Generac 20kW User Manual

Serial Number
CENTURION
STANDBY GENERATOR
OWNER'S MANUAL
QT
1.5L
20kW
A new standard of reliability
®
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
CENTURIONCENTURION
Not intended for use in critical life support applications.
CAUTION
This manual should remain with the unit.
Cover016 Rev. 0 09/05 Part No. 0F7933
Standby Generator Sets
Table of Contents
SECTION PAGE
SAFETY RULES ................................................ 1-1
INTRODUCTION .....................................................1-3
Read this Manual Thoroughly ...................................1-3
Operation and Maintenance ......................................1-3
How to Obtain Service ..............................................1-3
IDENTIFICATION RECORD .....................................2-1
Data Label ................................................................2-1
EQUIPMENT DESCRIPTION ...................................3-1
Equipment Description ................................................3-1
Engine Oil Recommendations ......................................3-1
Coolant Recommendations...........................................3-1
ENGINE PROTECTIVE DEVICES ............................4-1
High Coolant Temperature Switch ............................4-1
Low Coolant Level Sensor .........................................4-1
Low Oil Pressure Switch ...........................................4-1
Overcrank Shutdown ................................................4-1
Overspeed Shutdown ................................................4-1
RPM Sensor Loss Shutdown .....................................4-1
DC Fuse ....................................................................4-1
FUEL SYSTEMS .....................................................5-1
Fuel Requirements ....................................................5-1
Natural Gas Fuel System ..........................................5-1
Propane Vapor Withdrawal Fuel System....................5-1
LP Fuel System .........................................................5-1
SPECIFICATIONS ...................................................6-1
Generator .................................................................6-1
Engine.......................................................................6-1
Cooling System .........................................................6-1
Fuel System ..............................................................6-1
Electrical System ......................................................6-1
Cold Weather Kit .......................................................6-2
Reconfiguring the Fuel System ..................................6-2
GENERAL INFORMATION .......................................7-1
Generator AC Lead Connections ..................................7-1
Four-lead, Single-phase Stator ..................................7-1
Alternator Power Winding Connections ........................7-1
3-phase Alternators ..................................................7-1
INSTALLATION .......................................................8-1
Installation ...................................................................8-1
Preparation Before Start-up .........................................8-1
Transfer Switch ........................................................8-1
Fuel System ..............................................................8-1
Generator Set Lubrication ........................................8-1
Prior to Initial Start-up .............................................8-1
Engine Coolant .........................................................8-1
Belt Tension ..............................................................8-1
Electrical System ......................................................8-1
Initial Inspection for QT Genset Start-up .....................8-1
Start-up Checklist ........................................................8-2
Preparation for Start-up............................................8-2
Start-up Inspection ...................................................8-2
OPERATION ...........................................................9-1
Generator Control and Operation ................................9-1
Operating Unit with Manual Transfer Switch ...............9-1
Engine Start-up and Transfer ...................................9-1
Retransfer and Shutdown .........................................9-1
Operating Unit with Automatic Transfer Switch ...........9-1
MAINTENANCE .....................................................10-1
Maintenance Performed by Authorized
Service Facilities .....................................................10-1
Every Three Months ...............................................10-1
Once Every Six Months ...........................................10-1
Once Annually .........................................................10-1
First 100 Operating Hours ......................................10-1
Every 500 Operating Hours ....................................10-1
Every 800 Operating Hours ....................................10-1
Exhaust Manifold Procedure ......................................10-1
Intake Manifold Procedure .........................................10-1
Cylinder Head Procedure ...........................................10-1
Cooling System ..........................................................10-2
Overload Protection for Engine DC
Electrical System ....................................................10-2
Checking Fluid Levels ................................................10-2
Check Engine Oil ....................................................10-2
Battery Fluid ...........................................................10-2
Engine Coolant .......................................................10-2
Maintenance Owner/Operator Can Perform ................10-3
Check Engine Oil Level ...........................................10-3
Check Battery .........................................................10-3
Exercise System ......................................................10-3
Inspect Cooling System ...........................................10-3
Check Engine Coolant Level....................................10-3
Perform Visual Inspection .......................................10-3
Inspect Exhaust System ..........................................10-3
Check Fan Belt ........................................................10-3
Inspect Engine Governor ........................................10-3
Changing Engine Oil ...............................................10-3
Changing the Engine Air Cleaner ............................10-3
Spark Plugs ............................................................10-4
Coolant Change .......................................................10-4
Miscellaneous Maintenance ........................................10-4
Cleaning the Generator ...........................................10-4
Battery ....................................................................10-4
Battery Maintenance ...............................................10-4
Battery Replacement ...............................................10-5
SERVICE SCHEDULE ...........................................11-1
TROUBLESHOOTING ...........................................12-1
Troubleshooting Guide ...............................................12-1
NOTES EXPLODED VIEWS & PARTS LISTS WIRING DIAGRAMS & SCHEMATICS WARRANTY
Content004 Rev. 0 09/05
Standby Generator Sets
Important Safety Instructions
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators, potential operators, and service and repair technicians for this equipment.
The engine exhaust from this product
contains chemicals known to the state
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before install­ing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The generator can operate safely, efficiently and reli­ably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fundamental rules or precautions.
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all inclusive. If a pro­cedure, work method or operating technique is used that the manufacturer does not specifically recom­mend, ensure that it is safe for others. Also make sure the procedure, work method or operating tech­nique utilized does not render the generator unsafe.
WARNING:
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglect­ing its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main­tain this equipment.
Potentially lethal voltages are generated by
these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running generators.
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends that this equipment be installed, serviced and repaired by an Authorized Service Dealer or other competent, qualified electrician or installation tech­nician who is familiar with applicable codes, stan­dards and regulations. The operator also must comply with all such codes, standards and regula­tions.
• Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electri­cal and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed, operated and serviced in accordance with the manufacturer’s instructions and recommendations. Following installation, do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes, standards, laws and regulations.
• The engine exhaust fumes contain carbon monox­ide gas, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. For that reason, adequate ventilation must be provided. Exhaust gases must be piped safely away from any building or enclosure that houses the generator to an area where people, animals, etc., will not be harmed. This exhaust system must be installed properly, in strict compliance with applicable codes and stan­dards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and venti­lating air is critical in any room or building hous­ing the generator to prevent buildup of explosive gases and to ensure correct generator operation. Do not alter the installation or permit even partial blockage of ventilation provisions, as this can seri­ously affect safe operation of the generator.
• Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.
1-1
Safety 001 Rev. 0 08/05
Standby Generator Sets
Important Safety Instructions
• Before performing any maintenance on the gen­erator, disconnect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating con­ditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• All generators covered by this manual produce
dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as well as the standby generator. Avoid contact with bare wires, terminals, connections, etc., on the generator as well as the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before operating the gen­erator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• If personnel must stand on metal or concrete while installing, operating, servicing, adjusting or repair­ing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
• The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static electricity. Never disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maxi­mum electrical current (ampacity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and pos­sibly fatal electrical shock.
• Connecting this unit to an electrical system nor­mally supplied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the electric utility distribution system when the generator is operat­ing. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.
Safety 001 Rev. 0 08/05
• Generators installed with an automatic transfer switch will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to person­nel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
• In case of accident caused by electric shock, imme­diately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting imple­ment, such as a dry rope or board, to free the vic­tim from the live conductor. If the victim is uncon­scious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equip­ment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving com­ponents causing injury.
FIRE HAZARDS
• Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extin­guisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
EXPLOSION HAZARDS
• Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no com­bustible materials are left in the generator com­partment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surround­ing the generator clean and free from debris.
• These generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulat­ing the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. Fuel supply lines must be prop­erly installed, purged and leak tested according to applicable fuel-gas codes before placing this equip­ment into service.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.
1-2
Standby Generator Sets
Important Safety Instructions
INTRODUCTION
Thank you for purchasing this model of the standby generator set product line.
Every effort was expended to make sure that the information and instructions in this manual were both accurate and current at the time the manual was written. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con­tact the nearest Authorized Service Dealer for start­ing, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular service or operation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in personal injury or property damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal injury or property damage.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock
hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom­mends that the operator read this Owner's Manual and thoroughly understand all instructions before using this equipment. The manufacturer also strong­ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service and replacement of parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.
Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion
hazard.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capable of handling all service needs.
When contacting an Authorized Service Dealer or the factory about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.
AUTHORIZED SERVICE DEALER LOCATION
To locate the nearest AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
or locate us on the web at:
www.generac.com
1-3
Safety 001 Rev. 0 08/05
Standby Generator Sets
I
GE
OR
M
CE
CE
S
QT
USA
E
.
A
S
SE
L
R
T
General Information
IDENTIFICATION RECORD
DATA LABEL
Every generator set has a DATA LABEL that contains important information pertinent to the generator. The data label, which can be found attached to the gen­erator’s lower connection box, lists the unit’s serial number and its rated voltage, amps, wattage capacity, phase, frequency, rpm, power factor, etc.
Data Label
ENERATOR SET DAT
MODEL
RATED VOLTA
NOTE:
For actual information related to this particular model, please refer to the Manual Drawing Listing located at the end of this manual, or to the data label affixed to the unit.
Generator Model and Serial Number
This number is the key to numerous engineering and manufacturing details pertaining to your unit. Always supply this number when requesting service, order­ing parts or seeking information.
MADE IN
ERIA
PHA
RATED AMP
POWER FACT
ENGINE RP
PRODUCTION DAT
ALTERNATOR SUBTRANSIENT REACTAN
ALTERNATOR TRANSIENT REACTAN
CLAS
ROTO
STATORWINDING INSULATION AT 25C AMBIEN
GENERAC POWER SYSTEMS, INC
WAUKESHA, W
2-1
Identy 002 Rev. 0 09/05
Standby Generator Sets
Equipment Description
EQUIPMENT DESCRIPTION
This equipment is a revolving field, alternating cur­rent generator set. It is powered by a gaseous fueled engine operating at 1800 rpm for 4-pole direct drive units, 3600 rpm for 2-pole direct drive units and 2300 - 3000 rpm for quiet drive gear units. See the Specifications section for exact numbers. The unit comes complete with a sound attenuated enclosure, internally mounted muffler, control console, main­line circuit breaker, battery charger, and protective alarms as explained in the following paragraph.
All AC connections, including the power leads from the alternator, 120 volt battery charger input and control connections to the transfer switch are avail­able in the main connection box.
The generator incorporates the following generator features:
• Rotor and Stator insulation is Class F rated as defined by NEMA MG1-32.6, NEMA MG1-1.66. The generator is self ventilated and drip-proof con­structed.
• The voltage waveform deviation, total harmonic content of the AC waveform and telephone influ­ence factor have been evaluated and are acceptable according to NEMA MG1-32.
ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base anti-freeze and deionized water. Cooling system capacity is listed in the specifications. Use only deion­ized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
Do not use any chromate base rust inhibitor
with ethylene glycol base anti-freeze or chro­mium hydroxide (“green slime”) forms and will cause overheating. Engines that have been oper­ated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. The manufacturer also recommends that any soluble oil inhibitor is NOT used for this equipment.
DANGER
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling liquid or steam could result.
Ethylene glycol base antifreeze is poisonous.
Do not use mouth to siphon coolant from the radiator, recovery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are attracted to the smell and taste of antifreeze even though it is poisonous to them.
Temperature Oil Grade (Recommended) Above 80° F (27° C) SAE 30W or 15W-40 32° to 80° F (0° to 27° C) SAE 20W-20 or 15W-40 Below 32° F (0° C) See Note
Any attempt to crank or start the engine before
it has been properly serviced with the recom­mended oil may result in an engine failure.
NOTE:
For temperatures below 32° F, it is strongly recom­mended to use the optional Cold Weather Start Kit (part number listed in the Specification Section). The oil grade for temperatures below 32° F is 5W­30 synthetic oil.
3-1
Equip001 Rev. 0 08/05
Standby Generator Sets
Engine Protective Devices
ENGINE PROTECTIVE DEVICES
The standby generator may be required to operate for long periods of time without an operator on hand to monitor such engine conditions as coolant tempera­ture, oil pressure or rpm. For that reason, the engine has several devices designed to protect it against potentially damaging conditions by automatically shutting down the unit when the oil pressure is too low, the coolant temperature is too high, the coolant level is too low, or the engine is running too fast.
NOTE:
Engine protective switches and sensors are men­tioned here for the reader’s convenience. Also refer to the applicable control panel manual for additional automatic engine shutdown informa­tion.
HIGH COOLANT TEMPERATURE SWITCH
This switches contacts close if the temperature should exceed approximately 140° C (284° F), initiating an engine shutdown. The generator will automatically restart and the LED will reset once the temperature has returned to a safe operating level.
LOW COOLANT LEVEL SENSOR
Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut­down. To prevent such overheating, the engine has a low coolant level sensor. If the level of engine coolant drops below the level of the low coolant level sensor, the engine automatically shuts down.
LOW OIL PRESSURE SWITCH
This switch has normally closed contacts that are held open by engine oil pressure during cranking and operating. Should oil pressure drop below the 8 psi range, switch contacts close, and the engine shuts down. The unit should not be restarted until oil is added, and the AUTO/OFF/MANUAL switch must be turned to OFF and then back to AUTO.
OVERCRANK SHUTDOWN
After a prespecified duration of cranking, this func­tion ends the cranking if the engine has failed to start. The overcrank LED will turn ON. Turn OFF the AUTO/OFF/MANUAL switch, then turn switch back to AUTO to reset the generator control board.
NOTE:
If the fault is not corrected, the overcrank feature will continue to activate.
Approximate Crank Cycle Times
• 15 seconds ON
• 7 seconds OFF
• 7 seconds ON
• 7 seconds OFF
• Repeat for 45 seconds Approximately 90 seconds total.
OVERSPEED SHUTDOWN
A speed circuit controls engine cranking, start-up, operation and shutdown. Engine speed signals are delivered to the circuit board whenever the unit is running. Should the engine overspeed above a safe, preset value, the circuit board initiates an automatic engine shutdown. Contact the nearest Authorized Dealer if this failure occurs.
RPM SENSOR LOSS SHUTDOWN
If the speed signal to the control panel is lost, engine shutdown will occur.
DC FUSE
This fuse is located inside of the control panel. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. (See the exploded views and parts lists at the end of this manual for replacement part number.)
4-1
EngProt001 Rev. 0 08/05
Standby Generator Sets
Fuel Systems
FUEL SYSTEM
FUEL REQUIREMENTS
The standby generator may be equipped with one of the following fuel systems:
• Natural gas fuel system
• Propane vapor (PV) fuel system
The Manual Drawing Listing that is affixed to the unit includes the “Identification Code,” which may be used to identify the type of fuel system installed on the unit.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask the fuel supplier for the Btu content of the fuel.
Required fuel pressure for natural gas is 5 inches
to 14 inches water column (0.18 to 0.5 psi); and for liquid propane, 5 inches to 14 inches of water column (0.18 to 0.5 psi).
NOTE:
Any piping used to connect the generator to the fuel supply should be of adequate size to ensure the fuel pressure NEVER drops below five inches water column for natural gas or 5 inches water column for propane vapor for all load ranges.
NOTE:
It is the responsibility of the installer to make sure that only the correct recommended fuel is sup­plied to the generator fuel system. Thereafter, the owner/operator must make certain that only the proper fuel is supplied.
NATURAL GAS FUEL SYSTEM
Natural gas is supplied in its vapor state. In most cases, the gas distribution company provides piping from the main gas distribution line to the standby generator site. The following information applies to natural gas fuel systems.
• Gas pressure in a building is usually regulated by national, state and local codes.
• To reduce gas pressure to a safe level before the gas enters a building, a primary regulator is needed. The natural gas supplier may or may not supply such a regulator.
• It is the responsibility of the gas supplier to make sure sufficient gas pressure is available to operate the primary regulator.
• Gas pressure at the inlet to the fuel shutoff sole­noid should not exceed approximately 14 inches water column (0.5 psi). Optimum pressure at the fuel shutoff solenoid is 11 inches water column (0.4 psi).
PROPANE VAPOR WITHDRAWAL FUEL SYSTEM
This type of system utilizes the vapors formed above the liquid fuel in the supply tank. Approximately 10 to 20 percent of the tank capacity is needed for fuel expansion from the liquid to the vapor state. The vapor withdrawal system is generally best suited for smaller engines that require less fuel. The installer should be aware of the following:
• The natural gas and LP gas systems are similar. However, the natural gas system delivers gas at a pressure of approximately five inches water col­umn to the carburetor.
• When ambient temperatures are low and engine fuel consumption is high, the vapor withdrawal system may not function efficiently.
• Ambient temperatures around the supply tank must be high enough to sustain adequate vaporiza­tion, or the system will not deliver the needed fuel volume.
• In addition to the cooling effects of ambient air, the vaporization process itself provides an additional cooling effect.
LP FUEL SYSTEM
LP is supplied as a liquid in pressure tanks. It is usually made up of propane, butane, or a mixture of the two gases. Propane tends to vaporize readily even at temperatures as low as -20° F (-29° C). However, butane reverts to its liquid state when temperatures drop below 32° F (0° C).
LP in a liquid withdrawal system must be converted to its gaseous state before it is introduced into the engine carburetor. A vaporizer-converter is generally used to accomplish this. In such a converter, heated engine coolant is ported through the converter to provide the necessary heat for conversion of the fuel from a liquid to a gaseous state.
5-1
FuelSys001 Rev. 0 08/05
Standby Generator Sets
Specifications
SPECIFICATIONS
GENERATOR
Type ............................................................................. Synchronous
Rotor Insulation ....................................................................Class F
Stator Insulation ...................................................................Class F
Total Harmonic Distortion .........................................................< 5%
Telephone Interference Factor (TIF) .......................................... < 50
Alternator Output Leads 3-phase ........................................... 4-wire
Bearings .........................................................................Sealed Ball
Coupling .......................................................................Flexible Disc
Load Capacity (Standby Rating) ............................................20kW*
* NOTE: Generator rating and perfomance in accordance with ISO8528-5, BS5514, SAE J1349,
ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural
gas.
Excitation System .................................................................... Direct
Generator Output Voltage/kW - 60 Hz kW Amp CB Size 120/240V, 1-phase, 1.0 pf 20 83 100 120/208V, 3-phase, 0.8 pf 20 69 100 Generator Locked Rotor KVA Available @ Voltage Dip of 35%
Single-phase or 208 3-phase ............................................. 34 KVA
ENGINE
Make ................................................................................... Generac
Model ..................................................................................... In Line
Cylinders and Arrangement ............................................................ 4
Displacement ....................................................................... 1.5 Liter
Bore ...................................................................................... 2.97 in.
Stroke ................................................................................... 3.23 in.
Compression Ratio ............................................................... 9.4-to-1
Air Intake System ................................................ Natually Aspirated
Valve Seats ................................................................... Replaceable
Lifter Type .......................................................................... Hydraulic
Engine Parameters
Rated Synchronous RPM ..............................................60 Hz, 3600
HP at rated kW ..................................................................60 Hz, 32
Exhaust System
Exhaust Flow at Rated Output 60 Hz .................................. 177 cfm
Exhaust Temperature at Rated Output .................................. 910° F
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz ................................................... 70 cfm
Governor
Type .................................................................................. Electronic
Frequency Regulation ...................................................Isochronous
Steady State Regulation ........................................................± .25%
Adjustments:
Speed ............................................................................ Selectable
Engine Lubrication System
Type of Oil Pump ...................................................................... Gear
Oil Filter .............................................................Full Flow, Cartridge
Crankcase Oil Capacity ....................................................4 U.S. qts.
COOLING SYSTEM
Type ....................................................................................... Closed
Water Pump .................................................................... Belt Driven
Fan Speed ................................................................................ 2550
Fan Diameter .....................................................................15 inches
Fan Mode ..............................................................................Pusher
Air Flow (inlet air including alternator and
combustion air) .......................................................... 1528 ft3/min.
Coolant Capacity ...........................................................2.0 U.S. gal.
Heat Rejection to Coolant ..........................................107,000 Btu/h
Maximum Operating Air Temp. on Radiator .............. 60° C (150° F)
Maximum Ambient Temperature ................................50° C (140° F)
FUEL SYSTEM
Type of Fuel ......................................... Natural Gas, Propane Vapor
Carburetor ...................................................................... Down Draft
Secondary Fuel Regulator .................................................Standard
Fuel Shut-off Solenoid ........................................................Standard
Operating Fuel Pressure ...................... 5 in. - 14 in. Water Column
Fuel Consumption - ft3/hr (Natural Gas/LPV)
Exercise 25% 50% 75% 100% Cycle Load Load Load Load
60/24 124/49 188/75 250/99 515/125
ELECTRICAL SYSTEM
Battery Charge Alternator ............................................12V, 15 Amp
Static Battery Charger ............................................................2 Amp
Recommended Battery ...................................... Group 26, 525CCA
System Voltage .....................................................................12 Volts
Voltage Regulator
Type .................................................................................. Electronic
Sensing ........................................................................ Single-phase
Regulation ................................................................................± 1%
Features ................................................. V/F Adjustable, Adjustable
Voltage and Gain LED Indicators
Power Adjustment for Ambient Conditions
Temperature Deration
3% for every 10° C above °C ..................................................... 25
1.65% for every 10° above °F .................................................... 77
Altitude Deration
1% for every 100 m above m ................................................... 182
3% for every 1000 ft. above ft. ................................................. 600
Controller ................... R-100 (0F7380D - 240V)
(0F7381D - 208V)
6-1
GenSpec013 Rev. A 09/05
Standby Generator Sets
Specifications
Figure 1 — Interconnections
CONTROL PANEL
TO ALTERNATOR
GENERATOR CONNECTION BOX
Ground Level Concrete Slab
COLD WEATHER KIT
N1 N2 23 194
CIRCUIT BREAKER
183 178
Battery Charger Input
120 Volt + Neutral Grd
STUB-UP AREA
See Install Dwg for
Dimensions
GROUND
NEUTRAL
FRAME RAIL
For cold climates, optional cold weather kit (part number 0F6148) is recommended. The kit includes:
• Battery Warmer
• 4” Junction Box with hardware
• 6 qt. pack 5W-30 synthetic oil (engine)
RECONFIGURING THE FUEL SYSTEM
NOTE:
All models are configured for natural gas or LP vapor from the factory.
To reconfigure the fuel system from NG to LP, follow these steps:
1. Turn the main gas supply off.
2. Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure
6.2).
3. Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.
4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure and type for configuration.
GenSpec013 Rev. A 09/05
Transfer Switch
NEUTRAL
Gen
N1 N2 23
4- # 14 GA WIRES TO GENERATOR CONNECTION BOX
194
186
178
To Generator Control Panel
CIRCUIT BREAKER SIZE KW VOLTS / AMPS LUG SIZE 20 240 1 Ø 100 #4 to 1/0 20 208 3 Ø 80 #4 to 1/0
Load Out
TO GENERATOR CONNECTION BOX
10. Reverse the procedure to convert back to natural gas.
11. The Dip switch inside the control panel must be in the LP or NG position when switching to differ­ent fuels.
Figure 6.2 — Reconfigure the Fuel System
Utility In
Port 1
PLUG
NG FUEL SYSTEM
FUEL HOSE
BRASS HOSE FITTING
PORT 1
HOUSING PORTS
OUT
FUEL HOSE
BRASS HOSE FITTING
OUT PORT 2
HOUSING PORTS
NOTE:
Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.
Port 2
LP FUEL SYSTEM
DANGER
Serious injury or damage may occur if not con-
figured properly. Please consult an Authorized Dealer with any questions.
6-2
PLUG
S6
3
S3
CO
S
N
S4
S2
S5
S1
L
3
)
S1
S1
S4
S4
6
S6
S3
S3
S5
S5
S2
S2
Standby Generator Sets
General Information
GENERATOR AC LEAD CONNECTIONS
See “Voltage Codes”. This generator may be rated at any one of three voltages, either single-phase or three-phase. The electrical wires in the unit’s AC con­nection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. If there are any questions regard­ing lead connection, refer to the wiring diagrams at the back of this manual.
Voltage codes apply to the type of stator assembly installed on a particular generator.
FOUR-LEAD, SINGLE-PHASE STATOR
Four-lead generators (see Figure 7.1) are designed to supply electrical loads with voltage code “A” (240V, 1-phase, 60 Hz). Electrical power is produced in the stator power windings. These windings were con­nected at the factory to the main circuit breaker as shown in Figure 7.1.
The rated voltage between each circuit breaker ter­minal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
ALTERNATOR POWER WINDING CONNECTIONS
3-PHASE ALTERNATORS
The generator is designed to supply 3-phase electri­cal loads. Electric power is produced in the alterna­tor power windings. These windings were connected at the factory to the main circuit breaker with a “Y” configuration as shown in Figures 7.2 and 7.3.
The rated voltage between circuit breaker terminals E1-E2, E1-E3 and E2-E3 is either 480V or 208V depending on the model.
The rated voltage between each circuit breaker termi­nal and the neutral point 00 is either 277V or 120V depending on the model.
Figure 7.2 — Stator Power Winding
Connections - 3-phase, 277/480V (6 Lead)
NNECTION
-
NEUTRA
E
L-
Figure 7.3 — Stator Power Winding
Connections - 3-phase, 120/208V (6 Lead)
-
S
E
00 (NEUTRAL
-
7-1
ACConn001 Rev. 0 08/05
Standby Generator Sets
Installation
INSTALLATION
Refer to the separate “Installation Guide QT Product Line” supplied with the unit.
PREPARATION BEFORE START-UP
The instructions in this section assume that the standby generator has been properly installed, ser­viced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules”, as well as all other safety information in this manual, before attempting to operate this (and related) equipment.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to the “Maintenance” section and the “Service Schedule”.
TRANSFER SWITCH
If this generator is used to supply power to any elec­trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec­trical backfeed between two different electrical sys­tems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.
FUEL SYSTEM
Make sure the fuel supply system to the genera­tor (a) delivers the correct fuel at the correct pres­sure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” for more information.
GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.
NOTE:
This engine is shipped from the manufacturer with “break-in” oil. This oil should be changed after 30 hours of operation.
Check the oil level in the generator gearbox (if so equipped) prior to initial use and at the intervals indicated by the “Service Schedule.” The recom­mended oil is SAE 90 gear lubricant.
Also, if the engine is equipped with a mechanical gov­ernor, make sure the governor is properly lubricated with clean engine oil.
PRIOR TO INITIAL START-UP
Prior to initially starting the generator, it must
be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
ENGINE COOLANT
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant” sections.
BELT TENSION
Check-the engine-fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8­inch (10 to 16 mm).
ELECTRICAL SYSTEM
Make sure the generator is properly connected to an approved earth ground.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
Check to ensure that there are no loose electrical con­nections. Restrain any loose wires to keep them clear of any moving generator set components.
INITIAL INSPECTION FOR QT GENSET STARTUP
Inspect for the following.
• Freight Damage.
• Manuals present.
• Fluid Levels ( Oil, coolant, battery, Gear Drive).
• Correct fuel piping.
• Correct muffler installation for QT50, QT70,
QT100 - QT150.
• Adequate air flow, clearances and ventilation per
installation drawings and applicable codes.
• Correct AC and DC wire size, connections and
grounding. Control and communication wiring to/ from the transfer switch must be run in a separate conduit from the AC power leads.
• Battery charger connection to 120 VAC.
• Communication wires connected between transfer
switch and generator (HTS only).
• Unit secured to pad.
8-1
Install001 Rev. 0 08/05
Standby Generator Sets
Installation
START-UP CHECKLIST
Before working on the generator, ensure the fol-
lowing:
• The AUTO/OFF/MANUAL switch is in the OFF position.
• The 120VAC supply to the battery charger is switched OFF.
PREPARATION FOR START-UP
• Ensure that the 120VAC circuit breaker to the bat­tery charger is open.
• Remove the fuse from the the control panel. For the H-100 and R-100: Open the front door of the control box and remove the 15 Amp ATO fuse in the lower left-hand corner of the control box.
• Connect the battery cables to the battery. Attach negative battery cable last.
• Close the 120VAC circuit breaker to the battery charger.
• Measure the voltage at the battery before and after the charger is turned on.
• Verify all AC electrical connections are tight at the circuit breaker and transfer switch.
• Visually inspect entire area looking for loose paper, plastic wrappings, leaves, etc.
• Check all hoses clamps fittings for leaks or dam­age.
• Check all electrical plugs throughout the genera­tor. Ensure each plug is seated correctly and fully inserted into its receptacle.
• Verify the AUTO/OFF/MANUAL switch is in OFF position.
• Open the valve to the engine fuel line.
• Bleed the fuel system of air. (necessary for long fuel lines).
• Open the generator main line circuit breaker.
• Connect a manometer to the gas line and record the static pressure. It must be as listed in the Specifications.
• Insert the fuse into the control panel.
• Move the AUTO/OFF/MANUAL switch to the man­ual position. The engine should now crank and start.
• Check voltage at the generator terminals.
• For 3-phase units, check phase rotation at the transfer switch terminals. The generator phase rotation must match the utility phase rotation.
• Check for coolant, fuel, oil, and exhaust leaks.
• Close the generators main line circuit breaker.
• Turn the generator set off.
• Connect the UTILITY supply to the transfer switch.
• Set the AUTO/OFF/MANUAL switch to AUTO.
• Disconnect utility power before the transfer switch.
Engine should start, transfer to load. Run at least 15 minutes on generator power.
Make certain all 3-phase loads are functioning correctly (correct phase rotation).
• Reconnect Utility power
Transfer switch will transfer back to Utility and
engine will shut down within the given time parameters set up for the specific transfer switch and controller.
• Install all covers, access plates and door panels.
• Put the Owners Manual in a safe and accessible place.
• Make certain the AUTO/OFF/MANUAL switch is in the AUTO position.
START-UP INSPECTION
When a start-up is performed by an Authorized Service Dealer, a standard three-part form titled “Start-up Inspection for Standby Power Systems” (part no. 067377), should be completed by the instal­lation technician or engineer. See page 1-3 for infor­mation on locating the nearest Authorized Service Dealer. The installer should complete the form and disseminate copies as follows:
• White copy: Mail to Generac Warranty Department, P.O. Box 340, 211 Murphy Dr., Eagle, WI 53119-
2062.
• Pink Copy: For service file of installing dealer.
• Yellow Copy: For the customer’s records.
Install001 Rev. 0 08/05
8-2
GENERATOR CONTROL AND
Standby Generator Sets
Operation
OPERATION
Refer to the appropriate control panel operator’s manual for this unit.
OPERATING UNIT WITH MANUAL TRANSFER SWITCH
If the generator was installed in conjunction with a transfer switch capable of manual operation only, the following procedure applies. A manually operated transfer switch is one that will not provide automatic start-up and does not include an intelligence circuit.
ENGINE START-UP AND TRANSFER
For additional information, refer to the applicable control panel manual for this unit, as well as any lit­erature pertaining to the specific transfer switch.
DANGER
The Maintenance Disconnect Switch and the
AUTO/OFF/MANUAL switches (if so equipped) must be set properly, or the generator will crank and start as soon as the utility power to the transfer switch is turned off. Refer to applicable control panel and transfer switch manuals for more information.
Do not proceed until certain that utility source
voltage is available to the transfer switch and the transfer switch main contacts are set to UTILITY.
Do not attempt manual operation until all power
supplies to the transfer switch have been posi­tively turned off, or extremely dangerous - pos­sibly lethal - electrical shock will result.
Transfer switch enclosure doors should be kept
closed and locked. Only authorized personnel should be allowed access to the transfer switch interior. Extremely high and dangerous voltages are present in the transfer switch.
In order to transfer load from the utility source to the generator, follow these directions:
• Turn OFF or disconnect the utility power circuit to the transfer switch, using the means provided (such as the utility source main line circuit break­er).
• Set the transfer handle to its UTILITY (NORMAL) position with load circuits connected to the utility power supply.
• Set the standby generator’s main line circuit break­er to its OFF (or OPEN) position.
• Start the generator.
Do not crank the engine continuously for longer
than 30 seconds, or the heat may damage the starter motor.
• Let engine stabilize and warm up.
• Check all applicable instrument and gauge read­ings. When certain that all readings are correct, move the transfer switch manual handle to its STANDBY (GENERATOR) position, i.e., load cir­cuits supplied by the generator.
• Set the standby generator’s main line circuit break­er to its ON (or CLOSED) position.
• Load circuits are now powered by the standby generator.
RETRANSFER AND SHUTDOWN
For additional information, refer to the applicable control panel manual for this unit, as well as any lit­erature pertaining to the specific transfer switch.
To transfer the load back to the utility power source and shut down the generator, follow these direc­tions:
• Set the standby generator’s main line circuit break­er to its OFF (or OPEN) position.
• Manually move the transfer switch handle to its UTILITY (NORMAL) position, i.e., load circuits connected to the utility.
• Turn ON the utility power supply to the transfer switch, using the means provided (such as the util­ity power source main line circuit breaker).
• Let the generator run at no-load for a few minutes to stabilize internal temperatures.
• Shut down the generator.
OPERATING UNIT WITH AUTOMATIC TRANSFER SWITCH
If the generator has been installed with an automatic transfer switch, such as an RTS, HTS, or GTS-type transfer switch, the engine may be started and stopped automatically or manually.
NOTE:
Refer to the applicable manual for your trans­fer switch and to “Transfer Switch Start Signal Connections”. In addition, please note the dangers under “Engine Start-up and Transfer.”
9-1
Oper001 Rev. 0 08/05
Standby Generator Sets
Maintenance
MAINTENANCE PERFORMED BY AUTHORIZED SERVICE FACILITIES
Before working on the generator, ensure the fol-
lowing:
• The AUTO/OFF/MANUAL switch is in the OFF position.
• The 15A fuse has been removed from the con­trol box.
• The 120VAC supply to the battery charger is switched OFF.
EVERY THREE MONTHS
1. Check battery condition.
2. Inspect and test fuel system.
3. Check transfer switch.
4. Inspect exhaust system.
5. Check engine ignition system.
6. Check fan belts.
ONCE EVERY SIX MONTHS
1. Test Engine Safety Devices (low oil pressure, low
coolant level, high coolant temperature).
COOLING SYSTEM
Air intake and outlet openings in the generator com­partment must be open and unobstructed for contin­ued proper operation. This includes such obstruc­tions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down. (See the installation diagram.)
The exhaust system parts from this product get
extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM
Engine cranking, start up and running are controlled by a solid state Engine Controller circuit board. Battery voltage is delivered to that circuit board via a 15 amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
ONCE ANNUALLY
1. Test engine governor; adjust or repair, if needed.
2. Clean, inspect generator.
3. Flush cooling system.
FIRST 100 OPERATING HOURS
1. Change engine oil and oil filter. After initial
change, service engine oil and filter at 150 operat­ing hours or six months, whichever comes first.
2. Retorque cylinder head.
3. Retorque intake and exhaust manifold.
EVERY 500 OPERATING HOURS
1. Service air cleaner.
2. Check starter.
3. Check engine DC alternator.
EVERY 800 OPERATING HOURS
1. Retorque cylinder head.
2. Retorque intake and exhaust manifold.
3. Check engine compression.
4. Check valve clearance.
If a circuit breaker opens or a fuse element
melts, find the cause of the overload before resetting the circuit breaker or replacing the fuse.
CHECKING FLUID LEVELS
CHECK ENGINE OIL
Check engine crankcase oil level (Figure 10.1) at least every 20 hours of operation, or prior to use.
• Remove oil dipstick and wipe dry with a clean, lint­free cloth.
• Install oil dipstick, then remove again.
• Oil should be between FULL and ADD marks.
• If oil level is below the dipstick ADD mark, remove oil fill cap-. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommen­dations” for recommended oils.
10-1
Maint006 Rev. 0 08/05