Generac Power Systems 00784-2, 09290-4 Owners And Installation Manual

POWER SYSTEMS, INC.
®
Owner’s Manual and
Installation Instructions
Air-cooled Recreational
Vehicle Generators
• Model Nos: 00784-2 and 09290-4
Generac®Power Systems, Inc.
INTRODUCTION
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual, contact Generac or your nearest Generac Authorized Service Dealer for starting, operating and servicing pro­cedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, you can read instructions that, if not strictly complied with, will result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, you can read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, you can read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property of you and others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator (driver) is responsible for proper and safe use of the vehicle and its equipment, and the safe­ty of all vehicle occupants. We strongly recommend that the operator read this manual and thoroughly understand all instructions before using this equip­ment. We also strongly recommend instructing other occupants in the vehicle to properly start and operate the generator. This prepares them if they need to oper­ate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts for generator model numbers 009290-4 and 00784-2. In addition, the lat­ter portion of this manual contains information nec­essary for the proper installation of these generators.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safe­ty checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac Authorized Service Dealer. Normal maintenance ser­vice and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of your generator ensure a minimum number of problems and keep operating expenses at a minimum. See your Generac Authorized Service Dealer for service aids and acces­sories.
HOW TO OBTAIN SERVICE
When your generator requires servicing or repairs, simply contact a Generac Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all of your service needs.
When contacting a Generac Authorized Service Dealer or the factory about parts and service, always supply the complete model number and serial number of your unit as given on its data decal, which is located on your generator.
Model No. ____________ Serial No. ______________
AUTHORIZED SERVICE
DEALER LOCATION
To locate the GENERAC AUTHORIZED SERVICE
DEALER nearest you, please call this number:
1-800-333-1322
ONLY DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
Table of Contents
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generatorss
Generac®Power Systems, Inc. 1
Part I — Owner’s Manual
Introduction ........................................Inside Front Cover
Read This Manual Thoroughly..................................IFC
Contents ..................................................................IFC
Operation and Maintenance ......................................IFC
How to Obtain Service ..............................................IFC
Authorized Service Dealer Locator Number ................IFC
Safety Rules ........................................................................2
Section 1 – General Information....................................4
1.1 Generator Identification ........................................4
1.2 Generator Applicability ..........................................5
1.3 Installation ............................................................5
1.4 Safety ....................................................................5
1.5 Generator AC Connection System..........................5
1.6 Specifications ........................................................6
Section 2 – Operation ......................................................7
2.1 Generator Control Panel ........................................7
2.2 Optional Remote Start/Stop Panel ........................7
2.3 Automatic Choke ..................................................7
2.4 Before Starting the Engine ....................................8
2.5 Starting the Generator ..........................................8
2.6 Stopping the Generator ........................................9
2.7 Applying Loads to Generator ................................9
2.8 Protection Systems ................................................9
2.9 Additional Information ........................................10
Section 3 – Maintenance ..............................................11
3.1 Checking the Engine Oil Level ............................11
3.2 Changing the Engine Oil and/or Oil Filter ............11
3.3 Maintaining the Engine Air Cleaner ....................12
3.4 Clean Air Intake Screen ......................................12
3.5 Checking the Engine Spark Plug..........................12
3.6 Fuel Filter (Gasoline Only) ..................................13
3.7 Spark Arrestor Muffler ........................................13
3.8 Cleaning the Generator ........................................13
3.9 Battery Maintenance ............................................13
3.10 Major Service Manual ..........................................14
3.11 Drive Belt ............................................................14
3.12 Exercising the Generator ....................................14
3.13 Out of Service Procedure ....................................14
3.14 Wattage Reference Guide......................................15
Notes ..................................................................................16
P
artII — Installation Instructions
Safety Rules ......................................................................18
Section 1 – General Information ................................20
1.1 Purpose and Scope of the Manual ......................20
1.2 Safety ..................................................................20
1.3 Standards Booklets ............................................20
1.4 Equipment Description........................................20
1.5 Generator Engine Operating Speed ....................20
1.6 Generator AC Connection System........................20
Section 2 – Installation ..................................................22
2.1 Location and Support ..........................................22
2.2 Generator Compartments ....................................23
2.3 Cooling and Ventilating Air ..................................26
2.4 Gasoline Fuel System ..........................................27
2.5 Exhaust System ..................................................28
2.6 Electrical connections..........................................29
2.7 Battery Installation ..............................................32
2.8 Optional Accessories............................................32
Section 3 – Post Installation Start-up and
Adjustments ................................................33
3.1 Post Installation Tests ..........................................33
3.2 Before Initial Start-up ..........................................33
3.3 Initial Start-up ....................................................33
3.4 Testing Under Load ............................................33
3.5 Installation Checklist ..........................................34
Section4–Troubleshooting ........................................35
4.1 Troubleshooting Guide ........................................35
Section 5 – Electrical Data ............................................36
Section 6 – Exploded Views and Parts Lists ............38
Section7–Warranty......................................................48
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and main­tained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit, are, therefore, not all-inclusive. If you use a procedure, work method or operating tech­nique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that you choose does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GENERAL HAZAR
DS
• For safety reasons, Generac recommends that the installation, initial start-up and mainte­nance of this equipment is carried out by a Generac Authorized Service Dealer.
• The engine exhaust fumes contain carbon monox­ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in noncompli­ance with such codes and standards. The genera­tor compartment must be completely vapor sealed from the vehicle interior. There must be no possi­bility of exhaust fumes entering the vehicle interi­or. Never operate this equipment with a leaking or defective exhaust system.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator compartment. Without sufficient cooling airflow, the engine/generator quickly overheats, which causes serious damage to the generator. Do not alter the installation or per­mit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
• Inspect the generator regularly, and contact your nearest Generac Authorized Service Dealer immedi­ately for parts needing repair or replacement.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas of the recreational vehicle. Safety should be stressed to all operators and potential operators of this equipment.
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
Generac®Power Systems, Inc. 3
ELECTRICAL HAZARDS
• The generator covered by this manual produces dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• During installation onto the vehicle, have the genera­tor properly grounded (bonded) either by solid mounting to the vehicle frame or chassis, or by means of an approved bonding conductor. DO NOT disconnect the bonding conductor, if so equipped. DO NOT reconnect the bonding conductor to any generator part that might be removed or disassem­bled during routine maintenance. If the grounding conductor must be replaced, use only a flexible con­ductor that is of No. 8 American Wire Gauge (AWG) copper wire minimum.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a rope or board, to free the victim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIREHAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
• Keep a fire extinguisher in the vehicle at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the recreational vehicle generator electrical system. Keep the extinguisher properly charged and be familiar with its use. If you have any question per­taining to fire extinguishers, consult your local fire department.
EXP
LOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Gasoline is extremely FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flame, sparks or any source of heat in the vicinity while handling gasoline. Comply with all laws gov­erning the storage and handling of gasoline.
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
4 Generac®Power Systems, Inc.
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Please record the following information from the generator DATA DECAL or information decal.
1. Model Number ____________________ 2. Serial Number __________________
3. kW Rating __________________________ 4. Rated Voltage __________________
5. Phase ______________________________ 6. Hertz __________________________
1.1 GENERATOR IDENTIFICATION
REFERENCE NUMBER IDENTIFICATION
1. Generator Air Intake Screen
2. Data Plate
3. Engine Start/Stop Switch
4. 15 amp Fuse
5. 25 or 30 Amp (2 Pole) Circuit Breaker
6. Optional Remote Panel Receptacle
7. Generator AC Output Leads
8. Fuel Inlet
9. Fuel Primer Switch
10. Fuel Pump
11. Oil Filter
12. Starter Contactor
13. Oil Drain Plug
14. Oil Dipstick and Filler Tube
1
3
2
4
11
10
9
8
12
7
6
5
14
13
Generac®Power Systems, Inc. 5
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
1.2 GENERATOR APPLICABILITY
These generators have been designed and manufac­tured for supplying electrical power for recreational vehicles. You should not modify the generator or use it for any application other than for what it was designed. If there are any questions pertaining to its application, write or call the factory. Do not use the unit until you have been advised by a competent authority.
For fire safety, the generator must have been properly installed in compliance with ANSI
119.2-1975/NFPA 501C-1974, “Standard for Recreational Vehicles, Part III – Installation of Electrical Systems.” The generator also must have been installed in strict compliance with the manufacturer’s detailed installation instruc­tions. After installation, do nothing that might render the unit in noncompliance with such codes, standards and instructions.
1.2.1 PRIMEPACT 70
Use this generator to supply electrical power for operating 230-volt, single-phase, 50 Hertz, AC elec­trical loads. These loads can require up to 7,000 watts (7.0 kW) of power, but cannot exceed 30.4 AC amperes of current at 230 volts.
1.2.2 PRIMEPACT 50
Use this generator to supply electrical power for operating 230 volt, single phase, 50 Hertz AC electri­cal loads. These loads can require up to 5,000 watts (5.0 kW) of power, but cannot exceed 20.8 amperes of current at 230 volts.
Do not overload the generator. Some installa­tions may require that electrical loads be alter­nated to avoid overloading. Applying exces­sively high electrical loads may damage the generator and may shorten its life. Add up the rated watts of all electrical lighting, appliance, tool and motor loads the generator will power at one time. This total should not be greater than the wattage capacity of the generator. If an electrical device nameplate gives only volts and amps, multiply volts times amps to obtain watts (volts x amps = watts). Some electric motors require more watts of power (or amps of current) for starting than for continuous operation.
1.3 INSTALLATION
This manual has been prepared under the assump­tion that a competent, qualified technician installed the generator into a recreational vehicle. We also assume the installer complied with all applicable codes, standards and regulations pertaining to instal­lation.
Owners/Operators should make sure nothing is done during installation that might render the unit unsafe or in noncompliance with applicable codes standards and instructions. They should be sure the unit has been installed to allow adequate ventilation for cool­ing and exhaust air.
1.4 SAFETY
Before attempting to use the generator set, carefully read the “Safety Rules” section of this manual. Comply strictly with these rules to prevent accidents and damage to equipment and/or property. We sug­gest copying and posting the “Safety Rules” in poten­tial hazard areas of the vehicle. Stress safety to all operators and potential operators of this equipment.
1.5 GENERATOR AC
CONNECTION SYSTEM
This generator set is equipped with dual stator AC power windings. These two-stator windings supply electrical power to customer electrical loads.
NOTE:
One side of the winding is grounded.
Figure 1.1 – Connections for 230 Volts Only
6 Generac®Power Systems, Inc.
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
1.6 SPECIFICATIONS
1.6.1 FUEL REQUIREMENTS
These generators are equipped with a gasoline fuel sys­tem. Depending on the installation, the generator may have either a separate fuel tank, or it may “share” the vehicle engine’s fuel tank.
NOTE:
Some installations using a “shared” fuel tank may have a generator fuel pickup tube that is shorter than the vehicle engine’s pickup tube. Such an arrangement causes the generator engine to “run out of gas” while adequate fuel for the vehicle remains in the tank.
To reduce lead and carbon deposits use high quality UNLEADED gasoline with the generator. Leaded REG­ULAR grade gasoline is an acceptable substitute.
NOTE:
Using unleaded gasoline contributes to longer engine valve life by reducing lead and carbon deposits.
Generac does not recommend using any gasoline containing alcohol (such as “gasohol”). If you use any gasoline containing alcohol, it must not contain more than 10 percent ethanol, and it must be removed from the generator during storage. Do NOT use any gasoline containing methanol. If you use gasoline with alcohol, inspect more frequently for fuel leaks and other abnormalities.
1.6.2 ENGINE OIL REQUIREMENTS
Use only high quality detergent oil classified “For Service SF” and with an oil viscosity rating of SAE 10W-30 oil. Do not pour in any additives to the rec­ommended oil. Engine crankcase capacity is 1.4 liters. See Section 3.2 on page 11 for oil level check and filing procedures.
1.6.3 ENGINE
Type of Engine ......................................GN-480, Twin-cylinder
Cooling Method..........................................................Air-cooled
Rated Horsepower ..........................................16 @ 3,600 rpm
Displacement ....................................................................480cc
Compression Ratio ........................................................8.6 to 1
Cylinder Block ..........................Aluminum w/Cast Iron Sleeve
Type of Governor ..............................Mechanical, Fixed Speed
Engine Governor Speed ............................................3000 rpm
Air Cleaner..........................Paper Element w/Foam Precleaner
Starter..........................................................12-volt DC Electric
Ignition System........................Solid-state w/Flywheel Magneto
Recommended Spark Plug
Champion ..................................................................RC12YC
AC....................................................................................R45S
Fram Autolite ......................................................................65
Spark Plug Gap ........................................0.030 inch (0.8 mm)
1.6.4 GENERATOR PP50G/PP70G
Rated Maximum Continuous
AC Output ....................5,000 (5.0 kW)/7,000 Watts (7.0 kW)
Rated Voltage ..............................................................230 Volts
Rated Maximum Continuous
AC Current ................................21.8 Amperes/30.4 Amperes
Phase ................................................................................Single
Rotor RPM ........................................................................3,000
Number of Rotor Poles ............................................................2
Engine RPM ............................................................2,900/3,000
Rated AC Frequency ........................................................50 Hz
Weight......................................................................222 Pounds
Length........................................................25 inches (635 mm)
Width ..................................................18.5 inches (469.9 mm)
Height..............................................16.75 inches (425.45 mm)
Generac®Power Systems, Inc. 7
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.1 GENERATOR CONTROL PANEL
The following features are mounted on the generator control panel (Figure 2.1):
Figure 2.1 – Generator Control Panel
2.1.1 FUEL PRIMER
Before starting a cold engine (if it has not been start­ed in more than two weeks), you must press this switch for approximately five seconds to bring fuel from the tank to the fuel pump. This rocker type switch springs back into its original position when you release it.
2.1.2 START/STOP SWITCH
To crank and start the engine, hold this switch in the START position. Release the switch when the engine starts. To stop an operating engine, press and hold the switch in the STOP position until the engine shuts off. The switch center position is the RUN position.
2.1.3 FUSE
The fuse protects the engine’s DC control circuit against electrical overload. If the fuse element has melted open due to overloading, the engine cannot be cranked. If you must replace the fuse, use only an identical replacement.
2.1.4 MAIN BREAKER
The main breaker protects the generator’s AC output circuit against overload and provides a method of turning OFF the generator’s 230-volt AC output to the vehicle circuits. These generators have either a 25 Amp, 2-Pole circuit breaker (PP50) or a 30 Amp 2-Pole circuit breaker (PP70).
2.2 OPTIONAL REMOTE
START/STOP PANEL
A remote mounted Start/Stop Panel (Figure 2.2) is available that allows you to start and stop the gener­ator engine conveniently from inside the vehicle. The remote panel includes a Start/Stop switch, hour meter, generator run lamp and a wire harness.
Figure 2.2 — Optional Remote Panel
(Models 004057 and 004184)
2.3 AUTOMATIC CHOKE
This engine is equipped with an automatic choke that consists of two main components: a choke solenoid and prechoke.
2.3.1 CHOKE SOLENOID
During engine cranking (Start/Stop switch at START), a solid-state choke module signals the choke solenoid to activate and cycle (choke on/choke off) until the engine starts. The choke solenoid thus opens and closes the carburetor choke valve only when the engine is cranking. When the engine starts, the choke stops cycling.
2.3.2 PRECHOKE
The choke system also has a temperature-sensitive metal strip that adjusts choke valve angle according to ambient temperatures (i.e., in cold ambient tem­peratures, choke valve closes more). Once the engine starts, an element heats the temperature-sensitive strip to a normal operating condition, opening the choke valve. This may take about three minutes in cooler weather.
8 Generac®Power Systems, Inc.
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.4 BEFORE STARTING THE ENGINE
NOTE:
Instructions and information in this manual assume the generator has been properly installed, connected, serviced, tested and adjusted by a qualified installation technician or installation contractor.
2.4.1 INSTALLATION
Generator installation must have been properly com­pleted so it complies with all applicable codes, stan­dards and regulations and with the manufacturer's recommendations.
2.4.2 ENGINE LUBRICATION
Have the engine crankcase properly serviced with the recommended oil before starting. Refer to Section 1.6.3 (Page 6) and Sections 3.1 and 3.2 (Page 11) for oil ser­vicing procedures and recommendations.
Any attempt to crank or start the engine before you have properly serviced it with the recom­mended oil may result in an engine failure.
2.4.3 FUEL SUPPLY
The engine must have an adequate supply of proper fuel to operate. Before starting it, check that sufficient fuel is available.
NOTE:
Depending on the installation, the generator may have either a separate fuel tank, or it may “share” the vehicle engine’s fuel tank.
2.4.4 COOLING AND VENTILATING AIR
Air inlet and outlet openings in the generator com­partment must be open and unobstructed for contin­ued proper operation. Without sufficient cooling and ventilating airflow, the engine/generator quickly over­heats, which causes it to shut down and may damage the generator.
2.4.5 ENGINE EXHAUST GAS
Before starting the generator engine, you should be sure there is no way for exhaust gases to enter the vehicle interior and endanger people or animals. Close windows, doors and other openings in the vehi­cle that, if open, might permit exhaust gases to enter the vehicle.
The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen­trations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOX­IDE POISONING ARE (a) inability to think coher­ently; (b) vomiting; (c) twitching muscles; (d) throbbing temples; (e) dizziness; (f) headaches; (g) weakness; and (h) sleepiness. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP.
2.5 STARTING THE GENERATOR
To start the generator from either the generator con­trol panel or from the optional remote panel, proceed as follows:
1. Turn OFF electrical loads using the means pro-
vided in your vehicle (such as a main line circuit breaker or transfer switch).
NOTE:
If starting from the generator control panel, turn OFF loads by setting the generator’s main circuit breaker to the OFF (or open) position. If starting from a remote panel, turn OFF loads using the means provided in the vehicle (such as a main cir­cuit breaker). Electrical load circuits will be turned ON after the generator has started, stabi­lized and warmed up.
2. If you have not started the engine in more than
two weeks, press the Fuel Pump Primer switch and hold it for about five seconds to prime the fuel system. However, if the engine is warm, skip Step 2.
3. Hold the engine Start/Stop switch in the START
position to crank the engine. Release the switch when the engine starts.
If the engine does not start after it has been cranking for 15 seconds, release the Start/Stop switch and try again. Holding the switch for longer than 15 seconds can damage the starter motor.
4. Let the engine run at no-load for a few minutes to
stabilize and warm up.
5. Turn ON electrical loads using the means
provided (such as a main circuit breaker or transfer switch).
Generac®Power Systems, Inc. 9
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
2.6 STOPPING THE GENERATOR
1. Turn OFF all electrical loads using the means provided (such as a main circuit breaker or transfer switch).
2. Let generator run at no-load for a few minutes, to stabilize internal engine generator temperatures.
3. Place the Start/Stop switch in its STOP position.
2.7 APPLYING LOADS TO GENERATOR
When applying electrical loads to the generator, observe these guidelines:
• Before applying electrical loads, let the generator
stabilize and warm up for a minute or two.
• DO NOT overload the generator.
2.7.1 LETTING THE ENGINE STABILIZE
The generator supplies correct rated voltage only at the proper governed speed. Some electrical appli­ances may be extremely sensitive to voltage. Incorrect voltages can damage such appliances.
If electrical loads are applied at reduced operating speeds, such loads imposed on the engine when suffi­cient power is not available may shorten engine life. Never turn ON electrical loads until after the generator engine has started and stabilized at no-load.
2.7.2 DO NOT OVERLOAD THE GENERATOR
You can read the rated wattage/amperage capacity of your generator on the generator data decal (see Section 1.1 on Page 4).
Applying electrical loads in excess of the unit’s rated capacity will cause the engine/generator to automati­cally shut down.
To avoid overloading, add up the wattage of all con­nected electrical lighting, appliance, tool and motor loads. This total should not be greater than the gen­erator’s rated wattage capacity.
• Most lighting, appliance, tool and motor loads indi-
cate their required watts on their nameplate or data plate. For light bulbs, simply note the wattage rating of the bulb.
• If a load does not show its rated wattage, multiply
that load’s rated VOLTS times AMPS to obtain WATTS.
• Induction type motors (such as those that run the
vehicle’s furnace fan, refrigerator, air conditioner, etc.) need about 2-1/2 times more watts of power for starting than for running (for a few seconds during motor starting). Be sure to allow for this when connecting electrical loads to the generator. First, figure the watts needed to start electric motors in the system. To that figure, add the run­ning wattages of other items that will be operated by the generator.
• Do not apply heavy electrical loads for the first two
or three hours of operation.
2.8 PROTECTION SYSTEMS
2.8.1 LOW OIL PRESSURE SWITCH
This switch (Figure 2.3) has normally open (N.O.) con­tacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below a preset level, switch contacts close, and the engine automatically shuts down. The unit should not be restarted until oil is added.
2.8.2 HIGH TEMPERATURE SWITCH
This switch (Figure 2.3), which has normally open (N.O.) contacts, is mounted near the oil filter. The contacts close if the temperature should exceed approximately 284º F (140º C), initiating an engine shutdown.
Figure 2.3 – Low Oil Pressure and
High Temperature Switches
2.8.3 FIELD BOOST
The Controller Circuit Board houses a field boost diode and resistor. These two components are part of a “field boost” circuit (Figure 2.4). During engine cranking only, a positive DC (battery) voltage is deliv­ered through the diode, resistor, brushes and slip rings, and the generator rotor. Application of this voltage to the rotor “flashes the field” whenever it is started. Flashing of the field each time the generator starts makes sure that a sufficiently strong magnetic field is available to produce “pickup” voltage in the stator windings.
10 Generac®Power Systems, Inc.
Section 2 – Operation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Figure 2.4 – Field Boost Circuit
2.8.4 OVERVOLTAGE PROTECTION
A solid-state voltage regulator (Figure 2.5) controls the generator’s AC output voltage. This regulator sup­plies an excitation current to the rotor. By regulating the rotor’s excitation current, the strength of its mag­netic field is regulated and, in turn, the voltage deliv­ered to connected electrical loads is controlled. When the AC frequency is 50 Hertz, voltage is regulated at 115 volts.
NOTE:
The solid state voltage regulator is only con­nected across 1/2 of the output winding.
Figure 2.5 – Solid State Voltage Regulator
The voltage regulator also incorporates a “voltage surge protection circuit.” This circuit prevents trou­blesome surges in the generator AC output voltage. Voltage surge is a common cause of damage to elec­tronic equipment.
2.9 ADDITIONAL INFORMATION
2.9.1 25-HOUR BREAK-IN PERIOD
The first 25 hours of operation is the break-in period for the generator. Properly breaking in the generator is essential to minimize fuel consumption and pro­vide maximum engine performance. During this 25­hour break-in period, follow this procedure:
• Run the unit at varying electrical loads to help seat the engine piston rings properly.
• Check the engine oil level frequently. Add oil if needed. It is normal for the generator engine to consume more oil than is normal until the piston rings have properly seated.
• For the 75-hour operation following the break-in period, avoid light electrical loads. Load the generator at 50 percent (or more) of its rated wattage capacity. Repeated light loads during these 75 hours can cause improper seating of engine pis­ton rings, resulting in blowby and high oil con­sumption.
• After operating the unit for 25 hours, complete the tasks recommended under Section 2.10.2.
2.9.2 25-HOUR CHECK-UP
After the 25-hour break-in period, contact a Generac Authorized Service Dealer for the following mainte­nance. The vehicle owner is responsible for any charges:
• Change the engine crankcase oil and oil filter.
• Inspect the cooling and ventilation openings.
• Check the engine ignition system.
• Inspect the entire electrical system.
• Inspect the engine exhaust system.
2.9.3 OPERATION IN HIGH GRASS OR BRUSH
Never operate the generator while the vehicle is parked over high grass, weeds, brush, leaves or any other combustible substance. Such materials can ignite and burn from the heat of the exhaust system. The generator exhaust system becomes extremely hot dur­ing operation and remains hot for a long time after it has shut down.
2A
Generac®Power Systems, Inc. 11
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities and requirements, see “Engine Oil Requirements,” Section 1.6.2 (Page 6). Check the engine crankcase oil level at least every eight hours of operation, or before you use it. To check the engine oil level, proceed as follows (see Figure 3.1):
1. Be sure the generator is as level as possible.
2. Remove the dipstick and wipe it dry with a clean,
lint-free cloth.
3. Install and tighten the dipstick cap; then, remove
it again. The oil level should be at the dipstick “Full” mark.
4. If necessary, remove the oil fill cap on the rocker
cover and slowly add oil until it reaches the dip­stick “Full” mark. DO NOT FILL ABOVE THE “FULL” MARK.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
5. Install and tighten the oil fill cap and the dipstick
before operating the engine.
3.2 CHANGING THE ENGINE OIL AND/OR OIL FILTER
• Change the engine oil after the first 25 hours of
operation (after the 25-hour break-in period, see Section 2.9.1, Page 10). Thereafter, change the oil every 100 operating hours. Change the oil more frequently if operating consistently under heavy load or at high ambient temperatures.
• Change the engine oil filter after the first 25 hours
of operation, and every 100 operating hours there­after.
To change the oil and/or oil filter, proceed as
follows:
1. Run the engine until it is thoroughly warmed up
(at least five minutes) then shut OFF the engine.
2. With the engine still warm from running, remove
the oil drain plug (Figure 3.1). Drain the oil into a suitable container.
3. After the oil has drained, replace the oil drain plug.
(If only changing the oil, go to step 7.)
4. With the oil drained, remove the old oil filter by
turning it counterclockwise (Figure 3.2).
5. Apply a light coating of clean engine oil to the gas-
ket of the new filter.
6. Screw the new filter on by hand until its gasket
lightly contacts the oil filter adapter. Then, tight­en the filter an additional 3/4 to one turn.
7. Remove the dipstick and fill crankcase with the proper type and amount of recommended oil (see Section 1.6.2, Page 6). The engine crankcase can hold about 1.4 liters. DO NOT FILL ABOVE THE “FULL” MARK.
8. Install and tighten the dipstick before operating the engine.
9. Start the engine and check for leaks.
NOTE:
Check the oil level and fill to the “FULL” mark after checking for leaks. The filter will retain some oil.
Figure 3.1 — Oil Dipstick/Fill Tube and
Location of Oil Drain Plug
Figure 3.2 — Engine Oil Filter
OIL DIPSTICK
OIL DRAIN PLUG
12 Generac®Power Systems, Inc.
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.3 MAINTAINING THE ENGINE AIR CLEANER
3.3.1 CLEANING THE FOAM PRECLEANER
Clean and re-oil the foam precleaner every three months or every 25 hours of operation, whichever occurs first. Service the foam precleaner more fre­quently if operating the generator in extremely dusty or dirty conditions. Use the following procedure (Figure 3.3):
1. Turn the knob counterclockwise to loosen.
2. Remove the cover, foam precleaner and paper filter.
3. Remove the foam precleaner from the cover.
4. Wash the foam precleaner in liquid detergent and
water.
5. Wrap the foam precleaner in a clean cloth and
gently squeeze it dry.
6. Saturate the foam precleaner in clean engine oil.
Gently squeeze it in a clean cloth to remove excess oil and to distribute oil (DO NOT TWIST).
7. Install the foam precleaner into the cover, fol-
lowed by the paper filter. Tabs at edges of paper filter must lock into slots on cover.
8. Install the cover, foam precleaner and paper filter.
9. Replace knob to retain the filter in place.
Figure 3.3 – Engine Air Cleaner
3.4 CLEAN AIR INTAKE SCREEN
Clean all foreign material from the air intake screen (Figure 3.4) at least once every 100 hours of opera­tion. Clean more often if necessary.
Inspect the area around the generator exhaust muf­fler periodically and remove all grass, leaves, dirt, etc., from this area.
Figure 3.4 – Cleaning Air Intake
3.5 CHECKING THE ENGINE SPARK PLUG
Clean the spark plug and reset the spark plug gap every 100 hours of operation.
1. Clean the area around the base of the spark plug
to keep dirt and debris out of the engine. Clean by scraping or washing using a wire brush and com­mercial solvent. Do not blast the spark plug to clean.
2. Remove the spark plug and check the condition.
Replace the spark plug if worn or if reuse is ques­tionable.
3. Check the spark plug gap using a wire feeler
gauge. Adjust the gap to 0.030 inch (0.76 mm) by carefully bending the ground electrode (Figure 3.5).
Figure 3.5 – Setting the Spark Plug Gap
Sparking can occur if the wire terminal does not fit firmly on the spark plug terminal end. If necessary, re-form the wire terminal to obtain a tight fit.
PAPER FILTER
FOAM PRE-CLEANER
COVER
KNOB
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
3.6 FUEL FILTER (GASOLINE ONLY)
Remove and replace the fuel filter (Figure 3.6) once each year or every 100 hours of operation, whichever comes first.
Figure 3.6 – Fuel Filter
3.7 SPARK ARRESTOR MUFFLER
If the generator is not equipped with a spark arrestor exhaust muffler and is to be used on any forest cov­ered, brush covered or grass covered unimproved land, you may have to install a spark arrestor. The spark arrestor must be maintained in effective work­ing order by the vehicle owner/operator.
For assistance in ordering, installing and maintaining spark arrestor exhaust mufflers, contact your nearest Generac Authorized Service Dealer.
Exhaust mufflers supplied by Generac are spark arrestor types. Generac exhaust mufflers for recre­ational vehicle generators do not have a spark arrestor screen, but are of the more efficient “toroid” or “swirl” type. To remove carbon and combustion deposits from such mufflers, remove the plug from the muffler and run the engine for approximately 15 minutes. Shut down the engine, let the muffler cool and install the plug.
Be sure to reinstall the muffler plug tightly. Engine vibration could cause a loose plug to fall out. Without the plug in place, hot engine exhaust is directed out the opening. This hot exhaust, depending on the installation, could be directed to areas not able to withstand the extreme heat such as wooden floor boards or other flammable material. This could result in a fire.
3.8 CLEANING THE GENERATOR
Keep the generator set as clean and dry as possible. Protect the unit against excessive dust, dirt, corrosive vapors, road splash, etc. Permitting dirt and mois­ture to accumulate on generator windings will have an adverse effect on the insulation resistance of those windings.
When moisture is allowed to remain in contact with windings, some of the moisture will be retained in voids and cracks in the insulation. This causes a reduced insulation resistance and will eventually cause problems. Dirt will make the problem worse, since dirt tends to hold moisture in contact with windings. Salt (as from sea air) also will worsen the problem since it tends to absorb moisture from the air. Salt and moisture, when combined, form a good electrical conductor.
Do NOT use a forceful spray of water to clean the generator. Water will enter the generator interior and cause problems, and may also cont­aminate the generator fuel system.
3.9 BATTERY MAINTENANCE
All lead-acid batteries will discharge when not in use. The generator battery should be inspected as follows:
3.9.1 WEEKLY
• Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
• Check the battery fluid level of unsealed batteries
and, if necessary, fill with Distilled Water Only. Do not use tap water in batteries.
3.9.2 EVERY SIX MONTHS
• Have the state of charge and condition checked.
This should be done with an automotive-type bat­tery hydrometer.
NOTE:
Servicing of the battery is to be performed or supervised by personnel knowledgeable of batter­ies and the required precautions. Keep unautho­rized personnel away from batteries.
Damage will result if the battery connections are made in reverse.
Generac®Power Systems, Inc. 13
TO FUEL PUMP
CUSTOMER FUEL CONNECTION
FUEL FILTER
14 Generac®Power Systems, Inc.
Do not dispose of the battery in a fire. The battery is capable of exploding. Storage batter­ies give off explosive hydrogen gas. This gas can form an explosive mixture around the bat­tery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks, or any spark producing tools or equipment near the battery. Discharge static electricity from your body before touch­ing the battery by first touching a grounded metal surface.
A battery presents a risk of electrical shock and high short circuit current. The following precautions are to be observed when working on batteries:
• Remove watches, rings or other metal objects;
• Use tools with insulated handles;
• Wear rubber gloves and boots;
• Do not lay tools or metal parts on top of the battery;
• Disconnect any charging source prior to connecting or disconnecting battery terminals; and
• Do not use any jumper cables or booster battery to crank and start the generator engine. If any battery has discharged, remove it for recharging.
Do not open or mutilate the battery. Released electrolyte has been known to be harmful to the skin and eyes, and to be toxic.
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing;
• Where electrolyte contacts the skin, wash it off immediately with water;
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical attention; and
• Spilled electrolyte is to be washed down with an acid neutralizing agent. A common practice is to use a solution of 1 pound (500 grams) bicarbonate of soda to 1 gallon (4 liters) or water. The bicar­bonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
3.10 MAJOR SERVICE MANUAL
To obtain a service manual for your generator, con­tact Generac or your nearest Generac Authorized Service Dealer. Make sure to identify your MODEL NUMBER and SERIES.
3.11 DRIVE BELT
The engine drives the generator rotor by means of a pulley and drive belt arrangement. The drive belt and pulleys are warranted for the life of the generator. Drive belt tension was properly adjusted before the unit was shipped from the factory. If you suspect that drive belt tension is incorrect, contact a Generac Authorized Service Dealer.
3.12 EXERCISING THE GENERATOR
Generac recommends that you start and operate the generator at least once every seven days. Let the unit run for at least 30 minutes to “exercise” the engine.
3.13 OUT OF SERVICE PROCEDURE
3.13.1 REMOVAL FROM SERVICE
If you cannot exercise the generator every seven days, and it is to be out of service longer than 30 days, pre­pare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 10W-30 oil having API classification “For Service SF.”
4. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
5. Remove the spark plug and pour two or three tablespoons of clean, fresh engine oil into the spark plug threaded openings. Reinstall and tighten the spark plug.
6. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
7. Clean and wipe the entire generator.
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 15
3.13.2 RETURN TO SERVICE
To return the unit to service after storage, proceed as follows:
1. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommend­ed oil is used in the engine (see Section 1.5.4, Page 6). If necessary, drain and refill with the proper oil.
2. Check the state of the battery. Fill all cells of unsealed batteries to the proper level with distilled water. DO NOT USE TAP WATER IN THE BAT­TERY. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery.
3. Clean and wipe the entire generator.
4. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incorrectly.
5. Turn OFF all electrical loads. Add fuel if neces­sary and then start the engine.
6. Allow the unit to warm up thoroughly.
7. Apply electrical loads to at least 50 percent of the unit’s rated wattage capacity.
8. When the engine is thoroughly warmed up, shut it down.
9. Your generator is now ready for service.
3.14 WATTAGE REFERENCE GUIDE
Running
Watts
Battery Charger ..................................................500
Belt Sander (3”)................................................1000
Chain Saw ........................................................1200
Circular Saw (6-12”) ............................800 to 1000
Disc Sander (9”) ..............................................1200
Hand Drill (1”) ................................................1100
Hedge Trimmer ..................................................450
Impact Wrench ..................................................500
Lawn Mower ....................................................1200
Electric Range (one element) ............................1500
Television ..............................................750 to 1000
Coffee Maker ....................................................1000
Electric Skillet..................................................1250
Hair Dryer ........................................................1200
Light Bulb ..........................................................100
Microwave Oven ................................................700
Oil Burner on Furnace ......................................300
Oil Fired Space Heater (140,000 Btu) ................400
Radio ........................................................50 to 200
Slow Cooker ......................................................200
*Furnace Fan (1/3 HP) ........................................500
*Refrigerator ......................................................600
*Air Conditioner (12,000 Btu)..........................1700
*Compressor (1HP) ..........................................2000
*Deep Freeze ......................................................500
*Milk Cooler ....................................................1100
*Submersible Pump (1-1/2 HP) ........................2800
*Submersible Pump (1 HP) ..............................2000
*Paint Sprayer, Airless (1/3 HP) ........................600
*Table Saw (10”) ................................1750 to 2000
* Allow 2-1/2 times the listed watts for starting these devices.
Section 3 – Maintenance
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
16 Generac®Power Systems, Inc.
Notes
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 17
PART II
INSTALLATION
INSTRUCTIONS
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!!
18 Generac®Power Systems, Inc.
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
NOTICE TO INSTALLER
These Installation Instructions have been published by Generac to aid in the installation of the products described in this manual. Generac assumes that installation personnel are familiar with the proce­dures for installing such products, or similar prod­ucts that Generac manufactures. Generac also assumes that personnel have been trained in the rec­ommended installation procedures for these prod­ucts and that such training includes (a) use of com­mon hand tools, (b) use of special Generac tools, and (c) use of any tools and/or equipment from other sup­pliers.
Generac cannot possibly know of and advise the recreational vehicle trade of all conceivable methods, procedures or techniques by which to perform an installation. Nor can Generac anticipate every possi­ble hazard that might result from each installation method, procedure or technique. Generac has not undertaken any such wide evaluation. Therefore, people who use a method, procedure or technique that Generac does not specifically recommend must first completely satisfy themselves that their safety, the safety of the vehicle's occupants and the product's safety is not endangered by the method, procedure or technique selected.
Information, illustrations, specifications, etc., con­tained in these Installation Instructions are based on the latest information available at the time of publi­cation. Every effort has been expended to be sure that such data is both accurate and current. However, the manufacturer reserves the right to change, alter or otherwise improve this product at any time without prior notice.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running generators.
GENERAL HA
ZARDS
• For safety reasons, Generac recommends that the installation, initial start-up and mainte­nance of this equipment is carried out by a Generac Authorized Service Dealer.
• The engine exhaust fumes contain carbon monox­ide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. This exhaust sys­tem must be installed properly, in strict compli­ance with applicable codes and standards. Following installation, you must do nothing that might render the system unsafe or in noncompli­ance with such codes and standards. The genera­tor compartment must be completely vapor sealed from the vehicle interior. There must be no possi­bility of exhaust fumes entering the vehicle interi­or. Never operate this equipment with a leaking or defective exhaust system.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical to correct generator operation and is required to expel toxic fumes and fuel vapors from the generator compartment. Without sufficient cooling airflow, the engine/generator quickly overheats, which causes serious damage to the generator. Do not alter the installation or per­mit even partial blockage of ventilation provisions, as this can seriously affect safe operation of the generator.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
• Before performing any maintenance on the genera­tor, disconnect its battery cables to prevent acci­dental start up. Disconnect the cable from the bat­tery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
• Never insert any tool or other object through open­ings in the generator interior, even if the unit is not running. You might seriously injure yourself or damage the equipment.
DANGER: For fire safety, installation of a generator into a recreational vehicle must comply strictly with article 551, NFPA 70; ANSI C1-1975; AND, ANSI A119.2-1975/NFPA 501C “Standard for Recreational Vehicles” (Part 3, “Installation of Electrical Systems”). In addition, installation must comply with the manufacturer’s instructions and recommendations.
Generac®Power Systems, Inc. 19
Safety Rules
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
ELECTRICAL HAZARDS
• The generator covered by this manual produces dangerous electrical voltages and can cause fatal electrical shock. Avoid contact with bare wires, ter­minals, connections, etc., while the unit is running. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If you must work around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• During installation onto the vehicle, properly ground (bond) the generator either by solid mount­ing to the vehicle frame or chassis, or by means of an approved bonding conductor. DO NOT connect the bonding conductor to any generator part that might be removed or disassembled during routine maintenance. If the grounding conductor must be replaced, use only a flexible conductor that is of No. 8 American Wire Gauge (AWG) copper wire minimum.
• If the vehicle electrical circuits can be powered by any other source of electricity (such as a “dock­side” power receptacle), there must be no possibil­ity of connecting the different power sources to the vehicle circuits at the same time. The dockside (utility) power source must be positively isolated from the vehicle circuits whenever the generator is operating. Failure to isolate the vehicle circuits from the dockside power supply when the genera­tor is running may result in damage to the genera­tor or serious injury or death to dockside (utility) power workers due to backfeed of electrical ener­gy.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a rope or board, to free the victim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIREHAZARDS
• For fire safety, the generator must be installed and maintained properly. Installation always must comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed in accordance with the manufacturer’s instructions and recommendations. Following proper installa­tion, do nothing that might alter a safe installation and render the unit in noncompliance with the aforementioned codes, standards, laws and regu­lations.
• Keep a fire extinguisher in the vehicle at all times. Extinguishers rated “ABC” by the National Fire Protection Association are appropriate for use on the recreational vehicle generator electrical system. Keep the extinguisher properly charged and be familiar with its use. If you have any question per­taining to fire extinguishers, consult your local fire department.
EXP
LOSION HAZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• Gasoline is extremely FLAMMABLE and its vapors are EXPLOSIVE. Do not permit smoking, open flame, sparks or any source of heat in the vicinity while handling gasoline. Comply with all laws gov­erning the storage and handling of gasoline.
• Fuel lines must be properly installed and fastened, and free of leaks. There must be no possibility of gasoline vapors entering the vehi­cle interior.
• You are required to install an approved, flexible, nonconductive fuel line between the generator fuel connection point and rigid fuel lines.
20 Generac®Power Systems, Inc.
1.1 PURPOSE AND SCOPE OF THE MANUAL
These Installation Instructions have been prepared especially for the purpose of familiarizing installers and owners of the applicable equipment with the product's installation requirements. Give serious consideration to all information and instructions in the manual, both for safety and for continued reliable operation of the equipment.
Because of the different recreational vehicle models and the variations between the models, it would be extremely difficult, if not impractical, to provide detailed instructions for every possible installation. For that reason, instructions and illustrations in this manual are general in nature. Illustrations are not intended to serve as detailed installation blueprints.
The installation should comply strictly with all applicable codes, standards and regulations pertain­ing to the installation and use of this product. If any portion of this manual appears to be in conflict with such codes, standards or regulations, the applicable codes, standards or regulations must take prece­dence over the manual.
1.2 SAFETY
Before handling, installing, operating or servicing this equipment, carefully read the “Notice to Installer” and “Safety Rules” on Pages 18 and 19. Comply with all safety rules to prevent death, personal injury or damage to equipment and/or property. Stress safety to all installers, operators and service technicians who work on this equipment.
1.3 STANDARDS BOOKLETS
Installation, use and servicing of this equipment should comply strictly with published standards, as well as the manufacturer's recommendations. The following standards booklets (latest revision) are available from the sources indicated:
1. NFPA Standard 501C, “Standard for Recreational
Vehicles,” available from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269.
2. NFPA 70, “NFPA Handbook of the National
Electric Code,” available same as Item 1.
3. ANSI C1-1975 and ANSI 119.2-1975, available
from the American National Standards Institute, 1430 Broadway, New York, NY 10018.
4. ANSI A119.2/NFPA 501C, available from the
Recreational Vehicle Association, 1896 Preston White Drive, Reston, VA 22090.
5. California Administrative Code, Title 25, avail-
able from the State of California, Documents Section, P.O. Box 1015, North Highlands, CA
95660.
6. CSA Electrical Bulletin 946, available from the Canadian Standards Association, Housing and Constructions Materials Section, 178 Rexdale Boulevard, Rexdale, Ontario, Canada, M9W 1R3.
1.4 EQUIPMENT DESCRIPTION
Instructions and information in this section pertain to Generac air-cooled generators. These generators are designed specifically for installing in recreational vehicles. They operate 230-volt, single-phase, 50­Hertz, AC electrical loads that require 20.8 amps (PP50) or 30.4 amps (PP70).
1.5 GENERATOR ENGINE
OPERATING SPEED
The generator’s revolving field (rotor) is driven by a single-cylinder, four-cycle engine through a pulley and drive belt arrangement. The generator supplies 230 volts AC at 50 Hertz when the rotor is operating at 3,000 rpm. The drive belt arrangement allows the engine to operate at a lower speed than the rotor.
1.6 GENERATOR AC
CONNECTION SYSTEM
This generator set is equipped with dual stator AC power windings as shown in Figure 1.1. These two­stator windings supply electrical power to customer electrical loads by means of a dual two-wire connec­tion system. Note, however, that the neutral is grounded.
Figure 1.1 – Connections for 230 Volts Only
NOTE:
Do NOT connect loads in excess of circuit breaker ratings.
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 21
Figure 1.2 – Major Features and Dimensions
Section 1 – General Information
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
PrimePact 50 and 70
Control Panel
Fuel Filter
Fuel Pump
Oil Filter
Oil Drain Plug
Starter Contactor
Oil Fill/Oil Level
Spark Plugs
(both sides, not shown)
Air Filter
Ground Lug
22 Generac®Power Systems, Inc.
2.1 LOCATION AND SUPPORT
2.1.1 GENERATOR LOCATION
The most desirable location for the generator set is between the vehicle's main frame members. However, this is seldom possible. Most units must be installed on the side of the vehicle and are difficult to reinforce.
Many recreational vehicles have been factory equipped with an area for the generator set. Some vehicles may even have a generator compartment provided by the vehicle manufacturer.
Plan the generator location based on the following:
• The generator set must be installed on a frame­work that is part of the recreational vehicle, as out­lined in Section 2.1.2.
• The location must provide an access opening that is large enough to permit generator removal (unless the generator is to be removed from under­neath the supporting framework).
• The location must provide easy access to frequent­ly serviced components, such as filters, oil drains, spark plugs and other common maintenance parts.
• The location must provide sufficient room to allow minimum clearances as outlined in Section 2.2. If sound insulation is to be used on the compartment walls and ceiling, the minimum recommended applies to the space between the generator and such insulation.
• The location must provide adequate cooling and ventilating airflow for the generator without a great deal of work and expense.
2.1.2 GENERATOR SUPPORT
The generator must be securely attached to a metal framework that has been made part of the vehicle frame structure by bolting or welding. The metal framework on which the generator will rest and which will restrain the generator set should consist of at least two horizontal beams. These beams should consist of (a) 1-1/2-inch square, 11-gauge steel tubing OR (b) 1-1/2-inch, 11-gauge angle iron. A typical sup­porting frame with horizontal support tubing, is shown in Figure 2.1.
The generator can be installed so that it sits on top of the horizontal support tubing if the vehicle design permits. Another method is to suspend the generator below the horizontal support tubing by means of suit­able, structurally sound metal framework. The fol­lowing general rules apply:
• Vehicle construction MUST be capable of support­ing the weight of the generator.
• Whether the generator is mounted above the hori­zontal support tubing or suspended below the tub­ing, the supporting frame used must be structural­ly sound.
• If the generator cannot be bolted directly to the supporting frame or support tubing, consider using additional tubing, angle brackets or other supports to give the supporting frame sufficient strength.
Figure 2.1 – Typical Horizontal Support Frame
2.1.3 SUSPENDED MOUNTING
If you are going to suspend the generator below the horizontal support tubing, the suspension method you use with the vehicle frame members must (a) be able to support the weight of the generator AND (b) provide sufficient restraint for the generator. One typ­ical suspended mounting system is shown in Figure
2.2. The location of a suspended mounting system
must be carefully planned, keeping the following gen­eral rules in mind:
• Protect the generator against road splash and debris. Baffles or splash guards may be required to protect certain areas of the generator. To make sure the gen­erator is adequately protected, road test the installa­tion through mud, water and slush.
Figure 2.2 – Typical Suspended Mounting System
• The installer must make certain that the selected location will permit adequate cooling and ventilat­ing airflow to be supplied.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 23
2.1.4 GENERATOR RESTRAINT
Use four 3/8"-16 hardened steel bolts (Grade 5) to fas­ten the generator to the supporting frame or the sup­port tubing. These bolts must pass through (a) the gen­erator mounting base, (b) the compartment floor (if a compartment is used) and (c) the supporting frame­work (Figure 2.3). All bolts must be long enough so that when tight, at least three threads are visible past the retaining lock nuts. Refer to Section 2.2 for the location of the generator mounting holes.
Figure 2.3 – Typical Generator Restraint
2.2 GENERATOR COMPARTMENTS
Whether the generator set is being installed inside a compartment specifically manufactured to house a gen­erator or inside a compartment that the installer con­structs, the compartment MUST meet certain specifi­cations as outlined in the following sections:
2.2.1 COMPARTMENT SIZE
Plan the compartment size carefully. Provide a mini­mum clearance of 1/2 inch (13 mm) on the front and top, 1 inch (25 mm) on the sides, and 1/2 inch (13 mm) from the back for air circulation AFTER the compartment has been lined with metal and sound insulation (Figure 2.4).
NOTE:
Refer to “Figure 1.2 – Major Features and Dimensions” on Page 21.
Figure 2.4 – Clearances
2.2.2 COMPARTMENT CONSTRUCTION
• The generator compartment should be either con­structed of, or lined with, 26-gauge galvanized steel.
NOTE:
Aluminum is NOT an acceptable alternative to gal­vanized steel due to aluminum’s low melting point.
• If the compartment is lined with galvanized steel, it may be constructed of any material. Generac rec­ommends that the compartment be constructed of 1/2-inch thick plywood (not strandboard), with the floor made of a double thickness of 1/2-inch ply­wood with the grain of the wood at cross section for added strength (Figure 2.5).
Figure 2.5 – Typical Compartment Construction
• If constructing a compartment, line the exterior (underside) of the compartment floor with 26­gauge galvanized steel.
• All seams, splices and joints of the compartment walls (unless vapor tight by design) should be caulked to prevent poisonous, flammable or explo­sive vapors from entering the vehicle interior.
NOTE:
Caulking must be done so that the caulking mate­rial will stay in place permanently. Pressing such materials as putty tape onto joints and seams is not acceptable. A high quality silicone rubber base sealant is recommended.
• Holes and openings made in the compartment walls to allow for the passage of electrical conduit, conductors, hoses, cables, etc., into the vehicle liv­ing area must be sealed vapor tight with silicone rubber base sealant.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Plywood
Compartment
Insulation
1 1/2" Clearance on Top
1/2"
in Front
1" Each Side
1" Clearance
in Back
24 Generac®Power Systems, Inc.
• If flexible metal conduit is used, it must be sealed internally at the end where it terminates inside the compartment’s electrical junction box.
NOTE:
Flexible metal conduit, due to its unique con­struction, is NOT vapor tight along its entire length.
• Seams and joints of the galvanized steel (whether used as a liner or for the compartment itself) must be lapped and mechanically secured. Such seams may be manufactured, welded, bolted, riveted or screwed. Manufactured lock seams are shown in Figure 2.6. Installer constructed compartments typically utilize a standard lap joint.
Figure 2.6 – Types of Lock Seams
• After the compartment has been metal lined and vapor sealed, line the compartment interior walls and ceiling with an approved, nonflammable sound insulating material. See Section 2.2.3.
Do not install any flammable material directly above or around the compartment. Heat, transferred through the compartment structure, may be sufficient to ignite, char or discolor seat cushions, fiberboard and other flammable materials. You may need to use approved nonflammable insulating materials in high temperature areas.
2.2.3 SOUND INSULATING MATERIALS
Once installers have determined that a compartment is properly constructed and metal lined, they can add acoustical material. This may include additional sealant or insulating material, to reflect noise away from the vehicle interior.
Sound insulating materials should be of a nonflam­mable type. One excellent insulating material is a 1­inch (25 mm) thick fiberglass having a 2-pound den­sity. When fiberglass is used, its coated side should face toward the compartment interior.
Do not install sound insulation or any absorbent material on the compartment floor interior. Such materials will become soaked with combustible or explosive vapors and liq­uids and will become a fire hazard.
Using a combination of sound insulating materials can often reduce noise more effectively than a single material. For example, a sheet of lead or visco-elastic material, along with a layer of other acoustical mate­rial, is more effective than when a single material is used.
2.2.4 ACOUSTICS
For additional noise abatement, the installer may wish to consider the following:
• Using special sound insulating materials.
• Construction of a special noise abatement compartment.
NOTE:
Any method used to reduce noise must not adversely affect the flow of cooling and ventilating air into or out of the compartment.
In addition to the effective use of sound insulating materials, construction of a special noise abatement compartment might be considered to reduce noise levels. Such a compartment might be constructed as follows (Figure 2.7):
• Use 5/8-inch thick or 3/4-inch thick plywood in the compartment.
• Construct the compartment floor of a double thick­ness of 5/8-inch or 3/4-inch plywood.
• Line the compartment interior walls and floor, as well as the underside of the floor, with 26-gauge galvanized steel.
• Vapor seal all compartment seams and joints.
• Over the galvanized steel lining, install a combina­tion of acoustical materials as mentioned in Section 2.2.3.
To prevent fire or explosion, do not install any insulation or other absorbent materials on the interior or underside of the compartment floor.
• Seal all compartment door edges to prevent noise leakage around the door perimeter.
• Line the compartment door interior (except for air openings) with suitable, fireproof sound insulation (such as 1-inch (25 mm) thick fiberglass with a 2­pound density).
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 25
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Figure 2.7 – Typical Noise Abatement
2.2.5 COMPARTMENT FLOOR CUTOUTS
You must provide openings in the generator compart­ment for the following items (Figure 2.8):
• Engine exhaust and cooling air outlets
• Generator cooling air inlet
• Four holes for passage of generator mounting bolts. See Section 2.1.4 (Page 23).
Fuel lines and exhaust piping must not pene­trate into the vehicle living area.
Figure 2.8 — Compartment Floor Cutout
26 Generac®Power Systems, Inc.
2.3 COOLING AND VENTILATING AIR
It is absolutely essential that an adequate flow of air for cooling, ventilating and engine combustion be supplied to the generator set. Without sufficient air­flow, the engine/generator quickly overheats. Such overheating can cause serious operating difficulties and also may cause fire and personal injury. The installer must make sure that sufficient air is avail­able to the generator for cooling, ventilating and com­bustion. The installer also must provide for a path for exhausting the cooling air to the exterior of a com­partment, if so equipped.
Never use discharged cooling air for heating or permit such air to enter the vehicle interior. This air contains deadly carbon monoxide gas and other poisonous, flammable or explosive gases.
2.3.1 GENERATOR AIRFLOW
Engine operation drives cooling fans for the two-stage cooling air system. A pressure fan draws cooling air into the top of the generator (Figure 2.9). This airflow cools the engine/generator and electronic compo­nents. The second part of the cooling system, a suc­tion fan, draws air that is heated from a hot engine into a collector pan at the base of the unit. This heat­ed air (although cooler than exhaust muffler) is then deflected out the bottom toward the ground.
Figure 2.9 – Airflow Through Engine/Generator
2.3.2 COOLING AIR INLET OPENINGS
The minimum size of the air inlet opening, whether the generator is housed in a conventional compart­ment or not, is at least 100 square inches (see Figure 2.10). This rule applies whether inlet air is brought in through an opening in the compartment door, an opening in the vehicle skirt, through duct­work, or by any other means.
NOTE:
Screening, louvers or expanded metal that cover air openings restrict airflow. You must compensate for this by making the actual air opening propor­tionately larger. See Section 2.3.3 (Page 27).
Figure 2.10 – Air Inlet in Compartment Door
NOTE:
Be sure to meet the minimum clearances illustrat­ed in Figure 2.4 (Page 23).
When the unit is installed on a suspended mounting system, one of several different methods of supplying airflow may be used as follows:
• Provide a door in the vehicle skirt having an air inlet opening (Figure 2.11).
Figure 2.11 – Suspended Mount: Inlet Door
• Using ductwork (Figure 2.12, Page 27). The installer must be sure air is available to the top of the generator since air inlets are located at the top.
• By providing an opening in the vehicle skirt and space behind the generator for cooling airflow (Figure 2.13 Page 27). Recommended clearance behind the back of the generator is at least 1/2 inch (13 mm).
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 27
Figure 2.12 – Air Inlet Using Ductwork
Figure 2.13 – Air Inlet in Vehicle Skirt
2.3.3 COMPENSATING FOR RESTRICTIONS
Such materials as screening, louvers or expanded metal can restrict the free flow of air. Compensate for this restriction by making the actual air opening pro­portionately larger.
Some materials may offer only a 60 percent “free air inlet area.” Other more efficient materials may pro­vide up to a 90 percent free air inlet area. The per­centage of free air inlet opening is usually available from the material supplier or manufacturer.
To determine the actual air inlet opening size required, divide 100 square inches by the per­centage of free air inlet area for the material you will use.
For example: If you plan to use screening with an 80
percent free air inlet area, divide 100 by 0.8, which results in 125 square inches. Minimum actual size of air inlet opening in this case is 125 square inches.
2.3.4 TESTING THE INSTALLATION
Generac recommends testing the installation to be sure adequate cooling airflow is available to the unit before placing the unit into service. If the unit shows signs of overheating, you will need to enlarge the air openings. Never place a unit into service until absolutely certain that cooling and ventilation is ade­quate.
NOTE:
You must test the installation, especially if you bring in air from below the generator set.
2.4 GASOLINE FUEL SYSTEM
The installation of a gasoline fuel system (Figure
2.14) for a recreational vehicle generator set must
comply with applicable codes, standards and regula­tions. The entire fuel system must be completely free of leaks. There must be no possibility of gasoline vapors entering the vehicle interior.
Figure 2.14 – Generator Fuel System
Gasoline is highly flammable, and its vapors are explosive. Comply with all codes, standards and regulations pertaining to gasoline fuel systems used in recreational vehicle generators. Properly install and maintain the fuel system and keep it entirely free of leaks. Gasoline vapors must not enter the vehicle interior.
Factory installed generator fuel system components include (a) fuel filter, (b) 12-volt DC electric pump, (c) engine carburetor, and (d) interconnecting lines and fittings. Connect a fuel supply line to the fuel filter inlet. Use a flexible length of approved fuel hose between the fuel filter inlet connection and rigid fuel lines.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Fuel Pump
Fuel Filter
Fuel Line
VEHICLE FLOOR
MINIMUM
CLEARANCE
1-1/2"
VEHICLE
SKIRT
AIR
INLET
28 Generac®Power Systems, Inc.
2.4.1 FUEL TANK
Either the generator must share the vehicle engine's fuel tank, or you must install a separate fuel tank for the generator set. All fuel tanks installed on the vehi­cle must be constructed, installed and restrained so they comply with applicable codes, standards and regulations.
If the generator is to share the vehicle engine's tank, separate fuel pickup tubes are required for the engine and the generator. Generac recommends that you make the fuel pickup tube 2 to 3 inches (51 to 76 mm) shorter than the vehicle engine's pickup tube. This prevents the generator from depleting the entire fuel supply during prolonged generator operating periods.
Do NOT tee the generator fuel supply line into the vehicle engine fuel supply line. If this is done, the generator will be starved of fuel when both engines are operating at the same time. Also, while the vehicle engine is not run­ning, generator operation may drain the vehi­cle engine supply line, making it difficult to start the vehicle engine.
2.4.2 GENERATOR FUEL SUPPLY LINE
2.4.2.1 Rigid Fuel Lines
Those lines used to supply fuel from a tank to the generator must comply with applicable codes, stan­dards and regulations. The following general rules apply to rigid fuel lines:
• Rigid lines should be of annealed, seamless, drawn aluminum or steel.
• Lines and fittings must comply with SAE J512F, “Standard Automotive Fittings,” or with ANSI B126.26 (latest edition).
• Route the fuel line so that at least 2 inches (51 mm) of clearance is maintained between the line and any exhaust system parts.
• Do not attach electrical wiring to fuel lines. Route the wiring so it cannot come into contact with any fuel line.
• Route fuel lines so if they leak, fuel does not drip onto any electrical or exhaust system parts.
• Use nonferrous metal straps without sharp edges to secure fuel lines.
2.4.2.2 Flexible Fuel Line
Use an approved flexible length of fuel hose between the generator fuel inlet connection and rigid fuel lines. This prevents breaking of the line caused by vibration, shifting, settling or movement. The follow­ing rules apply:
• The flexible hose must comply with SAE J30B, “Standard for Fuel and Oil Hose.” It must be approved for use with gasoline.
• The hose should be at least 6 inches (152 mm) longer than is needed to prevent the hose from rupturing if the generator shifts or settles.
2.5 EXHAUST SYSTEM
The generator exhaust system must be safely and properly installed. Only approved mufflers and other exhaust system parts must be used. A properly installed exhaust system must be vapor tight, quiet and completely safe.
The generator engine gives off DEADLY carbon monoxide gas through its exhaust system. This dangerous gas, if breathed in sufficient concen­trations, can cause unconsciousness or even death. Never operate the generator set with the vehicle inside any garage or other enclosed area. DO NOT OPERATE THE GENERATOR IF THE EXHAUST SYSTEM IS LEAKING OR HAS BEEN DAMAGED. SYMPTOMS OF CARBON MONOX­IDE POISONING ARE (a) inability to think coher­ently; (b) vomiting; (c) twitching muscles; (d) throbbing temples; (e) dizziness; (f) headaches; (g) weakness; and (h) sleepiness. IF YOU FEEL ANY OF THESE SYMPTOMS, MOVE INTO FRESH AIR IMMEDIATELY. IF SYMPTOMS PERSIST, GET MEDICAL HELP. Do not operate the generator until its exhaust system has been inspected and properly repaired.
Never tee the generator engine exhaust pipe into the vehicle engine exhaust piping. This causes excessive back pressure on the genera­tor engine. Also, water from one engine can damage the other engine.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Generac®Power Systems, Inc. 29
2.5.1 MUFFLERS AND SPARK ARRESTORS
This muffler meets code and standard requirements of the U.S. Forest Service. Use only mufflers and parts approved by Generac. Any person(s) installing an unapproved muffler, or an unapproved exhaust system part, or modifying an exhaust system in any way that might cause a hazard, is liable for any dam­age, injury or warranty expense that might be caused by such unapproved installation or modification.
Failure to provide and maintain a spark arrestor may be in violation of the law. If this generator is used on any forest covered, brush covered or grass covered unimproved land, you must provide a spark arrestor. The vehicle owner or operator must maintain this device in good condition. In the state of California, the preceding is required by law (Section 4442 of the California Public Resources Code). Other states may have similar laws. Federal laws apply on federal lands.
2.5.2 TYPE OF EXHAUST SYSTEM
Two types of exhaust systems for PRIMEPACT series generators are available from Generac. They include the following:
• “Out-the-bottom” exhaust system dimensions are 1 5/16” O.D., model 9742.
• “Out-the-side” exhaust system dimensions are 1” O.D., 18 gauge, modelS 9743 and 9326.
NOTE:
No matter what type of exhaust kit best fits your recreational vehicle, the mounting base has open­ings for either “bottom-out” or “side-out” exhaust systems. Use the cover plate provided with the generator to cover the opening you do NOT use.
2.5.3 EXHAUST SYSTEM SAFETY
• Maintain a clearance of at least 3 inches (76 mm) between exhaust system parts and any com­bustible material (such as wood, felt, cotton, organic fibers or other like material). If you cannot maintain the 3-inch (76 mm) clearance, locate, insulate or shield the exhaust part(s) so that the temperature of any combustible material is not raised more than 117° F (65° C) above the ambient air temperature.
• Extend the exhaust system at least 1 inch (25 mm) past the outer edge of the vehicle. Do not terminate the exhaust system under the vehicle.
• Terminate the exhaust tailpipe such that exhaust gases will not be drawn back into the generator compartment and recirculated.
• If there is any possibility of the tailpipe or muffler being damaged, protect these damage-prone areas by means of a protective device (such as a skid bar).
• Install the generator exhaust system according to safe automotive practices.
• Use enough exhaust system hangers to prevent any part of the system from being dislocated.
• Use exhaust system parts recommended by Generac. Using unapproved exhaust mufflers and exhaust system parts is the responsibility of the person(s) installing such unauthorized parts.
• Do not terminate the exhaust system under any opening, window or vent that can be opened or is not permanently sealed from the vehicle interior.
• Exhaust piping must be large enough to prevent excessive back pressure on the generator engine.
• Never tee the generator engine exhaust pipe into the vehicle engine exhaust piping. This causes excessive back pressure on the generator engine. Also, water from one engine can damage the other engine.
• Plan exhaust system installation carefully. Comply with all applicable codes, standards and regula­tions.
2.6 ELECTRICAL CONNECTIONS
Be sure to read Section 1.6 on Page 20.
The following general rules apply to electrical con­nections in a recreational vehicle:
• Qualified electricians who are familiar with applic­able codes, standards and regulations should install electrical wiring.
• The wiring should comply with codes, standards and regulations. The National Electrical Code (NFPA 70), and state and local codes apply.
• Switches and circuit breakers should be of a type approved for use in recreational vehicles and must be mounted and installed to prevent damage from road shock.
• Wiring must be of adequate size, have approved insulative qualities and be properly supported.
• Conduit and wire openings into the generator com­partment (if used) must be vapor-sealed to prevent entry of flammable, explosive or poisonous gases into the vehicle.
2.6.1 ELECTRICAL JUNCTION BOX
Install an approved, square electrical junction box with a blank cover on the interior or exterior wall of the area you plan to install the generator (NOT on the generator). Route the generator's AC output leads into this junction box through approved flexible con­duit. This is the point of first termination for genera­tor AC output leads.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
30 Generac®Power Systems, Inc.
2.6.2 WIRING
• Wiring should be of stranded copper to reduce the chance that vibration may cause breakage.
• Wire gauge size should be large enough to handle at least 115 percent of the installed generator's rated maximum current.
• If neutral conductors are used, they must be the same size as other leg wires.
• Route power supply conductors from generator AC output leads T1 (red), T3 (black) and the green ground wire through approved flexible conduit to the electrical junction box on the compartment wall.
If flexible metal conduit is used between the gener-
ator and the compartment junction box, the con­duit end that terminates the compartment junction box must be vapor-sealed. Flexible metal conduit is NOT vapor tight along its entire length.
• From the junction box, route power supply wires through approved conduit to either (a) double­pole, double-throw transfer switch, or (b) approved isolation receptacle. Connecting to a transfer switch or isolation receptacle must pre­vent vehicle electrical circuits from being connect­ed to two different power supplies at the same time (such as generator and dockside power).
• Conductors must be rated 221° F (105° C) or must be of a larger conductor size.
2.6.3 GENERATOR AC CONNECTIONS
Generator AC output leads T1 (red), and T3 (black) come out of the generator as shown in Figure 2.17. Lead T1 (red) is “hot”. There is also a green lead that connects to ground in the junction box of the recre­ational vehicle.
Figure 2.17 – Generator AC Output Leads
Do NOT connect electrical loads in excess of any circuit breaker rating or you will develop problems with circuit breaker tripping, which causesalossofACoutput.Also,doNOT exceed the generator's rated wattage capacity. Add the watts or amperes of all lighting, appli­ance, tool and motor loads the generator will operate at one time. This total should be less than the unit's rated wattage/amperage capaci­ty.
2.6.4 CONDUIT
Route the connections between the generator and the junction box through approved, flexible conduit. The following general rules apply:
• Cut wiring to the required length and allow extra wire for junction box connections.
• Carefully prepare conduit ends to prevent sharp edges from cutting through wiring insulation.
• Route conduit so it does not interfere with genera­tor movement.
• If you use metallic conduit, vapor seal the end of the conduit where it enters the junction box. Do this because flexible metallic conduit is not vapor proof along its entire length.
2.6.5 ISOLATING DIFFERENT POWER SOURCES
Connections from the junction box must terminate in a double-pole, double-throw transfer switch (Figure
2.18, Page 31). An alternate method for isolating dif­ferent power sources is by using an isolating recepta­cle (Figure 2.19, Page 31). Whichever method you use, you must be certain that both power sources are NOT connected at the same time.
2.6.6 POWER SUPPLY CORD
The power supply cord must comply with all applic­able codes, standards and regulations. It must be large enough to handle the full amperage to which it will be subjected.
2.6.7 GROUND FAULT CIRCUIT INTER­RUPTERS
The National Electrical Code (NFPA 70, 551-7) requires that you install ground fault circuit inter­rupters (GFCIs) on all external and some internal electrical receptacles. Contact your manufacturer or dealer for recommendations.
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
T3 T2 T1
Green
(Ground)
Generac®Power Systems, Inc. 31
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Figure 2.18 — Transfer Switch Isolation Method
Figure 2.19 — Installation With Isolation Receptacle
32 Generac®Power Systems, Inc.
2.7 BATTERY INSTALLATION
2.7.1 RECOMMENDED BATTERY
Install a battery that meets the following require­ments:
• The battery must be a 12-volt, automotive type storage battery.
• For prevailing ambient temperatures above 32° F (0° C), use a battery rated 70 amp-hours and capable of delivering at least 400 cold-cranking amperes.
• For prevailing ambient temperatures below 32° F (0° C), use a battery rated 95 amp-hours and capa­ble of delivering at least 600 cold-cranking amperes.
NOTE:
If the battery is to be used to power other vehicle accessories, as well as start the generator, you may need a battery with a larger capacity.
2.7.2 BATTERY CABLES
Using battery cables that are too long or too small in diameter may cause a drop in voltage, which causes starting problems. For the best cold weather starting, the voltage drop between battery terminals and the generator connection point should not exceed 0.12 volts per 100 amperes of cranking current.
PRIMEPACT generators are rated at about 100 DC amperes of cranking current.
Select battery cables based on (a) cable length and (b) prevailing ambient temperatures. Generally, the longer the cable and the colder the weather, the larg­er the cable size must be, as shown in the chart.
* For warm weather, use No 2 cable up to 20 feet.
2.7.3 BATTERY CABLE CONNECTIONS
1. Connect the battery cable from the battery post or
terminal indicated by a POSITIVE, POS or (+) to the lug on the starter contactor (Figure 2.20).
NOTE:
Check to be sure the battery cable boot for the starter cable has been installed.
2. Connect the battery cable from the battery post
indicated by a NEGATIVE, NEG or (-) to the frame ground connection (Figure 2.20).
3. Connect cables so the connectors are clean
and tight.
Figure 2.20 – Connecting Battery Cables
2.7.4 BATTERY COMPARTMENT
Install the generator battery in its own, vented com­partment. Place the battery compartment away from any source of heat, sparks or flame.
Provide ventilation openings in the battery compart­ment. The minimum size of openings should be 2 square inches at the top of the compartment. Mount the battery on a strong, rigid supporting structure, where leaks and spills of battery fluid will not cause damage.
2.8 OPTIONAL ACCESSORIES
A plug-in receptacle (Figure 2.21) is provided on the generator set, above the muffler enclosure. Use this receptacle to connect an optional remote-mounted start/stop panel to the generator. Installation of such a panel will permit you to start and stop the genera­tor engine from any convenient location inside the vehicle.
Figure 2.21 – Remote Panel Plug-in Receptacle
Section 2 – Installation
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
CABLE LENGTH
in Feet (meters) CABLE SIZE
0to10(0to3) 2*
11 to 15 (3.4 to 4.5) 0
16 to 20 (4.5 to 6) 000
Generac®Power Systems, Inc. 33
2.8.1 REMOTE PANEL MODELS
The remote panels mount a rocker type start/stop switch, a “Generator Run” advisory lamp and an hourmeter. The hourmeter should be used in con­junction with the maintenance operations found in Part I of this manual.
• Model 004057 includes the remote panel and a 10 foot long, 4 wire harness.
• Model 004184 includes the remote panel and a 30 foot long, 4 wire harness.
3.1 POST INSTALLATION TESTS
The air-cooled generator set was factory tested and adjusted. You should not be required to adjust the unit any further except under special circumstances.
Do not make any unnecessary adjustments. Factory settings are correct for most applica­tions. When making adjustments, however, be careful to avoid overspeeding the engine.
3.2 BEFORE INITIAL START-UP
Before starting, complete the following:
1. Check the engine crankcase oil level and, if nec-
essary, fill to the dipstick “FULL” mark (cross­hatched area) with the recommended oil. Do not fill above the FULL mark.
2. Check the fuel supply. Gas fuel lines must have
been properly purged and leak tested in accor­dance with applicable fuel codes. All fuel shutoff valves in the fuel supply lines must be open.
3.3 INITIAL START
When you are absolutely certain that the unit has been properly installed and prepared for use, start the engine as follows:
1. Turn off all electrical loads. Do this by setting the
generator’s main circuit breakers to their “OFF” (or open) position.
2. Refer to Part I, Section 2.5, “Starting the
Generator” (Page 8), for cranking and starting instructions. The engine may require more cranking for initial starting since the fuel lines have to be primed (use of the primer switch will shorten this time).
3. Let the engine warm up for about five minutes to allow internal temperatures to stabilize.
4. Carefully inspect the engine/generator for fuel, oil and exhaust system leaks. Before proceeding to the next step, correct any leakage immediately.
5. When all tests and adjustments at no-load are completed, apply electrical loads and check for proper operation under load. See Section 3.4. Run the unit at least 30 minutes with loads applied.
6. Turn off all electrical loads by setting the genera­tor’s main circuit breakers to their “OFF” (or open) position.
7. Let the unit run at no-load for a few minutes to stabilize internal engine/-generator temperatures. Then, shut down the engine.
NOTE:
The generator set was thoroughly tested and adjusted at the factory before shipping. No addi­tional adjustment should be necessary. Only qual­ified service technicians who have been trained should perform adjustments outlined in this man­ual.
3.4 TESTING UNDER LOAD
Apply electrical loads equal to about 75 to 100 per­cent of the unit's rated wattage/amperage capacity.
Let the unit run at least 30 minutes with load applied. During this part of the test, check that the unit is not running excessively hot and that adequate cooling airflow is available. You must not allow the unit to overheat during prolonged operation.
NOTE:
The generator engine is equipped with a high tem­perature switch. The switch has normally closed (N.C.) contacts. When the engine temperature is too high, switch contacts close, and the engine shuts down automatically.
GENERAC RECOMMENDS THAT YOU TEST THE GENERATOR FOR ADEQUATE COOLING.
Section3–PostInstallation Start-up and Adjustments
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
34 Generac®Power Systems, Inc.
3.5 INSTALLATION CHECKLIST
LOCATION AND SUPPORT
Generator is properly located.
Generator is properly supported.
Generator is properly restrained.
GENERATOR COMPARTMENT
Compartment construction is proper.
Holes/Openings are vapor-sealed.
Compartment size is correct.
Compartment is vapor-sealed.
Sound insulation is correct.
Floor cutouts are properly completed.
COOLING AND VENTILATING AIR
Airflow is adequate.
Air inlet opening is correct.
Compensate for restrictions.
Check that installation has been tested.
GASOLINE FUEL SYSTEM
Fuel tank complies with all applicable codes.
Fuel system is properly installed and checked
for leaks.
EXHAUST SYSTEM
Exhaust system complies with all applicable
codes.
Exhaust system is properly and safely installed.
ELECTRICAL CONNECTIONS
Connections comply with local code requirements
and all National Electrical Codes.
Junction box is properly installed.
Wiring meets all standards.
All connections are correct.
Conduit is properly installed and sealed.
Generator is properly bonded to the vehicle.
BATTERY INSTALLATION
Recommended battery is installed.
Recommended cables are installed.
Cables are clean and tight.
Cables are connected properly.
Proper ventilation is provided.
Terminals are coated with anti-corrosion grease,
and terminal covers are positioned.
OPTIONAL ACCESSORIES
Check that remote start/stop panels (if used) are
installed properly.
Check that hourmeter kit (if used) is installed
properly.
Check that any other options and accessories (if
used) are installed properly.
POST INSTALLATION TESTS
Check that all tests are completed properly.
Section3–PostInstallation Start-up and Adjustments
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
DATE OF INSTALLATION ____________________________________________________
NAME OF INSTALLER ______________________________________________________
SIGNATURE OF INSTALLER ________________________________________________
Generac®Power Systems, Inc. 35
Section4–Troubleshooting
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
4.1 TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
Engine won’t crank. 1. 15 amp fuse blown. 1. Replace blown fuse.
2. Loose, or corroded or defective 2. Tighten, clean or replace, battery cable(s). as necessary.
3. Battery is discharged or defective. 3. Recharge or replace battery.
4. Defective starter contactor. 4. Replace starter contactor.
5. Defective starter motor. 5. Replace starter motor.
6. Defective Start/Stop switch 6. Replace switch
7. Defective Engine Control Board 7. Contact an authorized service dealer.
Engine cranks, won't start. 1. Out of fuel. 1. Refill fuel tank.
2. Fuel shutoff valve is closed. 2. Open fuel shutoff valve(s).
3. Fuel pump not operating. 3. Repair or replace pump.
4. Automatic choke not operating properly. 4. Repair, replace or adjust.
5. Engine is flooded. 5. Wait 5-10 minutes; try again.
6. Fuel filter is clogged. 6. Replace filter if clogged.
7. Engine spark plugs defective. 7. Clean, regap or replace as needed.
8. Bad ignition magneto on engine. 8. Replace if defective.
9. Bad carburetor. 9. Adjust, repair or replace.
10. Dirty air cleaner. 10. Clean or replace as needed.
Engine starts hard, runs rough. 1. Dirty engine air cleaner. 1. Clean or replace as needed.
2. Automatic Choke sticking. 2. Free choke linkage as needed.
3. Defective spark plugs. 3. Clean, regap or replace.
4. Defective ignition magneto. 4. Replace it if defective.
Engine starts, then shuts down. 1. Engine oil level is low. 1. Add oil as needed.
2. Bad low oil pressure switch. 2. Replace, if bad.
3. Defective High Temp Switch 3. Replace Switch, if bad.
4. Water in fuel. 4. Drain fuel tank and refill.
No AC output voltage. 1. Main breaker(s) open. 1. Close main breaker(s).
2. Transfer switch (if so equipped) is 2. Reset transfer switch. set to wrong position.
3. Failure in vehicle electrical system. 3. See vehicle manual.
4. Generator component failure. 4. Contact an authorized service facility.
36 Generac®Power Systems, Inc.
Section 5 – Electrical Data
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Wiring Diagram & Electrical Schematic — Drawing No. 0D6579
Generac®Power Systems, Inc. 37
Section 5 – Electrical Data
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Wiring Diagram & Electrical Schematic — Drawing No. 0D6579
38 Generac®Power Systems, Inc.
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Base and Pulleys – Drawing No. 0D6577-A
Generac®Power Systems, Inc. 39
ITEM PART NO. QTY. DESCRIPTION
1 086318 1 BASE, MOUNTING 2 090141 1 GROUND CABLE 3 046911 4 MOUNT, (RUBBER) 4 025017 8 CAPSCREW, HEX HD.3/8"-16 X 1/2" 5 046526 2 LOCKWASHER-M10 6 022129 8 LOCKWASHER, 5/16" -M8 7 072391 2 SKID, RUBBER MOUNT 8 077603 2 SAFETY BOLT 5/16"-18 x 3 1/2"
9 022259 2 NUT, HEX-5/16"-18 10 052858 6 NUT, FLANGED LOCK-M8-1.25 11 051730 2 CAPSCR. HEX HD.-M8-1.25 x 60mm 12 029459 2 SPRING, BELT TENSION 13 075215 2 WASHER, SPRING CNTR 14 073146 4 SLIDE (NYLON) 15 075209 2 SUPPORT, NYLON SLIDE 16 073174 1 MANIFOLD, EXHAUST 17 079678 2 RING, SEALING 18 040976 4 SHCS, M8-1.25 x 20mm 19 072383 2 GASKET, COLLECTOR PAN 20 090859 1 COVER PLATE -EXTERNAL 21 075224D 1 PULLEY, ENGINE (PP70)
075224G 1 PULLEY, ENGINE (PP50)
22 073106D 1 PULLEY, ALT. (PP70)
073106G 1 PULLEY, ALT. (PP50) 23 075216 1 BELT (POLY V 4L)-40" 24 049451 1 WASHER, PULLEY RETAINER,
7GA. 0.41" x 1.62" 25 042633 1 HHCS, 3/8"-24 X 1" (GRADE 5) 26 077017 1 GUIDE, BLOWER HOUSING 27 073118 1 CAPSCR., HEX HD.-3/8"-24 x 2-1/4" 28 074906 7 TAPTITE, M6-1.00 x 20mm 29 091123 1 BRACKET-FUEL PUMP 30 072375 1 HOUSING, BLOWER 31 073185 1 SPACER, BLOWER HOUSING 2-3/8" 32 022097 7 LOCKWASHER, ¼"-M6 33 077682 1 CAPSCR. HEX HD.-M5-0.80 x 80mm 34 075242 4 SPRING, GENERATOR SET MT 35 049813 2 NUT, HEX M6 x 1.0mm 36 045757 2 CAPSCREW, HEX HEAD-
M6-1.0 x 25mm 37 090475 1 FUEL PUMP 38 087769 1 FUEL FILTER 39 087768 1 FITTING-1/8" PIPE TO ¼" TUBE 40 087770 1 FUEL LINE 41 022413 1 CAPSCREW, HEX HD.-1/4"-20 x 1" 42 0D4788 1 PIPE PLUG 3/8" SQ. HD. 43 075710A 1 FILL TUBE & PLUG 44 074958 1 CAP & DIPSTICK ASSEMBLY 45 067871 1 O-RING, CAP 46 0A5508 1 OIL FILL TUBE GASKET
ITEM PART NO. QTY. DESCRIPTION
47 075711 1 PIPE, OIL DRAIN ADAPTOR 48 0A8475 1 SPECIAL LOCK WASHER, M5 49 0A5802 1 TINNERMAN CLIP 50 022237 8 LOCKWASHER, 3/8" 51 022145 2 FLATWASHER, 5/16" -M8 52 0742600133 1 CABLE, STARTER 53 0D1227 1 CONTACTOR, STARTER 54 0D1741A 1 BOOT, BATTERY CABLE 55 0D1741 2 BOOT, BATTERY CABLE 56 073179 1 OIL FILTER SUPPORT 57 070185 1 FILTER, OIL (FRAM#PH3614) 58 0A8584 1 SWITCH OIL PRESSURE 59 074948 3 FITTING-5/16" 60 074950 1 TUBE, OUTER OIL 61 074951 1 TUBE, INNER OIL 62 073134 1 ADAPTOR, OIL FILTER ADAPTER 63 038750 3 CAPSCREW, HEX HEAD-
M6-1.00 x 30mm 64 074949 1 FITTING, BARBED 90-DEGREE-5/16" 65 068548 1 GASKET, OIL FILTER ADAPTER 66 0C4006 1 CABLE, BATTERY 67 029289 -- TAPE, FOAM-1/16" THICK x 8' 68 024114 2 NUT, HEX 5/16 - 24 STEEL 69 075281 1 SWITCH, HIGH TEMPERATURE 70 0C1085 2 SCREW, PAN HEAD-M3-0.50 x 8mm 71 043182 2 LOCKWASHER-M3 72 022158 2 NUT, HEX #10-32 STEEL 73 075237 4 WASHER, SPRING RETAINER 74 0D1624 1 BOOT, OIL PRESSURE SWITCH 75 075474 1 BOOT, TEMPERATURE SWITCH 76 090800 1 ELBOW, EXHAUST 77 094670 1 CLAMP, EXHAUST 78 075226 1 COVER, AIR 79 056893 23 CRIMPTITE, NO. 10-24 x 1/2" 80 075229 1 SLIDE PAN, GASKET 81 0D3158 1 WELDMENT, SLIDE PAN-RV 82 079246 6 CAPSCREW, HEX HEAD- M6-1.00 x
16mm WITH LOCK WASHER 83 022473 7 FLATWASHER, ¼" -M6 84 022152 2 WASHER, LOCK #10 85 072384C 1 COVER, EXHAUST OUTLET 86 092120 2 NUT, LOCK TRIC M6-1.0 87 077643 1 GASKET, EXHAUST OUTLET 90 0A1658 3 LOCKWASHER, SPECIAL ¼" 91 090088 1 CLAMP, VINYL COATED 93 081105 2 FLANGE NUT, (SPECIAL) 5/16"-18 94 023897 6 FLAT WASHER, #10 -M5 95 067210A 1 DECAL-GROUND 96 045756 9 TAPTITE, M6-1.00 x 10mm 97 022131 1 FLATWASHER, M10
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Base and Pulleys – Drawing No. 0D6577-A
40 Generac®Power Systems, Inc.
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Alternator and Control Panel – Drawing No. 0D6578-A
Generac®Power Systems, Inc. 41
ITEM PART NO. QTY. DESCRIPTION
1 0C9675 1 LOWER BEARING CARRIER 2 073163H 1 ROTOR ASSEMBLY (PP70)
093940H 1 ROTOR ASSEMBLY (PP50)
3 021441H 1 STATOR ASSEMBLY (PP70)
080095H 1 STATOR ASSEMBLY (PP50) 4 073159 1 BALL BEARING 5 031971 1 BALL BEARING 6 0C9674 1 UPPER BEARING CARRIER 7 077006 4 STUD-STATOR 8 052858 4 M8-1.25 FLANGE LOCK NUT 9 066386 1 BRUSH HOLDER
10 066849 2 M5-0.8 x 16 LG. TAPTITE 11 027756 4 NYLON WASHER 12 086314 1 GENERATOR TOP HOUSING 13 075234 1 RESISTOR 14 022473 2 ¼"/ M6-FLAT WASHER 15 022097 5 ¼"/ M6-LOCK WASHER 16 055816 1 M6-1.0 x 70 LG. CAPSCREW 17 090141 2 GROUND CABLE 18 0A1658 2 SPECIAL LOCK WASHER, ¼" 19 074906 4 M6-1.0 x 20 LG. TAPTITE 20 092234 1 CONTROLLER P.C.B. 21 0D2724 2 BOOT, ROCKER SWITCH 22 022129 4 5/16"/ M8 LOCKWASHER 23 031879 2 WASHER FLAT #4 24 086316 1 PANEL SHEET METAL 25 053650 1 4-PIN CONNECTOR 26 0C4258 1 CONDUIT ASSEMBLY 27 075244 1 ASSEMBLY, REMOTE CABLE 28 023484S 1 BUSHING 29 074908 1 M5-0.8 x 10 LONG TAPTITE 30 075476 4 M4-0.7 x 16 LG. CAPSCREW 31 022264 4 #8/ M4-LOCK WASHER 32 065795 1 BATTERY CHARGER RECTIFIER
ITEM PART NO. QTY. DESCRIPTION
33 090987 2 M3-0.5 x 12 LG. PPHMS 34 086317A 1 PANEL SUPPORT BRACKET 35 075235 2 M5-0.8 x 30 LG. CAPSCREW 36 082737 4 VIBRATION MOUNT 37 049813 4 M6-1.0 HEX NUT 38 049815 1 M5-08 x 16 LG. HEX HD. CAPSCR. 39 043182 2 M3-LOCK WASHER 40 0A8475 3 M5-SPECIAL LOCK WASHER 41 054502 1 C/BREAKER 3.0A 42 094192 1 HARNESS, CUSTOMER CONNECTION 43 083049 1 REGULATOR VOLTAGE 44 022152 6 M5-LOCK WASHER 45 051716 4 M5-0.8 HEX NUT 46 082081 1 CIRCUIT BREAKER 30A (PP70)
074968 1 CIRCUIT BREAKER 25A (PP50) 47 045771 4 M8-1.25 HEX NUT 48 025105 4 #6-32 x ¼" SCREW W/LOCK WASHER 49 086315 1 PANEL COVER 50 090734 4 M4-0.7 x 12 LG. CAPSCR.W/LOCK-
WASHER & FLAT WASHER 51 022985 1 #6-FLAT WASHER 52 032300 1 FUSE HOLDER 53 022676 1 FUSE AGC-15A. 54 087798 1 SWITCH S.P.D.T. 6A.-(START-STOP) 55 092113 1 SWITCH S.P.D.T.-(FUEL PUMP) 56 075210A 1 TERMINAL BLOCK 57 0A8475A 1 #8 SPECIAL LOCK WASHER 58 051715 1 M4-0.7 HEX NUT 59 090157 1 DECAL, CB RATING 30A. (PP70)
092854 1 DECAL, CB RATING 25A. (PP50) 60 055440 2 M5-0.8 x 25, CAPSCREW 61 094191 1 DECAL, CUSTOMER CONNECTION 62 031791 1 CLAMP, HOSE 63 023897 3 #10/ M5-FLAT WASHER
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Alternator and Control Panel – Drawing No. 0D6578-A
42 Generac®Power Systems, Inc.
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Engine Sheet Metal – Drawing No. 0D3150-A
Generac®Power Systems, Inc. 43
ITEM PART NO. QTY. DESCRIPTION
1 --------- 1 SEE ENGINE EXPLODED VIEW of ENGINE 2 99258 1 KEY-WOODRUFF 6 x 22MM 3 67198N 1 BEVELLED WASHER 4 67890 1 HEX NUT 5 87865 1 PLUG, FLYWHEEL ACCESS 6 A4456 1 3/8" SPECIAL LOCK WASHER 7 86313 1 HOUSING, ENGINE TOP
8 56893 23 SCREW (CRIMPTITE) NO. 10-24 x 1/2" 10 87750 1 SCROLL, FLYWHEEL 11 74916 1 COVER, BASE CYL. #2 12 74908 9 SCREW (TAPTITE) M5 x 10MM 13 73190 1 WRAPPER CYL. #2 14 78858 1 COVER, VALLEY 15 78859 1 WRAPPER, CYL. #1 16 74902 2 WRAPPER, BARREL 17 66476 4 HHCS/LW-M6 x 1.0 x 12MM 19 73191 1 COVER, BASE CYL. #1 20 42907 2 CAPSCREW, HEX HD.-M8 x 1.25 x 16MM 21 22129 2 LOCK WASHER-M8 22 75246 4 SCREW (TAPTITE) 3/8"-16 x 1-1/4" 23 133-74260 1 WIRE ASSEMBLY-NO, 16 24 74900 1 STARTER COVER 25 73186 1 WRAPPER, CRANKCASE 26 81108 1 BUSHING, SNAP 27 22717B 1 GROMMET -RUBBER 28 22717A 3 GROMMET -RUBBER 29 67866A 1 O-RING 30 77001A 1 PLUG, OIL FILL 31 73132 2 BOOT, SPARK PLUG 33 87858A 1 GROUND WIRE ASEMBLY-CYL. #1 34 29289 2FT. FOAM TAPE 35 87858B 1 GROUND WIRE ASSEMBLY-CYL. #2 36 50277 1 OIL DRAIN DECAL
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Engine Sheet Metal – Drawing No. 0D3150-A
44 Generac®Power Systems, Inc.
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Engine – Drawing No. 79216-G
Generac®Power Systems, Inc. 45
ITEM PART NO. QTY. DESCRIPTION
1 069331 1 CYLINDER ASSEMBLY 2 069333 1 SLEEVE BEARING 3 067805 1 OIL SEAL 4 0851100101 1 NO. 1 CYLINDER HEAD ASSEMBLY 5 0851100102 1 NO. 2 CYLINDER HEAD ASSEMBLY 6 070169 4 SEALING WASHER 7 069332 2 CYLINDER HEAD GASKET 8 0851100104 1 BREATHER ASSEMBLY
9 072315 1 BREATHER GASKET 10 089967 1 BREATHER SCREW 11 070596 1 BREATHER TUBE 12 069336 1 OIL SUMP GASKET 13 069325 8 CYLINDER HEAD BOLT 14 067888 2 3/8” NPT OIL DRAIN PLUG 15 072334 1 CRANKSHAFT ASSEMBLY 16 075247 1 OIL SUMP ASSEMBLY 17 067924 1 OIL SEAL 18 067878 9 OIL SUMP BOLT 19 075248 2 STANDARD PISTON ASSEMBLY 20 075249 2 STANDARD PISTON RING SET 21 069327 4 PISTON PIN RING 22 075250 2 PISTON PIN ASSEMBLY 23 089972 2 CONNECTING ROD ASSEMBLY 24 072346 4 CONNECTING ROD BOLT 25 069316 2 EXHAUST VALVE 26 069317 2 INTAKE VALVE 27 067816 4 VALVE SPRING 28 069320 4 VALVE SPRING RETAINER 29 070513 4 VALVE KEEPER 30 070584 4 VALVE TAPPET 31 070530 1 CAMSHAFT ASSEMBLY 32 072358 1 INTAKE MANIFOLD 33 069379 2 CARBURETOR MOUNTING GASKET 34 067895 2 INTAKE MANIFOLD GASKET 35 070594 2 CARBURETOR MOUNTING BOLT 36 067158 4 INTAKE MANIFOLD MOUNTING BOLT 37 068574 1 1/8” NPT PLUG PIPE 38 068554A 1 GOVERNOR SHAFT SEAL 39 068573 1 OIL PUMP O-RING 40 070506 1 OIL GALLEY O-RING 41 070554 1 CARBURETOR SPACER 42 070568 4 ROCKER ARM STUD
ITEM PART NO. QTY. DESCRIPTION
43 075253 4 WASHER VALVE COVER SEAL 44 067885 4 M6 NYLON NUT 45 075254 4 VALVE ADJUST SCREW 46 070535 1 OIL SCREEN 47 0C2881 1 STARTER MOTOR (NOT SHOWN) 50 067891 1 IGNITION COIL 51 075236 4 IGNITION ARMATURE SCREW 52 072347 2 SPARK PLUG 53 075258 1 ENGINE GASKET KIT 57 066480 1 AIR CLEANER GASKET 59 072361 1 GOVERNOR SHAFT BUSHING 60 072362 1 GOVERNOR SHAFT BUSHING 61 070199 1 BREATHER BAFFLE 62 072366 1 COTTER PIN 64 072365 1 GOVERNOR SHAFT WASHER 65 068555 2 CRANKCASE DOWEL 66 067806 4 CYLINDER HEAD DOWEL 73 068572 2 OIL PUMP SCREW 74 075272 2 SPARK PLUG TERMINAL 75 070122 4 VALVE STEM SEAL 76 067910 2 INTAKE VALVE SEAT 78 067813 4 VALVE GUIDE 81 070592 1 AIR CLEANER BASE 82 073123 1 AIR FILTER (NOT SHOWN) 83 070593 1 AIR CLEANER COVER 84 0C3633 1 AIR CLEANER COVER SCREW 85 067156 2 AIR CLEANER BASE SCREW 86 069341 1 PRE-CLEANER ELEMENT 88 070597 1 AIR INLET TUBE 89 072305 1 BREATHER DEFLECTOR 90 067920 2 VALVE COVER GASKET 91 069328 1 VALVE COVER 92 070547 1 OIL PUMP ASSEMBLY 93 070536 1 GOVERNOR SLIDER 94 070577 4 PUSH ROD 95 070599 4 ROCKER ARM ASSEMBLY 97 070566 4 ROCKER ARM SUPPORT 98 075271 1 VALVE OVERHAUL KIT
99 067897 2 EXHAUST GASKET (NOT SHOWN) 100 091481 1 GASKET AND CAP ASSEMBLY 101 091480 1 ROCKER ARM COVER 102 0D1198 1 GOVERNOR CRANK
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Engine – Drawing No. 79216-G
46 Generac®Power Systems, Inc.
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators Carburetor – Drawing No. 0D6576-A
Generac®Power Systems, Inc. 47
ITEM PART NO. QTY. DESCRIPTION
1 073112B 1 CARBURETOR ASSEMBY 2 074962C 1 SPRING, GOVERNOR - GREEN (PP55G/LP, PP66G/LP)
074962E 1 SPRING, GOVERNOR - PURPLE (PP50G-50Hz)
074962G 1 SPRING, GOVERNOR - BROWN (PP70G/LP, PP70G-50Hz) 3 070155 1 LEVER, GOVERNOR 4 070108 1 ROD, GOVERNOR TO CARBURETOR 5 056893 5 SCREW CRMPTIT 10-24 X ½ 6 074961 1 BRACKET, GOVERNOR ADJUSTER 7 047227 1 SCREW, GOVERNOR ADJUSTER 8 037398 1 NUT, HEX LOCK (NYLON) 9 073131 1 BRACKET, AIR CLEANER SUPPORT
10 066476 2 SCREW, HHSW M6-1.0 X 12 11 070575 2 SCREW, HHSW M6-1.0 X 25 12 070125 1 SPRING, ANTI-LASH 13 073374 1 BRACKET, CHOKE SUPPORT 14 074947 1 ROD, CHOKE CONTROL 15 089473 1 BI-METAL ASSEMBLY, CHOKE 16 091306 1 SOLENOID, CHOKE 17 077091 1 HAIR PIN, COTTER 18 031879 4 WASHER FLAT #4 19 022159 4 WASHER LOCK #4 20 077075 1 COVER, CHOKE COIL 21 072536 4 SCREW, PPMS #4-40 X ¼ 22 087770 1 TUBE FUEL GASOLINE - 5/16" I.D. 23 074946 1 LINK, CHOKE 24 070594 2 SCREW HHC M6-1.0 X 93 WITH LOCK WASHER 25 030340 1 HOSE ¼" I.D., 4.5" LONG 26 0C2338D 1 DECAL, AIR CLEANER PRIMEPACT 70G (50Hz)
0C2338F 1 DECAL, AIR CLEANER PRIMEPACT 50G (50Hz)
27 075252 1 KIT, CARBURETOR OVERHAUL-NOT SHOWN 28 0A7782A 1 FLYWHEEL ASSEMBLY 29 040173 2 CLAMP, HOSE (SCREW TYPE) 30 066829 2 RIVET-1/8" DIAMETER x 1/8" LONG 31 075944 1 BRACKET, GOVERNOR SPRING
Section 6 — Exploded Views and Parts Lists
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
Carburetor – Drawing No. 0D6576-A
48 Generac®Power Systems, Inc.
Section7–Warranty
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
CALIFORNIA AND FEDERAL EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and the United States Environmental Protection Agency (EPA), together with Generac Power Systems, Inc. (Generac), are pleased to explain the Emission Control System Warranty on your new engine.* New utility, and lawn and garden equipment engines must be designed, built and equipped to meet stringent anti-smog stan­dards for the state of California and the federal government. Generac will warrant the emission control system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modification or improp­er maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition and exhaust systems. Generac will repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1997 and later model year engines are warranted for two years as hereinafter noted. If, dur­ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance on your engine. However, Generac cannot deny warranty solely because of the lack of receipts or for your failure to ensure the completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect, improper maintenance or unap­proved modifications, or the use of counterfeit and/or ‘grey market’ parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a prob­lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility. To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System Warranty (ECS Warranty), which is provided to you by Generac pursuant to California and federal law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe important rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty ser­vice, evidence must be presented showing the date of the sale to the original purchaser/owner. The purchaser/owner shall be responsible for any expenses or other charges incurred for service calls and/or transportation of the product to/from the inspection or repair facilities. The purchaser/owner also shall be responsible for any and/or all damages or losses incurred while the engine is being transported/shipped for inspection or warranty repairs.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol­lowing address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part 1
Generac®Power Systems, Inc. 49
Section7–Warranty
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1997 and later model year engines:
(a) Applicability: This warranty shall apply to 1997 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall contin­ue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment, and to each subsequent purchaser/owner, that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the EPA and CARB pursuant
to their respective authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine manu­facturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection (4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-
ble for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the purchaser/owner. Such use shall not reduce Generac’s ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or ‘grey market’ parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim. Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of such an unapproved, add-on, modified, counterfeit and/or ‘grey market’ part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
*Generac engine types covered by this warranty statement include the following:
1) Utility
2) Lawn and Garden Equipment
3) Recreational Vehicle (RV) Generator
4) Industrial Mobile (IM) Generator
Part 2
1) Fuel Metering System:
1.1) Gasoline carburetor assembly and its internal components (if so equipped).
a) Fuel filter (if so equipped) b) Carburetor gaskets c) Fuel pump (if so equipped)
1.2) LPG carburetion assembly and its internal components (if so equipped).
a) Fuel controller (if so equipped) b) Mixer and its gaskets (if so equipped) c) Carburetor and its gaskets (if so equipped) d) Primary gas regulator (if so equipped) e) LP liquid vaporizer (if so equipped)
2) Air Induction System including: a) Intake pipe/manifold b) Air cleaner
3) Ignition System including: a) Spark plug b) Ignition module
4) Catalytic Muffler Assembly (if so equipped) including: a) Muffler gasket b) Exhaust manifold
5) Crankcase Breather Assembly including: a) Breather connection tube
Part No. 0D6583 Revision 0 (10/26/01) Printed in U.S.A.
Section7–Warranty
PRIMEPACT 50 and 70 (50Hz) Recreational Vehicle Generators
GENERAC POWER SYSTEMS THREE-YEAR LIMITED WARRANTY
FOR RECREATIONAL VEHICLE GENERATORS
NOTE: ALL UNITS MUST BE INSTALLED BY GENERAC POWER SYSTEMS AUTHORIZED SERVICE FACILITIES.
For a period of 3 (three) years or 2,000 (two thousand) hours of operation from the date of original sale, whichever occurs first, Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac generators sold and rated for “Recreational Vehicle” (RV) appli­cations, as Generac has defined Recreational Vehicle generator applications.
WARRANTY SCHEDULE – COMMERCIAL APPLICATIONS
YEAR ONE – 100% (one hundred percent) coverage on part(s), labor, removal and reinstallation listed:
• Engine – All components
• Alternator – All components
WARRANTY SCHEDULE – CONSUMER/PERSONAL APPLICATIONS
YEARS ONE AND TWO – 100% (one hundred percent) coverage on part(s), labor, removal and reinstallation listed:
• Engine – All components
• Alternator – All components YEAR Three – 100% (one hundred percent) only on selected part(s) and labor listed (Any labor and part(s) not listed, and removal and
reinstallation are the owner’s responsibility):
Rotor, Stator, IMPACT Series Variable Speed Computer Control Board Part Numbers A3369, A6060, Cylinder Block, Cylinder Head,
Crankshaft, Piston(s), Valve, Valve Lifter(s), Intake and Exhaust Manifolds
FOR THE LIFE OF THE RECREATIONAL VEHICLE GENERATOR (IF SO EQUIPPED)
The drive train belt and pulleys (if so equipped) on generators used in recreational vehicles shall be warranted against failure due to defec­tive materials or normal usage for the life of the generator. For the original purchaser/owner, this drive train warranty shall include part(s) and labor (removal and reinstallation are not included) plus $50 (fifty dollars – U.S.) payment upon return of the failed belt or pulley by the original purchaser/owner. For subsequent purchaser/owner, this drive train warranty shall cover belt and pulley part(s) ONLY (labor not included). Labor, removal and reinstallation is the responsibility of the subsequent purchaser/owner.
Generac RV generators manufactured prior to December 31, 1997, DO NOT have a transferable warranty. Generac RV generators manu­factured after January 1, 1998, have a transferable warranty to the second owner ONLY for the remainder of the three-year limited war­ranty. Proof-of-purchase is required and must be presented to a Generac Authorized Warranty Service Dealer prior to the performance of any warranty service.
All warranty expense allowances are subject to the conditions defined in Generac’s WARRANTY PLOICY AND PROCEDURES MAN UAL.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
Generac RVgenerators that utilize non-Generac replacement parts.
Costs of normal maintenance, adjustments, installation and start-up.
Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all
mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
Damage related to rodent infestation.
Products that are modified or altered in a manner not authorized by Generac in writing.
Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replace-
ment of the defective part(s).
Failure due to misapplication.
Telephone, cellular phone, facsimile, internet access or other communication expenses.
Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
Expenses related to “customer instruction” or troubleshooting where no manufacturing defect is found.
Rental equipment used while warranty repairs are being performed.
Overnight freight costs for replacement part(s).
Overtime labor.
Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GEN­ERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GEN­ERAC’S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limita­tion may not apply to you.
This warranty gives you specific legal rights. You also may have other rights that vary from state to state.
GENERAC
®
POWER SYSTEMS, INC.
P.O.BOX 297
WHITEWATER, WI 53190
Revised 10/05/01