Generac 004678-2 User Manual

Page 1
POWER SYSTEMS, INC.
®
Owner’s Manual
GTS “HS”T ype
Automatic
Transfer Switch
Models: 004635-3
(200 Amp, 250 Volts)
(100 Amp, 250Volts)
This manual should remain with the unit.
Page 2
Generac®Power Systems, Inc.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating tech­nique Generac does not specifically recommend, ensure that it is safe for others. Also make sure the procedure, work method or operating technique cho­sen does not render the transfer switch unsafe.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert per­sonnel to special instructions about a particular operation that may be hazardous if performed incor­rectly or carelessly. Observe them carefully. Their def­initions are as follows:
After this heading, read instructions that, if not strictly complied with, will result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory statements that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
GENERAL HAZARDS
• Any AC generator that is used for backup power if a NORMAL (UTILITY) power source failure occurs, must be isolated from the NORMAL (UTILITY) power source by means of an approved transfer switch. Failure to properly isolate the NORMAL and STANDBY power sources from each other may result in injury or death to electric utility workers, due to backfeed of electrical energy.
• Improper or unauthorized installation, operation, service or repair of the equipment is extremely dangerous and may result in death, serious per­sonal injury, or damage to equipment and/or per­sonal property.
• Extremely high and dangerous power voltages are present inside an installed transfer switch. Any contact with high voltage terminals, contacts or wires will result in extremely hazardous, and pos­sibly LETHAL, electric shock. DO NOT WORK ON THE TRANSFER SWITCH UNTIL ALL POWER VOLTAGE SUPPLIES TO THE SWITCH HAVE BEEN POSITIVELY TURNED OFF.
• Competent, qualified personnel should install, operate and service this equipment. Adhere strict­ly to local, state and national electrical and build­ing codes. When using this equipment, comply with regulations the National Electrical Code (NEC), CSA Standard; C22.1 Canadian Electric Code and Occupational Safety and Health Administration (OSHA) have established.
• Never handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK MAY RESULT.
!
!
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS! Read the following information carefully before attempting to install, operate or service this equipment. Also read the instructions and information on tags, decals, and labels that may be affixed to the transfer switch. Replace any decal or label that is no longer legible.
DANGER! Connection of a generator to an electrical system normally supplied by an electric utility shall be by means of suitable transfer equipment so as to isolate the electric system from utility distribution system when the generator is operating (Article 701 Legally Required Standby Systems or Article 702 Optional Standby Systems, as applicable). Failure to isolate electric system by these means may result in damage to generator and may result in injury or death to utility workers due to backfeed of electrical energy.
!
!
!
!
DANGER
!
Page 3
Table of Contents
Generac®Power Systems, Inc. 1
Safety Rules..........................................Inside Front Cover
Section 1 — General Information ..................................2
1.1 Introduction ............................................................2
1.2 Equipment Description ............................................2
1.3 Transfer Switch Data Decal......................................2
1.4 Transfer Switch Enclosure ......................................2
1.5 Safe Use Of Transfer Switch ....................................2
Section 2 — Installation ....................................................3
2.1 Introduction to Installation ......................................3
2.2 Unpacking ................................................................3
2.3 Mounting ..................................................................3
2.4 Connecting Power Source and Load Lines................3
2.4.1 2-Pole Mechanism ..........................................3
2.5 Connecting Start Circuit Wires ................................4
Section 3 — Operation ......................................................4
3.1 Functional Tests & Adjustments ..............................4
3.2 Manual Operation ....................................................4
3.2.1 Close to Normal Source Side ........................4
3.2.2 Close to Emergency Source Side....................5
3.2.3 Return to Normal Source Side ......................5
3.3 Voltage Checks..........................................................5
3.4 Generator Tests Under Load ....................................6
Section 4 – Notes................................................................7
Section 5 – Installation Diagram ....................................8
Section 6 – Electrical Data ..............................................9
Section 7 – Exploded Views & Parts Lists ..................12
Section 8 – Warranty ......................................Back Cover
• Remove all jewelry (such as rings, watches, bracelets, etc.) before working on this equipment.
• If work must be done on this equipment while standing on metal or concrete, place insulative mats over a dry wood platform. Work on this equipment only while standing on such insulative mats.
• Never work on this equipment while physically or mentally fatigued.
• Keep the transfer switch enclosure door closed and bolted at all times. Only qualified personnel should be permitted access to the switch interior.
• In case of an accident caused by electric shock, immediately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor but AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconduct­ing implement, such as a dry rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• When an automatic transfer switch is installed for a standby generator set, the generator engine may crank and start at any time without warning. To avoid possible injury that might be caused by such sudden start-ups, the system’s automatic start cir­cuit must be disabled before working on or around the generator or transfer switch. Then place a “DO NOT OPERATE” tag on the transfer switch and on the generator. Remove the Negative (Neg) or (–) bat­tery cable.
Page 4
2 Generac®Power Systems, Inc.
Section 1 — General Information
Generac GTS “HS” Type Transfer Switch
1.1 INTRODUCTION
This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to prevent accidents or damage to equipment that might otherwise be caused by carelessness, incorrect appli­cation, or improper procedures.
Every effort has been expended to make sure that the contents of this manual are both accurate and cur­rent. Generac, however, reserves the right to change, alter or otherwise improve the product at any time without prior notice.
1.2 EQUIPMENT DESCRIPTION
The automatic transfer switch is used for transfer­ring electrical load from a UTILITY (NORMAL) power source to a EMERGENCY ( STANDBY) power source. Such a transfer of electrical loads occurs automati­cally when the UTILITY power source has failed or is substantially reduced and the EMERGENCY source voltage and frequency have reached an acceptable level. The transfer switch prevents electrical feedback between two different power sources (such as the UTILITY and EMERGENCY sources) and, for that reason, codes require it in all standby electric system installations.
The transfer switch consists of a transfer mecha­nism, a relay control, and a terminal strip for con­nection of sensing wires.
This switch is suitable for control of motors, electric discharge lamps, tungsten filament and electric heat­ing equipment where the sum of motor full load ampere ratings and the ampere ratings of other loads do not exceed the ampere rating of the switch and the tungsten load does not exceed 30 percent of the switch rating.
The transfer switch is for use in optional standby sys­tems only.
The transfer switch is suitable for use on a circuit capable of 10,000 rms symmetrical amperes, 240 VAC when protected by a circuit breaker without an adjustable short time response or by fuses.
1.3 TRANSFER SWITCH DATA DECAL
A DATA DECAL is permanently affixed to the transfer switch enclosure. Use this transfer switch only with the specific limits shown on the DATA DECAL and on other decals and labels that may be affixed to the switch. This will prevent damage to equipment and property.
When requesting information or ordering parts for this equipment, make sure to include all information from the DATA DECAL.
Record the Model and Serial numbers in the space pro­vided below for future reference.
1.4 TRANSFER SWITCH ENCLOSURE
The standard switch enclosure is a National Electrical Manufacturer’s Association (NEMA) 3R type. NEMA 3R type enclosures primarily provide a degree of protection against falling rain and sleet and is not damaged by the formation of ice on the enclosure.
1.5 SAFE USE OF TRANSFER SWITCH
Before installing, operating or servicing this equip­ment, read the SAFETY RULES (inside front cover) carefully. Comply strictly with all SAFETY RULES to prevent accidents and/or damage to the equipment. Generac recommends that a copy of the SAFETY RULES are posted near the transfer switch. Also, be sure to read all instructions and information found on tags, labels and decals affixed to the equipment.
Two publications that outline the safe use of transfer switches are the following:
• NFPA 70; National Electrical Code
• UL 1008, STANDARD FOR SAFETY-AUTOMATIC TRANSFER SWITCHES
ASSEMBLY # SERIAL #
Page 5
Generac®Power Systems, Inc. 3
2.1 INTRODUCTION TO INSTALLATION
This equipment has been wired and tested at the fac­tory. Installing the switch includes the following pro­cedures:
• Mounting the enclosure.
• Connecting power source and load leads.
• Connecting the generator start circuit.
• Connecting any auxiliary contact (if needed)
• Testing functions.
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any damage that might have occurred during ship­ment. The purchaser must file with the carrier any claims for loss or damage incurred while in transit.
Check that all packing material is completely removed from the switch prior to installation.
2.3 MOUNTING
Mounting dimensions for the transfer switch enclo­sure are in this manual. Enclosures are typically wall-mounted. See “Installation Diagram”, Section 5.
Handle transfer switches carefully when installing. Do not drop the switch. Protect the switch against impact at all times, and against construction grit and metal chips. Never install a transfer switch that has been dam­aged.
Install the transfer switch as close as possible to the electrical loads that are to be connected to it. Mount the switch vertically to a rigid supporting structure. To prevent switch distortion, level all mounting points. If necessary, use washers behind mounting holes to level the unit.
2.4 CONNECTING POWER SOURCE AND LOAD LINES
Make sure to turn OFF both the UTILITY (NORMAL) and EMERGENCY ( STANDBY) power supplies before trying to connect power source and load lines to the transfer switch. Supply voltages are extremely high and dangerous. Contact with such high volt­age power supply lines causes extremely haz­ardous, possibly lethal, electrical shock.
Wiring diagrams and electrical schematics are pro­vided in this manual. Power source and load connec­tions are made at a transfer mechanism, inside the switch enclosure.
2.4.1 2-POLE MECHANISM
These switches (Figure 2.1) are used with a single­phase system, when the single-phase NEUTRAL line is to be connected to a Neutral Lug and is not to be switched.
Figure 2.1 — Typical 2-Pole Transfer Mechanism
(200 Amp Shown)
Solderless, screw-type terminal lugs are standard.
Conductor sizes must be adequate to handle the max­imum current to which they will be subjected to, based on the 75°C column of tables, charts, etc. used to size conductors. The installation must comply fully with all applicable codes, standards and regulations.
Before connecting wiring cables to terminals, remove any surface oxides from the cable ends with a wire brush. All power cables should enter the switch next to transfer mechanism terminals. If ALUMINUM con­ductors are used, apply corrosion inhibitor to con­ductors. Tighten terminal lugs to the torque values as noted on the decal located on the inside of the door. After tightening terminal lugs, carefully wipe away any excess corrosion inhibitor.
All power cables should enter the switch next to the transfer mechanism terminals.
Use a torque wrench to tighten the conduc­tors, being sure not to over tighten, or dam­age to the switch base could occur. If not tightened enough, a loose connection would result, causing excess heat which could dam­age the switch base.
!
Section 2 — Installation
Generac GTS “HS” Type Transfer Switch
Switch Wire Conductor Tightening Rating Range Torque
100A #14-1/0 AWG 50 in-lbs. 200A #6-250 MCM 275 in-lbs.
!
DANGER
Page 6
4 Generac®Power Systems, Inc.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
Connect power source load conductors to clearly marked transfer mechanism terminal lugs as follows
1. Connect UTILITY (NORMAL) power source cables
to switch terminals N1, N2.
2. Connect EMERGENCY (STANDBY) source power
cables to transfer switch terminals E1, E2.
3. Connect customer LOAD leads to switch termi-
nals T1, T2.
Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.
Be sure to maintain proper electrical clearance between live metal parts and grounded metal. Allow at least 1/2 inch for 100-400 amp circuits.
2.5 CONNECTING START CIRCUIT WIRES
Control system interconnections (Section 6) consist of UTILITY 1 and 2, LOAD 1 and 2, and leads 23 and
194. Control system interconnection leads must be
run in a conduit that is separate from the AC power lead. Recommended wire gauge sizes for this wiring depends on the length of the wire, as recommended below:
NOTE:
When this ATS is used with an air-cooled genera­tor, the LOAD 1 and LOAD 2 wires are not used.
3.1 FUNCTIONAL TESTS AND ADJUSTMENTS
Following transfer switch installation and inter­connection, inspect the entire installation careful­ly. A competent, qualified electrician should inspect it. The installation should comply strictly with all applicable codes, standards, and regula­tions. When absolutely certain the installation is proper and correct, complete a functional test of the system.
Perform functional tests in the exact order presented in this manual, or damage could be done to the switch.
IMPORTANT: Before proceeding with functional tests, read and make sure all instructions and infor­mation in this section are understood. Also read the information and instructions of labels and decals affixed to the switch. Note any options or accessories that might be installed and review their operation.
3.2 MANUAL OPERATION
Do NOT manually transfer under load. Disconnect transfer switch from all power sources by approved means, such as a main circuit breaker(s).
A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically. To check manual operation, proceed as follows:
1. Turn the generator’s AUTO-OFF-MANUAL switch to OFF.
2. Turn OFF both UTILITY and EMERGENCY power supplies to the transfer switch, with what­ever means provided (such as the main line cir­cuit breakers).
3. Note position of transfer mechanism main con­tacts by observing the moveable contact carrier arm.
• Manual operation handle towards the top of switch mechanism - LOAD terminals (T1, T2) are connected to UTILITY terminals (N1, N2).
• Manual operation handle towards the bottom of switch mechanism - LOAD terminals (T1, T2) are connected to EMERGENCY terminals (E1, E2).
Do not use excessive force when operating the transfer switch manually or damage could be done to the manual handle.
3.2.1 CLOSE TO NORMAL SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of manual operation handle in Figure 3.1. If the handle is UP, the contacts are closed in the NORMAL position, no further action is required. If the handle is DOWN, proceed with Step
1.
Step 1: With the handle inserted into the actuating
shaft, move handle UP. Be sure to hold on to the handle as it will move quickly after the center of travel.
!
MAXIMUM WIRE LENGTH RECOMMENDED WIRE
SIZE
460 feet (140m) No.18 AWG.
461 to 730 feet (223m) No.16 AWG.
731 to 1,160 feet (354m) No.14 AWG.
1,161 to 1,850 feet (565m) No.12 AWG.
!
DANGER
!
Page 7
Generac®Power Systems, Inc. 5
3.2.2 CLOSE TO EMERGENCY SOURCE SIDE
Before proceeding, verify the position of the switch by observing the position of the manual operation han­dle in Figure 3.1. If the handle is DOWN, the contacts are closed in the EMERGENCY (STANDBY) position. No further action is required. If the handle is UP, pro­ceed with Step 1.
Step 1: With the handle inserted into the actuating
shaft, move the handle DOWN. Be sure to hold on to the handle as it will move quickly after the center of travel.
3.2.3 RETURN TO NORMAL SOURCE SIDE
Manually actuate switch to return manual operating handle to the UP position.
3.3 VOLTAGE CHECKS
1. Turn ON the UTILITY power supply to the trans­fer switch with whatever means provided (such as the UTILITY main line circuit breaker).
PROCEED WITH CAUTION. THE TRANSFER SWITCH IS NOW ELECTRICALLY HOT. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY HAZARDOUS AND POSSIBLY FATAL ELECTRI­CAL SHOCK.
2. With an accurate AC voltmeter, check for correct voltage.
Single-phase utility supply:
Measure across ATS terminal lugs N1 and N2. Also check N1 to NEUTRAL and N2 to NEUTRAL.
3. When certain that UTILITY supply voltage is cor­rect and compatible with transfer switch ratings, turn OFF the UTILITY supply to the transfer switch.
4. On the generator panel, set the AUTO-OFF­MANUAL switch to MANUAL position. The gener­ator should crank and start.
5. Let the generator stabilize and warm up at no­load for at least five minutes.
6. Set the generator's main circuit breaker (CB1) to its ON or CLOSED position.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
Figure 3.1 — Actuating Transfer Switch
Attach handle to actuating shaft.
NOTE: Return handle to storage position in enclosure when finished with manual transfer.
Move handle
UP for the
NORMAL
position.
Move handle
DOWN for the
EMERGENCY
(standby)
position.
DANGER
Page 8
6 Generac®Power Systems, Inc.
PROCEED WITH CAUTION. GENERATOR OUT­PUT VOLTAGE IS NOW BEING DELIVERED TO TRANSFER SWITCH TERMINALS. CONTACT WITH LIVE TERMINALS RESULTS IN EXTREMELY DANGEROUS AND POSSIBLY FATAL ELECTRI­CAL SHOCK.
7. With an accurate AC voltmeter and frequency meter, check the no-load, voltage and frequency.
Single-phase generator supply:
Measure across ATS terminal lugs E1 to E2. Also check E1 to NEUTRAL and E2 to NEUTRAL.
a. Frequency ......................................60-62 Hertz
b. Terminals E1 to E2 ........................240-246 VAC
c. Terminals E1 to NEUTRAL ............120-123 VAC
d. Terminals E2 to NEUTRAL ............120-123 VAC
8. Set the generator’s main circuit breaker (CB1) to its OFF or OPEN position.
9. Set the AUTO/OFF/MANUAL switch to the OFF position to shut down the generator.
NOTE:
Do NOT proceed until generator AC output voltage and frequency are correct and within stated limits. If the no-load voltage is correct but no-load fre­quency is incorrect, the engine governed speed probably requires adjustment. If no-load frequen­cy is correct but voltage is not, the voltage regula­tor may require adjustment.
3.4 GENERATOR TESTS UNDER LOAD
1. Set the generator's main circuit breaker to its OFF or OPEN position.
2. Manually actuate the transfer switch main con­tacts to their EMERGENCY (STANDBY) position. Refer to Manual Operation (Section 3.2).
3. To start the generator, set the AUTO-OFF­MANUAL switch to MANUAL. When engine starts, let it stabilize for a few minutes.
4. Turn the generator's main circuit breaker to its ON or CLOSED position. The generator now pow­ers all LOAD circuits. Check generator operation under load as follows:
Turn ON electrical loads to the full rated wattage/amperage capacity of the generator. DO NOT OVERLOAD.
With maximum rated load applied, check voltage and frequency across transfer switch terminals E1 and E2. Voltage should be greater than 230 volts and frequency should be greater than 59 Hertz.
Let the generator run under rated load for at least 30 minutes. With unit running, listen for unusual noises, vibration, overheating, etc., that might indicate a problem.
5. When checkout under load is complete, set main circuit breaker of the generator to its OFF or OPEN position.
6. Let the generator run at no-load for several minutes. Then, shut down by setting the AUTO­OFF-MANUAL switch to its OFF position.
7. Move the switch's main contacts back to their UTILITY position. For example, load connected to UTILITY power supply. Refer to Manual Operation (Section 3.2). Handle and operating lever of transfer switch should be in UP position.
8. Turn on the utility power supply to transfer switch, using whatever means provided (such as a utility main line circuit breaker). The utility power source now powers the loads.
9. Set the generator's AUTO-OFF-MANUAL switch to
its AUTO position. The system is now set for fully automatic operation.
Section 3 — Operation
Generac GTS “HS” Type Transfer Switch
DANGER
Page 9
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
Generac®Power Systems, Inc. 7
Page 10
8 Generac®Power Systems, Inc.
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
Page 11
Generac®Power Systems, Inc. 9
Section 4 — Notes
Generac GTS “HS” Type Transfer Switch
Page 12
Section 5 — Installation Diagram
Generac GTS “HS” Type Transfer Switch
Drawing No. 0E7081
[
] [
]
OC
OU
SU
OR
,
C
S
[
]
[
]
[
] [
]
[
]
[ ]
10 Generac®Power Systems, Inc.
1.63"
1.5mm
11.57"
94mm
.25"
.3mm
16.54"
20mm
1.77"
5mm
14.84"
77mm
20.02"
08.5mm
ITABLE F T
7.07" E
K
1-1/2" AND 2" CONDUIT SIZE
79.5mm
"
PLA
KN
Page 13
Generac®Power Systems, Inc. 11
O
S
C
O
S
-
@
50
. ,
T
,
1
2
94
1
U
L
C
ON
U
L
UG
S
R CH
Y
Y
O
D
O
R
19
23
U
U
C
G
OR
O
L
O
: O
S
S
S
CH
S
US
E
U
O
CO
U
S.
O
1
LO
O
ST (
)
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Transfer Switch Interconnections
TRA NE
TI
NNE
AD
TILITY
TILITY
L
1
B
IT ND
AND
WIT
T B
FER
M
TE
WER LEAD
N IN TW
TRAN
N
P
LEAD
R
DIFFERENT
TRA NE
L
L PANE
ENERAT
NTR
A
ME
TILIT
PPL
A
T
L
4
AD 1
FE
WIT
TRAN
TILITY 2
TILITY 1
TE TE
OPTIONAL
REM
SWITCH
T
SPS
TE
Vac MIN
H T
2
WIT
2A
SWITCH TYPE
ELECTRICAL RATINGS
PEN
-
Page 14
ONCNCNO
COMC1COM
C2
H
Y
.
:
R
)
K
OR
A
1
2
4
94
3
94
6
3
6
OR
)
)
D
R
S
05
0
1
2
2
*
)
5
3
3
S
1
S
12 Generac®Power Systems, Inc.
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Electrical Schematic - Drawing No. 0E6093-A
12
TILITY
AT
N
2
TB
1
NOTE ALL CONTACTS SHOWN WIT TRANSFER SWITCH IN UTILIT POSITION
2
1
2
0
* - NOT USED WITH PREPACKAGED STANDBY GENERATOR
LEGEN
AT
XA1,XB
F1,2,3 &
VR1,VR
TRANSFER SWITCH CONTACT
SOLENOID COIL (UTILITY CLOSING
SOLENOID COIL (STANDBY CLOSING
RELAY, TRANSFE
TERMINAL STRIP (CUSTOMER CONNECTION
LIMIT SWITCHES, ACTUATO
FUSE, 5
VARIST
NB - NEUTRAL BLOC
F
LOAD
TB
LOAD
TILITY
NEUTRAL
OPTIONAL
TB
Page 15
Generac®Power Systems, Inc. 13
T
) *
OL
S
94
6
05
3
94
3
3
3
94
05
12
6
OCK
0
D
S
)
S
)
Section 6 — Electrical Data
Generac GTS “HS” Type Transfer Switch
Electrical Schematic - Drawing No. 0E6093-A
C1
AT
12
1
2
* - NOT USED WITH PREPACKAGE
TANDBY GENERATOR
2
C2
2
2
1
NEUTRAL BL
F
2
1
0
47822-
TOMER CONTR
NNECTION
AD 1
TILITY 1
TILITY 2
AD 2
4
3
OPTIONAL
Page 16
14 Generac®Power Systems, Inc.
600V
T
)
A
C
OSU
Q
B
)
8X16T
8X16T
95
,
U
U
O
S
5
C
G
S
UGS
SU
O
CO
G C 98
O
0
5595
0
083
9 ,
U
O
S
U
S
0/
0
T
63378T 63378-T
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0E8403$-B
4
7
-
-
2
1
-
UE ITEM #3 TO 24-30 IN.LBS
OTE: TOR
POWER TERMINAL LUG ASSEMBLY
RE
L N
17
A
PPER
RATIN
4
R
4
INC.
T 7
R #
WI.
ITABLE F
7
LT
F AT LEA
ARE
AUKESHA
R #
M V
M AMP
44
24
L
M WIRE
2
AXIM
AXIM
7
MIN
GENERAC POWER SYSTEMS
R AL
LL TERMINAL
H
ATIN
WIT
-
GROUND LUG ASSEMBLY
Page 17
Generac®Power Systems, Inc. 15
ITEM PART NO. QTY. DESCRIPTION
1 0C2237 1 TR SW-HSB 100A 2P 250V 2 077033 6 LUG SLDLSS 1/0-#14X9/16 AL/CU 3 036932 6 SCREW PPHM #10-32 X 1/4 4 022152 6 WASHER LOCK #10 5 066849 4 SCREW HHTT M5-0.8 X 16 BP 6 045771 1 NUT HEX M8-1.25 G8 YEL CHR 7 062684 1 LUG SLDLSS 2/0-#12 X 11/32 CU 8 0C3168 1 WASHER LOCK SPECIAL 5/16
9 022129 1 WASHER LOCK M8-5/16 10 073590A 4 FUSE 5A X BUSS 11 073591 4 FUSE HOLDER 12 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 13 0A1495 6 SCREW HHTT M4-0.7 X 10 BP 14 063617 1 RELAY PNL 12VDC DPDT 10A@240VA 15 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA Z/JS 16 0A1661 2 RIVET POP .156 X .675 AL 17 0C4449 1 ASSY NEUTRAL BLOCK 100A 18 0E6057 1 WELDMENT XFER SW BOX HSB 19 0E6056 1 COVER TRANSFER SWITCH BOX HSB
20**** 0E5567 1 DECAL TRANSFER SWITCH
21 0A2595 1 DECAL TERMINAL STRIP 22 0E8443 1 DECAL SWITCH RATING
23*** 095282 1 DECAL-LIVE CIRCUIT
24 067210A 1 DECAL GROUND LUG 25 0A9457 1 DECAL NEUTRAL 26 0A9517 1 DECAL MANUAL 5A FUSE
27* 077036D 1 DECAL TEST SEQUENCE 3R
28 081221 1 DECAL-UL LIST HSB 29 064101 4 NUT HEX FL WHIZ 3/8-16 30 0E6055 1 SUBPLT TRANSFER SWITCH HSB
31***** 063378 4 HOLDER CABLE TIE 32***** 028739 4 TIE WRAP UL 3.9" X .10" NATL
33 064113 1 STUD WINGNUT M6-1.0 X 20MM NY
34** 077441 0 HANDLE TRANSFER SW H.S.
35 0E6303 1 WIRE A 36 0E6303A 1 WIRE B 37 0E6303C 1 WIRE E1 38 0E6094 1 WIRE HARNESS 100/200A 2P HS (NOT SHOWN)
* CENTER DECAL ON INSIDE OF THE COVER (ITEM #19) ** SUPPLIED WITH TRANSFER SWITCH ITEM #1. *** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER. **** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7" FROM TOP OF ENCLOSURE. ***** SUPPLIED WITH HARNESS (P/N 0E6094).
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
100A Transfer Switch Assembly – Drawing No. 0E8403$-B
Page 18
LO
LO
UTILITY
UTILITY
194
23
U
8
3
9
S
C
OSU
)
A
O
S
Q
8X16
95
WS34X14S
S
O
G
U
0/
0
U
16 Generac®Power Systems, Inc.
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E5782$-E
UE ITEM
IN-LB
72
OTE: TOR
T
4
TRAL E
AD 2
AD 1
2
1
22-T 7
RE
L N
­2 7
1
-
GROUND LUG ASSEMBLY
17
A
E
LTA
MBER
MBER
TEM V
DEL N
Y
ERIAL N
24 2
Page 19
Generac®Power Systems, Inc. 17
Section 7 — Exploded Views and Parts List
Generac GTS “HS” Type Transfer Switch
200A Transfer Switch Assembly – Drawing No. 0E5782$-E
ITEM PART NO. QTY. DESCRIPTION
1 0D9618 1 TR SW-HSB 200A 2P 250V
2 0E3375 6 LUG SLDLSS 250-#6 AL/CU
3 0E6058 6 SCREW SHC 1/4-20X3/8
4 022097 6 WASHER LOCK M6-1/4
5 066849 5 SCREW HHTT M5-0.8 X 16 BP
6 045771 1 NUT HEX M8-1.25 G8 YEL CHR
7 057329 1 LUG SLDLSS 350-#6 X 13/32 AL/CU
8 027482 1 WASHER SHAKEPROOF EXT 5/16 STL
9 022129 1 WASHER LOCK M8-5/16 10 073590A 4 FUSE 5A X BUSS
11***** 073591 4 FUSE HOLDER
12 090388 2 SCREW HHTT M6-1.0 X 12 ZINC 13 0A1495 6 SCREW HHTT M4-0.7 X 10 BP
14***** 063617 1 RELAY PNL 12VDC DPDT 10A@240VA
15 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA Z/JS 16 0A1661 2 RIVET POP .156 X .675 AL 17 0C4449A 1 ASS'Y-NTRL BL150-200A 18 0E6057 1 WELDMENT XFER SW BOX HSB 19 0E6056 1 COVER TRANSFER SWITCH BOX HSB
20**** 0E5567 1 DECAL TRANSFER SWITCH
21 0A2595 1 DECAL TERMINAL STRIP
22*** 095282 1 DECAL-LIVE CIRCUIT
23 0E8443 1 DECAL SWITCH RATING 24 064101 4 NUT LOCK FL 3/8-16 25 0E6055 1 SUBPLT TRANSFER SWITCH HSB
26***** 063378 5 HOLDER CABLE TIE 27***** 028739 5 TIE WRAP UL 3.9" X .10" NATL
29 067210A 1 DECAl GROUND LUG 30 0A9457 1 DECAL NEUTRAL 31 0A9517 1 DECAL MANUAL 5A FUSE
32 * 0E6190 1 DECAL TEST SEQUENCE 2P TS 3R
33 081221 1 DECAL-UL LIST HSB 34 0E6193 1 BRACKET ARM EXTENDER 35 0C4739 2 SCREW PPHM M3-0.5 X 6
36 ** 0E6155 1 ARM EXTENDER PIN
37 0E6094 1 HARN 100/200A 2P HS
38 ** 0E6033 2 90 DEGREE DN SPADE CONNECTOR
40 0E6303 1 WIRE A 41 0E6303A 1 WIRE B 42 0E6303B 1 WIRE-E1
* CENTER DECAL ON INSIDE OF THE COVER (ITEM #19) ** SUPPLIED WITH TRANSFER SWITCH ITEM #1. *** PLACE DECAL ON OUTSIDE OF COVER, LOWER RIGHT CORNER. **** NOT SHOWN ON THIS ASSEMBLY, CENTER DECAL ON FRONT OF COVER, 7" FROM TOP OF ENCLOSURE. ***** SUPPLIED WITH HARNESS (P/N 0E6094)
Page 20
Part No. 0E6347 Revision D (02/05/04) Printed in U.S.A.
Section 8 — Warranty
Generac GTS “HS” Type Transfer Switch
GENERAC POWER SYSTEMS STANDARD TWO-YEAR LIMITED WARRANTY
FOR GENERAC TRANSFER SWITCH SYSTEMS
NOTE: ALL UNITS MUST HAVE A START-UP INSPECTION PERFORMED BY AN AUTHORIZED GENERAC DEALER.
For a period of 2 (two) years from the date of sale/start date, Generac Power Systems, Inc. will, at its option, repair or replace any part(s) which, upon examination, inspection, and testing by Generac Power Systems or a Generac Power Systems Authorized Warranty Service Facility, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equipment that the purchaser/owner claims to be defective must be returned to, and examined by the nearest Generac Power Systems Authorized Warranty Service Facility. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the purchaser/owner. This warranty applies only to Generac Power Systems Transfer Switch applications, as Generac Power Systems, Inc. have defined Transfer Switch application, provided said Transfer Switch has been initially installed and inspected on-site by a Generac Power Systems Authorized Service Dealer or branch thereof. A scheduled maintenance agreement with a local Authorized Generac Power Systems Dealer is highly recommended to verify adequate service has been performed on the unit throughout the warranty period.
WARRANTY SCHEDULE
YEAR ONE — 100% (one hundred percent) coverage on mileage*, labor, and parts listed.
ALL COMPONENTS
YEAR TWO — 100% (one hundred percent) coverage on parts listed.
ALL COMPONENTS — *PARTS ONLY
• *Travel allowance is limited to 300 miles maximum, or 7.5 hours maximum (per occurrence), round trip, to the nearest authorized Generac Service Facility.
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a non Generac genset is substituted for use and directly causes damage to the Generac Transfer Switch, no warranty coverage shall apply.
• All warranty expense allowances are subject to the conditions defined in Generac Power Systems Warranty, Policies, and Procedures Flat Rate Manual.
• Units that have been resold are not covered under the Generac Power Systems Warranty, as this Warranty is not transferable.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
1. Any unit built/manufactured prior to January 1, 2002.
2. Unit enclosure is only covered against rust or corrosion the first year of the warranty provision.
3. Costs of normal maintenance i.e. tune-ups, associated part(s), adjustments, loose/leaking clamps, installation and start-up.
4. Use of Non-Generac replacement part(s) will void the warranty in its entirety.
5. Any failure caused by contaminated fuels, oils, coolants/antifreeze or lack of proper fuels, oils or coolants/antifreeze.
6. Failures due, but not limited to, normal wear and tear, accident, misuse, abuse, negligence, or improper installation or sizing.
7. Failures caused by any external cause or act of God such as collision, fire, theft, freezing, vandalism, riot or wars, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado, hurricane, terrorist acts or nuclear holocaust.
8. Products that are modified or altered in a manner not authorized by Generac Power Systems in writing.
9. Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
10. Failure due to misapplication, misrepresentation, or bi-fuel conversion.
11. Telephone, telegraph, teletype or other communication expenses.
12. Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
13. Rental equipment used while warranty repairs are being performed i.e. rental generators, cranes, etc..
14. Overtime labor or more than one person performing repairs.
15. Any and all expenses incurred investigating performance complaints unless defective Generac materials and or work­manship were the direct cause of the problem.
16. *Engine coolant heaters (block-heaters), heater controls and circulating pumps after the first year.
17. *Starting batteries, fuses, light bulbs, engine fluids, tires, brakes, and overnight freight cost for replacement part(s).
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, SPECIFICALLY, GENERAC
POWER SYSTEMS MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICU­LAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC POWER SYSTEMS ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED
ABOVE. IN NO EVENT SHALL GENERAC POWER SYSTEMS BE LIABLE FOR ANY INCIDENTAL, OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC POWER SYSTEMS, INC. NEGLIGENCE.
Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitations may
not apply to you. Purchaser/owner agrees to make no claims against Generac Power Systems, Inc. based on negligence.
This warranty gives you specific legal rights. You also may have other rights that vary from state to state.
GENERAC®POWER SYSTEMS, INC. • P.O. BOX 8 • WAUKESHA, WI 53187
PH: (262) 544-4811 • FAX: (262) 544-4851
Bulletin 0166260SBY / Printed in USA 5.02
Loading...