GE MDS DS-EL806-24 Users Manual

Page 1
5. If constant interference is present in a particular frequency zone, it may be necessary to “lock out” that zone from the radio’s hopping pattern. The radio includes built-in tools to help users do this. Refer to the discussion of the SKIP command (Page 49) for more information. In the USA, a maximum of four zones may be skipped, per FCC rules. Check the regulatory requirements for your region.
6. Interference can also come from out-of-band RF sources such as paging systems. Installation of a bandpass filter, such as Part No. 20-2822A02 in the antenna system may provide relief from this type of interference.
7. Proper use of the RETRY and REPEAT commands may be helpful in areas with heavy interference.
The RETRY command sets the maximum number of times (1 to 10) that a radio will re-transmit upstream data over the air. Values greater than 1 successively improve the chances of a message getting through when interference is a problem.
The REPEAT command sets a fixed number of unconditional retransmissions for downstream data.
8. The RF power output of all radios in a system should be set for the lowest level necessary for reliable communications. This lessens the chance of causing unnecessary interference to nearby systems and keeps power consumption to a minimum.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 33
Page 2
10.0 PROGRAMMING REFERENCE
All programming and control of the transceiver is performed through a PC terminal connected to the radio or the Evaluation Board DIAG connector. There are no manual adjustments or jumper settings used for configuration. This section explains how to establish terminal communication, and provides a complete list of user commands.
10.1 Programming Methods
Terminal Interface Mode
A PC may be used by operating it in a basic terminal mode (e.g., a HyperTerminal session) and entering the radio commands listed in the tables contained in this section. The PC must be connected to the radio via its 16-pin header connector, or, if using the Evaluation Board, via the modular diagnostics connector. In the latter case, an RJ-11 to DB-9 Adapter Cable (Part No. 03-3246A01) is required. A cable of this type may be constructed using the information shown in Figure 10 on Page 11.
Once a PC terminal is connected, communication (baud rate) is automatically established through the command interface. To access the command interface, press the ESCAPE key, followed by one or more ENTER keystrokes (delivered at about half-second intervals), until the “>” prompt is displayed.
NOTE: The diagnostic interface uses 8 data bits, 1 stop bit, and no parity. It automati-
cally configures itself to function at 1200, 2400, 4800, 9600, 19200, 38400, 57600, and 115200 bps.
If the DLINK setting is ON, the interface will start out in Diagnostic Link mode. This is a special protocol used to support Network-Wide Diagnostics. The pro­cess described in the paragraph above causes the radio to exit diagnostic link mode and enter command mode. If there is no input in command mode for 5 minutes, the interface will revert back to diagnostic link mode.
PC-Based Configuration Software
The Windows™-based TransNET Configuration Software (P/N 06-4059A01) is designed for use with the OEM Transceiver. This software provides access to all of the radio’s capabilities with the benefit of context-sensitive help. The program is shipped as part of the TransNET Support Package CD included with every order.
10.2 User Commands
A series of tables begin on the next page listing the various user commands for the OEM transceiver. The tables provide abbreviated command descriptions. Complete descriptions follow in Section 9.3.
34 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 3
Entering Commands
The proper procedure for entering commands is to type the command, followed by an keystroke. For programming commands, the command is followed by , the appropriate information or values, and
ENTER
then .
ENTER
SPACE
Table 11. Network ConfigurationMaster Station
COMMAND DESCRIPTION
BAND [abc]
Details, page 41
BUFF [ON, OFF]
Details, page 42
FEC [ON, OFF]
Details, page 44
HOPTIME [7, 28]
Details, page 44
REPEAT [0–10]
Details, page 47
RETRY [0–10]
Details, page 47
SAF [ON, OFF]
Details, page 49
SKIP [NONE, 1...8]
Details, page 49
Selects which of three frequency ranges the transceiver will operate in.
ON = Seamless data OFF = Fast byte throughput.
Sets/disables FEC (Forward Error Correction) setting.
Displays hop-time or sets it to 7 or 28 ms.
Sets/displays the xed downstream re-send count.
Sets/displays the maximum upstream re-send count for ARQ (Automatic Repeat Request) operation
Enables/disables the store-and-forward func­tion for the network controlled by this Master unit.
Skip one or more frequency zones
Table 12. Network-Wide Diagnostics
Command Description
DLINK [xxxxx/ON/OFF]
Details, page 43
DTYPE [NODE/ROOT]
Details, page 44
Controls operation of diagnostic link function.
Set radios operational characteristics for net­work-wide diagnostics
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 35
Page 4
Table 13. Operational ConfigurationSet/Program
Command Description
ADDR [1–65000]
Details, page 40
AMASK [0000 0000–FFFF FFFF]
Details, page 41
ASENSE [HI/LO]
Details, page 41
BAND [abc]
Details, page 41
BAUD [xxxxx abc]
Details, page 41
CODE [NONE, 1255]
Details, page 42
CTS [0–255]
Details, page 43
CTSHOLD [0–60000]
Details, page 43
DEVICE [DCE, CTS KEY]
Details, page 43
LEDS [ON, OFF]
Details, page 45
MODE [M, R, X]
Details, page 45
OWM [xxxxx]
Details, page 46
OWN [xxxxx]
Details, page 46
PORT [RS232, RS485]
Details, page 46
PWR
Details page 47
REPEAT [0–10]
Details, page 47
RXTOT [NONE, 0–1440]
Details, page 48
Program network address
Sets alarm response. Default: FFFF FFFF
Sense of the radios alarm output in the EIA-232 mode. Default: Alarm present = HI.
Selects which of three frequency ranges the transceiver will operate in.
Data communication parameters
Select the security/encryption setting in the radio.
CTS delay in milliseconds. (A value of 0 returns CTS immediately)
Hold time that CTS is present following last character from DATA port.
Device behavior: DCE (normal) or CTS Key
Enables/disables transceiver LEDs
Operating mode: where M = Master, R = Remote
Owners message, or alternate message (30 characters maximum)
Owners name, or alternate message (30 characters maximum)
Data port (DATA connector) interface signal­ing mode: RS232 or RS485
Forward power-output setting in dBm
Forward power output in dBm.
Maximum duration (in minutes) before time-out alarm. Default is OFF.
36 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 5
Table 13. Operational ConfigurationSet/Program (Continued)
Command Description
RTU [ON, OFF, 0-80]
Details, page 48
SLEEP [ON, OFF]
Details, page 50
UNIT [10000–65000]
Details, page 51
XADDR [0–31]
Details, page 51
XPRI [031]
Details, page 51
XMAP [00000000-FFFFFFFF]
Details, page 51
XRSSI [NONE, –40...–120]
Details, page 51
ZONE CLEAR
Details, page 51
Enable or Disable unit’s built-in RTU simula- tor. Default is OFF. Set RTU address betw een zero and 80.
Enable or Disable the radio’s Sleep mode function.
Unit address used for network-wide diagnos­tics. (Unique within associated network.)
This units Extended address Typically, the Master is set to zero (0).
Address of the primary Extended radio unit (Extension).
Included Extended units in MODE X. (Exten­sions and Remotes only).
Minimum RSSI level required to preserve syn­chronization with a non-primary radio. (Only meaningful when XPRI is not NONE)
Reset zone data statistics
Table 14. Operating StatusDisplay Only
Command Description
ADDR
Details page 40
AMASK
Details page 41
ASENSE
Details page 41
BAND
Details page 41
BAUD
Details page 41
BUFF
Details page 42
CODE
Details page 42
Network address
Alarm mask (response)
Current sense of the alarm output.
Shows which of three frequency ranges the transceiver is set to operate in (A, B, or C)
Data communication parameters. Example: BAUD 9600 8N1
Data buffering mode: ON = seamless data, OFF = fast byte throughput
Security/encryption operational status. NONE (Inactive), or “ACTIVE
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 37
Page 6
Table 14. Operating StatusDisplay Only (Continued)
Command Description
CTS
Details page 43
CTSHOLD
Details page 43
DEVICE
Details page 43
HOPTIME
Details page 44
HREV
Details, page 45
LEDS [ON, OFF]
Details, page 45
MODE
Details page 45
OWM
Details page 46
OWN
Details page 46
PORT
Details page 46
PWR
Details page 47
REPEAT
Details page 47
RETRY
Details page 47
SAF
Details page 49
SKIP
Details page 49
RSSI
Details page 48
CTS delay in milliseconds (0255 ms)
Hold time that CTS is present following last
character from DATA port. Device behavior
Alternatives: DCE and CTS KEY Hop-time value in milliseconds (ms).
Hardware revision level
Enables/disables transceiver LEDs
Current operating mode: M = Master
R = Remote X = Extension (Repeater)
Owners message or site name
Owners name or system name
Current data port (DATA connector) interface signaling mode: RS232 or RS485
Show forward power-output setting in dBm
The xed downstream re-send count.
The maximum upstream re-send count for ARQ (Automatic Repeat Request) operation.
The store-and-forward function status.
Table of frequency zones programmed to be skipped
Received signal strength indicator (dBm). Unavailable at Master unless SETUP is enabled.
38 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 7
Table 14. Operating StatusDisplay Only (Continued)
Command Description
RXTOT
Details page 48
RTU
Details page 48
SAF
Details page 49
SER
Details page 49
SHOW PWR
Details page 49
SHOW SYNC
Details page 49
SKIP
Details page 49
SLEEP
Details page 50
SREV
Details page 50
STAT
Details page 50
TEMP
Details page 50
UNIT
Details page 51
XADDR
Details page 51
XPRI
Details page 51
XMAP
Details page 51
XRSSI
Details page 51
The amount of time (in seconds) to wait before issuing a time-out alarm.
RTU simulators operational status (ON/OFF)
Store-and-forward mode status in this unit. (ON/OFF)
Serial number of radio
Show measured RF output power in dBm
Information on synchronization source and depth
Frequency zones that are skipped
Radios Sleep Mode setting. (At Remotes Only)
Transceiver rmware revision level
Current alarm status
Transceivers internal temperature (°C)
Programmed unit address for network-wide diagnostics
This units Extended address
Address of the primary Extended radio unit (Extension).
Included Extended units in MODE X. (Exten­sions and Remotes only).
Minimum RSSI level required to preserve syn­chronization with a non-primary radio. (Only meaningful when XPRI is not NONE)
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 39
Page 8
Table 15. Diagnostic and Test Functions
Command Description
KEY
Details, page 45
DKEY
Details, page 44
TX [xxxx]
Details, page 50
RX [xxxx]
Details, page 48
SETUP
Details, page 49
ZONE DATA
Details, page 51
ZONE CLEAR
Details, page 51
Enables the transmitter test. (Radio must be in Setup mode.)
Turns off the transmitter test. (Radio must be in Setup mode.)
Set/display transmit test frequency. (Radio must be in Setup mode.)
Set/display receive test frequency. (Radio must be in Setup mode.)
Enables Setup mode. Times out after 10 min­utes. Press “Q” to quit.
Zone data statistics
Clears the Zone Data log
10.3 Detailed Command Descriptions
The essential commands for most applications are Network Address (ADDR), Mode (MODE), and Baud Rate (BAUD). However, proper use of the additional commands allows you to tailor the transceiver for a specific use, or to conduct basic diagnostics on the radio. This section gives more detailed information for the commands listed above in section 9.2.
Most of the commands below can be used in two ways. First, you can type only the command name (for example, ADDR) to view the currently programmed data. Second, you can set or change the existing data by typing the command, followed by a space, and then the desired entry (for example,
ADDR 1234). In the list below, allowable programming variables, if any, are
shown in brackets [ ] following the command name.
ADDR [1–65000]
This command sets or displays the radio’s network address. The network address can range from 1 to 65000.
A network address must be programmed at the time of installation and must be common across each radio in a given network. Radios are typically
shipped with the network address unprogrammed, causing the address to display as NONE. If the address is not set (or is set to a wrong value) it leaves the system in an invalid state, preventing operation and generating an alarm.
NOTE: It is recommended that the last four digits of the master radios serial number
be used for the network address. This helps avoid conflicts with other users.
40 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 9
AMASK [0000 0000–FFFF FFFF]
This command sets the alarm bits that cause the alarm output signal to be triggered. The PWR LED will still flash for all alarms, but the alarm output signal will only be activated for those alarms that have the corresponding mask bit set. The hex value for the mask aligns directly with the hex value for the ALARM command. The default is FFFF FFFF. Through proper use of the
AMASK command, it is possible to tailor the alarm response of the radio.
Contact the factory for more information on configuring the alarm mask.
ASENSE [HI/LO]
This command is used to set the sense of the radio’s alarm output at Pin 3 of the 16-pin header connector. The default setting is HI which means an alarm exists when an RS-232 high is on Pin 3.
BAND [abc]
BAND command is used to select one of three frequency ranges that the
The transceiver will operate in (A, B, or C). All transceivers in a given network must have the same band setting or communication will not be possible. Conversely, radios may be set to different bands to enable up to three separate radio networks to operate in the same vicinity, without cross-network interference.
Each frequency band is approximately 26 MHz wide, and contains eight “zones” within. These zones are described in more detail under the ZONE
DATA command (see Page 51). The frequency ranges for each band are as
follows:
Band A: 2.4016–2.4270 GHz Band B: 2.4272–2.4526 GHz Band C: 2.4528–2.478.2 GHz
BAUD [xxxxx abc]
This command sets or displays the communication attributes for the normal payload communications through the DATA port. The command has no effect on the RJ-11 DIAG(NOSTICS) port.
The first parameter (xxxxx) is baud rate. Baud rate is specified in bits-per-second and must be one of the following speeds: 1200, 2400, 4800, 9600, 19200, 38400, 57600, or 115200. At baud rates of 19200 bps or less, the radio can support unlimited continuous data transmission at any hop rate.
The second parameter of the BAUD command (abc) is a 3-character block indicating how the data is encoded. The following is a breakdown of each character’s meaning:
a = Data bits (7 or 8) b = Parity (N for None, O for Odd, E for Even) c = Stop bits (1 or 2)
The factory default setting is 9600 baud, 8 data bits, no parity, 1 stop bit (Example: 19200 8N1).
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 41
Page 10
NOTE: 7N1, 8O2, and 8E2 are invalid communication settings and are not supported
by the transceiver.
BUFF [ON, OFF]
This command sets or displays the received data handling mode of the radio. The command parameter is either ON or OFF. (The default is OFF.) The setting of this parameter affects the timing of received data sent out the DATA connector. Data transmitted over the air by the radio is unaffected by the
BUFF setting.
If data buffering is set to OFF, the radio will operate with the lowest possible average latency. Data bytes are sent out the DATA port as soon as an incoming RF data frame is processed. Average and typical latency will both be below 10 ms, but idle character gaps may be introduced into the outgoing data flow.
If data buffering is ON, the radio will operate in a seamless mode. That is, data bytes will be sent over the air as quickly as possible, but the receiver will buffer the data until the entire packet has been collected. The delay introduced by data buffering is variable and depends on message size and the number of retransmissions required, but the radio will not create any gaps in the output data stream. This mode of operation is required for protocols such as MODBUS™ that do not allow gaps in their data transmission.
Seamless mode (BUFF ON) is intended only for applications where the message size is 256 characters or less. Enforcement of this rule is left up to the user. If more than 256 characters are transmitted data delivery will not be seamless and data may be lost.
Changes to the BUFF setting may only be made at the master radio. This is because the master radio broadcasts the buffer setting for the entire network. At remote radios, the buffer setting may be read when the radio is in synchronization with the master, but it may not be changed.
CODE [NONE, 1…255]
The CODE command is used to select or display the security/encryption setting in the radio.
The default is CODE NONE. Setting CODE to a value other than NONE provides an extra level security beyond that provided by the Network Address (ADDR). The disadvantage is increased complexity in managing the network.
The CODE command takes an argument 1255, or “NONE”. Entering CODE without an argument will display either “NONE” or “ACTIVE”. ACTIVE means that security/encryption has been enabled, but the radio will not display the security argument.
When a CODE value is active, all radios in the system must use the same code value. If the code value is not properly programmed, a remote radio will not synchronize with the master.
CAUTION: Record the CODE value and store it in a safe place. If the code is later forgotten, and a unit is to be added to the system, all radios in the network must be set to NONE and then reprogrammed to a new value.
42 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 11
CTS [0–255]
The CTS (clear-to-send) command sets or displays the timer value associated with the CTS line response. The command parameter ranges from 0 to 255 milliseconds.
For DCE operation, the timer specifies how long to wait after the RTS line goes high before asserting the CTS line. A timer value of zero means that the CTS line will be asserted immediately following the assertion of RTS.
For CTS Key operation (see the DEVICE command), the timer specifies how long to wait after asserting the CTS line before sending data out the DATA port. A timer value of zero means that data will be sent out the data port without imposing a key-up delay. (Other delays may be in effect from other radio operating parameters.)
CTSHOLD [0–60000]
Used in DEVICE CTS KEY mode, this command sets the amount of time in milliseconds that CTS remains present following transmission of the last character out the RXD pin of the DATA port. This “hold time” can be used to prevent squelch tail data corruption when communicating with other radios.
The CTSHOLD setting can range from 0 to 60000 (i.e., 60 seconds). The default value is 0, which means that CTS will drop immediately after the last character is transmitted. If the command is entered when the radio is in
DEVICE DCE mode, the response CTSHOLD N/A will be displayed.
DEVICE [DCE, CTS KEY]
The DEVICE command sets or displays the device behavior of the radio. The command parameter is either DCE or CTS KEY.
The default selection is DCE. In this mode, CTS will go high following RTS, subject to the CTS programmable delay time. Keying is stimulated by the input of characters at the data port. Hardware flow control is implemented by dropping the CTS line if data arrives faster than it can be transmitted.
If CTS KEY is selected, the radio is assumed to be controlling another radio, such as in a repeater or tail-end link system. The RTS line is ignored and the CTS line is used as a keyline control for the other radio. CTS is asserted immediately after the receipt of RF data, but data will not be sent out the DATA port until after the CTS programmable delay time has expired. (This gives the other radio time to key.)
Following transmission of the last byte of data, CTS will remain asserted for the duration specified by the CTSHOLD command. CTSHOLD should be set sufficiently high.
DLINK [xxxxx/ON/OFF]
DLINK ON enables use of Diagnostic Link mode and establishes it as the
default protocol on the RJ-11 DIAG port. Diagnostic Link mode is a special protocol used to support Network-Wide Diagnostics. DLINK must be set to
ON to support connection to InSite or to support chained diagnostics between
radio networks. DLINK OFF disables this feature. The default setting is ON.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 43
Page 12
The following DLINK baud rates selections are allowed:
• 1200 • 4800 • 9600 • 19200 (default)
• 38400 • 57600 • 115200
Example: DLINK 4800 sets the RJ-11 DIAG port to operate at 4800 bps when diagnostics is “closed”. This setting will not affect the port’s autobaud operation. Use only of DLINK ON, will enable the use 19200 or the most recently programmed value. The default is DLINK 19200 and DLINK ON.
NOTE: The same baud rate must be entered into the InSite Equipment Lists BAUD
NOTE: The DLINK rate must match the rate of any connected device to the diagnostic
field.
port. This may be either another radios diagnostic port, the InSite computer, or another data link device that eventually connects to the InSite computer.
DKEY
Disables the transmitter when it is keyed. See also KEY command.
DTYPE [NODE/ROOT]
The DTYPE command specifies the radio’s operational characteristics for network-wide diagnostics. The transceiver uses the following types:
NODE–The most common setting, and the default. This is the basic system radio device-type. Typically, the radio network is comprised of nodes and one root. Intrusive diagnostics can originate from any node. However, non-intrusive diagnostics can only be conducted from the root node.
ROOT–Always one, and only one, per network (including units associated through Extension units.) The root is the focal point of network-wide diagnostics information. Intrusive diagnostics can originate from any radio, including the root. However, the root is the only radio through which non-intrusive diagnostics can be conducted.
FEC [ON, OFF]
This command is used to view the FEC setting, or turn it on or off. The default setting is FEC ON. (It needs to be turned off when throughputs exceed 57,600 bps.) FEC is set at the master and is automatically passed on to all of the remotes in a network.
Setting FEC to ON improves sensitivity at the cost of reduced throughput. Typical SCADA/telemetry applications use low data rates and, as such, the FEC setting is normally transparent to them.
HOPTIME [7, 28]
The HOPTIME command is used to set or display the hop-time setting. The command is a digit corresponding to the hop-time setting in milliseconds. The default HOPTIME setting is 7. A setting of 28 must be used when throughputs exceed 57,600 bps.
44 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 13
Changes to the HOPTIME setting may only be made at the master radio. (This is because the Master radio establishes the hop-time setting for the entire network.) At remote radios, the hop-time setting may be read when the radio is in synchronization with the master, but it may not be changed.
INIT
The INIT command is used to reset the radio’s operating parameters to the factory defaults listed in Table 16 on Page 46. This may be helpful when trying to resolve configuration problems that resulted from the entry of one or more improper command settings. If you are unsure of which command setting caused the problem, this command allows you to get back to a known working state.
NOTE: Caution should be exercised when using the INIT command on radios in a sys-
SPECIAL NOTE: Installing firmware of Revision 2.0 or later into a radio with Revi-
tem employing the Store-and-Forward feature. Settings relating to the use of Extension services will be lost and will need to be re-entered. Inventory and record the settings for XADDR, XPRI and XMAP before using the INIT com­mand.
sions 1.x firmware will preserve the radios compatibility with other radios run­ning Revision 1.x firmware. If updating the radios firmware is part of a system-wide upgrade, the last step should be to use the INIT command at the Master station. Use of the
Table 16 on Page 46 to be applied
INIT command causes the changes shown in
HREV
Shows the Hardware revision of the radio.
KEY
Enables the transmitter. (Radio must be in Setup mode.) See also DKEY command.
LEDS [ON, OFF]
This command is used to view the LED setting, or to enable/disable LED operation. In power-critical applications (battery/solar powered sites, for example), it may be desirable to turn off the LEDs.
MODE [M, R, X]
The MODE command sets or displays the operating mode of the radio. A master radio is set by MODE M; a remote set by MODE R, and an Extension is set by MODE X.
All units default to remotes; other modes must be specifically programmed with the MODE command.
If MODE X is used, the MODE X radio should be programmed with an Extended Address (XADDR). Units that need to hear this MODE X radio must be programmed with an appropriate XPRI and/or XMAP value.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 45
Page 14
OWM [xxxxx]
The OWM command sets or displays an optional owner’s message, such as the system name. The entry can contain up to 30 characters.
OWN [xxxxx]
The OWN command sets or displays an optional owner’s name, such as the site name. The entry can contain up to 30 characters.
PORT [RS232, RS485]
Select or identify the current data interface signaling mode: RS232 or RS485. This is the port though which the payload data will pass. Pin descriptions for EIA-232 are on Page13 and EIA-485 can be found on Page13. Note: This command will always show TTL if the radio is only equipped for TTL service—see model number configuration code on Page 3.
PWR [17–21]
This command displays or sets the desired RF forward output power setting of the radio. The PWR command parameter is specified in dBm and can range from 20 dBm through 27 in 1 dBm steps. The default setting is 27 dBm (0.5 watt). To read the actual (measured) power output of the radio, use the SHOW
PWR command.
In the USA, maximum allowable power is governed by FCC limits on Effective Isotropic Radiated Power output (EIRP). The EIRP limit of +36 dBm means that any user with a net antenna gain greater than 10 dBi must decrease the PWR setting accordingly.
Table 16. INIT Command Generated Defaults
Corresponding
Parameter Default Setting
For all radios
Device operation DCE DEVICE DCE CTS delay 0
CTS hold-time 0 CTSHOLD 0 DATA Interface port 9600 baud
Alarm Mask FFFF FFFF AMASK Alarm Output Sense RS-232 High (+5.0 Vdc) ASENSE RX Time-out-Timer None/Disable RXTOT Transmitter
test frequency
(CTS is continuously asserted)
8 data bits
none (no parity)
1 stop bit
2.4xx GHz TX xxx
Command
CTS 0
BAUD 9600 8N1
46 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 15
Table 16. INIT Command Generated Defaults (Continued)
Corresponding
Parameter Default Setting
Receiver test frequency
Sleep Enable OFF SLEEP OFF Data Port Setting RS/EIA-232 PORT RS232 Primary Extension
Radio Address Synchronization
Source Map Extended Address 0 XADDR 0
For MASTER radios
Skipped frequencies None (radio will hop across all
Hop-time 7 ms HOPTIME 7 Buffer mode OFF BUFF OFF Retry Count 10 (max. 10 repeats for ARQ) RETRY 10 Repeat Count 3 (downstream repeats) REPEAT 3 Forward Error
Correction
2.4xx GHz RX xxx
0 (Master) XPRI 0
None XMAP 0
frequencies)
ON FEC ON
Command
SKIP NONE
REPEAT [0–10]
The REPEAT command affects “downstream” data. The command causes a Master or Extension to always repeat transmissions for the specified number of times (range is 0 to 10; default selection is 3). Unlike the RETRY command, there is no acknowledgment that a message has been received. To display the current setting, use the REPEAT command without entering a value.
RETRY [0–10]
The RETRY command affects upstream data. The command selects, or displays, the maximum number of times (0 to 10) that a remote radio will re-transmit data. The default setting is 10.
This command is associated with ARQ (Automatic Repeat Request) operation of the radio and is intended for use in areas with heavy radio interference.
When the RETRY command is issued without parameters, the maximum retransmission count is shown. A value of 0 represents no retries, while values of 1 or greater successively improve the chance of data delivery in spectrally harsh environments (at the expense of possibly increased latency). The RETRY value is only settable at the Master. It is readable by a synchronized Remote.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 47
Page 16
RSSI
This command displays the radio’s Received Signal Strength Indication in dBm (decibels relative to 1 mW). The output can range from –40 dBm to –120 dBm. Command availability and results depend on the mode of operation (master or remote). The closer to 0 dBm, the stronger the signal, thus a reading of –70 dBm is stronger than –80 dBm.
For a remote radio, under normal operation, RSSI is based on the average signal strength of the SYNC message received in each of the eight frequency zones. (RSSI is sampled each time a SYNC message is received.) When using the RSSI reading to align a directional antenna, it is important to make changes slowly so that the RSSI reading will provide meaningful results. It will take several seconds to indicate a change in signal level. The radio stays
in RSSI mode until is pressed.
ENTER
For a master radio, under normal operation, entering the RSSI command causes the response
NOT A VAILABLE to be returned. This is because a master
is normally receiving signals from several remote stations and an RSSI reading would be continually changing. The only exception is when the
SETUP command has been asserted. This disables hopping and allows
reading a “raw” RSSI signal level in real time from a master or remote radio.
NOTE: RSSI readings will not indicate signals stronger than –40 dBm.
RTU [ON, OFF, 0-80]
This command re-enables or disables the radio’s internal RTU simulator, which runs with proprietary polling programs such as poll.exe and rsim.exe. The internal RTU simulator is available whenever a radio has diagnostics enabled. This command also sets the RTU address that the radio will respond to.
The internal RTU can be used for testing system payload data or pseudo bit error rate (BER) testing. It can be helpful in isolating a problem to either the external RTU or the radio. The default RTU setting is OFF.
RX [xxxx]
This command sets or displays the test receive frequency used in place of hopping when the radio is in SETUP mode. The test receive frequency can be reprogrammed to any value between 2.4016 GHz and 2.4782 GHz, inclusive. The factory default setting is 2.42420 GHz.
RXTOT [NONE, 0–1440]
This command sets or displays the amount of time (in minutes) to wait for the next received data packet before issuing a receiver time-out alarm. The default setting is NONE.
48 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 17
SAF [ON, OFF]
This command enables/disables the operation of the Store-and-Forward services. It can be set only at the network’s Master station, but will effect all radios in the associated network. The default setting is OFF. See related commands: “XADDR [0–31]” on Page 51, “XPRI [0–31]” on Page 51, and
“XMAP [00000000-FFFFFFFF]” on Page 51.
SETUP
This command sets up the transceiver for checking antenna SWR or trans­mitter power with external measuring equipment. Do not use this mode during normal operation.
When the SETUP command is entered, the prompt changes to SETUP>, and:
• Hopping is disabled.
• Synthesizer frequencies are reset to the test frequencies specified by the
TX and RX commands described earlier.
• The radio can be keyed using the KEY command. DKEY is used to unkey the radio. (If the radio is left in a keyed state it is automatically unkeyed after several minutes.)
• The RSSI is sampled in a raw, continuous fashion regardless of whether the unit is a master or a remote.
Entering Q or QUIT returns the system to normal operation. A timer keeps the Setup mode from accidentally leaving the system disabled.
After 10 minutes the system behaves as if Q or QUIT had been entered, returning to normal operation.
SER
Displays the Serial Number of the radio.
SHOW PWR
The SHOW PWR command displays the actual (measured) RF power output in dBm. Unlike the PWR command, this command shows the actual level being measured, not the programmed RF power setting.
SHOW SYNC
When used at a Remote station, this command will display Extended Address and Unit Address of the Master or Extension radio to which the Remote is synchronized. The network depth at the remote, defined as the number of downstream links from the Master, is displayed in parentheses.
SKIP [NONE, 1...8]
This command sets or displays which, if any, of the eight 3.2 MHz-wide zones will be skipped from the radio’s hopping sequence. Skipping zones is one way of dealing with constant interference on one or more frequencies. See “DEALING WITH INTERFERENCE” on Page 32 for more information on dealing with interference.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 49
Page 18
The command parameter is either the keyword NONE or an undelimited string of up to four digits where each digit 1...8 represents a corresponding zone to skip. (For zone parameter input, the digits can appear in any order and can be optionally separated by a blank space.) The SKIP command is display-only at remote radios. (Remotes must be synchronized with the master radio to display the skip status.)
In the USA, a maximum of four zones may be skipped, per FCC rules. Check the regulatory requirements for your region before deleting zones.
SLEEP [ON, OFF]
This command is used to set or display the radio’s Sleep Mode setting. The default setting is SLEEP OFF. When this mode is enabled (ON), a ground or logic low on Pin 6 of the 16-pin header connector (J3) suspends all normal radio functions, and power consumption is reduced to approximately 8 mA. The radio remains in this state until the low is removed. This function cannot be turned on for a Master or Extension radio.
SREV
This command displays the version of the firmware currently loaded into the transceiver.
A display of 06-4040A01, 2.0.0 is an example of the firmware version identifier—part number followed by release/version number.
STAT
This command is used to check the alarm status of the radio. If no alarms exist, the message NO ALARMS PRESENT is returned.
If an alarm does exist, a two-digit alarm code (00–31) is displayed and the event is identified as a “Major” or “Minor” alarm. A brief description of the event is also given.
If more than one alarm exists, the word MORE appears, and additional alarms may be viewed by pressing the key. Detailed descriptions of the
ENTER
alarm codes are provided in Table 17 on Page 54.
TEMP
This command displays the internal temperature of the transceiver in degrees Celsius. (Note that the radio is specified to operate in an environment between –30 C° and +60 C°). This internal reading may be higher than the outside temperature by several degrees.
TX [xxxx]
This command sets or displays the test transmit frequency used in place of hopping whenever the radio is in Setup mode. The test transmit frequency can be reprogrammed to any value between 2.4016 GHz and 2.4782 GHz, inclusive. The factory default setting is 2.42420 GHz.
50 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 19
UNIT [10000–65000]
This command sets the unit addressing for network-wide diagnostics. The unit address is factory programmed to the last four digits of the serial number. If re-programmed in the field, the entry must consist of five digits between 10000 and 65000.
XADDR [0–31]
Display or program the Extended Address of this radio that will serve as a common address for the sub-network synchronized to this Master or Extension. This value can be listed in the XPRI parameter of associated Extension or Remote radios to allow them to synchronize to this radio. We recommend setting the Master to zero (0). It is easy to remember, and is the default address when the INIT command is used. (Programmed only in Master and Extension radios.)
XMAP [00000000-FFFFFFFF]
XMAP is a 32-bit hex entry where the least significant bit represents XADDR 0 and the most significant bit represents XADDR 31. The full 32-bit hex value represents the entire list of extensions with which the radio will be allowed to communicate. (Remotes and Extensions only.)
This parameter is easily programmed through the TransNET Configuration Software’s Store and Forward Settings panel.
XPRI [0–31]
Display or program the extended address of a primary radio with which this radio will attempt to synchronize and communicate. A setting of NONE will allow the unit to synchronize with any Master or Extension in the XMAP list. (Parameter only meaningful for a Remote or Extension.)
XRSSI [NONE, –40...–120]
The XRSSI command is used to set the RSSI minimum signal level required to preserve synchronization with a non-primary Extension radio. This parameter will be ignored if XPRI is set to NONE.
ZONE CLEAR
The ZONE CLEAR command clears the zone data for all zones in the Zone Data Log, resetting the count to 0. (Zone data is also cleared automatically upon reboot.)
ZONE DATA
The transceiver divides its frequency operating spectrum into eight
3.2 MHz-wide zones. (These are the same zones referenced by the SKIP command described earlier.) Data frame statistics are maintained for each zone to indicate the transmission quality of data through the network. This information is useful for identifying zones where significant interference exists.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 51
Page 20
Zone quality information can be accessed using the ZONE DATA command. For each zone (1–8), it shows you the number of data frames sent, the number received, and the number received with errors. If an excessive number of errors are seen in one or more frequency zones, it may indicate interference, and you should consider “skipping” those zones using the SKIP command.
Note: If a frequency zone has been skipped, all counts for that zone will be zeros.
The ZONE DATA format is displayed as follows:
1:TX TO TAL 00000000 1:RX TO TAL 00000000 1:RX ERROR 00000000
x: x: x:
8:TX TO TAL 00000000 8:RX TO TAL 00000000 8:RX ERROR 00000000
All data is based on payload packets. Incoming network data may be divided up into multiple packets for over-the-air transfers. The number before the colon represents the zone. TX TOT AL is the transmit packet total. RX TO TAL is the receive packet total. RX ERROR is the total number of received packets with CRC errors. All zone data is reset with the ZONE CLEAR command.
11.0 TROUBLESHOOTING
Successful troubleshooting of the radio system is not difficult, but requires a logical approach. It is best to begin troubleshooting at the master station, as the rest of the system depends on the master for polling instructions and synchronization data. If the master station has problems, the operation of the entire network will be affected.
When communication problems are found, it is good practice to begin by checking the simple things. All radios in the network must meet these basic requirements:
• Adequate and stable primary power
• An efficient and properly aligned antenna system
• Secure connections (RF, data & power)
• Proper programming of the radio’s operating parameters, especially Mode selection (MODE), Network Address (ADDR), and interface Baud Rate (BAUD)
• The correct interface between the radio and the connected data equipment (proper cable wiring, data format and timing).
• In store-and-forward systems there are several areas that must be carefully evaluated:
52 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 21
• Duplicate XADDR values on MODE M and MODE X radios will cause failures unless the radios are far enough apart to not hear each other .
• Errors in the synchronization qualifiers, XPRI and XMAP, on corresponding Remote radios.
SAF must be enabled at the Master
11.1 Alarm Codes
When an alarm condition exists, the transceiver creates an alarm code. These codes can be very helpful in resolving many system difficulties.
Checking for AlarmsSTAT command
To check for the presence of alarms, enter STAT. If no alarms exist, the message NO ALARMS PRESENT appears at the top of the display.
If an alarm does exist, a two-digit alarm code (00–31) is displayed, and it is identified as a major or minor alarm. A brief description of the alarm is also given. Alarm codes and their meanings are listed in Table 17.
If more than one alarm exists, the word screen; additional alarms can be viewed by pressing .
Major Alarms vs. Minor Alarms
Major alarms report serious conditions that generally indicate a hardware failure, or other abnormal condition that will prevent (or seriously hamper) further operation of the transceiver.
With the exception of alarm code 00 (network address not programmed), major alarms generally indicate the need for factory repair. Contact your factory representative for further assistance.
Minor alarms report conditions which, under most circumstances, will not prevent transceiver operation. This includes out-of-tolerance conditions, baud rate mismatches, etc. The cause of these alarms should be investigated and corrected to prevent system failure.
MORE appears at the bottom of the
ENTER
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 53
Page 22
Alarm Code Definitions
Table 17 contains a listing of all event codes that may be reported by the
transceiver.Additional alarm codes may be used in future firmware releases or are used by the factory.
Table 17. Alarm Codes
Alarm Code
00 Major The network address is not programmed. 01 Major Improper firmware detected for this radio model. 04 Major One or more of the programmable synthesizer loops is reporting
08 Major The system is reporting that it has not been calibrated. Factory
10 Major The DSP was unable to properly program the system to the ap-
12 Major Receiver time-out alarm. 16 Minor The unit address is not programmed. 17 Minor A data parity fault has been detected on the DATA connector.
18 Minor A data framing error has been detected on the DATA connector.
29 Minor RF output power fault detected. (Power differs by more than 2
30 Minor The system is reporting an RSSI reading below –105 dBm. 31 Minor The transceivers internal temperature is approaching an
Alarm Type Description
an out-of-lock condition.
calibration is required for proper radio operation.
propriate defaults. A hardware problem may exist.
This usually indicates a parity setting mismatch between the ra­dio and the RTU.
This may indicate a baud rate mismatch between the radio and the RTU.
dB from set level.) Often caused by high antenna system SWR. Check antenna, feedline and connectors.
out-of-tolerance condition. If the temperature drifts outside of the recommended operating range, system operation may fail.
54 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 23
11.2 LED Indicators
The LED indicators on the transceiver board (CR3, CR-4, CR-5 and CR-6) are an important troubleshooting tool and should be checked whenever a problem is suspected. Table 18 describes the function of each status LED.
Table 18. LED indicator descriptions
LED Name Description
RXD
TXD
DCD
GP
RXD (CR3) Receive Data
TXD (CR4) Transmit Data
DCD (CR5) Data Carrier Detect
GP (CR6) General Purpose
Serial receive data activity. Payload data from con­nected device.
Serial transmit data activity. Payload data to con­nected device.
ContinuousRadio is receiving/sending synchroni­zation frames
On within 10 seconds of power-up under normal conditions
ContinuousPower is applied to the radio; no problems detected
Flashing (5 times-per-second)Fault indication. See “TROUBLESHOOTING” on Page 52
OffRadio is unpowered or in Sleep mode
11.3 Troubleshooting Chart
Table 19 provides suggestions for resolving system difficulties that may be
experienced in the radio system. If problems persist, contact the factory for further assistance. Refer to the inside back cover of this guide for contact information.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 55
Page 24
Table 19. Troubleshooting chart
Difficulty Recommended System Checks
Unit is inoperative.
Interference is suspected.
No synchroniza­tion with master, or poor overall performance.
BER is too high. Data throughput is spotty.
Latency is too high.
a.Check for the proper supply voltage at the transceiver, J3 Pins
5 and11.
b.If using the Evaluation Board, the surface mount fuse may have
opened. Refer to Section 4.3 below for replacement instruc­tions.
a.Verify that the system has a unique network address. Nearby
systems with the same address will cause interference.
b.Check for interference and lockout any affected zone(s) using
the SKIP command (Page 49).
c.If omnidirectional antennas are used on remote stations, con-
sider changing to directional antennas. This will often limit inter­ference to and from other stations.
a.Check for secure interface connections at the radio and the
connected device.
b.Check the antenna, feedline and connectors. Reflected power
should be less than 10% of the forward power reading (SWR 2:1 or lower).
c.If the remote radio is in synchronization, but performance is
poor, check the received signal strength using the RSSI com­mand (Page 48). If RSSI is low, it may indicate antenna prob­lems, or misalignment of directional antenna headings.
d.Verify proper programming of system parameters: mode, net-
work address, data interface baud rate, transmitter power, CTS delay, etc. For store-and-forward applications, also verify the following: SAF is ON; extended address is properly pro- grammed at each extension; remotes are using the proper val­ues for XPRI and XMAP.
e.Check for alarms using the STAT command (Page 50) a.The RETRY and REPEAT commands may be increased to
deal with interference, or decreased to increase throughput and reduce latency.
b.Try turning on FEC. FEC on gives some coding gain, but
comes at the cost of reduced throughput.
a.Reduce the REPEAT count. b.Turn BUFF OFF. BUFF ON insures that no gaps occur in the
data, but this comes at the cost of increased latency.
c.Make sure HOPTIME is set to 7.
11.4 Network-Wide Remote Diagnostics
Diagnostics data from a remote radio can be obtained by connecting a laptop or personal computer running InSite diagnostics software (V6.6 or later) at any radio in the network.
56 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 25
NOTE: The diagnostics feature may not be available in all radios. The ability to query
and configure a radio via Network-wide Diagnostics is based on the feature op­tions purchased in the radio being polled.
If a PC is connected to any radio in the network, intrusive polling (polling which briefly interrupts payload data transmission) can be performed. To perform diagnostics without interrupting payload data transmission, connect the PC to a radio defined as the “root” radio. A radio is defined as a root radio using the DTYPE ROOT command locally, at the radio.
A complete explanation of remote diagnostics can be found in the Network-Wide Diagnostics System Handbook (Part No. 05-3467A01).
Table 20. Network-Wide Diagnostics Commands
Command Description
DLINK [xxxxx/ON/OFF]
Details, page 43
DTYPE [NODE/ROOT]
Details, page 44
1. Program one radio in the network as the root radio by entering the
DTYPE ROOT command at the radio.
2. At the root radio, use the DLINK ON and DLINK [baud rate] commands to configure the diagnostic link protocol on the RJ-11 port.
3. Program all other radios in the network as nodes by entering the
DTYPE NODE command at each radio.
4. Use the DLINK ON and DLINK [baud rate] commands to configure the diagnostic link protocol on the RJ-11 port of each node radio.
5. Connect a PC on which InSite software is installed to the root radio, or to one of the nodes, at the radio’s diagnostics port.
To connect a PC to the radio’s DIAG port, an RJ-11 to DB-9 adapter (Part No. 03-3246A01) is required. If desired, an adapter cable may be constructed from scratch, using the information shown in Figure 10 on
Page 11.
6. Launch the InSite program at the PC. (Refer to the InSite user’s manual for details.)
Set baud rate of diagnostics link
Set radios operational characteristics for net­work-wide diagnostics
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 57
Page 26
12.0 FIRMWARE UPGRADES
From time to time, the factory releases new firmware for its radio products. An upgraded file can be installed in existing radios to take advantage of engineering improvements or additional features.
12.1 Obtaining new firmware
The latest firmware for each radio type may be obtained free of charge from our website: www.microwavedata.com/service/technical/support/downloads/.
Firmware is also available on disks from the factory that are bundled with an installation utility (Radio Software Upgrade—upgrade.exe) for transferring the firmware file on the disk to the radio.
Saving a Web-site firmware file to your PC
Firmware upgrades are distributed as a plain-text (ASCII) file with a “.S28” extension. Browse to find the desired “.S28” file for your radio on the factory website at www.microwavedata.com. After finding your selection, use the right mouse button to select a path on your computer on which to save the file. (If this isn’t done, your browser may display the firmware file contents as text on the screen instead of downloading it to your local hard drive.)
After the “.S28” file has been saved to your computer, you may use either TransNET Configuration Software or Radio Software Upgrade programs to install this firmware in your radios.
12.2 Installing firmware in your radio
1. Connect a PC to radio’s diagnostic interface.
2. Start the TransNET Configuration Software. Open diagnostics port to the radio. The program will automatically read the radio’s profile.
3. From the File menu select Radio Firmware Upgrade and follow the prompts to install the new firmware into the radio. Do not press the Cancel button once the installation has started or it will leave the radio without any code. When the installation is complete, another radio may be connected to your PC and programmed.
NOTE: If a firmware installation fails, the radio is left unprogrammed and inoperative.
This is indicated by the PWR LED flashing slowly (1 second on/1 second off). This condition is only likely to occur if there is a power failure to the computer or radio during the installation process. The installation should be attempted again.
13.0 Security
Today, the operation and management of an enterprise is becoming increasing dependent on electronic information flow. An accompanying concern becomes the security of the communication infrastructure and the security of the data itself. We take this matter seriously, and provide several means for protecting the data carried over our wireless products.
58 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 27
Our radios address this issue primarily through the use of the following items:
1) A proprietary modem/data link layer—Data signals are processed using code and hardware specifically designed by the manufacturer.
2) A unique Network Address—This provides a unique identifier for each radio in a network. A radio is not addressable unless this unique code is included in the data string.
3) An optional encryption value (code)—Setting an encryption code requires the use of the CODE command. This command scrambles the radio’s hop pattern and encrypts payload data content. A radio requires the correct Network Address (ADDR) and CODE value in order to synchronize.
When the CODE command is used, the same value must be programmed into all radios in the network. See “CODE [NONE,
1…255]” on Page 42 for more details.
The effectiv e combination of CODE and ADDR discourage the use of an exhaustive search to gain access to a system.
The items described above provide sufficient security for most systems. For highly-sensitive applications, system designers should consider employing application level encryption into their polling protocols to further protect their systems. Third party software tools are available for adding encryption, and these should be considered as part of any advanced encryption scheme.
14.0 Product Specifications
GENERAL
Frequency Hopping Range: Up to xx frequencies within each band:
Hop Pattern: Based on network address Frequency Stability: ±1.5 ppm Half-Duplex Operation: ±1.6 MHz TX/RX split Network Addresses: 65,000 Temperature Range: –40° C to +70° C Humidity: <95% at +40° C; non-condensing Primary Power: 13.8 Vdc (5–25 Vdc range) Current Draw (typical):
Physical Dimensions: 1.81"W x 3.45"L x 0.63"H
Agency Approvals (pending): FCC Part 15.247 (E5MDS-EL806-2.4)
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 59
2.4016–2.4270 GHz (Band A)
2.4272–2.4526 GHz (Band B)
2.4528–2.478.2 GHz (Band C) Above are configurable in 3.2 MHz zones.
Transmit: 510 mA @ 13.8 Vdc Receive: 115 mA @ 13.8 Vdc Sleep Mode: 8 mA @ 13.8 Vdc
(46 x 87.5 x 16 mm)
FCC Limited Modular Approval (LMA)
Industry Canada RSS-210 and RSS-139
(CAN 3738A-MDSEL806-2.4)
Page 28
DATA CHARACTERISTICS
Data Interface: RS-232/422/485 Interface Connector: 16 pin header, female Data Rate: 1200, 2400, 4800, 9600, 19200, 38400,
Data Latency: 7 ms (typical) Byte Length: 10 or 11 bits Maximum Data Transmission: Continuous up to 115200 bps
57600, 115200 bps asynchronous
RF CHARACTERISTICS
TRANSMITTER: Power Output (at antenna connector): 50 mW to 0.5 Watt (+17 to +27 dBm)
Duty Cycle: Continuous Modulation Type: Binary CPFSK Output Impedance: 50 Ohms Spurious: –60 dBc Harmonics: –55 dBc
RECEIVER: Type: Double conversion superheterodyne
Sensitivity: –108 dBm @ 1 x 10 Intermodulation: 54 dB minimum (EIA) Desensitization: 75 dB Spurious: 70 dB minimum Bandwidth: 200 kHz Interference Ratio
(SINAD degraded by 3dB): Co-channel:–10 dB
Time Required to Synchronize with Master Radio: 0.5 seconds (typical)
Refer to Table 7 on Page 24
-6
BER
Adjacent channel:+30 dB Two channels away:+40 dB Three channels away:+48 dB
:
14.1 Detailed Pin Descriptions
The tables in this section give detailed pin functions for the transceiver’s 16-pin header connector, J3 (see Figure 21). The tables are organized according to the available signaling configurations of the OEM transceiver. (Figure 2 on Page 3 may be used to determine which configuration you have.) Signaling configuration is hardware fixed at the time of manufacture and will be one of the following:
• TTL signaling for both Payload and Diagnostic data
• Payload data TTL; Diagnostic data RS-232
• Payload data RS-232/RS-485 selectable; Diagnostic data RS-232
60 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 29
2
1 34
13 15
5
Figure 21. 16-pin Header Connector (J3) on OEM Transceiver Board
9
(See parts list (Page18) for information on
matching connector)
6
87 10 12 11 14 16
Table 21. Transceiver Connector J3 Pinouts
(Payload data TTL; Diagnostic data TTL)
Pin No.
Input/
Output
1IN --GroundConnects to ground (negative supply
2 OUT TTL, 3 Vdc Diagnostic TXDSupplies received diagnos-
3 OUT TTL, 3 Vdc Alarm conditionA low indicates normal opera-
4 IN TTL, 3 Vdc Diagnostic RXDAccepts diagnostic/adminis-
5 IN -- FCC 6-18 Vdc version: DC Input (5-25 Vdc)
6 IN TTL, 3 Vdc Sleep Mode InputA ground on this pin turns off
7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)A low indicates hop-
8 IN TTL, 3 Vdc Power Supply Shutdown ControlA ground on
9 -- -- Non-FCC 3 Vdc version: DC Input (Regulated
Signal
Type
Name/Description
potential).
tic/administrative data to the connected device.
tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)
trative data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre­serves the radios ability to be brought quickly back on line. See Sleep Mode Operation (Re-
mote units only) on Page 31 for details.
ping synchronization has been achieved.
this pin causes the OEM modules power supply to shut down.
3.3 Vdc)Supply Source must be capable of fur­nishing at least 7.5 watts.
FCC 6-18 Vdc version: Do not connect
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 61
Page 30
Table 21. Transceiver Connector J3 Pinouts
(Payload data TTL; Diagnostic data TTL) (Continued)
10 IN TTL, 3 Vdc Transmitted Data (TXD)Accepts payload data
11 IN -- FCC 6-18 Vdc version: DC Input (5-25 Vdc)
12 IN TTL, 3 Vdc Request to Send (RTS)A high causes CTS to
13 -- -- ReservedDo not connect. 14 OUT TTL, 3 Vdc Received Data (RXD)Supplies received pay-
15 IN -- GroundConnects to ground (negative supply
16 OUT TTL, 3 Vdc Clear to Send (CTS)Goes high after the pro-
from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
follow after the programmed CTS delay time has elapsed (DCE).
load data to the connected device.
potential).
grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).
Table 22. Transceiver Connector J3 Pinouts
(Payload data TTL; Diagnostic data RS-232)
Pin No.
Input/
Output
1IN --GroundConnects to ground (negative supply
2 OUT RS-232 Diagnostic TXDSupplies received diagnos-
3 OUT TTL, 3 Vdc Alarm conditionA low indicates normal opera-
4 IN RS-232 Diagnostic RXDAccepts diagnostic/adminis-
5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
Signal
Type
Name/Description
potential).
tic/administrative data to the connected device.
tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)
trative data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
62 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 31
Table 22. Transceiver Connector J3 Pinouts
(Payload data TTL; Diagnostic data RS-232) (Continued)
6 IN TTL, 3 Vdc Sleep Mode InputA ground on this pin turns off
7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)A low indicates hop-
8 IN TTL, 3 Vdc Power Supply Shutdown ControlA ground on
9 -- -- ReservedDo not connect.
10 IN TTL, 3 Vdc Transmitted Data (TXD)Accepts payload data
11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
12 IN TTL, 3 Vdc Request to Send (RTS)A high causes CTS to
13 -- -- ReservedDo not connect. 14 OUT TTL, 3 Vdc Received Data (RXD)Supplies received pay-
15 IN -- GroundConnects to ground (negative supply
16 OUT TTL, 3 Vdc Clear to Send (CTS)Goes high after the pro-
most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre­serves the radios ability to be brought quickly back on line. See Sleep Mode Operation (Re-
mote units only) on Page 31 for details.
ping synchronization has been achieved.
this pin causes the OEM modules power supply to shut down.
from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
follow after the programmed CTS delay time has elapsed (DCE).
load data to the connected device.
potential).
grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 63
Page 32
Table 23. Transceiver Connector J3 Pinouts
(Payload data RS-232; Diagnostic data RS-232)
Pin No.
Input/
Output
1IN --GroundConnects to ground (negative supply
2 OUT RS-232 Diagnostic TXDSupplies received diagnos-
3 OUT TTL, 3 Vdc Alarm conditionA low indicates normal opera-
4 IN RS-232 Diagnostic RXDAccepts diagnostic/adminis-
5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
6 IN TTL, 3 Vdc Sleep Mode InputA ground on this pin turns off
7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)A low indicates hop-
8 IN TTL, 3 Vdc Power Supply Shutdown ControlA ground on
9 -- -- ReservedDo not connect.
10 IN RS-232,
11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
12 IN RS-232,
Signal
Type
+/- 5 Vdc
+/- 5 Vdc
Name/Description
potential).
tic/administrative data to the connected device.
tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)
trative data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre­serves the radios ability to be brought quickly back on line. See Sleep Mode Operation (Re-
mote units only) on Page 31 for details.
ping synchronization has been achieved.
this pin causes the OEM modules power supply to shut down.
Transmitted Data (TXD)Accepts payload data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect Request to Send (RTS)A high causes CTS to
follow after the programmed CTS delay time has elapsed (DCE).
64 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 33
Table 23. Transceiver Connector J3 Pinouts
(Payload data RS-232; Diagnostic data RS-232) (Continued)
13 -- -- ReservedDo not connect. 14 OUT RS-232,
+/- 5 Vdc
15 IN -- GroundConnects to ground (negative supply
16 OUT RS-232,
+/- 5 Vdc
Received Data (RXD)Supplies received pay­load data to the connected device.
potential). Clear to Send (CTS)Goes high after the pro-
grammed CTS delay time has elapsed (DCE), or keys an attached radio when RF data arrives (CTS KEY).
Table 24. Transceiver Connector J3 Pinouts
(Payload data RS-485; Diagnostic data RS-232)
Pin No.
Input/
Output
1IN -- GroundConnects to ground (negative supply
2 OUT RS-232 Diagnostic TXDSupplies received diagnos-
3 OUT TTL, 3 Vdc Alarm conditionA low indicates normal opera-
4 IN RS-232 Diagnostic RXDAccepts diagnostic/adminis-
5 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
6 IN TTL, 3 Vdc Sleep Mode InputA ground on this pin turns off
7 OUT TTL, 3 Vdc Data Carrier Detect (DCD)A low indicates hop-
8 IN TTL, 3 Vdc Power Supply Shutdown ControlA ground on
9 -- -- ReservedDo not connect.
Signal
Type
Name/Description
potential).
tic/administrative data to the connected device.
tion. A high indicates an alarm. (See ASENSE [HI/LO] command for more information.)
trative data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
most circuits in a remote radio. This allows for greatly reduced power consumption, yet pre­serves the radios ability to be brought quickly back on line. See Sleep Mode Operation (Re-
mote units only) on Page 31 for details.
ping synchronization has been achieved.
this pin causes the OEM modules power supply to shut down.
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 65
Page 34
Table 24. Transceiver Connector J3 Pinouts
(Payload data RS-485; Diagnostic data RS-232) (Continued)
10 IN Differential RXD+/RXA (Transmitted Data+)Non-inverting
11 IN -- FCC 6-18 Vdc version: DC Input (6-18 Vdc)
12 IN Differential RXD-/RXA (Transmitted Data-)Inverting re-
13 -- -- ReservedDo not connect. 14 OUT Differential TXD+/TXA (Received Data+)Non-inverting
15 IN -- GroundConnects to ground (negative supply
16 OUT Differential TXD-/TXA (Received Data-)Inverting driver
receiver input. Accepts payload data from the connected device.
Supply Source must be capable of furnishing at least 7.5 watts.
Non-FCC 3 Vdc version: Do not connect
ceiver input.
driver output. Supplies received payload data to the connected device.
potential).
output.
66 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 35
15.0 dBm-Watts-Volts Conversion Chart
Table 25 is provided as a convenience for determining the equivalent voltage
or wattage of an RF power expressed in dBm with 50 Ohms load.
Table 25. dBm-Watts-Volts Conversion Chart
dBm V Po
+53 100.0 200W +50 70.7 100W +49 64.0 80W +48 58.0 64W +47 50.0 50W +46 44.5 40W +45 40.0 32W +44 32.5 25W +43 32.0 20W +42 28.0 16W +41 26.2 12.5W +40 22.5 10W +39 20.0 8W +38 18.0 6.4W +37 16.0 5W +36 14.1 4W +35 12.5 3.2W +34 11.5 2.5W +33 10.0 2W +32 9.0 1.6W +31 8.0 1.25W +30 7.10 1.0W +29 6.40 800mW +28 5.80 640mW +27 5.00 500mW +26 4.45 400mW +25 4.00 320mW +24 3.55 250mW +23 3.20 200mW +22 2.80 160mW +21 2.52 125mW +20 2.25 100mW +19 2.00 80mW +18 1.80 64mW +17 1.60 50mW +16 1.41 40mW +15 1.25 32mW +14 1.15 25mW +13 1.00 20mW +12 .90 16mW +11 .80 12.5mW +10 .71 10mW +9 .64 8mW +8 .58 6.4mW +7 .500 5mW +6 .445 4mW +5 .400 3.2mW +4 .355 2.5mW +3 .320 2.0mW +2 .280 1.6mW +1 .252 1.25mW
dBm V Po
0 .225 1.0mW
-1 .200 .80mW
-2 .180 .64mW
-3 .160 .50mW
-4 .141 .40mW
-5 .125 .32mW
-6 .115 .25mW
-7 .100 .20mW
-8 .090 .16mW
-9 .080 .125mW
-10 .071 .10mW
-11 .064
-12 .058
-13 .050
-14 .045
-15 .040
-16 .0355
dBm mV Po
-17 31.5
-18 28.5
-19 25.1
-20 22.5 .01mW
-21 20.0
-22 17.9
-23 15.9
-24 14.1
-25 12.8
-26 11.5
-27 10.0
-28 8.9
-29 8.0
-30 7.1 .001mW
-31 6.25
-32 5.8
-33 5.0
-34 4.5
-35 4.0
-36 3.5
-37 3.2
-38 2.85
-39 2.5
-40 2.25 .1µW
-41 2.0
-42 1.8
-43 1.6
-44 1.4
-45 1.25
-46 1.18
-47 1.00
-48 0.90
dBm mV Po
-49 0.80
-50 0.71 .01µW
-51 0.64
-52 0.57
-53 0.50
-54 0.45
-55 0.40
-56 0.351
-57 0.32
-58 0.286
-59 0.251
-60 0.225 .001µW
-61 0.200
-62 0.180
-63 0.160
-64 0.141
dBm µV Po
-65 128
-66 115
-67 100
-68 90
-69 80
-70 71 .1nW
-71 65
-72 58
-73 50
-74 45
-75 40
-76 35
-77 32
-78 29
-79 25
-80 22.5 .01nW
-81 20.0
-82 18.0
-83 16.0
-84 11.1
-85 12.9
-86 11.5
-87 10.0
-88 9.0
-89 8.0
-90 7.1 .001nW
-91 6.1
-92 5.75
-93 5.0
-94 4.5
-95 4.0
-96 3.51
-97 3.2
dBm µV Po
-98 2.9
-99 2.51
-100 2.25 .1pW
-101 2.0
-102 1.8
-103 1.6
-104 1.41
-105 1.27
-106 1.18
dBm nV Po
-107 1000
-108 900
-109 800
-110 710 .01pW
-111 640
-112 580
-113 500
-114 450
-115 400
-116 355
-117 325
-118 285
-119 251
-120 225 .001pW
-121 200
-122 180
-123 160
-124 141
-125 128
-126 117
-127 100
-128 90
-129 80 .1ƒW
-130 71
-131 61
-132 58
-133 50
-134 45
-135 40
-136 35
-137 33
-138 29
-139 25
-140 23 .01ƒW
MDS 05-xxxxA01, Rev. 01 TransNET OEM 2.4 Integration Guide 67
Page 36
68 T r ansNET OEM 2.4 Integration Guide MDS 05-xxxxA01, Rev . 01
Page 37
IN CASE OF DIFFICULTY...
MDS products are designed for long life and trouble-free operation. However, this equipment, as with all electronic equipment, may have an occasional component failure. The following information will assist you in the event that servicing becomes necessary.
CUSTOMER ASSISTANCE
Assistance for MDS products is available from our Customer Support Team during business hours (8:00 A.M.–5:30 P.M. Eastern Time). When calling, please give the complete model number of the radio, along with a description of the trouble/symptom(s) that you are experiencing. In many cases, problems can be resolved over the telephone, without the need for returning the unit to the factory. Please use one of the following means for product assistance:
Phone: 585 241-5510 E-Mail: techsupport@microwavedata.com FAX: 585 242-8369 Web: www.microwavedata.com
FACTORY SERVICE
Component level repair of radio equipment is not recommended in the field. Many components are installed using surface mount technology, which requires specialized training and equipment for proper servicing. For this reason, the equipment should be returned to the factory for any PC board repairs. The factory is best equipped to diagnose, repair and align your radio to its proper operating specifications.
If return of the equipment is necessary, you will be issued a Service Request Order (SRO) number. The SRO number will help expedite the repair so that the equipment can be repaired and returned to you as quickly as possible. Please be sure to include the SRO number on the outside of the shipping box, and on any correspondence relating to the repair. No equipment will be accepted for repair without an SRO number.
A statement should accompany the radio describing, in detail, the trouble symptom(s), and a description of any associated equipment normally connected to the radio. It is also important to include the name and telephone number of a person in your organization who can be contacted if additional information is required.
The radio must be properly packed for return to the factory. The original ship­ping container and packaging materials should be used whenever possible. All factory returns should be addressed to:
Microwave Data Systems Product Service Department (SRO No. XXXX) 175 Science Parkway Rochester, NY 14620 USA
When repairs have been completed, the equipment will be returned to you by the same shipping method used to send it to the factory. Please specify if you wish to make different shipping arrangements. To inquire about an in-process repair, you may contact our Product Services Group at 585-241-5540 (FAX: 585-242-8400), or via e-mail at ProductServices@microwavedata.com.
Page 38
Microwave Data Systems Inc.
175 Science Parkway Rochester, NY 14620
General Business: +1 585 242-9600
FAX: +1 585 242-9620
Web: www.microwavedata.com
A product of Microwave Data Systems Inc.
Loading...