SPLIT TYPE AIR CONDITIONER
Fig. 4
Cassette Type
INSTALLATION INSTRUCTION SHEET
(PART NO. 9366379027)
For authorized service personnel only.
WARNING!
CAUTION!
1 For the air conditioner to operate satisfactorily, install it as outlined in this installation instruction sheet.
2 Connect the indoor unit and outdoor unit with the room air conditioner piping and cords available from our
standard parts. This installation instruction sheet describes the correct connections using the installation set
available from our standard parts.
3 Installation work must be performed in accordance with national wiring standards by authorized personnel only.
4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a
flame, it produces a toxic gas.
5 Do not turn on the power until all installation work is complete.
•
Be careful not to scratch the air conditioner when handling it.
•
After installation, explain correct operation to the customer, using the operating manual.
•
Let the customer keep this installation instruction sheet because it is used when the air conditioner is serviced or moved.
•
The maximum length of the piping is shown in Table 1. If the units are further apart than this, correct operation
cannot be guaranteed.
STANDARD PARTS
The following installation parts are furnished. Use them as required.
INDOOR UNIT ACCESSORIES
Name and Shape Q’ty Application
Coupler heat insulation
Remote
controller
cord clamp
Screw
Special nut A
(large flange)
Special nut B
(small flange)
This mark indicates procedures which, if improperly performed, might lead to the death or serious
injury of the user.
This mark indicates procedures which, if improperly performed, might possibly result in personal
harm to the user, or damage to property.
WARNING
CAUTION
Since 2-way outlet as shown below causes performance
problems, do not set it.
For indoor side pipe joint
INDOOR UNIT
2
For installing the remote
controller cord
10
For installing the remote
10
controller cord clamp
For installing the remote
2
controller
For installing indoor unit
4
For installing indoor unit
4
Install the indoor unit on a place having a sufficient strength so that
(1)
it withstands against the weight of the indoor unit.
The inlet and outlet ports should not be obstructed; the air should
(2)
be able to blow all over the room.
Leave the space required to service the air conditioner (Fig. 2).
(3)
The ceiling rear height as shown in Fig. 3.
(4)
A place from where the air can be distributed evenly throughout the
(5)
room by the unit.
A place from where drainage can be extracted outdoors easily.
(6)
Install the unit where noise and vibrations are not amplified.
(7)
Fig. 2
Strong and durable ceiling
12”
(300 mm)
or more
AIR
12”
(300 mm)
or more
24” (600 mm)
or more
24” (600 mm)
or more
12”
(300 mm)
or more
CONNECTION PIPE REQUIREMENT
Table 1
Small
3/8”
(9.53 mm)
Diameter
(15.88 mm)
Maximum length
Large Cooling
5/8”
99 ft
(30 m)
Reverse
cycle
82 ft
(25 m)
Maximum height
(between indoor
and outdoor)
50 ft
(15 m)
• Use 0.7 mm to 1.2 mm thick pipe.
• Use pipe with water-resistant heat insulation.
• Use pipe that can withstand a pressure of 3,040 kPa.
ELECTRICAL REQUIREMENT
• Electric wire size and fuse/breaker capacity:
Table 2
Power
supply
cord
(mm2)
Connection
cord
2
(mm
)
Fuse/Breaker capacity (A)
•
Always use H07RN-F or equivalent to the connection cord.
Install the disconnect device with a contact gap of at least 3 mm
•
nearby the units (both indoor unit and outdoor unit).
MAX
MIN
MAX
MIN
4.0
3.5
2.5
1.0
30
Pull up while pressing the B section (Fig. 7).
•
Fig. 7 Part A detail view Fig. 8 Part A section view
B
Grille hinge wire
Remove the intake grille.
(4)
REMOVING THE PANEL FRAME
Pull up the corner sections (A) of the panel frame as shown in
•
Fig. 9. (4 locations)
Fig. 9 Part A detail view
A
B
A
Pull up in the direction of the arrow while holding down the C
•
section of Fig. 10. (4 locations)
Fig. 10 Part B detail view
Fig. 11
Panel frame
A
A
C
Fig. 14
(A) Standard setting
Drain pipe (I.D. 32 mm)
11-3/4” (298.5 mm)
9-25/32”
(248.5 mm)
11-3/4” (298.5 mm)
9-25/32”
(248.5 mm)
(70 mm)
(100 mm)
2-3/4”
3-15/16”
(127 mm)
5”
(70 mm)
(100 mm)
2-3/4”
3-15/16”
(92 mm)
3-5/8”
2-3/8”
(60 mm)
(B) Slender setting
2-3/8”
(60 mm)
12” (305.5 mm)
Drain pipe (I.D. 32 mm)
12” (305.5 mm)
3. BODY INSTALLATION
[The ceiling rear height is 9-1/4” (235 mm) or more.] [Standard setting]
[The ceiling rear height is 7-7/8” (200 mm) or more.] [Slender setting]
Install special nut A, then special nut B onto the hanging bolt (Fig. 15).
(1)
Raise the body and mount its hooks onto the hanging bolt be-
(2)
tween the special nuts (Fig. 15).
Turn special nut B to adjust the height of the body (Fig. 15).
(3)
Leveling
(4)
Using a level, or vinyl hose filled with water, fine adjust so that the
body is level.
WARNING
Perform final tightening by tightening the double nut firmly.
Fig. 15
Special nut A
After installing the body,
tighten the nuts.
Ceiling
* Must fit tightly against
ceiling without any gap.
Fig. 16
Special nut B
Hanging bolt
Hook
30 mm
or more
2 4
9-1/4” (235 mm)
7-7/8” (200 mm)
3
INSTALLING DRAIN PIPE
CAUTION
Install the drain pipe in accordance with the instructions
in this installation instruction sheet and keep the area
warm enough to prevent condensation. Problems with
the piping may lead to water leaks.
NOTE: Install the drain pipe.
•
Install the drain pipe with downward gradient (1/50 to 1/100) and so
there are no rises or traps in the pipe.
•
Use general hard polyvinyl chloride pipe (VP25) [outside diameter 11/4” (32 mm)] and connect it with adhesive (polyvinyl chloride) so that
there is no leakage.
•
When the pipe is long, install supporters.
•
Do not perform air bleeding.
•
Always heat insulate the indoor side of the drain pipe.
•
When desiring a high drain pipe height, raise it up to 31” (800 mm) or
less from the ceiling within a range of 6” (150 mm) from the body. A
rise dimension over this range will cause leakage.
Fig. 20
Air bleeding
Rise
Trap
6” (150 mm) or less
Supporter
Max 31”
5 to 6.5 ft (1.5 to 2 m)
(800 mm)
OUTDOOR UNIT INSTALLATION
1. OUTDOOR UNIT PROCESSING
When the outdoor unit will be exposed to strong wind, fasten it with bolts
or wire at the four places indicated by the arrows (Fig. 21, 22).
Fig. 21
Air flow
Bottom
31-21/32” (804 mm)
Drain pipe mounting hole
Bottom plate
Drain pipe
Drain cap
13-7/64”
(333 mm)
3/4” (19 mm)
CAUTION
If this product is used in an area where
the temperature falls below freezing
for long periods of time, do not connect the drain pipe. Instead, allow the
water to drain into a drain pan.
CONNECTING THE PIPING
1. FLARE PROCESSING
(1)
Cut the connection pipe with pipe cutters so that the pipe is not
deformed.
(2)
Holding the pipe downward so that cuttings cannot enter the pipe
and remove the burrs.
(3)
Remove the flare nut from the indoor unit pipe and outdoor unit
and assemble as shown in (Table 3) and insert the flare nut onto
the pipe, and flare with a flaring tool.
(4)
Check if the flared part “L” (Fig. 25) is spread uniformly and that
there are no cracks.
Table 3
Pipe
Small pipe
Large pipe
Fig. 25
Small (width across flats 22 mm)
Large (width across flats 24 mm)
2. BENDING PIPES
The pipes are shaped by your hands. Be careful not to collapse them.
Fig. 26
Do not bend the pipes in an angle more than 90°.
When pipes are repeatedly bent or stretched, the material will harden,
making it difficult to bend or stretch them any more. Do not bend or
stretch the pipes more than three times.
When bending the pipe, do not bend
it as is. The pipe will be collapsed. In
this case, cut the heat insulating pipe
with a sharp cutter as shown in Fig.
27, and bend it after exposing the
pipe. After bending the pipe as you
want, be sure to put the heat insulating pipe back on the pipe, and secure
it with tape.
CAUTION
To prevent breaking of the pipe, avoid sharp bends.
1
Bend the pipe with a radius of curvature of 150 mm or
over.
If the pipe is bent repeatedly at the same place, it will
2
break.
Flare nut
L dimension
Small pipe (9.53 mm dia.)
1.8 to 2.0 mm
Large pipe (15.88 mm dia.)
2.2 to 2.4 mm
Fig. 27
Remote
controller
Template For ceiling hole cutting
Binder For remote controller cord
(large)
(small)
Blower cover insulation For discharged air
Hook wire For installing intake grille
Installation to indoor unit
1
1
2
binding
For remote controller and
1
remote controller cord
binding
2
2
OUTDOOR UNIT ACCESSORIES
Hexagon wrench
Cable clip
For opening the refrigerant
valve on the outdoor unit
1
For power cord binding
2
39” (1,000 mm)
or more
39” (1,000 mm)
or more
91” (2,300 mm)
or more
Obstruction
Floor
This mechanism enables the cassette body to move 35 mm downward and realizes installation to the space of 200 mm. No special
works and option is needed.
Fig. 3
You can select 2-way setting
(A) Standard setting (B) Slender setting
9-1/4” (235 mm)
or more
OUTDOOR UNIT
1
7-7/8” (200 mm)
or more
INSTALLATION PROCEDURE
Install the air conditioner as follows:
INDOOR UNIT INSTALLATION
WARNING
Install the air conditioner in a location which can with-
•
stand a load of at least five times the weight of the main
unit and which will not amplify sound or vibration.
If the installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk
•
that the unit will come loose. Please take care.
REMOVING THE INTAKE GRILLE
(1)
Push the intake grille pushbuttons (two places).
(2)
Open the intake grille.
Fig. 5
PUSH
OPEN
Panel base
CAUTION
Always remove the panel frame after removing the intake
grille.
1. POSITION THE CEILING HOLE AND HANGING BOLTS
Fig. 12
□37” (□940 mm)
(Grille measurement)
Allowable space between
*
the unit and the ceiling
5 mm or less
INSTALLING THE PANEL FRAME
Fig. 17
*90° Turn
Vinyl hose
Panel base
Panel frame
Fig. 22
2. OUTDOOR UNIT CONNECTION CORD AND PIPE
CONNECTION PREPARATIONS
(1)
Remove outdoor unit valve cover.
Fig. 23
* After removing the screws,
remove valve cover
Valve cover
take off direction
3. CONNECTION PIPES
(1) Indoor unit side
Fig. 28
Indoor unit
Large pipe
Small pipe
CAUTION
1
Be sure to apply the pipe against the port on the
indoor unit correctly. If the centering is improper, the
flare nut cannot be tightened smoothly. If the flare nut
is forced to turn, the threads will be damaged.
2
Do not remove the flare nut from the indoor unit pipe
until immediately before connecting the connection
pipe.
When the flare nut is tightened properly by your hand, hold the body
side coupling with a separate spanner, then tighten with a torque
wrench (Fig. 29).
Fig. 29
Tapping screw
(painted)
Drain pipe
Drain cap
SELECTING THE MOUNTING POSITION
Especially, the installation place is very important for the split type air
conditioner because it is very difficult to move from place to place after the first installation.
Decide the mounting position together with the customer as follows:
The discharge direction can be selected as shown below.
Fig. 1
For fixing the valve cover
1
For outdoor unit drain
piping work (May not be
1
supplied, depending on
the model.)
2
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
WARNING
Install the unit where it will not be tilted by more than 5°
1
When installing the outdoor unit where it may
2
exposed to strong wind, fasten it securely.
If possible, do not install the unit where it will exposed to direct
sunlight. (If necessary, install a blind that does not interfere with the
air flow.)
Install the outdoor unit in a place where it will be free from being
dirty or getting wet by rain as much as possible.
Install the unit when connection to the indoor unit is easy.
During heating operation, drain water flows from the outdoor unit.
Therefore, install the outdoor unit in a place where the drain water
flow will not be obstructed.
Do not place animals and plants in the path of the warm air.
Take the air conditioner weight into account and select a place
where noise and vibration are small.
Select a place so that the warm air and noise from the air conditioner
do not disturb neighbors.
Provide the space shown in Fig. 4 so that the air flow is not blocked.
Also for efficient operation, leave open three of the four directions
front, rear, and both sides.
Remove the grille hinge wire.
(3)
Fig. 6
* With slender setting, turn the panel frame 90° as shown in the
diagram above.
Valve cover
Grille setting method has been changed at the marked positions on the panel frame and panel base.
Fig. 18
(A) Standard setting (B) Slender setting
Valve
(2)
Connect the piping, connection cord and power cord.
Fig. 24
Pipe
CAUTION
29-17/32” (750 mm)
(Hanging bolt position)
29-17/32” (750 mm)
(Hanging bolt position)
□35-3/64” (□890 mm)
(Ceiling opening measurement)
Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 29, in order to tighten the
2. HANGING PREPARATIONS
Firmly fasten the hanging bolts as shown in Fig. 13 or by another
•
method.
A
Install the hanging bolts at a place where they would be capable of
•
holding a weight of at least 50 kgf per bolt.
Fig. 13
Hole-in anchor
Hole-in plug
InsertConcrete
Fig. 19
(Example)
Mark
Panel frame
No mark
Power cord
Connection
cord
flare nut correctly.
Table 4: Flare nut tightening torque
Pipe
Small pipe
Large pipe
Tightening torque
30.4 to 34.3 N
73.5 to 78.4 N
·m (310 to 350 kgf·cm)
·m (750 to 800 kgf·cm)
Hanging bolt
M10
CAUTION
Be sure to connect the large pipe after connecting the small
pipe completely.
* Appearance of slender setting
- Continued on back -
(2) Outdoor unit side
Tighten the flare nut of the connection pipe at the outdoor unit
valve connector. The tightening method is the same as that as
at the indoor side.
Fig. 30
3-way valve
(Small pipe)
Connection pipe
(Large pipe)
2-way valve
Flare nut
5
VACUUM PROCESS
1. VACUUM
(1)
Remove the cap, and connect the gauge manifold and the vacuum pump to the charging valve by the service hoses.
(2)
Vacuum the indoor unit and the connecting pipes until the pressure in them lowers to below 1.5 mmHg.
(3)
Disconnect the service hoses and fit the cap to the charging valve
(Tightening torque : 70 to 90 kgf
(4)
Remove the blank caps, and fully open the spindles of the 2-way
and 3-way valves with a hexagon wrench (Torque : 2-way valve:
70 to 90 kgf
(5)
Tighten the blank caps of the 2-way valve and 3-way valve to the
·cm, 3-way valve: 100 to 120 kgf·cm).
specified torque (200 to 250 kgf
Fig. 31
Outdoor unit
Service hose with
valve core
Fig. 32
2. ADDITIONAL CHARGE
Refrigerant suitable for a piping length of 7.5 m is charged in the outdoor unit at the factory.
When the piping is longer than 7.5 m, additional charging is necessary.
For the additional amount, see the table below.
Pipe length
Heat & Cool
Additional
refrigerant
(Reverse cycle)
Cooling
model
Between 7.5 m and 30 m, when using a connection pipe other than
that in the table, charge additional refrigerant with 1.8 oz (50 g)/3.3 ft
(1 m) (Reverse cycle model), 0.7 oz (20 g)/3.3 ft (1 m) (Cooling model)
as the criteria.
1
When charging the refrigerant, always use a measuring cylinder.
2
Add refrigerant from the charging valve after the
completion of the work.
25 ft
(7.5 m)
None
None
·cm).
·cm).
Charging valve
Cap
LO
Service hose
Table 5
33 ft
(10 m)
4.4 oz
(125 g)
1.8 oz
(50 g)
CAUTION
(15 m)
13.2oz
(375 g)
5.3 oz
(150 g)
Refrigerant pipe
3-way valve
Blank cap
Gauge manifold
HI
Vacuum pump
49 ft
66 ft
(20 m)
22.0 oz
(625 g)
8.8 oz
(250 g)
6
INSTALLING THE COUPLER
HEAT INSULATION
After checking for gas leaks, insulate by wrapping insulation around
the two parts (large and small) of the indoor unit coupling, using the
coupler heat insulation.
After installing the coupler heat insulation, wrap both ends with vinyl
tape so that there is no gap.
Fig. 33
CAUTION
Must fit tightly against body without any gap.
7
ELECTRICAL WIRING
HOW TO CONNECT WIRING TO THE TERMINALS
A. For solid core wiring (or F-cable)
(1)
Cut the wire end with a wire cutter or wire-cutting pliers,
then strip the insulation to about 15/16” (25 mm) to expose
the solid wire.
(2)
Using a screwdriver, remove the terminal screw(s) on the
terminal board.
(3)
Using pliers, bend the solid wire to form a loop suitable for
the terminal screw.
(4)
Shape the loop wire properly, place it on the terminal
board and tighten securely with the terminal screw using a
screwdriver.
82 ft
(25 m)
30.9 oz
(875 g)
12.3 oz
(350 g)
99 ft
(30 m)
15.9 oz
(450 g)
B. For strand wiring
Cut the wire end with a wire cutter or wire-cutting pliers,
(1)
then strip the insulation to about 3/8” (10 mm) to expose
the strand wiring.
Using a screwdriver, remove the terminal screw(s) on the
(2)
terminal board.
Using a round terminal fastener or pliers, securely clamp a
(3)
round terminal to each stripped wire end.
Position the round terminal wire, and replace and tighten
(4)
the terminal screw using a screwdriver.
Fig. 34
HOW TO FIXED CONNECTION CORD AND
POWER SUPPLY CORD AT THE CORD CLAMP
After passing the connection cord and power supply cord
through the insulation tube, fasten it with the cord clamp.
Fig. 35
Insulation tube
Insulation tube
Cord clamp
Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.
1. INDOOR UNIT SIDE
WARNING
1
Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2
Match the terminal board numbers and connection
cord colors with those of the outdoor unit.
Erroneous wiring may cause burning of the electric parts.
3
Connect the connection cord firmly to the terminal
board. Imperfect installation may cause a fire.
4
Always fasten the outside covering of the connection
cord with the cord clamp. (If the insulator is chafed,
electric leakage may occur.)
5
Always connect the ground wire.
(1)
Remove the control box cover and cover (wire) B and install
the connection cord.
Fig. 36
Cover (wire) B
Control box cover
(2)
After wiring is complete, clamp the remote controller cord and
connection cord with the cord clamp.
(3)
Install the control box cover and cover (wire) B.
Fig. 37
Cord clamp
Fig. 38
Connection
cord
OUTDOOR
UNIT
Connection cord
(To the outdoor unit)
Terminal board
(Indoor unit)
Remote controller cord
Black
White
Terminal board
Red
Remote
controller
Ceiling height setting
Set the DIP switch for the ceiling height according to the table below.
Table 6
Ceiling height
2.5 ~ 3.0
3.0 ~ 3.5
More than 3.5
Less than 2.5
Fig. 39
Dip switch
(SW4)
(m)
Normal
High ceiling 1
High ceiling 2
Low ceiling
Indoor unit
PC board
DIP-SW4
123
SW 1
123
O
OFF
ON
OFF
ON
F
F
—
—
—
—
Indoor unit PC board
SW 4
123
F
O
OFF
OFF
ON
ON
F
CAUTION
If the setting for a low ceiling is selected, the capaci-
1
ty of the air conditioner decreases slightly.
Do not set any switches other than those specified
2
in this sheet or the remote controller installation instruction sheet. The air conditioner may not operate
correctly if any switches other than those specified
are changed.
2. OUTDOOR UNIT SIDE
WARNING
1
Before starting work, check that power is not being
supplied to the indoor unit and outdoor unit.
2
Match the terminal board numbers and connection
cord colors with those of the indoor unit side.
Erroneous wiring may cause burning of the electric parts.
3
Connect the connection cords and the power supply
cord firmly to the terminal board. Imperfect installation may cause a fire.
4
Always fasten the outside covering of the connection
cord and the power supply cord with cord clamps. (If
the insulator is chafed, electric leakage may occur.)
5
Always connect the ground wire.
Remove outdoor unit valve cover and connect the power cord
(1)
and the outdoor unit connection cord wired at the indoor unit.
Fasten the power cord and connection cord with cable clip and
(2)
binders as shown in (Fig. 41)
Fig. 40
Control box
Terminal board
(N)
Cable clip
Reinstall the
removed screws.
3
2
1
Make longer
than the other
wires.
Insulation tube
Cable clip
Cord clamp
Insulation tube
Power cord
Fig. 41
(3) Install the valve cover.
Fig. 42
Valve
cover
1
2
LN3
Power cord
Ground
Connection cord
(indoor unit and outdoor
unit connection cord)
Attach the
four fasteners.
8
GRILLE INSTALLATION
BLOWER COVER INSULATION
Install the blower cover insulation only when the outlet direction is not
specified.
Two blower cover insulations are packed with the indoor unit.
Install the blower cover insulation at the diffuser position shown in
Fig. 43. At this time, use the piping position as the criteria.
Fig. 43
2 direction example
(Piping direction)
A
A
Blower cover
insulation
A-A Section view
Accessory
part
Panel
base
Drain
pan
INSTALLING THE INTAKE GRILLE
Mount the grille hinge wire to the hook shaft as shown in
(1)
Fig. 44.
Fig. 44
A
• Latch the grille hinge wire to the hook shaft, and fasten.
Fig. 45 Part A detail view Fig. 46 Part A section view
Hook shaft
Grille hinge
wire
(2)
Install the hook wire.
Pass the hook wire through the panel base from the rear
•
side as shown in Fig. 47, and fasten to the reinforced
metal fitting of the intake grille using a screw.
Fig. 47
Hook wire
RFM (grille)
Fig. 48 Section view
Hook wire
Screw
(3) Loosen the screw, put the loop of the hook wire over it,
and tighten the screw again.
CAUTION
Install the intake grille hook wire to the grille assembly. If it falls, it may cause injuries.
(4)
Bring up the intake grille by pushing it up at an angle as
shown in Figs. 49, 50, and fasten.
Fig. 49
Fig. 50
9
10
POWER
WARNING
The rated voltage of this product is 220-240 V 50 Hz.
1
Before turning on verify that the voltage is within the
2
198 to 264 V range.
Always use a special branch circuit and install a special
3
receptacle to supply power to the air conditioner.
Use a special branch circuit breaker and receptacle
4
matched to the capacity of the air conditioner.
(Install in accordance with standard.)
Perform wiring work in accordance with standards so
5
that the air conditioner can be operated safely and
positively.
Install a leakage special branch circuit breaker in ac-
6
cordance with the related laws and regulations and
electric company standards.
CAUTION
When the voltage is low and the air conditioner is difficult
to start, contact the power company the voltage raised.
REMOTE CONTROLLER
INSTALLATION
When mounting the remote controller, refer to the enclosed REMOTE CONTROLLER INSTALLATION INSTRUCTION SHEET. Then, make the necessary settings on both
the remote controller and the main unit.
Insert the end of a flat blade screwdriver at the arrow parts of the
•
groove at the side of the remote controller case and remove the
remote controller case top by turning the screwdriver.
Disconnect the remote controller cord from the remote controller
•
terminal board.
Fig. 51
CLOCK
NON STOP
TIMER
MODE
CLOCK ADJUST
When remote controller exposed
(1)
1)
Make a notch in the thin part ( part of Fig. 51) at the remote controller case top and bottom with nippers, file, etc.
2)
Connect the remote controller cord to the remote controller
terminal board specified in (Fig. 52).
3)
Clamp the remote controller cord sheath with the binder
(small) as shown in (Fig. 52).
4)
Cut off the excess binder.
5)
Clamp the remote controller cord to a wall, etc. with the remote controller cord clamp furnished (Fig. 53).
Fig. 52
Remote controller cord
Binder (small)
Fig. 53
Tapping screw (flush heads)
When remote controller cord embedded
(2)
1)
Embed the remote controller cord and box.
2)
Pass the remote controller cord through the hole at the remote
controller case bottom and install the cord to the box (Fig. 54).
3)
Connect the remote controller cord to the remote controller
terminal board specified in (Fig. 52).
Fig. 54 [Example]
Remote controller
case top
Remote controller case bottom
•
After wiring work is complete, return the remote controller case
top to its original state.
Do not bundle the remote controller cord, or wire
1
the remote controller cord in parallel, with the indoor unit connection wire (to the outdoor unit) and
the power supply cord. It may cause erroneous operation.
When installing the remote controller and cord near
2
a source of electromagnetic waves, separate the remote controller from the source of the electromagnetic waves and use shielded cord.
Do not touch the remote controller PC board and PC
3
board parts directly with your hands.
TEMP
AUTO
°C
HIGH
COOL
ZONE
SET
Red
CONTROL
ENERGY SAVE
DAY OFF
White
DEFROST
MASTER
CONTROL
START/STOP
Black
21
SET TIME TEMP./DAY FAN
Remote controller cord
CAUTION
Remote controller
terminal board
Remote controller
cord clamp
Remote
controller
cord
11
TEST RUNNING
1. REMOTE CONTROLLER
Supply power to the crankcase heater 12 hours before the start
•
of operation in the winter.
For test running, when the remote controller FAN CONTROL but-
•
ton and MASTER CONTROL button are pressed simultaneously
for more than three seconds when the air conditioner is not running, the air conditioner starts and TEST is displayed on the remote controller display.
However, the SET TEMP./DAY setting button does not function,
but all other buttons, displays, and protection functions operate
(Fig. 55).
Fig. 55
CLOCK
NON STOP
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
When EE:EE blinks at the current time display, there is an error
•
inside the air conditioner. If the SET TIME button ( ) and SET
TEMP./DAY button ( ) are pressed simultaneously for more than
three seconds, the self diagnosis check will start and the error
contents will be displayed at the current time display (Fig. 56).
When the operation lamp lights, press the START/STOP button
and after operation lamp goes off, perform the same operation
(Fig. 56). Process the error contents by referring to (Table 7).
Fig. 56
CLOCK
NON STOP
21
TIMER
MODE
CLOCK ADJUST
TEMP
°C
HIGH
SET TIME TEMP./DAY FAN
ZONE
SET
CONTROL
ENERGY SAVE
DAY OFF
AUTO
DEFROST
CONTROL
START/STOP
Stop operation.
Error code
Communication error
(indoor unit remote controller)
Communication error
(indoor unit outdoor unit)
Room temperature sensor open
Room temperature sensor shortcircuited
Indoor heat exchanger temperature sensor open
Indoor heat exchanger temperature sensor
shortcircuited
Outdoor heat exchanger temperature sensor
open
Outdoor heat exchanger temperature sensor
shortcircuited
Power source connection error
Float switch operated
Outdoor temperature sensor open
Outdoor temperature sensor shortcircuited
Discharge pipe temperature sensor open
Discharge pipe temperature sensor shortcircuited
Outdoor high pressure abnormal
Discharge pipe temperature abnormal
Model abnormal
Indoor fan abnormal
Outdoor signal abnormal
Outdoor EEPROM abnormal
2. OUTDOOR UNIT
When the outdoor temperature drops, the outdoor unit's fans may
switch to low speed.
ERROR : HEAT &COOL MODEL (REVERSE CYCLE) ONLY
The LED lamps operate as follows (Table 8) according to the error
contents.
Error display
0.1 sec.
ON
OFF
0.5 sec.
ON
OFF
ON
OFF
ON
OFF
4 quick flash repeated
5 quick flash repeated
6 quick flash repeated
7 quick flash repeated
8 quick flash repeated
2 sec.
0.5 sec.
2 sec.
0.5 sec.
2 sec.
When the fault is cleared, the LED lamp goes off.
However, for discharge pipe temperature abnormal and high pressure abnormal, the LED lamp lights continuously for 24 hours, as
long as the power is not turned off.
ON
OFF
Quick flash continuedQuick flash continued
ON
OFF
Lighting continued1 quick flash repeated
ON
OFF
Lighting continued2 quick flash repeated
ON
OFF
Lighting continued3 quick flash repeated
Lighting continued
Lighting continued
Lighting continued
Lighting continued
Lighting continued
COOL
MASTER
TEMP
°C
CONTROL
ZONE
ENERGY SAVE
SET
DAY OFF
Table 7
Error contents
Table 8
0.1 sec.
AUTO
HIGH
COOL
DEFROST TEST
MASTER
CONTROL
START/STOP
AUTO
21
TIMER
SET TIME TEMP./DAY FAN
MODE
CLOCK ADJUST
ZONE
SET
CONTROL
ENERGY SAVE
DAY OFF
CONTROL
START/STOP
Error contentsLED2LED1
Model abnormal or
EEPROM abnormal
Power source
connection error
Discharge temperature
sensor error
Outdoor heat exchanger
temperature sensor error
Outdoor temperature sensor error
Communication signal error
Indoor unit error
Discharge temperature abnormal
High pressure abnormal
MASTER
12
3. CHECKING DRAINAGE
To check the drain, remove the water cover and fill with 2 to 3rof
water as shown in Fig. 57.
The drain pump operates when operating in the cooling mode.
Fig. 57
Drain pipe
Water cover
Watering pot
OPENING THE DUCT
CONNECTION HOLE
Fig. 58
Distribution duct Fresh air
Distribution duct
CAUTION
1
When performing hole opening work, be careful not to
damage the drain pan.
2
When connecting the distribution duct, to make the air
flow easily, block the outlet port with the blower cover
insulation as shown by the hatched lines in Fig. 58. For
the blocking direction, refer to Fig. 43.
1. DIMENSION
Screw position and connection hole which are fresh air duct and distribution duct.
Fig. 59
97
45
P. D 120
°
ø100
160
12-ø3.3 self tapping screw holes (for 4 mm)
45°
P. D 88
ø70
334.2
2. DISTRIBUTION DUCT AND FRESH AIR DUCT HOLE
PROCESSING
Use the distribution duct hole and fresh air duct hole by removing
the insulation material as shown below.
Fig. 60
Cut
Cabinet
Cut
Cut off the part (Cabinet) indicated by the arrow in the Fig. 60 with
•
nippers, needle nose pliers, etc.
Fig. 61
Knife
Insulation
(Inner box)
Open the holes and cut the insulation with a knife.
•
Be careful not to damage the internal parts.
*
Be careful not to cut yourself on the cutout in the metal plate.
*
Please remove the insulation (inner box) left over after cutting.
*
Connect the distribution duct.
•
When mounting the duct, block the gap so that there is no cold
*
Cabinet
air leakage.
Insulate the duct and cut connection.
*
CAUTION
The air conditioner cannot take in fresh air by itself. When
connecting a fresh air duct, always use a duct fan.
Unit: mm
113
PART NO. 9366379027