General ARG30F, ARG30FUAN, AOG30FNBWL, ARG30U, ARG30UUAN Technical Manual

...
Page 1
R410A
4 . DUCT TYPE :  AR 30FUAN, AR 30UUAN  ART30UUAN
D2D_AR008E/03
2006.05.30
Page 2
4-1. FEATURE
MODELS : AR 30FUAN / AO 30FNBWL AR 30UUAN / AO 30UNBWL ART30UUAN / AOT30UNBWL
FEATURES
Installation styles
Embedded in Ceiling
Hanging from Ceiling
DUCT TYPE
AR30W
Low static pressure mode function
1.Low static pressure mode 1 air volume at 70Pa (fan speed:high)
2.Normal Mode Air volume at 100Pa (fan speed:high)
When installed, normal middle static pressure mode, and low static pressure mode can be selected by switching over using DIP switch on the board in the control box. Therefore, these models can be op­erated under the wide range of conditions.
(230V)
/h)
3
Air volume (m
0 70 100
Static pressure (Pa)
1 2
DUCT TYPE
AR30W
Slim & compact design
In the case of bottom suction type, as seen from lower rear part.
Control Box that has been convex shape is now united with main unit (DIP Switch is located on the internal substrate.)
One-touch operating and easy-to-install long-life filter (optional)
In addition to the slim height of 270 mm which is our sales point, further com­pactification is attained by reducing 65 mm from the width with the flanking control box embedded inside the chassis.
Page 3
EASY MAINTENANCE
In the case of rear suction type, as seen from lower rear part.
Conventional model
1
3
4
New model
4
1
1.Control box
2.Fan casing
3.Fan
4.Motor
2
2
3
Bottom panel: 2 units
Large bottom panel: 1 unit
Structural improvement is attained by making the bottom panel two pieces, front and rear, and the internal fan casing is also made dismountable in two pieces namely, upper and lower ones.
DUCT TYPE
AR30W
The motor and fan maintenance and dismounting can be made easily by removing the rear panel and lower part of the casing with the main chassis installed.
DUCT TYPE
AR30W
Page 4
4-2. REMOTE CONTROLLER
4-2-1. WIRED REMOTE CONTROLLER
FEATURES
Various timer setup (ON / OFF / WEEKLY) are possible. Equipped with weekly timer as standard function.
(2 times Start / Stop per day for a week)
SUMOTUWETH FR SA
7
3126 9
15 18 21
When setting up a timer, operation mode and a temperature setup can be changed.
When a failure occurs,the error code is displayed. (Maximum of 16) Error indication.(A maximum of 16 error histories are memorizable.) Up to 16 indoor units can be simultaneously controlled.
Anti freeze and energy saving operation are possible. Easy installation with a slim shape with no boldge in the back.
The room temperature can be controlled by being detected the temperature accurately with built-in thermo sensor.
High performance and compact size
Three functions are combined in one unit.
DUCT TYPE
AR30W
Wired
remote
controller
Weekly
timer
Setback
timer
DUCT TYPE
AR30W
Built-in timers
Setback timerWeekly timer
Possible to set ON/OFF time to operate twice each day of the week.
SUMOTUWETH FR SA
7
3126 9
15 18 21
Setup screen example (Set to Wednesday: 8:00 to 20:00.)
0 3 6 9 12 15 18 21 Time
Easy-to-understand time bar display
24°C
SUMOTUWETH FR SA
7
3126 9
15 1821
Screen after setup
At "Weekly timer" + "Set back timer" setup
24°C 28°C 24°C
0 3 6 9 12 15 18 21 Time
Timer area
Operation area
Possible to set temperature for two time spans and for each day of the week.
SUMOTUWETH FR SA
3126 9
15 18 21
Setup screen example (Set from Sunday to Saturday: 12:00 to 15:00, 28 °C.)
28°C
0 3 6 9 12 15 18 21 Time
24°C
28°C
Simple installationEasy-to-understand operation
Components are compatible with standard switch boxes. Flat back construction allows equipment to be installed wherever it is needed.
[
Variable timer control
]
The operation/display sections are zoned accord­ing to time and operation, enabling variable pro­gramming to match application.
European switch box
JIS box
Page 5
FUNCTIONS
1
START/STOP button
Pressed to start and stop operation.
Display
2 7 8
9
10
SUMOTUWETH FR
369
CLOCK ADJUST
SET BACK
DELETE SET
12 15 18 21
DAY
DAY OFF
SA
13
1 3
ENERGY
SAVE
THERMO SENSOR
4
6
2
Set temperature button
Selects the setting temperature.
3
Master control button
Selects the operating mode(AUTO, HEAT, FAN, COOL, DRY).
4
Fan control button
Selects the fan speed (AUTO, LOW, MED, HIGH).
5
Energy save button
Turns the energy efficient mode on and off.
11
12
5
6
Thermo sensor
7
Timer mode (CLOCK ADJUST) button
Selects the timer mode (OFF TIMER, ON TIMER, WEEKLY TIMER) Set the current time.
8
Day (DAY OFF) button
Display panel
DUCT TYPE
AR30W
14
15
1617 18
Temporarily cancels of one day timer.
9
Set back button
pressed select the set back timer.
10
Set time button
DUCT TYPE
AR30W
Pessed to select the set back timer.
SUMOTUWETH FR
SA
11
Delete button
The schedule of a weekly timer is deleted.
369
12 15 18 21
1920
12
Set button
Sets the date, hour, minute and on-off time.
13
Operation lamp
Lights during operation and when the timer is on.
DIMENSION
[ Unit : mm ]
17
120
SUMOTUWETH FR
369
12 15 18 21
DAY
CLOCK ADJUST
DAY OFF
SET BACK
DELETE SET
Front View
120
SA
ENERGY
SAVE
THERMO
SENSOR
SPECIFICATION
SIZE (H x W x D mm) 120 x 120 x 17
WEIGHT ( g ) 160
CABLE LENGTH ( m )
POWER ( V )
10
12
14
Timer and clock display
15
Operation mode display
16
Fan speed display
17
Central control display
18
Temperature display
19
Stand by display Indicates during the oil recovery and defrosting operation.
20
Energy save display
Page 6
4-3. SPECIFICATIONS
AR 30FUAN AR 30UUAN ART30UUAN
AO 30FNBWL AO 30UNBWL AOT30UNBWL
240V 50Hz
Rows x Stages Fin Pitch
Rows x Stages Fin Pitch
Sirocco x 2
70
Copper tube
2 x 38
1.3
Propeller x 1
67
Outer diameter 38 mm / Inner diameter 36 mm
Steel
Galvanlzed steel sheet
270 x 1135 x 700
3.0(6.3)
9.52 ( 3 / 8 inc.)
ROTARY
Permanent Starting Condenser
Alminum fin
830 x 900 x 330
294 x 1000 x 39.9
Alminum fin
798 x 900 x 36.38
15.88 ( 5 / 8 inc.)
43 / 50 ( 95 / 110 )
69 /75 ( 152 / 165 )
FLARE
DUCTED MODELS
HEAT PUMP TYPE
198-264V 50Hz
2300
30(chargeless:7.5)
R410A
15
970 x 1050 x 445
300 x 1300 x 790
Beige (10YR7.5/1.0NN)
POE
0 to 43
-7 to 24
WIRED (3TA)
2200
Copper tube
3 x 14
1.4
1250
1185
1110
-
780
400
30 to 150
TYPE
MODEL NAME
INDOOR
OUTDOOR
POWER SOURCE
AVAILABLE VOLTAGE RANGE
CAPACITY
COOLING
RATED
HEATING
RATED
INPUT POWER
kW
CURRENT
A
STARTING CURRENT
kW/kW
MOISTURE REMOVAL
AIR CIRCULATION INDOOR
m3/h
OUTDOOR
FAN SPEED
INDOOR
r.p.m
OUTDOOR RECOMMENDED STATIC PRESSURE
FAN TYPE x Q'ty
FAN MOTOR OUTPUT
W
NOISE LEVEL (SOUND PRESSURE)
COOL/HEAT
INDOOR
dB(A)
OUTDOOR
COMPRESSOR
TYPE
STARTING METHOD
HEAT EXCHANGER TYPE
INDOOR
Coil
Fin
OUTDOOR
Coil
Fin
CASING COLOR
DIMENSIONS H × W × D NET
mm
GROSS
DRAIN PIPE MATERIAL
SIZE
REFRIGERANT TYPE
REFRIGERANT OIL
TYPE
OPERATION(OUTDOOR)
°C
REMOTE CONTROLLER TYPE
kg(lbs)
PIPE
CONNECTION METHOD
SIZE
mm
MAX LENGTH
MAX HEIGHT
WEIGHT
NET / GROSS
-
230V 50Hz
1400
1300
1200-3300
70
COOLING TYPE
EUROPEAN ENERGY LABEL COOLING C C -
COOLING RAT ED 2.99 2.99 3.15
HEATING RATED - 2.63 2.80
COOLING RAT ED 14.0 14.0 14.3
HEATING RATED - 12.4 13.1
EER COOLING 2.81 2.81 2.70
COP HEATING - 3.61 3.39
High 1430
Med 1350
Low 1260
Quiet -
High 3400
Low -
High 1260
Med 1210
Low 1150
DUCT TYPE
AR30W
Quiet -
High 800
Low 420
INDOOR
OUTDOOR
INDOOR
OUTDOOR
High 40/- 40/40 40/40
Med 38/- 38/38 38/38
Low 36/- 36/36 36/36
kW 8.40 8.40 8.50
BTU/h 28700 28700 29000
kW - 9.50 9.50
BTU/h - 32400 32400
A
l/h (pints/h)
Pa
53/- 53/54 53/54
40
DUCT TYPE
AR30W
OUTPUT W
mm
Coil Dimensions mm
mm
Coil Dimensions mm
INDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR
INDOOR
OUTDOOR 68 / 74 ( 150 /163 )
OUTDOOR
LIQUID
GAS
m
m
CHARGE kg
COOLING
HEATING -
Note: Specifications are based on the following conditions. Cooling: Indoor tem perature of 27 °CDB / 19 °CWB,and outdoor temperature of 35 °CDB/24 °CWB. Heating: Indoor temperature of 20 °CDB / 15 °CWB,and outdoor temperature of 7 °CDB/6 °CW B. Static pressure of measurement : 100Pa Pipe length : 7.5 m, Height difference : 0 m.(Outdoor unit - Indoor unit)
mm
Page 7
4-4. DIMENSIONS
4-4-1. OUTDOOR UNIT
MODELS : AO 30F, AO 30U, AOT30U
(Unit : mm)
Top view
900
830
21
DUCT TYPE
AR30W
9
Front view
77
31 330
400
12
DUCT TYPE
AR30W
Side view
650
Air flow
370
MOUNTING POSITION
When there are obstacles at the back or front sides.
m
e
r
00 m
1
or mo
m
m
e
600
mor
or
603
Bottom view
When there are obstacles at the back, side(s), and top.
600 mm or more
100 mm
o
r mo
re
2
5
0 mm
(
Se
r
v
o
i
c
r
mo
e
s
pa
r
e
c
e)
30
or mor
m
m
0
196
99
147
170
When there are obstacles at the back, side with the installation of more than one unit.
250
or
m
m
m
or
e
e
or
250
m
m
m
or
e
e
mm
or
00
m
3
or
Page 8
4-4-2. INDOOR UNIT
MODELS : AR 30F, AR 30U, ART30U
Front view
(Unit : mm)
DUCT TYPE
DUCT TYPE
AR30W
AR30W
Side view (L)
Side view (R)
Top view
Rear view
Page 9
MOUNTING POSITION
150 mm
or more
150 mm or more
MAINTENANCE HOLE
It shall be possible to install and remove the control box.
300mm
DUCT TYPE
AR30W
500mm
500mm
100mm
It shall be possible to install and remove the control box, fan units and filter.
300mm
500mm
1550mm
DUCT TYPE
AR30W
100mm
WHEN USING A SQUARE DUCT
3,2
219
23
109
18
18
P174 x 6 = 1044
Page 10
4-5. REFRIGERANT CIRCUIT
MODELS : AR 30F / AO 30F
Outdoor Unit Indoor Unit
DUCT TYPE
DUCT TYPE
AR30W
AR30W
MODELS : AR 30U / AO 30U, ART30U / AOT30U
Outdoor Unit
Indoor Unit
Page 11
4-6. WIRING DIAGRAMS
4-6-1. OUTDOOR UNIT
MODEL : AO 30F
DUCT TYPE
DUCT TYPE
AR30W
AR30W
MODEL : AO 30U
Page 12
MODEL : AOT30U
DUCT TYPE
DUCT TYPE
AR30W
AR30W
- (04 - 11) -
Page 13
4-6-2. INDOOR UNIT
MODEL : AR 30F
DUCT TYPE
DUCT TYPE
AR30W
AR30W
MODELS : AR 30U, ART30U
Page 14
4-7. CAPACITY TABLE
Outdoor temperature
Outdoor temperature
18°CDB
12°CWB
18°CDB
12°CWB
Indoor temperature
15°CWB
32°CDB
16°CWB
18°CWB
19°CWB
21°CWB
27°CDB
29°CDB
23°CWB
22°CWB
23°CDB
21°CDB
15°CWB
30°CDB
21°CWB
21°CDB
16°CWB
22°CWB
23°CDB
26°CDB
29°CDB
Indoor temperature
32°CDB
23°CWB
27°CDB
30°CDB
18°CWB
19°CWB
26°CDB
(°CDB)
29°CDB
Indoor temperature
32°CDB
23°CWB
27°CDB
30°CDB
18°CWB
19°CWB
26°CDB
23°CDB
21°CDB
15°CWB
18°CDB
21°CWB
16°CWB
22°CWB
Outdoor temperature
12°CWB
4-7-1. COOLING
MODELS : AR 30F / AO 30F
AFR 23.3
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 9.59 7.16 1.87 9.78 7.19 1.92 9.97 7.22 1.94 10.25 7.52 1.97 10.38 7.46 1.98 10.60 7.33 2.00 10.70 7.26 2.02 10.79 7.56 2.03
5 9.25 6.97 2.11 9.46 7.00 2.15 9.69 7.02 2.17 10.03 7.38 2.21 10.17 7.34 2.22 10.42 7.24 2.26 10.53 7.18 2.27 10.64 7.49 2.28
10 8.85 6.73 2.32 9.07 6.75 2.37 9.29 6.80 2.40 9.67 7.19 2.45 9.82 7.16 2.47 10.08 7.08 2.50 10.20 7.03 2.52 10.32 7.35 2.54
15 8.44 6.49 2.55 8.64 6.53 2.60 8.86 6.57 2.63 9.21 6.96 2.68 9.36 6.94 2.71 9.63 6.87 2.75 9.75 6.83 2.77 9.86 7.16 2.79
20 8.41 6.27 2.79 8.59 6.30 2.84 8.80 6.34 2.87 9.13 6.72 2.92 9.28 6.70 2.95 9.55 6.64 3.00 9.68 6.60 3.02 9.80 6.94 3.05
25 8.74 6.47 2.42 8.96 6.50 2.44 9.16 6.53 2.46 9.50 6.90 2.50 9.65 6.87 2.52 9.91 6.80 2.55 10.03 6.76 2.56 10.15 7.08 2.58
30 8.19 6.17 2.65 8.42 6.21 2.67 8.61 6.28 2.69 8.93 6.64 2.73 9.08 6.62 2.75 9.34 6.56 2.79 9.47 6.53 2.81 9.59 6.87 2.82
35 7.61 5.91 2.89 7.76 5.96 2.90 7.96 5.99 2.93 8.26 6.35 2.97 8.40 6.34 2.99 8.67 6.30 3.03 8.80 6.27 3.05 8.93 6.62 3.07
40 6.93 5.61 3.13 7.03 5.64 3.14 7.20 5.66 3.16 7.49 6.03 3.21 7.63 6.02 3.23 7.89 5.99 3.28 8.03 5.98 3.30 8.15 6.34 3.35
43 6.44 5.36 3.28 6.55 5.42 3.28 6.70 5.44 3.31 6.99 5.82 3.35 7.14 5.82 3.38 7.40 5.80 3.43 7.55 5.80 3.45 7.68 6.16 3.47
MODELS : AR 30U / AO 30U
AFR 23.3
COOLING CAPACITY
DUCT TYPE
DUCT TYPE
AR30W
(°CDB) TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 9.59 7.16 1.87 9.78 7.19 1.92 9.97 7.22 1.94 10.25 7.52 1.97 10.38 7.46 1.98 10.60 7.33 2.00 10.70 7.26 2.02 10.79 7.56 2.03
5 9.25 6.97 2.11 9.46 7.00 2.15 9.69 7.02 2.17 10.03 7.38 2.21 10.17 7.34 2.22 10.42 7.24 2.26 10.53 7.18 2.27 10.64 7.49 2.28
10 8.85 6.73 2.32 9.07 6.75 2.37 9.29 6.80 2.40 9.67 7.19 2.45 9.82 7.16 2.47 10.08 7.08 2.50 10.20 7.03 2.52 10.32 7.35 2.54
15 8.44 6.49 2.55 8.64 6.53 2.60 8.86 6.57 2.63 9.21 6.96 2.68 9.36 6.94 2.71 9.63 6.87 2.75 9.75 6.83 2.77 9.86 7.16 2.79
20 8.41 6.27 2.79 8.59 6.30 2.84 8.80 6.34 2.87 9.13 6.72 2.92 9.28 6.70 2.95 9.55 6.64 3.00 9.68 6.60 3.02 9.80 6.94 3.05
25 8.74 6.47 2.42 8.96 6.50 2.44 9.16 6.53 2.46 9.50 6.90 2.50 9.65 6.87 2.52 9.91 6.80 2.55 10.03 6.76 2.56 10.15 7.08 2.58
30 8.19 6.17 2.65 8.42 6.21 2.67 8.61 6.28 2.69 8.93 6.64 2.73 9.08 6.62 2.75 9.34 6.56 2.79 9.47 6.53 2.81 9.59 6.87 2.82
35 7.61 5.91 2.89 7.76 5.96 2.90 7.96 5.99 2.93 8.26 6.35 2.97 8.40 6.34 2.99 8.67 6.30 3.03 8.80 6.27 3.05 8.93 6.62 3.07
40 6.93 5.61 3.13 7.03 5.64 3.14 7.20 5.66 3.16 7.49 6.03 3.21 7.63 6.02 3.23 7.89 5.99 3.28 8.03 5.98 3.30 8.15 6.34 3.35
43 6.44 5.36 3.28 6.55 5.42 3.28 6.70 5.44 3.31 6.99 5.82 3.35 7.14 5.82 3.38 7.40 5.80 3.43 7.55 5.80 3.45 7.68 6.16 3.47
AR30W
MODELS : ART30U / AOT30U
AFR 23.8
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
0 9.71 7.27 1.97 9.89 7.31 2.03 10.09 7.33 2.04 10.38 7.64 2.07 10.50 7.58 2.09 10.72 7.45 2.11 10.82 7.38 2.12 10.92 7.68 2.13
5 9.36 7.08 2.22 9.57 7.11 2.26 9.81 7.14 2.29 10.15 7.50 2.33 10.29 7.46 2.34 10.55 7.35 2.38 10.66 7.29 2.39 10.77 7.61 2.41
10 8.96 6.83 2.44 9.18 6.86 2.50 9.40 6.91 2.53 9.79 7.30 2.58 9.94 7.27 2.60 10.20 7.19 2.64 10.32 7.14 2.66 10.44 7.46 2.68
15 8.54 6.60 2.68 8.74 6.63 2.74 8.97 6.68 2.77 9.32 7.07 2.83 9.47 7.05 2.85 9.74 6.98 2.90 9.87 6.94 2.92 9.98 7.27 2.94
20 8.51 6.37 2.94 8.70 6.40 2.99 8.90 6.44 3.02 9.24 6.82 3.08 9.39 6.80 3.11 9.66 6.74 3.16 9.79 6.71 3.18 9.91 7.05 3.21
25 8.85 6.57 2.55 9.07 6.60 2.58 9.27 6.64 2.60 9.62 7.01 2.63 9.77 6.98 2.65 10.03 6.90 2.69 10.15 6.86 2.70 10.27 7.19 2.72
30 8.28 6.27 2.79 8.52 6.31 2.81 8.71 6.38 2.84 9.04 6.75 2.88 9.19 6.73 2.90 9.46 6.67 2.94 9.59 6.64 2.96 9.71 6.98 2.97
35 7.71 6.00 3.04 7.85 6.05 3.06 8.05 6.09 3.08 8.36 6.45 3.13 8.50 6.44 3.15 8.77 6.40 3.19 8.90 6.37 3.21 9.03 6.73 3.23
40 7.01 5.70 3.30 7.12 5.73 3.31 7.28 5.75 3.33 7.58 6.12 3.38 7.72 6.12 3.41 7.99 6.09 3.46 8.12 6.08 3.48 8.25 6.44 3.53
43 6.52 5.44 3.45 6.63 5.50 3.46 6.78 5.53 3.48 7.08 5.91 3.53 7.22 5.91 3.56 7.49 5.89 3.61 7.64 5.89 3.63 7.77 6.26 3.66
AFR: Air flow rate (m3/min) TC : Total capacity (kW) SHC: Sensible Heat capacity (kW) PI : Power Input (kW)
Page 15
4-7-2. HEATING
(°CDB) (°CWB) TC PI TC PI TC PI TC PI TC PI TC PI TC PI
-7 -9 6.18 1.99 6.08 2.05 5.89 2.11 5.70 2.18 5.61 2.21 5.42 2.27 5.23 2.30
-4 -6 6.75 2.15 6.65 2.21 6.46 2.27 6.27 2.34 6.18 2.37 5.99 2.43 5.80 2.46
1 -1 7.60 2.43 7.51 2.49 7.32 2.56 7.13 2.62 7.03 2.65 6.84 2.71 6.65 2.75
5 3 9.31 2.49 9.22 2.55 9.03 2.60 8.84 2.66 8.74 2.68 8.55 2.74 8.36 2.76
7 6 9.79 2.52 9.69 2.58 9.50 2.63 9.31 2.68 9.22 2.71 9.03 2.76 8.84 2.79
12 10 10.45 2.71 10.36 2.76 10.17 2.81 9.98 2.87 9.88 2.89 9.69 2.95 9.50 2.97
15 13 10.55 2.81 10.45 2.87 10.26 2.92 10.07 2.97 9.98 3.00 9.79 3.05 9.60 3.08
20 15 9.79 2.52 9.69 2.58 9.50 2.63 9.31 2.68 9.22 2.71 9.03 2.76 8.84 2.79
24 17 9.22 2.37 9.12 2.42 8.93 2.47 8.74 2.52 8.65 2.55 8.46 2.60 8.27 2.63
18°CDB
20°CDB
Indoor temperature
Outdoor temperature
27°CDB
30°CDB
25°CDB
23°CDB
16°CDB
( °CDB)
( °CWB)
Outdoor temperature
27 °CDB
30 °CDB
25 °CDB
23 °CDB
16 °CDB
18 °CDB
20 °CDB
Indoor temperature
MODELS : AR 30U / AO 30U
AFR 23.3
MODELS : ART30U / AOT30U
AFR 23.8
HEATING CAPACITY
DUCT TYPE
DUCT TYPE
AR30W
-7 -9 6.18 2.12 6.08 2.18 5.89 2.25 5.70 2.32 5.61 2.35 5.42 2.42 5.23 2.45
-4 -6 6.75 2.28 6.65 2.35 6.46 2.42 6.27 2.49 6.18 2.52 5.99 2.59 5.80 2.62
1 -1 7.60 2.59 7.51 2.65 7.32 2.72 7.13 2.79 7.03 2.82 6.84 2.89 6.65 2.92
5 3 9.31 2.66 9.22 2.71 9.03 2.77 8.84 2.83 8.74 2.86 8.55 2.91 8.36 2.94
7 6 9.79 2.69 9.69 2.74 9.50 2.80 9.31 2.86 9.22 2.88 9.03 2.94 8.84 2.97
12 10 10.45 2.88 10.36 2.94 10.17 3.00 9.98 3.05 9.88 3.08 9.69 3.14 9.50 3.16
15 13 10.55 3.00 10.45 3.05 10.26 3.11 10.07 3.16 9.98 3.19 9.79 3.25 9.60 3.28
20 15 9.79 2.69 9.69 2.74 9.50 2.80 9.31 2.86 9.22 2.88 9.03 2.94 8.84 2.97
24 17 9.22 2.52 9.12 2.58 8.93 2.63 8.74 2.69 8.65 2.72 8.46 2.77 8.27 2.80
AFR: Air flow rate (m3/min) TC : Total capacity (kW) PI : Power Input (kW)
TC PI TC PI TC PI TC PI TC PI TC PI TC PI
AR30W
Page 16
4-8. CAPACITY COMPENSATION FOR PIPE LENGTH
5 7.5 10 15 20 25 30
15 - - - 0.952 0.919 0.888 0.857
10 - - 0.985 0.952 0.919 0.888 0.857
7.5 - 1.000 0.985 0.952 0.919 0.888 0.857
5 1.010 1.000 0.985 0.952 0.919 0.888 0.857
0 1.010 1.000 0.985 0.952 0.919 0.888 0.857
-5 1.002 0.992 0.977 0.944 0.912 0.881 0.850
-7.5 - 0.988 0.973 0.941 0.908 0.877 0.847
-10 - - 0.969 0.937 0.904 0.874 0.843
-15 - - - 0.929 0.897 0.867 0.836
PIPE LENGTH (m)
COOLING
HEIGHT DIFFERENCE (m)
Outdoor unit
is up-side
Outdoor unit is
bottom-side
AND HEIGHT DIFFERENCE
MODELS :
AR 30F / AO 30F
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
DUCT TYPE
DUCT TYPE
AR30W
AR30W
Page 17
MODELS : AR 30U / AO 30U, ART30U / AOT30U
PIPE LENGTH (m)
Outdoor unit is
bottom-side
Outdoor unit
is up-side
COOLING
HEIGHT DIFFERENCE (m)
HEIGHT DIFFERENCE (m)
PIPE LENGTH (m)
HEATING
Outdoor unit
is up-side
Outdoor unit is
bottom-side
COEFFICIENT OF COMPENSATION FOR HEIGHT DIFFERENCE
5 7.5 10 15 20 25 30
15 - - - 0.952 0.919 0.888 0.857
10 - - 0.985 0.952 0.919 0.888 0.857
7.5 - 1.000 0.985 0.952 0.919 0.888 0.857
5 1.010 1.000 0.985 0.952 0.919 0.888 0.857
0 1.010 1.000 0.985 0.952 0.919 0.888 0.857
-5 1.002 0.992 0.977 0.944 0.912 0.881 0.850
-7.5 - 0.988 0.973 0.941 0.908 0.877 0.847
-10 - - 0.969 0.937 0.904 0.874 0.843
-15 - - - 0.929 0.897 0.867 0.836
DUCT TYPE
AR30W
5 7.5 10 15 20 25 30
DUCT TYPE
AR30W
15 - - - 0.956 0.939 0.922 0.904
10 - - 0.979 0.961 0.943 0.927 0.909
7.5 - 0.993 0.982 0.964 0.946 0.929 0.911
5 1.005 0.995 0.984 0.966 0.948 0.931 0.913
0 1.010 1.000 0.989 0.971 0.953 0.936 0.918
-5 1.010 1.000 0.989 0.971 0.953 0.936 0.918
-7.5 - 1.000 0.989 0.971 0.953 0.936 0.918
-10 - - 0.989 0.971 0.953 0.936 0.918
-15 - - - 0.971 0.953 0.936 0.918
Page 18
4-9. ADDITIONAL CHARGE CALCULATION
R410A
2300
7.5 10 15 20 25 30 (MAX)
20g / m
R410A
2300
7.5 10 15 20 25 30 (MAX)
40g / m
MODELS :
REFRIGERANT TYPE
REFRIGERANT AMOUNT
AR 30F / AO 30F
g
REFRIGERANT CHARGE
PIPE LENGTH m
ADDITIONAL CHARGE
g
0 (Charge less) + 50 + 150 + 250 + 350 + 450
MODELS : AR 30U / AO 30U, ART30U /AOT30U
REFRIGERANT TYPE
REFRIGERANT AMOUNT g
REFRIGERANT CHARGE
DUCT TYPE
PIPE LENGTH m
AR30W
ADDITIONAL CHARGE
g
0 (Charge less) + 100 + 300 + 500 + 700 + 900
DUCT TYPE
AR30W
Page 19
4-10. OPERATION RANGE
AR*30F AO*30F
Cooling
Dry
Cooling
Dry
Heating 16 to 30 °C -7 to 24 °C
AR*30U
ART30U
AO*30U
AOT30U
About 80% or less
Model
Mode
Operation Range
Model
Mode
Operation Range
COOLING MODEL
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
HEAT PUMP MODEL
Indoor unit Outdoor unit Indoor temperature Indoor humidity Outdoor temperature
18 to 32 °C About 80% or less 0 to 43 °C
18 to 32 °C 0 to 43 °C
DUCT TYPE
DUCT TYPE
AR30W
AR30W
Page 20
30 50 80 100 120 140 150
m3/h
1800 1700 1540 1400 1240 1100 850
l/s 500 472 428 389 344 306 236
CFM 1059 1001 906 824 730 647 500
m3/h
1620 1520 1320 1240 1080 850 -
l/s 450 422 367 344 300 236 -
CFM 953 895 777 730 636 500 -
m3/h
1440 1350 1200 1060 920 - -
l/s 400 375 333 294 256 - -
CFM 848 795 706 624 541 - -
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
4-11. FAN PERFORMANCE AND AIR FLOW
70.0
80.0
90.0
100.0
110.0
120.0
130.0
140.0
500 1,000 1,500 2,000
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
COOLING
86.0
88.0
90.0
92.0
94.0
96.0
98.0
100.0
102.0
104.0
106.0
108.0
500 1,000 1,500 2,000
35.0
40.0
45.0
50.0
55.0
HEATING
4-11-1. NORMAL MODE
MODELS : AR 30F / AR 30U
160
Q-h Characteristic curve
DUCT TYPE
AR30W
140
120
100
80
60
40
20
STATIC PRESSURE(Pa)
0 500 1000 1500 2000
Air temp
Capacity
Cooling capacity(%)
Hi
Med
Low
DUCT TYPE
AR30W
Air temperature(°C)
Air temp
Capacity
Heating capacity(%)
Testcondition:NofilterandFanmode.
AIR FLOW (m3/h)
Air temperature(°C)
Page 21
MODEL : ART30U
30 50 80 100 120 140 150
m3/h
1850 1750 1580 1430 1260 1020 820
l/s 514 486 439 397 350 283 228
CFM 1089 1030 930 842 742 600 483
m3/h
1680 1580 1400 1280 1100 880 -
l/s 467 439 389 356 306 244 -
CFM 989 930 824 753 647 518 -
m3/h
1520 1430 1250 1120 960 - -
l/s 422 397 347 311 267 - -
CFM 895 842 736 659 565 - -
240V
FAN SPEED
Hi
Med
Low
Static pressure (Pa)
Q-h Characteristic curve
160
140
120
DUCT TYPE
AR30W
100
80
60
40
20
STATIC PRESSURE(Pa)
0
500 1000 1500 2000
Hi
Med
Low
DUCT TYPE
AR30W
140.0
130.0
120.0
110.0
100.0
90.0
Cooling capacity(%)
80.0
70.0 500 1,000 1,500 2,000
108.0
106.0
104.0
102.0
100.0
98.0
96.0
94.0
92.0
90.0
Heating capacity(%)
88.0
86.0
500 1,000 1,500 2,000
Air temp
Capacity
Air temp
Capacity
COOLING
HEATING
14.0
13.0
12.0
11.0
10.0
9.0
8.0
7.0
55.0
50.0
45.0
40.0
35.0
Air temperature(°C)
Air temperature(°C)
Testcondition:NofilterandFanmode.
AIR FLOW (m3/h)
Page 22
4-11-2. LOW STATIC MODE
30 50 70 100
m3/h
1600 1510 1420 1240
l/s 444 419 394 344
CFM 942 889 836 730
m3/h 1430 1350 1250 -
l/s 397 375 347 -
CFM 842 795 736 -
m3/h
1280 1200 1110 -
l/s 356 333 308 -
CFM 753 706 653 -
FAN SPEED
Hi
Med
Low
230V
Static pressure (Pa)
MODELS : AR 30F / AR 30U
Q-h Characteristic curve
120
100
DUCT TYPE
AR30W
DUCT TYPE
AR30W
80
Hi
Med
Low
DUCT TYPE
AR30W
60
40
20
STATIC PRESSURE(Pa)
0
500 1000 1500 2000
108.0
106.0
104.0
102.0
100.0
98.0
Cooling capacity(%)
96.0 1,200 1,300 1,400 1,500 1,600 1,700
104.0
103.0
Air temp
Capacity
Air temp
Capacity
COOLING
HEATING
14.0
13.5
13.0
12.5
12.0
11.5
11.0
42.0
41.0
102.0
101.0
100.0
99.0
Heating capacity(%)
98.0 1,200 1,300 1,400 1,500 1,600 1,700
Testcondition:NofilterandFanmode.
AIR FLOW (m3/h)
40.0
39.0
38.0
37.0
36.0
Air temperature(°C) Air temperature(°C)
Page 23
MODEL : ART30U
30 50 80 100
m3/h
1680 1580 1420 1250
l/s 467 439 394 347
CFM 989 930 836 736
m3/h
1520 1430 1250 -
l/s 422 397 347 -
CFM 895 842 736 -
m3/h
1380 1280 1120 -
l/s 383 356 311 -
CFM 812 753 659 -
Static pressure (Pa)
240V
FAN SPEED
Hi
Med
Low
Q-h Characteristic curve
120
Hi
100
80
DUCT TYPE
AR30W
60
Med
Low
DUCT TYPE
AR30W
40
20
STATIC PRESSURE(Pa)
0
500 1000 1500 2000
108.0
106.0
104.0
102.0
100.0
98.0
Cooling capacity(%)
96.0 1,200 1,300 1,400 1,500 1,600 1,700
104.0
103.0
Air temp
Capacity
Air temp
Capacity
COOLING
HEATING
14.0
13.5
13.0
12.5
12.0
11.5
11.0
42.0
41.0
102.0
101.0
100.0
99.0
Heating capacity(%)
98.0 1,200 1,300 1,400 1,500 1,600 1,700
Testcondition:NofilterandFanmode.
AIR FLOW (m3/h)
40.0
39.0
38.0
37.0
36.0
Air temperature(°C) Air temperature(°C)
Page 24
4-12. NOISE LEVEL CURVE
NC-45
4-12-1. OUTDOOR UNIT
COOLING HEATING
MODELS : AO 30F, AO 30U
MODELS : AO 30U, AOT30U
AOT30U
Condition Fan speed : High Voltage : 230 -240V /50Hz
80
70
NC-65
60
DUCT TYPE
AR30W
50
40
dB:(0dB=0.0002bar)
Octave band sound pressure level,
30
NC-60
NC-55
NC-50
NC-40
NC-35
NC-30
80
70
60
50
40
dB:(0dB=0.0002bar)
Octave band sound pressure level,
30
Condition Fan speed : High Voltage : 230 -240V /50Hz
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
DUCT TYPE
AR30W
NC-25
20
10
0
63 125 250 5 00 1,000 2,0 00 4,000 8,000
Octave band center frequency, Hz
NC-20
NC-15
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
NC-25
NC-20
NC-15
Page 25
4-12-2. INDOOR UNIT
HIGH
LOW
HIGH
LOW
COOLING HEATING
MODELS : AR 30F, AR 30U
MODELS : AR 30U, ART30U
ART30U
Condition Fan speed : High, Low Voltage : 230-240V /50Hz Static pressure : 100Pa
80
70
NC-65
60
DUCT TYPE
AR30W
50
40
dB:(0dB=0.0002bar)
Octave band sound pressure level,
30
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
80
70
60
50
40
dB:(0dB=0.0002bar)
Octave band sound pressure level,
30
Condition Fan speed : High, Low Voltage : 230-240V /50Hz Static pressure : 100Pa
NC-65
NC-60
NC-55
NC-50
NC-45
NC-40
NC-35
NC-30
DUCT TYPE
AR30W
NC-25
20
10
0
63 125 250 5 00 1,000 2,0 00 4,000 8,000
Octave band center frequency, Hz
NC-20
NC-15
20
10
0
63 125 250 500 1,000 2,000 4,000 8,000
Octave band center frequency, Hz
NC-25
NC-20
NC-15
Page 26
4-13. ELECTRIC CHARACTERISTICS
Main Fuse (Circuit breaker) Current
mm
2
Model Name
AR 30F
AR 30U
AO 30F
AO 30U
Power Supply
230
230
50
50
Rated Value
Mode
*1) Wiring Spec
302130
3.5
3.5
21
Indoor Fan Motor
0.15
0.15
0.67
0.67
0.7
0.7
-
36(240V)
Outdoor Fan Motor
0.14
0.14
ART30U
AOT30U
240
50
30
3.5
21
36(240V)
0.15
0.67
0.14
0.7
MODELS : AR 30F / AO 30F AR 30U / AO 30U, ART30U / AOT30U
Indoor unit
Outdoor unit
Voltage V
Frequency Hz
Current A 14.0 - 14.0 12.4 14.3 13.1
Input kW 2.99 - 2.99 2.63 3.15 2.80
Max Operating Current A 17.0 - 17.6 16.0 17.0 16.0
Starting Current A 70 - 70 70 70 70
A
Power Cable
*2)Limited wiring length m
Input kW
DUCT TYPE
AR30W
Belt heater W
Full Load Amp. A
Input kW
Full Load Amp. A
Cooling - Cooling Heating Cooling Heating
DUCT TYPE
AR30W
*1) Wiring Spec : Selected Sample
(Selected based on Japan Electrotechnical Standard and Codes Committee E0005)
*2) Limited Wiring length : This is the wiring length in case voltage descent is less than 2%.
When the wiring length becomes long, please select the wiring of a more larger diameter.
Page 27
4-14. SAFETY DEVICE
AO 30F
AO AOT30U
30U
FUSE (SIDE OF INDOOR UNIT)
AR 30F
AR ART30U
30U
5A 250V
150°C ± 5°C OFF
OFF : 25°C(78A 120°C(29.6A ON : 90 ± 10°C
3.15A 250V
150°C ± 5°C OFF
OUTDOOR UNIT
MODEL NAME PROTECTION FORM
-
FUSE ON PCB - - 3.15A 250V
FAN MOTOR PROTECTOR THERMAL PROTECTOR
COMPRESSOR -
INDOOR UNIT
MODEL NAME PROTECTION FORM
PCB FUSE -
DUCT TYPE
FAN MOTOR PROTECTOR THERMAL PROTECTOR
AR30W
DUCT TYPE
AR30W
Page 28
4-15. EXTERNAL INPUT & OUTPUT
PREP
ARA
When the external input / output is used, connect the external signal wire as shown in the figure below.
TION
CN106 (Black)
CN5
(Black)
PCB
Indoor unit PCB
CONTROL
INPUT
[Example]
You can control air conditioner on/off by external control. You can select either Edge and Pulse.
Indoor unit
+
1
2
3
Ch1
-
CN114
DUCT TYPE
AR30W
(White)
Field supply
DUCT TYPE
AR30W
DIP Switch (Indoor Unit)
SW state
ON
PulseEdge
SW2
DIP-Switch
NO.
OFF
2
1 Edge
1.The last command has priority.
2.The wire connection is separate from the power cable line.
Ch1 (Input)
Remote controller
Indoor unit
On
Off
On
Operation
Stop
2 Pulse
Ch1 (Input)
Remote controller
Indoor unit
Operation
Stop
200ms 200ms 200ms
On
Off
Page 29
OPERA
[Example]
TION DISPLA
Y
Operation indicator
Field supply
Operation
Ic
Vc
or
Vc : DC20V or Iess Ic : 10mA or Iess
Indoor unit
CN115
(WHITE)
+
2
1
-
Indoor unit
Stop
SHORT
CN115 (Output)
DUCT TYPE
AR30W
FRESH
AIR OUTPUT SETTING
OPEN
DUCT TYPE
AR30W
You can control sub fan by synchronizaton with fan operation of indoor unit.
[Example]
+
Indoor unit
-
CN14
(GREEN)
1
2
Indoor unit fan
CN14
(Output)
Field supplied
Operation
Stop
14V
0V
Fuse
Power
Fan, other
Page 30
EXTERNAL
ELECTRICAL HEA
TER OUTPUT SETTING
You can control Electrical heater (Booster) by sychronization with heating operation. When temperature is -10 to -3 degrees from Setpoint,External electrical heater is ON. When temperature is -1 degrees from Setpoint,External electrical heater Stops.
Jumper wire (Indoor Unit)
This is used to continue indoor unit fan operation for 1 minute after thermo OFF in heating mode. 1 minute delay control set by cutting JM3 on PCB.
[Example]
Fuse
Indoor unit
+
1
2
-
CN15
(ORANGE)
DUCT TYPE
AR30W
Indoor unit
Heating
Indoor
Operation
Stop
Operation
Field supplied
unit fan
Stop
14V
CN15
(Output)
0V
<Operation condition>
All conditions shall be met.
Under heating operation.
Fan mode : Either Hi, Med, Low, Quiet.
Power
External Heater, other.
1min
DUCT TYPE
AR30W
Cold air prevention function not working (Heat exchanger temperature over 27 C ).
Temperature subtracted set temperature from room temperature is between -10 C to -3 C.
-10 C < *T < -3 C *T=Room temperature
Compressor 3 minutes stop mode is released.
Defrosting mode is released.
<Release condition>
Do not meet above condition , or room temperature is 1 C below from set temperature.
CAUTION!
!
Please locate external a heater between the indoor unit and the ductwork. Please be sure to use delay control of a fan.
External Heater
Supply air
Indoor unit
Return air
Page 31
4-16. FUNCTION SETTING
4-16-1. INDOOR UNIT
1
Low static pressure function setting
SW 1
DIP SW
SW 2
Rotary SW SW 3 Indoor unit number setting
Jumper Wire
SWITCH POSITION
DUCT TYPE
AR30W
Duct type Indoor unit control circuit board
2
Forbidden
3
4
1 Room temperature correct coefficient of heating
2 External input select
3 Auto restart validity/invalidity
JM1 Room temperature correct coefficient of cooling
JM2 Commercial mode setting
JM3 Fan delay setting
INDOOR UNIT
DUCT TYPE
AR30W
CN114
CN106
CN115
CN4
CN5
CN16
CN14
CN15
MAIN PCBPOWER PCB
SW1 SW2
1 2 3 1 2 34
ON
OFF
SW1 SW2
SW3
ON
OFF
JM1 JM2 JM3
CN16
Page 32
4-16-2. SWITCH FUNCTION (INDOOR UNIT)
SW2-1 SW state
OFF +4 deg (Ceiling setting)
ON 0 deg (Room setting)
SW2-2 SW state
OFF Edge
ON Pulse
SW2-3 SW state
OFF Validity
ON Invalidity
SW3 SW state
0 single
1-15 Indoor unit address
SW1-1 SW state
OFF Normal
ON Low static pressure
SW1-2 OFF
SW1-3 OFF
SW1-4 OFF
DIP SWITCH SETTING
1. SW1 setting
1-1 Low static pressure function setting
In case of installing in low static , you can minimize air flow and noise.
( Factory setting)
1-2 Dip SW 1-2,1-3,1-4 setting forbidden
( Factory setting)
2. SW2 setting
DUCT TYPE
DUCT TYPE
AR30W
2-1 Room temperature correct coefficient of heating.
Decide the heating temperature correct coefficient vale of heating.
Heat temperature corrction
( Factory setting)
2-2 Control input setting
This switch is used to select the format of external input command as shown in the table below.
( Factory setting)
2-3 Auto restart setting
Auto restart function can be selected by turning this switch ON/OFF.
AR30W
( Factory setting)
ROTARY SWITCH SETTING
This switch can be used when group control system. Set the indoor unit address in the 1,2,-,15 order.
( Factory setting)
Page 33
JUMPER WIRE SETTING
Connector INPUT OUTPUT REMARKS
CN114
CONTROL INPUT
(OPERATION/STOP)
-
CN115 - OPERATION DISPLAY
CN14 - FRESH AIR
CN15 - ELECTRICAL HEATER
See external
input/output settings
for details.
JM2 JM state
Connect Residencial
Disconnect Commercial
JM3 JM state
Connect Invalidity
Disconnect Validity
JM1 JM state
Connect 0 deg
Disconnect + 2 deg
Room temperature correct coefficient of cooling.
Decide the cooling temperature correct coefficient value of cooling.
Cool temperature corrction
( Factory setting)
Commercial mode setting
"Hot start" can be canceled,fan operates continously when indoor unit is ON on every mode. When you select "FAN:AUTO"mode fan goes in "HIGH"
( Factory setting)
DUCT TYPE
Fan delay setting
AR30W
DUCT TYPE
AR30W
This setting can be used when the auxiliary heater is mounted. When the fan operation is stopped when the indoor unit is operating with an auxiliary heater,the fan operation continues one minutes.
( Factory setting)
EXTERNAL INPUT AND OUTPUT
Page 34
4-16-3. WIRED, SIMPLE REMOTE CONTROLLER CIRCUIT BOARD
Wired,Simple remote controller
1
Dual remote controller setting
2
Group control setting
DIP SW
SWITCH POSITION
Wired remote controller
Front case (back side)
3
4
Model setting
Auto changeover setting
5
6
Memory backup setting
DUCT TYPE
AR30W
OFF
ON
1 2 3 4 5 6
DUCT TYPE
AR30W
ON
DIP Switch
Simple remote controller
ON
ON
OFF
12345
6
DIP switches
Page 35
4-16-4. WIRED, SIMPLE REMOTE CONTROLLER
DIP SWITCH SETTING
1. SW setting
1-1 Dual remote controller setting
Set the remote controller DIP switch No.1 and 2 according to the following table.
( Factory setting)
Number of remote controller
1 (Normal)
2 (Dual)
1-2 Group control setting
Number of indoor unit connection (One/Multiple) This is switched according to the number of connected indoor units.
DUCT TYPE
AR30W
DIP-SW No.3
OFF
Master unit Slave unit
DIP-SW No.1
DIP-SW No.2
ON
OFF
( Factory setting)
Number of indoor unit
One unit connection
OFF
OFF
DIP-SW No.1
ON ON
DIP-SW No.2
DUCT TYPE
AR30W
ON Multiple unit connection
1-3 Model setting
The system type of the outdoor unit can be selected by setting up DIP switch No.4 as follows.
( Factory setting)
DIP-SW No.4
OFF
ON Cooling only model
Heat Pump model
Model
1-4 Auto changeover setting
Selecting auto changeover validity / invalidity.
( Factory setting)
DIP-SW No.5
OFF
ON Validity
Auto changeover
Invalidity
1-5 Memory backup setting
Set to ON to use batteries for the memory backup.if batteries are not used, all of the settings stored in memory will be deleted if there is a power failure.
This function is wired remotecontroll only.
( Factory setting)
DIP-SW No.6
OFF
ON Validity
Memory backup
Invalidity
Page 36
4-17. OPTIONAL PARTS
SIMPLE REMOTE CONTROLLERS UTB - YPB : FUJITSU BRAND UTB - GPB : GENERAL BRAND UTB - TPB : Australia only
Remote controller which gives priority to ease-of-use and allows operation of the necessary functions only.
REMOTE SENSOR UNIT UTD - RS100
Accurate and Comfortable
New amenity space can be offered by installing the thermo sensor in the remote controller. Because the remote controller has the switching function, the user can select the position of the sensor. (Room temperature sensor selection)
DUCT TYPE
AR30W
Example of room temperature sensor selection
Simple remote
controllers
Remote Sensor
in the bed room (effective at night)
DUCT TYPE
AR30W
Sensor part
Wired Remote Controller
LONG LIFE FILTER
THERMO
Day
The detecting point can be freely changed.
SENSOR
Night
Remote Controller in the living room (effective during the day)
Remote Sensor (Optional Parts)
UTD - LF25NA
Intake air filter can be mounted to the indoor unit.
Page 37
SQUARE FLANGE (UTD - SF045T)
ROUND FLANGE (UTD - RF204)
Round flange is used when the fresh air duct is installed.
DUCT TYPE
AR30W
DUCT TYPE
DUCT TYPE
AR30W
DUCT TYPE
AR30W
AR30W
Air intake hole
Round flange