Generac Power Systems 005914-0, 005915-0, 005916-0 Overview

STANDBY GENERATORS
ISO
9001: 2008
8 kVA - 10 kVA - 13 kVA
Air-Cooled Gas Engine Generator Sets
INCLUDES:
• Tri-ligual Two Line LCD Digital Nexus™ Controller (English/Spanish/French)
• Electronic Governor
• External Main Circuit Breaker & System Status LED
• Flexible Fuel Line Connector
• Composite Mounting Pad
• Natural Gas or LP Gas Operation
Standby Power Rating
Model 005914-0 (Steel - Bisque) - 8 kVA 50Hz Model 005915-0 (Steel - Bisque) - 10 kVA 50Hz Model 005916-0 (Steel - Bisque) - 13 kVA 50Hz
FEATURES
¡ INNOVATIVE DESIGN & PROTOTYPE TESTING are key components
of Generac's success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, allows you to choose Generac with the confidence that these systems will provide superior performance.
¡ TEST CRITERIA:
PROTOTYPE TESTED
MOTOR STARTING ABILITY
SYSTEM TORSIONAL TESTED
¡ SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION:
This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine.
¡ SINGLE SOURCE SERVICE RESPONSE from Generac's dealer
network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component.
ISO
9001: 2008
FEATURES Generac Standby Generator - 8 kVA - 10 kVA - 13 kVA
•Generac (OHVI) Design
•”Spiny-lok” cast iron cylinder walls
•Electronic ignition
•Full pressure lubrication system
ENGINE
•Low oil pressure shutdown system
•High temperature shutdown
•Revolving field
• Skewed stator
•Displaced phase excitation
GENERATOR
•Automatic voltage regulation
•Manual/Auto/Off switch
•Utility voltage sensing
Maximizes engine “breathing” for increased fuel efficiency. Plateau honed cylinder walls and plasma moly rings help engine run cooler, reducing oil consumption. Because heat is the primary cause of engine wear, the OHVI has a significantly longer life than competitive engines.
Rigid construction and added durability provide long engine life.
This assures smooth, quick starting every time.
Superior lubrication to all vital bearings means better performance, less maintenance and significantly longer engine life. Now featuring a 2 year/200 hour oil change interval.
Superior shutdown protection prevents catastrophic engine damage due to low oil.
Prevents damage due to overheating.
Allows for smaller, light weight unit that operates 25% more efficiently than a revolving armature generator.
Produces a smooth output waveform for compatibility with electronic equipment.
Maximizes motor starting capability.
Regulates the output voltage to ±2% prevents damaging voltage spikes.
Selects the operating mode.
Constantly monitors utility voltage, setpoints 65% dropout, 75% pick-up, of standard voltage.
•Utility interrupt delay
•Engine warm-up
•Engine cool-down
•Seven day exerciser
CONTROLS
•Trickle Battery charger
•Main Line Circuit Breaker
•Electronic governor
•Weather protective enclosure
•Enclosed critical grade muffler
UNIT
•Small, compact, attractive
•SAE
•1’ Flexible Fuel Line Connector
•Composite Mounting Pad
SYSTEM
INSTALLATION
Prevents nuisance start-ups of the engine, setpoint approximately 10 seconds.
Ensures engine is ready to assume the load, setpoint approximately 10 seconds.
Allows engine to cool prior to shutdown, setpoint approximately 1 minute.
Operates engine to prevent oil seal drying and damage between power outages.
Maintains battery charge level to insure starting.
Protects generator from overload.
Maintains constant 50 Hz frequency.
Ensures protection against mother nature. Hinged key locking roof panel for security. Lift-out front for easy access to all routine maintenance items. Electrostatically applied textured epoxy paint for added durability.
Quiet, critical grade muffler is mounted inside the unit to prevent injuries.
Makes for an easy, eye appealing installation.
Sound attenuated enclosure ensures quiet operation.
Easy Installation.
SPECIFICATIONS
GENERATOR Model 005914-0 (8 kVA) Model 005915-0 (10 kVA) Model 005916-0 (13 kVA)
Rated Maximum Continuous Power Capacity (LP) 8,000 Watts* 10,000 Watts* 13,000 Watts*
Rated Maximum Continuous Power Capacity (NG) 7,000 Watts** 10,000 Watts** 13,000 Watts**
Rated Voltage 110/220 110/220 110/220
Rated Maximum Continuous Load Current
220 Volts, Single Phase 36.4 LP/31.8 NG 45.5 LP/45.5 NG 59 LP/59 NG
Main Line Circuit Breaker 35 Amp 50 Amp 65 Amp
Phase 1 1 1
Number of Rotor Poles 2 2 2
Rated AC Frequency 50Hz 50Hz 50Hz
Power Factor 1 1 1
Battery Requirement (not included) Group 26
Unit Weight (Pounds/Kilograms) 387/175.4 425.5/193 445/201.8
Dimensions L x W x H (Inches/Millimeters) 48 x 25 x 29/1218 x 638 x 732 48 x 25 x 29/1218 x 638 x 732 48 x 25 x 29/1218 x 638 x 732 Sound output in dB(A) at 23 ft. with generator operating at normal load 60 60 60
12 Volts and
525 Cold-cranking
Amperes Minimum
ENGINE Model 005914-0 (8 kVA) Model 005915-0 (10 kVA) Model 005916-0 (13 kVA)
Type of Engine GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN GENERAC OHVI V-TWIN
Number of Cylinders 2 2 2
Displacement 530cc 992cc 992cc
Cylinder Block Aluminum w/Cast
Valve Arrangement Overhead Valve Overhead Valve Overhead Valve
Ignition System Solid-state Magneto Solid-state Magneto Solid-state Magneto
Governor System Electronic Electronic Electronic
Compression Ratio 9.5:1 9.5:1 9.5:1
Starter 12 Vdc 12 Vdc 12 Vdc
Oil Capacity Including Filter (Quarts/Liters) 1.7/1.6 1.9/1.8 1.9/1.8
Operating RPM 3,000 3,000 3,000
Fuel Consumption Natural Gas cu.ft./hr. (cu.meters/hr.)
1/2 Load Full Load
Liquid Propane cu.ft./hr (gal/hr)/cu.meters/hr. (liters/hr.)
1/2 Load Full Load
*Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 11 to 14 inches of water column for LP gas **Outputs are based upon natural gas value @ 1000 Btu per cubic feet and 2520 Btu per cubic feet with LP
@ 28.32 Btu per cubic meter and 71.36 Btu per cubic meter with LP
Iron Sleeve
156 (4.42) 220 (6.23)
58 (1.56)/1.64 (5.9) 84 (2.30)/2.38 (8.7)
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Aluminum w/Cast
Iron Sleeve
156 (4.42) 220 (6.23)
58 (1.56)/1.64 (5.9) 84 (2.30)/2.38 (8.7)
Group 26
12 Volts and
525 Cold-cranking
Amperes Minimum
Aluminum w/Cast
Iron Sleeve
183 (5.18) 261 (7.39)
59 (1.61)/1.67 (6.1) 94 (2.57)/2.66 (9.7)
®
CONTROLS
2-Line Plain Text LCD Display Mode Switch
-Auto Automatic Start on Utility failure. 7 day exerciser
-Off Stops unit. Power is removed. Control and charger still operate.
-Manual/Test (star t) Start with starter control, unit stays on. If utility fails, transfer to load takes place.
Engine Start Sequence Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration)
Engine Warm-up 10 seconds
Engine Cool-Down 1 minute
Starter Lock-out Starter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Trickle Battery Charger Standard
Automatic Voltage Regulator w/Overvoltage Protection Standard
Automatic Low Oil Pressure Shutdown Standard
Overspeed Shutdown Standard, 60Hz
High Temperature Shutdown Standard
Overcrank Protection Standard
Safety Fuse Standard
Rating definitions - All ratings in accordance with BS5514, ISO3046 and DIN6271. * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power decreases about 3.5 percent for each 1,000 feet (304.8 meters) above sea level; and also will decrease about 1 percent for each 12° C (10° F) above 15.5° C (60°F).
Simple user interface for ease of operation
TRANSFER
SWITCH
8KW - 17KW
(IF SUPPLIED)
TRANSFER
SWITCH
20KW
(IF SUPPLIED)
H1
W1
W2
H2
H1
W1
W2
Generac Standby Generator - 8 kVA - 10 kVA - 13 kVA
Design and specifications subject to change without notice. Dimensions shown are approximate. Contact your Carrier dealer for certified drawings. DO NOT USE THESE DIMENSIONS FOR INSTALLATION PURPOSES.
637.6 [25.1]
1218
[47.9]
731.9 [28.8]
®
642
[25.3]
LEFT SIDE VIEW
®
76.2 [3.0]
PEA GRAVEL
MINIMUM
1226 [48.3]
FRONT VIEW
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2011 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0190490SBY-B / Printed in U.S.A. 04/07/11
Loading...