses new refrigerant HFC (R407C).
For authorized service personnel only.
WARNING!
CAUTION!
1 For the air conditioner to operate satisfactorily, install as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available standards parts. This
installation instruction sheet describes the correct connections using the installation set available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 Also, do not use an extension cord.
5 Do not turn on the power until all installation work is complete.
6 Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation.
7 There is not extra refrigerant in the outdoor unit for air purging.
8 Use a vacuum pump for R407C exclusively.
9 Using the same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
: Use a clean gauge manifold and charging hose for R407C exclusively.
A If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it
produces a toxic gas.
• Be careful not to scratch the air conditioner when handling it.
• After installation, explain correct operation to the customer, using the operating manual.
• Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
This mark indicates procedures which, if improperly performed, might lead to the death or serious injury
of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal harm to
the user, or damage to property.
WARNING
STANDARD ACCESSORIES
The following installation accessories are supplied. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape
Wall hook bracket
Wall cap-B
Remote
control unit
Battery (penlight)
Remote control
unit holder
Cloth tape
Tapping screw (big)
(ø4 x 20)
Tapping screw (small)
(ø3 x 12)
Seal A
Q’ty
For indoor unit installation
1
For through hole connection pipe
protection
1
Use for air conditioner operation
1
For remote control unit
2
Use as remote control unit holder
1
For indoor unit installation
1
For wall hook bracket
installation
8
For remote contorol unit holder
installation
2
For indoor unit installation
1
Use
INSTALLATION PROCEDURE
1
The piping can be connected in the five directions indicated by 1,
2, 3, 4, and 5 in (Fig. 3). When the piping is connected in direction
2 or 5, cut along the piping groove in the side of the indoor unit
with a hacksaw. When connecting the piping in direction 3, cut a
notch in the thin wall at the under cover A.
Fig. 3
2 Right
1. INSTALLING THE WALL HOOK BRACKET
Install the wall hook bracket so that it is strong enough to withstand
the weight of an adult.
[Installation directly to a wall]
Before fastening the wall hook bracket to the wall with the screws,
level it by tapping the hook at the center of bracket to the wall with
the handle of a screwdriver.
• Fasten the wall hook bracket to the wall with 6 or more screws
• Check that there is no rattle at the wall hook bracket.
INDOOR UNIT INSTALLATION
(Rear)
4 Left rear
outlet
3 Bottom outlet
1 Rear outlet
CAUTION
Install the wall hook bracket horizontally and perpendicularly. If the wall hook bracket is tilted, water will drip to the
floor.
through the holes near the outer edge of the bracket.
outlet
5 Left
outlet
Fig. 4
Wall hook
bracket
Tapping screw (big)
Center notch
Tapped
(Handle of screwdriver)
Hook
Hook
Wall hook
bracket
String
Counter
weight
2. CUTTING THE HOLE IN THE WALL FOR THE
CONNECTING PIPING
WARNING
If the wall pipe is not used, the cord interconnecting the
indoor and outdoor units may touch metal and cause electric leakage.
(1) Cut a 65 mm diameter hole in the wall at the position shown in
(Fig. 5).
(2) When cutting the wall hole at the inside of the installation frame,
cut the hole to a point of intersection of center marks.
When cutting the wall hole at the outside of the installation frame,
cut the hole at least 10 mm below less.
(3) Cut the hole so that the outside end is lower (5 to 10 mm) than
the inside end.
(4) Always align the center of the wall hole. If misaligned, water leak-
age will occur.
(5) Cut the wall pipe to match the wall thickness, stick it into the
accessory wall cap-B, fasten the cap with vinyl tape, and stick
the pipe through the hole. (The connection pipe is supplied in
the installation set.) (Fig. 5)
Fig. 5
Lower
10 mm
or over
Fasten with
vinyl tape
(Wall pipe)
(Inside) (Outside)
Wall cap-B
(6) For 5 left piping and 2 right piping, cut the hole a little lower so
that drain water will flow freely (Fig. 5).
Wall
Center mark
Lower
10 mm
or over
5 to 10 mm low
65 mm dia.
hole
3. FORMING THE DRAIN HOSE AND PIPE
CAUTION
1 Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection pipe.
2 To prevent breaking of the pipe, avoid sharp bends. Bend
the pipe with a radius of curvature of 100 mm or over.
3 If the pipe is bent repeatedly at the same place, it will
break.
[1 Rear piping, 2 Right piping, 3 Bottom piping]
• Install the indoor unit piping in the direction of the wall hole and
bind the drain hose and pipe together with vinyl tape (Fig. 6).
• Install the piping so that the drain hose is at the bottom.
Fig. 6
Cut off the piping
outlet cutting
groove with a
hacksaw, etc.
Decorative
tape
Right piping
Notch the thin part of
under cover A.
• Perform “2 INDOOR UNIT WIRING” before performing this piping.
• Wrap the pipes of the indoor unit that are visible from the outside
with decorative tape.
• After passing the indoor piping and drain hose through the wall
hole, hang the indoor unit on the hooks at the top and bottom of
the wall hook bracket.
Bottom piping
Bind with vinyl tape
Pipe (top)
Rear piping
Indoor unit drain
hose (bottom)
Fig. 7
Indoor unit
(Fitting)
After hooking the indoor unit to the top hook, hook the
fittings of the indoor unit to the two bottom hooks while
lowering the unit and pushing it against the wall.
Bottom hooks
Wall hook
bracket
[For 4 Left rear piping, 5 Left piping]
Interchanging the drain hose
Interchange the drain cap and the drain hose.
Fig. 8
For left outlet
piping, cut off the
piping outlet
cutting groove
with a hacksaw.
Drain cap
Under cover A
Indoor unit drain
hose
Remove the drain cap by
pulling at the projection at
the end of the cap with
pliers, etc.
Removing the drain hose
CAUTION
After removing the drain hose, do not forget to install
the drain cap.
Remove the under cover A and pull off the drain hose.
Fig. 9
Indoor unit
Drain cap
Indoor unit
drain hose
Under cover A
See item 2. “INDOOR UNIT WIRING” for a description of how to
remove the under cover A.
Drain cap
Insert the drain cap until it butts against the drain port.
Top hooks
Installing the drain hose
Insert the drain hose into the drain port.
Fig. 10
Indoor unit
drain hose
Insert the drain hose until it
butts against the drain port.
Drain port
Indoor unit drain
hose
• For left piping and left rear piping, align the marks on the wall
hook bracket and shape the connection pipe.
• Bend the connection piping at a bend radius of 100 mm or over
and install no more than 35 mm from the wall.
Fig. 11
Connection pipe
(6.35mm (1/4”) dia.)
Align the marks.
Bend (R100) with
a pipe bender
• When extending the drain hose at the indoor unit, install the drain
insulation.
Connection pipe
Fig. 12
Drain insulation
Indoor unit
drain
Vinyl tape
Drain hose
• Place the indoor unit drain hose behind the piping.
hose
[Installing the indoor unit]
• Hang the indoor unit from the hooks at the top of the wall hook
bracket.
• Insert the spacer, etc. between the indoor unit and the wall hook
bracket and separate the bottom of the indoor unit from the wall.
Fig. 13
Indoor unit
Spacer
SELECTING THE MOUNTING POSITION
WARNING
1 Install at a place that can withstand the weight of the indoor and outdoor units and install positively so that the units will not
topple or fall.
2 Install the outdoor unit where it will not be tilted by more than 5°.
3 When installing the outdoor unit where it may exposed to strong wind, fasten it securely.
CAUTION
1 Do not install where there is the danger of combustible gas leakage.
2 Do not install near heat sources.
3 If children under 10 years old may approach the unit, take preventive measures so that they cannot reach the unit.
Decide the mounting position with the customer as follows:
1. INDOOR UNIT
(1) Install the indoor unit level on a strong wall which is not subject
to vibration.
(2) The inlet and outlet ports should not be obstructed : the air should
be able to blow all over the room.
(3) Do not install the unit where it will be exposed to direct sunlight.
(4) Install the unit where connection to the outdoor unit is easy.
(5) Install the unit where the drain pipe can be easily installed.
(6) Take servicing, etc. into consideration and leave the spaces
shown in (Fig. 1). Also install the unit where the filter can be re-
moved.
Fig. 1
6 cm or over
Left side
5 cm
or over
150 cm
or over
150 to 200 cm
Right
side
5 cm
or
over
2. OUTDOOR UNIT
(1) If possible, do not install the unit where it will exposed to direct
sunlight. (If necessary, install a blind that does not interfere with
the air flow.)
(2) Install the outdoor unit in a place where it will be free from being
dirty or getting wet by rain as much as possible.
(3) Install the unit when connection to the indoor unit is easy.
(4) During heating operation, drain water flows from the outdoor unit,
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed. (Reverse cycle model only)
(5) Do not place animals and plants in the path of the warm air.
(6) Take the air conditioner weight into account and select a place
where noise and vibration are small.
(7) Select a place so that the warm air and noise from the air condi-
tioner do not disturb neighbors.
(8) Provide the space shown in Fig. 2 so that the air flow is not
blocked. Also for efficient operation, leave open three of the four
directions front, rear, and both sides.
(9) Install the unit near the special branch circuit.
Fig. 2
30 cm
or over
1 cm or over
10 cm
or over
60 cm
or over
OUTDOOR UNIT ACCESSORIES
Name and Shape
Tapping screw
Binder
Putty
Hexagon wrench
Cable mark
A1-A
A1-A
A2-A
B1-A
A1-B
A2-B
B1-B
A2-A
B1-A
B2-A B2-A B2-B B2-B
A1-B
A2-B
B1-B
Q’ty
• For cabinet A and cabinet D
mounting (1)
2
• Spare (1)
For power cord and connection cords
binding
2
For sealing
1
For opening the refrigerant valve on
the outdoor unit
1
Stick on both ends of connection
cord (to prevent incorrect wiring)
1
Use
This installation instruction sheet refers to following installation parts.
Name Q’ty
Connection pipe assembly 4
Connection cord (3-conductor + Earth) 4
Wall pipe 4
Decorative tape 4
Vinyl tape 4
Wall cap 4
Saddle 4 sets
Drain hose 4
Tapping screws 4 sets
Sealant 4
Power supply cord 1
ELECTRICAL REQUIREMENT
••
• Electric wire size and fuse capacity:
••
Table 1
Power supply
cord (mm2)
Connection
cord (mm2)
• Always use H07RN-F or equivalent to the connection cord.
• Install the disconnect device with a contact gap of at least 3 mm
nearby the units. (Both indoor unit and outdoor unit.)
AIways make the air conditioner power supply a special branch circuit and provide a special switch and receptacle. Do not extend the
power cord.
MAX
MIN
MAX
MIN
5.0
3.5
3.5
1.0
2
INDOOR UNIT WIRING
WARNING
1 Before starting work, check that power is not being
supplied to the outdoor unit.
2 Match the terminal block numbers and connection cord
colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric
parts.
3 Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
5 Always connect the ground wire.
(1) Remove the front panel. (Remove the front panel in accordance
with “C FRONT PANEL REMOVAL” of these instructions.)
(2) Remove the under cover A.
Removing the under cover A
Fig. 14
Right bottom of
indoor unit
Pull
Cord clamp
(There is a
terminal block
inside.)
Under cover A
(3) Remove the cord clamp.
(4) Bend the end of the connection cord as shown in the figure.
(5) Connect the end of the connection cord fully into the terminal
block.
Fig. 15
Earth screw
Connection cord
(Equivalent to
H07RN-F 1.0 mm
2
3.5 mm
)
2
to
m
100 m
12 mm
m
18 m
Be sure that the cord is
not applied inside the
hatched lines.
35 mm
6) Fasten the connection cord with a cord clamp.
Fig. 16
Fasten the connection cord with the
position shown in the figure as
reference.
Terminal block
Reference
Sheath
Fig. 17
Fasten the outside
covering of the
connection cord with
cord clamp.
Connection cord
Insert the tab into the
square hole of the indoor
unit and fasten with a
screw.
(Tab)
Cord clamp
Installing the under cover A
• Fit the hooks of the under cover A to the indoor unit.
Fig. 18
Indoor unit
(Hook)
Indoor unit
terminal block
Screw
Wall hook bracket
OUTDOOR UNIT INSTALLATION
3
WARNING
1 Install the unit where it will not be tilted by more than
5°.
2 When installing the outdoor unit where it may exposed
to strong wind, fasten it securely.
• Set the unit on a strong stand, such as one made of concrete blocks to
minimize shock and vibration.
• Do not set the unit directly on the ground because it will cause trouble.
OUTDOOR UNIT PROCESSING
When the outdoor unit will be exposed to strong wind, fasten it with bolts
at the places indicated by the arrows (Fig. 19).
Fig. 19
Bottom
15-3/4” (400 mm)
25-19/32” (650 mm)
4-ø12 hole (Anchor bolt M10)
60 cm or over
Under cover A(Hook)
• After installing the bottom hook install the side hooks by pressing the bottom right end of under cover A from the bottom.
- Continuted on back -
4
CONNECTING THE PIPING
CAUTION
The maximum lengths of this product are shown in Table 1.
If the units are further apart than this, correct operation
can not be guaranteed.
1. LIMITATION OF REFRIGERANT PIPING
LENGTH
Table 2
Total max length (A1+A2)
Total max length (B1+B2)
Max length for each indoor unit
(A1 or A2 or B1 or B2)
Max height difference (H)
Fig. 20
OUTDOOR UNIT
30 m (98 ft)
30 m (98 ft)
25 m (82 ft)
10 m (33 ft)
INDOOR UNIT
2. FLARING
(1) Cut the connection pipe to the necessary length with a pipe cut-
ter.
(2) Hold the pipe downward so that cuttings will not enter the pipe
and remove the burrs.
(3) Insert the flare nut onto the pipe and flare the pipe with a flaring
tool.
Fig. 21
Check if [L] is flared uniformly and is not cracked or
scratched.
L dimension Thin pipe (6.35 mm dia.) 1.4 to 1.7 mm
Thick pipe (9.52 mm dia.) 1.8 to 2.0 mm
Thick pipe (12.7 mm dia.) 1.9 to 2.2 mm
L
3. BENDING
(1) When bending the pipe, be careful not to crush it.
(2) To prevent crushing of the pipe, do not bend the pipe at a radius
curvarture of 100 mm or more.
(3) If the copper pipe is bent or pulled to often, it will become stiff. Do
not bend the pipe more than three times at one place.
4. CONNECTION
(1) Install the outdoor unit wall cap (supplied with the optional in-
stallation set or procured at the site) to the wall hole pipe.
(2) Connect the outdoor unit and indoor unit piping.
(3) After matching the center of the flare surface and tightening the
nut hand tight, tighten the nut to the specified tightening torque
with a torque wrench. (Tighten the flare nut of the outdoor unit 3-
way valve after air purging.)
Fig. 22
Tighten with two wrenches.
Wrench (fixed)
Torque wrench
Indoor unit
pipe
Flare nut
Connection
pipe
Fig. 23
OUTDOOR UNIT
Connection pipe
Flare nut
Torque wrench
Fig. 24
To prevent gas leakage, coat
the flare surface with
refrigerator oil.
Table 3 Flare nut tightening torque
Flare nut
6.35 mm
(1/4”) dia.
9.52 mm
(3/8”) dia.
12.7 mm
(1/2”) dia.
Do not remove the cap from the connection pipe before connecting
the pipe.
Tightening torque
15.7 to 17.6 N·m
(160 to 180 kgf·cm)
29.4 to 34.3 N·m
(300 to 350 kgf·cm)
49.0 to 53.9 N·m
(500 to 550 kgf·cm)
Tightening torque standard
(using a 20 cm wrench)
Wirst strength
Arm strength
Arm strength
8
OUTDOOR UNIT WIRING
WARNING
1 Before starting work, check that power is not being
supplied to the outdoor unit.
2 Match the terminal block numbers and connection cord
colors with those of the indoor unit side.
Erroneous wiring may cause burning of the electric
parts.
3 Connect the connection cords firmly to the terminal
block. Imperfect installation may cause a fire.
4 Always fasten the outside covering of the connection
cord with cord clamps. (If the insulator is clamped, electric leakage may occur.)
5 Always connect the ground wire.
CAUTION
Use H07RN-F or equivalent as the connection cord (1.5
2
to 2.0 mm2) and power cord (3.5 mm2 to 5.0 mm2).
mm
(1) Remove the outdoor unit cabinet A and cabinet D.
Fig. 26
* Use the accessory screws at these points only
* After removing the screws, remove
cabinet A by pushing it down
Cabinet A
mounting direction
Cabinet D
(2) Process the end of the connection cords to the dimensions shown
in (Fig. 28) and bend the end of each cord as shown in (Fig. 27).
Fig. 27
(3) Connect the end of the power cord and connection cord fully
(4) Fasten the sheath with a cord clamp.
(5) Fasten the power cord and connection cord with cable clips and
Stripped length
12 to 13 mm
into the terminal block.
binders as shown in (Fig. 28).
Fig. 28
[Reverse cycle model]
Terminal block
B1UN B2UNA1UN A2UN
Cord clamp
Binder
(Insulator)
(Sheath)
Power cord
20 mm
Connection cord
20 mm
(Insulator)
(Sheath)
Fig. 29
Indoor and outdoor wire connection
OUTDOOR UNIT INDOOR UNIT
1
2
A1
3
1
2
A2
3
Power cord
220-240V
50 Hz · 1ø
EARTH
(6) Pass the connection cord and power cord through the hole of
L
N
POWER
the 3-way valve bracket and run them to the outside of the cabinet.
1
2
B1
3
1
2
B2
3
Connection cord
Connection cord
Connection cord
Connection cord
1
2
3
1
2
3
1
2
3
1
2
3
Fig. 30
±10
60
Outdoor unit
A1
A2
B1
B2
11
• Perform test operation and check items 1 and 2 below.
• For the operation method, refer to the operating manual.
• The outdoor unit may not run, depending on the room temperature.
In this case, press the test run button at the back of the remote control
unit while the room air conditioner is running.
(With the transmit section of the remote control unit facing the body,
press the TEST RUN button with the tip of a ball point pen.)
Fig. 38
Operation can be checked by lighting and flashing of the display section
OPERATION and TIMER lamps.
Perform judgement in accordance with the following.
• Test running
When the air conditioner is run by pressing the remote control unit
test run button, the OPERATION and TIMER lamps flash slowly at
the same time. To end test operation, press the remote control unit
START/STOP button.
• Error
The OPERATION, TIMER and SWING lamps operate as follows (Table 5 and 6) according to the error contents.
INDOOR UNIT
Indoor unit circuit board error
Indoor unit room temperature sensor wire
error
Indoor unit piping sensor wire error
Indoor unit fan error
Connection cord
Connection pipe
: Fast flashing : Slow flashing — :Off
OUTDOOR UNIT
Hole (3-way valve bracket)
Power cord and connection cord
(indoor unit and outdoor unit
connection wire)
THERMISTOR DISCHARGE PIPE
abnormal
• Above PCB:UNIT A, below PCB:UNIT B.
TEST RUNNING
Remote control
unit (rear)
TIME ADJUST button
Table 5
Error contents
Table 6
Error contents
TEST RUN button
Error display
OPERATION
(RED)
2 times
3 times
6 times
LED D18 blinking display
0.1 sec ON/0.1 sec OFF
TIMER SWING
(GREEN)
Error display (PCB)
(ORANGE)
—
—
—
—
CHECK ITEMS
(1) INDOOR UNIT
(1) Is operation of each button on the remote control unit normal?
(2) Does each lamp light normally?
(3) Do not air flow direction louvers operate normally?
(4) Is the drain normal?
(5) Is there any abnormal noise and vibration during operation?
(2) OUTDOOR UNIT
(1) Is there any abnormal noise and vibration during operation?
(2) Will noise, wind, or drain water from the unit disturb the neighbors?
(3) Is there any gas leakage?
• Do not operate the air conditioner in the test running state for a long
time.
• For the operation method, refer to the operating manual and perform
operation check.
12
Explain the following to the customer in accordance with the operating manual:
(1) Starting and stopping method, operation switching, temperature
adjustment, timer, air flow switching, and other remote control
unit operations.
(2) Air filter removal and cleaning, and how to use the air louvers.
(3) Give the operating and installation instruction sheets to the customer.
CUSTOMER GUIDANCE
5
VACUUM PROCESS AND
ADDITIONAL CHARGE
CAUTION
1 Do not purge the air with refrigerants but use a vacuum
pump to vacuum the installation! There is no extra refrigerant in the outdoor unit for air purging!
2 Use a vacuum pump for R407C exclusively. Using the
same vacuum pump for different refrigerants may damage the vacuum pump or the unit.
1. VACUUM
(1) Remove the cap, and connect the gauge manifold and the vacuum
pump to the charging valve by the service hoses.
(2) Vacuum the indoor unit and the connecting pipes until the pres-
sure gauge indicates -76 cmHg.
(3) When -76 cmHg is reached, operate the vacuum pump for at least
15 minutes.
(4) Disconnect the service hoses and fit the cap to the charging port
(Tightening torque : 8.8 to 11.8 N·m (90 to 120 kgf·cm)).
(5) Remove the blank caps, and fully open the spindles of the 2-way and
3-way valves with a hexagon wrench (Torque: 4.9 to 6.9 N·m (50 to 70
kgf·cm)).
(6) Tighten the blank caps of the 2-way valve and 3-way valve to the
specified torque:
2-way valves torque: 19.6 to 24.5 N·m (200 to 250 kgf·cm)
3-way valves (9.52 dia.) torque: 19.6 to 24.5 N·m (200 to 250 kgf·cm)
3-way valves (12.7 dia.) torque: 31.4 to 37.2 N·m (320 to 380 kgf·cm)
Fig. 25
Connecting pipe
OUTDOOR UNIT
Service hose with
valve core
Cap
OUTDOOR UNIT
2-way valve
3-way valve
Gauge manifold
3-way valve
Blank cap
Charging port
Connection pipe
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 20 m (A1+A2 or B1+B2) is charged
in the outdoor unit at the factory.
When the piping is longer than 20 m (A1+A2 or B1+B2), additional charging is necessary.
For the additional amount, see the table below.
Table 4
Total pipe length
A1+A2 or B1+B2
Additional refrigerant
(R407C)
1 When moving and installing the air conditioner, do not
mix gas other than the specified refrigerant R407C inside the refrigerant cycle.
2 When charging the refrigerant R407C, always use an
electronic balance for refrigerant charging (to measure the refrigerant by weight).
3 When charging the refrigerant, take
into account the slight change in the
composition of the gas and liquid
phases, and always charge from the
liquid phase side whose composition is stable.
4 Add refrigerant from the charging valve after the com-
pletion of the work.
5 The maximum length of the piping is 30 m (A1+A2 or
B1+B2). If the units are further apart than this, correct
operation can not be guaranteed.
66 ft
(20 m)
None
CAUTION
82 ft
(25 m)
3.5 oz
(100 g)
98 ft
(30 m)
7.1 oz
(200 g)
Gas
Liquid
oz/ft
( g/m)
0.71 oz/3.3 ft
(20 g/m)
R407C
6 9 10
GAS LEAKAGE INSPECTION
CAUTION
After connecting the piping, check the joints for gas leakage with gas leak detector.
(1) Insulate between pipes.
• For rear, right, and bottom piping, overlap the connection pipe
heat insulation and indoor unit pipe heat insulation and bind
them with vinyl tape so that there is no gap.
• For left and left rear piping, butt the connection pipe heat insulation
and indoor unit pipe heat insulation together and bind them with
and vinyl tape so that there is no gap.
Fig. 31
Connection pipe
(heat insulation)
• For left and left rear piping, wrap the area which accommodates
the rear piping housing section with cloth tape.
Indoor unit pipe (heat insulation)
FINISHING
Vinyl tape
Seal A
Butt connection pipe (heat insulation) against the
indoor unit pipe (heat insulation) and wrap with seal
A so that there is no gap.
Seal A
Check that:
• The top and bottom hooks are hooked firmly and the indoor
unit does not move to the front and rear or left and right.
• The indoor unit is accurately positioned horizontally and vertically.
• When connected from the left rear, the drain hose is at the bottom left of the wall pipe.
Fig. 35
(For connection from
the left rear)
(View from indoors)
Wall pipe
Connection
pipe
Drain hose
(2) Temporarily fasten the connection cord along the connection pipe
with vinyl tape. (Wrap to about 1/3 the width of the tape from the
bottom of the pipe so that water does not enter.)
(3) Fasten the connection pipe to the outside wall with a saddle, etc.
(4) Fill the gap between the outside wall pipe hole and the pipe with
sealer so that rain water and wind cannot blow in.
Fig. 36
Saddle
Connection cord
Outside wall cap
Sealer putty
1 The rated voltage of this product is 220-240 V A.C. 50 Hz.
2 Before turning on the verify that the voltage is within
3 Always use a special branch circuit and install a spe-
4 Use a circuit breaker and receptacle matched to the
5 Do not extend the power cord.
6 Perform wiring work in accordance with standards so
7 Install a leakage circuit breaker in accordance with the
Fig. 32
7
RECHARGING THE
Connection pipe
Cloth tape
Indoor unit pipe
Pipe
Wrap with cloth tape.
Wall
(Outdoors)
1 The power source capacity must be the sum of the room
REFRIGERANT
(5) Fasten the drain hose to the outside wall, etc.
Fig. 37
Check the following:
GOOD BAD BAD
Drain hose
Saddle
Lifted up
Wave
2 When the voltage is low and the air conditioner is diffi-
BAD
End in water
(1) Vacuum the outdoor unit, indoor unit and the connecting pipes until
the pressure gauge indicates -76 cmHg.
(2) After the vacuuming is finished, charge with the amount of refrig-
erant written on the rating plate.
• When charging the refrigerant, take into
account the slight change in the composition of the gas and liquid phases, and
always charge from the liquid phase side
whose composition is stable.
• When charging the refrigerant R407C, always use an electronic
balance for refrigerant charging (to measure the refrigerant by
weight).
Gas
R407CR407C
Liquid
• For left and left rear piping, bind the connection cord to the
top of the pipe with vinyl tape.
Fig. 33
Connection cord
Pipe
Vinyl tape
• For left and left rear piping, bundle the piping and drain hose
together by wrapping them with cloth tape over the range within
which they fit into the rear piping housing section.
Fig. 34
POWER
WARNING
the 198 V to 264 V range.
cial receptacle to supply power to the room air conditioner.
capacity of the room air conditioner. (Fuse
rating: 30 A)
When connecting the power supply to the outdoor unit,
always install a circuit breaker between the outdoor
unit and the power supply. Use the circuit breaker has
an isolation distance of at least 3 mm between the contacts of each pole.
that the room air conditioner can be operated safely
and positively.
related laws and regulations and electric company
standards.
CAUTION
air conditioner current and the current of other electrical appliances. When the current contracted capacity
is insufficient, change the contracted capacity.
cult to start, contact the power company the voltage
raised.
••
• breaker
••
13
FRONT PANEL REMOVAL
CAUTION
Install the front panel and intake grille securely. If installation is imperfect, the front panel or intake grille may fall
off and cause injury.
1. INTAKE GRILLE REMOVAL
(1) Open the intake grille.
(2) Open the intake grille and lift the intake grille upward until the
hook at the top of the intake grille is unhooked.
Fig. 39
(Hook)
Intake
grille
Open (Hook)
Lift
2. FRONT PANEL REMOVAL
(1) Remove the two tapping screws.
(2) Remove the front panel by lifting the bottom of the front panel
upward.
Fig. 40
Front
panel
Lift
Tapping screw
3. FRONT PANEL INSTALLATION
(1) Hook the top hole of the front panel to the hook of the base.
(2) Fasten the front panel with the screw.
Fig. 41
(Top hook)
(Top hole)
14
REMOTE CONTROL UNIT
HOLDER INSTALLATION
CAUTION
1 Check that the indoor unit correctly receives the sig-
nal from the remote control unit, then install the remote control unit holder.
2 Select the remote control unit holder selection site by
paying careful attention to the following:
Avoid places in direct sunlight.
Select a place that will not be affected by the heat from
a stove, etc.
Install the remote control unit holder to a wall or pillar with the tapping screws.
Fig. 42
Remote control unit
mounting
Remote
control unit
holder
Tapping
screw
(small)
Remote control unit
holder fixing
1 Set
2 Push
Remote
control unit
Service hose
Vacuum pump
Pipe
Drain hose
Wrap with cloth tape
Cloth tape
Pipe
Connection cord
Left piping
Front panel
Drain hose
Be sure that the top hole of the front panel is hooked securely to
the hook of the base.
PART NO. 9370823014