Not intended for use as Primary Power in place of utility
or in life-support applications.
DANGER
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!!
INTRODUCTION
Thank you for purchasing this model by Generac
Power Systems Inc.. This model is a compact, high
performance, air-cooled, engine-driven generator
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor installation. This generator will operate using either vapor
withdrawn liquid propane (LP) or natural gas (NG).
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact
the nearest Authorized Dealer for starting, operating
and servicing procedures.
Throughout this publication, and on tags and decals
affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their defini-
tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious personal injury, including death, in addition to property
damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compliance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows:
This symbol points out important safety informa-
tion that, if not followed, could endanger personal
safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual
and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly recommends instructing other users to properly
start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information,
including warranty, electrical diagrams, exploded
views and lists of repair parts, for model:
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by an Authorized
Dealer. Normal maintenance service and replacement
of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials
or workmanship within the terms of the warranty.
Individual operating habits and usage contribute to
the need for maintenance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See the Authorized Dealer
for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
simply contact an Authorized Dealer for assistance.
Service technicians are factory-trained and are capable of handling all service needs.
When contacting an Authorized Dealer about parts
and service, always supply the complete model number and serial number of the unit as given on its data
decal, which is located on the generator. See "The
Generator" section for decal location.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To locate the nearest AUTHORIZED
DEALER, please call this number:
1-800-333-1322
or locate us on the web at
www.generac.com
Table of Contents
Air-cooled 15 kW Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted near the unit’s installation site. Safety should be stressed to
all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become
familiar with this Owner’s Manual and with the
unit. The generator can operate safely, efficiently and
reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.
WARNING:
of California to cause cancer, birth
WARNING:
DANGER
Despite the safe design of this generator, operat-
ing this equipment imprudently, neglecting its
maintenance or being careless can cause possible
injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
Please read all hazards carefully!
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends
that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Dealer.
• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust
system must be installed properly, in strict compliance with applicable codes and standards.
Following installation, do nothing that might render the system unsafe or in noncompliance with
such codes and standards.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to correct generator operation.
Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The
generator MUST be installed outdoors.
• When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
• Inspect the generator regularly, and contact the
nearest Authorized Dealer for parts needing repair
or replacement.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
• Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
2
ELECTRICAL HAZARDS
• All generators covered by this manual produce
dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely
high and dangerous voltages to the transfer switch
as does the standby generator when it is in operation. Avoid contact with bare wires, terminals,
connections, etc., while the unit is running. Ensure
all appropriate covers, guards and barriers are in
place before operating the generator. If work must
be done around an operating unit, stand on an
insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. Local electrical codes also may require
proper grounding of the generator electrical system.
• After installing this home standby electrical system, the generator may crank and start at any
time without warning. When this occurs, load circuits are transferred to the STANDBY (generator)
power source. To prevent possible injury if such a
start and transfer occur, always set the generator’s
AUTO/OFF/MANUAL switch to its OFF position
before working on equipment and remove the 5A
and 15A fuses from the generator control panel.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
such as a rope or board, to free the victim from the
live conductor. If the victim is unconscious, apply
first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed
and maintained properly. Installation always must
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
IMPORTANT SAFETY INSTRUCTIONS
Air-cooled 15 kW Generators
• Keep a fire extinguisher near the generator at all
times. Extinguishers rated “ABC” by the National
Fire Protection Association are appropriate for
use on the standby electric system. Keep the extinguisher properly charged and be familiar with its
use. If there are any questions pertaining to fire
extinguishers, consult the local fire department.
EXPLOSION HAZARDS
• Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install
the fuel supply system according to applicable
fuel-gas codes. Before placing the home standby
electric system into service, fuel system lines must
be properly purged and leak tested according to
applicable code. After installation, inspect the fuel
system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed
below may be used as installation guide for this
equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from
the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES,
available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL
SYSTEMS, available from the American Society
of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
Section 1 — General Information
Air-cooled 15 kW Generators
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and
regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for
damage.
• This standby generator set has been factory supplied with a weather protective enclosure that is
intended for outdoor installation only.
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer switch. The transfer switch must effectively
isolate the electrical system from the utility
distribution system when the generator is operating (NEC 700, 701 and 702). Failure to isolate
an electrical system by such means will result in
damage to the generator and also may result in
injury or death to utility power workers due to
backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix his or her signature under the
consignor's memo of loss or damage.
If there is loss or damage after delivery, separate the
damaged materials and contact the carrier for claim
procedures.
“Concealed damage” is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
to run for long periods of time with no operator present to monitor engine conditions. For that reason, the
engine is equipped with the following systems that
protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 3. Overcrank
2. High Temperature Sensor 4. Overspeed
There are LED readouts on the control panel to notify
personnel that one of these faults has occurred. There
is also a “System Set” LED that is described below.
1.3 SYSTEM SET LED
The “System Set” LED is lit when all of the following
conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the Control PCB. If the utility
sense voltage is not connected to the unit or if it
is below 168 volts AC, then the system set light
will flash rapidly. This indicates that if the AUTO/
OFF/MANUAL switch is placed in the Auto position , the generator will start.
3. The “Not In Auto” dip switch is set to the OFF
position on the control board.
4. No alarms are present, for example, low oil pressure, high temperature, etc.
@ 23 ft (7m) at full load ............................... 71.5 db (A)
Normal Operating Range ............................ -20°F (-28.8°C)
* Maximum wattage and current are subject to and limited by such
factors as fuel Btu content, ambient temperature, altitude, engine
power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about
1 percent for each 6° C (42° F) above 16° C (60° F).
+ Total current in two separate curcuits. Current in each curcuit must
not exceed the value stated for 240V.
1.5.2 ENGINE
Type of Engine ...................................................... GT-990
Number of Cylinders .......................................................2
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997
California Air Resources Board for tamper-proof
dual fuel systems. The unit will run on natural gas or
LP gas, but it has been factory set to run on natural
gas. Should the primary fuel need to be changed to
LP gas, the fuel system needs to be reconfigured. See
"Reconfiguring the Fuel System" for instructions on
reconfiguration of the fuel system.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas; or at
least 2,520 Btus per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is five inches
to seven inches water column (0.18 to 0.25 psi);
and for liquid propane, 11 inches to 14 inches of
water column (0.4 to 0.5 psi).
NOTE:
Any piping used to connect the generator to the
fuel supply should be of adequate size to ensure
the fuel pressure NEVER drops below 4 inches
water colum for natural gas or 10 inches water
column for liquid propane for all load ranges.
1.7 FUEL CONSUMPTION
Model # Nat. Gas (*) LP Vapor (**)
1/2 Load Full Load 1/2 Load Full Load
05176 156 220 1.58/58 2.40/88
*Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.
1.8 RECONFIGURING THE
FUEL SYSTEM
To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 11 to 14 inches of water column (0.4 to
0.5 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the gas supply. (if connected)
2. Open the roof and remove the door.
3. Remove the battery. (if installed)
6
G
T
T
U
T
G
OSE
S
L
T
OR
OUSING PORT
JUSTER
SC
S
OU
S
C
C
O
C
O
C
C
O
C
C
O
C
C
O
C
C
O
C
OOR
E
3
S
N
O
COMMON
M
5
6
S
N
CY
OPEN
OWFUEL
UN
Section 2 — Installation
Air-cooled 15 kW Generators
4. Remove the engine air in baffle located on the lefthand side of the battery compartment. Two M6
screws are located on top of the baffle and two
M6 screws are located on the inside of the baffle
towards the back.
5. Remove the small hose clamp and hose from the
fuel regulator. It may be necessary to pry the hose
off of the brass fitting using a screwdriver to gently lift up the hose edge.
6. Remove the small brass hose fitting from the
regulator casting.
7. Place the small fuel jet, thread side first, into the
threaded hole originally occupied by the brass
hose fitting (Figure 1.3).
Figure 1.3 - Demand Regulator
TLET PORT
FUEL H
BRASS HOSE
FITTIN
IDLE CIRCUI
POR
1/8 NP
BRASS HOSE
FITTIN
AD
REW
REGULAT
H
MAL
FUEL JE
14. It may be necessary to make minor adjustments
to the preset adjustment screw settings to achieve
maximum power, particularly at higher altitudes.
If experiencing problems with the unit producing maximum power, follow the procedure in
"Adjusting the Fuel Regulator".
2.1 INSTALLATION
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available. Consider these factors:
• Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow,
etc. If prevailing winds will cause blowing or drifting snow, consider using a windbreak to protect
the unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to
allow three feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings to
the prevailing winds.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
8. Using a short No. 2 Phillips screw driver, thread
the small fuel jet into the regulator casting. Do
not over tighten.
9. Apply thread sealant to the threads of the hose
fitting and replace it into the regulator body.
10. Re-attach the small hose and hose clamp and
tighten as necessary.
11. Replace the engine air in baffle using the four M6
screws.
12. Identify both brass adjustment screws on the
regulator.
NOTE:
One adjustment screw can be accessed from the
front of the unit and the second can be accessed
from the back of the unit enclosure by removing
the plastic hole plug. The screw can be turned
with a long flat blade screwdriver.
13. To adjust the system to run on LP fuel, turn
BOTH adjuster screws 1/2 TURN CLOCKWISE.
The system should now be set for maximum
power and best perfomance. DO NOT, UNDER
ANY CIRCUMSTANCES, REMOVE THE SET
PINS FROM THE REGULATOR HOUSING.
THIS WILL VOID THE WARRANTY.
2.1.1 REMOTE MONITORING CONNECTIONS
Mounted in the transfer switch is relay contact board
(Figure 2.1) that can be used to remotely monitor
various functions of the generator system.
The contacts are rated as shown below. Failure to follow these ratings will cause unit failure.
• Arrangement: SPCT (Form C)
• Ratings: Resistive Load, 4Amp max switching
current at 30VDC; 2Amp max switching
current at 125VAC
• Wire Range: 26-14Awg
• Terminal tightening torque: 5 in/lb.
Figure 2.1 — Remote Monitoring Connections
N
N
N
N
N
N
N
N
N
N
N
N
ENGIN
R
WITCH I
EMERGEN
RELAY
WITCH I
AUT
ALAR
RELAY
L
RELAY
D
7
Section 2 — Installation
Air-cooled 15 kW Generators
Remote monitoring functions are only available with
the AUTO/OFF/MANUAL switch in the Auto or Manual
position. Since the contacts are SPDT, it is possible
to monitor either state of each alarm function.
Relay 1: Engine running, normally closed.
Engine not running, normally open
Relay 2: Transfer Switch in Emergency, normally
closed
Transfer Switch in Utility, normally open
Relay 3: Control panel switch in Auto, normally
open
Control panel switch in Manual or Off, nor-
mally closed
Relay 4: The common alarm is activated by any of
the following shutdown faults
Low Oil Pressure
High Engine Temperature
Overspeed
Overcrank
Common alarm active, normally open
No Common alarm, normally closed
Relay 5: Spare, not used on this model
Relay 6: Enclosure door open, normally closed
Enclosure door closed, normally open
2.1.2 ROOF OPEN ALARM
This generator is equipped with an alarm to detect
when the roof of the enclosure is open. A limit switch
that is installed in the generator enclosure controls
this alarm. During shipping, the generator's enclosure
panels may have shifted and this limit switch may
require adjustment. Simply loosen the two screws
and adjust the placement of the limit switch. The arm
of the limit switch should be in the depressed position when the enclosure roof is closed and the door
latch is secure (see Figure 2.2).
Figure 2.2 — Limit Switch
Up
2.1.3 TRANSFER SWITCH CONNECTION
These switches (Figure 2.3) are used with a singlephase system, when the single-phase NEUTRAL line
is to be connected to a Neutral Lug and is not to be
switched.
Figure 2.3 — Typical 2-Pole Transfer Mechanism
(200 Amp Shown)
UTILITY LUGS
UTILITY
CLOSING
COIL
GENERATOR
LUGS (E1 & E2)
GENERATOR
CLOSING
COIL
LOAD LUGS (T1 & T2)
Solderless, screw-type terminal lugs are standard.
Switch Wire Conductor Tightening
Rating Range Torque
200A #6-250 MCM 275 in-lbs.
Conductor sizes must be adequate to handle the
maximum current to which they will be subjected to,
based on the 75°C column of tables, charts, etc. used
to size conductors. The installation must comply fully
with all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove
any surface oxides from the cable ends with a wire
brush. All power cables should enter the switch next
to transfer mechanism terminals. If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs to the torque values as
noted on the decal located on the inside of the door.
After tightening terminal lugs, carefully wipe away
any excess corrosion inhibitor.
All power cables should enter the switch next to the
transfer mechanism terminals.
8
Down
Slots
Use a torque wrench to tighten the conductors,
being sure not to over tighten, or damage to
the switch base could occur. If not tightened
enough, a loose connection would result, causing excess heat which could damage the switch
base.
Section 2 — Installation
Air-cooled 15 kW Generators
Connect power source load conductors to clearly
marked transfer mechanism terminal lugs as follows
1. Connect UTILITY (NORMAL) power source cables
to switch terminals N1, N2.
2. Connect customer LOAD leads to switch termi-
nals T1, T2.
Conductors must be properly supported, of approved
insulative qualities, protected by approved conduit,
and of the correct wire gauge size in accordance with
applicable codes.
Be sure to maintain proper electrical clearance
between live metal parts and grounded metal. Allow
at least 1/2 inch for 100-400 amp circuits.
2.2 BATTERY INSTALLATION
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off, or
sparking may occur at the battery posts as the
cables are attached and cause an explosion.
Fill the battery with the proper electrolyte fluid if
necessary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
3. Remove the 5 amp fuse from the generator con-
trol panel.
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off, sparking can occur at the battery posts and cause an
explosion.
Battery cables were factory connected at the generator (Figure 2.4). Connect cables to battery posts as
follows:
4. Connect the red battery cable (from starter con-
tactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a negative, NEG or (—).
6. Replace the 5 amp fuse in the generator control
panel.
NOTE:
Damage will result if battery connections are made
in reverse.
9
Section 3 — Post Installation Start-up and Adjustments
Air-cooled 15 kW Generators
Figure 2.4 – Battery Cable Connections
NOTE:
The generator is equipped with a battery trickle
charger that is active when the unit is set up for
automatic operation. With the battery installed
and utility power source voltage available to the
transfer switch, the battery receives a trickle
charge while the engine is not running, to prevent
self-discharge. The trickle charger is designed to
help extend the life of the battery by maintaining the battery when the unit is not running. The
trickle charge feature cannot be used to recharge
a discharged battery.
3.1 BEFORE INITIAL START-UP
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as the
utility main line circuit breaker).
4. Check the engine crankcase oil level and, if neces-
sary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
5. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All
fuel shutoff valves in the fuel supply lines must
be open.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
3.2 CHECK TRANSFER SWITCH
OPERATION
Refer to the "Manual Operation" section of the owner’s
manual for manual operation procedures.
2.3 THE BATTERY
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
When replacing the battery, use the following type of
battery: Group 26/26R 12-volt battery with a rating
of 525 cold-cranking amps minimum at -17.8º C (0º
F) minimum. When using a maintenance-free battery,
it is not necessary to check the specific gravity or
electrolyte level. Have these procedures performed
at the intervals specified in the “Service Schedule.” A
negative ground system is used. Battery connections
are shown on the wiring diagrams. Make sure the
battery is correctly connected and terminals are tight.
Observe battery polarity when connecting the battery
to the generator set.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
3.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Turn on the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely
hazardous and possibly fatal electrical shock.
Proceed with caution.
2. Use an accurate AC voltmeter to check utility
power source voltage across terminals N1 and
N2. Nominal line-to-line voltage should be 240
volts AC.
10
Section 3 — Post Installation Start-up and Adjustments
Air-cooled 15 kW Generators
3. Check utility power source voltage across terminals N1 and the transfer switch neutral lug; then
across terminal N2 and neutral. Nominal line-toneutral voltage should be 120 volts AC.
4. When certain that utility supply voltage is compatible with transfer switch and load circuit ratings,
turn OFF the utility power supply to the transfer
switch.
5. Set the generator's main circuit breaker to its
OFF (or OPEN) position. Initial tests will be conducted at no-load condition.
6. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL. The engine should
crank and start.
7. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set
the generator’s main circuit breaker to its ON (or
closed) position.
DANGER
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
8. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal
lugs E1 and E2. Voltage should be 242-252 volts;
frequency should read about 61-63 Hertz.
9. Connect the AC voltmeter test leads across terminal lug E1 and neutral; then across E2 and
neutral. In both cases, voltage reading should be
121-126 volts AC.
10. Set the generator’s main circuit breaker to its
OFF (or open) position. Let the engine run at noload for a few minutes to stabilize internal engine
generator temperatures.
11. Set the generator's AUTO/OFF/MANUAL switch to
OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that
generator AC voltage and frequency are correct
and within the stated limits. Generally, if both AC
frequency and voltage are high or low, the engine
governor requires adjustment. If frequency is correct, but voltage is high or low, the generator’s
voltage regulator requires adjustment.
3.4 GENERATOR TESTS UNDER LOAD
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
To test the generator set with electrical loads applied,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or OPEN) position.
2. Set the generator's AUTO/OFF/MANUAL
switch to OFF.
3. Turn OFF the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
4. Manually set the transfer switch to the STANDBY
position, i.e., load terminals connected to the
generator's E1/E2 terminals. The transfer switch
operating lever should be down.
5. Set the generator's AUTO/OFF/MANUAL switch
to MANUAL. The engine should crank and start
immediately.
6. Let the engine stabilize and warm up for a few
minutes.
7. Set the generator’s main circuit breaker to its ON
(or closed) position. Loads are now powered by
the standby generator.
8. Turn ON electrical loads. Apply an electrical load
equal to the full rated wattage/amperage capacity
of the installed generator.
9. Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage
should be greater than 230 volts; frequency
should be greater than 58 Hertz.
10. Let the generator run at full rated load for 20-30
minutes. Listen for unusual noises, vibration or
other indications of abnormal operation. Check
for oil leaks, evidence of overheating, etc.
11. When testing under load is complete, turn OFF
electrical loads.
12. Set the generator's main circuit breakers to their
OFF (or open) positions.
13. Let the engine run at no-load for a few minutes.
14. Set the AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
11
E
Section 3 — Post Installation Start-up and Adjustments
Air-cooled 15 kW Generators
3.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation,
proceed as follows:
1. Set the generator’s main circuit breaker to it’s
OFF (or open) position.
2. Check that the AUTO/OFF/MANUAL switch is set
to OFF.
3. Manually set the transfer switch to the UTILITY
position, i.e., load terminals connected to the utility power source side.
4. Turn ON the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
5. Set the AUTO/OFF/MANUAL switch to AUTO.
Then set the generator’s main circuit breaker to
its ON (or closed) position. The system is now
ready for automatic operation.
6. Turn OFF the utility power supply to the transfer
switch.
With the AUTO/OFF/MANUAL switch at AUTO, the
engine should crank and start when the utility source
power is turned OFF. After starting, the transfer
switch should connect load circuits to the standby
side. Let the system go through its entire automatic
sequence of operation.
With the generator running and loads powered by
generator AC output, turn ON the utility power supply
to the transfer switch. The following should occur:
• After about 15 seconds, the switch should transfer
loads back to the utility power source.
• About one minute after retransfer, the engine
should shut down.
3.6 ADJUSTING THE REGULATOR
(NATURAL GAS ONLY)
Although the generator has been factory set to provide maximum power, it may be necessary in some
areas to adjust this setting. Because natural gas has
different BTU or power content across the country
the engine may not perform as designed.
If experiencing engine problems at high or full load
conditions follow these steps. It will require a frequency meter to perform this procedure.
1. Turn off utility power to the main distribution
panel in the house. This can be done by switching
the service main breaker to the off or open position.
2. Allow the generator to start before loading the
generator. Confirm the no-load frequency with
the roof open and door off is set at 63-63.5 Hz.
Transfer load to emergency circuits.
3. Turn on electrical loads. Be cautious not to overload the generator. Use the following chart as a
guide:
Model 120 Volts 240 Volts
005176 108.3 amps 54.1 amps
4. When full load has been achieved. Connect a frequency meter to the output lugs of the generator’s
main line circuit breaker.
5. The fuel regulator is fitted with two adjustment
screws. While watching the frequency meter,
slowly turn the adjustment screw clockwise or
counterclockwise one at a time until highest frequency is read on the meter. Only limited adjustment is available between the set pins. Under no
circumstances should any of the pins be removed
(Figures 3.1 and 3.2).
Figure 3.1 — Dual Fuel Regulators
V-twin Engine
Adjustment
Screw
(Both Sides)
Set Pin
(Both Sides)
6. When the highest frequency is reached maximum
power has been set. Then turn both adjustment
screws 1/4 turn counterclockwise. Regulator is
now set.
AdjustmentScrew
(One SideOnly)
410cc
Figure 3.2 — Placement of Regulator
Adjustment Screw
12
Section 3 — Post Installation Start-up and Adjustments
Air-cooled 15 kW Generators
7. Turn utility power to the main distribution panel
back on. This can be done by switching the service main breaker to the on or closed position.
Allow the generator to shut down.
Do not make any unnecessary adjustments.
Factory settings are correct for most applications. However, when making adjustments, be
careful to avoid overspeeding the engine.
If this procedure or equipment are not available,
locate the nearest Service Dealer and they can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
3.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
1. Loosen governor clamp bolt (See Figure 3.3).
Figure 3.3 — V-twin Engine Governor
Adjustment
Figure 3.4 — V-twin Full Load Speed Adjust
Screw
Full Load Speed Adjust Screw
3.7.1 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brackets with corrosion inhibiting spray such as WD-40®
or a comparable product.
3.8 VOLTAGE REGULATOR
Idle Spring
Governor
Shaft
(Rotate
Clockwise)
Governor Clamp Bolt
2. Completely remove the idle spring.
3. With governor arm at wide open throttle position,
rotate governor shaft fully clockwise. Tighten
clamp bolt to 84 inch-pounds.
4. Start unit and apply full load. Use full load speed
adjust screw (Figure 3.4) to adjust frequency to
58 Hz.
5. Remove load, stop engine, loosen the idle adjust
screw and reconnect the idle spring.
6. Using a hand, push the governor arm to the
closed throttle position. Make sure the idle spring
does not stretch at all.
7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the noload idle frequency to 63-63.5 Hz.
9. The governor is now set.
No Load Idle
Adjustment Screw
ADJUSTMENT
With the frequency between 62-63.5 Hertz, slowly
turn the slotted potentiometer (Figure 3.5) until line
voltage reads 244-252 volts.
NOTE:
Remove the access panel on top of the control
panel to adjust the voltage regulator.
Figure 3.5 – Voltage Adjustment Potentiometer
Turn to
adjust voltage.
NOTE:
The voltage regulator is housed above the generator's
control panel. The regulator maintains a voltage in
direct proportion to frequency. For example, at 62
Hertz, line-to-neutral voltage will be 124 volts.
13
Section 4 — Operation
Air-cooled 15 kW Generators
4.1 USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 4.1)
4.1.1 “AUTO” POSITION
Selecting this switch position activates fully automatic
system operation. It also permits starting and exercising
of the engine every seven days with the exercise timer
(see "Generator Test Under Load"). This position also is
used for remote starting, when it is set up.
4.1.2 “OFF” POSITION
This switch position shuts down the engine. This
position also prevents automatic operation.
4.1.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.
Figure 4.1 – Generator Control Panel
FUSE
5A
FUSE
15A
With the switch set to AUTO, the engine may
crank and start at any time without warning.
OFFAUTO
SET
EXERCISE
TIME
MAN.
Locat e your near estdealer at :
R
POWER SYSTEMS, INC.
FLA SHING GR EEN LED=
4FLASHINGREDLEDS=
Such automatic starting normally occurs when
utility power source voltage drops below a preset level or during the normal exercise cycle. To
prevent possible injury that might be caused by
such sudden starts, always set the switch to OFF
and remove both fuses before working on or
around the generator or transfer switch. Then,
place a “Do Not Operate” tag on the generator
panel and on the transfer switch.
R
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
N O UT IL IT Y S E N S E
EX ERCISER NOT SET
4.2 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their “Utility” position, i.e., loads connected
to the utility power source (Figure 4.2).
2. Be sure that normal utility power source voltage
is available to transfer switch terminal lugs N1
14
and N2.
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or closed) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to
“Sequence of Automatic Operation.”
4.3 SEQUENCE OF AUTOMATIC
OPERATION
The generator’s control panel houses a control logic
circuit board. This board constantly monitors utility power source voltage. Should that voltage drop
below a preset level, circuit board action will signal
the engine to crank and start. After the engine starts,
the circuit board signals the transfer switch to activate and connect load circuits to the standby power
supply (load terminal lugs T1/T2 connect to terminal
lugs E1/E2).
Upon restoration of utility source voltage above a
preset level, generator circuit board action signals the
transfer switch to transfer loads back to that power
supply. After retransfer, the engine is signalled to shut
down.
The actual sequence of operation is controlled by
sensors and timers on a control logic circuit board,
as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 70
percent of the nominal supply voltage, the sensor
energizes a 15-second timer.
• Once the timer has expired, the engine will crank
and start.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for
about 10 seconds before the load is transferred
to a standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of
the nominal rated voltage, transfer to standby
can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored to above 70
percent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action
de-energizes the transfer relay in the transfer
switch.
Section 4 — Operation
Air-cooled 15 kW Generators
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power
source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the
generator will then shut down.
4.4 MANUAL OPERATION
DANGER
Do NOT manually transfer under load.
Disconnect transfer switch from all power sources by approved means, such as a main circuit
breaker(s).
A manual HANDLE is shipped with the transfer
switch. Manual operation must be checked BEFORE
the transfer switch is operated electrically. To check
manual operation, proceed as follows:
1. Turn the generator’s AUTO/OFF/MANUAL switch
to OFF.
2. Turn OFF both UTILITY and EMERGENCY power
supplies to the transfer switch, with whatever
means provided (such as the main line circuit
breakers).
3. Note position of transfer mechanism main contacts by observing the moveable contact carrier
arm.
• Manual operation handle towards the top of
switch mechanism - LOAD terminals (T1, T2) are
connected to UTILITY terminals (N1, N2).
• Manual operation handle towards the bottom of
switch mechanism - LOAD terminals (T1, T2) are
connected to EMERGENCY terminals (E1, E2).
Do not use excessive force when operating the
transfer switch manually or damage could be
done to the manual handle.
4.4.1 CLOSE TO NORMAL SOURCE SIDE
Before proceeding, verify the position of the switch
by observing the position of manual operation handle
in Figure 4.2. If the handle is UP, the contacts are
closed in the NORMAL position, no further action is
required. If the handle is DOWN, proceed with Step
1.
Step 1: With the handle inserted into the actuating
shaft, move handle UP. Be sure to hold on to
the handle as it will move quickly after the
center of travel.
Figure 4.2 — Actuating Transfer Switch
Attach handle to actuating shaft.
Move handle
UP for the
NORMAL
(UTILITY)
position.
NOTE: Return handle to
storage position in enclosure
when finished with manual transfer.
Move handle
DOWN for the
EMERGENCY
(STANDBY)
position.
15
Section 4 — Operation
Air-cooled 15 kW Generators
4.4.2 CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch
by observing the position of the manual operation
handle in Figure 4.2. If the handle is DOWN, the
contacts are closed in the EMERGENCY (STANDBY)
position. No further action is required. If the handle
is UP, proceed with Step 1.
Step 1: With the handle inserted into the actuating
shaft, move the handle DOWN. Be sure to
hold on to the handle as it will move quickly
after the center of travel.
4.4.3 RETURN TO NORMAL SOURCE SIDE
Manually actuate switch to return manual operating
handle to the UP position.
4.5 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the transfer switch with whatever means provided (such as
the UTILITY main line circuit breaker).
DANGER
PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
HAZARDOUS AND POSSIBLY FATAL ELECTRICAL
SHOCK.
2. With an accurate AC voltmeter, check for correct
voltage.
Single-phase utility supply:
Measure across ATS terminal lugs N1 and N2. Also
check N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is correct and compatible with transfer switch ratings,
turn OFF the UTILITY supply to the transfer
switch.
4. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL position. The generator should crank and start.
5. Let the generator stabilize and warm up at noload for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to
its ON or CLOSED position.
DANGER
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED
TO TRANSFER SWITCH TERMINALS. CONTACT
WITH LIVE TERMINALS RESULTS IN EXTREMELY
DANGEROUS AND POSSIBLY FATAL ELECTRICAL
SHOCK.
7. With an accurate AC voltmeter and frequency
meter, check the no-load, voltage and frequency.
Single-phase generator supply:
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ....................................... 60-62 Hertz
b. Terminals E1 to E2 ........................ 240-246 VAC
c. Terminals E1 to NEUTRAL .............120-123 VAC
d. Terminals E2 to NEUTRAL ............. 120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to
its OFF or OPEN position.
9. Set the AUTO/OFF/MANUAL switch to the OFF
position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output voltage and frequency are correct and within stated
limits. If the no-load voltage is correct but noload frequency is incorrect, the engine governed
speed probably requires adjustment. If no-load
frequency is correct but voltage is not, the voltage
regulator may require adjustment.
4.6 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its
OFF or OPEN position.
2. Manually actuate the transfer switch main contacts to their EMERGENCY (STANDBY) position.
Refer to "Manual Operation".
3. To start the generator, set the AUTO/OFF/MANUAL
switch to MANUAL. When engine starts, let it stabilize for a few minutes.
4. Turn the generator's main circuit breaker to its
ON or CLOSED position. The generator now powers all LOAD circuits. Check generator operation
under load as follows:
• Turn ON electrical loads to the full rated wattage/amperage capacity of the generator. DO
NOT OVERLOAD.
• With maximum rated load applied, check
voltage and frequency across transfer switch
terminals E1 and E2. Voltage should be
greater than 230 volts and frequency should
be greater than 59 Hertz.
• Let the generator run under rated load for at
least 30 minutes. With unit running, listen for
unusual noises, vibration, overheating, etc.,
that might indicate a problem.
5. When checkout under load is complete, set main
circuit breaker of the generator to its OFF or
OPEN position.
6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/OFF/
MANUAL switch to its OFF position.
16
Section 4 — Operation
Air-cooled 15 kW Generators
7. Move the switch's main contacts back to their
UTILITY position. For example, load connected
to UTILITY power supply. Refer to "Manual
Operation". Handle and operating lever of transfer switch should be in UP position.
8. Turn on the UTILITY power supply to transfer
switch, using whatever means provided (such as
a UTILITY main line circuit breaker). The UTILITY power source now powers the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to
its AUTO position. The system is now set for fully
automatic operation.
4.7 SETTING THE EXERCISE TIMER
The generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise
once every seven days, on the day of the week and at
the time of day the following sequence is completed.
During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of
loads to the generator output does not occur during
the exercise cycle.
A switch on the control panel (see Figure 4.1) allows
for selection of the day and time for system exercise.
To select the desired day and time of day, the following sequence must be done at that time.
1. Verify that the AUTO/OFF/MANUAL switch is set
to AUTO.
2. Hold down the set timer switch until the generator starts (approximately 10 seconds) and then
release.
3. The generator will start and run for approximately
12 minutes and then shut down on its own. The
exerciser will then be set to run at that time of day
every week.
NOTE:
The exerciser will only work in the AUTO mode
and will not work unless this procedure is performed. The exerciser will need to be reset every
time the 12-volt battery is disconnected and then
reconnected. The exerciser WILL NOT work if
dip switch 2 (Remote Not Auto) on the controller
printed circuit board is ON.
4.8 PROTECTION SYSTEMS
4.8.1 LOW OIL PRESSURE SWITCH
This switch (Figure 4.3) has normally closed contacts that are held open by engine oil pressure during
cranking and operating. Should oil pressure drop
below the 8 psi range, switch contacts close, and the
engine shuts down. The unit should not be restarted
until oil is added, and the AUTO/OFF/MANUAL switch
must be turned to OFF and then back to AUTO.
4.8.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 4.3) close if the temperature should exceed approximately 140º C (284º
F), initiating an engine shutdown. The generator will
automatically restart and the LED will reset once the
temperature has returned to a safe operating level.
Figure 4.3 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
L
o
o
s
e
Oil
Drain
Hose
Oil Filter
4.8.3 OVERCRANK
This feature prevents the generator from damaging
itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from
starting. The unit will crank and rest for a preset time
limit. Then, it will stop cranking, and the LED will
light indicating an overcrank failure. The AUTO/OFF/
MANUAL switch will need to be set to OFF and then
back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature
will continue to activate.
High Temp Switch
n
17
Section 5 — Maintenance
Air-cooled 15 kW Generators
4.8.3.1 Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
4.8.4 OVERSPEED
This feature protects the generator from damage by
shutting it down if it happens to run faster than the
preset limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator
circuit. Contact the nearest Authorized Dealer if this
failure occurs.
5.1 FUSE
The generator panel’s 15 amp fuse (Figure 5.1) protects the DC control circuit against overload. The fuse
is wired in series with the battery output lead to the
panel. If the fuse element has melted open, the engine
cannot crank or start. Replace the fuse using only an
identical 15-amp replacement.
The generator panel’s 5 amp fuse protects the battery
charge circuit against overload. If the fuse element
has melted open, battery charging will not be possible. Replace the fuse using only an identical 5 amp
replacement. To remove fuse, push cap down and
rotate counterclockwise.
2. Remove the dipstick and wipe it dry with a clean
cloth.
Figure 5.2 — Oil Dipstick and Fill
Oil Dipstick
Oil Fill
3. Install the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT
FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its original position.
Figure 5.1 – Generator Control Panel
FUSE
5A
FUSE
15A
OFFAUTO
SET
EXERCISE
TIME
MAN.
Locat e your nearestdealer at :
R
FLA SHING GR EEN L ED=
4FLASHINGREDLEDS=
POWER SYSTEMS, INC.
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
N O U T IL IT Y S E N S E
EX ERCISER N OT S ET
R
5.2 CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see “Specifications”. For engine oil
recommendations, see "Changing the Engine Oil". To
check the engine oil level, proceed as follows (Figure
5.2):
1. Start the generator by moving the ATUO/OFF/
MANUAL switch to the MANUAL position. Allow
it to run for a short while and then shut it down
by moving the switch to the OFF position.
18
5.3 CHANGING THE ENGINE OIL
5.3.1 ENGINE OIL RECOMMENDATIONS
Use all season SAE 5W-30 synthetic oil or use SAE
30 oil of American Petroleum Institute (API) Service
Class SG, SH, SJ or SL.
Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil may result in an engine failure.
5.3.2 OIL CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Run the engine until it is thoroughly warmed up
then shut OFF the engine.
2. Immediately after the engine shuts OFF, pull the
oil drain hose (Figure 5.3) free of its retaining
clip. Remove the cap from the hose and drain the
oil into a suitable container.
Section 5 — Maintenance
Air-cooled 15 kW Generators
Figure 5.3 – Oil Drain Hose and Filter
L
o
o
s
e
n
Oil
Drain
Hose
Oil Filter
3. After the oil has drained, replace the cap onto the
end of the oil drain hose. Retain the hose in the
clip.
4. Refill with the proper recommended oil (see
"Changing the Engine Oil"). See the "Specifications"
section for oil capacities.
5.4 CHANGING THE OIL FILTER
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by
turning it counterclockwise.
2. Apply a light coating of clean engine oil to the
gasket of the new filter. See the "Specifications"
section for recommended filter.
3. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tighten
the filter an additional 3/4 to one turn (Figure
5.3).
4. Refill with the proper recommended oil (see
"Changing the Engine Oil"). See the "Specifications"
section for oil capacities.
5. Start the engine and check for leaks.
5.5 CHANGING THE ENGINE
AIR CLEANER
See Figures 1.1 and 1.2, for the location of the air
cleaner. Use the following procedure (Figure 5.4):
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover and air filter.
3. Wipe away dust or debris from inside of the air
box and around edges.
4. Install the new air cleaner into the air box.
5. Install the cover. Turn the two cover screws clockwise to tighten.
See the “Service Schedule” section for air cleaner
maintenance. See the "Specifications" section for air
filter replacement part number.
Figure 5.4 — Engine Air Cleaner
Screw
Cover
Filter
5.6 SPARK PLUG(S)
Reset the spark plugs gap or replace the spark plugs
as necessary. See the “Service Schedule” section for
maintenance requirements.
1. Clean the area around the base of the spark plugs
to keep dirt and debris out of the engine. Clean
by scraping or washing using a wire brush and
commercial solvent. Do not blast the spark plugs
to clean.
2. Remove the spark plugs and check the condition.
Replace the spark plugs if worn or if reuse is
questionable. See the “Service Schedule” section
for recommended inspection.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.50 mm (0.020 inch) for
by carefully bending the ground electrode (Figure
5.5).
Figure 5.5 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.50 mm (0.020 inch)
19
Section 5 — Maintenance
Air-cooled 15 kW Generators
5.7 BATTERY MAINTENANCE
The battery should be inspected per the “Service
Schedule”. The following procedure should be followed for inspection:
1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTERIES.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off,
and the 5A fuse is removed from the generator
control panel, or sparking may occur at the battery posts as the cables are attached, causing an
explosion.
5.8 ADJUSTING VALVE CLEARANCE
After the first 50 hours of operation, adjust the
valve clearance in the engine.
Important: If feeling uncomfortable about doing this
procedure or the proper tools are not available, contact the nearest Authorized Dealer for service assistance. This is a very important step to insure longest
life for the engine.
To adjust valve clearance:
• Make sure the engine is at room temperature.
• Make sure that the spark plug wire is removed
from the spark plug and out of the way.
• Remove the four screws attaching the valve cover
with a #2 or #3 phillips screwdriver.
• Make sure the piston is at Top Dead Center (TDC)
of its compression stroke (both valves closed). To
get the piston at TDC, remove the intake screen
at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench
to rotate the nut and hence the engine. While
watching the piston through the spark plug hole.
The piston should move up and down. The piston
is at TDC when it is up as high as it can go.
• Loosen the rocker jam nut. Use an 10mm allen
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve
stem with a feeler gauge. Correct clearance is
0.002-0.004 inch (0.05-0.1 mm). See Figure 5.6.
NOTE:
Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
20
Section 5 — Maintenance
Air-cooled 15 kW Generators
When valve clearance is correct, hold the pivot ball
stud in place with the allen wrench and tighten the
rocker arm jam nut. Tighten the jam nut to 174
in/lbs. torque. After tightening the jam nut, recheck
valve clearance to make sure it did not change.
Figure 5.6 - Valve Clearance Adjustment
Pivot Ball
Jam Nut
• Install new valve cover gasket.
• Re-attach the valve cover.
Start all four screws before tightening or it will not
be possible to get all the screws in place. Make
sure the valve cover gasket is in place.
• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.
Stud
NOTE:
Rocker
Arm
Valve
Stem
5.9 COOLING SYSTEM
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it
to quickly shut down. (See Figure 5.7 for vent locations.)
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of
the exhaust. Such materials may ignite and burn
from the heat of the exhaust system.
The maximum ambient temperature for the
generator is 48.9° C (104° F).
Figure 5.7 – Cooling Vent Locations
5.10 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water,
it MUST NOT be started and operated. Following
any submersion in water, have an Authorized Dealer
thoroughly clean and dry the generator.
5.11 CORROSION PROTECTION
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine
linkages with a light oil such as WD-40®.
5.12 OUT OF SERVICE PROCEDURE
5.12.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and it is to be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, it will signal a low
oil fault.
4. Set the AUTO/OFF/MANUAL switch to OFF and
turn off the utility power to the transfer switch.
5. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
oil. See ”Engine Oil Recommendations”.
6. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
7. Remove the spark plugs and spray fogging agent
into the spark plugs threaded openings. Reinstall
and tighten the spark plugs.
8. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
9. Clean and wipe the entire generator.
21
Section 5 — Maintenance
Air-cooled 15 kW Generators
5.12.2 RETURN TO SERVICE
To return the unit to service after storage, proceed
as follows:
1. Set the generator’s main circuit breaker to its
OFF (or OPEN) position.
2. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF.
3. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended oil is used in the engine (see "Enging Oil
Requirements"). If necessary, drain and refill with
the proper oil.
4. Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE
BATTERY. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery. See the “Specifications” section for type and
size.
5. Clean and wipe the entire generator.
6. Remove the 5A fuse from the generator control
panel.
7. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly. Replace the 5A fuse in the generator
control panel.
8. Open the fuel shutoff valve.
9. Start the unit by moving the AUTO/OFF/MANUAL
switch to MANUAL. Allow the unit to warm up
thoroughly.
10. Stop the unit and set the AUTO/OFF/MANUAL
switch to AUTO. Set the generator’s main circuit
breaker to its ON (or CLOSED) position.
11. Turn on the utility power to the transfer switch.
12. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise timer must be reset.
22
Section 5 — Maintenance
Air-cooled 15 kW Generators
7 KW - 40 KW SMALL STANDBY GENERATOR SETS
Following is a recommended maintenance schedule for small standby and residential generator sets from 7 kW to
40 kW in size, and applies to gas engine driven units. The established intervals in the schedule are the maximum
recommended when the unit is used in an average service application. They will need to be decreased (performed
more frequently) if the unit is used in a severe application. Use calendar time from the previous maintenance
interval to determine the next required maintenance interval.
Service Maintenance Interval Information:
The various service maintenance intervals are designated by interval numbers as follows:
1 An early inspection of the generator set to insure it is ready to operate when required and to identify any poten-
tial problem areas.
Performed monthly or following each 10 hours of operation of the unit and requires approximately .5 man-
hours per unit to complete.
This inspection may be performed by the end user providing the following safety steps are taken to prevent
the engine from starting automatically without warning:
To prevent injury, perform the following steps in the order indicated before starting any maintenance:
• Disable the generator set from starting and/or connecting to the load by setting the control panel Auto/Off/
Manual switch to the “OFF” position.
• Remove the control panel fuse.
• Turn off the battery charger.
• Remove the negative battery cable.
The battery charger must be turned off BEFORE removing the battery cable to prevent an over current condition
from burning out sensitive control panel components and circuits.
Following all maintenance, reverse these steps to insure the unit is returned to standby setup for normal
operation when required.
2 A wear-in service inspection of the generator set to insure it is ready to operate and carry the load when
required, and to identify any potential problem areas.
Performed ONLY ONCE following the first three months or the first 30 hours of operation after purchase of
the unit and requires approximately 2.5 man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an Authorized Service Dealer.
3 An operational inspection of the generator set to insure it is ready to operate and carry the load when required,
and to identify any potential problem areas.
Performed semi-annually or following each 50 hours of operation of the unit and requires approximately 1.5
man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an Authorized Service Dealer.
4 A mid-level inspection of the generator set to insure it is ready to operate and carry the load when required,
and to identify any potential problem areas.
Performed annually or following each 100 hours of operation of the unit and requires approximately 4.0
man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an Authorized Service Dealer.
5 A comprehensive inspection of the generator set to insure it is properly serviced and ready to operate and carry
the load when required, and to identify any potential problem areas.
Performed annually or following each 250 hours of operation of the unit and requires approximately 6.0
man-hours per unit to complete.
This inspection contains some maintenance tasks which require special tools, equipment, and/or knowledge
to accomplish and should be performed only by an Authorized Service Dealer.
mended Comp. Comp. to be done Comp. Required Comp. to be done Comp.
to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ Initials)
10 hrs. 6 months 50 hrs. 100 hrs. 250 hrs.
1. Disable the unit
from operating
per the first page
warning.
2. Check the engine
oil level. Adjust
as necessary.
3. Check the natural
gas delivery
system for leaks
and correct
pressure on gas
engine driven
units. Tighten
connections as
necessary.
4. Check the air
inlets and outlets
for debris. Clean
as necessary.
5. Check the battery
electrolyte level
and specific
gravity if
accessible. Adjust
as necessary.
6. Check the battery
posts, cables,
and charger for
loose
connections,
corrosion, and
proper operation.
Correct as
necessary.
7. Check the unit
wiring for loose
connections,
corrosion, and
damage. Correct
as necessary.
8. Check the engine
valve clearance.
Adjust as
necessary.
9. Visually inspect
the unit looking
for leaks, wear or
damage, loose
connections or
components, and
corrosion. Correct
as necessary.
mended Comp. Comp. to be done Comp. Required Comp. to be done Comp.
to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ Initials)
10 hrs. 6 months 50 hrs. 100 hrs. 250 hrs.
10. Test the engine
and transfer
switch safety
devices. Correct
and/or adjust as
necessary.
11. Initiate an
automatic start
and transfer of
the unit to site
load and exercise
it for at least 1
hour looking for
leaks, loose
connections or
components, and
abnormal
operating
conditions.
Correct as
necessary.
12. Start and
exercise the unit
at full rated load
(use a load bank
if the site load is
not enough) for
at least 2 hours
looking for leaks,
loose
connections or
components, and
abnormal
operating
conditions.
Correct as
necessary.
13. Perform an
engine oil
analysis (send a
sample to a lab
for results).
Change the
engine oil and
filters if the
analysis results
indicate this is
required.
14. Change the *
engine oil.
15. Replace the *
engine oil filter(s).
Recom-Task Task Required Task Task Required Task
* Change oil and fi lter after fi rst eight (8) hours of operation and then every 100 hours thereafter. Change sooner when operating under a heavy load or in
a dusty or dirty environment or in high ambient temperatures.
mended Comp. Comp. to be done Comp. Required Comp. to be done Comp.
to be done (Date- Required (Date- Semi- (Date- to be done (Date- Bi- (Date monthly/ Initials) to be done Initials) annually/ Initials) Annually/ Initials) annually/ Initials)
10 hrs. 6 months 50 hrs. 100 hrs. 250 hrs.
16. Replace the
engine air
filter(s).
17. Perform a 5
minute no-load
operational run
of the unit
looking for any
post service
problems.
18. Return the unit
to standby setup
for operation
when required.
26
Section 6 — Troubleshooting
Air-cooled 15 kW Generators
6.1 TROUBLESHOOTING GUIDE
Problem Cause Correction
The engine will not crank. 1. Fuse blown 1. Replace 15A fuse on generator
control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace
battery cables as necessary.
3. Defective starter motor 3. *
4. Dead Battery 4. Charge or replace battery.
The engine cranks but 1. Out of fuel 1. Replenish fuel.
will not start. 2. Defective fuel solenoid (FS) 2. *
3. Open #14 wire from 3. *
engine control board
4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
The engine starts hard 1. Air cleaner 1. Check, replace air cleaner.
and runs rough. plugged or damaged
2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s).
3. Fuel regulator not set. 3. Set fuel regulator.
4. Fuel pressure incorrect. 4. Confirm fuel pressure is at 11-14”
water column (0.4-0.5 psi) for LP,
and 5-7” water column (0.18-0.25
psi) for natural gas.
The AUTO/OFF/MANUAL switch 1. Defective switch 1. *
is set to OFF, but the engine 2. AUTO/OFF/MANUAL switch 2. *
continues to run. wired incorrectly
3. Defective control board 3. *
There is no AC output from 1. Main line circuit breaker open 1. Reset circuit breaker
the generator. to ON (or closed).
2. Generator internal failure 2. *
There is no transfer to 1. Defective transfer switch coil 1. *
standby after utility 2. Defective transfer relay 2. *
source failure. 3. Transfer relay circuit open 3. *
4. Defective control logic board 4. *
*Contact the nearest Authorized Dealer for assistance.
27
Section 7 — Mounting Dimensions
Air-cooled 15 kW Generators
Drawing No. 0F5927
28
R
CUSTO
D
CK
0
O
SP2
SP1
OP
0
868585
Y
DIAGRAM KE
Y
N
C
R
Y
S
SC
OR
OR
GTS
OR
OCK
S
CH
S
CH
SSU
CH
2
1
SC
Y
CH
M
D
S
OR
E
85
S
n
E
D
1 - 20 Vac Sense Transformer
o
SM
SC
316
ON
86
C
CIC
C1
6
85
86
56
SCR
6
3
86
8
85
3
0
8
0
6
3
J1
86
56
3
39
4
5A
66A
0
5
5
CO
OLDSW
3
55686
56
G
0
S
3A
0
3A
0
5B
C
R
5B
013A
0
3
3
0
5
9
0
0
0
351
351
3
94
229
66A
239
5A
5
0
225
86
SW3
SW3
CH
P
)
H
G
D
G
R
0
0
5
0
0
0
S
S
C
OR
C
OR
C
R
C3
OR
3
BA - BRUSH ASSEMBL
BCR - BATTERY CHARGE RELA
1 - 8 POSITION CONNECT
2 - 12 POSITION CONNECT
- 4 POSITION CONNECT
4 - 6 POSITION CONNECTI
B1 - MAIN OUTPUT BREAKE
CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATIO
D - DIOD
DSW - PCB MOUNTED DIP SWIT
FS - FUEL SOLENOI
F1 - FUSE 5A BATTERY CHARGE
F2 - FUSE 15 AMP SYSTE
F3, F4 - FUSE 5A SENSIN
RD - CONTROL PANEL GROUN
- TRANSFER SWITCH CONTACT
HTO - HIGH OIL TEMPERATURE SWITC
IC - INLINE CONNECT
IM1 - IGNITION MODULE, CYLINDER #
IM2 - IGNITION MODULE, CYLINDER #
LOP - LOW OIL PRE
- STARTER CONTACT
R - STARTER CONTACTOR RELA
SP1, SP2 - SPARK PLUG
W1 - AUTO / OFF / MANUAL SWIT
W2 - SET EXERCISE SWIT
- DOOR ALARM SWIT
M - STARTER MOT
TB - INSULATED TERMINAL BL
TR - RELAY, TRANSFE
TS - TERMINAL STRI
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.
* CENTER DECAL ON INSIDE OF THE COVER (ITEM #19)
** SUPPLIED WITH TRANSFER SWITCH (ITEM #1).
*** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER.
**** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7” FROM TOP OF ENCLOSURE.
***** SUPPLIED WITH HARNESS (P/N 0F5748)
47
Section 10 – Warranty
Air-cooled 15 kW Generators
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the
completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If there are any questions regarding the warranty rights and responsibilities, contact Generac at the following
address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 340
EAGLE, WI 53119
Part 1
48
Section 10 – Warranty
Air-cooled 15 kW Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue
for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal
components.
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
3) Ignition System including:
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube
49
Section 10 – Warranty
Air-cooled 15 kW Generators
GENERAC POWER SYSTEMS STANDARD LIMITED WARRANTY FOR
HOME STANDBY/LIGHT COMMERCIAL PRODUCT 45kW AND BELOW
For a period of two (2) years from the date of sale, or start-up by Authorized/Certified Generac Power Systems Dealer, or branch thereof, Generac
Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or
an Authorized/Certified Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with
the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/
Certified Generac Power Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby"
applications, as Generac Power Systems, Inc. has defined Standby, provided said generator has been properly installed and inspected on-site by
appropriate personnel. Scheduled maintenance, as outlined by the generator owner's manual, is highly recommended. This should be performed by
an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit throughout the
warranty period.
WARRANTY SCHEDULE
YEARS ONE and TWO — Limited comprehensive coverage on mileage, labor, and parts listed.
• - ALL COMPONENTS
*Start-up and/or On-line Registration, or Registration Card, along with Proof of Purchase, must be performed and/or sent in.
Guidelines:
• Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or
branch thereof.
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
• Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
• Use of Non-Generac replacement part(s) will void the warranty in its entirety.
• Engine coolant heaters (block-heaters), heater controls and circulating pumps are only covered during the first year of the warranty provision (If
applicable).
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to January 1, 2005.
2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).
3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and warranty.
5. Units used for prime power in place of existing utility power where utility is present or in place of utility power where utility power service does not
normally exist.
6. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
7. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
8. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s).
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.
11. Telephone, facsimile, cell phone, satellite, internet, or any other communication expenses.
12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).
13. Overtime, holiday, or emergency labor.
14. Planes, ferries, railroad, busses, helicopters, snowmobiles, snow-cats, off-road vehicle or any other mode of transportation deemed abnormal.
15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem.
16. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow
limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner
specific legal rights. Purchaser/owner also may have other rights that vary from state to state.
Generac Power Systems, Inc. • P.O. Box 8 • Waukesha, WI 53187
Part No. 0F5631Revision C (12/07/06)Printed in U.S.A.
Ph: (262) 544-4811 • Fax: (262) 544-4851
Bulletin 0171360SVE / Printed in U.S.A. 7.05
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.