If you do not understand any portion of this manual,
contact Generac or your nearest Generac Authorized
Service Dealer for starting, operating and servicing
procedures.
Throughout this publication, and on tags and
decals affixed to the generator, DANGER, WARNING,
CAUTION and NOTE blocks are used to alert you to
special instruction about a particular operation that
may be hazardous if performed incorrectly or care
lessly. Observe them carefully. Their definitions are
as follows:
DANGER
After this heading, you can read instructions that,
if not strictly complied with, will result in personal
injury or property damage.
--------ik WARNING Jk---------------
After this heading, you can read instructions that,
if not strictly complied with, may result in person
al injury or property damage.
------
ik CAUTION Jk
After this heading, you can read instructions that,
if not strictly complied with, could result in dam
age to equipment and/or property.
NOTE:
After this heading, you can read explanatory
statements that require special emphasis.
These safety warnings cannot eliminate the hazards
that they indicate. Common sense and strict compli
ance with the special instructions while performing
the service are essential to preventing accidents.
Four commonly used safety .symbols accompany the
Danger, Warning and Caution blocks. The type of
information each indicates follows:
This symbol points out important safety infor
A
mation that, if not followed, could endanger
personal safety and/or property of you and
others.
This symbol points out potential explosion
A
hazard.
This symbol points out potential fire hazard.
______________
-----------
The operator (driver) is responsible for proper and
safe use of the vehicle and its equipment, and the
safety of all vehicle occupants. We strongly recom
mend that the operator read this manual and thor
oughly understand all instructions before using this
equipment. We also strongly recommend instructing
other occupants in the vehicle to properly start and
operate the generator. This prepares them if they
need to operate the equipment in an emergency.
♦ CONTENTS
This manual contains pertinent owner’s information,
including warranty, electrical diagrams, exploded
views and lists of repair parts for generator model
numbers 009600-4 and 009734-4. In addition, the
latter portion of this manual contains information
necessary for the proper installation of these
generators.
♦ OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safe
ty checks, to make sure that all maintenance for safe
operation is performed promptly, and to have the
equipment checked periodically by a Generac
Authorized Service Dealer. Normal maintenance ser
vice and replacement of parts are the responsibility of
the owner/operator and, as such, are not considered
defects in materials or workmanship within the
terms of the warranty Individual operating habits
and usage contribute to the need for maintenance
service.
Proper maintenance and care of your generator
ensure a minimum number of problems and keep
operating expenses at a minimum. See your Generac
Authorized Service Dealer for service aids and acces
sories.
♦ HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs,
simply contact a Generac Authorized Service Dealer
for assistance. Service technicians are factory-trained
and are capable of handling all of your service needs.
When contacting a Generac Authorized Service
Dealer or the factory about parts and service, always
supply the complete model number and serial num
ber of your unit as given on its data decal, which is
located on your generator.
Model No.Serial No.
__________________________________
______________
______________
______
This symbol points out potential electrical
A
shock hazard.
Generac* Power Systems, Inc.
AUTHORIZED SERVICE
DEALER LOCATION
To locate the GENEPiAC AUTHORIZED SERVICE
DEALER nearest you, please call this number:
1-800-333-1322
ONLY DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
Table of Contents
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
operation be copied and posted in potential hazard areas of the recreational vehicle.
Safety should be stressed to all operators and potential operators of this equipment.
A
Safety Rules
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
SAVE THESE INSTRUCTIONS - The manufacturer suggests that these rules for safe .
WARNING:
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
I
Study these SAFETY RULES carefully before
installing, operating or servicing this equipment.
Become familiar with this manual and with the unit.
The generator can operate safely, efficiently and reli
ably only if it is properly installed, operated and
maintained. Many accidents are caused by failing to
follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possible
circumstance that might involve a hazard. The warn
ings in this manual, and on tags and decals
affixed to the unit, are, therefore, not all-inclusive. If
you use a procedure, work method or operating tech
nique Generac does not specifically recommend, you
must satisfy yourself that it is safe for you and others.
You also must make sure the procedure, work
method or operating technique that you choose does
not render the generator unsafe.
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglect
ing its maintenance or being careless can cause
possible injury or death. Permit only responsi
ble and capable persons to operate or maintain
this equipment.
Potentially lethal voltages are generated by
A
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
A GENERAL HAZARDS ^
For safety reasons, Generac recommends
that the installation, initial start-up and mainte
nance of this equipment is carried out by a
Generac Authorized Service Dealer.
The engine exhaust fumes contain carbon monox
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust sys
tem must be installed properly, in strict compli
ance with applicable codes and standards.
Following installation, you must do nothing that
might render the system unsafe or in noncompli
ance with such codes and standards. The genera
tor compartment must be completely vapor sealed
from the vehicle interior. There must be no possi
bility of exhaust fumes entering the vehicle interi
or. Never operate this equipment with a leaking or
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit is
operating.
Adequate, unobstructed flow of cooling and venti
lating air is critical to correct generator operation
and is required to expel toxic fumes and fuel
vapors from the generator compartment. Without
sufficient cooling airflow, the engine/generator
quickly overheats, which causes serious damage to
the generator. Do not alter the installation or per
mit even partial blockage of ventilation provisions,
as this can seriously affect safe operation of the
generator.
When working on this equipment, remain alert at
all times. Never work on the equipment when you
are physically or mentally fatigued.
Inspect the generator regularly, and contact your
nearest Generac Authorized Service Dealer imme
diately for parts needing repair or replacement.
Before performing any maintenance on the genera
tor, disconnect its battery cables to prevent acci
dental start up. Disconnect the cable from the bat
tery post indicated by a NEGATIVE, NEG or (-)
first. Reconnect that cable last.
Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating con
ditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
Generac* Power Systems, Inc.
Safety Rules
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
SAFETY RULES
A
ELECTRICAL HAZARDS
• The generator covered by this manual produces
dangerous electrical voltages and can cause fatal
electrical shock. Avoid contact with bare wires, ter
minals, connections, etc., while the unit is running.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If you
must work around an operating unit, stand on an
insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL
SHOCK MAY RESULT.
• During installation onto the vehicle, have the gen
erator properly grounded (bonded) either by solid
mounting to the vehicle frame or chassis, or by
means of an approved bonding conductor. DO
NOT disconnect the bonding conductor, if so
equipped. DO NOT reconnect the bonding conduc
tor to any generator part that might be removed or
disassembled during routine maintenance. If the
grounding conductor must be replaced, use only a
flexible conductor that is of No. 8 American Wire
Gauge (AWG) copper wire minimum.
• In case of accident caused by electric shock, imme
diately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT
WITH THE VICTIM. Use a nonconducting imple
ment, such as a rope or board, to free the victim
from the live conductor. If the victim is uncon
scious, apply first aid and get immediate medical
help.
• Never wear jewelry when working on this equip
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving com
ponents causing injury.
A
A
FIRE HAZARDS
For fire safety, the generator must be installed and
maintained properly. Installation always must
comply with applicable codes, standards, laws and
regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational iSafety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer’s instructions
and recommendations. Following proper installa
tion, do nothing that might alter a safe installation
and render the unit in noncompliance with tlie
aforementioned codes, standards, laws and regu
lations.
Keep a fire extinguisher in the vehicle at all times.
Extinguishers rated ’ABC” by the National Fire
Protection Association are appropriate for use on
the recreational vehicle generator electrical sys
tem. Keep the extinguisher properly charged and
be familiar with its use. If you have any question
pertaining to fire extinguishers, consult your local
fire department.
A
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure that no com
bustible materials are left in the generator com
partment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surround
ing the generator clean and free from debris.
Gasoline is extremely FLAMMABLE and its vapors
are EXPLOSIVE. Do not permit smoking, open
flame, sparks or any source of heat in the vicinity
while handling gasoline. Comply with all laws gov
erning the storage and handling of gasoline.
This generator may use liquid propane (LP) gas as
a fuel, LP gas is highly EXPLOSIVE. The gas is
heavier than air and tends to settle in low areas
where even the slightest spark can ignite the gas
and cause an explosion.
A
A
Generac® Power Systems, Inc.
GENERAL
INFORMATION
Section 1 - General Information
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
1.1 GENERATOR IDENTIFICATION
Please record the following information from the generator DATA DECAL or information decal.
1. Model Number
3. kW Rating
5. Phase________________________________6. Hertz
________________________
____________________________
2. Serial Number ____________________________
4. Rated Voltage
____________________________________
7.Generator AC Output Leads14. Oil Dipstick and Filler Tube
Generac* Power Systems, Inc.
Section 1 - General Information
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
GENERAL
INFORMATION
1.2 GENERATOR APPLICABILITY
These generators have been designed and manufac
tured for supplying electrical power for recreational
vehicles. You should not modify the generator or use
it for any application other than for what it was
designed. If there are any questions pertaining to its
application, write or call the factory. Do not use the
unit until you have been advised by competent
authority.
IMiNCilR
For fire safety, the generator must have been
properly installed in compliance with ANSI
119.2-1975/NFPA 501C-1974, "Standard for
Recreational Vehicles, Part III - Installation of
Electrical Systems." The generator also must
have been installed in strict compliance with
the manufacturer's detailed installation instruc
tions. After installation, do nothing that might
render the unit in noncompliance with such
codes, standards and instructions.
You can use your generator set to supply electrical
power for operating one of the following electrical
loads:
• PRIMEPACT 66G: 120 and/or 240 volts, single
phase, 60 Hz electrical loads. These loads can
require up to 6600 watts (6.6 kW) of power, but
cannot exceed 55 AC amperes of current at 120
volts or exceed 27.5 AC amperes at 240 volts.
• PRIMEPACT 66LP: 120 and/or 240 volts, single
phase, 60 Hz electrical loads. These loads can
require up to 6200 watts (6.2 kW) of power, but
cannot exceed 51.7 AC amperes of current at 120
volts or exceed 25.8 AC amperes at 240 volts.
-
-----
M. CAUTION M.
Do not overload the generator. Some installa
tions may require that electrical loads be alter
nated to avoid overloading. Applying exces
sively high electrical loads may damage the
generator and may shorten its life. Add up the
rated watts of all electrical lighting, appliance,
tool and motor loads the generator will power
at one time. This total should not be greater
than the wattage capacity of the generator. If
an electrical device nameplate gives only volts
and amps, multiply volts times amps to obtain
watts (volts X amps = watts). Some electric
motors require more watts of power (or amps
of current) for starting than for continuous
operation.
---------
-
1.3 INSTALLATION
This Owner’s Manual has been prepared under the
assumption that a competent, qualified technician
installed the generator into an industrial vehicle. We
also assume the installer complied with all applicable
codes, standards and regulations pertaining to instal
lation.
An INSTALLATION MANUAL was shipped with the
generator. That Manual contains manufacturer’s
instructions and recommendations for installing the
unit into an industrial vehicle. After installation,
installers should forward the Installation Manual to
Owners/Operators for their informaiion.
Owners/Operators have the responsibility to make
sure that nothing is done that might render the instal
lation unsafe or in non-compliance with applicable
codes, standards and instructions.
1.4 SAFETY
Before using the generator set, carefully read GEN
ERAL SjAFETY RULES inside the cover. Comply with
these RULES to prevent accidents and damage to
equipment and/or property. Generac suggests copy
ing and posting the GENERAL SAFETY RULES to
potential operators of this equipment.
1.5 GENERATOR AC CONNECTION
SYSTEIVi
These air-cooled generator sets are equipped with
dual stator AC power windings. These two stator
windings supply electrical power to customer electri
cal loads by means of a dual 2-wire connection sys
tem.
Generators may be installed to provide the following
outputs:
1) 120 'VAC loads only — one load with a mtiximum
total wattage requirement equal to the generator’s
rated power output (in watts), and 120V across the
generator output terminals. Figure 1.1, page 6,
shows the generator lead wire connections for
120VAC ONLY.
2) 120/240 VAC loads — one load with a maximum
total wattage requirement equal to the generator’s
rated power output, and 240V across the generator
output terminals; or two seperate loads, each with a
maximum total wattage requirement equal to half of
the generator’s rated power output (in watts), and
120V across the generator output terminals.
Figure 1.2, page 6, shows the generator lead wire
connections for 120/240 VAC loads.
Generac* Power Systems, Inc.
GENERAL
INFORMATION
Section 1 - General Information
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
Figure 1.1 - Connection for 120 Volts Only
Figure 1.2 - Connection for 120/240 Volts
1.6 SPECIFICATIONS
♦ 1.6.1 FUEL REQUIREMENTS
This generator is equipped with a gasoline fuel system
as standard equipment. Specific installations may pro
vide either a separate fuel tank for the generator, or the
generator may “share” the vehicle engine’s fuel tank.
Fuel Consumption (gph/ibs.ph)
Model
PrimePact 66G
PrimePact 66LP
No Load1/2 Load
0.33
0,47/2.010.85/3.62
0.590.99
Full Load
1,66/7.05
NOTE
Some installations using a “shared” fuel tank may
have a generator fuel pickup tube that is shorter
than the vehicle engine’s pickup tube. Such an
arrangement causes the generator engine to “run
out of gas” while adequate fuel for the vehicle
remains in the tank.
To reduce lead and carbon deposits use high quality
UNLEADED gasoline with the generator. Leaded
REGULAR grade gasoline is an acceptable substitute.
NOTE:
Using unleaded gasoline contributes to longer engine
valve life by reducing lead and carbon deposits.
------
Jk CAUTION Jk
-----------
Generac does not recommend using any
A
gasoline containing alcohol (such as "gasohol").
If you use any gasoline containing alcohol, it
must not contain more than 10 percent ethanol,
and it must be removed from the generator
during storage. Do NOT use any gasoline
containing methanol. If you use gasoline with
alcohol, inspect more frequently for fuel leaks
and other abnormalities.
♦ 1.6.2 ENGINE OIL REQUIREMENTS
_______________
Use only high quality detergent oil classified “For
Service SF” and with an oil viscosity rating of SAE
lOW-30 oil. Do not pour in any additives to the rec
ommended oil. Engine crankcase capacity is 1.4
liters. See Section 3.2 on page 11 for oil level check
and filing procedures.
♦ 1.6.3 GENERATOR SPECIFICATIONS
SERIES
Rotor RPM36003600
Rotor Poles
Engine RPM27002700
Rated Max. Continuous AC Output*
Voltage*
Rated Max. Continuous Current*
Phase11
Frequency
Battery Charging Current (Max.)
Weight
Length25 inches
Width
Height
* All units are reconnectable to 120 and/or 240 volts, dual voltage output. Units are not listed per RVIA/ANSI when reconnected for dual voltage output
t Rated maximum continuous current at 240 volts is 27,5 amps,
N Rated maximum continuous current at 240 volts is 25,8 amps.
6 Generac* Power Systems, Inc.
PRIMEPACT 66GPRIMEPACT 66LP
2
6600 watts (6.6 kW)6200 watts (6.2 kW)
120
55.0 AC ampst
60 Hertz
2
120
51.7 AC amps N
60 Hertz
2 amps (trickle charge)2 amps (trickle charge)
213 pounds
18,5 inches18.5 inches
15.75 inches15.75 inches
216 pounds
25.75 inches
Section 2 - Operation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
Fram Autolite ...................................................................65
Spark Plug Gap
Recommended Min. Battery
♦ 1.6.5 EMISSIONS COMPLIANCE PERIOD
.......................................
...........
400 Cold Cranking Amps
0.030 inch (0.8 mm)
* •
For nonhandled engines the Emissions Compliance
Period referred to on the Emissions Compliance
Label indicates the number of operating hours for
which the engine has been shown to meet Federal
emission requirements.
• For engines less than 225 cc displacement,
Category C= 125 hours, B=250 hours, and A=500
hours.
• For engines of 225 cc or more. Category C = 250
hours, B = 500 hours, and A= 1000 hours.
2.1 GENERATOR CONTROL PANEL
The following features are mounted on the generator
control panel (Figure 2.1):
♦ 2.1.1 FUEL PRIMER
Before starting a cold engine (if it has not been start
ed in more than two weeks), you must press this
switch for approximately ten seconds to bring fuel
from the tank to the fuel pump. This rocker type
switch springs back into its original position when
you release it.
♦ 2.1.2 START/STOP SWITCH
To crank and start the engine, hold this switch in the
START position. Release the switch when the engine
starts. To stop an operating engine, press and hold
the switch in the STOP position until the engine shuts
off. The switch center position is tlie RUN position.
♦ 2.1.3 15 AMP FUSE
The fuse protects the engine’s DC control circuit
against electrical overload. If the fuse elenieni lias
melted open due to overloading, the engine cannot be
cranked. If you must replace the fuse, use only an
identical 15 amp replacement fuse.
♦ 2.1.4 LINE BREAKERS
Protects generator’s AC output circiut against
overload, i.e,, prevents unit from exceeding
wattage/amperage capacity. This unit has two 30-amp
breakers.
If this generator has been reconnected for dual
voltage AC output (120/240 volts), you can install
line breakers having an amperage rating that is
different than that stated above. The replacement
line breakers consist of two separate breakers with
a connecting piece between the breaker handles
(so that both breakers will operate at the same
time). If the unit is reconnected for dual voltage,
it is no longer RVIA listed.
2.2 OPTIONAL REMOTE
START/STOP PANEL
A remote mounted Start/Stop Panel (Figure 2.2) is
available that allows you to start and stop the gener
ator engine conveniently from inside the vehicle. The
remote panel includes a Start/Stop switch, hour me
ter, generator run lamp and a wire harness.
Figure 2.2 — Optional Remote Panel
(Models 004057 and 004184)
♦ 2.3.2 PRECHOKE
The choke system also has a temperature-sensitive
metal strip that adjusts choke valve angle according
to ambient temperatures (i.e., in cold ambient tem
peratures, choke valve closes more). Once the engine
starts, an element heats the temperature-sensitive
strip to a normal operating condition, opening the
choke valve. This may take about three minutes in
cooler weather.
2.4 BEFORE STARTING THE ENGINE
NOTE:
Instructions and information in this manual
assume the generator has been properly installed,
connected, serviced, tested and adjusted by a
qualified installation technician or installation
contractor.
♦ 2.4.1 INSTALLATION____________________________
Generator installation must have been properly com
pleted so it complies with all applicable codes, stan
dards and regulations and with the manufacturer's
recom.mendations,
(For drawing, see Instruction Sheet P/N A9579)
2.3 AUTOMATIC CHOKE
This engine is equipped with an automatic choke that
consists of two main components: a choke solenoid
and prechoke.
♦ 2.3.1 CHOKE SOLENOID
During engine cranking (Start/Stop switch at
START), a solid-state choke module signals the
choke solenoid to activate and cycle (choke on/choke
off) until the engine starts. The choke solenoid thus
opens and closes the carburetor choke valve only
when the engine is cranking. When the engine starts,
the choke stops cycling.
________________________
♦ 2.4.2 ENGINE LUBRICATION
Have the engine crankcase properly serviced with the
recommended oil before starting. Refer to Section
1.6.3 (Page 6) and Sections 3.1 and 3.2 (Page 11) for
oil servicing procedures and recommendations.
------
ik CAUTION Jk
Any attempt to crank or start the engine before
A
you have properly serviced it with the recom
mended oil may result in an engine failure.
♦ 2.4.3 FUEL SUPPLY
The engine must have an adequate supply of proper
fuel to operate. Before starting it, check that sufficient
fuel is available.
Depending on the installation, the generator may
have either a separate fuel tank, or it may “share”
the vehicle engine’s fuel tank.
♦ 2.4.4 COOLING AND VENTILATING AIR
Air inlet and outlet openings in the generator com
partment must be open and unobstructed for contin
ued proper operation. Without sufficient cooling and
ventilating airflow, the engine/generator quickly over
heats, which causes it to shut down and may damage
the generator.
____________________________
NOTE:
-----------
CSenerac* Power Systems, Inc.
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
♦ 2.4.5 ENGINE EXHAUST GAS
____________________
Before starting the generator engine, you should be
sure there is no way for exhaust gases to enter the
vehicle interior and endanger people or animals.
Close windows, doors and other openings in the vehi
cle that, if open, might permit exhaust gases to enter
the vehicle.
DANGER
The generator engine gives off DEADLY carbon
monoxide gas through its exhaust system. This
dangerous gas, if breathed in sufficient concen
trations, can cause unconsciousness or even
death. Never operate the generator set with
the vehicle inside any garage or other enclosed
area. DO NOT OPERATE THE GENERATOR IF THE
EXHAUST SYSTEM IS LEAKING OR HAS BEEN
DAMAGED. SYMPTOMS OF CARBON MONOX
IDE POISONING ARE (a) inability to think coher
ently; (b) vomiting; (c) twitching muscles; (d)
throbbing temples; (e) dizziness; (f) headaches;
(g) weakness; and (h) sleepiness. IF YOU FEEL
ANY OF THESE SYMPTOMS, MOVE INTO FRESH
AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET
MEDICAL HELP.
2.5
Read the vehicle manufacturer’s instructions. The
owner/operator should become familiar with the
vehicle in which this generator is installed.
Differences exist between vehicles. For example,
some vehicles may use a transfer switch to isolate
dockside power from the generator, while other
vehicles may use an isolating receptacle. Some
vehicles may be equipped with a DC converter
which allows the generator to power certain DC
lighting and other DC loads.
To crank and start the generator engine, proceed as
follows:
1. Turn OFF electrical loads using the means pro
If starting from the generator control panel, turn
OFF loads by setting the generator’s main circuit
breaker to the OFF (or open) position. If starting
from a remote panel, turn OFF loads using the
means provided in the vehicle (such as a main cir
cuit breaker). Electrical load circuits will be
turned ON after the generator has started, stabi
lized and warmed up.
STARTING THE GENERATOR
NOTE:
vided in your vehicle (such as a main line circuit
breaker or transfer switch).
NOTE:
Section 2 - Operation
2.
If you have not started the engine in more than
OPERATION
two weeks, press the Fuel Pump Primer switch
and hold it for about 10 seconds. However, if the
engine is warm, skip Step 2.
3.
To crank and start the engine, hold the starf/stop
switch at START. Release the switch when the
engine starts.
--------
M. CAUTION ¿k
If the engine does not start after it has been
^ cranking for 15 seconds, release the Start/Stop
switch and wait 1 minute before trying again.
Holding the switch for longer than 15 seconds
can damage the starter motor.
--------------
Let the engine run at no-load for a few minutes to
stabilize and warm up.
5.
Turn ON electrical loads using the means
provided (such as a main circuit breaker or
transfer switch).
2.6 STOPPING THE GENERATOR
1. Turn OFF all electrical loads using the means
provided (such as a main circuit breaker or
transfer switch).
2. Let generator run at no-load for a few minutes, to
stabilize internal engine generator temperatures.
3. Place the Start/Stop switch in its STOP position.
The engine will come to a complete stop.
2J APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator,
observe these guidelines:
• Before applying electrical loads, let the generator
stabilize and warm up for a minute or two.
• DO NOT overload the generator.
• 2.7.1 LETTING THE ENGINE STABILIZE
The generator supplies correct rated voltage only at
the proper governed speed. Some electrical appli
ances may be extremely sensitive to voltage. Incorrect
voltages can damage such appliances.
If electrical loads are applied at reduced operating
speeds, such loads imposed on the engine when suf
ficient power is not available may shorten engine life.
Never turn ON electrical loads until after the genera
tor engine has started and stabilized at no-load.
You can read the rated wattage/amperage capacity of
your generator on the generator data decal (see
Section 1.1 on Page 4).
Applying electrical loads in excess of the unit’s rated
capacity will cause the engine/generator to automati
cally shut down.
To avoid overloading, add up the wattage of all con
nected electrical lighting, appliance, tool and motor
loads. This total should not be greater than the gen
erator’s rated wattage capacity.
• Most lighting, appliance, tool and motor loads indi
cate their required watts on their nameplate or
data plate. For light bulbs, simply note the wattage
rating of the bulb.
• If a load does not show its rated wattage, multiply
that load’s rated VOLTS times AMPS to obtain
WATTS.
• Induction type motors (such as those that run the
vehicle's furnace fan, refrigerator, air conditioner,
etc.) need about 2-1/2 times more watts of power
for starting than for running (for a few seconds
during motor starting). Be sure to allow for this
when connecting electrical loads to the generator.
First, figure the watts needed to start electric
motors in the system. To that figure, add the run
ning wattages of other items that will be operated
by the generator.
• Do not apply heavy electrical loads for the first two
or three hours of operation.
2.8 PROTECTION SYSTEMS
• 2.8.1 LOW OIL PRESSURE SWITCH
This switch (Figure 2.3 on page 10) has normally
open (N.O.) contacts that are held open by engine oil
pressure during cranking and operating. Should oil
pressure drop below a preset level, switch contacts
close, and the engine automatically shuts down. The
unit should not be restarted until oil is added.
_____________
♦ 2.8.2 HIGH TEMPERATURE SWITCH
This switch (Figure 2.3), which has normally open
(N.O.) contacts, is mounted near the oil filter. The
contacts close if the temperature should exceed
approximately 284° F (140° C), initiating an engine
shutdown.
______________
Figure 2.3 - Low Oil Pressure and
High Temperature Switches
HIGH
♦ 2.8.3 FIELD BOOST
The Controller Circuit Board houses a field boost
diode and resistor that are not part of the automatic
choke circuit. These two components are part of a
“field boost” circuit (Figure 2.4). During engine
cranking only, a positive DC (battery) voltage is deliv
ered through the diode, resistor, brushes and slip
rings, and the generator rotor. Application of this
voltage to the rotor “flashes the field” whenever it is
started . Flashing of the field each time the generator
starts makes sure that a sufficiently strong magnetic
field is available to produce “pickup” voltage in the
stator windings.
Figure 2.4 - Field Boost Circuit
1 O Generac* Power Systems, Inc.
CLOSEST TO
BEARING
Section 3 - Maintenance
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
MAINTENANCE
♦ 2.8.4 OVERVOLTAGE PROTECTION___________
A solid-state voltage regulator (Figure 2.5) controls
the generator’s AC output voltage. This regulator sup
plies an excitation current to the rotor. By regulating
the rotor’s excitation current, the strength of its mag
netic field is regulated and, in turn, the voltage deliv
ered to connected electrical loads is controlled. 'When
the AC frequency is 50 Hertz, voltage is regulated at
The voltage regulator also incorporates a “voltage
surge protection circuit.” This circuit prevents trou
blesome surges in the generator AC output voltage.
Voltage surge is a common cause of damage to elec
tronic equipment.
• 2.8.5 25-HOUR BREAK-IN PERIOD
_______________
The first 25 hours of operation is the break-in period
for the generator. Properly breaking in the generator
is essential to minimize fuel consumption and pro
vide maximum engine performance. During this 25hour break-in period, follow this procedure:
• Run the unit at varying electrical loads to help seat
the engine piston rings properly.
• Check the engine oil level frequently. Add oil if
needed. It is normal for the generator engine to
consume more oil than is normal until the piston
rings have properly seated.
• For the 75-hour operation following the break-in
period, avoid light electrical loads. Load the
generator at 50 percent (or more) of its rated
wattage capacity. Repeated light loads during these
75 hours can cause improper seating of engine pis
ton rings, resulting in blowby and high oil con
sumption.
• After operating the unit for 25 hours, complete the
tasks recommended under Section 2.8.6.
♦ 2.8.6 25-HOUR CHECK-UP
After the 25-hour break-in period, contact a Generac
Authorized Service Dealer for the following mainte
nance. The vehicle owner is responsible for any
charges:
• Change the engine crankcase oil and oil filter.
• Check all fluid levels.
• Inspect the cooling and ventilation openings.
• Check the engine ignition system.
• Inspect the entire electrical system.
• Inspect the engine exhaust system.
• 2.8.7 OPERATION IN HIGH GRASS
OR BRUSH
------
A
3.1
-Jà WARNING Ml
Never operate the generator while the vehicle
is parked over high grass, weeds, brush,
leaves or any other combustible substance.
Such materials can ignite and burn from the
heat of the exhaust system. The generator
exhaust system becomes extremely hot dur
ing operation and remains hot for a long time
after it has shut down.
CHECKING THE ENGINE OIL
--------------
LEVEL
For oil capacities and reciuirements, see “Engine Oil
Requirements,” Section 1.6.2 (Page 6). Check the
engine crankcase oil level at least every eight hours of
operation, or before you use it. To check the engine
oil level, proceed as follows (see Figure 3.1):
Be sure the generator is as level as possible.
1.
Remove the dipstick and wipe it dry with a clean,
2.
lint-free cloth.
Install and tighten the dipstick cap; then, remove
3.
it again. The oil level should be at the dipstick
“Full” mark.
If necessary, remove the oil fill cap on the rocker
4.
cover and slowly add oil until it reaches the dip
stick “Full” mark. DO NOT FILL ABOVE THE
“FULL MARK.
-------Mlcaution Jk
Never operate the engine with the oil level
A
below the "Add" mark on the dipstick. Doing
this could damage the engine.
5. Install and tighten the oil fill cap and the dipstick
before operating the engine.
• Change the engine oil after the first 25 hours of
operation (after the 25-hour break-in period, see
Section 2.8.5, Page 10). Thereafter, change the
oil every 100 operating hours. Change the oil more
frequently if operating consistently under heavy
load or at high ambient temperatures.
• Change the engine oil filter after the first 25 hours
of operation, and every 100 operating hours there
after.
To change the oil and/or oil filter, proceed as
follows:
1. Run the engine until it is thoroughly warmed up
(at least five minutes) then shut OFF
the engine.
2. With the engine still warm from running, remove
the oil drain plug (Figure 3.1). Drain the oil into
a suitable container.
3. After the oil has drained, replace the oil drain
plug. (If only changing the oil, go to step 7.)
4. With the oil drained, remove the old oil filter by
turning it counterclockwise (Figure 3.2 on page 12).
5. Apply a light coating of clean engine oil to the gas
ket of the new filter.
6. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tight
en the filter an additional 3/4 to one turn.
7. Remove the dipstick and fill crankcase with the
proper type and amount of recommended oil (see
Section 1.6.2, Page 6). The engine crankcase can
hold about 1.4 liters. DO NOT FILL /\BOVE THE
‘TULL’ MARK.
8. Install and tighten the dipstick before operating
the engine.
9. Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL’ mark after
checking for leaks. The filter will retain some oil.
Figure 3.1 — Oil Dipstick/Fill Tube and
Location of Oil Drain Plug
3.3
MAINTAINING THE ENGINE
AIR CLEANER
♦ 5.5.1 CLEANING THE FOAM PRECLEANER
Clean and re-oil the foam precleaner every three
months or every 25 hours of operation, whichever
occurs first. Service the foam precleaner more fre
quently if operating the generator in extremely dusty
or dirty conditions. Use the following procedure
(Figure 3.3):
1. Turn the knob counterclockwise to loosen.
2. Remove the cover, foam precleaner and paper fil
ter.
3. Remove the foam precleaner from the cover.
4. Wash the foam precleaner in liquid detergent and
water.
5. Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6. Saturate the foam precleaner in clean engine oil.
Gently squeeze it in a clean cloth to remove
excess oil and to distribute oil (DO NOT T’WIST).
7. Install the foam precleaner into the cover, fol
lowed by the paper filter. Tabs at edges of paper
1 a Generac* Power Systems, Inc.
Section 3 - Maintenance
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
MAINTENANCE
filter must lock into slots on cover.
8. Install the cover, foam precleaner and paper filter.
9. Replace knob to retain the filter in place.
Figure 3.3 - Engine Air Cleaner
PAPER
FILTER
FOAM
PRE-CLEANER
3.4 CLEAN AIR INTAKE SCREEN
Clean all foreign material from the air intake screen
(Figure 3.4) at least once every 100 hours of opera
tion. Clean more often if necessary.
Inspect the area around the generator exhaust muf
fler periodically and remove all grass, leaves, dirt,
etc., from this area.
Figure 3.4 - Cleaning Air Intake
Figure 3.5 - Setting the Spark Plug Gap
SET PLUG GAP AT 0.030 inch
—ik CAUTiON ik----------------
Sparking can occur if the wire terminal does
A
not fit firmly on the spark plug terminal end. If
necessary, re-form the wire terminal to obtain a
tight fit.
3.6 FUEL FILTER (gasolineonly)
Remove and replace the fuel filter (Figure 3.6)
once each year or every 100 hours of operation,
whichever comes first.
Figure 3.6 - Fuel Filter
FUEL FILTER
TO FUEL PUMP
----------------
►
CLEAN THESE AREAS
3.5 CHECKING THE ENGINE
SPARK PLUG
Clean the spark plug and reset the spark plug gap
every 100 hours of operation.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Clean by
scraping or washing using a wire brush and com
mercial solvent. Do not blast the spark plug to
clean.
2. Remove the spark plug and check the condition.
Replace the spark plug if worn or if reuse is ques
tionable.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm)
by carefully bending the ground electrode
(Figure 3.5).
CUSTOMER FUEL CONNECTION
3.7 SPARK ARRESTOR MUFFLER
If the generator is not equipped with a spark arrestor
exhaust muffler and is to be used on any forest cov
ered, brush covered or grass covered unimproved
land, you may have to install a spark arrestor. The
spark arrestor must be maintained in effective work
ing order by the vehicle owner/operator.
For assistance in ordering, installing and maintaining
spark arrestor exhaust mufflers, contact your nearest
Generac Authorized Service Dealer.
Exhaust mufflers supplied by Generac are spark
arrestor types. Generac exhaust mufflers for recre
ational vehicle generators do not have a spark
arrestor screen, but are of the more efficient “toroid”
or “swirl” type. To remove carbon and combustion
deposits from such mufflers, remove the plug from
the muffler and run the engine for approximately 15
minutes. Shut down the engine, let the muffler cool
and install the plug.
Engine vibration could cause a loose plug to
fall out. Without the plug in place, hot engine
exhaust is directed out the opening. This hot
exhaust, depending on the installation, could
be directed to areas not able to withstand the
extreme heat such as wooden floor boards or
other flammable material. This could result in a
fire.
3.8 CLEANING THE GENERATOR
Keep the generator set as clean and dry as possible.
Protect the unit against excessive dust, dirt, corrosive
vapors, road splash, etc. Permitting dirt and mois
ture to accumulate on generator windings will have
an adverse effect on the insulation resistance of those
windings.
When moisture is allowed to remain in contact with
windings, some of the moisture will be retained in
voids and cracks in the insulation. This causes a
reduced insulation resistance and will eventually
cause problems. Dirt will make the problem worse,
since dirt tends to hold moisture in contact with
windings. Salt (as from sea air) also will worsen the
problem since it tends to absorb moisture from the
air. Salt and moisture, when combined, form a good
electrical conductor.
------
-ik CAUTION Mk
Do NOT use a forceful spray of water to clean
A
the generator. Water will enter the generator
interior and cause problems, and may also cont
aminate the generator fuel system.
---------
3.9 BATTERY MAINTENANCE
All lead-acid batteries will discharge when not in use.
The generator battery should be inspected as follows:
♦ 3.9.1 WEEKLY
• Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
• Check the battery fluid level of unsealed batteries
and. if necessary, fill with Distilled Water Only. Do
not use tap water in batteries.
♦ 5.9.2 EVERY SIX MONTHS
• Have the state of charge and condition checked.
This should be done with an automotive-type bat
tery hydrometer.
Servicing of the battery is to be performed or
supervised by personnel knowledgeable of batter
ies and the required precautions. Keep unautho
rized personnel away from batteries.
1 Generac* Power Systems, Ino.
_________________________________
_______________________
NOTE:
Damage will result if the battery connections are
made in reverse.
DANGER
Do not dispose of the battery in a fire. The
battery is capable of exploding. Storage batter
ies give off explosive hydrogen gas. This gas
can form an explosive mixture around the bat
tery for several hours after charging. The
slightest spark can ignite the gas and cause an
explosion. Such an explosion can shatter the
battery and cause blindness or other injury.
Any area that houses a storage battery must be
properly ventilated. Do not allow smoking,
open flame, sparks, or any spark producing
tools or equipment near the battery. Discharge
static electricity from your body before touch
ing the battery by first touching a grounded
metal surface.
A battery presents a risk of electrical shock
A
and high short circuit current. The following
precautions are to be observed when working
on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the
battery;
• Disconnect any charging source prior to connecting
or disconnecting battery terminals; and
• Do not use any jumper cables or booster battery to
crank and start the generator engine. If any battery
has discharged, remove it for recharging.
--------A WARNING A
Do not open or mutilate the battery. Released
A
electrolyte has been known to be harmful to
the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is
A
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following
procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off
immediately with water;
• Where electrolyte contacts the eyes, flush
thoroughly and immediately with water and seek
medical attention; and
• Spilled electrolyte is to be washed down with an
acid neutralizing agent. A common practice is to
use a solution of 1 pound (500 grams) bicarbonate
of soda to 1 gallon (4 liters) or water. The bicar
bonate of soda solution is to be added until the
evidence of reaction (foaming) has ceased. The
resulting liquid is to be flushed with water and the
area dried.
-----------
Section 3 - Maintenance
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
MAINTENANCE
3.10 IVIAJOR SERVICE MANUAL
To obtain a service manual for your generator, con
tact Generac or your nearest Generac Authorized
Service Dealer. Make sure to identify your MODEL
NUMBER and SERIES.
3.11 DRIVE BELT
The engine drives the generator rotor by means of a
pulley and drive belt arrangement. The drive belt and
pulleys are warranted for the life of the generator.
Drive belt tension was properly adjusted before the
unit was shipped from the factory. If you suspect that
drive belt tension is incorrect, contact a Generac
Authorized Service Dealer.
3.12 EXERCISING THE GENERATOR
Generac recommends that you start and operate the
generator at least once every seven days. Let
the unit run for at least 30 minutes to “exercise”
the engine.
3.13OUT OF SERVICE PROCEDURE
♦ 5.15.1 REMOVAL FROM SERVICE
If you cannot exercise the generator every seven days,
and it is to be out of service longer than 30 days, pre
pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. While the engine is still warm from running,
drain the oil completely. Refill the crankcase with
SAE 1OW-30 oil having API classification “For
Service SF.”
4. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
5. Remove the spark plug and pour two or three
tablespoons of clean, fresh engine oil into the
spark plug threaded openings. Reinstall and
tighten the spark plug.
6. Remove the battery and store it in a cool, dry
room on a wooden board. Never store the battery
on any concrete or earthen floor.
7. Clean and wipe the entire generator.
♦ 5.15.2 RETURN TO SERVICE
To return the unit to service after storage, proceed
as follows:
1. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommend
ed oil is used in the engine (see Section 1.5.4,
Page 6). If necessary drain and refill with the
proper oil.
_______________
2. Check the state of the battery. Fill all cells of
unsealed batteries to die proper level wltli distilled
water. DO NOT USE TAP WATER IN THE BAT
TERY. Recharge the battery to 100 percent state of
charge, or, if defective, replace the battery.
3. Clean and wipe the entire generator.
4. Reconnect the batteiy. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly.
5. Turn OFF all electrical loads. Add fuel if neces
sary and then start the engine,
6. Allow the unit to warm up thoroughly
7. Apply electrical loads to at least 50 percent of the
unit’s rated wattage capacity.
v8. When the eirgine is thoroughly warmed up, shut
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
DANGER: For fire safety, installation of a generator into a recreational vehicle must comply strictly
with article 551, NFPA 70; ANSI Cl-1975; AND, ANSI A119.2-1975/NFPA 501C “Standard for
Recreational Vehicles” (Part 3, “Installation of Electrical Systems”). In addition, installation must
comply with the manufacturer’s instructions and recommendations.
NOTICE TO INSTALLER
These Installation Instructions have been published
by Generac to aid in the installation of the products
described in this manual. Generac assumes that
installation personnel are familiar with the proce
dures for installing such products, or similar prod
ucts that Generac manufactures. Generac also
assumes that personnel have been trained in the rec
ommended installation procedures for these prod
ucts and that such training includes (a) use of com
mon hand tools, (b) use of special Generac tools, and
(c) use of any tools and/or equipment from other sup
pliers.
Generac cannot possibly know of and advise the
recreational vehicle trade of all conceivable methods,
procedures or techniques by which to perform an
installation. Nor can Generac anticipate every possi
ble hazard that might result from each installation
method, procedure or technique. Generac has not
undertaken any such wide evaluation. Therefore,
people who use a method, procedure or technique
that Generac does not specifically recommend must
first completely satisfy themselves that their safety,
the safety of the vehicle's occupants and the product’s
safety is not endangered by the method, procedure or
technique selected.
Information, illustrations, specifications, etc., con
tained in these Installation Instructions are based on
the latest information available at the time of publi
cation. Every effort has been expended to be sure that
such data is both accurate and current. However, the
manufacturer reserves the right to change, alter or
otherwise improve this product at any time without
prior notice.
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
its maintenance or being careless can cause
possible injury or death. Permit only responsible
and capable persons to operate or maintain this
equipment.
Potentially lethal voltages are generated by
A
these machines. Ensure all steps are taken to
render the machine safe before attempting to
work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running
generators.
^ GENERAL HAZARDS A
• For safety reasons, Generac recommends
that the installation, initial start-up and mainte
nance of this equipment is carried out by a
Generac Authorized Service Dealer.
• The engine exhaust fumes contain carbon monox
ide, which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. This exhaust sys
tem must be installed properly, in strict compli
ance with applicable codes and standards.
Following installation, you must do nothing that
might render the system unsafe or in noncompli
ance with such codes and standards. The genera
tor compartment must be completely vapor sealed
from the vehicle interior. There must be no possi
bility of exhaust fumes entering the vehicle interi
or. Never operate this equipment with a leaking or
defective exhaust system.
• Keep hands, feet, clothing, etc., away from drive
belts, fans, and other moving or hot parts. Never
remove any drive belt or fan guard while the unit is
operating.
• Adequate, unobstructed flow of cooling and venti
lating air is critical to correct generator operation
and is required to expel toxic fumes and fuel
vapors from the generator compartment. Without
sufficient cooling airflow, the engine/generator
quickly overheats, which causes serious damage to
the generator. Do not alter the installation or per
mit even partial blockage of ventilation provisions,
as this can seriously affect safe operation of the
generator.
• When working on this equipment, remain alert at
all times. Never work on the equipment when you
are physically or mentally fatigued.
• Before performing any maintenance on the genera
tor, disconnect its battery cables to prevent acci
dental start up. Disconnect the cable from the bat
tery post indicated by a NEGATIVE, NEG or (-)
first. Reconnect that cable last.
• Never use the generator or any of its parts as a
step. Stepping on the unit can stress and break
parts, and may result in dangerous operating con
ditions from leaking exhaust gases, fuel leakage,
oil leakage, etc.
• Never insert any tool or other object through open
ings in the generator interior, even if the unit is not
running. You might seriously injure yourself or
damage the equipment.
1 S Generac* Power Systems, Inc.
Safety Rules
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
/K
A
ELECTRICAL HAZARDS
The generator covered by this manual produces
dangerous electrical voltages and can cause fatal
electrical shock. Avoid contact with bare wires, ter
minals, connections, etc,, while the unit is running.
Ensure all appropriate covers, guards and barriers
are in place before operating the generator. If you
must work around an operating unit, stand on an
insulated, dry surface to reduce shock hazard.
Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands
or feet are wet. DANGEROUS ELECTRICAL
SHOCK MAY RESULT.
During installation onto the vehicle, properly
ground (bond) the generator either by solid mount
ing to the vehicle frame or chassis, or by means of
an approved bonding conductor. DO NOT connect
the bonding conductor to any generator part that
might be removed or disassembled during routine
maintenance. If the grounding conductor must be
replaced, use only a flexible conductor that is of
No. 8 American Wire Gauge (AWG) copper wire
minimum.
If the vehicle electrical circuits can be powered by
any other source of electricity (such as a "dockside” power receptacle), there must be no possibil
ity of connecting the different power sources to the
vehicle circuits at the same lime. The dockside
(utility) power source must be positively isolated
from the vehicle circuits whenever the generator is
operating. Failure to isolate the vehicle circuits
from the dockside power supply when the genera
tor is running may result in damage to the genera
tor or serious injury or death to dockside (utility)
power workers due to backfeed of electrical ener
A
gy-
In case of accident caused by electric shock, imme
diately shut down the source of electrical power. If
this is not possible, attempt to free the victim from
the live conductor. AVOID DIRECT CONTACT
WITH THE VICTIM. Use a nonconducting imple
ment, such as a rope or board, to free the victim
from the live conductor. If the victim is uncon
scious, apply first aid and get immediate medical
help.
Never wear jewelry when working on this equip
ment. Jewelry can conduct electricity resulting in
electric shock, or may get caught in moving com
ponents causing injury.
A
FIRE HAZARDS
For fire safety, the generator must be installed and
maintained properly. Installation always must
comply with applicable codes, standards, laws and
regulations. Adhere strictly to local, state and
national electrical and building codes. Comply
with regulations the Occupational Safety and
Health Administration (OSHA) has established.
Also, ensure that the generator is installed in
accordance with the manufacturer's instructions
and recommendations. Following proper installa
tion, do nothing that might alter a safe installation
and render the unit in noncompliance with the
aforementioned codes, standards, laws and regu
lations.
Keep a fire extinguisher in the vehicle at all times.
Extinguishers rated ‘ABC” by the National Fire
Protection Association £ire appropriate for use on
the recreational vehicle generator electrical system.
Keep the extinguisher properly charged and be
familial' with its use. If you have any question per
taining to fire extinguishers, consult your local fire
department.
EXPLOSION HAZARDS
Do not smoke around the generator. Wipe up any
fuel or oil spills immediately. Ensure tliat no com
bustible materials are left in the generator com
partment, or on or near the generator, as FIRE or
EXPLOSION may result. Keep the area surround
ing the generator clean and free from debris.
Gasoline is extremely FLAMMABLE and its vapors
are EXPLOSIVE. Do not permit smoking, open
flame, sparks or any source of heat in the vicinity
while handling gasoline. Comply with all laws gov
erning the storage and handling of gasoline.
Fuel lines must be properly installed and
fastened, and free of leaks. There must be
no possibility of gasoline vapors entering the vehi
cle interior.
You are required to install an approved, flexible,
nonconductive fuel line between the generator fuel
connection point and rigid fuel lines.
If the generator is equipped with a liquid propane
(LP) gas fuel system, install the unit so it complies
with all codes, standards and regulations pertain
ing to such systems. LP gas is highly explosive. The
gas tends to settle in low areas where even the
slightest spark can ignite it and cause an explo
sion. Do not allow gas vapors to enter the vehicle.
A
A
Benerac® Power Systems, Inc. 1 B
GENERAL
INFORMATION
Section 5 - General Information
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
5.1 PURPOSE ÄND SCOPE OF THE
INSTALLATION INSTRUCTIONS
These Installation Instructionshave been prepared
especially for the purpose of familiarizing installers and
owners of the applicable equipment with the product's
installation requirements. Give serious consideration to
all information and instructions in the manual, both for
safety and for continued reliable operation of the equip
ment.
Because of the different recreational vehicle models and
the variations between the models, it would be extremely
difficult, if not Impractical, to provide detailed instruc
tions for every possible installation. For that reason,
instructions and illustrations in this manual are general
in nature. Illustrations are not intended to serve as
detailed installation blueprints.
The installation should comply strictly with all applica
ble codes, standards and regulations pertaining to the
installation and use of this product. If any portion of
this manual appears to be in conflict with such codes,
standards or regulations, the applicable codes, stan
dards or regulations must take precedence over the
manual.
5.2 SAFETY
Before handling, installing, operating or servicing this
equipment, carefully read the “Notice to Installer” and
“Safely Rules” on Pages 18 and 19. Comply with all safe
ty rules to prevent death, personal injury or damage to
equipment and/or property. Stress safety to all
installers, operators and service technicians who work
on this equipment.
5.3 STANDARDS BOOKLETS
Installation, use and servicing of this equipment should
comply strictly with published standards, as well as the
manufacturer's recommendations. The following stan
dards booklets (latest revision) are available from the
sources indicated:
1. NFPA Standard 501C, "Standard for Recreational
Vehicles,” available from the National Fire
Protection Association, Batterymarch Park, Quincy,
MA 02269.
2. NFPA 70, “NFPA Handbook of the National Electric
Code," available same as Item 1.
3. ANSI Cl-1975 and ANSI 119.2-1975, available from
the American National Standards Institute, 1430
Broadway, New York, NY 10018.
4. ANSI A119.2/NFPA 501C, available from the
Recreational Vehicle Association, 1896 Preston
White Drive, Reston, VA 22090.
5. California Administrative Code, Idtle 25, available
from the State of California, Documents Section,
PO. Box 1015, North Highlands, CA 95660.
20 Generac* Power Systems, !nc.
6. CSA Electrical Bulletin 946, available from the
Canadian Standards Association, Housing and
Constructions Materials Section, 178 Rexdale
Boulevard, Rexdale, Ontario, Canada, M9W 1R3.
5.4 EQUiPIVIENT DESCRIPTION
Instructions and information in this section pertain to
Generac air-cooled generators. These generators are
designed specifically for installing in recreational vehi
cles. They operate 120-volt, single-phase, 60-Hertz, AC
electrical loads that require 55.0 amps (gasoline) or
51.7 amps (LP fuel) at 120 volts.
5.5 GENERATOR ENGINE
OPERATING SPEED
The generator’s revolving field (rotor) is driven by a sin
gle-cylinder, four-cycle engine through a pulley and drive
belt arrangement. The generator supplies 120 volts AC
at 60 Hertz when the rotor is operating at 3,600
rpm.The drive belt arrangement allows the engine to
operate at a lower speed than the rotor.
5.6 GENERATOR AC
CONNECTION SYSTEM
These air-cooled generator sets are equipped with dual
stator AC power windings. These two stator windings
supply electrical power to customer electrical loads by
means of a dual 2-wire connection system.
Generators may be installed to provide the following
outputs:
1) 120 VAC loads only — one load with a maximum total
wattage requirement equal to the generator’s rated
power output (in watts), and 120V across the generator
output terminals. (See Fig. 5.1 below)
2) 120/240 VAC loads — one load with a maximum total
wattage requirement equal to the generator’s rated
power output, and 240 V across the generator output
terminals; or two seperate loads, each with a maximum
total wattage requirement equal to half of the genera
tor’s rated power output (in watts), and 120 V across
the generator output terminals. (See Fig. 5.3 on page 22)
Figure 5.1 - Connection for 120 Volts Only
GROUNDED
NEUTRAL
Section 5 - General Information
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
• The AC connection system on all air-cooled
PRIMEPACT series generators uses a GROUNDED
neutral.
• A separate green ground wire is connected to the
recreational vehicle’s junction box.
• Loads connected across T1 (Red) to T2 (White), and
T3 (Black) to T2 (White), must not exceed 27.5 amps
for PrimePacl 66G, or 25.8 amps for PrimePact 66LP
with a voltage of 120V across each set of terminals.
NOTE:
Do NOT connect loads in excess of eircuit
breaker ratings.
6.1 LOCATION AND SUPPORT
• 6.1.1 GENERATOR LOCATION
The most desirable location for the generator set is
between the vehicle's main frame members. However,
this is seldom possible. Most units must be installed on
the side of the vehicle and are difficult to reinforce.
Many recreational vehicles have been factory equipped
with an area for the generator set. Some vehicles may
even have a generator compartment provided by the
vehicle manufacturer.
Plan the generator location based on the following:
• The generator set must be installed on a framework
that is part of the recreational vehicle, as outlined in
Section 6.1.2.
• The location must provide an access opening that is
large enough to permit generator removal (unless the
generator is to be removed from underneath the sup
porting framework).
• The location must provide easy access to frequently
serviced components, such as filters, oil drains,
spark plugs and other common maintenance parts.
• The location must provide sufficient room to allow
minimum clearances as outlined in Section 6.2. If
sound insulation is to be used on the compartment
* •
walls and ceiling, the minimum recommended
applies to the space between the generator and such
insulation.
• The location must provide adequate cooling and ven
tilating airflow for the generator without a great deal
of work and expense.
• 6.1.2 GENERATOR SUPPORT
__________________
The generator must be securely attached to a metal
framework that has been made part of the vehicle frame
structure by bolting or welding. The metal framework
on which the generator will rest and which will restrain
the generator set should consist of at least two horizon
tal beams. These beams should consist of (a) 1-1/2-inch
square, 11 -gauge steel tubing OR (b) 1-1/2-inch, 11gauge angle iron. A typical supporting frame with hori
zontal support tubing, is shown in Figure 6.1.
The generator can be installed so that it sits on top of
the horizontal support tubing if the vehicle design per
mits. Another method is to suspend the generator below
the horizontal support tubing by means of suitable,
structurally sound metal framework The following gen
eral rules apply:
• Vehicle construction MUST be capable of supporting
the weight of the generator.
• Whether the generator is mounted above the horizon
tal support tubing or suspended below the tubing, the
supporting frame used must be structurally sound.
• If the generator cannot be bolted directly to
the supporting frame or support tubing, consider
using additional tubing, angle brackets
or other supports to give the supporting frame suffi
cient strength.
Figure 6.1 - Typical Horizontal Support Frame
♦ 6.1.3 SUSPENDED MOUNTING
_____________________
If you are going to suspend the generator below the hor
izontal support tubing, the suspension method you use
with the vehicle frame members must (a) be able to sup
port the weight of the generator AND (b) provide suffi
cient restraint for the generator. One typical suspended
mounting system is shown in Figure 6.2. The location of
a suspended mounting system must be carefully
planned, keeping the following general rules in mind:
22 Generac® Power Systems, Inc.
Section 6 - Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
Protect the generator against road splash and debris.
Baffles or splash guards may be required to protect cer
tain areas of the generator. To make sure the generator
is adequately protected, road test tire installation
through mud, water and slush.
Figure 6.2 - Typical Suspended Mounting System
GENERATOR MOUNTING
HOLES FOR 3/8"-16
BOLTS (BOTH SIDES)
• The installer must make certain that the selected
location will permit adequate cooling and ventilating
airflow to be supplied.
♦ 6.1.4 GENERATOR RESTRAINT
Use four 3/8"-16 hardened steel bolts (Grade 5) to fasten
the generator to the supporting frame or the support tub
ing. These bolts must pass through (a) the generator
mounting base, (b) tlie compartment floor (if a compart
ment is used) and (c) the supporting framework
(Figure 6.3). All bolts must be long enough so that when
tight, at least three threads are visible past the retaining
lock nuts. Refer to Section 6.2 for the location of the gen
erator mounting holes.
Figure 6.3 - Typical Generator Restraint
from the back for air circulation .ATTER the compart
ment has been lined with metal and sound insulation
(Figure 6.4).
NOTE;
Refer to “Figure 5.2
Major Features and
Dimensions” on Page 21.
Figure 6.4 - Clearances
• 6.2.2 COMPARTMENT CONSTRUaiON
•
• The generator compartment should be either con
structed of, or lined with, 26-gauge galvanized steel.
NOTE:
Aluminum is NOT an acceptable alternative
to galvanized steel due to aluminum’s low
melting point.
• If the compartment is lined with galvanized steel, it
may be constructed of any material. Generac recom
mends that the compartment be constructed of 1/2inch thick plywood (not strandboard), with the floor
made of a double thickness of 1/2-inch plywood with
the grain of the wood at cross section for added
strength (Figure 6,5).
6.2 GENERATOR COMPARTMENTS
Whether the generator set is being installed inside a com
partment specifically manufactured to house a generator
or inside a compartment tliat the installer constructs, the
compartment MUST meet certain specifications as out
lined in the following sections:
♦ 6.2.1 COMPARTMENT SIZE
Plan the compartment size carefully. Provide a mini
mum clearance of 1/2 inch (13 mm) on the front and
top, 1 inch (25 mm) on the sides, and 1/2 inch (13 mm)
• If constructing a compartment, line the exterior
(underside) of the compartment floor with 26-gauge
galvanized steel.
• All seams, splices and joints of the compartment
walls (unless vapor tight by design) should be
caulked to prevent poisonous, flammable or explo
sive vapors from entering the vehicle interior,
NOTE;
Caulking must be done so that the caulking material
will stay in place permanently. Pressing such materi
als as putty tape onto joints and seams is not accept
able. A high quality silicone rubber base sealant is
recommended.
• Holes and openings made in the compartment walls
to allow for the passage of electrical conduit, conduc
tors, hoses, cables, etc., into the vehicle living area
must be sealed vapor tight with silicone rubber base
sealant.
• If flexible metal conduit is used, it must be sealed
internally at the end where it terminates inside the
compartment’s electrical junction box.
NOTE:
Flexible metal conduit, due to its unique construc
tion, is NOT vapor tight along its entire length.
• Seams and joints of the galvanized steel (whether
used as a liner or for the compartment itself) must be
lapped and mechanically secured. Such seams may
be manufactured, welded, bolted, riveted or screwed.
Manufactured lock seams are shown in Figure 6.6.
Installer constructed compartments typically utilize a
standard lap joint.
Figure 6.6 - Types of Lock Seams
IL Iff a
LOCKED STANDING H I
* 1 OFF SI
DOUBLE LOCK DOUBLE!
STAKDARD LAP JOINT
r
WHE LOCH
After the compartment has been metal lined and
vapor sealed, line the compartment interior walls and
ceiling with an approved, nonflammable sound insu
lating material. See Section 6.2.3.
DANGER
Do not install any flammable material directly
A
above or around the compartment. Heat,
S'liJ Generac* Power Systems, Inc.
transferred through the compartment structure,
may be sufficient to ignite, char or discolor
seat cushions, fiberboard and other flammable
materials. You may need to use approved
nonflammable insulating materials in high
temperature areas.
♦ 6.2.3 SOUND INSULATING MATERIALS
______________
Once installers have determined that a compartment is
properly constructed and metal lined, they can add
acoustical material. This may include additional sealant
or insulating material, to reflect noise away from the
vehicle interior.
Sound insulating materials should be of a nonflamma
ble type. One excellent insulating material is a 1 -inch
(25 mm) thick fiberglass having a 2-pound density.
When fiberglass is used, its coated side should face
toward the compartment interior.
DANGER
A Do not install sound insulation or any absorbent
material on the compartment floor interior. Such
materials will become soaked with combustible or
explosive vapors and liquids and will become a
fire hazard.
Using a combination of sound insulating materials can
often reduce noise more effectively than a single mater
ial. For example, a sheet of lead or visco-elastic materi
al, along with a layer of other acoustical material, is
more effective than when a single material is used.
• 6.2.4 ACOUSTICS
For additional noise abatement, the installer may wish
to consider the following:
• Using special sound insulating materials.
• Construction of a special noise abatement compart
ment.
Any method used to reduce noise must not adverse
ly affect the flow of cooling and ventilating air into or
out of the compartment.
In addition to the effective use of sound insulating mate
rials, construction of a special noise abatement com
partment might be considered to reduce noise levels.
Such a compartment might be construe Led as follows
(Figure 6.7, page 25):
• Use 5/8-inch thick or 3/4-inch thick plywood in the
compartment.
• Construct the compartment floor of a double thick
ness of 5/8-inch or 3/4-inch plywood.
• Line the compartment interior walls and floor, as well
as the underside of the floor, with 26-gauge galva
nized steel.
•
NOTE:
Section 6 - Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
Vapor seal all compartment seams and joints.
Over the galvanized steel lining, install a combination
of acoustical materials as mentioned in Section 6.2.3.
DANGER
To prevent fire or explosion, do not install any
insulation or other absorbent materials on the
interior or underside of the compartment floor.
• Seal all compartment door edges to prevent noise
leakage around the door perimeter.
• Line the compartment door interior (except for air
openings) with suitable, fireproof sound insulation
(such as 1 -inch (25 mm) thick fiberglass with a 2-
pound density).
Figure 6.8 — Compartment Floor Cutout
Figure 6.7 - Typical Noise Abatement
INSTALLATION
Section 6 - Installation
PRIWIEPACT 66G and 66LP Recreational Vehicle Generators
• 6.2.5 COMPARTMENT FLOOR CUTOUTS
___________
You must provide openings in the generator compart
ment for the following items (Figure 6.8, Page 25):
• Engine exhaust and cooling air outlets
• Generator cooling air inlet
• Four holes for passage of generator mounting bolts.
See Section 6.1.4 (Page 23).
DANGER
Fuel lines and exhaust piping must not penetrate
A
into the vehicle living area.
6.3 COOLING AND VENTILATING AIR
It is absolutely essential that an adequate flow of air for
cooling, ventilating and engine combustion be supplied
to the generator set. Without sufficient airflow, the
engine/generator quickly overheats. Such overheating
can cause serious operating difficulties and also may
cause fire and personal injury. The installer must make
sure that sufficient air is available to the generator for
cooling, ventilating and combustion. The installer also
must provide for a path for exhausting the cooling air to
the exterior of a compartment, if so equipped.
♦ 6.3.2 COOLING AIR INLET OPENINGS
_______________
The minimum size of the air inlet opening, whether the
generator is housed in a conventional compartment or
not, is at least 100 square inches (see Figure 6.10).
This rule applies whether inlet air is brought in through
an opening in the compartment door, an opening in the
vehicle skirt, through ductwork, or by any other means.
NOTE:
Screening, louvers or expanded metal that cover air
openings restrict airflow. You must compensate for
this by making the actual air opening proportionate
ly larger. See Section 6.3.3 (Page 27).
Figure 6.10 - Air inlet in Compartment Door
100 SQUARE INCHES
UNRESTRICTED
MINIMUM OPENINGS
DANGER
Never use discharged cooling air for heating or
A
permit such air to enter the vehicle interior. This
air contains deadly carbon monoxide gas and
other poisonous, flammable or explosive gases.
♦ 6.3.1 GENERATOR AIRFLOW
Engine operation drives cooling fans for the two-stage
cooling air system. A pressure fan draws cooling air into
the top of the generator (Figure 6.9). This airflow cools
the engine/generator and electronic components. The
second part of the cooling system, a suction fan, draws
air that is heated from a hot engine into a collector pan
at the base of the unit. This heated air (although cooler
than exhaust muffler) is then deflected out the bottom
toward the ground.
Figure 6.9 - Airflow Through Engine/Generator
NOTE:
Be sure to meet the minimum clearances illustrated
in Figure 6.4 (Page 23).
When the unit is installed on a suspended mounting
system, one of several different methods of supplying
airflow may be used as follows:
• Provide a door in the vehicle skirt having an air inlet
opening (Figure 6.11).
Figure 6.11 - Suspended Mount: Inlet Door
26 Generac* Power Systems,
Using ductwork (Figure 6.12, Page 27). The installer
must be sure air is available to the top of the genera
tor since air inlets are located at the top.
By providing an opening in the vehicle skirt and space
Section 6 - Instaffation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
behind the generator for cooling airflow
(Figure 6.13 ). Recommended clearance behind the
back of the generator is at least 1/2 inch (13 mm).
Figure 6.12 - Air Inlet Using Ductwork
ANTI-SPLASH
Figure 6.13 - Air Inlet in Vehicle Skirt
♦ 6.5.4 TESTING THE INSTALLATION__________________
Generac recommends testing the installation to be sure
adequate cooling airflow is available to the unit before
placing the unit into service. If the unit shows signs of
overheating, you will need to enlarge the air openings.
Never place a unit into service until absolutely certain
that cooling and ventilation is adequate.
NOTE:
You must test the installation, especially if you bring
in air from below the generator set.
6.4 GASOLINE FUEL SYSTEIVI
The installation of a gasoline fuel system (Figure 6.14)
for a recreational vehicle generator set must comply
with applicable codes, standards and regulations. The
entire fuel system must be completely free of leaks.
There must be no possibility of gasoline vapors entering
the vehicle interior.
Figure 6.14 - Generator Fuel System
♦ 6.3.3 COMPENSATING FOR RESTRICTIONS
Such materials as screening, louvers or expanded metal
can restrict the free flow of air. Compensate for this
restriction by making the actual air opening propor
tionately larger.
Some materials may offer only a 60 percent “free air
inlet area.” Other more efficient materials may provide
up to a 90 percent free air inlet area. The percentage of
free air inlet opening is usually available from the mate
rial supplier or manufacturer.
To determine the actual air inlet opening size
required, divide 100 square inches by the percent
age of free air inlet area for the material you will use.
For example: If you plan to use screening with an 80
percent free air inlet area, divide 100 by 0.8, which
results in 125 square inches. Minimum actual size of
air inlet opening in this case is 125 square inches.
DANGER
Gasoline is highly flammable, and its vapors are
A
explosive. Comply with all codes, standards and
regulations pertaining to gasoline fuel systems
used in recreational vehicle generators. Properly
install and maintain the fuel system and keep it
entirely free of leaks. Gasoline vapors must not
enter the vehicle interior.
Factory installed generator fuel system components
include (a) fuel filter, (b) 12-volt DC electric pump, (c)
engine carburetor, and (d) interconnecting lines and fit
tings. Connect a fuel supply line to the fuel filter inlet.
Use a flexible length of approved fuel hose between the
fuel filter inlet connection and rigid fuel lines.
Either the generator must share the vehicle engine’s fuel
tank, or you must install a separate fuel tank for the
generator set. All fuel tanks installed on the vehicle
must be constructed, installed and restrained so they
comply with applicable codes, standards and regula
tions.
If the generator is to share the vehicle engine's tank, sep
arate fuel pickup tubes are required for the engine and
the generator. Generac recommends that you make the
fuel pickup tube 2 to 3 inches (51 to 76 mm) shorter
than the vehicle engine's pickup tube. This prevents the
generator from depleting the entire fuel supply during
prolonged generator operating periods.
------
ik CAUTION Mk
Do NOT tee the generator fuel supply line into
A
the vehicle engine fuel supply line. If this is done,
the generator will be starved of fuel when both
engines are operating at the same time. Also,
while the vehicle engine is not running, generator
operation may drain the vehicle engine supply
line, making it difficult to start the vehicle engine.
♦ 6.4.2 GENERATOR FUEL SUPPLY LINE
6.4.2.1 Rigid Fuel Lines
----------
___________
Those lines used to supply fuel from a tank to the gen
erator must comply with applicable codes, standards
and regulations. The following general rules apply to
rigid fuel lines:
• Rigid lines should be of annealed, seamless, drawn
aluminum or steel.
• Lines and fittings must comply with SAE J512F,
“Standard Automotive Fittings,” or with ANSI
B126.26 (latest edition).
• Route the fuel line so that at least 2 inches (51 mm)
of clearance is maintained between the line and any
exhaust system parts.
• Do not attach electrical wiring to fuel lines. Route the
wiring so it cannot come into contact with any fuel
line.
“ Route fuel lines so if they leak, fuel does not drip onto
any electrical or exhaust system parts.
• Use nonferrous metal straps without sharp edges to
secure fuel lines.
• The hose should be at least 6 inches (152 mm) longer
than is needed to prevent the hose from rupturing if
the generator shifts or settles.
6.5 LP GAS FUEL SYSTEM
—A mm A—
A LP gas is highly EXPLOSIVE. The gas is heavier
than air and tends to settle in low areas. Even the
slightest spark can ignite it and cause and explo
sion. Only competent, qualified people should be
allowed to install, test, adjust or service an LP gas
fuel system. Install the optional fuel system in
compliance with applicable codes, standards and
regulations. After the installation, do not do any
thing that might render the system in noncompli
ance with applicable codes and standards.
The LP powered range of generators are fitted with a
nonadjustable, factory set system. These systems are
tamper-proof to meet 1997 California Air Resources
Board requirements for engine emission.
♦ 6.5.1 PARTS NOT INCLUDED IN FUEL SYSTEM
The propane fuel system does NOT include such items
as (a) gas tank, (b) gas piping, (c) fittings, (d) valves, and
(e) primary regulator, used to store the gaseous fuel and
deliver it to the gaseous fuel solenoid (Figure 2.15, Page
29).
DANGER
Use only approved components in the fuel supply
system. All components must be properly installed
in accordance with applicable codes. Improper
installation or use of unauthorized components
may result in fire or an explosion. Follow
approved methods to test the system for leaks.
No leakage is permitted. Do not allow fuel vapors
to enter the vehicle interior.
6.4.2.2 Flexible Fuel Line
Use an approved flexible length of fuel hose between the
generator fuel inlet connection and rigid fuel lines. This
prevents breaking of the line caused by vibration, shift
ing, settling or movement. The following rules apply:
• The flexible hose must comply with SAE J30B,
"Standard for Fuel and Oil Hose.” It must be
approved for use with gasoline.
SS Generac* Power Systems, Inc.
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
Figure 6.15 - Typical Propane Gas Fuel System ♦ 6.5.4 PRIMARY REGULATOR
Gas pressure delivered to the solenoid valve must be
properly regulated by means of a primary gas regulator.
Mount the primary regulator at the gas tank outlet or in
the supply line from the gas tank. The following rules
apply:
• For best results, the primary regulator supplies
gaseous fuel to the secondary regulator at 11 inches
water column. Do
umn.
• The Installer must be sure the primary regulator is
rated at sufficient gas flow to operate the generator
plus all other gas appliances in the circuit.
Recommended MINIMUM gas flow rate for all air
cooled PRIMEPACT series generators is 67 cubic feet
per hour.
If an existing primary gas regulator does not have a
sufficient flow capacity for the generator and other
gas appliances in the circuit, (a) install a primary
regulator with adequate flow rate, or (b) install a sep
arate regulator only and rated at least 67 cubic feet
per hour. The inlet side of any primary regulator that
supplies the generator must connect directly to a gas
• 6.5.2 SOME IMPORTANT CONSiPERATiONS
When installing an LP gas system, consider seriously
pressure tank. Do NOT tee
gas circuit feeding other areas.
the following items;
• All fittings, lines, hoses and clamps must be tight and
free of leaks. Apply a pipe sealant to threads when
assembling threaded connections. This reduces the
possibility of leakage.
• Test the entire fuel system for leaks using approved
test methods.
® Optimum gas pressure at the inlet to the gaseous fuel
solenoid valve and secondary regulator is 11 inches
water column.
*> The installer’s fuel supply connection point is at the
gaseous fuel solenoid valve. This is a 3/4-inch
(female) connection. Provide a suitable 3/4-inch NPT
(male) connector to attach to the fuel supply line.
• Use a length of approved flexible fuel hose between
• 6.5.5 GASEOUS CARBURETION
LP gas vapors should be supplied to the secondary reg
ulator inlet at about 11 inches water column (positive
pressure). The engine pistons draw air in during the
intake stroke (Figure 6.16). This air passes through a
carburetor venturi, which creates a low pressure that is
proportional to the quantity of air being pumped. The
low pressure from the carburetor venturi acts on the
regulator diaphragm to pull the diaphragm toward the
source of low pressure. A lever attached to the
diaphragm opens a valve to permit gas glow through the
carburetor.
Figure 6.16 - LP Gas Carburetion Diagram
the gaseous fuel solenoid valve and rigid gas piping.
The flexible line should be at least 6 inches longer
than necessary.
• 6.5.3 VAPOR WITHDRAWAL
LP gas is stored in pressure tanks as a liquid. The gas
systems used with these generators were designed only
for vapor withdrawal type systems. Vapor withdrawal
systems use the gas vapors that form above the liquid
fuel in the tank. Do NOT attempt to use the generator
LOW PRESSURE
AREA
with any liquid withdrawal type system.
Section 6 - Installation
NOT exceed 14 inches water col
NOTE:
GAS AT
ZERO PRESSURE
INSTALLATION
the
generator line into a
____________
GAS AT
POSrnVE
PRESSURE
______
Oenerac* Power Systems, Inc. H3
INSTALLATION
Section 6 - Installation
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
llie greater the airflow through the carburetor venturi,
the lower the pressure at the venturi throat. The lower
the pressure at the venturi throat, the greater the
diaphragm movement, and tlie greater the movement of
the regulator valve. The more the regulator valve opens,
the greater the gas How that is proportional to airflow
through the generator.
The following facts about the secondary regulator must
be emphasized:
• The regulator must be sensitive to venliui throat
pressure changes throughout the operating range.
• The regulator must be properly adjusted so it will
stop the flow of gas when the engine is not running
(no air flow through the carburetor).
• The siiglitest airflow (and vacuum in the venturi
throat) should move the regulator valve off its seat
and permit gas to flow.
• 6.5.6 FUEL SUPPLY LINES
• LP gas lines must be accessible, but protected against
possible damage.
• Do NO'F connect electrical wiring to any LP gas fuel
line or run wiring alongside the lines.
• Ffoute gas lines away from hot engine exhausts.
• Retain gas lines with metal clamps that do not have
sharp edges.
• Install an approved lengl.h of flexible hose between
the gaseous fuel solenoid valve and rigid fuel supply
lines. Tlie flexible line must be nonmetallic, nonor-
ganlc and noiicondiiclive. It must be approved for use
with LP gas,
• 6.5.7 EXCESS FLOW VALVE
LP gas tanks should have an excess flow valve, accord
ing to NFPA 501C, Para.grapli 3-4.4. This valve and the
gas lines must be carefully sized so the valve will close
when a fuel line is severed or broken. Coiisull the
Natural-LP Gas Association for information and limita
tions of excess flow valves.
Manual shutoff valves on the supply tank and elsewhere
in the system must be fully open when operating the
generator. The excess flow valve functions properly only
if all valves are fully open.
♦ 6.5.8 LEAKAGE TESTS
Do not place the generator into service until you have
properly tested the gas system for leaks. To lest the sys
tem. you need a separate source of 12 volts DC to open
the gaseous fuel solenoid valve.
The leak test must comply fully with NFPA, Paragraph
318. All connections, hoses, valve regulators, fittings,
and other fuel system parts must be tested under gas or
air pressure of not less than 90 psi (620 kPa), while
using soap and water or an equivalent solution to check
for leaks. Other approved methods of testing for leaks
may be used, if appropriate. DO NOT USE ANY FLAMFi
TO TEST FOR LEAKS.
DANGER
Gaseous fuel lines between the tank and the sec
A
ondary regulator are under a positive pressure
(about 11 inches water column). Gas pressure at
the outlet side of the secondary regulator, howev
er, is a negative pressure and can draw flame
inside a line or fitting and cause an explosion.
6.6
The generator exhaust system must be safely and prop
erly installed. Only approved mufflers and other^
exhaust system parts mu.st be used. A properly installed
exhaust system must be vaf)or tight, quiet and cornjrletely safe.
The jt ri-’cmh r siiqinfi giro:- off DEADLY carbon
luon'i’uih <jci ihiruqb 'Г f xhauit system. This
dang-r.Ki fjas li bi- in '.ufficient concentra
tions, tan c -u or even death.
Nevor up,tfie gen- afo* set with the vehicle
irijidu ariv А'Л i •rthm enclosed area. DO NOT
OPFP'UT nir t s flEF.A ПН IF ТЧЁ EXHAUST SYS-
lEiVl !'i I L'-Tif'" ПГ NA - flfr.N DAMAGED. SYMPТОМ' or •'.'GflON sVOiMOXlDf POISONING ARE
(d) iriai* ’ity li. .hiri’-c M ib) vomiting; (c)
twitdiing mu.des itl; biiobbing temples; (e)
dizzir-e ^t) Is'dduvd» . (g) vw akness; and (h)
sieeoifi'm К /Oi" -tfLAtJ'» OF THESE SYMP
TOMS. iVJtiVF INFO Fhi ..H All IMMEDIATELY. IF
SYMPfOMS PLRSISi w T MLDiCAL HELP. Do not
operate the gt-rierato' until its exhaust system has
been inspected and properly repaired.
------
M, CAUTION --------------
Never tee the generator engine exhaust pipe into
A
the vehicle engine exhaust piping. This causes
excessive back pressure on the generator engine.
Also, water from one engine can damage the
other engine.
♦ 6.6.1 MUFFLERS AND SPARK ARRESTORS
This muffler meets code and standard requirements of
(he U.S. Forest Service. Use only mufflers and parts
approved by Geiierac. Any p)erson(s) installing an unap
proved muffler, or an unapproved exhaust system part,
or modifying an exhaust system in any way that might
cause a hazard, is liable for any damage, injury or war
ranty expense that might be caused by such unapproved
installation or modification.
30 Generac® Power Systems, tnc.
Section 6 - Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
Failure to provide and maintain a spark arrestor may be
in violation of the law. If this generator is used on any
forest covered, brush covered or grass covered unim
proved land, you must provide a spark arrestor. The
vehicle owner or operator must maintain this device in
good condition. In the state of California, the preceding
is required by law (Section 4442 of the California Public
Resources Code), Other states may have similar laws.
Federal laws apply on federal lands,
• 6.6.2 TYPE OF EXHAUST SYSTEM
l\vo types of exhaust systems for PRIMEPACT series
generators are available ifrom Generac. They include the
following:
• “Out-the-bottorn” exhaust system dimensions are
1 5/16” O.D., model 9742.
• “Out-the-side” exhaust system dimensions are
1” O.D., 18 gauge, models 9743 and 9326.
NOTE:
No matter what type of exhaust kit best fits your
recreational vehicle, the mounting base has open
ings for either “bottom-out” or “side-out” exhaust
systems. Use the cover plate provided with the gen
erator to cover the opening you do NOT use.
• 6.6.3 EXHAUST SYSTEM SAFETY
* •
• Maintain a clearance of at least 3 inches (76 mm)
between exliaust system parts and any combustible
material (such as wood, felt, cotton, organic fibers or
other like material). If you cannot maintain the 3-iiich
(76 mm) clearance, locate, insulate or shield the
exhaust part(s) so that the temperature of any com
bustible material is not raised more than 117° F (65°
C) above the ambient air temperature.
• Extend the exhaust system at least 1 inch (25 mm)
past the outer edge of the vehicle. Do not terminate
the exhaust system under the vehicle,
• Terminate the exhaust tailpipe such that exhaust
gases will not be drawn back into the generator com
partment and recirculated.
• If there is any possibility of the tailpipe or muffler
being damaged, protect these damage-prone areas by
means of a protective device (such as a skid bar).
• Install the generator exhaust system according to safe
automotive practices.
• Use enough exhaust system hangers to prevent any
part of the system from being dislocated.
• Use exhaust system parts recommended by Generac.
Using unapproved exhaust mufflers and exhaust sys
tem parts is the responsibility of the person(s)
Installing such unauthorized parts.
• Do not terminate the exhaust system under any open
ing, window or vent that can be opened or is not per
manently sealed from the vehicle interior.
• Exhaust piping must be large enough to prevent
excessive back pressure on the generator engine.
• Never tee the generator engine exhaust pipe into the
vehicle engine exhaust piping. This causes excessive
back pressure on the generator engine. Also, water
from one engine can damage the other engine.
• Plan exhaust system Installation carefully. Comply
with all applicable codes, standards and regulations.
6.7 ELECTRICAL CONNECTIONS
Be sure to read Section 5.6 on Page 20.
The following general rules apply to electrical connec
tions in a recreational vehicle:
• Qualified electricians who are familiar with applica
ble codes, standards and regulations should install
electrical wiring.
• The wiring should comply with codes, standards and
regulations. The National Electrical Code (NFPA 70),
and state and local codes apply.
• Switches and circuit breakers should be of a type
approved for use in recreational vehicles and must be
mounted and installed to prevent damage Ixorn road
shock.
• Wiling must be of adequate size, have approved irisulative qualities and be properly supported.
• Conduit and wire openings into the generator com
partment (if used) must be vapor-sealed to prevent
entry of flammable, explosive or poisonous gases into
the vehicle.
• 6.7.1 ELECTRICAL JUNCTION BOX
Install an approved, square electrical junction box witli
a blank cover on the interior or exterior wall of the area
you plan to install the generator (NOT on the generator).
Route the generator's AC output leads into this junction
box through approved flexible conduit. This is the point
of first termination for generator AC output leads.
• 6.7.2 WIRING
• Wiring should be of stranded copper to reduce the
chance that vibration may cause breakage.
• Wire gauge size should be large enough to handle at
least 115 percent of the installed generator's rated
maximum current.
• If neutral conductors are used, they must be the same
size as other leg wires.
• Route power supply conductors from generator AC
output leads T1 (red), T2 (white), T3 (black) and the
green ground wire through approved flexible conduit
to the electrical junction box on the compartment
wall.
If flexible metal conduit is used between the genera
tor and the compartment junction box, the conduU
end that terminates the compartment junction box
must be vapor-sealed. Flexible metal conduit is NOT
• From the junction box, route power supply wires
through approved conduit to either (a) double-pole,
double-throw transfer switch, or (b) approved isola
tion receptacle. Connecting to a transfer switch or
isolation receptacle must prevent vehicle electrical
circuits from being connected to two different power
supplies at the same time (such as generator and
dockside power).
• Conductors must be rated 221° F (105° C) or must be
of a larger conductor size.
• 6.7.5 GENERATOR AC CONNEQIONS
Generator AC output leads T1 (red), T2 (white) and T3
(black) come out of the generator as shown in
Figure 6.17. Leads T1 (red) and T3 (black) are “hot,”
while T2 (white) is the grounded neutral lead. There is
also a green lead that connects to ground in the junction
box of the recreational vehicle.
Figure 6.17 - Generator AC
Output
Leads
♦ 6.7.4 CONDUIT
Route the connections between the generator and the
junction box through approved, flexible conduit. The
following general rules apply:
• Cut wiring to the required length and allow extra wire
for junction box connections.
• Carefully prepare conduit ends to prevent sharp
edges from cutting through wiring insulation.
• Route conduit so it does not interfere with generator
movement.
• If you use metallic conduit, vapor seal the end of the
conduit where it enters the junction box. Do this
because flexible metallic conduit is not vaporproof
along its entire length.
• 6.7.5 ISOLATING DIFFERENT POWER SOURCES
Connections from the junction box must terminate in a
double-pole, double-throw transfer switch (Figure 6.18,
Page 3.3), An alternate method for isolating different
power sources is by using an Isolating receptacle
(Figure 6.19, Page 33). Whichever method you use, you
must be certain that both power sources are NOT con
nected at the same time.
♦ 6.7.6 POWER SUPPLY CORD
The power supply cord must comply with all applicable
codes, standards and regulations. It must be large
enough to handle the full amperage to which it will be
subjected. (See page 33 for illustration.)
Line T1 (red) to T2 (white) is protected against overload
by a 30-amp circuit breaker (CBl). Use this line-to-neutral connection separately to operate 120-volt, singlephase, 60 Hertz, AC loads requiring up to 3,300 watts
of power for PrimePact 66G or 3,100 watts for
PrimePact 66LP Line T3 (black) to T2 (white) also is
protected against overload by a 30-amp circuit breaker
(CB2). Use this line-to-neutral connection separately to
operate similar loads. However, be sure the total unit
load does not exceed the maximum rating of the gener
ator. The neutral line (T2, white) on all units is a
grounded neutral.
------
M. CAUTION M.-----------
Do NOT connect electrical loads in excess of any
A
circuit breaker rating or you will develop prob
lems with circuit breaker tripping, which causes a
loss of AC output. Also, do NOT exceed the gener
ator's rated wattage capacity. Add the watts or
amperes of all lighting, appliance, tool and motor
loads the generator will operate at one time. This
total should be less than the unit's rated
wattage/amperage capacity.
3S
Generac* Power Systems, Inc.
• 6.7.7 GROUND FAULT CIRCUIT INTERRUPTERS
The National Electrical Code (NFPA 70, 551-7) requires
that you install ground fault circuit interrupters (GFCIs)
on all external and some internal electrical receptacles.
Contact your manufacturer or dealer for recommenda
tions.
6.8 BATTERY INSTALLATION
• 6.8.1 RECOMMENDED BATTERY ________________
Install a battery that meets the following requirements:
• The battery must be a 12-volt, automotive type
storage battery.
• For prevailing ambient temperatures above 32° F (0°
C), use a battery rated 70 amp-hours and capable of
delivering 400 cold-cranking amperes.
• For prevailing ambient temperatures below 32° F (0°
C), use a battery rated 95 amp-hours and capable of
delivering 400 cold-cranking amperes.
NOTE:
If the battery is to be used to power other vehicle
accessories, as well as start the generator, you may
need a battery with a larger capacity.
__
Section 6 - Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
♦ 6.8.2 BATTERY CABLES
Using battery cables that are too long or too small in
diameter may cause a drop in voltage, which causes
starting problems. For the best cold weather starting,
the voltage drop between battery terminals and the gen
erator connection point should not exceed 0.12 volts
per 100 amperes of cranking current.
Figure 6.18 — Transfer Switch Isolation Method
PRIMEPACT generators are rated at about 100 DC
amperes of cranking current.
Select battery cables based on (a) cable length and (b)
prevailing ambient temperatures. Generally, the longer
the cable and the colder the weather, the larger the cable
size must be, as shown in the chart.
2ND AIR
Figure 6.19 — Installation With Isolation Receptacle
Generac* Power Systems, Inc. 33
DOCKSIDE
POWER
RECEPTACLE
POWER
SUPPLY
CORD
INSTALLATION
Section 6 - Installation
PRlMEPACr 66G and 66LP Recreational Vehicle Generators
CABLE LENGTH
in Feet (meters)CABLE SIZE
0 to 10 (0 to 3)2* *
1 1 to 15 (3,4 to 4.5)
16 to 20 (4.5 to 6)
*For warm weather, use No. 2 cable up to 20 feet.
0
000
♦ 6.8.5 BATTERY CABLE CONNECTIONS
1. Connect the battery cable from the battery post or
terminal indicated iay a POSITIVE, POS or ( + ) to the
lug on the starter contactor (Figure 6.20).
NOTE:
Check to be sure the battery cable boot for the
starter cable has been installed.
2. Connect the battery cable from the battery post indi
cated by a NFfGATlVE. NEG or (-) to the frame
ground coimectioii (Figure 6.20).
3.
Connect cables so the connectors are clean
and tight.
Figure 6.20 - Connecting Battery Cables
SIDE VIEW OF GENERATOR
6.9 OPTIONAL ACCESSORIES
A plug-in receptacle (Figure 6.21) is provided on the
generator set, above tlie muffler enclosure. Use this
receptacle to connect an optional remote-mounted
start/stop panel to the generator. Installation of such a
pane! will permit you to start and stop the generator
engine from any convenient location inside the vehicle.
Figure 6.21 - Remote Panel Plug-in Receptacle
[#■ r r;
WIRE #18(STOP)
WIRE #14
(ENGINE RUN
SIGNAL)
WIRE #17
(CRA.NK)
- WIRE #0
(GROUND)
• 6.9.1 REMOTE PANEL MODELS
The remote panels mount a rocker type start/stop
switch, a "Generator Run” advisory lamp and an
hourmeter. The hourrneter should be used in conjunc
tion with the maintenance operations found in Part I of
this manual.
• Model 004057 includes the reinóte panel and a 10
fool long, 4 wire harness.
• Model 004184 includes the remote panel and a 30
foot long. 4 wire harness.
♦ 6.8.4 BATTERY COMPARTMENT
Install the generator battery in its own, vented compart
ment. Place the battery compartment away from any
source of heat, sparks or flame.
Provide ventilation openings in the battery compart
ment. The minimum size of openings should be 2
square inches at the top of the compartment. Mount the
battery on a strong, rigid supporting structure, where
leaks and spills of battery fluid will not cause damage.
34 Generac® Power Systems, Inc.
Section 7 - Post Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
INSTALLATION
II POST INSTALLATION TESTS
The air-cooled generator set was factory tested and
adjusted. You should not be required to adjust the unit
any further except under special circumstances.
-A WARNING A~
Do not make any unnecessary adjustments.
Factory settings are correct for most applications.
A
When making adjustments, however, be careful to
avoid overspeeding the engine.
12 BEFORE INITIAL START-UP
Before starting, complete the following;
1. Check the engine crankcase oil level and, if neces
sary, fill to the dipstick “FULL’ mark (cross-hatched
area) with the recommended oil. Do not fill above
the FULL mark.
Check the fuel supply. Gas fuel lines must have been
2.
properly purged and leak tested in accordance with
applicable fuel codes. All fuel shutoff valves in the
fuel supply lines must be open.
DANGER
If a liquid propane (LP) gas fuel system has been
A
installed, it must be properly tested for leaks
before operating the system in compliance with
ANSI A119.2/NFPA 501C. No leakage is permitted.
You must be sure no gasoline fuel vapors enter
the vehicle interior.
7. Let the unit run at no-load for a few minutes to sta
bilize internal engine/'generator temperatures.
Then, shut down the engine,
NOTE;
The generator set was thoroughly tested and adjust
ed at the factory before shipping. No additional
adjustment should be necessary. Only qualified ser
vice technicians who have been trained should per
form adjustments outlined in this manual.
7.4 TESTING UNDER LOAD
Apply electrical loads equal to about 75 to 100 percent
of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied.
During this part of the test, check that the unit is not
running excessively hot and that adequate cooling air
flow is available. You must not allow the unit to overheat
during prolonged operation.
NOTE:
The generator engine is equipped with a high tem
perature switch. The switch has normally closed
(N.C.) contacts. When the engine temperature is too
high, switch contacts close, and the engine shuts
down automatically.
GENERAC RECOMMENDS THAT YOU TEST THE
GENERATOR FOR ADEQUATE COOLING.
13 INITIAL START
When you are absolutely certain that the unit has been
properly installed and prepared for use, start the engine
as follows:
1.
Turn off all electrical loads. Do this by setting the
generator’s main circuit breakers to their “OFF” (or
open) position.
Refer to Part I, Section 2.5, “Starting the Generator”
2.
(Page 8), for cranking and starting instructions. The
engine may require more cranking for initial start
ing since the fuel lines have to be primed (use of the
primer switch will shorten this time).
Let the engine warm up for about five minutes to
allow internal temperatures to stabilize.
Carefully inspect the engine/generator for fuel, oil
4,
and exhaust system leaks. Before proceeding to the
next step, correct any leakage immediately.
5.
When all tests and adjustments at no-load are com
pleted, apply electrical loads and check for proper
operation under load. See Section 7.4. Run the unit
at least 30 minutes with loads applied.
6.
Turn off all electrical loads by setting the generator’s
main circuit breakers to their “OFF” (or open) posi
tion.
Generac* Power Systems, Inc. 35
INSTALLATION
Section 7 - Post Installation
PRIMEPACT 66G and 66LP Recreational Vehicle Cenerators
7.5 INSTALLATION CHECKLIST
♦ LOCATION AND SUPPORT
lJ Generator is properly located.
U Generator is properly supported.
□ Generator is properly restrained.
♦ GENERATOR COMPARTMENT
□ Coiiipartment construction is proper.
U Holes/Openings are vapror-sealed.
□ Compartment size is correct.
□ Compartment is vapor-sealed.
□ Sound insulation is correct.
□ Floor cutouts are properly completed.
♦ COOLING AND VENTiLATiNG Ali
U Airflow is adequate.
J Air inlet opening is correct.
U Compensate for restrictions.
U Check that installation has been tested.
♦ GASOLINE FUEL SYSTEM
LJ Fuel tank complies with all af)plicable codes.
□ Fuel system is properly installed and checked
for leaks.
♦ OPTIONAL LP GAS FUEL SYSTEM
□ Fuel system is properly installed and checked
for leaks.
□ Pressure at regulator inlet is correct.
□ Rated flow of primary regulator is correct.
□ All parts are properly installed,
□ Fuel system is properly tested/adjusted.
♦ EXHAUST SYSTEM
□ Exhaust system complies with all applicable codes.
□ Exhaust system is properly and safely installed.
♦ ELECTRICAL CONNECTIONS
□ Connections comply with local code requirements
and all National Electrical Codes.
□ Junction box is properly installed.
□ Wiring meets all standards.
□ All connections are correct.
□ Conduit is properly installed and sealed.
□ Generator is properly bonded to the veliicle.
♦ BATTERY INSTALLATION
□ Recommended battery is installed,
□ Recommended cables are iiistalied.
□ Cables are clean and light.
□ Cables are connected properly.
□ Proper ventilation is proCded.
□ Terminal'’ arp coaled wiib anti-corrosion grease, and
terminal coi' t n< po~,>i'.uied.
♦ OPTIONAL ACCLSjORIeS
□ Check that remote start/stop panels (if used) are
installed properly.
□ Check that hour meter kit (if used) is installed
properly.
□ Check that any other options and accessories (if
used) are installed properly.
# POST INSTALLATION TESTS
□ Check that all tests are completed properly.
DATE OF INSTALLATION
NAME OF INSTALLER
SIGNATURE OF INSTALLER
36 Generac* Power Systems, Inc.
8.1 TROUBLESHOOTING GUIDE
Section 8 - Troubleshooting
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
TROUBLESHOOTING
0^
PROBLEM
Engine won’t crank.
Engine cranks, won't start.
Engine starts hard, runs rough.
CAUSE
1.
15 amp fuse blown.
2.Loose, or corroded or defective
battery cable(s).
Battery is discharged or defective.
3.
Defective starter contactor.
4,
5.Defective starter motor.
6.Defective Start/Stop switch.
7.Defective Engine Control Board
1.Out of fuel.
2.Fuel shutoff valve is closed.
3.Fuel pump not operating.
Automatic choke not operating properly.
4.
5.Engine is flooded.
6.Fuel filter is clogged.
7,Engine spark plugs defective..
Bad ignition magneto on engine.
8.
9.Bad carburetor.
Dirty air cleaner.
10,
1.Dirty engine air cleaner.
Automatic choke is sticking.
2.
Defective spark plugs.
3.
4.Defective ignition magneto.
CORRECTION
1,Replace blown fuse.
Tighten, clean or replace,
2.
as necessary.
Recharge or replace battery.
3.
Replace starter contactor.
4.
Replace starter motor.
5.
Replace switch.
6.
Contact an authorized service dealer.
7.
1.Refill fuel tank.
Open fuel shutoff valve(s).
2,
Repair or replace pump.
3.
4.Repair, replace or adju.st.
5.Wait 5-10 minutes; try again.
6.Replace filter if clogged.
7.Clean, regap or replace as needed.
8.Replace if defective.
9.Adjust, repair or replace.
10.Clean or replace as needed.
Clean or replace as needed.
1.
Free choke linkage as needed.
2.
Clean, regap or replace.
3.
4,Replace it if defective.
Engine starts, then shuts down.
No AC output voltage.
Engine oil level is low.
1.
Bad low oil pressure switch.
2.
Defective high temp switch.
3.
4.
Water in fuel.
1,Main breaker(s) open.
Transfer switch (if so equipped) is
2.
set to wrong position.
Failure in vehicle electrical system.
3.
Generator component failure.
4.
1,Add oil as needed.
2.Replace, if bad.
Replace, if bad.
3.
4.Drain fuel tank and refill.
1,Close main breaker(s).
2.Reset transfer switch.
See vehicle manual.
3.
Contact an authorized service facility.
4.
'ü'Mí íí''| j’'(í’0 uM”
ü
ELECTRICAL
^ DATA
Section 9 - Electrical Data
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
Electrical Schematic and Wiring Diagram - Drawing No. D3148-A
0387502M6-1.0 X 30MM HEX HD. CAPSCR.25070108
13037398
14074961
15
0568935#10-24 X 1/2" SCREW
16047227
QTY.DESCRIPTIONITEM
2HOSE CLAMP
4STREET ELBOWS
REGULATOR MOUNTING BRACKET21
M6 LOCK WASHER
HEX LOCK NUT (NYLON)+0287394
1
GOVERNOR ADJUSTER BRACKET+0551629CC
1
1GOVERNOR ADJUSTER SCREW28
PART NO. QTY.
17074962C1
074962G
18066476
190C2338E1
0C2338C1
200759441
0A7782A
220701551
0762422
23
240701251
270731311
061696 1
(-r) NOT SHOWN
50 Generac* Power Systems, Inc.
DESCRIPTION
GOVERNOR SPRING (PP55G/LP, PP66G/LP)
GOVERNOR SPRING (PP70G/LP, Q70G)
1
2
M6-1.0 X 12MM HEX SCREW W/LOCK WASHER
AIR CLEANER DECAL-PRIMEPACT 70LP
AIR CLEANER DECAL-PRIMEPACT 66LP
AIR CLEANER DECAL-PRIMEPACT 55LP
GOVERNOR SPRING BRACKET
FLYWHEEL ASSEMBLY
1
GOVERNOR LEVER
1/8" I.D. X 1/8" RIVET
ANTI-LASH SPRING
GOVERNOR-TO-CARBURETOR ROD
1
4“ LONG TIE WRAP
PIPE SEALANT
AIR CLEANER SUPPORT BRACKET
BARBED 90 DEG. 3/8" X 1/2”
Section 11 — Notes
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
NOTES
Generac* Power Systems, Inc. 5T
Section 12 - Warranty
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (GARB) and the United States Environmental Protection Agency (EPA), together with
Geiierac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new engine.*
New utility, and lawn and garden equipment engines must be designed, built and equipped to meet stringent anti^sinog statu
dards for the state of California and tlie federal government. Generac will warrant the emission control .system on your
engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improjt'
er maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition and exhaust systems. Generac will reptair
your engine at no cost to you for diagnosis, replacement parts and labor, sliould a warrantable condition occur.
MANUFACTURER'S EMISSION CONTROL SYSTEM WARRANTY CO¥ERAGE:
Emissions control systems on 1997 and later model year engines are warranted for two years as hereinafter noted. If, dur^
ing such warranty period, any emlssiomrelated component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warraiiiy Service Facillly.
PURCHASER'S/OWNErS WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you me responsible for the comp)letion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely because of the lack of receipts or for your failure to ensure
the completion of all scheduled maiiiLenaiice.
As the engine purchaser/owner, you should, however, be awaix that Generac may deny any and/or all wan-anty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unajr-^
proved modifications, or the use of counterfeit and/or ’grey market' parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized 'Warranty Service Facility as soon as a prob
lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting eitiier your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California and federal law. See also the “Generac
Limited Warranties for Generac Power Systems, Inc..’’ which is enclosed herewith on a separate sheet, also provided to you
by Generac. The EC,S Warranty applies only to the emission control system of your new engine. If there is any conflict In
terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where
the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe
important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser
vice, evidence must be presented showing the date of the sale to the original purchaser/owner. The purchaser/owner shall
be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the
inspection or repair facilities. The purchaser/owner also shall be responsible for any and/or all damages or losses incurred
while the engine is being transported/shlpped for inspection or warranty repairs.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol
lowing address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, Wl 53190
Part 1
Sa Generac* Power Systems, Inc.
Section 12 - Warranty
PRIMEPACT 66C and 66LP Recreational Vehicle Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines:
(a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall contin
ue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment, and to each subsequent purchaser/owner, that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant
to their respective authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a wds-
ranted emissions-related part to fall to be Identical in all material respects to the part as described in the engine manu
facturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner's
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular Inspection as specified in the Owner's Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace
as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty
shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner's
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi
ble for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proxlmately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emis.sion-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce
Generac’s ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or ‘grey market’ parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or 'grey market’ part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System;
1.1) Gasoline carburetor assembly and its
internal components (if so equipped).
a) Fuel filter (if so equipped)
b) Carburetor gaskets
c) Fuel pump (if so equipped)
1.2) LPG carburetion assembly and its
internal components (if so equipped).
a) Fuel controller (if so equipped)
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
3) Ignition System including;
a) Spark plug
b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
5) Crankcase Breather Assembly including:
a) Breather connection tube
e) LP liquid vaporizer (if so equipped)
*Generac engine types covered by this warranty statement include the following:
1) Utility
2) Lawn and Garden Equipment
3) Recreational Vehicle (RV) Generator
4) Industrial Mobile (IM) Generator
Part 2
Generac* Power Systems, Inc. 53
Section 12 - Warranty
PRIMEPACT 66G and 66LP Recreational Vehicle Generators
GENERAC POWER SYSTEMS' THREE-YEAR LIMITED WARRANTY
FOR RECREATIONAL VEHICLE GENERATORS
NOTE; ALL UNITS MUST BE INSTALLED BY GENERAC POWER SYSTEMS AUTHORIZED SERVICE FACILITIES.
For a period of 3 (three) years or 2.000 (two thousand) liours of operation from the date of original sale, whichever occurs first. Generar
Power Systems. Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or
a Generac Authorized Warranty Service Facility, is found to be defective under normal use and service, in accordance with the warranty
schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be returned to and examined by the nearest
Generac Authorized Warranty Service Facility. All transportation costs under the warranty, including return to the factory, are to be borne
tmd prc|5aid by the purchaser/owner. 'fliis warranty applies only to Generac generators sold and rated for ''Recreatioual Veliicle” (RV) appli.
cations, as Generac has defined Recreational Vehicle generator applications. This wtirranty is effective only upon Geiierac's receipt, from
the original purchaser/owner. of a completed Warranty Registration Card. This card is the only valid registration identification and must be
presented at time of request for warranty service. Claims will not be accepted witliout presentation of the Warranty Registration Card. 'I'hc
factory recommends exercising the unit one half-hour every season.
WARRANTY SCHEDULE - COMMERCIAL APPLICATIONS
YEAR ONE - 100% (one hundred percent) coverage on parl(s). labor, removal and reinstallation listed:
YEARS ONE AND TWO ^ 100% ( one hundred percent) coverage on part(s). labor, removal and reinslallation listed:
• Engine - All components
• Alternator - /Ml components
• Transfer System - All components
YE.AR Three ~ 100% (one hundred percent) only on selected part(s) and labor listed (Any lalror and part:(s) not listed, and removal and réin
• Rotor, Stator, Computer Control Board, (if applicable with regard to the generator) Cylinder Block. Cylinder Head, Crankshaft, Pistoii(s), Valve,
Valve Lifter(s). Intake and Exliausl Manifolds
The drive train belt and pulleys (if so equijaped) on generators used iia recreational veliicles sliall be warranted against failure due to defec
tive materials or normal usage for the life of the generator. For the original purchaser/owaier. this drive train warranty shall include part(s)
and labor (removal and réinstallation are not included) plus $50 (fifty dollars - U.S.) payment upon return of the failed bell or pulley by
the original purchaser/owner. For subsequent purchaser/owner. this drive train warranty shall cover belt and pulley part(s) ONLY (labor not
inchided). Labor, removal and réinstallation is the responsibility of tlie subsequent purchaser./owner,
Generac RV generators manufactured prior to December 31, 1997, DO NOT have a transferable warranty. Generac RV generators manu
factured after January 1, 1998. have a transferable warranty to the second owner ONLY for the remainder of the three-year limited war
ranty. Proof-of-purchase is required and must be presented to a Generac Authorized Warranty Service Facility prior to the performance of
any warranty service.
All warranty expense allowances are subject to the conditions defined in Generac s superзеШкеinformationmanual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING;
• Costs of normal maintenance, adjustments, installation and start-up,
• Failures caused by any contaminated fuels or oils.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As witli all
mechanical devices, the GN-Series engines need periodic partis) service and replacement to perform well. This warranty will not coverrepair when normal use has exliausted the life of a part(s) or engine,
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing,
liglitning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane,
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects In materials or worknianshiij. or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, telegraph, teletype or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within tlie terms of a specific unit warranty period.
• Rental equipment used while warranty repairs are being performed.
• Overnight freight costs for replacement part(s),
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER
WARRANTIES AS TO THE MERCHAN'FABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how
long an implied warranty lasts, so the above limitation may not apply to you,
GENERAC’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GEN
ERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES. EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so tlie above limita
tion may not apply to you, Purchaser/owaier agrees to make no claims against Generac based on negligence.
This warraiUy gives you specific legal rights. You also may have oilier rights Üiat vary from state to state.
Part IMa. C2S33
stallation are the owner's responsibility):
FOR THE LIFE OF THE RECREATIONAL VEHICLE GENERATOR (IF SO EQUIPPED)
GEIMERAC® POWER SVSTEIVIS, INC.
P.O. BOX
в
• WAUKESHA, Wl 531
Revision О (03/23/01 ]
BV
Printed in U.S.A.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.