Generac 005036-0 User Manual

Automatic Transfer Switch
Owner’s Manual
ATS Service Entrance
HS Type Transfer Switch
Models: 005036-0, 100 Amp, 250 Volts
and 004945-1, 200 Amp, 250 Volts
This manual should remain with the unit.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS - This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to
install, operate or service this equipment. Also read the instructions and information on tags,
decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible.
DANGER! Connection of a generator to an electrical system normally supplied by an electric
utility shall be by means of suitable transfer equipment so as to isolate the electric system
from utility distribution system when the generator is operating (Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy.
 
Generac Power Systems, Inc., hereafter referred to as the “manufacturer”, cannot anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique cho­sen does not render the transfer switch unsafe.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert person­nel to special instructions about a particular opera­tion that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their defini­tions are as follows:
DANGER
After this heading, read instructions that, if not
strictly complied with, will result in personal inju­ry, including without limitation, death, or property damage.
After this heading, read instructions that, if not
strictly complied with, may result in personal inju­ry or property damage.
After this heading, read instructions that, if not
strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements
that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety infor-
mation that, if not followed, could endanger personal safety and/or property.
This symbol points out potential explosion haz-
ard.
This symbol points out potential fire hazard.
  This symbol points out potential electrical shock
hazard.
GENERAL HAZARDS
• Any AC generator that is used for backup power if a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy.
• Improper or unauthorized installation, operation, service or repair of the equipment is extremely dangerous and may result in death, serious per­sonal injury, or damage to equipment and/or per­sonal property.
• Extremely high and dangerous power voltages are present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and pos­sibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF.
Table of Contents
• Competent, qualified personnel should install, operate and service this equipment. Adhere strictly to local, state and national electrical and building codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established.
• Never handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• Jewelry conducts electricity and wearing it may cause dangerous electrical shock. Remove all jew­elry (such as rings, watches, bracelets, etc.) before working on this equipment.
• If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats.
• Never work on this equipment while physically or mentally fatigued.
• Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior.
• In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconduct­ing implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• When an automatic transfer switch is installed for a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the system’s automatic start cir­cuit must be disabled before working on or around the generator or transfer switch. For that purpose, a SAFETY DISCONNECT is provided inside the transfer switch. Always set that switch to its OFF position before working on the equipment. Then place a “DO NOT OPERATE” tag on the transfer switch and on the generator. Remove the Negative (Neg) or (–) battery cable.
Safety Rules .........................................Inside Front Cover
Section 1 — General Information ...................................2
1.1 Introduction............................................................. 2
1.2 Equipment Description ........................................... 2
1.2.1 Transfer Switch Mechanism .......................... 2
1.2.2 Service Disconnect Circuit Breaker ............... 2
1.3 Transfer Switch Data Decal ..................................... 2
1.4 Transfer Switch Enclosure ...................................... 3
1.5 Safe Use Of Transfer Switch .................................... 3
Section 2 — Installation ....................................................3
2.1 Introduction to Installation ...................................... 3
2.2 Unpacking ............................................................... 3
2.3 Mounting ................................................................. 3
2.4 Connecting Power Source and Load Lines ............... 3
2.5 Connecting Start Circuit Wires ................................ 4
Section 3 — Operation .......................................................4
3.1 Functional Tests & Adjustments .............................. 4
3.2 Manual Operation .................................................... 4
3.2.1 Close to Normal Source Side ........................ 5
3.2.2 Close to Emergency Source Side ................... 5
3.2.3 Return to Normal Source Side ...................... 5
3.3 Voltage Checks ......................................................... 6
3.4 Generator Tests Under Load ................................... 6
Section 4 – Installation Diagram ....................................7
Section 5 – Electrical Data ...............................................8
Section 6 – Exploded Views & Parts Lists ..................12
Section 7 – Notes .............................................................16
Section 8 – Warranty ...................................... Back Cover
For authorized service,
reference the dealer locator
number found in the generator
owner’s manual.
1
Section 1 — General Information
ATS “HS” Type Transfer Switch
1.1 INTRODUCTION
This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect appli­cation, or improper procedures.
Every effort has been expended to make sure that the contents of this manual are both accurate and cur­rent. The manufacturer, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.
1.2 EQUIPMENT DESCRIPTION
The automatic transfer switch is used for transfer­ring electrical load from a UTILITY (NORMAL) power source to an EMERGENCY (STANDBY) power source. Such a transfer of electrical loads occurs automati­cally when the UTILITY power source has failed or is substantially reduced and the EMERGENCY source voltage and frequency have reached an acceptable level. The transfer switch prevents electrical feedback between two different power sources (such as the UTILITY and EMERGENCY sources) and, for that reason, codes require it in all standby electric system installations.
The transfer switch consists of a transfer mecha­nism, service disconnect circuit breaker, a relay control, fuses, and a terminal strip for connection of sensing wires.
This transfer switch is suitable for use as service entrance equipment.
1.2.1 TRANSFER SWITCH MECHANISM
These switches (Figure 1.1) are used with a single­phase system, when the single-phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched.
Solderless, screw-type terminal lugs are standard.
Switch Wire Conductor Tightening Rating Range Torque
100A #14-1/0 AWG 50 in-lbs. 200A #6-250 MCM 275 in-lbs.
This transfer switch is suitable for control of motors, electric discharge lamps, tungsten filament and elec­tric heating equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.
2
Figure 1.1 — Typical ATS Transfer Mechanism
UTILITY LUGS
UTILITY CLOSING COIL
GENERATOR LUGS (E1 & E2)
GENERATOR CLOSING COIL
LOAD LUGS (T1 & T2)
This transfer switch is for use in optional standby systems only.
This transfer switch is suitable for use on a circuit capable of 10,000 rms symmetrical amperes, 240 VAC maximum.
1.2.2 SERVICE DISCONNECT CIRCUIT
BREAKER
The service disconnect circuit breaker for the 100 amp models are:
• Siemens, Type BQ, 2-pole
• 120/240VAC, 100A
• 50/60 Hertz
• Heating, Air Conditioning and Refrigeration (HACR) rated
• Wire range: #1 - #8 AWG.
• The conductor tightening torque is 50 in-lbs.
The service disconnect circuit breaker for the 200 amp models are:
• Siemens, Type QN, 2-pole
• 120/240VAC, 200A
• 50/60 Hertz
• Heating, Air Conditioning and Refrigeration (HACR) rated
• Wire range: 300 KCMIL - 4 AWG
• The conductor tightening torque is 250 in-lbs.
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.
Section 2 — Installation
GTS “HS” Type Transfer Switch
When requesting information or ordering parts for this equipment, make sure to include all information from the DATA DECAL.
Record the Model and Serial numbers in the space provided below for future reference.
MODEL #
SERIAL #
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) 3R type. NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet and is undamaged by the formation of ice on the enclosure.
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this equip­ment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. The manufacturer recommends that a copy of the SAFETY RULES are posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equip­ment.
Two publications that outline the safe use of transfer switches are the following:
• NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER SWITCHES
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the factory. Installing the switch includes the following procedures:
• Mounting the enclosure.
• Connecting power source and load leads.
• Connecting the generator sensing and transfer relay circuits.
• Connecting any auxiliary contact (if needed)
• Testing functions.
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any damage that might have occurred during ship­ment. The purchaser must file with the carrier any claims for loss or damage incurred while in transit.
Check that all packing material is completely removed from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclo­sure are in this manual. Enclosures are typically wall-mounted. See “Installation Diagram”, Section 5.
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch against impact at all times, and against construc­tion grit and metal chips. Never install a transfer switch that has been damaged.
This transfer switch is mounted in a NEMA 3R enclo­sure. It can be mounted outside or inside and should be based on the layout of installation, convenience and proximity to the utility supply and load center.
Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.
2.4 CONNECTING POWER SOURCE AND LOAD LINES
DANGER
Make sure to turn OFF both the UTILITY
(NORMAL) and EMERGENCY ( STANDBY) power supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high voltage power sup­ply lines causes extremely hazardous, possibly lethal, electrical shock.
Wiring diagrams and electrical schematics are pro­vided in this manual.
Two suggested installation methods are shown. One for new installations and/or retrofit and one for ret­rofit.
NOTE:
All installations must comply with national, state and local codes. It is the responsibility of the installer to perform an installation that will pass the final electrical inspection.
The utility supply connection is made at the circuit breaker terminals. The generator supply and custom­er load connections are made at the transfer switch mechanism, inside the switch enclosure.
3
Section 3 — Operation
ATS “HS” Type Transfer Switch
Conductor sizes must be adequate to handle the maximum current to which they will be subjected to, based on the 75°C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables must enter the enclosure through the knockouts. If not using the knockouts, entry must be at or below knockouts. If ALUMINUM conductors are used, apply corrosion inhibitor to conductors. Tighten terminal lugs to the torque values as noted in Section 1.2.2, and on the decal located on the inside of the door. After tightening ter­minal lugs, carefully wipe away any excess corrosion inhibitor.
Use a torque wrench to tighten the conduc-
tors, being sure not to overtighten, or damage to the switch base could occur. If not tightened enough, a loose connection would result, caus­ing excess heat which could damage the switch base.
Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol­lows
1. Connect UTILITY (NORMAL) power source cables to circuit breaker.
2. Connect EMERGENCY (STANDBY) source power cables to transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch termi­nals T1, T2.
Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.
2.5 CONNECTING START CIRCUIT
WIRES
Control system interconnections consist of N1 and N2, T1 and T2, and leads 23 and 194. Control system interconnection leads must be run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:
MAXIMUM WIRE LENGTH RECOMMENDED WIRE SIZE
460 feet (140m) No. 18 AWG. 461 to 730 feet (223m) No. 16 AWG. 731 to 1,160 feet (354m) No. 14 AWG. 1,160 to 1,850 feet (565m) No. 12 AWG.
4
NOTE:
When this ATS is used with an air-cooled genera­tor, the LOAD 1 and LOAD 2 wires are not used.
3.1 FUNCTIONAL TESTS AND ADJUSTMENTS
Following transfer switch installation and inter­connection, inspect the entire installation care­fully. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regula­tions. When absolutely certain the installation is proper and correct, complete a functional test of the system.
Perform functional tests in the exact order pre-
sented in this manual, or damage could be done to the switch.
IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and information in this section are understood. Also read the infor­mation and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.
3.2 MANUAL OPERATION
DANGER
Do NOT manually transfer under load.
Disconnect transfer switch from all power sourc­es by approved means, such as the main circuit breaker(s).
A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows:
1. Turn the generator’s AUTO/OFF/MANUAL switch
to OFF.
2. Turn OFF both UTILITY (service disconnect cir-
cuit breaker) and EMERGENCY (generator main line to circuit breaker) power supplies to the transfer switch.
3. Turn the GENERATOR DISCONNECT SWITCH
to the OFF position.
4. Note position of transfer mechanism main con-
tacts by observing the moveable contact carrier arm. This can be viewed through the long narrow slot in the inside cover of the ATS. The top of the moveable contact carrier arm is yellow to be eas­ily identified.
• Manual operation handle in the UP position ­LOAD terminals (T1, T2) are connected to UTIL­ITY terminals (N1, N2).
Figure 3.1 — Actuating Transfer Switch
Attach handle to the moveable contact carrier arm.
Move handle UP for the
NORMAL (UTILITY) position.
Section 3 — Operation
ATS “HS” Type Transfer Switch
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
Move handle DOWN for the
STANDBY (EMERGENCY)
position.
• Manual operation handle in the DOWN posi­tion - LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).
Do not use excessive force when operating the
transfer switch manually or damage could be done to the manual handle.
3.2.1 CLOSE TO NORMAL SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of manual operation handle in Figure 3.1. If the handle is UP, the contacts are closed in the NORMAL (UTILITY) position, no further action is required. If the handle is DOWN, proceed with Step
1.
Step 1: With the handle inserted into the moveable
contact carrier arm, move handle UP. Be sure to hold on to the handle as it will move quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 3.1. If the handle is DOWN, the contacts are closed in the EMERGENCY (STANDBY) position. No further action is required. If the handle is UP, proceed with Step 1.
Step 1: With the handle inserted into the moveable
contact carrier arm, move the handle DOWN. Be sure to hold on to the handle as it will move quickly after the center of travel.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
3.2.3 RETURN TO NORMAL SOURCE SIDE
Step 1: Manually actuate switch to return manual
operating handle to the UP position.
Step 2: Remove manual operating handle from move-
able contact carrier arm. Return handle to storage bracket.
5
Section 3 — Operation
ATS “HS” Type Transfer Switch
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the trans­fer switch using the service disconnect circuit breaker.
DANGER
PROCEED WITH CAUTION. THE TRANSFER
SWITCH IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRICAL SHOCK.
2. With an accurate AC voltmeter, check for correct voltage. Measure across ATS terminal lugs N1 and N2. Also check N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is cor­rect and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch.
4. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The gen­erator should crank and start.
5. Let the generator stabilize and warm up at no­load for at least five minutes.
6. Turn the GENERATOR DISCONNECT SWITCH to the ON position.
7. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.
DANGER
PROCEED WITH CAUTION. GENERATOR
OUTPUT VOLTAGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRICAL SHOCK.
8. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency.
Measure across ATS terminal lugs E1 to E2. Also
check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ....................................... 60-62 Hertz
b. Terminals E1 to E2 ........................ 240-246 VAC
c. Terminals E1 to NEUTRAL ............. 120-123 VAC
d. Terminals E2 to NEUTRAL ............. 120-123 VAC
9. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position.
10. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output volt­age and frequency are correct and within stated limits. If the no-load voltage is correct but no-load frequency is incorrect, the engine governed speed may require adjustment. If no-load frequency is correct but voltage is not, the voltage regulator may require adjustment.
3.4 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its OFF or OPEN position.
2. Manually actuate the transfer switch main con­tacts to their EMERGENCY (STANDBY) position. Refer to Manual Operation (Section 3.2).
3. To start the generator, set the AUTO/OFF/ MANUAL switch to MANUAL. When engine starts, let it sta­bilize for a few minutes.
4. Turn the generator's main circuit breaker to its ON or CLOSED position. The generator now pow­ers all LOAD circuits. Check generator operation under load as follows:
• Turn ON electrical loads to the full rated watt­age/amperage capacity of the generator. DO NOT OVERLOAD.
• With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2. Voltage should be greater than 230VAC and frequency should be greater than 59 Hertz.
• Let the generator run under rated load for at least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem.
5. When checkout under load is complete, set main circuit breaker of the generator to its OFF or OPEN position.
6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO/ OFF/MANUAL switch to its OFF position.
7. Move the switch's main contacts back to their UTILITY position. For example, LOAD connect­ed to UTILITY power supply. Refer to Manual Operation (Section 3.2). Handle and operating lever of transfer switch should be in UP posi­tion.
8. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.
9. Set the generator's AUTO/OFF/MANUAL switch to its AUTO position.
10. Set the GENERATOR DISCONNECT SWITCH to the ON position. The system is now set for fully automatic operation.
6
]
]
]
OR
E
3
S
]
0A6599tv
"
]
E
E
E
E
S
]
OCK
)
ON
0A6599tv
]
Section 4 — Installation Diagram
ATS “HS” Type Transfer Switch
Drawing No. 0F0016-B
597mm[23.50"
271mm[10.67"
MOUNTING HOLE
6.3mm[0.25"
26.5mm[1.04"
561mm[22.09
PADL
CUSTOMER SUPPLIED
LOCATI
34mm[1.34"
179.5mm[7.07"
KNOCKOUT SUITABL
FOR 3/4" & 1" CONDUIT SIZ
KNOCKOUT SUITABLE F
1", 1-1/4", 1-1/2" CONDUIT SIZ
PLACE
KNOCKOUT SUITABL
FOR 1", 1-1/4", 1-1/2" CONDUIT SIZ
324mm[12.76"
7
Section 5 — Electrical Data
G
O
O
O
O
COO
U
S
S
O
SCO
C
C
O
O
O S
O
U
OU
G
Y
O
O
O
OU
C
C
CO
S
,
C
S
C
C
US
S
O
O
O
C
SCO
C
S
S
US
S
S
C
C
C
O
G
JU
S
S
O
O
OC
CO
S
S
ATS “HS” Type Transfer Switch
Transfer Switch Interconnections - Drawing No. 0F0017-A
E
MEET
.
E ENTRAN
DE
MPER WILL NEED
ERVI
IZED T
AL
NDIN
ED A
TALLED
I
NAL & L
E A B
BE IN
ATI
EVI
F AT
T
NNE
E DI
ERVI
T
.
NE BY A
DE
STATE AND
IAN AND M
BE D
AL
TRI
N T
TRI
ED ELE
AL ELE
EN
TALLATI
EET ALL NATIONAL
I
T
NNE
NDIN
I
ND BAR
R
ARD
N
TI
NNE
N PANELB
TRAL BAR E
N
FIT
TALLATI
R RETR
EW IN
TE: IN
ARD
ANELB
NIT
LED
R
R
M
LTERNAT
TAT
R
T
T
N AIR
T1 & T2 N
ED
ND SOME LIQUID COOLED UNITS
-WIRE
4
R
L PANEL
ND BAR
R
ENERAT
NTR
KET
TILIT
8
L
R
R
D
SCO
CT
ON
G
D
OT
COO
S
T
CE
D
T
S.
O
D
)
G
OR
E
&
).
TILIT
Y
T
UST
OR
OR
OM
33
OC
S.
D
SCO
CT
S
S
KE
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Transfer Switch Interconnections - Drawing No. 0F0017-A
IF ATS IS USED AS SERVICE ENTRAN
DEVICE A BONDING JUMPER WILL NEE
TO BE INSTALLED SIZED TO MEE
ATIONAL & LOCAL CODE
EXISTING WIRES T
PANELBOAR
SEE ABOVE NOTE
INSULATED SPLICIN
NNECTOR
NEW WIRES CAN B
PULLED FROM ATS
PANELBOARD
ERVICE DI
NNE
AT
NOTE: INSTALLATION TO BE DONE BY A
LICENSED ELECTRICIAN AND M
MEET ALL NATIONAL, STATE AN
L
AL ELECTRICAL CODE
FR ALTERNAT
TAT
*-WIRES T1 & T2 N
DI
NNE
BONDIN
NNECTI
IN PANELBOAR
NEUTRAL BA
ROUND BA
PANELBOAR
AC GENERATOR
NTROL PANE
ED ON AIR
AND SOME LIQUID COOLED UNIT
LED UNIT
RETROFI
9
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Wiring Diagram/Schematic - Drawing No. 0F0015-A
10
Section 5 — Electrical Data
ATS “HS” Type Transfer Switch
Wiring Diagram/Schematic - Drawing No. 0F0015-A
11
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0F0466$-D
46
44
DETAIL A-A
(POWER TERMINAL LUG ASSY)
TIGHTEN ITEM #43: 24-30 IN/LBS
NOTE:
43
44
43
DETAIL B-B
(POWER TERMINAL LUG ASSY)
TIGHTEN ITEM #43: 24-30 IN/LBS
46
NOTE:
33
3
2
15
16
6
TERMINAL TIGHTENING
TORQUE 50 INCH-POUNDS
!
32
4
10
31
47
48
TERM. XA1
TERM. XA2
TERMINAL TIGHTENING
TORQUE 50 INCH-POUNDS
SWITCH XA
TERM. XA3
SWITCH LEVER
SWITCH LEVER
TERM. XB1
SWITCH XB
TERM. XB3
51
54
NOTE:
TERM. XB2
ASSEMBLE SENSING WIRE
CLEARANCE IS GIVEN FOR
RING TERMINALS SO
5
ACCESS TO LOWER LUG
SCREWS.
!
0A6599tv
0A6599tv0A6599tv
63378-T
0A9457
63378-T
A
A
63378-T
A
30A, 600V D2806-T
63378-T
0D3587
Replace with UL
listed fuse of same
600 Volt, 5 amp.
type and rating
63378-T63378-T
LISTED
US
64NL
63378-T
B
B
E1
B
D2806-T 30A, 600V
R
STAND-BY SYSTEMS
FOR USE IN OPTIONAL
C
AUTOMATIC TRANSFER SWITCH
63378-T
194WIRE
23WIRE
T2
T1
N2WIRE
N1
47822-T
38
30
378 37
QTY. 1 ITEM #37 ABOVE SUBPLATE
QTY. 2 ITEM #37's BELOW SUBPLATE
4 PLACES
0A6599tv
19
7
24
P/N 0A2595
NOTE WIRE ORIENTATION
WARNING
(12 VDC)
(12 VDC)
(OPTIONAL)
NEUTRAL
(240 VAC)
WIRE
(240 VAC)
WIRE
(240 VAC)
CUSTOMER CONNECTIONS
(240 VAC)
WIRE
DECAL DETAILS
(NOT TO SCALE)
VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED
20
0E9999
0E3485
OF
29
COVER
INSIDE
0E3484
18
0C8308
49 45
23
41 4240
28
0A6599tv0A6599tv 0A6599tv
0A6599tv
VIEW SHOWN WITH ITEMS #18 & #19 REMOVED
17
INSIDE RIGHT SIDE
50
OR ALUUMINUM WIRE OF AT LEAST 75° c RATING
ALL TERMINALS LUGS ARE SUITABLE FOR COPPER
#0C1026 OR #0D8440 0R #0E0117 OR #0E5241A
SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY
RATING
SWITCH
INSIDE LEFT SIDE
22
WAUKESHA, WI.
GENERAC POWER SYSTEMS, INC.
MAXIMUM VOLTS - 240
MAXIMUM AMPS - 100
TRANSFER SYSTEM DATA
1/4 STL 22097-S
22473-S 1-4X20STL
22473-S 1-4X20STL
!
13
26
27
52
53
1211 31
19
0F2710
MODEL NUMBER
SERIAL NUMBER
SYSTEM VOLTAGE
0C4449A-RS
18
D2806-E 30A, 600V
1
1211 31
21
30A, 600V D2806-S
48850-E
14
TERMINAL TIGHTENING
TORQUE 45 INCH-POUNDS
B
35
8
36
1/4 STL 22097-S
22473-S 1-4X20STL
22473-S 1-4X20STL
934
DETAIL "A"
9
34
35
DETAIL A
(GROUND LUG ASSEMBLY)
ENCLOSURE
12
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0F0466$-D
ITEM PART NO. QTY. DESCRIPTION
1 0C2237 1 TRANSFER SW- HSB 100A 2P 250V 2 0E7886H 1 CB 0100A 2P 240V S BQ2 LB 3 0E7890 1 BRKT CB MTG BACK 4 0E9906 1 BRACKET, DISCONNECT SWITCH 100A 5 063378 8 HOLDER, CABLE TIE 6 0D3728 1 SWITCH TOG SPST 15A @ 125V 7 0E9999 1 DECAL SERVICE DISCONNECT SWITCH 8 049813 4 NUT HEX M6 X 1.0 G8 YEL CHR 9 0E6523 1 GROUND BAR (5)4-14 AWG CONN 10 *** 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 11 *** 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ 12 073590A 4 FUSE 5A X BUSS 1 3 *** 047822 1 BLOCK TERM 20A 7 X 6 X 1100V 14 0A1661 2 RIVET POP .156 X .675 AL 15 0C4449 1 ASS’Y-NTRL BL 150-200A 16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 17 0E1473 1 WELDMENT TRANSFER SWITCH BOX 18 0E9907 1 COVER INSIDE XFER SWITCH BOX 19 0E1477 1 COVER TRANSFER SWITCH BOX 20 0F0668 1 DECALTRANSFER SWITCH 21 0E3070 1 SUBPLT XFER SW HSB 22 0E9734 REF DECAL SWITCH RATING 23 0E3484 1 DECAL WARN MANUAL OPER HANDLE 24 0E3485 1 DECAL SERVICE DISCONNECT 25 067210A 1 DECAL GROUND LUG (NOT SHOWN) 26 0A9457 1 DECAL NEUTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0F0776 1 DECAL TEST SEQ. 2P TS HS 3R 30 081221 1 DECAL-UL LIST HSB 31 045764 6 SCREW HHTT M4-0.7 X 8 BP 32 074908 2 SCREW HHTT M5-0.8 X 10 BP 33 066849 34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP 35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL 36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD 37 022473 8 WASHER FLAT 1/4-M6 ZINC 38 022097 4 WASHER LOCK M6-1/4 39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN) 40 0E6193 1 BRACKET ARM EXTENDER 41 064526 2 SCREW HWHS #6-25 X 3/8 ZNC 42 ** 0E6155 1 ARM EXTENDER PIN 43 036933 6 SCREW PPHM #10-32 X 3/8 44 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 45 0C8308 1 DECAL TERMINAL SHOCK HAZARD 46 022152 6 WASHER LOCK #10 47 0912 48 0912970086 1 WIRE ASSY 2AWG 100A 2-P T/S N2A 49 095282 1 DECAL LIVE-CIRCUIT 50 0F2710 1 DECAL XFER SWITCH DATA SE 100A 51 066849 4 SCREW HHTT M5-0.8 X 16 52 0E6303 1 WIRE – A 53 0E6303A 1 WIRE – B 54 0E6303C 1 WIRE – E1
B 2 SCREW HHTT M5-0.8 X 8 BP
970085 1 WIRE ASSY 2AWG 100A 2-P T/S N1A
*** SUPPLIED WITH WIRE HARNESS ITEM #39 ** SUPPLIED WITH TRANSFER SWITCH (ITEM #1)
13
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E9801$-F
38
8
SWITCH
22097-S 1/4 STL
22473-S
22473-S
1-4X20STL
1-4X20STL
0C4449A-RS
30A, 600V
D2806-E
22097-S 1/4 STL
22473-S 1-4X20STL
D2806-S 30A, 600V
48850-E
22097-S 1/4 STL
22473-S
22473-S
1-4X20STL
1-4X20STL
22097-S
1/4 STL
22473-S 1-4X20STL
BUSBAR HARDWARE
DETAIL
ENCLOSURE
RATING
SWITCH
SWITCH IS FOR USE WITH CONTROL PANEL ASSEMBLY
#0C1026 OR #0D8440 0R #0E0117 OR #0E5241A
MAXIMUM AMPS - 200
MAXIMUM VOLTS - 240
TRANSFER SYSTEM DATA
120/240
SYSTEM VOLTAGE
MODEL NUMBER
SERIAL NUMBER
DETAIL A
(GROUND LUG ASSEMBLY)
ALL TERMINALS LUGS ARE SUITABLE FOR COPPER
OR ALUUMINUM WIRE OF AT LEAST 75° c RATING
0F2712
BUSBAR
16
INSIDE RIGHT SIDE
55
19
GENERAC POWER SYSTEMS, INC.
WAUKESHA, WI.
INSIDE LEFT SIDE
22
17
26
0A6599tv0A6599tv0A6599tv
0A9457
3111 12
4
46
27
18
Replace with UL listed fuse of same type and rating 600 Volt, 5 amp.
0D3587
47
15
0C4449A-T
31
3
2
53
52
NOTE:LOCATE HOLE IN BUSBAR
UNDER BALL END OF SCREW
0A6599tv0A6599tv0A6599tv
TIGHTENING TORQUE 250 IN-LBS
33
31
UTILITY
(C1 & VR1)
71037 388
D2806-T
30A, 600V
63378-T
AA
63378-T
63378-T
SEE SIDE VIEW FOR HARDWARE DETAIL TORQUE ITEM #8 TO 12 FT-LBS
56
53038
63378-T
5
386645
43
44
TORQUE ITEM #6 TO 72 IN-LBS.
1
STANDBY
D2806-T
30A, 600V
21
(C2 & VR2)
63378-T
11 3112
47822-T
T2
T1N2N1
(240 VAC)
(240 VAC)
(240 VAC)
WIRE
WIRE
WIRE
WIRE
32
0A6599tv0A6599tv0A6599tv
CUSTOMER CONNECTIONS
36
43
DETAIL "A"
35349
13
28 14
E1E1
BB
63378-T
194
23
(12 VDC)
(12 VDC)
(240 VAC)
NEUTRAL
WIRE
WIRE
(OPTIONAL)
WARNING
P/N 0A2595
NOTE WIRE ORIENTATION
R
C
AUTOMATIC TRANSFER SWITCH
FOR USE IN OPTIONAL
STAND-BY SYSTEMS
63378-T
63378-T
LISTED
US
64NL
0A6599tv0A6599tv0A6599tv
0A6599tv
50
32 3737 38
QTY. 2 ITEM #37's BELOW SUBPLATE QTY. 1 ITEM #37 ABOVE SUBPLATE 4 PLACES
48
37
7
DECAL DETAILS VIEWS SHOWN WITH ITEMS #18 & #19 FULLY ASSEMBLED (NOT TO SCALE)
24
19
0E3485
34
0E9999
9
40 4241
35
0E3484
20
51
29
INSIDE
OF
COVER
AUTOMATIC
TRANSFER SWITCH
NEMA 3R - INDOOR/OUTDOOR USE
23
14
0C8308
54 49
18
Section 6 — Exploded Views and Parts List
ATS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E9801$-F
ITEM PART NO. QTY. DESCRIPTION
1 0D9618 1 TRANSFER SW- HSB 200A 2P 250V 2 0E3628 1 CIRCUIT BREAKER 0200A 2P 120/240V S QN 3 0E3664 1 BASE QN CIRCUIT BREAKER 4 0E3553 2 BUSBAR 200A HSB XFER SW 5 0E3375 4 LUG SLDLSS 250-#6 AL/CU 6 0F1252 4 SCREW BHSC 1/4-20 X 3/8 7 036656 2 SCREW SHC 1/4-20 X 1 G8.8 NZ 8 022127 2 NUT HEX 1/4-20 STEEL 9 0E6523 1 GROUND BAR (5)4-14 AWG CONN 10 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 11 0D2806 2 FUSEBLOCK 30A 600V 2POS W/SQ 12 073590A 4 FUSE 5A X BUSS 13 047822 1 BLOCK TERM 20A 7 X 6 X 1100V 14 0A1661 2 RIVET POP .156 X .675 AL 15 0C4449A 1 ASS’Y-NTRL BL150-200A 16 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 17 0E1473 1 WELDMENT TRANSFER 18 0E9989 1 COVER INSIDE XFER SWITCH BOX 19 0E1477 1 COVER TRANSFER SWITCH BOX 20 0F0668 1 DECALTRANSFER SWITCH 21 0E3070 1 SUBPLT XFER SW HSB 22 0E3477 REF DECAL SWITCH RATING 23 0E3484 1 DECAL WARN MANUAL OPER HANDLE 24 0E3485 1 DECAL SERVICE DISCONNECT 25 067210A 1 DECAL GROUND LUG (NOT SHOWN) 26 0A9457 1 DECAL NEUTRAL 27 0D3587 1 DECAL FUSE REPLACEMENT 28 0A2595 1 DECAL TERMINAL STRIP 29 0E7109 1 DECAL TEST SEQ.2P TS HS 3R 30 063378 8 HOLDER CABLE TIE 31 045764 8 SCREW HHTT M4-0.7 X 8 BP 32 049813 5 NUT HEX M6 X 1.0 G8 YEL CHR 33 0749 34 0C3992 2 SCREW HHTT M4-0.7 X 16 BP 35 026579 2 WASHER SHAKEPROOF EXT #8 STEEL 36 0E7213 2 SCREW THUMB 1/4-20 X 1/2 W/SHLD 37 022473 14 WASHER FLAT 1/4-M6 ZINC 38 022097 10 WASHER LOCK M6-1/4 39 0E9987 1 WIRE HARNESS HSB (NOT SHOWN) 40 0E6193 1 BRACKET ARM EXTENDER 41 064526 2 SCREW HWHS #6-25 X 3/8 42 * 0E6155 1 ARM EXTENDER PIN 43 * 0E6032 2 90 DEGREE UP SPADE CONNECTOR 44 * 0E6033 2 90 DEGREE DN SPADE CONNECTOR 45 * 0E6034 2 STRAIGHT SPADE CONNECTOR 46 0E6303 47 0E6303A 1 WIRE B 48 0E6303B 1 WIRE E1 49 0C8308 1 DECAL TERMINAL SHOCK HAZARD 50 081221 1 DECAL-UL LIST HSB 51 0E9999 1 DECAL-SERVICE DISCONNECT SWITCH 52 0E9988 1 BRACKET SERVICE SWITCH 53 0D3728 1 TOBBLE SWITCH, SERVICE 54 095282 1 DECAL LIVE-CIRCUIT 55 0F2712 1 DECAL XFER SWITCH DATA SE 200A 56 066849 5 SCREW HHTT M5-0.8 X 16
08 2 SCREW HHTT M5-0.8 X 10 BP
1 WIRE A
SWITCH BOX
* SUPPLIED WITH TRANSFER SWITCH ITEM #1
15
Section 7 — Notes
ATS “HS” Type Transfer Switch
16 Generac® Power Systems, Inc.
Section 7 — Notes
ATS “HS” Type Transfer Switch
Generac® Power Systems, Inc. 17
Section 8 — Warranty
ATS “HS” Type Transfer Switch
GENERAC POWER SYSTEMS, INC. WARRANTY/SERVICE
Generac Power Systems, Inc. will warrant that from the date of purchase, our transfer switch will be free from defects in material and workmanship for the items and periods set forth in the warranty statement found in the owners manual of the Generac Power Systems Inc. generator that this transfer switch will be utilized with.
Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Generac Authorized Warranty Service Dealer by visiting our website at www.gener­ac.com or by calling the dealer locator number at 1-800-333-1322. Select the prompt that describes the brand name of the generator.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR
IMPLIED, SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.
Some states do not allow limitations on how long an implied warranty lasts, so the above
limitation may not apply to you.
GENERAC’S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S)
AS STATED ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS, INC. BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC’S NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential dam-
ages, so the above limitations may not apply to you.
This warranty gives you specific legal rights. You also may have other rights that vary from
state to state.
GENERAC® POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Part No. 0E9905 Revision F (07/21/05) Printed in U.S.A.
Loading...