Not intended for use as Primary Power in place of utility
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
or in life-support applications.
DANGER
GENERAC
POWERSYSTEMS, INC.
R
R
INTRODUCTION
Thank you for purchasing this model by Generac
Power Systems Inc.. This model is a compact, high
performance, air-cooled, engine-driven generator
designed to automatically supply electrical power to
operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal
enclosure that is intended exclusively for outdoor installation. This generator will operate using either vapor
withdrawn liquid propane (LP) or natural gas (NG).
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, contact
the nearest Authorized Dealer for starting, operating
and servicing procedures.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert personnel to special instructions about a particular operation that may be hazardous if performed incorrectly
or carelessly. Observe them carefully. Their defini-
tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in serious personal injury, including death, in addition to property
damage.
After this heading, read instructions that, if not
strictly complied with, may result in serious personal injury or property damage.
The operator is responsible for proper and safe use
of the equipment. The manufacturer strongly recommends that the operator read this Owner's Manual
and thoroughly understand all instructions before
using this equipment. The manufacturer also strongly recommends instructing other users to properly
start and operate the unit. This prepares them if they
need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information,
including warranty, electrical diagrams, exploded
views and lists of repair parts, for three different
models:
It is the operator's responsibility to perform all safety
checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by an Authorized
Dealer. Normal maintenance service and replacement
of parts are the responsibility of the owner/operator
and, as such, are not considered defects in materials
or workmanship within the terms of the warranty.
Individual operating habits and usage contribute to
the need for maintenance service.
Proper maintenance and care of the generator ensures
a minimum number of problems and keep operating
expenses at a minimum. See the Authorized Dealer
for service aids and accessories.
After this heading, read instructions that, if not
strictly complied with, could result in damage to
equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compliance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety symbols accompany the
DANGER, WARNING and CAUTION blocks. The type
of information each indicates is as follows:
This symbol points out important safety informa-
tion that, if not followed, could endanger personal
safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs,
simply contact an Authorized Dealer for assistance.
Service technicians are factory-trained and are capable of handling all service needs.
When contacting an Authorized Dealer about parts
and service, always supply the complete model number and serial number of the unit as given on its data
decal, which is located on the generator. See Figure 1.1
or Figure 1.2 in Section 1.4 for decal location.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To lo ca te t he ne ar es t AU TH OR IZ ED DE AL ER ,
please call this number:
1-800-333-1322
or locate us on the web at:
www.generac.com
Table of Contents
Air-cooled 7 kW, 12 kW and 15 kW Generators
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................ IFC
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted near the unit’s installation site. Safety should be stressed to
all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
defects or other reproductive harm.
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become
familiar with this Owner’s Manual and with the
unit. The generator can operate safely, efficiently and
reliably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible
circumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed
to the unit are, therefore, not all-inclusive. If using
a procedure, work method or operating technique
the manufacturer does not specifically recommend,
ensure that it is safe for others. Also make sure the
procedure, work method or operating technique utilized does not render the generator unsafe.
WARNING:
of California to cause cancer, birth
WARNING:
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
Please read all hazards carefully!
2
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends
that the installation, initial start-up and maintenance of this equipment is carried out by an
Authorized Dealer.
• The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust
system must be installed properly, in strict compliance with applicable codes and standards.
Following installation, do nothing that might render the system unsafe or in noncompliance with
such codes and standards.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit
is operating.
• Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation.
Do not alter the installation or permit even partial
blockage of ventilation provisions, as this can seriously affect safe operation of the generator. The
generator MUST be installed outdoors.
• When working on this equipment, remain alert
at all times. Never work on the equipment when
physically or mentally fatigued.
• Inspect the generator regularly, and contact the
nearest Authorized Dealer for parts needing repair
or replacement.
• Before performing any maintenance on the gen-
erator, disconnect its battery cables to prevent
accidental start up. Disconnect the cable from the
battery post indicated by a NEGATIVE, NEG or (–)
first. Reconnect that cable last.
• Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
ELECTRICAL HAZARDS
• All generators covered by this manual produce
dangerous electrical voltages and can cause fatal
electrical shock. Utility power delivers extremely
high and dangerous voltages to the transfer switch
as does the standby generator when it is in operation. Avoid contact with bare wires, terminals,
connections, etc., while the unit is running. Ensure
all appropriate covers, guards and barriers are in
Air-cooled 7 kW, 12 kW and 15 kW Generators
place before operating the generator. If work must
be done around an operating unit, stand on an
insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of
the generator to be connected to an approved earth
ground. Local electrical codes also may require
proper grounding of the generator electrical system.
• After installing this home standby electrical system, the generator may crank and start at any
time without warning. When this occurs, load circuits are transferred to the STANDBY (generator)
power source. To prevent possible injury if such a
start and transfer occur, always set the generator’s
AUTO/OFF/MANUAL switch to its OFF position
before working on equipment and remove the 5A
and 15A fuses from the generator control panel.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT WITH
THE VICTIM. Use a nonconducting implement,
such as a rope or board, to free the victim from the
live conductor. If the victim is unconscious, apply
first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed
and maintained properly. Installation always must
comply with applicable codes, standards, laws
and regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installation, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regulations.
• Keep a fire extinguisher near the generator at all
times. Extinguishers rated “ABC” by the National
Fire Protection Association are appropriate for
use on the standby electric system. Keep the extinguisher properly charged and be familiar with its
use. If there are any questions pertaining to fire
extinguishers, consult the local fire department.
IMPORTANT SAFETY INSTRUCTIONS
EXPLOSION HAZARDS
• Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install
the fuel supply system according to applicable
fuel-gas codes. Before placing the home standby
electric system into service, fuel system lines must
be properly purged and leak tested according to
applicable code. After installation, inspect the fuel
system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed
below may be used as installation guide for this
equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from
the National Fire Protection Association, 470
Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL
SYSTEMS FOR HEALTH CARE FACILITIES,
available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED
PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85
John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, avail-
able from the Food and Energy Council, 909
University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND
MAINTENANCE OF FARM STANDBY ELECTRICAL
SYSTEMS, available from the American Society
of Agricultural Engineers, 2950 Niles Road, St.
Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
3
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
DANGER
Only qualified electricians or contractors should
attempt such installations, which must comply
strictly with applicable codes, standards and
regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents
for damage.
• This standby generator set has been factory supplied with a weather protective enclosure that is
intended for outdoor installation only.
If this generator is used to power electrical load
circuits normally powered by a utility power
source, it is required by code to install a transfer switch. The transfer switch must effectively
isolate the electrical system from the utility
distribution system when the generator is operating (NEC 700, 701 and 702). Failure to isolate
an electrical system by such means will result in
damage to the generator and also may result in
injury or death to utility power workers due to
backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix his or her signature under the
consignor's memo of loss or damage.
If there is loss or damage after delivery, separate the
damaged materials and contact the carrier for claim
procedures.
“Concealed damage” is understood to mean damage
to the contents of a package that is not in evidence at
the time of delivery, but is discovered later.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have
to run for long periods of time with no operator present to monitor engine conditions. For that reason, the
engine is equipped with the following systems that
protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 3. Overcrank
2. High Temperature Sensor 4. Overspeed
There are LED readouts on the control panel to notify
personnel that one of these faults has occurred. There
is also a “System Set” LED that is described below.
1.3 SYSTEM SET LED
The “System Set” LED is lit when all of the following
conditions are true:
1. The AUTO/OFF/MANUAL switch is set to the
AUTO position.
2. The utility voltage being supplied to the unit is
being sensed by the Control PCB. If the utility
sense voltage is not connected to the unit or if it
is below 168 volts AC, then the system set light
will flash rapidly. This indicates that if the AUTO/
OFF/MANUAL switch is placed in the Auto position , the generator will start.
3. The “Not In Auto” dip switch is set to the OFF
position on the control board.
4. No alarms are present, for example, low oil pressure, high temperature, etc.
240 Volts 25.0 NG/29.2 LP 50 NG/50.0 LP 54.2 NG/62.5 LP
Main Line Circuit Breaker 30 Amp 50 Amp 65 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 60 Hz 60 Hz 60 Hz
Power Factor 1 1 1
Recommended Air Filter Part # 0C8127 Part # 0C8127 Part # 0C8127
Battery Requirement Group 26/26R Group 26/26R Group 26/26R
12 Volts and 12 Volts and 12 Volts and
350 Cold-cranking 525 Cold-cranking 525 Cold-cranking
Amperes Minimum Amperes Minimum Amperes Minimum
Weight 375 Pounds 470 Pounds 487 Pounds
Output Sound Level @ 23 ft (7m) at full load 68 db (A) 70.5db (A) 71.5 db (A)
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (42° F) above 16° C (60° F).
+ Total current in TWO separate curcuits. Current in each curcuit must not exceed the value stated for 240V.
1.5.2 ENGINE
Model 04673 Model 04674 Model 04675
Type of Engine GH-410 GT-990 GT-990
Number of Cylinders 1 2 2
Rated Horsepower 14.5 @ 3,600 rpm 30 @ 3,600 rpm 30 @ 3,600 rpm
Displacement 410cc 992cc 992cc
Cylinder Block Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast
Iron Sleeve Iron Sleeve Iron Sleeve
Valve Arrangement Overhead Valves Overhead Valves Overhead Valves
Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid-state w/Magneto
Recommended Spark Plug RC14YC RC12YC RC12YC
Spark Plug Gap 0.76 mm (0.030 inch) 0.508 mm (0.020 inch) 0.508 mm (0.020 inch)
Compression Ratio 8.6:1 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc 12Vdc
Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts
Recommended Oil Filter Part # 070185B Part # 070185B Part # 070185B
Recommended Air Filter Part # 0C8127 Part # 0C8127 Part # 0C8127
Operating RPM 3,600 3,600 3,600
6
M
M
OSE
G
G
T
OU
T
T
OSE
JUS
T
SCREW
UG
S
S
UG
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
1.6 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal
system. This type of system uses the vapors formed
above the liquid fuel in the storage tank.
The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997
California Air Resources Board for tamper-proof
dual fuel systems. The unit will run on natural gas or
LP gas, but it has been factory set to run on natural
gas. Should the primary fuel need to be changed to
LP gas, the fuel system needs to be reconfigured. See
Section 1.9 for instructions on reconfiguration of the
fuel system.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas; or at
least 2,520 Btus per cubic foot for LP gas. Ask the
fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches to
7 inches water colum (0.18 to 0.25 psi); and for
liquid propane, 10 inches to 12 inches of water
column (0.36 to 0.43 psi).
NOTE:
Any piping used to connect the generator to the
fuel supply should be of adequate size to ensure
the fuel pressure NEVER drops below 4 inches
water colum for natural gas or 10 inches water
column for liquid propane for all load ranges.
1.7 FUEL CONSUMPTION
Model # Nat. Gas (*) LP Vapor (**)
1/2 Load Full Load 1/2 Load Full Load
*Natural gas is in cubic feet per hour.
**LP is in gallons per hour/cubic feet per hour.
3. Remove the battery (if installed).
4. Disconnect wire #0 and wire #14 from the gas
solenoid on top of the demand regulator.
5. Remove the carburetor fuel hose from the outlet
port of the demand regulator.
6. Remove the demand regulator by removing the
fastener that retains the regulator mounting
bracket.
7. Remove the square headed steel pipe plug from
outlet port #1 and the brass hose barb fitting
from outlet port #2.
8. Refit the brass hose barb fitting to outlet port #1
and the square headed steel pipe plug to outlet
port #2.
9. Reverse procedure steps 1-5 to reinstall demand
regulator.
10. Take the plastic plug supplied in the poly-bag
with the generator and press it into the 3/4” hole
on the bottom of the air cleaner base (Figure
4.6).
11. Reverse the procedure to convert back to natural
gas.
Figure 1.3 – Demand Regulator
HOSE & PL
WITCHED SIDE
FUEL H
BRASS HOSE
FITTIN
AD
TMEN
NG FUEL SYSTE
PL
LP FUEL SYSTE
FUEL H
BRASS HOSE
FITTIN
TLE
POR
FUEL JE
1.8 RECONFIGURING THE
FUEL SYSTEM
1.8.1 7 KW, 410CC
To reconfigure the fuel system from NG to LP, follow
these steps (Figure 1.3):
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
1. Turn off the main gas supply (if connected).
2. Open the roof and remove the door.
NOTE:
The natural gas adjustment screw is preset during installation and should not need any further
adjustment.
1.8.2 12KW AND 15KW, V-TWIN ENGINES
To reconfigure the fuel system from NG to LP, follow
these steps:
NOTE:
The primary regulator for the propane supply is
NOT INCLUDED with the generator. A fuel pressure of 10 to 12 inches of water column (0.36 to
0.43 psi) to the fuel inlet of the generator MUST
BE SUPPLIED.
7
G
T
T
U
T
G
OSE
S
L
T
OR
OUSING PORT
JUSTER
SC
S
OU
S
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
1. Turn off the gas supply. (if connected)
2. Open the roof and remove the door.
3. Remove the battery. (if installed)
4. Remove the engine air in baffle located on the left-
hand side of the battery compartment. Two M6
screws are located on top of the baffle and two
M6 screws are located on the inside of the baffle
towards the back.
5. Remove the small hose clamp and hose from the
fuel regulator. It may be necessary to pry the hose
off of the brass fitting using a screwdriver to gently lift up the hose edge.
6. Remove the small brass hose fitting from the
regulator casting.
7. Place the small fuel jet, thread side first, into the
threaded hole originally occupied by the brass
hose fitting (Figure 1.4).
Figure 1.4 - Demand Regulator
TLET PORT
FUEL H
BRASS HOSE
FITTIN
IDLE CIRCUI
POR
1/8 NP
8. Using a short No. 2 Phillips screw driver, thread
the small fuel jet into the regulator casting. Do
not over tighten.
9. Apply thread sealant to the threads of the hose
fitting and replace it into the regulator body.
10. Re-attach the small hose and hose clamp and
tighten as necessary.
11. Replace the engine air in baffle using the four M6
screws.
12. Identify both brass adjustment screws on the
regulator.
One adjustment screw can be accessed from the
front of the unit and the second can be accessed
from the back of the unit enclosure by removing
the plastic hole plug. The screw can be turned
with a long flat blade screwdriver.
13. To adjust the system to run on LP fuel, turn
BOTH adjuster screws 1/2 TURN CLOCKWISE.
The system should now be set for maximum
power and best perfomance. DO NOT, UNDER
ANY CIRCUMSTANCES, REMOVE THE SET
PINS FROM THE REGULATOR HOUSING.
THIS WILL VOID THE WARRANTY.
8
BRASS HOSE
FITTIN
AD
REW
NOTE:
REGULAT
H
MAL
FUEL JE
14. It may be necessary to make minor adjustments
to the preset adjustment screw settings to achieve
maximum power, particularly at higher altitudes.
If experiencing problems with the unit producing
maximum power, follow the procedure in Section
2.6 (Adjusting the Fuel Regulator).
1.9 LOCATION
1.9.1 GENERATOR
Install the generator set, in its protective enclosure,
outdoors, where adequate cooling and ventilating air
is always available. Consider these factors:
• Install the unit where air inlet and outlet open-
ings will not become obstructed by leaves, grass,
snow, etc. If prevailing winds will cause blowing or
drifting, consider using a windbreak to protect the
unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to
allow three feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings to
the prevailing winds.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
• Install the generator as close as possible to
the transfer switch. HOWEVER, REMEMBER
THAT LAWS OR CODES MAY REGULATE THE
DISTANCE.
1.9.2 TRANSFER SWITCH
1.9.2.1 7 kW, 12 kW and 15 kW Units
Transfer switches for use with these generators
are sold separately and can be purchased from
Authorized Dealers.
• Install the transfer switch on a firm, sturdy sup-
porting structure.
• To prevent switch distortion, level the switch if
necessary. This can be done by placing washers
between the switch enclosure and mounting surface.
• Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
• Protect the switch at all times against excessive
moisture, dust, dirt, lint, construction grit and corrosive vapors.
• Failure to utilize the manufacturer’s transfer switch
with this generator may void the warranty.
Section 1 — General Information
Air-cooled 7 kW, 12 kW and 15 kW Generators
1.10 BATTERY INSTALLATION
Fill the battery with the proper electrolyte fluid if
necessary and have the battery fully charged before
installing it.
Before installing and connecting the battery, complete
the following steps:
1. Set the generator's AUTO/OFF/MANUAL switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
3. Remove the 5 amp fuse from the generator control panel.
If the AUTO/OFF/MANUAL switch is not set to its
OFF position, the generator can crank and start
as soon as the battery cables are connected. If
the utility power supply is not turned off, sparking can occur at the battery posts and cause an
explosion.
Battery cables were factory connected at the generator (Figure 1.5). Connect cables to battery posts as
follows:
4. Connect the red battery cable (from starter contactor) to the battery post indicated by a positive,
POS or (+).
5. Connect the black battery cable (from frame
ground) to the battery post indicated by a negative, NEG or (—).
6. Replace the 5 amp fuse in the generator control
panel.
NOTE:
Damage will result if battery connections are made
in reverse.
Figure 1.5 – Battery Cable Connections
NOTE:
The generator is equipped with a battery trickle
charger that is active when the unit is set up for
automatic operation. With the battery installed
and utility power source voltage available to the
transfer switch, the battery receives a trickle
charge while the engine is not running, to prevent
self-discharge. The trickle charger is designed to
help extend the life of the battery by maintaining the battery when the unit is not running. The
trickle charge feature cannot be used to recharge
a discharged battery.
1.11 THE BATTERY
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batteries and
the required precautions. Keep unauthorized personnel away from batteries.
When replacing the battery, use the following type of
battery: Group 26/26R 12-volt battery with a rating
of 350 cold-cranking amps minimum for 7 kW; 525
cold-cranking amps minimum for 12 and 15 kW at
-18º C (0º F) minimum. When using a maintenancefree battery, it is not necessary to check the specific
gravity or electrolyte level. Have these procedures
performed at the intervals specified in the “Service
Schedule.” A negative ground system is used. Battery
connections are shown on the wiring diagrams. Make
sure the battery is correctly connected and terminals
are tight. Observe battery polarity when connecting
the battery to the generator set.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive.
9
Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off, or
sparking may occur at the battery posts as the
cables are attached and cause an explosion.
2.1 BEFORE INITIAL START-UP
Before starting, complete the following:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Set the generator's AUTO/OFF/MANUAL switch to
the OFF position.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as the
utility main line circuit breaker).
4. Check the engine crankcase oil level and, if neces-
sary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
5. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in
accordance with applicable fuel-gas codes. All
fuel shutoff valves in the fuel supply lines must
be open.
2.2 CHECK TRANSFER SWITCH
OPERATION
Refer to Section 3.5 of the owner’s manual for manual operation procedures.
DANGER
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Turn on the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
DANGER
The transfer switch is now electrically “hot.”
Contact with “hot” parts will result in extremely
hazardous and possibly fatal electrical shock.
Proceed with caution.
2. Use an accurate AC voltmeter to check utility
power source voltage across terminals N1 and
N2. Nominal line-to-line voltage should be 240
volts AC.
3. Check utility power source voltage across termi-
nals N1 and the transfer switch neutral lug; then
across terminal N2 and neutral. Nominal line-toneutral voltage should be 120 volts AC.
4. When certain that utility supply voltage is compat-
ible with transfer switch and load circuit ratings,
turn OFF the utility power supply to the transfer
switch.
5. Set the generator's main circuit breaker to its
OFF (or open) position. Initial tests will be conducted at no-load condition.
6. On the generator panel, set the AUTO/OFF/
MANUAL switch to MANUAL. The engine should
crank and start.
7. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set
the generator’s main circuit breaker to its ON (or
closed) position.
DANGER
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
10
Proceed with caution! Generator power voltage
is now supplied to the transfer switch. Contact
with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
8. Connect an accurate AC voltmeter and a frequency meter across transfer switch terminal
lugs E1 and E2. Voltage should be 242-252 volts;
frequency should read about 61-63 Hertz.
9. Connect the AC voltmeter test leads across terminal lug E1 and neutral; then across E2 and
neutral. In both cases, voltage reading should be
121-126 volts AC.
10. Set the generator’s main circuit breaker to its
OFF (or open) position. Let the engine run at noload for a few minutes to stabilize internal engine
generator temperatures.
11. Set the generator's AUTO/OFF/MANUAL switch to
OFF. The engine should shut down.
NOTE:
It is important not to proceed until certain that
generator AC voltage and frequency are correct
and within the stated limits. Generally, if both AC
frequency and voltage are high or low, the engine
governor requires adjustment. If frequency is correct, but voltage is high or low, the generator’s
voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied,
proceed as follows:
1. Set generator’s main circuit breaker to its OFF
(or open) position.
2. Set the generato r's AU TO/OFF/ MANUAL
switch to OFF.
3. Turn OFF the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
Do not attempt manual transfer switch opera-
tion until all power voltage supplies to the
transfer switch have been positively turned off.
Failure to turn off all power voltage supplies
will result in extremely hazardous and possibly
fatal electrical shock.
4. Manually set the transfer switch to the STANDBY
position, i.e., load terminals connected to the
generator's E1/E2 terminals. The transfer switch
operating lever should be down.
5. Set the generator's AUTO/OFF/MANUAL switch
to MANUAL. The engine should crank and start
immediately.
6. Let the engine stabilize and warm up for a few
minutes.
7. Set the generator’s main circuit breaker to its ON
(or closed) position. Loads are now powered by
the standby generator.
8. Turn ON electrical loads. Apply an electrical load
equal to the full rated wattage/amperage capacity
of the installed generator.
9. Connect an accurate AC voltmeter and a frequency meter across terminal lugs E1 and E2. Voltage
should be greater than 230 volts; frequency
should be greater than 58 Hertz.
10. Let the generator run at full rated load for 20-30
minutes. Listen for unusual noises, vibration or
other indications of abnormal operation. Check
for oil leaks, evidence of overheating, etc.
11. When testing under load is complete, turn OFF
electrical loads.
12. Set the generator's main circuit breakers to their
OFF (or open) positions.
13. Let the engine run at no-load for a few minutes.
14. Set the AUTO/OFF/MANUAL switch to OFF. The
engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation,
proceed as follows:
1. Set the generator’s main circuit breaker to it’s
OFF (or open) position.
2. Check that the AUTO/OFF/MANUAL switch is set
to OFF.
3. Manually set the transfer switch to the UTILITY
position, i.e., load terminals connected to the utility power source side.
4. Turn ON the utility power supply to the transfer
switch, using the means provided (such as a utility main line circuit breaker).
5. Set the AUTO/OFF/MANUAL switch to AUTO.
Then set the generator’s main circuit breaker to
its ON (or closed) position. The system is now
ready for automatic operation.
6. Turn OFF the utility power supply to the transfer
switch.
With the AUTO/OFF/MANUAL switch at AUTO, the
engine should crank and start when the utility source
power is turned OFF. After starting, the transfer
switch should connect load circuits to the standby
side. Let the system go through its entire automatic
sequence of operation.
With the generator running and loads powered by
generator AC output, turn ON the utility power supply
to the transfer switch. The following should occur:
• After about 15 seconds, the switch should transfer
loads back to the utility power source.
• About one minute after retransfer, the engine
should shut down.
11
Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
2.6 ADJUSTING THE REGULATOR
(NATURAL GAS ONLY)
Although the generator has been factory set to provide maximum power, it may be necessary in some
areas to adjust this setting. Because natural gas has
different BTU or power content across the country
the engine may not perform as designed.
If experiencing engine problems at high or full load
conditions follow these steps. It will require a frequency meter to perform this procedure.
1. Turn off utility power to the main distribution
panel in the house. This can be done by switching
the service main breaker to the off or open position.
2. Allow the generator to start before loading the
generator. Confirm the no-load frequency with
the roof open and door off is set at 63-63.5 Hz.
Transfer load to emergency circuits.
3. Turn on appliances, lights, pumps, etc., that are
on the emergency circuits in an attempt to fully
load the generator. Be cautious not to overload
the generator. Use the following chart as a guide:
4. When 3/4 load has been achieved. Connect a fre-
quency meter to the output lugs of the generator’s
main line circuit breaker.
5. The fuel regulator is fitted with one (7 kW), or two
(12 & 15 kW) adjustment screws. While watching
the frequency meter, slowly turn the adjustment
screw clockwise or counterclockwise one at a
time until highest frequency is read on the meter.
Only limited adjustment is available between the
set pins. Under no circumstances should any of
the pins be removed (Figures 2.1 and 2.2).
Figure 2.1 — Dual Fuel Regulators
Adjustment
Screw
(Both Sides)
Set Pin
(Both Sides)
12
V-twin
Adjustment
Screw
(One Side
Only)
410
Set
Pin
6. When the highest frequency is reached maximum
power has been set. Then turn both adjustment
screws 1/4 turn counterclockwise. Regulator is
now set.
Figure 2.2 — Placement of Regulator
Adjustment Screw
7. Turn utility power to the main distribution panel
back on. This can be done by switching the service main breaker to the on or closed position.
Allow the generator to shut down.
Do not make any unnecessary adjustments.
Factory settings are correct for most applications. However, when making adjustments, be
careful to avoid overspeeding the engine.
If this procedure or equipment are not available,
locate the nearest Authorized Dealer and they can
perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7 ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
2.7.1 7 KW UNITS
1. Loosen the governor clamp bolt (Figure 2.3).
2. Hold the governor lever at its wide open throttle
position, and rotate the governor shaft clockwise
as far as it will go. Then, tighten the governor
lever clamp bolt to 70 inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up
at no-load.
4. Connect an AC frequency meter across the generators AC output leads.
5. Turn the primary adjust screw to obtain a frequency reading of 61.5 Hz. Turn the secondary
adjust screw to obtain a frequency reading of
62.5 Hz.
Section 2 — Post Installation Start-up and Adjustments
Air-cooled 7 kW, 12 kW and 15 kW Generators
6. When frequency is correct at no load, check the
AC voltage reading. If voltage is incorrect, the voltage regulator may require adjustment.
Figure 2.3 — Single Cylinder Engine Governor
Adjustment
SECONDARY
ADJUST SCREW
GOVERNOR
SHAFT
GOVERNOR
CLAMP
BOLT
2.7.2 12 KW AND 15 KW UNITS
PRIMARY
ADJUST
SCREW
1. Loosen governor clamp bolt (See Figure 2.4).
Figure 2.4 — V-twin Engine Governor
Adjustment
7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the noload idle frequency to 63-63.5 Hz.
9. The governor is now set.
Figure 2.5 — V-twin Full Load Speed Adjust
Screw
Full Load Speed Adjust Screw
2.7.3 ADDITIONAL CORROSION
PROTECTION
Periodically spray all engine linkage parts and brackets with corrosion inhibiting spray such as WD-40 or
a comparable product.
Idle Spring
Governor
Shaft
(Rotate
Clockwise)
Governor Clamp Bolt
No Load Idle
Adjustment Screw
2. Completely remove the idle spring.
3. With governor arm at wide open throttle position,
rotate governor shaft fully clockwise. Tighten
clamp bolt to 84 inch-pounds.
4. Start unit and apply full load. Use full load speed
adjust screw (Figure 2.5) to adjust frequency to
58 Hz.
5. Remove load, stop engine, loosen the idle adjust
screw and reconnect the idle spring.
6. Using a hand, push the governor arm to the
closed throttle position. Make sure the idle spring
does not stretch at all.
2.8 VOLTAGE REGULATOR
ADJUSTMENT
With the frequency between 62-63.5 Hertz, slowly
turn the slotted potentiometer (Figure 2.6) until line
voltage reads 244-252 volts.
NOTE:
Remove the access panel on top of the control
panel to adjust the voltage regulator.
Figure 2.6 – Voltage Adjustment Potentiometer
13
Section 3 — Operation
Air-cooled 7 kW, 12 kW and 15 kW Generators
NOTE:
The voltage regulator is housed above the generator's
control panel. The regulator maintains a voltage in
direct proportion to frequency. For example, at 62
Hertz, line-to-neutral voltage will be 124 volts.
3.1 BREAK-IN PROCEDURE
Once the unit has been installed, with utility power
connected to the transfer switch, and all electrical
checks have been made, it is strongly recommended
that the following “Break-in Procedure” be completed
to ensure correct generator operation in the future.
1. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
2. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
3. The unit will start, and the transfer switch will
transfer to standby.
4. Run the unit for one hour at 25 percent load.
5. Run the unit for one hour at 50 percent load.
6. Run the unit for one hour at 75 percent load.
7. Run the unit for one hour at 100 percent load.
8. Turn ON the utility power supply to the transfer
switch, which will allow the transfer switch to
transfer back to utility power. The unit will continue to run for one minute and then shut down.
9. Allow the unit to cool.
10. Drain the oil and remove the oil filter. Replace
the oil filter according to Section 4.4, “Changing
the Oil Filter”. Replace the oil with synthetic oil
as recommended in Section 4.3, “Changing the
Engine Oil”.
11. The generator is now ready for service.
3.2 USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 3.1)
3.2.1 “AUTO” POSITION
Selecting this switch position activates fully automatic
system operation. It also permits starting and exercising
of the engine every seven days with the exercise timer
(see Section 3.6). This position also is used for remote
starting, when it is set up.
3.2.2 “OFF” POSITION
This switch position shuts down the engine. This
position also prevents automatic operation.
3.2.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the
engine. Transfer to standby power will not occur
unless there is a utility failure.
14
Figure 3.1 – Generator Control Panel
FUSE
5A
FUSE
15A
With the switch set to AUTO, the engine may
crank and start at any time without warning.
OFFAUTO
SET
EXERCISE
TIME
MAN.
Locate y our nearestdealer at :
R
POWER SYSTEMS, INC.
FLA SHIN G GREEN LED =
4FLASHINGREDLEDS=
Such automatic starting normally occurs when
utility power source voltage drops below a preset level or during the normal exercise cycle. To
prevent possible injury that might be caused by
such sudden starts, always set the switch to OFF
and remove both fuses before working on or
around the generator or transfer switch. Then,
place a “Do Not Operate” tag on the generator
panel and on the transfer switch.
R
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
NO UTILITY SENSE
EX ERCISER N OT SET
3.3 AUTOMATIC TRANSFER
OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their “Utility” position, i.e., loads connected
to the utility power source (Figure 3.2).
2. Be sure that normal utility power source voltage
is available to transfer switch terminal lugs N1
and N2.
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or closed) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to
Section 3.4, “Sequence of Automatic Operation.”
3.4 SEQUENCE OF AUTOMATIC
OPERATION
The generator’s control panel houses a control logic
circuit board. This board constantly monitors utility power source voltage. Should that voltage drop
below a preset level, circuit board action will signal
the engine to crank and start. After the engine starts,
the circuit board signals the transfer switch to activate and connect load circuits to the standby power
supply (load terminal lugs T1/T2 connect to terminal
lugs E1/E2).
Section 3 — Operation
Air-cooled 7 kW, 12 kW and 15 kW Generators
Upon restoration of utility source voltage above a
preset level, generator circuit board action signals the
transfer switch to transfer loads back to that power
supply. After retransfer, the engine is signalled to shut
down.
The actual sequence of operation is controlled by
sensors and timers on a control logic circuit board,
as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 60
percent of the nominal supply voltage, the sensor
energizes a 15-second timer.
• Once the timer has expired, the engine will crank
and start.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for
about 10 seconds before the load is transferred
to a standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of
the nominal rated voltage, transfer to standby
can occur.
D. Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored to above 70
percent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action
de-energizes the transfer relay in the transfer
switch.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power
source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the
generator will then shut down.
3.5 MANUAL TRANSFER OPERATION
3.5.1 TRANSFER TO GENERATOR
POWER SOURCE
To start the generator and activate the transfer switch
manually, proceed as follows:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Set the generator’s AUTO/OFF/MANUAL switch
to OFF.
3. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utility
main line circuit breaker).
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies to the
switch have been positively turned off. Failure
to turn off all power voltage supplies may result
in extremely hazardous and possibly fatal electrical shock.
4. Use the manual transfer handle inside the transfer switch to move the main contacts to their
“Standby” position, i.e., loads connected to the
standby power source (Figure 3.2).
5. To crank and start the engine, set the AUTO/OFF/
MANUAL switch to MANUAL.
6. Let the engine stabilize and warm up for a few
minutes.
7. Set the generator’s main circuit breaker to its ON
(or closed) position. The standby power source
now powers the loads.
Figure 3.2 – Manual Transfer Switch Operation
3.5.2 TRANSFER BACK TO UTILITY POWER
SOURCE
When utility power has been restored, transfer back
to that source and shut down the generator. This can
be accomplished as follows:
1. Set the generator’s main circuit breaker to its
OFF (or open) position.
2. Let the engine run for a minute or two at no-load
to stabilize the internal temperatures.
3. Set the generator’s AUTO/OFF/MANUAL switch to
its OFF (or open) position. The engine should
shut down.
4. Check that utility power supply to the transfer
switch is turned OFF.
15
Section 3 — Operation
Air-cooled 7 kW, 12 kW and 15 kW Generators
DANGER
Do not attempt to activate the transfer switch
manually until all power voltage supplies
to the switch have been positively turned off.
Failure to turn off all power voltage supplies
may result in extremely hazardous and possibly
fatal electrical shock.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their
“Utility” position, i.e., loads connected to the utility power source (Figure 3.2).
6. Turn ON the utility power supply to the transfer
switch using the means provided.
7. Set the system to automatic operation as outlined
in “Automatic Transfer Operation,” Section 3.3.
3.6 SETTING THE EXERCISE TIMER
The generator is equipped with an exercise timer.
Once it is set, the generator will start and exercise
once every seven days, on the day of the week and at
the time of day the following sequence is completed.
During this exercise period, the unit runs for approximately 12 minutes and then shuts down. Transfer of
loads to the generator output does not occur during
the exercise cycle.
A switch on the control panel (see Figure 3.1) allows
for selection of the day and time for system exercise.
To select the desired day and time of day, the following sequence must be done at that time.
1. Verify that the AUTO/OFF/MANUAL switch is set
to AUTO.
2. Hold down the set timer switch until the generator starts (approximately 10 seconds) and then
release.
3. The generator will start and run for approximately
12 minutes and then shut down on its own. The
exerciser will then be set to run at that time of day
every week.
NOTE:
The exerciser will only work in the AUTO mode
and will not work unless this procedure is performed. The exerciser will need to be reset every
time the 12-volt battery is disconnected and then
reconnected. The exerciser WILL NOT work if
dip switch 2 (Remote Not Auto) on the controller
printed circuit board is ON.
3.7 PROTECTION SYSTEMS
3.7.1 LOW OIL PRESSURE SWITCH
This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during
cranking and operating. Should oil pressure drop
below the 8 psi range, switch contacts close, and the
engine shuts down. The unit should not be restarted
until oil is added, and the AUTO/OFF/MANUAL switch
must be turned to OFF and then back to AUTO.
3.7.2 HIGH TEMPERATURE SWITCH
This switch’s contacts (Figure 3.3) close if the temperature should exceed approximately 140º C (284º
F), initiating an engine shutdown. The generator will
automatically restart and the LED will reset once the
temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
Low Oil Switch
L
o
o
s
e
n
Oil
Drain
Hose
Oil Filter
3.7.3 OVERCRANK
This feature prevents the generator from damaging
itself when it continually attempts to start and another problem, such as no fuel supply, prevents it from
starting. The unit will crank and rest for a preset time
limit. Then, it will stop cranking, and the LED will
light indicating an overcrank failure. The AUTO/OFF/
MANUAL switch will need to be set to OFF and then
back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature
will continue to activate.
High Temp Switch
16
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators
3.7.3.1 Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds
Approximately 90 seconds total
3.7.4 OVERSPEED
This feature protects the generator from damage by
shutting it down if it happens to run faster than the
preset limit. This protection also prevents the generator from supplying an output that could potentially damage appliances connected to the generator
circuit. Contact the nearest Authorized Dealer if this
failure occurs.
4.1 FUSE
The generator panel’s 15 amp fuse (Figure 4.1) protects the DC control circuit against overload. The fuse
is wired in series with the battery output lead to the
panel. If the fuse element has melted open, the engine
cannot crank or start. Replace the fuse using only an
identical 15-amp replacement.
The generator panel’s 5 amp fuse protects the battery
charge circuit against overload. If the fuse element has
melted open, battery charging will not be possible.
Replace the fuse using only an identical 5 amp replacement. To remove fuse, push cap down and rotate counterclockwise.
2. Remove the dipstick and wipe it dry with a
clean cloth.
3. Install the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If necessary, add oil to the “Full” mark only. DO NOT
FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level
below the “Add” mark on the dipstick. Doing
this could damage the engine.
4. Install the dipstick.
5. Reset the AUTO/OFF/MANUAL switch to its original position.
Figure 4.2 — Oil Dipstick and Fill, 7 kW
Oil Dipstick and Fill
Figure 4.1 – Generator Control Panel
FUSE
5A
FUSE
15A
OFFAUTO
SET
EXERCISE
TIME
MAN.
Locate y our nearestdealer at :
R
POWER SYSTEMS, INC.
FLA SHIN G GREEN LED =
4FLASHINGREDLEDS=
R
SYSTEM SET
LOW OIL
HIGH TEMP.
OVER SPEED
OVER CRANK
NO UTILITY SENSE
EX ERCISER N OT SET
4.2 CHECKING THE ENGINE
OIL LEVEL
For oil capacities, see “Specifications,” Section 1.5.
For engine oil recommendations, see Section 4.3.1.
To check the engine oil level, proceed as follows
(Figure 4.2):
1. Start the generator by moving the Auto/Off/
Manual switch to the MANUAL position. Allow it
to run for a short while and then shut it down by
moving the switch to the OFF position.
Figure 4.3 — Oil Dipstick and Fill,
12 kW and 15 kW
Oil Dipstick
Oil Fill
17
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators
4.3 CHANGING THE ENGINE OIL
4.3.1 ENGINE OIL RECOMMENDATIONS
Use oil of American Petroleum Institute (API) Service
Class SG, SH or SJ. Use all season SAE 5W-30
Synthetic oil. Organic break-in oil is required before
using synthetic oil.
NOTE:
The unit is supplied with “break-in” oil. See the
“Break-in Procedure,” Section 3.1, for the first
required oil change.
Any attempt to crank or start the engine before
it has been properly serviced with the recommended oil may result in an engine failure.
4.3.2 OIL CHANGE PROCEDURE
To change the oil, proceed as follows:
1. Run the engine until it is thoroughly warmed up
then shut OFF the engine.
2. Immediately after the engine shuts OFF, pull the
oil drain hose (Figure 4.4) free of its retaining
clip. Remove the cap from the hose and drain the
oil into a suitable container.
Figure 4.4 – Oil Drain Hose and Filter
L
o
o
s
e
n
4.4 CHANGING THE OIL FILTER
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by
turning it counterclockwise.
2. Apply a light coating of clean engine oil to the
gasket of the new filter. See Section 1.5.1 for recommended filter.
3. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tighten
the filter an additional 3/4 to one turn (Figure
4.4).
4. Refill with the proper recommended oil (see
Section 4.3.1). See Section 1.5.2 for oil capacities.
5. Start the engine and check for leaks.
4.5 CHANGING THE ENGINE
AIR CLEANER
4.5.1 7 KW, 12 KW AND 15 KW
GENERATORS
See Figures 1.1 and 1.2, for the location of the air
cleaner. Use the following procedure (Figure 4.6):
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover and air filter.
3. Wipe away dust or debris from inside of the air
box and around edges.
4. Install the new air cleaner into the air box.
5. Install the cover. Turn the two cover screws clockwise to tighten.
See the “Service Schedule,” Section 4.13 for air
cleaner maintenance. See Section 1.5.1 for air filter
replacement part number.
Oil
Drain
Hose
Oil Filter
3. After the oil has drained, replace the cap onto the
end of the oil drain hose. Retain the hose in the
clip.
4. Refill with the proper recommended oil (see
Section 4.3.1). See Section 1.5.2 for oil capacities.
18
Figure 4.6 — 7 kW, Engine Air Cleaner Location
Fuel
Air Cleaner
Regulator
3/4" Hole
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators
Figure 4.7 — 12 kW and 15 kW Engine
Air Cleaner
Screw
Cover
Filter
4.6 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark
plug(s) as necessary. See Section 4.13 for maintenance requirements.
1. Clean the area around the base of the spark
plug(s) to keep dirt and debris out of the engine.
Clean by scraping or washing using a wire brush
and commercial solvent. Do not blast the spark
plug(s) to clean.
2. Remove the spark plug(s) and check the condition. Replace the spark plug(s) if worn or if reuse
is questionable. See Section 4.13 for recommended inspection.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.76 mm (0.030 inch)
for 7 kW and 0.50 mm (0.020 inch) for 12/15 kW
by carefully bending the ground electrode (Figure
4.8).
Figure 4.8 – Setting the Spark Plug Gap
SET PLUG GAP AT 0.76 mm/0.50 mm
(0.030 inch/0.020 inch)
4.7 BATTERY MAINTENANCE
The battery should be inspected per the “Service
Schedule,” Section 4.13. The following procedure
should be followed for inspection:
1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTERIES.
3. Have the state of charge and condition checked.
This should be done with an automotive-type battery hydrometer.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding.
A battery presents a risk of electrical shock
and high short circuit current. The following precautions are to be observed when working on
batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery; and
• Disconnect charging source prior to connecting or
disconnecting battery terminals.
Do not open or mutilate the battery. Released
electrolyte has been known to be harmful to the
skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, immediately
flush thoroughly with water and seek medical
attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
Lead-acid batteries present a risk of fire because
they generate hydrogen gas. The
19
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators
following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from body before touching the battery by first touching a grounded metal
surface.
Be sure the AUTO/OFF/MANUAL switch is set to
the OFF position before connecting the battery
cables. If the switch is set to AUTO or MANUAL,
the generator can crank and start as soon as the
battery cables are connected.
Be sure the utility power supply is turned off, and
the 5A fuse is removed from the generator control
panel, or sparking may occur at the battery posts
as the cables are attached, causing an explosion.
4.8 ADJUSTING VALVE CLEARANCE
After the first six months of operation, adjust the
valve clearance in the engine.
Important: If feeling uncomfortable about doing this
procedure or the proper tools are not available, contact
the nearest Authorized Dealer for service assistance.
This is a very important step to insure longest life for
the engine.
To adjust valve clearance:
• Make sure the engine is at room temperature.
• Make sure that the spark plug wire is removed from
the spark plug and out of the way.
• Remove the four screws attaching the valve cover with
a #2 or #3 phillips screwdriver.
• Make sure the piston is at Top Dead Center (TDC) of
its compression stroke (both valves closed). To get
the piston at TDC, remove the intake screen at the
front of the engine to gain access to the flywheel nut.
Use a large socket and socket wrench to rotate the
nut and hence the engine. While watching the piston
through the spark plug hole. The piston should move
up and down. The piston is at TDC when it is up as
high as it can go.
• Loosen the rocker jam nut. Use an 10mm allen
wrench to turn the pivot ball stud while checking
clearance between the rocker arm and the valve stem
with a feeler gauge. Correct clearance is 0.002-0.004
inch (0.05-0.1 mm).
NOTE:
Hold the rocker arm jam nut in place as the pivot
ball stud is turned.
When valve clearance is correct, hold the pivot ball stud
in place with the allen wrench and tighten the rocker
arm jam nut. Tighten the jam nut to 174 in/lbs. torque.
After tightening the jam nut, recheck valve clearance to
make sure it did not change.
Figure 4.10 - Valve Clearance Adjustment
Rocker
Pivot Ball
Stud
Jam Nut
• Install new valve cover gasket.
• Re-attach the valve cover.
NOTE:
Start all four screws before tightening or it will not
be possible to get all the screws in place. Make sure
the valve cover gasket is in place.
• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.
Arm
Valve
Stem
4.9 COOLING SYSTEM
Air inlet and outlet openings in the generator compartment must be open and unobstructed for continued
proper operation. This includes such obstructions as
high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it to
quickly shut down. (See Figure 4.9 for vent locations.)
Figure 4.9 – Cooling Vent Locations
20
Air-cooled 7 kW, 12 kW and 15 kW Generators
The exhaust from this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of the
exhaust. Such materials may ignite and burn from
the heat of the exhaust system.
The maximum ambient temperature for the
generator is 48.9° C (104° F).
4.10 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it MUST
NOT be started and operated. Following any submersion
in water, have an Authorized Dealer thoroughly clean and
dry the generator.
4.11 CORROSION PROTECTION
Periodically wash and wax the enclosure using automotive type products. Frequent washing is recommended
in salt water/coastal areas. Spray engine linkages with
a light oil such as WD-40.
4.12 OUT OF SERVICE PROCEDURE
4.12.1 REMOVAL FROM SERVICE
If the generator cannot be exercised every seven days,
and it is to be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, it will signal a low oil
fault.
4. Set the AUTO/OFF/MANUAL switch to OFF and turn
off the utility power to the transfer switch.
5. While the engine is still warm from running, drain
the oil completely. Refill the crankcase with oil. See
”Engine Oil Recommendations,” Section 4.3.1.
6. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
7. Remove the spark plug(s) and spray fogging agent
into the spark plug(s) threaded openings. Reinstall
and tighten the spark plug(s).
8. Remove the battery and store it in a cool, dry room
on a wooden board. Never store the battery on any
concrete or earthen floor.
9. Clean and wipe the entire generator.
Section 4 — Maintenance
4.12.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as
follows:
1. Set the generator’s main circuit breaker to its OFF
(or open) position.
2. Verify that utility power is turned off and that the
AUTO/OFF/MANUAL switch is set to OFF.
3. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended
oil is used in the engine (see Section 4.3.1). If necessary, drain and refill with the proper oil.
4. Check the state of the battery. Fill all cells of unsealed
batteries to the proper level with distilled water. DO
NOT USE TAP WATER IN THE BATTERY. Recharge
the battery to 100 percent state of charge, or, if
defective, replace the battery. See “Specifications,”
Section 1.5, for type and size.
5. Clean and wipe the entire generator.
6. Remove the 5A fuse from the generator control
panel.
7. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected incorrectly. Replace the 5A fuse in the generator control
panel.
8. Open the fuel shutoff valve.
9. Start the unit by moving the AUTO/OFF/MANUAL
switch to MANUAL. Allow the unit to warm up thoroughly.
10. Stop the unit and set the AUTO/OFF/MANUAL
switch to AUTO. Set the generator’s main circuit
breaker to its ON (or closed) position.
11. Turn on the utility power to the transfer switch.
12. The generator is now ready for service.
NOTE:
If the battery was dead or disconnected, the exercise
timer must be reset.
21
Section 4 — Maintenance
Air-cooled 7 kW, 12 kW and 15 kW Generators
4.13 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest Authorized Dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action Inspect Change Clean W = Weekly
R = Replace as Necessary M = Monthly
* = Notify Dealer Y = Yearly
if Repair is Needed.
FUEL
Fuel lines and connections*X M
LUBRICATION
Oil levelX M
OilX AFTER BREAK-IN,
AND Y
Oil filterX AFTER BREAK-IN,
AND Y
COOLING
Enclosure louversX X W
BATTERY
Remove corrosion, X X M
ensure dryness
Clean and tighten
battery terminals
Check charge state
Electrolyte levelX R EVERY 6 M
(unsealed batteries only)*
ENGINE AND MOUNTING
Air cleanerX R Y
Spark plug(s)X R Y
GENERAL CONDITION
Vibration, Noise, Leakage,X M
Temperature*
COMPLETE TUNE-UP*TO BE COMPLETED BY AN AUTHORIZED DEALER
X X M
X R EVERY 6 M
22
Section 5 — Troubleshooting
Air-cooled 7 kW, 12 kW and 15 kW Generators
5.1 TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
The engine will not crank. 1. Fuse blown 1. Replace 15A fuse on generator
control panel.
2. Loose, corroded or defective 2. Tighten, clean or replace
battery cables as necessary.
3. Defective starter contactor (7 kW) 3. *
4. Defective starter motor 4. *
5. Dead Battery 5. Charge or replace battery.
The engine cranks but 1. Out of fuel 1. Replenish fuel.
will not start. 2. Defective fuel solenoid (FS) 2. *
3. Open #14 wire from 3. *
engine control board
4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
The engine starts hard 1. Air cleaner 1. Check, replace air cleaner.
and runs rough. plugged or damaged
2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s).
3. Fuel regulator not set. 3. Set fuel regulator.
4. Fuel pressure incorrect. 4. Confirm fuel pressure is at 10-12"
water column (0.36-0.43 psi) for
LP, and 5-7” water colum (0.18-
0.25 psi) for natural gas.
The AUTO/OFF/MANUAL switch 1. Defective switch 1. *
is set to OFF, but the engine 2. AUTO/OFF/MANUAL switch 2. *
continues to run. wired incorrectly
3. Defective control board 3. *
There is no AC output from 1. Main line circuit breaker open 1. Reset circuit breaker
the generator. to ON (or closed).
2. Generator internal failure 2. *
There is no transfer to 1. Defective transfer switch coil 1. *
standby after utility 2. Defective transfer relay 2. *
source failure. 3. Transfer relay circuit open 3. *
4. Defective control logic board 4. *
Unit consumes large 1. Break-in procedure 1. *
amounts of oil. not followed (see Section 2.1)
*Contact the nearest Authorized Dealer for assistance.
BA - BRUSH ASSEMBL
BCR - BATTERY CHARGE RELA
CB1 - CIRCUIT BREAKER, MAIN OUTPU
CB2 - CIRCUIT BREAKER, ALT. EXCITATIO
D - DIOD
FS - FUEL SOLENOI
F1 - FUSE 15 AM
F2 - FUSE 5 AM
HTO - HIGH OIL TEMPERATURE SWIT
HM - HOUR RUN METE
IM - IGNITION MODUL
LOP - LOW OIL PRE
- STARTER CONTACTE
RE SWIT
P - SPARK PL
W1 - AUTO / OFF / MANUAL SWIT
W2 - SET EXERCISE SWIT
M - STARTER MOT
TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, during such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the
completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unapproved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs. The
warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty service, evidence must be presented showing the date of the sale to the original purchaser/owner.
If there are any questions regarding the warranty rights and responsibilities, contact Generac at the following
address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 340
EAGLE, WI 53119
Part 1
52
Section 10 – Warranty
Air-cooled 7 kW, 12 kW and 15 kW Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the
date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue
for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a
warranted emissions-related part to fail to be identical in all material respects to the part as described in the engine
manufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsible
for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal
components.
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
* Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
3) Ignition System including:
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube
53
Section 10 – Warranty
Air-cooled 7 kW, 12 kW and 15 kW Generators
GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY
FOR GENERAC RESIDENTIAL AND LIGHT COMMERCIAL UNITS
For a period of two (2) years or two thousand (2,000) hours of operation from the date of sale, which ever occurs first, Generac Power Systems, Inc.
will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or an Authorized/Certified
Generac Power Systems Dealer, or branch thereof, is found to be defective under normal use and service, in accordance with the warranty schedule
set forth below. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Authorized/Certified Generac Power
Systems Dealer, or branch thereof. This warranty applies only to Generac Power Systems Generators used in "Standby" applications, as Generac
Power Systems, Inc. has defined Standby. Scheduled maintenance, as outlined by the generators owners manual, is highly recommended. This should
be performed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof. This will verify service has been performed on the unit
throughout the warranty period.
WARRANTY SCHEDULE
YEAR ONE and TWO — one hundred percent (100%) coverage on mileage, labor, and parts listed (proof of purchase and maintenance required).
• Engine ALL COMPONENTS
• Alternator ALL COMPONENTS
• Transfer System ALL COMPONENTS
Guidelines:
Tr av e l a l l o wa n c e f o r A i r a nd L i qu i d c oo l e d u n i t s i s l im i t e d t o 6 0 m i l e s m a x im u m , a n d 2 .0 h o ur s m a xi m u m o r $ 10 0 . 0 0 m a x im u m ( pe r occurrence, whichever is less), round trip, to the nearest authorized Generac Service Facility, and only applies to permanently wired and mounted units. Any and all warranty repairs and/or concerns, must be performed and/or addressed by an Authorized/Certified Generac Power Systems Dealer, or branch thereof.
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the generator set. If a Non-Generac Power
Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the generator set, no warranty coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate
Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
• Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
• Use of Non-Generac replacement part(s) will void the warranty in its entirety.
• Engine coolant heaters (block-heaters), heater controls and circulating pumps after the first year.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to July 1, 2004.
2. Costs of normal maintenance (i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up).
3. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
4. Units sold, rated or used for "Prime Power", "Trailer Mounted" or "Rental Unit" applications as Generac Power Systems have defined Prime Power,
Trailer Mounted or Rental Unit. Contact a Generac Power Systems Distributor for Prime Power, Trailer Mounted or Rental Unit definition and
warranty.
5. Failures caused by any external cause or act of God such as, but not limited to, collision, fire, theft, freezing, vandalism, riot or wars, lightning,
earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
6. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
7. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.
8. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the
defective part(s).
9. Damage related to rodent and/or insect infestation.
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.
11. Telephone, facsimile, cell phone, satellite, Internet, or any other communication expenses.
12. Rental equipment used while warranty repairs are being performed (i.e. rental generators, cranes, etc.).
13. Overtime, holiday, or emergency labor.
14. Modes of transportation deemed abnormal (refer to Generac Power Systems Warranty, Policies, Procedures and Flat Rate Manual).
15. Steel enclosures that are rusting due to improper installation, location in a harsh or saltwater environment or scratched where integrity of paint
applied is compromised.
16. Any and all expenses incurred investigating performance complaints unless defective Generac materials and/or workmanship were the direct
cause of the problem.
17. Starting batteries, fuses, light bulbs, engine fluids, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC POWER SYSTEMS
MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow
limitations on how long an implied warranty lasts, so the above limitation may not apply to purchaser/owner.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT
SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A
DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may not apply to purchaser/
owner. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence. This warranty gives purchaser/owner
specific legal rights. Purchaser/owner also may have other rights that vary from state to state.
Generac Power Systems, Inc. • P.O. Box 8 • Waukesha, WI 53187
Part No. 0F3983Revision C (11/03/05)Printed in U.S.A.
Ph: (262) 544-4811 • Fax: (262) 544-4851
Bulletin 0166550SBY / Printed in U.S.A. 6.04
ERRATA SHEET
ALL 8.5 kW THROUGH 15 kW HOME STAND-BY GENERATORS WITH
GT-990/760 ENGINES
2/24/06
! IMPORTANT INFORMATION !
THE SPARK PLUG GAP FOR ALL 8.5 kW THROUGH
THE 15 kW HOME STAND-BY GENERATORS WITH
THE GT-990/760 ENGINES SHOULD BE SET AT 1.02
mm (0.040 inch). THE RECOMMENDED SPARK PLUG
IS CHAMPION #RC12YC (PART NO. 0G0767A).
P/N: 0G0730 REV. A
PRE PACKAGED UNITS ONLY
85
44
77
84
80
82
79
78
81
80
72
87
76
82
48
41
40
68
72
86
5
44
47
73
52
45
95
47
19
A
6
12
91
63
97
50
16
96
64
71
69
30
17
51
29
49
66
55
75
28
65
31
46
74
8
50
11
49
51
9
35
57
27
56
49
35
49
49
90
1
91
26
60
44
62
48
61
51
58
4949
50
22
67
59
93
38
89
14
63
13
51
48
37
43
49
2
43
46
24
A
36
32
47
49
20
51
4
23
51
34
94
51
21
7
33
50
18
52
91
15
70
58
42
71
47
54
35
25
93
3
39
10
69
35
63
25
92
68
10C61401ASSEMBLY, ENCLOSURE BASE
0D19011ASSEMBLY, ENCLOSURE BASE (7KW)
20C67352SUPPORT, ROOF FOLDING
30F00631ENCLOSURE, FRONT
40C70621ENCLOSURE, EXHAUST SIDE
0C7062A1ENCLOSURE, EXHAUST SIDE (7KW)
5 0F00661ENCLOSURE, SIDE & BACK
0F0066A1ENCLOSURE, SIDE & BACK (7KW)
60E98731ENCLOSURE, ROOF
70C70651PANEL, ALTERNATOR DIVIDER
0C7065A1PANEL, ALTERNATOR DIVIDER (7KW)
80C8101A1PANEL, MUFFLER BOX SIDE
0C88611PANEL, MUFFLER BOX SIDE (7KW)
90C8101B1COVER, MUFFLER BOX
0C88621COVER, MUFFLER BOX (7KW)
100C82831GASKET, DOOR SEAL
110C8284A1FOAM, BACK ENCLOSURE
120C8284B1FOAM, ROOF ENCLOSURE
130C8284C1FOAM, FRONT ENCLOSURE
140C82851BRACKET, BATTERY SUPPORT
150C8899A1PAD, 24"X48" WITH MOUNTING HOLES
160D11281PANEL, ENGINE DIVIDER
0D1128A1PANEL, ENGINE DIVIDER (7KW)
170E42441BAFFLE, INTAKE
0D1605A1BAFFLE, INTAKE (7KW)
180D16061HOUSING, FAN
0D52641BAFFLE, EXHAUST (7KW)
190D18392BRACKET, TOP SUPPORT
200D18402BRACKET, BOTTOM SUPPORT
210D24251DUCT, BASE AIR
220D25881GASKET, FRONT DIVIDER
0D2588A1GASKET, FRONT DIVIDER (7KW)
230D26761COVER, FRONT EXHAUST ENCLOSURE
240D26771COVER, BACK EXHAUST ENCLOSURE
250D2979B2CLOTH, HARDWARE 266.7mm x 146mm
0D2979B3CLOTH, HARDWARE 266.7mm x 146mm
(7KW)
260D2979C1CLOTH, HARDWARE 543mm x 146mm
270D2979D1CLOTH, HARDWARE 266.7mm x 387.4mm
0D2979E1CLOTH, HARDWARE (7KW)
280E42451FOAM, FRONT INTAKE BAFFLE
0D3058A1FOAM, FRONT INTAKE BAFFLE (7KW)
290E4245A1FOAM, TOP INTAKE BAFFLE
300E4245B1FOAM, BACK INTAKE BAFFLE
0D3058C1FOAM, BACK INTAKE BAFFLE (7KW)
310D3057D1FOAM, BACK ENCL. STRIP
320D3059A1FOAM, EXHAUST SIDE ENCLOSURE END
330D3059B1FOAM, EXHAUST SIDE ENCLOSURE FRONT
340D3059C1FOAM, EXHAUST FAN HOUSING
350D717624WASHER, SELF LOCKING
22WASHER, SELF LOCKING (7KW)
360D3059D1FOAM, FRONT EXHAUST ENCLOSURE COVER
370D3059E1FOAM, BACK EXHAUST ENCLOSURE COVER
380C7781A2DOOR, PAWL
390D30371LATCH, QUARTER TURN LOCKING
400D25371HINGE, LIFT OFF, TYPE A PIN
410D25381HINGE, LIFT OFF, TYPE B PIN
420D3037A1LATCH, QUARTER TURN NON-LOCKING
430A21154WASHER NYLON .250”
440220979WASHER LOCK M6-1/4”
450224738WASHER FLAT ¼” ZINC
460F071014RIVET POP 0.125 X 0.337
4704741114SCREW HHC M6-1.0 X 16 G8.8
04741112SCREW HHC M6-1.0 X 16 G8.8 (7KW)
480431165SCREW HHC M6-1.0 X 12 G8.8
0431166SCREW HHC M6-1.0 X 12 G8.8 (7KW)
490D370018NUT, LOCKING FLANGE M6-1.0
0D370016NUT, LOCKING FLANGE M6-1.0 (7KW)
500D466211SCREW HHTT M8-1.2 X 20 BP
5109038836SCREW TAPTITE M6-1.0 X 12 BP
24SCREW TAPTITE M6-1.0 X 12 BP (7KW)
520921202NUT LOCK TRIC M6 X 1.0 Y/ZNC
540D31671GASKET, BATTERY SUPPORT BRACKET
550A33281PLUG, PLASTIC 0.593
560554141LUG SLDLSS #2-#8X17/64 CU
570920791SCREW TAPTITE M6-1.0X25 BP
580A16582L/WASH SPECIAL ¼
590C29371BRACKET, BATTERY HOLD DOWN (7KW)
600867291CONTACTOR, STARTER (7KW)
610388040AJ01CABLE, #6 RED BATTERY 38.5”
620221272NUT HEX 1/4-20 STEEL (7KW)
630221296WASHER LOCK 5/16
0221297WASHER LOCK 5/16 (7KW)
640749088SCREW TAPTITE M5-0.8 X 10 BP
650D23461HARNESS, ENGINE
0D23451HARNESS, ENGINE (7KW)
66023484F1BUSHING, SNAP SB-1000-12
670221421SCREW HHC 5/16-18 X 3/4 G5 (7KW)
680A78362RIVET,1/8” X 0.126" - 0.375" LSH POP
690A84752L/WASH SPECIAL #10
7009129700691ASSEMBLY, ROOF / DOOR GROUND WIRE
7109129700702ASSEMBLY, ROOF / DOOR GROUND WIRE
720554502PLUG PLASTIC 1.375
730E596811GASKET, EXTRUDED TRIM
740D37011PLATE, "HOT"
750D34721GROMMET 2.75 X 1/16
760C87421EXTERNAL CONNECTION BOX
770C89111POWER BLOCK
780D84421HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX
0D86521HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (7KW)
790369372SCREW PPHM #10-32 X 1
800221525WASHER LOCK #10
810517132WASHER FLAT M5
820221585NUT HEX #10-32 STEEL
830D30311FUEL LINE, 3/4"OUTDOOR (NOT SHOWN)
840268501WASHER SHAKPROOF EXT 1/4 STEEL
850498131NUT HEX M6-1.0 G8 YELLOW CHROME
860D2537A1HINGE, LIFT OFF, TYPE A KNUCKLE
870D2538A1HINGE, LIFT OFF, TYPE B KNUCKLE
890E28741SCREW HHTR 1/4-20 X 3/4
900431074SCREW HHC M8-1.25 X 25
910221458WASHER FLAT 5/16
920457714NUT HEX M8-1.25
930C39062SELF-ALIGN SCREW M6 HH
940E43211PANEL, EXHAUST ALIGNMENT
950E1330A1GROMMET, 38.1 CROSS SLIT WITH HOLE
960E96921BRACKET, REGULATOR MOUNTING
970429072SCREW HHC M8-1.25 X 16mm