Generac 005030-0, 005031-0 User Manual

Owner’s Manual
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!!
This manual should remain with the unit.
Liquid-cooled, Prepackaged
Standby Generators
Model Number 005030-0 (15kW)
005028-0 (20kW) 005031-0 (25kW)
Thank you for purchasing this model of the QuietSource™ standby generator series.
Every effort was expended to make sure that the information and instructions in this manual are both accurate and current at the time the manual was writ­ten. However, the manufacturer reserves the right to change, alter or otherwise improve this product(s) at any time without prior notice.
READ THIS MANUAL THOROUGHLY
If any portion of this manual is not understood, con­tact the nearest Authorized Service Dealer for start­ing, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAU­TION and NOTE blocks are used to alert personnel to special instructions about a particular service or oper­ation that may be hazardous if performed incorrectly or carelessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not strictly complied with, will result in serious person­al injury, including death, or property damage.
After this heading, read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property of others.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. The manufacturer strongly recom­mends that the operator reads this Owner's Manual and thoroughly understands all instructions before using this equipment. The manufacturer also strong­ly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by an Authorized Service Dealer. Normal maintenance service adjust­ments and replacement of parts are the responsibility of the owner/operator and, as such, are not consid­ered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for maintenance service.
Proper maintenance and care of the generator ensures a minimum number of problems and keep operating expenses at a minimum. See an Authorized Service Dealer for service aids and accessories.
Operating instructions presented in this manual assume that the standby electric system has been installed by an Authorized Service Dealer or other competent, qualified contractor. Installation of this equipment is not a “do-it-yourself” project.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, contact an Authorized Service Dealer for assistance. Service technicians are factory-trained and are capa­ble of handling all service needs.
When contacting an Authorized Service Dealer about parts and service, always supply the complete model number of the unit as given on the front cover of this manual or on the DATA LABEL affixed to the unit.
AUTHORIZED SERVICE
DEALER LOCATION
To locate the nearest GENERAC AUTHORIZED
SERVICE DEALER, please call this number:
1-800-333-1322
OR
Locate us on the web at:
www.generac.com
DANGER
!
Table of Contents
Liquid-cooled 15, 20 and 25 kW Generators
1
INTRODUCTION................................................IFC
Read this Manual Thoroughly......................................IFC
Operation and Maintenance ........................................IFC
How to Obtain Service ................................................IFC
Authorized Service Dealer Location ............................IFC
SAFETY RULES ....................................................2
Standards Index..............................................................3
Section 1 — GENERAL INFORMATION ............4
1.1 Generator ..............................................................4
1.2 Transfer Switch ....................................................4
1.3 ATS Mode (Automatic Operation) ..........................4
1.4 Engineered Transfer Switch (2-wire Start
GTS Mode) ............................................................4
1.5 Generator AC Connection Systems........................4
1.6 Main Circuit Breaker ............................................5
1.7 Generator Fuel System ..........................................5
1.8 Engine Protective Devices ......................................5
1.9 Unpacking ............................................................6
1.10 Lifting the Generator ............................................6
1.11 Specifications ........................................................7
1.12 Fuel Consumption ................................................7
1.13 Reconfiguring the Fuel System for LP Vapor..........7
1.14 Engine Oil Recommendations ..............................8
1.15 Coolant Recommendations....................................8
1.16 Before Installation ................................................8
Section 2 — INSTALLATION ............................9
2.1 Standby Generator Installation ............................9
2.2 Generator Location................................................9
2.3 Generator Mounting and Support ........................9
2.4 Basic Standby Electric System ............................10
2.5 Emergency Circuit Isolation Method....................10
2.6 Total Circuit Isolation Method ............................10
2.7 Grounding the Generator ....................................10
2.8 Generator AC Neutral Connections......................11
2.9 Automatic Transfer Switch (ATS Mode) ..............11
2.10 Engineered Transfer Switch (2-wire Start
GTS Mode) ..........................................................12
2.11 Battery Installation ..............................................13
2.12 Preparation Before Start-Up................................14
Section 3 OPERATION ................................15
3.1 Control Console Components..............................15
3.2 Manual Transfer and Startup..............................15
3.3 Engine Governor Gain Adjustments ....................16
3.4 Manual Retransfer and Shutdown ......................17
3.5 Automatic Operation ..........................................17
3.6 Weekly Exercise Cycle..........................................17
3.7 Control Board DIP Switch Settings ....................18
3.8 Voltage Regulator Adjustment..............................18
Section 4 — MAINTENANCE ..........................19
4.1 Maintenance Performed by Authorized
Service Facilities ..................................................19
4.2 Exhaust Manifold Procedure ..............................19
4.3 Intake Manifold Procedure ..................................19
4.4 Cylinder Head Procedure ....................................20
4.5 Cooling System....................................................20
4.6 Overload Protection for Engine DC
Electrical System ................................................20
4.7 Checking Fluid Levels ........................................20
4.8 Maintenance Owner/Operator
Can Perform ........................................................21
4.9 Miscellaneous Maintenance ................................22
4.10 Scheduled Maintenance ......................................24
Section 5 — TROUBLESHOOTING ..................27
Section 6 — NOTES ........................................28
Section 7 — ELECTRICAL DATA ....................30
Section 8 — EXPLODED VIEWS AND
PARTS LISTS ..............................38
Section 9 — INSTALLATION DIAGRAM ..........55
Section 10 — WARRANTY ...............................56
2
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar with this Owner’s Manual and with the unit. The gen- erator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fun­damental rules or precautions.
The manufacturer cannot anticipate every possible cir­cumstance that might involve a hazard. The warnings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique that the manufac­turer does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique chosen does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to install, operate or main­tain this equipment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running gen­erators.
GENERAL HAZARDS
• For safety reasons, the manufacturer recommends that this equipment be installed, serviced and repaired by an Authorized Service Dealer or other competent, qualified electrician or installation technician who is familiar with applicable codes, standards and regulations. The operator also must comply with all such codes, standards and regu­lations.
• Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the generator is installed, operated and serv­iced in accordance with the manufacturer’s instructions and recommendations. Following installation, do nothing that might render the unit unsafe or in noncompliance with the aforementioned codes, standards, laws and regula­tions.
• The engine exhaust fumes contain carbon monoxide gas, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. For that reason, adequate ventilation must be provided.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical to prevent buildup of explosive gases and to ensure correct generator operation. Do not alter the instal­lation or permit even partial blockage of ventilation provi­sions, as this can seriously affect safe operation of the gen­erator.
• Keep the area around the generator clean and uncluttered. Remove any materials that could become hazardous.
• When working on this equipment, remain alert at all times. Never work on the equipment when physically or mentally fatigued.
• Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only fac­tory-approved parts.
• Before performing any maintenance on the generator, dis­connect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
!
!
!
Important Safety Instructions
Liquid-cooled 15, 20 and 25 kW Generators
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment.
!
!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
!
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
!
!
!
!
DANGER
!
3
ELECTRICAL HAZARDS
• All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous volt­ages to the transfer switch as well as the standby generator. Avoid contact with bare wires, terminals, connections, etc., on the generator as well as the transfer switch, if applicable. Ensure all appropriate covers, guards and barriers are in place before operating the generator. If work must be done around an operating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet.
DANGEROUS ELECTRICAL SHOCK MAY RESULT.
• If personnel must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden plat­form. Work on the equipment only while standing on such insulative mats.
• The National Electrical Code (NEC), Article 250 requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static elec­tricity. Never disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum electrical current (ampacity) to which they will be subjected.
• Before installing or servicing this (and related) equipment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in haz­ardous and possibly fatal electrical shock.
• Connecting this unit to an electrical system normally sup­plied by an electric utility shall be by means of a transfer switch so as to isolate the generator electric system from the electric utility distribution system when the generator is operating. Failure to isolate the two electric system power sources from each other by such means will result in dam­age to the generator and may also result in injury or death to utility power workers due to backfeed of electrical ener­gy.
• Generators installed with an automatic transfer switch will crank and start automatically when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the genera­tor control panel and on the transfer switch.
• In case of accident caused by electric shock, immediately shut down the source of electrical power. If this is not pos­sible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
FIRE HAZARDS
• Keep a fire extinguisher near the generator at all times. Do NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insu­lation. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
EXPLOSION HA
ZARDS
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• These generator sets may operate using one of several types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks immediately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel-gas codes before placing this equipment into service.
• Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detectors accordingly.
STANDARDS INDEX
In the absence of pertinent standards, codes, regulations and laws, the published information listed below may be used as installation guide for this equipment.
1. NFPA No. 37, STATIONARY COMBUSTION ENGINES
AND GAS TURBINES, available from the National Fire Protection Association, 470 Atlantic Avenue, Boston, MA
02210.
2. NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR
HEALTH CARE FACILITIES, available same as Item 1.
3. NFPA No. 54, NATIONAL FUEL GAS CODE, available
same as Item 1.
4. NFPA No. 58, AMERICAN NATIONAL STANDARD FOR
STORAGE AND HANDLING OF LIQUEFIED PETROLE­UM GAS, available same as Item 1.
5. NFPA No. 70, NFPA HANDBOOK OF NATIONAL ELEC-
TRIC CODE, available same as Item 1.
6. Article X, NATIONAL BUILDING CODE, available from
the American Insurance Association, 85 John Street, New York, N.Y. 10038.
7. AGRICULTURAL WIRING HANDBOOK, available from the
Food and Energy Council, 909 University Avenue, Columbia, MO 65201.
8. ASAE EP-3634, INSTALLATION AND MAINTENANCE OF
FARM STANDBY ELECTRICAL SYSTEMS, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
9. NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQ-
UIDS CODE, available same as Item 1.
Important Safety Instructions
Liquid-cooled 15, 20 and 25 kW Generators
4
1.1 GENERATOR
This equipment is a liquid-cooled, engine-driven gen­erator set. The generator is designed to supply elec­trical power that operates critical electrical loads during utility power failure. The unit has been facto­ry-installed in a weather resistant, all metal enclosure and is intended for outdoor installation only. Use this generator as a source of electrical power for the oper­ation of 120 and/or 240VAC, single-phase loads.
These models are available. They are rated as follows:
Model 005031-0: Provides 25,000 watts (25 kW) of single­phase power.
Model 005028-0: Provides 20,000 watts (20 kW) of single­phase power.
Model 005030-0: Provides 15,000 watts (15 kW) of single­phase power.
If this generator is used to power electrical load circuits normally powered by a utility power source, it is required by code to install a trans­fer switch. The transfer switch must effectively isolate the electric system from the utility distri­bution system when the generator is operating (NEC 701). Failure to isolate an electrical system by such means results in damage to the genera­tor and may also result in injury or even death to utility power workers due to backfeed of electrical energy.
1.2 TRANSFER SWITCH
This generator system is intended to be used with a matched automatic transfer switch. It may be supplied in either a NEMA 1 enclosure or a NEMA 3R enclo­sure. The NEMA 1 enclosure is intended for indoor use only. The NEMA 3R enclosure is weather proof and can be used indoors or outdoors. Follow these rules:
• Install the transfer switch on a firm, sturdy sup­porting structure.
• To prevent switch distortion, level the switch if nec­essary. This can be done by placing washers between the switch enclosure and the mounting surface.
• Never install the switch where water or any corro­sive substance might drip onto the enclosure.
• Protect the switch at all times against excessive moisture, dust, dirt, lint, construction grit and cor­rosive vapors.
If a transfer switch is not included, one may be pur­chased separately from an Authorized Dealer.
1.3 AUTOMATIC TRANSFER SWITCH (ATS MODE)
When this generator, along with an HS Type automat­ic transfer switch has been installed and connected, a circuit board in the generator control panel con­stantly monitors the utility voltage and controls the operation of the transfer switch.
In ATS Mode utility voltage sensing, weekly exercis­ing, and load transferring is under the control of the generator.
Should the utility voltage drop below a preset value, and remain at this low voltage for a preset amount of time, the generator cranks and starts. After the gen­erator starts, the transfer switch transfers the load circuits to the generator so the generator can power them. When the utility source voltage has been restored, the transfer switch re-transfers the load cir­cuits back to the utility source voltage and the gener­ator shuts down.
1.4 ENGINEERED TRANSFER SWITCH (2-WIRE START GTS MODE)
When required, the pre-packaged standby generator can be installed with an engineered W-type transfer switch which controls utility voltage sensing, weekly exercising and load transferring.
UTILITY voltage sensing, weekly exercising and load transferring is then under the control of the Engineered W-type transfer switch (GTS Mode).
1.5 GENERATOR AC CONNECTION SYSTEMS
The generator was shipped from the factory with its stator AC output leads connected in a single-phase, 3-wire generator AC connection system (Figure 1.1). The stator assembly in this system consists of a pair of stationary windings, with two leads brought out of each winding. Each single winding can supply 120 VAC, 60 Hertz. When the two windings are connected in series, a 240 VAC, 60 Hertz AC output results. Typically the two “hot” leads in the circuit are Wires No. 11 and 44. The “Neutral” leads are the junction of Wires 22 and 33.
!
Section 1 - General Information
Liquid-cooled 15, 20 and 25 kW Generators
Model Rating Phase Actual Current C/B Rating* % over rating Circuit Breaker
005031-0 25,000 W 1 104.2 A 125 A 120% 125A BQ2 005028-0 20,000 W 1 83.3 A 100 A 120% 100A BQ2 005030-0 15,000 W 1 62.5 70 A 112% 70A BQ2
* Amp Rating of C/B structured under model.
Figure 1.2 - Main Circuit Breaker
5
Figure 1.1 - Generator AC Connection System
1.6 MAIN CIRCUIT BREAKER
The generator’s main circuit breaker is included with the unit as shipped from the factory. The breaker for each unit is described in Figure 1.2.
1.7 GENERATOR FUEL SYSTEM
This unit has been factory tested and adjusted using a natural gas fuel system. If propane (LP) gas is pre­ferred, refer to Section 1.13, Reconfiguring the Fuel System for LP Vapor.
Fuel pressure for a natural gas set up should be five
inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.
Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.
NOTE:
A seperate gas line and regulator may be needed to assure proper gas pressure to the generator. Improper gas pressure can cause hard starting and affect engine durability.
Gaseous fuels such as natural and LP (propane) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explo­sion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas. LP gas is heavier than air and tends to settle in low areas.
1.8 ENGINE PROTECTIVE DEVICES
The engine has several safety switches which cause the engine to automatically shut down under the fol­lowing conditions: low oil pressure, high coolant tem­perature, engine overspeed, low coolant level or over­crank (Figure 1.3).
Figure 1.3 - Engine Protective Devices
1.8.1 LOW OIL PRESSURE SWITCH
This switch is normally-closed (N.C.) but is held open by engine oil pressure during engine running. Should operating oil pressure drop below about 8-10 psi (55-68 kPa), the switch contacts close and the engine shuts down automatically (Figure 1.4).
Figure 1.4 - Low Oil Pressure Switch
1.8.2 HIGH COOLANT TEMPERATURE SWITCH
Normally open (N.O.) thermostatic switch has sens­ing tip which is immersed in captive coolant. Should coolant temperature exceed about 230°F (110°C), the switch contacts close, which causes the engine to shut down automatically (Figure 1.5).
Section 1 - General Information
Liquid-cooled 15, 20 and 25 kW Generators
(BLACK)
0
NEUTRAL
(WHITE)
(BLACK)
!
6
Figure 1.5- High Coolant Temperature Switch
1.8.3 LOW COOLANT LEVEL SWITCH
Should engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shutdown. To prevent such overheating without automatic shut down, the engine has a low coolant level sensor. If the engine coolant drops too low, the engine automatical­ly shuts down (Figure 1.6).
Figure 1.6 - Low Coolant Level Sensor
1.8.4 OVERSPEED SHUTDOWN
Should AC frequency exceed about 72 Hz, circuit board action will automatically shutdown the engine.
1.8.5 OVERCRANK SHUTDOWN
The engine control board uses a cyclic cranking process when attempting to start the engine. The first crank cycle is a 15-second crank followed by a seven­second rest. This is followed by five more crank cycles each with a seven second crank followed by a seven-second rest.
If the engine fails to start after all six attempts, the start attempt is stopped and the overcrank LED turns on.
1.8.6 LOW BATTERY
The engine control board continually monitors the battery voltage and turns on the low battery LED if the battery voltage falls below 12 VDC for one minute. Low battery voltage is a non-latching alarm, which will automatically clear if the battery voltage rises above 12 VDC. If battery voltage goes below 6 VDC during cranking, the low battery voltage alarm is latched, cranking is terminated, and the low battery LED stays on.
1.8.7 15A DC FUSE
This fuse is located inside the control panel. It pro­tects the panel wiring and components from damag­ing overload. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating.
1.9 UNPACKING
1.9.1 UNPACKING PRECAUTIONS
Handle shipping cartons and crates with care. Use care to avoid damage from dropping, bumping, colli­sion, etc. Store and unpack cartons with the proper side up, as noted on the shipping carton.
1.9.2 INSPECTION
Upon delivery, carefully inspect the generator for any damage that may have occurred during shipment. If loss or damage is noted at the time of delivery, have the person(s) making delivery note all damage on the freight bill or affix their signature under the consign­or’s memo of loss or damage.
1.10 LIFTING THE GENERATOR
When lifting or hoisting equipment is used, be careful not to touch overhead power lines. The generators weight of more than 900 pounds requires proper tools, equipment, and qualified personnel to be used in all phases of handling and unpacking.
!
Section 1 — General Information
Liquid-cooled 15, 20 and 25 kW Generators
1.11 SPECIFICATIONS
1.11.1 ENGINE
Make ......................................................................................Ford
Displacement ............................................153 inches
3
(2.5 liters)
Cylinder Arrangement......................................................4, in-line
Valve Arrangement................................................Overhead Cam
Firing Order........................................................................1-3-4-2
Number of Main Bearings............................................................5
Compression Ratio..........................................................9.37 to 1
No. of Teeth on Crank ............................................................36-1
Ignition Timing (Waste Spark System)
at 1800 rpm (NG) ..........................................36 degrees BTDC
at 1800 rpm (LP vapor) ................................28` degrees BTDC
Spark Plug Gap ............................................................0.044 inch
Recommended Spark Plugs
Motorcraft ................................................................AWSF-52-C
Oil Pressure....................................................................30-50 psi
Crankcase Oil Capacity......................4.5 U.S. quarts (4.26 liters)
Recommended Engine Oil........................................SAE 15W-40
Type of Cooling System ..................Pressurized, closed recovery
Cooling Fan ..............................................................Pusher Type
Cooling System Capacity ......................2 U.S. gallons (7.6 liters)
Recommended Coolant ............Use a 50-50 mixture of ethylene
glycol base and deionized water.
Home standby control board assembly part number 0E9704 must be used on 1800 rpm gen­erators.
1.12 FUEL CONSUMPTION
15 kW Models
Using Natural Gas ........................................236 cu. ft. per hour
Using LP Gas ..................................................92 cu. ft. per hour
20 kW Models
Using Natural Gas ........................................307 cu. ft. per hour
Using LP Gas ................................................122 cu. ft. per hour
25 kW Models
Using Natural Gas ........................................441 cu. ft. per hour
Using LP Gas ................................................175 cu. ft. per hour
NOTE:
Fuel consumption is given at rated maximum con­tinuous power output when using natural gas rated at 1000 Btu per cubic foot; or LP gas rated 2520 Btu per cubic foot. Actual fuel consumption obtained may vary depending on such variables as applied load, ambient temperature, engine condi­tions and other environmental factors.
Fuel pressure for a natural gas set up should be five inches to 14 inches of water column (0.18 to 0.5 psi) at all load ranges.
Fuel pressure for an LP vapor set up should be 11 inches to 14 inches of water column (0.4 to 0.5 psi) at all load ranges.
1.13 RECONFIGURING THE FUEL SYSTEM FOR LP VAPOR
NOTE:
All models are configured for natural gas (NG) from the factory.
To reconfigure the fuel system from NG to LP vapor, follow these steps:
1. Turn the main gas supply off.
!
Section 1 — General Information
Liquid-cooled 15, 20 and 25 kW Generators
7
1.11.2 GENERATOR
* Rated power of generator is subject to and limited by such factors as ambient temperature, altitude, engine condition, and other fac-
tors. Engine power will decrease about 3.5% for each 1000 feet above sea level and will decrease an additional 1% for each 10°F above 60°F. Maximum output power of the generator is limited by maximum engine power.
Single-phase Single-phase Single-phase
Model 005031-0 005028-0 005030-0 Rated Max. Cont. 25 20 15 AC Power Output (kW)* Rated Voltage (volts) 120/240 120/240 120/240 No. of Rotor Poles 4 4 4 Driven Speed of Rotor (rpm) 1800 1800 1800 Rotor Excitation System Direct excited brush type Direct excited brush type Direct excited brush type Type of Stator 4 Wire 4 Wire 4 Wire Rotor Insulation Class F Class F Class F Stator Insulation Class H Class H Class H
8
2. Remove the carburetor fuel hose from the outlet port (Port 1) of the demand regulator (Figure
1.8).
3. Remove the brass hose fitting from the outlet port (Port 1) of the demand regulator.
4. Remove pipe plug from Port 2.
5. Install brass hose fitting into Port 2.
6. Install pipe plug into Port 1.
7. Connect carburetor gas hose to brass fitting.
8. Tighten all clamps and plugs.
9. Make sure fuel supply is of the proper pressure and type for configuration (not to exceed 14 inch­es water column).
10. Move DIP switch position 4 on the control board to the off position (LP vapor, see Figure 3.2 and Section 3.7).
11. Reverse the procedure to convert back to natural gas.
Figure 1.8 — Reconfigure the Fuel System
NOTE:
Port 1 is for NG only and Port 2 is for LP vapor only. No provision for dual fuel has been made.
Serious injury or damage may occur if not con­figured properly. Please consult an Authorized Service Dealer with any questions.
1.14 ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE, SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil having the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
NOTE:
Synthetic oil is highly recommended when the generator will be operating in ambient tempera­tures which regularly exceed 90° F and/or fall below 30° F.
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended oil may result in an engine failure.
1.15 COOLANT RECOMMENDATIONS
Use a mixture of half low silicate ethylene glycol base anti-freeze and half deionized water. Cooling system capacity is about 8 U.S. quarts (7.6 liters). Use only deionized water and only low silicate anti-freeze. If desired, add a high quality rust inhibitor to the rec­ommended coolant mixture. When adding coolant, always add the recommended 50-50 mixture.
Do not use any chromate base rust inhibitor with ethylene glycol base anti-freeze or chromi­umhydroxide (“green slime”) forms and will cause overheating. Engines that have been operated with a chromate base rust inhibitor must be chemically cleaned before adding eth­ylene glycol base anti-freeze. Using any high silicate anti-freeze boosters or additives will also cause overheating. DO NOT use any solu­ble oil inhibitor for this equipment.
1.16 BEFORE INSTALLATION
Before installing this equipment, check the ratings of both the generator and the transfer switch. Read “Emergency Isolation Method” and “Total Circuit Isolation Method” in the installation manual (Part No.
079699).
The generator’s rated wattage/amperage capacity must be adequate to handle all electrical loads that the unit will power. It may be necessary to group the critical (essential) loads together and wire them into a separate “emergency” distribution panel.
This generator can be installed in conjunction with an engineered transfer switch, if necessary (see Section 2.10).
The standard prepackaged transfer switch (ATS mode) does not have sensing or controlling circuit boards. Instead, the generator control console hous­es a “Printed Circuit Board Assembly”, which con­trols all phases of operation, including engine start up and load transfer.
!
Temperature Oil Grade (Recommended)
Above 80° F (27° C) SAE 30W or 15W-40
32° to 80° F (-1° to 27° C) SAE 20W-20 or 15W-40
Below 32° F (0° C) SAE 10W or 15W-40
Section 1 — General Information
Liquid-cooled 15, 20 and 25 kW Generators
Port 1
PLUG
NG FUEL SYSTEM
FUEL HOSE
BRASS HOSE FITTING
OUT
PORT 1
FUEL INLET
FUEL HOSE
BRASS HOSE FITTING
OUT PORT 2
Port 2
PLUG
LP FUEL SYSTEM
DANGER
!
!
9
2.1 STANDBY GENERATOR
INSTALLATION
Connecting this generator to an electrical sys­tem normally supplied by an electric utility shall be by means of a transfer switch, so as to isolate the electric system from the utility distri­bution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.
If an open bottom is used, the engine-genera­tor must be installed over non-combustible materials and should be located such that com­bustible materials are not capable of accumu­lating under the generator set.
Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regula­tions pertaining to the installation.
After the system has been installed, do nothing that might render the installation in noncompli­ance with such codes, standards and regula­tions.
NOTE:
For more information about the installation of a standby system contact an Authorized Service Dealer.
2.1.1 NFPA STANDARDS
The following published standards booklets pertain­ing to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:
• NFPA No. 37, STATIONARY COMBUSTION
ENGINES AND GAS TURBINES.
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYS-
TEMS FOR HEALTH CARE FACILITIES.
• NFPA No. 220, STANDARD TYPES OF BUILDING
CONSTRUCTION
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
• NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND
USE OF PORTABLE FIRE EXTINGUISHERS.
2.1.2 OTHER PUBLISHED STANDARDS
In addition to NFPA standards, the following infor­mation pertaining to the installation and use of standby electric systems is available:
• Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
• AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.
• ASAE EP-364.2, INSTALLATION AND MAINTE­NANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
• A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYS­TEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y.
10018.
2.2 GENERATOR LOCATION
Install the generator set, in its protective enclosure outdoors, where adequate cooling and ventilating air always is available. Consider these factors:
• Install the unit where air inlet and outlet openings will not become obstructed by leaves, grass, snow, etc. If prevailing winds will cause blowing or drift­ing, consider using a windbreak to protect the unit.
• Install the generator on high ground where water levels will not rise and endanger it.
• Allow sufficient room on all sides of the generator for maintenance and servicing. A required mini­mum allowance of space to any solid structure is three feet. Five feet allowance of space is recom­mended.
• Where strong prevailing winds blow from one direction, face the generator air inlet openings into the prevailing winds.
• Install the generator as close as possible to the transfer switch. This reduces the length of wiring and conduit.
• Install the generator as close as possible to the fuel supply, to reduce the length of piping. HOWEVER, REMEMBER THAT LAWS OR CODES MAY REG­ULATE THE DISTANCE.
2.3 GENERATOR MOUNTING AND
SUPPORT
Retain the generator compartment to a concrete slab with 1/4-inch masonry type anchor bolts. Be sure the bolts are long enough to retain the compartment. The slab should be at least six inches thick and should extend beyond the enclosure to a distance of at least three inches on all sides.
!
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
DANGER
10
2.4 BASIC STANDBY ELECTRIC SYSTEM
Figure 2.1 shows a schematic diagram of a basic standby electric system. Both the UTILITY power supply and the STANDBY GENERATOR output are connected to an approved transfer switch. The trans­fer switch is required by electrical code and serves the following functions:
• Permits the LOAD circuits to be connected to only
one power supply at a time.
• Prevents electrical backfeed between the generator
and the UTILITY power circuits.
Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker.
Figure 2.1 – Basic Standby Electric System
NOTE:
The manufacturer recommends the use of a Generac Power Systems transfer switch in con­junction with this generator.
2.5 EMERGENCY CIRCUIT ISOLATION METHOD
This prevents overloading the generator by keeping electrical loads below the wattage/amperage capacity of the generator. If the generator is powering only crit­ical loads, within its wattage/amperage capacity, dur­ing utility power outages, consider using the emer­gency circuit isolation method.
Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” The generator only supplies electrical circuits connected to the emergency distribution panel during utility power outages. Load circuits powered by that panel must be within the wattage/amperage capacity of the generator set. The transfer switch must meet the following requirements:
• It must have an ampere rating equal to the total amperage rating of the emergency distribution panel circuit.
• It must be installed between the building’s main distribution panel and the emergency distribution panel.
2.6 TOTAL CIRCUIT ISOLATION
METHOD
When a generator capable of powering all electrical loads in the circuit is to be installed, the “Total Circuit Isolation Method” may be used. The following apply to the transfer switch in this type of system.
• Ampere rating of the transfer switch must equal the ampere rating of the normal incoming utility service.
• The transfer switch is installed between the utility service entrance and the building distribution panel.
2.7 GROUNDING THE GENERATOR
A GROUNDING LUG (Figure 2.2) is provided on the generator mounting base for the purpose of ground­ing the frame and the external electrically conductive parts of the equipment to an approved earth ground and/or grounding rods where required by the National Electrical Code. Consult a qualified electri­cian for grounding requirements in the area. Grounding procedures must meet local regulations.
Do not connect the ground wire to any pipe that carries a flammable or explosive substance – FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against electrical shock in the event of a ground fault condi­tion in the generator or in connected electrical devices. In addition, grounding helps dissipate static electricity that often builds up in ungrounded devices.
Figure 2.2 – Generator Grounding Lug (typical)
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
DANGER
11
2.8 GENERATOR AC NEUTRAL CONNECTIONS
The manufacturer uses an UNGROUNDED AC neu­tral. Grounding is recommended only at the main service entrance. If the neutral wire is grounded and one of the phase loads becomes grounded, the exces­sive current opens the load circuit breaker or col­lapses the generator field. The actual result depends on the electrical characteristics of the particular installed generator.
2.9 AUTOMATIC TRANSFER SWITCH (ATS MODE)
When this generator, along with an HS Type automat­ic transfer switch has been installed and connected, a circuit board in the generator control panel con­stantly monitors the utility voltage and controls the operation of the transfer switch.
To implement this mode of operation, Position 2 of the eight-position DIP switch, which is located on the generator circuit board (see Figure 3.2), must be in the OFF position. In ATS Mode utility voltage sensing, weekly exercising, and load transferring is under the control of the generator.
Should the utility voltage drop below a preset value, and remain at this low voltage for a preset amount of time, the generator cranks and starts. After the gen­erator starts, the transfer switch transfers the load circuits to the generator so the generator can power them. When the utility source voltage has been restored, the transfer switch re-transfers the load cir­cuits back to the utility source voltage and the gener­ator shuts down.
The HS Type transfer switch is controlled by the gen­erator circuit board via control wires 23 and 194. Wire 23 connects the relay driver output (collector of an NPN transistor) on the generator circuit board to the "low side" (Terminal 23) of the transfer relay coil in the transfer switch. Wire 194 connects positive battery voltage from the generator circuit board to the "high side" (Terminal 194) of the transfer relay coil in the transfer switch.
If generator wires 23 and 194 are not wired to the correct terminals in the transfer switch, the circuit board in the generator control panel will be damaged.
In order for the generator utility voltage sensing and battery charging functions to work, it is necessary to provide a 5 amp fused 240Vac utility source connec­tion from the transfer switch main N1 and N2 termi­nals to the generator control panel N1 and N2 termi­nals (See Figure 2.3).
Transfer Switch terminals N1 and N2 (also called Utility 1 and Utility 2) are the input utility AC power connections to the Transfer Switch. Transfer Switch terminals T1 and T2 (also called Load 1 and Load 2) are the transfer switch AC output power terminals that go to the load circuit distribution panel. Transfer Switch terminals E1 and E2 are the AC power termi­nals that come from the generator's main alternator.
!
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
Figure 2.3 - Connection Diagram (ATS Mode)
FUSE
N1 N2
FUSE
HS TYPE
TRANSFER
SWITCH
FROM UTILITY
N1 N2
194
23
E1 E2
MAIN LINE
CIRCUIT
BREAKER
OR FUSE
T1 T2
TO LOAD
FEEDER CIRCUITS
LOAD
DISTRIBUTION
PANEL
GENERATOR
194
23
178 183
N2 N1
E1 E2
12
2.10 ENGINEERED TRANSFER SWITCH (2-WIRE START GTS MODE)
When required, the pre-packaged standby generator can be installed with an engineered W Type transfer switch which controls utility voltage sensing, weekly exercising and load transferring.
When Position 2 of the eight-position DIP switch, which is located on the generator circuit board (See Figure 3.2), is in the ON position then utility voltage sensing, weekly exercising and load transferring is under the control of the Engineered W Type transfer switch (GTS Mode).
Generator DIP Switch Position 2 ON = 2-Wire Start GTS Mode
• The generator control board will NOT monitor the
utility.
• The generator control board will NOT perform a
weekly exercise. (The five red LEDs will flash one at a time in GTS mode.)
• The generator control board will NOT activate the
transfer output.
The generator control board WILL monitor all engine conditions and shut down on all the faults listed in this document.
For the W Type transfer switch to control utility volt­age sensing, weekly exercising and load transferring, suitable wiring must also be connected from the transfer switch 178 and 183, 2-Wire Start terminals to the corresponding generator 178 and 183 2-Wire
Start terminals. Recommended wire gauge sizes for the 2-Wire Start wiring depend on the length of the wire (see wiring length chart).
Route the 2-Wire Start control wires through suitable, approved conduit which is separate from the AC power leads. Connection of wire 178 to wire 183 by relay contact closure action (volt free switch contacts) in the transfer switch must result in generator engine cranking and startup (See Figure 2.4).
Do NOT connect battery voltage, utility voltage (N1/N2) or load voltage (T1/T2) to either the 178 or the 183 2-Wire start terminals as this will damage the generator control board.
In order for the generator battery charging function to work, it is necessary to provide a 5 amp fused 240Vac utility source connection from the transfer switch main N1 and N2 terminals to the generator control panel N1 and N2 terminals (See Figure 2.4).
!
Figure 2.4 - Connection Diagram (GTS Mode)
MAXIMUM WIRE LENGTH RECOMMENDED WIRE
SIZE
460 feet (140m) No. 18 AWG.
461 to 730 feet (223m) No. 16 AWG.
731 to 1,160 feet (354m) No. 14 AWG.
1,161 to 1,850 feet (565m) No. 12 AWG.
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
FUSE
FUSE
FROM UTILITY
N1 N2 N1 N2
W-TYPE
TRANSFER
SWITCH
E1 E2
MAIN LINE
BREAKER
OR FUSE
178 183
CIRCUIT
T1 T2
TO LOAD
FEEDER CIRCUITS
LOAD
DISTRIBUTION
PANEL
GENERATOR
194
23
178 183
N2 N1
E1 E2
13
Transfer Switch terminals N1 and N2 (also called Utility 1 and Utility 2) are the input utility AC power connections to the Transfer Switch. Transfer Switch terminals T1 and T2 (also called Load 1 and Load 2) are the transfer switch AC output power terminals that go to the load circuit distribution panel. Transfer Switch terminals E1 and E2 are the AC power termi­nals that come from the generator's main alternator.
When in GTS mode, the control board will respond as follows based on the generator AUTO/OFF/MANU­AL switch position.
OFF — The generator will not start and run in this position
MANUAL — The generator control board will start and run the generator whenever the switch is in the manual position.
AUTO — The generator control board will monitor the 2-Wire start circuit (terminals 178 and 183 in the generator control panel). When a 2-Wire start signal is issued by the W type engineered transfer switch, via a relay contact closure that connects wire 178 to wire 183, the generator control board will immedi­ately start and run the generator. When the 2-Wire start signal is removed the control board will imme­diately stop the generator.
2.11 BATTERY INSTALLATION
Standby generators installed with automatic transfer switches will crank and start automati­cally when NORMAL (UTILITY) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, do not connect battery cables until certain that normal source voltage at the transfer switch is correct; the generator main line circuit breaker is switched to OFF; the AUTO/OFF/MANUAL switch on the control con­sole is switched to OFF; the 15A and 5A fuses have been removed from the control console; utility fed supply to battery charger (terminals N1 and N2) is removed; and the system is ready to be placed into operation. Ensure that the 5A and 15A fuses in the control panel are removed when connecting or disconnecting battery cables.
Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.
Battery electrolyte fluid is an extremely corro­sive sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.
Do not dispose of the battery in a fire. The bat­tery is capable of exploding.
Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.
The battery represents a risk of high short cir­cuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.
2.11.1 VENTED BATTERIES
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically conductive and corrosive. The following proce­dures are to be observed:
• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off immediately with water,
• Where electrolyte contacts the eyes, flush thor­oughly and immediately with water and seek med­ical attention, and
• Spilled electrolyte is to be washed down with an acid-neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbon­ate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead acid batteries present a risk of fire because they generate hydrogen gas. The fol­lowing procedure are to be followed:
• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touch­ing batteries by first touching a grounded metal surface.
Servicing of batteries is to be performed or super­vised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized person­nel away from batteries.
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
DANGER
!
!
!
!
14
The recommended battery is Group 26, 12VDC, 550 CCA/75 AH minimum. All batteries must be at 100 percent state-of-charge before they are installed on the generator.
When using maintenance-free batteries, it is not nec­essary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals specified in Section 4, “Maintenance.” A negative ground system is used. Battery connections are shown on the wiring diagrams. Make sure all batter­ies are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.
NOTE:
Damage will result if the battery connections are made in reverse.
2.12 PREPARATION BEFORE START-UP
The instructions in this section assume that the standby generator has been properly installed, serv­iced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on pages 2 and 3, as well as all other safety information in this manual, before attempting to operate this (and related) equip­ment.
2.12.1 PRIOR TO INITIAL START-UP
Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quantities of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service intervals, please refer to Section 4, “Maintenance.”
2.12.2 TRANSFER SWITCH
If this generator is used to supply power to any elec­trical system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents elec­trical backfeed between two different electrical sys­tems, (for additional information, see the applicable transfer switch manual for this unit). The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compliance with applicable codes, standards and regulations.
2.12.3 FUEL SYSTEM
Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and volume and, (b) is properly purged and leak tested according to code. No fuel leakage is permitted.
2.12.4 GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” and “Engine Oil Recommendations”.
NOTE:
This engine is shipped from the manufacturer with 15W-40 oil. This oil should be changed after 30 hours of operation.
2.12.5 ENGINE COOLANT
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” and “Coolant”.
2.12.6 BELT TENSION
Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approximately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8­inches (10 to 16 mm).
2.12.7 ELECTRICAL SYSTEM
Make sure the generator is properly connected to an approved earth ground and/or ground rod.
Make sure the generator battery is fully charged, properly installed and interconnected, and ready for use.
Check to ensure that there are no loose electrical con­nections. Restrain any loose wires to keep them clear of any moving generator set components.
!
Section 2 — Installation
Liquid-cooled 15, 20 and 25 kW Generators
15
Section 3 - Operation
Liquid-cooled 15, 20 and 25 kW Generators
3.1 CONTROL CONSOLE COMPONENTS
The components of a home standby generator control console (Figure 3.1) are as follows:
Figure 3.1 - Generator Control Console
3.1.1 AUTO/OFF/MANUAL SWITCH
Use this three-position switch as follows:
• Set the switch to AUTO for fully automatic opera-
tion. See “Automatic Operation” (Section 3.6).
• Set switch to MANUAL position to crank and start
the generator engine.
• Set switch to OFF position to shut down an oper-
ating engine. With OFF selected, operation will not be possible.
With switch set to AUTO, engine can crank and start suddenly without warning. Such automat­ic start up normally occurs when utility source voltage drops below a pre-set level. To prevent possible injury that might be caused by such sudden starts, set AUTO/OFF/ MANUAL switch to OFF before working on or around the unit. Then, place a “DO NOT OPERATE” tag on con­trol console.
3.1.2 FAULT INDICATOR LEDS
(SEE CHART ON PAGE 16)
These red LEDs turn ON when one or more of the fol­lowing engine faults occurs and the engine shuts down.
• Low Oil Pressure
• Overcrank
• Low Battery
• Overspeed/Engine Speed Signal Fault
• High Coolant Temperature/Low Coolant Level
See Section 1.7 for further explanation of engine pro­tection functions.
3.1.3 15 AMP FUSE
This fuse protects the control console’s DC control circuit against electrical overload and is located inside the control panel. If the fuse has melted open because of an overload, engine cranking and startup cannot occur. If the fuse needs to be replaced, use only an identical 15-amp replacement fuse (type ATO).
3.1.4 5 AMP FUSE
This fuse protects the battery charger against electri­cal overload and is located inside the control panel. If the fuse needs to be replaced, use only an identical 5­amp replacement fuse (type ATO).
NOTE:
This fuse will not remove the + battery input power from the PCB when it opens. This means the exercise timer will not be reset.
3.1.5 SET EXERCISE TIME SWITCH
This switch allows programming the generator to start and exercise automatically. “See Weekly Exercise Cycle” (see Figure 3.3 and Section 3.6).
3.1.6 SYSTEM READY LED
The System Ready LED (green) has two main pur­poses. First, the LED will be ON when the AUTO/OFF/MANUAL switch is in the AUTO position, utility is present, and there are no system alarms. This ON state indicates the system is fully ready for automatic operation.
The system ready LED will be OFF when the switch is in the MANUAL or OFF positions.
The system ready LED is also used to indicate the presence of utility sensing at the PCB when the switch is either in the AUTO or MANUAL modes. The LED will flash at the rate of 1/2 second on, 1/2 second off if the utility sensing level is below the transfer back threshold.
This secondary function is only available with DIP switch two in the OFF position (ATS - automatic transfer switch application).
3.2 MANUAL TRANSFER AND START-UP
To transfer electrical loads to the Standby (EMER­GENCY) power source side and start the engine man­ually, refer to the Owner’s Manual of the particular transfer switch.
!
CAUTION
Q
.
CAUTION
,
.
TENTION: POUR L'ALIMENTATION DE RESERVE, CONNECTER LA SORTIE DE
ATRICE A UN COMMUTATEUR DE CALIBRE APPROPRIE, CONFORMENENT AU
.
G
C
.
Y
E
S
G.
G
OUTDOO
!
0
USE OF S
D
ON
0F2629
.
L
SET
SE
E
S
)
S
.
O
D
O
K
Y
SYS
Y
O
OFF
SE
5
T
S:
T
(
)
OFF
COO
.
COO
L
SS.
(
)
N
VER CRAN
VER SPEE
LOW
L. LEVE
HI
L. TEMP
LOW OIL PRE
LED INDICATOR
FLASHING GREEN LED = NO UTILITY SEN
FLASHING RED LED'S = EXERCISER NOT SE
IN AUTO MODE ONLY
SOLID GREEN LED = SYSTEM READY, UTILITY POWER O
RED LED'S = INDIVIDUAL FAUL
SEE OWNER'S MANUAL FOR COMPLETE LED DETAILS
EXERCI
1) PLACE AUTO/OFF/MANUAL SWITCH TO AUTO POSITION
2) HOLD "SET EXERCISE TIME" SWITCH IN "ON" POSITION FOR THREE SECOND
AND RELEASE. (SEE OWNER'S MANUAL FOR COMPLETE DETAILS
THE EXERCISER IS NOW SET. ALL FIVE RED LED'S WILL FLASH FOR 10 SECOND
THEN THE UNIT WILL START, RUN THROUGH THE EXERCISE CYCLE AND SHUTDOWN
TO SET EXERCISER TIM
LOW BATTER
AUT
MANUA
TEM READ
DANGER
RISK OF ELECTRICAL SHOCK. DO NOT REMOVE COVER. NO USER SERVICEABLE
PARTS INSIDE. REFER SERVICING TO
FOR STAND-BY SERVICE CONNECT OUTPUT OF GENERATOR TO SUITABLY RATED TRANSFER SWITCH IN ACCORDANCE WITH CANADIAN ELECTRICAL CODE
CANADIEN DE L'ECTRICITE, PREMIERE PARTIE
UALIFIED SERVICE PERSONNEL
PART I
WARNIN
AN AUTOMATICALLY START AT ANYTIME WITHOUT NOTICE
REMOVE FUSE ON CONTROL PANEL AND NEGATIVE BATT
ERVICIN
WARNIN
THIS EMERGENCY POWER SYSTEM IS DESIGNED EXCLUSIVELY FOR
R INSTALLATION ONLY
YNTHETIC OIL IS RECOMMENDE
E7193
16
3.3 ENGINE GOVERNOR GAIN ADJUSTMENTS
Engine speed governing is also controlled by the engine control board. The engine governor has been set by the factory during final testing of the generator and should not be adjusted.
If, however, adjustments are necessary, the following procedure should be followed (Figure 3.2 and Section
3.7):
1. Move DIP switch 8 to the TEST mode (OFF posi-
tion).
2. Set all three potentiometers (pots) fully counter-
clockwise.
3. Under no load condition, increase the GAIN pot
as much as possible without causing instability.
4. Apply 1/4, 1/2, 3/4 and full load to the unit.
Decrease the GAIN pot if there is instability at any load point.
5. Under full load condition, increase the stability
pot until the unit returns to 60 Hertz (or 50 Hertz in 50 Hertz applications).
Figure 3.2 — Control Board Dip Switch Location
Section 3 - Operation
Liquid-cooled 15, 20 and 25 kW Generators
Condition System Low Low High Over Over Switch Position
Ready (Green) Bat (Red) Oil (Red) Temp (Red) Speed (Red) Crank (Red) Manual Auto Off
Generator Switch is OFF X OFF OFF OFF OFF O in the OFF Mode.
System Ready for ON X OFF OFF OFF OFF O Automatic Start
Generator Switch is OFF X OFF OFF OFF OFF O in the MANUAL Mode
Weekly Exerciser X Flashing Flashing Flashing Flashing Flashing O O O is not set (-----------------------------------1 sec rate---------------------------------------)
Battery Voltage <12.2V X ON OOO for >1 minute (Non-latching)
Battery Voltage <6V OFF ON OO
Unit Shutdown due OFF X ON O O to Low Oil Pressure
Unit Shutdown due to High Coolant Temperature OFF X ON O O or Low Coolant Level
Unit Shutdown due OFF X ON O O to Engine Overspeed
Unit Failed to Start OFF X ON O O during it’s Crank Cycle
Utility Voltage is Flashing X OO <45% of Nominal 1 sec rate
Engine Speed Signal Fault OFF X Flashing O O
Control Board is OFF X The five RED LED’s will turn on one at a time O O O in GTS Mode
X = indicates that the LED can be ON or OFF depending on the operating conditions.
Loading...
+ 42 hidden pages