Generac RTS12EZA1, RTS14EZA1, RTS16EZA1, RTS10EZA1 User Manual

GENERAC® EZ SWITCH™
Pre-wired Automatic Transfer Switch
with Built In Load Center
100 Amp, 250 VAC, NEMA 1
Model RTS10EZA1 – 10 Circuit Switch Model RTS12EZA1 – 12 Circuit Switch Model RTS14EZA1 – 14 Circuit Switch Model RTS16EZA1 – 16 Circuit Switch
DESCRIPTION STANDARD FEATURES
The Generac EZ Switch™ is designed to operate with 8-17kW air-cooled generators. This 100 amp Transfer switch has an integrated load center for picking up the emergency circuits. It is especially useful where the main service is large and only a portion of the building load will be served by the generator. It is available with a built in 10, 12, 14 or 16-circuit load center to supply only those circuits that are essential during an emergency. All standard and load center transfer switches are UL and CUL Listed and suitable for use as optional standby systems (NEC702).
All EZ Switches are housed in a steel NEMA 1 enclosure, with electrostatically applied and baked powder paint. The Heavy Duty Generac Contactor is a UL recognized device, designed for years of service. The control at the generator handles all the timing, sensing and exercising functions.
CONTACTOR RATING
The transfer switch contactor is rated at 250 VAC and is available in a single phase configuration only.
®
Generac EZ Switch™
H2
H1
W1
FUNCTIONS
All Timing and sensing functions originate in the generator controller
Utility voltage drop-out ......................................................................................................................................................................................................................<60%
Timer to generator start ...................................................................................................................................... 10 second factory set, adjustable between 10-30 seconds
Engine warm up delay ................................................................................................................................................................................................................. 5 seconds
Standby voltage sensor ..................................................................................................................................................................................................60% for 5 seconds
Utility voltage pickup .........................................................................................................................................................................................................................>80%
Re-transfer time delay ............................................................................................................................................................................................................... 15 seconds
Engine cool-down timer ............................................................................................................................................................................................................ 60 seconds
Exerciser .............................................................................................................................................................................................................. 12 minutes every 7 days
The transfer switch can be operated manually without power applied.
SPECIFICATIONS
Model RTS10EZA1 RTS12EZA1 RTS14EZA1 RTS16EZA1
Voltage 240, 1ø 240, 1ø 240, 1ø 240, 1ø
Circuits***50A, 240V 1
40A, 240V 1 1 1
30A, 240V 1 1
20A, 240V 1 1 1
20A, 120V 3 3 6 5
15A, 120V 3 5 4 5
Phase 1
Rated AC Frequency 60 Hz
Enclosure Material Steel
Enclosure Type NEMA 1
Unit Weight (lbs./kilos) 57/25.9 60.8/27.5 64/29 68/30.8
Withstand Rating (Amps) 10,000
Lug Range 2/0 - #14
Load Transition Type Open Transition
Wire Gauge (Hot, Neutral, Ground, Control) 10, 10, 10, 18 8, 8, 10, 18 6, 6, 8, 18 6, 6, 8, 18
EZ Switch™ Features
• Electrically operated, mechanically-held contacts for fast, positive connections.
• Rated for all classes of load, 100% equipment rated, both inductive and resistive.
• 2 pole, 250 VAC contactors.
• 160 millisecond transfer time.
• Dual coil design.
• Main contacts are silver plated or silver alloy to resist welding and sticking.
• NEMA 1 (indoor rated) enclosure is standard on the 100 amp switch.
• 2 Year Limited Warranty
Terminal Wire Ranges
ATS Rated Amps Switch Terminal Neutral Lug/Stud Ground Lug 100A 2-Pole UL 1 x 1/0-12 1 x 3/8-16 Stud 1 x 2/0-14
®
Generac Power Systems, Inc. • S45 W29290 HWY. 59, Waukesha, WI 53189 • generac.com
©2012 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice. Bulletin 0186640SBY-D / Printed in U.S.A. 02/17/12
H1
H2
Mechanical Dimensions (in inches/mm)
Current Rating
No. of
Poles
Height Width Depth
H1 H2 W1 W2
W2
®
W1
7/177.8100 UL Listed 2 26.5/673.1 29.25/742.9 8.14/206.7 12.5/317.5