Generac Power Systems 04389-0, 04456-0, 04390-0 Installation And Owner's Manual

POWER SYSTEMS, INC.
®
Installation and
Owner’s Manual
Air-cooled, Prepackaged
Models: 04389-0 (6 kW NG, 7 kW LP) 04456-0 (10 kW NG, 12 kW LP) 04390-0 (13 kW NG, 15 kW LP)
DEADLY EXHAUST FUMES.
OUTDOOR INSTALLATION ONLY!!
Not intended for use as Primary Power in place of utility or in life­support applications.
GENERAC
POWER SYSTEMS, INC.
R
R
!
!
DANGER
Generac®Power Systems, Inc.
INTRODUCTION
Thank you for purchasing this model of the Guardian product line by Generac Power Systems Inc. This model is a compact, high performance, air-cooled, engine-driven generator designed to automatically supply electrical power to operate critical loads dur­ing a utility power failure.
This unit is factory installed in an all-weather , metal enclo­sure that is intended exclusively for outdoor installation. This generator will operate using either vapor withdrawn liquid propane (LP) or natural gas (NG).
READ THIS MAN UAL THOROUGHLY
If you do not understand any portion of this manual, contact Generac or your nearest Generac/Guardian Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, you can read instructions that, if not strictly complied with, will result in serious personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, may result in personal injury, including death, or property damage.
After this heading, you can read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, you can read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property of you and others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. We strongly recommend that the operator read this Owner's Manual and thoroughly understand all instructions before using this equip­ment. We also strongly recommend instructing other users to properly start and operate the unit. This pre­pares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for three different Guardian models:
• 04389-0 – 6 kW NG, 7 kW LP, single-cylinder GH­410 Engine
• 04456-0 – 10 kW NG, 12 kW LP, V-twin GT-760 Engine
• 04390-0 – 13 kW NG, 15 kW LP, V-twin GT-990 Engine
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safe­ty checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac/Guardian Authorized Dealer. Normal main­tenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for mainte­nance service.
Proper maintenance and care of your generator ensure a minimum number of problems and keep operating expenses at a minimum. See your Generac/Guardian Authorized Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs, simply contact a Generac/Guardian Authorized Dealer for assistance. Service technicians are factory­trained and are capable of handling all of your service needs.
When contacting a Generac/Guardian Authorized Dealer or the factory about parts and service, always supply the complete model number and serial number of your unit as given on its data decal, which is locat­ed on your generator. See Figure 1.1 or Figure 1.2 in Section 1.6 (Page 5) for decal location.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To locate the GENERAC/GUARDIAN AUTHORIZED
DEALER nearest you, please call this number:
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
DANGER
!
Table of Contents
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Generac®Power Systems, Inc. 1
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ........................IFC
Contents ..........................................................IFC
Operation and Maintenance ............................IFC
How to Obtain Service ....................................IFC
Authorized Dealer Locator Number ....................IFC
Safety Rules ........................................................2
Standards Index..................................................3
Section 1 – General Information ..................4
1.1 Unpacking/Inspection....................................4
1.2 Protection Systems........................................4
1.3 Additional Generator Features ......................4
1.3.1 7 kW, 12 kW, and 15 kW Units ..........4
1.4 Your Generator ..............................................5
1.5 Specifications ................................................6
1.5.1 Generator ..........................................6
1.5.2 Engine ................................................6
1.6 Fuel Requirements and Recommendations....7
1.7 Fuel Consumption ........................................7
1.8 Reconfiguring the Fuel System ......................7
1.9 Location ........................................................8
1.9.1 Generator ..........................................8
1.9.2 Transfer Switch..................................8
1.10 Battery Installation ........................................8
1.11 The Battery....................................................9
Section 2 – Post Installation Start-up
and Adjustments ........................9
2.1 Before Initial Startup ....................................9
2.2 Check Transfer Switch Operation................10
2.3 Electrical Checks ........................................10
2.4 Generator Tests Under Load ......................10
2.5 Checking Automatic Operation....................11
2.6 Adjusting the Regulator (Natural Gas Only) ..11
2.7 Engine Governor Adjustment ......................12
2.7.1 7 kW Units ......................................12
2.7.2 12 kW and 15 kW Units ..................12
2.7.3 Additional Corrosion Protection ......13
2.8 Voltage Regulator Adjustment......................13
Section 3 – Operation ....................................13
3.1 Break-in Procedure......................................13
3.2 Using the Auto/Off/Manual Switch ..............13
3.2.1 “Auto” Position..................................13
3.2.2 “Off ” Position....................................13
3.2.3 “Manual” Position ............................13
3.3 Automatic Transfer Operation ....................14
3.4 Sequence of Automatic Operation................14
3.5 Manual Transfer Operation ........................14
3.5.1 Transfer to Generator
Power Source......................................14
3.5.2 Transfer Back to Utility
Power Source......................................15
3.6 Setting the Exercise Timer ..........................15
3.7 Protection Systems......................................16
3.7.1 Low Oil Pressure Switch ..................16
3.7.2 High Temperature Switch ................16
3.7.3 Overcrank ........................................16
3.7.4 Overspeed ........................................16
Section 4 – Maintenance ..............................16
4.1 Fuse ............................................................16
4.2 Checking the Engine Oil Level ....................16
4.3 Changing the Engine Oil..............................17
4.3.1 Engine Oil Recommendations ..........17
4.3.2 Oil Change Procedure ......................17
4.4 Changing the Oil Filter ................................17
4.5 Changing the Engine Air Cleaner ................18
4.5.1 7 kW, 12 kW and 15 kW
Generators........................................18
4.6 Spark Plug(s) ..............................................18
4.7 Battery Maintenance....................................18
4.8 Adjusting Valve Clearance............................19
4.9 Cooling System............................................20
4.10 Attention After Submersion ........................20
4.11 Out of Service Procedure ............................20
4.12 Corrosion Protection ..................................21
4.13 Service Schedule ........................................22
Section 5 – Troubleshooting ........................23
5.1 Troubleshooting Guide................................23
Section 6 – Electrical Data............................24
Section 7 – Exploded Views and
Parts Lists ....................................32
Section 8 – Notes............................................53
Section 9 – Mounting Dimensions..............55
Section 10 – Warranty....................................56
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating tech­nique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that you choose does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GENERAL HA ZAR
DS
• For safety reasons, Generac recommends
that the installation, initial start-up and maintenance of this equipment is carried out by a Generac/Guardian Authorized Dealer.
• The engine exhaust fumes contain carbon monox-
ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in noncompli­ance with such codes and standards.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti-
lating air is critical to correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seri­ously affect safe operation of the generator. The generator MUST be installed outdoors.
• When working on this equipment, remain alert at
all times. Never work on the equipment when you are physically or mentally fatigued.
• Inspect the generator regularly, and contact your
nearest Generac/Guardian Authorized Dealer for parts needing repair or replacement.
• Before performing any maintenance on the genera-
tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
!
!
!
IMPORTANT SAFETY INSTRUCTIONS
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment.
!
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
!
!
!
!
DANGER
!
Generac®Power Systems, Inc. 3
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera­tion. Avoid contact with bare wires, terminals, con­nections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insu­lated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. Local electrical codes also may require proper grounding of the generator electrical system.
• After installing this home standby electrical sys­tem, the generator may crank and start at any time without warning. When this occurs, load circuits are transferred to the STANDBY (generator) power source. To prevent possible injury if such a start and transfer occur, always set the generator’s Auto/Off/Manual switch to its OFF position before working on equipment and remove the fuse.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. A V OID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
• Keep a fire extinguisher near the generator at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the standby electric system. Keep the extin­guisher properly charged and be familiar with its use. If you have any question pertaining to fire extinguishers, consult your local fire department.
EXPL
OSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Install the fuel supply system according to applica­ble fuel-gas codes. Before placing the home stand­by electric system into service, fuel system lines must be properly purged and leak tested according to applicable code. After installation, you must inspect the fuel system periodically for leaks. No leakage is permitted.
STANDARDS INDEX
In the absence of pertinent standards, codes, regula­tions and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA 02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-
TEMS FOR HEALTH CARE FACILITIES, avail­able same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE,
available same as Item 1.
4. NFPA No. 58, AMERICAN NA TIONAL STANDARD
FOR STORAGE AND HANDLING OF LIQUEFIED PETROLEUM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL
ELECTRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available
from the Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND MAINTE-
NANCE OF FARM STANDBY ELECTRICAL SYS­TEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE, available same as Item 1.
IMPORTANT SAFETY INSTRUCTIONS
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
• This standby generator set has been factory sup­plied with a weather protective enclosure that is intended for outdoor installation only.
• This standby generator set is packaged with an automatic transfer switch with built in load center. The combination transfer switch and load center is pre-wired with a 2 foot and 30 foot conduit. Circuit breakers for emergency circuit connections are included.
• This UL listed, 2-pole switch is rated at 100 AC amperes at 250 volts maximum. This transfer
switch is for indoor use only.
If this generator is used to power electrical load circuits normally powered by a utility power source, you are required by code to install a trans­fer switch. The transfer switch must effectively iso­late the electrical system from the utility distribu­tion system when the generator is operating (NEC
701). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor's memo of loss or damage.
If you note loss or damage after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
1.2 PROTECTION SYSTEMS
Unlike an automobile engine, the generator may have to run for long periods of time with no operator present to monitor engine conditions. F or that reason, the engine is equipped with the following systems that protect it against potentially damaging conditions:
1. Low Oil Pressure Sensor 3. Overcrank
2. High Temperature Sensor 4. Overspeed
There are LED readouts on the control panel to noti­fy you that one of these faults has occurred. There is also a “System Set” LED that is lit when all of the fol­lowing conditions are true:
1. The Auto/Off/Manual switch is set to the AUTO position.
2. The “Not In Auto” dip switch is set to the OFF position on the control board.
3. No alarms are present.
1.3 ADDITIONAL GENERATOR
FEATURES
1.3.1 7 KW, 12 KW, AND 15 KW UNITS
The 7 kW, 12 kW and 15 kW air-cooled Guardians offer additional features that are not factory preset:
1. Remote Start – This allows for remote starting of the generator by means of the #183 (common) and #178 (normally open) lines with the Auto/Off/Manual switch set to AUTO. Closure of the circuit starts the unit; opening of the circuit stops the unit. See Figure 1.1.
NOTE:
This function will work only with the unit in the AUTO mode.
Figure 1.1 – Remote Start/Alarm Options
–Type 14 AWG wire is recommended. –These options should be wired to the unit by a qualified electrician or
Generac/Guardian Authorized Dealer.
2. Remote/Common Alarm – This allows for an alarm, light, horn, etc., to activate when any fault has occurred. Lines #210 (common) and #211 (normally open) provide a “closure” on common fault, which can be used for 120 volts, 10 amps maximum. See Figure 1.1.
3. Remote Not Auto – The generator will not auto­matically start during a utility failure.
Section 1 General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
4 Generac®Power Systems, Inc.
DANGER
183
178
210
211
183
178
211
210
Section 1 General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Generac®Power Systems, Inc. 5
1.4 YOUR GENERATOR
Figure 1.3 – 12 kW/15 kW, V-twin GT-760/GT-990 Engine
Figure 1.2 – 7 kW, Single Cylinder GH-410 Engine
Data Decal
Exhaust Enclosure
Control Panel
Air Filter
Fuel Regulator
Oil Filter
Oil Dipstick
Exhaust Enclosure
Air Filter
Battery Compartment
Data Decal
Control Panel
Fuel Regulator
Battery Compartment
Oil Filter
6 Generac®Power Systems, Inc.
Section 1 General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
1.5 SPECIFICATIONS
1.5.1 GENERATOR
Model 04389 Model 04456 Model 04390
Rated Max. Continuous Power Capacity (Watts*) 6,000 NG/7,000 LP 10,000 NG/12,000 LP 13,000 NG/15,000 LP† Rated Voltage 120/240 120/240 120/240 Rated Max. Continuous Load Current (Amps)
120 Volts 50.0 NG/58.3 LP 83.3 NG/100.0 LP 108.3 NG/125.0 LP
240 Volts 25.0 NG/29.2 LP 41.6 NG/50.0 LP 54.2 NG/62.5 LP Main Line Circuit Breaker 30 Amp 50 Amp 60 Amp/70 Amp† Phase 1 1 1 Number of Rotor Poles 2 2 2 Rated AC Frequency 60 Hz 60 Hz 60 Hz Power Factor 1 1 1 Recommended Air Filter Generac Part # C8127 Generac Part # C8127 Generac Part # C8127 Battery Requirement Group 26/26R Group 26/26R Group 26/26R
12 Volts and 12 Volts and 12 Volts and
350 Cold-cranking 550 Cold- cranking 550 Cold- cranking
Amperes Minimum Amperes Minimum Amperes Minimum
Weight 452 Pounds 470 Pounds 487 Pounds
Output Sound Level @ 23 ft (7m) at full load 68 db (A) 70.5db (A) 71.5 db (A)
Normal Operating Range -20°F (-28.8°C) to 104°F (40°C)
* Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60° F).
† 15,000 watt with upgrade kit 04578-0. Kit includes power harnesses and 70 amp 2-pole circuit breaker .
1.5.2 ENGINE
Model 04389 Model 04456 Model 04390
Type of Engine GH-410 GT-760 GT-990 Number of Cylinders 1 2 2 Rated Horsepower 14.5 @ 3,600 rpm 26 @ 3,600 rpm 30 @ 3,600 rpm Displacement 410cc 760cc 992cc Cylinder Block Aluminum w/Cast Aluminum w/Cast Aluminum w/Cast
Iron Sleeve Iron Sleeve Iron Sleeve Valve Arrangement Overhead Valves Overhead Valves Overhead Valves Ignition System Solid-state w/Magneto Solid-state w/Magneto Solid- state w/Magneto Recommended Spark Plug RC12YC RC12YC RC12YC Spark Plug Gap 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) 0.76 mm (0.030 inch) Compression Ratio 8.6:1 9.5:1 9.5:1 Starter 12 Vdc 12 Vdc 12Vdc Oil Capacity Including Filter Approx. 1.5 Qts Approx. 1.7 Qts Approx. 1.7 Qts Recommended Oil Filter Generac Part # 70185 Generac Part # 70185 Generac Part # 70185 Recommended Air Filter Generac Part # 0C8127 Generac Part # 0C8127 Generac Part # 0C8127 Operating RPM 3,600 3,600 3,600
Generac®Power Systems, Inc. 7
1.6 FUEL REQUIREMENTS AND RECOMM ENDATIONS
With LP gas, use only the vapor withdrawal system. This type of system uses the vapors formed
above the liquid fuel in the storage tank. The engine has been fitted with a fuel carburetion
system that meets the specifications of the 1997 California Air Resources Board for tamper-proof dual fuel systems. The unit will run on natural gas or LP gas, but it has been factory set to run on natural gas. Should the primary fuel need to be changed to LP gas, the fuel system needs to be reconfigured. See Section 1.8 (Page 7) for instructions on reconfigura­tion of the fuel system.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask your fuel supplier for the Btu content of your fuel.
Fuel pressure for both natural gas and liquid propane set ups should be 11 inches to 14 inches
of water column (0.6 psi) at all load ranges.
NOTE:
A seperate gas line and regulator may be needed to assure proper gas pressure (11-14”) to the gen­erator. Low gas pressure can cause hard starting and could affect engine durability.
1.7 FUEL CONSUM PTION
*Natural gas is in cubic feet per hour. **LP is in gallons per hour/cubic feet per hour.
Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
1.8 RECONFIGU RI NG TH E FUEL SYSTEM
1.8.1 7 KW
To reconfigure the fuel system from NG to LP, follow these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose(s) from the outlet
port(s) of the demand regulator (Figure 1.4).
3. Disconnect wire #0 and wire #14 from the gas solenoid located on the top of the demand regu­lator.
4. Remove the demand regulator by rotating coun­terclockwise.
5. Remove the brass hose fitting(s) from the outlet port of the demand regulator.
6. Remove the brass metering jet(s) (loosen coun­terclockwise) from the housing port of the demand regulator located on the side of the regu­lator.
7. Install new LP metering jet(s) (tighten clockwise) in the outlet port of the demand regulator.
8. Refit the brass hose fittings to the outlet port of the demand regulator.
9. Reverse procedure steps 1-4 to reinstall demand regulator.
10. Reverse the procedure to convert back to natural gas.
Figure 1.4 – Demand Regulator
NOTE:
The natural gas adjustment screw is preset during installation and should not need any further adjustment.
1.8.2 V-TWIN
To reconfigure the fuel system from NG to LP, follow these steps:
NOTE:
The primary regulator for the propane supply is NOT INCLUDED with the generator. You must sup­ply a fuel pressure of 11 to 14 inches of water col­umn (0.6 psi) to the fuel inlet of the generator.
1. Locate the fuel demand regulator underneath the control panel.
2. Identify both fuel adjustment screws.
NOTE:
One adjustment screw can be accessed from the front of the unit and the second can be accessed from the back of the unit.
Section 1 General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Model # Nat. Gas (*) LP Vapor (**)
1/2 Load Full Load 1/2 Load Full Load
04389 74 105 0.91/33 1.21/44.1 04456 104 168 1.22/44.5 1.97/71.8 04390 148.5 240 1.73/63.2 2.80/102.3
FUEL HOSE
BRASS HOSE FITTING
HOUSING PORTS
FUEL HOSE
BRASS HOSE FITTING
FUEL JET
HOUSING PORTS
HOUSING PORTS
HOUSING PORTS
DANGER
NG FUEL SYSTEM
LP FUEL SYSTEM
3. The unit has been factory set to run on NG fuel. To reset the system to run on LP fuel, turn the two adjustment screws 1/2 turn clockwise. Use a large screwdriver to make this adjustment. Be sure to replace the plastic plug in the back of the enclosure once the adjustment has been made.
4. The fuel system will now allow the engine to run on LP fuel. It may be necessary to make minor adjustments to the set screw settings to achieve maximum power. If you experience problems with the unit producing maximum power, follow the procedure in Section 2.6 (Adjusting the Regulator).
1.9 LOCATION
1.9.1 GENERATOR
Install the generator set, in its protective enclosure, outdoors, where adequate cooling and ventilating air is always available. Consider these factors:
• Install the unit where air inlet and outlet openings
will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift­ing, you may need to consider using windbreak to protect the unit.
• Install the generator on high ground where water
levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator
for maintenance and servicing. A good rule is to allow 3 feet of space on all sides.
• Where strong prevailing winds blow from one
direction, face the generator air inlet openings to the prevailing winds.
• Install the generator as close as possible to the fuel
supply, to reduce the length of piping.
• Install the generator as close as possible to the
transfer switch. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REGULATE THE DIS­TANCE.
1.9.2 TR ANSF ER SWITCH
1.9.2.1 7 kW, 12 kW and 15 kW Units
The transfer switch shipped with this generator is enclosed in a NEMA 1 enclosure. This type of enclo- sure is intended for indoor use only. Follow these rules:
• Install the transfer switch indoors on a firm, stur-
dy supporting structure.
• T o prevent switch distortion, level the switch if nec-
essary. This can be done by placing washers between the switch enclosure and mounting sur­face.
• Never install the switch where water or any corro-
sive substance might drip onto the enclosure.
• Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and corrosive vapors.
1.10 BAT TERY INSTALLATION
Fill the battery with the proper electrolyte fluid if nec­essary and have the battery fully charged before installing it.
Before installing and connecting the battery, complete the following steps:
1. Set the generator's Auto/Off/Manual switch to
OFF.
2. Turn off utility power supply to the transfer
switch.
If the Auto/Off/Manual switch is not set to its OFF position, the generator can crank and start as soon as the battery cables are connected. If the utility power supply is not turned off, sparking can occur at the battery posts and cause an explosion.
Battery cables were factory connected at the genera­tor (Figure 1.5). Connect cables to battery posts as follows:
3. Connect the red battery cable (from starter con-
tactor) to the battery post indicated by a positive, POS or (+).
4. Connect the black battery cable (from frame
ground) to the battery post indicated by a nega­tive, NEG or (—).
NOTE:
Damage will result if battery connections are made in reverse.
Figure 1.5 – Battery Cable Connections
Section 1 General Information
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
8 Generac®Power Systems, Inc.
Generac®Power Systems, Inc. 9
NOTE:
Your generator is equipped with a battery trickle charger that is active when your unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent self-discharge. The trickle charger is designed to help extend the life of your battery by maintaining the battery when the unit is not running. The trickle charge feature cannot be used to recharge a discharged battery.
1.11 THE BATTERY
Servicing of the battery is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
When replacing the battery, use the following type of battery: Group 26/26R 12-volt battery with a rating of 350 cold-cranking amps minimum for 7 kW; 550 cold-cranking amps minimum for 12 and 15 kW at -
17.8º C (0º F) minimum. When using a maintenance­free battery, it is not necessary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in the “Service Schedule.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure the battery is correctly connected and terminals are tight. Observe battery polarity when connecting the battery to the generator set.
Do not dispose of the battery in a fire. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery; and
• Disconnect charging source prior to connecting or dis-
connecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive.
The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before touching the battery by first touching a grounded metal surface.
Be sure the Auto/Off/Manual switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off, or sparking may occur at the battery posts as you attach the cables and cause an explosion.
2.1 BEFORE I N ITIAL START-UP
Before starting, complete the following:
1. Set the generator's Auto/Off/Manual switch to the
OFF position.
2. Turn OFF the utility power supply to the transfer
switch using the means provided (such as the utility main line circuit breaker).
3. Check the engine crankcase oil level and, if nec-
essary, fill to the dipstick FULL mark with the recommended oil. Do not fill above the FULL mark.
4. Check the fuel supply. Gaseous fuel lines must
have been properly purged and leak tested in accordance with applicable fuel-gas codes. All fuel shutoff valves in the fuel supply lines must be open.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
!
Section 2 Post Installation Start-up and Adjustments
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
!
DANGER
!
!
10 Generac®Power Systems, Inc.
2.2 CHECK TRANSFER SWITCH OPERATION
Refer to Section 3.5 (Page 14), of the owner’s manual for manual operation procedures.
Do not attempt manual transfer switch opera­tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
2.3 ELECTRICAL CHECKS
Complete electrical checks as follows:
1. Turn on the utility power supply to the transfer
switch using the means provided (such as a utili­ty main line circuit breaker).
The transfer switch is now electrically “hot.” Contact with “hot” parts will result in extreme­ly hazardous and possibly fatal electrical shock. Proceed with caution.
2. Use an accurate AC voltmeter to check utility
power source voltage across terminals N1 and N2. Nominal line-to-line voltage should be 240 volts AC.
3. Check utility power source voltage across termi-
nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to ­neutral voltage should be 120 volts AC.
4. When certain that utility supply voltage is com-
patible with transfer switch and load circuit rat­ings, turn OFF the utility power supply to the transfer switch.
5. Set the generator's main circuit breaker to its
OFF (or open) position. Initial tests will be con­ducted at no-load condition.
6. On the generator panel, set the Auto/Off/Manual
switch to MANUAL. The engine should crank and start.
7. Let the engine warm up for about five minutes to
allow internal temperatures to stabilize. Then, set the generator’s main circuit breaker to its ON (or closed) position.
Proceed with caution! Generator power voltage is now supplied to the transfer switch. Contact with live transfer switch parts will result in dangerous and possibly fatal electrical shock.
8. Connect an accurate AC voltmeter and an AC fre­quency meter across transfer switch terminal lugs E1 and E2. Voltage should be 242-252 volts; frequency should read about 61-63 Hertz.
9. Connect the AC voltmeter test leads across termi­nal lug E1 and neutral; then across E2 and neu­tral. In both cases, voltage reading should be 121­126 volts AC.
10. Set the generator’s main circuit breaker to its OFF (or open) position. Let the engine run at no­load for a few minutes to stabilize internal engine generator temperatures.
11. Set the generator's Auto/Off/Manual switch to OFF. The engine should shut down.
NOTE:
It is important that you do not proceed until you are certain that generator AC voltage and frequen­cy are correct and within the stated limits. Generally, if both AC frequency and voltage are high or low, the engine governor requires adjust­ment. If frequency is correct, but voltage is high or low, the generator’s voltage regulator requires adjustment.
2.4 GENERATOR TESTS UNDER LOAD
To test the generator set with electrical loads applied, proceed as follows:
1. Set generator’s main circuit breaker to its OFF (or open) position.
2. Set the generator's Auto/Off/Manual switch to OFF.
3. Turn OFF the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
Do not attempt manual transfer switch opera­tion until all power voltage supplies to the transfer switch have been positively turned off. Failure to turn off all power voltage supplies will result in extremely hazardous and possibly fatal electrical shock.
4. Manually set the transfer switch to the STANDBY position, i.e., load terminals connected to the generator's E1/E2 terminals. The transfer switch operating lever should be down.
5. Set the generator's Auto/Off/Manual switch to MANUAL. The engine should crank and start immediately.
6. Let the engine stabilize and warm up for a few minutes.
7. Set the generator’s main circuit breaker to its ON (or closed) position. Loads are now powered by the standby generator.
Section 2 Post Installation Start-up and Adjustments
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
DANGER
DANGER
DANGER
Generac®Power Systems, Inc. 11
8. Turn ON electrical loads. Apply an electrical load equal to the full rated wattage/amperage capacity of the installed generator.
9. Connect an accurate AC frequency meter across terminal lugs E1 and E2. Voltage should be greater than 230 volts; frequency should be greater than 58 Hertz.
10. Let the generator run at full rated load for 20-30 minutes. Listen for unusual noises, vibration or other indications of abnormal operation. Check for oil leaks, evidence of overheating, etc.
11. When testing under load is complete, turn OFF electrical loads.
12. Set the generator's main circuit breakers to their OFF (or open) positions.
13. Let the engine run at no -load for a few minutes.
14. Set the Auto/Off/Manual switch to OFF. The engine should shut down.
2.5 CHECKING AUTOMATIC
OPERATION
To check the system for proper automatic operation, proceed as follows:
1. Check that the Auto/Off/Manual switch is set to OFF.
2. Manually set the transfer switch to the UTILITY position, i.e., load terminals connected to the util­ity power source side.
3. Turn ON the utility power supply to the transfer switch, using the means provided (such as a util­ity main line circuit breaker).
4. Set the Auto/Off/Manual switch to AUTO. The sys­tem is now ready for automatic operation.
5. Turn OFF the utility power supply to the transfer switch.
With the Auto/Off/Manual switch at AUTO, the engine should crank and start when the utility source power is turned OFF. After starting, the transfer switch should connect load circuits to the standby side. Let the system go through its entire automatic sequence of operation.
With the generator running and loads powered by generator AC output, turn ON the utility power sup­ply to the transfer switch. The following should occur:
• After about six seconds, the switch should transfer
loads back to the utility power source.
• About one minute after retransfer, the engine
should shut down.
2.6 ADJUSTING THE R EGUL ATOR (NATURAL GAS ONLY)
Although the generator has been factory set to pro­vide maximum power, it may be necessary in some areas to adjust this setting. Because natural gas has different BTU or power content across the country the engine may not perform as designed.
If you experience engine problems at high or full load conditions follow these steps. It will require a fre­quency meter to perform this procedure.
1. Turn off utility power to the main distribution
panel in the house. This can be done by switching the service main breaker to the off or open posi­tion.
2. Allow the generator to start and the transfer
switch to transfer load to emergency circuits.
3. Turn on appliances, lights, pumps, etc., that are
on the emergency circuits in an attempt to fully load the generator. Be cautious not to overload the generator. Use the following chart as a guide:
4. When full load has been achieved. Connect a fre-
quency meter to the output lugs of the generator’s main line circuit breaker.
5. The fuel regulator is fitted with one (7 kW), or two
(12 and 15 kW) adjustment screws. While watch­ing the frequency meter, slowly turn the adjust­ment screw clockwise or counterclockwise. Only limited adjustment is available between the set pins. Under no circumstances should any of the pins be removed (Figures 2.1 and 2.2).
Figure 2.1 — Dual Fuel Regulators
6. When the highest frequency is reached maximum
power has been set.
Section 2 Post Installation Start-up and Adjustments
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Unit 120 Volts 240 Volts
7 kW 50.0 amps 25.0 amps 12 kW 83.3 amps 41.6 amps 15 kW 108.3 amps 54.1 amps
Adjustment Screw
(Both sides)
V Twin
Set Pins
Adjustment Screw
(One Side Only)
410
Set Pins
12 Generac®Power Systems, Inc.
Figure 2.2 — Placement of Regulator
7. Turn utility power to the main distribution panel back on. This can be done by switching the serv­ice main breaker to the on or closed position. Allow the generator to shut down.
Do not make any unnecessary adjustments. Factory settings are correct for most applica­tions. However, when making adjustments, be careful to avoid overspeeding the engine.
If this procedure or equipment are not available to you, locate the Generac Guardian Dealer nearest you and they can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7 ENGINE GOVERNOR ADJ USTMENT
If both AC frequency and voltage are correspondingly high or low, adjust the engine governor as follows:
2.7.1 7 KW UNITS
1. Loosen the governor clamp bolt (Figures 2.3 on page 12).
2. Hold the governor lever at its wide open throttle position, and rotate the governor shaft clockwise as far as it will go. Then, tighten the governor lever clamp bolt to 70 inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up at no-load.
4. Connect an AC frequency meter across the gener­ators AC output leads.
5. Turn the speed adjust nut to obtain a frequency reading of 62 Hz.
6. When frequency is correct at no load, check the AC voltage reading. If voltage is incorrect, the volt­age regulator may require adjustment.
Figure 2.3 — Engine Governor Adjustment
2.7.2 12 KW AND 15 KW UNITS
1. Loosen governor clamp bolt (See Figure 2.3).
2. Completely remove the idle spring.
3. With governor arm at wide open throttle position, rotate governor shaft fully clockwise. Tighten clamp bolt to 84 inch-pounds.
4. Start unit and apply full load. Use full load speed adjust screw (Figure 2.4) to adjust frequency to 58 Hz.
5. Remove load, stop engine, loosen the idle adjust screw and reconnect the idle spring.
6. Using your hand, push the governor arm to the closed throttle position. Make sure the idle spring does not stretch at all.
7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the no­load idle speed to 62.5 Hz.
9. The governor is now set.
Figure 2.4 — Full Load Speed Adjust Screw
!
Section 3 Operation
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Adjustment Screw
Idle Spring
Governor Shaft
(Rotate Clockwise)
Governor Clamp Bolt
No Load Idle Adjustment Screw
Full Load Speed Adjust Screw
Generac®Power Systems, Inc. 13
Section 3 Operation
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
2.7.3 ADDITIONAL CORROSION PROTECTION
Periodically spray all engine linkage parts and brack­ets with corrosion inhibiting spray such as WD-40 or a comparable product.
2.8 VOLTAGE REGULATOR ADJUSTMENT
With the frequency between 61-62 Hertz, slowly turn the slotted potentiometer (Figure 2.5) until line volt­age reads 244-252 volts.
NOTE:
You must remove the access panel on top of the control panel to adjust the voltage regulator.
Figure 2.5 – Voltage Adjustment Potentiometer
NOTE:
The voltage regulator is housed above the genera­tor's control panel. The regulator maintains a volt­age in direct proportion to frequency at a 2-to-1 ratio. For example, at 62 Hertz, line-to-neutral voltage will be 124 volts.
3.1 BREAK-I N P ROCEDU RE
Once the unit has been installed and all electrical checks have been made, it is strongly recommended that the following “Break-in Procedure” be completed to ensure correct generator operation in the future.
1. Set the generator’s Auto/Off/Manual switch to
AUTO.
2. Turn OFF the utility power supply to the transfer
switch using the means provided (such as a utili­ty main line circuit breaker).
3. The unit will start, and the transfer switch will
transfer to standby.
4. Using the transfer switch’s built-in emergency
load center, turn on circuits to load the generator to approximately 25% load and run the unit for one hour.
5. Run the unit for one hour at 50 percent load.
6. Run the unit for one hour at 75 percent load.
7. Run the unit for one hour at 100 percent load.
8. Turn ON the utility power supply to the transfer switch, which will allow the transfer switch to transfer back to utility power. The unit will con­tinue to run for one minute and then shut down.
9. Allow the unit to cool.
10. Drain the oil and remove the oil filter . Replace the oil filter according to Section 4.4, “Changing the Oil Filter” (Page 16). Replace the oil with synthet­ic oil as recommended in Section 4.3, “Changing the Engine Oil” (Page 15).
11. The generator is now ready for service.
3.2 USING THE AUTO/OFF/MANUAL
SWITCH (FIGUR E 3.1)
3.2.1 “AUTO POSITION
Selecting this switch position activates fully automatic system operation. It also allows you to start and exercise the engine every seven days with the setting of the exer­cise timer (see Section 3.6, Page 14). This position also is used for remote starting, when it is set up.
3.2.2 OFF POSITION
This switch position shuts down the engine. This position also prevents automatic operation.
3.2.3 MANUAL” POSITION
Set the switch to MANUAL to crank and start the engine. Transfer to standby power will not occur unless there is a utility failure.
Figure 3.1 – Generator Control Panel
14 Generac®Power Systems, Inc.
Section 3 Operation
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a pre­set level or during the normal exercise cycle. To prevent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.
3.3 AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are
set to their “Utility” position, i.e., loads connected to the utility power source (Figure 3.2, Page 13).
2. Be sure that normal utility power source voltage
is available to transfer switch terminal lugs N1 and N2.
3. Set the generator’s Auto/Off/Manual switch to
AUTO.
4. Set the generator’s main circuit breaker to its ON
(or closed) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to “Sequence of Automatic Operation.”
3.4 SEQUENCE OF AUTOMATIC OPERATION
The generator’s control panel houses a control logic circuit board. This board constantly monitors utility power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power sup­ply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).
Upon restoration of utility source voltage above a pre­set level, generator circuit board action signals the transfer switch to transfer loads back to that power supply . After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A.Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 60 per­cent of the nominal supply voltage, the sensor energizes a 15-second timer.
• Once the timer has expired, the engine will crank and start.
B. Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about 10 seconds before the load is transferred to a standby source.
C. Standby Voltage Sensor
• This sensor monitors generator AC output volt­age. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D.Utility Voltage Pickup Sensor
• This sensor monitors utility power supply volt­age. When that voltage is restored above 80 per­cent of the nominal source voltage, a retransfer time delay starts timing.
E. Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15- second delay, circuit board action de-energizes transfer relay in the transfer switch.
• Retransfer to utility power source then occurs.
F. Engine Cool- down Timer
• When the load is transferred back to utility power source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the generator will then shut down.
3.5 MANUAL TRANSFER OP ER ATION
3.5.1 TR ANSF ER TO GENERATOR POWER SOURCE
T o start the generator and activate the transfer switch manually, proceed as follows:
1. Set the generator’s Auto/Off/Manual switch to OFF.
2. Set the generator’s main circuit breaker to its OFF (or open) position.
3. Turn OFF the utility power supply to the transfer switch using the means provided (such as a utility main line circuit breaker).
!
Generac®Power Systems, Inc. 15
Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.
4. Use the manual transfer handle inside the trans­fer switch to move the main contacts to their “Standby” position, i.e., loads connected to the standby power source (Figure 3.2).
Figure 3.2 – Manual Transfer Switch Operation
5. Turn ON the utility power supply to the transfer switch using the means provided (such as a utili­ty main line circuit breaker).
6. To crank and start the engine, set the Auto/Off/Manual switch to MANUAL.
7. Let the engine stabilize and warm up for a few minutes.
8. Set the generator’s main circuit breaker to its ON (or closed) position. The standby power source now powers the loads.
3.5.2 TRANSFER BACK T O UTILITY POWER
SOURCE
When utility power has been restored, you will want to transfer back to that source and shut down the generator. This can be accomplished as follows:
1. Set the generator’s main circuit breaker to its OFF (or open) position.
2. Let the engine run for a minute or two at no-load to stabilize the internal temperatures.
3. Set the generator’s Auto/Off/Manual switch to its OFF (or open) position. The engine should shut down.
4. Check that utility power supply to the transfer switch is turned OFF.
Do not attempt to activate the transfer switch manually until all power voltage supplies to the switch have been positively turned off. Failure to turn off all power voltage supplies may result in extremely hazardous and possibly fatal electrical shock.
5. Use the manual transfer handle inside the trans­fer switch to move the main contacts back to their “Utility” position, i.e., loads connected to the util­ity power source (Figure 3.2 on page 13).
6. Turn ON the utility power supply to the transfer switch using the means provided.
7. Set the system to automatic operation as outlined in “Automatic Transfer Operation,” Section 3.3 (Page 12).
3.6 SETTING THE EXERCISE TI M ER
Your generator is equipped with an exercise timer. Once it is set, the generator will start and exercise once every seven days, on the day of the week and at the time of day you complete the following sequence. During this exercise period, the unit runs for approx­imately 12 minutes and then shuts down. Transfer of loads to the generator output does not occur during the exercise cycle.
A switch on the control panel (see Figure 3.1, Page
12) allows you to select the day and time for system
exercise. To select the desired day and time of day, you must perform the following sequence at that time.
1. Verify that the Auto/Off/Manual switch is set to AUTO.
2. Hold down the set timer switch until the genera­tor starts (approximately 10 seconds) and then release.
3. The generator will start and run for approximately 12 minutes and then shut down on its own. The exerciser will then be set to run at that time of day every week.
NOTE:
The exerciser will only work in the AUTO mode and will not work unless this procedure is performed. The exerciser will need to be reset every time the 12-volt battery is disconnected and then reconnected. The exerciser WILL NOT work if dip switch 2 (Remote Not Auto) is ON.
Section 3 Operation
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
DANGER
DANGER
16 Generac®Power Systems, Inc.
3.7 PROTECTION SYSTEMS
3.7.1 LOW OIL PR ESSURE SWITCH
This switch (Figure 3.3) has normally closed contacts that are held open by engine oil pressure during crank­ing and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the Auto/Off/Manual switch must be turned to OFF and then back to AUTO.
3.7.2 HIGH TEMP ERATURE SWITCH
This switch’s (Figure 3.3) contacts close if the tem­perature should exceed approximately 140º C (284º F), initiating an engine shutdown. Your generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
Figure 3.3 – Low Oil Pressure and
High Temperature Switches
3.7.3 OVERCRANK
This feature prevents the generator from damaging itself when it continually attempts to start and anoth­er problem, such as no fuel supply, prevents it from starting. The unit will crank and rest for a preset time limit. Then, it will stop cranking, and the LED will light indicating an overcrank failure. The Auto/Off/Manual switch will need to be set to OFF and then back to AUTO to reset the generator control board.
NOTE:
If the fault is not repaired, the overcrank feature will continue to activate.
3.7.3.1 Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds Approximately 90 seconds total
3.7.4 OVERSPEED
This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit. This protection also prevents the gener­ator from supplying an output that could potentially damage appliances connected to the generator cir­cuit. Contact your nearest Generac/Guardian Authorized Dealer if this failure occurs.
4.1 FUSE
The generator panel’s 15 amp fuse (Figure 4.1) protects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, you cannot crank or start the engine. You should replace the fuse using only an identical 15-amp replacement.
The generator panel’s 5 amp fuse protects the battery charge circuit against overload. If the fuse element has melted open, you will not have battery charging capa­bility. You should replace the fuse using only an identi­cal 5 amp replacement. T o remove fuse, push cap down and rotate counterclockwise.
Figure 4.1 – Generator Control Panel
4.2 CHECKING THE ENGI N E OIL LEVEL
For oil capacities, see “Specifications,” Section 1.5 (Page 6). For engine oil recommendations, see Section 4.3.1. To check the engine oil level, proceed as follows (Figure 4.2):
1. Start the generator by moving the Auto/
Off/Manual switch to the MANUAL position. Allow it to run for a short while and then shut it down by moving the switch to the OFF position.
2. Remove the dipstick and wipe it dry with a
clean cloth.
3. Install the dipstick; then, remove it again. The oil
level should be at the dipstick “Full” mark. If nec­essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Low Oil Switch
High Temp Switch
L
o
o
s
e
n
Oil Drain Hose
Oil Filter
Generac®Power Systems, Inc. 17
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
4. Install the dipstick.
5. Reset the Auto/Off/Manual switch to its original position.
Figure 4.2 — Oil Dipstick and Fill, 7 kW
Figure 4.3 — Oil Dipstick and Fill,
12 kW and 15 kW
4.3 CHANGING THE ENGI N E OI L
4.3.1 ENGI N E OI L RECOMMEN DATIONS
Use oil of American Petroleum Institute (API) Service Class SG, SH or SJ. Use all season SAE 5W-30 Synthetic oil. Organic break-in oil is required before using synthetic oil.
NOTE:
The unit is supplied with “break-in” oil. See the “Break-in Procedure,” Section 3.1 (Page 12), for the first required oil change.
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended oil may result in an engine failure.
4.3.2 OI L CHANGE P ROCEDU RE
To change the oil, proceed as follows:
1. Run the engine until it is thoroughly warmed up then shut OFF the engine.
2. Immediately after the engine shuts OFF, pull the oil drain hose (Figure 4.4) free of its retaining clip. Remove the cap from the hose and drain the oil into a suitable container.
Figure 4.4 – Oil Drain Hose and Filter
3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip.
4. Refill with the proper recommended oil (see Section 4.3.1). See Section 1.5.2 (Page 6) for oil capacities.
4.4 CHANGING THE OI L F I LTER
Change the engine oil filter as follows:
1. With the oil drained, remove the old oil filter by turning it counterclockwise.
2. Apply a light coating of clean engine oil to the gas­ket of the new filter. See Section 1.5.1 (P age 6) for recommended filter.
3. Screw the new filter on by hand until its gasket lightly contacts the oil filter adapter. Then, tighten the filter an additional 3/4 to one turn (Figure 4.4).
4. Refill with the proper recommended oil (see Section 4.3.1, Page 15). See Section 1.5.2 (P age 6) for oil capacities.
5. Start the engine and check for leaks.
!
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
!
Oil Dipstick and Fill
Oil Dipstick
L
o
o
s
e
n
Oil Drain Hose
Oil Filter
Oil Fill
18 Generac®Power Systems, Inc.
4.5 CHANGING THE ENGI N E AIR CLEANER
4.5.1 7 KW, 12 KW AND 15 KW GENERATORS
See Figures 1.2 and 1.3, (Page 5), for the location of your air cleaner. Use the following procedure (Figure
4.6):
1. Turn the two screws counterclockwise to loosen.
2. Remove the cover and air filter.
3. Wipe away dust or debris from inside of the air box and around edges.
4. Install the new air cleaner into the air box.
5. Install the cover. Turn the two cover screws clock­wise to tighten.
See the “Service Schedule,” Section 4.11 (Page 19) for air cleaner maintenance. See Section 1.5.1 (Page 6) for air filter replacement part number.
Figure 4.6 — 7 kW, Engine Air Cleaner Location
Figure 4.7 — 12 kW and 15 kW Engine
Air Cleaner
4.6 SPARK PLUG(S)
Reset the spark plug(s) gap or replace the spark plug(s) as necessary. See Section 4.11 (Page 19) for maintenance requirements.
1. Clean the area around the base of the spark plug(s) to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and commercial solvent. Do not blast the spark plug(s) to clean.
2. Remove the spark plug(s) and check the condi­tion. Replace the spark plug(s) if worn or if reuse is questionable. See Section 4.11 (Page 20) for recommended inspection.
3. Check the spark plug gap using a wire feeler gauge. Adjust the gap to 0.76 mm (0.030 inch) for 7 kW and 0.50 mm (0.020 inch) for 12/15 kW by carefully bending the ground electrode (Figure
4.8).
Figure 4.8 – Setting the Spark Plug Gap
4.7 BAT TERY MAINTENANCE
The battery should be inspected per the “Service Schedule,” Section 4.11 (Page 19). The following pro­cedure should be followed for inspection:
1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONL Y. DO NOT USE TAP W A TER IN BATTERIES.
3. Have the state of charge and condition checked. This should be done with an automotive-type bat­tery hydrometer.
Do not dispose of the battery in a fire. The battery is capable of exploding.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
SET PLUG GAP AT 0.76 mm
(0.030 inch)
Air Cleaner
Fuel
Regulator
Screw
Cover
Filter
DANGER
Generac®Power Systems, Inc. 19
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery; and
• Disconnect charging source prior to connecting or dis­connecting battery terminals.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically con­ductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead-acid batteries present a risk of fire because they generate hydrogen gas. The following procedures are to be followed:
• DO NOT SMOKE when near the battery;
• DO NOT cause flame or spark in battery area; and
• Discharge static electricity from your body before touching the battery by first touching a grounded metal surface.
Be sure the Auto/Off/Manual switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the gen­erator can crank and start as soon as the battery cables are connected.
Be sure the utility power supply is turned off, or sparking may occur at the battery posts as you attach the cables and cause an explosion.
4.8 ADJUSTING VALVE CLEARANCE
After the first 50 hours of operation, you should adjust the valve clearance in the engine.
Important: If you feel uncomfortable about doing this
procedure or you don't have the proper tools, please contact your Generac Authorized dealer for service assistance. This is a very important step to insure longest life for your engine.
To adjust valve clearance:
• Make sure the engine is at room temperature.
• Make sure that the spark plug wire is removed from the spark plug and out of the way.
• Remove the four screws attaching the valve cover with a #2 or #3 phillips screwdriver.
• Make sure the piston is at Top Dead Center (TDC) of
its compression stroke (both valves closed). To get the piston at TDC, remove the intake screen at the front of the engine to gain access to the flywheel nut. Use a large socket and socket wrench to rotate the nut and hence the engine. While watching the piston through the spark plug hole. The piston should move up and down. The piston is at TDC when it is up as high as it can go.
• Loosen the rocker jam nut. Use an 10mm allen
wrench to turn the pivot ball stud while checking clear­ance between the rocker arm and the valve stem with a feeler gauge. Correct clearance is 0.002-0.004 inch (0.05-0.1 mm).
NOTE:
You must hold the rocker arm jam nut in place as you turn the pivot ball stud.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change.
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
!
!
!
20 Generac®Power Systems, Inc.
Figure 4.10 - Valve Clearance Adjustment
• Install new valve cover gasket.
• Re-attach the valve cover.
NOTE:
Start all four screws before tightening or you will not be able to get all the screws in place. Make sure the valve cover gasket is in place.
• Re-attach the spark plug wire to the spark plug.
• Repeat the process for the other cylinder.
4.9 COOLING SYSTEM
Air inlet and outlet openings in the generator compart­ment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to quickly shut down. (See Figure 4.9 for vent locations.)
Figure 4.9 – Cooling Vent Locations
The exhaust from this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
The maximum ambient temperature for your generator is 48.9° C (104° F).
4.10 ATTENTION AFTER SUBMERSION
If the generator has been submerged in water, it MUST NOT be started and operated. Following any submersion in water, have a Generac/Guardian Authorized Dealer thoroughly clean and dry the generator.
4.11 CORROSION PROTECTION
Periodically wash and wax the enclosure using automo­tive type products. Frequent washing is recommended in salt water/coastal areas. Spray engine linkages with a light oil such as WD-40.
!
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Pivot Ball
Jam Nut
Stud
Rocker
Arm
Valve Stem
Generac®Power Systems, Inc. 21
4.12 OUT OF SERVICE PROCEDUR E
4.12.1 REMOVAL FROM SERVICE
If you cannot exercise the generator every seven days, and it is to be out of service longer than 90 days, pre­pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. Once the unit has shut down, it will signal a low oil fault.
4. Set the Auto/Off/Manual switch to OFF and turn off the utility power to the transfer switch.
5. While the engine is still warm from running, drain the oil completely. Refill the crankcase with oil. See ”Engine Oil Recommendations,” Section 4.3.1 (Page
15).
6. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
7. Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).
8. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
9. Clean and wipe the entire generator.
4.12.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Verify that utility power is turned off and that the Auto/Off/Manual switch is set to OFF.
2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommended oil is used in the engine (see Section 4.3.1, Page 15). If necessary, drain and refill with the proper oil.
3. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT USE T AP WATER IN THE BA TTERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery. See “Specifications,” Section 1.5 (Page 6), for type and size.
4. Clean and wipe the entire generator.
5. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incor­rectly.
6. Open the fuel shutoff valve.
7. Start the unit by moving the Auto/Off/Manual switch to MANUAL. Allow the unit to warm up thoroughly.
8. Stop the unit and set the Auto/Off/Manual switch to AUTO.
9. Turn on the utility power to the transfer switch.
10. Your generator is now ready for service.
NOTE:
If the battery was dead or disconnected, you must reset the exercise timer.
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
22 Generac®Power Systems, Inc.
Section 4 Maintenance
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
4.13 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by your nearest Generac/Guardian Authorized Dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action Inspect Change Clean W = Weekly R = Replace as Necessary M = Monthly * = Notify Dealer Y = Yearly
if Repair is Needed. H = Hours
FUEL
Fuel lines and connections* XM
LUBRICATION
Oil level XM Oil X AFTER BREAK-IN,
EVERY 100 H AND Y
Oil filter X AFTER BREAK-IN,
EVERY 200 H AND Y
COOLING
Enclosure louvers XXW
BATTERY
Remove corrosion, XXM
ensure dryness
Clean and tighten
XXM
battery terminals
Check charge state X R EVERY 6 M Electrolyte level X R EVERY 6 M
(unsealed batteries only)*
ENGINE AND MOUNTING
Air cleaner X R 100 H AND Y Spark plug(s) X R 100 H AND Y
GENERAL CONDITION
Vibration, Noise, Leakage, XM Temperature*
COMPLETE TUNE-UP* TO BE COMPLETED BY A GENERAC/ Y
GUARDIAN AUTHORIZED DEALER
Generac®Power Systems, Inc. 23
Section 5 Troubleshooting
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
5.1 TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
The engine will not crank. 1. Fuse blown 1. Replace fuse.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary.
3. Defective starter contactor (7 kW) 3. *
4. Defective starter motor 4. *
5. Dead Battery 5. Charge or replace battery.
The engine cranks but 1. Out of fuel 1. Replenish fuel. will not start. 2. Defective fuel solenoid (FS) 2. *
3. Open #14 wire from 3. * engine control board
4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s).
5. Valve lash out of adjustment. 5. Reset valve lash.
The engine starts hard 1. Air cleaner 1. Check, replace air cleaner. and runs rough. plugged or damaged
2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s).
The Auto/Off/Manual switch 1. Defective switch 1. * is set to OFF, but the engine 2. Auto/Off/Manual switch 2. *
continues to run. wired incorrectly
3. Defective control board 3. *
There is no AC output from 1. Main line circuit breaker open 1. Reset circuit breaker the generator. to ON (or closed).
2. Generator internal failure 2. *
There is no transfer to 1. Defective transfer switch coil 1. * standby after utility 2. Defective transfer relay 2. * source failure. 3. Transfer relay circuit open 3. *
4. Defective control logic board 4. *
Unit consumes large 1. Break-in procedure 1. * amounts of oil. not followed (see Section 2.1)
*Contact your nearest Generac/Guardian Authorized Dealer for assistance.
24 Generac®Power Systems, Inc.
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 12 & 15 kW – Drawing No. 0C7830-B
Generac®Power Systems, Inc. 25
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Wiring Diagram – 12 & 15 kW – Drawing No. 0C7830-B
26 Generac®Power Systems, Inc.
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 12 & 15 kW – Drawing No. 0C7836-B
Generac®Power Systems, Inc. 27
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Electrical Schematic – 12 & 15 kW – Drawing No. 0C7836-B
79
AB
46
13
28 Generac®Power Systems, Inc.
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Wiring Diagram – 7 kW – Drawing No. 0D5700-B
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - MAIN OUTPUT BREAKER CB2 - CIRCUIT BREAKER, ALTERNATOR EXCITATION D - DIODE
DSW - PCB MOUNTED DIP SWITCH FS - FUEL SOLENOID F1 - FUSE 15 AMP F2 - FUSE 5 AMP GRD - CONTROL PANEL GROUND HTO - HIGH OIL TEMPERATURE SWITCH HM - HOUR METER
IC - INLINE CONNECTOR
ICT - INTERCONNECTION TERMINALS
IM - IGNITION MODULE LOP - LOW OIL PRESSURE SWITCH
RAR - REMOTE ALARM RELAY SP - SPARK PLUG SW1 - AUTO / OFF / MANUAL SWITCH SW2 - SET EXERCISE SWITCH SM - STARTER MOTOR TB - INSULATED TERMINAL BLOCK TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
SP
IM
85
HTO
86
LOP
ENGINE WIRING
D
IC
IC
3 2
BATTERY
1
CHARGER
14
FS
14
0
0
(UTILITY)
14
2 1
225A
224A
13A
0
IC
TB
14
0
18
86
0
13
0
56
SS
6 5
85
4 3
2
13
1
C1
56
0
14
18
56
86
85
CONTROL
PRINTED CIRCUIT BOARD
0
14
351
14
56
86
53421
J2
J1
BLACK
CUSTOMER SUPPLIED
-
12V
BATTERY
RED
16
+
SM
DSW
123
ON
ON - INDICATES
1 - 20 Vac Sense Transformer 2 - Remote Not Auto 3 - 50 Hz Operation 4 - SPARE
4
Generac®Power Systems, Inc. 29
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Wiring Diagram – 7 kW – Drawing No. 0D5700-B
224A
225
224
N2
N1
225
N2
224
0
225
224
N1
13
0
351
225A
224A
TX
77
225A 224A
14
13A
162
VOLTAGE
REGULATOR
0
0
66A
N2
N1
15B
229
0
BCR
1 3
4 6
7 9
A B
11 22
4 0 6
4
CONTROL PANEL BOX
225A
66
0
77
11
22
4
0
162
4
BA
RAR
CB2
162
2
4
66
0
77
6
66A
0
0
4
2
6
11
22
55
0
55
GRD
211
0
194
23
210
11 10
9 8 7 6 5 4
0
3 2
1
C2
CLOSEST TO BEARING
BA
4 0
2
11
6
22
178
STATOR
55
66A
77
66
11
44
33
22
4
21
711 10 9 8 5643
1617 15 14 13 12
194
17 15
224
14
5623
18
14
66A
0
239
15A
14
225
13
13A
351
15A
0
13
F2 F1
0
15
13
-+
HM
17
15
AUTO
MANUAL
N2
N1
183
351
CUSTOMER CONNECTION
178
239
0
SW1
SW2
CB1
OUTPUT TO TRANSFER
SWITCH CONTACTOR
44
11
OFF
240V GENERATOR
22
33
ICT
NEUTRAL CONNECTION
183
23
N2
N1
194
C - REMOTE START
TRANSFER RELAY COIL
TRANSFER RELAY COIL
UTILITY FROM T/SW
UTILITY FROM T/SW
210
211
178
NO - REMOTE ALARM
C - REMOTE ALARM
NO - REMOTE START
J2
14
16 17
15
11
13
12
10
J1
30 Generac®Power Systems, Inc.
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Electrical Schematic – 7 kW – Drawing No. 0D5701-A
11
22
3
2 1
BATTERY
CHARGER
13A
11
0
225B
224B
2 1
13A
13A
225A
F2
13
F1
BCR
77
0
22
ELECTRONIC
VOLTAGE
REGULATOR
11
22
4
C2-10
4
0
6
BA
FIELD
0
162
CB2
C2-8
C2-7
2
DPE WINDING
(STATOR)
DIAGRAM KEY
BA - BRUSH ASSEMBLY BCR - BATTERY CHARGE RELAY CB1 - CIRCUIT BREAKER, MAIN OUTPUT CB2 - CIRCUIT BREAKER, ALT. EXCITATION D - DIODE FS - FUEL SOLENOID F1 - FUSE 15 AMP F2 - FUSE 5 AMP HTO - HIGH OIL TEMPERATURE SWITCH HM - HOUR RUN METER
IM - IGNITION MODULE LOP - LOW OIL PRESSURE SWITCH
RAR - REMOTE ALARM RELAY SC - STARTER CONTACTER SP - SPARK PLUG SW1 - AUTO / OFF / MANUAL SWITCH SW2 - SET EXERCISE SWITCH SM - STARTER MOTOR TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)
C2-1
6
BATTERY CHARGE
WINDING
C2-4
55
0
0
C2-9
C2-11
0
77
66
0
ENGINE RUN
WINDING
(STATOR)
4
C2-2
HTO
C1-4
C2-3
66A
CONTROL
PRINTED CIRCUIT
BOARD
66
0
85
221 53 4
J2
0
15B
SW2
229351
J1
0
14
15
0
0
LOP
14
C1-3
15B
86
4
225
224
14
66A
86
66A
23
239
194
15A
56
225
23
194
66A
18
17
15
0
224
10
11 12 13 14 15 16 17
4
1
2
3 4 5 6 7
14
8 9
Generac®Power Systems, Inc. 31
Section 6 Electrical Data
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Electrical Schematic – 7 kW – Drawing No. 0D5701-A
225
15
224
224A
13
17
56VA
1VA
229
11
TX
N2
22
N1
17
15B
0
194
239
229
23
15
15B
15A
229
C2-6
N1
RAR
C2-5
178
N2
11
183
SW1
239
15
194
23
22
POWER WINDING
(STATOR)
11
211 210 178 183 194
23
N2
N1
33
44
CB1
CUSTOMER
CONNECTIONS
NEUTRAL
120V
120V
240V
239
15A
15
C1-1
C1-5
13
14
56
SC FS HM
000
C1-6
0
18
17
0
0
C1-2
14 14
D
IM
SP
SM
SC
RED
BLACK
BATTERY
12V
CUSTOMER SUPPLIED
32 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Enclosure – Drawing No. 0D3416-K
26
35
2
47
46
43
20
49
43
49
49
82
51
80
A
51
25
33
8
34
87
35
76
72
86
82
23
48
5
49
52
18
44
72
48
47
51
31
45
50
11 49
51
91
63
92
50
38
70
49
49
58
69
50
66
71
93
71
67
49
59
13
69
63
75
30
42
14
55
17
51
29
28
88
54
35
25
93
3
39
10
68
40
41
73
52
A
47
19
62
51
91
15
27
57
56
58
1
21
9
35
49
90
7
44
6
12
60
61
68
16
64
65
48 51
22
89
85
44
77
84
78
81
79
80
46
74
37
24
36
32
4
Generac®Power Systems, Inc. 33
ITEM PART NO. QTY. DESCRIPTION
1 0C6140 1 ASSEMBLY, ENCLOSURE BASE (12KW / 15KW)
0D1901 1 ASSEMBLY, ENCLOSURE BASE (7KW) 2 0C6735 2 SUPPORT, ROOF FOLDING 3 0C7061 1 ENCLOSURE, FRONT 4 0C7062 1 ENCLOSURE, EXHAUST SIDE (12KW / 15KW)
0C7062A 1 ENCLOSURE, EXHAUST SIDE (7KW) 5 0C7063 1 ENCLOSURE, SIDE & BACK (12KW / 15KW)
0C7063A 1 ENCLOSURE, SIDE & BACK (7KW)
0C7063B 1 ENCLOSURE, SIDE & BACK (16KW) 6 0C7064 1 ENCLOSURE, ROOF 7 0C7065 1 PANEL, ALTERNATOR DIVIDER (12KW / 15KW)
0C7065A 1 PANEL, ALTERNATOR DIVIDER (7KW) 8 0C8101A 1 PANEL, MUFFLER BOX SIDE (12KW / 15KW)
0C8861 1 PANEL, MUFFLER BOX SIDE (7KW) 9 0C8101B 1 COVER, MUFFLER BOX (12KW / 15KW)
0C8862 1 COVER, MUFFLER BOX (7KW)
10 0C8283 1 GASKET, DOOR SEAL 11 0C8284A 1 FOAM, BACK ENCLOSURE 12 0C8284B 1 FOAM, ROOF ENCLOSURE 13 0C8284C 1 FOAM, FRONT ENCLOSURE 14 0C8285 1 BRACKET, BATTERY SUPPORT (12KW / 15KW) 15 0C8899A 1 PAD, 24"X48" WITH MOUNTING HOLES 16 0D1128 1 PANEL, ENGINE DIVIDER (12KW / 15KW)
0D1128A 1 PANEL, ENGINE DIVIDER (7KW)
17 0D1605 1 BAFFLE, INTAKE (12KW / 15KW)
0D1605A 1 BAFFLE, INTAKE (7KW)
18 0D1606 1 HOUSING, FAN (12KW / 15KW)
0D5264 1 BAFFLE, EXHAUST (7KW)
19 0D1839 2 BRACKET, TOP SUPPORT 20 0D1840 2 BRACKET, BOTTOM SUPPORT 21 0D2425 1 DUCT, BASE AIR (12KW / 15KW) 22 0D2588 1 GASKET, FRONT DIVIDER 23 0D2676 1 COVER, FRONT EXHAUST ENCLOSURE 24 0D2677 1 COVER, BACK EXHAUST ENCLOSURE 25 0D2979B 2 CLOTH, HARDWARE 266.7mm x 146mm
(12KW / 15KW)
0D2979B 3 CLOTH, HARDWARE 266.7mm x 146mm
(7KW) 26 0D2979C 1 CLOTH, HARDWARE 543mm x 146mm 27 0D2979D 1 CLOTH, HARDWARE 266.7mm x 387.4mm
0D2979E 1 CLOTH, HARDWARE (7KW)
28 0D3057A 1 FOAM, FRONT INTAKE BAFFLE (12KW / 15KW)
0D3058A 1 FOAM, FRONT INTAKE BAFFLE (7KW) 29 0D3057B 1 FOAM, TOP INTAKE BAFFLE (12KW / 15KW) 30 0D3057C 1 FOAM, BACK INTAKE BAFFLE (12KW / 15KW)
0D3058C 1 FOAM, BACK INTAKE BAFFLE (7KW) 31 0D3057D 1 FOAM, BACK ENCL.STRIP (12KW / 15KW) 32 0D3059A 1 FOAM, EXHAUST SIDE ENCLOSURE END 33 0D3059B 1 FOAM, EXHAUST SIDE ENCLOSURE FRONT 34 0D3059C 1 FOAM, EXHAUST FAN HOUSING
(12KW / 15KW)
35 0D7176 24 WASHER, SELF LOCKING (12KW / 15KW)
22 WASHER, SELF LOCKING (7KW) 36 0D3059D 1 FOAM, FRONT EXHAUST ENCLOSURE COVER 37 0D3059E 1 FOAM, BACK EXHAUST ENCLOSURE COVER 38 0C7781 2 DOOR, PAWL 39 0D3037 1 LATCH, QUARTER TURN LOCKING 40 0D2537 1 HINGE, LIFT OFF, TYPE A PIN 41 0D2538 1 HINGE, LIFT OFF, TYPE B PIN 42 0D3037A 1 LATCH, QUARTER TURN NON-LOCKING 43 0A2115 4 WASHER NYLON .250"
ITEM PART NO. QTY. DESCRIPTION
44 022097 9 WASHER LOCK M6-1/4" 45 022473 4 WASHER FLAT ¼" ZINC 46 036261 14 RIVET POP .125 X .129-.133/#30 47 047411 12 SCREW HHC M6-1.0 X 16 G8.8 48 043116 5 SCREW HHC M6-1.0 X 12 G8.8 (12KW / 15KW)
043116 6 SCREW HHC M6-1.0 X 12 G8.8 (7KW) 49 0D3700 18 NUT, LOCKING FLANGE M6-1.0 50 083512 11 SCREW TAPTITE M8-1.20 X 16 BP 51 090388 34 SCREW TAPTITE M6-1.0 X 12 BP
(12KW / 15KW)
22 SCREW TAPTITE M6-1.0 X 12 BP (7KW) 52 092120 2 NUT LOCK TRIC M6 X 1.0 Y/ZNC 54 0D3167 1 GASKET, BATTERY SUPPORT BRACKET 55 0A3328 1 PLUG, PLASTIC 0.593 HEYCO 1675 56 055414 1 LUG SLDLSS #2-#8X17/64 CU 57 092079 1 SCREW TAPTITE M6-1.0X25 BP 58 0A1658 2 L/WASH SPECIAL ¼ 59 0C2937 1 BRACKET, BATTERY HOLD DOWN (7KW) 60 086729 1 CONTACTOR, STARTER (7KW) 61 0388040AJ0 1 CABLE, #6 RED BATTERY 38.5" 62 022127 2 NUT HEX 1/4-20 STEEL (7KW) 63 022129 4 WASHER LOCK 5/16 (12KW / /15KW)
022129 5 WASHER LOCK 5/16 (7KW) 64 074908 8 SCREW TAPTITE M5-0.8 X 10 BP 65 0D2346 1 HARNESS, ENGINE (12KW / 15KW)
0D2345 1 HARNESS, ENGINE (7KW) 66 023484F 1 BUSHING, SNAP SB-1000-12 67 022142 1 SCREW HHC 5/16-18 X 3/4 G5 (7KW) 68 0A7836 2 RIVET,1/8" X 0.126" - 0.375" LSH POP 69 0A8475 2 L/WASH SPECIAL #10 70 0912970069 1 ASSEMBLY, ROOF/DOOR GROUND WIRE 71 0912970070 2 ASSEMBLY, ROOF/DOOR GROUND WIRE 72 055450 2 PLUG PLASTIC 1.375 (12KW / 15KW) 73 0D2023 10.5 GASKET, CLIP-ON SELF GRIPPING 74 0D3701 1 PLATE, "HOT" 75 0D3472 1 GROMMET 2.75 X 1/16 76 0C8742 1 EXTERNAL CONNECTION BOX 77 0C8911 1 POWER BLOCK 78 0D3338 1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (12KW / 15KW)
0D3419 1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (7KW)
0D3928 1 HARNESS GENERATOR TO EXTERNAL
CONNECTION BOX (16KW) 79 036937 2 SCREW PPHM #10-32 X 1 80 022152 5 WASHER LOCK #10 81 023897 2 WASHER FLAT #10 ZINC 82 022158 5 NUT HEX #10-32 STEEL 83 0D3031 1 FUEL LINE, 3/4"OUTDOOR (NOT SHOWN) 84 026850 1 WASHER SHAKPROOF EXT 1/4 STEEL 85 049813 1 NUT HEX M6-1.0 G8 YELLOW CHROME 86 0D2537A 1 HINGE, LIFT OFF, TYPE A KNUCKLE 87 0D2538A 1 HINGE, LIFT OFF, TYPE B KNUCKLE 88 047411 2 SCREW HHC M6-1.0 X 16 G8.8 89 0A2311 1 SCREW SWAGE 1/4-20 X 1 90 043107 4 SCREW HHC M8-1.25 X 25 91 022145 8 WASHER FLAT 5/16 92 045771 4 NUT HEX M8-1.25 93 0C3906 2 SELF-ALIGN SCREW M6 HH
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Enclosure – Drawing No. 0D3416-K
34 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Control Panel – Drawing No. 0D3418-D
17
41
22
37
8,9
8,32
38
24
27
10
16
4
17
23
23
31
15
14
16
29 28
12
17
40
42
44
20
45
31
25
23
16 34
43
33
1
14
15
39
36
21
15
35
29 28
14 30
29 28
3
27
38
7
6
23
16
31
2
21
35
19
4
17
11
13
5
Generac®Power Systems, Inc. 35
ITEM PART NO. QTY. DESCRIPTION
1 0A9947E 1 CIRCUIT BREAKER 30 X 2 240V
SQD QOU230 (7KW)
0A9947F 1 CIRCUIT BREAKER 50 X 2 240V
SQD QOU245 (12KW)
0A9947C 1 CIRCUIT BREAKER 60 X 2 240V
SQD QOU260 (13KW) 2 0A18010SRV 1 ASSEMBLY, BATTERY CHARGER ENGINE 3 0830490SRV 1 ASSEMBLY, POTTED REGULATOR W/FIN 4 0C2174 2 RELAY, 12V 25A SPST (12KW / 15KW)
0C2174 1 RELAY, 12V 25A SPST (7KW) 5 075210A 1 TERMINAL BLOCK 6 0D3062 4 HEX. STAND-OFF #6-32 X 3/8" 7 0C62110SRV 1 ASSEMBLY, HOME STANDBY CONTROLLER
(12KW / 15KW)
0C6211ASRV 1 ASSEMBLY, HOME STANDBY CONTROLLER
(7KW) 8 032300 2 HOLDER, FUSE 9 022676 1 FUSE, 15 AMP X AGC15
10 033873 1 SWITCH, ROCKER 11 0A2769 1 LUG, GROUND 8-TABS 12 023484E 1 SNAP BUSHING 13 075476 2 SCREW PPHM M4-0.7 X 16 14 022264 6 WASHER LOCK M4 15 051715 6 NUT HEX M4-0.7 G8 YELLOW CHROME 16 043182 8 WASHER LOCK M3 (12KW / 15KW)
043182 6 WASHER LOCK M3 (7KW)
17 043181 8 SCREW PHM M3-0.5 X 10 (12KW / 15KW)
043181 6 SCREW PHM M3-0.5 X 10 (7KW) 18 0D7618 1 DECAL, CONTROL PANEL (NOT SHOWN) 19 054502 1 CIRCUIT BREAKER 3 X 1 ETA 46-500-P
(12KW / 15KW)
053623 1 CIRCUIT BREAKER 2.5 X 1 ETA 46-500-P
(7KW)
20 0C6002A 1 CONTROL, PANEL BOTTOM (12KW / 15KW)
0D2985 1 CONTROL, PANEL BOTTOM (7KW)
ITEM PART NO. QTY. DESCRIPTION
21 075235 4 SCREW HHC M5-0.8 X 30 G8.8 22 0D5240 1 SWITCH, SPDT (ON)-ON N/D 23 051714 8 NUT HEX M3-0.5 G8 YELLOW CHROME 24 0C1457 1 HOURMETER 25 036261 2 RIVET POP .125 X .129-.133/#30 26 0C7756 1 HARNESS, CONTROL PANEL WIRE
(NOT SHOWN) (12KW / 15KW)
0D5831 1 HARNESS, CONTROL PANEL WIRE
(NOT SHOWN) (7KW)
27 074908 4 SCREW TAPTITE, M5-0.8 X 10 BP
(12KW / 15KW) 28 049226 6 WASHER LOCK M5 29 051716 6 NUT HEX M5-0.8 G8 YELLOW CHROME 30 0C3910 1 TRANSFORMER 240/16V 1VA&56VA 31 031879 6 WASHER FLAT #4 ZINC (12KW / 15KW)
031879 4 WASHER FLAT #4 ZINC (7KW) 32 099727 1 FUSE 5A X AGC5 33 0C3701 1 DIN RAIL ASSEMBLY 34 063617 1 RELAY PANEL 12VDC DPDT 10A@240VA 35 075475 4 SCREW PPHM M4-0.7 X 10 36 022985 2 WASHER FLAT #6 ZINC 37 0C6002C 1 COVER, CONTROL PANEL COMPONENT
(12KW / 15KW)
0D2988 1 COVER, CONTROL PANEL COMPONENT
(7KW) 38 092036 8 SCREW PPHMS/LW 6-32 X 1/4L 39 045770 2 SCREW HHC M5-0.8 X 10 G8.8 40 0C7171 1 COVER, CONTROL PANEL (12KW / 15KW)
0D2989 1 COVER, CONTROL PANEL (7KW) 41 0D3700 10 NUT FLANGE M6-1.0 NYLOK 42 0912970069 1 ASSEMBLY, ROOF/DOOR GROUND WIRE 43 0A2311 1 SCREW SWAGE 1/4-20 X 1 Z/YC 44 0A1658 1 L/WASH SPECIAL 1/4" 45 022473 1 WASHER FLAT 1/4 ZINC
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Control Panel – Drawing No. 0D3418-D
36 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW GTS Load Center Assembly – Drawing No. 0D3997-C
17
18
24
12
37
10
14
31
7
9
4
29
1
13
15
36
30
9
27
22
16
23
6
11
5
4
3
2
39
19 25
40
22
16
21
23
26
38
33
8
32
34
35
34
Generac®Power Systems, Inc. 37
ITEM PART NO. QTY. DESCRIPTION
1 0D4801 1 BOX GTS LOAD CENTER 2 0D4800 1 COVER, 8 POSITION GTS LOAD CENTER 3 0C2237 1 TRANSFER SWITCH HOME STANDBY 100A2P250V 4 074908 6 SCREW TAPTITE M5-0.8 X 10 BP 5 024912 1 SCREW TAPTITE 1/4-20 X 5/8 BP 6 0A1658 1 LOCK WASHER, SPECIAL-1/4" 7 063617 1 RELAY PANEL 12VDC DPDT 10A@240VA 8 0D3030A 1 BASE, MOUNTING 8 CIRCUIT 125A/240V
9 0A1495 4 SCREW TAPTITE M4-0.7X10 BP 10 0A1661 2 RIVET POP .156 X .160-.164/#20 11 022473 1 WASHER FLAT 1/4 ZINC 12 0D3094 1 HARNESS,GTS TO MAIN PANEL 13 0D4684A 1 HARNESS ADAPTER PLATE 14 0D3319 1 PANEL-SUB BREAKER BASE 15 056326 1 FT TRIM VINYL BLACK 1/8GP 16 022152 6 WASHER LOCK #10 17 087680 1 NUT WING M6-1.0 18 077441 1 HANDLE, TRANSFER SWITCH HOME STANDBY 19 063378 4 HOLDER CABLE TIE 21 074138 2 LUG DIS QK NI-S 10X45 DEG BR/T 22 036932 6 SCREW PPHM #10-32 X 1/4 23 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 24 048850 1 BLOCK TERMINAL 20A 5 X 6 X 1100V 25 028739 4 TIE WRAP 3.9" X .10" NAT'L UL 26 038150 2 WASHER FLAT #8 ZINC 27 0D3191 1 COVER, RELAY & TERM BLOCK 28 0D3088 1 WIRE HARNESS,GTS LOAD CENTER (NOT SHOWN FOR CLARITY) 29 073591 2 FUSE HOLDER 30 073590A 2 ASSEMBLY FUSE 5A X BUSS HLDR73591 31 040213B 4 PCB SUPPORT SNAP-IN 1-3/8" 32 0C8037 1 CIRCT BRK 20 X 1 HOM120 33 075475 2 SCREW PPHM M4-0.7 X 10 34 0C8036 5 CIRCT BRK 15 X 1 HOM115 35 0C8035 1 CIRCT BRK 30 X 2 HOM230 36 0D3320 1 COVER - HARNESS ENTRY 37 0D4802 1 HARNESS, GTS TO EXT CONN BOX 38 022264 2 WASHER LOCK M4 39 0A7215 4 SCREW SW 1/4-20X5/8 N WA JS500 40 0A2110 4 SCREW SWAGE 1/4-20 X 1/2 ZINC
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
7 kW GTS Load Center Assembly – Drawing No. 0D3997-C
38 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW GTS Load Center Assembly – Drawing No. 0D3996-B
12
17
18
24
42
37
10
14
31
7
9
4
29
1
13
15
36
30
9
27
22
16
23
6
11
5
4
3
2
39
19 25
40
22
16
21
23
26
38
41
8
35
33
32
34
34
Generac®Power Systems, Inc. 39
ITEM PART NO. QTY. DESCRIPTION
1 0D3086 1 BOX GTS LOAD CENTER
2 0D3092 1 COVER, 12 POSITION GTS LOAD CENTER
3 0C2237 1 TRANSFER SWITCH HOME STANDBY 100A2P250V
4 074908 6 SCREW TAPTITE M5-0.8 X 10 BP
5 024912 1 SCREW TAPTITE 1/4-20 X 5/8 BP
6 0A1658 1 LOCK WASHER, SPECIAL-1/4"
7 063617 1 RELAY PANEL 12VDC DPDT 10A@240VA
8 0D3030 1 BASE, MOUNTING 12 CIRCUIT 125A/240V
9 0A1495 4 SCREW TAPTITE M4-0.7X10 BP 10 0A1661 2 RIVET POP .156 X .160-.164/#20 11 022473 1 WASHER FLAT 1/4 ZINC 12 055450 1 PLUG PLASTIC 1.375 (10KW / 12KW / 13KW)
025034 1 PLUG STEEL 1.0625 STMPSN 3811 (14KW / 15KW / 16KW) 13 0D4684 1 HARNESS ADAPTER PLATE 14 0D3319 1 PANEL-SUB BREAKER BASE 15 056326 1 FT TRIM VINYL BLACK 1/8GP 16 022152 6 WASHER LOCK #10 17 087680 1 NUT WING M6-1.0 18 077441 1 HANDLE, TRANSFER SWITCH HOME STANDBY 19 063378 4 HOLDER CABLE TIE 21 074138 2 LUG DIS QK NI-S 10X45 DEG BR/T 22 036932 6 SCREW PPHM #10-32 X 1/4 23 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 24 048850 1 BLOCK TERMINAL 20A 5 X 6 X 1100V 25 028739 4 TIE WRAP 3.9" X .10" NAT'L UL 26 038150 2 WASHER FLAT #8 ZINC 27 0D3191 1 COVER, RELAY & TERM BLOCK 28 0D3088 1 WIRE HARNESS,GTS LOAD CENTER (NOT SHOWN FOR CLARITY) 29 073591 2 FUSE HOLDER 30 073590A 2 ASSEMBLY FUSE 5A X BUSS HLDR73591 31 040213B 4 PCB SUPPORT SNAP-IN 1-3/8" 32 0C8037 3 CIRCT BRK 20 X 1 HOM120 33 0D3190 1 CIRCT BRK 20 X 2 HOM220 34 0C8036 5 CIRCT BRK 15 X 1 HOM115 35 0C8035 1 CIRCT BRK 30 X 2 HOM230 36 0D3320 1 COVER - HARNESS ENTRY 37 0D3093 1 HARNESS, GTS TO EXT CONN BOX (10KW / 12KW / 13KW)
0D3926 1 HARNESS, GTS LD CTR TO EXT CONN BOX (14KW / 15KW / 16KW) 38 022264 2 WASHER LOCK M4 39 0A7215 4 SCREW SW 1/4-20X5/8 N WA JS500 40 0A2110 4 SCREW SWAGE 1/4-20 X 1/2 ZINC 41 075475 2 SCREW PPHM M4-0.7 X 10 42 0D3094 1 HARNESS,GTS TO MAIN PANEL
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
12 kW and 15 kW GTS Load Center Assembly – Drawing No. 0D3996-B
40 Generac®Power Systems, Inc.
38
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Eng ine – Drawing No. 0D3415-A Part 1
KIT CONTAINS ITEMS
3 39
37
34
36
35
34
22
65
2, 5, 19, 20, 39, 40, 47, 63, 92, 141
66
8, 11, 12, 13 4, 5, 6
67
16, 17, 18
68
48, 49, 50, 51, 52, 53, 54, 55, 56, 58, 59, 61
69
7, 48, 49, 50, 51, 52, 53, 54, 55, 56, 58, 59
70
27, 28, 29
71
3, 32, 33, 34, 35, 36, 40, 71
72
40
41
42
45
44
29
43
46
28
27
47
48
3
49
31
50
26
32
51
33
3
21
12
13
9
10
25
11
24
23
30
16
15
14
8
53
54
55
56
18
17
19
20
7
6
5
4
61
3
2
52
62
63
1
64
57
58
59
60
Generac®Power Systems, Inc. 41
ITEM PART NO. QTY. DESCRIPTION
1 0C5729 1 ASSEMBLY, CRANKCASE HOUSING
WITH SLEEVE 2 0C3008 1 SEAL, 38 I.D.CRANKSHAFT 3 090388 8 SCREW, TAPTITE M6-1.0 X 12 BP 4 0C5372 1 ASSEMBLY, BREATHER 5 0C3005 1 GASKET, BREATHER COVER 6 0C3003 3 SEPARATOR, OIL BREATHER 7 0C2231 1 ASSEMBLY, HEAD #1 G&S 8 071983 4 RETAINER, PISTON PIN 20 9 0C2981 1 ROCKER, COVER NO OIL FILL
10 045761A 4 STUD M8-1.25/10MM X 30 G5 ZINC 11 0C5848 2 PISTON, HC 12 021533 2 SET, PISTON RING 90MM 13 071980 2 PIN PISTON D20 14 0D4041 1 ASSEMBLY, CAMSHAFT & GEAR 15 0C2983 1 SHAFT, GOVERNOR 16 0C2985 1 ROLLER BEARING, GOVERNOR 17 0D4042 1 ASSEMBLY,GOVERNOR GEAR 18 0A7811 1 SPOOL, GOVERNOR MACHINED 19 0C2977 1 GASKET, CRANK CASE 20 0C5943 1 SEAL, OIL PASSAGE 21 0D4040E 1 ASSEMBLY, CRANKSHAFT HORIZONTAL
DIRECT DRIVE (GT-990)
21 0D4122E 1 ASSEMBLY, CRANKSHAFT AND GEAR HOR-
IZONTAL DIRECT DRIVE (GT-760)
22 0C2969 2 ASSEMBLY, CONNECTING ROD (GT-990) 22 0D3105 1 ASSEMBLY, CONNECTING ROD (GT-760) 23 0D2157 2 SCREW SHC M6-1.0 X 50 G8.8 24 0C5313 1 SCREEN, OIL PICKUP 25 0D4123 1 ASSEMBLY, OIL PUMP 26 078699E 2 SLEEVE, SEAMED DOWEL 10 DIA. 27 0C3011 2 COVER, OIL RELIEF 28 0C3009 2 SPRING, OIL RELIEF 29 0C3010 2 BALL, 1/2D OIL RELIEF 30 093873 2 WASHER, LOCK RIB M6 31 0C5315 1 GEROTOR, OUTER 32 0C5998 1 CLAMP, OIL TUBE 33 0D1667 1 ARM, GOVERNOR 34 0C2991 2 E-RING, GOVERNOR ARM 35 0C2988 1 THRUST WASHER, GOVERNOR
ITEM PART NO. QTY. DESCRIPTION
36 0C2992 1 BUSHING, GOVERNOR LOWER 37 0C3971C 1 ASSEMBLY, DIPSTICK WITH HANDLE 38 0C5305 1 TUBE, DIPSTICK 39 0C3027 1 O-RING, OIL CLR 40 0C3007 1 SEAL, 42 I.D.CRANKSHAFT 41 0C5731 1 ASSEMBLY, HOUSING COVER
WITH SLEEVE 42 0C3006 9 SCREW, HHFC M10-1.5 X 55 43 0C8566 8 SCREW HHFC M6-1.0 X 20 44 093064 1 ASSEMBLY, OIL FILL CAP 45 0C8808 2 HOOK, LIFTING 46 0C2982 1 ROCKER, COVER WITH OIL FILL 47 0C2979 2 GASKET, VALVE COVER 48 086515 8 KEEPER, V ALVE SPRING 49 0D2274 4 RETAINER, VALVE SPRING 50 0D3867 4 SPRING, V ALVE 51 078672 2 SEAL, VALVE STEM D7 52 0C5371 4 WASHER, VAL VE SPRING 53 072694 4 STUD, D20 PIVOT BALL 54 083907 4 ARM, SOLID ROCKER 55 0D3998 4 NUT, HEX M8-1.0 G8 YELLOW CHROM 56 0C2235 2 PLATE, PUSH ROD GUIDE 57 0C2976 12 SCREW HHFC M8-1.25 X 65 58 086516 2 VALVE, EXHAUST 59 0C2229 2 VALVE, INTAKE 60 083897 4 TAPPET, SOLID 61 0C2231A 1 ASSEMBLY, HEAD #2 G&S 62 088396C 4 PUSHROD, 139.6 VERTICAL 63 0C2978 2 GASKET, HEAD 64 043790A 1 BARBED ELBOW 90 3/8NPT X 3/8 L0CKTITE 65 0D4010 1 KIT GASKET 66 0D4011 1 KIT-PISTON RINGS 67 0D4012 1 KIT BREATHER ASSEMBLY 68 0D4013 1 KIT GOVERNOR ASSEMBLY 69 0D4014 1 KIT HEAD ASSEMBLY CYLINDER 1 70 0D4014A 1 KIT HEAD ASSEMBLY CYLINDER 2 71 0D4015 1 KIT OIL RELIEF 72 0D4016 1 KIT GEAR COVER
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
GT-990/760 Eng ine – Drawing No. 0D3415-A Part 1
42 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GT-990/760 Eng ine – Drawing No. 0D3415-A Part 2
81
82
80
78
73
79
117
75
76
95
74
77
94
130
138
115
114
116
118
96
122
121
119
97
124
124
98
99
125
123
125
120
137
126
136
131
139
127
132
133
140 135
134
128
129
83
86
85
84
92
93
96
87
88
89
88
90
97
91
98
112
101
102
107
108
103
104
109
105
110
106
100
100
113
111
Generac®Power Systems, Inc. 43
ITEM PART NO. QTY. DESCRIPTION
73 0C5136A 2 KNOB, AIR CLEANER 74 0C3024 1 COVER, AIRBOX NG/LP 75 0C3040 1 PRE-CLEANER, 76 0C8127 1 ELEMENT, AIR CLEANER 77 0C7720 1 MIXER / AIRBOX, ASSEMBLY 78 0D2595 4 SCREW SHOULDER (8MM) M6-1.0 X 18 79 0D4417 4 WASHER,RUBBER 1/4" X 1/8" THICK 80 0C3025 1 SWITCH, OIL PRESS 81 0D3083 1 ASSEMBLY, OIL DRAIN HOSE 82 0C7292 1 NIPPLE, 3/4"-16 UNF 83 070185 1 FILTER, OIL D 69 X 64 LONG 84 075281 1 SWITCH, THERMAL 284F 85 0C1085 2 SCREW PPHM M3-0.5 X 8 86 043182 2 WASHER LOCK M3 87 035461A 2 BARBED STR 1/4NPT X 3/8
WITH VIBRA SEAL 88 040173 4 CLAMP HOSE #5.5 .62 - .62 89 0C9806 2 HOSE, 3/8" I.D.X 6" LONG 90 0C3026 1 COOLER, OIL 91 0C9764 4 PLASTITE,1/4-15 X 3/4 92 0C3043 2 GASKET, MANIFOLD / PORT 93 0C7694 1 MANIFOLD INTAKE CYLINDER 2 94 0C7693 1 MANIFOLD INTAKE CYLINDER 1 95 0C3041 2 SLEEVE, RUBBER 96 070008 4 WASHER FLAT M8 SS 97 070006 4 WASHER LOCK M8 SSTL 98 040976 4 SCREW SHC M8-1.25 X 20 G12.9 99 0C3016A 1 PLATE, BACKING GT990 WITH OIL COOL
100 0C1069 23 SCREW TAPTITE M6-1.0X8
YELLOW CHROME
101 085011 1 INSULATOR ASSEMBLY IGNITION 102 0C3725B 1 FLYWHEEL ASSEMBLY 103 0C3031 1 FAN, NYLON 104 0C3032 1 PLATE, FAN 105 0A5992 2 WASHER SHAKEPROOF INT M8 SS 106 051754 2 SCREW HHC M8-1.25 X 12 G8.8 107 0C3033 1 WASHER, M5
ITEM PART NO. QTY. DESCRIPTION
108 0C3034 1 NUT,HEX M24 109 0C8549 1 SNORKEL, AIR INTAKE 110 0C3022A 1 HOUSING, BLOWER NG COOLER 111 0D1131 1 GUARD, FAN 112 045756 4 SCREW TAPTITE M6-1X10
YELLOW CHROME 113 0C9763 4 NUT, GROMMET 1/4 PLUG 114 0C3036 1 HOSE, BREATHER 115 0C8558 1 CLAMP, MANIFOLD 116 0C8564 1 PLASTITE,#12-16X 3/4 117 0C3018 1 WRAPPER, UPPER CYLINDER 1 118 0C3019 1 WRAPPER, LOWER CYLINDER 1 119 0D1142A 1 WRAPPER, LOWER CYLINDER 2 120 0D1143 1 WRAPPER, UPPER CYLINDER 2 121 066849B 2 SCREW TAPTITE M5-0.8 X 8 BP 122 0C3053 1 ASSEMBLY, GROUND WIRE 123 0C3052 2 ASSEMBLY, IGNITION COIL 124 022097 4 WASHER LOCK M6-1/4 125 092079 4 SCREW TAPTITE M6-1.0 X 25 BP 126 0C3017 1 STARTER 127 0D4529 2 SPARKPLUG 128 022129 2 WASHER LOCK M8-5/16 129 061906 2 SCREW HHC M8-1.25 X 85 G8.8 130 082774 1 KEY, WOODRFF 4 X 19D 131 052859 1 NUT HEX LOCK M10-1.50 132 0C8468 1 SPRING, ANTI-LASH 133 0C3048 1 ROD, GOVERNOR CONTROL 134 0D3754 1 ASSEMBLY, GOVERNOR LEVER 135 0D3742 1 SPRING, GOVERNOR 136 0C8482 1 ASSEMBLY, GOVERNOR ADJUSTER 137 0D2576 1 SCREW SHC M10-1.5 X 70 G10.9 138 033469 1 SPACER .22 X .37 X .25 CAD PLT 139 0D3743 1 SPRING, GOVERNOR IDLE 140 0D3705 1 ASSEMBLY, GOVERNOR ADJUSTER
BRACKET 141 0C2993 1 SEAL, GOVERNOR SHAFT (NOT SHOWN)
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
GT-990/760 Eng ine – Drawing No. 0D3415-A Part 2
44 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 7 kW Generator – Drawing No. 0D3504-B
36
45
30
47
49
50
11
23
34
10
25
19
35
32
44
24
48
34
16
29
18
28
26
10
28
27
46
34
6
51
7
39
21
38
5
52
33
31
12
13
8 4
9
31
37
32
17
28
31
40
31
38
1
2
3
22
14
20
15
41
19
42
10
43
30
17
32
28
31
32
Generac®Power Systems, Inc. 45
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
7 kW Generator – Drawing No. 0D3504-B
ITEM PART NO. QTY. DESCRIPTION
1 0C6934 1 ADAPTOR, ENGINE 2 0C9935H 1 STATOR 3 0C9934H 1 ROTOR 4 0C6043A 1 CARRIER, REAR BEARING 5 0C8096 1 FAN, 8" CURVED BLADE 6 0C9593 1 MUFFLER 7 0D3220 1 TAIL PIPE, MUFFLER 8 0C8860 1 PANEL, MUFFLER BASE
9 031971 1 BEARING #6205-2NSE-C3 10 0C3168 3 5/16 SPECIAL L/WASH 11 056147 1 BOLT ROTOR HHCS 5/16"-24 X 13-1/2" G5 12 0D1847 4 BOLT STATOR IHHC M8-1.25 x 305mm 13 0C7038C 1 BRACKET, ALTERNATOR MOUNTING 14 0D1647 1 DUCT, ALTERNATOR AIR 15 0D2558 1 GASKET, ALTERNATOR AIR DUCT 16 0C7038B 1 BRACKET, ENGINE MOUNTING 17 0C7758 4 RUBBER MOUNT 18 0388050AE0 1 CABLE, #6 40" BLACK BATTERY 19 0C2417A 1 EARTH STRAP 3/8X 3/8 20 082121C 1 CLIP-J VINYL COAT .625 ID 21 066386 1 ASSEMBLY BRUSH HOLDER 22 029451 1.8 FT TAPE ELEC UL FOAM 1/8 X 1/2 23 049451 1 WASHER FLAT .406ID X 1.62OD 24 022237 4 WASHER LOCK 3/8 25 022511 4 BOLT HHC 3/8-16 X 1-1/4 G5 26 022131 4 WASHER FLAT 3/8 ZINC 27 039287 4 SCREW HHC M8-1.25 X 45 G8.8 28 022145 14 WASHER FLAT 5/16 ZINC 29 049820 4 NUT LOCK HEX M8-1.25 NYL INSRT 30 090388 3 SCREW TAP M6-1.0X12 BP 31 022129 13 WASHER LOCK M8-5/16 32 022259 8 NUT HEX 5/16-18 STEEL 33 059637 2 SCREW TAPTITE 3/8-16X 3/4" BP 34 048031K 3 BAND, HOSE CLAMP 35.05 DIA. 35 0C9592 1 BELLOWS 36 057822 2 CLAMP HOSE #8 .53 - 1.00 37 040976 2 SCREW SHC M8-1.25 X 20 G12.9 38 0C2824 3 SCREW TAPR #10-32 X 9/16 39 025145 1 U-BOLT 5/16"-18 X 1.25" W/ SADDLE 40 090239 1 GASKET, EXHAUST 41 0C6989 1 STINGER, ENGINE AIR IN 42 0D1214 1 BASE, AIR CLEANER 43 0C8127 1 ELEMENT, AIR CLEANER 44 0C3024 1 COVER, AIR CLEANER NG/LP 45 0D2273 1 TUBE, 1.25"O.D.x 20Ga. x 12.125" LONG 46 055934N 1 CLAMP VINYL 1.31 X .281 Z 47 074994 1.25 FT HOSE 1\2ID LP GAS 48 0C5136A 2 KNOB, AIR CLEANER 49 074906 4 SCREW TAPTITE M6-1 X 20 BP 50 022473 4 WASHER FLAT 1/4 ZINC 51 0D4662 6 SCREW HHTT M8-1.2 X 20 BP 52 0C8290 1 GASKET, PANEL
46 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators 12 kW and 15 kW Generator – Drawing No. 0D3417-A
11
23
16
36
36
35
29
28
29
26
18
10
28
27
6
34
7
39
21
8
13
4
9
38
5
24
12
33
31
37
32
17
28
31
40
38
1
2
3
24
25
20
14
22
15
17
10
19
32
30
32
19
10
28
31
32
Generac®Power Systems, Inc. 47
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
12 kW and 15 kW Generator – Drawing No. 0D3417-A
ITEM PART NO. QTY. DESCRIPTION
1 0C6934 1 ADAPTOR, ENGINE
2 0C7930 1 STATOR 12KW
0D2359 STATOR 15KW
3 0C7944 1 ROTOR 12KW
0D2356 ROTOR 15KW 4 0C6043 1 CARRIER, REAR BEARING 5 0D2336 1 FAN, 12" CURVED BLADE 6 0C6042 1 MUFFLER 7 0D3220 1 TAIL PIPE, MUFFLER 8 0C8101 1 PANEL, MUFFLER BASE 9 056482 1 BEARING 1.1811-2.8346
10 0C3168 3 5/16 SPECIAL LOCK WASHER 11 0D1838 1 BOLT, IHHC 3/8"-24 x 15.50" 12 0D1846 4 BOLT, IHHC M8-1.25 x 345mm 13 0C7038 1 BRACKET, ALTERNATOR MOUNTING 14 0D1609 1 DUCT, ALTERNATOR AIR 15 0D2559 1 GASKET, ALTERNATOR AIR DUCT 16 0C7038A 1 BRACKET, ENGINE MOUNTING 17 0C7758 4 RUBBER MOUNT 18 0388050AD0 1 CABLE, #6 48" BLACK BATTERY 19 0C2417A 1 EARTH STRAP 3/8X 3/8 20 082121C 1 CLIP-J, VYNL COAT 0.625" ID 21 066386 1 ASSEMBLY BRUSH HOLDER 22 029451 2.6 FT TAPE ELEC UL FOAM 1/8 X 1/2 23 049451 1 WASHER FLAT .406ID X 1.62OD 24 022237 5 WASHER LOCK 3/8 25 022511 4 SCREW HHC 3/8-16 X 1-1/4 G5 26 022131 4 WASHER FLAT 3/8 ZINC 27 039288 4 SCREW HHC M8-1.25 x 55 G8.8 28 022145 14 WASHER FLAT 5/16 ZINC 29 049820 4 NUT LOCK HEX M8-1.25 NYL INSERT 30 045756 2 SCREW T APTITE M6-1.0X10 YC 31 022129 10 WASHER LOCK M8-5/16 32 022259 8 NUT HEX 5/16-18 STEEL 33 059637 2 SCREW TAPTITE 3/8-16 X 3/4 CZ 34 083512 4 SCREW TAPTITE M8-1.20 X 16 YC 35 074994 2.83 FT HOSE RES 1/2 LP GAS 36 057822 4 CLAMP HOSE #8 .53 - 1.00 37 052858 4 NUT LOCK M8 38 0C2824 3 SCREW TAP-R #10-32 x 9/16 39 025145 1 U-BOLT 5/16"-18 X 1.25" WITH SADDLE 40 0C4138 2 GASKET, EXHAUST PORT
48 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0D3539-B Part 1
9
8
11
7
3
4
10
42
5
2
1
52
16
6
54
1
49
40
41
22
21
13
11
12
51
46
14
32
53
26
44
48
23
38
47
24
25
25
15
50
35
17
31
30
29
28
27
37
36
34
20
19
18
43
39
33
45
Generac®Power Systems, Inc. 49
ITEM PART NO. QTY. DESCRIPTION
1 071978 1 ASSEMBLY, CONNECTING ROD 2 071980 1 PIN, PISTON D20 3 021533 1 SET, PISTON RING 90MM 4 0C5848 1 PISTON, HC 5 071983 2 RETAINER, PISTON PIN 20 6 0D4287 1 ASSEMBLY, CRANKSHAFT
GH410 SMALL TAPER 7 0A7628 1 ARM, GOVERNOR RC45 8 078658 1 PIN, "R" GOVERNOR ARM 9 078659 2 WASHER, GOVERNOR ARM THRUST
10 088261E 1 CRANKCASE, SUBASSEMBLY
WITH PLUGS GH410
11 072655 2 SEAL, 35 I.D.CRANKSHAFT 12 0A7975 1 ASSEMBLY, GOVERNOR GEAR 13 078645 1 C-RING, GOVERNOR GEAR RETAINER 14 0A7811 1 SPOOL, GOVERNOR- MACHINE 15 0A9877 1 ASSEMBLY, CAMSHAFT & GEAR 16 076701 1 GASKET , CRANKCASE 17 021713B 1 GASKET, HEAD 410 18 078691 1 COVER, OIL PRESSURE RELIEF 19 0A5771 1 SPRING, OIL RELIEF 360 20 0A5776 1 BALL, DIA 11/32 PRESSURE RELIEF 21 076361 1 WASHER, THRUST GOVERNOR GEAR 22 0A8898D 1 ASSEMBLY, COVER, GEAR TOP
CHECK / FILL
23 0D2274 2 RETAINER, VALVE SPRING 24 0C4391 2 VALVE SPRING LF 25 086025 1 SET,GEROTOR 12 THK 26 0C7393 1 BALANCER 27 021714 1 ASSEMBLY,CYLINDER HEAD
SEATS & GUIDES
ITEM PART NO. QTY. DESCRIPTION
28 086516 1 VALVE, EXHAUST 29 086517 1 VALVE, INTAKE 30 088396B 2 PUSH ROD 31 083897 2 TAPPET 32 077158 1 ASSEMBLY, SCREEN OIL PICK-UP 33 0C3150 1 GASKET, ROCKER COVER 410 34 072694 2 STUD, D20 PIVOT BALL 35 083907 2 ROCKER ARM 36 072696 2 NUT, JAM (ROCKER ARM) 37 078694 1 PLATE, PUSH ROD GUIDE 38 021742 4 SCREW, HHFL M10-1.5 X 105 39 0C3972 1 ASSEMBLY, ROCKER COVER BREATHER 40 076329 1 PLUG, OIL FILL PLASTIC 41 086254 1 O-RING 17.8 I.D.x 2.4 42 0D4788 1 PLUG, STANDARD PIPE 3/8 STEEL
SQUARE HEAD 43 074908 1 SCREW, TAPTITE M5-0.8 X 10 BP 44 086515 4 KEEPER, V ALVE SPRING 45 078606 4 SCREW & LOCKWASHER M6-1 X 12 46 0A1442 8 SCREW, HHFC M8-1.25 X 42 47 078672 1 SEAL, VALVE STEM D7 48 089673 2 WASHER, VAL VE SPRING 49 0B2104 1 WASHER, LARGE SPRING 50 078699C 2 DOWEL, SEAMED SLEEVE 51 0A7627 1 SHAFT, GOVERNOR RC55 52 043790A 1 BARBED ELBOW 90 3/8NPT X 3/8
LOCKTITE 53 088590 1 DOWEL DIA 12 X 18L 54 078699B 1 DOWEL, SLEEVE SEAMED 12 DIA.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
GN410 Engine – Drawing No. 0D3539-B Part 1
50 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators GN410 Engine – Drawing No. 0D3539-B Part 2
6
14
38
37
35
18
36
26
1
27
28
6
31
32
30
16
15
34
35
18
33
10
9
12
11
25
8
4
2
19
18
17
40
3
6
41
29
6
39
6
7
13
6
5
23
24
22
44
43
42
21
20
Generac®Power Systems, Inc. 51
ITEM PART NO. QTY. DESCRIPTION
1 0C1069 5 SCREW , TAPTITE M6-1.0X8
YELLOW CHROME 2 0D2922 1 HOUSING, BLOWER 3 0C8435 1 TUBE, DIPSTICK 4 0C9997 1 GUARD, FAN 5 088434 1 WRAPPER, BOTTOM 6 045756 11 SCREW, TAPTITE M6-1X10
YELLOW CHROME 7 088433B 1 WRAPPER, TOP 8 0C3794 1 BUMPER, NEOPRENE 9 021544 1 STARTER ASSEMBLY, EATON
10 040976 2 SCREW, SHC M8-1.25 X 20 G12.9 11 022129 2 WASHER, LOCK M8-5/16 12 0C2458A 1 BACKPLATE, L/F D/F 13 083512 1 SCREW, TAPTITE M8-1.2 X 16 YC 14 0D1401 1 BREATHER TUBE 15 091039 1 GASKET, INTAKE ADAPTER 16 0C9619 1 ASSEMBLY, PLASTIC CARB 17 049811 2 WASHER, FLAT M6 18 022097 4 WASHER, LOCK M6-1/4 19 040945 2 SCREW, SHC M6-1.0 X 20 G12.9 20 086999 1 GASKET,OIL FILTR ADAPTER 21 0D5667A 1 ADAPTER, OIL FILTER 22 049821 2 SCREW, SHC M8-1.25 X 30 G12.9
ITEM PART NO. QTY. DESCRIPTION
23 099236 1 SWITCH, OIL 8.0 PSI 24 070185 1 FILTER, OIL DIA. 69 X 64 LG 25 082774 1 KEY, WOODRFF 4 X 19D 26 091222ESRV 1 FLYWHEEL WITH RING GEAR 32DEG. 27 067198N 1 WASHER,BELV-20 X 2.2 28 067890 1 NUT, HEX - FLYWHEEL 29 072347 1 SPARKPLUG 30 072734 1 ASSEMBLY,GOVERNOR LEVER 12 HP 31 072735 1 ROD,GOVERNOR CONTROL. 32 0C3978 1 SPRING, ANTI-LASH 33 0C6040 1 ASSEMBLY, WIRE 34 084542 1 ASSEMBLY, IGNITION COIL - GN LF 35 092079 2 SCREW, TAPTITE M6-1.0 X 25 BP 36 0A8222 1 SPRING, GOVERNOR 8# 37 083502 1 BOLT, GOVERNOR ADJUST M5 38 083503 1 NUT, M5-0.8 METAL LOCK 39 0D3083 1 ASSEMBLY, OIL DRAIN HOSE 40 0C8434 1 ASSEMBLY, CAP & DIPSTICK 41 090072 1 O-RING 9/16 X 3/4 X 3/32 42 075281 1 SWITCH, THERMAL 43 043182 2 WASHER LOCK M3 44 0C1085 2 SCREW PPHM M3-0.5 X 8
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
GN410 Engine – Drawing No. 0D3539-B Part 2
ITEM PART NO. QTY. DESCRIPTION
1 0C5322 1 CASTING, TWIN REGULATOR HOUSING 2 0C5765 1 SOLENOID , TWIN REGULATOR 3 0C4647 1 GASKET , SOLENOID 4 0C4680 1 PLUNGER, LP REGULATOR ASSEMBLY 5 0C6070 1 SPRING-SOLENOID, PLUNGER 6 022985 4 WASHER, FLAT #6 7 022264 4 WASHER, LOCK M4 8 075475 4 SCREW PPHM M4-0.7 X 10 9 0C5760D 2 JET, GN 990 ENGINE LP (12KW / 15KW)
0C5760A 1 JET, GN 410 ENGINE LP (7KW) 10 0C6606 2* BARBED STRAIGHT 1/2NPT x 1/2 11 097934 2* O-RING, CHECK VALVE 12 0C4645 2* ADJUSTER SCREW, TWIN REGULATOR 13 0C5761 2* LEVER, REGULATOR 14 0C5968 2* SUPPORT, INLET SEAL 15 0C6066 2* SEAL, INLET 16 0C5759 2* PIN, PIVOT ARM 17 0C5764 2 SPRING, REGULATOR (12KW / 15KW)
0C5764A 1 SPRING, REGULATOR (7KW) 18 070728 4 SCREW, PFIHM M3-0.5 x 5
(12KW / 15KW)
070728 2 SCREW, PFIHM M3-0.5 x 5 (7KW)
ITEM PART NO. QTY. DESCRIPTION
19 0C6069 2* GASKET, DIAPHRAGM 20 0C5762 2* COVER, TWIN REGULA TOR 21 045764 16 SCREW, TAPTITE M4X8 BP
(12KW / 15KW)
045764 8 SCREW, TAPTITE M4X8 BP (7KW) 22 0C6731 2* RIVET, POP .118 X .125 23 0C6067 2* SUPPORT, DIAPHRAGM 24 0C4706 2* DIAPHRAGM, TWIN REGULATOR/
SOLENOID 25 0C6068 2* CAP, DIAPHRAGM SUPPORT 26 0C4643A 2* INLET, TWIN REGULATOR 11.11 DIA. 27 026073 1 PLUG, STANDARD PIPE 1/8 STEEL
SQUARE HEAD 28 0A4032 4* PIN, LIMITED ADJUSTMENT 29 0D3308 4 WASHER, FLAT M3 X 10mm O.D.
(12KW / 15KW)
0D3308 2 WASHER, FLAT M3 X 10mm O.D.(7KW)
30 0C4643 1 INLET, TWIN REGULATOR NO HOLE -
NOT SHOWN (7KW)
* A QUANTITY OF 1 IS TO BE USED ON 7KW HOME STANDBY
52 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators Gas Regulator – Drawing No. 0D1259-A
8
7
2
21
10
5
6
20
25
24
22
10
28
12
28
23
19
28
11
17
9
4
3
1
12
28
26
11
27
15
14
16
13
17
29
18
26
16
15
14
13
29
18
19
23
22
24
20
25
21
Generac®Power Systems, Inc. 53
Section 8 Notes
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
54 Generac®Power Systems, Inc.
Section 8 Notes
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Generac®Power Systems, Inc. 55
Section 9 Mounting Dimensions
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
Drawing No. 0D3739-A
TYPE HOM 120/240v
CBHOM-F
TYPE HOM
CBHOM-F
120/240v
TYPE HOM 120/240v
CBHOM-F
TYPE HOM 120/240v
CBHOM-F
TYPE HOM 120/240v
CBHOM-F
TYPE HOM
CBHOM-F
120/240v
TYPE HOM
CBHOM-F
120/240v TYPE HOM
CBHOM-F
120/240v
TYPE HOM
CBHOM-F
120/240v TYPE HOM
CBHOM-F
120/240v
TYPE HOM
CBHOM-F
120/240v TYPE HOM
CBHOM-F
120/240v
M6PEM-T
M6PEM-T
M6PEM-T
M6PEM-T
REAR VIEW
LEFT SIDE VIEW
TRANSFER SWITCH
RIGHT SIDE VIEW
FRONT VIEW
AIR
OUTLET
AIR INTAKE
914mm [ 36.0" ]
ALL AROUND UNIT
MINIMUM OPEN AREA
AIR INTAKE
REAR VIEW
GROUNDING LUG
3/4" NPT FUEL INLET
GAS PRESSURE OF 11-14"
WATER COLUMN REQUIRED
1172.3 [46.2"]
260
[10.2"]
149
[5.9"]
AIR
OUTLET
RIGHT SIDE VIEW
490.7 [19.3"]
Ø30.2mm [Ø1.19"]
GUARDIAN
1193 [47"]
1232 [48.5"]
FRONT VIEW
M6PEM-T
308
[12"]
M6PEM-T
704
743
[27.7"]
CBHOM-F
TYPE HOM 120/240v
[29.25"]
LIFTING HOLES 4-CORNERS
"DO NOT LIFT BY THE ROOF"
MINUMUM
PEA GRAVEL
76.2mm [3.00"]
207 [8.14"]
M6PEM-T
120/240v
120/240v
120/240v
120/240v
120/240v
120/240v
TYPE HOM
TYPE HOM
TYPE HOM
TYPE HOM
TYPE HOM
TYPE HOM
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
CBHOM-F
TYPE HOM
TYPE HOM
TYPE HOM
TYPE HOM
TYPE HOM
120/240v
120/240v
120/240v
120/240v
120/240v
M6PEM-T
604 [23.5"]
TRANSFER SWITCH
716 [28"]
622 [24.5"]
LEFT SIDE VIEW
56 Generac®Power Systems, Inc.
CALIFOR NIA EM ISSION CONTROL WAR R ANT Y STATEMENT
YOUR WARRANTY R IGHTS AND OB LIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi­cation or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EM ISSION CONTROL SYSTEM WARR ANT Y COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur­ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASERS/OWNERS WARRANTY R ESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap­proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for contacting a Generac Authorized Warranty Service Facility as soon as a problem occurs.
The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days. Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe impor­tant rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty serv­ice, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at one of the following addresses:
For Air-cooled Product ... For Liquid-cooled Product ...
AT TENTION WARRANT Y DEPARTMENT ATTENTION WARRANTY DEPARTMENT GENERAC POWER SYSTEMS, INC. GENERAC POWER SYSTEMS, INC. P.O. BOX 297 211 MURPHY DRIVE WHITEWATER, WI 53190 EAGLE, WI 53119
Part 1
Section 10 – Warranty
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
NOTE: This Emission Control Warranty Statement pertains to this product only IF the generator size is 15 kW or below.
Generac®Power Systems, Inc. 57
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con­tinue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man­ufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions -related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions -related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions -related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-
ble for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
*Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
Section 10 – Warranty
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
1) Fuel Metering System:
1.2) LPG/Natural Gas carburetion assembly and its internal components.
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
GENERAC POWER SYSTEMS "TWO YEAR" STANDARD WARRANTY FOR GUARDIAN
®
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years or 2000 hours of operation from the date of original sale, whichever occurs first, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accor­dance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the war­ranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Guardian prepackaged emergency automatic standby generators sold and rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
• Engine - All Components
• Alternator - All Components
• Transfer System - All Components All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate
Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Generac Guardian generators that utilize non- Generac replacement parts.
• Any Generac Guardian generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLA CE OF ALL OTHER W ARRANTIES, EXPRESSED OR IMPLIED . SPECIFICALLY , GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC®POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part No. 0D3169 Revision 4 (01/21/02) Printed in U.S.A .