Generac 004626-1, 004373-2 User Manual

Page 1
POWER SYSTEMS, INC.
®
Owner’s Manual
Liquid-cooled, Prepackaged
Standby Generators
Models:
w/ 200 Amp Transfer Switch)
004626-1 (40 kW/Single-phase
w/ 200 Amp Transfer Switch California Emissions)
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS
SHOULD ATTEMPT INSTALLATION!!
*This Manual Should
Remain With The Unit*
POWER SYSTEMS, INC.
®
®
DANGER
Page 2
Generac®Power Systems, Inc.
INTRODUCTION
Thank you for purchasing the Guardian product line by Generac Power Systems. This model is a compact, high performance, liquid-cooled, engine-driven gen­erator designed to automatically supply electrical power to operate critical loads during a utility power failure.
This unit is factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.
READ THIS MANUAL THOROUGHLY
If you do not understand any portion of this manual, contact Generac or the nearest Generac/Guardian Authorized Dealer for starting, operating and servicing procedures.
Throughout this publication, and on tags and decals affixed to the generator, DANGER, WARNING, CAUTION and NOTE blocks are used to alert you to special instruction about a particular operation that may be hazardous if performed incorrectly or care­lessly. Observe them carefully. Their definitions are as follows:
After this heading, read instructions that, if not strictly complied with, will result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, may result in personal injury or property damage.
After this heading, read instructions that, if not strictly complied with, could result in damage to equipment and/or property.
NOTE:
After this heading, read explanatory state­ments that require special emphasis.
These safety warnings cannot eliminate the hazards that they indicate. Common sense and strict compli­ance with the special instructions while performing the service are essential to preventing accidents.
Four commonly used safety symbols accompany the DANGER, WARNING and CAUTION blocks. The type of information each indicates is as follows:
This symbol points out important safety informa­tion that, if not followed, could endanger personal safety and/or property.
This symbol points out potential explosion hazard.
This symbol points out potential fire hazard.
This symbol points out potential electrical shock hazard.
The operator is responsible for proper and safe use of the equipment. Generac strongly recommends that
the operator read this Owner's Manual and thor-
oughly understand all instructions before using this equipment. Generac also strongly recommends instructing other users to properly start and operate the unit. This prepares them if they need to operate the equipment in an emergency.
CONTENTS
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for Guardian models:
004373-1 & 004626-0.
OPERATION AND MAINTENANCE
It is the operator's responsibility to perform all safety checks, to make sure that all maintenance for safe operation is performed promptly, and to have the equipment checked periodically by a Generac/ Guardian Authorized Dealer. Normal maintenance service and replacement of maintenance parts are the responsibility of the owner/operator and, as such, are not considered defects in materials or workmanship within the terms of the warranty. Individual operating habits and usage contribute to the need for mainte­nance service.
Proper maintenance and care of the generator ensure a minimum number of problems and keep operating expenses at a minimum. See a Generac/Guardian Authorized Dealer for service aids and accessories.
HOW TO OBTAIN SERVICE
When the generator requires servicing or repairs, simply contact a Generac/Guardian Authorized Dealer for assistance. Service technicians are factory­trained and are capable of handling all service needs.
When contacting a Generac/Guardian Authorized Dealer or the factory about parts and service, always supply the complete model number and serial num­ber of the unit as given on its data decal, which is located on the generator.
Model No. ____________ Serial No. ______________
AUTHORIZED
DEALER LOCATION
To locate the GENERAC/GUARDIAN AUTHORIZED
DEALER nearest you, please call this number:
1-800-333-1322
DEALER LOCATION INFORMATION
CAN BE OBTAINED AT THIS NUMBER.
DANGER
!
Page 3
Table of Contents
Guardian Liquid-cooled 40 kW Generator
Generac®Power Systems, Inc. 1
Introduction ......................Inside Front Cover
Read This Manual Thoroughly ......................IFC
Contents ........................................................IFC
Operation and Maintenance............................IFC
How to Obtain Service ....................................IFC
Authorized Dealer Locator Number ..................IFC
Safety Rules ......................................................2
Section 1 – General Information..................4
1.1 Unpacking/Inspection ..................................4
1.1.1 Lifting the Generator ........................4
1.2 The Generator..............................................4
1.3 Generator AC Connection Systems ..............4
1.4 Prepackaged Transfer Switch ......................4
1.5 Automatic System Operation........................4
1.6 Main Circuit Breaker ..................................5
1.7 Engine Protective Devices ............................5
1.7.1 Low Oil Pressure Switch ..................5
1.7.2 High Coolant
Temperature Switch ........................5
1.7.3 Low Coolant Level Switch ................5
1.7.4 Overspeed Shutdown ......................5
1.7.5 Overcrank Shutdown ......................5
1.7.6 DC Fuse............................................5
1.8 Specifications ..............................................5
1.8.1 Generator ........................................5
1.8.1.1 Generator Load
and Compatibility ....................6
1.8.2 Engine ..............................................6
1.9 Fuel Requirements
and Recommendations ............................6
1.9.1 Conversion to LP Gas Vapor ............6
1.10 Engine Oil Recommendations ......................7
1.11 Coolant ........................................................7
1.12 Emission Control System ............................7
Section 2 – Installation ..................................8
2.1 Basic Standby Electric System ....................8
2.2 Emergency Circuit Isolation Method ............9
2.3 Total Circuit Isolation Method......................9
2.4 Grounding the Generator ............................9
2.5 Generator AC Neutral Connections ..............9
2.6 Transfer Switch Start Signal Connections....9
2.6.1 Pre-Packaged Type Switch..................9
2.6.2 “GTS” Type Switch ............................9
2.7 Battery Installation ....................................10
2.7.1 Vented Batteries ..............................10
2.8 Preparation Before Start-up ......................10
2.8.1 Prior to Initial Start-up ....................11
2.8.2 Transfer Switch ..............................11
2.8.3 Fuel System ....................................11
2.8.4 Generator Set Lubrication ..............11
2.8.5 Engine Coolant ................................11
2.8.6 Belt Tension ....................................11
2.8.7 Electrical System ............................11
2.8.8 Rodent Protection ............................11
Section 3 – Operation ..................................12
3.1 Control Console Components ......................12
3.1.1 AC Voltmeter ..................................12
3.1.2 AC Ammeter ..................................12
3.1.3 AC Frequency Meter ......................12
3.1.4 DC Voltmeter..................................12
3.1.5 Hourmeter......................................12
3.1.6 Auto/Off/Manual Switch..................12
3.1.7 Fault Indicator Lamp......................12
3.1.8 15-amp Fuse ..................................12
3.1.9 7.5 Amp Inline Fuse ......................12
3.1.10 Voltage-phase Selector Switch ........12
3.1.11 Set Exercise Time Switch ..............12
3.2 Using the Auto/Off/Manual Switch ..............12
3.2.1 “Auto” Position................................12
3.2.2 “Off” Position..................................13
3.2.3 “Manual” Position ..........................13
3.3 Automatic Transfer Operation....................13
3.4 Sequence of Automatic Operation ..............13
3.5 Engine Heater ..............................................13
3.6 Weekly Exercise Cycle ................................14
Section 4 – Maintenance ............................14
4.1 Checking the Engine Oil Level....................14
4.2 Changing the Engine Oil and Filter ............15
4.2.1 Engine Oil Recommendations ........15
4.2.2 Oil and Filter Change Procedure ......15
4.3 Changing the Engine Air Cleaner................15
4.4 Spark Plugs................................................16
4.5 Battery Maintenance ..................................16
4.6 Cooling System ..........................................17
4.7 Overload Protection for
Engine DC Electrical System......................17
4.8 DC Fuse ....................................................17
4.9 Engine Coolant ..........................................17
4.10 Miscellaneous Maintenance ........................17
4.10.1 Cleaning the Generator ..................17
4.10.2 Rodent Protection ..........................18
4.11 Out of Service Procedure ............................18
4.11.1 Removal From Service....................18
4.11.2 Return to Service............................18
4.12 Service Schedule ........................................19
Section 5 – Troubleshooting ......................20
Section 6 – Electrical Data ....................21-29
Section 7 – Exploded Views and
Parts Lists ............................30-54
Section 8 – Notes ..........................................55
Section 9 – Installation Drawings........56-57
Section 10 – Warranty ..................Back Cover
Page 4
2 Generac®Power Systems, Inc.
Study these SAFETY RULES carefully before installing, operating or servicing this equipment. Become familiar
with this Owner’s Manual and with the unit. The gen-
erator can operate safely, efficiently and reliably only if it is properly installed, operated and maintained. Many accidents are caused by failing to follow simple and fun­damental rules or precautions.
Generac cannot possibly anticipate every possible circumstance that might involve a hazard. The warn­ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If you use a procedure, work method or operating technique Generac does not specifically recommend, you must satisfy yourself that it is safe for you and others. You also must make sure the procedure, work method or operating technique that is chosen does not render the generator unsafe.
Despite the safe design of this generator, operating this equipment imprudently, neglecting its maintenance or being careless can cause possible injury or death. Permit only responsible and capable persons to operate or maintain this equip­ment.
Potentially lethal voltages are generated by these machines. Ensure all steps are taken to render the machine safe before attempting to work on the generator.
Parts of the generator are rotating and/or hot during operation. Exercise care near running gen­erators.
GENERAL HA
ZARDS
• For safety reasons, Generac recommends that the installation, initial start-up and maintenance of this equipment is carried out by a Generac/Guardian Authorized Dealer.
• Installation, operation, servicing and repair of this (and related) equipment must always comply with applicable codes, standards, laws and regulations. Adhere strictly to local, state and national electrical and building codes. Comply with regulations the Occupational Safety and Health Administration (OSHA) has established. Also, ensure that the gener­ator is installed, operated and serviced in accordance with the manufacturer’s instructions and recommen­dations. Following installation, do not do anything that might render the unit unsafe or in noncompli­ance with the aforementioned codes, standards, laws and regulations.
• The engine exhaust fumes contain carbon monoxide, which can be DEADLY. This dangerous gas, if breathed in sufficient concentrations, can cause unconsciousness or even death. For that reason, ade­quate ventilation must be provided. Exhaust gases must be piped safely away from any building or enclosure that houses the generator to an area where people, animals, etc., will not be harmed. This exhaust system must be installed properly, in strict compliance with applicable codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts, fans, and other moving or hot parts. Never remove any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating air is critical in any room or building housing the gen­erator to prevent buildup of explosive gases and to ensure correct generator operation. Do not alter the installation or permit even partial blockage of ventila­tion provisions, as this can seriously affect safe oper­ation of the generator.
• Keep the area around the generator clean and unclut­tered. Remove any materials that could become haz­ardous.
• When working on this equipment, remain alert at all times. Never work on the equipment when you are physically or mentally fatigued.
!
!
!
Important Safety Instructions
Guardian Liquid-cooled 40 kW Generator
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators and potential operators of this equipment.
!
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
WARNING:
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during installation and maintenance of the generator and batteries.
!
!
This product contains or emits chemicals known to the state of California to cause
cancer, birth defects or other reproductive harm.
WARNING:
!
!
!
!
!
DANGER
!
Page 5
Generac®Power Systems, Inc. 3
• Inspect the generator regularly, and promptly repair or replace all worn, damaged or defective parts using only factory-approved parts.
• Before performing any maintenance on the generator, disconnect its battery cables to prevent accidental start-up. Disconnect the cable from the battery post indicated by a NEGATIVE, NEG or (–) first. Reconnect that cable last.
• Never use the generator or any of its parts as a step. Stepping on the unit can stress and break parts, and may result in dangerous operating conditions from leaking exhaust gases, fuel leakage, oil leakage, etc.
ELECTRICAL HAZARDS
• All generators covered by this manual produce dan­gerous electrical voltages and can cause fatal electri­cal shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in operation. Avoid con­tact with bare wires, terminals, connections, etc., while the unit is running. Ensure all appropriate cov­ers, guards and barriers are in place before operating the generator. If work must be done around an oper­ating unit, stand on an insulated, dry surface to reduce shock hazard.
• Do not handle any kind of electrical device while standing in water, while barefoot, or while hands or feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• If people must stand on metal or concrete while installing, operating, servicing, adjusting or repairing this equipment, place insulative mats over a dry wooden platform. Work on the equipment only while standing on such insulative mats.
• The National Electrical Code (NEC) requires the frame and external electrically conductive parts of the generator to be connected to an approved earth ground and/or grounding rods. This grounding will help prevent dangerous electrical shock that might be caused by a ground fault condition in the generator set or by static electricity. Never disconnect the ground wire.
• Wire gauge sizes of electrical wiring, cables and cord sets must be adequate to handle the maximum elec­trical current (ampacity) to which they will be sub­jected to.
• Before installing or servicing this (and related) equip­ment, make sure that all power voltage supplies are positively turned off at their source. Failure to do so will result in hazardous and possibly fatal electrical shock.
• Connecting this unit to an electrical system normally supplied by an electric utility shall be by means of a transfer switch so as to isolate the genrator electric system from the utility electric system while in oper­ation. Failure to isolate the two electric system power sources from each other by such means will result in damage to the generator and may also result in injury or death to utility power workers due to backfeed of electrical energy.
• Generators installed with an automatically transfer switch will crank and start automatically when nor­mal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to personnel, disable the generator’s automatic start circuit (battery cables, etc.) before working on or around the unit. Then, place a “Do Not Operate” tag on the generator control panel and on the transfer switch.
• In case of accident caused by electric shock, immedi­ately shut down the source of electrical power. If this is not possible, attempt to free the victim from the live conductor. AVOID DIRECT CONTACT WITH THE VICTIM. Use a nonconducting implement, such as a rope or board, to free the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medical help.
• Never wear jewelry when working on this equipment. Jewelry can conduct electricity resulting in electric shock, or may get caught in moving components causing injury.
F
IRE HAZARDS
• Keep a fire extinguisher near the generator at all times. DO NOT use any carbon tetra-chloride type extinguisher. Its fumes are toxic, and the liquid can deteriorate wiring insulation. Keep the extinguisher properly charged and be familiar with its use. If there are any questions pertaining to fire extinguishers, consult the local fire department.
EXPLOSION HAZARDS
• Properly ventilate any room or building housing the generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel or oil spills immediately. Ensure that no combustible materials are left in the generator compartment, or on or near the generator, as FIRE or EXPLOSION may result. Keep the area surrounding the generator clean and free from debris.
• Generac generator sets may operate using one of sev­eral types of fuels. All fuel types are potentially FLAMMABLE and/or EXPLOSIVE and should be handled with care. Comply with all laws regulating the storage and handling of fuels. Inspect the unit’s fuel system frequently and correct any leaks imme­diately. Fuel supply lines must be properly installed, purged and leak tested according to applicable fuel­gas codes before placing this equipment into service.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids such as natural gas and liquid propane (LP) gas are extremely EXPLOSIVE. Natural gas is lighter than air, and LP gas is heavier than air; install leak detec­tors accordingly.
Important Safety Instructions
Guardian Liquid-cooled 40 kW Generator
Page 6
4 Generac®Power Systems, Inc.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for damage.
• This standby generator set has been factory installed in an all-weather, metal enclosure that is intended exclusively for outdoor installation.
If this generator is used to power electrical load circuits normally powered by a utility power source, code requires to install a transfer switch. The transfer switch must effectively isolate the electrical system from the utility distribution sys­tem when the generator is operating (NEC 701). Failure to isolate an electrical system by such means will result in damage to the generator and also may result in injury or death to utility power workers due to backfeed of electrical energy.
If any loss or damage is noted at time of delivery, have the person(s) making the delivery note all damage on the freight bill or affix his or her signature under the consignor's memo of loss or damage.
If there is loss or damage after delivery, separate the damaged materials and contact the carrier for claim procedures.
“Concealed damage” is understood to mean damage to the contents of a package that is not in evidence at the time of delivery, but is discovered later.
1.1.1 LIFTING THE GENERATOR
When lifting or hoisting equipment is used, be careful not to touch overhead power lines.
The generator’s weight of more than 2,000 pounds requires proper tools and equipment, and qualified personnel to be used in all phases of handling and unpacking.
1.2 THE GENERATOR
This liquid-cooled, Guardian generator set is designed to supply electrical power to operate critical electrical loads during utility power failure. Use this generator as a source of electrical power for the operation of 120 and/or 240-volt, single-phase loads.
1.3 GENERATOR AC
CONNECTION SYSTEMS
Figure 1.1 represents a single-phase, four-wire genera­tor AC connection system. The stator assembly in this system consists of a pair of stationary windings with two leads brought out of each winding. Each single winding can supply a 120-volt, 60-Hertz AC output.
When the two windings are connected in series, a 240­volt, 60-Hertz AC output results. Typically, the two “hot” leads in the circuit are Wires 11 and 44. The neutral leads are the junction of Wires 22 and 33.
Figure 1.1 – Single-phase
Generator AC Connection System
1.4 PREPACKAGED TRANSFER SWITCH
The transfer switch shipped with this generator is rated 200 amps maximum at 120/240 volts AC single-phase. The enclosure of the transfer switch is NEMA 3R. This type of enclosure is intended for indoor or outdoor use.
Follow these rules:
• Install the transfer switch on a firm, sturdy support­ing structure.
• To prevent switch distortion, level the switch if nec­essary. This can be done by placing washers between the switch enclosure and mounting surface.
• Never install the switch where any corrosive sub­stance might drop onto the enclosure.
• Where practical, protect the switch against excessive moisture, dust, dirt, lint, and construction grit. Always prevent corrosive vapors from coming in con­tact with enclosure.
1.5 AUTOMATIC SYSTEM OPERATION
When this generator, along with its transfer switch, has been installed and interconnected, a circuit board in the generator panel continuously monitors utility power source voltage. Should that voltage drop below a preset value, and remain at such a low state for a preset amount of time, the generator cranks and starts. After the gener­ator starts, the transfer switch transfers load circuits so the generator can power them.
When utility source voltage has been restored, the switch transfers back to the utility source voltage, and the generator then shuts down after a brief cool-down time.
Section 1 General Information
Guardian Liquid-cooled 40 kW Generator
!
Neutral Block
Page 7
1.6 MAIN CIRCUIT BREAKER
The generator’s main circuit breaker is included with the unit as shipped from the factory. The breaker for each unit is described as follows:
1.7 ENGINE PROTECTIVE DEVICES
The engine has several safety switches that cause it to automatically shut down under the following condi­tions: low oil pressure, high coolant temperature, low coolant level, engine overspeed and overcrank.
1.7.1 LOW OIL PRESSURE SWITCH
This switch is normally closed (N.C.) but is held open by engine oil pressure during engine running. Should oper­ating oil pressure drop below approximately 10 psi (68 kPa), the switch contacts close, and the engine shuts down automatically (Figure 1.2).
Figure 1.2 – Engine Protective Devices
1.7.2 HIGH COOLANT TEMPERATURE SWITCH
This normally open (N.O.) thermostatic switch has a sensing tip that is immersed in captive coolant. Should the coolant temperature exceed approximately 121° C (250° F), the switch contacts close, which causes the engine to shut down automatically (Figure 1.2).
1.7.3 LOW COOLANT LEVEL SWITCH
Should the engine coolant level drop below the level of the high coolant temperature switch, it is possible for the engine to overheat without automatic shut down. To pre­vent such overheating without automatic shut down, the engine has a low coolant level sensor. If the engine coolant drops too low, the engine automatically shuts down (Figure 1.2).
1.7.4 OVERSPEED SHUTDOWN
The control module assembly (CMA) circuit board on liquid-cooled units receives AC frequency (rpm) signals directly from the stator AC power windings. Should AC frequency exceed approximately 72 Hertz, circuit board action will automatically shut down the engine.
1.7.5 OVERCRANK SHUTDOWN
After 90 seconds of crank-rest cycles (about seven sec­onds cranking/seven seconds at rest), this function ends cranking if the engine fails to start in that 90-second span.
1.7.6 DC FUSE
This fuse is located on the front panel of the control sys­tem. It protects the panel wiring and components from damaging overload. Always remove this fuse before commencing work on the generator. The unit will not start or crank if the fuse is blown. Replace the fuse with one of the same size, type, and rating. Generac uses an AGC fuse rated at 15 amps.
1.8 SPECIFICATIONS
1.8.1 GENERATOR
Models 004373-2 & 004626-1
Rated Maximum Continuous AC Power Output (kW)* 40
Rated Voltage (volts) 120/240 Rated Maximum Continuous
Current at 240 Volts, 16 7 Single-phase (amps)
Number of Rotor Poles 4 Driven Speed of Rotor (rpm) 1,800 Type of Stator Four-wire Rotor Excitation System Direct Excited
Brush-type System Stator Insulation Class “H” Rotor Insulation Class “F”
*Rated power of generator is subject to and limited by such factors as ambient tempera-
ture, altitude, engine condition and other factors. Engine power will decrease about 3.5
percent for each 1,000 feet above sea level; and also will decrease an additional 1 percent
for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of the gener-
ator is limited by maximum engine power.
Section 1 General Information
Guardian Liquid-cooled 40 kW Generator
Generac®Power Systems, Inc. 5
Model Number Circuit Breaker Rating
004373-2 200-amp breaker 004626-1 200-amp breaker
Page 8
6 Generac®Power Systems, Inc.
1.8.1.1 Generator and Load Compatibility
The generator must be fully compatible with the rated voltage, number of phases and frequency of the con­nected electrical loads. The generator, connected elec­trical devices, or both, can be damaged if voltage, num­ber of phases and frequency are not compatible.
Note:
This manual assumes that the standby generator has been properly selected, installed and intercon­nected by a competent, qualified electrician or installation contractor. Once the installation is complete, do nothing that may result in noncom­patibility between the generator and connected electrical loads.
1.8.2 ENGINE
Make........................................................General Motors
Displacement ................................4.3 liters (262 cu. in.)
Cylinder Arrangement ................................................V-6
Valve Arrangement..................................Overhead Valves
Firing Order ..................................................1-6-5-4-3-2
Number of Main Bearings ..............................................4
Compression Ratio ..............................................9.4-to-1
No. of Teeth on Flywheel ............................................168
Ignition System ................................................Electronic
Ignition Timing at 1,800 rpm ..............40 degrees BTDC
Rated Horsepower at 1,800 rpm..................................67
Spark Plug Gap ..............................0.045 inch (1.1 mm)
Recommended Spark Plugs ......AC 41-932 or equivalent
Oil Pressure ......................................................30-50 psi
Crankcase Oil Capacity ..............4.5 U.S. quarts (4.25 L)
Recommended Engine Oil ............................SAE 15W-40
Type of Cooling System ......Pressurized, closed recovery
Cooling Fan ..................................................Pusher Type
Cooling System Capacity ..............4.5 U.S. gallons (17 L)
Recommended Coolant ..................Use a 50-50 mixture of
ethylene glycol and soft water.
Fuel Consumption
Natural Gas
004373-2 & 004626-1 ........................................720 cfh
LP Gas
004373-2 & 004626-1..............................288 cfh/7.9gph
1.9 FUEL REQUIREMENTS AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system.
This type of system uses the vapors formed above the liquid fuel in the storage tank.
Recommended fuels should have a Btu content of at least 1,000 Btus per cubic foot for natural gas; or at least 2,520 Btus per cubic foot for LP gas. Ask your fuel supplier for the Btu content of your fuel.
Fuel pressure for both natural gas and liquid propane setups should be 11 inches to 14 inches of water column (0.6 psi) at all load ranges.
Gaseous fuels such as natural gas and liquid propane (LP) gas are highly explosive. Even the slightest spark can ignite such fuels and cause an explosion. No leakage of fuel is permitted. Natural gas, which is lighter than air, tends to collect in high areas; LP gas is heavier than air and tends to settle in low areas – install leak detectors accord­ingly.
1.9.1 CONVERSION TO LP GAS VAPOR
The generator is shipped from the factory configured for using natural gas as fuel. To convert the fuel system to LP gas, proceed as follows (Figure 1.3).
1. Remove end cap from the pressure reducer valve.
2. Turn the tension screw counterclockwise until all ten-
sion is removed from the inner spring.
3. Install and tighten the end cap.
4. Invert the pressure reducer valve. In other words, turn
it upside down (end cap facing downward).
5. Purge and leak test the entire fuel system according to
gaseous fuel codes. NO LEAKS can appear at any point in the system.
Figure 1.3 – Conversion to LP Gas Vapor
Section 1 General Information
Guardian Liquid-cooled 40 kW Generator
Page 9
1.10 ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the factory. Use a high-quality detergent oil classified “For Service CC, SD, SE or SF.” Detergent oils keep the engine cleaner and reduce carbon deposits. Use oil hav­ing the following SAE viscosity rating, based on the ambient temperature range anticipated before the next oil change:
Any attempt to crank or start the engine before it has been properly serviced with the recommended oil may result in an engine failure.
1.11 COOLANT
Use a mixture of half low silicate, ethylene glycol base antifreeze and half soft water. Use only soft water and only low silicate antifreeze. If desired, add a high qual­ity rust inhibitor to the recommended coolant mixture. When adding coolant, always add the recommended 50­50 mixture.
Do not remove the radiator pressure cap while the engine is hot or serious burns from boiling liquid or steam could result.
Ethylene glycol base antifreeze is poisonous. Do not use mouth to siphon coolant from the radiator, recov­ery bottle or any container. Wash hands thoroughly after handling. Never store used antifreeze in an open container because animals are atracted to the smell and taste of antifreeze even though it is poison­ous to them.
Do not use any chromate base rust inhibitor with eth­ylene glycol base antifreeze, or chromium hydroxide (“green slime”) will form and cause overheating. Engines that have been operated with a chromate base rust inhibitor must be chemically cleaned before adding ethylene glycol base antifreeze. Using any high silicate antifreeze boosters or additives also will cause overheating. Generac also recommends that any soluble oil inhibitor NOT be used for this equipment.
1.12 EMISSIONS CONTROL SYSTEM
(Model 004626-1)
This model is equipped with an active exhaust emis­sions control system to comply with certain California air district regulations for natural gas emergency gener­ating sets, including the South Coast Air Quality Management District. Do not tamper with or disable any part of this system, including the exhaust catalyst,
carburetor, oxygen sensor, air-fuel ratio controller, sole­noid valve and gas regulator. These items are not sub­ject to periodic maintenance or adjustment.
This model is of a size (greater than 50 brakehorse­power) that may require a review by air permitting authorities prior to installation and operation. Consult the local air management district for details and specif­ic requirements.
Figure 1.4 - Emissions Control System
1.12.1 AIR FUEL RATIO CONTROLLER
The air fuel ratio controller is an advanced micro­processor designed to work with a three-way catalyst and a feedback (rich bias) carburetor to provide close­loop fuel management. Its digital adaptive control is able to compensate for variations in fuel mixtures and engine tunes. It is time based activated. (For example, it will activate after 45 seconds from receiving the power signal.) The part number for the air fuel ratio controller is 0D4221.
P
rinciple of Operation:
The oxygen sensor, installed on the exhaust pipe, between the engine and the catalytic muffler (closer to the engine), continuously monitors the exhaust gas composition. A feedback signal is sent from the oxygen sensor to the air fuel ratio controller, which controls the fuel system to maintain the optimal, stoichiometric air fuel ratio. The air fuel mixture to the engine is controlled by biasing the diaphragm in the fuel regulator using vacuum (from the carburetor). This vacuum signal is directed to the fuel regulator via the control valve. The air fuel ratio controller determines the amount of vacuum signal sent to the fuel regulator. The more vacuum sent to the regulator, the more restricted the fuel flow will be, therefore the leaner the air fuel mixture.
Section 1 General Information
Guardian Liquid-cooled 40 kW Generator
Generac®Power Systems, Inc. 7
Temperature Oil Grade(Recommended)
Above 80º F (27º C) SAE 30W or 15W-40
32º to 80º F (-1º C to 27º C) SAE 20W-20 or 15W-40
Below 32º F (0º C) SAE 10W or 15W-40
!
Page 10
8 Generac®Power Systems, Inc.
If an open bottom is used, the engine-generator is to be installed over non-combustible materials and should be located such that combustible materials are not capable of accumulating under the generator set.
Only qualified, competent installation contractors or electricians thoroughly familiar with applicable codes, standards and regulations should install this standby electric power system. The installation must comply strictly with all codes, standards and regulations per­taining to the installation.
After the system has been installed, you must not do anything that might render the installation in noncom­pliance with such codes, standards and regulations.
NOTE:
For more information about the installation of a stand­by system, you can order Engine-Generator Standby
Electric Power Systems Installer’s Guide and Reference Manual (part #046622) from a Generac
Authorized Service Dealer.
NFPA STANDARDS
The following published standards booklets pertaining to standby electric systems are available form the National Fire Protection Association (NFPA), Batterymarch Park, Quincy, MA 02269:
• NFPA No. 37, STATIONARY COMBUSTION ENGINES AND GAS TURBINES.
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS FOR HEALTH CARE FACILITIES.
• NFPA No. 220, STANDARD TYPES OF BUILDING CONSTRUCTION
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
• NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND USE OF PORTABLE FIRE EXTINGUISHERS.
OTHER PUBLISHED STANDARDS
In addition to NFPA standards, the following informa­tion pertaining to the installation and use of standby electric systems is available:
• Article X, NATIONAL BUILDING CODE, available from the American Insurance Association, 85 John Street, New York, N.Y. 10038.
• AGRICULTURAL WIRING HANDBOOK, obtainable from the Food and Energy Council, 909 University Avenue, Columbia, MO, 65201.
• ASAE EP-364.2, INSTALLATION AND MAINTE­NANCE OF FARM STANDBY ELECTRIC POWER, available from the American Society of Agricultural Engineers, 2950 Niles Road, St. Joseph, MI 49085.
• A52.1, AMERICAN NATIONAL STANDARD FOR CHIMNEYS, FIREPLACES AND VENTING SYS­TEMS, available from the American National Standard Institute, 1430 Broadway, New York, N.Y.
10018.
• NEC HANDBOOK available from the National Fire Protection Association, 1 Batterymarch Park, PO Box 9146, Quincy, MA 02269-9959.
2.1 BASIC STANDBY ELECTRIC SYSTEM
Figure 2.1 shows a schematic diagram of a basic stand­by electric system. Both the UTILITY power supply and the STANDBY (generator) output are connected to an approved transfer switch. The transfer switch is required by electrical code and serves the following functions:
• Permits the LOAD circuits to be connected to only one power supply at a time.
• Prevents electrical backfeed between STANDBY power and the UTILITY power circuits.
Notice that both the STANDBY and the UTILITY power supplies to the transfer switch are protected against overload by a main line circuit breaker.
NOTE:
Generac recommends the use of a Generac Power Systems “pre-packaged” type transfer switch (Part No. 0D4406) in conjunction with this generator.
Section 2 Installation
Guardian Liquid-cooled 40 kW Generator
STANDBY GENERATOR INSTALLATION
Connecting this generator to an electrical system normally supplied by an electric utility shall be by means of a transfer switch (such as the Generac “GTS” type transfer switch), so as to isolate the electric system from the utility distribution system when the generator is operating. Failure to isolate the electric system by these means will result in damage to the generator and may also result in injury or death to utility workers due to backfeed of electrical energy.
DANGER
Page 11
Generac®Power Systems, Inc. 9
Figure 2.1 – Basic Standby Electric System
2.2 EMERGENCY CIRCUIT ISOLATION METHOD
This prevents overloading the generator by keeping elec­trical loads below the wattage/amperage capacity of the generator. If the generator is powering only critical loads, within its wattage/amperage capacity, during util­ity power outages, consider using the emergency circuit isolation method.
Critical electrical loads are grouped together and wired into a separate “Emergency Distribution Panel.” Load circuits powered by that panel are within the wattage/amperage capacity of the generator set. When this method is used, it is difficult to overload the gener­ator. The transfer switch must meet the following requirements:
• It must have an ampere rating equal to or greater
than the total amperage rating of the emergency dis­tribution panel circuit.
• It must be installed between the building’s main distri-
bution panel and the emergency distribution panel.
2.3 TOTAL CIRCUIT ISOLATION METHOD
When a generator capable of powering all electrical loads in the circuit is to be installed, use the “Total Circuit Isolation Method.” It is possible for the genera­tor to be overloaded when this isolation method is employed. The following apply to the transfer switch in this type of system.
• Ampere rating of the transfer switch must be equal to
or greater than the ampere rating of the normal incoming utility service.
• The transfer switch must be installed between the
utility service entrance and the building distribution panel.
2.4 GROUNDING THE GENERATOR
The National Electrical Code requires the frame and external electrically conductive parts of this equipment to be properly connected to an approved earth ground and/or grounding rods. For that purpose, a GROUND LUG (Figure 2.2) is provided on the generator mounting base. Consult a qualified electrician for grounding requirements in your area. Grounding procedures must meet local regulations.
Do not connect the ground wire to any pipe that carries a flammable or explosive substance – FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against electri­cal shock in the event of a ground fault condition in the generator or in connected electrical devices. In addition, grounding helps dissipate static electricity that often builds up in ungrounded devices.
Figure 2.2 – Generator Grounding Lug (typical)
2.5 GENERATOR AC NEUTRAL CONNECTIONS
Generac uses an UNGROUNDED AC neutral. Grounding is recommended only at the main service entrance.
2.6 TRANSFER SWITCH START SIGNAL CONNECTIONS
2.6.1 Pre-Packaged Type Switch
Connect the six signal wires from the automatic trans­fer switch to the engine generator control, which is located on the upper right side and inside the lower control panel. Match wires 23, 194, N1, N2, T1 and T2 in the transfer switch to the corresponding wires on the terminal strip in the lower panel. The conductors for these wires must be in seperate conduit from the main AC output wires.
2.6.2 GTS Type Engineered Switch
Connect the two-wire start signal from the automatic transfer switch to the automatic start connection, which is located in the right hand corner inside the lower panel. Match wires 178 and 183 in the transfer switch to 178 and 183 on the terminal strip in the control panel. The conductors for the two-wire start circuit must be in their own conduit.
NOTE:
When using a GTS switch, it is necessary to con­nect a 240V AC supply to N1 and N2 terminals of the generator to provide for battery charging. Wires T1, T2, 23 and 194 should not be connected.
Section 2 Installation
Guardian Liquid-cooled 40 kW Generator
DANGER
Page 12
10 Generac®Power Systems, Inc.
2.7 BATTERY INSTALLATION
Standby generators installed with automatic trans­fer switches will crank and start automatically when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per­sonnel, do not connect battery cables until the normal source voltage at the transfer switch is cor­rect and the system is ready to be placed into operation.
Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat­tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.
Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.
Do not dispose of the battery in a fire. The battery is capable of exploding.
Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.
The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.
2.7.1 VENTED BATTERIES
The electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is electrically con­ductive and corrosive. The following procedures are to be observed:
• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off immediately with water,
• Where electrolyte contacts the eyes, flush thoroughly and immediately with water and seek medical atten­tion, and
• Spilled electrolyte is to be washed down with an acid­neutralizing agent. A common practice is to use a solution of one pound (500 grams) bicarbonate of soda to one gallon (4 liters) of water. The bicarbonate of soda solution is to be added until the evidence of reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the area dried.
Lead acid batteries present a risk of fire because they generate hydrogen gas. The following proce­dures are to be followed:
• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touching batteries by first touching a grounded metal surface.
Servicing of batteries is to be performed or supervised by personnel knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from batteries.
For recommended batteries, see “Battery Maintenance” page 16. All batteries must be at 100 percent state-of­charge before they are installed on the generator.
When using maintenance-free batteries, it is not neces­sary to check the specific gravity or electrolyte level. Have these procedures performed at the intervals spec­ified in Section 4, “Maintenance.” A negative ground sys­tem is used. Battery connections are shown on the wiring diagrams. Make sure all batteries are correctly connected and terminals are tight. Observe battery polarity when connecting batteries to the generator set.
Note:
Damage will result if the battery connections are reversed.
2.8 PREPARATION BEFORE START-UP
The instructions in this section assume that the standby generator has been properly installed, serviced, tested, adjusted and otherwise prepared for use by a competent, qualified installation contractor. Be sure to read the “Safety Rules” on Pages 2 and 3, as well as all other safe­ty information in this manual, before attempting to oper­ate this (and related) equipment.
Section 2 Installation
Guardian Liquid-cooled 40 kW Generator
DANGER
!
!
!
!
Page 13
2.8.1 PRIOR TO INITIAL START-UP
Prior to initially starting the generator, it must be properly prepared for use. Any attempt to crank or start the engine before it has been properly serviced with the recommended types and quanti­ties of engine fluids (oil, coolant, fuel, etc.) may result in an engine failure.
Before starting the generator for the first time, the installer must complete the following procedures. For follow-up maintenance information and/or service inter­vals, please refer to Section 4, “Maintenance.”
2.8.2 Transfer Switch
If this generator is used to supply power to any electri­cal system normally powered by an electric utility, the National Electrical Code requires that a transfer switch be installed. The transfer switch prevents electrical backfeed between two different electrical systems. (For additional information, see the applicable transfer switch manual for this unit.) The transfer switch, as well as the generator and other standby components, must be properly located and mounted in strict compli­ance with applicable codes, standards and regulations.
2.8.3 Fuel System
Make sure the fuel supply system to the generator (a) delivers the correct fuel at the correct pressure and (b) is properly purged and leak tested according to code. No fuel leakage is permitted. See “Specifications” (Page 6) for more information.
2.8.4 Generator Set Lubrication
Check the engine crankcase oil level before operating and add oil to the proper level – the dipstick “FULL” mark. Never operate the engine with the oil level below the dipstick “ADD” mark. See “Specifications” (Page 5) and “Engine Oil Recommendations” (Page 7).
NOTE:
This engine is shipped from the manufacturer with SAE 15W-40 oil. This oil should be changed after 30 hours of operation.
2.8.5 Engine Coolant
Have the engine cooling system properly filled with the recommended coolant mixture. Check the system for leaks and other problems. See “Specifications” (Page 5) and “Coolant” (Page 7).
2.8.6 Belt Tension
Check the engine fan belt tension and condition prior to placing the unit into service and at recommended intervals. Belt tension is correct when a force of approx­imately 22 pounds (10 kg), applied midway between pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16 mm).
2.8.7 Electrical System
Make sure the generator is properly connected to an approved earth ground and/or ground rod.
Make sure the generator battery is fully charged, proper­ly installed and interconnected, and ready for use.
Check to ensure that there are no loose electrical con­nections. Restrain any loose wires to keep them clear of any moving generator set components.
2.8.8 Rodent Protection
Make sure the four 3-inch diameter cap plugs (part # 0A8785) are properly installed in the tie-down holes in the side rails of the unit’s base frame (Figure 2.3). The cap plugs are shipped in a plastic bag located in the lower connection box. These plugs are needed to pre­vent rodents from accessing the interior of the genera­tor set. On acoustic units, cap plugs also are needed to stay within noise specification limits.
Figure 2.3 - Base Frame Cap Plugs
Section 2 Installation
Guardian Liquid-cooled 40 kW Generator
Generac®Power Systems, Inc. 11
!
Page 14
12 Generac®Power Systems, Inc.
3.1 CONTROL CONSOLE COMPONENTS
The components of a liquid-cooled generator control console (Figure 3.1) are as follows:
Figure 3.1 – Control Console
3.1.1 AC VOLTMETER
The voltmeter displays generator AC output voltage dur­ing operation. Voltage is regulated by a solid-state volt­age regulator and is proportional to AC frequency. Refer to the unit’s DATA PLATE for rated AC voltage.
3.1.2 AC AMMETER
This indicates current draw of connected electrical loads during operation. DO NOT EXCEED THE UNIT’S RATED MAXIMUM CONTINUOUS CURRENT. Refer to the unit DATA PLATE.
3.1.3 AC FREQUENCY METER
This indicates generator AC output frequency in Hertz (cycles per second). Frequency is proportional to engine speed. Units with a four-pole rotor, supply 60 Hertz at 1,800 rpm. The frequency reading with no electrical loads connected (no-load condition) should be between 60-62 Hertz.
3.1.4 DC VOLTMETER
The generator is equipped with a belt-driven DC alter­nator, which maintains battery state of charge when the engine operates. The control module assembly (CMA) also incorporates a trickle charge circuit that maintains battery state of charge during nonoperating periods. Battery voltage should read approximately12.5 to 14.5 volts DC. A low battery voltage indicates the battery is discharging.
3.1.5 HOURMETER
This indicates the time the engine-generator has operat­ed, in hours and tenths of hours. Use the hourmeter along with the periodic maintenance schedule for your generator set.
3.1.6 AUTO/OFF/MANUAL SWITCH
See Section 3.2.
3.1.7 FAULT INDICATOR LAMP
This lamp goes ON when one or more of the following engine faults occurs and when engine shuts down.
• Low oil pressure • High coolant temperature
• Low coolant level • Overcrank
• Overspeed
3.1.8 15-AMP FUSE
This fuse protects the control console’s DC control cir­cuit against electrical overload. If the fuse has melted open because of an overload, engine cranking and start­up cannot occur. Replace the fuse with an identical AGC 15-amp replacement fuse.
3.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)
This inline fuse is connected in the 15A line that runs between the Auto/Off/Manual switch and position 10 of the 76009A PCB. This fuse protects the start, fuel, field boost, and transfer outputs from the PCB and will open if there is excessive current draw on any one of these outputs.
3.1.10 VOLTAGE-PHASE SELECTOR SWITCH
This switch permits selection between either line-to-line or line-to-neutral voltage and amperage readings on the console AC voltmeter and AC ammeter.
3.1.11 SET EXERCISE TIME SWITCH
This switch allows to program the generator to start and exercise automatically. (See Section 3.6, page 14)
3.2 USING THE AUTO/OFF/MANUAL
SWITCH
3.2.1 “AUTO POSITION
Selecting this switch position activates fully automatic system operation. It also allows the unit to start and exercise the engine every seven days with the setting of the exercise timer.
Section 3 Operation
Guardian Liquid-cooled 40 kW Generator
15
Page 15
3.2.2 OFF POSITION
This switch position shuts down the engine. This posi­tion also prevents operation.
3.2.3 MANUAL” POSITION
Set the switch to Manual to crank and start the engine. Transfer to standby power will not automatically occur unless there is a utility failure.
With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting normally occurs when utility power source voltage drops below a preset level or during the normal exercise cycle. To pre­vent possible injury that might be caused by such sudden starts, always set the switch to OFF and remove the fuse before working on or around the generator or transfer switch. Then, place a “Do Not Operate” tag on the generator panel and on the transfer switch.
3.3 AUTOMATIC TRANSFER OPERATION
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set to their “Utility” position, i.e., loads connected to the utility power source.
2. Be sure that normal utility power source voltage is available to transfer switch terminal lugs N1 and N2.
3. Set the generator’s Auto/Off/Manual switch to AUTO.
4. Set the generator’s main circuit breaker to its ON (or closed) position.
With the preceding steps complete, the generator will start automatically when utility source voltage drops below a preset level. After the unit starts, loads are transferred to the standby power source. Refer to “Sequence of Automatic Operation.”
3.4 SEQUENCE OF AUTOMATIC OPERATION
The generator’s control panel houses a control logic cir­cuit board. This board constantly monitors utility power source voltage. Should that voltage drop below a preset level, circuit board action will signal the engine to crank and start. After the engine starts, the circuit board signals the transfer switch to activate and connect load circuits to the standby power supply (load terminal lugs T1/T2 connect to terminal lugs E1/E2).
Upon restoration of utility source voltage above a preset level, generator circuit board action signals the transfer switch to transfer loads back to that power supply. After retransfer, the engine is signalled to shut down.
The actual sequence of operation is controlled by sensors and timers on a control logic circuit board, as follows:
A. Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 60 per­cent of the nominal supply voltage, the sensor ener­gizes a 15-second timer.
• Once the timer has expired, the engine will crank and start.
B.Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about 10 seconds before the load is transferred to a stand­by source.
C.Standby Voltage Sensor
• This sensor monitors generator AC output voltage. When the voltage has reached 50 percent of the nominal rated voltage, transfer to standby can occur.
D.Utility Voltage Pickup Sensor
• This sensor monitors utility power supply voltage. When that voltage is restored above 80 percent of the nominal source voltage, a retransfer time delay starts timing.
E.Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de­energizes transfer relay in the transfer switch.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the generator will then shut down.
3.5 ENGINE HEATER
This Generac standby generator comes equipped with a block heater (Figure 3.2, page 14) that is similar to the block heaters used in automotive applications. The block heater must be connected to a customer supplied 120V AC circuit.
!
Generac®Power Systems, Inc. 13
Section 3 Operation
Guardian Liquid-cooled 40 kW Generator
Page 16
Figure 3.2 – Engine Block Heater
Refer to applicable wiring diagram(s) and electrical schematic(s) at the back of this manual for wiring con­nections.
3.6 WEEKLY EXERCISE CYCLE
The generator will start and exercise once every seven days. During this weekly exercise, the unit runs for approximately 20 minutes and shuts down. Transfer of loads to generator output does not occur during the exercise unless power is lost during the exercise period.
To select the day of the week and time of day for exer­cising, proceed as follows:
• Set the Auto/Off/Manual switch to OFF.
• Set generator’s main circuit breaker to its OFF (or open) position.
• Locate the rocker switch on the control panel identi­fied with the words “Set Exercise Time” (Figure 3.3).
• Push “Set Exercise Time” switch to the ON position for 20 to 30 seconds and then release. The switch will spring back into its original position when released.
• Wait 30 seconds before setting the Auto/Off/ Manual switch to the AUTO position.
NOTE:
The unit will exercise 20 minutes before it is set. Example: Set – Noon; Exercise – 11:40 a.m.
If you switch the Auto/Off/Manual switch is switched too soon, the engine may start. If engine does start, it will shut down automatically in about two (2) minutes.
• Set the generator’s main circuit breaker to its ON (or closed) position.
• The generator is now programmed to start and exer­cise every seven days thereafter, on the day and at the time of day the switch was activated.
• Place a sign on the generator’s control panel and on
the transfer switch that indicates the day and time the generator will be exercising.
NOTE:
If the battery terminals are disconnected or the control panel fuse is removed, the exercise timer needs to be reset for automatic exercise operation.
Figure 3.3 – “Set Exercise” Switch on Control Panel
4.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities, see “Specifications,” Section 1.7.2, Page 6. For engine oil recommendations, see Section
4.2.1. To check the engine oil level, proceed as follows (Figure 4.1):
1. Remove the dipstick and wipe it dry with a clean cloth.
2. Install the dipstick cap; then, remove it again. The oil level should be at the dipstick “Full” mark. If nec­essary, add oil to the “Full” mark only. DO NOT FILL ABOVE THE “FULL” MARK.
3. Install the dipstick.
Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
!
T
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
14 Generac®Power Systems, Inc.
OUTLET
INLE
!
Page 17
Figure 4.1 – Oil Dipstick and Fill
4.2 CHANGING THE ENGINE OIL AND FILTER
4.2.1 Engine Oil Recommendations
Use oil of API Service Class SG, SH or SJ. The recommended oil grade for the engine is SAE 15W-40.
NOTE:
The unit is supplied with “break-in” oil. See the “Service Schedule,” Section 4.12 (Page 19), for the first required oil change.
Any attempt to crank or start the engine before it has been properly serviced with the recom­mended oil may result in an engine failure.
4.2.2 Oil and Filter Change Procedure
To change the oil and filter, proceed as follows:
Refer to the “Service Schedule,” (Section 4.12, Page 19) for engine oil and filter change frequencies.
Drain the oil while the engine is still warm from run­ning. This means, warm up the engine, shut it down and drain it immediately as follows:
1. Remove the oil drain hose from its retaining clip, located on the generator base frame.
2. Loosen and remove the oil drain hose cap, located on the base frame end of the hose. Drain the oil completely into a suitable container.
3. When all of the oil has drained, install and tighten the oil drain hose cap.
4. Turn the oil filter (Generac part number 0A37970001, Figure 4.2) counterclockwise and remove it. Properly dispose of the old filter.
Figure 4.2 – Oil Filter
5. Apply a light coating of engine oil to the seal of new oil filter. Install the filter and tighten by hand only. DO NOT OVERTIGHTEN.
6. Remove the oil fill cap (Figure 4.1). Add the recom­mended oil (see Section 4.2.1). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is 4.5 U.S. quarts (4.25 L).
After refilling the crankcase with oil, always check the oil level on the dipstick. Never operate the engine with the oil level below the “Add” mark on the dipstick. Doing this could damage the engine.
7. Start the engine and check for oil leaks.
8. Check the oil level after checking for leaks to ensure that the oil is filled to the proper level.
4.3 CHANGING THE ENGINE AIR CLEANER
To replace the engine air cleaner, (Generac part num­ber 0A4637, simply remove the air cleaner cover and replace the air filter making sure it is positioned properly before reattaching the cover. (See Figure
4.3, page 16)
!
!
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
Generac®Power Systems, Inc. 15
OIL FILL CAP
OIL DIPSTICK
OIL FILTER
OIL DRAIN HOSE
TO BASE
Page 18
16 Generac®Power Systems, Inc.
Figure 4.3 – Engine Air Cleaner
See the “Service Schedule,” Section 4.12, Page 19, for rec­ommended air cleaner maintenance.
4.4 SPARK PLUGS
Reset the spark plug gap or replace the spark plugs as necessary. See Section 4.12, Page 19.
1. Clean the area around the base of the spark plugs to keep dirt and debris out of the engine. Clean the plugs by scraping using a wire brush. Do not “blast” the spark plugs to clean.
2. Remove the spark plugs and check the condition. Replace the spark plugs if worn or if reuse is ques­tionable. See the “Service Schedule,” Section 4.12, Page 19, for recommended inspection.
3. Check the spark plug gap using a feeler gauge. Adjust the gap to 0.045 inch (1.1 mm) by carefully bending the ground electrode (Figure 4.4).
Figure 4.4 – Setting the Spark Plug Gap
4.5 BATTERY MAINTENANCE
The battery should be inspected per the “Service Schedule,” Section 4.12, Page 19. The following proce­dure should be followed for inspection:
1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTERIES.
3. Have the state of charge and condition checked. This should be done with an automotive-type bat­tery hydrometer or load test.
Standby generators installed with automatic transfer switches will crank and start automatical­ly when normal (utility) source voltage is removed or is below an acceptable preset level. To prevent such automatic start-up and possible injury to per­sonnel, do not connect battery cables until the normal source voltage at the transfer switch is correct and the system is ready to be placed into operation.
Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charging. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shatter the bat­tery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smoking, open flame, sparks or any spark producing tools or equipment near the battery.
Battery electrolyte fluid is an extremely caustic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If fluid is spilled, flush the affected area immediately with clear water.
Do not dispose of the battery in a fire. The bat­tery is capable of exploding.
Do not open or mutilate the battery. Released electrolyte can be toxic and harmful to the skin and eyes.
The battery represents a risk of high short circuit current. When working on the battery, always remove watches, rings or other metal objects, and only use tools that have insulated handles.
Battery replacement
Generac uses a Group 27F vented type battery that has 600 CCA @ 0º F. Generac’s part number is 058665.
Note:
The BCI number should be located directly on the battery.
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
Air Cleaner
DANGER
!
!
!
Page 19
Generac®Power Systems, Inc. 17
4.6 COOLING SYSTEM
Air intake and outlet openings in the generator compart­ment must be open and unobstructed for continued prop­er operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.
Without sufficient cooling and ventilating air flow, the engine/generator quickly overheats, which causes it to shut down.
The exhaust system of this product gets extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.
4.7 OVERLOAD PROTECTION FOR ENGINE DC ELECTRICAL SYSTEM
Engine cranking, start-up and running are controlled by a solid-state engine controller circuit board. Battery voltage is delivered to that circuit board via a 15-amp fuse. These overcurrent protection devices will open if the circuit is overloaded.
If a circuit breaker opens or a fuse element melts, you should find the cause of the overload before resetting the circuit breaker or replacing the fuse.
4.8 DC FUSE
The generator panel’s 15-amp AGC fuse (Figure 4.4) pro­tects the DC control circuit against overload. The fuse is wired in series with the battery output lead to the panel. If the fuse element has melted open, cranking or starting the engine cannot occur. Replace the fuse using only an identical 15-amp AGC replacement.
Figure 4.4 – Location of 15-amp Fuse
4.9 ENGINE COOLANT
Check the coolant level in the coolant recovery bottle.
• Add the recommended coolant mixture as necessary. See Section 1.10 on Page 7.
• Periodically remove the radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at the bottom of the radia­tor filler neck. If the coolant level is low, inspect the gasket in the radiator pressure cap. Replace the cap, if necessary. To have the pressure cap tested, contact a Generac/Guardian Authorized Dealer. Inspect the cool­ing system and coolant recovery system for leaks.
4.10 MISCELLANEOUS MAINTENANCE
4.10.1 Cleaning the Generator
Keep the generator as clean and as dry as possible. Dirt and moisture that accumulate on internal generator windings have an adverse effect on insulation resist­ance.
Periodically, clean the generator’s exterior surfaces. A soft brush may be used to loosen caked on dirt. Use a vacuum system or dry, low pressure air to remove any accumulations of dirt. The generator is housed inside an all-weather enclosure; clean the enclosure with a soft, damp cloth or sponge and water.
Once each year, have the generator cleaned and inspect­ed by a Generac/Guardian Authorized Dealer. Service technicians will use dry, low pressure air to clean inter­nal windings. Parts inside the control console should be cleaned and inspected at this time as well.
Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessive­ly low, the generator may require drying.
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
15
Page 20
18 Generac®Power Systems, Inc.
4.10.2 Rodent Protection
The intrusion of rodents into the generator set can cause a wide range of problems, from failure of the unit to start, to personal injury and, in extreme circum­stances, short circuit or fire. Although the unit was designed to limit this problem, further precautions can be taken by the owner to help minimize both the chance of rodent entry and the extent of any damage. The fol­lowing inspection should be performed.
1. The base frame of the unit contains an optional fuel inlet location and four lifting holes that are capped at the factory. These caps are sometimes removed for transportation during installation but always should be replaced afterwards. Check that they are secured in place. The same applies for any access ports in the roof of the enclosure. If any of these caps are missing, contact a Generac/Guardian Authorized Dealer.
2. Inside the generator set, the chance of rodent entry into the control panel is greatly reduced by the inclu­sion of adjustable wire connectors. Check that the wire connector screws are tight, thus closing off any gap between the access holes and the wires.
4.11 OUT OF SERVICE PROCEDURE
4.11.1 Removal From Service
If the generator cannot exercise every seven days, and it is to be out of service longer than 90 days, prepare the generator for storage as follows:
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line and allow the unit to shut down.
3. Once the unit has shut down, it will signal a fault on the control panel.
4. Set the Auto/Off/Manual switch to OFF and turn off the utility power to the transfer switch.
5. While the engine is still warm from running, drain the oil completely. Refill the crankcase with SAE 15W-40 oil having API Service Class SG, SH or SJ.
6. Attach a tag to the engine indicating the viscosity and classification of the oil in the crankcase.
7. Remove the spark plug(s) and spray fogging agent into the spark plug(s) threaded openings. Reinstall and tighten the spark plug(s).
8. Remove the battery and store it in a cool, dry room on a wooden board. Never store the battery on any concrete or earthen floor.
9. Clean and wipe the entire generator.
4.11.2 Return To Service
To return the unit to service after storage, proceed as follows:
1. Verify that utility power is turned off to the transfer switch and that the Auto/Off/Manual switch is set to OFF.
2. Check the tag on the engine for oil viscosity and classification. Verify that the correct recommended oil is used in engine. See Section 4.2.1 (Page 14). If necessary, drain and refill with the proper oil.
3. Check the battery. Fill all cells to the proper level with distilled water. DO NOT USE TAP WATER IN THE BATTERY. Remove the battery before charging. Recharge the battery to 100 percent state of charge, or, if defective, replace the battery with a 12-volt DC Group 27F battery rated for 90 amp hours (part #
058665).
4. Clean and wipe the entire generator.
5. Reconnect the battery. Observe battery polarity. Damage may occur if the battery is connected incor­rectly.
6. Open the fuel shutoff valve.
7. Start the unit by moving the Auto/Off/Manual switch to MANUAL. Allow the unit to warm up thoroughly.
8. Stop the unit and set the Auto/Off/Manual switch to AUTO.
9. Turn on the utility power to the transfer switch.
10. The generator is now ready for service.
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
Page 21
Generac®Power Systems, Inc. 19
Section 4 Maintenance
Guardian Liquid-cooled 40 kW Generator
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by your nearest Generac/Guardian Authorized Dealer.
SYSTEM/COMPONENT PROCEDURE FREQUENCY
X = Action Inspect Change Clean W = Weekly R = Replace/Adjust as Needed M = Monthly * = Notify Dealer Y = Yearly
if Repair is Needed. H = Hours
FUEL
Fuel lines and connections* X EVERY 3 M
LUBRICATION
Oil level X M Oil X FIRST 9 H,
EVERY 150 H / 6 M
Oil filter X FIRST 9 H,
EVERY 150 H / 6 M
Oil line leakage* X 100 H
COOLING
Engine cooling system* X M Coolant X Y Enclosure louvers X X W
EXHAUST
Exhaust system X EVERY 3 M Retorque Exhaust Manifold* X FIRST 100 H AND
EVERY 800 H
BATTERY
Charge and condition X R X EVERY 3 M
FAN BELT
Tension and condition* X R EVERY 3 M
ENGINE
Retorque cylinder head* X FIRST 100 H AND
EVERY 800 H
Retorque intake manifold* X FIRST 100 H AND
EVERY 800 H Starter motor* X R EVERY 500 H DC alternator* X R EVERY 500 H AND Y Air cleaner* X R EVERY 500 H Compression* X EVERY 800 H Valve clearance* X R EVERY 800 H Governor* X R Y Safety devices* X R EVERY 6 M Spark plugs X R 500 H AND Y Ignition system* X R EVERY 3 M
GENERAL
Overall condition X X M Exercise system W
COMPLETE TUNE-UP* TO BE COMPLETED BY A GENERAC/ Y
GUARDIAN AUTHORIZED DEALER
Page 22
20 Generac®Power Systems, Inc.
Section 5 Troubleshooting
Guardian Liquid-cooled 40 kW Generator
5.1 TROUBLESHOOTING GUIDE
PROBLEM CAUSE CORRECTION
The engine will not crank. 1. Fuse blown 1. Replace fuse.
2. Loose, corroded or defective 2. Tighten, clean or replace battery cables as necessary.
3. Defective starter contactor 3. *
4. Defective starter motor 4. *
5. Dead Battery 5. Charge or replace battery.
The engine cranks but 1. Out of fuel 1. Replenish fuel. will not start. 2. Defective fuel solenoid (FS) 2. *
3. Open #14 wire from 3. * engine control board
4. Defective spark plug(s) 4. Clean, re-gap or replace plug(s).
5. Dirty/Blocked air filter 5. Clean or replace as required.
The engine starts hard 1. Air cleaner 1. Check, clean or replace air cleaner. and runs rough. plugged or damaged
2. Defective spark plug(s) 2. Clean, re-gap or replace plug(s).
3. Dirty/Blocked air filter 3. Clean or replace as required.
The engine starts, but then 1. Engine oil level low 1. Check oil and add oil as needed. shuts down. 2. Defective low oil 2. *
pressure switch
3. Defective high temperature 3. * switch
4. Defective control board 4. *
5. Low coolant level 5. Check coolant level, repair leaks
and refill.
The Auto/Off/Manual switch 1. Defective switch 1. * is set to OFF, but the engine 2. Defective control board 2. *
continues to run.
There is no AC output from 1. Generator main line circuit 1. Reset circuit breaker the generator. breaker open to ON (or closed).
2. Generator internal failure 2. *
There is no transfer to 1. Generator main line circuit 1. Reset circuit breaker standby after utility breaker open to ON (or closed).
source failure. 2. Defective transfer switch coil 2. *
3. Defective transfer relay 3. *
4. Transfer relay circuit open 4. *
5. Defective control logic board 5. *
*Contact your nearest Generac/Guardian Authorized Dealer for assistance.
Page 23
Generac®Power Systems, Inc. 21
Section 6 Electrical Data
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generator
Electrical Schematic (Control Panel) – Drawing No. 0D4993-B
A
CAP
LEGEND
CAP - CAPACITOR
CB1 - CIRCUIT BREAKER - EXCITATION
D1 - DIODE- 600V, 12A
F1 - FUSE 15 AMPS
BVM - METER, BATTERY VOLTAGE
AM - METER, AC OUTPUT CURRENT
INSULATE UNUSED WIRE END
USE YELLOW WIRE FOR 208V, 3 PHASE
14
USE BLUE WIRE FOR 240V, 1 PHASE
AVR - AUTOMATIC VOLTAGE REGULATOR
F2 - FUSE 7.5 AMPS IN-LINE
178
F1
BLUE
176
176
E
194
194
4
PCB
183
14
0
YELLOW
23
BLUE
RED
T2
TR1
T2
BLACK
T1
TS2
BLACK
23
N2
N1
T1
RED
BLACK
ORANGE
225A
BLUE
RED
BLUE
BLACK
GCU
YELLOW
BROWN
BLACK
ACTUATOR
TO GOVERNOR
23
CONNECTOR
1 2 3 OFF
CONTACTS
2
CONTROLLER
O
X
OOO
OXX
O
O
X
X
O
X
X
O
X
O
X
O
X
O
O
O
X
X
OOX
O
XO
O
O
O
O
2 - 3
X
X
X
X
12 - 3
12 - 7
-
12 - 11
15 - 14
X INDICATES CLOSED
15 - 18
19 - 16
19 - 14
+
AM
1211
67
2 - 7
2 - 11
0
BLUE
BLUE
T2 RED
S16 S15 T1
0
HZ
S15
65
PSW
PHASE SELECTOR SWITCH
POSITION
VM
64
19
15
3
15
14
16
17
A
B
13
0
0
BVM
-
HM
+
+
15C
15
-
OFF POSITION
15A
N.C.
SW2
15C
14
14
SHOWN IN
15C
15A
15
225A
13
176
L1
15
15
15C
15A
F2
0
183
14
13
SW1
239
15A
178
14
15C
10
12
9
178
11
239
D
229
7
5
560
2
85
13
1
4
PSW - SWITCH, PHASE SELECTOR
TR1 - TRANSFORMER, UTILITY SENSING 24VA
SW2 - SWITCH, SET EXERCISE
SW1 - SWITCH, AUTO/OFF/MANUAL
R1 - RESISTOR, FIELD BOOST
TS1,TS2 - TERMINAL STRIP
PCB - CIRCUIT BOARD CONTROLLER
L1 - LIGHT, FAULT INDICATOR
HZ - METER, FREQUENCY
HM - HOURMETER
GCU - GOVERNOR CONTROLLER UNIT
VM - METER, AC OUTPUT VOLTAGE
178
183
194
T1
N1
T2
23
N2
0
183
194
0
229
13
14
4
56
85
0
AVR
3
2
5
6
1
4
4
6
S15
S16
162
1
S15
S16
S16
14
18
16
7
3
TS1
S3
00
S15
H
S16
G
S1
Q
K
4
15 15 15
229
13
14
14
56
85
85
5
10123
6
11
14
6
0
4
R1
1
29
D
4
C
F
D1
2 162
E
TO ENGINE (CONNECTOR EH)
57
58
N
M
O
TO LOWER PANEL (CONNECTOR CP)
0
T1
N1
N2
TSW
23
194
183
178 178
X
J
B
T2
A
V
U
Page 24
22 Generac®Power Systems, Inc.
Section 6 Electrical Data
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generator Wiring Diagram (Control Panel) – Drawing No. 0D4992-A
BLUE
BLUE
1
44
2
1
4
E
D
V
C
183
B
H
W
J
0
A
X
B
K
X
L
194
W
V
U
23
T2
T1
23
0
T1
T2
194
183
1
4 1
85
85
56
14
14
13
56
13
85
85
BLUE
BLUE
0
14
14
56
14
85
85
GCU
BLACK
BROWN
YELLOW
ORANGE
ACTUATOR
TO GOVERNOR
2
6
S16
S15
178
H
G
F
U
G
A
C
M
T
N2
S1
J
T
K
S
L
R
F
M
E
PIN
Q
N
D
P
O
O
P
N
Q
S
R
00
N1
CP
6
S15
2
S1
00
S3
57
58
S1
2
S16
00
S3
57
N1
N2
T2
23
58
178
T1
N1
N2
T2
194
23
183
219
218
4
150
86
85
69
68
56
229
4
15
1
15A
15A
14
14
13
79
0
RED
0
0
0
14
13
14
85
85
23
TS1
13
GRD
CAP
14
BLACK
0
56
13
14
14
13
15
N1
N2
N2
0
BLACK
RED
85
2
58
T1
0
T1
T2
178
85
15
56
229
4
4
14
14
14
1
0
00
F1
15
4
162
1
2
N1
AVR
56
0
85
14
14
13
00
S16
BLUE
S16
HZ
S15
BLUE
AM
S16
6
S15
0
S15
0
0
67
64
VM
S16
S15
65
64
14
HM
4
14
2
CB1
85
85
6
5
6
5
DEUTSCH
7
8
-
85
14
0
4
3
3
421
10911
10
0
67
+
-
00
BVM
0
0
64
65
12
19
15
16
PSW
73
57
57
14 18
2
11
58
S1
194
183
15
15C
0
15C
65
67
00
S3
S1
0
S3
178
15C
0
15C
OFF
START/MANUAL
15A
239
SW1
183
T1
T2
229
15C
AUTO
178
178
15C
23
194
4
56
229
4
0
14
0
14
14
4
D1
162
R1
4
29
4
BLACK
BLACK
TS2
N1
N2
56
EH
12
11
12
14
14
13
A
14
+
S15
S3
S16
2
6
4
0
0
S15
0
S16
162
S16
S15
6
53641
N1
N2
65
14
15C
15
N.C.
SW2
F2
14
BLUE
225A
15
15A
4
85 23
194
56
14
178 15A 239
BLUE
RED
0
BLACK
15C
RED
T2
T1
BLACK
225A
T1 T1
T2 T2
LEGEND
CP - CONNECTION, LOWER PANEL
CAP - CAPACITOR
BVM - METER, BATTERY VOLTAGE
AM - METER, AC OUTPUT CURRENT
D1 - DIODE- 600V, 12A
CB1 - CIRCUIT BREAKER- EXCITATION
AVR - AUTOMATIC VOLTAGE REGULATOR
EH - ENGINE HARNESS CONNECTION
F2 - FUSE 7.5A IN-LINE
GCU - GOVERNOR CONTROLLER UNIT
F1 - FUSE 15A
S16
15
+
L1
-
15
176
S15
S16
229
D
E
A
B
BLUE
PCB
1417 16 15 13 12 11 5810 9 7 6 4321
TR1
BLUE
LPC - LOWER PANEL CONNECTION
HZ - METER, FREQUENCY
HM - HOURMETER
USE BLUE WIRE FOR 240V, 1 PHASE
USE YELLOW WIRE FOR 208V, 3 PHASE
TS1, TS2 - TERMINAL STRIPS
R1 - RESISTOR, FIELD BOOST
SW2 - SWITCH- SET EXERCISE
PSW - SWITCH- PHASE SELECTOR
TR1 - TRANSFORMER UTILITY SENSING 24 VA
PCB - CIRCUIT BOARD CONTROLLER
L1 - LIGHT - FAULT INDICATOR
SW1 - SWITCH- AUTO/MANUAL/OFF
INSULATE UNUSED WIRE END
VM - METER, AC OUTPUT VOLTAGE
Page 25
Generac®Power Systems, Inc. 23
Section 6 Electrical Data
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generator
Schematic (Control Panel) – Drawing No. 0D6975
160
161
79
0
0
0
161
00
79
160
LEGEND
CAP - CAPACITOR
CB1 - CIRCUIT BREAKER - EXCITATION
D1 - DIODE- 600V, 12A
F1 - FUSE 15 AMPS
BVM - METER, BATTERY VOLTAGE
AM - METER, AC OUTPUT CURRENT
AVR - AUTOMATIC VOLTAGE REGULATOR
F2 - FUSE 7.5 AMPS IN-LINE
HZ - METER, FREQUENCY
HM - HOURMETER
14
TR1 - TRANSFORMER, UTILITY SENSING 24VA
TS1,TS2 - TERMINAL STRIP
PCB - CIRCUIT BOARD CONTROLLER
L1 - LIGHT, FAULT INDICATOR
VM - METER, AC OUTPUT VOLTAGE
SW2 - SWITCH, SET EXERCISE
SW1 - SWITCH, AUTO/OFF/MANUAL
R1 - RESISTOR, FIELD BOOST
PFC - POWER FLOW CONTROLLER
PSW - SWITCH, PHASE SELECTOR
USE YELLOW WIRE FOR 208V, 3 PHASE
INSULATE UNUSED WIRE END
USE BLUE WIRE FOR 240V, 1 PHASE
178
13
15
BLUE
176
176
AVR
2
162
F1
PCB
0
183
14
0
0
14
BAT-
BAT+
HZ
PSW
PHASE SELECTOR SWITCH
S16
S16
S15
YELLOW
TR1
BLACK
T2
T1
MPU SHIELD
MPU-
MPU+
PFC
ACT-
ACT+
POSITION
1 2 3 OFF
CONTACTS
VM
64
65
2
19
15
14
18
16
194
23
BLUE
RED
T2
T1
225A
23
194
3E4
15
14
16
RED
T2
0
S15
T1
A17
S15
B
S16
3
5
S15
S16
13
0
0
BVM
-
HM
+
15C
15
14
0
­176
+
L1
15
15
N.C.
15
14
SHOWN IN
OFF POSITION
15A
SW2
225A
15C
15C
15C
15A
15A
F2
183
14
13
CAP
0
161
79
160
15
229
13
14
56
SW1
239
85
15E
15C
178
10
12
9
178
11
239
D
229
7
14
5
56
2
85
0
13
1
4
4
1
6
4
0
4
6
1
X
X
X
O
X
2 - 3
TS2
0
0
161
X
O
X
X
O
O
O
X
O
X
X
12 - 3
2 - 11
2 - 7
0
3117
79
160
O
O
12 - 7
X
O
0
O
X
O
O
12 - 11
-
O
O
O
X
15 - 14
0
O
X
X
O
15 - 18
AM
O
O
X
X
19 - 16
161
79
160
O
X
O
O
X INDICATES CLOSED
19 - 14
+
67
12
178
183
194
23
T1
N1
T2
23
N2
183
178
194
0
162
S3
00
4
TS1
15
229
13
14
14
56
85
85
891
2
7
101112
5
14
6
0
436
R1
1
D
4
29
C
D1
2
F
E
S1
S15
S16
G
Q
H
K
TO ENGINE (CONNECTOR EH)
57
58
N
M
O
TO LOWER PANEL (CONNECTOR CP)
0
T1
N1
T2
A
V
U
23
N2
178
183
194
BJX
WST
Page 26
PFC
24 Generac®Power Systems, Inc.
Section 6 — Electrical Data
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generator Wiring Diagram (Control Panel) – Drawing No. 0D6974
1
4
4
183
1
85
85
MPU SHIELD
MPU-
MPU+
ACT-
ACT+
BAT-
BAT+
00
S16
S16
HZ
S15
2
2
1
6
S16
S15
4
E
D
V
C
183
B
W
J
0
A
X K
X
L
194
W
V
23
T2
T1
23
0
T1
T2
194
178
H
G
T
S
E
DF
O
N
S
R
N1
23
S1
J
K
L
R
M
PIN
Q
N
P
O
P
Q
00
CP
N1
N2
T2
23
F
U
G
H
A
B
C
M
U
T
N2
183
4 1
219
218
4
150
86
85
85
69
85
68
56
56
229
4
15
15A
15A
14
14
14
14
13
13
79
0
0
0
56
13
0
14
14
56
14
85
85
0
0
79
161
160
0
14
1
RED
TS1
13
GRD
0
CAP
14
14
BLACK
13
0
14
56
13
85
14
85
14
6
S15
S1
S3
57
58
00
S3
57
58
178
T1
N1
N2
T1
T2
194
178
23
85
56
229
4
0
13
F1
15
N1
N2
N1
N2
0
BLACK
RED
56
85
S16
6
2
S15
S15
00
14
-
+
S15
S1
2
S16
HM
S3
2
S16
58
0
T1
T2
2
6
85
15
4
4
4
14
14
14
1
00
14
14
0
0
S15
0
2
S16
CB1
15
162
142
162
4
S16
S15
1
6
365
AVR
N1
N2
0
85
0
85
85
6
4
5
DEUTSCH
91110 12
987
14
14
13
0
0
79
161
160
AM
0
0
0
67
14
0
67
+
-
BVM
0
65
1915
711 3
5757
58
S1
194
0
64
PSW
0
15C
67
12
16
00
18
S3
15C
S1
14
0
2
S3
0
183
178
15
15C
23
194
4
56
229
4
0
14
0
14
D1
162
R1
29
4
4
56
3
2
1
21 437865
EH
11
10
12
14
14
13
161
160
00
15C
START/MANUAL
SW1
183
T1
T2
229
4
TS2
S16
64
VM
S15
65
64
65
14
65
15C
OFF
15C
15A
AUTO
239
178
178
N.C.
SW2
F2
S16
15C
15
BLUE
15
+
L1
-
15
225A
T1
15
T2
15E
4
85 23
194
56
178 15E
RED
0
BLACK
239
RED
T2
T1
14
T1
T2
176
S15
S16
229
E
BDA
14
11151617 1314 12 678910 12435
15C
225A
BLUE
PCB
TR1
BLUE
BLACK
D1 – DIODE, 600V 12A
EH – ENGINE HARNESS CONNECTION
F1 – FUSE 15A
HM – HOURMETER
HZ – METER, FREQUENCY
LPC – LOWER PANEL CONNECTION
PCB – CIRCUIT BOARD CONTROLLER
PFC – POWER FLOW CONTROLLER
PSW – SWITCH, PHASE SELECTOR
R1 – RESISTOR, FIELD BOOST
SW1 – SWITCH, AUTO/MANUAL/OFF
SW2 – SWITCH, SET EXERCISE
USE BLUE WIRE FOR 240V, 1 PHASE
USE YELLOW WIRE FOR 208V, 3 PHASE
INSULATE UNUSED WIRE END
TR1 – TRANSFORMER UTILITY SENSING 24 VA
TS1, TS2 – TERMINAL STRIPS
VM – METER, AC OUTPUT VOLTAGE
BLACK
BLACK
N1
N2
LEGEND:
AM – METER, AC OUTOUT CURRENT
BLUE
AVR – AUTOMATIC VOLTAGE REGULATOR
BVM – METER, BATTERY VOLTAGE
CAP – CAPACITOR
CB1 – CIRCUIT BREAKER, EXCITATION
CP – CONNECTION, LOWER PANEL
Page 27
Generac®Power Systems, Inc. 25
Section 6 Electrical Data
(Model Nos. 004373-2 & 004262-1) Guardian Liquid-cooled 40 kW Generator
Electrical Schematic Engine (4.3L) – Drawing No. 0A4592-B
Page 28
26 Generac®Power Systems, Inc.
Section 6 Electrical Data
(Model Nos. 004373-2 & 004262-1) Guardian Liquid-cooled 40 kW Generator Wiring Diagram Engine (4.3L) – Drawing No. 0A4591-B
Page 29
Generac®Power Systems, Inc. 27
Section 6 Electrical Data
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generator
Electrical Schematic – Stepper Motor – Drawing No. 0A5858
Page 30
28 Generac®Power Systems, Inc.
Section 6 Electrical Data
(Model Nos. 004373-2 & 004262-1) Guardian Liquid-cooled 40 kW Generators
Wiring Diagram - Lower Panel - Drawing No. 0D5997
BRUSH HOLDER
MTG. SCREW.
FROM STANDARD GENERAC GTS
2-WIRE START CONNECTION
CLOSEST TO BEARING.
1
BRUSH WITH RED(4) LEAD
TS4
4
2
RED
A R
DIRECT
183
178
22
6
1
2
6
1
4
0
2
183
0
1
4
C
183
B
0
A
X
194
W
23
T2
183
0
2
6
6
58
57
S16
S1
S15
S1
S3
57
58
00
6
2
D
W
X
K
T1
S16
S15
178
H
G
F
E
U
V
H
J
B
L
M
V
U
J
T
K
S
G
F
A
D
C
N
T
S
L
R
M
E
PIN
Q
N
P
O
O
P
Q
R
00
N1
N2
CP
S15
S3
57
58
A S
(390mm)
5
11
33
44
0
CT1
CT2
CP = CONTROL PANEL CONNECTOR LOWER PANEL
AR = ALTERNATOR ROTOR
AS = ALTERNATOR STATOR
CB2 = CIRCUIT BREAKER - MAIN
LEGEND
TP = THERMAL PROTECTER
NB = NEUTRAL BLOCK
TS3 = TERMINAL STRIP, PRE-PACKAGED TRANSFER SWITCH CONNECTION
DPE = EXCITATION WINDING
CT1 & CT2 = CURRENT TRANSFORMER
TS4 = TERMINAL STRIP, 2-WIRE START CONNECTION
58
0
57
S16
S15
S3
CUSTOMER CONNECTION
120/240V. 1-PHASE
CB2
120V.
00
E1
E3
N1
N2
T1
T2
23
194
TS3
SWITCH
TRANSFER
CONNECTION
PREPACKAGE
NB
E3 TO 00
E1 TO 00
E1 TO E3 240V.
Page 31
Generac®Power Systems, Inc. 29
TS3
TS4
NB
Section 6 Electrical Data
(Model Nos. 004373-2 & 004262-1) Guardian Liquid-cooled 40 kW Generators
Electrical Schematic - Lower Panel - Drawing No. 0D5997
6
THERMAL PROTECTOR BYPASS
6
DPE
S1
AS
11
CT1
0
3322
57
1
4
5
5
TP
44
1
AR
RED
4
BRUSH UNITS
2
00
S3
58
CT2
D
C
F
E
K
Q
M
N
O
0
S15
CB2
E1
NB
CUSTOMER CONNECTION
120/240-V. 1-PHASE
E3
S16
TS3
TS4
194
23
T2
T1
N2
N1
183
178
A
G
H
X
W
V
U
T
S
B
J
TO CONTROL PANEL (CONNECTOR CP)
Page 32
30 Generac®Power Systems, Inc.
A
A
0
0 0
+
-
RISK OF ELECTRICAL SHOCK.
DO NOT REMOVE COVER.
NO USER SERVICEABLE PARTS INSIDE.
REFER SERVICING TO QUALIFIED
MAY CAUSE ENGINE TO START. IF
POSITION. FAILURE TO WAIT 30 SEC.
OFF/MANUAL SWITCH TO THE "AUTO"
20 SECONDS AND THEN RELEASE.
TIME" SWITCH TO "ON" POSITION FOR
PUSH AND HOLD "SET EXERCISE
TO "OFF" POSITION.
PLACE AUTO/OFF/MANUAL SWITCH
OFF AUTOMATICALLY WITHIN 2 MIN.
ENGINE DOES START, IT WILL SHUT
D
R
E
EVERY 7 DAYS, AT TIME SET.
GENERATOR WILL NOW EXERCISE
O C E S
N
3 T
I A W
0
N I
T S
E S
X E
T
S
PLACE AUTO/
81988
.
E
S
O I T C U
N
E S
I C R
M I T
CAUTION
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generators
Control Panel - Drawing No. 0D4995-C
34
DO NOT REMOVE COVER.
RISK OF ELECTRICAL SHOCK.
CAUTION
VDC
REFER SERVICING TO QUALIFIED
NO USER SERVICEABLE PARTS INSIDE.
1
0
3
2
31
32
30
A
HRS
PANEL FACE
22
VHz
+
33
E M
I T
E S
I C R E X E
T E S
S N O I T C
.
U
S
R
D
T
N
S
O
N
C
I
E S 0 3 T I A
POSITION. FAILURE TO WAIT 30 SEC.
OFF/MANUAL SWITCH TO THE "AUTO"
20 SECONDS AND THEN RELEASE.
TIME" SWITCH TO "ON" POSITION FOR
PUSH AND HOLD "SET EXERCISE
TO "OFF" POSITION.
PLACE AUTO/OFF/MANUAL SWITCH
PLACE AUTO/
W
81988
MAY CAUSE ENGINE TO START. IF
OFF AUTOMATICALLY WITHIN 2 MIN.
ENGINE DOES START, IT WILL SHUT
EVERY 7 DAYS, AT TIME SET.
GENERATOR WILL NOW EXERCISE
3
48
45 46 47
27
-
62 63
5049
18
28
2524
29
26
23
43
53 58
51 52
3
53 58
39
51 52
61
41
42
36
0 0 0
18 49 50
1
61
60
8
9
A
A
60
37
12
56 57
55
54
14
12
2
3
10 11
9
5
8
DEUTSCH
6
7
20
PIN
Q
P
R
O
S
E
F
D
T
N
G
C
A
U
M
H
B
J
V
L
W
K
X
21
19
18 49 50
5 6
35
4
16
17
18
59
13
52 53 58
15
VIEW A-A
14
12
54 55 56 57
Page 33
Generac®Power Systems, Inc. 31
ITEM PART NO. QTY. DESCRIPTION
1 0D1523 1 PANEL BTM & BACK CONTROL PANEL 2 0D1521A 1 CONTROL PANEL, FRONT W/ SILK SCREEN 3 0D1522 2 PANEL,SIDE COVER CONTROL PANEL 4 067680** 1 ASSY VOLTAGE REGULATOR 60HZ 5 0C8243 1 WASHER LOCK HDP DEUTSCH 6 0C8244 1 NUT, HDP DEUTSCH 8 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P
9 057907 1 RES WW LUG 10R 10% 25W 10 064008 1 COVER CON PNL TOP (NOT SHOWN) 12 055444 1 HEATSINK 13 030468 1 WASHER STEP NYLON .20 14 049939 1 RECTIFIER MSC 12A 600V 1N1206R 15 070370 1 WASHER MICA .203 16 022158 1 NUT HEX #10-32 STEEL 17 023762 1 WASHER SHAKEPROOF EXT #10 STL 18 023897 15 WASHER FLAT #10 ZINC 19 076009ASRV 1 PP LOGIC ASM 50/60HZ 20 040213 4 PCB SUPPORT SNAP-IN 1/4" 21 027744 1 GROMMET 3/4 X 5/32 X 5/16 22 082573 1 SWITCH ROCKER DPST 125V SPD 23 076020 1 SWITCH TOG DPDT 15/10 SP 24 032300 1 HOLDER FUSE 25 022676 1 FUSE 15A X AGC15 26 064009 1 LIGHT 12VDC .02A LED RED PILOT 27 061945 1 SWITCH SELECTOR 6A AMP/V 28 076037 1 VOLTMETER DC 8-18V 29 070081 1 HOURMETER 30 070043 1 VOLTMETER AC 0-300 31 070045 1 AMMETER AC 0-200
ITEM PART NO. QTY. DESCRIPTION
32 070042 1 FREQUENCY METER 240V 55-65HZ 33 081988 1 DECAL EXERCISE INFO 34 0C1229 1 DECAL CUST CONN BOX 35 098647** 1 ASSY L.C. ELECT GOV 36 0A3968 1 CAPACITOR FILTER ASY 37 048766 REF BLOCK TERM 20A 2 X 6 X 1100V 39 083264 1 TFMR ASM,CMA 240/12V 41 057335 REF BLOCK TERM 20A 20 X 6 X 1100V 42 076061 1 DECAL, TERM. STRIP 43 029333 6 TIE WRAP 7.4" X .19" NATL UL 45 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20 46 022507 4 SCREW HHC 1/4-20 X 1/2 G5 47 022127 4 NUT HEX 1/4-20 STEEL 48 022097 4 WASHER LOCK M6-1/4 49 033121 14 SCREW HHC #10-32 X 1/2 50 022152 14 WASHER LOCK #10 51 036902 4 SCREW PPHM #6-32 X 1/2 52 022155 6 WASHER LOCK #6 53 022985 8 WASHER FLAT #6 ZINC 54 036918 8 SCREW PPHM #8-32 X 1/2 55 022264 8 WASHER LOCK #8-M4 56 038150 8 WASHER FLAT #8 ZINC 57 022471 8 NUT HEX #8-32 STEEL 58 022188 6 NUT HEX #6-32 STEEL 59 036908 2 SCREW PPHM #6-32 X 1-1/4 60 0C2428 4 SCREW PHTT #6-32 X 1/2 ZYC
61 0C2323 4 SCREW PHTT #6-32 X 5/8 ZYC 62* 0D5324 1 FUSE & HOLDER LITTEL 7.5A 63* 0A9611 REF. FUSE 7.5AXBK/AGC7.5NX
* PART OF CONTROL PANEL WIRE HARNESS ** SERVICE REPLACEMENT PART IS SAME PART NUMBER
WITH 0SRVADDED.
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generators
Control Panel - Drawing No. 0D4995-C
Page 34
32 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generators
Control Panel - Drawing No. 0D6978-A
60
2
AVR BEHIND COVER
34
INSIDE.
CAUTION
DO NOT REMOVE COVER.
RISK OF ELECTRICAL SHOCK.
NO USER SERVICEABLE PARTS
1
Hz
0
3
VDC
AV
HRS
51 5158 58
2
32
31
BEHIND COVER
(IF SO EQUIPPED)
21 38 61
GOVERNOR CONTROL
40
-+
7
25
30
27
28
7
11
53 54 55 56
44 45 46 47
41
24
8
59
23
29
26
58
59
43
33
81988
ETEX
NUCTIO S
SNSECO D
R
E
STIN
0
E STIMRCISE
PLACE AUTO/
GENERATOR WILL NOW EXERCISE
EVERY 7 DAYS, AT TIME SET.
ENGINE DOES START, IT WILL SHUT
OFF AUTOMATICALLY WITHIN 2 MIN.
PUSH AND HOLD "SET EXERCISE
TIME" SWITCH TO "ON" POSITION FOR
20 SECONDS AND THEN RELEASE.
OFF/MANUAL SWITCH TO THE "AUTO"
POSITION. FAILURE TO WAIT 30 SEC.
MAY CAUSE ENGINE TO START. IF
PLACE AUTO/OFF/MANUAL SWITCH
TO "OFF" POSITION.
WAIT 3 .
6362
18 48 49 22
51 52 57
3
50
50 51 52 57
39
9
PANEL FACE
35
A
A
581253 54 55 56
37
42
36
0 0 0
12
23
1110
41
9
5
8
DEUTSCH
6
7
53545556
PIN
Q
P
S
O
E
FRD
T
N
C
G
A
U
M
H
B
J
V
L
W
K
X
20
19
4
18
4849
65
494818
1
16
17
18
VIEW A-A
13
14
15
12
Page 35
Generac®Power Systems, Inc. 33
ITEM PART NO. QTY. DESCRIPTION
1 0D7397 1 PNL BTM & BACK CNTL PNL 04626 2 0D1521A 1 CONTROL PANEL FRONT W/ SILK
SCREEN 3 0D1522 1 PANEL SIDE COVER CONTROL PANEL 4 067680** 1 ASSY VOLTAGE REGULATOR 60HZ 5 0C8243 1 WASHER LOCK HDP DEUTSCH 6 0C8244 1 NUT, HDP DEUTSCH 7 0A6321 1 PANEL LEFT SIDE E 8 048467 1 CIRCT BRK 7 X 1 ETA 46-500-P 9 057907 1 RES WW LUG 10R 10% 25W
10 064008 1 COVER CON PNL TOP (NOT SHOWN) 11 0A6323 1 CHASSIS AVR & E-GOV 12 055444 1 HEATSINK 13 030468 1 WASHER STEP NYLON .20 14 049939 1 RECTIFIER MSC 12A 600V 1N1206R 15 070370 1 WASHER MICA .203 16 022158 1 NUT HEX #10-32 STEEL 17 023762 1 WASHER SHAKEPROOF EXT #10 STL 18 023897 15 WASHER FLAT #10 ZINC 19 076009ASRV 1 PP LOGIC ASM 50/60HZ 20 040213 4 PCB SUPPORT SNAP-IN 1/4" 21 0A3394 1 DECAL, ELEC GOVERNOR 22 082573 1 SWITCH ROCKER DPST 125V SPD 23 076020 1 SWITCH TOG DPDT 15/10 SP 24 032300 1 HOLDER FUSE 25 022676 1 FUSE 15A X AGC15 26 064009 1 LIGHT 12VDC .02A LED RED PILOT 27 061945 1 SWITCH SELECTOR 6A AMP/V 28 076037 1 VOLTMETER DC 8-18V 29 070081 1 HOURMETER 30 070043 1 VOLTMETER AC 0-300 31 070045 1 AMMETER AC 0-200 32 070042 1 FREQUENCY METER 240V 55-65HZ 33 081988 1 DECAL EXERCISE INFO
ITEM PART NO. QTY. DESCRIPTION
34 0C1229 1 DECAL CUST CONN BOX 35 0D3440 1 CONTROLLER, B-C #DPG-2103 36 0A3968 1 CAPACITOR FILTER ASY 37 048766 REF BLOCK TERM 20A 2 X 6 X 1100V 38 0A1441B 1 COVER PLATE AVR 39 083264 1 TFMR ASM,CMA 240/12V 40 0A1441C 1 COVER PLATE EGOV 41 057335 REF BLOCK TERM 20A 20 X 6 X 1100V 42 076061 1 DECAL TERM. STRIP 43 029333 6 TIE WRAP 7.4" X .19" NATL UL 44 040479 4 VIB MNT 1.0 X 1.0 X 1/4-20 45 022507 4 SCREW HHC 1/4-20 X 1/2 G5 46 022127 4 NUT HEX 1/4-20 STEEL 47 022097 4 WASHER LOCK M6-1/4 48 033121 14 SCREW HHC #10-32 X 1/2 49 022152 14 WASHER LOCK #10 50 036902 4 SCREW PPHM #6-32 X 1/2 51 022155 6 WASHER LOCK #6 52 022985 8 WASHER FLAT #6 ZINC 53 036918 8 SCREW PPHM #8-32 X 1/2 54 022264 8 WASHER LOCK #8-M4 55 038150 8 WASHER FLAT #8 ZINC 56 022471 8 NUT HEX #8-32 STEEL 57 022188 6 NUT HEX #6-32 STEEL 58 0C2428 8 SCREW PHTT #6-32 X 1/2 ZYC 59 0C2323 4 SCREW PHTT #6-32 X 5/8 ZYC 60 0A2284 4 SCREW SWAGE 8-32 X 1/2 Z/YC
61 0C1127 1 DECAL AVR COVER 62* 0D5324 4 FUSE & HOLDER LITTEL 7.5A 63* 0A9611 1 FUSE 7.5AXBK/AGC7.5NX
* PART OF CONTROL PANEL WIRE HARNESS ** SERVICE REPLACEMENT PART IS SAME PART NUMBER
WITH 0SRVADDED.
Section 7 Exploded Views and Parts Lists
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generators
Control Panel - Drawing No. 0D6978-A
Page 36
11
34 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generator Electronic Governor – Drawing No. 0A2615-F
ITEM PART NO.QTY. DESCRIPTION
1 098290 1 ASSEMBLY MOTOR STEPPER 2 0A3439 1 BRACKET GOVERNOR MOUNTING 3 098958A 1 CONNECTOR INTERFACE ASSEMBLY 4 021888 1 LEVER STEPPER MOTOR 5 082508 2 BALL JOINT PLA .25-.28
9 036409 2 NUT HEX 1/4-28 STEEL 11 043146 3 SCREW HHC M6-1.0 X 10 G8.8 12 098941A 2 HOUSING GOVERNOR CONNECT 13 098942A 2 COVER CONN HOUSING 14 098225 4 SCREW FHM #2 X 5/8 SELF TAP 15 022097 4 WASHER LOCK M6-1/4 16 064526 1 SCREW TAP HWH #6-25 X 3/8 ZINC 17 029333A 1 TIE WRAP 7.4" X .19" BLACK UL 18 074031 - LIQUID NEOPRENE (NOT SHOWN) 19 051716 2 NUT HEX M5-0.8 G8 YEL CHR 20 049226 2 WASHER LOCK M5 21 076040 2 SCREW PPHM M5-0.8 X 16 22 098647* 1 ASSEMBLY L.C. ELECTRONIC GOVERNOR 23 036409 2 NUT HEX 1/4-28 STEEL 24 0C2184 1 STUD THR 1/4-28 X 3-1/2 G2 ZINC
* SERVICE REPLACEMENT PART IS SAME PART NUMBER WITH KSRVADDED.
15
16
ITEM (18) NEOPRENE
14
13
COATING
3
12
1
"A"
9
15
4
SECURE WIRE HARNESS WITH TIE WRAP AS SHOWN.
17
WIRE HARNESS
9
23
EXISTING ENGINE HARDWARE
CARB. ARM (REF.)
24
5
2
19
20
22
21
15
11
"A"
14
13
3
12
Page 37
ITEM PART NO. QTY. DESCRIPTION
1 0C3250 1 ASSEMBLY BASE MOUNTING
(DIRECT-COUPLED) 3 055414 1 LUG SLDLSS #2-#8 X 17/64 CU 4 0A4084 2 MOUNT ENGINE (R&L) 5 022129 2 WASHER LOCK M8-5/16 6 045771 2 NUT HEX M8-1.25 G8 YEL CHR 7 022237 6 WASHER LOCK 3/8 8 029745 6 SCREW HHC 3/8-16 X 1 G5
10 043107 2 SCREW HHC M8-1.25 X 25 G8.8 11 022145 2 WASHER FLAT 5/16 ZINC 12 027482 3 WASHER SHAKEPROOF EXT 5/16 STL 13 055597 4 SCREW HHC M12-1.75 X 85 G8.8 14 052251 2 DAMPENER VIBRATION 40 BLUE 15 052257 4 SPACER .49 X .62 X 1.87 PWDR/ZINC 16 052252 4 DAMPENER VIBRATION 17 052259 4 WASHER FLAT M12 18 052860 4 NUT LOCKING M12-1.75 19 0536210098 1 ASSEMBLY GROUNDWIRE 10"/3/8 20 052251A 2 DAMPENER VIBRATION 50 WHITE 21 044118 1 BARBED STRAIGHT 1/2 NPT X 5/8 22 057823 2 CLAMP HOSE #10 .56 - 1.06 23 057448 11" HOSE 5/8 ID TYPE 3 SINGLE
ITEM PART NO. QTY. DESCRIPTION
24 024310 1 PLUG STD PIPE 1/2 STEEL SQ HD * 25 0A8785 4 PLUG BUTTON 3" DIA. * 26 0C4360 8 PLATE VARMINT * 27 071693 16 WASHER FLAT .281 ID X 1.0 OD * 28 0C2454 16 SCREW TH-FRM M6-1 X 16 N WA Z/JS * 29 0C4753 1 PLUG 3/4 BUTTON
30 022413 1 SCREW HHC 1/4-20 X 1 G5
31 022473 1 WASHER FLAT 1/4 ZINC
32 022097 1 WASHER LOCK M6-1/4
33 022127 1 NUT HEX 1/4-20 STEEL
NOTES: 1) * ITEMS 25, 26, 27, 28 & 29 ARE INCLUDED FOR
UNITS WITH ENCLOSURES ONLY. NOT INCLUDED WITH OPEN SETS.
2) ITEM 25 (PLUG BUTTON 3" DIA.) IS USED AFTER SHIPPING. HOLES ARE TO REMAIN UNCOVERED FOR SHIPPING PURPOSES. PLUGS CAN BE FOUND IN THE MANUAL BAG LOCATED INSIDE THE LOWER CONNECTION BOX.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generator
Mounting Base – Drawing No. 0C4399-D
Generac®Power Systems, Inc. 35
*28
*27
*27
*26
29
24
*27
*28
19
11
14
15
*26
23
10
6
5
8
7
21
22
12
19
To Oil Drain On Oil Pan.
*26
33
32
16
11
10
18
20
15
*27
*28
12
18
4
5
6
1
16
17
13
3
*27
12
31
30
*25
17
13
Page 38
36 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generator Engine Common Parts – Drawing No. 0A4304-L
15
17
38
34
26
16
12
1
9
47
18
30
29
28
27
2
44
8
7
43
43
40
22
40
25
39
45
41
23
40
21
46
40
34
26
35
34
42
20
34
24
35
19
37
14
3
34
4
13
36
11
31
33
10
5
6
31
32
Page 39
Generac®Power Systems, Inc. 37
ITEM PART NO.QTY. DESCRIPTION
1* 0A9046 1 ENGINE 4.3L GM
2 0A4084 2 MOUNT, ENGINE (R & L) 3 0A4239 1 PULLEY CRANKSHAFT 4 0A4240 1 PULLEY WATER PUMP 5 0A5640 1 SPACER FAN 50MM 4.3L (35KW UNITS ONLY)
0A5640A 1 SPACER FAN 62MM (45KW UNITS ONLY)
6 0A5639 1 FAN 17" REVRS ROT (35KW UNITS ONLY)
0D3293A 1 FAN COOLING 22" DIA REVRS ROT
(45KW UNITS ONLY) 7 077996 1 CAP HOSE 8 057823 1 CLAMP HOSE #10 .56 - 1.06 9 035579 1 BUSHING REDUCER 1/4 TO 1/8
10 037065 1 SCREW HHC 7/16-20 X 2-1/4 G5 11 022302 1 WASHER LOCK 7/16 12 0A8584 1 SWITCH OIL PRESSURE 13 052644 1 SPACER .5 X 1.5 X .25 STL/ZINC 14 0A4278A 1 BELT SERPENTNE 72.5" 15 0A4930A 1 HEAT SHIELD LEFT 16 0A4085 1 GASKET EXHAUST MANIFOLD 17 0A3927 1 MANIFOLD LEFT EXHAUST 18 0C7947 2 BOLT U 3/8-16 X 2.50 19 0A1232 1 DC ALTERNATOR ASSEMBLY 20 0A7801B 1 PULLEY PLOY-V 82 OD. 21 021928 1 BRACKET ALT. SUPPORT 22 0C6239 1 BRACKET MOUNTING WELD ASSEMBLY
ITEM PART NO.QTY. DESCRIPTION
23 0A4241 1 PULLEY GROOVED IDLER 24 0C2885 1 PULLEY TENSIONER 25 0A5737C 1 SPACER DC ALTERNATOR 34MM 26 022131 8 WASHER FLAT 3/8-M10 ZINC 27 077456 1 ADAPTOR M12-1.75 3/8 NPT 28 044117 1 BARBED STRAIGHT 3/8 NPT X 5/8 29 057823 1 CLAMP HOSE #10 .56 - 1.06 30 057448 1 HOSE 5/8 ID TYPE 3 SINGLE (12") 31 022129 8 WASHER LOCK M8-5/16 32 022142 4 SCREW HHC 5/16-18 X 3/4 G5 (45KW) 33 048614 4 SCREW HHC 5/16-24 X 3/4 G5 34 022237 12 WASHER LOCK 3/8 35 029745 4 SCREW HHC 3/8-16 X 1 G5 36 042633 3 SCREW HHC 3/8-24 X 1 G5 37 033819 1 SCREW HHC 3/8-16 X 4 G5 38 022241 4 NUT HEX 3/8-16 STEEL 39 0A5768 1 WASHER FLAT HEAVY DUTY 40 046526 5 WASHER LOCK M10 41 049814 2 SCREW HHC M10-1.5 X 25 G8.8 42 0C3756 1 BOLT TENSIONER PULLEY 43 045772 2 NUT HEX M10-1.5 G8 YEL CHR 44 0D2514 8 SPARK PLUG 5.7L GM 45 052259 1 WASHER FLAT M12 46 055934D 1 CLAMP VINYL 1.06 X .406 Z 47 0A37970001 1 FILTER OIL
*For internal engine parts use Engine Parts Manual P/N 0D3749.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generator
Engine Common Parts – Drawing No. 0A4304-L
Page 40
38 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators Engine Parts – Drawing No. 0D6980-A
Page 41
Generac®Power Systems, Inc. 39
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators
Engine Parts – Drawing No. 0D6980-A
ITEM PART NO. QTY. DESCRIPTION
1 0A9046 1 ENGINE 4.3L GM 2 0A9118A 1 FLYWHL 4.3L GM SAE 3 070022 1 WASHER STAR M12 EXT 4 0A6021 6 SCREW HHC 7/16-20 X 1 G8 6 059056A 1 STARTER 5.7L/7.4L GM 8 0A9050 2 BOLT STARTER 4.3L
9 022237 17 WASHER LOCK 3/8 10 045772 1 NUT HEX M10-1.5 G8 YEL CHR 11 049226 1 WASHER LOCK M5 12 051716 1 NUT HEX M5-0.8 G8 YEL CHR 13 0A4244 1 CONNECTOR COIL TO DISTRIBUTOR 14 0A4215 1 DIP STICK 4.3L GM 15 0A4231 1 TUBE DIP STICK 4.3L 16 059057 10" HOSE 3/4 ID SAE-30R2 17 0A2440 2 GASKET THERMOSET 18 026568 2 SCREW HHC 3/8-16 X 2-3/4 G5 19 099729A 1 HOUSING THERM IMPREX 20 061012 1 PLUG STD PIPE 1/8 SOCKET HEAD 21 069939 1 HOUSING THERMOSTAT/WATER INLET 22 035606 1 SENSOR HI COOLANT SHUTDOWN 23 0A4930B 1 HEAT SHIELD RIGHT 24 0A4084 1 MOUNT ENGINE 25 029745 3 SCREW HHC 3/8-16 X 1 G5 26 044101 2 BRACKET SUPPORT SPARK PLUG WIRE 27 023152 2 SCREW HHC 3/8-16 X 3/4 G5
ITEM PART NO. QTY. DESCRIPTION
28 022131 2 WASHER FLAT 3/8-M10 ZINC 29 058030 2 RETAINER PLUG WIRES 30 0A4085 1 GASKET EXHAUST MANIFOLD 31 0A3928 1 MANIFOLD RIGHT EXHAUST 32 0C7947 2 BOLT U 3/8-16 X 2.50 33 057794 2 RETAINER SPARK PLUG WIRES 34 0A4277 1 WIRES SPARK PLUG 4.3L 35 022241 4 NUT HEX 3/8-16 STEEL 36 057795 1 CONNECTOR C/C VENT 37 048191 2 PIN DOWEL M10 X 24 38 032303 6 SCREW HHC 3/8-16 X 3-1/2 G5 39 0A3852 3 PLATE FLEX GM 40 098239 1 CASTING ADAPTOR 41 057522 1 SENSOR COOLANT LEVEL 42 0D2244M 1 ASSY MAGPICKUP (3/8-24 MALE)
(MODEL 004626 0NLY)
43 075885 1 THERMOSTAT 195 DEG
* 0D6979 1 40KW GUARDIAN WIRE HARNESS (NOT
SHOWN FOR MOD. 004626-0)
* 0A4308 1 HARNESS 4.3L STD WIRE (NOT SHOWN
FOR MOD. 004373-1)
Page 42
40 Generac®Power Systems, Inc.
36
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators Generator – Drawing No. 0D9490
41
42
40
40
31
38
37
43
STATOR
LEADS
33
36
43
43
37
39
34
21
SCROLL DETAIL
5
1
38
40
42
31
40
13
41
24
23
14
22
25
29
2
26
27
28
12
10
21
11
15
16
17
32
19
18
35
7
30
3
31
TO ENGINE FLYWHEEL
2
5
4
1
9
8
6
35
20
19
18
TO ENGINE
FlLYWHEEL ADJUSTMENT
THREAD IN SENSOR (6) UNTIL CONTACT
IS MADE WITH RING GEAR, THEN BACK OFF
NOTE:
1/2 TO 3/4 TURN AND TIGHTEN NUT.
DO NOT ROTATE ENGINE DURING THIS ADJUSTMENT.
CAUTION:
Page 43
Generac®Power Systems, Inc. 41
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators
Generator – Drawing No. 0D9490
ITEM PART NO. QTY. DESCRIPTION
1 051768 7 SCREW HHC M12-1.75 X 25 G8.8
2 051769 7 WASHER LOCK M12
3 0A8240 2 FLEX PLATE SAE10
4 039253 6 SCREW HHC M8-1.25 X 20 G8.8
5 022129 7 WASHER LOCK M8-5/16
6 082130D 1 ASSEMBLY MAG PICKUP 72"
7 0C4286 1 ASSEMBLY FAN W/PRESS DISC 10.75 X 3
8* 0A2601 1 SCREW HHC M16-2.0 X 45 G8.8
9* 0A2602 1 WASHER FLAT .688 ID X 3.25 OD 10* 0A1138 1 KEY SQ 3/8 X 2-1/2 STEEL 11* 021941 1 COUPLER 390 SAE
12 020808A 1 ROTOR 390 40 1P DIRECT 13* 052624 1 BEARING BALL 6212 SEALED 14* 070892 1 SLIP RING -MACHINED-
15 0A5580 4 SCREW HHC M14-2.0 X 140 G8.8
16 0A1633 4 WASHER 390 SAE ALT.
17 020729A 1 STATOR 390 40 AD2 SAE
18 022131 12 WASHER FLAT 3/8-M10 ZINC
19 022237 11 WASHER LOCK 3/8
20 022511 11 SCREW HHC 3/8-16 X 1-1/4 G5
21 068113 1 CARRIER REAR BEARING 15"
22 068115 1 LOWER PANEL 15
23 043123 4 WASHER LOCK M14
24 051779 4 NUT HEX M14-2.0 G8 YEL CHR
ITEM PART NO. QTY. DESCRIPTION
25 046852 1 SCREW HHTT #10-32 X 1/4 CZ 26 022145 1 WASHER FLAT 5/16 ZINC 27 039287 4 SCREW HHC M8-1.25 X 45 G8.8 FT 28 071641 1 BRUSH HOLDER ASSEMBLY 29 071639 1 HOLDER BRUSH SUPPORT 30 0A2110 2 SCREW SWAGE 1/4-20 X 1/2 Z/YC 31 022473 8 WASHER FLAT 1/4 ZINC 32 022746 1 SCREW HHC 3/8-16 X 1-3/4 G5 33 031980 2 TIE WRAP UL 14.6 X .14 NATL 34 083549 1 SLEEVE RUBBER 35 0A4089 1 ASSEMBLY SCROLL 390 SAE
KIT 0A4089 PARTS 36 0A2491 2 SHROUD ALTERNATOR SHEET METAL 37 0A2497 2 SCREEN SHROUD SAE 38 0A2496 2 BRACKET TENSIONER SAE SCROLL 39 056326 8.4 FT TRIM VINYL BLACK 1/8 GP 40 022097 6 WASHER LOCK M6-1/4 41 045757 2 SCREW HHC M6-1.0 X 25 G8.8 42 047411 4 SCREW HHC M6-1.0 X 16 G8.8 43 0A2110 12 SCREW SWAGE 1/4-20 X 1/2 Z/YC
* ROTOR REPLACEMENT PARTS
Page 44
ITEM PART NO. QTY. DESCRIPTION
1 0C3594 10 ASSEMBLY M6 HINGE 3 0A3359 40 SCREW BHSC M6-1.0 X 16 SS 4 0A3360 40 SHAKEPROOF INT M6 SS 5 0C2522 (A) 5 DOOR SMALL STD. WELD 6 0C2527 (A) 1 CORNER POST LH REAR 7 0C2528 (A) 1 CORNER POST RH REAR 8 0C2535 (A) 1 CORNER POST LH FRONT
9 0C2536 (A) 1 CORNER POST RH FRONT 10 0C2547 (A) 2 REAR BRACE TOP & BOTTOM 11 0C2550 (A) 4 SIDE BRACE TOP & BOTTOM 12 0C2555 (A) 2 SIDE SUPPORT 13 0C2560 (A) 1 ROOF ONE-PIECE WLDMT 15 0D7904 (A) 1 FRONT BRACE TOP 16 0C2633 5 PLATE STRIKER 17 0C6749 20 SCREW PPHM M4-0.7 X 12 SS 18 060069 5 PADDLE HANDLE LOCK 19 0C6748 20 NUT LOCK HEX M4-0.7 SS NYL INS 20 080490 20 WASHER FLAT #8 SS 21 087233 5 RIVET POP 3/16 X 1/4 22 0C4065 (A) 1 DUCT FRONT LH 23 0C4064 (A) 1 DUCT FRONT RH
ITEM PART NO. QTY. DESCRIPTION
24 0C4066 (A) 1 DUCT BOTTOM 25 0C4067 (A) 1 DUCT FRONT PANEL 26 0C4117 (A) 1 DUCT FRONT TOP RH 28 0C2634A 1 ASSEMBLY COVER ACCESS 29 0C2454 76 SCREW TH-FRM M6-1X16 N WA Z/JS 30 022129 2 WASHER LOCK M8-5/16 31 042907 2 SCREW HHC M8-1.25 X 16 G8.8 32 022473 15 WASHER FLAT M6-1/4 ZINC 33 022097 1 WASHER LOCK M6-1/4 34 022127 1 NUT HEX 1/4-20 STEEL 35 0A9881 49.1 FT. GASKET DOOR RUBBER 36 0C3393 2 SCREW SHOULDER 39 0C3400 (A) 1 COVER EXHAUST HOLE 42 0C3397 4 FASTENER RATCHET 43 066760 39-3/8" STRIP SEALANT 1/8 X 1 44 022145 2 WASHER FLAT 5/16 ZINC
OPTIONAL COMPARTMENT MATERIALS: ALL P/N'S WITH AN "A" SUFFIX INDICATE ALUMINUM MATERIAL OPTION.
42 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators Compartment – Drawing No. 0D8992
28
26
13
23
29
25
31
30
44
22
43
24
36
1
4
3
15
39
29
8
1
4
3
32 33 34
9
12
11
35
12
5
11
BASE
32 29
FRAME
11
11
10
5
20
19
6
5
10
7
42
16
21
18
17
Page 45
Generac®Power Systems, Inc. 43
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators
Radiator – Drawing No. 0D7992-B
ITEM PART NO. QTY. DESCRIPTION
1 0D7825 1 RADIATOR COPPER BRASS 2 0D8251 1 FAN GUARD, BOTTOM 3 0D8252 1 FAN GUARD, TOP 4 024655 4 SCREW HHTT 1/4-20 X 1 CZ 5 022097 4 WASHER LOCK M6-1/4 6 022473 4 WASHER FLAT 1/4 ZINC 7 0D7174 1 VENTURI 4.3L 22" FAN
0D7174A 1 VENTURI 4.3L 17" FAN
9 0D7870 1 RADIATOR HOSE LOWER 10 035685 4 CLAMP HOSE #28 1.32 - 2.25 11 047290 1 HOSE 3/8 ID SINGLE BRAID 12 040173 2 CLAMP HOSE #5.5 .62 - .62 13 049340 1 BARBED EL 90 1/4 NPT X 3/8 14 036865 1 DRAINCOCK 15 029032 1 HOSE 9/32 ID (64"LG) 16 052250 3 TAPE FOAM 1 X 1 (29"LG) 17 058443 10 SCREW CRIMPTITE 1/4-20 X 5/8 18 029745 4 SCREW HHC 3/8-16 X 1 G5 19 022237 4 WASHER LOCK 3/8 20 022131 4 WASHER FLAT 3/8-M10 ZINC 21 0D7850 1 RADIATOR HOSE UPPER
ITEM PART NO. QTY. DESCRIPTION
22 076749 1 BOTTLE, COOLANT RECOVERY 23 0D7975 1 WATER BOTTLE BRACKET 24 090388 1 SCREW HHTT M6-1.0 X 12 YC 27 048031C 1 CLAMP HOSE BAND 1/4
29 0C4341 2 SUPPORT RADIATOR A GRP 30 * 0A6984 1 BRACKET AIR DUCT TOP/BOT 31 * 0D7942 1 SUPPORT AIR DUCT RH SIDE 32 * 0D7943 1 SUPPORT AIR DUCT LH SIDE 33 * 022413 8 SCREW HHC 1/4-20 X 1 G5 34 * 022097 8 WASHER LOCK M6-1/4 35 * 022473 8 WASHER FLAT 1/4 ZINC 36** 0D7924 1 SCREEN FRONT 37** 024655 4 SCREW HHTT 1/4-20 X 1 CZ 38** 022097 4 WASHER LOCK M6-1/4 39** 022473 4 WASHER FLAT 1/4 ZINC
* OPTIONAL WITH KIT 0D7948
** OPTIONAL WITH KIT 0D7947
KIT PART NO. 0D7947
38
39
37
KIT PART NO. 0D7948
30
35
34
33
31
18
36
29
32
31
27
16
12
20
19
14
12
11
15
1
27
10
"A"
16
6
10
9
22
24
23
22
7
5
4
3
17
TO "A"
2
17
KIT PART NO. 0D8121
21
10
Page 46
ITEM PART NO. QTY. DESCRIPTION
1 064945 1 GASKET CARBURETOR ADAPTOR 2 0A4120 1 ADAPTOR CARBURETOR W/INLET 3 033212 4 SCREW HHC 5/16-18 X 1-1/4 G5 4 022129 4 WASHER LOCK M8-5/16 5 052865 1 GASKET CARBURETOR 6 0A7631 1 CARB. REWORK 4.3L (NATURAL GAS +
VAPOR)
0C5716 1 CARBURETOR REWORK (LPG LIQUID) 7 029745 2 SCREW HHC 3/8-16 X 1 G5 8 022237 2 WASHER LOCK 3/8 9 026307 1 ELBOW 90 DEG STREET 3/4
10 028641 1 NIPPLE TOE 3/4 NPT X 2 11 057824 1 CLAMP HOSE #16 .87 - 1.50 12 057422 1 HOSE 1IN ID LP GAS (NATURAL GAS +
VAPOR) (42")
057422 1 HOSE 1IN ID LP GAS (LPG LIQUID) (12")
ITEM PART NO. QTY. DESCRIPTION
13 0A6344 1 BARBED ELBOW 90 DEG 1/8 NPT X 3/8 14 047290 1 HOSE 3/8 ID SINGLE BRAID (9") 15 0A4121 1 VALVE PCV 16 082508 1 BALL JOINT PLA .25-28 17 055934Z 1 CLAMP VINYL 1.13 X .406 Z 18 022097 1 WASHER LOCK M6-1/4 19 036409 2 NUT HEX 1/4-28 STEEL 20 0A4632B 1 PLATE AIR CLEANER BOTTOM 21 0A4637 1 FILTER AIR 11.5" 22 0A5763 1 ARM THROTTLE-REWORK 23 0A4632A 1 PLATE AIR CLEANER TOP 24 062522 1 STUD TH 1/4-20 X 3 G2 ZNC FULL 25 037561 1 NUT WING 1/4-20 NYLK 26 061258 1 GASKET AIR CLEANER 27 057796 1 GROMMET 28 057795 1 CONNECTOR C/C VENT
44 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generators Carburetor – Drawing No. 0A5764-G
USE FASTENER LOCATED ON ALTERNATOR FAN SCROLL
2
1
13
FRONT OF ENGINE
14
TO REGULATOR
19
6
7
8
5
3
24
12
11
10
9
17
19
18
22
TO STEPPER MOTOR
4
25
23
21
16
20
15
27
26
TO ALTERNATOR
28
FAN SCROLL
Page 47
Generac®Power Systems, Inc. 45
ITEM PART NO. QTY. DESCRIPTION
1 064945 1 GASKET CARBURETOR ADAPTOR 2 0A4120 1 ADAPTOR CARBURETOR W/INLET 3 033212 4 SCREW HHC 5/16-18 X 1-1/4 G5 4 022129 4 WASHER LOCK M8-5/16 5 0C7059 1 GASKET GOVERNOR THROTTLE BODY 6 0C7650A 1 MIXER (ONLY) NATURAL GAS 7 029745 2 SCREW HHC 3/8-16 X 1 G5 8 022237 2 WASHER LOCK 3/8 9 026307 1 ELBOW 90 DEG STREET 3/4
10 028641 1 NIPPLE TOE (THREADED ONE END) 3/4
NPT X 2 11 057824 1 CLAMP HOSE #16 .87-1.50 12 057422 44" HOSE 1 IN ID LP GAS 13 0A6344 1 BARBED ELBOW 90 1/8 NPT X 3/8 14 047290 9" HOSE 3/8 ID SINGLE BRAID 15 0A4121 1 VALVE PCV 16 0D2803 1 ACTUATOR THROTTLE 42MM
ITEM PART NO. QTY. DESCRIPTION
17 055934Z 1 CLAMP VINYL 1.13 X .406 Z 18 0A6613 1 GASKET CARB IMPCO 225 19 036409 1 NUT HEX 1/4-28 STEEL 20 0A4632B 1 PLATE AIR CLEANR BOTTOM 21 0A4637 1 FILTER AIR 11.5" CA326 22 0C7820 1 MACHINING CARBURETOR ADAPTOR 23 0A4632A 1 PLATE AIR CLEANER TOP 24 062522 1 STUD THR 1/4-20 X 3 F THR G2 ZNC 25 037561 1 NUT WING 1/4-20 NYLK 26 061258 1 GASKET AIR CLEANER 27 057796 1 GROMMET 28 057795 1 CONNECTOR C/C VENT 30 0C7060 1 GASKET CARBURETOR ADAPTOR 31 022152 8 WASHER LOCK #10 32 064090 4 SCREW PHM SEMS #12-24 X 5/8 EX 33 0C7908 4 SCREW SHC #10-32 X 5/8 G8.8 NZ
Section 7 Exploded Views and Parts Lists
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generators
Carburetor – Drawing No. 0D6977-B
USE FASTENER LOCATED ON ALTERNATOR FAN SCROLL
TO REGULATOR
19
6
18
22
24
9
12
11
10
17
31
25
23
32
TO ALTERNATOR FAN SCROLL
31
33
FRONT OF ENGINE
7
8
3
4
2
1
13
14
30
16
5
21
20
15
27
26
28
Page 48
46 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generators Regulator – Drawing No. 0C2776-D
ITEM PART NO. QTY. DESCRIPTION
1 065907 1 SUPPORT SOLENOID NAT GAS 2 026307 3 ELBOW 90 DEG STREET 3/4 3 076691 1 NIPPLE PIPE 3/4 NPT X 4.5 BLK IRN 4 043768A 1 SOLENOID GAS FUEL 5 026490 1 NIPPLE PIPE 3/4 NPT X 2 6 026577 2 BUSHING REDUCER 1 TO 3/4 7 055944 1 REGULATOR NAT GAS LPG VAPOR 8 067018 1 SUPPORT REGULATOR
9 0C2775 1 BRACKET REGULATOR 4.3L 10 061910 4 SCREW HHTT #10-24 X 3/4 YC 11 022145 6 WASHER FLAT 5/16 ZINC 12 022129 6 WASHER LOCK M8-5/16 13 030795 4 SCREW HHC 5/16-18 X 1 G5
ITEM PART NO. QTY. DESCRIPTION
14 025655 1 PLUG STD PIPE 3/4 STEEL SQ HD 15 022132 2 WASHER FLAT 9/16 ZINC 16 051778 2 SCREW HHC M14-2.0 X 25 G8.8 17 028641 1 NIPPLE TOE 3/4 NPT X 2 18 057824 2 CLAMP HOSE #16 .87 - 1.50 19 057422 1 HOSE 1IN ID LP GAS 20 043123 2 WASHER LOCK M14 21 051779 2 NUT HEX M14-2 G8 YEL CHR 23 027482 1 WASHER SHAKEPROOF EXT 5/16 STL 24 0C3168 1 WASHER LOCK SPECIAL 5/16 25 022259 1 NUT HEX 5/16-18 STEEL 26 058359 1 LUG RNGTNG INS 22-18 X 5/16 X .477 27 0D1509 1 DECAL INLET PRESSURE
P
RE
SS
URE
1
4
"
H
O
M
AXIM
U
M
IN
LET
2
D
1
5
0
9
TO
CARBURETOR
For LPG Vapor Withdrawal Turn
Regulator (Item 7)
Upside Down, Remove Items A & B
Then Replace End Cap.
B
A
END CAP
6
7
18
19
18
17
5
4
2
3
25
12
2
21
20
1
26
6
8
9
11
2
12
13
10
11
23
11
9
LET
0 5
1
O
D
IN
2
H
M
"
U
4 1
E
AXIM
R
U
M
S
S E R
P
14
27
24
11
12
15
16
MOUNTING BASE
12
13
13
11
12
13
Page 49
Generac®Power Systems, Inc. 47
ITEM PART NO. QTY. DESCRIPTION
1 065907 1 SUPPORT SOLENOID NAT GAS 2 026307 3 ELBOW 90 DEG STREET 3/4 3 076691 1 NIPPLE PIPE 3/4 NPT X 4.5 BLK IRN 4 043768A 1 SOLENOID GAS FUEL 5 026490 1 NIPPLE PIPE 3/4 NPT X 2 6 026577 2 BUSHING REDUCER 1 TO 3/4 7 0D2758 1 REGULATOR N/G (R600S) 8 028237 2 SADDLE 1-3/8
9 0C2775 1 BRACKET REGULATOR 10 028238 2 BOLT U 5/16-18 X 1.53 11 022145 10 WASHER FLAT 5/16 ZINC 12 022129 10 WASHER LOCK M8-5/16 13 030795 4 SCREW HHC 5/16-18 X 1 G5 14 025655 1 PLUG STD PIPE 3/4 STEEL SQ HD
ITEM PART NO. QTY. DESCRIPTION
15 022132 2 WASHER FLAT 9/16 ZINC 16 051778 2 SCREW HHC M14-2.0 X 25 G8.8 17 028641 1 NIPPLE TOE 3/4 NPT X 2 18 057824 2 CLAMP HOSE #16 .87-1.50 19 057422 1 HOSE 1 IN ID LP GAS 20 043123 2 WASHER LOCK M14 21 051779 2 NUT HEX M14-2 G8 YEL CHR 23 027482 1 WASHER SHAKEPROOF EXT 5/16 STL 24 0C3168 1 WASHER LOCK SPECIAL 5/16 25 022259 5 NUT HEX 5/16-18 STEEL 26 058359 1 LUG RNGTNG INS 22-18 X 5/16 X .477 27 0D2616 1 SUPPORT REGULATOR 28 0D1509 1 DECAL INLET PRESSURE
Section 7 Exploded Views and Parts Lists
(Model No. 004626-1) Guardian Liquid-cooled 40 kW Generators
Regulator – Drawing No. 0D4823-B
TO
CARBURETOR
For LPG Vapor Withdrawal Turn
Regulator (Item 7) Upside Down, Remove Items A & B
Then Replace End Cap.
B
A
END CAP
21
20
10
6
7
6
5
4
2
3
25
26
2
12
1
11
23
11 12 25
27
18
19
18
17
2
8
9
11
12
13
MOUNTING BASE
11
12
13
11
12
28
15
16
14
24
11
12
13
13
Page 50
ITEM PART NO. QTY. DESCRIPTION
1 080723 1 HOSE CONNECTION TEE 1.75-.62 2 035685 2 CLAMP, HOSE #28 1.32-2.25 3 057822 4 CLAMP, HOSE #8 .53-1.00 4 084918C 1 HEATER, ENGINE 1800W 120V.
*084918D 1 HEATER, ENGINE 2000W 240V. 5 050967 1 HOSE, 5/8" I.D. RIA 250F (36”) 6 0A6283 1 HOSE, PREFORMED BLOCK HEATER 7 053660 1 BARBED ST. 1/4" NPT x 5/8 I.D. 8 084427 1 BRACKET, HEATER 9 047411 2 SCREW HHC M6-1.0 X 16 G8.8
10 022097 4 WASHER, LOCK-M6-1/4 11 022473 4 WASHER, FLAT 1/4 ZINC 12 049813 2 NUT, HEX-M6 X 1.00 G8 YEL CHR 13 042568 2 SCREW, HHC-M6-1.0 x 20MM G8.8 14 **077043E 36" FLEXIBLE CONDUIT 1" BLACK
*USED ON "R" VOLTAGE GENERATORS ONLY
**ITEM #14 USED ONLY ON 4.3L UNITS
48 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators Engine Coolant Heater – Drawing No. 087434-D
Lower Radiator Hose
To Water Pump
To Engine
To Lower Radiator
2
1
3
14
Block
7
3 6 5
13
3
11
3
4
11
10
9
8
10
12
Page 51
Generac®Power Systems, Inc. 49
ITEM PART NO. QTY. DESCRIPTION
2 058665 1 BATTERY 12VDC 90-AH 27F (NOT PROVIDED) 3 061902 1 HOLD DOWN BATTERY 4 059473 1 HOLD DOWN BATTERY 5 038805H 1 CABLE BATTERY BLACK #1 X 23.00 6 038804N 1 CABLE BATTERY RED #1 X 15.00
038804T 1 CABLE BATTERY RED #1 X 31.00 (GEAR BOX-NON-GUARDIAN UNITS) 7 0A4010 2 SCREW HHC M8-1.25 X 60 FT G8.8 8 052858 2 NUT LOCK FLANGE M8-1.25 9 049820 2 NUT LOCK HEX M8-1.25 (NYLON INSERT)
11 023152 1 SCREW HHC 3/8-16 X 3/4 G5 12 022131 1 WASHER FLAT M10-3/8 ZINC 13 025507 1 WASHER SHAKEPROOF EXT 7/16 STL 14 022237 1 WASHER LOCK 3/8
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators
Battery – Drawing No. A6708-F
TO STARTER
11
SOLENOID
12
13
5
RED
6
9
3
14
TO ENGINE BLOCK
BLACK
2
9
8
4
8
7
7
Page 52
50 Generac®Power Systems, Inc.
OWNERS MANUAL
C
ONNE
CTI
ON SEE
REMO
T
E S
T
AR
T
178
183
FOR CIRCUIT BREAKER AND NEUTRAL BLOCK
RECOMMENDED TERMINAL TIGHTENING TORQUES
LUG TO CIRCUIT BREAKER
FASTEN COMPRESSION
524040
40
ITEM
NEUTRAL BLOCK
CIRCUIT BREAKER
LINE SIDE
LOAD SIDE
CIRCUIT BREAKER
DESCRIPTION
#
19 FT-LB
30 FT-LB
FROM ALTERNATOR
RING TERMINALS
NA
CABLE TO COMPRESSION LUG
STRIPPED END OF STRANDED
12.5 FT-LB
NA
NA
23 FT-LB
23 FT-LB
NA
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators Lower Panel – Drawing No. 0D8848-A
13
30
29
12
31
35
37
36
18
2
11
32
E
L
E
A T S
U R
183
N
A
N
A
T
O
M
S
I
T
4
S
178
E
C
R
E
T
E
O
N
N M
N E
W
O
O
C
R
9
10
ALT.
LEADS &
SENSING
WIRE
52
35
37
36
1
REF.
BOTTOM OF
CONTROL PANEL
36
37
35
6
4
34
36
33
37
38
46
44
47
49
50
ALT.
LEADS &
59
58
60
40
F F
O
ON
H S
P
I U R P T O T
47
48
SENSING
WIRE
57
58
SIEMENS
FD 3 POLE
42
56
(600V)
(200A)
47
44
45
43
47
44
55
45
54
53
NA
23 FT-LB
23 FT-LB
RECOMMENDED TERMINAL TIGHTENING TORQUES
CABLE TO COMPRESSION LUG
STRIPPED END OF STRANDED
NA
FASTEN COMPRESSION
LUG TO CIRCUIT BREAKER
30 FT-LB
RING TERMINALS
FROM ALTERNATOR
NA
12.5 FT-LB
NA
19 FT-LB
FOR CIRCUIT BREAKER AND NEUTRAL BLOCK
LINE SIDE
LOAD SIDE
CIRCUIT BREAKER
40
NEUTRAL BLOCK
CIRCUIT BREAKER
52
DESCRIPTION
#
ITEM
Page 53
Generac®Power Systems, Inc. 51
ITEM PART NO. QTY. DESCRIPTION
1 068115 1 LOWER PANEL 15 2 0D5489 1 COVER LOWER CONNECTION BOX 4 023484N 2 BUSHING SNAP SB-2.5-31 6 056739 1 RELAY SOLENOID 12VDC PNL MNT
9 0D3388 1 DECAL REMOTE START CONNECTION 10 058710 2 TRANSFORMER 200A TO 5A 5VA 11 0D5492 1 HARNESS LOWER PANEL 4.3L GRDN
(048766) REF. BLOCK TERM 20A 2 X 6 X 1100V 12 022985 2 WASHER FLAT #6 ZINC 13 068116 1 COVER LOWER PANEL 15 18 0D5840 1 DECAL CUSTOMER CONNECTN FOR TS 29 022264 2 WASHER LOCK M4 30 0C2212 2 SCREW PHTT M4-0.7 X 16 ZYC 31 022142 4 SCREW HHC 5/16-18 X 3/4 G5 32 022145 4 WASHER FLAT 5/16 ZINC 33 022129 4 WASHER LOCK M8-5/16 34 045771 4 NUT HEX M8-1.25 G8 YEL CHR 35 022287 19 SCREW HHC 1/4-20 X 3/4 G5 36 022473 23 WASHER FLAT 1/4 ZINC 37 022097 23 WASHER LOCK M6-1/4 38 022127 4 NUT HEX 1/4-20 STEEL 40 0D5574 1 CB 0200A 3P 600V S FD6 LL
ITEM PART NO. QTY. DESCRIPTION
41 0D5595A 1 KIT CB MOUNT S(FD) 390S
PARTS SHOWN BELOW (I/N'S: 42-50) 42 0D5689 1 PLATE CB MOUNT S (FD) 390S 43 0D5693 1 COVER CB TERMINALS S (FD 3P) 44 022097 12 WASHER LOCK M6-1/4 45 022287 8 SCREW HHC 1/4-20 X 3/4 G5 46 022127 12 NUT HEX 1/4-20 STEEL 47 022473 4 WASHER FLAT 1/4 ZINC 48 081320 4 SCREW SHC 1/4-20 X 4.5 G8.8 NZ 49 022237 3 WASHER LOCK 3/8 50 048527 3 SCREW SHC 3/8-16 X 3/4 G5 51 0D5463B KIT NEUTRAL BLOCK 390/200-400A
PARTS SHOWN BELOW (I/N'S: 52-60) 52 0D5464B 1 NEUTRAL BLOCK 390/200-400A 53 057073 2 JUNCTION BLOCK 3/8-16 54 022152 4 WASHER LOCK #10 55 033530 4 SCREW PHM #10-32 X 5/8 CAD 56 022237 2 WASHER LOCK 3/8 57 022241 2 NUT HEX 3/8-16 STEEL 58 022145 2 WASHER FLAT 5/16 ZINC 59 022129 1 WASHER LOCK M8-5/16 60 045771 1 NUT HEX M8-1.25 G8 YEL CHR
Section 7 Exploded Views and Parts Lists
(Model Nos. 004373-2 & 004626-1) Guardian Liquid-cooled 40 kW Generators
Lower Panel – Drawing No. 0D8848-A
Page 54
52 Generac®Power Systems, Inc.
Section 7 Exploded Views and Parts Lists
(Model No 004626-1) Guardian Liquid-cooled 40 kW Generators Exhaust Muffler – Drawing No. 0D6976-A
Page 55
Generac®Power Systems, Inc. 53
ITEM PART NO. QTY. DESCRIPTION
1 059902A 1 CAP RAIN 2.50 / 2.69 2 0C9641 1 TUBE STRAIGHT 'A' GROUP 3 0D4208 1 MUFFLER CATALYST 4.3L 4 0D5061 4 MOUNTING BAND A-GRP CATALYST 5 0C4126 2 BRACKET MUFFLER MOUNTING 6 0D5787 1 TUBE ELBOW 90 DEG 2.5" 7 0A5215B 2 PIPE FLEX 2.5" 8 0D5792 1 TUBE 2.5" SMALL TEE
9 0D5793 1 TUBE ELBOW 90 DEG 2.5" FLARED 10 0C4170 2 BRACKET EXHAUST SHIELD 11 0C4305 1 SHIELD A-GRP HEAT 12 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA
Z/JS 13 0C3433A 4 CLAMP BAND 2.5" 14 022129 16 WASHER LOCK M8-5/16 15 022145 20 WASHER FLAT 5/16 ZINC 16 045771 4 NUT HEX M8-1.25 G8 YEL CHR 18 042907 16 SCREW HHC M8-1.25 X 16 G8.8
ITEM PART NO. QTY. DESCRIPTION
19 080762 8 BOLT U 3/8-16 X 2.62 20 022237 16 WASHER LOCK 3/8 21 022241 16 NUT HEX 3/8-16 STEEL 22 0D5187 1 SHIELD HEAT CROSSOVER 4.3L 23 0D5190 1 SHIELD HEAT EXHAUST 4.3L 24 077879 3 FT HOSE VACUUM 5/32 25 0D4221 1 KIT AIR/FUEL RATIO CONTROLLER 26 0D4512 1 BRACKET AIR/FUEL CONTROLLER 27 043116 2 SCREW HHC M6-1.0 X 12 G8.8 28 022471 5 NUT HEX #8-32 STEEL 29 022264 5 WASHER LOCK #8-M4 30 038150 8 WASHER FLAT #8 ZINC 31 036918 5 SCREW PPHM #8-32 X 1/2 32 049811 2 WASHER FLAT M6 33 022097 2 WASHER LOCK M6-1/4 34 049813 2 NUT HEX M6 X 1.0 G8 YEL CHR 35 0D8780 1 DECAL IMPORTANT EXHAUST
EMISSION INFO
Section 7 Exploded Views and Parts Lists
(Model No 004626-1) Guardian Liquid-cooled 40 kW Generators
Exhaust Muffler – Drawing No. 0D6976-A
Page 56
Section 7 Exploded Views and Parts Lists
(Model No. 004373-2) Guardian Liquid-cooled 40 kW Generators
Generator – Drawing No. 0D5786
ITEM PART NO. QTY. DESCRIPTION
1 059902A 1 CAP RAIN 2.50 / 2.69 2 0C9641 1 TUBE STRAIGHT 'A' GROUP 3 0C9650 1 MUFFLER 2-1/2" INLET/OUTLET 4 0C4114A 2 CLAMP BAND MUFFLER 6.5" 5 0C4126 2 BRACKET MUFFLER MOUNTING 6 0D5787 1 TUBE ELBOW 90 DEG 2.5" 7 0A5215B 2 PIPE FLEX 2.5" 8 0D5792 1 TUBE 2.5" SMALL TEE
9 0D5793 1 TUBE ELBOW 90 DEG 2.5" FLARED 10 0C4170 2 BRACKET EXHAUST SHIELD 11 0C4305 1 SHIELD A-GRP HEAT
ITEM PART NO. QTY. DESCRIPTION
12 0C2454 2 SCREW TH-FRM M6-1 X 16 N WA Z/JS 13 0C3433A 4 CLAMP BAND 2.5" 14 022129 12 WASHER LOCK M8-5/16 15 022145 12 WASHER FLAT 5/16 ZINC 16 0C9748 1 PLUG M18-1.5 18 042907 12 SCREW HHC M8-1.25 X 16 G8.8 19 080762 8 BOLT U 3/8-16 X 2.62 20 022237 16 WASHER LOCK 3/8 21 022241 16 NUT HEX 3/8-16 STEEL 22 0D5187 1 SHIELD HEAT CROSSOVER 4.3L 23 0D5190 1 SHIELD HEAT EXHAUST 4.3L
54 Generac®Power Systems, Inc.
20
19
21
20
22
19
9
19
To Engine
2.5" Dia. Clamp Assembly
13
7
13
19
16
19
To Engine
21
23
8
Compartment
Front
14
18
1
21
20
19
6
14
5
18
19
5
4
10
10
13
7
15
To
15
2
19
19
3
18
14
15
11
4
12
Page 57
Generac®Power Systems, Inc. 55
Section 8 Notes
Guardian Liquid-cooled 40 kW Generators
Page 58
56 Generac®Power Systems, Inc.
1
Hz
Section 9 Installation Drawings
Guardian Liquid-cooled 40 kW Generators Installation Drawing – Drawing No. 0D5335
NOTE 7
R677 [R26.66"]
TYP
247 [9.73"]
204 [8.03"]
839 [33.01"]
TYP
ALT AIR OU
220 [8.65"] STUB-UP AREA
STUB-UP AREA SEE NOTE 8 AND CHART
794 [31.28"]
STUB-UP
A1
AREA
C
49 [1.92"]
TYP
MOUNTING HOLES
Ø13.5 [Ø0.53"]
8 HOLES ON BOTTOM
110 [4.33"] TYP.
570 [22.44"] TYP.
NOTE 9
1117 [43.98"]
ALT
TYP AIR OUT
NOTE 1
71 [2.79"]
140 [5.50"]
TOP OR PLAN VIEW
665 [26.19"]
37 [1.44"]
2397 [94.37"]
454 [17.87"]
NOTE 5
NOTE 3
AAVVHz
NOTE 2
NOTE 6
103 [4.06"]
53 [2.09"]
835 [32.87"]
936 [36.85"]
LEFT SIDE VIEW
NATURAL GAS INLET 3/4" NPT FEMALE
OIL DRAIN 1/2" N.P.T. FEMALE
Page 59
Generac®Power Systems, Inc. 57
Section 9 Installation Drawings
Guardian Liquid-cooled 40 kW Generators
Installation Drawing – Drawing No. 0D5335
RECOMMENDED FUEL/ELECTRICAL STUB-UPS
(SEE TOP VIEW)
DESCRIPTION
AC LOAD LEAD CONDUIT
INSIDE STUB-UP FOR
FUEL CONNECTIONS
NOTE:
FUEL SYSTEM SET UP WITH OUTSIDE STUB UPS (SEE LEFT SIDE VIEW). SMALL FUEL SYSTEM MODIFICATIONS REQUIRED FOR INSIDE STUB-UPS.
WEIGHT DATA
UNIT: 729.7 kg [1609 lbs] STEEL COMPARTMENT: 208.6 kg [460 lbs]
UNITS: mm [INCHES]
965 [37.99"]
(LEFT)
INSIDE
BASE
A1
C
NOTES:
1. STANDARD BLOCK HEATER REQUIRES 120V AC CONNECTION
2. CONNECTION POINTS FOR AC LOAD LEADS, TRANSFER SWITCH, AND
ENGINE AUTOMATIC START/STOP CONTROL WIRES PROVIDED IN
AC CONNECTION PANEL.
3. EXHAUST MUFFLER SUPPORT BRACKETS SUPPLIED WITH OPTIONAL COMPARTMENT.
4. 12 VOLT NEGATIVE GROUND SYSTEM BATTERY TRAY INSIDE DIMENSIONS: 178 X 342.5 [7" X 13.5"]
5. 2.5" I.D. FLEX EXHAUST
6. MAIN LINE CIRCUIT BREAKER.
7. DOORS MUST BE OPENED 90 DEG. TO BE REMOVED.
8. A1 MAY BE USED
9. SEE DRAWING C3850 FOR DUCT REMOVAL. REMOVAL OF FRONT DUCT WILL PROVIDE ACCESS TO MUFFLER FOR SERVICING.
ENGINE SERVICE CONNECTIONS
INLET NATURAL GAS = 3/4" NPT COUPLING OIL DRAIN = 1/2" NPT COUPLING EXHAUST OUTLET -
FOR CIRCUIT BREAKER STUB-UP LOCATION.
2.5" OD MUFFLER OUTLET
1160 [45.67"]
877 [34.51"]
REAR VIEW
LIFTING EYE
(4 PLACES)
CENTER OF
GRAVITY
981 [38.62"]
(1) 12V BATTERY SEE NOTE 4
158 [6.22"]
1930 [75.98"]
RIGHT SIDE VIEW
Page 60
Part No. 0D8908 Revision 0 (03/06/02) Printed in U.S.A.
Section 10 – Warranty
Guardian Liquid-cooled 40 kW Generators
GENERAC POWER SYSTEMS "TWO YEAR" STANDARD WARRANTY FOR GUARDIAN
®
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale Generac Power Systems, Inc. (Generac) will, at its option, repair or replace any part which, upon examination, inspection and testing by Generac or a Generac Authorized Warranty Service Dealer, is found to be defective under normal use and service, in accordance with the warranty schedule set forth below. Any equip­ment that the purchaser/owner claims to be defective must be returned to and examined by the nearest Generac Authorized Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and pre­paid by the purchaser/owner. This warranty applies only to Generac Guardian prepackaged emergency automatic standby gen­erators sold and rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and maintenance is required):
• Engine - All Components
• Alternator - All Components
• Transfer System - All Components All warranty expense allowances are subject to the conditions defined in Generac's Warranty Policies, Procedures and Flat Rate
Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Generac Guardian generators that utilize non-Generac replacement parts.
• Any Generac Guardian generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire, freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or conse­quential damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
GENERAC®POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190